Fm 403 Mod 10 Fire & Life Safety Systems
Transcript of Fm 403 Mod 10 Fire & Life Safety Systems
FM-403FM-403Building Systems & TechnologyBuilding Systems & Technology
Dave Leathers, CFMJim Whittaker, P.E.
Chris Hodges, P.E., RRC
Instructors:
GMU Facility Management Program
Module 10 – Fire and Life Safety SystemsModule 10 – Fire and Life Safety Systems
Purpose• Protect occupants• Protect the asset• Fire suppression• Fire detection• Notification• Evacuation• Extinguish
• Fire alarm systems– Detect– React– Notify– Control– Evacuate
Fire and Life Safety Systems
Fire Protection Program
• Main components of fire protection:– Early detection and alarm system– Means of egress– Compartmentalization– Smoke Control– Fire Suppression Systems– Emergency Power
Fire and Life Safety Systems
Basic Fire Protection Principles
• All the elements for basic fire protection can be broken down into these categories: – passive fire protection systems– active fire protection systems
Fire and Life Safety Systems
Passive Fire Protection• Control the ignition, growth
and spread of fire through the use of fire-resistive materials, or by providing physical barriers to the movement of flame or smoke.
Fire and Life Safety Systems
Passive Fire Protection• Intended to maintain the following:
– Provide structural integrity of floor, wall and ceiling assemblies during a fire for a specified time period
– Compartmentalize the room or space to control the fire spread
– Provide exiting systems for occupants to safely evacuate the building
Fire and Life Safety Systems
Active Fire Protection• Take direct physical action to reduce the
growth rate of fire or the migration of smoke.• Fire sprinkler and smoke control systems that
receive signals, alert occupants, and cause certain fire control measures to occur.
Fire and Life Safety Systems
Fire Protection Codes & Design Standards
• National Fire Protection Agency (NFPA) standards include:– NFPA 10 - Fire Extinguishers
– NFPA 70 - Electrical Systems
– NFPA 72 - Fire Alarm Systems
– NFPA 96 - Kitchen Hoods
– NFPA 90A and 90B - Mechanical Systems
– NFPA 101 - Life Safety
– NFPA 99 - Healthcare Systems and several other standards for special hazard systems
Fire and Life Safety Systems
• Fire codes are often written so that the authority to enforce the code can be a municipality, or other government agency.
• These authorities are called AHJ’s, or Authorities Having Jurisdiction.
Fire Protection Codes & Design Standards
Fire and Life Safety Systems
Performance based fire protection
approach • Evaluating the hazard presented and the
development of the most appropriate method to protect this given hazard– Risk Assessment – Evaluate Hazards – Manage Fire Impact
– Determine Appropriate Fire Protection Tools
Fire and Life Safety Systems
Passive Fire Protection Systems
• The purpose of compartmentalizing is to protect building occupants and property by:– Confining the fire, heat smoke and toxic gases to the
area of origin until the fire is extinguished or completely burns itself out
– Providing areas of refuge for the occupants and protecting firefighters
Fire and Life Safety Systems
Passive Fire Protection Systems
• Primary role of the HVAC system in Fire Protection is to contain smoke allowing occupants to escape– Stairwell pressurization– Atrium exhaust– Fire floor, floor above
and below containment
Fire and Life Safety Systems
Passive Fire Protection Systems
• Smoke rather than actual flames accounts for about 90% of all fire casualties
• One solution is to minimize the use of furnishings and construction materials that produce large quantities of smoke
Fire and Life Safety Systems
Active Fire Protection SystemsTwo Primary Functions
• Fire Detection and Notification
• Fire Suppression
Fire and Life Safety Systems
Fire Detection and Notification Systems
• Purpose– Detect smoke and fire– Notify occupants and firefighters (alarms)– Allow for evacuation of occupants
Fire and Life Safety Systems
Fire Detection and Notification Systems
• Immediate and reliable detection of fire and smoke is essential
• If detection is delayed, paths of egress can become blocked
• Since most buildings and parts of building are vacant at some time, automatic fire detection is usually required
Fire and Life Safety Systems
Fire Detection System Components
• Detectors:– Smoke detectors– Duct detectors– Heat detectors– Pull stations– Flow switches
• Notifiers:– Speakers– Horns/bells– Lights
• Controllers:– Local control panels– Annunciator panels– Main control panels– Tamper switches– Central station notification
device• Other
– Wire– HVAC system connections– Computer, printer, etc.– Trouble alarms
Fire and Life Safety Systems
Fire Detection System
MainPanel
AnnunciatorPanel
MonitoringService
Computer Power In
LocalPanels
FlowSwitch
PullStation
Smoke/Heat
SmokeEF
Horns/Speakers
Lights/Strobes
Fire Suppressions Systems
Fire and Life Safety Systems
Fire Suppressions Systems
• Purpose– Contain the fire– Eliminate the fire
Fire and Life Safety Systems
Fire Suppression System Components
• Piping• Control valves• Fire pumps• Jockey pumps• Air compressors• Fire extinguishers• Chemical systems
• Alarm valves• Sprinkler heads• Automatic valves• Back flow preventers• Strainers• Control valve locks• Indicators
Fire and Life Safety Systems
Fire Suppression System Types
• Wet type system• Dry type system• Pre-action system• Chemical system• Hose• Fire extinguisher
Fire and Life Safety Systems
Fire Suppression System Components
• Automatic Sprinkler Control Design Objectives– “In general terms of property protection, sprinkler
systems are typically designed to achieve fire control...”
