Moeller Wiring Manual 02/05 4-1 4 Rotary Switches Page Overview 4-2 ON-OFF Switches, main switches, maintenance switches 4-3 Changeover switches, reversing switches 4-5 (Reversing) star-delta switches 4-6 Multi-speed switches 4-7 Interlock circuits 4-11 Meter selector switches 4-12 Meter selector switches 4-13 Heater switches 4-14 Step switches 4-15 Rotary switches and switch-disconnectors with ATEX approval 4-17 For Immediate Delivery call KMParts.com at (866) 595-9616

Transcript of For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary...

Page 1: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

F

Moeller Wiring Manual 02/05

Rotary Switches

or Immediate Deliv

4

Page

Overview 4-2

ON-OFF Switches, main switches, maintenance switches 4-3

Changeover switches, reversing switches 4-5

(Reversing) star-delta switches 4-6

Multi-speed switches 4-7

Interlock circuits 4-11

Meter selector switches 4-12

Meter selector switches 4-13

Heater switches 4-14

Step switches 4-15

Rotary switches and switch-disconnectors with ATEX approval 4-17

4-1ery call KMParts.com at (866) 595-9616

Page 2: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Moeller Wiring Manual 02/05

4

F

Rotary SwitchesOverview

Use and mounting forms

Moeller rotary switches and switch-disconnectors are used as:a Main switches, main switches used as

Emergency-Stop devices,b ON-OFF switches,c Safety switches,d Changeover switches, e Reversing switches, star-delta switches,

multi-speed switches,f Step switches, control switches, coding

switches, meter selector switches.

The following mounting forms are available:g Flush mounting,h Centre mounting,i Surface mounting,j Service distribution board mounting,k Rear mounting.

Refer to the latest issue of our Main Catalogue for “Industrial Switchgear”.Other contact arrangements are listed in the K115 specialist catalog in addition to the switches listed in the Main Catalogue.

Basic type

P Iu Use as Mounting type

[KW] [A] a b c d e f g h i j k

TM 3.0 10 – x – x – x k k – k –

T0 6.5 20 x x – x x x + k k k +

T3 13 32 x x – x x – + k k k +

T5b 22 63 x x x x x – + – k – +

T5 30 100 x – x x – – + – k – +

T6 55 160 x – – x – – – – + – +

T8 132 3151) x – – x – – – – + – +

P1-25 13 25 x x x – – – + k + k +

P1-32 15 32 x x x – – – + k + k +

P3-63 37 63 x x x – – – + – + k +

P3-100 50 100 x x x – – – + – + k +

P5-125 45 125 x x – – – – + – – – +

P5-160 55 160 x x – – – – + – – – +

P5-250 90 250 x x – – – – + – – – +

P5-315 110 315 x x – – – – + – – – +

P = Max. motor rating; 400/415 V; AC-23 AIu = Max. rated uninterrupted current1) In enclosed version (surface mounting), max. 275 A.kDepending on the number of contact units, function and contact sequence.+ Irrespective of the number of contact units, function and contact sequence.

4-2or Immediate Delivery call KMParts.com at (866) 595-9616

Page 3: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Moeller Wiring Manual 02/05

F

Rotary SwitchesON-OFF Switches, Main Switches, Maintenance Switches

4

ON-OFF switches, main switches

These switches can also be used as switch-disconnectors for lighting, heating or combined loads.Main switches to IEC/EN 60 204 for rear mounting switches with door interlock, padlocking feature, finger-proof incoming terminals, N and PE terminal, red thumb-grip handle (black, if required), warning label.If it is not clear which drive is associated with which main switch, an additional maintenance switch is required close to each drive.

Maintenance switches are fitted to electrical machines or installations to provide safe working conditions in accordance with the safety regulations.By attaching his own padlock to the SVB padlocking feature, the electrician can protect himself against anyone switching on without authorization (a section “Circuit diagram example for maintenance switches with a load shedding contact and (or) switch position indicator”, page 4-4).

