First Revision No. 1510-NFPA 70-2015 [ Global Input ]
Change title of Article 400 to Flexible Cords and Flexible Cables
Submitter Information Verification
Submitter Full Name: CMP 6Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Mon Jan 19 17:01:44 EST 2015
Committee Statement
CommitteeStatement:
This is being done to mirror the scope of the article in 400.1, and also to clear up any misconceptions that might lead one to believe thatthis article covers the cable wiring methods addressed in Chapter three.
ResponseMessage:Public Input No. 2460-NFPA 70-2014 [Article 400]
Ballot Results
This item has passed ballot
12 Eligible Voters0 Not Returned
12 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention
Affirmative AllBrush, Edwin F.Friedman, Samuel B.Huddleston, Jr., Robert L.Kent, Gerald W.Laidler, William F.Picard, Paul R.Riedl, KennethSmith, Michael W.Stacey, JohnWall, Carl TimothyXerri, MarioZimnoch, Joseph S.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
1 of 1802 4/22/2015 10:39 AM
ksheaText Box
First Revision No. 1519-NFPA 70-2015 [ Global Input ]
See attached file for renumbering in Articles 400 and 402
Supplemental Information
File Name DescriptionPanel_6_Global_FR_1519_cjf_renumbering.docx
Submitter Information Verification
Submitter Full Name: CMP 6Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Jan 20 13:25:27 EST 2015
Committee Statement
CommitteeStatement:
This will make the NEC more user friendly by following an already established pattern that the .10 and .12 sections of an article isuses permitted and uses not permitted, respectively.
ResponseMessage:Public Input No. 4207-NFPA 70-2014 [Section No. 402.5]Public Input No. 4210-NFPA 70-2014 [Section No. 402.3]Public Input No. 796-NFPA 70-2014 [Section No. 400.7]Public Input No. 804-NFPA 70-2014 [Section No. 402.11]
Ballot Results
This item has passed ballot
12 Eligible Voters0 Not Returned
12 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention
Affirmative AllBrush, Edwin F.Friedman, Samuel B.Huddleston, Jr., Robert L.Kent, Gerald W.Laidler, William F.Picard, Paul R.Riedl, KennethSmith, Michael W.Stacey, JohnWall, Carl TimothyXerri, MarioZimnoch, Joseph S.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
2 of 1802 4/22/2015 10:39 AM
First Revision No. 18-NFPA 70-2015 [ Global Input ]
See attached file of revised Table 110.26(A)(1).
Supplemental Information
File Name DescriptionFR_18_edited.docx
Submitter Information Verification
Submitter Full Name: CMP 1Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Wed Jan 21 04:30:01 EST 2015
Committee Statement
CommitteeStatement:
This revision incorporates the work of a Correlating Committee Task Group to: (1) resolve issues with actions taken by Code-making Panels1 and 8 on proposals and comments in the 2014 NEC cycle relative to changing the voltage threshold in articles under their purview from600 volts to 1000 volts, (2) address indoor and outdoor electrical substations, and (3) evaluate other higher voltage threshold requirementsto be included relative to present trends.
The revision of this table brings in the voltage ranges and clearance distances from Table 110.34(A).
The correlation of SI units is consistent with other tables in Article 110 such as Table 110.34(A).
Editorially removed the word as from Condition 2.
ResponseMessage:Public Input No. 688-NFPA 70-2014 [Section No. 110.26(A)(1)]Public Input No. 2859-NFPA 70-2014 [Section No. 110.26(A)(1)]Public Input No. 3262-NFPA 70-2014 [Section No. 110.26(A)(1)]Public Input No. 1556-NFPA 70-2014 [Section No. 110.26(A)(1)]
Ballot Results
This item has passed ballot
12 Eligible Voters0 Not Returned
12 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention
Affirmative AllAnthony, Michael A.Barrios, Louis A.Boyce, Kenneth P.Deike, Jr., Roland E.Gallo, Ernest J.Hickman, Palmer L.Hittinger, David L.Iverson, Donald R.Pierce, James F.Sassaman, Harry J.Sayler, Kent A.Sood, Mohinder P.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
3 of 1802 4/22/2015 10:39 AM
First Revision No. 2128-NFPA 70-2015 [ Global Input ]
Annex C
1. Reorder existing Tables, as follows:
(1) C.5 becomes C.6
(2) C.5(A) becomes C.6(A)
(3) C.6 becomes C.5
(4) C.6(A) becomes C.5(A)
2. Insert new Tables C.7 and C.7(A), per attached, and renumber existing C.7 through C.12(A).
3. Update Table of Contents at beginning of Annex C.
Supplemental Information
File Name DescriptionTable_C.7_2128_BC.docx Table_C.7.A_2128_BC.docx FR_2128_Table_C.7_edited.docx FR_2128_Table_C.7A_edited.docx
Submitter Information Verification
Submitter Full Name: CMP 8Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Mon Jan 19 17:18:18 EST 2015
Committee Statement
CommitteeStatement:
Existing tables for LFNC-A and LFNC-B have been re-ordered, alphabetically.
