FIRST WATCH NINE MILE - KE Mechanicalkemechanical.com/user_uploads/10/First Watch Mech only...
Transcript of FIRST WATCH NINE MILE - KE Mechanicalkemechanical.com/user_uploads/10/First Watch Mech only...
8
7
6
5
5
4
3
2
1
1
A. SUPPORT MUST BE FIELD INSTALLED TOSECURE TERMINATION KIT TO STRUCTURE
B. IF TWO OR MORE VENTS ARE USED NEAREACH OTHER THEN MAINTAIN A MINIMUMCLEARANCE OF 0'-2" BETWEEN THE FIRSTTWO AND A MINIMUM OF 0'-36" BETWEENEACH ADDITIONAL PAIR OF VENTS.
1. VENT OUTLET2. MAINTAIN 18" ABOVE ROOF3. SUPPORT (FIELD SUPPLIED)4. ELBOW (FIELD SUPPLIED)5. COMBUSTION AIR INLET6. ROOF BOOT/FLASHING (FIELD SUPPLIED)7. CONCENTRIC VENT TERMINATION
FURNISHED BY HEATER MFGR.8. ROOF SYSTEM
KEYED NOTES:
GENERAL NOTES:
OW
NE
RS
HIP
OF
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E
All
report
s, pla
ns, specifi
catio
ns, com
pute
r fil
es, fie
ld d
ata
, note
s a
nd o
ther
docum
ents
and in
str
um
ents
pre
pare
d b
y the C
onsultant as in
str
um
ents
of serv
ice s
hall
rem
ain
the p
ropert
y o
f th
e C
onsultant. T
he C
onsultant shall
reta
in a
ll com
mon law
, sta
tuto
ry a
nd o
ther
reserv
ed r
ights
, in
clu
din
g, w
ithout lim
itatio
n, th
e c
opyright th
ere
to.
Project No.
Title
Issue Date
Sheet
This drawing is the property of ARCHITECTURALGROUP INT'L and is not to be reproduced orcopied in whole or in part. It is only to be usedfor the project and site specifically identified herinand is not to be used on any other project.It is to be returned upon request.Scales as stated hereon are valid on the originaldrawing only. Contractor shall carefully review alldimensions and conditions shown hereon and atonce report to the Architect any error, inconsis-tancy or omission he may discover.
Revisions:
Mark Date By Description
Issued
WWW.KLHENGRS.COM
MECHANICAL/ELECTRICAL ENGINEERS
LEXINGTON, KENTUCKYCOLUMBUS, OHIO
NEW YORK, NEW YORK
1538 ALEXANDRIA PIKE, SUITE11 FT. THOMAS, KENTUCKY
41075 800-354-9783859-442-8050
859-442-8058 FAX
P601
PLUMBINGSPECIFICATIONS
10/25/2018
FIRST WATCHNINE MILE
PENSACOLA, FL
20873
11/12/2018 KLH
AGI REVIEW
11/15/2018 KLH
PERMIT
PLUMBING SPECIFICATIONSGENERALThe General Conditions, Supplementary Conditions and Instructions to Bidders shall apply to and be part of thisspecification.Contractor shall comply with all applicable codes, rules and regulations.Contractor shall obtain and pay for all permits, certificates of inspection and approvals required.SCOPE OF WORKWater Piping SystemsGas Piping SystemsSoil, Waste, and Vent Piping SystemsPlumbing FixturesPlumbing EquipmentGENERAL STANDARDSThe applicable provisions of the following standards shall govern:American Society for Test Materials (ASTM);American Standards Association (ASA);Underwriters Laboratories (UL);National Fire Protection Association (NFPA);International Plumbing CodeInternational Building CodeThe installation of all plumbing work shall conform to the applicable local building codes, plumbing codes andstatutes.EXCAVATION AND BACKFILLDo all excavation and backfilling. Lay sewer and underground piping lines on 6" compacted sand. Backfill underbuilding and all drives, roads and walks with bank-run gravel.WATER PIPING SYSTEMSProvide reduced pressure backflow preventer on the existing water serviceBackflow preventers for all equipmentDomestic cold-water pipingDomestic filtered-water pipingDomestic hot-water pipingDomestic recirculating water pipingTrap primers for floor drains (provide shut-off valve before each trap primer)Install water pressure regulators where necessary to limit the incoming water pressure to 80 psi inside the building.Interior Water Piping:Copper tube.Wall Thickness: Type L, hard-drawn temper.Fittings: Wrought-copper, solder-joints.Double Check Valve Assembly Backflow Preventer (domestic building service):Provide and install a double check valve assembly backflow preventer on water service main where the water serviceenters the building. Double check valve assembly backflow preventer shall be equal to Watts Series LF007QT, andshall be sized equal to the size of the water service. Approved Manufacturers of equal products shall be Conbracoand Wilkins.Reduced Pressure Backflow Preventer (domestic building service):Provide and install a reduced pressure backflow preventer on water service main where the water service enters thebuilding. Reduced pressure backflow preventer shall be equal to Watts Series LF919QT, and shall be sized equal tothe size of the water service. Approved Manufacturers of equal products shall be Conbraco and Wilkins.NATURAL GAS PIPING SYSTEMSBuilding distribution system from landlord provided stub to gas-fired equipment connections.Gas solenoid valves.Building Distribution Piping:All piping from outside new foundation wall to gas fired equipment connections: Black steel pipe.Pipe Size 2" and Smaller: Black steel pipePipe Weight: Schedule 40Fittings: Malleable iron threadedPipe size 2-1/2" and larger: black steel pipePipe weight: schedule 40Fittings: wrought-steel buttweldingField prepare and paint exterior natural gas piping, fittings, etc… with alkyd anticorrosive metal primer and topcoat with exterior alkyd enamel flat. Color to match building exterior and approved by the architectSOLENOID VALVESProvide brass or aluminum solenoid valve with nitrile rubber seats and discs, stainless steel springs, 120 volt, 60 hz,Class B, continuous duty molded replaceable coil, visual position indicator. Provide NEMA ICS 6, Type 4 coilenclosure. Valve will be normally open, fail safe closed.Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may beincorporated into the Work include, and limited to, the following:ASCO Power Technologies, LP; Division of Emerson.Dungs, Karl, Inc.Eclipse Combustion, Inc.Goyen Valve Corp.; Tyco Environmental Systems.Magnatrol Valve Corporation.Watts Regulator Co.; Division of Watts Water Technologies, Inc.General: Plumbing contractor shall be responsible for installing gas piping run-outs to all gas-fired equipment,including equipment supplied by the HVAC and electric contractors. Piping shall be installed full-size (as indicated onthe drawings) to each units gas inlet connection, burner, regulator, etc. Plumbing Contractor shall provide and installgas cock and make final connections. Connections to each gas-fired equipment item shall include a drip leg andshutoff gas cock. Comply with equipment manufacturer's instruction. For connections to gas-fired rooftop equipment,plumbing contractor shall be responsible for the roof penetration and shall install the gas piping through the roof in alocation that has been coordinated with the HVAC contractor.SOIL, WASTE AND VENT PIPING SYSTEMFurnish and install a complete soil, waste and vent system for all plumbing fixtures.Floor DrainsInterior Piping:Schedule 40 PVC pipe and fittings shall be used throughout. Contractor shall maintain integrity of fire ratings. Pipingshall not be run in plenum spaces and contractor shall provide and install intumescent collars when penetrating arated wall, floor, or other assembly. Provide 10'-0" cast iron piping for floor drain receiving dishwasher disposal.Piping alignment shall be as indicated on the drawings using approved Y branches or eighth bends for directionchanges and shall be surely supported or secured to maintain such alignment.Pitch of piping shall be uniform at a minimum of 1/4" per foot for 2" piping and smaller and 1/8" per foot for 2-1/2"piping and larger.Protection shall be given all footings, other structural elements during underground work adjacent to such items. Referto structural drawings.Vent all fixtures, connect branch vents to main vent risers at least three feet and six inches above vented fixtures.Pitch vent lines back to soil or waste pipe, free of drops and sags.Cleanouts shall be full size of pipe up to 4", and 4" for larger sizes. For underground and concealed lines, providecleanouts in accessible positions at each right angle turn and at intervals not to exceed fifty feet. In floors, install flushwith finish floor with extension pipe from cleanout "Y".CLEANOUTSJosam, Smith, Wade, Zurn, Watts, or MifabFLOOR DRAINSJosam, Smith, Wade, Zurn, Watts, Mifab, Sioux Chief, or OateyThe plumbing contractor shall provide trap primers for all floor drains. Trap primer shall be equal to Mifab MR-500 trapprimer valve.ROOF FLASHINGFlash all vents with 4 lb. sheet lead. Vent flashing shall be turned down into top of vent.Flashing for vents shall be per roofing company recommendations.PLUMBING FIXTURESWater closets.Urinals.Lavatories.Service sinks.Water FiltersManufacturer: Subject to compliance with requirements, provide plumbing fixtures and trim of one of the following:Plumbing Fixtures:American Standard, U.S. Plumbing Products.Eljer Plumbingware Div., Engineered Brass Corp.Kohler Co.Crane Co.Zurn Industries, Inc.Acorn Engineering Co.Bradley Corp.WilloughbyMetcraft Inc.Schier ProductsPlumbing Trim:American Standard, U.S. Plumbing Products.Chicago Faucet Co.Eljer Plumbingware Div., Wallace-Murray Corp.Kohler Co.Speakman Co.T & S Brass and Bronze Works, Inc.McGuireZurn Industries, Inc.SymmonsGeberit Manufacturing, Inc.Union Brass Manufacturing CompanyDelta Commercial FaucetsMoen Commercial FaucetsFlush Valves:Sloan Valve Co. Zurn Industries, Inc.Geberit Manufacturing, Inc.Delta Commercial Flush ValvesMoen Commercial Flush ValvesFixture Seats:Bemis Mfg. Co.Church Olsonite Corp., Olsonite Seats.CentocoService Sinks:American Standard, U.S. Plumbing Products.Eljer Plumbingware Div., Wallace-Murray Corp.Fiat Products, Unit of Mark Control Corp.Kohler Co.Stern-Williams Co., Inc.MusteeZurn Industries, Inc.Creative IndustriesFixture Carriers:Josam Mfg. Co.Smith.Wade