T0-2-1P1-25P1-32P3-63P3-100P5-125P5-160P5-250P5-315

Maintenance switches (safety switches) with auxiliary contacts

T0-3-15680

P1-25/.../P1-32/.../P3-63/.../P3-100/.../...N/NHI11

1) Load shedding contact

FS 908

ON

OFF

123456

L1

L2

L3

0 1

FS 908

ON

OFFL1

L2

L3

123456789

101112

N

N

0 1

1)

FS 908

ON

OFF

123456NN

13142122

N

L1

L2

L3N

1)

0 1

4-3or Immediate Delivery call KMParts.com at (866) 595-9616

Page 4: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Rotary SwitchesON-OFF Switches, Main Switches, Maintenance Switches

Moeller Wiring Manual 02/05

4

F

Circuit diagram example for maintenance switches with a load shedding contact and (or) switch position indicator

T0(3)-3-15683 maintenance switch

T0(3)-3-15683 circuit diagram

Function Load shedding: When switching on, the main current contacts close first, then the contactor is activated via the late-make N/O contact. When switching off, the contactor is first disconnected by opening of the early-break contact, then the main contacts isolate the motor supply.Switch position indication: The position of the switch can be signalled to the control panel or mimic diagram panel via additional NO and NC contacts.

P1: OnP2: OffQ11: Load shedding

Q11

L2

NL3

L1

F1

Q112

1

4

3

6

5

F2

1 3 5

2 4 6

M3

7 9 11

8 10 12

Q1

U V W

A2Q11

A1

A2P1 P2

F0

95

96

21

22

F2

O

13

14

I13

14

1-2,3-4,5-6

7-8,11-12

9-10

4-4or Immediate Delivery call KMParts.com at (866) 595-9616

Page 5: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Moeller Wiring Manual 02/05

F

Rotary SwitchesChangeover Switches, Reversing Switches

4

Changeover switches

Reversing switches

T0-3-8212T3-3-8212T5B-3-8212T5-3-8212T6-3-8212T8-3-8212

FS 684

01 2

123456789

101112

01 2L2L1 L3

T0-3-8401T3-3-8401T5B-3-8401T5-3-8401

FS 684

01 2

21 0123456789

10

L2L1 L3

4-5or Immediate Delivery call KMParts.com at (866) 595-9616

Page 6: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Moeller Wiring Manual 02/05

4

F

Rotary Switches(Reversing) Star-Delta Switches

Star-delta switches

Reversing star-delta switches

T0-4-8410T3-4-8410

T5B-4-8410T5-4-8410

FS 635

Y0

123456789

10111213141516

L1 L2 L3 0 Y Δ

U2

U1

V1V2

W1

W2

T0-6-15877T3-6-15877

1) Standard contactor interlock a section “Interlock Circuits”, page 4-11

FS 638

Y0

Y

123456789

10111213141516

L1L2L3

U2

U1

V1V2

W1

W2

1718192021222324

0Y Y

SOND 28 )1

4-6or Immediate Delivery call KMParts.com at (866) 595-9616

Page 7: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Moeller Wiring Manual 02/05

F

Rotary SwitchesMulti-Speed Switches

4

2 speeds, non-reversing

2 separate windings

Tapped winding arrangementT0-4-8440T3-4-8440T5B-4-8440T5-4-8440

a without links

FS 644

01

2

123456789

10111213141516

L1L2L3

1U

1W 1V

2W 2V

2U

1 20

T0-3-8451T3-3-8451T5B-3-8451T5-3-8451

FS 644

01

2

123456789

101112

L1L2L31 2

1U

1W 1V

2U

2W 2V

0

4-7or Immediate Delivery call KMParts.com at (866) 595-9616

Page 8: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Rotary SwitchesMulti-Speed Switches

Moeller Wiring Manual 02/05

4

F

2 speeds, reversing

Tapped winding arrangementT0-6-15866T3-6-15866

T5B-7-15866T5-7-15866

2 separate windings, reversingT0-5-8453T3-5-8453

FS 629

10

12 2

FS 441

10

12 2

123456789

10111213141516

L1L2 L3

1718192021222324

12 0 1 2

1U

1W 1V

2W 2V

2U

FS 629

10

12 2

123456789

1011121314151617181920

12 0 1 2

1U

1W 1V

2U

2W 2V

L1L2L3

4-8or Immediate Delivery call KMParts.com at (866) 595-9616

Page 9: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Rotary SwitchesMulti-Speed Switches

Moeller Wiring Manual 02/05

F

4

3 speeds, non-reversing

Tapped winding arrangement, single winding for low speedT0-6-8455T3-6-8455T5B-6-8455T5-6-8455

0-(A)y- (B)d = (B)y y

FS 616

1

0

2

3

0 1 2 3123456789

101112131415161718192021222324

L1 L2 L3

1U

1W 1V

A B

1U

1W 1V

2W 2V

2U

4-9or Immediate Delivery call KMParts.com at (866) 595-9616

Page 10: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Rotary SwitchesMulti-Speed Switches

