© ABB Group March 3, 2011 | Slide 1 Fuzzy Cognitive Map for Health Assessment of IEC 61850 Based Devices and Functions Salman Mohagheghi ABB Inc., US Corporate Research Center, Raleigh, NC, USA

Transcript of Fuzzy Cognitive Map for Health Assessment of IEC 61850...

© ABB Group March 3, 2011 | Slide 1

Fuzzy Cognitive Map for Health Assessment of IEC

61850 Based Devices and FunctionsSalman MohagheghiABB Inc., US Corporate Research Center, Raleigh, NC, USA

© ABB Group March 3, 2011 | Slide 2

Contents

Introduction

Communication within the Substation� Overview of IEC 61850� Communication Services� Data Model� Health State of Devices and Functions

Cognitive Maps� Historical Approach� Fuzzy Logic� Fuzzy Cognitive Maps

Case Studies

Concluding Remarks

© ABB Group March 3, 2011 | Slide 3

IntroductionSmart Grid

� Communication and metering infrastructure

� Self-healing mechanisms

� Desired power quality level

� Advanced monitoring systems

� Efficient demand responsive programs

� Future proof design

� Interoperable infrastructure

© ABB Group March 3, 2011 | Slide 4

Communication within the SubstationsIEC 61850 Overview

� Data Modeling- Object oriented platform-independent modeling of all the functions.

� Fast Transfer of Events and Messages- GOOSE and GSSE for the peer-to-peer communication mode.

� Setting Groups- Control blocks allow the user to switch from any active group of setting values to another.

� Sampled Values- Transfer of sampled values from modern switchgear and nonconventional CT/VTs.

� Data Storage and Representation- Configured data of the substation is stored in XML format using the Substation Configuration Language (SCL).

IEC 61850 is a standard specifically designed for implementing

substation automation (SA) systems.

The main features of the standard are:

© ABB Group March 3, 2011 | Slide 5

Communication within the SubstationsIEC 61850 Substation Automation Topology

© ABB Group March 3, 2011 | Slide 6

Communication within the SubstationsServices

© ABB Group March 3, 2011 | Slide 7

Communication within the SubstationsLogical Node

� Virtual Units: objects defined in the object oriented context of the standard.

� LN is a collection of data objects, data-set objects, descriptive attributes, report control objects, log-control objects and a list of sampled values.

� The type of data contained in a LN can be operational (e.g. measurement values, position status) or configuration data (e.g. IED self descriptive).

� The substation automation functions are broken down into LNs.

© ABB Group March 3, 2011 | Slide 8

Communication within the SubstationsIEC 61850 Data Models

© ABB Group March 3, 2011 | Slide 9

Communication within the SubstationsHealth State in IEC 61850

� IEC 61850 defines health attributes for the logical nodes and

the external devices connected to them. These include:

� Health: state of the logical node related to hardware or

software. Mandatory data with three states:

� Ok (green): no problems, normal operation

� Warning (yellow): minor problems, but in safe operation

mode

� Alarm (red): severe problem, no operation possible

� EEHealth: state of the external equipment, for example a

circuit breaker controlled by the logical node XCBR. Optional data with the above three states.

� PhyHealth: Mandatory attribute that refers to the health state of the physical device.

© ABB Group March 3, 2011 | Slide 10

Cognitive MapsHistorical Approach

� Introduced in 1970s for representing social scientific knowledge.

� Signed digraphs where a positive link from vertex A to vertex B indicates that A causally increases B, whereas a negative link from A to B means that should A happen, the chances of

B happening are reduced.

� Indirect Effect of A on B over the path pi is negative if the

number of negative signs (of the edges) is odd, and

positive otherwise.

� Total Effect of A on B would then be derived from the

indirect effects over all possible paths: the total effect of

A on B is negative if all the indirect effects are negative, is positive if all the indirect effects are positive, and

indeterminate otherwise.