Zurn Industries, Inc., Hydromechanics Div.Watts DrainagePLUMBING EQUIPMENTWater heatersThermostatic Mixing ValvesCATHODIC PROTECTIONProvide dielectric insulation at points where copper or brass pipe comes in contact with ferrous piping, reinforcingsteel or other dissimilar metal in structure.WATER HAMMER ARRESTORSRemove shock conditions from all piping. Provide and install shock absorbers on all piping serving flush valve fixtures.VALVESProvide stops on domestic water supplies to isolate hot and cold water to each fixture, including all equipment andequipment provided by others.Fixtures, item or units furnished by the manufacturer with integral stops or stops specified with the fixture areconsidered to be properly valved off at the fixtures.Access shall be provided to all valves.All valves shall comply with lead-free regulations.Valves on domestic water piping shall be ball valves or butterfly valves depending on size.All valves installed on domestic water piping 3” and smaller shall be ball valves.Ball Valves - 1 Inch and Smaller: 2-piece body, 600 psi CWP, 150 psi SWP, Cast Bronze body, full port, teflon seats,blowout-proof stem, adjustable packing gland, chrome plated bronze ball, with screwed ends, and vinyl-covered steelhandle. Provide solder ends. Provide extended valve stems for valves used on insulated lines. Provide equal to NibcoSeries 585-70-NS.Ball Valves - 1-1/4 Inch to 3 Inch: 3-piece body, 600 psi CWP, 150 psi SWP, Cast Bronze body, conventional port,teflon seats, blowout-proof stem, adjustable packing gland, chrome plated bronze ball, screwed ends, andvinyl-covered steel handle. Provide solder ends. Provide extended valve stems for valves used on insulated lines.Provide equal to Nibco Series 590-Y.ButterflyCheck ValvesSwing Check Valves - Class 125, cast bronze body and cap, horizontal swing, Y-pattern, with a bronze disc, andhaving threaded or solder ends. Provide solder ends for domestic hot and cold water service. Provide equal to NibcoS-413.Balancing Valves for Hot Water Return1/2" to 2”: All dezincification resistant brass construction, straight pattern globe, non-rising stem, two test ports,memory stop, position display, rated for 240 psi to 250 degrees F. Provide equal to Nibco Circuit Balancing Valvemodel T and S1710 (threaded or socket). Valve must be listed for potable water use by manufacturer. Ball-stylebalancing valves may be substituted with Engineer's Approval.ManufacturersNibcoMilwaukeeWattsApolloKitz CorporationPIPE JOINTS AND CONNECTIONAll cutting and patching of finished construction of building shall be performed by this contractor under the section ofspecifications covering these materials.Any minor adjustment in location of alignment of new work or to connect to existing utilities shall be performed asdirected by the Architect without additional cost to the Owner.The contractor shall be responsible for damages to the grounds, walks, road, building, piping systems, electricalsystems, and their equipment and contents, caused by leaks in the piping systems being installed or having beeninstalled by him. He shall repair at his expense all damaged so caused. All repair work shall be done as directed byand in such manner as satisfactory to the Architect.Owner reserves the right to make emergency repairs as required to keep equipment in operation without voiding thecontractor's guarantee bond nor relieving the contractor of his responsibilities during the bonding period.PLUMBING INSULATIONInsulate domestic cold water piping, associated fittings and valves with 1/2” wall thickness insulation.Insulate domestic hot water piping, associated fittings and valves with 1” wall thickness insulation.Insulate domestic hot water return piping, associated fittings and valves with 1” wall thickness insulation.Insulate waste piping, supply piping, stops, and valves under handicap accessible plumbing fixtures.FLEXIBLE ELASTOMERIC INSULATIONClosed-cell, sponge- or expanded-rubber materials. Comply with ASTM C 534, Type I for tubular materials and TypeII for sheet materials.Manufacturers:Armstrong Armaflex IIRubatex R-180-FSNomaco K-FlexInsulation shall be listed and labeled per ASTM E 84 for plenum installations employing slip on techniques.Joints shall be sealed with Armstrong #520 or Rubatex #373 adhesive or as required by manufacturer. Pipe insulationexposed outside shall be covered with a vinyl wrap.FIBERGLASS INSULATIONFiberglass piping insulation: ASTM C 547, Class 1Encase pipe fittings insulation with one-piece premolded PVC fitting covers.Vapor Barrier Material: Paper-backed aluminum foil, except as otherwise indicated, strength and permeability ratingequivalent to adjoining pipe insulation jacketing.Staples, Bands, Wires, and Cement: As recommended by insulation manufacturer for applications indicated.Adhesives, Sealers, and Protective Finishes: As recommended by insulation manufacturer for applications indicated.Manufacturers:Armstrong World Industries, Inc.Owens-Corning Fiberglass Corp.Keene Corp.CertainTeed.Johns Manville.INSULATION FOR HANDICAP ACCESSIBLE FIXTURESAll handicap lavatory P-trap and angle stop assemblies shall be insulated with Trap Wrap Protective Kit manufacturedby ProFlo model PF202WH or equal. Abrasion resistant , anti-microbial vinyl exterior cover shall be smooth. For traps,the insulation shall have a cleanout nut cap to allow service to the trap without disassembly. For stops, the insulationshall have a lock lid that prevents tampering but allows access without removal of the insulation. Fasteners shallremain substantially out of sight.Manufacturers: Subject to compliance with requirements:ProFloTruebroPlumberexINTERRUPTION OF SERVICESWhen it is required to interrupt existing services, this contractor shall first notify the Architect that an interruption isrequired. It should be noted that facilities must by kept in operation as much as possible.This contractor shall advise the Architect of the length of time the service will be interrupted and shall get permissionfrom the Architect before proceeding with the work.WARRANTYThis contractor shall warrant that all work under this section shall be free of defective work, materials and parts for aperiod of one year after acceptance of the work and shall repair, revise, and replace, at no cost to the Owner, anysuch defects occurring within the warranty period.HEAT TRACING FOR PLUMBING PIPINGProvide heat tracing and associated insulation for all water piping subject to freezing.Provide heat tracing and associated insulation for all sanitary traps and all horizontal sanitary piping subject tofreezing.Power connections, splice fittings, and end caps shall be provided for a complete/operational system. Where theseitems are shown, deviations from the proposed layout shall be accepted in the interest of saving cost if there is a moreefficient layout; however, if changes result in an increased cost to another contractor (i.e. electrical contractor), thoseincreased costs shall be borne by the contractor making the deviations.Product: Raychem Corporation xl-trace or chromalox “rapid trace”, self-regulating heat trace sized at 8 watts perlinear foot rating, or as recommended by manufacturer. Install heat trace directly on pipe and valves within insulationwithin jacket.Manufacturers:Raychem; a division of tyco thermal controls.Chromalox, inc.; wiegard industrial division; emerson electric company.BH thermal Corporation.Delta-Therm Corporation.Easy Heat Inc.Nelson Heat Trace.Pyrotenax; a division of Tyco thermal controls.Thermon manufacturing co.Trasor corp.
SCALE: NONE
235123.00-02 - CONCENTRIC ROOF VENT TERMINATION
ON ROOFHP-1
ON ROOFK18
ON ROOFK19
ON ROOFMUA-1
1361 LBS.
ON ROOFEF-3
220 LBS.
ON ROOFEF-4
99 LBS.
ON ROOFEF-1
45 LBS.
ON ROOFEF-2
45 LBS.ROUTE PVC CONDENSATE PIPING TO NEAREST STORM DRAIN. FIELD VERIFY EXACT LOCATION.
PROVIDE MIRO 1.5 PIPE SUPPORTS PER MANUFACTURER GUIDELINES (TYPICAL).
ON ROOFRTU-1
1998 LBS.
ON ROOFRTU-2
1546 LBS.
ON ROOFRTU-3
1546 LBS.
M02
M02
M02
M05
M05
M03
M04
M06M06
M01
EXISTING 42" MINIMUM PARAPET EXTENDS AROUND PERIMEMTER OF ROOF
INSTALL ON RAISED CURB OR EQUIPMENT STAND IN ACCORDANCE WITH 1510.10 OF FBCB.
CONDENSATE SHALL NOT BE DEPOSITED IN GUTTER/DOWNSPOUT IF THE CONDENSATE WILL DISCHARGE ON PAVEMENT OR OTHERWISE CREATE A NUISANCE AND/OR HAZARD.
GC TO PROVIDE PENETRATIONS FOR REMOTE CONDENSERS.
3/4" CD
3/4" CD
3/4" CD
1" CD
3/4" CD
1" CD
MECHANICAL LEGEND
SYMBOL DESCRIPTION
SUPPLY DUCT WITH ELBOW TURNED UPUP
SUPPLY DUCT WITH ELBOW TURNED DOWNDN
RETURN DUCT WITH ELBOW TURNED UPUP
RETURN DUCT WITH ELBOW TURNED DOWNDN
EXHAUST DUCT WITH ELBOW TURNED UPUP
EXHAUST DUCT WITH ELBOW TURNED DOWNDN
OW
NE
RS
HIP
OF
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E
All
report
s, pla
ns, specifi
catio
ns, com
pute
r fil
es, fie
ld d
ata
, note
s a
nd o
ther
docum
ents
and in
str
um
ents
pre
pare
d b
y the C
onsultant as in
str
um
ents
of serv
ice s
hall
rem
ain
the p
ropert
y o
f th
e C
onsultant. T
he C
onsultant shall
reta
in a
ll com
mon law
, sta
tuto
ry a
nd o
ther
reserv
ed r
ights
, in
clu
din
g, w
ithout lim
itatio
n, th
e c
opyright th
ere
to.
