start
programmes
Accessiores
Communications
Hyperterminal
Then we have to give name and then
we have to select COM3/COM5 for
making communications and forbaud rate we have to select the
default settings
Then we can see the
temp
Commands will be displayed only after doing this following
File --> Properties--> settings-->ASDI set up --> then we have to
select ECO then ok --> then ok
Lumasense consists 6 relays
--> OTI ALARM
-->OTI TRIP
-->WTI ALARM
-->WTI TRIP
-->COOLING STAGE -1 ON
--> COOLING STAGE-2 ON
For all these relays there will be two set
points one is above temperature ,below
temperature.
For each relay there will be one source
nothing but the temperature channels
Note:- Each command should be preceeded by the symbol
' >'
PROGRAMMING STEPS FOR THERMASSET2
PREPARED BY CHECKED BY
PDFprocessed
withCutePDFevaluationeditionwww.C
utePDF.com
4/3/2010
PDFprocessed
withCutePDFevaluationeditionwww.C
utePDF.com
NPK MVS
http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/http://www.cutepdf.com/ -
8/3/2019 f.o Programming
2/6
PROGRAMMING STEPS FOR THERMASSET2
PREPARED BY CHECKED BY
4/3/2010
NPKMVS
-
8/3/2019 f.o Programming
3/6
N Y
NORMAL MODE
START
To set above
temperature of the relay
Y/N
To see the temperature
settings of all the relays
>r1
1: 145.00 150.00 1
Okay
>b1=155
Attempting Below greater than Above.>b1=140
Okay
>r1
1: 140.00 180.00 1
Okay
>r1
1: 145.00 150.00 1
Okay
>a1=135
Attempting Above less than Below.>a1= 135 Note space between = and
1.
Wrong character in parameter.
>a1=180
Okay
>rall
relay normally operate in three modes
--> normal mode
-->force mode
--> retrive mode
sx-> associates relay x with a source(temp probe channel )
s--> is the source parameter for the logic
syntax: >sx=source-code
ex: >s1=4(1st relay soruce is 4 )
PROGRAMMING STEPS FOR THERMASSET2
PREPARED BY CHECKED BY
4/3/2010
NPK MVS
-
8/3/2019 f.o Programming
4/6
FORCE MODE
>force
To sets force
temperature value for measurement
channel x
synatx >tx=Force-Temperature value
&
>tall(reports force temperature of all
measurement channels)
relay normally operate in three modes--> normal mode
-->force mode
--> retrive mode
>xforce
exit forced temeprature mode
PROGRAMMING STEPS FOR THERMASSET2
PREPARED BY CHECKED BY
4/3/2010
NPK MVS
-
8/3/2019 f.o Programming
5/6
RETIRVE MODE
>rtrv
To retrive the relay
synatx >rtrv=Number-of-data-reprots
(in mins/secs)
for ex
relay normally operate in three modes--> normal mode
-->force mode
--> retrive mode
PROGRAMMING STEPS FOR THERMASSET2
PREPARED BY CHECKED BY
4/3/2010
NPKMVS
-
8/3/2019 f.o Programming
6/6
GENERAL COMMANDS
MAX--> Reports the max temp for
all measurement channels
syntax: >max
>tallreport force temperautes
To change the temperature
range for analogue o/ps
>dall
Displays the analogue o/p range
corresponding to the temperatur
ranges of all channels
to change higher temperature value
syntax:>htx=parameter value
ex: To change value from 200-->150
>ht1=150
to change lower temperature value
syntax:>ltx=parameter value
ex: To change value from -30-->0
>lt1=0
IN Thermasset2 ,
temp measurement range is (-30 TO 200 deg)
-30-->4mA
200-->20mA
PROGRAMMING STEPS FOR THERMASSET2
PREPARED BY CHECKED BY
4/3/2010
NPK MVS