FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination...

339
FOURTH AVENUE BUILDING POWER SYSTEMS STUDY SHORT-CIRCUIT, COORDINATION, AND ARC FLASH ANALYSIS 2/13/2015 4100 194th St SW Suite 400, Lynnwood, Washington 98036-4613 206-667-0555 800-667-0610 Fax: 206-667-0554 www.sparling.com

Transcript of FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination...

Page 1: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

FOURTH AVENUE

BUILDING POWER

SYSTEMS STUDYSHORT-CIRCUIT, COORDINATION, AND ARC

FLASH ANALYSIS

2/13/2015

4100 194th St SW • Suite 400, Lynnwood, Washington 98036-4613

206-667-0555 800-667-0610 Fax: 206-667-0554

www.sparling.com

Page 2: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Fourth Avenue Building Power Systems Study

Portland State University February 13, 2015

Table of Contents

1.0 PROJECT OVERVIEW .................................................................................................................... 2

1.0 EXECUTIVE SUMMARY ................................................................................................................ 2

1.1 Short-Circuit Analysis ....................................................................................................................... 2

1.2 Protective Device Coordination Study ................................................................................................ 2

1.3 Arc Flash Hazard Analysis................................................................................................................. 3

1.4 Finding and Recommendations .......................................................................................................... 3

2.0 SHORT-CIRCUIT ANALYSIS ......................................................................................................... 3

2.1 System Modeling ............................................................................................................................... 4

2.2 Short-circuit Results .......................................................................................................................... 4

3.0 PROTECTIVE DEVICE COORDINATION STUDY ........................................................................ 7

3.1 Protection Device Protection Philosophy............................................................................................ 7

3.2 Coordination Results and Recommendations ...................................................................................... 8

4.0 ARC FLASH HAZARD ANALYSIS ................................................................................................ 8

4.1 Overview of NFPA 70E and OSHA regulation................................................................................... 8

4.2 Calculations and Assumptions ........................................................................................................... 9

4.3 Results and Recommendations ........................................................................................................... 9

Table of Appendices

APPENDIX A - Short Circuit Calculations

APPENDIX B - One-Line Diagram

APPENDIX C - Time Current Curves

APPENDIX D - Arc Flash Summary

APPENDIX E – Arc Flash Category Level 2 Reduction Summary

Page 3: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Fourth Avenue Building Power Systems Study

Portland State University February 13, 2015

1.0 PROJECT OVERVIEW

The Campus Wide Assessment and Correction of Arc Flash Hazards consists of performing short-circuit,

over-current protection coordination and arc flash hazard analysis and recommendation to lower the Arc

Flash Category to Level 2 or less for protective devices within the distribution equipment.

1.0 EXECUTIVE SUMMARY

This report contains the results of analysis performed on the Fourth Avenue Building electrical

distribution system at the Portland State University in Portland, Oregon. The studies performed

included short circuit, protective device coordination and arc flash evaluation for the distribution

equipment as indicated on the one-line drawings in Appendix B.

The results of this study are based on the manufacturer’s published performance data and our

understanding that the Owner has maintained the equipment as recommended by the manufacturer.

The purpose of this study is to evaluate the existing electrical system, as detailed below.

The executive summary contains the description and guide to the rest of the report. In addition, it

also contains the recommendations of the entire study.

1.1 Short-Circuit Analysis

The purpose of the short-circuit analysis is to determine the available fault current at pertinent

locations throughout the distribution system. Based on the model created, the available fault duties

were compared to the interrupting ratings of the devices studied.

A review of the fault current calculations showed that some of the electrical equipment modeled

within the system did not have adequate withstand ratings. Refer to TABLE 2.2 Locations of Fail

Equipment.

Complete short circuit analysis input & output reports as well as device evaluation tables are

contained in the Appendices.

The available fault currents determined by the short-circuit study will be used in the coordination and

device evaluation analysis. Short-circuit currents for each bus is annotated on the one-line drawings in

Appendix B.

1.2 Protective Device Coordination Study

The purpose of the study is to determine protective device characteristics, settings, or sizes, which

provide a balance between equipment protection and selective device operation that is optimum for

the electrical system.

The recommended device settings provided in this report should provide adequate system protection

and coordination.

Page 4: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Fourth Avenue Building Power Systems Study

Portland State University February 13, 2015

1.3 Arc Flash Hazard Analysis

The arc-flash study requires short-circuit and coordination studies for the different modes in which

the system may operate. After the short-circuit and coordination studies have been performed, the arc

flash hazard analysis determines the worst-case arc-flash hazards and associated incident energy

conditions.

The arc flash analysis details are provided in Section 4. The arc flash summary, device PPE

recommendations, and Flash Hazard labels are provided in Appendix D. Each adjustable protective

device listed in Section 3 must remain at the stated settings in order to achieve and maintain incident

energy levels listed in Table D.1 located in Appendix D.

These recommended settings were typically chosen to provide optimum protective device selectivity

while minimizing the resulting arc flash incident energy at each location where possible. As such, all

recommended settings must be successfully implemented prior to the application of the corresponding

arc flash hazard labels.

Most of the locations studied were found to have incident energy levels that are within Category 0-2

protection. No work should be done on or around any energized equipment without the use of a

proper level of PPE and adequate training.

There are (5) five pieces of equipment that was designated Category 3 and above. Refer to TABLE

4.3 for Locations with Category 3 and above.

1.4 Finding and Recommendations

The majority of the low voltage distribution equipment were found to have no inspection tags during

the field investigation to indicate that the equipment has been tested or maintained during the life of

the equipment per the recommended maintenance guidelines of ANSI/NETA MTS and NFPA 70B.

A review of the fault current calculations showed that some of the electrical equipment modeled

within the system did not have adequate withstand ratings.

To reduce the other protective devices it is recommended to replace and or test the circuit breaker and

adjust the trip setting.

The Protective Device Settings and the Arc Flash Summary to support the Category to Level 2 or less

recommendation are located in Appendix E. Refer to TABLE 4.4 Recommendation to reduce the

Equipment Category Levels.

2.0 SHORT-CIRCUIT ANALYSIS

The short-circuit calculations were done using PTW, a computer software package by SKM Systems

Analysis. PTW performs short-circuit calculations based on IEEE Std 399, IEEE Std C37.010, IEEE

Std. C37.5 and IEEE Std C37.13. The field investigation data was input into the SKM System

Page 5: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Fourth Avenue Building Power Systems Study

Portland State University February 13, 2015

Analysis, Inc. PowerTools for Windows A_FAULT program and analyzed to determine the

maximum fault levels at the electrical distribution equipment covered within the study.

The short-circuit study determines the fault currents that flow in the system during various fault

conditions. The calculated fault currents are used in the device evaluation, coordination studies, and

arc flash studies.

In order to minimize equipment damage, it is essential to use equipment with short circuit ratings

equal to or greater than the available short circuit current to which the equipment will be subjected.

Multiple short-circuit scenarios were only not necessary when examining fault-current values because

the building is not served with multiple sources of power.

Complete short circuit analysis input & output reports as well as device evaluation tables are

contained in the Appendix A.

2.1 System Modeling

Short-circuit currents were calculated for a three phase bolted fault and single-line-to-ground fault at

each bus shown on the one-line diagram found in Appendix B. The system was modeled for worst-

case fault currents.

Information regarding the system model used for the computer simulation is included in Appendix A.

2.2 Short-circuit Results

The results of the short-circuit analysis, including calculated branch contributions, are provided in

Appendix A. The as-found one-line diagram with referenced bus identification is included in

Appendix B.

A review of the fault current calculations showed that some of the electrical equipment modeled

within the system did not have adequate withstand ratings.

The Equipment Evaluation Report compares protective device ratings with short-circuit calculations.

The program also checks for missing input data and compares continuous ratings to calculated design

and operating conditions. Equipment that fails the evaluation are reported in table form and color-

coded by the one-line diagrams. The results of the Equipment Evaluation Report are provided in

Appendix A.

TABLE 2.2 Locations of Fail Equipment

Device Name Connected Bus Status Recommendation

4K PENTHOUSE C MCC-3 Fail Replace circuit breaker that can

Page 6: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Fourth Avenue Building Power Systems Study

Portland State University February 13, 2015

handle the available fault current.

110 A WWP2 CB P4Y Fail Replace circuit breaker that can

handle the available fault current.

150 A WWP3 CB P4Y Fail Replace circuit breaker that can

handle the available fault current.

150 A WWP4 CB P4Y Fail Replace circuit breaker that can

handle the available fault current.

200 A 4D2 CB P4Y Marginal Replace circuit breaker that can

handle the available fault current.

200 A H6A CB P4Y Marginal Replace circuit breaker that can

handle the available fault current.

200 A H7A CB P4Y Marginal Replace circuit breaker that can

handle the available fault current.

30 A ASU9A CB P4Y Marginal Replace circuit breaker that can

handle the available fault current.

100 A 4F CB P4Z Fail Replace circuit breaker that can

handle the available fault current.

150 A 4GE CB P4Z Fail Replace circuit breaker that can

handle the available fault current.

200 A 4A CB P4Z Fail Replace circuit breaker that can

handle the available fault current.

4C CB P4Z Fail Replace circuit breaker that canhandle the available fault current.

4D CB P4Z Fail Replace circuit breaker that can

handle the available fault current.

4DE CB P4Z Fail Replace circuit breaker that canhandle the available fault current.

4I CB P4Z Fail Replace circuit breaker that can

handle the available fault current.

4K CB 1 P4Z Fail Replace circuit breaker that canhandle the available fault current.

4L CB 1 P4Z Fail Replace circuit breaker that can

handle the available fault current.

Page 7: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Fourth Avenue Building Power Systems Study

Portland State University February 13, 2015

4M CB 1 P4Z Fail Replace circuit breaker that can

handle the available fault current.

ELEV #50 DISC CB P4Z Fail Replace circuit breaker that canhandle the available fault current.

MCC12 CB P4Z Fail Replace circuit breaker that can

handle the available fault current.

XFMR P2Z CB P4Z Fail Replace circuit breaker that canhandle the available fault current.

XFMR 2A CB PNL 4A Fail Replace circuit breaker that can

handle the available fault current.

2B1 CB PNL 4B Fail Replace circuit breaker that canhandle the available fault current.

2CA CB PNL 4C-12 Fail Replace circuit breaker that can

handle the available fault current.

2D1 CB PNL 4D1 Fail Replace circuit breaker that canhandle the available fault current.

4F-13 CB PNL 4J Marginal Replace circuit breaker that can

handle the available fault current.

SF1A CB PNL 4J Fail Replace circuit breaker that canhandle the available fault current.

SF1B CB PNL 4J Fail Replace circuit breaker that can

handle the available fault current.

20 A XFMR 2J CB PNL 4J2 Fail Replace circuit breaker that can

handle the available fault current.

XFMR 2J CB PNL 4J2 Fail Replace circuit breaker that can

handle the available fault current.

4B CB PNL P4A Fail Replace circuit breaker that can

handle the available fault current.

4G-104 CB PNL P4A Fail Replace circuit breaker that can

handle the available fault current.

XFMR 2GA CB PNL P4A Fail Replace circuit breaker that can

handle the available fault current.

XFMR 2GB CB PNL P4A Fail Replace circuit breaker that can

handle the available fault current.

Page 8: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Fourth Avenue Building Power Systems Study

Portland State University February 13, 2015

4C-12 CB PNL P4B Fail Replace circuit breaker that can

handle the available fault current.

4CH CB PNL P4B Fail Replace circuit breaker that canhandle the available fault current.

2C-12 CB PNL P4D Fail Replace circuit breaker that can

handle the available fault current.

4D1 CB PNL P4D Marginal Replace circuit breaker that canhandle the available fault current.

KL CB PNL P4D Marginal Replace circuit breaker that can

handle the available fault current.

UPS A CB1 UPS A CB1 BUS Fail Replace circuit breaker that canhandle the available fault current.

3.0 PROTECTIVE DEVICE COORDINATION STUDY

The associated time-current curves were developed using SKM System Analysis' Captor software.

The protective device coordination study determines overcurrent protective relay and circuit breaker

settings in order to provide optimal protection and coordination. In developing the device settings,

consideration was given to both isolation of faults, protection of cables, and protection of

transformers.

3.1 Protection Device Protection Philosophy

Using the appropriate maximum fault currents, the time-current curves were plotted as operating time

versus current magnitudes to show protective device tripping and/or clearing characteristics and

coordination among these devices.

When modeling it may not be possible to locate time-current curve for some circuit breakers; we

assumed the trip characteristics of these circuit breakers are similar to those of the replacement circuit

breakers. This assumption only affects the time-current curves presented for certain locations and

does not affect the equipment evaluation or arc-flash hazard analysis.

The difficulties in locating a time-current curve for these circuit breakers are due to the age of the

device. Additionally, due to the age of these devices, it is recommended that these protective devices

be tested for proper operation and replaced if necessary.

Efforts were made to provide the best coordination possible with the protective devices installed in

the existing system. Areas where breaker trip curves overlap indicate areas of possible non-selective

breaker operation. Where possible, efforts were made to reduce non-selective breaker operation

Page 9: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Fourth Avenue Building Power Systems Study

Portland State University February 13, 2015

while maintaining adequate system protection. In some cases, because of device limitations, device

coordination could not be improved. Device limitations included fixed trip settings of breakers.

3.2 Coordination Results and Recommendations

Time-Current Curve (TCC) sets for the systems studied are contained in Appendix C. Each curve set

contains a simplified single-line diagram that graphically describes the relationship between the

devices studied. The referenced plot illustrates the coordination of the listed device with the relevant

“upstream” and “downstream” protective devices. The recommended settings were chosen to provide

the best compromise between complete selectivity and device protection. The protective devices

listed in Appendix C should be set per the suggested settings.

IMPORTANT NOTE: The arc flash incident energy calculations are based on the recommended

settings as given in this study, all recommended settings must be successfully implemented prior to

affixing of the arc flash hazard labels!

4.0 ARC FLASH HAZARD ANALYSIS

SKM Systems Analysis software provides calculations based on either the NFPA 70E or IEEE 1584

calculation procedures. NFPA 70E method estimates incident energy based on a theoretical maximum

value of power dissipated by arcing faults, whereas IEEE 1584 estimates incident energy with

empirical equations developed from statistical analysis of measurements taken from laboratory tests.

The IEEE 1584 method is intended to be more realistic rather than conservative, and aims to avoid

accidents due to limitations provided by over-protection to workers.

4.1 Overview of NFPA 70E and OSHA regulation

Any location where work may be performed on or near energized electrical conductors is subject to

the arc flash standards. PPE used to guard against arc flash hazard should be considered the last line

of defense.

This analysis presents only the results of an incident energy evaluation conducted in accordance with

NFPA 70E, Article 130.5(B). The risk depends on a number of factors. These include the nature of

the task being performed and the condition of the equipment. Selection of personal protective

equipment (PPE) must be made based on the incident energy level that is presented in this report and

a risk assessment to be made by the qualified person.

Page 10: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Fourth Avenue Building Power Systems Study

Portland State University February 13, 2015

4.2 Calculations and Assumptions

The SKM program calculates the three-phase arcing fault current at each bus in the system based on

the available three-phase bolted fault current determined through the short-circuit analysis. The

duration of the arc is determined from the time-current characteristics of the applicable phase

overcurrent devices and the calculated arc fault current. Once the arcing fault current and fault

duration are known, the software calculates the available incident energy and flash-protection

boundary for each location under study.

Since the greatest arc flash hazards may not result from the highest fault current, multiple scenarios

must be analyzed and compared. These scenarios have been evaluated in order to determine the

worst-case incident energy at each location within the system.

The following Scenario #1 assumptions were used in performing the arc flash analysis to ensure

conservative and worst-case results:

· IEEE 1584 calculation procedures

· The minimum available fault current at any location is equal to 50% of the fault current

value.

· Arc Flash calculations shall be based on actual overcurrent protective device clearing time.

Maximum clearing time will be capped at 2 seconds based on IEEE 1584-2002 section

B.1.2. Where it is not physically possible to move outside of the flash protection boundary

in less than 2 seconds during an arc flash event, a maximum clearing time based on the

specific location shall be utilized.

· Maximum expected bolted fault condition. SKM calculates the arcing current at 100% of

the IEEE 1584 estimate.

· Minimum expected bolted fault condition. SKM calculate the arcing current at 85% of the

IEEE 1584 estimate.

The following Scenario #2 assumptions were used in performing the arc flash analysis and ensure

conservative, worst-case results:

· Same as Scenario #1 assumptions.

· Model the distribution system during loss of utility power.

4.3 Results and Recommendations

This section of the report contains the interpretation for the arc flash hazard analysis. Additionally,

due to the age of these devices, actual heat and radiation exposure may be more or less than

reflected in the analysis.

Most of the equipment in this study is between Categories 0 and 2 as indicated on the Arc Flash

Analysis Summary Table located in Appendix D.

Page 11: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Fourth Avenue Building Power Systems Study

Portland State University February 13, 2015

There are (5) five pieces of equipment that was designated Category 3 and above. Refer to TABLE

4.4 for recommendation to achieve the lower levels.

TABLE 4.3 Locations with Category 3 and above.

Equipment Category 3 and above Comment

GEN SET CB (EMDP-P) Category 3 Refer to Table 4.4

400 A 4G CB (PNL 4G) Category 3 Refer to Table 4.4

3200 A Main

CB1 (USB-1)

Dangerous! Refer to Table 4.4

3200 A Main

CB2 (USB-2)

Dangerous! Refer to Table 4.4

3200 A Main

CB3 (USB-5)

Dangerous! Refer to Table 4.4

Each adjustable protective device listed in Appendix C must remain at the stated settings in order to

achieve and maintain incident energy levels listed in Table D.1 located in Appendix D.

Refer to Table D.1 Arc Flash Analysis Summary Table and equipment warning labels in Figure D.1

in Appendix D for detailed arc flash results. Table D.1 details the arc flash analysis giving the

working distance, incident energy in calories/square centimeters, and required personal FR clothing

category. See the arc flash summary table heading descriptions for descriptions of each Table D.1

column and their meaning located in Appendix D.

To reduce the other protective devices it is recommended to replace and or test the circuit breaker

and adjust the trip setting.

The Protective Device Settings and the Arc Flash Summary to support the Category Level

recommendations are located in Appendix E.

TABLE 4.4 Recommendation to reduce the Equipment Category Levels

Equipment Category Comment

GEN SET CB (EMDP-P) Category 1 Test or replace Circuit Breaker

and adjust setting.

400 A 4G CB (PNL 4G) Category 1 Test or replace Circuit Breakerand adjust setting.

3200 A Main

CB1 (USB-1)

Category 2 Test or replace Circuit Breaker

and adjust setting.

3200 A MainCB2 (USB-2)

Category 2 Test or replace Circuit Breakerand adjust setting.

3200 A Main

CB3 (USB-5)

Category 2 Test or replace Circuit Breaker

and adjust setting.

Page 12: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Fourth Avenue Building Power Systems Study

Portland State University February 13, 2015

Each adjustable protective device listed in Appendix E must be either tested or replaced to ensure

that the incident energy levels located within Appendix E can be achieved.

IMPORTANT NOTE: The Arc flash hazard analysis methods and calculations used within this

study are based on the protective devices operating as designed and being applied, maintained

and tested as per the manufacturer’s specifications and accepted industry standards. Periodic

maintenance and testing of the electrical equipment is highly recommended as endorsed by

the NFPA-70B Standard, Recommended Standard for Electrical Equipment Maintenance, toconfirm the safe and acceptable operation of the power system equipment and protective

devices.

IMPORTANT NOTE: Sparling, Inc. and ECCO will not be responsible for the misuse or

misapplication of the information contained in this analysis. Those providing service for electrical

equipment should contact the equipment manufacturer or other qualified individual, if anyquestions arise.

Page 13: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

APPENDIX A

Page 14: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Input Report Interpretation Input Data Tables are provided on the following pages.

The following is a guide for interpreting the input data.

1. Service Transformer Data

· Service Transformer data includes the transformer kVA rating and X/R ratios are obtained

from Eaton Campus Study.

2. Feeder Data

· Impedance values for conductors were obtained from SKM database and are based on the

Tables 4A-7 and 4A-8 of IEEE Std 141 (Red Book).

· Impedance values are based on NEC Table 310.15 (B)(16) conductor temperatures of 75

degree Celsius for Copper and 90 degree Celsius for Aluminum.

· Conductors type, size and length were field verified by the Electrical Contractor ECCO.

Page 15: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

DAPPER Fault Contribution Complete Report

Comprehensive Short Circuit Study Settings

Three Phase Fault

Single Line to Ground

Line to Line Fault

Line to Line to Ground

All BusesFaulted Bus

Yes

Yes

Yes

No

No

Motor Contribution

Transformer Tap

Xformer Phase Shift

Yes

Yes

Bus Voltages

Branch Currents

Phase or Sequence

Fault Current Calculation

Asym Fault Current at Time 0.50

First Bus From Fault

First Branch From Fault

Report phase quantities

Asymmetrical RMS (with DC offset and Decay)

Cycles

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

USB-1 033,520 0 0 44,536 43,582 032,802

P4Y FEED 1,7932,069 0 0 2,749 0 0InCABLE 1,350

TIE FEED 00 0 0 0 0 0InCABLE 0

USB-1 FEED 00 0 0 0 0 0InCABLE 0

1500KVA XFMR1 41,78931,451 0 0 41,787 0 0In2W-XFMR 31,452 32,802

SWGW 1 UTIL BUS 010,000,074 0 0 13,827,160 13,827,126 010,000,049

1500KVA XFMR1 6975 0 0 103 0 0In2W-XFMR 50

1

Project: 4TH AVENUE BUILDING NORMAL POWER SHORT CIRCUIT

Page 16: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

SWGR #1 13,827,05710,000,000 0 0 13,827,056 0 0InUTILITY 9,999,999 10,000,054

P4Y 031,784 0 0 40,740 38,510 030,153

150KVA XFMR FEED 00 0 0 0 0 0InCABLE 0

4D2 FEED 621768 0 0 985 0 0InCABLE 486

ASU9A FEED 3442 0 0 54 0 0InCABLE 27

P4Y FEED 36,83329,708 0 0 38,079 0 0InCABLE 28,841 30,153

WWP2 FEED 342424 0 0 543 0 0InCABLE 268

WWP3 FEED 341422 0 0 541 0 0InCABLE 267

WWP4 FEED 340421 0 0 540 0 0InCABLE 267

ASU9 BUS 02,643 0 0 2,643 2,207 02,207

ASU9A FEED 2,2022,633 0 0 2,633 0 0InCABLE 2,202 2,207

ASU9A-1 FEED 1221 0 0 21 0 0InCABLE 12

ASU9A-2 FEED 1221 0 0 21 0 0InCABLE 12

150 KVA XFMR SEC BUS 012,301 0 0 13,842 14,535 012,862

L1 DISC FEED 00 0 0 0 0 0InCABLE 0

L1A DISC FEED 00 0 0 0 0 0InCABLE 0

2

Page 17: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

150KVA XFMR 14,53512,301 0 0 13,842 0 0In2W-XFMR 12,862 12,862

PNL L1A 05,878 0 0 5,897 5,095 05,076

L1A FEED 5,0955,878 0 0 5,897 0 0InCABLE 5,076 5,076

PNL L1 06,046 0 0 6,069 5,263 05,241

L1 FEED 5,2636,046 0 0 6,069 0 0InCABLE 5,241 5,241

PNL 4D2 014,132 0 0 14,166 11,526 011,497

4D2 FEED 11,17713,492 0 0 13,524 0 0InCABLE 11,149 11,497

CHWP1A FEED 225415 0 0 416 0 0InCABLE 225

CHWP1B FEED 3871 0 0 71 0 0InCABLE 38

CWP1A FEED 2953 0 0 53 0 0InCABLE 29

CWP1B FEED 3871 0 0 71 0 0InCABLE 38

DHRC-1 FEED 96177 0 0 178 0 0InCABLE 96

USB-2 049,298 0 0 67,616 58,010 041,450

4G FEED 00 0 0 0 0 0InCABLE 0

4J1 FEED 00 0 0 0 0 0InCABLE 0

ATS-1 FEED 6886 0 0 118 0 0InCABLE 48

3

Page 18: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

EDP15 XFMR FEED 00 0 0 0 0 0InCABLE 0

MCC10 FEED 440561 0 0 769 0 0InCABLE 314

P4X FEED 306390 0 0 535 0 0InCABLE 218

P4Z FEED 5,4346,927 0 0 9,501 0 0InCABLE 3,883

TIE FEED 00 0 0 0 0 0InCABLE 0

USB-2 FEED 00 0 0 0 0 0InCABLE 0

WCU-4 SW FEED 3,9064,979 0 0 6,829 0 0InCABLE 2,791

WCU-5 SW FEED 3,9064,979 0 0 6,829 0 0InCABLE 2,791

1500KVA XFMR2 43,98731,429 0 0 43,107 0 0In2W-XFMR 31,430 41,450

PNL USB-1 030,134 0 0 35,283 32,850 028,314

MBP-B FEED1 00 0 0 0 0 0InCABLE 0

USB-1 FEED 32,85030,134 0 0 35,283 0 0InCABLE 28,314 28,314

PNL 4G 010,657 0 0 10,667 8,263 08,241

45KVA XFMR FEED 00 0 0 0 0 0InCABLE 0

4G FEED 8,26310,657 0 0 10,667 0 0InCABLE 8,241 8,241

ASU9A-1 BUS 02,245 0 0 2,245 1,874 01,874

4

Page 19: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

ASU9A-1 FEED 1,8712,240 0 0 2,240 0 0InCABLE 1,871 1,874

ASU9A-1 1221 0 0 21 0 0InIND-MTR 12

ASU9A-2 BUS 01,951 0 0 1,951 1,628 01,628

ASU9A-2 FEED 1,6261,946 0 0 1,946 0 0InCABLE 1,626 1,628

ASU9A-2 1221 0 0 21 0 0InIND-MTR 12

150 KVA XFMR PRI BUS 023,314 0 0 24,521 21,313 020,290

150KVA XFMR FEED 21,31323,314 0 0 24,521 0 0InCABLE 20,290 20,290

150KVA XFMR 00 0 0 0 0 0In2W-XFMR 0

L1A FUSE BUS 010,327 0 0 10,795 10,501 010,079

L1A DISC FEED 10,50110,327 0 0 10,795 0 0InCABLE 10,079 10,079

L1A FEED 00 0 0 0 0 0InCABLE 0

L1 FUSE BUS 010,778 0 0 11,396 11,253 010,678

L1 DISC FEED 11,25310,778 0 0 11,396 0 0InCABLE 10,678 10,678

L1 FEED 00 0 0 0 0 0InCABLE 0

WWP4 BUS 011,546 0 0 11,547 9,587 09,586

WWP4 FEED 9,43811,279 0 0 11,280 0 0InCABLE 9,437 9,586

5

Page 20: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

WWP4 236426 0 0 426 0 0InIND-MTR 236

WWP3 BUS 013,077 0 0 13,079 10,923 010,921

WWP3 FEED 10,76512,795 0 0 12,798 0 0InCABLE 10,764 10,921

WWP3 237426 0 0 426 0 0InIND-MTR 237

WWP2 BUS 019,705 0 0 19,778 17,042 016,995

WWP2 FEED 16,84419,362 0 0 19,434 0 0InCABLE 16,797 16,995

WWP2 245426 0 0 427 0 0InIND-MTR 245

45KVA XFMR PRI BUS 09,819 0 0 9,823 7,666 07,655

45KVA XFMR FEED 7,6669,819 0 0 9,823 0 0InCABLE 7,655 7,655

45KVA XFMR 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR SEC BUS 04,769 0 0 4,793 4,993 04,966

2G FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 4,9934,769 0 0 4,793 0 0In2W-XFMR 4,966 4,966

CHWP1B BUS 02,841 0 0 2,841 2,349 02,349

CHWP1B FEED 2,3372,819 0 0 2,819 0 0InCABLE 2,337 2,349

CHWP1B 3971 0 0 71 0 0InIND-MTR 39

6

Page 21: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

CHWP1A BUS 03,138 0 0 3,138 2,552 02,552

CHWP1A FEED 2,4622,981 0 0 2,981 0 0InCABLE 2,462 2,552

CHWP1A 231426 0 0 426 0 0InIND-MTR 231

CWP1B BUS 03,092 0 0 3,092 2,560 02,560

CWP1B FEED 2,5483,071 0 0 3,071 0 0InCABLE 2,548 2,560

CWP1B 3971 0 0 71 0 0InIND-MTR 39

CWP1A BUS 03,088 0 0 3,088 2,558 02,558

CWP1A FEED 2,5493,072 0 0 3,072 0 0InCABLE 2,549 2,558

CWP1A 2953 0 0 53 0 0InIND-MTR 29

DHRC-1 BUS 012,599 0 0 12,614 10,218 010,204

DHRC-1 FEED 10,14612,466 0 0 12,481 0 0InCABLE 10,132 10,204

DHRC-1 96177 0 0 178 0 0InIND-MTR 96

PNL 2G 04,586 0 0 4,604 4,735 04,715

2G FEED 4,7354,586 0 0 4,604 0 0InCABLE 4,715 4,715

PNL 4J1 033,753 0 0 37,191 29,903 026,605

7

Page 22: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

4J1 FEED 29,90333,753 0 0 37,191 0 0InCABLE 26,605 26,605

4J2 FEED 00 0 0 0 0 0InCABLE 0

15KVA XFMR 2J SEC BUS 02,341 0 0 2,356 2,377 02,362

2J FEED 00 0 0 0 0 0InCABLE 0

15KVA XFMR 2J 2,3772,341 0 0 2,356 0 0In2W-XFMR 2,362 2,362

PNL 2J 02,091 0 0 2,095 2,061 02,058

2J FEED 2,0612,091 0 0 2,095 0 0InCABLE 2,058 2,058

PNL 4J2 033,154 0 0 36,359 29,171 026,078

4J2 FEED 29,17133,154 0 0 36,359 0 0InCABLE 26,078 26,078

XFMR 2J FEED 00 0 0 0 0 0InCABLE 0

PNL USB-2 042,286 0 0 48,428 40,257 034,617

MBP-A FEED1 00 0 0 0 0 0InCABLE 0

USB-2 FEED 40,25742,286 0 0 48,428 0 0InCABLE 34,617 34,617

GEN 1 BUS 02,307 0 0 3,618 3,618 02,307

ATS-1 EM FEED 00 0 0 0 0 0InCABLE 0

GEN-1 3,6182,307 0 0 3,618 0 0InGEN 2,307 2,307

8

Page 23: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

EMDP-P 027,947 0 0 30,501 23,726 021,164

14E FEED 00 0 0 0 0 0InCABLE 0

4E FEED 00 0 0 0 0 0InCABLE 0

EMCC-T6 FEED 00 0 0 0 0 0InCABLE 0

EMDP-P FEED 23,67927,863 0 0 30,410 0 0InCABLE 21,122 21,164

ROOF MOTOR FEED 4986 0 0 94 0 0InCABLE 44

ROOF J-BOX BUS 06,045 0 0 6,045 4,843 04,843

ROOF MOTOR 1 FEED 2343 0 0 43 0 0InCABLE 23

ROOF MOTOR 2 FEED 2343 0 0 43 0 0InCABLE 23

ROOF MOTOR FEED 4,8195,999 0 0 5,999 0 0InCABLE 4,819 4,843

ROOF TOP MOTOR 1 BUS 05,961 0 0 5,961 4,777 04,777

ROOF MOTOR 1 FEED 4,7655,938 0 0 5,938 0 0InCABLE 4,765 4,777

ROOF TOP MOTOR 1 2343 0 0 43 0 0InIND-MTR 23

ROOF TOP MOTOR 2 BUS 05,879 0 0 5,879 4,713 04,713

ROOF MOTOR 2 FEED 4,7015,856 0 0 5,856 0 0InCABLE 4,701 4,713

ROOF TOP MOTOR 2 2343 0 0 43 0 0InIND-MTR 23

9

Page 24: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL EMCC-T6 01,116 0 0 1,116 930 0930

EMCC-T6 FEED 9301,116 0 0 1,116 0 0InCABLE 930 930

15KVA XFMR 2E PRI BUS 09,453 0 0 9,453 7,590 07,589

XFMR 2E FEED 7,5909,453 0 0 9,453 0 0InCABLE 7,589 7,589

15KVA XFMR 2E 00 0 0 0 0 0In2W-XFMR 0

15KVA XFMR 2E SEC BUS 02,271 0 0 2,283 2,327 02,314

2E FEED 00 0 0 0 0 0InCABLE 0

15KVA XFMR 2E 2,3272,271 0 0 2,283 0 0In2W-XFMR 2,314 2,314

PNL 4E 013,112 0 0 13,120 10,263 010,245

4E FEED 10,26313,112 0 0 13,120 0 0InCABLE 10,245 10,245

XFMR 2E FEED 00 0 0 0 0 0InCABLE 0

PNL 2E 02,138 0 0 2,144 2,153 02,147

2E FEED 2,1532,138 0 0 2,144 0 0InCABLE 2,147 2,147

15KVA XFMR 12E PRI BUS 022,487 0 0 22,846 17,665 017,201

XFMR 12E FEED 17,66522,487 0 0 22,846 0 0InCABLE 17,201 17,201

10

Page 25: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

45KVA XFMR 12E 00 0 0 0 0 0In2W-XFMR 0

15KVA XFMR 12E SEC BUS 05,107 0 0 5,142 5,240 05,205

12E FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 12E 5,2405,107 0 0 5,142 0 0In2W-XFMR 5,205 5,205

PNL 14E 023,898 0 0 24,546 18,972 018,198

14E FEED 18,97223,898 0 0 24,546 0 0InCABLE 18,198 18,198

XFMR 12E FEED 00 0 0 0 0 0InCABLE 0

XFMR P1 FEED 00 0 0 0 0 0InCABLE 0

PNL 12E 04,960 0 0 4,990 5,035 05,005

12E FEED 5,0354,960 0 0 4,990 0 0InCABLE 5,005 5,005

30KVA XFMR P1 PRI BUS 02,483 0 0 2,483 2,072 02,072

XFMR P1 FEED 2,0722,483 0 0 2,483 0 0InCABLE 2,072 2,072

30KVA XFMR P1 00 0 0 0 0 0In2W-XFMR 0

30KVA XFMR P1 SEC BUS 02,287 0 0 2,289 2,453 02,448

P1 FEED 00 0 0 0 0 0InCABLE 0

30KVA XFMR P1 2,4532,287 0 0 2,289 0 0In2W-XFMR 2,448 2,448

11

Page 26: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL P1 02,208 0 0 2,210 2,342 02,338

P1 FEED 2,3422,208 0 0 2,210 0 0InCABLE 2,338 2,338

MCC10 027,077 0 0 29,443 22,629 020,278

CHWP-4 FEED 59106 0 0 116 0 0InCABLE 53

CWP-4 FUSE FEED 158283 0 0 307 0 0InCABLE 141

MCC10 FEED 22,32426,529 0 0 28,847 0 0InCABLE 20,004 20,278

P18-3 FEED 99177 0 0 192 0 0InCABLE 88

P18-3 BUS 010,121 0 0 10,121 8,196 08,196

P18-3 FEED 8,14710,030 0 0 10,031 0 0InCABLE 8,147 8,196

P18-3 96177 0 0 177 0 0InIND-MTR 96

CHWP-4 BUS 015,998 0 0 16,002 12,677 012,668

CHWP-4 FEED 12,63915,925 0 0 15,930 0 0InCABLE 12,630 12,668

CHWP-4 56106 0 0 106 0 0InIND-MTR 56

CWP-4 FUSE BUS 016,062 0 0 16,068 12,701 012,691

CWP-4 FEED 149283 0 0 283 0 0InCABLE 149

CWP-4 FUSE FEED 12,59815,867 0 0 15,872 0 0InCABLE 12,588 12,691

12

Page 27: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

CWP-4 BUS 012,053 0 0 12,054 9,684 09,683

CWP-4 FEED 9,59511,888 0 0 11,889 0 0InCABLE 9,594 9,683

CWP-4 152284 0 0 284 0 0InIND-MTR 152

P4Z 044,629 0 0 55,775 45,021 035,723

4A FEED 00 0 0 0 0 0InCABLE 0

4C FEED 00 0 0 0 0 0InCABLE 0

4D FEED 00 0 0 0 0 0InCABLE 0

4DE FEED 237352 0 0 440 0 0InCABLE 188

4F FEED 00 0 0 0 0 0InCABLE 0

4GE FEED 438651 0 0 814 0 0InCABLE 348

4I FEED 3,4135,075 0 0 6,342 0 0InCABLE 2,708

4K FEED 1 00 0 0 0 0 0InCABLE 0

4L FEED 1 00 0 0 0 0 0InCABLE 0

4M FEED 1 188280 0 0 350 0 0InCABLE 150

ELEV#50 DISC FEED 237353 0 0 441 0 0InCABLE 188

MCC12 FEED 255379 0 0 474 0 0InCABLE 202

13

Page 28: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

P4Z FEED 40,25837,547 0 0 46,924 0 0InCABLE 31,944 35,723

XFMR P2Z FEED 00 0 0 0 0 0InCABLE 0

PNL 4A 028,859 0 0 29,440 23,083 022,443

4A FEED 23,08328,859 0 0 29,440 0 0InCABLE 22,443 22,443

XFMR 2A FEED 00 0 0 0 0 0InCABLE 0

75KVA XFMR 2A PRI BUS 026,509 0 0 26,806 20,997 020,642

XFMR 2A FEED 20,99726,509 0 0 26,806 0 0InCABLE 20,642 20,642

75KVA XFMR 2A 00 0 0 0 0 0In2W-XFMR 0

75KVA XFMR 2A SEC BUS 07,618 0 0 7,914 8,115 07,803

2A-1 FEED 00 0 0 0 0 0InCABLE 0

75KVA XFMR 2A 8,1157,618 0 0 7,914 0 0In2W-XFMR 7,803 7,803

PNL 2A-1 07,207 0 0 7,424 7,447 07,225

2A-1 FEED 7,4477,207 0 0 7,424 0 0InCABLE 7,225 7,226

2A-2 FEED 00 0 0 0 0 0InCABLE 0

PNL 2A-2 06,946 0 0 7,118 7,048 06,876

2A-2 FEED 7,0486,946 0 0 7,118 0 0InCABLE 6,876 6,876

14

Page 29: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2B FEED 00 0 0 0 0 0InCABLE 0

PNL 2B 01,472 0 0 1,472 1,254 01,254

2B FEED 1,2541,472 0 0 1,472 0 0InCABLE 1,254 1,254

30KVA XFMR 2F1 PRI BUS 02,027 0 0 2,027 1,684 01,684

XFMR 2F1 FEED 1,6842,027 0 0 2,027 0 0InCABLE 1,684 1,684

30KVA XFMR 2F1 00 0 0 0 0 0In2W-XFMR 0

30KVA XFMR 2F1 SEC BUS 02,271 0 0 2,272 2,468 02,464

2F1 FEED 00 0 0 0 0 0InCABLE 0

30KVA XFMR 2F1 2,4682,271 0 0 2,272 0 0In2W-XFMR 2,464 2,464

PNL 2F1 01,913 0 0 1,914 1,985 01,984

2F1 FEED 1,9851,913 0 0 1,914 0 0InCABLE 1,984 1,985

PNL 4F 09,520 0 0 9,520 7,618 07,618

4F FEED 7,6189,520 0 0 9,520 0 0InCABLE 7,618 7,618

XFMR 2F FEED 00 0 0 0 0 0InCABLE 0

XFMR 2F1 FEED 00 0 0 0 0 0InCABLE 0

30KVA XFMR 2F PRI BUS 07,893 0 0 7,893 6,383 06,383

15

Page 30: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

XFMR 2F FEED 6,3837,893 0 0 7,893 0 0InCABLE 6,383 6,383

30KVA XFMR 2F 00 0 0 0 0 0In2W-XFMR 0

30KVA XFMR 2F SEC BUS 03,993 0 0 4,007 4,171 04,153

2F FEED 00 0 0 0 0 0InCABLE 0

30KVA XFMR 2F 4,1713,993 0 0 4,007 0 0In2W-XFMR 4,153 4,153

PNL 2F 03,747 0 0 3,755 3,833 03,823

2F FEED 3,8333,747 0 0 3,755 0 0InCABLE 3,823 3,823

30KVA XFMR 2GE PRI BUS 07,620 0 0 7,620 6,080 06,079

XFMR 2GE FEED 6,0807,620 0 0 7,620 0 0InCABLE 6,079 6,079

30KVA XFMR 2GE 00 0 0 0 0 0In2W-XFMR 0

30KVA XFMR 2GE SEC BUS 04,255 0 0 4,270 4,464 04,446

2GE FEED 00 0 0 0 0 0InCABLE 0

30KVA XFMR 2GE 4,4644,255 0 0 4,270 0 0In2W-XFMR 4,446 4,446

PNL 2GE 03,307 0 0 3,308 3,258 03,257

2GE FEED 3,2583,307 0 0 3,308 0 0InCABLE 3,257 3,257

PNL 4GE 09,913 0 0 9,914 7,770 07,769

16

Page 31: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

4GE FEED 7,5519,499 0 0 9,500 0 0InCABLE 7,550 7,769

MCC2 FEED 350670 0 0 670 0 0InCABLE 350

XFMR 2GE FEED 00 0 0 0 0 0InCABLE 0

MCC2 09,761 0 0 9,762 7,639 07,637

ASU 14R FEED 2853 0 0 53 0 0InCABLE 28

ASU 14S FEED 147282 0 0 282 0 0InCABLE 147

ASU 15R FEED 2853 0 0 53 0 0InCABLE 28

ASU 15S FEED 147282 0 0 282 0 0InCABLE 147

MCC2 FEED 7,4199,345 0 0 9,346 0 0InCABLE 7,418 7,637

ASU 15S BUS 05,804 0 0 5,804 4,659 04,659

ASU 15S FEED 4,5855,668 0 0 5,668 0 0InCABLE 4,585 4,659

ASU 15S 152284 0 0 284 0 0InIND-MTR 152

ASU 15R BUS 01,686 0 0 1,686 1,393 01,393

ASU 15R FEED 1,3861,673 0 0 1,673 0 0InCABLE 1,386 1,393

ASU 15R 2953 0 0 53 0 0InIND-MTR 29

ASU 14R BUS 01,516 0 0 1,516 1,254 01,254

17

Page 32: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

ASU 14R FEED 1,2461,504 0 0 1,504 0 0InCABLE 1,246 1,254

ASU 14R 2953 0 0 53 0 0InIND-MTR 29

ASU 14S BUS 05,625 0 0 5,625 4,520 04,520

ASU 14S FEED 4,4475,492 0 0 5,492 0 0InCABLE 4,447 4,520

ASU 14S 152284 0 0 284 0 0InIND-MTR 152

75KVA XFMR P2Z PRI BUS 018,683 0 0 18,684 15,114 015,111

XFMR P2Z FEED 15,11418,683 0 0 18,684 0 0InCABLE 15,111 15,111

75KVA XFMR P2Z 00 0 0 0 0 0In2W-XFMR 0

75KVA XFMR P2Z SEC BUS 06,132 0 0 6,321 6,498 06,285

P2Z FEED 00 0 0 0 0 0InCABLE 0

75KVA XFMR P2Z 6,4986,132 0 0 6,321 0 0In2W-XFMR 6,285 6,285

PNL P2Z 05,822 0 0 5,925 5,993 05,888

P2Z FEED 5,9935,822 0 0 5,925 0 0InCABLE 5,888 5,888

SONNYS FEED 00 0 0 0 0 0InCABLE 0

SONNY'S 04,145 0 0 4,151 3,866 03,861

SONNYS FEED 3,8664,145 0 0 4,151 0 0InCABLE 3,861 3,861

18

Page 33: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

ELE#50 BUS 015,000 0 0 15,001 12,114 012,113

ELE#50 FEED 12,00314,796 0 0 14,796 0 0InCABLE 12,002 12,113

ELE #50 191355 0 0 355 0 0InIND-MTR 191

ELE#50 DISC BUS 020,132 0 0 20,135 16,193 016,187

ELE#50 FEED 190354 0 0 354 0 0InCABLE 190

ELEV#50 DISC FEED 16,06519,895 0 0 19,899 0 0InCABLE 16,060 16,187

MCC12 09,342 0 0 9,342 7,372 07,372

CHWP-5 FEED 56106 0 0 106 0 0InCABLE 56

CWP5 FUSE FEED 147280 0 0 280 0 0InCABLE 147

MCC12 FEED 7,2459,101 0 0 9,101 0 0InCABLE 7,244 7,372

CWP5 BUS 03,624 0 0 3,624 2,949 02,949

CWP5 FEED 2,8863,510 0 0 3,510 0 0InCABLE 2,886 2,949

CWP5 154284 0 0 284 0 0InIND-MTR 154

CHWP-5 BUS 03,230 0 0 3,230 2,649 02,649

CHWP-5 FEED 2,6293,195 0 0 3,195 0 0InCABLE 2,629 2,649

CHWP-5 58106 0 0 106 0 0InIND-MTR 58

19

Page 34: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

CWP5 FUSE BUS 03,937 0 0 3,937 3,201 03,201

CWP5 FEED 154283 0 0 283 0 0InCABLE 154

CWP5 FUSE FEED 3,1353,819 0 0 3,819 0 0InCABLE 3,135 3,201

PNL 4D 015,000 0 0 15,006 11,814 011,800

2D2 FEED 00 0 0 0 0 0InCABLE 0

4D FEED 11,81415,000 0 0 15,006 0 0InCABLE 11,800 11,800

XFMR 2D FEED 00 0 0 0 0 0InCABLE 0

PNL 2D2 010,729 0 0 10,729 8,625 08,625

2D2 FEED 8,62510,729 0 0 10,729 0 0InCABLE 8,625 8,625

45KVA XFMR 2D PRI BUS 013,370 0 0 13,372 10,619 010,614

XFMR 2D FEED 10,61913,370 0 0 13,372 0 0InCABLE 10,614 10,614

45KVA XFMR 2D 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR 2D SEC BUS 04,931 0 0 4,956 5,110 05,082

2D FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2D 5,1104,931 0 0 4,956 0 0In2W-XFMR 5,082 5,082

PNL 2D 04,766 0 0 4,785 4,882 04,862

20

Page 35: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2D FEED 4,8824,766 0 0 4,785 0 0InCABLE 4,862 4,862

2D1 FEED 00 0 0 0 0 0InCABLE 0

PNL 2D1 01,535 0 0 1,535 1,341 01,341

2D1 FEED 1,3411,535 0 0 1,535 0 0InCABLE 1,341 1,341

PNL 4DE 020,112 0 0 20,329 15,498 015,218

4DE FEED 15,34119,806 0 0 20,019 0 0InCABLE 15,064 15,218

DHRC2 FEED 91177 0 0 179 0 0InCABLE 89

DHRC3 FEED 91177 0 0 179 0 0InCABLE 89

DHRC2 BUS 017,302 0 0 17,373 13,296 013,188

DHRC2 FEED 13,22217,158 0 0 17,228 0 0InCABLE 13,115 13,188

DHRC2 91177 0 0 178 0 0InIND-MTR 90

DHRC3 BUS 017,302 0 0 17,373 13,296 013,188

DHRC3 FEED 13,22217,158 0 0 17,228 0 0InCABLE 13,115 13,188

DHRC3 91177 0 0 178 0 0InIND-MTR 90

4M CB 2 BUS 013,514 0 0 13,515 10,792 010,791

4M FEED 1 10,69713,337 0 0 13,337 0 0InCABLE 10,696 10,791

21

Page 36: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

4M FEED 2 150282 0 0 282 0 0InCABLE 150

PNL 4M 013,250 0 0 13,250 10,580 010,579

4M FEED 2 10,48613,073 0 0 13,073 0 0InCABLE 10,484 10,579

SF2A FUSE FEED 75141 0 0 141 0 0InCABLE 75

SF2B FUSE FEED 75141 0 0 141 0 0InCABLE 75

SF2B BUS 03,608 0 0 3,608 2,966 02,966

SF2B FEED 2,9403,562 0 0 3,562 0 0InCABLE 2,940 2,966

SF2B 78142 0 0 142 0 0InIND-MTR 78

SF2B FUSE FEED BUS 03,704 0 0 3,704 3,045 03,045

SF2B FEED 78142 0 0 142 0 0InCABLE 78

SF2B FUSE FEED 3,0193,658 0 0 3,658 0 0InCABLE 3,019 3,045

SF2A BUS 03,996 0 0 3,996 3,283 03,283

SF2A FEED 3,2573,949 0 0 3,949 0 0InCABLE 3,257 3,283

SF2A 78142 0 0 142 0 0InIND-MTR 78

SF2A FUSE FEED BUS 04,115 0 0 4,115 3,380 03,380

SF2A FEED 78142 0 0 142 0 0InCABLE 78

22

Page 37: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

SF2A FUSE FEED 3,3534,067 0 0 4,067 0 0InCABLE 3,353 3,380

4K CB 2 BUS 09,445 0 0 9,446 5,911 05,910

4K FEED 1 5,9119,445 0 0 9,446 0 0InCABLE 5,910 5,910

4K FEED 2 00 0 0 0 0 0InCABLE 0

PNL 4K 09,281 0 0 9,282 5,828 05,828

4K FEED 2 5,8289,281 0 0 9,282 0 0InCABLE 5,828 5,828

PNL 4I 028,078 0 0 31,247 19,911 018,699

4I FEED 17,28222,520 0 0 25,061 0 0InCABLE 16,230 18,699

CHILLER 1 FEED 2,4035,083 0 0 5,656 0 0InCABLE 2,257

MCC4 FEED 249527 0 0 587 0 0InCABLE 234

CHILLER 1 BUS 020,473 0 0 21,105 13,290 013,071

CHILLER 1 FEED 11,14915,587 0 0 16,068 0 0InCABLE 10,966 13,071

CHILLER 1 2,3705,477 0 0 5,646 0 0InIND-MTR 2,331

MCC4 025,567 0 0 27,331 17,836 017,058

ASU11 FEED 65141 0 0 150 0 0InCABLE 63

ASU12 FEED 65141 0 0 150 0 0InCABLE 63

23

Page 38: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

ASU13 FEED 66141 0 0 151 0 0InCABLE 63

CWP1 FEED 49106 0 0 113 0 0InCABLE 47

MCC4 FEED 17,59925,057 0 0 26,785 0 0InCABLE 16,831 17,058

ASU13 BUS 03,973 0 0 3,973 3,193 03,193

ASU13 FEED 3,1683,929 0 0 3,929 0 0InCABLE 3,168 3,193

ASU13 76142 0 0 142 0 0InIND-MTR 76

ASU11 BUS 02,845 0 0 2,845 2,306 02,306

ASU11 FEED 2,2842,806 0 0 2,806 0 0InCABLE 2,284 2,306

ASU11 77142 0 0 142 0 0InIND-MTR 77

ASU12 BUS 02,845 0 0 2,845 2,306 02,306

ASU12 FEED 2,2842,806 0 0 2,806 0 0InCABLE 2,284 2,306

ASU12 77142 0 0 142 0 0InIND-MTR 77

CWP1 BUS 02,649 0 0 2,649 2,153 02,153

CWP1 FEED2 2,1372,620 0 0 2,620 0 0InCABLE 2,137 2,153

CWP1 58106 0 0 106 0 0InIND-MTR 58

CWP1 FUSE 2 BUS 03,963 0 0 3,963 3,188 03,188

24

Page 39: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

CWP1 FEED 3,1703,929 0 0 3,929 0 0InCABLE 3,170 3,188

CWP1 FEED2 57106 0 0 106 0 0InCABLE 57

PNL 4L 018,951 0 0 19,010 14,768 014,674

4L FEED 2 14,76818,951 0 0 19,010 0 0InCABLE 14,674 14,674

4L CB 2 BUS 019,276 0 0 19,341 15,027 014,926

4L FEED 1 15,02719,276 0 0 19,341 0 0InCABLE 14,926 14,926

4L FEED 2 00 0 0 0 0 0InCABLE 0

PNL 4C 022,452 0 0 22,594 17,588 017,395

4C FEED 17,58822,452 0 0 22,594 0 0InCABLE 17,395 17,395

XFMR 2C FEED 00 0 0 0 0 0InCABLE 0

XFMR 2C2 FEED 00 0 0 0 0 0InCABLE 0

30KVA XFMR 2C2 PRI BUS 016,982 0 0 16,987 13,489 013,478

XFMR 2C2 FEED 13,48916,982 0 0 16,987 0 0InCABLE 13,478 13,478

30KVA XFMR 2C2 00 0 0 0 0 0In2W-XFMR 0

30KVA XFMR 2C2 SEC BUS 02,120 0 0 2,133 2,155 02,142

2C2 FEED 00 0 0 0 0 0InCABLE 0

25

Page 40: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

30KVA XFMR 2C2 2,1552,120 0 0 2,133 0 0In2W-XFMR 2,142 2,142

PNL 2C2 02,068 0 0 2,079 2,085 02,075

2C2 FEED 2,0852,068 0 0 2,079 0 0InCABLE 2,075 2,075

30KVA XFMR 2C PRI BUS 020,062 0 0 20,105 15,776 015,708

XFMR 2C FEED 15,77620,062 0 0 20,105 0 0InCABLE 15,708 15,708

45KVA XFMR 2C 00 0 0 0 0 0In2W-XFMR 0

30KVA XFMR 2C SEC BUS 05,072 0 0 5,103 5,213 05,181

2C FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2C 5,2135,072 0 0 5,103 0 0In2W-XFMR 5,181 5,181

PNL 2C 04,829 0 0 4,851 4,880 04,859

2C FEED 4,8804,829 0 0 4,851 0 0InCABLE 4,859 4,859

1000KVA XFMR EDP15 SEC

BUS

056,260 0 0 72,756 84,585 063,886

EDP15 FEED 00 0 0 0 0 0InCABLE 0

1000KVA XFMR EDP15 84,58556,260 0 0 72,756 0 0In2W-XFMR 63,886 63,887

PNL EDP15 050,023 0 0 59,640 63,213 052,967

26

Page 41: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

EDP-E FEED 00 0 0 0 0 0InCABLE 0

EDP15 FEED 63,21350,023 0 0 59,640 0 0InCABLE 52,967 52,968

1000KVA XFMR EDP15 PRI

BUS

038,906 0 0 44,116 36,175 031,339

EDP15 XFMR FEED 36,17538,906 0 0 44,116 0 0InCABLE 31,339 31,339

1000KVA XFMR EDP15 00 0 0 0 0 0In2W-XFMR 0

PNL EDP-E 026,215 0 0 27,089 23,231 022,357

2D3 FEED 00 0 0 0 0 0InCABLE 0

EDP-E FEED 23,23126,215 0 0 27,089 0 0InCABLE 22,357 22,357

PNL 2D3 04,056 0 0 4,056 3,199 03,198

2D3 FEED 3,1994,056 0 0 4,056 0 0InCABLE 3,198 3,198

WCU-4 SW BUS 031,255 0 0 35,281 25,356 022,179

WCU-4 FEED 2,9105,381 0 0 6,074 0 0InCABLE 2,546

WCU-4 SW FEED 22,50925,998 0 0 29,347 0 0InCABLE 19,689 22,179

WCU-5 SW BUS 031,255 0 0 35,281 25,356 022,179

WCU-5 FEED 2,9105,381 0 0 6,074 0 0InCABLE 2,546

WCU-5 SW FEED 22,50925,998 0 0 29,347 0 0InCABLE 19,689 22,179

27

Page 42: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL P4X 027,853 0 0 30,386 23,505 020,983

EF-11 FUSE FEED 60106 0 0 116 0 0InCABLE 53

ELEV1 CB FEED 81143 0 0 156 0 0InCABLE 72

ELEV2 CB FEED 81144 0 0 157 0 0InCABLE 72

P4X FEED 23,28727,465 0 0 29,963 0 0InCABLE 20,789 20,983

EF-11 BUS 03,938 0 0 3,938 3,257 03,257

EF-11 FEED 3,2393,905 0 0 3,905 0 0InCABLE 3,239 3,257

EF-11 59106 0 0 106 0 0InIND-MTR 59

EF-11 FUSE BUS 04,368 0 0 4,368 3,611 03,611

EF-11 FEED 59106 0 0 106 0 0InCABLE 59

EF-11 FUSE FEED 3,5924,334 0 0 4,334 0 0InCABLE 3,592 3,611

27KVA XFMR ELEV1 SEC

BUS

0763 0 0 771 744 0737

ELEV1 FEED 115177 0 0 179 0 0InCABLE 114

27KVA XFMR ELEV1 646614 0 0 621 0 0In2W-XFMR 640 737

27KVA XFMR ELEV1 PRI BUS 04,576 0 0 4,576 3,755 03,755

ELEV1 XFMR FEED 3,7184,509 0 0 4,509 0 0InCABLE 3,718 3,755

28

Page 43: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

27KVA XFMR ELEV1 79145 0 0 145 0 0In2W-XFMR 79

ELEV1 CB2 BUS 07,208 0 0 7,208 5,883 05,883

ELEV1 CB FEED 5,8397,129 0 0 7,129 0 0InCABLE 5,839 5,883

ELEV1 XFMR FEED 78144 0 0 144 0 0InCABLE 78

ELEV1 BUS 0739 0 0 747 714 0709

ELEV1 FEED 618594 0 0 600 0 0InCABLE 614 709

ELEV1 114177 0 0 179 0 0InIND-MTR 113

WCU-4 BUS 029,072 0 0 32,460 22,777 020,155

WCU-4 FEED 19,99723,760 0 0 26,529 0 0InCABLE 17,695 20,155

WCU-4 2,8615,477 0 0 6,115 0 0InIND-MTR 2,531

WCU-5 BUS 029,072 0 0 32,460 22,777 020,155

WCU-5 FEED 19,99723,760 0 0 26,529 0 0InCABLE 17,695 20,155

WCU-5 2,8615,477 0 0 6,115 0 0InIND-MTR 2,531

27KVA XFMR ELEV2 SEC

BUS

0790 0 0 801 762 0754

ELEV2 FEED 114177 0 0 179 0 0InCABLE 113

27KVA XFMR ELEV2 664638 0 0 647 0 0In2W-XFMR 656 754

29

Page 44: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

27KVA XFMR ELEV2 PRI BUS 07,215 0 0 7,215 5,892 05,892

ELEV2 XFMR FEED 5,8497,137 0 0 7,137 0 0InCABLE 5,849 5,892

27KVA XFMR ELEV2 79144 0 0 144 0 0In2W-XFMR 79

ELEV2 CB2 BUS 08,901 0 0 8,901 7,234 07,234

ELEV2 CB FEED 7,1888,816 0 0 8,816 0 0InCABLE 7,188 7,234

ELEV2 XFMR FEED 78144 0 0 144 0 0InCABLE 78

ELEV2 BUS 0761 0 0 770 724 0719

ELEV2 FEED 629613 0 0 620 0 0InCABLE 624 719

ELEV2 113177 0 0 179 0 0InIND-MTR 112

SWGW 2 UTIL BUS 010,000,439 0 0 13,827,642 13,827,448 010,000,292

1500KVA XFMR2 405439 0 0 608 0 0In2W-XFMR 293

SWGR #2 13,827,04310,000,000 0 0 13,827,035 0 0InUTILITY 9,999,999 10,000,297

USB-5 035,917 0 0 51,367 48,943 034,156

4J FEED 478526 0 0 752 0 0InCABLE 333

EB2 FEED 3,0793,389 0 0 4,847 0 0InCABLE 2,149

MCC3 FEED 818901 0 0 1,288 0 0InCABLE 571

30

Page 45: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

P4A FEED 00 0 0 0 0 0InCABLE 0

P4B FEED 00 0 0 0 0 0InCABLE 0

P4D FEED 00 0 0 0 0 0InCABLE 0

1500KVA XFMR3 44,57131,104 0 0 44,483 0 0In2W-XFMR 31,105 34,156

UTIL BUS 010,000,160 0 0 13,827,284 13,827,209 010,000,106

1500KVA XFMR3 148160 0 0 222 0 0In2W-XFMR 107

UTIL 13,827,06110,000,000 0 0 13,827,062 0 0InUTILITY 9,999,999 10,000,111

PNL 4J 023,997 0 0 26,560 22,277 020,074

4J FEED 21,95623,479 0 0 25,987 0 0InCABLE 19,786 20,074

PNL 4F-13 FEED 109177 0 0 195 0 0InCABLE 98

SF1A FUSE FEED 109176 0 0 195 0 0InCABLE 98

SF1B FUSE FEED 109177 0 0 196 0 0InCABLE 99

SF1A FUSE BUS 05,660 0 0 5,660 4,692 04,692

SF1A FEED 98177 0 0 177 0 0InCABLE 98

SF1A FUSE FEED 4,6535,592 0 0 5,592 0 0InCABLE 4,653 4,692

SF1A BUS 05,166 0 0 5,166 4,281 04,281

31

Page 46: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

SF1A FEED 4,2455,101 0 0 5,101 0 0InCABLE 4,245 4,281

SF1A 98177 0 0 177 0 0InIND-MTR 98

SF1B FUSE BUS 07,905 0 0 7,905 6,556 06,556

SF1B FEED 98177 0 0 177 0 0InCABLE 98

SF1B FUSE FEED 6,5107,823 0 0 7,823 0 0InCABLE 6,510 6,556

SF1B BUS 06,987 0 0 6,987 5,794 05,794

SF1B FEED 5,7526,911 0 0 6,911 0 0InCABLE 5,752 5,794

SF1B 98177 0 0 177 0 0InIND-MTR 98

SFGA FUSE BUS 08,772 0 0 8,772 5,553 05,553

SFGA FEED 75177 0 0 177 0 0InCABLE 75

SFGA FUSE FEED 5,5118,673 0 0 8,673 0 0InCABLE 5,511 5,553

SFGA BUS 08,051 0 0 8,051 5,044 05,044

SFGA FEED 5,0057,957 0 0 7,957 0 0InCABLE 5,005 5,044

SFGA 74177 0 0 177 0 0InIND-MTR 74

PNL 4F-13 020,589 0 0 21,959 17,357 016,479

PNL 4F-13 FEED 17,26220,420 0 0 21,779 0 0InCABLE 16,388 16,479

32

Page 47: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

SFGA FUSE FEED 99177 0 0 189 0 0InCABLE 94

PNL P4A 035,366 0 0 49,852 47,116 033,399

P4A FEED 47,11635,366 0 0 49,852 0 0InCABLE 33,399 33,399

PNL 4B FEED 00 0 0 0 0 0InCABLE 0

PNL 4G-104 FEED 00 0 0 0 0 0InCABLE 0

XFMR 2GA FEED 00 0 0 0 0 0InCABLE 0

XFMR 2GB FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2GA PRI BUS 031,187 0 0 33,336 30,237 028,561

XFMR 2GA FEED 30,23731,187 0 0 33,336 0 0InCABLE 28,561 28,561

45KVA XFMR 2GA 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR 2GA SEC BUS 06,430 0 0 6,478 6,585 06,538

2GA FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2GA 6,5856,430 0 0 6,478 0 0In2W-XFMR 6,538 6,538

PNL 2GA 05,900 0 0 5,927 5,866 05,840

2GA FEED 5,8665,900 0 0 5,927 0 0InCABLE 5,840 5,840

2GA2 FEED 00 0 0 0 0 0InCABLE 0

33

Page 48: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL 2GA2 05,708 0 0 5,731 5,619 05,598

2GA2 FEED 5,6195,708 0 0 5,731 0 0InCABLE 5,598 5,598

45KVA XFMR 2GB PRI BUS 031,187 0 0 33,336 30,237 028,561

XFMR 2GB FEED 30,23731,187 0 0 33,336 0 0InCABLE 28,561 28,561

45KVA XFMR 2GB 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR 2GB SEC BUS 06,430 0 0 6,478 6,585 06,538