Project No.
Title
Issue Date
Sheet
This drawing is the property of ARCHITECTURALGROUP INT'L and is not to be reproduced orcopied in whole or in part. It is only to be usedfor the project and site specifically identified herinand is not to be used on any other project.It is to be returned upon request.Scales as stated hereon are valid on the originaldrawing only. Contractor shall carefully review alldimensions and conditions shown hereon and atonce report to the Architect any error, inconsis-tancy or omission he may discover.
Revisions:
Mark Date By Description
Issued
WWW.KLHENGRS.COM
MECHANICAL/ELECTRICAL ENGINEERS
LEXINGTON, KENTUCKYCOLUMBUS, OHIO
NEW YORK, NEW YORK
1538 ALEXANDRIA PIKE, SUITE11 FT. THOMAS, KENTUCKY
41075 800-354-9783859-442-8050
859-442-8058 FAX
M100
MECHANICAL ROOFPLAN
10/25/2018
FIRST WATCHNINE MILE
PENSACOLA, FL
20873
11/12/2018 KLH
AGI REVIEW
11/15/2018 KLH
PERMIT
SCALE:
NORTH
1/4" = 1'-0"MECHANICALROOF PLAN
KEYED NOTES
M01 ROOF MOUNTED MAKE-UP AIR UNIT. REFERENCE FOOD SERVICE DRAWINGS AND SCHEDULE FORADDITIONAL INFORMATION.
M02 LANDLORD PROVIDED RTU. BALANCE TO THE SCHEDULED AIRFLOW. INTAKE SHALL BE A MINIMUM OF10'-0" FROM ANY EXHAUST /FLUE.
M03 GREASE EXHAUST FAN ON ROOF. REFERENCE SPECIFICATIONS AND FOOD SERVICE FOR ADDITIONALREQUIREMENTS. CONTRACTOR TO PROVIDE OPENING IN ROOF FOR DUCT, CURB AND FAN.
M04 DISHWASHER EXHAUST FAN ON ROOF. REFERENCE FOOD SERVICE DRAWINGS FOR ADDITIONALREQUIREMENTS.
M05 EXHAUST FAN ON ROOF. PROVIDE DUCT TRANSITION AT FAN.
M06 REMOTE CONDENSING UNIT PROVIDED AND INSTALLED BY OTHERS. REFER TO KITCHEN EQUIPMENTPLANS FOR FURTHER DETAIL. VERIFY FINAL LOCATION WITH KITCHEN EQUIPMENT INSTALLER.
FIELD VERIFY ALL CONDITIONS
DESIGN DRAWINGS ARE SCHEMATIC. THIS CONTRACTOR SHALL VISIT THE SITE PRIOR TO BIDDING OR AWARD OF CONTRACT TO INSPECT EXISTING FIELD CONDITIONS. THIS CONTRACT SHALL INCLUDE ALL LABOR AND MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO EXISTING CONDITIONS.
THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR OWNER PRIOR TO BIDDING FOR INTERPRETATIONS AND CLARIFICATIONS OF THE DESIGN AND INCLUDE IN HIS BID ALL COSTS TO MEET THE DESIGN INTENT. CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER OR OWNER AFTER BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED AT CONTRACTORS COST.
BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL CODES AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE COSTS FOR ALL WORK INSTALLED IN STRICT ACCORDANCE WITHGOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT WITHSTANDING. THE CONTRACTOR SHALL ALERT ARCHITECT, ENGINEER OR OWNER OF ANY APPARENT DISCREPANCIES BETWEEN GOVERNING CODES AND DESIGN INTENT.
HVAC GENERAL NOTES
A. COORDINATE ROOF TOP EQUIPMENT PLACEMENT WITH ARCHITECTURAL DRAWINGS. COORDINATE EXACT LOCATION WITH EXISTING STRUCTURE AND LANDLORD'S ROOFING CONTRACTOR.
B. REFER TO FOOD SERVICE DRAWINGS FOR ADDITIONAL SCOPE OF WORK.
C. INSTALL ALL DUCT, PIPE ECT. AS HIGH AS POSSIBLE. COORDINATE INSTALLATION OF WORK WITH OTHER CONTRACTORS.
D. PROVIDE FLEXIBLE CONNECTION BETWEEN DUCT WORK AND ALL EQUIPMENT WITH RATING PARTS.
E. ALL DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS. ALL JOINTS SEALED PRIOR TO INSULATION. ALL DUCTWORK TO BE CONCEALED UNLESS NOTED OTHERWISE. DUCTWORK SIZES INDICATED ARE ACTUAL DUCT SIZES. ADDITIONAL CLEARANCE SHALL BE CONSIDERED FOR INSULATION.
F. ALL ROOFING WORK SHALL BE PERFORMED BY LANDLORDS ROOFING CONTRACTOR AT THIS CONTRACTORS EXPENSE TO MAINTAIN ROOF WARRANTY. COORDINATED ROOF PENETRATIONS WITH THIS CONTRACTOR. VERIFY CONTRACTOR WITH LANDLORD.
TT
T
HS
TS
HS
TS
HS
TS
DSD
DSD
DSD
DSD
MECHANICAL LEGEND
SYMBOL DESCRIPTION
WORK SHOWN FADED INDICATES EXISTING WORK TO REMAIN OR NEW WORK BY OTHERS AS APPLICABLE
WORK SHOWN BOLD-DASHED INDICATES SELECTIVE DEMOLITION WORK
WORK SHOWN BOLD-CONTINUOUS INDICATES NEW WORK
CDCONDENSATE DRAIN
RR RETURN REGISTER
EXHAUST REGISTERER
CEILING DIFFUSERCD
2'x2' SQUARE CEILING DIFFUSER WITH 10" NECK
SUPPLY DUCT WITH ELBOW TURNED UPUP
SUPPLY DUCT WITH ELBOW TURNED DOWNDN
RETURN DUCT WITH ELBOW TURNED UPUP
RETURN DUCT WITH ELBOW TURNED DOWNDN
EXHAUST DUCT WITH ELBOW TURNED UPUP
EXHAUST DUCT WITH ELBOW TURNED DOWNDN
SUPPLY DUCT
RETURN DUCT
EXHAUST DUCT
OUTSIDE AIR DUCT
1" LINED DUCTWORK
FLEXIBLE DUCTWORK CONNECTION
BRANCH TAKEOFF
REDUCER, CONCENTRIC
DUCT MOUNTED SMOKE DETECTOR (HARD WIRE INTERLOCK TO FAN MOTOR BY E.C.) FURNISHED BY E.C., INSTALLED BY M.C. DSD
TEMPERATURE SENSORTS
LOW VOLTAGE THERMOSTATT
HS HUMIDITY SENSOR
24X12 SA
24X12 RA
24X12 EA
24X12 OA
CD-10"Ø
ER-1200 CFM
ER-1160 CFM
ER-250 CFM
SD-1380 CFM
24x12 DN750CFMTYP. OF 4
16x6 DN250CFMTYP. OF 4
10"ø EA
10"ø EA
8"ø EA
6"ø EA
SD-1365 CFM
BLANK OFF SD IN DIRECTION OF HOOD.
SD-1150 CFM
8"ø SA
M11
M11
M11
M11
M11M11
M07
MUA-1
EF-1
EF-2
EF-3
EF-4
RTU-1
RTU-2
RTU-3
RR-14000 CFM
M15
M14
M08
M16
M18
RTU-1:3
RTU-1
M10
M13
RTU-2
M13RTU-3
M13
M17
M17
DINING
102
WOMEN'S
TOILET
ROOM
105
OFFICE
107
MEN'S
TOILET ROOM
104
TOLIET ROOM
VESTIBULE
103
WAITING/
HOSTESS
101
KITCHEN
106
SD-1100 CFM
SD-1100 CFM
ER-1160 CFM
8"ø EA
SR-1250 CFM
SR-1250 CFM
SR-1250 CFM
SR-1250 CFM
SR-1250 CFM
SR-1250 CFM
SR-1250 CFM
SR-1250 CFM
SR-1250 CFM
SR-1300 CFM
SR-1300 CFM
SR-1300 CFM
SR-1320 CFM
SR-1320 CFM
SR-1320 CFM
SR-1320 CFM
SR-1320 CFM
SR-1320 CFM
SR-1320 CFM
SR-1320 CFM
SR-1320 CFM
SR-1320 CFM
M21
M09
M09
M09
22"x18" SA
18"ø EA
M12
16"x12" SA
20"x16" SA
SD-1505 CFM
SD-1505 CFM
22"x
16"
SA
12"ø SA
12"ø SA
SD-1365 CFM
SD-1365 CFM
SD-1365 CFM
12"ø SA
12"ø SA12"ø SA
18"ø SA12"ø SA
14"ø SA 14"ø SA 14"ø SA
18"ø SA
14"ø SA
14"ø SA
14"ø SA
16"ø SA
20"ø SA
14"ø SA
10"ø SA
16"ø SA
14"ø SA
10"ø EA
12"ø SA
BLANK OFF SD IN DIRECTION OF HOOD.
