Easy Universal Sway Brace
Features• Use for both lateral and longitudinal sway brace applications• Unique slotted holes provide for easy slip-on installation eliminating loose hardware• Snap-off bolt head helps enable easy installation and inspection of seismic sway braces• Works with 1" through 2" brace pipes and 1/4" angle iron braces to reduce inventory• Meets NFPA®-13 requirements for seismic sway bracing
SpecificationsMaterial: SteelFinish: Electro-galvanized
Part Number Pipe Size NB/DN A B Listings Approvals
CSBEZU0100EG 1" 25 mm 174.6 mm 25.4 mm UL, FM
CSBEZU0125EG 1 1/4" 32 mm 187.4 mm 25.4 mm UL, FM
CSBEZU0150EG 1 1/2" 40 mm 196.9 mm 25.4 mm UL, FM
CSBEZU0200EG 2" 50 mm 206.4 mm 30.2 mm UL, FM
CSBEZU0250EG 2 1/2" 65 mm 225.4 mm 30.2 mm cUL, UL, FM
CSBEZU0300EG 3" 80 mm 238.1 mm 30.2 mm cUL, UL, FM
CSBEZU0400EG 4" 100 mm 269.9 mm 38.1 mm cUL, UL, FM
CSBEZU0500EG 5" 125 mm 308 mm 38.1 mm cUL, UL, FM
CSBEZU0600EG 6" 150 mm 346.1 mm 50.8 mm cUL, UL, FM
www.erico.com 3
UL® Loads
Lateral Longitudinal
Part Number LightwallService Pipe
Sch 10 Service Pipe Sch 40 Service PipeLightwall
Service PipeSch 10 Service Pipe Sch 40 Service Pipe
CSBEZU0100EG N/A 2910 N 2910 N N/A 2910 N 2910 N
CSBEZU0125EG 2910 N 2910 N 2910 N 2910 N 2910 N 2910 N
CSBEZU0150EG 2910 N 2910 N 2910 N 2910 N 2910 N 2910 N
CSBEZU0200EG 13340 N 13340 N 13340 N 2910 N 2910 N 2910 N
CSBEZU0250EG 13340 N 13340 N 13340 N 5620 N 5620 N 5620 N
CSBEZU0300EG 13340 N 13340 N 13340 N 5620 N 5620 N 5620 N
CSBEZU0400EG 13340 N 13340 N 13340 N 5620 N 5620 N 5620 N
CSBEZU0500EG 13340 N 13340 N 13340 N 7110 N 7110 N 7110 N
CSBEZU0600EG 13340 N 13340 N 13340 N 7110 N 7110 N 7110 N
FM® Loads (Lightwall, Sch 10 and Sch 40 Service Pipes)
Horizontal Capacity per Installation Angle from Vertical
Lateral LongitudinalPart Number
30° - 44° 45° - 59° 60° - 74° 75° - 90° 30° - 44° 45° - 59° 60° - 74° 75° - 90°
CSBEZU0100EG 3825 N 5425 N 6670 N 7430 N 1735 N 2445 N 2980 N 3335 N
CSBEZU0125EG 3825 N 5425 N 6670 N 7430 N 1735 N 2445 N 2980 N 3335 N
CSBEZU0150EG 3825 N 5425 N 6670 N 7430 N 1735 N 2445 N 2980 N 3335 N
CSBEZU0200EG 6805 N 9610 N 11790 N 13165 N 2315 N 3070 N 3690 N 4136 N
CSBEZU0250EG 6805 N 9610 N 11790 N 13165 N 2315 N 3070 N 3690 N 4136 N
CSBEZU0300EG 6805 N 9610 N 11790 N 13165 N 2315 N 3070 N 3690 N 4136 N
CSBEZU0400EG 6985 N 9875 N 12100 N 13480 N 2800 N 4005 N 4895 N 5470 N
CSBEZU0500EG 6985 N 9875 N 12100 N 13480 N 2800 N 4005 N 4895 N 5470 N
CSBEZU0600EG 8805 N 12500 N 15300 N 17080 N 3245 N 4450 N 5470 N 6095 N
www.erico.com 4
Standard Universal Sway Brace