2GB FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2GB 6,5856,430 0 0 6,478 0 0In2W-XFMR 6,538 6,538

PNL 2GB 05,900 0 0 5,927 5,866 05,840

2GB FEED 5,8665,900 0 0 5,927 0 0InCABLE 5,840 5,840

2GB2 FEED 00 0 0 0 0 0InCABLE 0

PNL 2GB2 05,708 0 0 5,731 5,619 05,598

2GB2 FEED 5,6195,708 0 0 5,731 0 0InCABLE 5,598 5,598

PNL 4G-104 031,277 0 0 34,936 28,938 027,455

PNL 4G-104 FEED 28,93831,277 0 0 34,936 0 0InCABLE 27,455 27,455

34

Page 49: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL 4B 015,806 0 0 15,946 11,212 011,191

PNL 4B FEED 11,21215,806 0 0 15,946 0 0InCABLE 11,191 11,191

XFMR 2B1 FEED 00 0 0 0 0 0InCABLE 0

PNL 2B1 05,249 0 0 5,335 5,220 05,131

2B1 FEED 5,2205,249 0 0 5,335 0 0InCABLE 5,131 5,131

2B2 FEED 00 0 0 0 0 0InCABLE 0

PNL 2B2 05,104 0 0 5,176 5,022 04,947

2B2 FEED 5,0225,104 0 0 5,176 0 0InCABLE 4,947 4,947

PNL P4B 032,497 0 0 42,786 38,957 029,629

P4B FEED 38,95732,497 0 0 42,786 0 0InCABLE 29,629 29,629

PNL 4C-12 FEED 00 0 0 0 0 0InCABLE 0

PNL 4H FEED 00 0 0 0 0 0InCABLE 0

PNL 4C-12 020,317 0 0 20,535 15,084 015,051

PNL 4C-12 FEED 15,08420,317 0 0 20,535 0 0InCABLE 15,051 15,051

XFMR 2CA FEED 00 0 0 0 0 0InCABLE 0

XFMR 2CA PRI BUS 018,623 0 0 18,716 13,783 013,768

35

Page 50: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

XFMR 2CA FEED 13,78318,623 0 0 18,716 0 0InCABLE 13,768 13,768

50KVA XFMR 2CA 00 0 0 0 0 0In2W-XFMR 0

XFMR 2CA SEC BUS 07,703 0 0 7,752 8,030 07,978

2CA FEED 00 0 0 0 0 0InCABLE 0

50KVA XFMR 2CA 8,0307,703 0 0 7,752 0 0In2W-XFMR 7,978 7,978

PNL 2CA 07,076 0 0 7,099 7,167 07,145

2C1 FEED 00 0 0 0 0 0InCABLE 0

2CA FEED 7,1677,076 0 0 7,099 0 0InCABLE 7,145 7,145

PNL 2C1 05,833 0 0 5,838 5,615 05,611

2C1 FEED 5,6155,833 0 0 5,838 0 0InCABLE 5,611 5,611

2C2-12 FEED 00 0 0 0 0 0InCABLE 0

PNL 2C2-12 05,608 0 0 5,611 5,352 05,349

2C2-12 FEED 5,3525,608 0 0 5,611 0 0InCABLE 5,349 5,349

PNL 4H 025,272 0 0 26,125 20,415 020,208

PNL 4H FEED 20,41525,272 0 0 26,125 0 0InCABLE 20,208 20,208

PNL P4D 032,109 0 0 41,923 37,999 029,140

36

Page 51: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

P4D FEED 37,99932,109 0 0 41,923 0 0InCABLE 29,140 29,140

PNL 4D1 FEED 00 0 0 0 0 0InCABLE 0

XFMR 2C-12 FEED 00 0 0 0 0 0InCABLE 0

XFMR KL FEED 00 0 0 0 0 0InCABLE 0

XFMR P2D FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR P2D PRI BUS 018,384 0 0 18,394 15,700 015,694

XFMR P2D FEED 15,70018,384 0 0 18,394 0 0InCABLE 15,694 15,694

45KVA XFMR P2D 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR P2D SEC BUS 04,094 0 0 4,118 4,195 04,170

P2D FUSE FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR P2D 4,1954,094 0 0 4,118 0 0In2W-XFMR 4,170 4,170

P2D FUSE BUS 03,852 0 0 3,866 3,871 03,857

P2D FEED 00 0 0 0 0 0InCABLE 0

P2D FUSE FEED 3,8713,852 0 0 3,866 0 0InCABLE 3,857 3,857

PNL P2D 03,210 0 0 3,213 2,876 02,875

P2D FEED 2,8763,210 0 0 3,213 0 0InCABLE 2,875 2,875

37

Page 52: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL 4D1 026,131 0 0 27,358 21,675 021,311

PNL 4D1 FEED 21,67526,131 0 0 27,358 0 0InCABLE 21,311 21,311

XFMR 2D1 FEED 00 0 0 0 0 0InCABLE 0

XFMR 2D1 PRI BUS 021,016 0 0 21,101 16,754 016,730

XFMR 2D1 FEED 16,75421,016 0 0 21,101 0 0InCABLE 16,730 16,730

45KVA XFMR 2D1 00 0 0 0 0 0In2W-XFMR 0

XFMR 2D1 SEC BUS 04,551 0 0 4,580 4,664 04,635

2D1-02 FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2D1 4,6644,551 0 0 4,580 0 0In2W-XFMR 4,635 4,635

PNL 2D1-02 04,255 0 0 4,271 4,268 04,253

2D1-02 FEED 4,2684,255 0 0 4,271 0 0InCABLE 4,253 4,253

112.5KVA XFMR KL PRI BUS 016,899 0 0 17,117 13,949 013,723

XFMR KL FEED 13,94916,899 0 0 17,117 0 0InCABLE 13,723 13,723

112.5KVA XFMR KL 00 0 0 0 0 0In2W-XFMR 0

XFMR 2C-12 PRI BUS 011,835 0 0 11,837 7,719 07,719

38

Page 53: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

XFMR 2C-12 FEED 7,71911,835 0 0 11,837 0 0InCABLE 7,719 7,719

75KVA XFMR 2C-12 00 0 0 0 0 0In2W-XFMR 0

XFMR 2C-12 SEC BUS 06,124 0 0 6,288 6,573 06,376

2C-12 FEED 00 0 0 0 0 0InCABLE 0

75KVA XFMR 2C-12 6,5736,124 0 0 6,288 0 0In2W-XFMR 6,376 6,376

PNL 2C-12 04,830 0 0 4,846 4,726 04,714

2C-12 FEED 4,7264,830 0 0 4,846 0 0InCABLE 4,714 4,714

2C3 FEED 00 0 0 0 0 0InCABLE 0

PNL 2C3 04,615 0 0 4,625 4,465 04,458

2C3 FEED 4,4654,615 0 0 4,625 0 0InCABLE 4,458 4,458

MCC-3 031,935 0 0 41,525 37,321 028,778

2G1 JUNC FEED 00 0 0 0 0 0InCABLE 0

2P-1 CB FEED 00 0 0 0 0 0InCABLE 0

ELEV 4&5 FEED 329422 0 0 549 0 0InCABLE 254

MCC3 FEED 36,61731,031 0 0 40,350 0 0InCABLE 28,235 28,778

P-19-1 FEED 2835 0 0 46 0 0InCABLE 21

39

Page 54: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

P-19-2 FEED 2835 0 0 46 0 0InCABLE 21

PNL 4K PENTHOUSE FEED 321412 0 0 536 0 0InCABLE 247

P-19-1 BUS 01,340 0 0 1,340 781 0781

P-19-1 FEED 7791,334 0 0 1,334 0 0InCABLE 779 781

P-19-1 1435 0 0 35 0 0InIND-MTR 14

P-19-2 BUS 01,340 0 0 1,340 781 0781

P-19-2 FEED 7791,334 0 0 1,334 0 0InCABLE 779 781

P-19-2 1435 0 0 35 0 0InIND-MTR 14

75KVA XFMR 2P-1 PRI BUS 014,160 0 0 14,167 9,559 09,559

XFMR 2P-1 FEED 9,55914,160 0 0 14,167 0 0InCABLE 9,559 9,559

75KVA XFMR 2P-1 00 0 0 0 0 0In2W-XFMR 0

75KVA XFMR 2P-1 SEC BUS 04,356 0 0 4,499 4,621 04,461

2P-1 FEED 00 0 0 0 0 0InCABLE 0

75KVA XFMR 2P-1 4,6214,356 0 0 4,499 0 0In2W-XFMR 4,461 4,461

PNL 2P-1 04,183 0 0 4,299 4,344 04,219

2P-1 FEED 4,3444,183 0 0 4,299 0 0InCABLE 4,219 4,219

40

Page 55: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2P-2 FEED 00 0 0 0 0 0InCABLE 0

2P-1 BUS 014,854 0 0 14,863 9,971 09,970

2P-1 CB FEED 9,97114,854 0 0 14,863 0 0InCABLE 9,970 9,970

XFMR 2P-1 FEED 00 0 0 0 0 0InCABLE 0

PNL 2P-2 03,984 0 0 4,054 4,034 03,965

2P-2 FEED 4,0343,984 0 0 4,054 0 0InCABLE 3,965 3,965

ELEV 4&5 JUNCTION 014,366 0 0 14,367 9,218 09,218

ELEV 4 FUSE FEED 91212 0 0 212 0 0InCABLE 91

ELEV 4&5 FEED 9,10414,101 0 0 14,102 0 0InCABLE 9,104 9,218

ELEV 5 FUSE FEED 91212 0 0 212 0 0InCABLE 91

ELEV 4 BUS 07,595 0 0 7,595 4,565 04,565

ELEV 4 FEED 4,5277,502 0 0 7,502 0 0InCABLE 4,527 4,565

ELEV 4 85213 0 0 213 0 0InIND-MTR 85

ELEV 5 BUS 07,595 0 0 7,595 4,565 04,565

ELEV 5 FEED 4,5277,502 0 0 7,502 0 0InCABLE 4,527 4,565

ELEV 5 85213 0 0 213 0 0InIND-MTR 85

41

Page 56: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

ELEV 5 FUSE BUS 012,566 0 0 12,566 7,900 07,900

ELEV 5 FEED 89212 0 0 212 0 0InCABLE 89

ELEV 5 FUSE FEED 7,84812,443 0 0 12,443 0 0InCABLE 7,848 7,900

ELEV 4 FUSE BUS 012,566 0 0 12,566 7,900 07,900

ELEV 4 FEED 89212 0 0 212 0 0InCABLE 89

ELEV 4 FUSE FEED 7,84812,443 0 0 12,443 0 0InCABLE 7,848 7,900

PNL 4K PENTHOUSE 021,147 0 0 21,905 16,358 016,156

PNL 4K PENTHOUSE FEED 16,15220,748 0 0 21,491 0 0InCABLE 15,953 16,157

TOWER41 FUSE FEED 107208 0 0 215 0 0InCABLE 106

TOWER42 FUSE FEED 107207 0 0 214 0 0InCABLE 105

XFMR 2K FEED 00 0 0 0 0 0InCABLE 0

XFMR 2K-232 FEED 00 0 0 0 0 0InCABLE 0

XFMR 2L-1 FEED 00 0 0 0 0 0InCABLE 0

9KVA XFMR 2K PRI BUS 017,076 0 0 17,129 12,964 012,949

XFMR 2K FEED 12,96417,076 0 0 17,129 0 0InCABLE 12,949 12,949

9KVA XFMR 2K 00 0 0 0 0 0In2W-XFMR 0

42

Page 57: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

9KVA XFMR 2K SEC BUS 02,528 0 0 2,544 2,575 02,559

2K FEED 00 0 0 0 0 0InCABLE 0

9KVA XFMR 2K 2,5752,528 0 0 2,544 0 0In2W-XFMR 2,559 2,559

PNL 2K 02,331 0 0 2,337 2,321 02,316

2K FEED 2,3212,331 0 0 2,337 0 0InCABLE 2,316 2,316

2K1 FEED 00 0 0 0 0 0InCABLE 0

PNL 2K1 02,153 0 0 2,155 2,105 02,103

2K1 FEED 2,1052,153 0 0 2,155 0 0InCABLE 2,103 2,103

TOWER41 BUS 01,819 0 0 1,819 1,475 01,475

TOWER41 FEED 1,4401,758 0 0 1,758 0 0InCABLE 1,440 1,475

TOWER41 115213 0 0 213 0 0InIND-MTR 115

TOWER41 FUSE BUS 02,023 0 0 2,023 1,640 01,640

TOWER41 FEED 115212 0 0 212 0 0InCABLE 115

TOWER41 FUSE FEED 1,6031,959 0 0 1,959 0 0InCABLE 1,603 1,640

TOWER42 BUS 01,619 0 0 1,619 1,313 01,313

43

Page 58: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

TOWER42 FEED 1,2781,558 0 0 1,558 0 0InCABLE 1,277 1,313

TOWER42 115213 0 0 213 0 0InIND-MTR 115

TOWER42 FUSE BUS 01,777 0 0 1,777 1,441 01,441

TOWER42 FEED 115212 0 0 212 0 0InCABLE 115

TOWER42 FUSE FEED 1,4041,714 0 0 1,714 0 0InCABLE 1,404 1,441

45KVA XFMR 2L-1 PRI BUS 013,528 0 0 13,535 10,353 010,350

XFMR 2L-1 FEED 10,35313,528 0 0 13,535 0 0InCABLE 10,350 10,350

45KVA XFMR 2L-1 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR 2L-1 SEC BUS 03,803 0 0 3,825 3,916 03,893

2L-1 FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2L-1 3,9163,803 0 0 3,825 0 0In2W-XFMR 3,893 3,893

PNL 2L-1 03,598 0 0 3,613 3,636 03,622

2L-1 FEED 3,6363,598 0 0 3,613 0 0InCABLE 3,622 3,622

2L-2 FEED 00 0 0 0 0 0InCABLE 0

PNL 2L-2 03,472 0 0 3,483 3,470 03,459

2L-2 FEED 3,4703,472 0 0 3,483 0 0InCABLE 3,459 3,459

44

Page 59: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2L-3 FEED 00 0 0 0 0 0InCABLE 0

PNL 2L-3 03,100 0 0 3,105 3,005 03,001

2L-3 FEED 3,0053,100 0 0 3,105 0 0InCABLE 3,001 3,001

45KVA XFMR 2K-232 PRI BUS 014,503 0 0 14,517 11,066 011,061

XFMR 2K-232 FEED 11,06614,503 0 0 14,517 0 0InCABLE 11,061 11,061

45KVA XFMR 2K-232 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR 2K-232 SEC

BUS

03,627 0 0 3,649 3,726 03,704

2K-232 CB FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2K-232 3,7263,627 0 0 3,649 0 0In2W-XFMR 3,704 3,704

PNL 2K-232 SEC1 02,953 0 0 2,958 2,856 02,852

2K-232 FEED 2,8562,953 0 0 2,958 0 0InCABLE 2,852 2,852

2K-232 SEC2 FEED 00 0 0 0 0 0InCABLE 0

PNL 2K-232 SEC2 02,836 0 0 2,839 2,716 02,713

2K-232 SEC2 FEED 2,7162,836 0 0 2,839 0 0InCABLE 2,713 2,713

2K-232 SEC3 FEED 00 0 0 0 0 0InCABLE 0

2K-232 CB1 BUS 03,481 0 0 3,497 3,526 03,510

45

Page 60: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2K-232 CB FEED 3,5263,481 0 0 3,497 0 0InCABLE 3,510 3,510

2K-232 FEED 00 0 0 0 0 0InCABLE 0

PNL 2K-232 SEC3 02,726 0 0 2,729 2,589 02,587

2K-232 SEC3 FEED 2,5892,726 0 0 2,729 0 0InCABLE 2,587 2,587

2G1 JUNC 022,304 0 0 22,493 16,680 016,657

2G1 JUNC FEED 16,68022,304 0 0 22,493 0 0InCABLE 16,657 16,657

2H FUSE FEED 00 0 0 0 0 0InCABLE 0

2H FUSE BUS 020,688 0 0 20,782 15,026 015,017

2H FUSE FEED 15,02620,688 0 0 20,782 0 0InCABLE 15,017 15,017

2H JUNC FEED 00 0 0 0 0 0InCABLE 0

2H JUNC 017,220 0 0 17,237 11,820 011,819

2H JUNC FEED 11,82017,220 0 0 17,237 0 0InCABLE 11,819 11,819

2H-1 FUSE FEED 00 0 0 0 0 0InCABLE 0

2H-2 FUSE1 FEED 00 0 0 0 0 0InCABLE 0

25KVA XFMR 2H-1 PRI BUS 08,987 0 0 8,987 6,603 06,603

2H-1 XFMR FEED 6,6038,987 0 0 8,987 0 0InCABLE 6,603 6,603

46

Page 61: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

25KVA XFMR 2H-1 00 0 0 0 0 0In2W-XFMR 0

25KVA XFMR 2H-1 SEC BUS 04,757 0 0 4,772 4,974 04,954

2H-1 FEED 00 0 0 0 0 0InCABLE 0

25KVA XFMR 2H-1 4,9744,757 0 0 4,772 0 0In2W-XFMR 4,954 4,954

2H-1 FUSE BUS 012,549 0 0 12,550 8,891 08,891

2H-1 FUSE FEED 8,89112,549 0 0 12,550 0 0InCABLE 8,891 8,891

2H-1 XFMR FEED 00 0 0 0 0 0InCABLE 0

PNL 2H-1 03,843 0 0 3,845 3,791 03,789

2H-1 FEED 3,7913,843 0 0 3,845 0 0InCABLE 3,789 3,789

25KVA XFMR 2H-2 PRI BUS 08,987 0 0 8,987 6,603 06,603

2H-2 XFMR FEED 6,6038,987 0 0 8,987 0 0InCABLE 6,603 6,603

25KVA XFMR 2H-2 00 0 0 0 0 0In2W-XFMR 0

25KVA XFMR 2H-2 SEC BUS 04,757 0 0 4,772 4,974 04,954

2H-2 FUSE2 FEED 00 0 0 0 0 0InCABLE 0

25KVA XFMR 2H-2 4,9744,757 0 0 4,772 0 0In2W-XFMR 4,954 4,954

2H-2 FUSE BUS 012,549 0 0 12,550 8,891 08,891

47

Page 62: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2H-2 FUSE1 FEED 8,89112,549 0 0 12,550 0 0InCABLE 8,891 8,891

2H-2 XFMR FEED 00 0 0 0 0 0InCABLE 0

2H-2 FUSE2 BUS 03,843 0 0 3,845 3,791 03,789

2H-2 FEED 00 0 0 0 0 0InCABLE 0

2H-2 FUSE2 FEED 3,7913,843 0 0 3,845 0 0InCABLE 3,789 3,789

PNL 2H-2 03,489 0 0 3,490 3,373 03,372

2H FEED 00 0 0 0 0 0InCABLE 0

2H-2 FEED 3,3733,489 0 0 3,490 0 0InCABLE 3,372 3,372

2H-3 FEED 00 0 0 0 0 0InCABLE 0

PNL 2H 02,205 0 0 2,205 1,992 01,992

2H FEED 1,9922,205 0 0 2,205 0 0InCABLE 1,992 1,992

PNL 2H-3 03,363 0 0 3,364 3,228 03,227

2H-3 FEED 3,2283,363 0 0 3,364 0 0InCABLE 3,227 3,227

EB2 BUS 032,994 0 0 42,564 38,086 029,949

EB2 FEED 35,45929,581 0 0 38,161 0 0InCABLE 27,883 29,949

EB2 2,6353,424 0 0 4,417 0 0InIND-MTR 2,072

48

Page 63: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

FIRE PUMP BUS 01,723 0 0 1,741 1,297 01,296

FIRE PUMP FEED1 1,1181,373 0 0 1,387 0 0InCABLE 1,117 1,296

FIRE PUMP 214426 0 0 430 0 0InIND-MTR 213

FIRE PUMP CB1 BUS 01,743 0 0 1,762 1,321 01,319

FIRE PUMP FEED1 215425 0 0 430 0 0InCABLE 214

FIRE PUMP FEED2 1,1401,391 0 0 1,405 0 0InCABLE 1,138 1,319

FIRE PUMP CB2 BUS 01,909 0 0 1,938 1,531 01,526

FIRE PUMP FEED2 225420 0 0 427 0 0InCABLE 224

FIRE PUMP FEED3 1,3311,540 0 0 1,564 0 0InCABLE 1,328 1,526

FIRE PUMP CB3 BUS 02,335 0 0 2,467 2,283 02,179

FIRE PUMP FEED3 266409 0 0 432 0 0InCABLE 254

FIRE PUMP FEED4 2,0231,938 0 0 2,047 0 0InCABLE 1,931 2,179

FIRE PUMP XFMR SEC BUS 02,346 0 0 2,483 2,311 02,197

FIRE PUMP FEED4 268408 0 0 432 0 0InCABLE 255

FIRE PUMP XFMR 2,0491,948 0 0 2,062 0 0In2W-XFMR 1,948 2,197

FIRE PUMP UTIL BUS 010,000,013 0 0 13,827,075 13,827,070 010,000,008

49

Page 64: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

FIRE PUMP XFMR 1213 0 0 18 0 0In2W-XFMR 9

FIRE PUMP UTIL 13,827,05810,000,000 0 0 13,827,058 0 0InUTILITY 9,999,999 10,000,013

UPS CB1 BUS 027,126 0 0 29,717 26,843 024,668

MBP-B FEED1 26,84327,126 0 0 29,717 0 0InCABLE 24,668 24,668

MBP-B FEED2 00 0 0 0 0 0InCABLE 0

UPS B BUS1 026,793 0 0 29,190 26,289 024,281

MBP-B FEED2 26,28926,793 0 0 29,190 0 0InCABLE 24,281 24,281

MBP-B FEED3 00 0 0 0 0 0InCABLE 0

UPS-B 00 0 0 0 0 0In 0

UPS B BUS2 01,202 0 0 1,659 0 00

MBP-B FEED3 00 0 0 0 0 0InCABLE 0

MBP-B FEED4 0600 0 0 829 0 0InCABLE 0

UPS-B 0601 521 521 922 799 799In 0

UPS B CB3 BUS 01,202 0 0 1,659 0 00

MBP-B FEED4 0601 0 0 830 0 0InCABLE 0

SSD-B FEED 0601 0 0 829 0 0InCABLE 0

50

Page 65: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL SSD-B 01,202 0 0 1,659 0 00

SSD-B FEED 0601 0 0 830 0 0InCABLE 0

STS-A FEED1 0300 0 0 415 0 0InCABLE 0

STS-B FEED1 0300 0 0 415 0 0InCABLE 0

UPS A CB1 BUS 036,429 0 0 38,828 31,631 029,300

MBP-A FEED1 31,63136,429 0 0 38,828 0 0InCABLE 29,300 29,300

MBP-A FEED2 00 0 0 0 0 0InCABLE 0

UPS A BUS1 035,806 0 0 37,970 30,872 028,751

MBP-A FEED2 30,87235,806 0 0 37,970 0 0InCABLE 28,751 28,751

MBP-A FEED3 00 0 0 0 0 0InCABLE 0

UPS-A 00 0 0 0 0 0In 0

UPS A BUS2 01,202 0 0 1,659 0 00

MBP-A FEED3 00 0 0 0 0 0InCABLE 0

MBP-A FEED4 0600 0 0 829 0 0InCABLE 0

UPS-A 0601 521 521 922 799 799In 0

UPS A CB3 BUS 01,202 0 0 1,659 0 00

51

Page 66: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

MBP-A FEED4 0601 0 0 830 0 0InCABLE 0

SSD-A FEED 0601 0 0 829 0 0InCABLE 0

PNL SSD-A 01,202 0 0 1,659 0 00

SSD-A FEED 0601 0 0 830 0 0InCABLE 0

STS-A FEED2 0300 0 0 415 0 0InCABLE 0

STS-B FEED2 0300 0 0 415 0 0InCABLE 0

STS-B 01,202 0 0 1,658 0 00

STS-B FEED1 0601 0 0 829 0 0InCABLE 0

STS-B FEED2 0601 0 0 829 0 0InCABLE 0

U4B FEED 00 0 0 0 0 0InCABLE 0

PNL U4B 01,200 0 0 1,653 0 00

PDU1 FEED 00 0 0 0 0 0InCABLE 0

PDU3 FEED 00 0 0 0 0 0InCABLE 0

U4B FEED 01,200 0 0 1,653 0 0InCABLE 0

PDU1 01,187 0 0 1,563 0 00

PDU1 FEED 01,187 0 0 1,563 0 0InCABLE 0

52

Page 67: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PDU3 01,176 0 0 1,502 0 00

PDU3 FEED 01,176 0 0 1,502 0 0InCABLE 0

STS-A 01,202 0 0 1,658 0 00

STS-A FEED1 0601 0 0 829 0 0InCABLE 0

STS-A FEED2 0601 0 0 829 0 0InCABLE 0

U4A FEED 00 0 0 0 0 0InCABLE 0

PNL U4A 01,200 0 0 1,653 0 00

PDU2 FEED 00 0 0 0 0 0InCABLE 0

PDU4 FEED 00 0 0 0 0 0InCABLE 0

U4A FEED 01,200 0 0 1,653 0 0InCABLE 0

PDU2 01,187 0 0 1,563 0 00

PDU2 FEED 01,187 0 0 1,563 0 0InCABLE 0

PDU4 01,181 0 0 1,527 0 00

PDU4 FEED 01,181 0 0 1,527 0 0InCABLE 0

PNL KL 010,084 0 0 10,882 11,134 010,255

53

Page 68: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

KL FUSE FEED 11,13410,084 0 0 10,882 0 0InCABLE 10,255 10,255

112.5KVA XFMR KL SEC BUS 010,895 0 0 12,009 12,786 011,490

KL FUSE FEED 00 0 0 0 0 0InCABLE 0

112.5KVA XFMR KL 12,78610,895 0 0 12,009 0 0In2W-XFMR 11,490 11,490

15KVA XFMR 2J PRI BUS 021,409 0 0 21,420 17,374 017,357

XFMR 2J FEED 17,37421,409 0 0 21,420 0 0InCABLE 17,357 17,357

15KVA XFMR 2J 00 0 0 0 0 0In2W-XFMR 0

ATS-1 NORMAL BUS 035,882 0 0 41,516 33,369 028,144

ATS-1 FEED 33,31635,797 0 0 41,417 0 0InCABLE 28,099 28,144

ATS-1 33,31635,797 0 0 41,417 0 0In 28,099

ATS-1 BUS 035,882 0 0 41,516 33,369 028,144

EMDP-P FEED 5486 0 0 100 0 0InCABLE 45

ATS-1 EM BUS 02,116 0 0 3,021 2,862 02,025

ATS-1 EM FEED 2,8622,116 0 0 3,021 0 0InCABLE 2,025 2,025

ATS-1 5486 0 0 100 0 0In 45

XFMR 2B1 SEC BUS 06,186 0 0 6,390 6,648 06,419

54

Page 69: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2B1 FEED 00 0 0 0 0 0InCABLE 0

75KVA XFMR 2B1 6,6486,186 0 0 6,390 0 0In2W-XFMR 6,419 6,419

XFMR 2B1 PRI BUS 013,737 0 0 13,777 9,783 09,776

XFMR 2B1 FEED 9,78313,737 0 0 13,777 0 0InCABLE 9,776 9,776

75KVA XFMR 2B1 00 0 0 0 0 0In2W-XFMR 0

USDP-B 019,318 0 0 26,711 26,711 019,318

PNL EDP-D CB1 FEED 00 0 0 0 0 0InCABLE 0

PNL U XFMR FEED 00 0 0 0 0 0InCABLE 0

XFMR 2UPSN-1 FEED 00 0 0 0 0 0InCABLE 0

XFMR 2UPSS-1 FEED 00 0 0 0 0 0InCABLE 0

UPSDP-B UTIL 26,71119,318 0 0 26,711 0 0InUTILITY 19,318 19,318

45KVA XFMR U PRI BUS 07,858 0 0 7,858 6,770 06,770

PNL U XFMR FEED 6,7707,858 0 0 7,858 0 0InCABLE 6,770 6,770

45KVA XFMR U 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR U SEC BUS 03,364 0 0 3,378 3,496 03,479

PNL U FEED 00 0 0 0 0 0InCABLE 0

55

Page 70: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

45KVA XFMR U 3,4963,364 0 0 3,378 0 0In2W-XFMR 3,479 3,479

PNL U 03,224 0 0 3,234 3,304 03,292

PNL 2U-1 FEED 00 0 0 0 0 0InCABLE 0

PNL U FEED 3,3043,224 0 0 3,234 0 0InCABLE 3,292 3,292

PNL 2U-1 02,353 0 0 2,354 2,226 02,224

PNL 2U-1 FEED 2,2262,353 0 0 2,354 0 0InCABLE 2,224 2,224

75KVA EDP-D XFMR PRI BUS 03,126 0 0 3,126 2,621 02,621

PNL EDP-D XFMR FEED1 2,6213,126 0 0 3,126 0 0InCABLE 2,621 2,621

75KVA EDP-D XFMR 00 0 0 0 0 0In2W-XFMR 0

75KVA EDP-D XFMR SEC

BUS

04,709 0 0 4,722 5,284 05,250

PNL EDP-D XFMR FEED2 00 0 0 0 0 0InCABLE 0

75KVA EDP-D XFMR 5,2844,709 0 0 4,722 0 0In2W-XFMR 5,250 5,250

PNL EDP-D 03,906 0 0 3,916 4,031 04,008

PNL 1 FEED 00 0 0 0 0 0InCABLE 0

PNL 2 FEED 00 0 0 0 0 0InCABLE 0

PNL 3 FEED 00 0 0 0 0 0InCABLE 0

56

Page 71: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL 4 FEED 00 0 0 0 0 0InCABLE 0

PNL 5 FEED 00 0 0 0 0 0InCABLE 0

PNL 6 FEED 00 0 0 0 0 0InCABLE 0

PNL 7 FEED 00 0 0 0 0 0InCABLE 0

PNL EDP-D FEED 4,0313,906 0 0 3,916 0 0InCABLE 4,008 4,008

PNL EDP-D CB1 BUS 03,418 0 0 3,418 2,869 02,869

PNL EDP-D CB1 FEED 2,8693,418 0 0 3,418 0 0InCABLE 2,869 2,869

PNL EDP-D XFMR FEED1 00 0 0 0 0 0InCABLE 0

PNL EDP-D CB2 BUS 04,446 0 0 4,456 4,860 04,834

PNL EDP-D FEED 00 0 0 0 0 0InCABLE 0

PNL EDP-D XFMR FEED2 4,8604,446 0 0 4,456 0 0InCABLE 4,834 4,834

PNL 7 03,543 0 0 3,549 3,540 03,524

PNL 7 FEED 3,5403,543 0 0 3,549 0 0InCABLE 3,524 3,524

PNL 6 03,723 0 0 3,731 3,779 03,760

PNL 6 FEED 3,7793,723 0 0 3,731 0 0InCABLE 3,760 3,760

PNL 5 03,753 0 0 3,761 3,819 03,799

57

Page 72: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL 5 FEED 3,8193,753 0 0 3,761 0 0InCABLE 3,799 3,799

PNL 4 03,032 0 0 3,036 2,901 02,893

PNL 4 FEED 2,9013,032 0 0 3,036 0 0InCABLE 2,893 2,893

PNL 3 03,032 0 0 3,036 2,901 02,893

PNL 3 FEED 2,9013,032 0 0 3,036 0 0InCABLE 2,893 2,893

PNL 2 02,135 0 0 2,136 1,904 01,901

PNL 2 FEED 1,9042,135 0 0 2,136 0 0InCABLE 1,901 1,901

PNL 1 02,135 0 0 2,136 1,904 01,901

PNL 1 FEED 1,9042,135 0 0 2,136 0 0InCABLE 1,901 1,901

75KVA XFMR 2UPSS-1 PRI

BUS

05,731 0 0 5,731 4,781 04,781

XFMR 2UPSS-1 FEED 4,7815,731 0 0 5,731 0 0InCABLE 4,781 4,781

75KVA XFMR 2UPSS-1 00 0 0 0 0 0In2W-XFMR 0

75KVA XFMR 2UPSS-1 SEC

BUS

05,826 0 0 5,906 6,431 06,310

2UPSS-1 FEED 00 0 0 0 0 0InCABLE 0

75KVA XFMR 2UPSS-1 6,4315,826 0 0 5,906 0 0In2W-XFMR 6,310 6,310

58

Page 73: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL 2UPSS-1 05,555 0 0 5,618 5,987 05,896

2UPSS-1 FEED 5,9875,555 0 0 5,618 0 0InCABLE 5,896 5,896

2UPSS-2 FEED 00 0 0 0 0 0InCABLE 0

PNL 2UPSS-2 05,428 0 0 5,484 5,788 05,707

2UPSS-2 FEED 5,7885,428 0 0 5,484 0 0InCABLE 5,707 5,707

2UPSS-3 FEED 00 0 0 0 0 0InCABLE 0

PNL 2UPSS-3 05,306 0 0 5,356 5,601 05,530

2UPSS-3 FEED 5,6015,306 0 0 5,356 0 0InCABLE 5,530 5,530

2UPSS-4 FEED 00 0 0 0 0 0InCABLE 0

PNL 2UPSS-4 05,189 0 0 5,234 5,426 05,363

2UPSS-4 FEED 5,4265,189 0 0 5,234 0 0InCABLE 5,363 5,363

45KVA XFMR 2UPSN-1 PRI

BUS

04,426 0 0 4,426 3,641 03,641

XFMR 2UPSN-1 FEED 3,6414,426 0 0 4,426 0 0InCABLE 3,641 3,641

45KVA XFMR 2UPSN-1 00 0 0 0 0 0In2W-XFMR 0

75KVA XFMR 2UPSN-1 SEC

BUS

04,277 0 0 4,287 4,650 04,634

59

Page 74: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2UPSN-1 FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2UPSN-1 4,6504,277 0 0 4,287 0 0In2W-XFMR 4,634 4,634

PNL 2UPSN-1 03,993 0 0 4,000 4,235 04,227

2UPSN-1 FEED 4,2353,993 0 0 4,000 0 0InCABLE 4,227 4,227

2UPSN-2 FEED 00 0 0 0 0 0InCABLE 0

PNL 2UPSN-2 03,889 0 0 3,894 4,087 04,081

2UPSN-2 FEED 4,0873,889 0 0 3,894 0 0InCABLE 4,081 4,081

60

Page 75: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

DAPPER Fault Contribution Complete Report

Comprehensive Short Circuit Study Settings

Three Phase Fault

Single Line to Ground

Line to Line Fault

Line to Line to Ground

All BusesFaulted Bus

Yes

Yes

Yes

No

No

Motor Contribution

Transformer Tap

Xformer Phase Shift

Yes

Yes

Bus Voltages

Branch Currents

Phase or Sequence

Fault Current Calculation

Asym Fault Current at Time 0.50

First Bus From Fault

First Branch From Fault

Report phase quantities

Asymmetrical RMS (with DC offset and Decay)

Cycles

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

USB-1 033,520 0 0 44,536 43,582 032,802

P4Y FEED 1,7932,069 0 0 2,749 0 0InCABLE 1,350

TIE FEED 00 0 0 0 0 0InCABLE 0

USB-1 FEED 00 0 0 0 0 0InCABLE 0

1500KVA XFMR1 41,78931,451 0 0 41,787 0 0In2W-XFMR 31,452 32,802

SWGW 1 UTIL BUS 010,000,074 0 0 13,827,160 13,827,126 010,000,049

1500KVA XFMR1 6975 0 0 103 0 0In2W-XFMR 50

1

Project: 4TH AVENUE BUILDING EMERGENCY POWER SHORT CIRCUIT

Page 76: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

SWGR #1 13,827,05710,000,000 0 0 13,827,056 0 0InUTILITY 9,999,999 10,000,054

P4Y 031,784 0 0 40,740 38,510 030,153

150KVA XFMR FEED 00 0 0 0 0 0InCABLE 0

4D2 FEED 621768 0 0 985 0 0InCABLE 486

ASU9A FEED 3442 0 0 54 0 0InCABLE 27

P4Y FEED 36,83329,708 0 0 38,079 0 0InCABLE 28,841 30,153

WWP2 FEED 342424 0 0 543 0 0InCABLE 268

WWP3 FEED 341422 0 0 541 0 0InCABLE 267

WWP4 FEED 340421 0 0 540 0 0InCABLE 267

ASU9 BUS 02,643 0 0 2,643 2,207 02,207

ASU9A FEED 2,2022,633 0 0 2,633 0 0InCABLE 2,202 2,207

ASU9A-1 FEED 1221 0 0 21 0 0InCABLE 12

ASU9A-2 FEED 1221 0 0 21 0 0InCABLE 12

150 KVA XFMR SEC BUS 012,301 0 0 13,842 14,535 012,862

L1 DISC FEED 00 0 0 0 0 0InCABLE 0

L1A DISC FEED 00 0 0 0 0 0InCABLE 0

2

Page 77: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

150KVA XFMR 14,53512,301 0 0 13,842 0 0In2W-XFMR 12,862 12,862

PNL L1A 05,878 0 0 5,897 5,095 05,076

L1A FEED 5,0955,878 0 0 5,897 0 0InCABLE 5,076 5,076

PNL L1 06,046 0 0 6,069 5,263 05,241

L1 FEED 5,2636,046 0 0 6,069 0 0InCABLE 5,241 5,241

PNL 4D2 014,132 0 0 14,166 11,526 011,497

4D2 FEED 11,17713,492 0 0 13,524 0 0InCABLE 11,149 11,497

CHWP1A FEED 225415 0 0 416 0 0InCABLE 225

CHWP1B FEED 3871 0 0 71 0 0InCABLE 38

CWP1A FEED 2953 0 0 53 0 0InCABLE 29

CWP1B FEED 3871 0 0 71 0 0InCABLE 38

DHRC-1 FEED 96177 0 0 178 0 0InCABLE 96

USB-2 049,212 0 0 67,495 57,951 041,410

4G FEED 00 0 0 0 0 0InCABLE 0

4J1 FEED 00 0 0 0 0 0InCABLE 0

ATS-1 FEED 00 0 0 0 0 0InCABLE 0

3

Page 78: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

EDP15 XFMR FEED 00 0 0 0 0 0InCABLE 0

MCC10 FEED 440561 0 0 769 0 0InCABLE 315

P4X FEED 306390 0 0 534 0 0InCABLE 219

P4Z FEED 5,4386,927 0 0 9,501 0 0InCABLE 3,886

TIE FEED 00 0 0 0 0 0InCABLE 0

USB-2 FEED 00 0 0 0 0 0InCABLE 0

WCU-4 SW FEED 3,9094,979 0 0 6,829 0 0InCABLE 2,793

WCU-5 SW FEED 3,9094,979 0 0 6,829 0 0InCABLE 2,793

1500KVA XFMR2 43,98531,429 0 0 43,105 0 0In2W-XFMR 31,430 41,410

PNL USB-1 030,134 0 0 35,283 32,850 028,314

MBP-B FEED1 00 0 0 0 0 0InCABLE 0

USB-1 FEED 32,85030,134 0 0 35,283 0 0InCABLE 28,314 28,314

PNL 4G 010,654 0 0 10,663 8,261 08,240

45KVA XFMR FEED 00 0 0 0 0 0InCABLE 0

4G FEED 8,26110,654 0 0 10,663 0 0InCABLE 8,240 8,240

ASU9A-1 BUS 02,245 0 0 2,245 1,874 01,874

4

Page 79: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

ASU9A-1 FEED 1,8712,240 0 0 2,240 0 0InCABLE 1,871 1,874

ASU9A-1 1221 0 0 21 0 0InIND-MTR 12

ASU9A-2 BUS 01,951 0 0 1,951 1,628 01,628

ASU9A-2 FEED 1,6261,946 0 0 1,946 0 0InCABLE 1,626 1,628

ASU9A-2 1221 0 0 21 0 0InIND-MTR 12

150 KVA XFMR PRI BUS 023,314 0 0 24,521 21,313 020,290

150KVA XFMR FEED 21,31323,314 0 0 24,521 0 0InCABLE 20,290 20,290

150KVA XFMR 00 0 0 0 0 0In2W-XFMR 0

L1A FUSE BUS 010,327 0 0 10,795 10,501 010,079

L1A DISC FEED 10,50110,327 0 0 10,795 0 0InCABLE 10,079 10,079

L1A FEED 00 0 0 0 0 0InCABLE 0

L1 FUSE BUS 010,778 0 0 11,396 11,253 010,678

L1 DISC FEED 11,25310,778 0 0 11,396 0 0InCABLE 10,678 10,678

L1 FEED 00 0 0 0 0 0InCABLE 0

WWP4 BUS 011,546 0 0 11,547 9,587 09,586

WWP4 FEED 9,43811,279 0 0 11,280 0 0InCABLE 9,437 9,586

5

Page 80: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

WWP4 236426 0 0 426 0 0InIND-MTR 236

WWP3 BUS 013,077 0 0 13,079 10,923 010,921

WWP3 FEED 10,76512,795 0 0 12,798 0 0InCABLE 10,764 10,921

WWP3 237426 0 0 426 0 0InIND-MTR 237

WWP2 BUS 019,705 0 0 19,778 17,042 016,995

WWP2 FEED 16,84419,362 0 0 19,434 0 0InCABLE 16,797 16,995

WWP2 245426 0 0 427 0 0InIND-MTR 245

45KVA XFMR PRI BUS 09,816 0 0 9,820 7,665 07,654

45KVA XFMR FEED 7,6659,816 0 0 9,820 0 0InCABLE 7,654 7,654

45KVA XFMR 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR SEC BUS 04,769 0 0 4,793 4,993 04,966

2G FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 4,9934,769 0 0 4,793 0 0In2W-XFMR 4,966 4,966

CHWP1B BUS 02,841 0 0 2,841 2,349 02,349

CHWP1B FEED 2,3372,819 0 0 2,819 0 0InCABLE 2,337 2,349

CHWP1B 3971 0 0 71 0 0InIND-MTR 39

6

Page 81: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

CHWP1A BUS 03,138 0 0 3,138 2,552 02,552

CHWP1A FEED 2,4622,981 0 0 2,981 0 0InCABLE 2,462 2,552

CHWP1A 231426 0 0 426 0 0InIND-MTR 231

CWP1B BUS 03,092 0 0 3,092 2,560 02,560

CWP1B FEED 2,5483,071 0 0 3,071 0 0InCABLE 2,548 2,560

CWP1B 3971 0 0 71 0 0InIND-MTR 39

CWP1A BUS 03,088 0 0 3,088 2,558 02,558

CWP1A FEED 2,5493,072 0 0 3,072 0 0InCABLE 2,549 2,558

CWP1A 2953 0 0 53 0 0InIND-MTR 29

DHRC-1 BUS 012,599 0 0 12,614 10,218 010,204

DHRC-1 FEED 10,14612,466 0 0 12,481 0 0InCABLE 10,132 10,204

DHRC-1 96177 0 0 178 0 0InIND-MTR 96

PNL 2G 04,586 0 0 4,604 4,735 04,715

2G FEED 4,7354,586 0 0 4,604 0 0InCABLE 4,715 4,715

PNL 4J1 033,714 0 0 37,153 29,887 026,588

7

Page 82: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

4J1 FEED 29,88733,714 0 0 37,153 0 0InCABLE 26,588 26,589

4J2 FEED 00 0 0 0 0 0InCABLE 0

15KVA XFMR 2J SEC BUS 02,341 0 0 2,356 2,377 02,362

2J FEED 00 0 0 0 0 0InCABLE 0

15KVA XFMR 2J 2,3772,341 0 0 2,356 0 0In2W-XFMR 2,362 2,362

PNL 2J 02,091 0 0 2,095 2,061 02,058

2J FEED 2,0612,091 0 0 2,095 0 0InCABLE 2,058 2,058

PNL 4J2 033,116 0 0 36,322 29,156 026,062

4J2 FEED 29,15633,116 0 0 36,322 0 0InCABLE 26,062 26,062

XFMR 2J FEED 00 0 0 0 0 0InCABLE 0

PNL USB-2 042,223 0 0 48,364 40,228 034,589

MBP-A FEED1 00 0 0 0 0 0InCABLE 0

USB-2 FEED 40,22842,223 0 0 48,364 0 0InCABLE 34,589 34,589

GEN 1 BUS 02,392 0 0 3,737 3,697 02,363

ATS-1 EM FEED 8986 0 0 134 0 0InCABLE 57

GEN-1 3,6082,307 0 0 3,603 0 0InGEN 2,307 2,363

8

Page 83: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

EMDP-P 02,171 0 0 3,056 2,829 02,032

14E FEED 00 0 0 0 0 0InCABLE 0

4E FEED 00 0 0 0 0 0InCABLE 0

EMCC-T6 FEED 00 0 0 0 0 0InCABLE 0

EMDP-P FEED 2,7542,084 0 0 2,934 0 0InCABLE 1,978 2,032

ROOF MOTOR FEED 7586 0 0 122 0 0InCABLE 54

ROOF J-BOX BUS 01,902 0 0 2,093 1,840 01,703

ROOF MOTOR 1 FEED 2843 0 0 48 0 0InCABLE 26

ROOF MOTOR 2 FEED 2843 0 0 48 0 0InCABLE 26

ROOF MOTOR FEED 1,7861,818 0 0 2,000 0 0InCABLE 1,652 1,703

ROOF TOP MOTOR 1 BUS 01,897 0 0 2,083 1,831 01,697

ROOF MOTOR 1 FEED 1,8041,855 0 0 2,037 0 0InCABLE 1,672 1,697

ROOF TOP MOTOR 1 2843 0 0 48 0 0InIND-MTR 26

ROOF TOP MOTOR 2 BUS 01,892 0 0 2,073 1,821 01,692

ROOF MOTOR 2 FEED 1,7941,850 0 0 2,027 0 0InCABLE 1,667 1,692

ROOF TOP MOTOR 2 2843 0 0 48 0 0InIND-MTR 26

9

Page 84: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL EMCC-T6 0937 0 0 937 797 0797

EMCC-T6 FEED 797937 0 0 937 0 0InCABLE 797 797

15KVA XFMR 2E PRI BUS 02,026 0 0 2,355 2,121 01,857

XFMR 2E FEED 2,1212,026 0 0 2,355 0 0InCABLE 1,857 1,857

15KVA XFMR 2E 00 0 0 0 0 0In2W-XFMR 0

15KVA XFMR 2E SEC BUS 01,882 0 0 1,912 2,056 02,031

2E FEED 00 0 0 0 0 0InCABLE 0

15KVA XFMR 2E 2,0561,882 0 0 1,912 0 0In2W-XFMR 2,031 2,031

PNL 4E 02,069 0 0 2,573 2,331 01,906

4E FEED 2,3312,069 0 0 2,573 0 0InCABLE 1,906 1,906

XFMR 2E FEED 00 0 0 0 0 0InCABLE 0

PNL 2E 01,800 0 0 1,817 1,923 01,910

2E FEED 1,9231,800 0 0 1,817 0 0InCABLE 1,910 1,910

15KVA XFMR 12E PRI BUS 02,147 0 0 2,912 2,678 02,002

XFMR 12E FEED 2,6782,147 0 0 2,912 0 0InCABLE 2,002 2,002

10

Page 85: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

45KVA XFMR 12E 00 0 0 0 0 0In2W-XFMR 0

15KVA XFMR 12E SEC BUS 03,437 0 0 3,577 4,036 03,928

12E FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 12E 4,0363,437 0 0 3,577 0 0In2W-XFMR 3,928 3,928

PNL 14E 02,153 0 0 2,953 2,720 02,010

14E FEED 2,7202,153 0 0 2,953 0 0InCABLE 2,010 2,010

XFMR 12E FEED 00 0 0 0 0 0InCABLE 0

XFMR P1 FEED 00 0 0 0 0 0InCABLE 0

PNL 12E 03,377 0 0 3,502 3,914 03,820

12E FEED 3,9143,377 0 0 3,502 0 0InCABLE 3,820 3,820

30KVA XFMR P1 PRI BUS 01,483 0 0 1,491 1,302 01,297

XFMR P1 FEED 1,3021,483 0 0 1,491 0 0InCABLE 1,297 1,297

30KVA XFMR P1 00 0 0 0 0 0In2W-XFMR 0

30KVA XFMR P1 SEC BUS 01,916 0 0 1,928 2,161 02,147

P1 FEED 00 0 0 0 0 0InCABLE 0

30KVA XFMR P1 2,1611,916 0 0 1,928 0 0In2W-XFMR 2,147 2,147

11

Page 86: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL P1 01,865 0 0 1,874 2,077 02,067

P1 FEED 2,0771,865 0 0 1,874 0 0InCABLE 2,067 2,067

MCC10 027,052 0 0 29,419 22,620 020,268

CHWP-4 FEED 59106 0 0 116 0 0InCABLE 53

CWP-4 FUSE FEED 158283 0 0 307 0 0InCABLE 141

MCC10 FEED 22,31526,504 0 0 28,823 0 0InCABLE 19,994 20,268

P18-3 FEED 99177 0 0 192 0 0InCABLE 88

P18-3 BUS 010,119 0 0 10,119 8,195 08,195

P18-3 FEED 8,14610,029 0 0 10,029 0 0InCABLE 8,146 8,195

P18-3 96177 0 0 177 0 0InIND-MTR 96

CHWP-4 BUS 015,992 0 0 15,996 12,675 012,665

CHWP-4 FEED 12,63615,919 0 0 15,924 0 0InCABLE 12,627 12,665

CHWP-4 56106 0 0 106 0 0InIND-MTR 56

CWP-4 FUSE BUS 016,056 0 0 16,061 12,698 012,688

CWP-4 FEED 149283 0 0 283 0 0InCABLE 149

CWP-4 FUSE FEED 12,59515,860 0 0 15,866 0 0InCABLE 12,585 12,688

12

Page 87: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

CWP-4 BUS 012,050 0 0 12,051 9,682 09,682

CWP-4 FEED 9,59311,885 0 0 11,886 0 0InCABLE 9,593 9,682

CWP-4 152284 0 0 284 0 0InIND-MTR 152

P4Z 044,562 0 0 55,699 44,988 035,694

4A FEED 00 0 0 0 0 0InCABLE 0

4C FEED 00 0 0 0 0 0InCABLE 0

4D FEED 00 0 0 0 0 0InCABLE 0

4DE FEED 237352 0 0 440 0 0InCABLE 188

4F FEED 00 0 0 0 0 0InCABLE 0

4GE FEED 438651 0 0 814 0 0InCABLE 348

4I FEED 3,4165,075 0 0 6,343 0 0InCABLE 2,710

4K FEED 1 00 0 0 0 0 0InCABLE 0

4L FEED 1 00 0 0 0 0 0InCABLE 0

4M FEED 1 189280 0 0 350 0 0InCABLE 150

ELEV#50 DISC FEED 237353 0 0 441 0 0InCABLE 188

MCC12 FEED 255379 0 0 474 0 0InCABLE 203

13

Page 88: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

P4Z FEED 40,22137,480 0 0 46,847 0 0InCABLE 31,912 35,694

XFMR P2Z FEED 00 0 0 0 0 0InCABLE 0

PNL 4A 028,833 0 0 29,416 23,073 022,432

4A FEED 23,07328,833 0 0 29,416 0 0InCABLE 22,432 22,432

XFMR 2A FEED 00 0 0 0 0 0InCABLE 0

75KVA XFMR 2A PRI BUS 026,488 0 0 26,786 20,989 020,634

XFMR 2A FEED 20,98926,488 0 0 26,786 0 0InCABLE 20,634 20,634

75KVA XFMR 2A 00 0 0 0 0 0In2W-XFMR 0

75KVA XFMR 2A SEC BUS 07,618 0 0 7,914 8,114 07,803

2A-1 FEED 00 0 0 0 0 0InCABLE 0

75KVA XFMR 2A 8,1147,618 0 0 7,914 0 0In2W-XFMR 7,803 7,803

PNL 2A-1 07,206 0 0 7,424 7,446 07,225

2A-1 FEED 7,4467,206 0 0 7,424 0 0InCABLE 7,225 7,225

2A-2 FEED 00 0 0 0 0 0InCABLE 0

PNL 2A-2 06,945 0 0 7,118 7,048 06,876

2A-2 FEED 7,0486,945 0 0 7,118 0 0InCABLE 6,876 6,876

14

Page 89: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2B FEED 00 0 0 0 0 0InCABLE 0

PNL 2B 01,472 0 0 1,472 1,254 01,254

2B FEED 1,2541,472 0 0 1,472 0 0InCABLE 1,254 1,254

30KVA XFMR 2F1 PRI BUS 02,027 0 0 2,027 1,684 01,684

XFMR 2F1 FEED 1,6842,027 0 0 2,027 0 0InCABLE 1,684 1,684

30KVA XFMR 2F1 00 0 0 0 0 0In2W-XFMR 0

30KVA XFMR 2F1 SEC BUS 02,270 0 0 2,272 2,468 02,464

2F1 FEED 00 0 0 0 0 0InCABLE 0

30KVA XFMR 2F1 2,4682,270 0 0 2,272 0 0In2W-XFMR 2,464 2,464

PNL 2F1 01,913 0 0 1,914 1,985 01,984

2F1 FEED 1,9851,913 0 0 1,914 0 0InCABLE 1,984 1,984

PNL 4F 09,518 0 0 9,518 7,618 07,617

4F FEED 7,6189,518 0 0 9,518 0 0InCABLE 7,617 7,617

XFMR 2F FEED 00 0 0 0 0 0InCABLE 0

XFMR 2F1 FEED 00 0 0 0 0 0InCABLE 0

30KVA XFMR 2F PRI BUS 07,892 0 0 7,892 6,383 06,383

15

Page 90: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

XFMR 2F FEED 6,3837,892 0 0 7,892 0 0InCABLE 6,383 6,383

30KVA XFMR 2F 00 0 0 0 0 0In2W-XFMR 0

30KVA XFMR 2F SEC BUS 03,993 0 0 4,007 4,171 04,153

2F FEED 00 0 0 0 0 0InCABLE 0

30KVA XFMR 2F 4,1713,993 0 0 4,007 0 0In2W-XFMR 4,153 4,153

PNL 2F 03,747 0 0 3,755 3,833 03,823

2F FEED 3,8333,747 0 0 3,755 0 0InCABLE 3,823 3,823

30KVA XFMR 2GE PRI BUS 07,619 0 0 7,619 6,079 06,079

XFMR 2GE FEED 6,0797,619 0 0 7,619 0 0InCABLE 6,079 6,079

30KVA XFMR 2GE 00 0 0 0 0 0In2W-XFMR 0

30KVA XFMR 2GE SEC BUS 04,255 0 0 4,270 4,464 04,446

2GE FEED 00 0 0 0 0 0InCABLE 0

30KVA XFMR 2GE 4,4644,255 0 0 4,270 0 0In2W-XFMR 4,446 4,446

PNL 2GE 03,307 0 0 3,307 3,258 03,257

2GE FEED 3,2583,307 0 0 3,307 0 0InCABLE 3,257 3,257

PNL 4GE 09,912 0 0 9,912 7,769 07,768

16

Page 91: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

4GE FEED 7,5509,498 0 0 9,498 0 0InCABLE 7,549 7,768

MCC2 FEED 350670 0 0 670 0 0InCABLE 350

XFMR 2GE FEED 00 0 0 0 0 0InCABLE 0

MCC2 09,759 0 0 9,760 7,638 07,637

ASU 14R FEED 2853 0 0 53 0 0InCABLE 28

ASU 14S FEED 147282 0 0 282 0 0InCABLE 147

ASU 15R FEED 2853 0 0 53 0 0InCABLE 28

ASU 15S FEED 147282 0 0 282 0 0InCABLE 147

MCC2 FEED 7,4189,343 0 0 9,344 0 0InCABLE 7,417 7,637

ASU 15S BUS 05,803 0 0 5,803 4,658 04,658

ASU 15S FEED 4,5855,668 0 0 5,668 0 0InCABLE 4,585 4,658

ASU 15S 152284 0 0 284 0 0InIND-MTR 152

ASU 15R BUS 01,686 0 0 1,686 1,393 01,393

ASU 15R FEED 1,3861,673 0 0 1,673 0 0InCABLE 1,386 1,393

ASU 15R 2953 0 0 53 0 0InIND-MTR 29

ASU 14R BUS 01,516 0 0 1,516 1,254 01,254

17

Page 92: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

ASU 14R FEED 1,2461,504 0 0 1,504 0 0InCABLE 1,246 1,254

ASU 14R 2953 0 0 53 0 0InIND-MTR 29

ASU 14S BUS 05,625 0 0 5,625 4,520 04,520

ASU 14S FEED 4,4475,491 0 0 5,491 0 0InCABLE 4,447 4,520

ASU 14S 152284 0 0 284 0 0InIND-MTR 152

75KVA XFMR P2Z PRI BUS 018,675 0 0 18,676 15,110 015,107

XFMR P2Z FEED 15,11018,675 0 0 18,676 0 0InCABLE 15,107 15,107

75KVA XFMR P2Z 00 0 0 0 0 0In2W-XFMR 0

75KVA XFMR P2Z SEC BUS 06,132 0 0 6,320 6,498 06,284

P2Z FEED 00 0 0 0 0 0InCABLE 0

75KVA XFMR P2Z 6,4986,132 0 0 6,320 0 0In2W-XFMR 6,284 6,284

PNL P2Z 05,822 0 0 5,925 5,993 05,888

P2Z FEED 5,9935,822 0 0 5,925 0 0InCABLE 5,888 5,888

SONNYS FEED 00 0 0 0 0 0InCABLE 0

SONNY'S 04,145 0 0 4,151 3,866 03,861

SONNYS FEED 3,8664,145 0 0 4,151 0 0InCABLE 3,861 3,861

18

Page 93: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

ELE#50 BUS 014,996 0 0 14,996 12,112 012,111

ELE#50 FEED 12,00114,791 0 0 14,792 0 0InCABLE 12,000 12,111

ELE #50 191355 0 0 355 0 0InIND-MTR 191

ELE#50 DISC BUS 020,123 0 0 20,126 16,189 016,183

ELE#50 FEED 190354 0 0 354 0 0InCABLE 190

ELEV#50 DISC FEED 16,06119,886 0 0 19,890 0 0InCABLE 16,056 16,183

MCC12 09,340 0 0 9,341 7,372 07,371

CHWP-5 FEED 56106 0 0 106 0 0InCABLE 56

CWP5 FUSE FEED 147280 0 0 280 0 0InCABLE 147

MCC12 FEED 7,2449,099 0 0 9,100 0 0InCABLE 7,243 7,371

CWP5 BUS 03,624 0 0 3,624 2,949 02,949

CWP5 FEED 2,8853,509 0 0 3,509 0 0InCABLE 2,885 2,949

CWP5 154284 0 0 284 0 0InIND-MTR 154

CHWP-5 BUS 03,230 0 0 3,230 2,649 02,649

CHWP-5 FEED 2,6293,195 0 0 3,195 0 0InCABLE 2,629 2,649

CHWP-5 58106 0 0 106 0 0InIND-MTR 58

19

Page 94: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

CWP5 FUSE BUS 03,937 0 0 3,937 3,201 03,201

CWP5 FEED 154283 0 0 283 0 0InCABLE 154

CWP5 FUSE FEED 3,1353,819 0 0 3,819 0 0InCABLE 3,135 3,201

PNL 4D 014,994 0 0 15,001 11,812 011,798

2D2 FEED 00 0 0 0 0 0InCABLE 0

4D FEED 11,81214,994 0 0 15,001 0 0InCABLE 11,798 11,798

XFMR 2D FEED 00 0 0 0 0 0InCABLE 0

PNL 2D2 010,726 0 0 10,726 8,624 08,623

2D2 FEED 8,62410,726 0 0 10,726 0 0InCABLE 8,623 8,623

45KVA XFMR 2D PRI BUS 013,366 0 0 13,368 10,617 010,612

XFMR 2D FEED 10,61713,366 0 0 13,368 0 0InCABLE 10,612 10,612

45KVA XFMR 2D 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR 2D SEC BUS 04,931 0 0 4,956 5,110 05,082

2D FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2D 5,1104,931 0 0 4,956 0 0In2W-XFMR 5,082 5,082

PNL 2D 04,766 0 0 4,785 4,882 04,862

20

Page 95: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2D FEED 4,8824,766 0 0 4,785 0 0InCABLE 4,862 4,862

