2-Way and 3-Way Diverter Valve and Check Valve Installaton and Operation Instructions Diverter Valve The Pentair Water Pool and Spa ® user adjustable diverter valve is designed to be used a DIVERTER valve, NOT a BACKWASH valve. The FullFloXF™ 2-Way and 3-Way Diverter valves can operated by hand or with a motorized valve actuator (such as the CVA-24 by Pentair Water Pool and Spa ® ). 3-Way Diverter valves are used to divert incoming water flow (from pump, etc.) applied at the INLET port to either of the different branches of the systems plumbing (filter, heater, solar collectors, skimmer, etc.). 2-Way Diverter and Check valves are used to block the flow of water in one direction only. The 2-Way and 3-Way Diverter valves can also be used to regulate (limit) water flow coming out of the valve by adjusting the diverter mechanism covering a portion of the OUTLET port. All Diverter valves should ONLY be used with the Diverter mechanism regulating or shutting off flow on the down stream (OUTLET) side of the flow. Plumbing The Diverter and Check valves are sized for use with 2-1/2” or 3” CPVC/PVC pipe fittings. 2-1/2” pipe can be plumbed directly into the valve port’s socket, 3” plumbing requires an appropriate 3” (coupling or 90° elbow) slipped over the valve port’s spigot. Can also be used with any size PVC plumbing with appropriate adapters Note: Be cautious that no glue enters the inside of the valve body past the ports. The recommended pipe glue to use is, WELD-ON ® 724 CPVC, GRAY or glue types such as WELD-ON ® 790 MULTI-PURPOSE SOLVENT CEMENT. SERIOUS BODILY INJURY OR DEATH CAN RESULT IF THE 3” VALVE IS NOT INSTALLED AND USED CORRECTLY. INSTALLERS, POOL OPERATORS AND POOL OWNERS MUST READ THESE WARNINGS AND ALL INSTRUCTIONS BEFORE INSTALLING THIS VALVE. IMPORTANT NOTICE - Attention Installer: This Installation and Operation Instructions (“Instructions”) contains important information about the installation, operation and safe use of the 3-inch pump. These Instructions should be given to the owner and/or operator of this equipment. This 3” Valve is intended for use in swimming pool and spa applications. This valve must be installed by a qualified pool and spa service professional or plumber in accordance with all applicable local codes and ordinances. Improper installation may create an electrical hazard which could result in death or serious injury to pool users, installers, or others due to electrical shock, and may also cause damage to property. Most states and local codes regulate the construction, installation, and operation of public pools and spas, and the construction of residential pools and spas. It is important to comply with these codes, many of which directly regulate the installation and use of this product. Consult your local building and health codes for more information. 2-Way & 3-Way Diverter Valve (2-1/2” Socket x 3” Spigot) Figure 2. 3-Way Diverter Valve Ports Port B (INLET) (“INLET” typical common port) Water flow into or out of valve. Port C Port A Figure 1. 3-Way Diverter Valve 3” Pipe 3” Coupler 3” Pipe 2-1/2” Pipe (Slip Fit) Note: The diverter valve “INLET” (“common”) port can be oriented from any one of the three ports (see page 3) FullFloXF DO NOT increase pump size; this may increase the flow rate through the system and exceed the maximum flow rate stated on the drain cover. Exceeding the maximum flow rate stated on the drain cover could result in death or serious injury to pool users and may also cause property damage. 1 OFF indicator marks position of CLOSED port

Transcript of FullFloXF - Pentair · the CVA-24 by Pentair Water Pool and Spa ®). 3-Way Diverter valves are used...

Page 1: FullFloXF - Pentair · the CVA-24 by Pentair Water Pool and Spa ®). 3-Way Diverter valves are used to divert incoming water flow (from pump, etc.) applied at the INLET port to either

2-Way and 3-Way Diverter Valve and Check ValveInstallaton and Operation Instructions

Diverter ValveThe Pentair Water Pool and Spa® user adjustable diverter valve is designed to be used a DIVERTER valve, NOT aBACKWASH valve.