Features• Use for both lateral and longitudinal sway brace applications• Snap-off bolt head helps enable easy installation and inspection of seismic sway braces• Works with 1" through 2" brace pipes and 1/4" angle iron braces to reduce inventory• Slotted design grabs service pipe for added gripping strength• Meets NFPA®-13 requirements for seismic sway bracing
SpecificationsMaterial: Steel
Part Number Pipe Size NB/DN A B Listings Approvals
Finish: Electro-galvanized
CSBSTU0100EG 1" 25 mm 174.6 mm 25 mm UL, FM
CSBSTU0125EG 1 1/4" 32 mm 187.4 mm 25.4 mm UL, FM
CSBSTU0150EG 1 1/2" 40 mm 196.9 mm 25.4 mm UL, FM
CSBSTU0200EG 2" 50 mm 206.4 mm 30.2 mm UL, FM
CSBSTU0250EG 2 1/2" 65 mm 225.4 mm 30.2 mm cUL, UL, FM
CSBSTU0300EG 3" 80 mm 238.1 mm 30.2 mm cUL, UL, FM
CSBSTU0400EG 4" 100 mm 269.9 mm 38.1 mm cUL, UL, FM
CSBSTU0500EG 5" 125 mm 308 mm 38.1 mm cUL, UL, FM
CSBSTU0600EG 6" 150 mm 346.1 mm 50.8 mm cUL, UL, FM
CSBSTU0800EG 8" 200 mm 400.1 mm 50.8 mm cUL, UL, FM
CSBSTU1000EG 10" 250 mm 457.2 mm 50.8 mm cUL, UL, FM
www.erico.com 5
Part Number Pipe Size NB/DN A B Listings Approvals
Finish: Hot-dip galvanized
CSBSTU0100HD 1" 25 mm 174.6 mm 25 mm UL, FM
CSBSTU0125HD 1 1/4" 32 mm 187.4 mm 25.4 mm UL, FM
CSBSTU0150HD 1 1/2" 40 mm 196.9 mm 25.4 mm UL, FM
CSBSTU0200HD 2" 50 mm 206.4 mm 30.2 mm UL, FM
CSBSTU0300HD 3" 80 mm 238.1 mm 30.2 mm cUL, UL, FM
CSBSTU0400HD 4" 100 mm 269.9 mm 38.1 mm cUL, UL, FM
CSBSTU0500HD 5" 125 mm 308 mm 38.1 mm cUL, UL, FM
CSBSTU0600HD 6" 150 mm 346.1 mm 50.8 mm cUL, UL, FM
CSBSTU0800HD 8" 200 mm 400.1 mm 50.8 mm cUL, UL, FM
CSBSTU1000HD 10" 250 mm 457.2 mm 50.8 mm cUL, UL, FM
UL Loads
Lateral Longitudinal
Part Number LightwallService Pipe
Sch 10 Service Pipe Sch 40 Service PipeLightwall
Service PipeSch 10 Service Pipe Sch 40 Service Pipe
CSBSTU0100xx N/A 2910 N 2910 N N/A 2910 N 2910 N
CSBSTU0125xx 2910 N 2910 N 2910 N 2910 N 2910 N 2910 N
CSBSTU0150xx 2910 N 2910 N 2910 N 2910 N 2910 N 2910 N
CSBSTU0200xx 13340 N 13340 N 13340 N 2910 N 2910 N 2910 N
CSBSTU0250xx 13340 N 13340 N 13340 N 8960 N 8960 N 8960 N
CSBSTU0300xx 13340 N 13340 N 13340 N 8960 N 8960 N 8960 N
CSBSTU0400xx 13340 N 13340 N 13340 N 8960 N 8960 N 8960 N
CSBSTU0500xx 13340 N 13340 N 13340 N N/A 8960 N 8960 N
CSBSTU0600xx 13340 N 13340 N 13340 N 8960 N 8960 N 8960 N
CSBSTU0800xx N/A 13340 N 13340 N N/A 8960 N 8960 N
CSBSTU1000xx N/A 13340 N 13340 N N/A 13340 N 13340 N
FM Loads (Lightwall, Sch 10 and Sch 40 Service Pipes)
Horizontal Capacity per Installation Angle from Vertical
Lateral LongitudinalPart Number
30° - 44° 45° - 59° 60° - 74° 75° - 90° 30° - 44° 45° - 59° 60° - 74° 75° - 90°
CSBSTU0100xx 3825 N 5425 N 6670 N 7430 N 4315 N 3200 N 3825 N 4270 N
CSBSTU0125xx 3825 N 5425 N 6670 N 7430 N 4315 N 3200 N 3825 N 4270 N
CSBSTU0150xx 3825 N 5425 N 6670 N 7430 N 4315 N 3200 N 3825 N 4270 N
CSBSTU0200xx 6805 N 9610 N 11790 N 13165 N 3870 N 3070 N 3690 N 4136 N
