PUMP #1 PUMP #2 MAGNETIC CONTACTOR #1 MAGNETIC CONTACTOR #2 L1 L2 BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!! FOLLOW NATIONAL, STATE AND LOCAL CODES! The Model ALT alternating relay is used to alternate between two loads. It is commonly used in duplex pumping applications to balance the runtime of both pumps. The voltage must be specified in the ALT part number—Table 1 identifies all available Model ALTs. TABLE 1: ALT Model Numbers MODEL ALT-S The Model ALT-S has a single-pole, double-throw output relay and is used in single high-level float applications. When the float switch opens, the alternating relay changes state forcing the other pump to run the next time the float closes. CONNECTIONS (MODEL ALT-S) 1. Mount the Model OT08 octal socket in a convenient location inside the pump control panel. 2. Connect one of the pump's magnetic contactor coils (#1) between socket terminal 2 and L1 of the power supply (see Figure 1). 3. Connect the other pump's magnetic contactor coil (#2) between socket terminal 8 and L1. 4. Connect the power supply L1 to socket terminal 3 and L2 to terminal 4. 5. Connect socket terminals 1 and 5 to one side of the pilot device (pressure switch, float switch or other isolated contact). 6. Connect the unconnected side of the pilot device to L2. 7. Plug the Model ALT into the socket. FIGURE 1: Typical Wiring Diagram for the Model ALT-S ALT-24-S 20–26VAC, SPDT relay ALT-24-X 20–26VAC, DPDT relay ALT-24-S-SW 20–26VAC, SPDT relay w/ manual/automatic switch ALT-24-X-SW 20–26VAC, DPDT relay, w/ manual/automatic switch ALT-115-S 95–125VAC, SPDT relay ALT-115-X 95–125VAC, DPDT relay ALT-115-S-SW 95–125VAC, SPDT relay, w/ manual/automatic switch ALT-115-X-SW 95–125VAC, DPDT relay, w/ manual/automatic switch ALT-230-S 195-250VAC, SPDT relay ALT-230-X 195–250VAC, DPDT relay ALT-230-S-SW 195–250VAC, SPDT relay, w/ manual/automatic switch ALT-230-X-SW 195–250VAC, DPDT relay, w/ manual/automatic switch 2880 North Plaza Drive, Rapid City, SD 57702 (800) 843-8848 · (605) 348-5580 www.symcom.com INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL ALT 1 4 5 8 23 76 SUPPLY PILOT DEVICE L2 L1 NC NO C 1 4 5 8 23 76 MAG. COIL #2 MAG. COIL #1 PRESSURE SWITCH, FLOAT SWITCH OR OTHER ISOLATED CONTACT

Transcript of FORSYMCOM'S MODELALT/media/protection-relays/product-manuals/... · MANUAL/AUTOMATIC SWITCH. The...

Page 1: FORSYMCOM'S MODELALT/media/protection-relays/product-manuals/... · MANUAL/AUTOMATIC SWITCH. The ALT is also available with a built-in switch (-SW option) that can be used to manually

PUMP#1

PUMP#2

MAGNETICCONTACTOR

#1

MAGNETICCONTACTOR

#2

L1 L2

BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!!FOLLOW NATIONAL, STATE AND LOCAL CODES!

The Model ALT alternating relay is used toalternate between two loads. It is commonlyused in duplex pumping applications tobalance the runtime of both pumps. Thevoltage must be specified in the ALT partnumber—Table 1 identifies all availableModel ALTs.

TABLE 1: ALT Model NumbersMODEL ALT-S

The Model ALT-S has a single-pole, double-throw output relay and is used insingle high-level float applications. When the float switch opens, the alternatingrelay changes state forcing the other pump to run the next time the float closes.

CONNECTIONS (MODEL ALT-S)1. Mount the Model OT08 octal socket in a convenient location inside the pump control panel.2. Connect one of the pump's magnetic contactor coils (#1) between socket terminal 2 and L1 of the

power supply (see Figure 1).3. Connect the other pump's magnetic contactor coil (#2) between socket terminal 8 and L1.4. Connect the power supply L1 to socket terminal 3 and L2 to terminal 4.5. Connect socket terminals 1 and 5 to one side of the pilot device (pressure switch, float switch or other isolated contact).6. Connect the unconnected side of the pilot device to L2.7. Plug the Model ALT into the socket.