The FullFloXF™ 2-Way and 3-Way Diverter valves can operated by hand or with a motorized valve actuator (such asthe CVA-24 by Pentair Water Pool and Spa®). 3-Way Diverter valves are used to divert incoming water flow (from pump,etc.) applied at the INLET port to either of the different branches of the systems plumbing (filter, heater, solarcollectors, skimmer, etc.). 2-Way Diverter and Check valves are used to block the flow of water in one direction only.The 2-Way and 3-Way Diverter valves can also be used to regulate (limit) water flow coming out of the valve byadjusting the diverter mechanism covering a portion of the OUTLET port. All Diverter valves should ONLY be used withthe Diverter mechanism regulating or shutting off flow on the down stream (OUTLET) side of the flow.

PlumbingThe Diverter and Check valves are sized for use with 2-1/2” or 3” CPVC/PVC pipe fittings. 2-1/2” pipe can be plumbeddirectly into the valve port’s socket, 3” plumbing requires an appropriate 3” (coupling or 90° elbow) slipped over the valveport’s spigot. Can also be used with any size PVC plumbing with appropriate adaptersNote: Be cautious that no glue enters the inside of the valve body past the ports. The recommended pipe glueto use is, WELD-ON® 724 CPVC, GRAY or glue types such as WELD-ON® 790™ MULTI-PURPOSE SOLVENTCEMENT.

SERIOUS BODILY INJURY OR DEATH CAN RESULT IF THE 3” VALVE IS NOT INSTALLED ANDUSED CORRECTLY. INSTALLERS, POOL OPERATORS AND POOL OWNERS MUST READ THESE

WARNINGS AND ALL INSTRUCTIONS BEFORE INSTALLING THIS VALVE.

IMPORTANT NOTICE - Attention Installer: This Installation and Operation Instructions (“Instructions”) containsimportant information about the installation, operation and safe use of the 3-inch pump. These Instructions shouldbe given to the owner and/or operator of this equipment. This 3” Valve is intended for use in swimming pool andspa applications.

This valve must be installed by a qualified pool and spa service professional or plumber in accordancewith all applicable local codes and ordinances. Improper installation may create an electrical hazard

which could result in death or serious injury to pool users, installers, or others due to electrical shock, and may also causedamage to property. Most states and local codes regulate the construction, installation, and operation of public pools andspas, and the construction of residential pools and spas. It is important to comply with these codes, many of which directlyregulate the installation and use of this product. Consult your local building and health codes for more information.

2-Way & 3-Way Diverter Valve (2-1/2” Socket x 3” Spigot)

Figure 2. 3-Way Diverter Valve Ports

Port B (INLET)(“INLET” typical common port)Water flow into or out of valve.

Port C

Por

t A

Figure 1. 3-Way Diverter Valve

3” Pipe

3” Coupler

3” Pipe

2-1/2” Pipe(Slip Fit)

Note: The divertervalve “INLET”(“common”) portcan be orientedfrom any one of thethree ports(see page 3)

FullFloXF™

DO NOT increase pump size; this may increase the flow rate through the system and exceed the maximumflow rate stated on the drain cover. Exceeding the maximum flow rate stated on the drain cover couldresult in death or serious injury to pool users and may also cause property damage.

1

OFF indicatormarks position ofCLOSED port

Page 2: FullFloXF - Pentair · the CVA-24 by Pentair Water Pool and Spa ®). 3-Way Diverter valves are used to divert incoming water flow (from pump, etc.) applied at the INLET port to either

Valve Handle OperationTo reposition the valve handle:

• Rotate the handle to the desired “OFF” position. The diverter valve handle OFF indicator, represents the current position of thevalve’s internal diverter seal which will stop the flow of water. The valve handle stop-pins determine the position of thediverter valve’s internal seal to stop or allow water flow. Note: When a motorized valve actuator is installed, stop-pins are notrequired.