CSBSTU0250xx 6805 N 9610 N 11790 N 13165 N 3870 N 3070 N 3690 N 4136 N
CSBSTU0300xx 6805 N 9610 N 11790 N 13165 N 3870 N 3070 N 3690 N 4136 N
CSBSTU0400xx 6985 N 9875 N 12100 N 13480 N 6895 N 6185 N 7475 N 8320 N
CSBSTU0500xx 6985 N 9875 N 12100 N 13480 N 6895 N 6185 N 7475 N 8320 N
CSBSTU0600xx 8805 N 12500 N 15300 N 17080 N 6540 N 5205 N 6270 N 6985 N
www.erico.com 6
FM Loads (4.8 mm wall and Sch 40 Service Pipes)
Horizontal Capacity per Installation Angle from Vertical
Lateral LongitudinalPart Number
30° - 44° 45° - 59° 60° - 74° 75° - 90° 30° - 44° 45° - 59° 60° - 74° 75° - 90°
CSBSTU0800xx 9075 N 12855 N 15745 N 17570 N 5340 N 7560 N 9295 N 10365 N
CSBSTU1000xx 9075 N 12855 N 15745 N 17570 N 5340 N 7560 N 9295 N 10365 N
www.erico.com 7
Quick Grip Jr. Lateral Sway Brace
Features• Easy two-step installation elminates extra trips between structure and service pipe• Works with 1" and 1 1/4" (25 mm and 32 mm) brace pipes to reduce inventory• Snap-off bolt head helps enable easy installation and inspection of seismic sway braces• Meets NFPA®-13 requirements for seismic sway bracing
SpecificationsMaterial: SteelFinish: Electro-galvanized
Part Number Pipe Size NB/DNHeight
HWidth
W
CSBQIKCL0100EG 1" 25 mm 130.2 mm 65.3 mm
CSBQIKCL0125EG 1 1/4" 32 mm 136.5 mm 74.4 mm
CSBQIKCL0150EG 1 1/2" 40 mm 142.9 mm 80.2 mm
CSBQIKCL0200EG 2" 50 mm 161.9 mm 92.3 mm
www.erico.com 8
UL Loads
LateralPart Number Service Pipe Schedule
25 mm Brace Pipe 32 mm Brace Pipe
Lightwall N/A N/A
10 2910 N 2910 NCSBQIKCL0100EG
40 2910 N 2910 N
Lightwall 2910 N 2400 N
10 2910 N 2400 NCSBQIKCL0125EG
40 2910 N 2400 N
Lightwall 3330 N 2910 N
10 3330 N 2910 NCSBQIKCL0150EG
40 3330 N 2910 N
Lightwall 3330 N 2400 N
10 3330 N 2400 NCSBQIKCL0200EG
40 3330 N 2400 N
FM Loads
Lateral
Horizontal per Installation Angle from VerticalPart Number Service Pipe Schedule
30° - 44° 45° - 59° 60° - 74° 75° - 90°
Lightwall 1290 N 1830 N 2200 N 2445 N
10 665 N 935 N 1245 N 1400 NCSBQIKCL0100EG
40 2115 N 2960 N 3670 N 4115 N
Lightwall 1290 N 1830 N 2200 N 2445 N
10 665 N 935 N 1245 N 1400 NCSBQIKCL0125EG
40 2115 N 2960 N 3670 N 4115 N
Lightwall 1290 N 1830 N 2200 N 2445 N
10 665 N 935 N 1245 N 1400 NCSBQIKCL0150EG
40 2115 N 2960 N 3670 N 4115 N
Lightwall 1735 N 2445 N 2980 N 3335 N
10 1555 N 2225 N 2760 N 3070 NCSBQIKCL0200EG
40 2180 N 3070 N 3780 N 4225 N
www.erico.com 9
Quick Grip Lateral Sway Brace
The Quick Grip Lateral Brace, part of the CADDY® line of fire sprinkler bracing systems from ERICO, is designed to helpsimplify installations when bracing service pipe for seismic or other catastrophic events. It features an innovative design forquick attachment of brace pipe to service pipe saving time and money.