2D1 FEED 00 0 0 0 0 0InCABLE 0

PNL 2D1 01,535 0 0 1,535 1,341 01,341

2D1 FEED 1,3411,535 0 0 1,535 0 0InCABLE 1,341 1,341

PNL 4DE 020,100 0 0 20,318 15,494 015,214

4DE FEED 15,33619,794 0 0 20,008 0 0InCABLE 15,059 15,214

DHRC2 FEED 91177 0 0 179 0 0InCABLE 89

DHRC3 FEED 91177 0 0 179 0 0InCABLE 89

DHRC2 BUS 017,294 0 0 17,365 13,293 013,185

DHRC2 FEED 13,21917,150 0 0 17,220 0 0InCABLE 13,112 13,185

DHRC2 91177 0 0 178 0 0InIND-MTR 90

DHRC3 BUS 017,294 0 0 17,365 13,293 013,185

DHRC3 FEED 13,21917,150 0 0 17,220 0 0InCABLE 13,112 13,185

DHRC3 91177 0 0 178 0 0InIND-MTR 90

4M CB 2 BUS 013,511 0 0 13,511 10,791 010,789

4M FEED 1 10,69513,333 0 0 13,333 0 0InCABLE 10,694 10,789

21

Page 96: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

4M FEED 2 150282 0 0 282 0 0InCABLE 150

PNL 4M 013,246 0 0 13,247 10,579 010,577

4M FEED 2 10,48413,069 0 0 13,070 0 0InCABLE 10,483 10,577

SF2A FUSE FEED 75141 0 0 141 0 0InCABLE 75

SF2B FUSE FEED 75141 0 0 141 0 0InCABLE 75

SF2B BUS 03,608 0 0 3,608 2,966 02,966

SF2B FEED 2,9403,562 0 0 3,562 0 0InCABLE 2,940 2,966

SF2B 78142 0 0 142 0 0InIND-MTR 78

SF2B FUSE FEED BUS 03,704 0 0 3,704 3,044 03,044

SF2B FEED 78142 0 0 142 0 0InCABLE 78

SF2B FUSE FEED 3,0193,658 0 0 3,658 0 0InCABLE 3,019 3,044

SF2A BUS 03,996 0 0 3,996 3,283 03,283

SF2A FEED 3,2573,949 0 0 3,949 0 0InCABLE 3,257 3,283

SF2A 78142 0 0 142 0 0InIND-MTR 78

SF2A FUSE FEED BUS 04,114 0 0 4,114 3,380 03,380

SF2A FEED 78142 0 0 142 0 0InCABLE 78

22

Page 97: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

SF2A FUSE FEED 3,3534,067 0 0 4,067 0 0InCABLE 3,353 3,380

4K CB 2 BUS 09,443 0 0 9,444 5,910 05,910

4K FEED 1 5,9109,443 0 0 9,444 0 0InCABLE 5,910 5,910

4K FEED 2 00 0 0 0 0 0InCABLE 0

PNL 4K 09,279 0 0 9,280 5,827 05,827

4K FEED 2 5,8279,279 0 0 9,280 0 0InCABLE 5,827 5,827

PNL 4I 028,057 0 0 31,228 19,906 018,693

4I FEED 17,27522,498 0 0 25,041 0 0InCABLE 16,222 18,693

CHILLER 1 FEED 2,4045,083 0 0 5,657 0 0InCABLE 2,258

MCC4 FEED 249527 0 0 587 0 0InCABLE 234

CHILLER 1 BUS 020,465 0 0 21,099 13,288 013,069

CHILLER 1 FEED 11,14715,578 0 0 16,060 0 0InCABLE 10,963 13,069

CHILLER 1 2,3715,477 0 0 5,646 0 0InIND-MTR 2,332

MCC4 025,550 0 0 27,315 17,832 017,053

ASU11 FEED 65141 0 0 150 0 0InCABLE 63

ASU12 FEED 65141 0 0 150 0 0InCABLE 63

23

Page 98: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

ASU13 FEED 66141 0 0 151 0 0InCABLE 63

CWP1 FEED 49106 0 0 113 0 0InCABLE 47

MCC4 FEED 17,59525,040 0 0 26,770 0 0InCABLE 16,826 17,053

ASU13 BUS 03,973 0 0 3,973 3,192 03,192

ASU13 FEED 3,1683,929 0 0 3,929 0 0InCABLE 3,168 3,192

ASU13 76142 0 0 142 0 0InIND-MTR 76

ASU11 BUS 02,845 0 0 2,845 2,306 02,306

ASU11 FEED 2,2842,806 0 0 2,806 0 0InCABLE 2,284 2,306

ASU11 77142 0 0 142 0 0InIND-MTR 77

ASU12 BUS 02,845 0 0 2,845 2,306 02,306

ASU12 FEED 2,2842,806 0 0 2,806 0 0InCABLE 2,284 2,306

ASU12 77142 0 0 142 0 0InIND-MTR 77

CWP1 BUS 02,649 0 0 2,649 2,153 02,153

CWP1 FEED2 2,1372,620 0 0 2,620 0 0InCABLE 2,137 2,153

CWP1 58106 0 0 106 0 0InIND-MTR 58

CWP1 FUSE 2 BUS 03,963 0 0 3,963 3,188 03,188

24

Page 99: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

CWP1 FEED 3,1703,929 0 0 3,929 0 0InCABLE 3,170 3,188

CWP1 FEED2 57106 0 0 106 0 0InCABLE 57

PNL 4L 018,941 0 0 19,000 14,764 014,670

4L FEED 2 14,76418,941 0 0 19,000 0 0InCABLE 14,670 14,670

4L CB 2 BUS 019,266 0 0 19,331 15,022 014,922

4L FEED 1 15,02219,266 0 0 19,331 0 0InCABLE 14,922 14,922

4L FEED 2 00 0 0 0 0 0InCABLE 0

PNL 4C 022,438 0 0 22,580 17,582 017,389

4C FEED 17,58222,438 0 0 22,580 0 0InCABLE 17,389 17,389

XFMR 2C FEED 00 0 0 0 0 0InCABLE 0

XFMR 2C2 FEED 00 0 0 0 0 0InCABLE 0

30KVA XFMR 2C2 PRI BUS 016,975 0 0 16,980 13,486 013,475

XFMR 2C2 FEED 13,48616,975 0 0 16,980 0 0InCABLE 13,475 13,475

30KVA XFMR 2C2 00 0 0 0 0 0In2W-XFMR 0

30KVA XFMR 2C2 SEC BUS 02,120 0 0 2,133 2,155 02,142

2C2 FEED 00 0 0 0 0 0InCABLE 0

25

Page 100: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

30KVA XFMR 2C2 2,1552,120 0 0 2,133 0 0In2W-XFMR 2,142 2,142

PNL 2C2 02,068 0 0 2,079 2,085 02,075

2C2 FEED 2,0852,068 0 0 2,079 0 0InCABLE 2,075 2,075

30KVA XFMR 2C PRI BUS 020,051 0 0 20,094 15,771 015,703

XFMR 2C FEED 15,77120,051 0 0 20,094 0 0InCABLE 15,703 15,703

45KVA XFMR 2C 00 0 0 0 0 0In2W-XFMR 0

30KVA XFMR 2C SEC BUS 05,072 0 0 5,103 5,213 05,181

2C FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2C 5,2135,072 0 0 5,103 0 0In2W-XFMR 5,181 5,181

PNL 2C 04,829 0 0 4,850 4,880 04,859

2C FEED 4,8804,829 0 0 4,850 0 0InCABLE 4,859 4,859

1000KVA XFMR EDP15 SEC

BUS

056,232 0 0 72,720 84,553 063,862

EDP15 FEED 00 0 0 0 0 0InCABLE 0

1000KVA XFMR EDP15 84,55356,232 0 0 72,720 0 0In2W-XFMR 63,862 63,862

PNL EDP15 050,001 0 0 59,616 63,195 052,951

26

Page 101: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

EDP-E FEED 00 0 0 0 0 0InCABLE 0

EDP15 FEED 63,19550,001 0 0 59,616 0 0InCABLE 52,951 52,951

1000KVA XFMR EDP15 PRI

BUS

038,853 0 0 44,063 36,151 031,316

EDP15 XFMR FEED 36,15138,853 0 0 44,063 0 0InCABLE 31,316 31,316

1000KVA XFMR EDP15 00 0 0 0 0 0In2W-XFMR 0

PNL EDP-E 026,209 0 0 27,084 23,228 022,354

2D3 FEED 00 0 0 0 0 0InCABLE 0

EDP-E FEED 23,22826,209 0 0 27,084 0 0InCABLE 22,354 22,354

PNL 2D3 04,056 0 0 4,056 3,199 03,198

2D3 FEED 3,1994,056 0 0 4,056 0 0InCABLE 3,198 3,198

WCU-4 SW BUS 031,226 0 0 35,254 25,347 022,170

WCU-4 FEED 2,9125,381 0 0 6,076 0 0InCABLE 2,547

WCU-4 SW FEED 22,49825,969 0 0 29,319 0 0InCABLE 19,678 22,170

WCU-5 SW BUS 031,226 0 0 35,254 25,347 022,170

WCU-5 FEED 2,9125,381 0 0 6,076 0 0InCABLE 2,547

WCU-5 SW FEED 22,49825,969 0 0 29,319 0 0InCABLE 19,678 22,170

27

Page 102: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL P4X 027,826 0 0 30,361 23,495 020,973

EF-11 FUSE FEED 60106 0 0 116 0 0InCABLE 53

ELEV1 CB FEED 81143 0 0 156 0 0InCABLE 72

ELEV2 CB FEED 81144 0 0 157 0 0InCABLE 72

P4X FEED 23,27727,438 0 0 29,937 0 0InCABLE 20,778 20,973

EF-11 BUS 03,937 0 0 3,937 3,257 03,257

EF-11 FEED 3,2393,905 0 0 3,905 0 0InCABLE 3,239 3,257

EF-11 59106 0 0 106 0 0InIND-MTR 59

EF-11 FUSE BUS 04,368 0 0 4,368 3,611 03,611

EF-11 FEED 59106 0 0 106 0 0InCABLE 59

EF-11 FUSE FEED 3,5924,334 0 0 4,334 0 0InCABLE 3,592 3,611

27KVA XFMR ELEV1 SEC

BUS

0763 0 0 771 744 0737

ELEV1 FEED 115177 0 0 179 0 0InCABLE 114

27KVA XFMR ELEV1 646614 0 0 621 0 0In2W-XFMR 640 737

27KVA XFMR ELEV1 PRI BUS 04,576 0 0 4,576 3,755 03,755

ELEV1 XFMR FEED 3,7184,508 0 0 4,508 0 0InCABLE 3,718 3,755

28

Page 103: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

27KVA XFMR ELEV1 79145 0 0 145 0 0In2W-XFMR 79

ELEV1 CB2 BUS 07,207 0 0 7,207 5,882 05,882

ELEV1 CB FEED 5,8397,128 0 0 7,128 0 0InCABLE 5,839 5,882

ELEV1 XFMR FEED 78144 0 0 144 0 0InCABLE 78

ELEV1 BUS 0739 0 0 747 714 0709

ELEV1 FEED 618594 0 0 600 0 0InCABLE 614 709

ELEV1 114177 0 0 179 0 0InIND-MTR 113

WCU-4 BUS 029,048 0 0 32,439 22,770 020,147

WCU-4 FEED 19,98823,735 0 0 26,506 0 0InCABLE 17,686 20,147

WCU-4 2,8625,477 0 0 6,116 0 0InIND-MTR 2,533

WCU-5 BUS 029,048 0 0 32,439 22,770 020,147

WCU-5 FEED 19,98823,735 0 0 26,506 0 0InCABLE 17,686 20,147

WCU-5 2,8625,477 0 0 6,116 0 0InIND-MTR 2,533

27KVA XFMR ELEV2 SEC

BUS

0790 0 0 801 762 0754

ELEV2 FEED 114177 0 0 179 0 0InCABLE 113

27KVA XFMR ELEV2 664638 0 0 647 0 0In2W-XFMR 656 754

29

Page 104: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

27KVA XFMR ELEV2 PRI BUS 07,214 0 0 7,214 5,891 05,891

ELEV2 XFMR FEED 5,8497,136 0 0 7,136 0 0InCABLE 5,849 5,891

27KVA XFMR ELEV2 79144 0 0 144 0 0In2W-XFMR 79

ELEV2 CB2 BUS 08,899 0 0 8,899 7,233 07,233

ELEV2 CB FEED 7,1878,814 0 0 8,814 0 0InCABLE 7,187 7,233

ELEV2 XFMR FEED 78144 0 0 144 0 0InCABLE 78

ELEV2 BUS 0761 0 0 770 724 0719

ELEV2 FEED 629613 0 0 620 0 0InCABLE 624 719

ELEV2 113177 0 0 179 0 0InIND-MTR 112

SWGW 2 UTIL BUS 010,000,438 0 0 13,827,640 13,827,447 010,000,291

1500KVA XFMR2 404438 0 0 606 0 0In2W-XFMR 292

SWGR #2 13,827,04310,000,000 0 0 13,827,035 0 0InUTILITY 9,999,999 10,000,296

USB-5 035,917 0 0 51,367 48,943 034,156

4J FEED 478526 0 0 752 0 0InCABLE 333

EB2 FEED 3,0793,389 0 0 4,847 0 0InCABLE 2,149

MCC3 FEED 818901 0 0 1,288 0 0InCABLE 571

30

Page 105: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

P4A FEED 00 0 0 0 0 0InCABLE 0

P4B FEED 00 0 0 0 0 0InCABLE 0

P4D FEED 00 0 0 0 0 0InCABLE 0

1500KVA XFMR3 44,57131,104 0 0 44,483 0 0In2W-XFMR 31,105 34,156

UTIL BUS 010,000,160 0 0 13,827,284 13,827,209 010,000,106

1500KVA XFMR3 148160 0 0 222 0 0In2W-XFMR 107

UTIL 13,827,06110,000,000 0 0 13,827,062 0 0InUTILITY 9,999,999 10,000,111

PNL 4J 023,997 0 0 26,560 22,277 020,074

4J FEED 21,95623,479 0 0 25,987 0 0InCABLE 19,786 20,074

PNL 4F-13 FEED 109177 0 0 195 0 0InCABLE 98

SF1A FUSE FEED 109176 0 0 195 0 0InCABLE 98

SF1B FUSE FEED 109177 0 0 196 0 0InCABLE 99

SF1A FUSE BUS 05,660 0 0 5,660 4,692 04,692

SF1A FEED 98177 0 0 177 0 0InCABLE 98

SF1A FUSE FEED 4,6535,592 0 0 5,592 0 0InCABLE 4,653 4,692

SF1A BUS 05,166 0 0 5,166 4,281 04,281

31

Page 106: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

SF1A FEED 4,2455,101 0 0 5,101 0 0InCABLE 4,245 4,281

SF1A 98177 0 0 177 0 0InIND-MTR 98

SF1B FUSE BUS 07,905 0 0 7,905 6,556 06,556

SF1B FEED 98177 0 0 177 0 0InCABLE 98

SF1B FUSE FEED 6,5107,823 0 0 7,823 0 0InCABLE 6,510 6,556

SF1B BUS 06,987 0 0 6,987 5,794 05,794

SF1B FEED 5,7526,911 0 0 6,911 0 0InCABLE 5,752 5,794

SF1B 98177 0 0 177 0 0InIND-MTR 98

SFGA FUSE BUS 08,772 0 0 8,772 5,553 05,553

SFGA FEED 75177 0 0 177 0 0InCABLE 75

SFGA FUSE FEED 5,5118,673 0 0 8,673 0 0InCABLE 5,511 5,553

SFGA BUS 08,051 0 0 8,051 5,044 05,044

SFGA FEED 5,0057,957 0 0 7,957 0 0InCABLE 5,005 5,044

SFGA 74177 0 0 177 0 0InIND-MTR 74

PNL 4F-13 020,589 0 0 21,959 17,357 016,479

PNL 4F-13 FEED 17,26220,420 0 0 21,779 0 0InCABLE 16,388 16,479

32

Page 107: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

SFGA FUSE FEED 99177 0 0 189 0 0InCABLE 94

PNL P4A 035,366 0 0 49,852 47,116 033,399

P4A FEED 47,11635,366 0 0 49,852 0 0InCABLE 33,399 33,399

PNL 4B FEED 00 0 0 0 0 0InCABLE 0

PNL 4G-104 FEED 00 0 0 0 0 0InCABLE 0

XFMR 2GA FEED 00 0 0 0 0 0InCABLE 0

XFMR 2GB FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2GA PRI BUS 031,187 0 0 33,336 30,237 028,561

XFMR 2GA FEED 30,23731,187 0 0 33,336 0 0InCABLE 28,561 28,561

45KVA XFMR 2GA 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR 2GA SEC BUS 06,430 0 0 6,478 6,585 06,538

2GA FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2GA 6,5856,430 0 0 6,478 0 0In2W-XFMR 6,538 6,538

PNL 2GA 05,900 0 0 5,927 5,866 05,840

2GA FEED 5,8665,900 0 0 5,927 0 0InCABLE 5,840 5,840

2GA2 FEED 00 0 0 0 0 0InCABLE 0

33

Page 108: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL 2GA2 05,708 0 0 5,731 5,619 05,598

2GA2 FEED 5,6195,708 0 0 5,731 0 0InCABLE 5,598 5,598

45KVA XFMR 2GB PRI BUS 031,187 0 0 33,336 30,237 028,561

XFMR 2GB FEED 30,23731,187 0 0 33,336 0 0InCABLE 28,561 28,561

45KVA XFMR 2GB 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR 2GB SEC BUS 06,430 0 0 6,478 6,585 06,538

2GB FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2GB 6,5856,430 0 0 6,478 0 0In2W-XFMR 6,538 6,538

PNL 2GB 05,900 0 0 5,927 5,866 05,840

2GB FEED 5,8665,900 0 0 5,927 0 0InCABLE 5,840 5,840

2GB2 FEED 00 0 0 0 0 0InCABLE 0

PNL 2GB2 05,708 0 0 5,731 5,619 05,598

2GB2 FEED 5,6195,708 0 0 5,731 0 0InCABLE 5,598 5,598

PNL 4G-104 031,277 0 0 34,936 28,938 027,455

PNL 4G-104 FEED 28,93831,277 0 0 34,936 0 0InCABLE 27,455 27,455

34

Page 109: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL 4B 015,806 0 0 15,946 11,212 011,191

PNL 4B FEED 11,21215,806 0 0 15,946 0 0InCABLE 11,191 11,191

XFMR 2B1 FEED 00 0 0 0 0 0InCABLE 0

PNL 2B1 05,249 0 0 5,335 5,220 05,131

2B1 FEED 5,2205,249 0 0 5,335 0 0InCABLE 5,131 5,131

2B2 FEED 00 0 0 0 0 0InCABLE 0

PNL 2B2 05,104 0 0 5,176 5,022 04,947

2B2 FEED 5,0225,104 0 0 5,176 0 0InCABLE 4,947 4,947

PNL P4B 032,497 0 0 42,786 38,957 029,629

P4B FEED 38,95732,497 0 0 42,786 0 0InCABLE 29,629 29,629

PNL 4C-12 FEED 00 0 0 0 0 0InCABLE 0

PNL 4H FEED 00 0 0 0 0 0InCABLE 0

PNL 4C-12 020,317 0 0 20,535 15,084 015,051

PNL 4C-12 FEED 15,08420,317 0 0 20,535 0 0InCABLE 15,051 15,051

XFMR 2CA FEED 00 0 0 0 0 0InCABLE 0

XFMR 2CA PRI BUS 018,623 0 0 18,716 13,783 013,768

35

Page 110: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

XFMR 2CA FEED 13,78318,623 0 0 18,716 0 0InCABLE 13,768 13,768

50KVA XFMR 2CA 00 0 0 0 0 0In2W-XFMR 0

XFMR 2CA SEC BUS 07,703 0 0 7,752 8,030 07,978

2CA FEED 00 0 0 0 0 0InCABLE 0

50KVA XFMR 2CA 8,0307,703 0 0 7,752 0 0In2W-XFMR 7,978 7,978

PNL 2CA 07,076 0 0 7,099 7,167 07,145

2C1 FEED 00 0 0 0 0 0InCABLE 0

2CA FEED 7,1677,076 0 0 7,099 0 0InCABLE 7,145 7,145

PNL 2C1 05,833 0 0 5,838 5,615 05,611

2C1 FEED 5,6155,833 0 0 5,838 0 0InCABLE 5,611 5,611

2C2-12 FEED 00 0 0 0 0 0InCABLE 0

PNL 2C2-12 05,608 0 0 5,611 5,352 05,349

2C2-12 FEED 5,3525,608 0 0 5,611 0 0InCABLE 5,349 5,349

PNL 4H 025,272 0 0 26,125 20,415 020,208

PNL 4H FEED 20,41525,272 0 0 26,125 0 0InCABLE 20,208 20,208

PNL P4D 032,109 0 0 41,923 37,999 029,140

36

Page 111: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

P4D FEED 37,99932,109 0 0 41,923 0 0InCABLE 29,140 29,140

PNL 4D1 FEED 00 0 0 0 0 0InCABLE 0

XFMR 2C-12 FEED 00 0 0 0 0 0InCABLE 0

XFMR KL FEED 00 0 0 0 0 0InCABLE 0

XFMR P2D FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR P2D PRI BUS 018,384 0 0 18,394 15,700 015,694

XFMR P2D FEED 15,70018,384 0 0 18,394 0 0InCABLE 15,694 15,694

45KVA XFMR P2D 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR P2D SEC BUS 04,094 0 0 4,118 4,195 04,170

P2D FUSE FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR P2D 4,1954,094 0 0 4,118 0 0In2W-XFMR 4,170 4,170

P2D FUSE BUS 03,852 0 0 3,866 3,871 03,857

P2D FEED 00 0 0 0 0 0InCABLE 0

P2D FUSE FEED 3,8713,852 0 0 3,866 0 0InCABLE 3,857 3,857

PNL P2D 03,210 0 0 3,213 2,876 02,875

P2D FEED 2,8763,210 0 0 3,213 0 0InCABLE 2,875 2,875

37

Page 112: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL 4D1 026,131 0 0 27,358 21,675 021,311

PNL 4D1 FEED 21,67526,131 0 0 27,358 0 0InCABLE 21,311 21,311

XFMR 2D1 FEED 00 0 0 0 0 0InCABLE 0

XFMR 2D1 PRI BUS 021,016 0 0 21,101 16,754 016,730

XFMR 2D1 FEED 16,75421,016 0 0 21,101 0 0InCABLE 16,730 16,730

45KVA XFMR 2D1 00 0 0 0 0 0In2W-XFMR 0

XFMR 2D1 SEC BUS 04,551 0 0 4,580 4,664 04,635

2D1-02 FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2D1 4,6644,551 0 0 4,580 0 0In2W-XFMR 4,635 4,635

PNL 2D1-02 04,255 0 0 4,271 4,268 04,253

2D1-02 FEED 4,2684,255 0 0 4,271 0 0InCABLE 4,253 4,253

112.5KVA XFMR KL PRI BUS 016,899 0 0 17,117 13,949 013,723

XFMR KL FEED 13,94916,899 0 0 17,117 0 0InCABLE 13,723 13,723

112.5KVA XFMR KL 00 0 0 0 0 0In2W-XFMR 0

XFMR 2C-12 PRI BUS 011,835 0 0 11,837 7,719 07,719

38

Page 113: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

XFMR 2C-12 FEED 7,71911,835 0 0 11,837 0 0InCABLE 7,719 7,719

75KVA XFMR 2C-12 00 0 0 0 0 0In2W-XFMR 0

XFMR 2C-12 SEC BUS 06,124 0 0 6,288 6,573 06,376

2C-12 FEED 00 0 0 0 0 0InCABLE 0

75KVA XFMR 2C-12 6,5736,124 0 0 6,288 0 0In2W-XFMR 6,376 6,376

PNL 2C-12 04,830 0 0 4,846 4,726 04,714

2C-12 FEED 4,7264,830 0 0 4,846 0 0InCABLE 4,714 4,714

2C3 FEED 00 0 0 0 0 0InCABLE 0

PNL 2C3 04,615 0 0 4,625 4,465 04,458

2C3 FEED 4,4654,615 0 0 4,625 0 0InCABLE 4,458 4,458

MCC-3 031,935 0 0 41,525 37,321 028,778

2G1 JUNC FEED 00 0 0 0 0 0InCABLE 0

2P-1 CB FEED 00 0 0 0 0 0InCABLE 0

ELEV 4&5 FEED 329422 0 0 549 0 0InCABLE 254

MCC3 FEED 36,61731,031 0 0 40,350 0 0InCABLE 28,235 28,778

P-19-1 FEED 2835 0 0 46 0 0InCABLE 21

39

Page 114: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

P-19-2 FEED 2835 0 0 46 0 0InCABLE 21

PNL 4K PENTHOUSE FEED 321412 0 0 536 0 0InCABLE 247

P-19-1 BUS 01,340 0 0 1,340 781 0781

P-19-1 FEED 7791,334 0 0 1,334 0 0InCABLE 779 781

P-19-1 1435 0 0 35 0 0InIND-MTR 14

P-19-2 BUS 01,340 0 0 1,340 781 0781

P-19-2 FEED 7791,334 0 0 1,334 0 0InCABLE 779 781

P-19-2 1435 0 0 35 0 0InIND-MTR 14

75KVA XFMR 2P-1 PRI BUS 014,160 0 0 14,167 9,559 09,559

XFMR 2P-1 FEED 9,55914,160 0 0 14,167 0 0InCABLE 9,559 9,559

75KVA XFMR 2P-1 00 0 0 0 0 0In2W-XFMR 0

75KVA XFMR 2P-1 SEC BUS 04,356 0 0 4,499 4,621 04,461

2P-1 FEED 00 0 0 0 0 0InCABLE 0

75KVA XFMR 2P-1 4,6214,356 0 0 4,499 0 0In2W-XFMR 4,461 4,461

PNL 2P-1 04,183 0 0 4,299 4,344 04,219

2P-1 FEED 4,3444,183 0 0 4,299 0 0InCABLE 4,219 4,219

40

Page 115: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2P-2 FEED 00 0 0 0 0 0InCABLE 0

2P-1 BUS 014,854 0 0 14,863 9,971 09,970

2P-1 CB FEED 9,97114,854 0 0 14,863 0 0InCABLE 9,970 9,970

XFMR 2P-1 FEED 00 0 0 0 0 0InCABLE 0

PNL 2P-2 03,984 0 0 4,054 4,034 03,965

2P-2 FEED 4,0343,984 0 0 4,054 0 0InCABLE 3,965 3,965

ELEV 4&5 JUNCTION 014,366 0 0 14,367 9,218 09,218

ELEV 4 FUSE FEED 91212 0 0 212 0 0InCABLE 91

ELEV 4&5 FEED 9,10414,101 0 0 14,102 0 0InCABLE 9,104 9,218

ELEV 5 FUSE FEED 91212 0 0 212 0 0InCABLE 91

ELEV 4 BUS 07,595 0 0 7,595 4,565 04,565

ELEV 4 FEED 4,5277,502 0 0 7,502 0 0InCABLE 4,527 4,565

ELEV 4 85213 0 0 213 0 0InIND-MTR 85

ELEV 5 BUS 07,595 0 0 7,595 4,565 04,565

ELEV 5 FEED 4,5277,502 0 0 7,502 0 0InCABLE 4,527 4,565

ELEV 5 85213 0 0 213 0 0InIND-MTR 85

41

Page 116: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

ELEV 5 FUSE BUS 012,566 0 0 12,566 7,900 07,900

ELEV 5 FEED 89212 0 0 212 0 0InCABLE 89

ELEV 5 FUSE FEED 7,84812,443 0 0 12,443 0 0InCABLE 7,848 7,900

ELEV 4 FUSE BUS 012,566 0 0 12,566 7,900 07,900

ELEV 4 FEED 89212 0 0 212 0 0InCABLE 89

ELEV 4 FUSE FEED 7,84812,443 0 0 12,443 0 0InCABLE 7,848 7,900

PNL 4K PENTHOUSE 021,147 0 0 21,905 16,358 016,156

PNL 4K PENTHOUSE FEED 16,15220,748 0 0 21,491 0 0InCABLE 15,953 16,157

TOWER41 FUSE FEED 107208 0 0 215 0 0InCABLE 106

TOWER42 FUSE FEED 107207 0 0 214 0 0InCABLE 105

XFMR 2K FEED 00 0 0 0 0 0InCABLE 0

XFMR 2K-232 FEED 00 0 0 0 0 0InCABLE 0

XFMR 2L-1 FEED 00 0 0 0 0 0InCABLE 0

9KVA XFMR 2K PRI BUS 017,076 0 0 17,129 12,964 012,949

XFMR 2K FEED 12,96417,076 0 0 17,129 0 0InCABLE 12,949 12,949

9KVA XFMR 2K 00 0 0 0 0 0In2W-XFMR 0

42

Page 117: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

9KVA XFMR 2K SEC BUS 02,528 0 0 2,544 2,575 02,559

2K FEED 00 0 0 0 0 0InCABLE 0

9KVA XFMR 2K 2,5752,528 0 0 2,544 0 0In2W-XFMR 2,559 2,559

PNL 2K 02,331 0 0 2,337 2,321 02,316

2K FEED 2,3212,331 0 0 2,337 0 0InCABLE 2,316 2,316

2K1 FEED 00 0 0 0 0 0InCABLE 0

PNL 2K1 02,153 0 0 2,155 2,105 02,103

2K1 FEED 2,1052,153 0 0 2,155 0 0InCABLE 2,103 2,103

TOWER41 BUS 01,819 0 0 1,819 1,475 01,475

TOWER41 FEED 1,4401,758 0 0 1,758 0 0InCABLE 1,440 1,475

TOWER41 115213 0 0 213 0 0InIND-MTR 115

TOWER41 FUSE BUS 02,023 0 0 2,023 1,640 01,640

TOWER41 FEED 115212 0 0 212 0 0InCABLE 115

TOWER41 FUSE FEED 1,6031,959 0 0 1,959 0 0InCABLE 1,603 1,640

TOWER42 BUS 01,619 0 0 1,619 1,313 01,313

43

Page 118: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

TOWER42 FEED 1,2781,558 0 0 1,558 0 0InCABLE 1,277 1,313

TOWER42 115213 0 0 213 0 0InIND-MTR 115

TOWER42 FUSE BUS 01,777 0 0 1,777 1,441 01,441

TOWER42 FEED 115212 0 0 212 0 0InCABLE 115

TOWER42 FUSE FEED 1,4041,714 0 0 1,714 0 0InCABLE 1,404 1,441

45KVA XFMR 2L-1 PRI BUS 013,528 0 0 13,535 10,353 010,350

XFMR 2L-1 FEED 10,35313,528 0 0 13,535 0 0InCABLE 10,350 10,350

45KVA XFMR 2L-1 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR 2L-1 SEC BUS 03,803 0 0 3,825 3,916 03,893

2L-1 FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2L-1 3,9163,803 0 0 3,825 0 0In2W-XFMR 3,893 3,893

PNL 2L-1 03,598 0 0 3,613 3,636 03,622

2L-1 FEED 3,6363,598 0 0 3,613 0 0InCABLE 3,622 3,622

2L-2 FEED 00 0 0 0 0 0InCABLE 0

PNL 2L-2 03,472 0 0 3,483 3,470 03,459

2L-2 FEED 3,4703,472 0 0 3,483 0 0InCABLE 3,459 3,459

44

Page 119: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2L-3 FEED 00 0 0 0 0 0InCABLE 0

PNL 2L-3 03,100 0 0 3,105 3,005 03,001

2L-3 FEED 3,0053,100 0 0 3,105 0 0InCABLE 3,001 3,001

45KVA XFMR 2K-232 PRI BUS 014,503 0 0 14,517 11,066 011,061

XFMR 2K-232 FEED 11,06614,503 0 0 14,517 0 0InCABLE 11,061 11,061

45KVA XFMR 2K-232 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR 2K-232 SEC

BUS

03,627 0 0 3,649 3,726 03,704

2K-232 CB FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2K-232 3,7263,627 0 0 3,649 0 0In2W-XFMR 3,704 3,704

PNL 2K-232 SEC1 02,953 0 0 2,958 2,856 02,852

2K-232 FEED 2,8562,953 0 0 2,958 0 0InCABLE 2,852 2,852

2K-232 SEC2 FEED 00 0 0 0 0 0InCABLE 0

PNL 2K-232 SEC2 02,836 0 0 2,839 2,716 02,713

2K-232 SEC2 FEED 2,7162,836 0 0 2,839 0 0InCABLE 2,713 2,713

2K-232 SEC3 FEED 00 0 0 0 0 0InCABLE 0

2K-232 CB1 BUS 03,481 0 0 3,497 3,526 03,510

45

Page 120: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2K-232 CB FEED 3,5263,481 0 0 3,497 0 0InCABLE 3,510 3,510

2K-232 FEED 00 0 0 0 0 0InCABLE 0

PNL 2K-232 SEC3 02,726 0 0 2,729 2,589 02,587

2K-232 SEC3 FEED 2,5892,726 0 0 2,729 0 0InCABLE 2,587 2,587

2G1 JUNC 022,304 0 0 22,493 16,680 016,657

2G1 JUNC FEED 16,68022,304 0 0 22,493 0 0InCABLE 16,657 16,657

2H FUSE FEED 00 0 0 0 0 0InCABLE 0

2H FUSE BUS 020,688 0 0 20,782 15,026 015,017

2H FUSE FEED 15,02620,688 0 0 20,782 0 0InCABLE 15,017 15,017

2H JUNC FEED 00 0 0 0 0 0InCABLE 0

2H JUNC 017,220 0 0 17,237 11,820 011,819

2H JUNC FEED 11,82017,220 0 0 17,237 0 0InCABLE 11,819 11,819

2H-1 FUSE FEED 00 0 0 0 0 0InCABLE 0

2H-2 FUSE1 FEED 00 0 0 0 0 0InCABLE 0

25KVA XFMR 2H-1 PRI BUS 08,987 0 0 8,987 6,603 06,603

2H-1 XFMR FEED 6,6038,987 0 0 8,987 0 0InCABLE 6,603 6,603

46

Page 121: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

25KVA XFMR 2H-1 00 0 0 0 0 0In2W-XFMR 0

25KVA XFMR 2H-1 SEC BUS 04,757 0 0 4,772 4,974 04,954

2H-1 FEED 00 0 0 0 0 0InCABLE 0

25KVA XFMR 2H-1 4,9744,757 0 0 4,772 0 0In2W-XFMR 4,954 4,954

2H-1 FUSE BUS 012,549 0 0 12,550 8,891 08,891

2H-1 FUSE FEED 8,89112,549 0 0 12,550 0 0InCABLE 8,891 8,891

2H-1 XFMR FEED 00 0 0 0 0 0InCABLE 0

PNL 2H-1 03,843 0 0 3,845 3,791 03,789

2H-1 FEED 3,7913,843 0 0 3,845 0 0InCABLE 3,789 3,789

25KVA XFMR 2H-2 PRI BUS 08,987 0 0 8,987 6,603 06,603

2H-2 XFMR FEED 6,6038,987 0 0 8,987 0 0InCABLE 6,603 6,603

25KVA XFMR 2H-2 00 0 0 0 0 0In2W-XFMR 0

25KVA XFMR 2H-2 SEC BUS 04,757 0 0 4,772 4,974 04,954

2H-2 FUSE2 FEED 00 0 0 0 0 0InCABLE 0

25KVA XFMR 2H-2 4,9744,757 0 0 4,772 0 0In2W-XFMR 4,954 4,954

2H-2 FUSE BUS 012,549 0 0 12,550 8,891 08,891

47

Page 122: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2H-2 FUSE1 FEED 8,89112,549 0 0 12,550 0 0InCABLE 8,891 8,891

2H-2 XFMR FEED 00 0 0 0 0 0InCABLE 0

2H-2 FUSE2 BUS 03,843 0 0 3,845 3,791 03,789

2H-2 FEED 00 0 0 0 0 0InCABLE 0

2H-2 FUSE2 FEED 3,7913,843 0 0 3,845 0 0InCABLE 3,789 3,789

PNL 2H-2 03,489 0 0 3,490 3,373 03,372

2H FEED 00 0 0 0 0 0InCABLE 0

2H-2 FEED 3,3733,489 0 0 3,490 0 0InCABLE 3,372 3,372

2H-3 FEED 00 0 0 0 0 0InCABLE 0

PNL 2H 02,205 0 0 2,205 1,992 01,992

2H FEED 1,9922,205 0 0 2,205 0 0InCABLE 1,992 1,992

PNL 2H-3 03,363 0 0 3,364 3,228 03,227

2H-3 FEED 3,2283,363 0 0 3,364 0 0InCABLE 3,227 3,227

EB2 BUS 032,994 0 0 42,564 38,086 029,949

EB2 FEED 35,45929,581 0 0 38,161 0 0InCABLE 27,883 29,949

EB2 2,6353,424 0 0 4,417 0 0InIND-MTR 2,072

48

Page 123: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

FIRE PUMP BUS 01,723 0 0 1,741 1,297 01,296

FIRE PUMP FEED1 1,1181,373 0 0 1,387 0 0InCABLE 1,117 1,296

FIRE PUMP 214426 0 0 430 0 0InIND-MTR 213

FIRE PUMP CB1 BUS 01,743 0 0 1,762 1,321 01,319

FIRE PUMP FEED1 215425 0 0 430 0 0InCABLE 214

FIRE PUMP FEED2 1,1401,391 0 0 1,405 0 0InCABLE 1,138 1,319

FIRE PUMP CB2 BUS 01,909 0 0 1,938 1,531 01,526

FIRE PUMP FEED2 225420 0 0 427 0 0InCABLE 224

FIRE PUMP FEED3 1,3311,540 0 0 1,564 0 0InCABLE 1,328 1,526

FIRE PUMP CB3 BUS 02,335 0 0 2,467 2,283 02,179

FIRE PUMP FEED3 266409 0 0 432 0 0InCABLE 254

FIRE PUMP FEED4 2,0231,938 0 0 2,047 0 0InCABLE 1,931 2,179

FIRE PUMP XFMR SEC BUS 02,346 0 0 2,483 2,311 02,197

FIRE PUMP FEED4 268408 0 0 432 0 0InCABLE 255

FIRE PUMP XFMR 2,0491,948 0 0 2,062 0 0In2W-XFMR 1,948 2,197

FIRE PUMP UTIL BUS 010,000,013 0 0 13,827,075 13,827,070 010,000,008

49

Page 124: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

FIRE PUMP XFMR 1213 0 0 18 0 0In2W-XFMR 9

FIRE PUMP UTIL 13,827,05810,000,000 0 0 13,827,058 0 0InUTILITY 9,999,999 10,000,013

UPS CB1 BUS 027,126 0 0 29,717 26,843 024,668

MBP-B FEED1 26,84327,126 0 0 29,717 0 0InCABLE 24,668 24,668

MBP-B FEED2 00 0 0 0 0 0InCABLE 0

UPS B BUS1 026,793 0 0 29,190 26,289 024,281

MBP-B FEED2 26,28926,793 0 0 29,190 0 0InCABLE 24,281 24,281

MBP-B FEED3 00 0 0 0 0 0InCABLE 0

UPS-B 00 0 0 0 0 0In 0

UPS B BUS2 01,202 0 0 1,659 0 00

MBP-B FEED3 00 0 0 0 0 0InCABLE 0

MBP-B FEED4 0600 0 0 829 0 0InCABLE 0

UPS-B 0601 521 521 922 799 799In 0

UPS B CB3 BUS 01,202 0 0 1,659 0 00

MBP-B FEED4 0601 0 0 830 0 0InCABLE 0

SSD-B FEED 0601 0 0 829 0 0InCABLE 0

50

Page 125: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL SSD-B 01,202 0 0 1,659 0 00

SSD-B FEED 0601 0 0 830 0 0InCABLE 0

STS-A FEED1 0300 0 0 415 0 0InCABLE 0

STS-B FEED1 0300 0 0 415 0 0InCABLE 0

UPS A CB1 BUS 036,383 0 0 38,785 31,612 029,280

MBP-A FEED1 31,61236,383 0 0 38,785 0 0InCABLE 29,280 29,280

MBP-A FEED2 00 0 0 0 0 0InCABLE 0

UPS A BUS1 035,762 0 0 37,929 30,854 028,732

MBP-A FEED2 30,85435,762 0 0 37,929 0 0InCABLE 28,732 28,732

MBP-A FEED3 00 0 0 0 0 0InCABLE 0

UPS-A 00 0 0 0 0 0In 0

UPS A BUS2 01,202 0 0 1,659 0 00

MBP-A FEED3 00 0 0 0 0 0InCABLE 0

MBP-A FEED4 0600 0 0 829 0 0InCABLE 0

UPS-A 0601 521 521 922 799 799In 0

UPS A CB3 BUS 01,202 0 0 1,659 0 00

51

Page 126: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

MBP-A FEED4 0601 0 0 830 0 0InCABLE 0

SSD-A FEED 0601 0 0 829 0 0InCABLE 0

PNL SSD-A 01,202 0 0 1,659 0 00

SSD-A FEED 0601 0 0 830 0 0InCABLE 0

STS-A FEED2 0300 0 0 415 0 0InCABLE 0

STS-B FEED2 0300 0 0 415 0 0InCABLE 0

STS-B 01,202 0 0 1,658 0 00

STS-B FEED1 0601 0 0 829 0 0InCABLE 0

STS-B FEED2 0601 0 0 829 0 0InCABLE 0

U4B FEED 00 0 0 0 0 0InCABLE 0

PNL U4B 01,200 0 0 1,653 0 00

PDU1 FEED 00 0 0 0 0 0InCABLE 0

PDU3 FEED 00 0 0 0 0 0InCABLE 0

U4B FEED 01,200 0 0 1,653 0 0InCABLE 0

PDU1 01,187 0 0 1,563 0 00

PDU1 FEED 01,187 0 0 1,563 0 0InCABLE 0

52

Page 127: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PDU3 01,176 0 0 1,502 0 00

PDU3 FEED 01,176 0 0 1,502 0 0InCABLE 0

STS-A 01,202 0 0 1,658 0 00

STS-A FEED1 0601 0 0 829 0 0InCABLE 0

STS-A FEED2 0601 0 0 829 0 0InCABLE 0

U4A FEED 00 0 0 0 0 0InCABLE 0

PNL U4A 01,200 0 0 1,653 0 00

PDU2 FEED 00 0 0 0 0 0InCABLE 0

PDU4 FEED 00 0 0 0 0 0InCABLE 0

U4A FEED 01,200 0 0 1,653 0 0InCABLE 0

PDU2 01,187 0 0 1,563 0 00

PDU2 FEED 01,187 0 0 1,563 0 0InCABLE 0

PDU4 01,181 0 0 1,527 0 00

PDU4 FEED 01,181 0 0 1,527 0 0InCABLE 0

PNL KL 010,084 0 0 10,882 11,134 010,255

53

Page 128: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

KL FUSE FEED 11,13410,084 0 0 10,882 0 0InCABLE 10,255 10,255

112.5KVA XFMR KL SEC BUS 010,895 0 0 12,009 12,786 011,490

KL FUSE FEED 00 0 0 0 0 0InCABLE 0

112.5KVA XFMR KL 12,78610,895 0 0 12,009 0 0In2W-XFMR 11,490 11,490

15KVA XFMR 2J PRI BUS 021,396 0 0 21,408 17,369 017,351

XFMR 2J FEED 17,36921,396 0 0 21,408 0 0InCABLE 17,351 17,351

15KVA XFMR 2J 00 0 0 0 0 0In2W-XFMR 0

ATS-1 NORMAL BUS 035,797 0 0 41,403 33,320 028,109

ATS-1 FEED 33,32035,797 0 0 41,403 0 0InCABLE 28,109 28,109

ATS-1 2,8572,116 0 0 3,020 0 0In 2,023

ATS-1 BUS 02,202 0 0 3,143 2,934 02,077

EMDP-P FEED 7786 0 0 123 0 0InCABLE 54

ATS-1 EM BUS 02,202 0 0 3,143 2,934 02,077

ATS-1 EM FEED 2,8572,116 0 0 3,020 0 0InCABLE 2,023 2,077

ATS-1 7786 0 0 123 0 0In 54

XFMR 2B1 SEC BUS 06,186 0 0 6,390 6,648 06,419

54

Page 129: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2B1 FEED 00 0 0 0 0 0InCABLE 0

75KVA XFMR 2B1 6,6486,186 0 0 6,390 0 0In2W-XFMR 6,419 6,419

XFMR 2B1 PRI BUS 013,737 0 0 13,777 9,783 09,776

XFMR 2B1 FEED 9,78313,737 0 0 13,777 0 0InCABLE 9,776 9,776

75KVA XFMR 2B1 00 0 0 0 0 0In2W-XFMR 0

USDP-B 019,318 0 0 26,711 26,711 019,318

PNL EDP-D CB1 FEED 00 0 0 0 0 0InCABLE 0

PNL U XFMR FEED 00 0 0 0 0 0InCABLE 0

XFMR 2UPSN-1 FEED 00 0 0 0 0 0InCABLE 0

XFMR 2UPSS-1 FEED 00 0 0 0 0 0InCABLE 0

UPSDP-B UTIL 26,71119,318 0 0 26,711 0 0InUTILITY 19,318 19,318

45KVA XFMR U PRI BUS 07,858 0 0 7,858 6,770 06,770

PNL U XFMR FEED 6,7707,858 0 0 7,858 0 0InCABLE 6,770 6,770

45KVA XFMR U 00 0 0 0 0 0In2W-XFMR 0

45KVA XFMR U SEC BUS 03,364 0 0 3,378 3,496 03,479

PNL U FEED 00 0 0 0 0 0InCABLE 0

55

Page 130: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

45KVA XFMR U 3,4963,364 0 0 3,378 0 0In2W-XFMR 3,479 3,479

PNL U 03,224 0 0 3,234 3,304 03,292

PNL 2U-1 FEED 00 0 0 0 0 0InCABLE 0

PNL U FEED 3,3043,224 0 0 3,234 0 0InCABLE 3,292 3,292

PNL 2U-1 02,353 0 0 2,354 2,226 02,224

PNL 2U-1 FEED 2,2262,353 0 0 2,354 0 0InCABLE 2,224 2,224

75KVA EDP-D XFMR PRI BUS 03,126 0 0 3,126 2,621 02,621

PNL EDP-D XFMR FEED1 2,6213,126 0 0 3,126 0 0InCABLE 2,621 2,621

75KVA EDP-D XFMR 00 0 0 0 0 0In2W-XFMR 0

75KVA EDP-D XFMR SEC

BUS

04,709 0 0 4,722 5,284 05,250

PNL EDP-D XFMR FEED2 00 0 0 0 0 0InCABLE 0

75KVA EDP-D XFMR 5,2844,709 0 0 4,722 0 0In2W-XFMR 5,250 5,250

PNL EDP-D 03,906 0 0 3,916 4,031 04,008

PNL 1 FEED 00 0 0 0 0 0InCABLE 0

PNL 2 FEED 00 0 0 0 0 0InCABLE 0

PNL 3 FEED 00 0 0 0 0 0InCABLE 0

56

Page 131: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL 4 FEED 00 0 0 0 0 0InCABLE 0

PNL 5 FEED 00 0 0 0 0 0InCABLE 0

PNL 6 FEED 00 0 0 0 0 0InCABLE 0

PNL 7 FEED 00 0 0 0 0 0InCABLE 0

PNL EDP-D FEED 4,0313,906 0 0 3,916 0 0InCABLE 4,008 4,008

PNL EDP-D CB1 BUS 03,418 0 0 3,418 2,869 02,869

PNL EDP-D CB1 FEED 2,8693,418 0 0 3,418 0 0InCABLE 2,869 2,869

PNL EDP-D XFMR FEED1 00 0 0 0 0 0InCABLE 0

PNL EDP-D CB2 BUS 04,446 0 0 4,456 4,860 04,834

PNL EDP-D FEED 00 0 0 0 0 0InCABLE 0

PNL EDP-D XFMR FEED2 4,8604,446 0 0 4,456 0 0InCABLE 4,834 4,834

PNL 7 03,543 0 0 3,549 3,540 03,524

PNL 7 FEED 3,5403,543 0 0 3,549 0 0InCABLE 3,524 3,524

PNL 6 03,723 0 0 3,731 3,779 03,760

PNL 6 FEED 3,7793,723 0 0 3,731 0 0InCABLE 3,760 3,760

PNL 5 03,753 0 0 3,761 3,819 03,799

57

Page 132: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL 5 FEED 3,8193,753 0 0 3,761 0 0InCABLE 3,799 3,799

PNL 4 03,032 0 0 3,036 2,901 02,893

PNL 4 FEED 2,9013,032 0 0 3,036 0 0InCABLE 2,893 2,893

PNL 3 03,032 0 0 3,036 2,901 02,893

PNL 3 FEED 2,9013,032 0 0 3,036 0 0InCABLE 2,893 2,893

PNL 2 02,135 0 0 2,136 1,904 01,901

PNL 2 FEED 1,9042,135 0 0 2,136 0 0InCABLE 1,901 1,901

PNL 1 02,135 0 0 2,136 1,904 01,901

PNL 1 FEED 1,9042,135 0 0 2,136 0 0InCABLE 1,901 1,901

75KVA XFMR 2UPSS-1 PRI

BUS

05,731 0 0 5,731 4,781 04,781

XFMR 2UPSS-1 FEED 4,7815,731 0 0 5,731 0 0InCABLE 4,781 4,781

75KVA XFMR 2UPSS-1 00 0 0 0 0 0In2W-XFMR 0

75KVA XFMR 2UPSS-1 SEC

BUS

05,826 0 0 5,906 6,431 06,310

2UPSS-1 FEED 00 0 0 0 0 0InCABLE 0

75KVA XFMR 2UPSS-1 6,4315,826 0 0 5,906 0 0In2W-XFMR 6,310 6,310

58

Page 133: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

PNL 2UPSS-1 05,555 0 0 5,618 5,987 05,896

2UPSS-1 FEED 5,9875,555 0 0 5,618 0 0InCABLE 5,896 5,896

2UPSS-2 FEED 00 0 0 0 0 0InCABLE 0

PNL 2UPSS-2 05,428 0 0 5,484 5,788 05,707

2UPSS-2 FEED 5,7885,428 0 0 5,484 0 0InCABLE 5,707 5,707

2UPSS-3 FEED 00 0 0 0 0 0InCABLE 0

PNL 2UPSS-3 05,306 0 0 5,356 5,601 05,530

2UPSS-3 FEED 5,6015,306 0 0 5,356 0 0InCABLE 5,530 5,530

2UPSS-4 FEED 00 0 0 0 0 0InCABLE 0

PNL 2UPSS-4 05,189 0 0 5,234 5,426 05,363

2UPSS-4 FEED 5,4265,189 0 0 5,234 0 0InCABLE 5,363 5,363

45KVA XFMR 2UPSN-1 PRI

BUS

04,426 0 0 4,426 3,641 03,641

XFMR 2UPSN-1 FEED 3,6414,426 0 0 4,426 0 0InCABLE 3,641 3,641

45KVA XFMR 2UPSN-1 00 0 0 0 0 0In2W-XFMR 0

75KVA XFMR 2UPSN-1 SEC

BUS

04,277 0 0 4,287 4,650 04,634

59

Page 134: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

2UPSN-1 FEED 00 0 0 0 0 0InCABLE 0

45KVA XFMR 2UPSN-1 4,6504,277 0 0 4,287 0 0In2W-XFMR 4,634 4,634

PNL 2UPSN-1 03,993 0 0 4,000 4,235 04,227

2UPSN-1 FEED 4,2353,993 0 0 4,000 0 0InCABLE 4,227 4,227

2UPSN-2 FEED 00 0 0 0 0 0InCABLE 0

PNL 2UPSN-2 03,889 0 0 3,894 4,087 04,081

2UPSN-2 FEED 4,0873,889 0 0 3,894 0 0InCABLE 4,081 4,081

60

Page 135: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Device Evaluation Comprehensive Bus Report

Connected Bus StatusBus

Voltage

Calc

Int kADevNameInt

Rating %

Frame

Voltage

Calc

Mom kA

Mom

Rating %

Series

Rating

Dev

Int kA

Dev

Mom kAFrame/Trip

2H FUSE BUS Pass480 10.342H JUNC FUSE 600 20.69 200.080 / 70

2H-1 FUSE BUS Pass480 6.272H-1 FUSE 600 12.55 200.030

2H-2 FUSE BUS Pass480 6.272H-2 FUSE1 600 12.55 200.030

2H-2 FUSE2 BUS Pass120 1.922H-2 FUSE2 600 3.84 200.0100

2K-232 CB1 BUS Pass120 8.362K-232 CB1 240 3.51 42.0150

2P-1 BUS Pass480 59.422P-1 CB 480 14.85 25.0100

4K CB 2 BUS Pass480 26.984K CB 2 480 9.44 35.0200

4L CB 2 BUS Pass480 77.064L CB 2 480 19.27 25.0250 / 200

4M CB 2 BUS Pass480 54.044M CB 2 480 13.51 25.0150

CHILLER 1 BUS Pass480 58.47CHILLER1 CB2 480 20.47 35.0250

CWP1 FUSE 2 BUS Pass480 1.98CWP1 FUSE2 600 3.96 200.030

CWP-4 FUSE BUS Pass480 8.03CWP-4 60 A FUSE 600 16.06 200.060

CWP5 FUSE BUS Pass480 1.97CWP5 FUSE 600 3.94 200.0100

1

Project: FAB

Page 136: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Connected Bus StatusBus

Voltage

Calc

Int kADevNameInt

Rating %

Frame

Voltage

Calc

Mom kA

Mom

Rating %

Series

Rating

Dev

Int kA

Dev

Mom kAFrame/Trip

EF-11 FUSE BUS Pass480 2.18EF-11 FUSE 600 4.37 200.060

ELE#50 DISC BUS Pass480 10.06ELE#50 FUSE 600 20.12 200.0100 / 90

ELEV 4 FUSE BUS Pass480 6.28ELEV 4 FUSE 600 12.57 200.060 / 50

ELEV 5 FUSE BUS Pass480 6.28ELEV 5 FUSE 600 12.57 200.060 / 50

ELEV1 CB2 BUS Pass480 40.04ELEV1 CB2 480 7.21 18.0100

ELEV2 CB2 BUS Pass480 49.44ELEV2 CB2 480 8.90 18.0100

EMDP-P Pass480 3.7214E CB 480 2.42 65.0100

Pass480 3.724E CB 480 2.42 65.0100

Pass480 3.72EMCC-T6 CB 480 2.42 65.040

Pass480 3.72ROOF MOTOR CB 480 2.42 65.0125

FIRE PUMP CB1 BUS Pass480 6.97FIRE PUMP CB1 480 1.74 25.0125

FIRE PUMP CB2 BUS Pass480 5.45FIRE PUMP CB2 480 1.91 35.0600

FIRE PUMP CB3 BUS Pass480 6.67FIRE PUMP CB3 480 2.34 35.0175

GEN 1 BUS Pass480 8.28GEN SET CB 480 2.90 35.01,200 / 400

L1 FUSE BUS Pass120 5.39L1 200 A FUSE 250 10.78 200.0200

L1A FUSE BUS Pass120 5.16L1A 200 A FUSE 250 10.33 200.0200

MCC10 Pass480 77.29CHWP-4 CB 480 27.05 35.050

Pass480 13.53CWP-4 CB 480 27.05 200.0150

Pass480 77.29P18-3 CB 480 27.05 35.050

MCC12 Pass480 26.69CHWP-5 CB 480 9.34 35.030

MCC2 Pass480 4.88ASU 14R FUSE 600 9.76 200.030 / 25

Pass480 4.88ASU 14S FUSE 600 9.76 200.0100

Pass480 4.88ASU 15R FUSE 600 9.76 200.030 / 25

Pass480 4.88ASU 15S FUSE 600 9.76 200.0100

MCC-3 Pass480 16.612G1 JUNC FUSE 600 33.21 200.0200

2

Page 137: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Connected Bus StatusBus

Voltage

Calc

Int kADevNameInt

Rating %

Frame

Voltage

Calc

Mom kA

Mom

Rating %

Series

Rating

Dev

Int kA

Dev

Mom kAFrame/Trip

MCC-3 Pass480 16.612P-1 FUSE 600 33.21 200.0100

Fail480 205.264K PENTHOUSE C 480 36.95 18.0225

Pass480 16.61ELEV 4&5 FUSE 600 33.21 200.0100

Pass480 16.61P-19-1 FUSE 600 33.21 200.012

Pass480 16.61P-19-2 FUSE 600 33.21 200.012

Pass480 16.61PNL 4K PENTHOUS 600 33.21 200.0200

MCC4 Pass480 12.78ASU11 FUSE 600 25.55 200.060

Pass480 12.78ASU12 FUSE 600 25.55 200.060

Pass480 12.78ASU13 FUSE 600 25.55 200.060

Pass480 12.78CWP1 FUSE 600 25.55 200.030

P2D FUSE BUS Pass120 1.93P2D FUSE 250 3.86 200.0100

P4Y Fail480 130.50110 A WWP2 CB 480 32.62 25.0110

Fail480 130.50150 A WWP3 CB 480 32.62 25.0150

Fail480 130.50150 A WWP4 CB 480 32.62 25.0150

Marginal480 93.21200 A 4D2 CB 480 32.62 35.0200

Marginal480 93.21200 A H6A CB 480 32.62 35.0200

Marginal480 93.21200 A H7A CB 480 32.62 35.0200

Marginal480 93.2130 A ASU9A CB 480 32.62 35.030

Pass480 50.19400 A XFMR CB 480 32.62 65.0400

P4Z Fail480 127.62100 A 4F CB 480 44.67 35.0100

Fail480 178.67150 A 4GE CB 480 44.67 25.0150

Fail480 127.62200 A 4A CB 480 44.67 35.0200

Fail480 127.624C CB 480 44.67 35.0200

Fail480 178.674D CB 480 44.67 25.0150

Fail480 127.624DE CB 480 44.67 35.0200

3

Page 138: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Connected Bus StatusBus

Voltage

Calc

Int kADevNameInt

Rating %

Frame

Voltage

Calc

Mom kA

Mom

Rating %

Series

Rating

Dev

Int kA

Dev

Mom kAFrame/Trip

P4Z Fail480 127.624I CB 480 44.67 35.0400

Fail480 178.674K CB 1 480 44.67 25.0200

Fail480 127.624L CB 1 480 44.67 35.0200

Fail480 178.674M CB 1 480 44.67 25.0150

Fail480 127.62ELEV #50 DISC CB 480 44.67 35.090

Fail480 127.62MCC12 CB 480 44.67 35.0200

Fail480 178.67XFMR P2Z CB 480 44.67 25.0110

PNL 14E Pass480 9.39XFMR 12E CB 480 2.35 25.090

Pass480 9.39XFMR P1 CB 480 2.35 25.050

PNL 2A-2 Pass120 31.57PNL 2B CB 240 6.95 22.0100

PNL 2K-232 SEC1 Pass120 29.532K-232 CB2 240 2.95 10.0150

PNL 2UPSN-1 Pass120 42.27PNL 2UPSN-1 CB 240 4.23 10.0150

PNL 2UPSS-1 Pass120 16.84PNL 2UPSS-1 CB 480 5.90 35.0250

PNL 4A Fail480 205.95XFMR 2A CB 480 28.83 14.0150 / 125

PNL 4B Fail480 112.902B1 CB 480 15.81 14.020

Pass480 71.854B CB0 480 15.81 22.0200 / 175

PNL 4C-12 Fail480 203.172CA CB 240 20.32 10.020

PNL 4D Pass480 59.982D2 CB 480 14.99 25.070

Pass480 59.98XFMR 2D CB 480 14.99 25.060

PNL 4D1 Fail480 186.652D1 CB 480 26.13 14.060

PNL 4D2 Pass480 56.53150 A DHRC-1 CB 480 14.13 25.0150

Pass480 56.5320 A CWP1A CB 480 14.13 25.0125 / 20

Pass480 56.5320 A CWP1B CB 480 14.13 25.0125 / 20

Pass480 56.5325 A CHWP1A CB 480 14.13 25.0125 / 25

Pass480 56.5325 A CHWP1B CB 480 14.13 25.0125 / 25

4

Page 139: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Connected Bus StatusBus

Voltage

Calc

Int kADevNameInt

Rating %

Frame

Voltage

Calc

Mom kA

Mom

Rating %

Series

Rating

Dev

Int kA

Dev

Mom kAFrame/Trip

PNL 4DE Pass480 57.43DHRC2 CB 480 20.10 35.0150

Pass480 57.43DHRC3 CB 480 20.10 35.0150

PNL 4E Pass480 8.28XFMR 2E CB 480 2.07 25.030

PNL 4F Pass480 67.98XFMR 2F CB 480 9.52 14.0100 / 50

Pass480 67.98XFMR 2F1 CB 480 9.52 14.0100 / 50

PNL 4G Pass480 30.4460 A XFMR CB 480 10.65 35.060

PNL 4GE Pass480 39.65MCC2 CB 480 9.91 25.020

Pass480 39.65XFMR 2GE CB 480 9.91 25.020

PNL 4I Pass480 80.16CHILLER1 CB1 480 28.06 35.0250 / 225

Pass480 80.16MCC4 CB 480 28.06 35.0250 / 225

PNL 4J Marginal480 95.994F-13 CB 480 24.00 25.035

Fail480 171.41SF1A CB 480 24.00 14.0100 / 60

Fail480 171.41SF1B CB 480 24.00 14.0100 / 70

PNL 4J2 Fail480 236.5420 A XFMR 2J CB 480 33.12 14.020

Fail480 236.54XFMR 2J CB 480 33.12 14.020

PNL 4K PENTHOUSE Pass480 84.592K CB 480 21.15 25.040

Pass480 84.592K-232 XFMR CB 480 21.15 25.0100

Pass480 84.592L-1 CB 480 21.15 25.070

Pass480 60.42TOWER41 CB 480 21.15 35.050

Pass480 60.42TOWER42 CB 480 21.15 35.050

PNL 4M Pass480 52.99SF2A CB 480 13.25 25.0100

Pass480 37.85SF2B CB 480 13.25 35.0100

PNL EDP15 Pass120 81.46EDP-E CB 240 52.95 65.0800

PNL EDP-D Pass120 2.00PNL 1 CB 240 4.01 200.0200

Pass120 2.00PNL 2 CB 240 4.01 200.0200

5

Page 140: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Connected Bus StatusBus

Voltage

Calc

Int kADevNameInt

Rating %

Frame

Voltage

Calc

Mom kA

Mom

Rating %

Series

Rating

Dev

Int kA

Dev

Mom kAFrame/Trip

PNL EDP-D Pass120 2.00PNL 3 CB 240 4.01 200.0200

Pass120 2.00PNL 4 CB 240 4.01 200.0200

Pass120 2.00PNL 5 CB 240 4.01 200.0200

Pass120 2.00PNL 6 CB 240 4.01 200.0200

Pass120 2.00PNL 7 CB 240 4.01 200.0150

PNL EDP-D CB1 BUS Pass480 18.99PNL EDP-D CB1 480 3.42 18.060

PNL EDP-D CB2 BUS Pass120 7.44PNL EDP-D CB2 240 4.83 65.0250 / 200

PNL EDP-E Pass120 13.102D3 CB 240 26.21 200.0250 / 225

PNL KL Pass120 5.13KL FUSE 600 10.26 200.0400

PNL P2Z Pass120 9.06SONNY'S CB 240 5.89 65.0200

PNL P4A Fail480 179.274B CB 480 39.44 22.0200 / 175

Fail480 313.384G-104 CB 480 43.87 14.0150 / 125

Fail480 313.38XFMR 2GA CB 480 43.87 14.030

Fail480 313.38XFMR 2GB CB 480 43.87 14.070

PNL P4B Fail480 155.354C-12 CB 480 34.18 22.0200 / 175

Fail480 155.354CH CB 480 34.18 22.0200 / 175

PNL P4D Fail480 134.072C-12 CB 480 33.52 25.0110

Marginal480 95.774D1 CB 480 33.52 35.0100

Marginal480 95.77KL CB 480 33.52 35.0200

Pass480 51.57P2D CB 480 33.52 65.040

PNL P4X Pass480 79.50EF-11 CB 480 27.83 35.060

Pass480 79.50ELEV1 CB1 480 27.83 35.060

Pass480 79.50ELEV2 CB1 480 27.83 35.060

PNL SSD-A Pass480 1.88STS-A CB2 415 1.32 70.0630

Pass480 1.88STS-B CB2 415 1.32 70.0630

6

Page 141: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Connected Bus StatusBus

Voltage

Calc

Int kADevNameInt

Rating %

Frame

Voltage

Calc

Mom kA

Mom

Rating %

Series

Rating

Dev

Int kA

Dev

Mom kAFrame/Trip

PNL SSD-B Pass480 1.88STS-A CB1 415 1.32 70.0630

Pass480 1.88STS-B CB1 415 1.32 70.0630

PNL U Pass120 32.92PNL 2U-1 CB 240 3.29 10.0150

PNL U4A Pass480 3.75PDU2 CB 480 1.31 35.0200

Pass480 3.75PDU4 CB 480 1.31 35.0200

PNL U4B Pass480 3.75PDU1 CB 480 1.31 35.0200

Pass480 3.75PDU3 CB 480 1.31 35.0200

SF1A FUSE BUS Pass480 2.83SF1A FUSE 600 5.66 200.060

SF1B FUSE BUS Pass480 3.95SF1B FUSE 600 7.91 200.060

SF2A FUSE FEED BUS Pass480 2.06SF2A FUSE 600 4.11 200.060

SF2B FUSE FEED BUS Pass480 1.85SF2B FUSE 600 3.70 200.060

SFGA FUSE BUS Pass480 4.39SFGA FUSE 600 8.77 200.060

STS-A Pass480 1.88STS-A CB3 415 1.32 70.0630

Pass480 1.88STS-A CB4 415 1.32 70.0630

STS-B Pass480 1.88STS-B CB3 415 1.32 70.0630

Pass480 1.88STS-B CB4 415 1.32 70.0630

TOWER41 FUSE BUS Pass480 1.01TOWER41 FUSE 600 2.02 200.060

TOWER42 FUSE BUS Pass480 0.89TOWER42 FUSE 600 1.78 200.060

UPS A CB1 BUS Fail480 103.95UPS A CB1 480 36.38 35.060

UPS A CB3 BUS Pass480 3.76UPS A CB3 480 1.32 35.060

UPS B CB3 BUS Pass480 3.76UPS B CB3 480 1.32 35.060

UPS CB1 BUS Pass480 77.50UPS B CB1 480 27.13 35.060

USB-1 Pass480 51.57200 A EH3A CB 480 33.52 65.0800 / 200

Pass480 51.573200 A Main CB1 480 33.52 65.03,200

Pass480 51.57400 A H2A CB 480 33.52 65.0800 / 400

7

Page 142: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Connected Bus StatusBus