Handle Stop-Pins PositionsThe two movable stop-pins can be set to allow the valve handle’s position to completely stop the flow of water, regulate a limitedflow, or allow the maximum flow.

To set the stop-pins:

• Insert the stop-pins in the pin holes according to the corresponding “degree indicator” displayed on top of the handle. Thestop-pin positions can be set to 180°, L90° (left-side) and R90° (right side). Repositioning of either stop-pins allows the handleto be set to any desired percentage of water flow.

OFF

Stop PinsSet for

180°

OFF

PORT 3 (Common Port)

PORT 1 PORT 2

3-Way Driverter Valve:Example: Stop-pins set to 180° - Inlet is Port 3 with flow directed out of Port 1 or Port 2 depending on the handleposition.

2

PORT 3 Open PORT 1 Open

PORT 1 PORT 2

10

6 1/2"1 3/4"SOC

DEPTH

1 7/8"SPIGOT

3 1/4"

5

3 1/4"

SOCKET2-1/2"

3 1/2"SPIGOT

DIVERTER AND CHECK VALVE LAYING LENGTHS FOR 2-1/2" X 3" SOCKET X SPIGOT

6-1/8”Dia

5 1/8"

2 3/4"

3 1/8"

Valve (side view)

PORT 3 (Common Port)

Page 3: FullFloXF - Pentair · the CVA-24 by Pentair Water Pool and Spa ®). 3-Way Diverter valves are used to divert incoming water flow (from pump, etc.) applied at the INLET port to either

1

2

3

4

5

6

7

8 9

10

11

12

Figure 4. Diverter valve cover screws(Tightening Sequence)

Torque: 36 lb*in (4.1 N*m)

Diverter Valve Top Cover Removal and InstallationTo remove the diverter valve top cover (see Figure 3):

1. Remove the valve handle lock screw and handle from the valve shaft.2. Using a No. 2 Philips screwdriver, remove the twelve (12) cover screws. Set the screws aside.3. When removing the cover: Do not insert a screw driver blade between the valve body and the top cover to pry open.

Temporarily install the handle and thumb screw to aid lifting the cover and diverter shaft out and off the valve body.Be careful not to drop or lose the cover o-ring.

To install the diverter valve top cover (see Figure 4 and 5):

1. Lubricate the cover o-ring with silicon o-ring grease and place it on the cover flange. Install the cover and diverter shaft inreverse order of removal from the valve body. If the diverter shaft was removed from the cover, make sure the two o-ring(spacer goes between o-rings) are in place and lubricated with silicon o-ring grease.

2. Align the notch (on cover) and tab (on valve body) this will position the top cover molded name “INLET” over the center or“common” port as shown in Figure 3. Make sure the cover and valve body screw holes are aligned.

3. Install the twelve (12) cover screws. Using a No. 2 Phillips screwdriver, torque the screws sequentially to 36 lb*in (4.1 N*m).using the crisscross tightening sequence shown in Figure 4.

4. Mount the handle onto the diverter shaft (the handle is keyed to fit on the shaft in only one position).5. Install the handle lock screw and finger tighten to secure in place.6. Manually verify that the diverter valve rotates smoothly in both directions.

1HANDEL LOCK SCREW

2STOP-PINS

3HANDLE

4COVER SCREWS

5COVER

7

9DIVERTER SHAFT ASSEMBLY

6 O-RING

8

metI.oN

traPrebmuN

noitpircseD

12345678901

Z470172Z270172Z811072Z770172Z511072Z611072Z370172

930291Z601072Z701072

KCOLELDNAHWERCSPOTSELDNAHNIP

ELDNAH)TIK/SWERCS21(TIKWERCS

REVOCEVLAVRETREVID)D'QER1(AEROHS07N-ANUB842-2,GNIR-O

)D'QER1(RECAPS,GNIR-O)D'QER2(AEROHS07N-ANUB611-2,GNIR-O

YLBMESSATFAHSRETREVIDEVLAVYAW-3RALOSYSSARETREVID

EVLAVKCEHCNWODNIARDHTIW

Diverter Valve Parts List

Typical “Common” Port 3

INLET

Figure 3.