– “Fire control can be described as limiting the fire size by decreasing the rate of heat release and pre-wetting adjacent combustibles, while
NFPA Fire Protection Handbook, 19th Edition, p. 10-193.
Fire and Life Safety Systems
Wet Pipe
System
Dry Pipe
System
Pre-action
System
Fire Pumps
• Typically, three types of fire pumps are used: – horizontal split-case, – vertical in-line – and vertical shaft turbine.
Fire and Life Safety Systems
Horizontal Split-case Fire Pump
Fire and Life Safety Systems
Vertical Shaft Turbine Fire Pump
Fire and Life Safety Systems
Vertical In-line Fire Pump
Fire and Life Safety Systems
Maintenance
• Only as good as the design, installation and maintenance of the systems.
• Passive systems do not have the same testing and inspection requirements or standards as active fire protection systems.
• Once the passive system is installed, inspected and accepted by the building official and the certificate of occupancy is issued, the system is generally not re-inspected unless changes to the structure affecting the passive system occur.
Fire and Life Safety Systems
Maintenance – Passive Systems
• Make sure not to overlook passive systems!
• Fire and smoke dampers• Fire-rated walls and
assemblies– Can be voided with a simple
hole
Fire and Life Safety Systems
Maintenance –Testing & Maintenance Program
• Has the occupancy classification changed?
• Have any walls been relocated?
• Are the exits free of obstructions?
• Are the emergency lights operational?
• Have any fire extinguishers been removed or relocated?
• Are fire and smoke walls still intact?
Fire and Life Safety Systems
Fire Alarms Maintenance
• A systematic approach to fire alarm system maintenance should include the following three components: – Inspection and Testing – Maintenance Management
– Operational Considerations
Fire and Life Safety Systems
Fire Alarms Maintenance
Fire Alarm SystemsProblems Maintenance
False alarmsDevices not installed correctlySmoke detectors dirtyTrouble alarmsNot up to current codeAlarms not heardWorking with local authoritiesUnderstanding the code
Test part of the system monthlyClean smoke detectorsOversee all device installationsHave system tested periodically by a
qualified companyDocument all test results
Fire and Life Safety Systems
Suppression Systems Maintenance
Suppression SystemsProblems Maintenance
FreezeAccidental dischargeInadequate flowImproper inspectionsSprinkler heads obstructedControl valves closed or inoperableFailure or fire pumpInadequate number of extinguishersDry system inspectionWater in dry pipe systemsAir compressor or jockey pump failureSprinkler damage in garages
Inspections for open and locked valvesPeriodic operation of fire pumpSystem flow testsMaintenance of jockey pump and
compressorFire extinguisher inspectionsChemical system inspectionsKeeping fume hoods cleanOperation and inspection of automatic
valves
Fire and Life Safety Systems
Fire Pump Maintenance• Two procedures should be followed for testing automatic
transfer switches. – The first procedure consists of simulating normal power
failure while the pump is delivering peak power output to cause connection of the pump motor to the alternate power source. This is to verify that higher than normal currents do not occur during testing of the transfer switch.
– Second, engine generator sets providing emergency or standby power to fire pump assemblies and automatic transfer switches shall be tested routinely and exercised in accordance with NFPA 110, Standard for Emergency and Standby Power Systems. This test is to verify the proper operation of the transfer switch.
Fire and Life Safety Systems
Fire Pump Maintenance
• The fire pump controller is required to have an interconnected transfer switch.
• Operation of the transfer switch is critical, since the main power may fail or be shut off during a fire incident.
Fire and Life Safety Systems
Fire Protection Deficiencies
• Means of Egress
• Fire Detection and Alarm
• Fire Suppression
• Fire Rated Separations
• Emergency Lighting / Exit Signs
Fire and Life Safety Systems
WHAT TO LOOK FOR . . .WHAT TO LOOK FOR . . .
Identification of Identification of DefectsDefects
Fire and Life Safety Systems
• What To Look For . . . Have Alterations Been Made That Could Affect Life/Safety
• Recommendations Periodically Test Detection and Alarm Systems
Routinely Check Egress Routes & Doors
Remove Stored Combustible Materials
Be Careful With Tenant Improvements & Fitouts
Are Alarms Adequate, Y2K & ADA Compliant Is Emergency Egress & Lighting Adequate? Code Violations – Storage, Signage, Fire Stopping, Doors Is Compartmentation & Sprinkler Coverage Adequate? Recalled Sprinklers – Central Omega & Star Sprinklers
Fire and Life Safety Systems
Dead End CorridorsMeans of Egress
NFPA 101 Life Safety Code
• 50 feet in sprinklered Business Occupancies
• 20 Feet in all other occupancies
• Exceptions include small suites and wide areas.