M09
ABOVE FIXTURE
36"x16" RA UP
36"x16" RA UP
36"x16" RA
36"x16" RA
SR-1250 CFM
M20
M19M19
16"x14" SA
OW
NE
RS
HIP
OF
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E
All
report
s, pla
ns, specifi
catio
ns, com
pute
r fil
es, fie
ld d
ata
, note
s a
nd o
ther
docum
ents
and in
str
um
ents
pre
pare
d b
y the C
onsultant as in
str
um
ents
of serv
ice s
hall
rem
ain
the p
ropert
y o
f th
e C
onsultant. T
he C
onsultant shall
reta
in a
ll com
mon law
, sta
tuto
ry a
nd o
ther
reserv
ed r
ights
, in
clu
din
g, w
ithout lim
itatio
n, th
e c
opyright th
ere
to.
Project No.
Title
Issue Date
Sheet
This drawing is the property of ARCHITECTURALGROUP INT'L and is not to be reproduced orcopied in whole or in part. It is only to be usedfor the project and site specifically identified herinand is not to be used on any other project.It is to be returned upon request.Scales as stated hereon are valid on the originaldrawing only. Contractor shall carefully review alldimensions and conditions shown hereon and atonce report to the Architect any error, inconsis-tancy or omission he may discover.
Revisions:
Mark Date By Description
Issued
WWW.KLHENGRS.COM
MECHANICAL/ELECTRICAL ENGINEERS
LEXINGTON, KENTUCKYCOLUMBUS, OHIO
NEW YORK, NEW YORK
1538 ALEXANDRIA PIKE, SUITE11 FT. THOMAS, KENTUCKY
41075 800-354-9783859-442-8050
859-442-8058 FAX
M101
MECHANICALFLOOR PLAN
10/25/2018
FIRST WATCHNINE MILE
PENSACOLA, FL
20873
11/12/2018 KLH
AGI REVIEW
11/15/2018 KLH
PERMIT
KEYED NOTES
M07 EXTEND AND CONNECT DUCT UP TO MAKE-UP AIR UNIT. PROVIDEFLEXIBLE CONNECTION AT UNIT.
M08 EXTEND SUPPLY AIR DUCT DOWN TO SUPPLY CONNECTIONS TO HOOD.PROVIDE TRANSITION DUCT AND BALANCING DAMPER AT HOOD.
M09 ELECTRICAL CONTRACTOR SHALL FURNISH A NEW ADDRESSABLESMOKE DETECTOR. MECHANICAL CONTRACTOR SHALL INSTALL SMOKEDETECTOR IN NEW AIR DUCT MAIN. MECHANICAL CONTRACTOR SHALLINTERLOCK SMOKE DETECTOR TO FAN MOTOR. ELECTRICALCONTRACTOR SHALL WIRE SMOKE DETECTOR TO REMOTEANNUNCIATOR. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONALINFORMATION INCLUDING ANNUNCIATOR LOCATION.
M10 PROVIDE THERMOSTAT AND EXTEND CONTROL WIRING FROM RTU ANDSPACE SENSOR TO THIS LOCATION.
M11 EXTEND DUCTWORK UP TO UNIT THROUGH OPENING IN ROOF ANDCONNECT TO ROOFTOP UNIT. VERTICAL DUCTWORK SAME SIZE ASEQUIPMENT. PROVIDE FLEXIBLE CONNECTION IN VERTICAL DUCT.
M12 EXTEND WELDED GALVANIZED GREASE DUCT UP THROUGH ROOF TOEXHAUST FAN ON ROOF. PROVIDE APPROVED FLANGED AND GASKETEDDUCT TRANSITION AT EXHAUST FAN. PROVIDE HI-TEMPERATURE DUCTWRAP ON ENTIRE LENGTH OF GREASE DUCT. PROVIDE DUCT CLEAN-OUTAND ACCESS DOORS AS REQUIRED BY IMC AND AUTHORITY HAVINGJURISDICTION. REFERENCE SPECIFICATIONS AND FOOD SERVICE (FS)DRAWINGS FOR ADDITIONAL REQUIREMENTS. CONTRACTOR TOPROVIDE OPENING IN ROOF FOR DUCT, CURB AND FAN.
M13 PROVIDE SPACE SENSOR AT THIS LOCATION. EXTEND CONTROL WIRINGTO THERMOSTATS LOCATED IN OFFICE.
M14 ALUMINUM EXHAUST DUCT DOWN TO DISHWASHER HOOD FLANGEDCONNECTION AND CONNECT. REFERENCE FOOD SERVICE (FS)DRAWINGS FOR ADDITIONAL REQUIREMENTS. EXTEND ALUMINUM DUCTUP THRU ROOF TO EXHAUST FAN.
M15 TYPE II DISHWASHER EXHAUST HOOD. REFERENCE FOOD SERVICE (FS)DRAWINGS FOR ADDITIONAL REQUIREMENTS.
M16 TYPE I KITCHEN HOOD. REFERENCE FOOD SERVICE (FS) DRAWINGS FORADDITIONAL REQUIREMENTS.
M17 EXTEND EXHAUST DUCT UP THRU ROOF TO EXHAUST FAN. PROVIDEDUCT TRANSITION AT FAN.
M18 LOCATE EXHAUST GRILLE OVER TOASTER. LOCATE AS CLOSE ASCEILING TILE WILL PERMIT. EXTEND ALUMINUM DUCT FROM GRILLE TO10"X10" VERTICAL ALUMINUM DUCT UP TO EXHAUST FAN AND CONNECT.SLOPE FROM GRILLE TO VERTICAL DUCT.
M19 PROVIDE 1" AIRSPACE BETWEEN BOTTOM OF DOOR AND FINISHEDFLOOR FOR AIRFLOW.
M20 PROVIDE 1.5" AIRSPACE BETWEEN BOTTOM OF DOOR AND FINISHEDFLOOR FOR AIRFLOW.
M21 PROVIDE DOUBLE WALL DUCTWORK WITH 1" INSULATION FOR ALLEXPOSED DUCTWORK.
FIELD VERIFY ALL CONDITIONS
DESIGN DRAWINGS ARE SCHEMATIC. THIS CONTRACTOR SHALL VISIT THE SITE PRIOR TO BIDDING OR AWARD OF CONTRACT TO INSPECT EXISTING FIELD CONDITIONS. THIS CONTRACT SHALL INCLUDE ALL LABOR AND MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO EXISTING CONDITIONS.
THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR OWNER PRIOR TO BIDDING FOR INTERPRETATIONS AND CLARIFICATIONS OF THE DESIGN AND INCLUDE IN HIS BID ALL COSTS TO MEET THE DESIGN INTENT. CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER OR OWNER AFTER BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED AT CONTRACTORS COST.
BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL CODES AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE COSTS FOR ALL WORK INSTALLED IN STRICT ACCORDANCE WITHGOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT WITHSTANDING. THE CONTRACTOR SHALL ALERT ARCHITECT, ENGINEER OR OWNER OF ANY APPARENT DISCREPANCIES BETWEEN GOVERNING CODES AND DESIGN INTENT.
SCALE:
NORTH
1/4" = 1'-0"MECHANICAL FLOOR PLAN
HVAC GENERAL NOTES
A. COORDINATE ROOF TOP EQUIPMENT PLACEMENT WITH ARCHITECTURAL DRAWINGS. COORDINATE EXACT LOCATION WITH EXISTING STRUCTURE AND LANDLORD'S ROOFING CONTRACTOR.
B. REFER TO FOOD SERVICE DRAWINGS FOR ADDITIONAL SCOPE OF WORK.
C. INSTALL ALL DUCT, PIPE ECT. AS HIGH AS POSSIBLE. COORDINATE INSTALLATION OF WORK WITH OTHER CONTRACTORS.
D. PROVIDE FLEXIBLE CONNECTION BETWEEN DUCT WORK AND ALL EQUIPMENT WITH RATING PARTS.
E. ALL DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS. ALL JOINTS SEALED PRIOR TO INSULATION. ALL DUCTWORK TO BE CONCEALED UNLESS NOTED OTHERWISE. DUCTWORK SIZES INDICATED ARE ACTUAL DUCT SIZES. ADDITIONAL CLEARANCE SHALL BE CONSIDERED FOR INSULATION.
F. ALL ROOFING WORK SHALL BE PERFORMED BY LANDLORDS ROOFING CONTRACTOR AT THIS CONTRACTORS EXPENSE TO MAINTAIN ROOF WARRANTY. COORDINATED ROOF PENETRATIONS WITH THIS CONTRACTOR. VERIFY CONTRACTOR WITH LANDLORD.
EQUIPMENT
0
KITCHEN PRESSURIZATION CALCULATION
TOTAL BUILDING PRESSURE CALCULATION
RTU-3
MAU-1
EF-1 (MS)
EF-2 (OVEN HOOD)
OUTSIDE AIR EXHAUST AIR TOTALS
EF-3 (KITCH HOOD)
EF-4 (DISH HOOD)
KITCHEN TOTALS
600
0
-50
-200
-3600
-600
-4450
3000
3600
3000
-50
-200
-3600
-600
0
0
0
0
EQUIPMENT
0RTU-3
MAU-1
EF-1 (RR/MS)
EF-2 (OVEN HOOD)
OUTSIDE AIR EXHAUST AIR TOTALS
EF-3 (KITCH HOOD)
EF-4 (DISH HOOD)
BUILDING TOTALS
600
0
-370
-200
-3600
-600
-4770
3000
5130
3000
-200
-3600
-600
0
0
0
0
0RTU-2 680
0RTU-1 850
360
-850
600
-370
600
680
850
OCCUPANCY/TEMPERATURE SCHEDULE
SEASONOCCUPIED UNOCCUPIED
SUMMER
WINTER
TIME TEMP.
6AM-4PM 74
6AM-4PM 72
TIME TEMP.
4PM-6AM 80
4PM-6AM 60
CHANGE-OVER SET POINT 2 DEG.