Features• Easy two-step installation elminates extra trips between structure and service pipe• Works with 1" and 1 1/4" (25 mm and 32 mm) brace pipes to reduce inventory• Yellow tips provide a visual indicator that the bolts have been properly torqued• Easy installation with an impact wrench from the bottom side of the clamp• Meets NFPA®-13 requirements for seismic sway bracing
SpecificationsMaterial: SteelFinish: Electro-galvanized
Part Number Pipe Size NB/DNHeight
HWidth
W
CSBQG0250EG 2 1/2" 65 mm 138.1 – 148.6 mm 172 mm
CSBQG0300EG 3" 80 mm 155 – 165.5 mm 190 mm
CSBQG0400EG 4" 100 mm 180.4 – 190.9 mm 222 mm
CSBQG0500EG 5" 125 mm 205.8 – 217.9 mm 260 mm
CSBQG0600EG 6" 150 mm 235.5 – 244.9 mm 298 mm
CSBQG0800EG 8" 200 mm 289.2 – 300 mm 351.8 mm
www.erico.com 10
UL Loads
LateralPart Number Service Pipe Size Service Pipe Schedule
25 mm Brace Pipe 32 mm Brace Pipe
Lightwall 8960 N 8960 N
10 8960 N 8960 NCSBQG0250EG 100 mm
40 8960 N 8960 N
Lightwall 8960 N 8960 N
10 8960 N 8960 NCSBQG0300EG 125 mm
40 8960 N 8960 N
Lightwall 8960 N 8960 N
10 8960 N 8960 NCSBQG0400EG 100 mm
40 8960 N 8960 N
10 8960 N 8960 NCSBQG0500EG 125 mm
40 8960 N 8960 N
Lightwall 8960 N 8960 N
10 8960 N 8960 NCSBQG0600EG 150 mm
40 8960 N 8960 N
10 8960 N 8960 NCSBQG0800EG 200 mm
40 8960 N 8960 N
FM Loads
Lateral
Horizontal Capacity per Installation Angle from VerticalPart Number Service Pipe SizeService Pipe
Schedule30° - 44° 45° - 59° 60° - 74° 75° - 90°
Lightwall 6270 N 8895 N 10900 N 12190 N
10 6270 N 8895 N 10900 N 12190 NCSBQG0250EG 65 mm
40 6270 N 8895 N 10900 N 12190 N
Lightwall 5295 N 7475 N 9163 N 10230 N
10 5295 N 7475 N 9163 N 10230 NCSBQG0300EG 80 mm
40 5295 N 7475 N 9163 N 10230 N
Lightwall 5295 N 7475 N 9163 N 10230 N
10 5295 N 7475 N 9163 N 10230 NCSBQG0400EG 100 mm
40 5295 N 7475 N 9163 N 10230 N
Lightwall 3870 N 5470 N 6715 N 7515 N
10 3870 N 5470 N 6715 N 7515 NCSBQG0500EG 125 mm
40 4315 N 6095 N 7475 N 8320 N
Lightwall 3870 N 5470 N 6715 N 7515 N
10 3870 N 5470 N 6715 N 7515 NCSBQG0600EG 150 mm
40 4315 N 6095 N 7475 N 8320 N
4.8 mm(Wall Thickness)
3515 N 4940 N 6050 N 6760 NCSBQG0800EG 200 mm
40 3515 N 4940 N 6050 N 6760 N
www.erico.com 11
cULus is a registered certification mark of UL LLC. FM is a registered certification mark of FM Approvals LLC, LTD. NFPA is a registered trademark of National Fire Protection Association, Inc. UL isa registered certification mark of UL LLC. WARNINGERICO products shall be installed and used only as indicated in ERICO’s product instruction sheets and training materials. Instruction sheets are available at www.erico.com and from your ERICOcustomer service representative. Improper installation, misuse, misapplication or other failure to completely follow ERICO’s instructions and warnings may cause product malfunction, propertydamage, serious bodily injury and death. WARRANTYERICO products are warranted to be free from defects in material and workmanship at the time of shipment. NO OTHER WARRANTY, WHETHER EXPRESS OR IMPLIED (INCLUDING ANYWARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), SHALL EXIST IN CONNECTION WITH THE SALE OR USE OF ANY ERICO PRODUCTS. Claims for errors, shortages,defects or nonconformities ascertainable upon inspection must be made in writing within 5 days after Buyer's receipt of products. All other claims must be made in writing to ERICO within6 months from the date of shipment or transport. Products claimed to be nonconforming or defective must, upon ERICO's prior written approval in accordance with its standard terms andprocedures governing returns, promptly be returned to ERICO for inspection. Claims not made as provided above and within the applicable time period will be barred. ERICO shall in no event beresponsible if the products have not been stored or used in accordance with its specifications and recommended procedures. ERICO will, at its option, either repair or replace nonconforming ordefective products for which it is responsible or return the purchase price to the Buyer. THE FOREGOING STATES BUYER’S EXCLUSIVE REMEDY FOR ANY BREACH OF ERICO WARRANTY AND FORANY CLAIM, WHETHER SOUNDING IN CONTRACT, TORT OR NEGLIGENCE, FOR LOSS OR INJURY CAUSED BY THE SALE OR USE OF ANY PRODUCT. LIMITATION OF LIABILITYERICO excludes all liability except such liability that is directly attributable to the willful or gross negligence of ERICO's employees. Should ERICO be held liable its liability shall in no event exceedthe total purchase price under the contract. ERICO SHALL IN NO EVENT BE RESPONSIBLE FOR ANY LOSS OF BUSINESS OR PROFITS, DOWNTIME OR DELAY, LABOR, REPAIR OR MATERIAL COSTSOR ANY SIMILAR OR DISSIMILAR CONSEQUENTIAL LOSS OR DAMAGE INCURRED BY BUYER. Copyright © 2012 ERICO International Corporation. All rights reserved.CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.