Voltage

Calc

Int kADevNameInt

Rating %

Frame

Voltage

Calc

Mom kA

Mom

Rating %

Series

Rating

Dev

Int kA

Dev

Mom kAFrame/Trip

USB-1 Pass480 51.57400 A H3A CB 480 33.52 65.0800 / 400

Pass480 51.57400 A H3B CB 480 33.52 65.0800 / 400

Pass480 51.57400 A H4A CB 480 33.52 65.0800 / 400

Pass480 51.57400 A H5A CB 480 33.52 65.0800 / 400

Pass480 51.57400 A HPA CB 480 33.52 65.0800 / 400

Pass480 51.57600 A USB-1 CB 480 33.52 65.0800 / 600

Pass480 51.57800 A EHRA CB 480 33.52 65.0800

Pass480 51.57800 A P4Y CB 480 33.52 65.0800

USB-2 Pass480 77.693200 A Main CB2 480 50.50 65.03,200

Pass480 77.69400 A 4G CB 480 50.50 65.0800 / 400

Pass480 77.69400 A 4J1 CB 480 50.50 65.0800 / 400

Pass480 77.69400 A ATS-1 CB 480 50.50 65.0800 / 400

Pass480 77.69600 A USB-2 CB 480 50.50 65.0800 / 600

Pass480 77.69800 A EDP15 CB 480 50.50 65.0800

Pass480 77.69800 A MCC10 CB 480 50.50 65.0800

Pass480 77.69800 A P4X CB 480 50.50 65.0800

Pass480 77.69800 A P4Z CB 480 50.50 65.0800

Pass480 77.69800 A WCU-4 CB 480 50.50 65.0800

Pass480 77.69800 A WCU-5 CB 480 50.50 65.0800

USB-5 Pass480 58.723200 A Main CB3 480 38.17 65.03,200

Pass480 58.72400 A P4D CB 480 38.17 65.0800 / 400

Pass480 58.724J CB 480 38.17 65.0800 / 400

Pass480 58.72800 A EB2 CB 480 38.17 65.0800

Pass480 58.72800 A MCC3 CB 480 38.17 65.0800

Pass480 58.72800 A P4A CB 480 38.17 65.0800

8

Page 143: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Connected Bus StatusBus

Voltage

Calc

Int kADevNameInt

Rating %

Frame

Voltage

Calc

Mom kA

Mom

Rating %

Series

Rating

Dev

Int kA

Dev

Mom kAFrame/Trip

USB-5 Pass480 58.72800 A P4B CB 480 38.17 65.0800

USDP-B Pass480 60.57PNL U XFMR CB 480 21.20 35.0400

Pass480 60.57XFMR 2UPSN-1 CB 480 21.20 35.0400

Pass480 60.57XFMR 2UPSS-1 CB 480 21.20 35.0400

WCU-4 SW BUS Pass480 48.04WCU-4 SW 480 31.23 65.0600 / 500

WCU-5 SW BUS Pass480 48.04WCU-5 SW 480 31.23 65.0600 / 500

9

Page 144: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

APPENDIX B

Page 145: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

S

P

Page 146: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

USB-1

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1

400 A H5A CB 400 A H4A CB 200 A EH3A CB 400 A H3A CB 400 A H2A CB 400 A H3B CB 400 A HPA CB 800 A EHRA CB 800 A P4Y CB

600 A USB-1 CB

P4Y FEED

P4Y

30 A ASU9A CB

ASU9A FEED

ASU9A-1 FEED ASU9A-2 FEED

ASU9A-1 ASU9A-2

400 A XFMR CB

150KVA XFMR FEED

S

P150KVA XFMR

L1A DISC FEED

L1A DISC SW

L1A 200 A FUSE

L1A FEED

PNL L1A

L1 DISC FEED

L1 DISC SW

L1 200 A FUSE

L1 FEED

PNL L1

150 A WWP4 CB

WWP4 FEED

WWP4

150 A WWP3 CB

WWP3 FEED

WWP3

110 A WWP2 CB

WWP2 FEED

WWP2

200 A H7A CB 200 A H6A CB200 A 4D2 CB

4D2 FEED

PNL 4D2

150 A DHRC-1 CB

DHRC-1 FEED

DHRC-1

20 A CWP1A CB

CWP1A FEED

CWP1A

20 A CWP1B CB

CWP1B FEED

CWP1B

25 A CHWP1A CB

CHWP1A FEED

CHWP1A

25 A CHWP1B CB

CHWP1B FEED

CHWP1B

USB-2

Open

3200 A TIE CB TIE FEED

USB-1 FEED

PNL USB-1

400 A 4G CB

4G FEED

PNL 4G

60 A XFMR CB

45KVA XFMR FEED

S

P45KVA XFMR

2G FEED

PNL 2G

4J1 FEED

PNL 4J1

S

P15KVA XFMR 2J

2J FEED

PNL 2J

400 A 4J1 CB

4J2 FEED

PNL 4J2

600 A USB-2 CB

USB-2 FEED

PNL USB-2

400 A ATS-1 CB

ATS-1 FEED

GEN-1

ATS-1 EM FEED

EMDP-P FEED

EMDP-P

ROOF MOTOR CB

ROOF MOTOR FEED

ROOF MOTOR 1 FEED

ROOF TOP MOTOR 1

ROOF MOTOR 2 FEED

ROOF TOP MOTOR 2

EMCC-T6 CB

EMCC-T6 FEED

PNL EMCC-T6

4E CB

4E FEED

XFMR 2E CB

XFMR 2E FEED

S

P

15KVA XFMR 2E

2E FEED

PNL 4E

PNL 2E

14E CB

14E FEED

XFMR 12E CB

XFMR 12E FEED

S

P

45KVA XFMR 12E

12E FEED

PNL 14E

PNL 12E

XFMR P1 CB

XFMR P1 FEED

S

P

30KVA XFMR P1

P1 FEED

PNL P1

800 A MCC10 CB

MCC10 FEED

MCC10

P18-3 CB

P18-3 FEED

P18-3

CHWP-4 CB

CHWP-4 FEED

CHWP-4

CWP-4 CB

CWP-4 FUSE FEED

CWP-4

CWP-4 60 A FUSE

CWP-4 FEED

800 A P4Z CB

P4Z FEED

P4Z

200 A 4A CB

4A FEED

PNL 4A

XFMR 2A CB

XFMR 2A FEED

S

P

75KVA XFMR 2A

2A-1 FEED

PNL 2A-1

2A-2 FEED

PNL 2A-2

2B FEED

PNL 2B

XFMR 2F1 FEED

S

P30KVA XFMR 2F1

2F1 FEED

PNL 2F1

PNL 4F

4F FEED

100 A 4F CB

GEN SET CB

XFMR 2F FEED

S

P 30KVA XFMR 2F

2F FEED

PNL 2F

XFMR 2GE FEED

S

P

30KVA XFMR 2GE

2GE FEED

PNL 2GE

PNL 4GE

4GE FEED

150 A 4GE CB

MCC2 FEED

XFMR 2GE CB MCC2 CB

MCC2

ASU 15S FUSE

ASU 15S FEED

ASU 15S

ASU 15R FUSE

ASU 15R FEED

ASU 15R

ASU 14R FUSE

ASU 14R FEED

ASU 14R

ASU 14S FUSE

ASU 14S FEED

ASU 14S

XFMR P2Z FEED

S

P

75KVA XFMR P2Z

P2Z FEED

XFMR P2Z CB

PNL P2Z

SONNYS FEED

SONNY'S

ELE#50 FUSE

ELE#50 FEED

ELE #50

ELEV #50 DISC CB

ELEV#50 DISC FEED

MCC12 CB

MCC12 FEED

MCC12

CWP5 FEED

CWP5

CHWP-5 FEED

CHWP-5 CB

CHWP-5

CWP5 FUSE

CWP5 FUSE FEED

4D CB

4D FEED

PNL 4D

2D2 CB

2D2 FEED

PNL 2D2

XFMR 2D FEED

S

P

45KVA XFMR 2D

2D FEED

XFMR 2D CB

PNL 2D

2D1 FEED

PNL 2D1

4DE CB

4DE FEED

PNL 4DE

DHRC2 CB DHRC3 CB

DHRC3 FEEDDHRC2 FEED

DHRC2 DHRC3

4M CB 1

4M FEED 1

4M CB 2

4M FEED 2

PNL 4M

SF2B CB SF2A CB

SF2B FEED

SF2B

SF2B FUSE

SF2B FUSE FEED

SF2A FEED

SF2A

SF2A FUSE

SF2A FUSE FEED

4K CB 1

4K FEED 1

4K CB 2

4K FEED 2

PNL 4K

4I CB

4I FEED

PNL 4I

CHILLER 1 FEED

CHILLER1 CB1

CHILLER1 CB2

CHILLER 1

MCC4 FEED

MCC4 CB

MCC4 ASU13 FUSE ASU13 FEED ASU13

ASU11 FUSE ASU11 FEED ASU11

ASU12 FUSE ASU12 FEED ASU12

CWP1 FUSE CWP1 FEED CWP1CWP1 FUSE2 CWP1 FEED2

PNL 4L

4L CB 1

4L FEED 1

4L CB 2

4L FEED 2

4C CB

4C FEED

PNL 4C

XFMR 2C2 FEED

S

P

30KVA XFMR 2C2

2C2 FEED

PNL 2C2

XFMR 2C FEED

S

P

45KVA XFMR 2C

2C FEED

PNL 2C

800 A EDP15 CB

EDP15 XFMR FEED

S

P1000KVA XFMR EDP15

EDP15 FEED

PNL EDP15

EDP-E CB

EDP-E FEED

PNL EDP-E

2D3 CB

2D3 FEED

PNL 2D3

800 A WCU-4 CB

WCU-4 SW FEED

WCU-4 SW

WCU-4

800 A WCU-5 CB

WCU-5 SW FEED

WCU-5 SW

WCU-5

800 A P4X CB

P4X FEED

PNL P4X

EF-11 CB

EF-11 FUSE FEED

EF-11 FEED

EF-11

EF-11 FUSE

ELEV1 CB1

ELEV1 CB FEED

ELEV1 CB2

ELEV1 XFMR FEED

S

P 27KVA XFMR ELEV1

ELEV1 FEED

ELEV1

WCU-4 FEED WCU-5 FEED

ELEV2 CB1

ELEV2 CB FEED

ELEV2 CB2

ELEV2 XFMR FEED

S

P 27KVA XFMR ELEV2

ELEV2 FEED

ELEV2

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

MBP-B FEED1

UPS B CB1

UPS-B

Open

UPS CB2

UPS B CB3

MBP-B FEED2

MBP-B FEED4

MBP-B FEED3

SSD-B FEED

PNL SSD-B

STS-B CB1

STS-B FEED1

STS-A CB1

STS-A FEED1

MBP-A FEED1

UPS A CB1

UPS-A

Open

UPS A CB2

UPS A CB3

MBP-A FEED2

MBP-A FEED4

MBP-A FEED3

SSD-A FEED

PNL SSD-A

STS-A CB2

STS-A FEED2

STS-B CB2

STS-B FEED2

STS-B

STS-B CB4STS-B CB3

U4B FEED

PNL U4B

PDU1 CB

PDU1 FEED

PDU1

PDU3 CB

PDU3 FEED

PDU3

STS-A

STS-A CB4STS-A CB3

U4A FEED

PNL U4A

PDU2 CB

PDU2 FEED

PDU2

PDU4 CB

PDU4 FEED

PDU4

SONNY'S CBXFMR 2F CBXFMR 2F1 CB

PNL 2B CB

XFMR 2J CB

XFMR 2J FEED

E N

ATS-1

Page 147: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

USB-5

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL

4J CB 800 A P4A CB

P4A FEED4J FEED

PNL 4J

SF1A CB

SF1A FUSE FEEDSF1A FUSESF1A FEEDSF1A

SF1B CB

SF1B FUSE FEEDSF1B FUSESF1B FEEDSF1B

4F-13 CB

SFGA FUSE FEED

SFGA

SFGA FUSE

SFGA FEED

PNL 4F-13

PNL 4F-13 FEED

PNL P4A

XFMR 2GA CB

XFMR 2GA FEED

S

P 45KVA XFMR 2GA

2GA FEED

PNL 2GA

PNL 2GA2

2GA2 FEED

XFMR 2GB CB

XFMR 2GB FEED

S

P 45KVA XFMR 2GB

2GB FEED

PNL 2GB

PNL 2GB2

2GB2 FEED

4G-104 CB

PNL 4G-104

PNL 4G-104 FEED

4B CB

PNL 4B

PNL 4B FEED

2B1 FEED

PNL 2B1

2B2 FEED

PNL 2B2

800 A P4B CB

P4B FEED

PNL P4B

4C-12 CB

PNL 4C-12

PNL 4C-12 FEED

XFMR 2CA FEED

S

P 50KVA XFMR 2CA

2CA FEED

PNL 2CA

2C1 FEED

PNL 2C1

2C2-12 FEED

PNL 2C2-12

4CH CB

PNL 4H

PNL 4H FEED

400 A P4D CB

P4D FEED

PNL P4D

P2D CB

XFMR P2D FEED

S

P

45KVA XFMR P2D

P2D FUSE FEED

P2D FUSE

P2D FEED

PNL P2D

4D1 CB

PNL 4D1

PNL 4D1 FEED

XFMR 2D1 FEED

S

P 45KVA XFMR 2D1

2D1-02 FEED

PNL 2D1-02

KL CB

XFMR KL FEED

S

P 112.5KVA XFMR KL

KL FUSE FEED

KL FUSE

2C-12 CB

XFMR 2C-12 FEED

S

P 75KVA XFMR 2C-12

2C-12 FEED

PNL 2C-12

2C3 FEED

PNL 2C3

800 A MCC3 CB

MCC3 FEED

MCC-3

P-19-1 FUSE

P-19-1

P-19-1 FEED

P-19-2 FUSE

P-19-2

P-19-2 FEED

2P-1 FUSE

2P-1 CB FEED

2P-1 CB

XFMR 2P-1 FEED

S

P75KVA XFMR 2P-1

2P-1 FEED

PNL 2P-1

2P-2 FEED

PNL 2P-2

ELEV 4&5 FUSE

ELEV 4&5 FEED

ELEV 4 FUSE FEED

ELEV 4

ELEV 5 FUSE FEED

ELEV 5

ELEV 4 FUSE ELEV 5 FUSE

ELEV 5 FEEDELEV 4 FEED

4K PENTHOUSE CB

PNL 4K PENTHOUSE FEED

PNL 4K PENTHOUSE FUSE

PNL 4K PENTHOUSE

2K CB

XFMR 2K FEED

S

P9KVA XFMR 2K

2K FEED

PNL 2K

2K1 FEED

PNL 2K1

TOWER41 FUSE

TOWER41

TOWER41 FEED

TOWER41 CB

TOWER41 FUSE FEED

TOWER42 FUSE

TOWER42

TOWER42 FEED

TOWER42 CB

TOWER42 FUSE FEED

2L-1 CB

XFMR 2L-1 FEED

S

P45KVA XFMR 2L-1

2L-1 FEED

PNL 2L-1

2L-2 FEED

PNL 2L-2

2L-3 FEED

PNL 2L-3

2K-232 XFMR CB

XFMR 2K-232 FEED

S

P45KVA XFMR 2K-232

2K-232 CB FEED

PNL 2K-232 SEC1

2K-232 SEC2 FEED

PNL 2K-232 SEC2

2K-232 CB1

2K-232 FEED

2K-232 CB2

2K-232 SEC3 FEED

PNL 2K-232 SEC3

2G1 JUNC FEED

2G1 JUNC FUSE

2H FUSE FEED

2H JUNC FUSE

2H JUNC FEED

2H-1 FUSE FEED

2H-1 FUSE

2H-1 XFMR FEED

S

P25KVA XFMR 2H-1

2H-1 FEED

PNL 2H-1

2H-2 FUSE1 FEED

2H-2 FUSE1

2H-2 XFMR FEED

S

P 25KVA XFMR 2H-2

2H-2 FUSE2 FEED

2H-2 FUSE2

2H-2 FEED

PNL 2H-2

2H FEED

PNL 2H

2H-3 FEED

PNL 2H-3

800 A EB2 CB

EB2 FEED

EB2

PNL KL

2B1 CB

XFMR 2B1 FEED

S

P75KVA XFMR 2B1

2CA CB 2D1 CB

Page 148: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

FIRE PUMP FEED1

FIRE PUMP

FIRE PUMP CB1

FIRE PUMP FEED2

FIRE PUMP CB2

FIRE PUMP FEED3

FIRE PUMP CB3

FIRE PUMP FEED4

S

P

FIRE PUMP XFMR

FIRE PUMP UTIL

PNL U XFMR CB

USDP-B

UPSDP-B UTIL

PNL U XFMR FEED

S

P45KVA XFMR U

PNL U FEED

PNL UPNL 2U-1 CB

PNL 2U-1 FEED

PNL 2U-1

PNL EDP-D CB1

PNL EDP-D XFMR FEED1S

P75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D CB2

PNL EDP-D FEED

PNL EDP-D

PNL EDP-D CB1 FEED

PNL 7 CB

PNL 7 FEED

PNL 7

PNL 6 CB

PNL 6 FEED

PNL 6

PNL 5 CB

PNL 5 FEED

PNL 5

PNL 4 CB

PNL 4 FEED

PNL 4

PNL 3 CB

PNL 3 FEED

PNL 3

PNL 2 CB

PNL 2 FEED

PNL 2

PNL 1 CB

PNL 1 FEED

PNL 1

XFMR 2UPSS-1 CB

XFMR 2UPSS-1 FEED

S

P75KVA XFMR 2UPSS-1

2UPSS-1 FEED

PNL 2UPSS-1

PNL 2UPSS-1 CB

2UPSS-2 FEED

PNL 2UPSS-2

2UPSS-3 FEED

PNL 2UPSS-3

2UPSS-4 FEED

PNL 2UPSS-4

XFMR 2UPSN-1 CB

XFMR 2UPSN-1 FEED

S

P45KVA XFMR 2UPSN-1

2UPSN-1 FEED

PNL 2UPSN-1

PNL 2UPSN-1 CB

2UPSN-2 FEED

PNL 2UPSN-2

Page 149: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

DAPPER Fault Analysis Input Report (English)

Utilities

Contribution

From Name

Bus

Name

In/Out

Service

Nominal

Voltage

-------- Contribution Data -------- PU (100 MVA Base)

X PUR PUX/RUnitsDuty

FIRE PUMP UTIL FIRE PUMP UTIL BUS 12,470 Amps 8.00In 9,999,999

SLG:

3P:

Amps 8.00 0.0000.000

Pos:

Zero:9,999,999

0.000 0.000

SWGR #1 SWGW 1 UTIL BUS 12,470 Amps 8.00In 9,999,999

SLG:

3P:

Amps 8.00 0.0000.000

Pos:

Zero:9,999,999

0.000 0.000

SWGR #2 SWGW 2 UTIL BUS 12,470 Amps 8.00In 9,999,999

SLG:

3P:

Amps 8.00 0.0000.000

Pos:

Zero:9,999,999

0.000 0.000

UPSDP-B UTIL USDP-B 480 Amps 8.00In 19,318

SLG:

3P:

Amps 8.00 6.1780.772

Pos:

Zero:19,318

0.772 6.178

UTIL UTIL BUS 12,470 Amps 8.00In 9,999,999

SLG:

3P:

Amps 8.00 0.0000.000

Pos:

Zero:9,999,999

0.000 0.000

Generators

Contribution

From Name

Bus

Name

In/Out

Service

Nominal

Voltage

-------- Contribution Data --------

Base kVA X" X/R

PU (100 MVA Base)

R PU X PU

GEN-1 480GEN 1 BUS 288.00 20.00 2.60 52.08In

2.60

52.082.60

0.15

0.15

0.15

20.00

20.00 52.08

Motors

Contribution

From Name

Bus

Name

In/Out

Service

Nominal

Voltage

--------- Contribution Data --------

Base kVA Xd" X/R

PU (100 MVA Base)

R PU X PU

# of

Motors

ASU 14R ASU 14R BUS 480 7.52 0.1692 10.00 224.926 2,249.354In1

ASU 14S ASU 14S BUS 480 40.11 0.1692 10.00 42.174 421.754In1

ASU 15R ASU 15R BUS 480 7.52 0.1692 10.00 224.926 2,249.354In1

1

Project: FAB

Page 150: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Contribution

From Name

Bus

Name

In/Out

Service

Nominal

Voltage

--------- Contribution Data --------

Base kVA Xd" X/R

PU (100 MVA Base)

R PU X PU

# of

Motors

ASU 15S ASU 15S BUS 480 40.11 0.1692 10.00 42.174 421.754In1

ASU11 ASU11 BUS 480 20.05 0.1692 10.00 84.347 843.508In1

ASU12 ASU12 BUS 480 20.05 0.1692 10.00 84.347 843.508In1

ASU13 ASU13 BUS 480 20.05 0.1692 10.00 84.347 843.508In1

ASU9A-1 ASU9A-1 BUS 480 3.01 0.1692 10.00 562.316 5,623.385In1

ASU9A-2 ASU9A-2 BUS 480 3.01 0.1692 10.00 562.316 5,623.385In1

CHILLER 1 CHILLER 1 BUS 480 193.52 0.1692 10.00 2.185 21.853In4

CHWP1A CHWP1A BUS 480 60.16 0.1692 10.00 28.116 281.169In1

CHWP1B CHWP1B BUS 480 10.03 0.1692 10.00 168.695 1,687.015In1

CHWP-4 CHWP-4 BUS 480 15.04 0.1692 10.00 112.463 1,124.677In1

CHWP-5 CHWP-5 BUS 480 15.04 0.1692 10.00 112.463 1,124.677In1

CWP1 CWP1 BUS 480 15.04 0.1692 10.00 112.463 1,124.677In1

CWP1A CWP1A BUS 480 7.52 0.1692 10.00 224.926 2,249.354In1

CWP1B CWP1B BUS 480 10.03 0.1692 10.00 168.695 1,687.015In1

CWP-4 CWP-4 BUS 480 40.11 0.1692 10.00 42.174 421.754In1

CWP5 CWP5 BUS 480 40.11 0.1692 10.00 42.174 421.754In1

DHRC-1 DHRC-1 BUS 480 25.07 0.1692 10.00 67.478 674.806In1

DHRC2 DHRC2 BUS 480 25.07 0.1692 10.00 67.478 674.806In1

DHRC3 DHRC3 BUS 480 25.07 0.1692 10.00 67.478 674.806In1

EB2 EB2 BUS 480 483.87 0.1692 10.00 3.496 34.959In1

EF-11 EF-11 BUS 480 15.04 0.1692 10.00 112.463 1,124.677In1

ELE #50 ELE#50 BUS 480 50.13 0.1692 10.00 33.739 337.403In1

ELEV 4 ELEV 4 BUS 480 30.08 0.1692 10.00 56.232 562.338In1

ELEV 5 ELEV 5 BUS 480 30.08 0.1692 10.00 56.232 562.338In1

ELEV1 ELEV1 BUS 480 25.07 0.1692 10.00 67.478 674.806In1

ELEV2 ELEV2 BUS 480 25.07 0.1692 10.00 67.478 674.806In1

FIRE PUMP FIRE PUMP BUS 480 60.16 0.1692 10.00 28.116 281.169In1

P18-3 P18-3 BUS 480 25.07 0.1692 10.00 67.478 674.806In1

P-19-1 P-19-1 BUS 480 5.01 0.1692 10.00 337.390 3,374.031In1

P-19-2 P-19-2 BUS 480 5.01 0.1692 10.00 337.390 3,374.031In1

ROOF TOP MOTOR 1 ROOF TOP MOTOR 1 BU 480 5.01 0.1382 10.00 275.647 2,756.583In1

ROOF TOP MOTOR 2 ROOF TOP MOTOR 2 BU 480 5.01 0.1382 10.00 275.647 2,756.583In1

SF1A SF1A BUS 480 25.07 0.1692 10.00 67.478 674.806In1

SF1B SF1B BUS 480 25.07 0.1692 10.00 67.478 674.806In1

SF2A SF2A BUS 480 20.05 0.1692 10.00 84.347 843.508In1

SF2B SF2B BUS 480 20.05 0.1692 10.00 84.347 843.508In1

SFGA SFGA BUS 480 25.07 0.1692 10.00 67.478 674.806In1

TOWER41 TOWER41 BUS 480 30.08 0.1692 10.00 56.232 562.338In1

TOWER42 TOWER42 BUS 480 30.08 0.1692 10.00 56.232 562.338In1

WCU-4 WCU-4 BUS 480 193.52 0.1692 10.00 2.185 21.853In4

WCU-5 WCU-5 BUS 480 193.52 0.1692 10.00 2.185 21.853In4

WWP2 WWP2 BUS 480 60.16 0.1692 10.00 28.116 281.169In1

2

Page 151: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Contribution

From Name

Bus

Name

In/Out

Service

Nominal

Voltage

--------- Contribution Data --------

Base kVA Xd" X/R

PU (100 MVA Base)

R PU X PU

# of

Motors

WWP3 WWP3 BUS 480 60.16 0.1692 10.00 28.116 281.169In1

WWP4 WWP4 BUS 480 60.16 0.1692 10.00 28.116 281.169In1

Cables

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

15KVA XFMR 12E S

PNL 12E

1 5 3/0 PVC Pos:

Zero:

2.6597 1.4410

3.6632

12E FEED In

4.2257

Non-MagneticCopper

EMDP-P

PNL 14E

1 18 1/0 PVC Pos:

Zero:

0.9922 0.3375

0.8586

14E FEED In

1.5773

Non-MagneticCopper

P4Y

150 KVA XFMR P

1 55 4/0 PVC Pos:

Zero:

1.5111 0.9501

2.4158

150KVA XFMR FEE In

2.4015

Non-MagneticCopper

75KVA XFMR 2A S

PNL 2A-1

1 8 4/0 PVC Pos:

Zero:

3.5167 2.2111

5.6222

2A-1 FEED In

5.5889

Non-MagneticCopper

PNL 2A-1

PNL 2A-2

1 6 4/0 PVC Pos:

Zero:

2.6375 1.3833

3.5167

2A-2 FEED In

4.1917

Non-MagneticCopper

PNL 2A-2

PNL 2B

1 50 8 PVC Pos:

Zero:

281.5972 20.9375

53.2639

2B FEED In

447.6736

Non-MagneticCopper

XFMR 2B1 SEC BU

PNL 2B1

1 30 4/0 PVC Pos:

Zero:

13.1875 8.2917

21.0833

2B1 FEED In

20.9583

Non-MagneticCopper

PNL 2B1

PNL 2B2

1 6 4/0 PVC Pos:

Zero:

2.6375 1.3833

3.5167

2B2 FEED In

4.1917

Non-MagneticCopper

30KVA XFMR 2C S

PNL 2C

1 6 1/0 PVC Pos:

Zero:

5.2917 1.8000

4.5792

2C FEED In

8.4125

Non-MagneticCopper

PNL 2CA

PNL 2C1

1 18 1/0 PVC Pos:

Zero:

15.8750 4.5000

11.4500

2C1 FEED In

25.2375

Non-MagneticCopper

XFMR 2C-12 SEC B

PNL 2C-12

1 20 2 PVC Pos:

Zero:

28.0556 5.4167

13.7778

2C-12 FEED In

44.5972

Non-MagneticCopper

30KVA XFMR 2C2 S

PNL 2C2

1 6 1 PVC Pos:

Zero:

6.6667 1.9000

4.8333

2C2 FEED In

10.5958

Non-MagneticCopper

PNL 2C1

PNL 2C2-12

1 4 1/0 PVC Pos:

Zero:

3.5278 1.0000

2.5444

2C2-12 FEED In

5.6083

Non-MagneticCopper

PNL 2C-12

PNL 2C3

1 4 2 PVC Pos:

Zero:

5.6111 1.0833

2.7556

2C3 FEED In

8.9194

Non-MagneticCopper

XFMR 2CA SEC B

PNL 2CA

1 6 1 PVC Pos:

Zero:

6.6667 1.5833

4.0292

2CA FEED In

10.5958

Non-MagneticCopper

45KVA XFMR 2D S

PNL 2D

2 7 1 PVC Pos:

Zero:

3.8889 1.1083

2.8194

2D FEED In

6.1809

Non-MagneticCopper

PNL 2D

PNL 2D1

2 130 6 PVC Pos:

Zero:

230.2083 24.7361

62.9236

2D1 FEED In

366.6632

Non-MagneticCopper

3

Page 152: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

XFMR 2D1 SEC BU

PNL 2D1-02

1 8 1 PVC Pos:

Zero:

8.8889 2.1111

5.3722

2D1-02 FEED In

14.1278

Non-MagneticCopper

PNL 4D

PNL 2D2

1 25 4 PVC Pos:

Zero:

3.4831 0.5490

1.3965

2D2 FEED In

5.3819

Non-MagneticCopper

PNL EDP-E

PNL 2D3

1 170 3/0 PVC Pos:

Zero:

90.4306 48.9931

124.5486

2D3 FEED In

143.6736

Non-MagneticCopper

15KVA XFMR 2E S

PNL 2E

1 5 6 PVC Pos:

Zero:

17.7083 1.9028

4.8403

2E FEED In

28.2049

Non-MagneticCopper

30KVA XFMR 2F S

PNL 2F

1 8 1 PVC Pos:

Zero:

8.8889 2.5333

6.4444

2F FEED In

14.1278

Non-MagneticCopper

30KVA XFMR 2F1 S

PNL 2F1

1 20 4 PVC Pos:

Zero:

44.5833 7.0278

17.8750

2F1 FEED In

68.8889

Non-MagneticCopper

45KVA XFMR SEC

PNL 2G

1 5 1/0 PVC Pos:

Zero:

4.4097 1.5000

3.8160

2G FEED In

7.0104

Non-MagneticCopper

MCC-3

2G1 JUNC

1 30 2 PVC Pos:

Zero:

2.6302 0.5833

1.4362

2G1 JUNC FEED In

8.2891

MagneticCopper

45KVA XFMR 2GA

PNL 2GA

1 10 2/0 PVC Pos:

Zero:

7.0139 2.9583

7.5208

2GA FEED In

11.1458

Non-MagneticCopper

PNL 2GA

PNL 2GA2

1 4 2/0 PVC Pos:

Zero:

2.8056 1.1833

3.0083

2GA2 FEED In

4.4583

Non-MagneticCopper

45KVA XFMR 2GB

PNL 2GB

1 10 2/0 PVC Pos:

Zero:

7.0139 2.9583

7.5208

2GB FEED In

11.1458

Non-MagneticCopper

PNL 2GB

PNL 2GB2

1 4 2/0 PVC Pos:

Zero:

2.8056 1.1833

3.0083

2GB2 FEED In

4.4583

Non-MagneticCopper

30KVA XFMR 2GE

PNL 2GE

1 5 10 PVC Pos:

Zero:

40.9722 2.8576

7.2674

2GE FEED In

65.1354

Non-MagneticCopper

PNL 2H-2

PNL 2H

1 60 2 PVC Pos:

Zero:

84.1667 16.2500

41.3333

2H FEED In

133.7917

Non-MagneticCopper

2G1 JUNC

2H FUSE BUS

1 6 2 PVC Pos:

Zero:

0.5260 0.1167

0.2872

2H FUSE FEED In

1.6578

MagneticCopper

2H FUSE BUS

2H JUNC

1 10 4 PVC Pos:

Zero:

1.3932 0.2743

0.6753

2H JUNC FEED In

4.3906

MagneticCopper

25KVA XFMR 2H-

PNL 2H-1

1 20 2 PVC Pos:

Zero:

28.0556 5.4167

13.7778

2H-1 FEED In

44.5972

Non-MagneticCopper

2H JUNC

2H-1 FUSE BUS

1 6 10 PVC Pos:

Zero:

3.0729 0.1896

0.4820

2H-1 FUSE FEED In

4.8852

Non-MagneticCopper

2H-1 FUSE BUS

25KVA XFMR 2H

1 8 10 PVC Pos:

Zero:

4.0972 0.2858

0.7267

2H-1 XFMR FEED In

6.5135

Non-MagneticCopper

2H-2 FUSE2 BUS

PNL 2H-2

1 10 2 PVC Pos:

Zero:

14.0278 2.7083

6.8889

2H-2 FEED In

22.2986

Non-MagneticCopper

2H JUNC

2H-2 FUSE BUS

1 6 10 PVC Pos:

Zero:

3.0729 0.1896

0.4820

2H-2 FUSE1 FEED In

4.8852

Non-MagneticCopper

4

Page 153: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

25KVA XFMR 2H-

2H-2 FUSE2 BUS

1 20 2 PVC Pos:

Zero:

28.0556 5.4167

13.7778

2H-2 FUSE2 FEED In

44.5972

Non-MagneticCopper

2H-2 FUSE BUS

25KVA XFMR 2H

1 8 10 PVC Pos:

Zero:

4.0972 0.2858

0.7267

2H-2 XFMR FEED In

6.5135

Non-MagneticCopper

PNL 2H-2

PNL 2H-3

1 4 2 PVC Pos:

Zero:

5.6111 1.0833

2.7556

2H-3 FEED In

8.9194

Non-MagneticCopper

15KVA XFMR 2J S

PNL 2J

1 6 8 PVC Pos:

Zero:

33.7917 2.5125

6.3917

2J FEED In

53.7208

Non-MagneticCopper

9KVA XFMR 2K S

PNL 2K

1 4 8 PVC Pos:

Zero:

22.5278 1.6750

4.2611

2K FEED In

35.8139

Non-MagneticCopper

PNL 2K

PNL 2K1

1 4 8 PVC Pos:

Zero:

22.5278 1.3972

3.5556

2K1 FEED In

35.8139

Non-MagneticCopper

45KVA XFMR 2K-

2K-232 CB1 BUS

1 7 1/0 PVC Pos:

Zero:

6.1736 2.1000

5.3424

2K-232 CB FEED In

9.8146

Non-MagneticCopper

2K-232 CB1 BUS

PNL 2K-232 SEC

1 30 1/0 PVC Pos:

Zero:

26.4583 9.0000

22.8958

2K-232 FEED In

42.0625

Non-MagneticCopper

PNL 2K-232 SEC1

PNL 2K-232 SEC

1 8 1/0 PVC Pos:

Zero:

7.0556 2.4000

6.1056

2K-232 SEC2 FEED In

11.2167

Non-MagneticCopper

PNL 2K-232 SEC2

PNL 2K-232 SEC

1 8 1/0 PVC Pos:

Zero:

7.0556 2.4000

6.1056

2K-232 SEC3 FEED In

11.2167

Non-MagneticCopper

45KVA XFMR 2L-1

PNL 2L-1

1 9 1/0 PVC Pos:

Zero:

7.9375 2.7000

6.8688

2L-1 FEED In

12.6188

Non-MagneticCopper

PNL 2L-1

PNL 2L-2

1 6 1/0 PVC Pos:

Zero:

5.2917 1.8000

4.5792

2L-2 FEED In

8.4125

Non-MagneticCopper

PNL 2L-2

PNL 2L-3

1 20 1/0 PVC Pos:

Zero:

17.6389 6.0000

15.2639

2L-3 FEED In

28.0417

Non-MagneticCopper

MCC-3

2P-1 BUS

1 80 1 PVC Pos:

Zero:

5.5556 1.5139

3.7257

2P-1 CB FEED In

17.5069

MagneticCopper

75KVA XFMR 2P-1

PNL 2P-1

1 10 4/0 PVC Pos:

Zero:

4.3958 2.7639

7.0278

2P-1 FEED In

6.9861

Non-MagneticCopper

PNL 2P-1

PNL 2P-2

1 6 2 PVC Pos:

Zero:

8.4167 1.6250

4.1333

2P-2 FEED In

13.3792

Non-MagneticCopper

75KVA XFMR 2UP

PNL 2UPSN-1

1 10 1/0 PVC Pos:

Zero:

8.8194 2.5000

6.3611

2UPSN-1 FEED In

14.0208

Non-MagneticCopper

PNL 2UPSN-1

PNL 2UPSN-2

1 4 1/0 PVC Pos:

Zero:

3.5278 1.0000

2.5444

2UPSN-2 FEED In

5.6083

Non-MagneticCopper

75KVA XFMR 2UP

PNL 2UPSS-1

1 10 250 PVC Pos:

Zero:

3.7569 2.2917

5.8264

2UPSS-1 FEED In

5.9722

Non-MagneticCopper

PNL 2UPSS-1

PNL 2UPSS-2

1 5 250 PVC Pos:

Zero:

1.8785 1.1458

2.9132

2UPSS-2 FEED In

2.9861

Non-MagneticCopper

PNL 2UPSS-2

PNL 2UPSS-3

1 5 250 PVC Pos:

Zero:

1.8785 1.1458

2.9132

2UPSS-3 FEED In

2.9861

Non-MagneticCopper

5

Page 154: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

PNL 2UPSS-3

PNL 2UPSS-4

1 5 250 PVC Pos:

Zero:

1.8785 1.1458

2.9132

2UPSS-4 FEED In

2.9861

Non-MagneticCopper

PNL 4G

45KVA XFMR PR

1 8 4 PVC Pos:

Zero:

1.1146 0.1757

0.4469

45KVA XFMR FEED In

1.7222

Non-MagneticCopper

P4Z

PNL 4A

1 50 3/0 PVC Pos:

Zero:

1.6623 0.9006

2.2895

4A FEED In

2.6411

Non-MagneticCopper

P4Z

PNL 4C

1 85 3/0 PVC Pos:

Zero:

2.8260 1.5310

3.8921

4C FEED In

4.4898

Non-MagneticCopper

P4Z

PNL 4D

1 130 2/0 PVC Pos:

Zero:

5.6988 2.4036

6.1107

4D FEED In

9.0560

Non-MagneticCopper

P4Y

PNL 4D2

1 130 2/0 PVC Pos:

Zero:

5.6988 2.4036

6.1107

4D2 FEED In

9.0560

Non-MagneticCopper

P4Z

PNL 4DE

1 130 250 PVC Pos:

Zero:

3.0525 2.2344

5.6819

4DE FEED In

4.8524

Non-MagneticCopper

EMDP-P

PNL 4E

1 100 1/0 PVC Pos:

Zero:

5.5122 1.8750

4.7700

4E FEED In

8.7630

Non-MagneticCopper

P4Z

PNL 4F

1 190 1/0 PVC Pos:

Zero:

10.4731 3.5625

9.0629

4F FEED In

16.6497

Non-MagneticCopper

USB-2

PNL 4G

1 295 4/0 PVC Pos:

Zero:

8.1048 5.0959

12.9575

4G FEED In

12.8806

Non-MagneticCopper

P4Z

PNL 4GE

1 190 1/0 PVC Pos:

Zero:

10.4731 3.5625

9.0629

4GE FEED In

16.6497

Non-MagneticCopper

P4Z

PNL 4I

1 100 500 PVC Pos:

Zero:

1.2760 2.0226

4.9783

4I FEED In

4.0191

MagneticCopper

USB-5

PNL 4J

1 85 350 PVC Pos:

Zero:

1.3576 1.4499

3.6855

4J FEED In

2.1582

Non-MagneticCopper

USB-2

PNL 4J1

1 55 350 PVC Pos:

Zero:

0.8785 0.9382

2.3848

4J1 FEED In

1.3965

Non-MagneticCopper

PNL 4J1

PNL 4J2

1 3 350 PVC Pos:

Zero:

0.0479 0.0512

0.1301

4J2 FEED In

0.0762

Non-MagneticCopper

P4Z

4K CB 2 BUS

1 280 3/0 PVC Pos:

Zero:

9.7830 4.8247

11.8854

4K FEED 1 In

30.8316

MagneticCopper

4K CB 2 BUS

PNL 4K

1 6 3/0 PVC Pos:

Zero:

0.1995 0.1081

0.2747

4K FEED 2 In

0.3169

Non-MagneticCopper

P4Z

4L CB 2 BUS

1 110 3/0 PVC Pos:

Zero:

3.6571 1.9813

5.0369

4L FEED 1 In

5.8103

Non-MagneticCopper

4L CB 2 BUS

PNL 4L

1 3 3/0 PVC Pos:

Zero:

0.0997 0.0540

0.1374

4L FEED 2 In

0.1585

Non-MagneticCopper

P4Z

4M CB 2 BUS

1 130 2/0 PVC Pos:

Zero:

7.1658 2.0313

5.1684

4M FEED 1 In

11.3919

Non-MagneticCopper

4M CB 2 BUS 1 4 2/0 PVC Pos: 0.1753 0.06164M FEED 2 In Non-MagneticCopper

6

Page 155: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

PNL 4M Zero: 0.15680.2786

MCC2

ASU 14R BUS

1 85 12 PVC Pos:

Zero:

68.9887 2.9108

7.4043

ASU 14R FEED In

109.6773

Non-MagneticCopper

MCC2

ASU 14S BUS

1 70 4 PVC Pos:

Zero:

9.7526 1.2821

3.2600

ASU 14S FEED In

15.0694

Non-MagneticCopper

MCC2

ASU 15R BUS

1 75 12 PVC Pos:

Zero:

60.8724 2.5684

6.5332

ASU 15R FEED In

96.7741

Non-MagneticCopper

MCC2

ASU 15S BUS

1 65 4 PVC Pos:

Zero:

9.0560 1.1905

3.0271

ASU 15S FEED In

13.9931

Non-MagneticCopper

MCC4

ASU11 BUS

1 115 8 PVC Pos:

Zero:

40.4796 2.5106

6.3889

ASU11 FEED In

64.3531

Non-MagneticCopper

MCC4

ASU12 BUS

1 115 8 PVC Pos:

Zero:

40.4796 2.5106

6.3889

ASU12 FEED In

64.3531

Non-MagneticCopper

MCC4

ASU13 BUS

1 80 8 PVC Pos:

Zero:

28.1597 1.7465

4.4444

ASU13 FEED In

44.7674

Non-MagneticCopper

P4Y

ASU9 BUS

1 55 12 PVC Pos:

Zero:

44.6398 2.1293

5.4165

ASU9A FEED In

70.9677

Non-MagneticCopper

ASU9 BUS

ASU9A-1 BUS

1 10 12 PVC Pos:

Zero:

8.1163 0.3872

0.9848

ASU9A-1 FEED In

12.9032

Non-MagneticCopper

ASU9 BUS

ASU9A-2 BUS

1 20 12 PVC Pos:

Zero:

16.2326 0.7743

1.9696

ASU9A-2 FEED In

25.8064

Non-MagneticCopper

ATS-1 EM BUS

GEN 1 BUS

1 275 500 PVC Pos:

Zero:

3.2943 4.4520

11.9238

ATS-1 EM FEED In

5.2279

Non-MagneticCopper

USB-2

ATS-1 NORMAL B

1 50 500 PVC Pos:

Zero:

0.5990 0.8095

2.1680

ATS-1 FEED In

0.9505

Non-MagneticCopper

PNL 4I

CHILLER 1 BUS

1 85 3/0 PVC Pos:

Zero:

2.8260 1.2765

3.2465

CHILLER 1 FEED In

4.4898

Non-MagneticCopper

PNL 4D2

CHWP1A BUS

1 65 10 PVC Pos:

Zero:

33.2899 2.3218

5.9047

CHWP1A FEED In

52.9225

Non-MagneticCopper

PNL 4D2

CHWP1B BUS

1 70 10 PVC Pos:

Zero:

35.8507 2.5004

6.3589

CHWP1B FEED In

56.9935

Non-MagneticCopper

MCC10

CHWP-4 BUS

1 20 6 PVC Pos:

Zero:

4.4271 0.3967

1.0095

CHWP-4 FEED In

7.0512

Non-MagneticCopper

MCC12

CHWP-5 BUS

1 50 10 PVC Pos:

Zero:

25.6076 1.5799

4.0169

CHWP-5 FEED In

40.7096

Non-MagneticCopper

MCC4

CWP1 FUSE 2 B

1 55 10 PVC Pos:

Zero:

28.1684 1.7378

4.4186

CWP1 FEED In

44.7806

Non-MagneticCopper

CWP1 FUSE 2 BUS

CWP1 BUS

1 30 10 PVC Pos:

Zero:

15.3646 0.9479

2.4102

CWP1 FEED2 In

24.4258

Non-MagneticCopper

PNL 4D2

CWP1A BUS

1 40 12 PVC Pos:

Zero:

32.4653 1.5486

3.9392

CWP1A FEED In

51.6128

Non-MagneticCopper

7

Page 156: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

PNL 4D2

CWP1B BUS

1 40 12 PVC Pos:

Zero:

32.4653 1.5486

3.9392

CWP1B FEED In

51.6128

Non-MagneticCopper

CWP-4 FUSE BUS

CWP-4 BUS

1 20 4 PVC Pos:

Zero:

2.7865 0.3663

0.9314

CWP-4 FEED In

4.3056

Non-MagneticCopper

MCC10

CWP-4 FUSE BU

1 20 6 PVC Pos:

Zero:

4.4271 0.3967

1.0095

CWP-4 FUSE FEED In

7.0512

Non-MagneticCopper

CWP5 FUSE BUS

CWP5 BUS

1 20 4 PVC Pos:

Zero:

2.7865 0.3663

0.9314

CWP5 FEED In

4.3056

Non-MagneticCopper

MCC12

CWP5 FUSE BUS

1 135 4 PVC Pos:

Zero:

18.8086 2.4727

6.2871

CWP5 FUSE FEED In

29.0625

Non-MagneticCopper

PNL 4D2

DHRC-1 BUS

1 20 1/0 PVC Pos:

Zero:

1.1024 0.3750

0.9540

DHRC-1 FEED In

1.7526

Non-MagneticCopper

PNL 4DE

DHRC2 BUS

1 20 1/0 PVC Pos:

Zero:

1.1024 0.3750

0.9540

DHRC2 FEED In

1.7526

Non-MagneticCopper

PNL 4DE

DHRC3 BUS

1 20 1/0 PVC Pos:

Zero:

1.1024 0.3750

0.9540

DHRC3 FEED In

1.7526

Non-MagneticCopper

USB-5

EB2 BUS

2 45 350 PVC Pos:

Zero:

0.3594 0.3203

0.8145

EB2 FEED In

0.5713

Non-MagneticCopper

1000KVA XFMR E

PNL EDP15

3 10 350 Pos:

Zero:

0.8519 0.9097

2.3125

EDP15 FEED In

1.3542

Non-MagneticCopper

USB-2

1000KVA XFMR E

4 150 350 PVC Pos:

Zero:

0.5990 0.5339

1.3574

EDP15 XFMR FEED In

0.9521

Non-MagneticCopper

PNL EDP15

PNL EDP-E

3 75 350 PVC Pos:

Zero:

6.3889 6.8229

17.3438

EDP-E FEED In

10.1563

Non-MagneticCopper

EF-11 FUSE BUS

EF-11 BUS

1 6 10 PVC Pos:

Zero:

3.0729 0.1896

0.4820

EF-11 FEED In

4.8852

Non-MagneticCopper

PNL P4X

EF-11 FUSE BUS

1 50 10 PVC Pos:

Zero:

25.6076 1.7860

4.5421

EF-11 FUSE FEED In

40.7096

Non-MagneticCopper

ELE#50 DISC BUS

ELE#50 BUS

1 25 2 PVC Pos:

Zero:

2.1918 0.4232

1.0764

ELE#50 FEED In

3.4842

Non-MagneticCopper

ELEV 4 FUSE BUS

ELEV 4 BUS

1 30 6 PVC Pos:

Zero:

6.6406 0.6836

1.6836

ELEV 4 FEED In

20.9271

MagneticCopper

ELEV 4&5 JUNCTI

ELEV 4 FUSE BU

1 6 6 PVC Pos:

Zero:

1.3281 0.1367

0.3367

ELEV 4 FUSE FEED In

4.1854

MagneticCopper

MCC-3

ELEV 4&5 JUNCT

1 30 6 PVC Pos:

Zero:

6.6406 0.6836

1.6836

ELEV 4&5 FEED In

20.9271

MagneticCopper

ELEV 5 FUSE BUS

ELEV 5 BUS

1 30 6 PVC Pos:

Zero:

6.6406 0.6836

1.6836

ELEV 5 FEED In

20.9271

MagneticCopper

ELEV 4&5 JUNCTI

ELEV 5 FUSE BU

1 6 6 PVC Pos:

Zero:

1.3281 0.1367

0.3367

ELEV 5 FUSE FEED In

4.1854

MagneticCopper

P4Z

ELE#50 DISC BU

1 50 2 PVC Pos:

Zero:

4.3837 0.8464

2.1528

ELEV#50 DISC FEE In

6.9683

Non-MagneticCopper

8

Page 157: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

PNL P4X

ELEV1 CB2 BUS

1 65 6 PVC Pos:

Zero:

14.3880 1.5460

3.9327

ELEV1 CB FEED In

22.9165

Non-MagneticCopper

27KVA XFMR ELE

ELEV1 BUS

1 25 8 Pos:

Zero:

8.7999 0.6543

1.6645

ELEV1 FEED In

13.9898

Non-MagneticCopper

ELEV1 CB2 BUS

27KVA XFMR EL

1 45 6 PVC Pos:

Zero:

9.9609 0.8926

2.2715

ELEV1 XFMR FEED In

15.8652

Non-MagneticCopper

PNL P4X

ELEV2 CB2 BUS

1 50 6 PVC Pos:

Zero:

11.0677 1.1892

3.0252

ELEV2 CB FEED In

17.6280

Non-MagneticCopper

27KVA XFMR ELE

ELEV2 BUS

1 30 8 Pos:

Zero:

10.5599 0.7852

1.9974

ELEV2 FEED In

16.7878

Non-MagneticCopper

ELEV2 CB2 BUS

27KVA XFMR EL

1 15 6 PVC Pos:

Zero:

3.3203 0.2975

0.7572

ELEV2 XFMR FEED In

5.2884

Non-MagneticCopper

EMDP-P

PNL EMCC-T6

1 300 8 PVC Pos:

Zero:

105.5990 7.8516

19.9740

EMCC-T6 FEED In

167.8776

Non-MagneticCopper

ATS-1 BUS

EMDP-P

1 50 500 PVC Pos:

Zero:

0.5990 0.8095

2.1680

EMDP-P FEED In

0.9505

Non-MagneticCopper

FIRE PUMP CB1 BU

FIRE PUMP BUS

1 15 2 XLPE Pos:

Zero:

1.3379 0.2591

0.7656

FIRE PUMP FEED1 In

3.7246

MagneticCopper

FIRE PUMP CB2 BU

FIRE PUMP CB1 B

1 115 2 XLPE Pos:

Zero:

10.2572 1.9865

5.8698

FIRE PUMP FEED2 In

28.5553

MagneticCopper

FIRE PUMP CB3 BU

FIRE PUMP CB2 B

1 250 2 XLPE Pos:

Zero:

22.2982 4.3186

12.7604

FIRE PUMP FEED3 In

62.0768

MagneticCopper

FIRE PUMP XFMR S

FIRE PUMP CB3 B

1 6 2 XLPE Pos:

Zero:

0.5352 0.1036

0.3063

FIRE PUMP FEED4 In

1.4898

MagneticCopper

112.5KVA XFMR K

PNL KL

1 12 400 PVC Pos:

Zero:

2.8500 2.7250

6.9333

KL FUSE FEED In

4.5250

Non-MagneticCopper

150 KVA XFMR SE

L1 FUSE BUS

1 12 3/0 PVC Pos:

Zero:

6.3833 3.4583

8.7917

L1 DISC FEED In

10.1417

Non-MagneticCopper

L1 FUSE BUS

PNL L1

1 65 3/0 PVC Pos:

Zero:

34.5764 18.7326

47.6215

L1 FEED In

54.9340

Non-MagneticCopper

150 KVA XFMR SE

L1A FUSE BUS

1 16 3/0 PVC Pos:

Zero:

8.5111 4.6111

11.7222

L1A DISC FEED In

13.5222

Non-MagneticCopper

L1A FUSE BUS

PNL L1A

1 65 3/0 PVC Pos:

Zero:

34.5764 18.7326

47.6215

L1A FEED In

54.9340

Non-MagneticCopper

PNL USB-2

UPS A CB1 BUS

2 50 500 PVC Pos:

Zero:

0.4915 0.3082

0.7845

MBP-A FEED1 In

0.7813

Non-MagneticAluminum

UPS A CB1 BUS

UPS A BUS1

2 6 500 PVC Pos:

Zero:

0.0590 0.0370

0.0941

MBP-A FEED2 In

0.0938

Non-MagneticAluminum

UPS A BUS1

UPS A BUS2

2 1 500 PVC Pos:

Zero:

0.0098 0.0062

0.0157

MBP-A FEED3 In

0.0156

Non-MagneticAluminum

UPS A BUS2

UPS A CB3 BUS

2 6 500 PVC Pos:

Zero:

0.0590 0.0370

0.0941

MBP-A FEED4 In

0.0938

Non-MagneticAluminum

9

Page 158: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

PNL USB-1

UPS CB1 BUS

2 50 500 PVC Pos:

Zero:

0.4915 0.3082

0.7845

MBP-B FEED1 In

0.7813

Non-MagneticAluminum

UPS CB1 BUS

UPS B BUS1

2 6 500 PVC Pos:

Zero:

0.0590 0.0370

0.0941

MBP-B FEED2 In

0.0938

Non-MagneticAluminum

UPS B BUS1

UPS B BUS2

2 1 500 PVC Pos:

Zero:

0.0098 0.0062

0.0157

MBP-B FEED3 In

0.0156

Non-MagneticAluminum

UPS B BUS2

UPS B CB3 BUS

2 6 500 PVC Pos:

Zero:

0.0590 0.0370

0.0941

MBP-B FEED4 In

0.0938

Non-MagneticAluminum

USB-2

MCC10

2 220 500 PVC Pos:

Zero:

1.3177 1.7808

4.7695

MCC10 FEED In

2.0911

Non-MagneticCopper

P4Z

MCC12

1 250 2/0 PVC Pos:

Zero:

10.9592 3.8520

9.7982

MCC12 FEED In

17.4154

Non-MagneticCopper

PNL 4GE

MCC2

1 10 350 PVC Pos:

Zero:

0.1597 0.1424

0.3620

MCC2 FEED In

0.2539

Non-MagneticCopper

USB-5

MCC-3

2 50 500 PVC Pos:

Zero:

0.2995 0.4047

1.0840

MCC3 FEED In

0.4753

Non-MagneticCopper

PNL 4I

MCC4

1 20 250 PVC Pos:

Zero:

0.4696 0.2865

0.7283

MCC4 FEED In

0.7465

Non-MagneticCopper

30KVA XFMR P1 S

PNL P1

1 6 2 PVC Pos:

Zero:

8.4167 1.9458

4.9500

P1 FEED In

13.3792

Non-MagneticCopper

MCC10

P18-3 BUS

1 42 6 PVC Pos:

Zero:

9.2969 0.8331

2.1201

P18-3 FEED In

14.8076

Non-MagneticCopper

MCC-3

P-19-1 BUS

1 110 12 PVC Pos:

Zero:

89.2795 3.3229

8.1832

P-19-1 FEED In

281.3690

MagneticCopper

MCC-3

P-19-2 BUS

1 110 12 PVC Pos:

Zero:

89.2795 3.3229

8.1832

P-19-2 FEED In

281.3690

MagneticCopper

P2D FUSE BUS

PNL P2D

1 25 1 PVC Pos:

Zero:

27.7778 7.5694

18.6285

P2D FEED In

87.5347

MagneticCopper

45KVA XFMR P2D

P2D FUSE BUS

1 8 1 PVC Pos:

Zero:

8.8889 2.1111

5.3722

P2D FUSE FEED In

14.1278

Non-MagneticCopper

75KVA XFMR P2Z S

PNL P2Z

2 6 4 PVC Pos:

Zero:

6.6875 0.8792

2.2354

P2Z FEED In

10.3333

Non-MagneticCopper

USB-5

PNL P4A

2 6 500 PVC Pos:

Zero:

0.0359 0.0486

0.1301

P4A FEED In

0.0570

Non-MagneticCopper

USB-5

PNL P4B

2 40 500 PVC Pos:

Zero:

0.2396 0.3238

0.8672

P4B FEED In

0.3802

Non-MagneticCopper

USB-5

PNL P4D

2 45 500 PVC Pos:

Zero:

0.2695 0.3643

0.9756

P4D FEED In

0.4277

Non-MagneticCopper

USB-2

PNL P4X

2 205 500 PVC Pos:

Zero:

1.2279 1.6594

4.4443

P4X FEED In

1.9486

Non-MagneticCopper

USB-1

P4Y

2 25 500 PVC Pos:

Zero:

0.1497 0.2024

0.5420

P4Y FEED In

0.2376

Non-MagneticCopper

10

Page 159: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

USB-2

P4Z

2 38 350 PVC Pos:

Zero:

0.3035 0.3241

0.8238

P4Z FEED In

0.4824

Non-MagneticCopper

PNL U4B

PDU1

2 90 2/0 PVC Pos:

Zero:

3.2617 0.6445

1.6406

PDU1 FEED In

5.1855

Non-MagneticAluminum

PNL U4A

PDU2

2 90 2/0 PVC Pos:

Zero:

3.2617 0.6445

1.6406

PDU2 FEED In

5.1855

Non-MagneticAluminum

PNL U4B

PDU3

2 160 2/0 PVC Pos:

Zero:

5.7986 1.1458

2.9167

PDU3 FEED In

9.2188

Non-MagneticAluminum

PNL U4A

PDU4

2 130 2/0 PVC Pos:

Zero:

4.7114 0.9310

2.3698

PDU4 FEED In

7.4902

Non-MagneticAluminum

PNL EDP-D

PNL 1

1 200 4/0 PVC Pos:

Zero:

87.9167 55.2778

140.5556

PNL 1 FEED In

139.7222

Non-MagneticCopper

PNL EDP-D

PNL 2

1 200 4/0 PVC Pos:

Zero:

87.9167 55.2778

140.5556

PNL 2 FEED In

139.7222

Non-MagneticCopper

PNL U

PNL 2U-1

1 65 1/0 PVC Pos:

Zero:

57.3264 19.5000

49.6076

PNL 2U-1 FEED In

91.1354

Non-MagneticCopper

PNL EDP-D

PNL 3

1 70 4/0 PVC Pos:

Zero:

30.7708 19.3472

49.1944

PNL 3 FEED In

48.9028

Non-MagneticCopper

PNL EDP-D

PNL 4

1 70 4/0 PVC Pos:

Zero:

30.7708 19.3472

49.1944

PNL 4 FEED In

48.9028

Non-MagneticCopper

PNL P4A

PNL 4B

1 120 3/0 PVC Pos:

Zero:

4.1927 2.7031

6.6563

PNL 4B FEED In

13.2135

MagneticCopper

PNL P4B

PNL 4C-12

1 65 2/0 PVC Pos:

Zero:

2.8776 1.1482

2.8268

PNL 4C-12 FEED In

9.0673

MagneticCopper

PNL P4D

PNL 4D1

1 25 1/0 PVC Pos:

Zero:

1.3889 0.4492

1.1057

PNL 4D1 FEED In

4.3772

MagneticCopper

PNL 4J

PNL 4F-13

1 40 350 PVC Pos:

Zero:

0.6563 0.6476

1.5938

PNL 4F-13 FEED In

2.0677

MagneticCopper

PNL P4A

PNL 4G-104

1 15 1/0 PVC Pos:

Zero:

0.8333 0.2695

0.6634

PNL 4G-104 FEED In

2.6263

MagneticCopper

PNL P4B

PNL 4H

1 30 1/0 PVC Pos:

Zero:

1.6667 0.5391

1.3268

PNL 4H FEED In

5.2526

MagneticCopper

MCC-3

PNL 4K PENTHOU

1 60 3/0 PVC Pos:

Zero:

2.0964 1.3516

3.3281

PNL 4K PENTHOUS In

6.6068

MagneticCopper

PNL EDP-D

PNL 5

1 10 4/0 PVC Pos:

Zero:

4.3958 2.7639

7.0278

PNL 5 FEED In

6.9861

Non-MagneticCopper

PNL EDP-D

PNL 6

1 12 4/0 PVC Pos:

Zero:

5.2750 3.3167

8.4333

PNL 6 FEED In

8.3833

Non-MagneticCopper

PNL EDP-D

PNL 7

1 25 4/0 PVC Pos:

Zero:

10.9896 6.9097

17.5694

PNL 7 FEED In

17.4653

Non-MagneticCopper

USDP-B 1 150 6 PVC Pos: 33.2031 2.9753PNL EDP-D CB1 FE In Non-MagneticCopper

11

Page 160: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

PNL EDP-D CB1 B Zero: 7.571652.8841

PNL EDP-D CB2 B

PNL EDP-D

1 40 350 PVC Pos:

Zero:

10.2222 10.9167

27.7500

PNL EDP-D FEED In

16.2500

Non-MagneticCopper

PNL EDP-D CB1 B

75KVA EDP-D XF

1 15 6 PVC Pos:

Zero:

3.3203 0.2975

0.7572

PNL EDP-D XFMR F In

5.2884

Non-MagneticCopper

75KVA EDP-D XFM

PNL EDP-D CB2 B

1 12 4/0 PVC Pos:

Zero:

5.2750 3.3167

8.4333

PNL EDP-D XFMR F In

8.3833

Non-MagneticCopper

45KVA XFMR U S

PNL U

1 8 1/0 PVC Pos:

Zero:

7.0556 2.0000

5.0889

PNL U FEED In

11.2167

Non-MagneticCopper

USDP-B

45KVA XFMR U P

1 25 10 PVC Pos:

Zero:

12.8038 0.8930

2.2711

PNL U XFMR FEED In

20.3548

Non-MagneticCopper

ROOF J-BOX BUS

ROOF TOP MOT

1 5 1/0 PVC Pos:

Zero:

0.2756 0.0781

0.1988

ROOF MOTOR 1 FE In

0.4382

Non-MagneticCopper

ROOF J-BOX BUS

ROOF TOP MOT

1 10 1/0 PVC Pos:

Zero:

0.5512 0.1563

0.3976

ROOF MOTOR 2 FE In

0.8763

Non-MagneticCopper

EMDP-P

ROOF J-BOX BU

1 300 1/0 PVC Pos:

Zero:

16.5365 4.6875

11.9271

ROOF MOTOR FEE In

26.2891

Non-MagneticCopper

SF1A FUSE BUS

SF1A BUS

1 6 8 PVC Pos:

Zero:

2.1120 0.1310

0.3333

SF1A FEED In

3.3576

Non-MagneticCopper

PNL 4J

SF1A FUSE BUS

1 54 8 PVC Pos:

Zero:

19.0078 1.1789

3.0000

SF1A FUSE FEED In

30.2180

Non-MagneticCopper

SF1B FUSE BUS

SF1B BUS

1 6 8 PVC Pos:

Zero:

2.1120 0.1310

0.3333

SF1B FEED In

3.3576

Non-MagneticCopper

PNL 4J

SF1B FUSE BUS

1 36 8 PVC Pos:

Zero:

12.6719 0.7859

2.0000

SF1B FUSE FEED In

20.1453

Non-MagneticCopper

SF2A FUSE FEED B

SF2A BUS

1 4 6 PVC Pos:

Zero:

0.8854 0.0793

0.2019

SF2A FEED In

1.4102

Non-MagneticCopper

PNL 4M

SF2A FUSE FEE

1 95 6 PVC Pos:

Zero:

21.0286 1.8843

4.7954

SF2A FUSE FEED In

33.4933

Non-MagneticCopper

SF2B FUSE FEED B

SF2B BUS

1 4 6 PVC Pos:

Zero:

0.8854 0.0793

0.2019

SF2B FEED In

1.4102

Non-MagneticCopper

PNL 4M

SF2B FUSE FEE

1 110 6 PVC Pos:

Zero:

24.3490 2.1819

5.5525

SF2B FUSE FEED In

38.7817

Non-MagneticCopper

SFGA FUSE BUS

SFGA BUS

1 6 6 PVC Pos:

Zero:

1.3281 0.1367

0.3367

SFGA FEED In

4.1854

MagneticCopper

PNL 4F-13

SFGA FUSE BUS

1 45 6 PVC Pos:

Zero:

9.9609 1.0254

2.5254

SFGA FUSE FEED In

31.3906

MagneticCopper

PNL P2Z

SONNY'S

1 35 1 PVC Pos:

Zero:

38.8889 11.0833

28.1944

SONNYS FEED In

61.8090

Non-MagneticCopper

UPS A CB3 BUS

PNL SSD-A

2 8 500 PVC Pos:

Zero:

0.0786 0.0493

0.1255

SSD-A FEED In

0.1250

Non-MagneticAluminum

12

Page 161: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

UPS B CB3 BUS

PNL SSD-B

2 8 500 PVC Pos:

Zero:

0.0786 0.0493

0.1255

SSD-B FEED In

0.1250

Non-MagneticAluminum

PNL SSD-B

STS-A

2 15 500 PVC Pos:

Zero:

0.1475 0.0924

0.2354

STS-A FEED1 In

0.2344

Non-MagneticAluminum

PNL SSD-A

STS-A

2 15 500 PVC Pos:

Zero:

0.1475 0.0924

0.2354

STS-A FEED2 In

0.2344

Non-MagneticAluminum

PNL SSD-B

STS-B

2 15 500 PVC Pos:

Zero:

0.1475 0.0924

0.2354

STS-B FEED1 In

0.2344

Non-MagneticAluminum

PNL SSD-A

STS-B

2 15 500 PVC Pos:

Zero:

0.1475 0.0924

0.2354

STS-B FEED2 In

0.2344

Non-MagneticAluminum

USB-1

USB-2

1 1 4000 **** Pos:

Zero:

0.0014 0.0008

0.0044

TIE FEED In

0.0085

BusCopper

TOWER41 FUSE B

TOWER41 BUS

1 20 8 PVC Pos:

Zero:

7.0399 0.4366

1.1111

TOWER41 FEED In

11.1918

Non-MagneticCopper

PNL 4K PENTHOUS

TOWER41 FUSE B

1 165 8 PVC Pos:

Zero:

58.0794 3.6022

9.1667

TOWER41 FUSE FE In

92.3327

Non-MagneticCopper

TOWER42 FUSE B

TOWER42 BUS

1 20 8 PVC Pos:

Zero:

7.0399 0.4366

1.1111

TOWER42 FEED In

11.1918

Non-MagneticCopper

PNL 4K PENTHOUS

TOWER42 FUSE B

1 190 8 PVC Pos:

Zero:

66.8793 4.1480

10.5556

TOWER42 FUSE FE In

106.3225

Non-MagneticCopper

STS-A

PNL U4A

2 15 500 PVC Pos:

Zero:

0.1475 0.0924

0.2354

U4A FEED In

0.2344

Non-MagneticAluminum

STS-B

PNL U4B

2 15 500 PVC Pos:

Zero:

0.1475 0.0924

0.2354

U4B FEED In

0.2344

Non-MagneticAluminum

USB-1

PNL USB-1

2 50 500 PVC Pos:

Zero:

0.4915 0.3082

0.7845

USB-1 FEED In

0.7813

Non-MagneticAluminum

USB-2

PNL USB-2

2 50 500 PVC Pos:

Zero:

0.4915 0.3082

0.7845

USB-2 FEED In

0.7813

Non-MagneticAluminum

WCU-4 SW BUS

WCU-4 BUS

2 45 500 PVC Pos:

Zero:

0.2695 0.3643

0.9756

WCU-4 FEED In

0.4277

Non-MagneticCopper

USB-2

WCU-4 SW BUS

2 205 500 PVC Pos:

Zero:

1.2279 1.6594

4.4443

WCU-4 SW FEED In

1.9486

Non-MagneticCopper

WCU-5 SW BUS

WCU-5 BUS

2 45 500 PVC Pos:

Zero:

0.2695 0.3643

0.9756

WCU-5 FEED In

0.4277

Non-MagneticCopper

USB-2

WCU-5 SW BUS

2 205 500 PVC Pos:

Zero:

1.2279 1.6594

4.4443

WCU-5 SW FEED In

1.9486

Non-MagneticCopper

P4Y

WWP2 BUS

1 40 2 PVC Pos:

Zero:

3.5069 0.8108

2.0625

WWP2 FEED In

5.5747

Non-MagneticCopper

P4Y

WWP3 BUS

1 80 2 PVC Pos:

Zero:

7.0139 1.6215

4.1250

WWP3 FEED In

11.1493

Non-MagneticCopper

P4Y

WWP4 BUS

1 95 2 PVC Pos:

Zero:

8.3290 1.9256

4.8984

WWP4 FEED In

13.2398

Non-MagneticCopper

13

Page 162: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

PNL 14E

15KVA XFMR 12

1 5 2 PVC Pos:

Zero:

0.4384 0.1013

0.2578

XFMR 12E FEED In

0.6968

Non-MagneticCopper

PNL 4A

75KVA XFMR 2

1 8 1/0 PVC Pos:

Zero:

0.4410 0.1500

0.3816

XFMR 2A FEED In

0.7010

Non-MagneticCopper

PNL 4B

XFMR 2B1 PRI B

1 20 1 PVC Pos:

Zero:

1.3889 0.3299

0.8394

XFMR 2B1 FEED In

2.2075

Non-MagneticCopper

PNL 4C

30KVA XFMR 2C

1 6 4 PVC Pos:

Zero:

0.8359 0.1099

0.2794

XFMR 2C FEED In

1.2917

Non-MagneticCopper

PNL P4D

XFMR 2C-12 PRI B

1 135 1/0 PVC Pos:

Zero:

7.5000 2.4258

5.9707

XFMR 2C-12 FEED In

23.6367

MagneticCopper

PNL 4C

30KVA XFMR 2C

1 10 6 PVC Pos:

Zero:

2.2135 0.1984

0.5048

XFMR 2C2 FEED In

3.5256

Non-MagneticCopper

PNL 4C-12

XFMR 2CA PRI B

1 8 2 PVC Pos:

Zero:

0.7014 0.1354

0.3444

XFMR 2CA FEED In

1.1149

Non-MagneticCopper

PNL 4D

45KVA XFMR 2

1 8 4 PVC Pos:

Zero:

1.1146 0.1465

0.3726

XFMR 2D FEED In

1.7222

Non-MagneticCopper

PNL 4D1

XFMR 2D1 PRI B

1 8 6 PVC Pos:

Zero:

1.7708 0.1587

0.4038

XFMR 2D1 FEED In

2.8205

Non-MagneticCopper

PNL 4E

15KVA XFMR 2E

1 8 10 PVC Pos:

Zero:

4.0972 0.2858

0.7267

XFMR 2E FEED In

6.5135

Non-MagneticCopper

PNL 4F

30KVA XFMR 2F

1 8 8 PVC Pos:

Zero:

2.8160 0.2094

0.5326

XFMR 2F FEED In

4.4767

Non-MagneticCopper

PNL 4F

30KVA XFMR 2F

1 135 8 PVC Pos:

Zero:

47.5195 3.5332

8.9883

XFMR 2F1 FEED In

75.5449

Non-MagneticCopper

PNL P4A

45KVA XFMR 2G

1 8 4 PVC Pos:

Zero:

1.1146 0.1757

0.4469

XFMR 2GA FEED In

1.7222

Non-MagneticCopper

PNL P4A

45KVA XFMR 2G

1 8 4 PVC Pos:

Zero:

1.1146 0.1757

0.4469

XFMR 2GB FEED In

1.7222

Non-MagneticCopper

PNL 4GE

30KVA XFMR 2G

1 5 12 PVC Pos:

Zero:

4.0582 0.1936

0.4924

XFMR 2GE FEED In

6.4516

Non-MagneticCopper

PNL 4J2

15KVA XFMR 2J P

1 6 10 PVC Pos:

Zero:

3.0729 0.1896

0.4820

XFMR 2J FEED In

4.8852

Non-MagneticCopper

PNL 4K PENTHOUS

9KVA XFMR 2K P

1 6 8 PVC Pos:

Zero:

2.1120 0.1570

0.3995

XFMR 2K FEED In

3.3576

Non-MagneticCopper

PNL 4K PENTHOUS

45KVA XFMR 2K

1 25 4 PVC Pos:

Zero:

3.4831 0.5490

1.3965

XFMR 2K-232 FEED In

5.3819

Non-MagneticCopper

PNL 4K PENTHOUS

45KVA XFMR 2L

1 30 4 PVC Pos:

Zero:

4.1797 0.6589

1.6758

XFMR 2L-1 FEED In

6.4583

Non-MagneticCopper

2P-1 BUS

75KVA XFMR 2P

1 6 1 PVC Pos:

Zero:

0.4167 0.1188

0.3021

XFMR 2P-1 FEED In

0.6622

Non-MagneticCopper

USDP-B

45KVA XFMR 2U

1 410 1/0 PVC Pos:

Zero:

22.5998 7.6875

19.5569

XFMR 2UPSN-1 FE In

35.9284

Non-MagneticCopper

14

Page 163: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

USDP-B

75KVA XFMR 2U

1 310 1/0 PVC Pos:

Zero:

17.0877 4.8438

12.3247

XFMR 2UPSS-1 FEE In

27.1654

Non-MagneticCopper

PNL P4D

112.5KVA XFMR

1 125 4/0 PVC Pos:

Zero:

3.4342 2.1593

5.4905

XFMR KL FEED In

5.4579

Non-MagneticCopper

PNL 14E

30KVA XFMR P1

1 320 4 PVC Pos:

Zero:

44.5833 7.0278

17.8750

XFMR P1 FEED In

68.8889

Non-MagneticCopper

PNL P4D

45KVA XFMR P2

1 20 6 PVC Pos:

Zero:

4.4271 0.4757

1.2101

XFMR P2D FEED In

7.0512

Non-MagneticCopper

P4Z

75KVA XFMR P2

1 55 2 PVC Pos:

Zero:

4.8220 0.9310

2.3681

XFMR P2Z FEED In

7.6651

Non-MagneticCopper

2-Winding Transformers

Xformer

Name Bus Conn. Volts FLA

Nominal

kVA

Z PU (100 MVA Base)

R pu jX pu

In/Out

Service

------------------Primary & Secondary---------------

1000KVA XFMR EDP15 1000KVA XFMR EDP1 D 480 1,203

1000KVA XFMR EDP1WG 120 4,811

1,000.0 Pos:

Zero:

0.5473

0.5473

5.4727

5.4727

In

112.5KVA XFMR KL 112.5KVA XFMR KL P D 480 135

112.5KVA XFMR KL SWG 120 541

112.5 Pos:

Zero:

10.7280

10.7280

35.7591

35.7591

In

1500KVA XFMR1 SWGW 1 UTIL BUS D 12,470 69

USB-1 WG 480 1,804

1,500.0 Pos:

Zero:

0.5780

0.5780

3.7800

3.7800

In

1500KVA XFMR2 SWGW 2 UTIL BUS D 12,470 69

USB-2 WG 480 1,804

1,500.0 Pos:

Zero:

0.3808

0.3808

3.8077

3.8077

In

1500KVA XFMR3 UTIL BUS D 12,470 69

USB-5 WG 480 1,804

1,500.0 Pos:

Zero:

0.3847

0.3847

3.8475

3.8475

In

150KVA XFMR 150 KVA XFMR PRI B D 480 180

150 KVA XFMR SEC BWG 120 722

150.0 Pos:

Zero:

9.7700

9.7700

32.5660

32.5660

In

15KVA XFMR 2E 15KVA XFMR 2E PRI B D 480 18

15KVA XFMR 2E SEC BWG 120 72

15.0 Pos:

Zero:

124.9400

124.9400

156.1733

156.1733

In

15KVA XFMR 2J 15KVA XFMR 2J PRI B D 480 18

15KVA XFMR 2J SEC BWG 120 72

15.0 Pos:

Zero:

124.9400

124.9400

156.1733

156.1733

In

25KVA XFMR 2H-1 25KVA XFMR 2H-1 PR D 480 30

25KVA XFMR 2H-1 SEWG 120 120

25.0 Pos:

Zero:

55.7240

55.7240

69.6520

69.6520

In

25KVA XFMR 2H-2 25KVA XFMR 2H-2 PR D 480 30

25KVA XFMR 2H-2 SEWG 120 120

25.0 Pos:

Zero:

55.7240

55.7240

69.6520

69.6520

In

27KVA XFMR ELEV1 27KVA XFMR ELEV1 P D 480 32

27KVA XFMR ELEV1 SWG 480 32

27.0 Pos:

Zero:

108.7444

108.7444

135.9296

135.9296

In

27KVA XFMR ELEV2 27KVA XFMR ELEV2 P D 480 32

27KVA XFMR ELEV2 SWG 480 32

27.0 Pos:

Zero:

108.7444

108.7444

135.9296

135.9296

In

15

Page 164: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Xformer

Name Bus Conn. Volts FLA

Nominal

kVA

Z PU (100 MVA Base)

R pu jX pu

In/Out

Service

------------------Primary & Secondary---------------

30KVA XFMR 2C2 30KVA XFMR 2C2 PR D 480 36

30KVA XFMR 2C2 SE WG 120 144

30.0 Pos:

Zero:

137.4333

137.4333

171.7900

171.7900

In

30KVA XFMR 2F 30KVA XFMR 2F PRI B D 480 36

30KVA XFMR 2F SEC BWG 120 144

30.0 Pos:

Zero:

66.6333

66.6333

83.2933

83.2933

In

30KVA XFMR 2F1 30KVA XFMR 2F1 PRI D 480 36

30KVA XFMR 2F1 SE WG 120 144

30.0 Pos:

Zero:

102.4500

102.4500

128.0633

128.0633

In

30KVA XFMR 2GE 30KVA XFMR 2GE PR D 480 36

30KVA XFMR 2GE SEWG 120 144

30.0 Pos:

Zero:

61.6367

61.6367

77.0467

77.0467

In

30KVA XFMR P1 30KVA XFMR P1 PRI B D 480 36

30KVA XFMR P1 SEC BWG 120 144

30.0 Pos:

Zero:

106.1967

106.1967

132.7467

132.7467

In

45KVA XFMR 45KVA XFMR PRI BU D 480 54

45KVA XFMR SEC BUWG 120 217

45.0 Pos:

Zero:

55.5289

55.5289

69.4111

69.4111

In

45KVA XFMR 12E 15KVA XFMR 12E PRI D 480 54

15KVA XFMR 12E SE WG 120 217

45.0 Pos:

Zero:

55.5289

55.5289

69.4111

69.4111

In

45KVA XFMR 2C 30KVA XFMR 2C PRI B D 480 54

30KVA XFMR 2C SECWG 120 217

45.0 Pos:

Zero:

55.5289

55.5289

69.4111

69.4111

In

45KVA XFMR 2D 45KVA XFMR 2D PRI B D 480 54

45KVA XFMR 2D SECWG 120 217

45.0 Pos:

Zero:

55.5289

55.5289

69.4111

69.4111

In

45KVA XFMR 2D1 XFMR 2D1 PRI BUS D 480 54

XFMR 2D1 SEC BUS WG 120 217

45.0 Pos:

Zero:

62.4689

62.4689

78.0867

78.0867

In

45KVA XFMR 2GA 45KVA XFMR 2GA PR D 480 54

45KVA XFMR 2GA SEWG 120 217

45.0 Pos:

Zero:

44.4222

44.4222

55.5289

55.5289

In

45KVA XFMR 2GB 45KVA XFMR 2GB PR D 480 54

45KVA XFMR 2GB SEWG 120 217

45.0 Pos:

Zero:

44.4222

44.4222

55.5289

55.5289

In

45KVA XFMR 2K-232 45KVA XFMR 2K-232 P D 480 54

45KVA XFMR 2K-232 SWG 120 217

45.0 Pos:

Zero:

77.7400

77.7400

97.1756

97.1756

In

45KVA XFMR 2L-1 45KVA XFMR 2L-1 PR D 480 54

45KVA XFMR 2L-1 SEWG 120 217

45.0 Pos:

Zero:

73.5756

73.5756

91.9689

91.9689

In

45KVA XFMR 2UPSN-1 45KVA XFMR 2UPSN- D 480 54

75KVA XFMR 2UPSN-WG 120 217

45.0 Pos:

Zero:

54.1400

54.1400

67.6756

67.6756

In

45KVA XFMR P2D 45KVA XFMR P2D PR D 480 54

45KVA XFMR P2D SE WG 120 217

45.0 Pos:

Zero:

69.4111

69.4111

86.7622

86.7622

In

45KVA XFMR U 45KVA XFMR U PRI B D 480 54

45KVA XFMR U SEC BWG 120 217

45.0 Pos:

Zero:

80.5156

80.5156

100.6444

100.6444

In

50KVA XFMR 2CA XFMR 2CA PRI BUS D 480 60

XFMR 2CA SEC BUS WG 120 241

50.0 Pos:

Zero:

34.9820

34.9820

43.7280

43.7280

In

75KVA EDP-D XFMR 75KVA EDP-D XFMR P D 480 90

75KVA EDP-D XFMR SWG 120 361

75.0 Pos:

Zero:

32.5573

32.5573

65.1147

65.1147

In

75KVA XFMR 2A 75KVA XFMR 2A PRI B D 480 90

75KVA XFMR 2A SECWG 120 361

75.0 Pos:

Zero:

26.2360

26.2360

52.4733

52.4733

In

16

Page 165: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Xformer

Name Bus Conn. Volts FLA

Nominal

kVA

Z PU (100 MVA Base)

R pu jX pu

In/Out

Service

------------------Primary & Secondary---------------

75KVA XFMR 2B1 XFMR 2B1 PRI BUS D 480 90

XFMR 2B1 SEC BUS WG 120 361

75.0 Pos:

Zero:

31.0067

31.0067

62.0133

62.0133

In

75KVA XFMR 2C-12 XFMR 2C-12 PRI BUS D 480 90

XFMR 2C-12 SEC BUSWG 120 361

75.0 Pos:

Zero:

31.0067

31.0067

62.0133

62.0133

In

75KVA XFMR 2P-1 75KVA XFMR 2P-1 PR D 480 90

75KVA XFMR 2P-1 SEWG 120 361

75.0 Pos:

Zero:

45.9133

45.9133

91.8280

91.8280

In

75KVA XFMR 2UPSS-1 75KVA XFMR 2UPSS- D 480 90

75KVA XFMR 2UPSS- WG 120 361

75.0 Pos:

Zero:

28.6213

28.6213

57.2440

57.2440

In

75KVA XFMR P2Z 75KVA XFMR P2Z PRI D 480 90

75KVA XFMR P2Z SE WG 120 361

75.0 Pos:

Zero:

32.5573

32.5573

65.1147

65.1147

In

9KVA XFMR 2K 9KVA XFMR 2K PRI B D 480 11

9KVA XFMR 2K SEC BWG 120 43

9.0 Pos:

Zero:

114.5222

114.5222

143.1556

143.1556

In

FIRE PUMP XFMR FIRE PUMP UTIL BUS D 12,470 3

FIRE PUMP XFMR SE WG 480 90

75.0 Pos:

Zero:

27.6080

27.6080

55.2160

55.2160

In

17

Page 166: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Low Voltage Fuses

Prot Dev ManufacturerConnected BusFunc Name Voltage Type Description Cartridge Cartridge Size Trip

2G1 JUNC FUSE MCC-3Phase BUSSMANN480 FRS-R, 600V ClassRK5

1-600A FRS-R 200 200

2H JUNC FUSE 2H FUSE BUSPhase GOULD SHAWMUT480 TRS, 600V ClassRK5

15-600A TRS 80 70

2H-1 FUSE 2H-1 FUSE BUSPhase GOULD SHAWMUT480 TRS, 600V ClassRK5

15-600A TRS 30 30

2H-2 FUSE1 2H-2 FUSE BUSPhase GOULD SHAWMUT480 TRS, 600V ClassRK5

15-600A TRS 30 30

2H-2 FUSE2 2H-2 FUSE2 BUSPhase GOULD SHAWMUT120 TRS, 600V ClassRK5

15-600A TRS 100 100

2P-1 FUSE MCC-3Phase LITTELFUSE480 FLSR, 600V RK5 15-600A FLSR 100 100

ASU 14R FUSE MCC2Phase BUSSMANN480 FRS, 600V Class K5 15-600A FRS 30 25

ASU 14S FUSE MCC2Phase BUSSMANN480 LPS-RK, 600VClass RK1

15-600A LPS-RK 100 100

ASU 15R FUSE MCC2Phase BUSSMANN480 FRS, 600V Class K5 15-600A FRS 30 25

ASU 15S FUSE MCC2Phase BUSSMANN480 LPS-RK, 600VClass RK1

15-600A LPS-RK 100 100

ASU11 FUSE MCC4Phase BUSSMANN480 FRS-R, 600V ClassRK5

1-600A FRS-R 60 60

ASU12 FUSE MCC4Phase BUSSMANN480 FRS-R, 600V ClassRK5

1-600A FRS-R 60 60

ASU13 FUSE MCC4Phase BUSSMANN480 FRS-R, 600V ClassRK5

1-600A FRS-R 60 60

CWP-4 60 AFUSE

CWP-4 FUSE BUSPhase LITTELFUSE480 IDSR, 600V ClassRK5

15-600A IDSR 60 60

Project: FAB

Page 167: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Prot Dev ManufacturerConnected BusFunc Name Voltage Type Description Cartridge Cartridge Size Trip

CWP1 FUSE MCC4Phase GOULD SHAWMUT480 TRS, 600V Class

RK5

15-600A TRS 30 30

CWP1 FUSE2 CWP1 FUSE 2 BUSPhase BUSSMANN480 FRS-R, 600V Class

RK5

1-600A FRS-R 30 30

CWP5 FUSE CWP5 FUSE BUSPhase BUSSMANN480 LPS-RK, 600V

Class RK1

15-600A LPS-RK 100 100

EF-11 FUSE EF-11 FUSE BUSPhase BUSSMANN480 FRS-R, 600V Class

RK5

1-600A FRS-R 60 60

ELE#50 FUSE ELE#50 DISC BUSPhase BUSSMANN480 LPS-RK, 600V

Class RK1

15-600A LPS-RK 100 90

ELEV 4 FUSE ELEV 4 FUSE BUSPhase LITTELFUSE480 IDSR, 600V Class

RK5

15-600A IDSR 60 50

ELEV 4&5 FUSE MCC-3Phase LITTELFUSE480 FLSR, 600V RK5 15-600A FLSR 100 100

ELEV 5 FUSE ELEV 5 FUSE BUSPhase LITTELFUSE480 IDSR, 600V Class

RK5

15-600A IDSR 60 50

KL FUSE PNL KLPhase BUSSMANN120 FRS-R, 600V Class

RK5

1-600A FRS-R 400 400

L1 200 A FUSE L1 FUSE BUSPhase BUSSMANN120 FRN-R, 250V Class

RK5

0.1-600A FRN-R 200 200

L1A 200 A FUSE L1A FUSE BUSPhase BUSSMANN120 FRN-R, 250V Class

RK5

0.1-600A FRN-R 200 200

P-19-1 FUSE MCC-3Phase BUSSMANN480 FRS-R, 600V Class

RK5

1-600A FRS-R 12 12

P-19-2 FUSE MCC-3Phase BUSSMANN480 FRS-R, 600V Class

RK5

1-600A FRS-R 12 12

P2D FUSE P2D FUSE BUSPhase BUSSMANN120 FRN-R, 250V Class

RK5

0.1-600A FRN-R 100 100

PNL 4K

PENTHOUSE

MCC-3Phase BUSSMANN480 FRS-R, 600V Class

RK5

1-600A FRS-R 200 200

SF1A FUSE SF1A FUSE BUSPhase BUSSMANN480 FRS-R, 600V Class

RK5

1-600A FRS-R 60 60

SF1B FUSE SF1B FUSE BUSPhase BUSSMANN480 FRS-R, 600V Class

RK5

1-600A FRS-R 60 60

SF2A FUSE SF2A FUSE FEED

BUS

Phase BUSSMANN480 FRS-R, 600V Class

RK5

1-600A FRS-R 60 60

SF2B FUSE SF2B FUSE FEED

BUS

Phase BUSSMANN480 FRS-R, 600V Class

RK5

1-600A FRS-R 60 60

SFGA FUSE SFGA FUSE BUSPhase LITTELFUSE480 IDSR, 600V Class

RK5

15-600A IDSR 60 60

TOWER41 FUSE TOWER41 FUSE

BUS

Phase BUSSMANN480 FRS-R, 600V Class

RK5

1-600A FRS-R 60 60

TOWER42 FUSE TOWER42 FUSE

BUS

Phase BUSSMANN480 FRS-R, 600V Class

RK5

1-600A FRS-R 60 60

Page 168: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

ADJUSTABLE LOW VOLTAGE CIRCUIT BREAKER SETTINGS

DESIGNATION

INST

P.U.

S.D.

TIME

S.D.

P.U.

L.D.

TIME

L.T.

P.U.

TRIP UNIT

SETTINGS

TYPE/MODELDescriptionAmps

Sensor/Plug

TYPE

MODELMFRFunctionLocation/NameAIC

kA

Frame

Frame

Amps ( I2T ) GFPU GFD

MDS-608 200800 CUTLER-HAMMER

Magnum DS,RMS 520

LSI, 800AF,200-800A Plugs

PhaseUSB-1, 200 A EH3ACB

20065 1 (200A) 24 10(2000A)

0.5 (I^2t In) M1(14)(2800A)Ground

MDS-632 3,2003,200 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 3200AF,

3000-3200A

Plugs

PhaseUSB-1, 3200 A Main

CB1

3,20065 1

(3200A)

24 10

(32000A

)

0.5 (I^2t Out) M1(10)

(32000A

)Ground

MDS-632 3,2003,200 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 3200AF,

3000-3200A

Plugs

PhaseUSB-2, 3200 A Main

CB2

3,20065 1

(3200A)

24 10

(32000A

)

0.5 (I^2t Out) M1(10)

(32000A

)Ground

MDS-632 3,2003,200 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 3200AF,

3000-3200A

Plugs

PhaseUSB-5, 3200 A Main

CB3

3,20065 1

(3200A)

24 10

(32000A

)

0.5 (I^2t Out) M1(10)

(32000A

)Ground

MDS-632 3,2003,200 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 3200AF,

3000-3200A

Plugs

PhaseUSB-1, 3200 A TIE CB 3,20065 1

(3200A)

24 10

(32000A

)

0.5 (I^2t Out) M1(10)

(32000A

)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 400 A 4G CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 400800 CUTLER-HAMMER

Magnum DS,RMS 520

LSI, 800AF,200-800A Plugs

PhaseUSB-2, 400 A 4J1 CB 40065 1 (400A) 24 10(4000A)

0.5 (I^2t In) M1(14)(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 400 A ATS-1

CB

40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 400 A H2A CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 400 A H3A CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 400 A H3B CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 400 A H4A CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

Project: FAB

Page 169: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

DESIGNATION

INST

P.U.

S.D.

TIME

S.D.

P.U.

L.D.

TIME

L.T.

P.U.

TRIP UNIT

SETTINGS

TYPE/MODELDescriptionAmps

Sensor/Plug

TYPE

MODELMFRFunctionLocation/NameAIC

kA

Frame

Frame

Amps ( I2T ) GFPU GFD

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 400 A H5A CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 400 A HPA CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-5, 400 A P4D CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-5, 4J CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 600800 CUTLER-HAMMER

Magnum DS,RMS 520

LSI, 800AF,200-800A Plugs

PhaseUSB-1, 600 A USB-1CB

60065 1 (600A) 24 10(6000A)

0.5 (I^2t In) M1(14)(8400A)Ground

MDS-608 600800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 600 A USB-2

CB

60065 1 (600A) 24 10

(6000A)

0.5 (I^2t In) M1(14)

(8400A)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-5, 800 A EB2 CB 80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 800 A EDP15

CB

80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 800 A EHRA

CB

80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 800 A MCC10

CB

80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-HAMMER

Magnum DS,RMS 520

LSI, 800AF,200-800A Plugs

PhaseUSB-5, 800 A MCC3CB

80065 1 (800A) 24 10(8000A)

0.5 (I^2t In) M1(14)(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-5, 800 A P4A CB 80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-5, 800 A P4B CB 80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 800 A P4X CB 80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

Page 170: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

DESIGNATION

INST

P.U.

S.D.

TIME

S.D.

P.U.

L.D.

TIME

L.T.

P.U.

TRIP UNIT

SETTINGS

TYPE/MODELDescriptionAmps

Sensor/Plug

TYPE

MODELMFRFunctionLocation/NameAIC

kA

Frame

Frame

Amps ( I2T ) GFPU GFD

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 800 A P4Y CB 80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 800 A P4Z CB 80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 800 A WCU-4

CB

80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 800 A WCU-5

CB

80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

SMD6 800800 SIEMENS SMD6, Sensitrip

III

LSI, 600-800APhasePNL EDP15, EDP-E

CB

80065 100 %

(800A)

27 10

(8000A)

0.45 I2t (I^2t In) 40

(32000A

)Ground

PG 4001,200 SQUARE D Powerpact

P-Frame,6.0A/P/H

LSI,

100-1200A, UL

PhaseGEN 1 BUS, GEN SET

CB

035 1 16 10

(4000A)

0.4 (I^2t Out) 15

(6000A)Ground

CHLD 500600 WESTINGH

OUSE

HLD/CHLDRMS310 LSPhaseWCU-4 SW BUS,

WCU-4 SW

065 1.0

(500A)

LTD 8.0

(4000A)

STD (I^2t In)

Ground

CHLD 500600 WESTINGH

OUSE

HLD/CHLDRMS310 LSPhaseWCU-5 SW BUS,

WCU-5 SW

065 1.0

(500A)

LTD 8.0

(4000A)

STD (I^2t In)

Ground

Page 171: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

LOW VOLTAGE THERMAL MAGNETIC MOLDED CASE BREAKERS SETTINGS

DESIGNATION TRIP UNITFRAME

TYPE/MODELDescriptionMFRLocation/NameAmps

Frame

TYPE

MODEL

Amps

Sensor/Plug LT SETTING INST SETTING

FixedFD 100100 CUTLER-HA

MMER

FD15-225A0P4Z

100 A 4F CB

FixedFD 110110 CUTLER-HA

MMER

FD15-225A0P4Y

110 A WWP2 CB

FixedEJ 100100 SQUARE D EJ15-125A0EMDP-P

14E CB

FixedFD 150150 CUTLER-HA

MMER

FD15-225A0P4Z

150 A 4GE CB

FixedFD 150150 CUTLER-HA

MMER

FD15-225A0PNL 4D2

150 A DHRC-1 CB

FixedFD 150150 CUTLER-HA

MMER

FD15-225A0P4Y

150 A WWP3 CB

FixedFD 150150 CUTLER-HAMMER

FD15-225A0P4Y

150 A WWP4 CB

Thermal Curve INST (100-125) FixedNGB 20125 SIEMENS NGG\NGB, 2-3

Poles

15-125AT0PNL 4D2

20 A CWP1A CB

Thermal Curve INST (100-125) FixedNGB 20125 SIEMENS NGG\NGB, 2-3

Poles

15-125AT0PNL 4D2

20 A CWP1B CB

FixedEHB 2020 CUTLER-HA

MMER

EHB, 2 & 3-Pole15-100A0PNL 4J2

20 A XFMR 2J CB

FixedFD 200200 CUTLER-HA

MMER

FD15-225A0P4Z

200 A 4A CB

FixedFD 200200 CUTLER-HA

MMER

FD15-225A0P4Y

200 A 4D2 CB

FixedFD 200200 CUTLER-HA

MMER

FD15-225A0P4Y

200 A H6A CB

FixedFD 200200 CUTLER-HA

MMER

FD15-225A0P4Y

200 A H7A CB

Project: FAB

Page 172: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

DESIGNATION TRIP UNITFRAME

TYPE/MODELDescriptionMFRLocation/NameAmps

Frame

TYPE

MODEL

Amps

Sensor/Plug LT SETTING INST SETTING

Thermal Curve INST (100-125) FixedNGB 25125 SIEMENS NGG\NGB, 2-3

Poles

15-125AT0PNL 4D2

25 A CHWP1A CB

Thermal Curve INST (100-125) FixedNGB 25125 SIEMENS NGG\NGB, 2-3

Poles

15-125AT0PNL 4D2

25 A CHWP1B CB

FixedEH 2020 SQUARE D EH15-100A0PNL 4B

2B1 CB

FixedFD 110110 CUTLER-HA

MMER

FD15-225A0PNL P4D

2C-12 CB

FixedBAB 2020 CUTLER-HAMMER

BAB, 1-Pole10-70A0PNL 4C-12

2CA CB

Thermal Curve INST (Fixed) FixedGHB 6060 CUTLER-HA

MMER

GHB15-100A, 2-3 Pole0PNL 4D1

2D1 CB

FixedFD 7070 CUTLER-HA

MMER

FD15-225A0PNL 4D

2D2 CB

Thermal Curve (Fixed) INST (1100-2500A) HICLF 225250 SIEMENS CLF70-250A0PNL EDP-E

2D3 CB

FixedFD 4040 CUTLER-HA

MMER

FD15-225A0PNL 4K PENTHOUSE

2K CB

Thermal Curve (Fixed) INST FixedQJ2H 150150 SIEMENS QJ2H60-225A02K-232 CB1 BUS

2K-232 CB1

Thermal Curve (Fixed) INST FixedQJ2 150150 SIEMENS QJ260-225A0PNL 2K-232 SEC1

2K-232 CB2

FixedFD 100100 CUTLER-HA

MMER

FD15-225A0PNL 4K PENTHOUSE

2K-232 XFMR CB

FixedFD 7070 CUTLER-HAMMER

FD15-225A0PNL 4K PENTHOUSE

2L-1 CB

Thermal Curve INST HIKA 100100 SQUARE D KA70-250A02P-1 BUS

2P-1 CB

FixedFD 3030 CUTLER-HA

MMER

FD15-225A0P4Y

30 A ASU9A CB

Thermal Curve (Fixed) INST (5-10 x Trip) 10HKD 400400 CUTLER-HA

MMER

HKD100-400A0P4Y

400 A XFMR CB

Page 173: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

DESIGNATION TRIP UNITFRAME

TYPE/MODELDescriptionMFRLocation/NameAmps

Frame

TYPE

MODEL

Amps

Sensor/Plug LT SETTING INST SETTING

Thermal Curve (Fixed) INST (900-2000A) HIF6 175200 SIEMENS F670-250A0PNL P4A

4B CB

Thermal Curve (Fixed) INST (900-2000A) HIF6 175200 SIEMENS F670-250A0PNL 4B

4B CB0

FixedFD 200200 CUTLER-HA

MMER

FD15-225A0P4Z

4C CB

Thermal Curve (Fixed) INST (900-2000A) HIF6 175200 SIEMENS F670-250A0PNL P4B

4C-12 CB

Thermal Curve (Fixed) INST (900-2000A) HIF6 175200 SIEMENS F670-250A0PNL P4B

4CH CB

FixedFD 150150 CUTLER-HA

MMER

FD15-225A0P4Z

4D CB

FixedFD 100100 CUTLER-HA

MMER

FD15-225A0PNL P4D

4D1 CB

FixedFD 200200 CUTLER-HA

MMER

FD15-225A0P4Z

4DE CB

FixedEJ 100100 SQUARE D EJ15-125A0EMDP-P

4E CB

FixedFD 3535 CUTLER-HA

MMER

FD15-225A0PNL 4J

4F-13 CB

Thermal Curve (Fixed) INST FixedEH 125150 SIEMENS EH15-150A0PNL P4A

4G-104 CB

Thermal Curve (Fixed) INST (5-10 x Trip) 10KD 400400 CUTLER-HA

MMER

KD100-400A0P4Z

4I CB

FixedFD 200200 CUTLER-HAMMER

FD15-225A0P4Z

4K CB 1

FixedFD 200200 CUTLER-HA

MMER

FD15-225A04K CB 2 BUS

4K CB 2

Thermal Curve (Fixed) INST FixedFJ 225225 SIEMENS FJ70-225A0MCC-3

4K PENTHOUSE CB

FixedFD 200200 CUTLER-HA

MMER

FD15-225A0P4Z

4L CB 1

Page 174: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

DESIGNATION TRIP UNITFRAME

TYPE/MODELDescriptionMFRLocation/NameAmps

Frame

TYPE

MODEL

Amps

Sensor/Plug LT SETTING INST SETTING

Thermal Curve INST HIKA 200250 SQUARE D KA70-250A04L CB 2 BUS

4L CB 2

FixedFD 150150 CUTLER-HA

MMER

FD15-225A0P4Z

4M CB 1

FixedFD 150150 CUTLER-HA

MMER

FD15-225A04M CB 2 BUS

4M CB 2

FixedFD 6060 CUTLER-HA

MMER

FD15-225A0PNL 4G

60 A XFMR CB

Thermal Curve (Fixed) INST (LO-HI) HIFXD6 225250 SIEMENS FXD6 Sentron70-250A0PNL 4I

CHILLER1 CB1

Thermal Curve (Fixed) INST (5-10 x Trip) 10JD 250250 CUTLER-HA

MMER

JD70-250A0CHILLER 1 BUS

CHILLER1 CB2

FixedFD 5050 CUTLER-HA

MMER

FD15-225A0MCC10

CHWP-4 CB

FixedFD 3030 CUTLER-HA

MMER

FD15-225A0MCC12

CHWP-5 CB

FixedFD 150150 CUTLER-HA

MMER

FD15-225A0PNL 4DE

DHRC2 CB

FixedFD 150150 CUTLER-HA

MMER

FD15-225A0PNL 4DE

DHRC3 CB

FixedFD 6060 CUTLER-HA

MMER

FD15-225A0PNL P4X

EF-11 CB

FixedFD 9090 CUTLER-HA

MMER

FD15-225A0P4Z

ELEV #50 DISC CB

FixedFD 6060 CUTLER-HAMMER

FD15-225A0PNL P4X

ELEV1 CB1

FixedFA 100100 SQUARE D FA15-100A0ELEV1 CB2 BUS

ELEV1 CB2

FixedFD 6060 CUTLER-HA

MMER

FD15-225A0PNL P4X

ELEV2 CB1

FixedFA 100100 SQUARE D FA15-100A0ELEV2 CB2 BUS

ELEV2 CB2

Page 175: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

DESIGNATION TRIP UNITFRAME

TYPE/MODELDescriptionMFRLocation/NameAmps

Frame

TYPE

MODEL

Amps

Sensor/Plug LT SETTING INST SETTING

FixedEJ 4040 SQUARE D EJ15-70A0EMDP-P

EMCC-T6 CB

Thermal Curve (Fixed) INST FixedED6, 3-Pole 125125 SIEMENS ED6 Sentron, 2 &

3-Pole

15-125A0FIRE PUMP CB1 BUS

FIRE PUMP CB1

Thermal Curve (Fixed) INST (LO-HI) HILXD6-A 600600 SIEMENS LXD6-A Sentron450-600A0FIRE PUMP CB2 BUS

FIRE PUMP CB2

FixedFD 175175 CUTLER-HA

MMER

FD15-225A0FIRE PUMP CB3 BUS

FIRE PUMP CB3

FixedFD 200200 CUTLER-HAMMER

FD15-225A0PNL P4D

KL CB

FixedFD 200200 CUTLER-HA

MMER

FD15-225A0P4Z

MCC12 CB

FixedFD 2020 CUTLER-HA

MMER

FD15-225A0PNL 4GE

MCC2 CB

Thermal Curve (Fixed) INST (LO-HI) HIFXD6 225250 SIEMENS FXD6 Sentron70-250A0PNL 4I

MCC4 CB

FixedFD 5050 CUTLER-HA

MMER

FD15-225A0MCC10

P18-3 CB

FixedHFD 4040 CUTLER-HA

MMER

HFD15-225A0PNL P4D

P2D CB

FixedFD 200200 CUTLER-HA

MMER

FD15-225A0PNL U4B

PDU1 CB

FixedFD 200200 CUTLER-HA

MMER

FD15-225A0PNL U4A

PDU2 CB

FixedFD 200200 CUTLER-HAMMER

FD15-225A0PNL U4B

PDU3 CB

FixedFD 200200 CUTLER-HA

MMER

FD15-225A0PNL U4A

PDU4 CB

Thermal Curve (Fixed) INST (900-2000A) HICLF 200200 SIEMENS CLF70-250A0PNL EDP-D

PNL 1 CB

Thermal Curve (Fixed) INST (900-2000A) HICLF 200200 SIEMENS CLF70-250A0PNL EDP-D

PNL 2 CB

Page 176: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

DESIGNATION TRIP UNITFRAME

TYPE/MODELDescriptionMFRLocation/NameAmps

Frame

TYPE

MODEL

Amps

Sensor/Plug LT SETTING INST SETTING

Thermal Curve (Fixed) INST FixedBLH 100100 SIEMENS BLH, 2 & 3-Pole15-100A0PNL 2A-2

PNL 2B CB

FixedQ2 150150 SQUARE D Q2100-225A0PNL U

PNL 2U-1 CB

Thermal Curve (Fixed) INST FixedQJ2 150150 SIEMENS QJ260-225A0PNL 2UPSN-1

PNL 2UPSN-1 CB

Thermal Curve (Fixed) INST, 600V HIGHFXD6-A 250250 SIEMENS FXD6A70-250A, 2-3 Poles0PNL 2UPSS-1

PNL 2UPSS-1 CB

Thermal Curve (Fixed) INST (900-2000A) HICLF 200200 SIEMENS CLF70-250A0PNL EDP-D

PNL 3 CB

Thermal Curve (Fixed) INST (900-2000A) HICLF 200200 SIEMENS CLF70-250A0PNL EDP-D

PNL 4 CB

Thermal Curve (Fixed) INST (900-2000A) HICLF 200200 SIEMENS CLF70-250A0PNL EDP-D

PNL 5 CB

Thermal Curve (Fixed) INST (900-2000A) HICLF 200200 SIEMENS CLF70-250A0PNL EDP-D

PNL 6 CB

Thermal Curve (Fixed) INST (800-1500A) HICLF 150150 SIEMENS CLF70-250A0PNL EDP-D

PNL 7 CB

MAXSEDA 6060 GE SEDA, Spectra RMS15-150A0PNL EDP-D CB1 BUS

PNL EDP-D CB1

MAXSFHA 200250 GE SFHA, Spectra RMS70-250A0PNL EDP-D CB2 BUS

PNL EDP-D CB2

Thermal Curve (Fixed) INST (5-10 x Trip) 10KD 400400 CUTLER-HA

MMER

KD100-400A0USDP-B

PNL U XFMR CB

Thermal Curve (Fixed) INST (5-10 x Trip) 10HKD 125125 CUTLER-HAMMER

HKD100-400A0EMDP-P

ROOF MOTOR CB

Thermal Curve (Fixed) INST FixedEH 60100 SIEMENS EH15-150A0PNL 4J

SF1A CB

Thermal Curve (Fixed) INST FixedEH 70100 SIEMENS EH15-150A0PNL 4J

SF1B CB

FixedFD 100100 CUTLER-HA

MMER

FD15-225A0PNL 4M

SF2A CB

Page 177: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

DESIGNATION TRIP UNITFRAME

TYPE/MODELDescriptionMFRLocation/NameAmps

Frame

TYPE

MODEL

Amps

Sensor/Plug LT SETTING INST SETTING

FixedFD 100100 CUTLER-HA

MMER

FD15-225A0PNL 4M

SF2B CB

Thermal Curve (Fixed) INST (5-10 x Trip) 10KD 200200 CUTLER-HA

MMER

KD100-400A0PNL P2Z

SONNY'S CB

Thermal Curve INST, (5-10X) 10XLGH 630630 CUTLER-HA

MMER

LG, Series G200-630A, Adj T+M,

IEC

0PNL SSD-B

STS-A CB1

Thermal Curve INST, (5-10X) 10XLGH 630630 CUTLER-HA

MMER

LG, Series G200-630A, Adj T+M,

IEC

0PNL SSD-A

STS-A CB2

Thermal Curve INST, (5-10X) 10XLGH 630630 CUTLER-HAMMER

LG, Series G200-630A, Adj T+M,IEC

0STS-A

STS-A CB3

Thermal Curve INST, (5-10X) 10XLGH 630630 CUTLER-HA

MMER

LG, Series G200-630A, Adj T+M,

IEC

0STS-A

STS-A CB4

Thermal Curve INST, (5-10X) 10XLGH 630630 CUTLER-HA

MMER

LG, Series G200-630A, Adj T+M,

IEC

0PNL SSD-B

STS-B CB1

Thermal Curve INST, (5-10X) 10XLGH 630630 CUTLER-HA

MMER

LG, Series G200-630A, Adj T+M,

IEC

0PNL SSD-A

STS-B CB2

Thermal Curve INST, (5-10X) 10XLGH 630630 CUTLER-HA

MMER

LG, Series G200-630A, Adj T+M,

IEC

0STS-B

STS-B CB3

Thermal Curve INST, (5-10X) 10XLGH 630630 CUTLER-HA

MMER

LG, Series G200-630A, Adj T+M,

IEC

0STS-B

STS-B CB4

FixedFD 5050 CUTLER-HA

MMER

FD15-225A0PNL 4K PENTHOUSE

TOWER41 CB

FixedFD 5050 CUTLER-HA

MMER

FD15-225A0PNL 4K PENTHOUSE

TOWER42 CB

FixedFD 6060 CUTLER-HAMMER

FD15-225A0UPS A CB1 BUS

UPS A CB1

FixedFD 6060 CUTLER-HA

MMER

FD15-225A0UPS A BUS1

UPS A CB2

FixedFD 6060 CUTLER-HA

MMER

FD15-225A0UPS A CB3 BUS

UPS A CB3

FixedFD 6060 CUTLER-HA

MMER

FD15-225A0UPS CB1 BUS

UPS B CB1

Page 178: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

DESIGNATION TRIP UNITFRAME

TYPE/MODELDescriptionMFRLocation/NameAmps

Frame

TYPE

MODEL

Amps

Sensor/Plug LT SETTING INST SETTING

FixedFD 6060 CUTLER-HA

MMER

FD15-225A0UPS B CB3 BUS

UPS B CB3

FixedFD 6060 CUTLER-HA

MMER

FD15-225A0UPS B BUS1

UPS CB2

FixedFD 9090 CUTLER-HAMMER

FD15-225A0PNL 14E

XFMR 12E CB

Thermal Curve (Fixed) INST FixedEH 125150 SIEMENS EH15-150A0PNL 4A

XFMR 2A CB

FixedFD 6060 CUTLER-HA

MMER

FD15-225A0PNL 4D

XFMR 2D CB

FixedFD 3030 CUTLER-HA

MMER

FD15-225A0PNL 4E

XFMR 2E CB

Thermal Curve (Fixed) INST FixedEH 50100 SIEMENS EH15-150A0PNL 4F

XFMR 2F CB

Thermal Curve (Fixed) INST FixedEH 50100 SIEMENS EH15-150A0PNL 4F

XFMR 2F1 CB

FixedEHD 3030 CUTLER-HA

MMER

EHD15-100A0PNL P4A

XFMR 2GA CB

FixedEHD 7070 CUTLER-HA

MMER

EHD15-100A0PNL P4A

XFMR 2GB CB

FixedFD 2020 CUTLER-HAMMER

FD15-225A0PNL 4GE

XFMR 2GE CB

FixedEHD 2020 CUTLER-HA

MMER

EHD15-100A0PNL 4J2

XFMR 2J CB

Thermal Curve (Fixed) INST (5-10 x Trip) 10KD 400400 CUTLER-HA

MMER

KD100-400A0USDP-B

XFMR 2UPSN-1 CB

Thermal Curve (Fixed) INST (5-10 x Trip) 10KD 400400 CUTLER-HA

MMER

KD100-400A0USDP-B

XFMR 2UPSS-1 CB

FixedFD 5050 CUTLER-HA

MMER

FD15-225A0PNL 14E

XFMR P1 CB

FixedFD 110110 CUTLER-HA

MMER

FD15-225A0P4Z

XFMR P2Z CB

Page 179: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

APPENDIX C

Page 180: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR1

0.5 1 10 100

1K 10K

100K

1M

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

1500KVA XFMR1

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

1500KVA XFMR1

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1

USB-1

TCC NAME: USB-1REFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: USB-1

Page 181: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR1P4Y FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

1500KVA XFMR1

P4Y FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

1500KVA XFMR1

P4Y FEED

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1

USB-1

800 A P4Y CB

P4Y FEED

P4Y

TCC NAME: P4YREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: P4Y

Page 182: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR1P4Y FEED

ASU9A FEEDASU9A-1 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERFDFDTrip 30.0 ASettings Phase Fixed

30 A ASU9A CB

1500KVA XFMR1

P4Y FEED

ASU9A FEED

ASU9A-1 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERFDFDTrip 30.0 ASettings Phase Fixed

30 A ASU9A CB

1500KVA XFMR1

P4Y FEED

ASU9A FEED

ASU9A-1 FEED

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1

USB-1

800 A P4Y CB

P4Y FEED

P4Y

30 A ASU9A CB

ASU9A FEED

ASU9A-1 FEED

ASU9A-1

TCC NAME: ASU9A-1REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: ASU9A-1

Page 183: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR1P4Y FEED

ASU9A FEEDASU9A-2 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERFDFDTrip 30.0 ASettings Phase Fixed

30 A ASU9A CB

1500KVA XFMR1

P4Y FEED

ASU9A FEED

ASU9A-2 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERFDFDTrip 30.0 ASettings Phase Fixed

30 A ASU9A CB

1500KVA XFMR1

P4Y FEED

ASU9A FEED

ASU9A-2 FEED

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1

USB-1

800 A P4Y CB

P4Y FEED

P4Y

30 A ASU9A CB

ASU9A FEED

ASU9A-2 FEED

ASU9A-2

TCC NAME: ASU9A-2REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: ASU9A-2

Page 184: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Y FEED

TX Inrush

1500KVA XFMR1

150KVA XFMR FEED

TX Inrush

150KVA XFMRL1A DISC FEEDL1A FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERHKDHKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

400 A XFMR CB

BUSSMANNFRN-R, 250V Class RK5FRN-RTrip 200.0 A

L1A 200 A FUSE

P4Y FEED

1500KVA XFMR1

150KVA XFMR FEED

150KVA XFMR

L1A DISC FEED

L1A FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERHKDHKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

400 A XFMR CB

BUSSMANNFRN-R, 250V Class RK5FRN-RTrip 200.0 A

L1A 200 A FUSE

P4Y FEED

1500KVA XFMR1

150KVA XFMR FEED

150KVA XFMR

L1A DISC FEED

L1A FEED

800 A P4Y CB

P4Y FEED

P4Y

USB-1

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1

400 A XFMR CB

150KVA XFMR FEED

S

P150KVA XFMR

L1A DISC FEED

L1A DISC SW

L1A 200 A F USE

L1A FEED

PNL L1A

TCC NAME: PNL L1AREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL L1A

Page 185: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Y FEED

TX Inrush

1500KVA XFMR1

150KVA XFMR FEED

TX Inrush

150KVA XFMRL1 DISC FEEDL1 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CBCUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERHKDHKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

400 A XFMR CB

BUSSMANNFRN-R, 250V Class RK5FRN-RTrip 200.0 A

L1 200 A FUSE

P4Y FEED

1500KVA XFMR1

150KVA XFMR FEED

150KVA XFMR

L1 DISC FEED

L1 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CBCUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERHKDHKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

400 A XFMR CB

BUSSMANNFRN-R, 250V Class RK5FRN-RTrip 200.0 A

L1 200 A FUSE

P4Y FEED

1500KVA XFMR1

150KVA XFMR FEED

150KVA XFMR

L1 DISC FEED

L1 FEED

800 A P4Y CB

P4Y FEED

P4Y

USB-1

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1

400 A XFMR CB

150KVA XFMR FEED

S

P150KVA XFMR

L1 DISC FEED

L1 DISC SW

L1 200 A FUSE

L1 FEED

PNL L1

TCC NAME: PNL L1REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL L1

Page 186: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Y FEED

TX Inrush

1500KVA XFMR1

WWP4 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A WWP4 CB

P4Y FEED

1500KVA XFMR1

WWP4 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A WWP4 CB

P4Y FEED

1500KVA XFMR1

WWP4 FEED

800 A P4Y CB

P4Y FEED

P4Y

USB-1

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1

150 A WWP4 CB

WWP4 FEED

WWP4

TCC NAME: WWP4REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: WWP4

Page 187: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Y FEED

TX Inrush

1500KVA XFMR1

WWP3 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A WWP3 CB

P4Y FEED

1500KVA XFMR1

WWP3 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A WWP3 CB

P4Y FEED

1500KVA XFMR1

WWP3 FEED

800 A P4Y CB

P4Y FEED

P4Y

USB-1

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1

150 A WWP3 CB

WWP3 FEED

WWP3

TCC NAME: WWP3REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: WWP3

Page 188: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Y FEED

TX Inrush

1500KVA XFMR1

WWP2 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERFDFDTrip 110.0 ASettings Phase Fixed

110 A WWP2 CB

P4Y FEED

1500KVA XFMR1

WWP2 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

CUTLER-HAMMERFDFDTrip 110.0 ASettings Phase Fixed

110 A WWP2 CB

P4Y FEED

1500KVA XFMR1

WWP2 FEED

800 A P4Y CB

P4Y FEED

P4Y

USB-1

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1

110 A WWP2 CB

WWP2 FEED

WWP2

TCC NAME: WWP2REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: WWP2

Page 189: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

DHRC-1 FEED4D2 FEED

P4Y FEED

TX Inrush

1500KVA XFMR1

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A DHRC-1 CB

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4D2 CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

DHRC-1 FEED

4D2 FEED

P4Y FEED

1500KVA XFMR1

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A DHRC-1 CB

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4D2 CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

DHRC-1 FEED

4D2 FEED

P4Y FEED

1500KVA XFMR1

150 A DHRC-1 CB

DHRC-1 FEED

DHRC-1

PNL 4D2

200 A 4D2 CB

4D2 FEED

P4Y

800 A P4Y CB

P4Y FEED

USB-1

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1TCC NAME: DHRC-1REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: DHRC-1

Page 190: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4D2 FEEDP4Y FEED

TX Inrush

1500KVA XFMR1

CWP1A FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4D2 CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

SIEMENSNGG\NGB, 2-3 PolesNGBTrip 20.0 ASettings Phase Thermal Curve INST (100-125) Fixed (180A)

20 A CWP1A CB

4D2 FEED

P4Y FEED

1500KVA XFMR1

CWP1A FEED

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4D2 CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

SIEMENSNGG\NGB, 2-3 PolesNGBTrip 20.0 ASettings Phase Thermal Curve INST (100-125) Fixed (180A)

20 A CWP1A CB

4D2 FEED

P4Y FEED

1500KVA XFMR1

CWP1A FEED

PNL 4D2

200 A 4D2 CB

4D2 FEED

P4Y

800 A P4Y CB

P4Y FEED

USB-1

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1

20 A CWP1A CB

CWP1A FEED

CWP1A

TCC NAME: CWP1AREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: CWP1A

Page 191: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4D2 FEEDP4Y FEED

TX Inrush

1500KVA XFMR1

CWP1B FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4D2 CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

SIEMENSNGG\NGB, 2-3 PolesNGBTrip 20.0 ASettings Phase Thermal Curve INST (100-125) Fixed (180A)

20 A CWP1B CB

4D2 FEED

P4Y FEED

1500KVA XFMR1

CWP1B FEED

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4D2 CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

SIEMENSNGG\NGB, 2-3 PolesNGBTrip 20.0 ASettings Phase Thermal Curve INST (100-125) Fixed (180A)

20 A CWP1B CB

4D2 FEED

P4Y FEED

1500KVA XFMR1

CWP1B FEED

PNL 4D2

200 A 4D2 CB

4D2 FEED

P4Y

800 A P4Y CB

P4Y FEED

USB-1

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1

20 A CWP1B CB

CWP1B FEED

CWP1B

TCC NAME: CWP1BREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: CWP1B

Page 192: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4D2 FEEDP4Y FEED

TX Inrush

1500KVA XFMR1

CHWP1A FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4D2 CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

SIEMENSNGG\NGB, 2-3 PolesNGBTrip 25.0 ASettings Phase Thermal Curve INST (100-125) Fixed (225A)

25 A CHWP1A CB

4D2 FEED

P4Y FEED

1500KVA XFMR1

CHWP1A FEED

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4D2 CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

SIEMENSNGG\NGB, 2-3 PolesNGBTrip 25.0 ASettings Phase Thermal Curve INST (100-125) Fixed (225A)

25 A CHWP1A CB

4D2 FEED

P4Y FEED

1500KVA XFMR1

CHWP1A FEED

PNL 4D2

200 A 4D2 CB

4D2 FEED

P4Y

800 A P4Y CB

P4Y FEED

USB-1

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1

25 A CHWP1A CB

CHWP1A FEED

CHWP1A

TCC NAME: CHWP1AREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: CHWP1A

Page 193: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4D2 FEEDP4Y FEED

TX Inrush

1500KVA XFMR1

CHWP1B FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4D2 CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

SIEMENSNGG\NGB, 2-3 PolesNGBTrip 25.0 ASettings Phase Thermal Curve INST (100-125) Fixed (225A)

25 A CHWP1B CB

4D2 FEED

P4Y FEED

1500KVA XFMR1

CHWP1B FEED

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4D2 CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Y CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB1

SIEMENSNGG\NGB, 2-3 PolesNGBTrip 25.0 ASettings Phase Thermal Curve INST (100-125) Fixed (225A)

25 A CHWP1B CB

4D2 FEED

P4Y FEED

1500KVA XFMR1

CHWP1B FEED

PNL 4D2

200 A 4D2 CB

4D2 FEED

P4Y

800 A P4Y CB

P4Y FEED

USB-1

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1

25 A CHWP1B CB

CHWP1B FEED

CHWP1B

TCC NAME: CHWP1BREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: CHWP1B

Page 194: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR2

0.5 1 10 100

1K 10K

100K

1M

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

1500KVA XFMR2

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

1500KVA XFMR2

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

TCC NAME: USB-2REFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: USB-2

Page 195: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR2P4X FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4X CB

1500KVA XFMR2

P4X FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4X CB

1500KVA XFMR2

P4X FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

800 A P4X CB

P4X FEED

PNL P4X

TCC NAME: P4XREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: P4X

Page 196: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR2P4X FEED

EF-11 FUSE FEEDEF-11 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4X CB

CUTLER-HAMMERFDFDTrip 60.0 ASettings Phase Fixed

EF-11 CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

EF-11 FUSE

1500KVA XFMR2

P4X FEED

EF-11 FUSE FEED

EF-11 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4X CB

CUTLER-HAMMERFDFDTrip 60.0 ASettings Phase Fixed

EF-11 CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

EF-11 FUSE

1500KVA XFMR2

P4X FEED

EF-11 FUSE FEED

EF-11 FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

800 A P4X CB

P4X FEED

PNL P4X

EF-11 CB

EF-11 FUSE FEED

EF-11 FEED

EF-11

EF-11 FUSE

TCC NAME: EF-11REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: EF-11

Page 197: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR2P4X FEED

ELEV1 CB FEEDELEV1 XFMR FEED

TX Inrush

27KVA XFMR ELEV1ELEV1 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4X CB

CUTLER-HAMMERFDFDTrip 60.0 ASettings Phase Fixed

ELEV1 CB1

SQUARE DFAFATrip 100.0 ASettings Phase Fixed

ELEV1 CB2

1500KVA XFMR2

P4X FEED

ELEV1 CB FEED

ELEV1 XFMR FEED

27KVA XFMR ELEV1

ELEV1 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4X CB

CUTLER-HAMMERFDFDTrip 60.0 ASettings Phase Fixed

ELEV1 CB1

SQUARE DFAFATrip 100.0 ASettings Phase Fixed

ELEV1 CB2

1500KVA XFMR2

P4X FEED

ELEV1 CB FEED

ELEV1 XFMR FEED

27KVA XFMR ELEV1

ELEV1 FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

800 A P4X CB

P4X FEED

PNL P4X

ELEV1 CB1

ELEV1 CB FEED

ELEV1 CB2

ELEV1 XFMR FEED

S

P 27KVA XFM R ELEV1

ELEV1 FEED

ELEV1

TCC NAME: ELEV1REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: ELEV1

Page 198: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4X FEED

TX Inrush

1500KVA XFMR2

ELEV2 CB FEEDELEV2 XFMR FEED

TX Inrush

27KVA XFMR ELEV2ELEV2 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4X CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 60.0 ASettings Phase Fixed

ELEV2 CB1

SQUARE DFAFATrip 100.0 ASettings Phase Fixed

ELEV2 CB2

P4X FEED

1500KVA XFMR2

ELEV2 CB FEED

ELEV2 XFMR FEED

27KVA XFMR ELEV2

ELEV2 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4X CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 60.0 ASettings Phase Fixed

ELEV2 CB1

SQUARE DFAFATrip 100.0 ASettings Phase Fixed

ELEV2 CB2

P4X FEED

1500KVA XFMR2

ELEV2 CB FEED

ELEV2 XFMR FEED

27KVA XFMR ELEV2

ELEV2 FEED

800 A P4X CB

P4X FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

PNL P4X

ELEV2 CB1

ELEV2 CB FEED

ELEV2 CB2

ELEV2 XFMR FEED

S

P 27KVA XFMR ELEV2

ELEV2 FEED

ELEV2

TCC NAME: ELEV2REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: ELEV2

Page 199: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

WCU-5 SW FEEDWCU-5 FEED

TX Inrush

1500KVA XFMR2

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A WCU-5 CB

WESTINGHOUSEHLD/CHLDCHLDTrip 500.0 ASettings Phase LTPU 1.0 (500A) LTD LTD STPU 8.0 (4000A) STD-I2T STD (I^2t In)

WCU-5 SW

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

WCU-5 SW FEED

WCU-5 FEED

1500KVA XFMR2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A WCU-5 CB

WESTINGHOUSEHLD/CHLDCHLDTrip 500.0 ASettings Phase LTPU 1.0 (500A) LTD LTD STPU 8.0 (4000A) STD-I2T STD (I^2t In)

WCU-5 SW

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

WCU-5 SW FEED

WCU-5 FEED

1500KVA XFMR2

800 A WCU-5 CB

WCU-5 SW FEED

WCU-5 SW

WCU-5

WCU-5 FEED

USB-2

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

TCC NAME: WCU-5REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: WCU-5

Page 200: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR2WCU-4 SW FEEDWCU-4 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A WCU-4 CB

WESTINGHOUSEHLD/CHLDCHLDTrip 500.0 ASettings Phase LTPU 1.0 (500A) LTD LTD STPU 8.0 (4000A) STD-I2T STD (I^2t In)

WCU-4 SW

1500KVA XFMR2

WCU-4 SW FEED

WCU-4 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A WCU-4 CB

WESTINGHOUSEHLD/CHLDCHLDTrip 500.0 ASettings Phase LTPU 1.0 (500A) LTD LTD STPU 8.0 (4000A) STD-I2T STD (I^2t In)

WCU-4 SW

1500KVA XFMR2

WCU-4 SW FEED

WCU-4 FEED

USB-2

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

800 A WCU-4 CB

WCU-4 SW FEED

WCU-4 SW

WCU-4

WCU-4 FEED

TCC NAME: WCU-4REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: WCU-4

Page 201: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR2

EDP15 XFMR FEED

TX Inrush

1000KVA XFMR EDP15

EDP15 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A EDP15 CB

1500KVA XFMR2

EDP15 XFMR FEED

1000KVA XFMR EDP15

EDP15 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A EDP15 CB

1500KVA XFMR2

EDP15 XFMR FEED

1000KVA XFMR EDP15

EDP15 FEED

USB-2

3200 A Main CB2

S

P

1500KVA XFMR 2

SWGR #2

800 A EDP15 CB

EDP15 XFMR FEED

S

P1000KVA XFMR EDP15

EDP15 FEED

PNL EDP15

TCC NAME: PNL EDP15REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL EDP15