FIGURE 1: Typical Wiring Diagram for the Model ALT-S

ALT-24-S 20–26VAC, SPDT relayALT-24-X 20–26VAC, DPDT relayALT-24-S-SW 20–26VAC, SPDT relay w/ manual/automatic switchALT-24-X-SW 20–26VAC, DPDT relay, w/ manual/automatic switchALT-115-S 95–125VAC, SPDT relayALT-115-X 95–125VAC, DPDT relayALT-115-S-SW 95–125VAC, SPDT relay, w/ manual/automatic switchALT-115-X-SW 95–125VAC, DPDT relay, w/ manual/automatic switchALT-230-S 195-250VAC, SPDT relayALT-230-X 195–250VAC, DPDT relayALT-230-S-SW 195–250VAC, SPDT relay, w/ manual/automatic switchALT-230-X-SW 195–250VAC, DPDT relay, w/ manual/automatic switch

2880 North Plaza Drive, Rapid City, SD 57702(800) 843-8848 · (605) 348-5580

www.symcom.com

INSTALLATION INSTRUCTIONSFOR SYMCOM'SMODEL ALT

1 458

2 3

7 6

SUPPLY

PILOTDEVICE

L2 L1

NC

NOC

1 458

2 3

7 6MAG. COIL

#2

MAG. COIL#1

PRESSURE SWITCH,FLOAT SWITCH OROTHER ISOLATED

CONTACT

lmpeterson
Stamp
lmpeterson
New Stamp
lmpeterson
Text Box
222 Disk Drive, Rapid City, SD 57701 (800) 843-8848 www.symcom.com
lmpeterson
Rectangle
Page 2: FORSYMCOM'S MODELALT/media/protection-relays/product-manuals/... · MANUAL/AUTOMATIC SWITCH. The ALT is also available with a built-in switch (-SW option) that can be used to manually

LEAD

LAG

S1

F1

F2

F3

L1

L2

L1

L2

L1

L2

F4

F5

F6

S2

12 3

4

567

8

PUMP#1

PUMP#2

MODEL ALT-X

The Model ALT-X has an internal double-pole, double-throw, cross-connectedrelay and is used in dual high-level float applications. The pumps alternate asin the ALT-S version, but the cross-connected relay configuration allows bothpumps to run simultaneously when both the lead and lag floats are closed.

CONNECTIONS (MODEL ALT-X)

1. Mount the Model OT08 octal socket in a convenient location inside the pump control panel.2. The control circuit should be separately fused to avoid disabling the control circuit when one pump is

disconnected for service.3. Connect Pump #1’s magnetic contactor coil between socket terminal 8 and L2 of the power supply.4. Connect Pump #2’s magnetic contactor coil between socket terminal 7 and L2 of the power supply.5. Connect the LEAD pilot device, S1 (pressure switch, float switch or other isolated contact), between

socket terminals 1 and 3. Each time S1 opens, the relay changes state forcing the other pump to runthe next time the float closes.

6. Connect the LAG pilot device, S2, between socket terminals 2 and 3.7. Connect L2 of the power supply to socket terminal 6 and L1 to terminal 3.8. Plug the Model ALT into the socket.

FIGURE 2: Typical Wiring Diagram for the Model ALT-X

MANUAL/AUTOMATIC SWITCHThe ALT is also available with a built-in switch (-SW option) that can be used to manually force one pump to run everytime the float closes. This is useful when a pump has been removed for repair or for test purposes. In the case of theModel ALT-X-SW, the switch essentially forces one pump to be the lead pump, while still allowing the second pump torun if both floats are closed.

F1 & F2: 1–2A TYPICAL SIZE

FOR CONTACTOR COILS

MAGNETIC CONTACTORS

F3–F6: SIZE FOR INDIVIDUAL PUMP APPLICATION

1 458

2 3

7 6

SUPPLY

PILOTDEVICE

MODEL ALT-X

OPTIONALPUMPSAVER® PUMP

PROTECTOR

OPTIONALPUMPSAVER® PUMP

PROTECTOR