OW
NE
RS
HIP
OF
IN
ST
RU
ME
NT
S O
F S
ER
VIC
EA
ll re
port
s, pla
ns, specifi
catio
ns, com
pute
r fil
es, fie
ld d
ata
, note
s a
nd o
ther
docum
ents
and in
str
um
ents
pre
pare
d b
y the C
onsultant as in
str
um
ents
of serv
ice s
hall
rem
ain
the p
ropert
y o
f th
e C
onsultant. T
he C
onsultant shall
reta
in a
ll com
mon law
, sta
tuto
ry a
nd o
ther
reserv
ed r
ights
, in
clu
din
g, w
ithout lim
itatio
n, th
e c
opyright th
ere
to.
Project No.
Title
Issue Date
Sheet
This drawing is the property of ARCHITECTURALGROUP INT'L and is not to be reproduced orcopied in whole or in part. It is only to be usedfor the project and site specifically identified herinand is not to be used on any other project.It is to be returned upon request.Scales as stated hereon are valid on the originaldrawing only. Contractor shall carefully review alldimensions and conditions shown hereon and atonce report to the Architect any error, inconsis-tancy or omission he may discover.
Revisions:
Mark Date By Description
Issued
WWW.KLHENGRS.COM
MECHANICAL/ELECTRICAL ENGINEERS
LEXINGTON, KENTUCKYCOLUMBUS, OHIO
NEW YORK, NEW YORK
1538 ALEXANDRIA PIKE, SUITE11 FT. THOMAS, KENTUCKY
41075 800-354-9783859-442-8050
859-442-8058 FAX
M102
MECHANICALSCHEDULES
10/25/2018
FIRST WATCHNINE MILE
PENSACOLA, FL
20873
11/12/2018 KLH
AGI REVIEW
11/15/2018 KLH
PERMIT
17. DUCT FLANGES18. BASE RAIL19. HUMIDIFIER20. CO2 SENSORS
21. ECON POWERED EXHAUST22. ECON BAROMETRIC RELIEF23. HOT GAS REHEAT COIL24. SHAFT GROUNDING BRUSHES
HVAC ACCESSORIESACCESSORIES:
1. MOTOR DAMPER2. ECONOMIZER3. ROOF CURB4. SMOKE DETECTOR
5. INTAKE HOOD6. VIBRATION ISOLATION7. FLAT FILTER8. FILTER/MIXING BOX
9. ACCESS DOOR10. FLEX CONNECTIONS11. MOUNTING COLLAR12. HOT GAS BYPASS
13. FACE/BYPASS DAMPER14. CONDENSATE PUMP15. MOTOR GUARD16. GREASE TRAP
HVAC VENTILATION SCHEDULE
NUMBER NAME AREA AIR CHGS OA CHGS PEOPLE RED OA PER PERSON OA PER SQ FT. REQ SUP ACT SUP REQ OA ACT OA ACT RET ACT EXH CRIT OA PRESSURE
101 WAITING/HOSTESS
207 SF 16 7.5 0.18 864 900 216 225 900 0 0.2455 E
102 DINING 680 SF 51 7.5 0.18 3060 3200 612 640 3200 0 0.2003 E
102 DINING 826 SF 47 7.5 0.18 2404 2500 601 625 2500 0 0.2364 E
103 TOLIET ROOMVESTIBULE
34 SF 0 0.06 0 0 0 0 0 0 0 E
104 MEN'S TOILETROOM
121 SF 0 95 100 19 20 0 160 0 N
105 WOMEN'STOILET ROOM
128 SF 0 95 100 19 20 0 160 0 N
106 KITCHEN 709 SF 8 7.5 0.12 1307 2840 196 426 0 50 0.0647 P
106A FRONT KITCHEN 274 SF 4 7.5 0.12 467 1010 70 152 0 200 0.0782 P
107 OFFICE 47 SF 1 5 0.06 67 150 10 22 150 0 0.0666 E
108 Space 1780 SF 6
109 Space 1503 SF 5
6309 SF
HVAC FANS SCHEDULE
EQUIPMENTMARK DESCRIPTION LOCATION STATUS
WEIGHT(lbs) MANUFACTURER MODEL EMERGENCY VOLTS PHASE WATTS (Watts) CFM (cfm)
ESP (inWC)
FAN RPM(rpm) BHP (hp) HP (hp) FLA (amps) MCA (amps) OCP (amps) Access
EF-1 CENTRIFUGALROOFVENTILATOR
ON ROOF 45 GREENHECK G-095-VG 120 1 370 0.3 1306 0.05 1,3
EF-2 CENTRIFUGALROOFVENTILATOR
ON ROOF 45 GREENHECK G-095-VG 120 1 200 0.3 1306 0.05 1,3
EF-3 CENTRIFUGALROOFVENTILATOR
ON ROOF BY OTHERS 220 CAPTIVEAIRE DU180HFA 208 3 3600 1.6 1456 1.656 9.5 BY OTHERS
EF-4 CENTRIFUGALROOFVENTILATOR
ON ROOF BY OTHERS 99 CAPTIVEAIRE DU30HFA 120 1 600 0.5 1250 0.11 4 BY OTHERS
CROOFCWALLCPARTCGLASSCSOLARCLIGHTSCEQUIPCPSENS
SENSIBLE HEAT GAIN FROM ROOFSENSIBLE HEAT GAIN FROM EXTERIOR WALLSSENSIBLE HEAT GAIN FROM PARITIONSSENSIBLE HEAT GAIN FROM GLAZINGSENSIBLE HEAT GAIN FROM SOLAR GAIN THROGH GLAZINGSENSIBLE HEAT GAIN FROM INTERIOR LIGHTINGSENSIBLE HEAT GAIN FROM PLUG LOADS, COMPUTERS, ETC.SENSIBLE HEAT GAIN FROM PEOPLE
CSSENSCFANCOASCTSENSCPLATCOALCTLATCTOT
TOTAL SENSIBLE HEAT GAIN TO SPACESENSIBLE HEAT GAIN FROM AIR HANDLER FANSENSIBLE HEAT GAIN FROM OUTDOOR VENTILATION AIRTOTAL SENSIBLE HEAT GAINLATENT HEAT GAIN FROM PEOPLELATENT HEAT GAIN FROM OUTDOOR VENTILATION AIRTOTAL LATENT HEAT GAINTOTAL HEAT GAIN (SENSIBLE + LATENT)
HROOFHWALLHPARTHGLASSHSLABHSPACEHOAHTOT
HEAT LOSS FROM ROOFHEAT LOSS FROM EXTERIOR WALLSHEAT LOSS FROM PARTITIONSHEAT LOSS FROM GLAZINGHEAT LOSS FROM SLABTOTAL HEAT LOSS FROM SPACEHEAT LOSS FROM OUTDOOR VENTILATION AIRTOTAL HEAT LOSS
HVAC LOADS COOLING LOAD BREAKDOWN HEATING LOAD BREAKDOWN
THE HEATING AND COOLING LOAD CALCULATIONS ARE BASED ON THE CLTD/CLF (COOLING LOAD TEMPERATURE DIFFERENCE/COOLING LOAD FACTOR) METHOD. ASSUMPTIONS AND EXECUTION OF THESE METHODS ARE PER ASHRAE 183-2007...