Moeller Wiring Manual 02/05

4

F

3 speeds, non-reversing

Tapped winding arrangement, single winding for high speedT0-6-8459T3-6-8459

T5B-6-8459T5-6-8459

0-(B)d- (B)y y -(A)y

FS 616

1

0

2

3

FS 420

21

03

0 1 2 3123456789

101112131415161718192021222324

L1 L2 L3

1U

1W 1V

A B

1U

1W 1V

2W 2V

2U

4-10or Immediate Delivery call KMParts.com at (866) 595-9616

Page 11: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Moeller Wiring Manual 02/05

F

Rotary SwitchesInterlock Circuits

4

Interlock circuits between rotary switches and contactors with overload relays provide neat and economical solutions for many switching drive tasks.The following points are common to all interlock circuits:

• Protection against automatic restarting after a motor overload or power failure

• The facility for remote disconnection (e.g. emergency-stop) can be provided by one or more Off pushbuttons.

Without mains disconnection (SOND 27)Mains disconnection only by contactorprimarily for star-delta circuit

With mains disconnection (SOND 28)Mains disconnection by contactor and switch

Interlock with contactor (SOND 29)Contactor can be energized only when switch is in the Off position

Interlock with contactor (SOND 30)Contactor can be energized only when switch is in an operating position

Q11

Q11

S0

F0

F2

0 21

M3~

Q11

Q1

Circuit as required

Control sectionSOND 27

Power section without mainsdisconnection Q11

Q11

S0

F0

F2

0 21

M3~

Q11

Q1

Control sectionSOND 28

Circuit as required

Power section without mainsdisconnection

Q11

S1

S0

F0

F2

0 21

M3~

Q11

Q1

Q11

Control sectionSOND 29

Power section

Circuit as required

Q11

S1

S0

F0

F2

0 21

M3~

Q11

Q1

Q11

Control sectionSOND 30

Power section

Circuit as required

4-11or Immediate Delivery call KMParts.com at (866) 595-9616

Page 12: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Moeller Wiring Manual 02/05

4

F

Rotary SwitchesSingle-Phase Starting Switches

Meter selector switches enable you to measure currents, voltages and power in three-phase systems with only one measuring device.

Numerous circuits are possible for the different measurements, some of the most common ones being shown below.

Voltmeter selector switches

Ammeter selector switches

T0-3-80073 x phase to phase3 x phase to neutral with “0” position

T0-2-159223 x phase to neutral without “0” position

T0-5-15925T3-5-15925For direct measurement

L1-L2

FS 1410759

0

L2-L3

L3-L1

L1-N

L2-N

L3-N

L3-L

1

123456789

101112

L2-L

3L1

-L2

0 L1-N

L2-N

L3-N

V

L1L2L3 N L1-L2L2-L3

L3-L1

FS 164854

123456

L3-L

1L2

-L3

L1-L

2

78V

L1L2L3

L1

L2

FS 9440

0

L3 L1L2L30123456789

101112131415161718

L1L2 L3

L1L2L3

A

0

4-12or Immediate Delivery call KMParts.com at (866) 595-9616

Page 13: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Moeller Wiring Manual 02/05

F

Rotary SwitchesMeter Selector Switches

4

Ammeter selector switches

Wattmeter selector switches

T0-3-8048T3-3-8048For measurement via transformers, complete rotation possible

L1

L2

FS 9440

0

L3

L1L2L3 00

L1L2L3

123456789

101112

A

T0-5-8043T3-5-8043Two-phase method (Aron circuit) for three-cable installations loaded as required. The sum of the two readings gives the total output.

The Aron circuit will give a correct result for four-cable systems only when the sum of the currents equals zero, i.e. only when the four-cable system is balanced.

FS 953

0

1 2

W1 20

L1L2L3

123456789

101112131415161718

1 2 3 11

4-13or Immediate Delivery call KMParts.com at (866) 595-9616

Page 14: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Moeller Wiring Manual 02/05

4

F

Rotary SwitchesHeater Switches

1-pole disconnection, 3 steps

T0-2-8316T3-2-8316T5B-2-8316

T0-2-15114, complete rotation possible

q switchedQ not switched

Further heater switches, 2- and 3-pole, with alternative circuitry, output stages, and number of steps are described in the Moeller Main Catalogue, Industrial Switchgear and in the catalogue K 115.