Align notch (on cover)and tab (on valve body)Also see illustrationbelow.

NOTCH

Tab

Figure 5.

3

Note: If reorienting the valve cover is necessary, the locating tab on valve body (fig. 5)must be removed (use file or wire cutters) to allow reorienting the valve cover to analternate position.

SOLAR DIVERTER VALVESHAFTSHOWING DRAIN

DOWN CHECK VALVE(SHAFT COMPONENTS NOT

SOLD SEPARATELY)

10

Page 4: FullFloXF - Pentair · the CVA-24 by Pentair Water Pool and Spa ®). 3-Way Diverter valves are used to divert incoming water flow (from pump, etc.) applied at the INLET port to either

Check ValveThe Pentair Water Pool and Spa® straight and 90° bodycheck valve is designed for use with return and intake waterflow. A clear top cover is provided for easy viewing of waterflow direction.

The 3” check valve can be used with 2-1/2” or 3” pipe. The2-1/2” pipe slip-fits into the valve ports (see Figure 1). The 3”pipe is connected to the valve using a 3” pipe coupler, a 45°elbow or a 90° elbow. Note: Be sure no glue enters theinside of the valve body past the ports. Therecommended pipe glue to use is, WELD-ON® 724 CPVC,GRAY or WELD-ON® 790™ MULTI-PURPOSE SOLVENTCEMENT.

Check Valve (2-1/2” Socket x 3” Spigot)

Check Valve Top Cover- Removal and Installation(see Figure 6 and 7)To remove the check valve top cover:

1. Mark the position of the check valve flapper or direction of arrow oncover. Use a No. 2 Philips screwdriver to remove the twelve (12)screws. Set the cover screws aside.

2. When removing the cover: Do not insert a screw driver blade betweenthe valve body and the top cover to pry open. If cover is stuck use a mallet orwooden dowel and tap lightly on the side of the cover (not on screwbosses) to loosen cover. Be careful not to drop or lose the cover o-ring.

To install the check valve top cover (see Figure 6 and 7)1. Make sure the cover o-ring is lubricated with silicon o-ring grease and

installed on the cover flange. Mount the check valve cover on top of thebody with the flapper oriented in same position as when removed.Align the notch (on cover) and tab (on valve body), see Figure 7).

2. Make sure the cover and valve body screw holes are aligned.3. Install the twelve (12) cover screws. Using a No. 2 Phillips screwdriver,

torque screws sequentially to 36 lb*in (4.1 N*m). using the

tightening sequence shown in Figure 6. Verify that the check valveflapper is oriented in the proper direction.

1

2

3

4

5

6

7

8 9

10

11

12

Figure 6.Check Valve Cover Screws (Tightening Sequence)

Straight Body Check Valve

90° Body Check Valve

Check Valve Parts ListmetI.oN

traPrebmuN

)tekcoS"5.2xtogipS"3(evlaVkcehC

1

23

Z911072

Z770172Z611072

TIKTNEMECALPERREPPALFEVLAVKCEHC)3&2smetIsedulcnI(

)TIK/SWERCS21(TIKWERCS)D'QER1(AEROHS07N-ANUB842-2GNIR-O

Check Valve FlapperReplacement Kit(Includes items 2, & 3)

Align topcover notchwith tab on

body

Tab (not shown)located on body

Figure 7.