Fire and Life Safety Systems
Dead End Corridorsand
Fire and Life Safety Systems
Insufficient Number of Exits
• < 500 = Two Exits• 500 to 999 = Three Exits• >1000 = Four Exits• Exceptions (Table 1017.2
Spaces With One Means of Egress)
Poorly Identified Exits
• Blocked Exit signs• No Exit Signs• Confusing Exit
Arrangements
Fire and Life Safety Systems
Reversed Door Swing
• Doors must swing in the direction of egress travel when serving 50 or more occupants.
• All means of egress doors in stairwells must swing in the direction of egress travel.
Fire and Life Safety Systems
Exiting in Hazardous Areas
• Not Permitted– Loading Docks– Mechanical Spaces– Any Hazardous
Areas
Fire and Life Safety Systems
Exit Discharge
• Must Lead Directly to a Public Way
• Many Exceptions– Interior Stairwells– Courts– Lobbies– Exit Passageways– Horizontal Exits
Fire and Life Safety Systems
Maintenance
• Storage in corridors• Blocked Doors• Locked Doors• Broken Components
– Handrails– Steps (Stairs)– Doors
Fire and Life Safety Systems
Maintenance and Testing Reports
• Review Recent Reports
• Determine Testing Cycle in NFPA 13
• Verify Existence and Extent of Maintenance and Testing Programs
Fire and Life Safety Systems
ADA Compliance
• Strobe Lights– Wall Mounted– No Ceiling Mounted– Locations
Fire and Life Safety Systems
Monitoring of All Necessary Systems– HVAC– Sprinkler System– Initiating Devices– Notification Appliances– Fire Pump– Magnetic Door Holders
Fire and Life Safety Systems
Monitoring
• Waterflow• Tamper Supervisory• Low Pressure• Fire Pump
Fire and Life Safety Systems
Improperly Protected Hazards
• Change in Use • Incorrect Installation• Incorrect Design• Incorrect Type of
System
Fire and Life Safety Systems
Recalled Sprinklers
• Central Omega• Star Sprinklers
Fire and Life Safety Systems
Penetrations
• Unsealed Penetrations not permitted in Fire Rated Construction
• Unprotected Openings not permitted in Fire Rated Construction
Fire and Life Safety Systems
Automatic Door Closing
• Required for Fire Rated Wall Assemblies
• Ensure operability
Fire and Life Safety Systems
Sign Locations
• Exit Signs– At every exit where
two or more exits are required
• Emergency Lighting– In all means of
egress
Fire and Life Safety Systems
Renovations, alterations and additions require the new construction to meet current codes. Existing systems to remain generally can remain as is and are “grandfathered” under the new codes…with the exception of possibly...
Fire alarm and suppression systems
Fire and Life Safety Systems
BUILDING CODE (EXISTING BUILDING ALTERATION, REPAIR & CONVERSION
D.C. BUILDING CODE SUPPLEMENT OF 1992
100.2.1 D.C. Building Code: BOCA 1990 as amended by D.C. Code Supplement
ARTICLE 33 – ALTERATION, REPAIR & CONVERSION OF EXISTING BUILDINGS
3307.0 High-Rise Buildings – Provisions shall apply to existing buildings over 75’ in height
3307.2 Sprinkler System – An automatic sprinkler system…shall be provided throughout each floor or fire area undergoing alteration or repair work, or being converted to a different use, whenever the extent of the work…exceeds the limits set forth in any of the three tests:
1. Cost of the work exceeds 50% of prorated assessed value
2. New interior walls exceed 50% of length of existing walls
3. Alteration or replacement of HVAC exceeds 2 out of 3 of…
a. Plumbing 150% of piping length…
b. Electrical 75% of wiring length…
c. HVAC serving 75% of the floor area, 75% of L of ductwork…
Fire and Life Safety Systems
Fire & Life SafetyFire and Life Safety Systems
Fire & Life Safety
No Fireproofing
Fire and Life Safety Systems
Dead End Corridor
Fire and Life Safety Systems
Fire & Life Safety
This Is Not An
Exit
?
Confusing Signage
Fire and Life Safety Systems
Fire & Life Safety
Inadequate Fire Stopping
Fire and Life Safety Systems
Inadequate Fire Stopping
Fire and Life Safety Systems
1. Compartmentalization – Open Penetrations
2. Fire Doors Propped, Inadequate Latches/Closers
3. Blocked Exits with Stored Materials
4. ADA Compliant Fire Notification Devices
5. Exits Discharging Into Un-rated Areas
6. Manual Pull Station Locations (Height/5’ of Exits)
7. Egress Doors Swing Wrong Way
8. Smoke/Heat Detection in Mechanical Rooms/Sys
9. Inadequate Sprinkler Coverage (TI Work)
10. Stair Guard Rails/Non-Slip Treads
Extra Credit: Sprinkler Monitors Deactivated, Damaged
Heads, Lack of Spare Heads
Top 10 Fire & Life Safety Code ViolationsTop 10 Fire & Life Safety Code Violations
Fire and Life Safety Systems