Page 202: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR2

EDP15 XFMR FEED

TX Inrush

1000KVA XFMR EDP15

EDP15 FEEDEDP-E FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A EDP15 CB

SIEMENSSMD6, Sensitrip IIISMD6Trip 800.0 APlug 800.0 ASettings Phase LTPU (20-100% x P) 100 % (800A) LTD (2.2-27 Sec.) 27 STPU (1.5-10 x LTPU) 10 (8000A) STD (0.05-0.5 Sec.) 0.45 I2t (I^2t In) INST (2-40 x LTPU) 40 (32000A) INST Override (Max) Max (10000A)

EDP-E CB

1500KVA XFMR2

EDP15 XFMR FEED

1000KVA XFMR EDP15

EDP15 FEED

EDP-E FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A EDP15 CB

SIEMENSSMD6, Sensitrip IIISMD6Trip 800.0 APlug 800.0 ASettings Phase LTPU (20-100% x P) 100 % (800A) LTD (2.2-27 Sec.) 27 STPU (1.5-10 x LTPU) 10 (8000A) STD (0.05-0.5 Sec.) 0.45 I2t (I^2t In) INST (2-40 x LTPU) 40 (32000A) INST Override (Max) Max (10000A)

EDP-E CB

1500KVA XFMR2

EDP15 XFMR FEED

1000KVA XFMR EDP15

EDP15 FEED

EDP-E FEED

USB-2

3200 A Main CB2

S

P

1500KVA XFMR 2

SWGR #2

800 A EDP15 CB

EDP15 XFMR FEED

S

P1000KVA XFMR EDP15

EDP15 FEED

PNL EDP15

EDP-E CB

EDP-E FEED

PNL EDP-E

TCC NAME: PNL EDP-EREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL EDP-E

Page 203: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR2

EDP15 XFMR FEED

TX Inrush

1000KVA XFMR EDP15

EDP15 FEEDEDP-E FEED

2D3 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A EDP15 CB

SIEMENSSMD6, Sensitrip IIISMD6Trip 800.0 APlug 800.0 ASettings Phase LTPU (20-100% x P) 100 % (800A) LTD (2.2-27 Sec.) 27 STPU (1.5-10 x LTPU) 10 (8000A) STD (0.05-0.5 Sec.) 0.45 I2t (I^2t In) INST (2-40 x LTPU) 40 (32000A) INST Override (Max) Max (10000A)

EDP-E CB

SIEMENSCLFCLFTrip 225.0 ASettings Phase Thermal Curve (Fixed) INST (1100-2500A) HI (2500A)

2D3 CB

1500KVA XFMR2

EDP15 XFMR FEED

1000KVA XFMR EDP15

EDP15 FEED

EDP-E FEED2D3 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A EDP15 CB

SIEMENSSMD6, Sensitrip IIISMD6Trip 800.0 APlug 800.0 ASettings Phase LTPU (20-100% x P) 100 % (800A) LTD (2.2-27 Sec.) 27 STPU (1.5-10 x LTPU) 10 (8000A) STD (0.05-0.5 Sec.) 0.45 I2t (I^2t In) INST (2-40 x LTPU) 40 (32000A) INST Override (Max) Max (10000A)

EDP-E CB

SIEMENSCLFCLFTrip 225.0 ASettings Phase Thermal Curve (Fixed) INST (1100-2500A) HI (2500A)

2D3 CB

1500KVA XFMR2

EDP15 XFMR FEED

1000KVA XFMR EDP15

EDP15 FEED

EDP-E FEED2D3 FEED

USB-2

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

800 A EDP15 CB

EDP15 XFMR FEED

S

P1000KVA XFMR EDP 15

EDP15 FEED

PNL EDP15

EDP-E CB

EDP-E FEED

2D3 CB

2D3 FEED

PNL 2D3

PNL EDP-E

TCC NAME: PNL 2D3REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2D3

Page 204: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR2P4Z FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

1500KVA XFMR2

P4Z FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

1500KVA XFMR2

P4Z FEED

USB-2

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

800 A P4Z CB

P4Z FEED

P4Z

TCC NAME: P4ZREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: P4Z

Page 205: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4C FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4C CB

P4Z FEED

1500KVA XFMR2

4C FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4C CB

P4Z FEED

1500KVA XFMR2

4C FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4C CB

4C FEED

PNL 4C

TCC NAME: PNL 4CREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4C

Page 206: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4C FEEDXFMR 2C FEED

TX Inrush

45KVA XFMR 2C2C FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4C CB

P4Z FEED

1500KVA XFMR2

4C FEED

XFMR 2C FEED

45KVA XFMR 2C

2C FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4C CB

P4Z FEED

1500KVA XFMR2

4C FEED

XFMR 2C FEED

45KVA XFMR 2C

2C FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4C CB

4C FEED

PNL 4C

XFMR 2C FEED

S

P

45KVA XFMR 2C

2C FEED

PNL 2C

TCC NAME: PNL 2CREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2C

Page 207: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4C FEEDXFMR 2C2 FEED

TX Inrush

30KVA XFMR 2C22C2 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CBCUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4C CB

P4Z FEED

1500KVA XFMR2

4C FEED

XFMR 2C2 FEED

30KVA XFMR 2C2

2C2 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CBCUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4C CB

P4Z FEED

1500KVA XFMR2

4C FEED

XFMR 2C2 FEED

30KVA XFMR 2C2

2C2 FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4C CB

4C FEED

PNL 4C

XFMR 2C2 FEED

S

P

30KVA XFMR 2C2

2C2 FEED

PNL 2C2

TCC NAME: PNL 2C2REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2C2

Page 208: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4L FEED 14L FEED 2

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4L CB 1

SQUARE DKAKATrip 200.0 ASettings Phase Thermal Curve INST HI (2000A)

4L CB 2

P4Z FEED

1500KVA XFMR2

4L FEED 1

4L FEED 2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4L CB 1

SQUARE DKAKATrip 200.0 ASettings Phase Thermal Curve INST HI (2000A)

4L CB 2

P4Z FEED

1500KVA XFMR2

4L FEED 1

4L FEED 2

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

PNL 4L

4L CB 1

4L FEED 1

4L CB 2

4L FEED 2

TCC NAME: PNL 4LREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4L

Page 209: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR24I FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

4I CB

P4Z FEED

1500KVA XFMR2

4I FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

4I CB

P4Z FEED

1500KVA XFMR2

4I FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4I CB

4I FEED

PNL 4I

TCC NAME: PNL 4IREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4I

Page 210: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR24I FEED

MCC4 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

4I CB

SIEMENSFXD6 SentronFXD6Trip 225.0 ASettings Phase Thermal Curve (Fixed) INST (LO-HI) HI (2500A)

MCC4 CB

P4Z FEED

1500KVA XFMR2

4I FEED

MCC4 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

4I CB

SIEMENSFXD6 SentronFXD6Trip 225.0 ASettings Phase Thermal Curve (Fixed) INST (LO-HI) HI (2500A)

MCC4 CB

P4Z FEED

1500KVA XFMR2

4I FEED

MCC4 FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4I CB

4I FEED

PNL 4I

MCC4 FEED

MCC4 CB

MCC4

TCC NAME: MCC4REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: MCC4

Page 211: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR24I FEED

MCC4 FEEDASU13 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

4I CB

SIEMENSFXD6 SentronFXD6Trip 225.0 ASettings Phase Thermal Curve (Fixed) INST (LO-HI) HI (2500A)

MCC4 CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

ASU13 FUSE

P4Z FEED

1500KVA XFMR2

4I FEED

MCC4 FEED

ASU13 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

4I CB

SIEMENSFXD6 SentronFXD6Trip 225.0 ASettings Phase Thermal Curve (Fixed) INST (LO-HI) HI (2500A)

MCC4 CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

ASU13 FUSE

P4Z FEED

1500KVA XFMR2

4I FEED

MCC4 FEED

ASU13 FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XF MR 2

SWGR #2

P4Z

4I CB

4I FEED

PNL 4I

MCC4 FEED

MCC4 CB

MCC4

ASU13 FUSE

ASU13 FEED

ASU13

TCC NAME: ASU13REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: ASU13

Page 212: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR24I FEED

MCC4 FEEDASU11 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

4I CB

SIEMENSFXD6 SentronFXD6Trip 225.0 ASettings Phase Thermal Curve (Fixed) INST (LO-HI) HI (2500A)

MCC4 CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

ASU11 FUSE

P4Z FEED

1500KVA XFMR2

4I FEED

MCC4 FEED

ASU11 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

4I CB

SIEMENSFXD6 SentronFXD6Trip 225.0 ASettings Phase Thermal Curve (Fixed) INST (LO-HI) HI (2500A)

MCC4 CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

ASU11 FUSE

P4Z FEED

1500KVA XFMR2

4I FEED

MCC4 FEED

ASU11 FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4I CB

4I FEED

PNL 4I

MCC4 FEED

MCC4 CB

MCC4

ASU11 FUSE

ASU11 FEED

ASU11

TCC NAME: ASU11REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: ASU11

Page 213: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR24I FEED

MCC4 FEEDASU12 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

4I CB

SIEMENSFXD6 SentronFXD6Trip 225.0 ASettings Phase Thermal Curve (Fixed) INST (LO-HI) HI (2500A)

MCC4 CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

ASU12 FUSE

P4Z FEED

1500KVA XFMR2

4I FEED

MCC4 FEED

ASU12 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

4I CB

SIEMENSFXD6 SentronFXD6Trip 225.0 ASettings Phase Thermal Curve (Fixed) INST (LO-HI) HI (2500A)

MCC4 CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

ASU12 FUSE

P4Z FEED

1500KVA XFMR2

4I FEED

MCC4 FEED

ASU12 FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4I CB

4I FEED

PNL 4I

MCC4 FEED

MCC4 CB

MCC4

ASU12 FUSE

ASU12 FEED

ASU12

TCC NAME: ASU12REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: ASU12

Page 214: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR24I FEED

MCC4 FEEDCWP1 FEEDCWP1 FEED2

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

4I CB

SIEMENSFXD6 SentronFXD6Trip 225.0 ASettings Phase Thermal Curve (Fixed) INST (LO-HI) HI (2500A)

MCC4 CB

GOULD SHAWMUTTRS, 600V Class RK5TRSTrip 30.0 A

CWP1 FUSE

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 30.0 A

CWP1 FUSE2

P4Z FEED

1500KVA XFMR2

4I FEED

MCC4 FEED

CWP1 FEEDCWP1 FEED2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

4I CB

SIEMENSFXD6 SentronFXD6Trip 225.0 ASettings Phase Thermal Curve (Fixed) INST (LO-HI) HI (2500A)

MCC4 CB

GOULD SHAWMUTTRS, 600V Class RK5TRSTrip 30.0 A

CWP1 FUSE

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 30.0 A

CWP1 FUSE2

P4Z FEED

1500KVA XFMR2

4I FEED

MCC4 FEED

CWP1 FEEDCWP1 FEED2

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4I CB

4I FEED

PNL 4I

MCC4 FEED

MCC4 CB

MCC4

CWP1 FUSE

CWP1 FEED

CWP1CWP1 FUSE2

CWP1 FEED2

TCC NAME: CWP1REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: CWP1

Page 215: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR24I FEED

CHILLER 1 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

4I CB

SIEMENSFXD6 SentronFXD6Trip 225.0 ASettings Phase Thermal Curve (Fixed) INST (LO-HI) HI (2500A)

CHILLER1 CB1

CUTLER-HAMMERJDJDTrip 250.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (2500A)

CHILLER1 CB2

P4Z FEED

1500KVA XFMR2

4I FEED

CHILLER 1 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

4I CB

SIEMENSFXD6 SentronFXD6Trip 225.0 ASettings Phase Thermal Curve (Fixed) INST (LO-HI) HI (2500A)

CHILLER1 CB1

CUTLER-HAMMERJDJDTrip 250.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (2500A)

CHILLER1 CB2

P4Z FEED

1500KVA XFMR2

4I FEED

CHILLER 1 FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4I CB

4I FEED

PNL 4I

CHILLER 1 FEED

CHILLER1 CB1

CHILLER1 CB2

CHILLER 1

TCC NAME: CHILLER1REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: CHILLER1

Page 216: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4K FEED 14K FEED 2

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4K CB 1

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4K CB 2

P4Z FEED

1500KVA XFMR2

4K FEED 1

4K FEED 2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4K CB 1

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4K CB 2

P4Z FEED

1500KVA XFMR2

4K FEED 1

4K FEED 2

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4K CB 1

4K FEED 1

4K CB 2

4K FEED 2

PNL 4K

TCC NAME: PNL 4KREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4K

Page 217: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4M FEED 14M FEED 2

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4M CB 1

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4M CB 2

P4Z FEED

1500KVA XFMR2

4M FEED 14M FEED 2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4M CB 1

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4M CB 2

P4Z FEED

1500KVA XFMR2

4M FEED 14M FEED 2

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4M CB 1

4M FEED 1

4M CB 2

4M FEED 2

PNL 4M

TCC NAME: PNL 4MREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4M

Page 218: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4M FEED 14M FEED 2

SF2B FEEDSF2B FUSE FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4M CB 1

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4M CB 2

CUTLER-HAMMERFDFDTrip 100.0 ASettings Phase Fixed

SF2B CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

SF2B FUSE

P4Z FEED

1500KVA XFMR2

4M FEED 1

4M FEED 2

SF2B FEED

SF2B FUSE FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4M CB 1

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4M CB 2

CUTLER-HAMMERFDFDTrip 100.0 ASettings Phase Fixed

SF2B CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

SF2B FUSE

P4Z FEED

1500KVA XFMR2

4M FEED 1

4M FEED 2

SF2B FEED

SF2B FUSE FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4M CB 1

4M FEED 1

4M CB 2

4M FEED 2

PNL 4M

SF2B CB

SF2B FEED

SF2B

SF2B FUSE

SF2B FUSE FEED

TCC NAME: SF2BREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: SF2B

Page 219: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4M FEED 14M FEED 2

SF2A FEEDSF2A FUSE FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4M CB 1

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4M CB 2

CUTLER-HAMMERFDFDTrip 100.0 ASettings Phase Fixed

SF2A CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

SF2A FUSE

P4Z FEED

1500KVA XFMR2

4M FEED 1

4M FEED 2

SF2A FEED

SF2A FUSE FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4M CB 1

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4M CB 2

CUTLER-HAMMERFDFDTrip 100.0 ASettings Phase Fixed

SF2A CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

SF2A FUSE

P4Z FEED

1500KVA XFMR2

4M FEED 1

4M FEED 2

SF2A FEED

SF2A FUSE FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4M CB 1

4M FEED 1

4M CB 2

4M FEED 2

PNL 4M

SF2A CB

SF2A FE ED

SF2A

SF2A FUSE

SF2A FUSE FEED

TCC NAME: SF2AREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: SF2A

Page 220: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4DE FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4DE CB

P4Z FEED

1500KVA XFMR2

4DE FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4DE CB

P4Z FEED

1500KVA XFMR2

4DE FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4DE CB

4DE FEED

PNL 4DE

TCC NAME: PNL 4DEREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4DE

Page 221: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4DE FEEDDHRC2 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4DE CB

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

DHRC2 CB

P4Z FEED

1500KVA XFMR2

4DE FEED

DHRC2 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4DE CB

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

DHRC2 CB

P4Z FEED

1500KVA XFMR2

4DE FEED

DHRC2 FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4DE CB

4DE FEED

PNL 4DE

DHRC2 CB

DHRC2 FEED

DHRC2

TCC NAME: DHRC2REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: DHRC2

Page 222: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4DE FEEDDHRC3 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4DE CB

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

DHRC3 CB

P4Z FEED

1500KVA XFMR2

4DE FEEDDHRC3 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

4DE CB

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

DHRC3 CB

P4Z FEED

1500KVA XFMR2

4DE FEEDDHRC3 FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4DE CB

4DE FEED

PNL 4DE

DHRC3 CB

DHRC3 FEED

DHRC3

TCC NAME: DHRC3REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: DHRC3

Page 223: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4D FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4D CB

P4Z FEED

1500KVA XFMR2

4D FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4D CB

P4Z FEED

1500KVA XFMR2

4D FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4D CB

4D FEED

PNL 4D

TCC NAME: PNL 4DREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4D

Page 224: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4D FEED2D2 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4D CB

CUTLER-HAMMERFDFDTrip 70.0 ASettings Phase Fixed

2D2 CB

P4Z FEED

1500KVA XFMR2

4D FEED

2D2 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4D CB

CUTLER-HAMMERFDFDTrip 70.0 ASettings Phase Fixed

2D2 CB

P4Z FEED

1500KVA XFMR2

4D FEED

2D2 FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4D CB

4D FEED

PNL 4D

2D2 CB

2D2 FEED

PNL 2D2

TCC NAME: PNL 2D2REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2D2

Page 225: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4D FEEDXFMR 2D FEED

TX Inrush

45KVA XFMR 2D2D FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4D CB

CUTLER-HAMMERFDFDTrip 60.0 ASettings Phase Fixed

XFMR 2D CB

P4Z FEED

1500KVA XFMR2

4D FEED

XFMR 2D FEED

45KVA XFMR 2D

2D FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4D CB

CUTLER-HAMMERFDFDTrip 60.0 ASettings Phase Fixed

XFMR 2D CB

P4Z FEED

1500KVA XFMR2

4D FEED

XFMR 2D FEED

45KVA XFMR 2D

2D FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A M ai n CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

4D CB

4D FEED

PNL 4D

XFMR 2D FEED

S

P

45KVA XFMR 2D

2D FEED

XFMR 2D CB

PNL 2D

TCC NAME: PNL 2DREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2D

Page 226: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4D FEEDXFMR 2D FEED

TX Inrush

45KVA XFMR 2D2D FEED

2D1 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4D CB

CUTLER-HAMMERFDFDTrip 60.0 ASettings Phase Fixed

XFMR 2D CB

P4Z FEED

1500KVA XFMR2

4D FEED

XFMR 2D FEED

45KVA XFMR 2D

2D FEED

2D1 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

4D CB

CUTLER-HAMMERFDFDTrip 60.0 ASettings Phase Fixed

XFMR 2D CB

P4Z FEED

1500KVA XFMR2

4D FEED

XFMR 2D FEED

45KVA XFMR 2D

2D FEED

2D1 FEED

USB-2

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR 2

SWGR #2

P4Z

4D CB

4D FEED

PNL 4D

XFMR 2D FEED

S

P

45KVA XFMR 2D

2D FEED

XFMR 2D CB

PNL 2D

2D1 FEED

PNL 2D1

TCC NAME: PNL 2D1REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2D1

Page 227: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

MCC12 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

MCC12 CB

P4Z FEED

1500KVA XFMR2

MCC12 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

MCC12 CB

P4Z FEED

1500KVA XFMR2

MCC12 FEED

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

MCC12 CB

MCC12 FEED

MCC12

USB-2 TCC NAME: MCC12REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: MCC12

Page 228: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

MCC12 FEEDCWP5 FEEDCWP5 FUSE FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

MCC12 CB

BUSSMANNLPS-RK, 600V Class RK1LPS-RKTrip 100.0 A

CWP5 FUSE

P4Z FEED

1500KVA XFMR2

MCC12 FEED

CWP5 FEED

CWP5 FUSE FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

MCC12 CB

BUSSMANNLPS-RK, 600V Class RK1LPS-RKTrip 100.0 A

CWP5 FUSE

P4Z FEED

1500KVA XFMR2

MCC12 FEED

CWP5 FEED

CWP5 FUSE FEED

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

MCC12 CB

MCC12 FEED

MCC12

USB-2

CWP5 FEED

CWP5

CWP5 FUSE

CWP5 FUSE FEED

TCC NAME: CWP5REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: CWP5

Page 229: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

MCC12 FEEDCHWP-5 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

MCC12 CB

CUTLER-HAMMERFDFDTrip 30.0 ASettings Phase Fixed

CHWP-5 CB

P4Z FEED

1500KVA XFMR2

MCC12 FEED

CHWP-5 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

MCC12 CB

CUTLER-HAMMERFDFDTrip 30.0 ASettings Phase Fixed

CHWP-5 CB

P4Z FEED

1500KVA XFMR2

MCC12 FEED

CHWP-5 FEED

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

MCC12 CB

MCC12 FEED

MCC12

USB-2

CHWP-5 FEED

CHWP-5 CB

CHWP-5

TCC NAME: CHWP-5REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: CHWP-5

Page 230: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

ELE#50 FEEDELEV#50 DISC FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

BUSSMANNLPS-RK, 600V Class RK1LPS-RKTrip 90.0 A

ELE#50 FUSE

CUTLER-HAMMERFDFDTrip 90.0 ASettings Phase Fixed

ELEV #50 DISC CB

P4Z FEED

1500KVA XFMR2

ELE#50 FEEDELEV#50 DISC FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

BUSSMANNLPS-RK, 600V Class RK1LPS-RKTrip 90.0 A

ELE#50 FUSE

CUTLER-HAMMERFDFDTrip 90.0 ASettings Phase Fixed

ELEV #50 DISC CB

P4Z FEED

1500KVA XFMR2

ELE#50 FEEDELEV#50 DISC FEED

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

P4Z

USB-2

ELE#50 FUSE

ELE#50 FEED

ELE #50

ELEV #50 DISC CB

ELEV#50 DISC FEED

TCC NAME: ELE#50REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: ELE#50

Page 231: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

XFMR P2Z FEED

TX Inrush

75KVA XFMR P2Z

P2Z FEEDSONNYS FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 110.0 ASettings Phase Fixed

XFMR P2Z CB

P4Z FEED

1500KVA XFMR2

XFMR P2Z FEED

75KVA XFMR P2Z

P2Z FEED

SONNYS FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 110.0 ASettings Phase Fixed

XFMR P2Z CB

P4Z FEED

1500KVA XFMR2

XFMR P2Z FEED

75KVA XFMR P2Z

P2Z FEED

SONNYS FEED

XFMR P2Z FEED

S

P

75KVA XFMR P2Z

P2Z FEED

XFMR P2Z CB

PNL P2Z

P4Z

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

TCC NAME: PNL P2ZREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL P2Z

Page 232: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

XFMR P2Z FEED

TX Inrush

75KVA XFMR P2Z

P2Z FEEDSONNYS FEED

P4Z FEED

TX Inrush

1500KVA XFMR2

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 110.0 ASettings Phase Fixed

XFMR P2Z CB

CUTLER-HAMMERKDKDTrip 200.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (2000A)

SONNY'S CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

XFMR P2Z FEED

75KVA XFMR P2Z

P2Z FEEDSONNYS FEED

P4Z FEED

1500KVA XFMR2

CUTLER-HAMMERFDFDTrip 110.0 ASettings Phase Fixed

XFMR P2Z CB

CUTLER-HAMMERKDKDTrip 200.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (2000A)

SONNY'S CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

XFMR P2Z FEED

75KVA XFMR P2Z

P2Z FEEDSONNYS FEED

P4Z FEED

1500KVA XFMR2

XFMR P2Z FEED

S

P

75KVA XFMR P2Z

P2Z FEED

XFMR P2Z CB

PNL P2Z

SONNYS FEED

SONNY'S

SONNY'S CB

P4Z

800 A P4Z CB

P4Z FEED

3200 A Mai n CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

TCC NAME: SONNY'SREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: SONNY'S

Page 233: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4GE FEEDP4Z FEED

TX Inrush

1500KVA XFMR2

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A 4GE CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

4GE FEED

P4Z FEED

1500KVA XFMR2

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A 4GE CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

4GE FEED

P4Z FEED

1500KVA XFMR2

PNL 4GE

4GE FEED

150 A 4GE CB

P4Z

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2 TCC NAME: PNL 4GEREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4GE

Page 234: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4GE FEEDP4Z FEED

TX Inrush

1500KVA XFMR2

XFMR 2GE FEED

TX Inrush

30KVA XFMR 2GE

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A 4GE CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 20.0 ASettings Phase Fixed

XFMR 2GE CB

4GE FEED

P4Z FEED

1500KVA XFMR2

XFMR 2GE FEED

30KVA XFMR 2GE

2GE FEED

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A 4GE CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 20.0 ASettings Phase Fixed

XFMR 2GE CB

4GE FEED

P4Z FEED

1500KVA XFMR2

XFMR 2GE FEED

30KVA XFMR 2GE

2GE FEED

PNL 4GE

4GE FEED

150 A 4GE CB

P4Z

800 A P4Z CB

P4Z FEED

3200 A M ai n CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

XFMR 2GE FEED

S

P

30KVA XFMR 2GE

2GE FEED

PNL 2GE

XFMR 2GE CB

TCC NAME: PNL 2GEREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2GE

Page 235: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4GE FEED

P4Z FEED

TX Inrush

1500KVA XFMR2

MCC2 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A 4GE CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 20.0 ASettings Phase Fixed

MCC2 CB

4GE FEED

P4Z FEED

1500KVA XFMR2

MCC2 FEED

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A 4GE CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 20.0 ASettings Phase Fixed

MCC2 CB

4GE FEED

P4Z FEED

1500KVA XFMR2

MCC2 FEED

PNL 4GE

4GE FEED

150 A 4GE CB

P4Z

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

MCC2

MCC2 FEED

MCC2 CB

TCC NAME: MCC2REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: MCC2

Page 236: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4GE FEED

P4Z FEED

TX Inrush

1500KVA XFMR2

MCC2 FEED

ASU 14S FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A 4GE CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 20.0 ASettings Phase Fixed

MCC2 CB

BUSSMANNLPS-RK, 600V Class RK1LPS-RKTrip 100.0 A

ASU 14S FUSE

4GE FEED

P4Z FEED

1500KVA XFMR2

MCC2 FEED

ASU 14S FEED

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A 4GE CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 20.0 ASettings Phase Fixed

MCC2 CB

BUSSMANNLPS-RK, 600V Class RK1LPS-RKTrip 100.0 A

ASU 14S FUSE

4GE FEED

P4Z FEED

1500KVA XFMR2

MCC2 FEED

ASU 14S FEED

PNL 4GE

4GE FEED

150 A 4GE CB

P4Z

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

MCC2

MCC2 FEED

MCC2 CB

ASU 14S FUSE

ASU 14S FEED

ASU 14S

TCC NAME: ASU14SREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: ASU14S

Page 237: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4GE FEED

P4Z FEED

TX Inrush

1500KVA XFMR2

MCC2 FEED

ASU 14R FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A 4GE CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 20.0 ASettings Phase Fixed

MCC2 CB

BUSSMANNFRS, 600V Class K5FRSTrip 25.0 A

ASU 14R FUSE

4GE FEED

P4Z FEED

1500KVA XFMR2

MCC2 FEED

ASU 14R FEED

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A 4GE CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 20.0 ASettings Phase Fixed

MCC2 CB

BUSSMANNFRS, 600V Class K5FRSTrip 25.0 A

ASU 14R FUSE

4GE FEED

P4Z FEED

1500KVA XFMR2

MCC2 FEED

ASU 14R FEED

PNL 4GE

4GE FEED

150 A 4GE CB

P4Z

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

MCC2

MCC2 FEED

MCC2 CB

ASU 14R FUSE

ASU 14R FEED

ASU 14R

TCC NAME: ASU14RREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: ASU14R

Page 238: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4GE FEED

P4Z FEED

TX Inrush

1500KVA XFMR2

MCC2 FEED

ASU 15R FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A 4GE CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 20.0 ASettings Phase Fixed

MCC2 CB

BUSSMANNFRS, 600V Class K5FRSTrip 25.0 A

ASU 15R FUSE

4GE FEED

P4Z FEED

1500KVA XFMR2

MCC2 FEED

ASU 15R FEED

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A 4GE CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 20.0 ASettings Phase Fixed

MCC2 CB

BUSSMANNFRS, 600V Class K5FRSTrip 25.0 A

ASU 15R FUSE

4GE FEED

P4Z FEED

1500KVA XFMR2

MCC2 FEED

ASU 15R FEED

PNL 4GE

4GE FEED

150 A 4GE CB

P4Z

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

MCC2

MCC2 FEED

MCC2 CB

ASU 15R FUSE

ASU 15R FEED

ASU 15R

TCC NAME: ASU15RREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: ASU15R

Page 239: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4GE FEED

P4Z FEED

TX Inrush

1500KVA XFMR2

MCC2 FEED

ASU 15S FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A 4GE CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 20.0 ASettings Phase Fixed

MCC2 CB

BUSSMANNLPS-RK, 600V Class RK1LPS-RKTrip 100.0 A

ASU 15S FUSE

4GE FEED

P4Z FEED

1500KVA XFMR2

MCC2 FEED

ASU 15S FEED

CUTLER-HAMMERFDFDTrip 150.0 ASettings Phase Fixed

150 A 4GE CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 20.0 ASettings Phase Fixed

MCC2 CB

BUSSMANNLPS-RK, 600V Class RK1LPS-RKTrip 100.0 A

ASU 15S FUSE

4GE FEED

P4Z FEED

1500KVA XFMR2

MCC2 FEED

ASU 15S FEED

PNL 4GE

4GE FEED

150 A 4GE CB

P4Z

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

MCC2

MCC2 FEED

MCC2 CB

ASU 15S FUSE

ASU 15S FEED

ASU 15S

TCC NAME: ASU15SREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: ASU15S

Page 240: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4F FEEDP4Z FEED

TX Inrush

1500KVA XFMR2

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 100.0 ASettings Phase Fixed

100 A 4F CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

4F FEEDP4Z FEED

1500KVA XFMR2

CUTLER-HAMMERFDFDTrip 100.0 ASettings Phase Fixed

100 A 4F CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

4F FEEDP4Z FEED

1500KVA XFMR2

PNL 4F

4F FEED

100 A 4F CB

P4Z

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2 TCC NAME: PNL 4FREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4F

Page 241: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4F FEEDP4Z FEED

TX Inrush

1500KVA XFMR2

XFMR 2F FEED

TX Inrush

30KVA XFMR 2F2F FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 100.0 ASettings Phase Fixed

100 A 4F CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

4F FEED

P4Z FEED

1500KVA XFMR2

XFMR 2F FEED

30KVA XFMR 2F

2F FEED

CUTLER-HAMMERFDFDTrip 100.0 ASettings Phase Fixed

100 A 4F CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

4F FEED

P4Z FEED

1500KVA XFMR2

XFMR 2F FEED

30KVA XFMR 2F

2F FEED

PNL 4F

4F FEED

100 A 4F CB

P4Z

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

XFMR 2F FEED

S

P

30KVA XFMR 2F

2F FEED

PNL 2F

TCC NAME: PNL 2FREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2F

Page 242: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4F FEEDP4Z FEED

TX Inrush

1500KVA XFMR2

XFMR 2F1 FEED

TX Inrush

30KVA XFMR 2F12F1 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 100.0 ASettings Phase Fixed

100 A 4F CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

4F FEED

P4Z FEED

1500KVA XFMR2

XFMR 2F1 FEED

30KVA XFMR 2F1

2F1 FEED

CUTLER-HAMMERFDFDTrip 100.0 ASettings Phase Fixed

100 A 4F CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

4F FEED

P4Z FEED

1500KVA XFMR2

XFMR 2F1 FEED

30KVA XFMR 2F1

2F1 FEED

PNL 4F

4F FEED

100 A 4F CB

P4Z

800 A P4Z CB

P4Z FEED

3200 A Mai n CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

XFMR 2F1 FEED

S

P30KVA XFMR 2F1

2F1 FEED

PNL 2F1

TCC NAME: PNL 2F1REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2F1

Page 243: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4Z FEED

TX Inrush

1500KVA XFMR2

4A FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4A CB

P4Z FEED

1500KVA XFMR2

4A FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4A CB

P4Z FEED

1500KVA XFMR2

4A FEED

P4Z

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

200 A 4A CB

4A FEED

PNL 4A

TCC NAME: PNL 4AREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4A

Page 244: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

XFMR 2A FEED

TX Inrush

75KVA XFMR 2A2A-1 FEED

4A FEEDP4Z FEED

TX Inrush

1500KVA XFMR2

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

SIEMENSEHEHTrip 125.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1150A)

XFMR 2A CB

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4A CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

XFMR 2A FEED

75KVA XFMR 2A

2A-1 FEED

4A FEEDP4Z FEED

1500KVA XFMR2

SIEMENSEHEHTrip 125.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1150A)

XFMR 2A CB

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4A CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

XFMR 2A FEED

75KVA XFMR 2A

2A-1 FEED

4A FEEDP4Z FEED

1500KVA XFMR2

PNL 4A

XFMR 2A CB

XFMR 2A FEED

S

P

75KVA XFMR 2A

2A-1 FEED

PNL 2A-1

200 A 4A CB

4A FEED

P4Z

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

TCC NAME: PNL 2A-1REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2A-1

Page 245: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

2B FEED

2A-2 FEED

XFMR 2A FEED

TX Inrush

75KVA XFMR 2A

2A-1 FEED

4A FEEDP4Z FEED

TX Inrush

1500KVA XFMR2

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

SIEMENSBLH, 2 & 3-PoleBLHTrip 100.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1100A)

PNL 2B CB

SIEMENSEHEHTrip 125.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1150A)

XFMR 2A CB

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4A CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

2B FEED2A-2 FEED

XFMR 2A FEED

75KVA XFMR 2A

2A-1 FEED

4A FEED

P4Z FEED

1500KVA XFMR2

SIEMENSBLH, 2 & 3-PoleBLHTrip 100.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1100A)

PNL 2B CB

SIEMENSEHEHTrip 125.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1150A)

XFMR 2A CB

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

200 A 4A CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4Z CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

2B FEED2A-2 FEED

XFMR 2A FEED

75KVA XFMR 2A

2A-1 FEED

4A FEED

P4Z FEED

1500KVA XFMR2

PNL 2 A-2

2B FEED

PNL 2 B

PNL 2 B CB

2A-2 FEED

PNL 4 A

XFMR 2A CB

XFMR 2A FEED

S

P

75KVA XFMR 2A

2A-1 FEED

PNL 2A-1

200 A 4A CB

4A FEED

P4Z

800 A P4Z CB

P4Z FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

TCC NAME: PNL 2BREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2B

Page 246: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

MCC10 FEED

TX Inrush

1500KVA XFMR2

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC10 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

MCC10 FEED

1500KVA XFMR2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC10 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

MCC10 FEED

1500KVA XFMR2

800 A MCC10 CB

MCC10 FEED

MCC10

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

TCC NAME: MCC10REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: MCC10

Page 247: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

MCC10 FEED

TX Inrush

1500KVA XFMR2

CWP-4 FUSE FEEDCWP-4 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC10 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

SIEMENSCFD6 Sentron ETICFD6Settings Phase INST (1100-2500A) HI (2500A)

CWP-4 CB

LITTELFUSEIDSR, 600V Class RK5IDSRTrip 60.0 A

CWP-4 60 A FUSE

MCC10 FEED

1500KVA XFMR2

CWP-4 FUSE FEED

CWP-4 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC10 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

SIEMENSCFD6 Sentron ETICFD6Settings Phase INST (1100-2500A) HI (2500A)

CWP-4 CB

LITTELFUSEIDSR, 600V Class RK5IDSRTrip 60.0 A

CWP-4 60 A FUSE

MCC10 FEED

1500KVA XFMR2

CWP-4 FUSE FEED

CWP-4 FEED

800 A MCC10 CB

MCC10 FEED

MCC10

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

CWP-4 CB

CWP-4 FUSE FEED

CWP-4

CWP-4 60 A FUSE

CWP-4 FEED

TCC NAME: CWP-4REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: CWP-4

Page 248: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

MCC10 FEED

TX Inrush

1500KVA XFMR2

CHWP-4 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC10 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 50.0 ASettings Phase Fixed

CHWP-4 CB

MCC10 FEED

1500KVA XFMR2

CHWP-4 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC10 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 50.0 ASettings Phase Fixed

CHWP-4 CB

MCC10 FEED

1500KVA XFMR2

CHWP-4 FEED

800 A MCC10 CB

MCC10 FEED

MCC10

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

CHWP-4 CB

CHWP-4 FEED

CHWP-4

TCC NAME: CHWP-4REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: CHWP-4

Page 249: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

MCC10 FEED

TX Inrush

1500KVA XFMR2

P18-3 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC10 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 50.0 ASettings Phase Fixed

P18-3 CB

MCC10 FEED

1500KVA XFMR2

P18-3 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC10 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERFDFDTrip 50.0 ASettings Phase Fixed

P18-3 CB

MCC10 FEED

1500KVA XFMR2

P18-3 FEED

800 A MCC10 CB

MCC10 FEED

MCC10

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

P18-3 CB

P18-3 FEED

P18-3

TCC NAME: P18-3REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: P18-3

Page 250: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4J1 FEED

TX Inrush

1500KVA XFMR2

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

400 A 4J1 CB CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

4J1 FEED

1500KVA XFMR2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

400 A 4J1 CB CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

4J1 FEED

1500KVA XFMR2

4J1 FEED

PNL 4J1

400 A 4J1 CB

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

USB-2

TCC NAME: PNL 4J1REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4J1

Page 251: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4J1 FEED

TX Inrush

15KVA XFMR 2J

4J2 FEED

TX Inrush

1500KVA XFMR2

XFMR 2J FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A 4J1 CB

CUTLER-HAMMEREHB, 2 & 3-PoleEHBTrip 20.0 ASettings Phase Fixed

20 A XFMR 2J CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMEREHDEHDTrip 20.0 ASettings Phase Fixed

XFMR 2J CB

4J1 FEED

15KVA XFMR 2J

2J FEED

4J2 FEED

1500KVA XFMR2

XFMR 2J FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A 4J1 CB

CUTLER-HAMMEREHB, 2 & 3-PoleEHBTrip 20.0 ASettings Phase Fixed

20 A XFMR 2J CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMEREHDEHDTrip 20.0 ASettings Phase Fixed

XFMR 2J CB

4J1 FEED

15KVA XFMR 2J

2J FEED

4J2 FEED

1500KVA XFMR2

XFMR 2J FEED

4J1 FEED

PNL 4J1

400 A 4J1 CB

3200 A Main CB2

S

P

1500KVA XF MR 2

SWGR #2

USB-2

S

P15KVA XFMR 2J

2J FEED

PNL 2J

4J2 FEED

PNL 4J2

XFMR 2J CB

XFMR 2J FEED

TCC NAME: PNL 2JREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2J

Page 252: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR24G FEED

45KVA XFMR FEED

TX Inrush

45KVA XFMR2G FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) 10 (4000A)

400 A 4G CB

CUTLER-HAMMERFDFDTrip 60.0 ASettings Phase Fixed

60 A XFMR CB

1500KVA XFMR2

4G FEED

45KVA XFMR FEED

45KVA XFMR

2G FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) 10 (4000A)

400 A 4G CB

CUTLER-HAMMERFDFDTrip 60.0 ASettings Phase Fixed

60 A XFMR CB

1500KVA XFMR2

4G FEED

45KVA XFMR FEED

45KVA XFMR

2G FEED

400 A 4G CB

4G FEED

60 A XFMR CB

45KVA XFMR FEED

S

P45KVA XFMR

2G FEED

PNL 4G

PNL 2G

USB-2

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

TCC NAME: PNL 2GREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2G

Page 253: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4G FEED

TX Inrush

1500KVA XFMR2

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) 10 (4000A)

400 A 4G CBCUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

4G FEED

1500KVA XFMR2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) 10 (4000A)

400 A 4G CBCUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

4G FEED

1500KVA XFMR2

400 A 4G CB

4G FEED

PNL 4G

USB-2

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

TCC NAME: PNL 4GREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4G

Page 254: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

ATS-1 FEEDEMDP-P FEED

TX Inrush

1500KVA XFMR2

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CBCUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

ATS-1 FEED

EMDP-P FEED

1500KVA XFMR2

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CBCUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

ATS-1 FEED

EMDP-P FEED

1500KVA XFMR2

400 A ATS-1 CB

ATS-1 FEED

EMDP-P FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

E N

ATS-1

EMDP-P

USB-2TCC NAME: EMDP-PREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: EMDP-P

Page 255: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

FIRE PUMP FEED1FIRE PUMP FEED2FIRE PUMP FEED3FIRE PUMP FEED4

TX Inrush

FIRE PUMP XFMR

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

SIEMENSED6 Sentron, 2 & 3-PoleED6, 3-PoleTrip 125.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (800A)

FIRE PUMP CB1

SIEMENSLXD6-A SentronLXD6-ATrip 600.0 ASettings Phase Thermal Curve (Fixed) INST (LO-HI) HI (6000A)

FIRE PUMP CB2

CUTLER-HAMMERFDFDTrip 175.0 ASettings Phase Fixed

FIRE PUMP CB3

FIRE PUMP FEED1

FIRE PUMP FEED2

FIRE PUMP FEED3

FIRE PUMP FEED4

FIRE PUMP XFMR

SIEMENSED6 Sentron, 2 & 3-PoleED6, 3-PoleTrip 125.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (800A)

FIRE PUMP CB1

SIEMENSLXD6-A SentronLXD6-ATrip 600.0 ASettings Phase Thermal Curve (Fixed) INST (LO-HI) HI (6000A)

FIRE PUMP CB2

CUTLER-HAMMERFDFDTrip 175.0 ASettings Phase Fixed

FIRE PUMP CB3

FIRE PUMP FEED1

FIRE PUMP FEED2

FIRE PUMP FEED3

FIRE PUMP FEED4

FIRE PUMP XFMR

FIRE PUMP FEED1

FIRE PUMP

FIRE PUMP CB1

FIRE PUMP FEED2

FIRE PUMP CB2

FIRE PUMP FEED3

FIRE PUMP CB3

FIRE PUMP FEED4

S

P

FIRE PUMP XFMR

FIRE PUMP UTIL

TCC NAME: FIRE PUMPREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: FIRE PUMP

Page 256: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4J FEED

TX Inrush

1500KVA XFMR3

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

4J CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

4J FEED

1500KVA XFMR3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

4J CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

4J FEED

1500KVA XFMR3

PNL 4J

4J CB

4J FEED

USB-5

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL

TCC NAME: PNL 4JREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4J

Page 257: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4J FEED

TX Inrush

1500KVA XFMR3

SF1A FUSE FEEDSF1A FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

4J CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

SIEMENSEHEHTrip 60.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1600A)

SF1A CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

SF1A FUSE

4J FEED

1500KVA XFMR3

SF1A FUSE FEED

SF1A FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

4J CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

SIEMENSEHEHTrip 60.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1600A)

SF1A CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

SF1A FUSE

4J FEED

1500KVA XFMR3

SF1A FUSE FEED

SF1A FEED

PNL 4J

4J CB

4J FEED

USB-5

3200 A Mai n CB3

S

P

1500KVA XFMR3

UTIL

SF1A CB

SF1A FUSE FEED

SF1A FUSE

SF1A FEEDSF1A

TCC NAME: SF1AREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: SF1A

Page 258: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

4J FEED

TX Inrush

1500KVA XFMR3

SF1B FUSE FEEDSF1B FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

4J CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

SF1B FUSE

SIEMENSEHEHTrip 70.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1600A)

SF1B CB

4J FEED

1500KVA XFMR3

SF1B FUSE FEEDSF1B FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

4J CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

SF1B FUSE

SIEMENSEHEHTrip 70.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1600A)

SF1B CB

4J FEED

1500KVA XFMR3

SF1B FUSE FEEDSF1B FEED

PNL 4J

4J CB

4J FEED

USB-5

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL

SF1B FUSE FEED

SF1B FUSE

SF1B FEEDSF1B

SF1B CB

TCC NAME: SF1BREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: SF1B

Page 259: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR34J FEED

SFGA FUSE FEEDSFGA FEED

PNL 4F-13 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

4J CB

CUTLER-HAMMERFDFDTrip 35.0 ASettings Phase Fixed

4F-13 CB

LITTELFUSEIDSR, 600V Class RK5IDSRTrip 60.0 A

SFGA FUSE 1500KVA XFMR3

4J FEED

SFGA FUSE FEED

SFGA FEED

PNL 4F-13 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

4J CB

CUTLER-HAMMERFDFDTrip 35.0 ASettings Phase Fixed

4F-13 CB

LITTELFUSEIDSR, 600V Class RK5IDSRTrip 60.0 A

SFGA FUSE 1500KVA XFMR3

4J FEED

SFGA FUSE FEED

SFGA FEED

PNL 4F-13 FEED

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL

USB-5

4J CB

4J FEED

4F-13 CB

SFGA FUSE FEED

SFGA

SFGA FUSE

SFGA FEED

PNL 4F-13

PNL 4F-13 FEED

PNL 4J

TCC NAME: SFGAREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: SFGA

Page 260: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR34J FEEDPNL 4F-13 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

4J CB

CUTLER-HAMMERFDFDTrip 35.0 ASettings Phase Fixed

4F-13 CB

1500KVA XFMR3

4J FEED

PNL 4F-13 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

4J CB

CUTLER-HAMMERFDFDTrip 35.0 ASettings Phase Fixed

4F-13 CB

1500KVA XFMR3

4J FEED

PNL 4F-13 FEED

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL

USB-5

4J CB

4J FEED

4F-13 CB

PNL 4F-13

PNL 4F-13 FEED

PNL 4J

TCC NAME: PNL 4F-13REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4F-13

Page 261: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

ROOF MOTOR 1 FEEDROOF MOTOR 2 FEED

ATS-1 EM FEED

ROOF MOTOR FEED

EMDP-P FEED

0.5 1 10 100

1K 10K

100K

1M

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

SQUARE DPowerpact P-Frame, 6.0A/P/HPGTrip 400.0 ASettings Phase LTPU/LTD (A 0.4-1.0 x S) 1 (400A); 16 STPU (1.5-10 x LTPU) 10 (4000A) STD (0-0.4) 0.4 (I^2t Out) INST (2-15 x S) 3 (1200A)

GEN SET CB

CUTLER-HAMMERHKDHKDTrip 125.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (1250A)

ROOF MOTOR CB

ROOF MOTOR 1 FEED

ROOF MOTOR 2 FEED

ATS-1 EM FEED

ROOF MOTOR FEED

EMDP-P FEED

SQUARE DPowerpact P-Frame, 6.0A/P/HPGTrip 400.0 ASettings Phase LTPU/LTD (A 0.4-1.0 x S) 1 (400A); 16 STPU (1.5-10 x LTPU) 10 (4000A) STD (0-0.4) 0.4 (I^2t Out) INST (2-15 x S) 3 (1200A)

GEN SET CB

CUTLER-HAMMERHKDHKDTrip 125.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (1250A)

ROOF MOTOR CB

ROOF MOTOR 1 FEED

ROOF MOTOR 2 FEED

ATS-1 EM FEED

ROOF MOTOR FEED

EMDP-P FEED

GEN-1

ROOF MOTOR 1 FEED

ROOF TOP MOTOR 1

ROOF MOTOR 2 FEED

ROOF TOP MOTOR 2

GEN SET CB

ATS-1 EM FEED

ROOF MOTOR CB

ROOF MOTOR FEED

EMDP-P FEED

E N

ATS-1

EMDP-P

TCC NAME: EM_ROOFTOP_MOTORSREFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: EM_ROOFTOP_MOTORS

Page 262: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Gen SC

GEN-1

ATS-1 EM FEEDEMDP-P FEED

0.5 1 10 100

1K 10K

100K

1M

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

SQUARE DPowerpact P-Frame, 6.0A/P/HPGTrip 400.0 ASettings Phase LTPU/LTD (A 0.4-1.0 x S) 1 (400A); 16 STPU (1.5-10 x LTPU) 10 (4000A) STD (0-0.4) 0.4 (I^2t Out) INST (2-15 x S) 3 (1200A)

GEN SET CB

GEN-1

ATS-1 EM FEED

EMDP-P FEED

SQUARE DPowerpact P-Frame, 6.0A/P/HPGTrip 400.0 ASettings Phase LTPU/LTD (A 0.4-1.0 x S) 1 (400A); 16 STPU (1.5-10 x LTPU) 10 (4000A) STD (0-0.4) 0.4 (I^2t Out) INST (2-15 x S) 3 (1200A)

GEN SET CB

GEN-1

ATS-1 EM FEED

EMDP-P FEED

GEN-1

GEN SET CB

ATS-1 EM FEED

EMDP-P FEED

E N

ATS-1

EMDP-P

TCC NAME: EM_EMDP-PREFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: EM_EMDP-P

Page 263: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Gen SC

GEN-1

ATS-1 EM FEEDEMDP-P FEED

EMCC-T6 FEED

0.5 1 10 100

1K 10K

100K

1M

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

SQUARE DPowerpact P-Frame, 6.0A/P/HPGTrip 400.0 ASettings Phase LTPU/LTD (A 0.4-1.0 x S) 1 (400A); 16 STPU (1.5-10 x LTPU) 10 (4000A) STD (0-0.4) 0.4 (I^2t Out) INST (2-15 x S) 3 (1200A)

GEN SET CB

SQUARE DEJEJTrip 40.0 ASettings Phase Fixed

EMCC-T6 CB

GEN-1

ATS-1 EM FEED

EMDP-P FEED

EMCC-T6 FEED

SQUARE DPowerpact P-Frame, 6.0A/P/HPGTrip 400.0 ASettings Phase LTPU/LTD (A 0.4-1.0 x S) 1 (400A); 16 STPU (1.5-10 x LTPU) 10 (4000A) STD (0-0.4) 0.4 (I^2t Out) INST (2-15 x S) 3 (1200A)

GEN SET CB

SQUARE DEJEJTrip 40.0 ASettings Phase Fixed

EMCC-T6 CB

GEN-1

ATS-1 EM FEED

EMDP-P FEED

EMCC-T6 FEED

GEN-1

GEN SET CB

ATS-1 EM FEED

EMDP-P FEED

E N

ATS-1

EMDP-P

EMCC-T6 CB

EMCC-T6 FEED

PNL EMCC-T6

TCC NAME: EM_PNL EMCC-T6REFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: EM_PNL EMCC-T6

Page 264: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Gen SC

GEN-1

ATS-1 EM FEEDEMDP-P FEED

4E FEED

0.5 1 10 100

1K 10K

100K

1M

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

SQUARE DPowerpact P-Frame, 6.0A/P/HPGTrip 400.0 ASettings Phase LTPU/LTD (A 0.4-1.0 x S) 1 (400A); 16 STPU (1.5-10 x LTPU) 10 (4000A) STD (0-0.4) 0.4 (I^2t Out) INST (2-15 x S) 3 (1200A)

GEN SET CB

SQUARE DEJEJTrip 100.0 ASettings Phase Fixed

4E CB

GEN-1

ATS-1 EM FEED

EMDP-P FEED

4E FEED

SQUARE DPowerpact P-Frame, 6.0A/P/HPGTrip 400.0 ASettings Phase LTPU/LTD (A 0.4-1.0 x S) 1 (400A); 16 STPU (1.5-10 x LTPU) 10 (4000A) STD (0-0.4) 0.4 (I^2t Out) INST (2-15 x S) 3 (1200A)

GEN SET CB

SQUARE DEJEJTrip 100.0 ASettings Phase Fixed

4E CB

GEN-1

ATS-1 EM FEED

EMDP-P FEED

4E FEED

GEN-1

GEN SET CB

ATS-1 EM FEED

EMDP-P FEED

E N

ATS-1

EMDP-P

4E CB

4E FEED

PNL 4E

TCC NAME: EM_PNL 4EREFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: EM_PNL 4E

Page 265: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Gen SC

GEN-1

ATS-1 EM FEEDEMDP-P FEED

14E FEED

0.5 1 10 100

1K 10K

100K

1M

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

SQUARE DPowerpact P-Frame, 6.0A/P/HPGTrip 400.0 ASettings Phase LTPU/LTD (A 0.4-1.0 x S) 1 (400A); 16 STPU (1.5-10 x LTPU) 10 (4000A) STD (0-0.4) 0.4 (I^2t Out) INST (2-15 x S) 3 (1200A)

GEN SET CB

SQUARE DEJEJTrip 100.0 ASettings Phase Fixed

14E CB

GEN-1

ATS-1 EM FEED

EMDP-P FEED

14E FEED

SQUARE DPowerpact P-Frame, 6.0A/P/HPGTrip 400.0 ASettings Phase LTPU/LTD (A 0.4-1.0 x S) 1 (400A); 16 STPU (1.5-10 x LTPU) 10 (4000A) STD (0-0.4) 0.4 (I^2t Out) INST (2-15 x S) 3 (1200A)

GEN SET CB

SQUARE DEJEJTrip 100.0 ASettings Phase Fixed

14E CB

GEN-1

ATS-1 EM FEED

EMDP-P FEED

14E FEED

GEN-1

ATS-1 EM FEED

GEN SET CB

E N

ATS-1

EMDP-P FEED

EMDP-P

PNL 14E

14E CB

14E FEED

TCC NAME: EM_PNL 14EREFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: EM_PNL 14E

Page 266: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

ATS-1 FEEDEMDP-P FEED

TX Inrush

1500KVA XFMR2

ROOF MOTOR 1 FEEDROOF MOTOR 2 FEEDROOF MOTOR FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERHKDHKDTrip 125.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (1250A)

ROOF MOTOR CB

ATS-1 FEED

EMDP-P FEED

1500KVA XFMR2

ROOF MOTOR 1 FEEDROOF MOTOR 2 FEED

ROOF MOTOR FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

CUTLER-HAMMERHKDHKDTrip 125.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (1250A)

ROOF MOTOR CB

ATS-1 FEED

EMDP-P FEED

1500KVA XFMR2

ROOF MOTOR 1 FEEDROOF MOTOR 2 FEED

ROOF MOTOR FEED

400 A ATS-1 CB

ATS-1 FEED

EMDP-P FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

E N

ATS-1

EMDP-P

USB-2

ROOF MOTOR 1 FEED

ROOF TOP MOTOR 1

ROOF MOTOR 2 FEED

ROOF TOP MOTOR 2

ROOF MOTOR CB

ROOF MOTOR FEED

TCC NAME: ROOFTOP_MOTORSREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: ROOFTOP_MOTORS

Page 267: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

EMCC-T6 FEED

ATS-1 FEEDEMDP-P FEED

TX Inrush

1500KVA XFMR2

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

SQUARE DEJEJTrip 40.0 ASettings Phase Fixed

EMCC-T6 CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

EMCC-T6 FEED

ATS-1 FEED

EMDP-P FEED

1500KVA XFMR2

SQUARE DEJEJTrip 40.0 ASettings Phase Fixed

EMCC-T6 CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

EMCC-T6 FEED

ATS-1 FEED

EMDP-P FEED

1500KVA XFMR2

USB-2

EMCC-T6 CB

EMCC-T6 FEED

PNL EMCC-T6

EMDP-P

400 A ATS-1 CB

ATS-1 FEED

EMDP-P FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

E N

ATS-1

TCC NAME: PNL EMCC-T6REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL EMCC-T6

Page 268: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

ATS-1 FEEDEMDP-P FEED

TX Inrush

1500KVA XFMR2

4E FEEDXFMR 2E FEED

TX Inrush

15KVA XFMR 2E2E FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

SQUARE DEJEJTrip 100.0 ASettings Phase Fixed

4E CB

CUTLER-HAMMERFDFDTrip 30.0 ASettings Phase Fixed

XFMR 2E CB

ATS-1 FEED

EMDP-P FEED

1500KVA XFMR2

4E FEED

XFMR 2E FEED

15KVA XFMR 2E

2E FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

SQUARE DEJEJTrip 100.0 ASettings Phase Fixed

4E CB

CUTLER-HAMMERFDFDTrip 30.0 ASettings Phase Fixed

XFMR 2E CB

ATS-1 FEED

EMDP-P FEED

1500KVA XFMR2

4E FEED

XFMR 2E FEED

15KVA XFMR 2E

2E FEED

USB-2

EMDP-P

400 A ATS-1 CB

ATS-1 FEED

EMDP-P FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

E N

ATS-1

4E CB

4E FEED

XFMR 2E CB

XFMR 2E FEED

S

P

15KVA XFMR 2E

2E FEED

PNL 4E

PNL 2E

TCC NAME: PNL 2EREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2E

Page 269: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

ATS-1 FEEDEMDP-P FEED

TX Inrush

1500KVA XFMR2

4E FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CBCUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

SQUARE DEJEJTrip 100.0 ASettings Phase Fixed

4E CB

ATS-1 FEED

EMDP-P FEED

1500KVA XFMR2

4E FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CBCUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

SQUARE DEJEJTrip 100.0 ASettings Phase Fixed

4E CB

ATS-1 FEED

EMDP-P FEED

1500KVA XFMR2

4E FEED

USB-2

EMDP-P

400 A ATS-1 CB

ATS-1 FEED

EMDP-P FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

E N

ATS-1

4E CB

4E FEED

PNL 4E

TCC NAME: PNL 4EREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4E

Page 270: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

ATS-1 FEEDEMDP-P FEED

TX Inrush

1500KVA XFMR2

14E FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

SQUARE DEJEJTrip 100.0 ASettings Phase Fixed

14E CB

ATS-1 FEED

EMDP-P FEED

1500KVA XFMR2

14E FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

SQUARE DEJEJTrip 100.0 ASettings Phase Fixed

14E CB

ATS-1 FEED

EMDP-P FEED

1500KVA XFMR2

14E FEED

USB-2

EMDP-P

400 A ATS-1 CB

ATS-1 FEED

EMDP-P FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

E N

ATS-1

14E CB

14E FEED

PNL 14E

TCC NAME: PNL 14EREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 14E

Page 271: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

ATS-1 FEEDEMDP-P FEED

TX Inrush

1500KVA XFMR2

14E FEEDXFMR 12E FEED

TX Inrush

45KVA XFMR 12E12E FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

SQUARE DEJEJTrip 100.0 ASettings Phase Fixed

14E CB

CUTLER-HAMMERFDFDTrip 90.0 ASettings Phase Fixed

XFMR 12E CB

ATS-1 FEEDEMDP-P FEED

1500KVA XFMR2

14E FEED

XFMR 12E FEED

45KVA XFMR 12E

12E FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

SQUARE DEJEJTrip 100.0 ASettings Phase Fixed

14E CB

CUTLER-HAMMERFDFDTrip 90.0 ASettings Phase Fixed

XFMR 12E CB

ATS-1 FEEDEMDP-P FEED

1500KVA XFMR2

14E FEED

XFMR 12E FEED

45KVA XFMR 12E

12E FEED

USB-2

EMDP-P

400 A ATS-1 CB

ATS-1 FEED

EMDP-P FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

E N

ATS-1

14E CB

14E FEED

PNL 14E

XFMR 12E CB

XFMR 12E FEED

S

P

45KVA XFMR 12E

12E FEED

PNL 12E

TCC NAME: PNL 12EREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 12E

Page 272: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

ATS-1 FEEDEMDP-P FEED

TX Inrush

1500KVA XFMR2

14E FEEDXFMR P1 FEED

TX Inrush

30KVA XFMR P1P1 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

SQUARE DEJEJTrip 100.0 ASettings Phase Fixed

14E CB

CUTLER-HAMMERFDFDTrip 50.0 ASettings Phase Fixed

XFMR P1 CB

ATS-1 FEEDEMDP-P FEED

1500KVA XFMR2

14E FEED

XFMR P1 FEED

30KVA XFMR P1

P1 FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A ATS-1 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 3 (9600A)

3200 A Main CB2

SQUARE DEJEJTrip 100.0 ASettings Phase Fixed

14E CB

CUTLER-HAMMERFDFDTrip 50.0 ASettings Phase Fixed

XFMR P1 CB

ATS-1 FEEDEMDP-P FEED

1500KVA XFMR2

14E FEED

XFMR P1 FEED

30KVA XFMR P1

P1 FEED

USB-2

EMDP-P

400 A ATS-1 CB

ATS-1 FEED

EMDP-P FEED

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

E N

ATS-1

14E CB

14E FEED

PNL 14E

XFMR P1 CB

XFMR P1 FEED

S

P

30KVA XFMR P1

P1 FEED

PNL P1

TCC NAME: PNL P1REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL P1

Page 273: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4A FEEDXFMR 2GA FEED

TX Inrush

45KVA XFMR 2GA2GA FEED2GA2 FEED

TX Inrush

1500KVA XFMR3

0.5 1 10 100

1K 10K

100K

1M

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4A CB

CUTLER-HAMMEREHDEHDTrip 30.0 ASettings Phase Fixed

XFMR 2GA CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

P4A FEED

XFMR 2GA FEED

45KVA XFMR 2GA

2GA FEED

2GA2 FEED

1500KVA XFMR3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4A CB

CUTLER-HAMMEREHDEHDTrip 30.0 ASettings Phase Fixed

XFMR 2GA CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

P4A FEED

XFMR 2GA FEED

45KVA XFMR 2GA

2GA FEED

2GA2 FEED

1500KVA XFMR3

800 A P4A CB

P4A FEED

PNL P4A

XFMR 2GA CB

XFMR 2GA FEED

S

P

45KVA XFMR 2GA

2GA FEED

PNL 2GA

PNL 2GA2

2GA2 FEED

USB-5

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL

TCC NAME: PNL 2GA2REFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: PNL 2GA2

Page 274: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3P4A FEED

XFMR 2GB FEED

TX Inrush

45KVA XFMR 2GB2GB FEED2GB2 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4A CB

CUTLER-HAMMEREHDEHDTrip 70.0 ASettings Phase Fixed

XFMR 2GB CB

1500KVA XFMR3

P4A FEEDXFMR 2GB FEED

45KVA XFMR 2GB

2GB FEED2GB2 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4A CB

CUTLER-HAMMEREHDEHDTrip 70.0 ASettings Phase Fixed

XFMR 2GB CB

1500KVA XFMR3

P4A FEEDXFMR 2GB FEED

45KVA XFMR 2GB

2GB FEED2GB2 FEED

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A P4A CB

P4A FEED

XFMR 2GB CB

XFMR 2GB FEED

S

P45KVA XFMR 2GB

2GB FEED

PNL 2GB

PNL 2GB2

2GB2 FEED

PNL P4A

USB-5

TCC NAME: PNL 2GB2REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2GB2

Page 275: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3P4A FEED

PNL 4G-104 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4A CB

SIEMENSEHEHTrip 125.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1150A)

4G-104 CB

1500KVA XFMR3

P4A FEED

PNL 4G-104 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4A CB

SIEMENSEHEHTrip 125.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1150A)

4G-104 CB

1500KVA XFMR3

P4A FEED

PNL 4G-104 FEED

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A P4A CB

P4A FEED

PNL P4A

USB-5

4G-104 CB

PNL 4G-104

PNL 4G-104 FEED

TCC NAME: PNL 4G-104REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4G-104

Page 276: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

PNL 4B FEED

2B1 FEED2B2 FEED

TX Inrush

1500KVA XFMR3P4A FEED

XFMR 2B1 FEED

TX Inrush

75KVA XFMR 2B1

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

SIEMENSF6F6Trip 175.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

4B CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4A CB

SQUARE DEHEHTrip 20.0 ASettings Phase Fixed

2B1 CB

PNL 4B FEED

2B1 FEED2B2 FEED

1500KVA XFMR3

P4A FEEDXFMR 2B1 FEED

75KVA XFMR 2B1

SIEMENSF6F6Trip 175.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

4B CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4A CB

SQUARE DEHEHTrip 20.0 ASettings Phase Fixed

2B1 CB

PNL 4B FEED

2B1 FEED2B2 FEED

1500KVA XFMR3

P4A FEEDXFMR 2B1 FEED

75KVA XFMR 2B1

4B CB

PNL 4B

PNL 4B FEED

2B1 FEED

PNL 2B1

2B2 FEED

PNL 2B2

2B1 CB

XFMR 2B1 FEED

S

P75KVA XFMR 2B1

PNL P4A

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A P4A CB

P4A FEED

USB-5

TCC NAME: PNL 2B2REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2B2

Page 277: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P4A FEED

PNL 4B FEED

TX Inrush

1500KVA XFMR3

P4B FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4A CB

SIEMENSF6F6Trip 175.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

4B CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4B CB

P4A FEED

PNL 4B FEED

1500KVA XFMR3P4B FEED

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4A CB

SIEMENSF6F6Trip 175.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

4B CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4B CB

P4A FEED

PNL 4B FEED

1500KVA XFMR3P4B FEED

800 A P4A CB

P4A FEED

4B CB

PNL 4B

PNL 4B FEED

USB-5

PNL P4A

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL

TCC NAME: PNL 4BREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4B

Page 278: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3P4B FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4B CB