Torque to: 36 lb*in (4.1 N*m)

4

Flapper hinge pin

2

3

1

Page 5: FullFloXF - Pentair · the CVA-24 by Pentair Water Pool and Spa ®). 3-Way Diverter valves are used to divert incoming water flow (from pump, etc.) applied at the INLET port to either

Head Loss Curves

2 00

2.50

3.00

3.50

4.00

4.50

5.00

1.00

1.25

1.50

1.75

2.00

2.25

Hea

d Lo

ss, F

t.

Pres

sure

Dro

p, P

SI

263056 & 263057 Diverter Valve's Head LossPort 3 to Port 2 Flow

0.00

0.50

1.00

1.50

2.00

0.00

0.25

0.50

0.75

0 20 40 60 80 100 120 140 160 180

Flow, GPM

3" Sch 40 Pipe 2-1/2" Sch 40 Pipe

0.60

0.80

1.00

1.20

1.40

0.30

0.40

0.50

0.60

Hea

d Lo

ss, F

t.

Pres

sure

Dro

p, P

SI

263056 & 263057 Diverter Valve Head LossPort 1 to Port 2 Flow

0.00

0.20

0.40

0.00

0.10

0.20

0 20 40 60 80 100 120 140 160 180

Flow, GPM

3"Sch 40 Pipe 2-1/2" Sch 40 pipe

0.60

0.80

1.00

1.20

1.40

0.30

0.40

0.50

0.60

Hea

d Lo

ss, F

t.

Pres

sure

Dro

p, P

SI

263059 Isolator Valve Head Loss

0.00

0.20

0.40

0.00

0.10

0.20

0 20 40 60 80 100 120 140 160 180

Flow, GPM

3" Sch 40 Pipe 2-1/2" Sch 40 Pipe

5

Page 6: FullFloXF - Pentair · the CVA-24 by Pentair Water Pool and Spa ®). 3-Way Diverter valves are used to divert incoming water flow (from pump, etc.) applied at the INLET port to either

2 00

3.00

4.00

5.00

1.00

1.25

1.50

1.75

2.00

Hea

d Lo

ss, F

t.

Pres

sure

Dro

p, P

SI

263068 90 Deg Isolator Valve Head Loss

0.00

1.00

2.00

0.00

0.25

0.50

0.75

0 20 40 60 80 100 120 140 160 180

Flow, GPM

3" Sch 40 Pipe 2-1/2" Sch 40 Pipe

0.80

1.00

1.20

1.40

1.60

0.30

0.40

0.50

0.60

0.70

Hea

d Lo

ss, F

t.

Pres

sure

Dro

p, P

SI

263060 Check Valve Head Loss

0.00

0.20

0.40

0.60

0.00

0.10

0.20

0 20 40 60 80 100 120 140 160 180

Flow, GPM

3" Sch 40 pipe 2-1/2" Sch 40 Pipe

1.50

2.00

2.50

3.00

3.50

0.80

1.00

1.20

1.40

1.60

Hea

d Lo

ss, F

t.

Pres

sure

Dro

p, P

SI

263077 90 Deg Check Valve Head Loss

0.00

0.50

1.00

0.00

0.20

0.40

0.60

0 20 40 60 80 100 120 140 160 180

Flow, GPM

3" Sch 40 Pipe 2-1/2" Sch 40 Pipe

P/N 270154 Rev. B 1/24/12 6

Customer Support (800) 831-71331620 Hawkins Avenue, Sanford, NC 27330 • (919) 566-800010951 W. Los Angeles Avenue, Moorpark, CA 93021 • (805) 553-5000FullFloXF™ and Pentair Water Pool and Spa® is a trademark and/or a registered trademark of Pentair Water Pool and Spa, Inc. and/or its affiliated companies in the UnitedStates and/or other countries. Weld-On® and Weld-On 790™ is a trademark and/or registered trademark of IPS Corporation. Unless noted, names and brands of othersthat may be used in this document are not used to indicate an affiliation or endorsement between the proprietors of these names and brands and Pentair Water Pool andSpa, Inc. Those names and brands may be the trademarks or registered trademarks of those parties or others.