FS 420

21

03

12345678

L1 L2 L30 1 2 3

1

I II III

2

3

IIIIII

FS 193840

1+2

1

0

2

12345678

0 11+2 2 0

4-14or Immediate Delivery call KMParts.com at (866) 595-9616

Page 15: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Moeller Wiring Manual 02/05

F

Rotary SwitchesStep Switches

4

One step closed in each position, complete rotation possible

T0-6-8239T3-6-8239

FS 301

12

3 4 567

891011

12

1 2 3 4123456789

1011

6 7 8 95 1110 12

1314151617181920212223

12

24

4-15or Immediate Delivery call KMParts.com at (866) 595-9616

Page 16: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Rotary SwitchesStep Switches

Moeller Wiring Manual 02/05

4

F

Stay-put switches

Changeover switches

On-Off stay-put switches (also usable as main switches, mains isolating device)

On-Off stay-put switches1-pole: T0-1-154012-pole: T0-1-154023-pole: T0-2-15403

FS 415

01

10123456

1-pole: T0-1-154212-pole: T0-2-154223-pole: T0-3-15423

1-pole: T0-1-154312-pole: T0-2-154323-pole: T0-3-15433

FS 429

02 1

123456789

101112

0 12

FS 1401

0HAND AUTO

123456789

101112

0 AUTOHAND

1-pole: T0-1-155212-pole: T0-2-155223-pole: T0-3-15523With pulsed contact in the intermediate position

FS 908

ON

OFF 123456789

101112

0 1

4-16or Immediate Delivery call KMParts.com at (866) 595-9616

Page 17: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Moeller Wiring Manual 02/05

F

Rotary SwitchesRotary Switches and Switch-Disconnectors with ATEX Approval

4

What does ATEX stand for?

ATmosphéres EXplosibles = ATEX

Explosive atmospheres

Gas Dust

Two standards

For manufacturers: 94/9/EC (binding from 06/2003)

For operators: 1999/92/EC (binding from 06/2006)

Device groups

GroupIII

Application fieldMiningeverything apart from mining

Selection of devices by device groups

GroupIIIIIIII

CategoryM1M212 3

Safetyvery highhighvery highhighnormal

Explosion risk assessment

Gas, steam, mistZone 0Zone 1Zone 2

Ex risk

continuous, frequent, long,occasionalnormally not, but otherwise for a short period

Dust

Zone 20Zone 21Zone 22

Selection of devices and protective systems by categories

Category

11, 21, 2, 3

Dust

Zone 20, 21, 22Zone 21, 22 Zone 22

Gas, steam, mist Zone 0, 1, 2 Zone 1, 2 Zone 2

Gas, steam, mistZone 0Zone 1Zone 2

4-17or Immediate Delivery call KMParts.com at (866) 595-9616

Page 18: For Immediate Delivery call KMParts.com at (866) 595 … · Moeller Wiring Manual 02/05 4-3 Rotary Switches 4 ON-OFF Switches, Main Switches, Maintenance Switches ON-OFF switches,

Rotary SwitchesRotary Switches and Switch-Disconnectors with ATEX Approval

Moeller Wiring Manual 02/05

4

F

ATEX approval for Moeller

Moeller offers T rotary switches (from 32 to 100 A) and P switch-disconnectors (from 25 to 100 A) in accordance with the binding ATEX Directive 94/6 EC (binding from 06/2006). The switches are provided with the equipment marking Ex II3D IP5X T90°C and are approved for the Ex zone 22 in explosive dust atmospheres.Explosive dust atmospheres are present in:• Mills,• Metal polishing workshops,• Woodworking facilities,• Cement industry,• Aluminium industry,• Animal feed industry,• Grain storage and preparation,• Agriculture,• Pharmacy etc.

The ATEX switches are used as:• Main switches• Maintenance switches• Repair switches,• ON-OFF switches or,

• Changeover switches.

The following ATEX switches are available:

Note Moeller ATEX switches have passed the EC prototype test for main, maintenance and repair switches for the current ranges from 25 to 100 A. They are approved for explosive dust atmospheres in accordance with category II 3D, with the test number: BVS 04E 106X.For further information see installation instructions AWA1150-2141.

General installation and application notes

• Only suitable cable glands may be used for category 3D!

• Use only temperature resistant cables (> 90°C)!• The maximum surface temperature is 90°C!• Operation only permissible at an ambient

temperature between –20 and +40°C!• Observe the technical data of the switch used!

• Never open the device in dust explosive atmospheres!

• Observe the requirements of EN 50281-1-2!• It should be checked that the device is free of

dust prior to assembly!• Do not open the device when energized!

Current range

T rotary switches

P switch-discon-nectors

25 A – P1-25/I2

32 A T3-.../I2 P1-32/I2

63 A T5B-.../I4 P3-63/I4

100 A T5-.../I5 P3-100/I5

4-18or Immediate Delivery call KMParts.com at (866) 595-9616