1500KVA XFMR3

P4B FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4B CB

1500KVA XFMR3

P4B FEED

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A P4B CB

P4B FEED

PNL P4B

USB-5

TCC NAME: PNL P4BREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL P4B

Page 279: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3P4B FEED

PNL 4C-12 FEEDXFMR 2CA FEED

TX Inrush

50KVA XFMR 2CA

2CA FEED

2C1 FEED2C2-12 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4B CB

SIEMENSF6F6Trip 175.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

4C-12 CB

CUTLER-HAMMERBAB, 1-PoleBABTrip 20.0 ASettings Phase Fixed

2CA CB

1500KVA XFMR3

P4B FEED

PNL 4C-12 FEED

XFMR 2CA FEED

50KVA XFMR 2CA

2CA FEED2C1 FEED

2C2-12 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4B CB

SIEMENSF6F6Trip 175.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

4C-12 CB

CUTLER-HAMMERBAB, 1-PoleBABTrip 20.0 ASettings Phase Fixed

2CA CB

1500KVA XFMR3

P4B FEED

PNL 4C-12 FEED

XFMR 2CA FEED

50KVA XFMR 2CA

2CA FEED2C1 FEED

2C2-12 FEED

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A P4B CB

P4B FEED

PNL P4B

4C-12 CB

PNL 4C-12

PNL 4C-12 FEED

XFMR 2CA FEED

S

P50KVA XFMR 2CA

2CA FEED

PNL 2CA

2C1 FEED

PNL 2C1

2C2-12 FEED

PNL 2C2-12

2CA CB

USB-5

TCC NAME: PNL 2C2-12REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2C2-12

Page 280: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3P4B FEED

PNL 4C-12 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4B CB

SIEMENSF6F6Trip 175.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

4C-12 CB

1500KVA XFMR3

P4B FEED

PNL 4C-12 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4B CB

SIEMENSF6F6Trip 175.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

4C-12 CB

1500KVA XFMR3

P4B FEED

PNL 4C-12 FEED

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A P4B CB

P4B FEED

4C-12 CB

PNL 4C-12

PNL 4C-12 FEED

PNL P4B

USB-5TCC NAME: PNL 4C2-12REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4C2-12

Page 281: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3P4B FEED

PNL 4H FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4B CB

SIEMENSF6F6Trip 175.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

4CH CB

1500KVA XFMR3

P4B FEED

PNL 4H FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A P4B CB

SIEMENSF6F6Trip 175.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

4CH CB

1500KVA XFMR3

P4B FEED

PNL 4H FEED

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A P4B CB

P4B FEED

USB-5

PNL P4B

4CH CB

PNL 4H

PNL 4H FEED

TCC NAME: PNL 4HREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4H

Page 282: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3P4D FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

400 A P4D CB

1500KVA XFMR3

P4D FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (5600A)

400 A P4D CB

1500KVA XFMR3

P4D FEED

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 400 A P4D CB

P4D FEED

PNL P4D

USB-5

TCC NAME: PNL P4DREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL P4D

Page 283: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

XFMR P2D FEED

TX Inrush

45KVA XFMR P2DP2D FUSE FEEDP2D FEED

TX Inrush

1500KVA XFMR3P4D FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERHFDHFDTrip 40.0 ASettings Phase Fixed

P2D CB

BUSSMANNFRN-R, 250V Class RK5FRN-RTrip 100.0 A

P2D FUSE

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A P4D CB

XFMR P2D FEED

45KVA XFMR P2D

P2D FUSE FEED

P2D FEED

1500KVA XFMR3

P4D FEED

CUTLER-HAMMERHFDHFDTrip 40.0 ASettings Phase Fixed

P2D CB

BUSSMANNFRN-R, 250V Class RK5FRN-RTrip 100.0 A

P2D FUSE

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A P4D CB

XFMR P2D FEED

45KVA XFMR P2D

P2D FUSE FEED

P2D FEED

1500KVA XFMR3

P4D FEED

P2D CB

XFMR P2D FEED

S

P

45KVA XFMR P2D

P2D FUSE FEED

P2D FUSE

P2D FEED

PNL P2D

PNL P4D

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 400 A P4D CB

P4D FEED

USB-5

TCC NAME: PNL P2DREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL P2D

Page 284: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3P4D FEED

PNL 4D1 FEEDXFMR 2D1 FEED

TX Inrush

45KVA XFMR 2D12D1-02 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A P4D CBCUTLER-HAMMERFDFDTrip 100.0 ASettings Phase Fixed

4D1 CB

CUTLER-HAMMERGHBGHBTrip 60.0 ASettings Phase Thermal Curve INST (Fixed) Fixed (800A)

2D1 CB

1500KVA XFMR3

P4D FEED

PNL 4D1 FEED

XFMR 2D1 FEED

45KVA XFMR 2D1

2D1-02 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A P4D CBCUTLER-HAMMERFDFDTrip 100.0 ASettings Phase Fixed

4D1 CB

CUTLER-HAMMERGHBGHBTrip 60.0 ASettings Phase Thermal Curve INST (Fixed) Fixed (800A)

2D1 CB

1500KVA XFMR3

P4D FEED

PNL 4D1 FEED

XFMR 2D1 FEED

45KVA XFMR 2D1

2D1-02 FEED

PNL P4D

3200 A Main CB3

S

P

1500KVA XFM R3

UTIL 400 A P4D CB

P4D FEED

USB-5

4D1 CB

PNL 4D1

PNL 4D1 FEED

XFMR 2D1 FEED

S

P45KVA XFM R 2D1

2D1-02 FEED

PNL 2D1-02

2D1 CB

TCC NAME: PNL 2D1-02REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2D1-02

Page 285: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3P4D FEED

XFMR KL FEED

TX Inrush

112.5KVA XFMR KLKL FUSE FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A P4D CB

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

KL CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 400.0 A

KL FUSE

1500KVA XFMR3

P4D FEED

XFMR KL FEED

112.5KVA XFMR KL

KL FUSE FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A P4D CB

CUTLER-HAMMERFDFDTrip 200.0 ASettings Phase Fixed

KL CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 400.0 A

KL FUSE

1500KVA XFMR3

P4D FEED

XFMR KL FEED

112.5KVA XFMR KL

KL FUSE FEED

PNL P4D

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 400 A P4D CB

P4D FEED

USB-5

KL CB

XFMR KL FEED

S

P112.5KVA XFMR KL

KL FUSE FEED

KL FUSE

PNL KL

TCC NAME: PNL KLREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL KL

Page 286: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3P4D FEED

XFMR 2C-12 FEED

TX Inrush

75KVA XFMR 2C-122C-12 FEED2C3 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A P4D CB

CUTLER-HAMMERFDFDTrip 110.0 ASettings Phase Fixed

2C-12 CB

1500KVA XFMR3

P4D FEED

XFMR 2C-12 FEED

75KVA XFMR 2C-12

2C-12 FEED

2C3 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 400.0 APlug 400.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (400A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (4000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (5600A)

400 A P4D CB

CUTLER-HAMMERFDFDTrip 110.0 ASettings Phase Fixed

2C-12 CB

1500KVA XFMR3

P4D FEED

XFMR 2C-12 FEED

75KVA XFMR 2C-12

2C-12 FEED

2C3 FEED

PNL P4D

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 400 A P4D CB

P4D FEED

USB-5

2C-12 CB

XFMR 2C-12 FEED

S

P75KVA XFMR 2C-12

2C-12 FEED

PNL 2C-12

2C3 FEED

PNL 2C3

TCC NAME: PNL 2C3REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2C3

Page 287: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

P-19-1 FEED

TX Inrush

1500KVA XFMR3MCC3 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 12.0 A

P-19-1 FUSE

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

P-19-1 FEED

1500KVA XFMR3

MCC3 FEED

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 12.0 A

P-19-1 FUSE

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

P-19-1 FEED

1500KVA XFMR3

MCC3 FEED

P-19-1 FUSE

P-19-1

P-19-1 FEED

MCC-3

USB-5

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A MCC3 CB

MCC3 FEED

TCC NAME: P-19-1REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: P-19-1

Page 288: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3MCC3 FEED

P-19-2 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 12.0 A

P-19-2 FUSE

1500KVA XFMR3

MCC3 FEED

P-19-2 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 12.0 A

P-19-2 FUSE

1500KVA XFMR3

MCC3 FEED

P-19-2 FEED

MCC-3

USB-5

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A MCC3 CB

MCC3 FEED

P-19-2 FUSE

P-19-2

P-19-2 FEED

TCC NAME: P-19-2REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: P-19-2

Page 289: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3MCC3 FEED

2P-1 CB FEEDXFMR 2P-1 FEED

TX Inrush

75KVA XFMR 2P-12P-1 FEED

2P-2 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

LITTELFUSEFLSR, 600V RK5FLSRTrip 100.0 A

2P-1 FUSE

SQUARE DKAKATrip 100.0 ASettings Phase Thermal Curve INST HI (1000A)

2P-1 CB

1500KVA XFMR3

MCC3 FEED

2P-1 CB FEED

XFMR 2P-1 FEED

75KVA XFMR 2P-1

2P-1 FEED

2P-2 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

LITTELFUSEFLSR, 600V RK5FLSRTrip 100.0 A

2P-1 FUSE

SQUARE DKAKATrip 100.0 ASettings Phase Thermal Curve INST HI (1000A)

2P-1 CB

1500KVA XFMR3

MCC3 FEED

2P-1 CB FEED

XFMR 2P-1 FEED

75KVA XFMR 2P-1

2P-1 FEED

2P-2 FEED

MCC-3

USB-5

3200 A Main CB3

S

P

1500KVA XFMR 3

UTIL 800 A MCC3 CB

MCC3 FEED

2P-1 FUSE

2P-1 CB FEED

2P-1 CB

XFMR 2P-1 FEED

S

P75KVA XFM R 2P-1

2P-1 FEED

PNL 2P-1

2P-2 FEED

PNL 2P-2

TCC NAME: PNL 2P-2REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2P-2

Page 290: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3MCC3 FEED

ELEV 4&5 FEEDELEV 4 FUSE FEEDELEV 4 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

LITTELFUSEFLSR, 600V RK5FLSRTrip 100.0 A

ELEV 4&5 FUSE

LITTELFUSEIDSR, 600V Class RK5IDSRTrip 50.0 A

ELEV 4 FUSE 1500KVA XFMR3

MCC3 FEED

ELEV 4&5 FEED

ELEV 4 FUSE FEED

ELEV 4 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

LITTELFUSEFLSR, 600V RK5FLSRTrip 100.0 A

ELEV 4&5 FUSE

LITTELFUSEIDSR, 600V Class RK5IDSRTrip 50.0 A

ELEV 4 FUSE 1500KVA XFMR3

MCC3 FEED

ELEV 4&5 FEED

ELEV 4 FUSE FEED

ELEV 4 FEED

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A MCC3 CB

MCC3 FEED

ELEV 4&5 FUSE

ELEV 4&5 FEED

ELEV 4 FUSE FEED

ELEV 4

ELEV 4 FUSE

ELEV 4 FEED

MCC-3

USB-5

TCC NAME: ELEV 4REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: ELEV 4

Page 291: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3MCC3 FEED

ELEV 5 FUSE FEEDELEV 5 FEEDELEV 4&5 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CBLITTELFUSEIDSR, 600V Class RK5IDSRTrip 50.0 A

ELEV 5 FUSE

LITTELFUSEFLSR, 600V RK5FLSRTrip 100.0 A

ELEV 4&5 FUSE

1500KVA XFMR3

MCC3 FEED

ELEV 5 FUSE FEED

ELEV 5 FEED

ELEV 4&5 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CBLITTELFUSEIDSR, 600V Class RK5IDSRTrip 50.0 A

ELEV 5 FUSE

LITTELFUSEFLSR, 600V RK5FLSRTrip 100.0 A

ELEV 4&5 FUSE

1500KVA XFMR3

MCC3 FEED

ELEV 5 FUSE FEED

ELEV 5 FEED

ELEV 4&5 FEED

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A MCC3 CB

MCC3 FEED

MCC-3

USB-5

ELEV 5 FUSE FEED

ELEV 5

ELEV 5 FUSE

ELEV 5 FEED

ELEV 4&5 FUSE

ELEV 4&5 FEED

TCC NAME: ELEV 5REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: ELEV 5

Page 292: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3MCC3 FEED

PNL 4K PENTHOUSE FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

SIEMENSFJFJTrip 225.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1480A)

4K PENTHOUSE CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

PNL 4K PENTHOUSE FUSE

1500KVA XFMR3

MCC3 FEED

PNL 4K PENTHOUSE FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

SIEMENSFJFJTrip 225.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1480A)

4K PENTHOUSE CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

PNL 4K PENTHOUSE FUSE

1500KVA XFMR3

MCC3 FEED

PNL 4K PENTHOUSE FEED

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A MCC3 CB

MCC3 FEED

MCC-3

USB-5

4K PENTHOUSE CB

PNL 4K PENTHOUSE FEED

PNL 4K PENTHOUSE FUSE

PNL 4K PENTHOUSE

TCC NAME: PNL 4K PENTHOUSEREFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 4K PENTHOUSE

Page 293: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

XFMR 2K FEED

TX Inrush

PNL 4K PENTHOUSE FEED

TX Inrush

1500KVA XFMR3MCC3 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 40.0 ASettings Phase Fixed

2K CB

SIEMENSFJFJTrip 225.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1480A)

4K PENTHOUSE CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

PNL 4K PENTHOUSE FUSE

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

XFMR 2K FEED

9KVA XFMR 2K

2K FEED

2K1 FEED

PNL 4K PENTHOUSE FEED

1500KVA XFMR3

MCC3 FEED

CUTLER-HAMMERFDFDTrip 40.0 ASettings Phase Fixed

2K CB

SIEMENSFJFJTrip 225.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1480A)

4K PENTHOUSE CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

PNL 4K PENTHOUSE FUSE

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

XFMR 2K FEED

9KVA XFMR 2K

2K FEED

2K1 FEED

PNL 4K PENTHOUSE FEED

1500KVA XFMR3

MCC3 FEED

2K CB

XFMR 2K FEED

S

P9KVA XFMR 2K

2K FEED

PNL 2 K

2K1 FEED

PNL 2K1

PNL 4 K PENTHOUSE

4K PENTHOUSE CB

PNL 4K PENTHOUSE FEED

PNL 4K PENTHOUSE FUSE

MCC-3

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A MCC3 CB

MCC3 FEED

USB-5

TCC NAME: PNL 2K1REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2K1

Page 294: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

PNL 4K PENTHOUSE FEED

TX Inrush

1500KVA XFMR3MCC3 FEED

TOWER41 FEEDTOWER41 FUSE FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

SIEMENSFJFJTrip 225.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1480A)

4K PENTHOUSE CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

PNL 4K PENTHOUSE FUSE

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CBBUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

TOWER41 FUSE

CUTLER-HAMMERFDFDTrip 50.0 ASettings Phase Fixed

TOWER41 CB

PNL 4K PENTHOUSE FEED

1500KVA XFMR3

MCC3 FEED

TOWER41 FEED

TOWER41 FUSE FEED

SIEMENSFJFJTrip 225.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1480A)

4K PENTHOUSE CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

PNL 4K PENTHOUSE FUSE

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I^2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CBBUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

TOWER41 FUSE

CUTLER-HAMMERFDFDTrip 50.0 ASettings Phase Fixed

TOWER41 CB

PNL 4K PENTHOUSE FEED

1500KVA XFMR3

MCC3 FEED

TOWER41 FEED

TOWER41 FUSE FEED

PNL 4K PENT HOUSE

4K PENTHOUSE CB

PNL 4K PENTHOUSE FEED

PNL 4K PENTHOUSE FUSE

MCC-3

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A MCC3 CB

MCC3 FEED

USB-5

TOWER41 FUSE

TOWER41

TOWER41 FEED

TOWER41 CB

TOWER41 FUSE FEED

TCC NAME: TOWER41REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: TOWER41

Page 295: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3MCC3 FEED

PNL 4K PENTHOUSE FEEDTOWER42 FEEDTOWER42 FUSE FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

SIEMENSFJFJTrip 225.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1480A)

4K PENTHOUSE CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

PNL 4K PENTHOUSE FUSE

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

TOWER42 FUSE

CUTLER-HAMMERFDFDTrip 50.0 ASettings Phase Fixed

TOWER42 CB

1500KVA XFMR3

MCC3 FEED

PNL 4K PENTHOUSE FEED

TOWER42 FEED

TOWER42 FUSE FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

SIEMENSFJFJTrip 225.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1480A)

4K PENTHOUSE CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

PNL 4K PENTHOUSE FUSE

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 60.0 A

TOWER42 FUSE

CUTLER-HAMMERFDFDTrip 50.0 ASettings Phase Fixed

TOWER42 CB

1500KVA XFMR3

MCC3 FEED

PNL 4K PENTHOUSE FEED

TOWER42 FEED

TOWER42 FUSE FEED

3200 A Main CB3

S

P

1500KVA XFMR3

800 A MCC3 CB

MCC3 FEED

4K PENTHOUSE CB

PNL 4K PENTHOUSE FEED

PNL 4K PENTHOUSE FUSE

TOWER42 FUSE

TOWER42

TOWER42 FEED

TOWER42 CB

TOWER42 FUSE FEED

UTIL

MCC-3

USB-5

PNL 4K PENTHOUSE

TCC NAME: TOWER42REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: TOWER42

Page 296: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

XFMR 2L-1 FEED

TX Inrush

45KVA XFMR 2L-12L-1 FEED2L-2 FEED

2L-3 FEED

TX Inrush

1500KVA XFMR3MCC3 FEED

PNL 4K PENTHOUSE FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERFDFDTrip 70.0 ASettings Phase Fixed

2L-1 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

SIEMENSFJFJTrip 225.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1480A)

4K PENTHOUSE CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

PNL 4K PENTHOUSE FUSE

XFMR 2L-1 FEED

45KVA XFMR 2L-1

2L-1 FEED2L-2 FEED

2L-3 FEED

1500KVA XFMR3

MCC3 FEED

PNL 4K PENTHOUSE FEED

CUTLER-HAMMERFDFDTrip 70.0 ASettings Phase Fixed

2L-1 CB

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

SIEMENSFJFJTrip 225.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1480A)

4K PENTHOUSE CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

PNL 4K PENTHOUSE FUSE

XFMR 2L-1 FEED

45KVA XFMR 2L-1

2L-1 FEED2L-2 FEED

2L-3 FEED

1500KVA XFMR3

MCC3 FEED

PNL 4K PENTHOUSE FEED

2L-1 CB

XFMR 2L-1 FEED

S

P45KVA XFMR 2L-1

2L-1 FEED

PNL 2L-1

2L-2 FEED

PNL 2L-2

2L-3 FEED

PNL 2L-3

PNL 4K PENTHOUSE

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A MCC3 CB

MCC3 FEED

4K PENTHOUSE CB

PNL 4K PENTHOUSE FEED

PNL 4K PENTHOUSE FUSE

MCC-3

USB-5

TCC NAME: PNL 2L-3REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2L-3

Page 297: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3MCC3 FEED

PNL 4K PENTHOUSE FEEDXFMR 2K-232 FEED

TX Inrush

45KVA XFMR 2K-2322K-232 CB FEED2K-232 SEC2 FEED

2K-232 FEED2K-232 SEC3 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

SIEMENSFJFJTrip 225.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1480A)

4K PENTHOUSE CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

PNL 4K PENTHOUSE FUSE

CUTLER-HAMMERFDFDTrip 100.0 ASettings Phase Fixed

2K-232 XFMR CB

SIEMENSQJ2HQJ2HTrip 150.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1750A)

2K-232 CB1

SIEMENSQJ2QJ2Trip 150.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1750A)

2K-232 CB2

1500KVA XFMR3

MCC3 FEED

PNL 4K PENTHOUSE FEED

XFMR 2K-232 FEED

45KVA XFMR 2K-232

2K-232 CB FEED

2K-232 SEC2 FEED

2K-232 FEED

2K-232 SEC3 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

SIEMENSFJFJTrip 225.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1480A)

4K PENTHOUSE CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

PNL 4K PENTHOUSE FUSE

CUTLER-HAMMERFDFDTrip 100.0 ASettings Phase Fixed

2K-232 XFMR CB

SIEMENSQJ2HQJ2HTrip 150.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1750A)

2K-232 CB1

SIEMENSQJ2QJ2Trip 150.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1750A)

2K-232 CB2

1500KVA XFMR3

MCC3 FEED

PNL 4K PENTHOUSE FEED

XFMR 2K-232 FEED

45KVA XFMR 2K-232

2K-232 CB FEED

2K-232 SEC2 FEED

2K-232 FEED

2K-232 SEC3 FEED

PNL 4K PENT HOUSE

3200 A Main CB3

S

P

1500KVA XFMR 3

UTIL 800 A MCC3 CB

MCC3 FEED

4K PENTHOUSE CB

PNL 4K PENT HOUSE FEED

PNL 4K PENT HOUSE FUS E

MCC-3

USB-5

2K-232 XFMR CB

XFMR 2K-232 FEED

S

P45KVA XFMR 2K-232

2K-232 CB FEED

PNL 2K-232 SEC1

2K-232 SEC2 FEED

PNL 2K-232 SEC2

2K-232 CB1

2K-232 FEED

2K-232 CB2

2K-232 SEC3 FEED

PNL 2K-232 SEC3

TCC NAME: PNL2K-232REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL2K-232

Page 298: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3MCC3 FEED

2G1 JUNC FEED2H FUSE FEED

2H JUNC FEED

2H-1 FUSE FEED

2H-1 XFMR FEED

TX Inrush

25KVA XFMR 2H-1

2H-1 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

2G1 JUNC FUSE

GOULD SHAWMUTTRS, 600V Class RK5TRSTrip 70.0 A

2H JUNC FUSE

GOULD SHAWMUTTRS, 600V Class RK5TRSTrip 30.0 A

2H-1 FUSE

1500KVA XFMR3

MCC3 FEED

2G1 JUNC FEED

2H FUSE FEED

2H JUNC FEED

2H-1 FUSE FEED

2H-1 XFMR FEED

25KVA XFMR 2H-1

2H-1 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

2G1 JUNC FUSE

GOULD SHAWMUTTRS, 600V Class RK5TRSTrip 70.0 A

2H JUNC FUSE

GOULD SHAWMUTTRS, 600V Class RK5TRSTrip 30.0 A

2H-1 FUSE

1500KVA XFMR3

MCC3 FEED

2G1 JUNC FEED

2H FUSE FEED

2H JUNC FEED

2H-1 FUSE FEED

2H-1 XFMR FEED

25KVA XFMR 2H-1

2H-1 FEED

3200 A Main CB3

S

P

1500KVA XFMR3

800 A MCC3 CB

MCC3 FEED

2G1 JUNC FEED

2G1 JUNC FUSE

2H FUSE FEED

2H JUNC FUSE

2H JUNC FEED

2H-1 FUSE FEED

2H-1 FUSE

2H-1 XFMR FEED

S

P25KVA XFMR 2H-1

2H-1 FEED

PNL 2H-1

MCC-3

USB-5

UTIL

TCC NAME: PNL 2H-1REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2H-1

Page 299: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3MCC3 FEED

2G1 JUNC FEED2H FUSE FEED

2H JUNC FEED

2H-2 FUSE1 FEED

2H-2 XFMR FEED

TX Inrush

25KVA XFMR 2H-2

2H-2 FUSE2 FEED2H-2 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

2G1 JUNC FUSE

GOULD SHAWMUTTRS, 600V Class RK5TRSTrip 70.0 A

2H JUNC FUSE

GOULD SHAWMUTTRS, 600V Class RK5TRSTrip 30.0 A

2H-2 FUSE1

GOULD SHAWMUTTRS, 600V Class RK5TRSTrip 100.0 A

2H-2 FUSE2

1500KVA XFMR3

MCC3 FEED

2G1 JUNC FEED

2H FUSE FEED

2H JUNC FEED

2H-2 FUSE1 FEED

2H-2 XFMR FEED

25KVA XFMR 2H-2

2H-2 FUSE2 FEED

2H-2 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I 2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

BUSSMANNFRS-R, 600V Class RK5FRS-RTrip 200.0 A

2G1 JUNC FUSE

GOULD SHAWMUTTRS, 600V Class RK5TRSTrip 70.0 A

2H JUNC FUSE

GOULD SHAWMUTTRS, 600V Class RK5TRSTrip 30.0 A

2H-2 FUSE1

GOULD SHAWMUTTRS, 600V Class RK5TRSTrip 100.0 A

2H-2 FUSE2

1500KVA XFMR3

MCC3 FEED

2G1 JUNC FEED

2H FUSE FEED

2H JUNC FEED

2H-2 FUSE1 FEED

2H-2 XFMR FEED

25KVA XFMR 2H-2

2H-2 FUSE2 FEED

2H-2 FEED

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL 800 A MCC3 CB

MCC3 FEED

2G1 JUNC FEED

2G1 JUNC FUSE

2H FUSE FEED

2H JUNC FUSE

2H JUNC FEED

USB-5

MCC-3

2H-2 FUSE1 FEED

2H-2 FUSE1

2H-2 XFMR FEED

S

P25KVA XFMR 2H-2

2H-2 FUSE2 FEED

2H-2 FUSE2

2H-2 FEED

PNL 2H-2

TCC NAME: PNL 2H-2REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: PNL 2H-2

Page 300: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

TX Inrush

1500KVA XFMR3MCC3 FEED

EB2 FEED

0.5 1 10 100

1K 10K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A EB2 CB1500KVA XFMR3

MCC3 FEED

EB2 FEED

CUTLER-HAMMERMagnum DS, DT 520MDS-632Trip 3200.0 APlug 3200.0 ASettings Phase LTPU, (0.4-1.0 x P) 1 (3200A) LTD, (2-24 Sec.) 24 STPU, (2-10 x Ir) 10 (32000A) STD, (0.1-0.5 Sec.) 0.5 (I 2t Out) INST, (2-14 x P) 4 (12800A)

3200 A Main CB3

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A MCC3 CB

CUTLER-HAMMERMagnum DS, RMS 520MDS-608Trip 800.0 APlug 800.0 ASettings Phase LTPU (0.4-1.0 x P) 1 (800A) LTD (2-24 Sec.) 24 STPU (2-10 x LTPU) 10 (8000A) STD (0.1-0.5 Sec.) 0.5 (I^2t In) INST (2-14 x P) M1(14) (11200A)

800 A EB2 CB1500KVA XFMR3

MCC3 FEED

EB2 FEED

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL

USB-5

800 A EB2 CB

EB2 FEED

EB2

TCC NAME: EB2REFERENCE VOLTAGE: 12470SCALE: x 1ONE LINE NAME: EB2

Page 301: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

PNL U XFMR FEED

TX Inrush

45KVA XFMR UPNL U FEEDPNL 2U-1 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

PNL U XFMR CB

SQUARE DQ2Q2Trip 150.0 ASettings Phase Fixed

PNL 2U-1 CB

PNL U XFMR FEED

45KVA XFMR U

PNL U FEED

PNL 2U-1 FEED

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

PNL U XFMR CB

SQUARE DQ2Q2Trip 150.0 ASettings Phase Fixed

PNL 2U-1 CB

PNL U XFMR FEED

45KVA XFMR U

PNL U FEED

PNL 2U-1 FEED

PNL U XFMR CB

UPSDP-B UTIL

PNL U XFMR FEED

S

P45KVA XFMR U

PNL U FEED

PNL UPNL 2U-1 CB

PNL 2U-1 FEED

PNL 2U-1

USDP-B TCC NAME: PNL 2U-1REFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: PNL 2U-1

Page 302: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

PNL U XFMR FEED

TX Inrush

45KVA XFMR UPNL U FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

PNL U XFMR CB

PNL U XFMR FEED

45KVA XFMR U

PNL U FEED

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

PNL U XFMR CB

PNL U XFMR FEED

45KVA XFMR U

PNL U FEED

PNL U XFMR CB

UPSDP-B UTIL

PNL U XFMR FEED

S

P45KVA XFMR U

PNL U FEED

PNL U

USDP-B

TCC NAME: PNL UREFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: PNL U

Page 303: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

PNL EDP-D XFMR FEED1

TX Inrush

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1

GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2PNL EDP-D FEED

PNL EDP-D CB1 FEED

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1

GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2PNL EDP-D FEED

PNL EDP-D CB1 FEED

UPSDP-B UTIL

USDP-B

PNL EDP-D C B1

PNL EDP-D XFMR FEED1

S

P75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D C B2

PNL EDP-D FEED

PNL EDP-D C B1 FEED

PNL EDP-D

TCC NAME: PNL EDP-DREFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: PNL EDP-D

Page 304: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

PNL EDP-D XFMR FEED1

TX Inrush

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 7 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1

GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

SIEMENSCLFCLFTrip 150.0 ASettings Phase Thermal Curve (Fixed) INST (800-1500A) HI (1500A)

PNL 7 CB

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 7 FEED

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1

GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

SIEMENSCLFCLFTrip 150.0 ASettings Phase Thermal Curve (Fixed) INST (800-1500A) HI (1500A)

PNL 7 CB

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 7 FEED

UPSDP-B UTIL

USDP-B

PNL EDP-D CB1

PNL EDP-D XFMR FEED1

S

P75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D CB2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL EDP-D

PNL 7 CB

PNL 7 FEED

PNL 7

TCC NAME: PNL 7REFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: PNL 7

Page 305: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

PNL EDP-D XFMR FEED1

TX Inrush

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 6 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1

GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

SIEMENSCLFCLFTrip 200.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

PNL 6 CB

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 6 FEED

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1

GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

SIEMENSCLFCLFTrip 200.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

PNL 6 CB

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 6 FEED

UPSDP-B UTIL

USDP-B

PNL EDP-D CB1

PNL EDP-D XFMR FEED1

S

P75KVA EDP -D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D CB2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL EDP-D

PNL 6 CB

PNL 6 FEED

PNL 6

TCC NAME: PNL 6REFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: PNL 6

Page 306: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

PNL EDP-D XFMR FEED1

TX Inrush

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 5 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

SIEMENSCLFCLFTrip 200.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

PNL 5 CB

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 5 FEED

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

SIEMENSCLFCLFTrip 200.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

PNL 5 CB

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 5 FEED

UPSDP-B UTIL

PNL EDP-D CB1

PNL EDP-D XFMR FEED1

S

P75KVA EDP -D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D CB2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL EDP-D

PNL 5 CB

PNL 5 FEED

PNL 5

USDP-B

TCC NAME: PNL 5REFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: PNL 5

Page 307: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

PNL EDP-D XFMR FEED1

TX Inrush

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 4 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1

GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

SIEMENSCLFCLFTrip 200.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

PNL 4 CB

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 4 FEED

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1

GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

SIEMENSCLFCLFTrip 200.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

PNL 4 CB

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 4 FEED

UPSDP-B UTIL

PNL EDP-D CB1

PNL EDP-D XFMR FEED1

S

P75KVA EDP -D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D CB2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL EDP-D

USDP-B

PNL 4 CB

PNL 4 FEED

PNL 4

TCC NAME: PNL 4REFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: PNL 4

Page 308: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

PNL EDP-D XFMR FEED1

TX Inrush

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 3 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1

GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

SIEMENSCLFCLFTrip 200.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

PNL 3 CB

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 3 FEED

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1

GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

SIEMENSCLFCLFTrip 200.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

PNL 3 CB

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 3 FEED

UPSDP-B UTIL

PNL EDP-D CB1

PNL EDP-D XFMR FEED1

S

P75KVA EDP -D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D CB2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL EDP-D

USDP-B

PNL 3 CB

PNL 3 FEED

PNL 3

TCC NAME: PNL 3REFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: PNL 3

Page 309: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

PNL EDP-D XFMR FEED1

TX Inrush

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 2 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1

GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

SIEMENSCLFCLFTrip 200.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

PNL 2 CB

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 2 FEED

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1

GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

SIEMENSCLFCLFTrip 200.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

PNL 2 CB

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 2 FEED

UPSDP-B UTIL

PNL EDP-D CB1

PNL EDP-D XFMR FEED1

S

P75KVA EDP -D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D CB2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL EDP-D

USDP-B

PNL 2 CB

PNL 2 FEED

PNL 2

TCC NAME: PNL 2REFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: PNL 2

Page 310: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

PNL EDP-D XFMR FEED1

TX Inrush

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 1 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1

GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

SIEMENSCLFCLFTrip 200.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

PNL 1 CB

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 1 FEED

GESEDA, Spectra RMSSEDATrip 60.0 ASettings Phase MAX

PNL EDP-D CB1

GESFHA, Spectra RMSSFHATrip 200.0 ASettings Phase MAX

PNL EDP-D CB2

SIEMENSCLFCLFTrip 200.0 ASettings Phase Thermal Curve (Fixed) INST (900-2000A) HI (2000A)

PNL 1 CB

PNL EDP-D XFMR FEED1

75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

PNL 1 FEED

UPSDP-B UTIL

PNL EDP-D CB1

PNL EDP-D XFMR FEED1

S

P75KVA EDP -D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D CB2

PNL EDP-D FEED

PNL EDP-D CB1 FEED

USDP-B

PNL 1 CB

PNL 1 FEED

PNL 1

PNL EDP-D

TCC NAME: PNL 1REFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: PNL 1

Page 311: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

XFMR 2UPSS-1 FEED

TX Inrush

75KVA XFMR 2UPSS-12UPSS-1 FEED2UPSS-2 FEED2UPSS-3 FEED2UPSS-4 FEED

0.5 1 10 100

1K 10K

100K

1M

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

XFMR 2UPSS-1 CB

SIEMENSFXD6AFXD6-ATrip 250.0 ASettings Phase Thermal Curve (Fixed) INST, 600V HIGH (2250A)

PNL 2UPSS-1 CB

XFMR 2UPSS-1 FEED

75KVA XFMR 2UPSS-1

2UPSS-1 FEED

2UPSS-2 FEED

2UPSS-3 FEED

2UPSS-4 FEED

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

XFMR 2UPSS-1 CB

SIEMENSFXD6AFXD6-ATrip 250.0 ASettings Phase Thermal Curve (Fixed) INST, 600V HIGH (2250A)

PNL 2UPSS-1 CB

XFMR 2UPSS-1 FEED

75KVA XFMR 2UPSS-1

2UPSS-1 FEED

2UPSS-2 FEED

2UPSS-3 FEED

2UPSS-4 FEED

XFMR 2UPSS-1 CB

XFMR 2UPSS-1 FEED

S

P75KVA XFMR 2UPSS-1

2UPSS-1 FEED

PNL 2UPSS -1

PNL 2UPSS -1 CB

2UPSS-2 FEED

PNL 2UPSS -2

2UPSS-3 FEED

PNL 2UPSS -3

2UPSS-4 FEED

PNL 2UPSS -4

USDP-B

UPSDP-B UTIL

TCC NAME: PNL 2UPSSREFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: PNL 2UPSS

Page 312: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

XFMR 2UPSN-1 FEED

TX Inrush

45KVA XFMR 2UPSN-12UPSN-1 FEED2UPSN-2 FEED

0.5 1 10 100

1K 10K

100K

0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIME IN SECONDS

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

XFMR 2UPSN-1 CB

SIEMENSQJ2QJ2Trip 150.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1750A)

PNL 2UPSN-1 CB

XFMR 2UPSN-1 FEED

45KVA XFMR 2UPSN-1

2UPSN-1 FEED

2UPSN-2 FEED

CUTLER-HAMMERKDKDTrip 400.0 ASettings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

XFMR 2UPSN-1 CB

SIEMENSQJ2QJ2Trip 150.0 ASettings Phase Thermal Curve (Fixed) INST Fixed (1750A)

PNL 2UPSN-1 CB

XFMR 2UPSN-1 FEED

45KVA XFMR 2UPSN-1

2UPSN-1 FEED

2UPSN-2 FEED

XFMR 2UPSN-1 CB

XFMR 2UPSN-1 FEED

S

P45KVA XFMR 2UPSN-1

2UPSN-1 FEED

PNL 2UPSN-1

PNL 2UPSN-1 CB

2UPSN-2 FEED

PNL 2UPSN-2

USDP-B

UPSDP-B UTIL

TCC NAME: 2UPSNREFERENCE VOLTAGE: 480SCALE: x 1ONE LINE NAME: 2UPSN

Page 313: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

APPENDIX D

Page 314: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Examples of typical protective clothing that cover the torso are included in Table D.

Table D: Hazard/Risk Classification as per NFPA 70E

Category Energy Level Typical PPE Examples

0 N/ANon-melting, flammable material

(e.g. untreated cotton, wool,

rayon, etc.)

1 5 cal/cm2

FR shirt and FR pants

2 8 cal/cm2 Cotton underwear plus FR shirt

and pants.

3 25 cal/cm2 Cotton underwear plus FR shirt

and pants plus FR coverall.

4 40 cal/cm2

Cotton underwear plus FR shirtand pants plus double layer

switching coat and pants.

Refer to NFPA 70E 130.7 (C) (16) for additional protective equipment that are required to protect

the various parts of the body.

D.1 Arc Flash Hazard Table Headings Guide and PPE Table

The arc flash hazard table summarizes the results of the arc flash hazard analysis. The calculations

are based on the protective relay and low voltage circuit breaker settings. The following is a brief

description of the arc flash hazard analysis table headings.

· Bus Name: The names in this column correlate to the one-line diagram located in Appendix

B.

· Protective Device Name: Lists the device primarily responsible for clearing a potential fault

at the associated bus.

· Bus Voltage (kV): Shows the nominal voltage of the bus in question.

· Bus Bolted Fault (kA): Shows the bolted fault current available for the bus location

referenced in the first column.

· Prot. Dev. Bolted Fault (kA): Displays the portion of calculated bolted fault currents that is

contributed through the protective device.

· Prot. Dev. Arcing Fault (kA): Displays the portion of calculated arcing fault currents that is

contributed through the protective device. These values demonstrate a reduction in available

fault current due to the arc resistance.

· Trip/Delay Time (sec): Displays the length of time required by the protective device to trip

in the presence of the arcing fault current calculated. This time represents the total clearing

time of low voltage fuses and breakers.

· Breaker Opening Time (sec): Shows the opening time of the associated breaker if it were to

be tripped by a relay. This time is added to the trip/delay time to determine the total clearing

time used to calculate the incident energy.

Page 315: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

A B C D E F G H I J K L M N O P Q R

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level Label # Cable Length

Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device

Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft)

(kA) (kA) (kA) (kA) (sec.) (sec.) (in)

EMDP-P GEN SET CB 0.48 2.17 1.78 2.08 1.71 2 0.000 Yes PNL 25 65 18 9.9 Category 3 (*N9)

(*S1)

# 0001 325.00

MCC10 800 A MCC10

CB

0.48 27.08 15.36 26.53 15.05 0.066 0.000 Yes PNL 25 35 18 3.5 Category 1 (*S0) # 0003 220.00

MCC12 MCC12 CB 0.48 9.34 6.19 9.10 6.03 0.017 0.000 Yes PNL 25 8 18 0.33 Category 0 (*S0) # 0004 250.00

MCC2 MCC2 CB 0.48 9.76 6.42 9.35 6.15 0.014 0.000 Yes PNL 25 8 18 0.29 Category 0 (*S0) # 0005 10.00

MCC-3 800 A MCC3

CB

0.48 31.93 17.68 31.03 17.18 0.066 0.000 Yes PNL 25 38 18 4.1 Category 2 (*S1) # 0002 50.00

MCC4 MCC4 CB 0.48 25.57 14.62 25.06 14.33 0.01 0.000 Yes PNL 25 11 18 0.50 Category 0 (*S0) # 0006 20.00

P4Y 800 A P4Y CB 0.48 31.78 17.61 29.71 16.46 0.066 0.000 Yes PNL 25 38 18 4.0 Category 2 (*S1) # 0007 25.00

P4Z 800 A P4Z CB 0.48 44.63 23.53 37.55 19.80 0.066 0.000 Yes PNL 25 46 18 5.5 Category 2 (*S0) # 0008 38.00

PDU1 PDU1 CB 0.48 1.19 1.06 1.19 1.06 2 0.000 No PNL 25 56 18 7.6 Category 2 (*N9)

(*S1)

# 0009 90.00

PDU2 PDU2 CB 0.48 1.19 1.06 1.19 1.06 2 0.000 No PNL 25 56 18 7.6 Category 2 (*N9)

(*S1)

# 0010 90.00

PDU3 PDU3 CB 0.48 1.18 1.05 1.18 1.05 2 0.000 No PNL 25 55 18 7.6 Category 2 (*N9)

(*S1)

# 0011 160.00

PDU4 PDU4 CB 0.48 1.18 1.06 1.18 1.06 2 0.000 No PNL 25 56 18 7.6 Category 2 (*N9)

(*S1)

# 0012 130.00

PNL 1 PNL EDP-D

CB2

0.12 2.14 2.14 2.14 2.14 0.315 0.000 Yes PNL 25 7 18 0.20 Category 0 (*N5)

(*N11) (*S1)

# 0013 240.00

PNL 12E XFMR 12E CB 0.12 3.38 3.38 3.38 3.38 2 0.000 Yes PNL 25 23 18 2.0 Category 1 (*N9)

(*N11) (*S1)

# 0013 10.00

PNL 14E 14E CB 0.48 2.15 1.50 2.15 1.50 0.748 0.000 Yes PNL 25 32 18 3.1 Category 1 (*N3)

(*S1)

# 0014 18.00

PNL 2 PNL EDP-D

CB2

0.12 2.14 2.14 2.14 2.14 0.315 0.000 Yes PNL 25 7 18 0.20 Category 0 (*N5)

(*N11) (*S1)

# 0016 240.00

PNL 2A-1 XFMR 2A CB 0.12 7.21 7.21 7.21 7.21 0.012 0.000 Yes PNL 25 3 18 0.02 Category 0 (*N11)

(*S0)

# 0015 16.00

PNL 2A-2 XFMR 2A CB 0.12 6.95 6.95 6.95 6.95 0.012 0.000 Yes PNL 25 3 18 0.02 Category 0 (*N11)

(*S0)

# 0016 22.00

PNL 2B PNL 2B CB 0.12 1.47 1.47 1.47 1.47 0.017 0.000 Yes PNL 25 1 18 0.01 Category 0 (*N11)

(*S0)

# 0017 50.00

PNL 2B1 2B1 CB 0.12 5.25 5.25 5.25 5.25 0.017 0.000 Yes PNL 25 3 18 0.03 Category 0 (*N11)

(*S1)

# 0018 50.00

PNL 2B2 2B1 CB 0.12 5.10 5.10 5.10 5.10 0.017 0.000 Yes PNL 25 3 18 0.03 Category 0 (*N11)

(*S1)

# 0019 56.00

PNL 2C 4C CB 0.12 4.83 4.83 4.83 4.83 2 0.000 Yes PNL 25 28 18 2.8 Category 1 (*N9)

(*N11) (*S0)

# 0020 97.00

PNL 2C1 2CA CB 0.12 5.83 5.83 5.83 5.83 0.01 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S1)

# 0022 32.00

PNL 2C-12 2C-12 CB 0.12 4.83 4.83 4.83 4.83 0.849 0.000 Yes PNL 25 18 18 1.2 Category 1 (*N11)

(*S1)

# 0021 155.00

PNL 2C2 4C CB 0.12 2.07 2.07 2.07 2.07 2 0.000 Yes PNL 25 18 18 1.2 Category 1 (*N9)

(*N11) (*S0)

# 0023 101.00

PNL 2C2-12 2CA CB 0.12 5.61 5.61 5.61 5.61 0.01 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S1)

# 0024 36.00

PNL 2C3 2C-12 CB 0.12 4.62 4.62 4.62 4.62 1.069 0.000 Yes PNL 25 20 18 1.4 Category 1 (*N11)

(*S1)

# 0025 159.00

ARC FLASH WORST CASE S0=NORMAL POWER S1=GENERATOR

Page 316: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

59

A B C D E F G H I J K L M N O P Q R

PNL 2CA 2CA CB 0.12 7.08 7.08 7.08 7.08 0.01 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S1)

# 0026 14.00

PNL 2D XFMR 2D CB 0.12 4.77 4.77 4.77 4.77 0.157 0.000 Yes PNL 25 8 18 0.22 Category 0 (*N11)

(*S1)

# 0027 15.00

PNL 2D1 XFMR 2D CB 0.12 1.53 1.53 1.53 1.53 2 0.000 Yes PNL 25 16 18 0.90 Category 0 (*N9)

(*N11) (*S0)

# 0028 145.00

PNL 2D1-02 2D1 CB 0.12 4.26 4.26 4.26 4.26 0.676 0.000 Yes PNL 25 15 18 0.84 Category 0 (*N11)

(*S1)

# 0029 16.00

PNL 2D2 4D CB 0.48 10.73 6.96 10.73 6.96 0.014 0.000 Yes PNL 25 8 18 0.32 Category 0 (*N5)

(*S0)

# 0030 155.00

PNL 2D3 2D3 CB 0.12 4.06 4.06 4.06 4.06 0.025 0.000 Yes PNL 25 3 18 0.03 Category 0 (*N11)

(*S1)

# 0031 170.00

PNL 2E XFMR 2E CB 0.12 1.80 1.80 1.80 1.80 1.937 0.000 Yes PNL 25 17 18 1.0 Category 0 (*N11)

(*S1)

# 0032 13.00

PNL 2F XFMR 2F CB 0.12 3.75 3.75 3.75 3.75 0.574 0.000 Yes PNL 25 13 18 0.63 Category 0 (*N11)

(*S1)

# 0033 16.00

PNL 2F1 XFMR 2F1 CB 0.12 1.91 1.91 1.91 1.91 1.635 0.000 Yes PNL 25 16 18 0.92 Category 0 (*N11)

(*S1)

# 0034 155.00

PNL 2G 60 A XFMR

CB

0.12 4.59 4.59 4.59 4.59 0.203 0.000 Yes PNL 25 9 18 0.27 Category 0 (*N11)

(*S1)

# 0035 13.00

PNL 2GA XFMR 2GA CB 0.12 5.90 5.90 5.90 5.90 0.022 0.000 Yes PNL 25 3 18 0.04 Category 0 (*N11)

(*S1)

# 0036 18.00

PNL 2GA2 XFMR 2GA CB 0.12 5.71 5.71 5.71 5.71 0.022 0.000 Yes PNL 25 3 18 0.04 Category 0 (*N11)

(*S1)

# 0037 22.00

PNL 2GB XFMR 2GB CB 0.12 5.90 5.90 5.90 5.90 0.026 0.000 Yes PNL 25 3 18 0.04 Category 0 (*N11)

(*S1)

# 0038 18.00

PNL 2GB2 XFMR 2GB CB 0.12 5.71 5.71 5.71 5.71 0.028 0.000 Yes PNL 25 4 18 0.05 Category 0 (*N11)

(*S1)

# 0039 22.00

PNL 2GE XFMR 2GE CB 0.12 3.31 3.31 3.31 3.31 0.257 0.000 Yes PNL 25 8 18 0.25 Category 0 (*N11)

(*S1)

# 0040 10.00

PNL 2H 2H-2 FUSE2 0.12 2.21 2.21 2.21 2.21 0.035 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S1)

# 0041 70.00

PNL 2H-1 2H-1 FUSE 0.12 3.84 3.84 3.84 3.84 0.008 0.000 Yes PNL 25 2 18 0.01 Category 0 (*N11)

(*S1)

# 0042 28.00

PNL 2H-2 2H-2 FUSE2 0.12 3.49 3.49 3.49 3.49 0.008 0.000 Yes PNL 25 2 18 0.01 Category 0 (*N11)

(*S1)

# 0043 10.00

PNL 2H-3 2H-2 FUSE2 0.12 3.36 3.36 3.36 3.36 0.008 0.000 Yes PNL 25 1 18 0.01 Category 0 (*N11)

(*S1)

# 0044 14.00

PNL 2J XFMR 2J CB 0.12 2.09 2.09 2.09 2.09 0.565 0.000 Yes PNL 25 10 18 0.35 Category 0 (*N11)

(*S1)

# 0045 12.00

PNL 2K 2K CB 0.12 2.33 2.33 2.33 2.33 1.134 0.000 Yes PNL 25 14 18 0.77 Category 0 (*N11)

(*S1)

# 0046 10.00

PNL 2K1 2K CB 0.12 2.15 2.15 2.15 2.15 1.331 0.000 Yes PNL 25 15 18 0.84 Category 0 (*N11)

(*S1)

# 0050 14.00

PNL 2K-232 SEC1 2K-232 CB2 0.12 2.95 2.95 2.95 2.95 0.012 0.000 Yes PNL 25 2 18 0.01 Category 0 (*N11)

(*S1)

# 0047

PNL 2K-232 SEC2 2K-232 CB2 0.12 2.84 2.84 2.84 2.84 0.012 0.000 Yes PNL 25 2 18 0.01 Category 0 (*N11)

(*S1)

# 0048 8.00

PNL 2K-232 SEC3 2K-232 CB2 0.12 2.73 2.73 2.73 2.73 0.012 0.000 Yes PNL 25 2 18 0.01 Category 0 (*N11)

(*S1)

# 0049 16.00

PNL 2L-1 2L-1 CB 0.12 3.60 3.60 3.60 3.60 1.118 0.000 Yes PNL 25 18 18 1.2 Category 0 (*N11)

(*S1)

# 0051 39.00

PNL 2L-2 2L-1 CB 0.12 3.47 3.47 3.47 3.47 1.241 0.000 Yes PNL 25 18 18 1.3 Category 1 (*N11)

(*S1)

# 0052 45.00

PNL 2L-3 2L-1 CB 0.12 3.10 3.10 3.10 3.10 1.722 0.000 Yes PNL 25 21 18 1.6 Category 1 (*N11)

(*S1)

# 0053 65.00

Page 317: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

60

61

62

63

64

65

66

67

68

69

70

71

72

73

74

75

76

77

78

79

80

81

82

83

84

85

86

87

88

89

90

91

92

93

A B C D E F G H I J K L M N O P Q R

PNL 2P-1 2P-1 FUSE 0.12 4.18 4.18 4.18 4.18 1.535 0.000 Yes PNL 25 23 18 1.9 Category 1 (*N11)

(*S1)

# 0054 96.00

PNL 2P-2 2P-1 FUSE 0.12 3.98 3.98 3.98 3.98 1.942 0.000 Yes PNL 25 25 18 2.3 Category 1 (*N11)

(*S1)

# 0055 102.00

PNL 2U-1 PNL 2U-1 CB 0.12 2.35 2.35 2.35 2.35 2 0.000 Yes PNL 25 19 18 1.4 Category 1 (*N9)

(*N11) (*S1)

# 0058 65.00

PNL 2UPSN-1 PNL 2UPSN-1

CB

0.12 3.99 3.99 3.99 3.99 0.012 0.000 Yes PNL 25 2 18 0.01 Category 0 (*N11)

(*S1)

# 0059

PNL 2UPSN-2 PNL 2UPSN-1

CB

0.12 3.89 3.89 3.89 3.89 0.012 0.000 Yes PNL 25 2 18 0.01 Category 0 (*N11)

(*S1)

# 0060 4.00

PNL 2UPSS-1 PNL 2UPSS-1

CB

0.12 5.55 5.55 5.55 5.55 0.014 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S1)

# 0061

PNL 2UPSS-2 PNL 2UPSS-1

CB

0.12 5.43 5.43 5.43 5.43 0.014 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S1)

# 0062 5.00

PNL 2UPSS-3 PNL 2UPSS-1

CB

0.12 5.31 5.31 5.31 5.31 0.014 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S1)

# 0063 10.00

PNL 2UPSS-4 PNL 2UPSS-1

CB

0.12 5.19 5.19 5.19 5.19 0.015 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S1)

# 0064 15.00

PNL 3 PNL EDP-D

CB2

0.12 3.03 3.03 3.03 3.03 0.026 0.000 Yes PNL 25 3 18 0.02 Category 0 (*N5)

(*N11) (*S1)

# 0065 110.00

PNL 4 PNL EDP-D

CB2

0.12 3.03 3.03 3.03 3.03 0.026 0.000 Yes PNL 25 3 18 0.02 Category 0 (*N5)

(*N11) (*S1)

# 0066 110.00

PNL 4A 200 A 4A CB 0.48 28.86 16.22 28.86 16.22 0.013 0.000 Yes PNL 25 13 18 0.73 Category 0 (*S0) # 0056 50.00

PNL 4B 4B CB 0.48 15.81 9.70 15.81 9.70 0.023 0.000 Yes PNL 25 14 18 0.75 Category 0 (*S1) # 0057 120.00

PNL 4C 4C CB 0.48 22.45 13.09 22.45 13.09 0.014 0.000 Yes PNL 25 12 18 0.61 Category 0 (*S0) # 0058 85.00

PNL 4C-12 4C-12 CB 0.48 20.32 12.01 20.32 12.01 0.023 0.000 Yes PNL 25 16 18 0.95 Category 0 (*S1) # 0059 65.00

PNL 4D 4D CB 0.48 15.00 9.27 15.00 9.27 0.014 0.000 Yes PNL 25 10 18 0.42 Category 0 (*S0) # 0060 130.00

PNL 4D1 4D1 CB 0.48 26.13 14.90 26.13 14.90 0.013 0.000 Yes PNL 25 13 18 0.66 Category 0 (*S1) # 0061 25.00

PNL 4D2 200 A 4D2 CB 0.48 14.13 8.81 13.49 8.41 0.015 0.000 Yes PNL 25 10 18 0.44 Category 0 (*S1) # 0062 130.00

PNL 4DE 4DE CB 0.48 20.11 11.91 19.81 11.73 0.014 0.000 Yes PNL 25 11 18 0.57 Category 0 (*S0) # 0063 130.00

PNL 4E 4E CB 0.48 2.07 1.45 2.07 1.45 0.803 0.000 Yes PNL 25 33 18 3.2 Category 1 (*N3)

(*S1)

# 0064 100.00

PNL 4F 100 A 4F CB 0.48 9.52 6.29 9.52 6.29 0.014 0.000 Yes PNL 25 8 18 0.29 Category 0 (*S0) # 0065 190.00

PNL 4F-13 4F-13 CB 0.48 20.59 12.15 20.42 12.05 0.014 0.000 Yes PNL 25 11 18 0.56 Category 0 (*S1) # 0066 40.00

PNL 4G 400 A 4G CB 0.48 10.66 5.89 10.66 5.89 0.5 0.000 Yes PNL 25 61 18 8.8 Category 3 (*N3)

(*S0)

# 0067 295.00

PNL 4G-104 4G-104 CB 0.48 31.28 17.37 31.28 17.37 0.012 0.000 Yes PNL 25 13 18 0.69 Category 0 (*S1) # 0068 15.00

PNL 4GE 150 A 4GE CB 0.48 9.91 6.51 9.50 6.24 0.015 0.000 Yes PNL 25 8 18 0.30 Category 0 (*S0) # 0069 190.00

PNL 4H 4CH CB 0.48 25.27 14.48 25.27 14.48 0.023 0.000 Yes PNL 25 18 18 1.2 Category 0 (*S1) # 0070 30.00

PNL 4I 4I CB 0.48 28.08 15.84 22.52 12.70 0.012 0.000 Yes PNL 25 12 18 0.64 Category 0 (*S0) # 0071 100.00

PNL 4J 4J CB 0.48 24.00 13.85 23.48 13.55 0.066 0.000 Yes PNL 25 32 18 3.1 Category 1 (*S1) # 0072 85.00

PNL 4J1 400 A 4J1 CB 0.48 33.75 18.54 33.75 18.54 0.066 0.000 Yes PNL 25 39 18 4.3 Category 2 (*S0) # 0073 55.00

PNL 4J2 400 A 4J1 CB 0.48 33.15 18.26 33.15 18.26 0.066 0.000 Yes PNL 25 39 18 4.2 Category 2 (*S0) # 0074 58.00

PNL 4K 4K CB 2 0.48 9.28 6.15 9.28 6.15 0.017 0.000 Yes PNL 25 8 18 0.33 Category 0 (*S0) # 0075 6.00

PNL 4K PENTHOUSE PNL 4K

PENTHOUSE

FUSE

0.48 21.15 12.43 20.75 12.20 0.004 0.000 Yes PNL 25 6 18 0.18 Category 0 (*S1) # 0076 60.00

PNL 4L 4L CB 1 0.48 18.95 11.32 18.95 11.32 0.014 0.000 Yes PNL 25 11 18 0.54 Category 0 (*N5)

(*S0)

# 0077 113.00

PNL 4M 4M CB 2 0.48 13.25 8.34 13.07 8.23 0.014 0.000 Yes PNL 25 9 18 0.38 Category 0 (*S0) # 0078 4.00

Page 318: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

94

95

96

97

98

99

100

101

102

103

104

105

106

107

108

109

110

111

112

113

114

115

116

117

118

119

120

121

A B C D E F G H I J K L M N O P Q R

PNL 5 PNL 5 CB 0.12 3.75 3.75 3.75 3.75 0.02 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S1)

# 0090 10.00

PNL 6 PNL 6 CB 0.12 3.72 3.72 3.72 3.72 0.02 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S1)

# 0091 12.00

PNL 7 PNL 7 CB 0.12 3.54 3.54 3.54 3.54 0.015 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S1)

# 0092 25.00

PNL EDP15 800 A EDP15

CB

0.12 50.02 50.02 50.02 50.02 0.066 0.000 Yes PNL 25 16 18 0.97 Category 0 (*N11)

(*S0)

# 0080 160.00

PNL EDP-D PNL EDP-D

CB2

0.12 3.91 3.91 3.91 3.91 0.025 0.000 Yes PNL 25 3 18 0.03 Category 0 (*N11)

(*S1)

# 0093 40.00

PNL EDP-E EDP-E CB 0.12 26.21 26.21 26.21 26.21 0.018 0.000 Yes PNL 25 6 18 0.14 Category 0 (*N11)

(*S0)

# 0079 75.00

PNL EMCC-T6 EMCC-T6 CB 0.48 0.94 0.74 0.94 0.74 0.294 0.000 Yes PNL 25 12 18 0.58 Category 0 (*N3)

(*S1)

# 0081 300.00

PNL KL KL FUSE 0.12 10.08 10.08 10.08 10.08 0.017 0.000 Yes PNL 25 4 18 0.05 Category 0 (*N11)

(*S1)

# 0082

PNL L1 L1 200 A

FUSE

0.12 6.05 6.05 6.05 6.05 0.017 0.000 Yes PNL 25 3 18 0.03 Category 0 (*N11)

(*S1)

# 0083 65.00

PNL L1A L1A 200 A

FUSE

0.12 5.88 5.88 5.88 5.88 0.018 0.000 Yes PNL 25 3 18 0.03 Category 0 (*N11)

(*S1)

# 0084 65.00

PNL P1 XFMR P1 CB 0.12 2.21 2.21 2.21 2.21 1.945 0.000 Yes PNL 25 18 18 1.3 Category 1 (*N11)

(*S0)

# 0085 326.00

PNL P2D P2D FUSE 0.12 3.21 3.21 3.21 3.21 0.017 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S1)

# 0086 25.00

PNL P2Z XFMR P2Z CB 0.12 5.82 5.82 5.82 5.82 0.039 0.000 Yes PNL 25 4 18 0.07 Category 0 (*N11)

(*S1)

# 0087 61.00

PNL P4A 800 A P4A CB 0.48 35.37 19.29 35.37 19.29 0.066 0.000 Yes PNL 25 40 18 4.5 Category 2 (*S1) # 0088 6.00

PNL P4B 800 A P4B CB 0.48 32.50 17.95 32.50 17.95 0.066 0.000 Yes PNL 25 38 18 4.1 Category 2 (*S1) # 0089 40.00

PNL P4D 400 A P4D CB 0.48 32.11 17.76 32.11 17.76 0.066 0.000 Yes PNL 25 38 18 4.1 Category 2 (*S1) # 0090 45.00

PNL P4X 800 A P4X CB 0.48 27.85 15.73 27.46 15.51 0.066 0.000 Yes PNL 25 35 18 3.6 Category 1 (*S0) # 0091 205.00

PNL SSD-A STS-B CB2 0.48 1.20 1.07 0.30 0.27 2 0.000 No PNL 25 56 18 7.7 Category 2 (*N9)

(*S1)

# 0092

PNL SSD-B STS-B CB1 0.48 1.20 1.07 0.30 0.27 2 0.000 No PNL 25 56 18 7.7 Category 2 (*N9)

(*S1)

# 0093

PNL U PNL U XFMR

CB

0.12 3.22 3.22 3.22 3.22 2 0.000 Yes PNL 25 23 18 1.9 Category 1 (*N9)

(*N11) (*S1)

# 0109 33.00

PNL U4A UPS B CB3 0.48 1.20 1.07 0.60 0.54 2 0.000 No PNL 25 56 18 7.7 Category 2 (*N5)

(*N9) (*S1)

# 0094 38.00

PNL U4B UPS B CB3 0.48 1.20 1.07 0.60 0.54 2 0.000 No PNL 25 56 18 7.7 Category 2 (*N5)

(*N9) (*S1)

# 0095 38.00

PNL USB-1 600 A USB-1

CB

0.48 30.13 16.83 30.13 16.83 0.066 0.000 Yes PNL 25 37 18 3.8 Category 1 (*S1) # 0096 50.00

PNL USB-2 600 A USB-2

CB

0.48 42.29 22.47 42.29 22.47 0.066 0.000 Yes PNL 25 44 18 5.3 Category 2 (*S0) # 0097 50.00

SONNY'S SONNY'S CB 0.12 4.14 4.14 4.14 4.14 0.014 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S0)

# 0098 35.00

STS-A UPS B CB3 0.48 1.20 1.07 0.60 0.54 2 0.000 No PNL 25 56 18 7.7 Category 2 (*N5)

(*N9) (*S1)

# 0099 23.00

STS-B UPS B CB3 0.48 1.20 1.07 0.60 0.54 2 0.000 No PNL 25 56 18 7.7 Category 2 (*N5)

(*N9) (*S1)

# 0100 23.00

USB-1 3200 A Main

CB1

0.48 33.52 18.43 31.45 17.29 2 0.000 Yes PNL 25 301 18 122 Dangerous! (*N9)

(*S1)

# 0101

Page 319: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

122

123

124

125

126

127

128

129

130

131

132

A B C D E F G H I J K L M N O P Q R

USB-2 3200 A Main

CB2

0.48 49.30 25.62 31.43 16.33 2 0.000 Yes PNL 25 304 18 124 Dangerous! (*N9)

(*S0)

# 0102

USB-5 3200 A Main

CB3

0.48 35.92 19.55 31.10 16.93 2 0.000 Yes PNL 25 300 18 121 Dangerous! (*N9)

(*S1)

# 0103

Category 0: Nonmelting

or Untreated Fiber with

Weight >= 4.5 oz/sq yd

0.0 - 1.2

cal/cm^2

#Cat 0 = 77 (*N11) - Out of IEEE

1584 Range, Lee

Equation Used.

Applicable for Open

Air only. Existing

Equipment type is not

Open Air!