HVAC LOAD SCHEDULE
EQUIPMENT MARK CROOF CWALL CPART CGLASS CSOLAR CLIGHTS CEQUIP CPSENS CSSENS CFAN COAS CTSENS CPLAT COAL CTLAT CTOT HROOF HWALL HPART HGLASS HSLAB HSPACE HOA HTOT HCU
RTU-1 4 0.7 0 1.7 8.2 6.8 0 12.4 34.2 2.3 13.6 84 10.4 27.7 38.1 122.1 5.6 1.6 0 5.4 2 14.8 33.7 48.5
RTU-2 3.9 2.8 0 3.9 23.6 6.7 0.6 15.4 57.1 2.3 17 87.3 12.9 34.6 47.5 134.8 5.5 6.3 0 12.1 4.1 28.1 42.1 70.2
RTU-3 4.1 4.3 0 0 0 7.1 63.1 3.1 81.9 3.2 12 95.4 2.6 24.4 27.1 122.5 5.8 9.6 0 0 1 16.5 29.7 46.3
HVAC DIFFUSERS AND REGISTERS SCHEDULE
TAG MANUFACTURER MODEL FACE MOUNTING MATERIAL FINISH DAMPER TYPE BORDER STYLE REMARKS
ER-1 PRICE 630FF-TB 24"x24" CEILING ALUMINUM STANDARD WHITE PARALLEL BLADE LAY IN MOUNTING
ER-2 PRICE 630FF-TB 24"x24" CEILING ALUMINUM STANDARD WHITE PARALLEL BLADE LAY IN MOUNTING
RR-1 PRICE 630FF-TB 48"x24" CEILING ALUMINUM STANDARD WHITE PARALLEL BLADE LAY IN MOUNTING
SD-1 PRICE ASCD 24"x24" CEILING ALUMINUM STANDARD WHITE OPPOSED BLADE LAY IN MOUNTING REFER TO DRAWINGS FOR DUCT CONNECTION SIZE
SR-1 PRICE SDGE 4"x18" DUCT ALUMINUM METALESCENT ALUM.BAKED ENAMEL
OPPOSED BLADE SURFACE MOUNT
DCMCSDCNTSC/BFUSEFLAMCACP
LOCAL DISCONNECTMOTOR CONTROL (POWER)DUCT SMOKE DETECTORCONTROLSTOGGLE SWITCHH.A.C.R. CIRCUIT BREAKER AT SOURCE PANELBOARDFUSE AT LOCAL DISCONNECT (VERIFY FIELD RATING)OPERATING FULL LOAD AMPSMINIMUM CIRCUIT AMPACITYCORD AND PLUG CONNECTION
ECEXFCGCHCMFRPCOR
ELECTRICAL CONTRACTOREXISTINGFIRE PROTECTION CONTRACTORGENERAL CONTRACTORHVAC CONTRACTORMANUFACTURERPLUMBING CONTRACTOROWNER OR OTHERS
CSMCCMGMSVFDMSROV
COMBINATION STARTERMOTOR CONTROL STARTERMAGNETIC STARTER OR CONTACTMANUAL STARTERVARIABLE FREQUENCY DRIVEMANUAL STARTER W/ CONTROL RELAYOVERCURRENT PROTECTION
TCCPTBASLOWLINERLINEMANFACOINT
TIMECLOCKCONTROL POWER TRANSFORMERBUILDING AUTOMATION SYSTEMLOW VOLTAGE CONTROLSLINE VOLTAGE CONTROLSREVERSE ACTING LINE VOLTAGE THERMOSTATMANUALFIRE ALARMCARBON MONOXIDE SENSORINTEGRAL TO EQUIPMENT
ABBREVIATIONS CONTRACTOR TYPE MOTOR CONTROL TYPE CONTROL TYPE
HVAC ELECTRICAL COORDINATION SCHEDULE
EQUIPMENTMARK DESCRIPTION
VOLTS(V) PHASE EMERGENCY BHP (HP) HP (HP) HTG (kW) WATTS FLA (A) MCA (A) OCP (A) DC TYPE DC FURN DC INST DC WIRE MC TYPE MC FURN MC INST MC WIRE CN TYPE CN FURN CN INST CN WIRE SD TYPE
EF-1 CENTRIFUGAL ROOF VENTILATOR 120 1 0.05 EC EC EC MG MFR MFR MFR TC EC EC EC
EF-2 CENTRIFUGAL ROOF VENTILATOR 120 1 0.05 EC EC EC MG MFR MFR MFR TC EC EC EC
EF-3 CENTRIFUGAL ROOF VENTILATOR 208 3 1.656 9.5 EC EC EC MG MFR MFR MFR LOW HC HC HC
EF-4 CENTRIFUGAL ROOF VENTILATOR 120 1 0.11 4 EC EC EC MG MFR MFR MFR TC EC EC EC
HP-1 AIR COOLED CONDENSING UNIT 208 3 21.5 30 EC EC EC MG MFR MFR MFR LOW HC HC HC
MUA-1 PACKAGED OUTDOOR HEATING ONLY MAKEUP AIR UNIT 208 3 0.92 8.3 EC EC EC MG MFR MFR MFR LOW HC HC HC DUCT SMOKE
RTU-1 PACKAGED OUTDOOR ROOFTOP UNIT 208 3 58 70 EC EC EC MG MFR MFR MFR LOW HC HC HC DUCT SMOKE
RTU-2 PACKAGED OUTDOOR ROOFTOP UNIT 208 3 58 70 EC EC EC MG MFR MFR MFR LOW HC HC HC DUCT SMOKE
RTU-3 PACKAGED OUTDOOR ROOFTOP UNIT 208 3 58 70 EC EC EC MG MFR MFR MFR LOW HC HC HC DUCT SMOKE
HVAC AIR COOLED CONDENSING UNIT SCHEDULE
Equipment Mark DESCRIPTION LOCATION STATUS WEIGHT (lbs) MANUFACTURER MODEL EER SEER VOLTS PHASE NOMINAL TONS FLA (amps) MCA (amps) OCP (amps) Access
HP-1 AIR COOLEDCONDENSINGUNIT
ON MUA BY OTHERS CAPTIVEAIRE A2-20D-MPU 208 3 5 21.5 30 BY OTHERS
HVAC MAKEUP AIR UNIT SCHEDULE
EQUIPMENTMARK DESCRIPTION LOCATION STATUS WEIGHT (lbs) MANUFACTURER MODEL VOLTS Static BHP HP RPM Voltage PHASE OACFM (cfm) FLA (amps) Access
MUA-1 PACKAGED OUTDOORHEATING ONLYMAKEUP AIR UNIT
ON ROOF BY OTHERS 1361 CAPTIVEAIRE A2-20D-MPU 208 0.5 0.92 1182 3 3000 8.3 BY OTHERS
HVAC ROOFTOP UNITS SCHEDULE
EQUIPMENTMARK DESCRIPTION LOCATION STATUS WEIGHT (lbs) MANUFACTURER MODEL MIN EER VOLTS PHASE CFM (cfm)
ESP (inWC)
FAN RPM(rpm)
BHP(hp) HP (hp)
OACFM(cfm)
NOMINALTONS
OA EAT DB(Deg F)
OA EAT WB(Deg F)
MAT CLG DB(Deg F)
MAT CLG WB(Deg F)
CLG MBH(mbh)
CLG SENS(mbh)
LAT DB(Deg F)
LAT CLG WB(Deg F)
MAT HTG(Deg F)
HTG MBH(mbh)
LAT HTG(Deg F)
GAS HTG IN(mbh)
GAS HTG OUT(mbh)
MIN GASPRESSURE (in
WC)
MAX GASPRESSURE (in
WC)FLA
(amps)MCA
(amps)OCP
(amps) ACCESSORIES
RTU-1 PACKAGEDOUTDOORROOFTOP UNIT
ROOF 1998 CARRIER 48HCDE11 12 208 3 3400 0.5 0 680 10 79 68 122 84 55 54 63 82 224 184 4.5 13.5 58 70 2,3,4,10,21,23
RTU-2 PACKAGEDOUTDOORROOFTOP UNIT
ROOF 1546 CARRIER 48HCDE14 12 208 3 3400 0.5 0 850 10 80 68 135 87 55 54 76 83 224 184 4.5 13.5 58 70 2,3,4,10,21,23
RTU-3 PACKAGEDOUTDOORROOFTOP UNIT
ROOF 1546 CARRIER 48HCDE11 12 208 3 4000 0.6 0 600 10 79 67 123 95 55 54 46 78 224 184 4.5 13.5 58 70 2,3,4,10,21,23
ALL WIND LOAD CALCULATIONS AND DETAILS PERTAINING TO ROOFTOP ATTCHMENT TO STRUCTURE SHALL BE INCLUDED ON STRUCTURAL ENGINEER'S PLANS.
TYPE I/II HOOD, MAKEUP AIR UNIT,GREASE AND DISH FAN DETAILS AND SPECIFICATIONS SHALL BE INCLUDING IN FOOD SERVICE VENDOR DRAWINGS.
WALK IN COOLER AND FREEZER ARE BY OTHERS.
NOTICE TO PLANS EXAMINER
K = MINIMUM OF 1/2"M = 1/2" PLUS MAXIMUM TOTAL STATIC
PRESSURE
H = (1" FOR EACH 1" OF MAXIMUM NEGATIVE STATIC PRESSURE) + 1"J = HALF OF HL = H + J + PIPE DIAMETER + INSULATION
NOTE: OUTDOOR UNITS AND UNITS LOCATED IN UNCONDITIONED SPACES WHICH PROVIDE COOLING IN THE WINTER MUST HAVE HEAT TRACE ON THE CONDENSATE PIPING.
E. PROVIDE UNION UPSTREAM AND DOWNSTREAM OF TRAP.
NEGATIVE PRESSURE
POSITIVE PRESSURE
L
J
CAP
CAP
PIPE FULL SIZEOF AIR UNIT DRAINCONNECTION
AIR UNIT CASING
SEE NOTE B
FLOW
H
GENERAL NOTES:
M
CAP
CAPPIPE FULL SIZEOF AIR UNIT DRAINCONNECTION
AIR UNIT CASING
SEE NOTE B
FLOWK
A. LOCATE TRAPS SO AS TO BE ACCESSIBLE FOR CLEANING.
B. CONDENSATE PIPING SHALL GRADUALLY SLOPE DOWN FROM DRAIN TRAP.
C. CONFIRM TRAP REQUIREMENTS WITH EQUIPMENT MANUFACTURER.
D. REFER TO SPECIFICATIONS FOR MATERIAL AND INSULATION REQUIREMENTS.
6
5
4
3
2
1
7
5
43
2
1
DIFFUSER)
CD (CEILING
REGISTER)
RR (RETURN
REGISTER)
ER (EXHAUST
(LINEAR DIFFUSER)
LD
(SUPPLY REGISTER)
SR
TERMINAL DEVICE
VAV
5
BR
AN
CH
MAIN BRANCH
BRANCH
BRANCH
MVD
SD
SD
SD
GENERAL NOTES:
1. PROVIDE SPLITTER DAMPER(SD) AT ALL MAIN BRANCHTAKEOFFS
2. PROVIDE MANUAL VOLUMEDAMPERS AT ALL BRANCHTAKEOFFS
3. PROVIDE MINIMUM 3 TIMESSTRAIGHT INLET DIAMETERTO ALL VAV TERMINALDEVICES
4. DAMPER NOT REQUIRED AT TERMINAL DEVICE TAKEOFF
5. ALL MANUAL DAMPERSSHALL BE LOCATED IN ANACCESSIBLE CEILING.PROVIDE ACCESS PANEL ASREQUIRED
FLOWAIR
FLOWAIR
BRANCH
BRANCH
BRANCH
MA
IN B
RA
NC
H
MAIN BRANCH
DUCT MAIN DUCT MAIN
MVD
MVD
MVD
MVD
MVD
MVD
AIRFLOW
AIRFLOWFLOW
AIR
MAIN BRANCH
DUCT TEE
AIR FLOW
AIR
FLOW FLOW
AIR
KEYED NOTES:1. 20 GAUGE DOUBLE SHEET
METAL AIR FOIL FULL DEPTH OFMAIN DUCT UP TO 12" WIDEBRANCHES 18 GAUGE ON WIDERBRANCHES
2. MAIN DUCT3. GALVANIZED 3/16" ROD4. VENTLOCK NO. 600-3 DAMPER
BLADE, BRACKET & LOCKINGBALL JOINT WITH 1/4"GALVANIZED OPERATOR PAD
5. BRANCH MAIN DUCT6. DOUBLE THICKNESS TURNING
VANES (TYPICAL)7. 3" RADIUS MINIMUM
Ø
1. SPUN ALUMINUM ROOF EXHAUSTER2. WOOD NAILER3. ANCHOR ALL FOUR SIDES OF CURB CAP INTO
NAILER WITH SCREWS AT 12" O.C.4. PREFABRICATED, INSULATED ALUMINUM CURB5. MOTOR OPERATED DAMPER WIRED TO
INTERFACE WITH EXHAUST FAN START/STOP6. CONDUIT THROUGH HOLE IN DAMPER SHELF7. POWER DISCONNECT8. ALUMINUM BIRDSCREEN9. CURB TYPE AND FLASHING PER ROOFING
MANUFACTURER'S REQUIREMENTS.10. RUBBER GASKET APPLIED TO TOP OF CURB11. ANCHOR TO ROOF DECK AS REQUIRED12. CENTER TRANSITION TO DUCTWORK FROM
DAMPER OR CURB. PROVIDE 3X DIAMETERSTRAIGHT RUN MINIMUM.
13. INSULATED DUCTWORK.
A. DELETE CANT FOR SINGLE MEMBRANE ROOFS.B. TOP OF CURB MUST BE LEVEL. FABRICATE
PITCH IN CURB OR SHIM AS NECESSARY.C. TOP OF CURB SHALL BE A MINIMUM OF 10"
ABOVE FINISHED ROOF SURFACE.CONTRACTOR HAS THE OPTION TO EITHERFURNISH A CURB WITH SUFFICIENT HEIGHT TOACCOMODATE ROOF INSULATION THICKNESSOR TO ADD PRESSURE TREATED WOODBLOCKING,
D.
SECURED TO THE ROOF DECK, BELOW
E.
THE CURB.LOCATE FAN A MINIMUM OF 10'-0" FROMEDGE OF ROOF, INTAKES, AND ROOF HATCH.INSTALL ROOF MEMBRANE UP UNDERFLASHING, FLASH PER ROOFING MFGR. RQMTS.
1
2 3
4
56
7
8
9
10
11
GEN NOTE CMIN 10"-SEE
EF-
GENERAL NOTES:
KEYED NOTES:13
12
KEYED NOTES:
90°
1. REGISTER WITH 0 DEGREE DEFLECTIONBLADE DAMPER(TO BE SIZED AS SCHEDULED)
2. SUPPLY DUCT3. SEAL JOINTS BETWEEN COLLAR AND MAIN
DUCT
1 1
2
33
3 3
90°
1. OMIT FLEX DUCT ON DISTRIBUTIONSYSTEMS THAT PENETRATE 1-HR FIREBARRIERS. REFER TO ARCHITECTURALPLANS FOR LOCATIONS OF FIRE BARRIERS.
GENERAL NOTES:
INSULATION
DUCTSUPPLYMAIN
KEYED NOTES:
9
1. MAXIMUM LENGTH OF INSUL. FLEX DUCTEQUALS 5 FEET. FLEX NOT PERMITTED ININACCESSIBLE CEILINGS
2. INSULATED DUCT, COLLAR AND DIFFUSER BY HVAC CONTRACTOR
3. SCOOP4. SPIN IN FITTING WITH MANUAL VOLUME
DAMPER5. INTERNAL BUTTERFLY DAMPER FOR
DRYWALL APPLICATIONS ONLY.(PROVIDE KEY FOR ADJUSTMENT)
6. SECURE TO CEILING PER MANUFACTURER'SRECOMMENDATIONS AND PER CEILING FINISH.PROVIDE GRID CLIPS PER MFG'R REQUIREMENTS.PROVIDE FRAMING FOR DRYWALLINSTALLATION.
7. HANGER, SECURE TO STRUCTURE ANDDUCTWORK
8. PEEL BACK INSULATION AND PROVIDE STRAPPINGAND SHEET METAL SCREWS AT FLEX CONNECTIONTO DUCT. THEN PROVIDE STRAPPING AROUNDINSULATION.
9. SUPPORT FLEX TO PREVENT COLLAPSING
6
2
5
8
18
4 2
3
7
2
4
3
9
7 7
6
5
4
3
3
8
1
2
2 2
3"3"
3"
MIN30"
COMMERCIALDISHWASHER
1. ROOF EXHAUSER, SEE DETAIL.2. HOOD TO BE SUPPORTED BY
NON-COMBUSTIBLE SUPPORTS3. 6" CLEARANCE4. INSULATED EXHAUST DUCT MIN. 24 GA.
STAINLESS STEEL5. INTERIOR WALL6. FLASH & COUNTER FLASH AT CURB.7. 6" MINIMUM OVERHANG ABOVE EQUIPMENT.8. ROOF SYSTEM9. CEILING
KEYED NOTES:
FRONT VIEW SIDE VIEW
A. TYPE I HOOD SHALL BE STAINLESS STEEL,18 GAUGE, WITH WELDED SEAMS AND UL710 LISTED.
B. EXHAUST DUCT SHALL BE 16 GA. BLACKIRON OR 18 GA. STAINLESS STEEL, FINISH #3, WITH CONTINUOUS LIQUID TIGHT WELDEDJOINTS AND SEAMS.
C. AIR VELOCITY SHALL BE PER CODE AND AHJ.D. PROVIDE INSULATION WRAP EQUAL TO 3M
"FIRE MASTER DUCT WRAP" WITH ULLISTINGS OF 723, 1978 AND 1479.
E. INSULATION SHALL BE A LIGHT WEIGHTNON-ASBESTOS, HIGH TEMPERATURE,INORGANIC, CERAMIC FIBER BLANKETTOTALLY ENCAPSULATED IN FOIL/SCRIMHAVING A SERVICE TEMPERATURE RANGEUP TO 2300 DEGREE F.
F. INSULATION SHALL BE A 2-HOUR FIRERESISTIVE RATED GREASE AIR DUCTENCLOSURE AS A SHAFT ALTERNATIVE ANDA METHOD FOR PROVIDING ZERO INCHCLEARANCE AROUND COMMERCIALKITCHEN GREASE DUCT EXHAUST SYSTEMSTO COMBUSTIBLE MATERIALS.
G. ALUMINUM GREASE FILTER WITH TROUGH,SHALL BE INSTALLED IN THE HOOD INCOMPLIANCE WITH CODE. FILTERS SHALLBE MOUNTED AT AN ANGLE OF 45 DEGREESMINIMUM.
H. PROVIDE STAINLESS STEEL ENCLOSUREPANEL BETWEEN TOP OF KITCHEN HOODAND CEILING, PER LOCAL CODEREQUIREMENTS.
GENERAL NOTES:
EQUIPMENTKITCHEN
6" MIN
10'-0" MIN. TO ROOFEDGE/ O.A. INTAKE
6" MIN6" MIN
4'-0" MAX.
KITCHENEQUIPMENT
ROOF
FLOOR
1. KITCHEN EXHAUST FAN U.L. LISTEDFOR GREASE (SEE KITCHENEXHAUSTER DETAIL).
2. 16 GAUGE INSULATED WELDEDBLACK IRON OR 18 GAUGEINSULATED WELDED STAINLESSSTEEL. DUCTWORK WRAPPEDWITH 2 LAYERS OF ZERO CLEARANCE DUCT WRAP (TYPICAL).3. HEAT SENSOR IN EACH COLLARINTERLOCKED TO VENTILATIONSYSTEM.
4. FLANGED & GASKETED DUCT TOEXHAUST FAN CONNECTION.
5. CLEAN OUT DOOR/LATCH (12"x12"MIN) MADE OF 16 GAUGE WELDEDBLACK IRON OR 18 GAUGE WELDEDSTAINLESS STEEL (TYPICAL).
6. MINIMUM 2% SLOPE TOWARD HOODWITH CLEANOUT A MINIMUM OFEVERY 15 FEET AND CHANGE INDIRECTION.
7. GREASE DUCT SUPPORT IS TO BESIZED, SPACED AND INSTALLED BYCODE.
8. HOOD W/ ANSUL SYSTEM.MAINTAIN 18" CLEARANCE TOCOMBUSTIBLES.
9. GREASE DRIP TRAY.
1
2
3
4
6
7
2
8
8
9
5
15'-0" MAX
KEYED NOTES:
18" MIN
40" MIN
1. GAS FIRED ROOFTOP UNIT LOCATEA MINIMUM OF 10'-0" FROM EDGEOF ROOF AND ROOF HATCH
2. CANVAS FLEXIBLE CONNECTION3. 1" ACOUSTICALLY LINED DUCTS4. 4x4 ANGLE FASTENED TO ROOF
DECK AND STRUCTURAL SYSTEM.PROVIDE SUPPORTS AS REQUIRED
5. FACTORY FABRICATED, INSULATEDROOF CURB (BY SAME MFG'R ASUNIT)
6. FASTEN CURB TO DECK7. INSULATED RADIUSED ELBOW8. UNION BY PLUMBING
CONTRACTOR (PC)9. GAS SHUT-OFF VALVE BY PC10. GAS LINE (BLACK STEEL) BY PC11. SECURE TO CURB12. WOOD NAILER13. ROOFING MEMBRANE, FLASH UP
TO BELOW WOOD NAILOR14. CANT STRIP15. ROOF DECK - CUT OPENINGS FOR
DUCT PENETRATIONS ONLY16. CONDENSATE TRAP - SEE
CONDENSATE DRAIN TRAP DETAIL17. HIGH WATER ALARM IN
CONDENSATE DRAIN PAN. WIRETO BREAK 24 VOLT CONTROL POWER IN THE CASE OF A HIGH WATER EVENT.