The new Table C.7 and Table C.7(A) identify fills for LFNC-C to Annex C for both concentrically stranded conductors and compactconductors.
Response Message:Public Input No. 1069-NFPA 70-2014 [Annex C]Public Input No. 1071-NFPA 70-2014 [Annex C]
Ballot Results
This item has passed ballot
13 Eligible Voters0 Not Returned
12 Affirmative All1 Affirmative with Comments0 Negative with Comments0 Abstention
Affirmative AllCampbell, David M.Cogburn, Larry D.Gerstetter, David A.Hengst, Kenneth W.Jackson, PeteJohnson, Gary K.Kendall, David H.Loyd, Richard E.Myers, Paul W.Offerdahl, Donald R.Roe, Rhett A.West, Rodney J.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
4 of 1802 4/22/2015 10:39 AM
Affirmative with CommentAllen, David F. The new Table C.7 and Table C.7(A) identify fills for LFNC-C to Annex C for both concentrically stranded conductors and compact conductors.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
5 of 1802 4/22/2015 10:39 AM
First Revision No. 343-NFPA 70-2015 [ Global Input ]
Article 220 shall read:
Branch Circuit, Feeder, and Service Load Calculations
Submitter Information Verification
Submitter Full Name: CMP 2Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Fri Jan 23 12:08:55 EST 2015
Committee Statement
Committee Statement: The proposed revisions enhance the clarity of the article.Response Message:
Ballot Results
This item has passed ballot
13 Eligible Voters0 Not Returned
12 Affirmative All1 Affirmative with Comments0 Negative with Comments0 Abstention
Affirmative AllBoynton, Charles L.Buuck, DanielDomitrovich, Thomas A.Duren, Ronald E.Harman, Thomas L.Hilbert, Mark R.King, Donald M.LaRocca, Robert L.Manche, AlanMcGovern, William J.Thorwegen, Jr., Stephen J.Wood, Thomas H.
Affirmative with CommentColuccio, Frank I agree with the committee statement
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
6 of 1802 4/22/2015 10:39 AM
First Revision No. 4508-NFPA 70-2015 [ Global Input ]
Edit title of Article 770
ARTICLE 770 Optical Fiber Cables and Raceways
Submitter Information Verification
Submitter Full Name: CMP 16Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Mon Jan 12 14:09:28 EST 2015
Committee Statement
CommitteeStatement:
CMP-16 edits the title of the article. Optical fiber raceways have been deleted from this article. This FIRST REVISION changes the title toArticle 770 back to the title it had from its introduction into the 1984 edition through the 1990 edition. When optical fiber raceways were addedto Article 770 in the1993 edition, the title was changed to Optical Fiber Cables and Raceways. Optical fiber raceways were removed from the2014 edition (replaced by communications raceways) but the Article title was not changed. The Article title should accurately reflect thecontents of the Article.
The Panel recognizes that Article titles are the responsibility of the Correlating Committee and recommends that the Correlating Committeeconcur with this FIRST REVISION.
ResponseMessage:Public Input No. 208-NFPA 70-2014 [Article 770]
Ballot Results
This item has passed ballot
17 Eligible Voters0 Not Returned
17 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention
Affirmative AllBish, GeorgeBrunssen, James E.Dawson, Fred C.Dorna, Gerald LeeIvans, Randolph J.Jensen, Robert W.Johnson, Steven C.Lawrence, EricMcCoy, William J.McNamara, JackMoore, Thomas E.Murphy, Michael F.Ohde, Harold C.Parrish, Thomas J.Pirkle, W. DouglasPrezioso, Luigi G.Zieman, Leo
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
7 of 1802 4/22/2015 10:39 AM
First Revision No. 4609-NFPA 70-2015 [ Global Input ]
830.110(A)(3)(3) Innerduct for Low-Power Network-Powered Broadband Communications Cables. Listed plenum communicationsraceway, listed riser communications raceway