Fluorescent Lightingcms.esi.info/Media/documents/Peppe_300bulkead_ML.pdf · Operating current CFL -...

1
Fluorescent Lighting Subject to modifications without notice Pepperl+Fuchs Group www.pepperl-fuchs.com USA: +1 330 486 0002 [email protected] [email protected] Singapore: +65 6779 9091 [email protected] Copyright Pepperl+Fuchs Germany: +49 621 776 2222 155 1.2 110 114 160 135 160 300 All Dimensions in mm. 300 - Ex d & Ex de Bulkhead Fitting for 13 Watt Compact Fluorescent and 60 Watt GLS Material All cast parts - light metal alloy Overtube - borosilicate glass / polycarbonate Reflector - 1.2mm galvanized mild steel Finish Cast metal parts - epoxy powder coated - RAL7032 Reflector – epoxy powder coat – white Cover Fixing M6 allen head stainless steel screws Gasket Nitrile O ring Earthing Internal Entries 2 x 20mm Ex d threaded entries fitted with Ex d stopping plugs Mounting 2 x Stainless Steel removable mounting brackets supplied as standard ENCLOSURE SPECIFICATION Control gear High frequency electronic ballast complying with all European standards relating to safety, operation and EMC (Immunity) Operating voltage 220 – 254 Volts 50/60Hz Operating current CFL - 0.08 Amps, GLS - 0.25 Amps Power factor 0.98 Terminals 2.5mm² connection block suitable for through wiring Lamps 13 Watt compact fluorescent or 60 Watt GLS ELECTRICAL SPECIFICATION HAZARDOUS AREA SPECIFICATION Marking to 94/9/EC II 2 GD Type of Protection 300 CFL/300 GLS series Ex de IIC T* Gb Ex tb IIIC T**°C Db 350 CFL/350 GLS series Ex d IIC T* Gb Ex tb IIIC T**°C Db Ambient Temp.°C Gas Temperature Class (T*C) Dust Temperature Class (T**)(°C) Lamp Type Orientation Min Max -20 +49 T6 85 CFL Horizontal -20 +54 T5 100 CFL Vertical -20 +41 T4 135 GLS Vertical -20 +60 T3 200 GLS Horizontal Ingress Protection Glass overtube - IP67 to EN60529:1992 poylcarbonate over tube - IP6X to EN60529:1992 Area Classification Zones 1,2,21,22 Certification No. SIRA00ATEX1107X GOST-R POCC GB.Mл14.B00223 Lamp Protection Type Overtube Product Code 1 x 13 Watts compact fluorescent de Borosilicate glass 300/CFL 1 x 60 Watts GLS de Borosilicate glass 300/GLS 1 x 13 Watts compact fluorescent d Borosilicate glass 350/CFL 1 x 60 Watts GLS d Borosilicate glass 350/GLS 1 x 13 Watts compact fluorescent de Polycarbonate 300/CFLP 1 x 13 Watts compact fluorescent d Polycarbonate 350/CFLP ORDERING INFORMATION Note: Add /WG to part number if a wire guard is required Pepperl+Fuchs light fittings are not supplied with lamps.

Transcript of Fluorescent Lightingcms.esi.info/Media/documents/Peppe_300bulkead_ML.pdf · Operating current CFL -...

Page 1: Fluorescent Lightingcms.esi.info/Media/documents/Peppe_300bulkead_ML.pdf · Operating current CFL - 0.08 Amps, GLS - 0.25 Amps Power factor 0.98 Terminals 2.5mm² connection block

Fluorescent Lighting

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222 155

1.2

110

114

160

135

160

300

All Dimensions in mm.

300 - Ex d & Ex de Bulkhead Fitting for 13 Watt Compact Fluorescent and 60 Watt GLS

Material All cast parts - light metal alloyOvertube - borosilicate glass / polycarbonateReflector - 1.2mm galvanized mild steel

Finish Cast metal parts - epoxy powder coated - RAL7032 Reflector – epoxy powder coat – white

Cover Fixing M6 allen head stainless steel screws

Gasket Nitrile O ring

Earthing Internal

Entries 2 x 20mm Ex d threaded entries fitted with Ex d stopping plugs

Mounting 2 x Stainless Steel removable mounting brackets supplied as standard

ENCLOSURE SPECIFICATION

Control gear High frequency electronic ballast complying with all European standards relating to safety, operation and EMC (Immunity)

Operating voltage 220 – 254 Volts 50/60Hz

Operating current CFL - 0.08 Amps, GLS - 0.25 Amps

Power factor 0.98

Terminals 2.5mm² connection block suitable for through wiring

Lamps 13 Watt compact fluorescent or 60 Watt GLS

ELECTRICAL SPECIFICATION

HAZARDOUS AREA SPECIFICATION

Marking to 94/9/EC II 2 GD

Type of Protection300 CFL/300 GLS series

Ex de IIC T* GbEx tb IIIC T**°C Db

350 CFL/350 GLS seriesEx d IIC T* GbEx tb IIIC T**°C Db

Ambient Temp.°C Gas Temperature Class (T*C)

Dust Temperature Class (T**)(°C)

Lamp Type

OrientationMin Max

-20 +49 T6 85 CFL Horizontal

-20 +54 T5 100 CFL Vertical

-20 +41 T4 135 GLS Vertical

-20 +60 T3 200 GLS Horizontal

Ingress Protection Glass overtube - IP67 to EN60529:1992poylcarbonate over tube - IP6X to EN60529:1992

Area Classification Zones 1,2,21,22

Certification No. SIRA00ATEX1107XGOST-R POCC GB.Mл14.B00223

Lamp Protection Type Overtube Product Code

1 x 13 Watts compact fluorescent de Borosilicate glass 300/CFL

1 x 60 Watts GLS de Borosilicate glass 300/GLS

1 x 13 Watts compact fluorescent d Borosilicate glass 350/CFL

1 x 60 Watts GLS d Borosilicate glass 350/GLS

1 x 13 Watts compact fluorescent de Polycarbonate 300/CFLP

1 x 13 Watts compact fluorescent d Polycarbonate 350/CFLP

ORDERING INFORMATION

Note: Add /WG to part number if a wire guard is requiredPepperl+Fuchs light fittings are not supplied with lamps.

1.2

148

649

325

390

Ø10.3

120

167

653

B

A

Calstar - Ex de Emergency Fluorescent Exit Fitting for 8 Watt Lamps

ORDERING INFORMATION

Wattage Lamp Length (mm) Weight (Kg) Overtube Product Code

1 x 8 Watts 300 3.8 Borosilicate glass 650/0211

1 x 8 Watts 300 3.8 Polycarbonate 650/0211P

Catalog_eng.indb 155 19.03.2010 10:16:21

falt