Category 1: Arc-rated

shirt & pants or arc-

rated coverall

1.2 - 4.0

cal/cm^2

#Cat 1 = 18 (*N3) - Arcing

Current Low

Tolerances Used

Category 2: Arc-rated

shirt & pants or arc-

rated coverall

4.0 - 8.0

cal/cm^2

#Cat 2 = 19 (*N5) -

Miscoordinated,

Upstream Device

Tripped

Category 3: Arc-rated

shirt & pants + arc-rated

coverall + arc-rated arc

flash suit

8.0 - 25.0

cal/cm^2

#Cat 3 = 2 (*N9) - Max Arcing

Duration Reached

Category 4: Arc-rated

shirt & pants + arc-rated

coverall + arc-rated arc

flash suit

25.0 - 40.0

cal/cm^2

#Cat 4 = 0

Category Dangerous!:

DO NOT WORK ON

LIVE!

40.0 - 999.0

cal/cm^2

#Danger = 3 NFPA 70E 2012

Annex D.7 - IEEE

1584 Bus Report

(80% Cleared Fault

Threshold, mis-

coordination checked

Worst Case (*S0) - Base Project

For additional

information refer to

NFPA 70 E, Standard

for Electrical Safety in

the Workplace.

(*S1) - Scenario1

Category 0: Nonmelting

or Untreated Fiber with

Weight >= 4.5 oz/sq yd,

Safety Glasses or

Goggles + Ear Canal

Inserts, Leather Gloves,

Safety glasses, Non-

melting or untreated

natural fiber

(cotton/wool/rayon/silk >

4.5 oz/sq yd), shirt (long-

sleeve), pants (long)., >

50V voltage rated tools

+ Class 0 (minimum)

gloves, Dielectric shoes

or insulating mat (step

and touch potential).

Page 320: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

133

134

A B C D E F G H I J K L M N O P Q R

Category 1: Arc-rated

shirt & pants or arc-

rated coverall , Hardhat

+ Arc-rated hard hat

liner + Safety Glasses

or Goggles + Ear Canal

Inserts, Leather Gloves,

Leather work shoes,

Safety glasses,

electrically rated hard

hat with hood and face

shield., 4 cal/sq cm, Arc-

rated shirt (long-sleeve)

plus Arc-rated pants

(long), or Arc-rated

coverall, plus arc-rated

face shield or arc flash

suit hood, Arc-rated

rainwear as needed., >

50V voltage rated tools

+ Class 0 (minimum)

gloves and leather

protectors (flash) as

needed., Leather shoes

(flash) as needed.

Dielectric shoes or

insulating mat (step and

touch potential).

Category 2: Arc-rated

shirt & pants or arc-

rated coverall , Hardhat

+ Arc-rated hard hat

liner + Safety Glasses

or Goggles + Ear Canal

Inserts, Leather Gloves,

Leather work shoes,

Safety glasses,

electrically rated hard

hat with hood and face

shield. Hearing

protection., 8 cal/sq cm,

Arc-rated shirt (long-

sleeve) plus Arc-rated

pants (long), or Arc-

rated coverall, plus arc-

rated flash suit hood or

arc-rated face shield

and arc rated balaclava,

Arc-rated rainwear as

needed., > 50V voltage

rated tools + Class 0

(minimum) gloves and

leather protectors

(flash)., Leather shoes

(flash) as needed.

Dielectric shoes or

insulating mat (step and

touch potential).

Page 321: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

135

A B C D E F G H I J K L M N O P Q R

Category 3: Arc-rated

shirt & pants + arc-rated

coverall + arc-rated arc

flash suit , Hardhat +

Arc-rated hard hat liner

+ Safety Glasses or

Goggles + Ear Canal

Inserts, Arc-rated

Gloves, Leather work

shoes, Safety glasses,

electrically rated hard

hat with hood and face

shield. Hearing

protection., 25 cal/sq

cm, Arc-rated shirt (long-

sleeve) plus Arc-rated

pants (long) plus Arc-

rated coverall, plus arc

rated arc flash suit

jacket, pants, & hood,

Arc-rated rainwear as

needed., > 50V voltage

rated tools + Class 0

(minimum) gloves and

leather protectors

(flash)., Leather shoes

(flash) as needed.

Dielectric shoes or

insulating mat (step and

touch potential).

Page 322: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

136

137

A B C D E F G H I J K L M N O P Q R

Category 4: Arc-rated

shirt & pants + arc-rated

coverall + arc-rated arc

flash suit , Hardhat +

Arc-rated hard hat liner

+ Safety Glasses or

Goggles + Ear Canal

Inserts, Arc-rated

Gloves, Leather work

shoes, Safety glasses,

electrically rated hard

hat with hood and face

shield. Hearing

protection., 40 cal/sq

cm, Arc-rated shirt (long-

sleeve) plus Arc-rated

pants (long) plus Arc-

rated coverall, plus arc

rated arc flash suit

jacket, pants, & hood,

Arc-rated rainwear as

needed., > 50V voltage

rated tools + Class 0

(minimum) gloves and

leather protectors

(flash)., Leather shoes

(flash) as needed.

Dielectric shoes or

insulating mat (step and

touch potential).

Category Dangerous!:

DO NOT WORK ON

LIVE!, DO NOT WORK

ON LIVE!, DO NOT

WORK ON LIVE!, DO

NOT WORK ON LIVE!,

DO NOT WORK ON

LIVE!, No FR Category

Found

Page 323: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

APPENDIX E

Page 324: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

USB-1

3200 A Main CB1

S

P

1500KVA XFMR1

SWGR #1

400 A H5A CB 400 A H4A CB 200 A EH3A CB 400 A H3A CB 400 A H2A CB 400 A H3B CB 400 A HPA CB 800 A EHRA CB 800 A P4Y CB

600 A USB-1 CB

P4Y FEED

P4Y

30 A ASU9A CB

ASU9A FEED

ASU9A-1 FEED ASU9A-2 FEED

ASU9A-1 ASU9A-2

400 A XFMR CB

150KVA XFMR FEED

S

P150KVA XFMR

L1A DISC FEED

L1A DISC SW

L1A 200 A FUSE

L1A FEED

PNL L1A

L1 DISC FEED

L1 DISC SW

L1 200 A FUSE

L1 FEED

PNL L1

150 A WWP4 CB

WWP4 FEED

WWP4

150 A WWP3 CB

WWP3 FEED

WWP3

110 A WWP2 CB

WWP2 FEED

WWP2

200 A H7A CB 200 A H6A CB200 A 4D2 CB

4D2 FEED

PNL 4D2

150 A DHRC-1 CB

DHRC-1 FEED

DHRC-1

20 A CWP1A CB

CWP1A FEED

CWP1A

20 A CWP1B CB

CWP1B FEED

CWP1B

25 A CHWP1A CB

CHWP1A FEED

CHWP1A

25 A CHWP1B CB

CHWP1B FEED

CHWP1B

USB-2

Open

3200 A TIE CB TIE FEED

USB-1 FEED

PNL USB-1

400 A 4G CB

4G FEED

PNL 4G

60 A XFMR CB

45KVA XFMR FEED

S

P45KVA XFMR

2G FEED

PNL 2G

4J1 FEED

PNL 4J1

S

P15KVA XFMR 2J

2J FEED

PNL 2J

400 A 4J1 CB

4J2 FEED

PNL 4J2

600 A USB-2 CB

USB-2 FEED

PNL USB-2

400 A ATS-1 CB

ATS-1 FEED

GEN-1

ATS-1 EM FEED

EMDP-P FEED

EMDP-P

ROOF MOTOR CB

ROOF MOTOR FEED

ROOF MOTOR 1 FEED

ROOF TOP MOTOR 1

ROOF MOTOR 2 FEED

ROOF TOP MOTOR 2

EMCC-T6 CB

EMCC-T6 FEED

PNL EMCC-T6

4E CB

4E FEED

XFMR 2E CB

XFMR 2E FEED

S

P

15KVA XFMR 2E

2E FEED

PNL 4E

PNL 2E

14E CB

14E FEED

XFMR 12E CB

XFMR 12E FEED

S

P

45KVA XFMR 12E

12E FEED

PNL 14E

PNL 12E

XFMR P1 CB

XFMR P1 FEED

S

P

30KVA XFMR P1

P1 FEED

PNL P1

800 A MCC10 CB

MCC10 FEED

MCC10

P18-3 CB

P18-3 FEED

P18-3

CHWP-4 CB

CHWP-4 FEED

CHWP-4

CWP-4 CB

CWP-4 FUSE FEED

CWP-4

CWP-4 60 A FUSE

CWP-4 FEED

800 A P4Z CB

P4Z FEED

P4Z

200 A 4A CB

4A FEED

PNL 4A

XFMR 2A CB

XFMR 2A FEED

S

P

75KVA XFMR 2A

2A-1 FEED

PNL 2A-1

2A-2 FEED

PNL 2A-2

2B FEED

PNL 2B

XFMR 2F1 FEED

S

P30KVA XFMR 2F1

2F1 FEED

PNL 2F1

PNL 4F

4F FEED

100 A 4F CB

GEN SET CB

XFMR 2F FEED

S

P 30KVA XFMR 2F

2F FEED

PNL 2F

XFMR 2GE FEED

S

P

30KVA XFMR 2GE

2GE FEED

PNL 2GE

PNL 4GE

4GE FEED

150 A 4GE CB

MCC2 FEED

XFMR 2GE CB MCC2 CB

MCC2

ASU 15S FUSE

ASU 15S FEED

ASU 15S

ASU 15R FUSE

ASU 15R FEED

ASU 15R

ASU 14R FUSE

ASU 14R FEED

ASU 14R

ASU 14S FUSE

ASU 14S FEED

ASU 14S

XFMR P2Z FEED

S

P

75KVA XFMR P2Z

P2Z FEED

XFMR P2Z CB

PNL P2Z

SONNYS FEED

SONNY'S

ELE#50 FUSE

ELE#50 FEED

ELE #50

ELEV #50 DISC CB

ELEV#50 DISC FEED

MCC12 CB

MCC12 FEED

MCC12

CWP5 FEED

CWP5

CHWP-5 FEED

CHWP-5 CB

CHWP-5

CWP5 FUSE

CWP5 FUSE FEED

4D CB

4D FEED

PNL 4D

2D2 CB

2D2 FEED

PNL 2D2

XFMR 2D FEED

S

P

45KVA XFMR 2D

2D FEED

XFMR 2D CB

PNL 2D

2D1 FEED

PNL 2D1

4DE CB

4DE FEED

PNL 4DE

DHRC2 CB DHRC3 CB

DHRC3 FEEDDHRC2 FEED

DHRC2 DHRC3

4M CB 1

4M FEED 1

4M CB 2

4M FEED 2

PNL 4M

SF2B CB SF2A CB

SF2B FEED

SF2B

SF2B FUSE

SF2B FUSE FEED

SF2A FEED

SF2A

SF2A FUSE

SF2A FUSE FEED

4K CB 1

4K FEED 1

4K CB 2

4K FEED 2

PNL 4K

4I CB

4I FEED

PNL 4I

CHILLER 1 FEED

CHILLER1 CB1

CHILLER1 CB2

CHILLER 1

MCC4 FEED

MCC4 CB

MCC4 ASU13 FUSE ASU13 FEED ASU13

ASU11 FUSE ASU11 FEED ASU11

ASU12 FUSE ASU12 FEED ASU12

CWP1 FUSE CWP1 FEED CWP1CWP1 FUSE2 CWP1 FEED2

PNL 4L

4L CB 1

4L FEED 1

4L CB 2

4L FEED 2

4C CB

4C FEED

PNL 4C

XFMR 2C2 FEED

S

P

30KVA XFMR 2C2

2C2 FEED

PNL 2C2

XFMR 2C FEED

S

P

45KVA XFMR 2C

2C FEED

PNL 2C

800 A EDP15 CB

EDP15 XFMR FEED

S

P1000KVA XFMR EDP15

EDP15 FEED

PNL EDP15

EDP-E CB

EDP-E FEED

PNL EDP-E

2D3 CB

2D3 FEED

PNL 2D3

800 A WCU-4 CB

WCU-4 SW FEED

WCU-4 SW

WCU-4

800 A WCU-5 CB

WCU-5 SW FEED

WCU-5 SW

WCU-5

P4X FEED

PNL P4X

EF-11 CB

EF-11 FUSE FEED

EF-11 FEED

EF-11

EF-11 FUSE

ELEV1 CB1

ELEV1 CB FEED

ELEV1 CB2

ELEV1 XFMR FEED

S

P 27KVA XFMR ELEV1

ELEV1 FEED

ELEV1

WCU-4 FEED WCU-5 FEED

ELEV2 CB1

ELEV2 CB FEED

ELEV2 CB2

ELEV2 XFMR FEED

S

P 27KVA XFMR ELEV2

ELEV2 FEED

ELEV2

3200 A Main CB2

S

P

1500KVA XFMR2

SWGR #2

MBP-B FEED1

UPS B CB1

UPS-B

Open

UPS CB2

UPS B CB3

MBP-B FEED2

MBP-B FEED4

MBP-B FEED3

SSD-B FEED

PNL SSD-B

STS-B CB1

STS-B FEED1

STS-A CB1

STS-A FEED1

MBP-A FEED1

UPS A CB1

UPS-A

Open

UPS A CB2

UPS A CB3

MBP-A FEED2

MBP-A FEED4

MBP-A FEED3

SSD-A FEED

PNL SSD-A

STS-A CB2

STS-A FEED2

STS-B CB2

STS-B FEED2

STS-B

STS-B CB4STS-B CB3

U4B FEED

PNL U4B

PDU1 CB

PDU1 FEED

PDU1

PDU3 CB

PDU3 FEED

PDU3

STS-A

STS-A CB4STS-A CB3

U4A FEED

PNL U4A

PDU2 CB

PDU2 FEED

PDU2

PDU4 CB

PDU4 FEED

PDU4

SONNY'S CBXFMR 2F CBXFMR 2F1 CB

PNL 2B CB

XFMR 2J CB

XFMR 2J FEED

E N

ATS-1

800 A P4X CB

= Recommended changes

Page 325: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

USB-5

3200 A Main CB3

S

P

1500KVA XFMR3

UTIL

4J CB 800 A P4A CB

P4A FEED4J FEED

PNL 4J

SF1A CB

SF1A FUSE FEEDSF1A FUSESF1A FEEDSF1A

SF1B CB

SF1B FUSE FEEDSF1B FUSESF1B FEEDSF1B

4F-13 CB

SFGA FUSE FEED

SFGA

SFGA FUSE

SFGA FEED

PNL 4F-13

PNL 4F-13 FEED

PNL P4A

XFMR 2GA CB

XFMR 2GA FEED

S

P 45KVA XFMR 2GA

2GA FEED

PNL 2GA

PNL 2GA2

2GA2 FEED

XFMR 2GB CB

XFMR 2GB FEED

S

P 45KVA XFMR 2GB

2GB FEED

PNL 2GB

PNL 2GB2

2GB2 FEED

4G-104 CB

PNL 4G-104

PNL 4G-104 FEED

4B CB

PNL 4B

PNL 4B FEED

2B1 FEED

PNL 2B1

2B2 FEED

PNL 2B2

800 A P4B CB

P4B FEED

PNL P4B

4C-12 CB

PNL 4C-12

PNL 4C-12 FEED

XFMR 2CA FEED

S

P 50KVA XFMR 2CA

2CA FEED

PNL 2CA

2C1 FEED

PNL 2C1

2C2-12 FEED

PNL 2C2-12

4CH CB

PNL 4H

PNL 4H FEED

400 A P4D CB

P4D FEED

PNL P4D

P2D CB

XFMR P2D FEED

S

P

45KVA XFMR P2D

P2D FUSE FEED

P2D FUSE

P2D FEED

PNL P2D

4D1 CB

PNL 4D1

PNL 4D1 FEED

XFMR 2D1 FEED

S

P 45KVA XFMR 2D1

2D1-02 FEED

PNL 2D1-02

KL CB

XFMR KL FEED

S

P 112.5KVA XFMR KL

KL FUSE FEED

KL FUSE

2C-12 CB

XFMR 2C-12 FEED

S

P 75KVA XFMR 2C-12

2C-12 FEED

PNL 2C-12

2C3 FEED

PNL 2C3

800 A MCC3 CB

MCC3 FEED

MCC-3

P-19-1 FUSE

P-19-1

P-19-1 FEED

P-19-2 FUSE

P-19-2

P-19-2 FEED

2P-1 FUSE

2P-1 CB FEED

2P-1 CB

XFMR 2P-1 FEED

S

P75KVA XFMR 2P-1

2P-1 FEED

PNL 2P-1

2P-2 FEED

PNL 2P-2

ELEV 4&5 FUSE

ELEV 4&5 FEED

ELEV 4 FUSE FEED

ELEV 4

ELEV 5 FUSE FEED

ELEV 5

ELEV 4 FUSE ELEV 5 FUSE

ELEV 5 FEEDELEV 4 FEED

4K PENTHOUSE CB

PNL 4K PENTHOUSE FEED

PNL 4K PENTHOUSE FUSE

PNL 4K PENTHOUSE

2K CB

XFMR 2K FEED

S

P9KVA XFMR 2K

2K FEED

PNL 2K

2K1 FEED

PNL 2K1

TOWER41 FUSE

TOWER41

TOWER41 FEED

TOWER41 CB

TOWER41 FUSE FEED

TOWER42 FUSE

TOWER42

TOWER42 FEED

TOWER42 CB

TOWER42 FUSE FEED

2L-1 CB

XFMR 2L-1 FEED

S

P45KVA XFMR 2L-1

2L-1 FEED

PNL 2L-1

2L-2 FEED

PNL 2L-2

2L-3 FEED

PNL 2L-3

2K-232 XFMR CB

XFMR 2K-232 FEED

S

P45KVA XFMR 2K-232

2K-232 CB FEED

PNL 2K-232 SEC1

2K-232 SEC2 FEED

PNL 2K-232 SEC2

2K-232 CB1

2K-232 FEED

2K-232 CB2

2K-232 SEC3 FEED

PNL 2K-232 SEC3

2G1 JUNC FEED

2G1 JUNC FUSE

2H FUSE FEED

2H JUNC FUSE

2H JUNC FEED

2H-1 FUSE FEED

2H-1 FUSE

2H-1 XFMR FEED

S

P25KVA XFMR 2H-1

2H-1 FEED

PNL 2H-1

2H-2 FUSE1 FEED

2H-2 FUSE1

2H-2 XFMR FEED

S

P 25KVA XFMR 2H-2

2H-2 FUSE2 FEED

2H-2 FUSE2

2H-2 FEED

PNL 2H-2

2H FEED

PNL 2H

2H-3 FEED

PNL 2H-3

800 A EB2 CB

EB2 FEED

EB2

PNL KL

2B1 CB

XFMR 2B1 FEED

S

P75KVA XFMR 2B1

2CA CB 2D1 CB

= Recommended changes

Page 326: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

FIRE PUMP FEED1

FIRE PUMP

FIRE PUMP CB1

FIRE PUMP FEED2

FIRE PUMP CB2

FIRE PUMP FEED3

FIRE PUMP CB3

FIRE PUMP FEED4

S

P

FIRE PUMP XFMR

FIRE PUMP UTIL

PNL U XFMR CB

USDP-B

UPSDP-B UTIL

PNL U XFMR FEED

S

P45KVA XFMR U

PNL U FEED

PNL UPNL 2U-1 CB

PNL 2U-1 FEED

PNL 2U-1

PNL EDP-D CB1

PNL EDP-D XFMR FEED1S

P75KVA EDP-D XFMR

PNL EDP-D XFMR FEED2

PNL EDP-D CB2

PNL EDP-D FEED

PNL EDP-D

PNL EDP-D CB1 FEED

PNL 7 CB

PNL 7 FEED

PNL 7

PNL 6 CB

PNL 6 FEED

PNL 6

PNL 5 CB

PNL 5 FEED

PNL 5

PNL 4 CB

PNL 4 FEED

PNL 4

PNL 3 CB

PNL 3 FEED

PNL 3

PNL 2 CB

PNL 2 FEED

PNL 2

PNL 1 CB

PNL 1 FEED

PNL 1

XFMR 2UPSS-1 CB

XFMR 2UPSS-1 FEED

S

P75KVA XFMR 2UPSS-1

2UPSS-1 FEED

PNL 2UPSS-1

PNL 2UPSS-1 CB

2UPSS-2 FEED

PNL 2UPSS-2

2UPSS-3 FEED

PNL 2UPSS-3

2UPSS-4 FEED

PNL 2UPSS-4

XFMR 2UPSN-1 CB

XFMR 2UPSN-1 FEED

S

P45KVA XFMR 2UPSN-1

2UPSN-1 FEED

PNL 2UPSN-1

PNL 2UPSN-1 CB

2UPSN-2 FEED

PNL 2UPSN-2

Page 327: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

ADJUSTABLE LOW VOLTAGE CIRCUIT BREAKER SETTINGS

DESIGNATION

INST

P.U.

S.D.

TIME

S.D.

P.U.

L.D.

TIME

L.T.

P.U.

TRIP UNIT

SETTINGS

TYPE/MODELDescriptionAmps

Sensor/Plug

TYPE

MODELMFRFunctionLocation/NameAIC

kA

Frame

Frame

Amps ( I2T ) GFPU GFD

MDS-608 200800 CUTLER-HAMMER

Magnum DS,RMS 520

LSI, 800AF,200-800A Plugs

PhaseUSB-1, 200 A EH3ACB

20065 1 (200A) 24 10(2000A)

0.5 (I^2t In) M1(14)(2800A)Ground

MDS-632 3,2003,200 CUTLER-H

AMMER

Magnum DS,

DT 520

LSI, 3200AF,

200-3200AP

PhaseUSB-1, 3200 A Main

CB1

3,20065 1

(3200A)

24 10

(32000A

)

0.5 (I^2t Out) 4

(12800A

)Ground

MDS-632 3,2003,200 CUTLER-H

AMMER

Magnum DS,

DT 520

LSI, 3200AF,

200-3200AP

PhaseUSB-2, 3200 A Main

CB2

3,20065 1

(3200A)

24 10

(32000A

)

0.5 (I^2t Out) 3

(9600A)Ground

MDS-632 3,2003,200 CUTLER-H

AMMER

Magnum DS,

DT 520

LSI, 3200AF,

200-3200AP

PhaseUSB-5, 3200 A Main

CB3

3,20065 1

(3200A)

24 10

(32000A

)

0.5 (I^2t Out) 4

(12800A

)Ground

MDS-632 3,2003,200 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 3200AF,

3000-3200A

Plugs

PhaseUSB-1, 3200 A TIE CB 3,20065 1

(3200A)

24 10

(32000A

)

0.5 (I^2t Out) M1(10)

(32000A

)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 400 A 4G CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) 10

(4000A)Ground

MDS-608 400800 CUTLER-HAMMER

Magnum DS,RMS 520

LSI, 800AF,200-800A Plugs

PhaseUSB-2, 400 A 4J1 CB 40065 1 (400A) 24 10(4000A)

0.5 (I^2t In) M1(14)(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 400 A ATS-1

CB

40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 400 A H2A CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 400 A H3A CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 400 A H3B CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 400 A H4A CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

Project: FAB

= Recommended changes to breaker settings

Page 328: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

DESIGNATION

INST

P.U.

S.D.

TIME

S.D.

P.U.

L.D.

TIME

L.T.

P.U.

TRIP UNIT

SETTINGS

TYPE/MODELDescriptionAmps

Sensor/Plug

TYPE

MODELMFRFunctionLocation/NameAIC

kA

Frame

Frame

Amps ( I2T ) GFPU GFD

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 400 A H5A CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 400 A HPA CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-5, 400 A P4D CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 400800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-5, 4J CB 40065 1 (400A) 24 10

(4000A)

0.5 (I^2t In) M1(14)

(5600A)Ground

MDS-608 600800 CUTLER-HAMMER

Magnum DS,RMS 520

LSI, 800AF,200-800A Plugs

PhaseUSB-1, 600 A USB-1CB

60065 1 (600A) 24 10(6000A)

0.5 (I^2t In) M1(14)(8400A)Ground

MDS-608 600800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 600 A USB-2

CB

60065 1 (600A) 24 10

(6000A)

0.5 (I^2t In) M1(14)

(8400A)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-5, 800 A EB2 CB 80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 800 A EDP15

CB

80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 800 A EHRA

CB

80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 800 A MCC10

CB

80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-HAMMER

Magnum DS,RMS 520

LSI, 800AF,200-800A Plugs

PhaseUSB-5, 800 A MCC3CB

80065 1 (800A) 24 10(8000A)

0.5 (I^2t In) M1(14)(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-5, 800 A P4A CB 80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-5, 800 A P4B CB 80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 800 A P4X CB 80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

Page 329: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

DESIGNATION

INST

P.U.

S.D.

TIME

S.D.

P.U.

L.D.

TIME

L.T.

P.U.

TRIP UNIT

SETTINGS

TYPE/MODELDescriptionAmps

Sensor/Plug

TYPE

MODELMFRFunctionLocation/NameAIC

kA

Frame

Frame

Amps ( I2T ) GFPU GFD

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-1, 800 A P4Y CB 80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 800 A P4Z CB 80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 800 A WCU-4

CB

80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

MDS-608 800800 CUTLER-H

AMMER

Magnum DS,

RMS 520

LSI, 800AF,

200-800A Plugs

PhaseUSB-2, 800 A WCU-5

CB

80065 1 (800A) 24 10

(8000A)

0.5 (I^2t In) M1(14)

(11200A

)Ground

SMD6 800800 SIEMENS SMD6, Sensitrip

III

LSI, 600-800APhasePNL EDP15, EDP-E

CB

80065 100 %

(800A)

27 10

(8000A)

0.45 I2t (I^2t In) 40

(32000A

)Ground

PG 4001,200 SQUARE D Powerpact

P-Frame,6.0A/P/H

LSI,

100-1200A, UL

PhaseGEN 1 BUS, GEN SET

CB

035 1 16 10

(4000A)

0.4 (I^2t Out) 3

(1200A)Ground

CHLD 500600 WESTINGH

OUSE

HLD/CHLDRMS310 LSPhaseWCU-4 SW BUS,

WCU-4 SW

065 1.0

(500A)

LTD 8.0

(4000A)

STD (I^2t In)

Ground

CHLD 500600 WESTINGH

OUSE

HLD/CHLDRMS310 LSPhaseWCU-5 SW BUS,

WCU-5 SW

065 1.0

(500A)

LTD 8.0

(4000A)

STD (I^2t In)

Ground

Page 330: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

A B C D E F G H I J K L M N O P Q R

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level Label # Cable Length

Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device

Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft)

(kA) (kA) (kA) (kA) (sec.) (sec.) (in)

EMDP-P 400 A ATS-1

CB

0.48 27.95 15.78 27.86 15.73 0.066 0.000 Yes PNL 25 35 18 3.6 Category 1 (*S0) # 0001 100.00

MCC10 800 A MCC10

CB

0.48 27.08 15.36 26.53 15.05 0.066 0.000 Yes PNL 25 35 18 3.5 Category 1 (*S0) # 0003 220.00

MCC12 MCC12 CB 0.48 9.34 6.19 9.10 6.03 0.017 0.000 Yes PNL 25 8 18 0.33 Category 0 (*S0) # 0004 250.00

MCC2 MCC2 CB 0.48 9.76 6.42 9.35 6.15 0.014 0.000 Yes PNL 25 8 18 0.29 Category 0 (*S0) # 0005 10.00

MCC-3 800 A MCC3

CB

0.48 31.93 17.68 31.03 17.18 0.066 0.000 Yes PNL 25 38 18 4.1 Category 2 (*S0) # 0002 50.00

MCC4 MCC4 CB 0.48 25.57 14.62 25.06 14.33 0.01 0.000 Yes PNL 25 11 18 0.50 Category 0 (*S0) # 0006 20.00

P4Y 800 A P4Y CB 0.48 31.78 17.61 29.71 16.46 0.066 0.000 Yes PNL 25 38 18 4.0 Category 2 (*S0) # 0007 25.00

P4Z 800 A P4Z CB 0.48 44.63 23.53 37.55 19.80 0.066 0.000 Yes PNL 25 46 18 5.5 Category 2 (*S0) # 0008 38.00

PDU1 PDU1 CB 0.48 1.19 1.06 1.19 1.06 2 0.000 No PNL 25 56 18 7.6 Category 2 (*N9)

(*S0)

# 0009 90.00

PDU2 PDU2 CB 0.48 1.19 1.06 1.19 1.06 2 0.000 No PNL 25 56 18 7.6 Category 2 (*N9)

(*S0)

# 0010 90.00

PDU3 PDU3 CB 0.48 1.18 1.05 1.18 1.05 2 0.000 No PNL 25 55 18 7.6 Category 2 (*N9)

(*S0)

# 0011 160.00

PDU4 PDU4 CB 0.48 1.18 1.06 1.18 1.06 2 0.000 No PNL 25 56 18 7.6 Category 2 (*N9)

(*S0)

# 0012 130.00

PNL 1 PNL EDP-D

CB2

0.12 2.14 2.14 2.14 2.14 0.315 0.000 Yes PNL 25 7 18 0.20 Category 0 (*N5)

(*N11) (*S0)

# 0013 240.00

PNL 12E XFMR 12E CB 0.12 3.38 3.38 3.38 3.38 2 0.000 Yes PNL 25 23 18 2.0 Category 1 (*N9)

(*N11) (*S1)

# 0013 10.00

PNL 14E 14E CB 0.48 23.90 13.80 23.90 13.80 0.017 0.000 Yes PNL 25 14 18 0.80 Category 0 (*S0) # 0014 18.00

PNL 2 PNL EDP-D

CB2

0.12 2.14 2.14 2.14 2.14 0.315 0.000 Yes PNL 25 7 18 0.20 Category 0 (*N5)

(*N11) (*S0)

# 0016 240.00

PNL 2A-1 XFMR 2A CB 0.12 7.21 7.21 7.21 7.21 0.012 0.000 Yes PNL 25 3 18 0.02 Category 0 (*N11)

(*S0)

# 0015 16.00

PNL 2A-2 XFMR 2A CB 0.12 6.95 6.95 6.95 6.95 0.012 0.000 Yes PNL 25 3 18 0.02 Category 0 (*N11)

(*S0)

# 0016 22.00

PNL 2B PNL 2B CB 0.12 1.47 1.47 1.47 1.47 0.017 0.000 Yes PNL 25 1 18 0.01 Category 0 (*N11)

(*S0)

# 0017 50.00

PNL 2B1 2B1 CB 0.12 5.25 5.25 5.25 5.25 0.017 0.000 Yes PNL 25 3 18 0.03 Category 0 (*N11)

(*S0)

# 0018 50.00

PNL 2B2 2B1 CB 0.12 5.10 5.10 5.10 5.10 0.017 0.000 Yes PNL 25 3 18 0.03 Category 0 (*N11)

(*S0)

# 0019 56.00

PNL 2C 4C CB 0.12 4.83 4.83 4.83 4.83 2 0.000 Yes PNL 25 28 18 2.8 Category 1 (*N9)

(*N11) (*S0)

# 0020 97.00

PNL 2C1 2CA CB 0.12 5.83 5.83 5.83 5.83 0.01 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S0)

# 0022 32.00

PNL 2C-12 2C-12 CB 0.12 4.83 4.83 4.83 4.83 0.849 0.000 Yes PNL 25 18 18 1.2 Category 1 (*N11)

(*S0)

# 0021 155.00

PNL 2C2 4C CB 0.12 2.07 2.07 2.07 2.07 2 0.000 Yes PNL 25 18 18 1.2 Category 1 (*N9)

(*N11) (*S0)

# 0023 101.00

PNL 2C2-12 2CA CB 0.12 5.61 5.61 5.61 5.61 0.01 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S0)

# 0024 36.00

PNL 2C3 2C-12 CB 0.12 4.62 4.62 4.62 4.62 1.069 0.000 Yes PNL 25 20 18 1.4 Category 1 (*N11)

(*S0)

# 0025 159.00

Arc Flash - Worst Case with Recommendations

S0 = Normal Power S1 = Emergency Power

= Changes in arc flash ratings with changes to breaker settings

Page 331: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

59

A B C D E F G H I J K L M N O P Q R

PNL 2CA 2CA CB 0.12 7.08 7.08 7.08 7.08 0.01 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S0)

# 0026 14.00

PNL 2D XFMR 2D CB 0.12 4.77 4.77 4.77 4.77 0.157 0.000 Yes PNL 25 8 18 0.22 Category 0 (*N11)

(*S1)

# 0027 15.00

PNL 2D1 XFMR 2D CB 0.12 1.53 1.53 1.53 1.53 2 0.000 Yes PNL 25 16 18 0.90 Category 0 (*N9)

(*N11) (*S0)

# 0028 145.00

PNL 2D1-02 2D1 CB 0.12 4.26 4.26 4.26 4.26 0.676 0.000 Yes PNL 25 15 18 0.84 Category 0 (*N11)

(*S0)

# 0029 16.00

PNL 2D2 4D CB 0.48 10.73 6.96 10.73 6.96 0.014 0.000 Yes PNL 25 8 18 0.32 Category 0 (*N5)

(*S0)

# 0030 155.00

PNL 2D3 2D3 CB 0.12 4.06 4.06 4.06 4.06 0.025 0.000 Yes PNL 25 3 18 0.03 Category 0 (*N11)

(*S1)

# 0031 170.00

PNL 2E XFMR 2E CB 0.12 1.80 1.80 1.80 1.80 1.937 0.000 Yes PNL 25 17 18 1.0 Category 0 (*N11)

(*S1)

# 0032 13.00

PNL 2F XFMR 2F CB 0.12 3.75 3.75 3.75 3.75 0.574 0.000 Yes PNL 25 13 18 0.63 Category 0 (*N11)

(*S1)

# 0033 16.00

PNL 2F1 XFMR 2F1 CB 0.12 1.91 1.91 1.91 1.91 1.635 0.000 Yes PNL 25 16 18 0.92 Category 0 (*N11)

(*S1)

# 0034 155.00

PNL 2G 60 A XFMR

CB

0.12 4.59 4.59 4.59 4.59 0.203 0.000 Yes PNL 25 9 18 0.27 Category 0 (*N11)

(*S1)

# 0035 13.00

PNL 2GA XFMR 2GA CB 0.12 5.90 5.90 5.90 5.90 0.022 0.000 Yes PNL 25 3 18 0.04 Category 0 (*N11)

(*S0)

# 0036 18.00

PNL 2GA2 XFMR 2GA CB 0.12 5.71 5.71 5.71 5.71 0.022 0.000 Yes PNL 25 3 18 0.04 Category 0 (*N11)

(*S0)

# 0037 22.00

PNL 2GB XFMR 2GB CB 0.12 5.90 5.90 5.90 5.90 0.026 0.000 Yes PNL 25 3 18 0.04 Category 0 (*N11)

(*S0)

# 0038 18.00

PNL 2GB2 XFMR 2GB CB 0.12 5.71 5.71 5.71 5.71 0.028 0.000 Yes PNL 25 4 18 0.05 Category 0 (*N11)

(*S0)

# 0039 22.00

PNL 2GE XFMR 2GE CB 0.12 3.31 3.31 3.31 3.31 0.257 0.000 Yes PNL 25 8 18 0.25 Category 0 (*N11)

(*S1)

# 0040 10.00

PNL 2H 2H-2 FUSE2 0.12 2.21 2.21 2.21 2.21 0.035 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S0)

# 0041 70.00

PNL 2H-1 2H-1 FUSE 0.12 3.84 3.84 3.84 3.84 0.008 0.000 Yes PNL 25 2 18 0.01 Category 0 (*N11)

(*S0)

# 0042 28.00

PNL 2H-2 2H-2 FUSE2 0.12 3.49 3.49 3.49 3.49 0.008 0.000 Yes PNL 25 2 18 0.01 Category 0 (*N11)

(*S0)

# 0043 10.00

PNL 2H-3 2H-2 FUSE2 0.12 3.36 3.36 3.36 3.36 0.008 0.000 Yes PNL 25 1 18 0.01 Category 0 (*N11)

(*S0)

# 0044 14.00

PNL 2J XFMR 2J CB 0.12 2.09 2.09 2.09 2.09 0.565 0.000 Yes PNL 25 10 18 0.35 Category 0 (*N11)

(*S1)

# 0045 12.00

PNL 2K 2K CB 0.12 2.33 2.33 2.33 2.33 1.134 0.000 Yes PNL 25 14 18 0.77 Category 0 (*N11)

(*S0)

# 0046 10.00

PNL 2K1 2K CB 0.12 2.15 2.15 2.15 2.15 1.331 0.000 Yes PNL 25 15 18 0.84 Category 0 (*N11)

(*S0)

# 0050 14.00

PNL 2K-232 SEC1 2K-232 CB2 0.12 2.95 2.95 2.95 2.95 0.012 0.000 Yes PNL 25 2 18 0.01 Category 0 (*N11)

(*S0)

# 0047

PNL 2K-232 SEC2 2K-232 CB2 0.12 2.84 2.84 2.84 2.84 0.012 0.000 Yes PNL 25 2 18 0.01 Category 0 (*N11)

(*S0)

# 0048 8.00

PNL 2K-232 SEC3 2K-232 CB2 0.12 2.73 2.73 2.73 2.73 0.012 0.000 Yes PNL 25 2 18 0.01 Category 0 (*N11)

(*S0)

# 0049 16.00

PNL 2L-1 2L-1 CB 0.12 3.60 3.60 3.60 3.60 1.118 0.000 Yes PNL 25 18 18 1.2 Category 0 (*N11)

(*S0)

# 0051 39.00

PNL 2L-2 2L-1 CB 0.12 3.47 3.47 3.47 3.47 1.241 0.000 Yes PNL 25 18 18 1.3 Category 1 (*N11)

(*S0)

# 0052 45.00

PNL 2L-3 2L-1 CB 0.12 3.10 3.10 3.10 3.10 1.722 0.000 Yes PNL 25 21 18 1.6 Category 1 (*N11)

(*S0)

# 0053 65.00

Page 332: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

60

61

62

63

64

65

66

67

68

69

70

71

72

73

74

75

76

77

78

79

80

81

82

83

84

85

86

87

88

89

90

91

92

93

A B C D E F G H I J K L M N O P Q R

PNL 2P-1 2P-1 FUSE 0.12 4.18 4.18 4.18 4.18 1.535 0.000 Yes PNL 25 23 18 1.9 Category 1 (*N11)

(*S0)

# 0054 96.00

PNL 2P-2 2P-1 FUSE 0.12 3.98 3.98 3.98 3.98 1.942 0.000 Yes PNL 25 25 18 2.3 Category 1 (*N11)

(*S0)

# 0055 102.00

PNL 2U-1 PNL 2U-1 CB 0.12 2.35 2.35 2.35 2.35 2 0.000 Yes PNL 25 19 18 1.4 Category 1 (*N9)

(*N11) (*S0)

# 0058 65.00

PNL 2UPSN-1 PNL 2UPSN-1

CB

0.12 3.99 3.99 3.99 3.99 0.012 0.000 Yes PNL 25 2 18 0.01 Category 0 (*N11)

(*S0)

# 0059

PNL 2UPSN-2 PNL 2UPSN-1

CB

0.12 3.89 3.89 3.89 3.89 0.012 0.000 Yes PNL 25 2 18 0.01 Category 0 (*N11)

(*S0)

# 0060 4.00

PNL 2UPSS-1 PNL 2UPSS-1

CB

0.12 5.55 5.55 5.55 5.55 0.014 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S0)

# 0061

PNL 2UPSS-2 PNL 2UPSS-1

CB

0.12 5.43 5.43 5.43 5.43 0.014 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S0)

# 0062 5.00

PNL 2UPSS-3 PNL 2UPSS-1

CB

0.12 5.31 5.31 5.31 5.31 0.014 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S0)

# 0063 10.00

PNL 2UPSS-4 PNL 2UPSS-1

CB

0.12 5.19 5.19 5.19 5.19 0.015 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S0)

# 0064 15.00

PNL 3 PNL EDP-D

CB2

0.12 3.03 3.03 3.03 3.03 0.026 0.000 Yes PNL 25 3 18 0.02 Category 0 (*N5)

(*N11) (*S0)

# 0065 110.00

PNL 4 PNL EDP-D

CB2

0.12 3.03 3.03 3.03 3.03 0.026 0.000 Yes PNL 25 3 18 0.02 Category 0 (*N5)

(*N11) (*S0)

# 0066 110.00

PNL 4A 200 A 4A CB 0.48 28.86 16.22 28.86 16.22 0.013 0.000 Yes PNL 25 13 18 0.73 Category 0 (*S0) # 0056 50.00

PNL 4B 4B CB 0.48 15.81 9.70 15.81 9.70 0.023 0.000 Yes PNL 25 14 18 0.75 Category 0 (*S0) # 0057 120.00

PNL 4C 4C CB 0.48 22.45 13.09 22.45 13.09 0.014 0.000 Yes PNL 25 12 18 0.61 Category 0 (*S0) # 0058 85.00

PNL 4C-12 4C-12 CB 0.48 20.32 12.01 20.32 12.01 0.023 0.000 Yes PNL 25 16 18 0.95 Category 0 (*S0) # 0059 65.00

PNL 4D 4D CB 0.48 15.00 9.27 15.00 9.27 0.014 0.000 Yes PNL 25 10 18 0.42 Category 0 (*S0) # 0060 130.00

PNL 4D1 4D1 CB 0.48 26.13 14.90 26.13 14.90 0.013 0.000 Yes PNL 25 13 18 0.66 Category 0 (*S0) # 0061 25.00

PNL 4D2 200 A 4D2 CB 0.48 14.13 8.81 13.49 8.41 0.015 0.000 Yes PNL 25 10 18 0.44 Category 0 (*S0) # 0062 130.00

PNL 4DE 4DE CB 0.48 20.11 11.91 19.81 11.73 0.014 0.000 Yes PNL 25 11 18 0.57 Category 0 (*S0) # 0063 130.00

PNL 4E 4E CB 0.48 13.11 8.27 13.11 8.27 0.017 0.000 Yes PNL 25 10 18 0.46 Category 0 (*S0) # 0064 100.00

PNL 4F 100 A 4F CB 0.48 9.52 6.29 9.52 6.29 0.014 0.000 Yes PNL 25 8 18 0.29 Category 0 (*S0) # 0065 190.00

PNL 4F-13 4F-13 CB 0.48 20.59 12.15 20.42 12.05 0.014 0.000 Yes PNL 25 11 18 0.56 Category 0 (*S0) # 0066 40.00

PNL 4G 400 A 4G CB 0.48 10.66 6.92 10.66 6.92 0.066 0.000 Yes PNL 25 20 18 1.5 Category 1 (*S0) # 0067 295.00

PNL 4G-104 4G-104 CB 0.48 31.28 17.37 31.28 17.37 0.012 0.000 Yes PNL 25 13 18 0.69 Category 0 (*S0) # 0068 15.00

PNL 4GE 150 A 4GE CB 0.48 9.91 6.51 9.50 6.24 0.015 0.000 Yes PNL 25 8 18 0.30 Category 0 (*S0) # 0069 190.00

PNL 4H 4CH CB 0.48 25.27 14.48 25.27 14.48 0.023 0.000 Yes PNL 25 18 18 1.2 Category 0 (*S0) # 0070 30.00

PNL 4I 4I CB 0.48 28.08 15.84 22.52 12.70 0.012 0.000 Yes PNL 25 12 18 0.64 Category 0 (*S0) # 0071 100.00

PNL 4J 4J CB 0.48 24.00 13.85 23.48 13.55 0.066 0.000 Yes PNL 25 32 18 3.1 Category 1 (*S0) # 0072 85.00

PNL 4J1 400 A 4J1 CB 0.48 33.75 18.54 33.75 18.54 0.066 0.000 Yes PNL 25 39 18 4.3 Category 2 (*S0) # 0073 55.00

PNL 4J2 400 A 4J1 CB 0.48 33.15 18.26 33.15 18.26 0.066 0.000 Yes PNL 25 39 18 4.2 Category 2 (*S0) # 0074 58.00

PNL 4K 4K CB 2 0.48 9.28 6.15 9.28 6.15 0.017 0.000 Yes PNL 25 8 18 0.33 Category 0 (*S0) # 0075 6.00

PNL 4K PENTHOUSE PNL 4K

PENTHOUSE

FUSE

0.48 21.15 12.43 20.75 12.20 0.004 0.000 Yes PNL 25 6 18 0.18 Category 0 (*S0) # 0076 60.00

PNL 4L 4L CB 1 0.48 18.95 11.32 18.95 11.32 0.014 0.000 Yes PNL 25 11 18 0.54 Category 0 (*N5)

(*S0)

# 0077 113.00

PNL 4M 4M CB 2 0.48 13.25 8.34 13.07 8.23 0.014 0.000 Yes PNL 25 9 18 0.38 Category 0 (*S0) # 0078 4.00

Page 333: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

94

95

96

97

98

99

100

101

102

103

104

105

106

107

108

109

110

111

112

113

114

115

116

117

118

119

120

121

A B C D E F G H I J K L M N O P Q R

PNL 5 PNL 5 CB 0.12 3.75 3.75 3.75 3.75 0.02 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S0)

# 0090 10.00

PNL 6 PNL 6 CB 0.12 3.72 3.72 3.72 3.72 0.02 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S0)

# 0091 12.00

PNL 7 PNL 7 CB 0.12 3.54 3.54 3.54 3.54 0.015 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S0)

# 0092 25.00

PNL EDP15 800 A EDP15

CB

0.12 50.02 50.02 50.02 50.02 0.066 0.000 Yes PNL 25 16 18 0.97 Category 0 (*N11)

(*S0)

# 0080 160.00

PNL EDP-D PNL EDP-D

CB2

0.12 3.91 3.91 3.91 3.91 0.025 0.000 Yes PNL 25 3 18 0.03 Category 0 (*N11)

(*S0)

# 0093 40.00

PNL EDP-E EDP-E CB 0.12 26.21 26.21 26.21 26.21 0.018 0.000 Yes PNL 25 6 18 0.14 Category 0 (*N11)

(*S0)

# 0079 75.00

PNL EMCC-T6 EMCC-T6 CB 0.48 0.94 0.74 0.94 0.74 0.294 0.000 Yes PNL 25 12 18 0.58 Category 0 (*N3)

(*S1)

# 0081 300.00

PNL KL KL FUSE 0.12 10.08 10.08 10.08 10.08 0.017 0.000 Yes PNL 25 4 18 0.05 Category 0 (*N11)

(*S0)

# 0082

PNL L1 L1 200 A

FUSE

0.12 6.05 6.05 6.05 6.05 0.017 0.000 Yes PNL 25 3 18 0.03 Category 0 (*N11)

(*S0)

# 0083 65.00

PNL L1A L1A 200 A

FUSE

0.12 5.88 5.88 5.88 5.88 0.018 0.000 Yes PNL 25 3 18 0.03 Category 0 (*N11)

(*S0)

# 0084 65.00

PNL P1 XFMR P1 CB 0.12 2.21 2.21 2.21 2.21 1.945 0.000 Yes PNL 25 18 18 1.3 Category 1 (*N11)

(*S0)

# 0085 326.00

PNL P2D P2D FUSE 0.12 3.21 3.21 3.21 3.21 0.017 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S0)

# 0086 25.00

PNL P2Z XFMR P2Z CB 0.12 5.82 5.82 5.82 5.82 0.039 0.000 Yes PNL 25 4 18 0.07 Category 0 (*N11)

(*S1)

# 0087 61.00

PNL P4A 800 A P4A CB 0.48 35.37 19.29 35.37 19.29 0.066 0.000 Yes PNL 25 40 18 4.5 Category 2 (*S0) # 0088 6.00

PNL P4B 800 A P4B CB 0.48 32.50 17.95 32.50 17.95 0.066 0.000 Yes PNL 25 38 18 4.1 Category 2 (*S0) # 0089 40.00

PNL P4D 400 A P4D CB 0.48 32.11 17.76 32.11 17.76 0.066 0.000 Yes PNL 25 38 18 4.1 Category 2 (*S0) # 0090 45.00

PNL P4X 800 A P4X CB 0.48 27.85 15.73 27.46 15.51 0.066 0.000 Yes PNL 25 35 18 3.6 Category 1 (*S0) # 0091 205.00

PNL SSD-A STS-B CB2 0.48 1.20 1.07 0.30 0.27 2 0.000 No PNL 25 56 18 7.7 Category 2 (*N9)

(*S0)

# 0092

PNL SSD-B STS-B CB1 0.48 1.20 1.07 0.30 0.27 2 0.000 No PNL 25 56 18 7.7 Category 2 (*N9)

(*S0)

# 0093

PNL U PNL U XFMR

CB

0.12 3.22 3.22 3.22 3.22 2 0.000 Yes PNL 25 23 18 1.9 Category 1 (*N9)

(*N11) (*S0)

# 0109 33.00

PNL U4A UPS B CB3 0.48 1.20 1.07 0.60 0.54 2 0.000 No PNL 25 56 18 7.7 Category 2 (*N5)

(*N9) (*S0)

# 0094 38.00

PNL U4B UPS B CB3 0.48 1.20 1.07 0.60 0.54 2 0.000 No PNL 25 56 18 7.7 Category 2 (*N5)

(*N9) (*S0)

# 0095 38.00

PNL USB-1 600 A USB-1

CB

0.48 30.13 16.83 30.13 16.83 0.066 0.000 Yes PNL 25 37 18 3.8 Category 1 (*S0) # 0096 50.00

PNL USB-2 600 A USB-2

CB

0.48 42.29 22.47 42.29 22.47 0.066 0.000 Yes PNL 25 44 18 5.3 Category 2 (*S0) # 0097 50.00

SONNY'S SONNY'S CB 0.12 4.14 4.14 4.14 4.14 0.014 0.000 Yes PNL 25 2 18 0.02 Category 0 (*N11)

(*S0)

# 0098 35.00

STS-A UPS B CB3 0.48 1.20 1.07 0.60 0.54 2 0.000 No PNL 25 56 18 7.7 Category 2 (*N5)

(*N9) (*S0)

# 0099 23.00

STS-B UPS B CB3 0.48 1.20 1.07 0.60 0.54 2 0.000 No PNL 25 56 18 7.7 Category 2 (*N5)

(*N9) (*S0)

# 0100 23.00

USB-1 3200 A Main

CB1

0.48 33.52 18.43 31.45 17.29 0.066 0.000 Yes PNL 25 39 18 4.2 Category 2 (*S0) # 0101

Page 334: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

122

123

124

125

126

127

128

129

130

131

132

A B C D E F G H I J K L M N O P Q R

USB-2 400 A ATS-1

CB

0.48 49.30 25.62 0.09 0.04 0.083 0.000 Yes PNL 25 53 18 7.1 Category 2 (*S0) # 0102

USB-5 3200 A Main

CB3

0.48 35.92 19.55 31.10 16.93 0.088 0.000 Yes PNL 25 48 18 6.0 Category 2 (*S0) # 0103

Category 0: Nonmelting

or Untreated Fiber with

Weight >= 4.5 oz/sq yd

0.0 - 1.2

cal/cm^2

#Cat 0 = 79 (*N11) - Out of IEEE

1584 Range, Lee

Equation Used.

Applicable for Open

Air only. Existing

Equipment type is not

Open Air!

Category 1: Arc-rated

shirt & pants or arc-

rated coverall

1.2 - 4.0

cal/cm^2

#Cat 1 = 18 (*N3) - Arcing

Current Low

Tolerances Used

Category 2: Arc-rated

shirt & pants or arc-

rated coverall

4.0 - 8.0

cal/cm^2

#Cat 2 = 22 (*N5) -

Miscoordinated,

Upstream Device

Tripped

Category 3: Arc-rated

shirt & pants + arc-rated

coverall + arc-rated arc

flash suit

8.0 - 25.0

cal/cm^2

#Cat 3 = 0 (*N9) - Max Arcing

Duration Reached

Category 4: Arc-rated

shirt & pants + arc-rated

coverall + arc-rated arc

flash suit

25.0 - 40.0

cal/cm^2

#Cat 4 = 0

Category Dangerous!:

DO NOT WORK ON

LIVE!

40.0 - 999.0

cal/cm^2

#Danger = 0 NFPA 70E 2012

Annex D.7 - IEEE

1584 Bus Report

(80% Cleared Fault

Threshold, mis-

coordination checked

Worst Case (*S0) - Base Project

For additional

information refer to

NFPA 70 E, Standard

for Electrical Safety in

the Workplace.

(*S1) - Scenario1

Category 0: Nonmelting

or Untreated Fiber with

Weight >= 4.5 oz/sq yd,

Safety Glasses or

Goggles + Ear Canal

Inserts, Leather Gloves,

Safety glasses, Non-

melting or untreated

natural fiber

(cotton/wool/rayon/silk >

4.5 oz/sq yd), shirt (long-

sleeve), pants (long)., >

50V voltage rated tools

+ Class 0 (minimum)

gloves, Dielectric shoes

or insulating mat (step

and touch potential).

Page 335: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

133

134

A B C D E F G H I J K L M N O P Q R

Category 1: Arc-rated

shirt & pants or arc-

rated coverall , Hardhat

+ Arc-rated hard hat

liner + Safety Glasses

or Goggles + Ear Canal

Inserts, Leather Gloves,

Leather work shoes,

Safety glasses,

electrically rated hard

hat with hood and face

shield., 4 cal/sq cm, Arc-

rated shirt (long-sleeve)

plus Arc-rated pants

(long), or Arc-rated

coverall, plus arc-rated

face shield or arc flash

suit hood, Arc-rated

rainwear as needed., >

50V voltage rated tools

+ Class 0 (minimum)

gloves and leather

protectors (flash) as

needed., Leather shoes

(flash) as needed.

Dielectric shoes or

insulating mat (step and

touch potential).

Category 2: Arc-rated

shirt & pants or arc-

rated coverall , Hardhat

+ Arc-rated hard hat

liner + Safety Glasses

or Goggles + Ear Canal

Inserts, Leather Gloves,

Leather work shoes,

Safety glasses,

electrically rated hard

hat with hood and face

shield. Hearing

protection., 8 cal/sq cm,

Arc-rated shirt (long-

sleeve) plus Arc-rated

pants (long), or Arc-

rated coverall, plus arc-

rated flash suit hood or

arc-rated face shield

and arc rated balaclava,

Arc-rated rainwear as

needed., > 50V voltage

rated tools + Class 0

(minimum) gloves and

leather protectors

(flash)., Leather shoes

(flash) as needed.

Dielectric shoes or

insulating mat (step and

touch potential).

Page 336: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

135

A B C D E F G H I J K L M N O P Q R

Category 3: Arc-rated

shirt & pants + arc-rated

coverall + arc-rated arc

flash suit , Hardhat +

Arc-rated hard hat liner

+ Safety Glasses or

Goggles + Ear Canal

Inserts, Arc-rated

Gloves, Leather work

shoes, Safety glasses,

electrically rated hard

hat with hood and face

shield. Hearing

protection., 25 cal/sq

cm, Arc-rated shirt (long-

sleeve) plus Arc-rated

pants (long) plus Arc-

rated coverall, plus arc

rated arc flash suit

jacket, pants, & hood,

Arc-rated rainwear as

needed., > 50V voltage

rated tools + Class 0

(minimum) gloves and

leather protectors

(flash)., Leather shoes

(flash) as needed.

Dielectric shoes or

insulating mat (step and

touch potential).

Page 337: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

136

137

A B C D E F G H I J K L M N O P Q R

Category 4: Arc-rated

shirt & pants + arc-rated

coverall + arc-rated arc

flash suit , Hardhat +

Arc-rated hard hat liner

+ Safety Glasses or

Goggles + Ear Canal

Inserts, Arc-rated

Gloves, Leather work

shoes, Safety glasses,

electrically rated hard

hat with hood and face

shield. Hearing

protection., 40 cal/sq

cm, Arc-rated shirt (long-

sleeve) plus Arc-rated

pants (long) plus Arc-

rated coverall, plus arc

rated arc flash suit

jacket, pants, & hood,

Arc-rated rainwear as

needed., > 50V voltage

rated tools + Class 0

(minimum) gloves and

leather protectors

(flash)., Leather shoes

(flash) as needed.

Dielectric shoes or

insulating mat (step and

touch potential).

Category Dangerous!:

DO NOT WORK ON

LIVE!, DO NOT WORK

ON LIVE!, DO NOT

WORK ON LIVE!, DO

NOT WORK ON LIVE!,

DO NOT WORK ON

LIVE!, No FR Category

Found

Page 338: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Drawing TitleNTS

PSU Capital Projects & Construction

Building TitleBuilding SubtitleProject Description

(Block XXX)

Building Address Line 1

Building Address Line 2

Revisions :

Drawn :

Checked :

Date :

FOR ALL STRUCTURAL, MECHANICAL, ELECTRICAL,

TELCO AV, AND FIRE SPRINKLER / ALARM INFORMATION

SEE ENGINEER'S DRAWINGS and SPECIFICATIONS.

E-20

BUILDING4TH AVENUE

3200A 400A 200A 400A 400A 400A 400A 800A 800A 600A SPACE400A SPACE

3200ATIE

400A 600A 400A 800A 800A 800A SPACE 800A 800A400A SPACE 800A

USB-1, USB-2LOCATION: LL ROOM 00-22

H5A H4A EH3A H3A H2A H3B HPA EHRA

P4Y800A

RM00-22

VF

D

M

WWP2

VF

D

M

WWP3

VF

D

M

WWP4

L1250A

RM25-03

L1A250A

RM25-03

VF

D

M

ASU9A

M

ASU9A

4D2150A

RM90-05

MMM

CWP1A

M

DHRC-1 CWP1BCHWP

1A

M

CHWP1B

4G225A

2G125A

4J1400A

RMP103

4J2400A

RMP103

2J225A

RMP103

AT

S-1

EMDP-P600A

3200A

4E100A

RM00-16

2E70A

RM00-16

14E225A

RM00-22

12E175A

RM00-22

P1100A

RMP114

MCC10100ARM

00-02

VF

D

M

P18-3

M

CHWP-4

M

CWP-44A

400A

RM00-22

2A-1250A

RM00-22

2A-2400A

RM00-22

2B125A

RM00-70

4F225A

RM80-01

2F225A

RM80-01

4GE225A

RM80-07

2GE100A

RM80-07

MCC2600A

RM80-07

MMM MASU 15S ASU 14SASU 14RASU 15R

VF

DVFD

VF

D

VFD

P2Z300A

RM00-22

SONNY'S250A

P4Z 800A (RM 00-22)

MELE #50

MCHWP-5

M

UNABLETO

LOCATE

MCC12600A

RM00-02

4D600A

RM90-05

2D2A

RM

2D125A

RM90-05

2D1100A

RM90-09

4C225A

RM00-16

2C2100A

RM00-16

2C225A

RM00-16

EDP152500A

RMP101

EDP-EA

RM60-21

2D3225A

RM82-04

20A

200A

200A

SP

AR

E10

0A

150A

200A

90A

110A

150A

4DE400A

RM90-05

MDHRC2

MDHRC3

M MWCU-4 WCU-5

P4X 2500ARM 00-22

VF

D

MEF-11

60A

M

ELEV1

M

ELEV2

3200A

USB-5LOCATION: ROOM 00-02

400A 800A 800A 400A 800A SPACE 800A 800A

4F400A

RM00-13

VF

D

MSFGA

P4A 800ARM 104

2GA175A

RM104

2GA2250A

RM104

2GB175A

RM104

2GB2250A

RM104

70A

4G200A

RM104

125A

4B225A

RM00-08

175

2B1200A

RM00-08

2B2200A

RM00-08

P4B800A

RM170-00

4C200A

RM00-12

4H200A

RM170-00

2CA225A

RM00-12

2C1200A

RM00-12

2C2200A

RM00-12

P4DA

RM00-02

P2D100A

RM00-02

4D1100A

RM00-02

2D1100A

RM00-02

2C375A

RM00-12

2C3200A

RM00-12

MCC-3 400ARM 00-09

VF

D

VF

D

MP-19-1

MP-19-2

2P-1225A

RM00-02

2P-2100A

RM00-02

MELEV 4

MELEV 5

225A

PANEL 4KROOM PENTHOUSE

40A

2K40A

2K1150A

50A

VF

D

M

TOWER41

50A

VF

D

M

TOWER42

70A 100A 50A

MEB2

KL

USB-1 USB-2

4J400A

RM180

NE

ED

SS

HU

TD

OW

N

2H-1100A

RM170

2H-2100A

RM170

2H-3200A

RM170

2H100A

RM115-03

VFD

VFD

M

M

SF 1B

SF 1A

2G1

2F1225A

RM86-03

225A

H6A H7A

SWITCHGEAR#1

SWITCHGEAR#2

60A60A

GGENERATOR

EMCC-T6

100A

ROOFTOP

M

M

30A

2K150A

RM232A

2KSEC 2250ARM

232A

2KSEC 3250ARM

232A

400A

200A

100A

150A

4M200A

RM228A

200A

4K200A

RM232A

200A

4L200A

RM209A

VF

D

VF

D

MMSF2ASF2B

4I400ARM2NDFLR

MECH

225AMCC #4LOCATION: 2ND FLOORMECHANICAL ROOM

CHILLER #1

ASU12

ASU11

ASU13

M

CWP1

MCWP1

VF

D

M

VF

D

VFD MASU#12

MASU#11

225A

ASU#13

2L-1150A

RM209A

2L-2250A

RM209A

2L-3250A

RM209A

Page 339: FOURTH AVENUE BUILDING POWER SYSTEMS STUDY...included short circuit, protective device coordination and arc flash evaluation for the distribution equipment as indicated on the one-line

Drawing TitleNTS

PSU Capital Projects & Construction

Building TitleBuilding SubtitleProject Description

(Block XXX)

Building Address Line 1

Building Address Line 2

Revisions :

Drawn :

Checked :

Date :

FOR ALL STRUCTURAL, MECHANICAL, ELECTRICAL,

TELCO AV, AND FIRE SPRINKLER / ALARM INFORMATION

SEE ENGINEER'S DRAWINGS and SPECIFICATIONS.

E-20

BUILDING4TH AVENUEUSB-1

UPS-B BC-B1 BC-B2 BC-B3

USB-2

UPS-A BC-A1 BC-A2 BC-A3

SSD-ASSD-B MBP-B MBP-A

ST

S-B

ST

S-A

PANEL - U4BLOCATION: ROOM 00-22A

15A SPARE 200A 200A SPARE

PANEL - U4ALOCATION: ROOM 00-22A

60A 60A 90A 90A 200A 150A 200A 150A

PDU #1

RM:OIT

DATACNTR

PDU #3

RM:OIT

DATACNTR

PDU #2

RM:OIT

DATACNTR

PDU #4

RM:OIT

DATACNTR

UPSDP-B600A

RM002-4A

150A 200A200A200A200A200A200A150ASPARE

1250A

RM55-06

2250A

RM55-06

3250A

RM60-05

4250A

RM60-05

5250A

RM60-21

6250A

RM60-21

7250A

RM60-21

PANEL EDP-DROOM 60-21

U225A

RM170

2U-1225A

RM140

G

USB 8ROOM P1 VAULT

TO:SWITCHGEAR #3

STA-1100A

RMP205B

STA-2100A

RMP205B

NC NO NC NO

TO

:S

WIT

CH

GE

AR

#1

TO

:S

WIT

CH

GE

AR

#3

TO

:S

WIT

CH

GE

AR

#2

TO

:S

WIT

CH

GE

AR

#3

DPC1600A

RM90-04A

DPC2600A

RM90-04A

TO UPS-2 SEEENGINEERING DRAWING

TO:SWITCHGEAR #3

MFIREPUMP

P4B800A

RM170-00

2AA250A

RM233

2AB250A

RM233

2BD250A

RM207

2BC250A

RM207

2BB250A

RM207

2BA250A

RM207

P4A 800ARM 104

70A 125A 17530A125A

SEE PAGE 1 FORFURTHER DETAILSON PANEL

SEE PAGE 1 FORFURTHER DETAILSON PANEL

XFMR 2BA XFMR 2AA

2BE250A

RMTELECOM

2AC250A

RMTELECOM