© ABB Group March 3, 2011 | Slide 11

Cognitive MapsWeighted Approach

� Alternative Solution: creating a weighted digraph

� removes the uncertainty related to the sign calculations

� requires higher level of granularity in defining the

dependencies of causes on one another

∑=

i

pABAB iww ,

BjjjjApAB niwwww ,,,, 211

×××= L

© ABB Group March 3, 2011 | Slide 12

Cognitive MapsFuzzy Logic

� Causality is fuzzy

� Fuzzy logic can deal with imprecise and vague information. It

enables representation of human knowledge with approximate terms and values

© ABB Group March 3, 2011 | Slide 13

Fuzzy Cognitive MapsQualitative Approach

� FCM provides a qualitative output (not a crisp number)

In other words:

Indirect Effect: weakest causal link in a path

Total Effect: Strongest of the weakest links

},,,{min,,,, 211 BjjjjApAB

mniwwww L=

},,{max ,, 1 mpABpABAB www L=

© ABB Group March 3, 2011 | Slide 14

Case StudyTransformer Bay

Transformer bay with protection/control functions:

line distance protection, tap changing functions with related protection functions, interlocking and reclosing functions, general monitoring

functions, and a generic control function for regulating the transformer

tap positions

© ABB Group March 3, 2011 | Slide 15

Case StudyFuzzy Cognitive Map

© ABB Group March 3, 2011 | Slide 16

Case StudyVoltage Transformer

� TVTR1: “Alarm” state for health.

� The impact of this health status on the IHMI (at the operator

desk):

� TVTR1 → MMXU → IHMI

� TVTR1 → PTOV → AVCO → GAPC → IHMI

� TVTR1 → CPOW → GAPC → IHMI

� TVTR1 → MMXN → GAPC → IHMI

� TVTR1 → PDIS → RREC → IHMI

The total effect of the Alarm health status of the TVTR1 on the

IHMI is determined as:

max{ min(V.H, V.H) + min(H, M, H, M) + min(L, H, M)

+ min(H, M, M) + min(V.H, V.H, V.H) }

= Very High

© ABB Group March 3, 2011 | Slide 17

Case StudyCircuit Breaker

� CB controlled by XCBR: “Warning” state for health (i.e. Warning

state for the EEHealth data of XCBR)

� The impact of this health status on the performance of the generic GAPC control function:

� XCBR → GAPC

� XCBR → CILO (Bay) → CILO (Station) → GAPC

� XCBR → CSWI → CILO (Bay) → CILO (St.) → GAPC

The total effect of the Warning health status of the CB on the

GAPC is determined as:

max{ min(M) + min(V.H, M, M) + min(V.H, V.H, M, M) }

= Medium

© ABB Group March 3, 2011 | Slide 18

Case StudyTap Changer

� YLTC: “Alarm” state for health

� The impact of this health status on the performance of the

ATCC logical node:

� YLTC → ATCC

� YLTC → AVCO → GAPC → ATCC

The total effect of the Alarm health status of YLTC on the

ATCC is determined as:

max{ min(V.H) + min(H, H, V.H) } = Very High

© ABB Group March 3, 2011 | Slide 19

Concluding Remarks

� IEC 61850 standard defines a data attribute indicating the health status of logical nodes (i.e., basic functions) and physical devices.

This attribute tags the data points traveling across the system.

� While this identifier attribute can be easily interpreted and utilized

in the device immediately connected to the source of the data, it is often not easy to find the impact of a non-ideal health status in a

web of multiple control and protection functions.

� A fuzzy cognitive map (FCM) is proposed for evaluating the impact

of non-ideal health status of logical nodes and physical devices in an interconnected network on the performance of the rest of the

system functions.

� FCM can monitor the devices and functions with a predefined

frequency to raise flags upon detecting non-ideal health.

� Expert knowledge can be used to determine the weights of the interdependences of logical nodes on one another.

© ABB Group March 3, 2011 | Slide 20