A. CONTRACTOR SHALL PROVIDE CURB TOMAINTAIN 14" MINIMUM ABOVE FINISHEDROOFING SYSTEM. PROVIDE ADDITIONALBLOCKING AS REQUIRED TO ACCOMMODATEROOF INSULATION THICKNESS
B. FINAL LOCATION AND STRUCTURALVERIFICATION BY OTHERS.
GENERAL NOTES:KEYED NOTES:
7
6
5 3
2
4
2
9
8
10
312 13
14
15
16
11
1
17
8
11
6
6
10
11 5
2
4
2
45
9
4
3
8
7
6
5
3
4
2
1
1. DUCT, COLLAR ANDRETURN/EXHAUST REGISTER
2. MANUAL VOLUME DAMPER3. SECURE TO CEILING PER
MANUFACTURER'SRECOMMENDATIONS AND PERCEILING FINISH. PROVIDE GRIDCLIPS PER MFG'R REQUIREMENTS
4. HANGER, SECURE TOSTRUCTURE AND DUCTWORK
5. ATTACH DUCT TO REGISTER6. BALANCING DAMPER FOR FINAL
BALANCING7. SHEET METAL DUCTWORK8. MAIN RETURN/EXHAUST DUCT9. TAP DROP TO RETURN/EXHAUST
REGISTER INTO BOTTOM OFBRANCH
10. SPIN IN FITTING11. HARD SHEET METAL ELBOW AT
CONNECTION TO AIR DEVICE.
KEYED NOTES:
LAY-IN MOUNT
SURFACE MOUNT
W
L
L=1/4W, 4" MIN
ROUND DUCT INSTALLATION
OW
NE
RS
HIP
OF
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E
All
report
s, pla
ns, specifi
catio
ns, com
pute
r fil
es, fie
ld d
ata
, note
s a
nd o
ther
docum
ents
and in
str
um
ents
pre
pare
d b
y the C
onsultant as in
str
um
ents
of serv
ice s
hall
rem
ain
the p
ropert
y o
f th
e C
onsultant. T
he C
onsultant shall
reta
in a
ll com
mon law
, sta
tuto
ry a
nd o
ther
reserv
ed r
ights
, in
clu
din
g, w
ithout lim
itatio
n, th
e c
opyright th
ere
to.
Project No.
Title
Issue Date
Sheet
This drawing is the property of ARCHITECTURALGROUP INT'L and is not to be reproduced orcopied in whole or in part. It is only to be usedfor the project and site specifically identified herinand is not to be used on any other project.It is to be returned upon request.Scales as stated hereon are valid on the originaldrawing only. Contractor shall carefully review alldimensions and conditions shown hereon and atonce report to the Architect any error, inconsis-tancy or omission he may discover.
Revisions:
Mark Date By Description
Issued
WWW.KLHENGRS.COM
MECHANICAL/ELECTRICAL ENGINEERS
LEXINGTON, KENTUCKYCOLUMBUS, OHIO
NEW YORK, NEW YORK
1538 ALEXANDRIA PIKE, SUITE11 FT. THOMAS, KENTUCKY
41075 800-354-9783859-442-8050
859-442-8058 FAX
M103
MECHANICALDETAILS
10/25/2018
FIRST WATCHNINE MILE
PENSACOLA, FL
20873
11/12/2018 KLH
AGI REVIEW
11/15/2018 KLH
PERMIT
SCALE: NONE
232113.23-05 - CONDENSATE DRAIN TRAP POSITIVE & NEGATIVE
SCALE: NONE
233300.00-01 - MANUAL DAMPER DETAIL
SCALE: NONE
233423.00-10 - ROOF EXHAUSTER A
SCALE: NONE
233713.00-01 - ANGLED REGISTER INSTALLATION 0 DEGREES
SCALE: NONE
233713.00-04 - DIFFUSER INSTALLATION TYPICAL
SCALE: NONE
233813.00-01 - DISHWASHER HOOD TYPE 2
SCALE: NONE
233813.00-04 - KITCHEN HOOD DETAIL UP BLAST
SCALE: NONE
237433.00-04 - ROOF CURB & MOUNTING C
SCALE: NONE
233713.00-21 - RETURN/EXHAUST REGISTER INSTALLATION
OW
NE
RS
HIP
OF
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E
All
report
s, pla
ns, specifi
catio
ns, com
pute
r fil
es, fie
ld d
ata
, note
s a
nd o
ther
docum
ents
and in
str
um
ents
pre
pare
d b
y the C
onsultant as in
str
um
ents
of serv
ice s
hall
rem
ain
the p
ropert
y o
f th
e C
onsultant. T
he C
onsultant shall
reta
in a
ll com
mon law
, sta
tuto
ry a
nd o
ther
reserv
ed r
ights
, in
clu
din
g, w
ithout lim
itatio
n, th
e c
opyright th
ere
to.
Project No.
Title
Issue Date
Sheet
This drawing is the property of ARCHITECTURALGROUP INT'L and is not to be reproduced orcopied in whole or in part. It is only to be usedfor the project and site specifically identified herinand is not to be used on any other project.It is to be returned upon request.Scales as stated hereon are valid on the originaldrawing only. Contractor shall carefully review alldimensions and conditions shown hereon and atonce report to the Architect any error, inconsis-tancy or omission he may discover.
Revisions:
Mark Date By Description
Issued
WWW.KLHENGRS.COM
MECHANICAL/ELECTRICAL ENGINEERS
LEXINGTON, KENTUCKYCOLUMBUS, OHIO
NEW YORK, NEW YORK
1538 ALEXANDRIA PIKE, SUITE11 FT. THOMAS, KENTUCKY
41075 800-354-9783859-442-8050
859-442-8058 FAX
M601
MECHANICALSPECIFICATIONS
10/25/2018
FIRST WATCHNINE MILE
PENSACOLA, FL
20873
11/12/2018 KLH
AGI REVIEW
11/15/2018 KLH
PERMIT
“
OW
NE
RS
HIP
OF
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E
All
report
s, pla
ns, specifi
catio
ns, com
pute
r fil
es, fie
ld d
ata
, note
s a
nd o
ther
docum
ents
and in
str
um
ents
pre
pare
d b
y the C
onsultant as in
str
um
ents
of serv
ice s
hall
rem
ain
the p
ropert
y o
f th
e C
onsultant. T
he C
onsultant shall
reta
in a
ll com
mon law
, sta
tuto
ry a
nd o
ther
reserv
ed r
ights
, in
clu
din
g, w
ithout lim
itatio
n, th
e c
opyright th
ere
to.
Project No.
Title
Issue Date
Sheet
This drawing is the property of ARCHITECTURALGROUP INT'L and is not to be reproduced orcopied in whole or in part. It is only to be usedfor the project and site specifically identified herinand is not to be used on any other project.It is to be returned upon request.Scales as stated hereon are valid on the originaldrawing only. Contractor shall carefully review alldimensions and conditions shown hereon and atonce report to the Architect any error, inconsis-tancy or omission he may discover.
Revisions:
Mark Date By Description
Issued
WWW.KLHENGRS.COM
MECHANICAL/ELECTRICAL ENGINEERS
LEXINGTON, KENTUCKYCOLUMBUS, OHIO
NEW YORK, NEW YORK
1538 ALEXANDRIA PIKE, SUITE11 FT. THOMAS, KENTUCKY
41075 800-354-9783859-442-8050
859-442-8058 FAX
M602
MECHANICALSPECIFICATIONS
10/25/2018
FIRST WATCHNINE MILE
PENSACOLA, FL
20873
11/12/2018 KLH
AGI REVIEW
11/15/2018 KLH
PERMIT
OW
NE
RS
HIP
OF
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E
All
report
s, pla
ns, specifi
catio
ns, com
pute
r fil
es, fie
ld d
ata
, note
s a
nd o
ther
docum
ents
and in
str
um
ents
pre
pare
d b
y the C
onsultant as in
str
um
ents
of serv
ice s
hall
rem
ain
the p
ropert
y o
f th
e C
onsultant. T
he C
onsultant shall
reta
in a
ll com
mon law
, sta
tuto
ry a
nd o
ther
reserv
ed r
ights
, in
clu
din
g, w
ithout lim
itatio
n, th
e c
opyright th
ere
to.
Project No.
Title
Issue Date
Sheet
This drawing is the property of ARCHITECTURALGROUP INT'L and is not to be reproduced orcopied in whole or in part. It is only to be usedfor the project and site specifically identified herinand is not to be used on any other project.It is to be returned upon request.Scales as stated hereon are valid on the originaldrawing only. Contractor shall carefully review alldimensions and conditions shown hereon and atonce report to the Architect any error, inconsis-tancy or omission he may discover.
Revisions:
Mark Date By Description
Issued
WWW.KLHENGRS.COM
MECHANICAL/ELECTRICAL ENGINEERS
LEXINGTON, KENTUCKYCOLUMBUS, OHIO
NEW YORK, NEW YORK
1538 ALEXANDRIA PIKE, SUITE11 FT. THOMAS, KENTUCKY
41075 800-354-9783859-442-8050
859-442-8058 FAX
M701
MECHANICALENERGY
COMPLIANCE
10/25/2018
FIRST WATCHNINE MILE
PENSACOLA, FL
20873
11/12/2018 KLH
AGI REVIEW
11/15/2018 KLH
PERMIT