FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for...

26
Printed in Canada Rev.07 December 2009 PISBSRSE FIREPLACE MODELS SB36 - SE36 SB42 Installation and Operating Instructions This installation manual will help you to obtain a safe, efficient, dependable installation for your fireplace and chimney system. Please read and understand these installation instructions before beginning your installation. Warning : Do not attempt to modify or alter the construction of the fireplace or its components. Any modification or alteration of construction may void the warranty, listings and approvals of this system. In such a case, Security Chimneys International will not be responsible for damages. SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. 2125 Monterey St., Laval, Quebec, Canada H7L 3T6 Tel.: (450) 973-9999 SE36 SB36 SB42 Hot! Do not touch! The glass and surfaces of this appliance will be hot during operation and will retain heat for a while after shutting off the appliance. Severe burn may result. Carefully supervise children in the same room as appliance. If small children are present in the home, it is recommended that this appliance be used with a fire screen kit. Listed to standards : UL-127, ULC-S610 This appliance has been certified as being exempt from EPA 40 CFR 60 standard

Transcript of FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for...

Page 1: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

Printed in Canada Rev.07 December 2009 PISBSRSE

FIREPLACE MODELS

SB36 - SE36

SB42

Installation and Operating

Instructions

This installation manual will help

you to obtain a safe, efficient,

dependable installation for your fireplace

and chimney system. Please read and

understand these installation instructions

before beginning your installation.

Warning: Do not attempt to modify or

alter the construction of the fireplace or

its components. Any modification or

alteration of construction may void the

warranty, listings and approvals of this

system. In such a case, Security

Chimneys International will not be

responsible for damages.

SAVE THESE INSTRUCTIONS

FOR FUTURE REFERENCE.

2125 Monterey St., Laval, Quebec, Canada H7L 3T6 Tel.: (450) 973-9999

SE36

SB36

SB42

• Hot! Do not touch! The glass and surfaces of this appliance

will be hot during operation and

will retain heat for a while after

shutting off the appliance.

Severe burn may result.

• Carefully supervise children in the same room as appliance.

• If small children are present in the home, it

is recommended that this appliance be used

with a fire screen kit.

Listed to standards :

UL-127, ULC-S610

This appliance has been

certified as being exempt from

EPA 40 CFR 60 standard

Page 2: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

i

CERTIFICATION

LABEL

Page 3: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

iii

TABLE OF CONTENTS

Page

Safety Rules .............................................................................................................................. 1

Fireplace Maintenance Creosote ............................................................................................................................... 2

Chimney Maintenance ......................................................................................................... 2

Chimney Fires ..................................................................................................................... 2

Fireplace Installation

Recommendations ............................................................................................................... 3

Tools and Building Supplies ............................................................................................... 4

Fireplace Installation Procedure .......................................................................................... 4

Locating the Fireplace ......................................................................................................... 4

Adjacent Walls .................................................................................................................... 4

Enclosure ............................................................................................................................. 5

Facing and Mantel ............................................................................................................... 5

Hearth Extension Requirements .......................................................................................... 6

Outside Air Installation ....................................................................................................... 7

Chimney Installation

General Notes .................................................................................................................... 10

Straight Installation ........................................................................................................... 11

Offset Installation ................................................................................................................ 13

Angled Wall Radiation Shield (Insulated Radiation Shield) .............................................. 17

Universal Roof Support Installation .................................................................................... 18

Universal Offset Support Installation .................................................................................. 18

Chimney Chase and Multiple Terminations ........................................................................ 19

Parts and Components ............................................................................................................ 20

Door Handle Installation (Model SE36) ................................................................................ 22

Fireplace Dimensions .............................................................................................................. 23

Page 4: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

1

SAFETY RULES FOR OPERATING YOUR

FIREPLACE MODEL SB36, SE36, SB42

� When in operation, a fireplace will draw air out of the house. If an outside air kit for the

fireplace is not installed, it may be necessary to leave a window or door open a little while using

the fireplace.

WARNING: When doors are installed on the fireplace, it should be operated with the doors fully

opened or fully closed. If the doors are left partly open, smoke may be drawn into

the room.

� Only use Security Chimneys International Ltd glass doors.

� Always keep the firescreen or the door closed and the damper opened when using the fireplace.

Keep the damper closed when the fireplace is not in use.

� When cleaning your fireplace, ashes should be placed in a metal container with a tight-fitting lid.

The closed container of ashes should be placed on a non-combustible floor or on the ground, well

away from all combustible materials, pending final disposal. If the ashes are disposed of by

burial in soil or otherwise locally dispersed, they should be retained in the closed container until

all cinders have thoroughly cooled.

CAUTION: Never leave children unattended when there is a fire burning in the fireplace.

CAUTION: This fireplace has been tested with Security Chimneys International Ltd wood

grates. They must always be used.

CAUTION: Keep combustible material at least 48" away from the front of the fireplace

opening.

CAUTION: Never use gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter fluid or

similar liquid to start or "freshen up" a fire in this fireplace. Keep all such liquid

well away from the fireplace at all times.

WARNING: This fireplace has provisions for the installation of a gas pipe and is intended only

for connection to a decorative gas appliance incorporating an automatic shutoff

device and complying with ANSI Z21.60-M96/CGA 2.26-M96, Standard for

Decorative Gas Appliances for Installation in Solid-Fuel Burning Fireplaces.

WARNING: THIS FIREPLACE HAS NOT BEEN TESTED WITH AN UNVENTED GAS LOG

SET. TO REDUCE RISK OF FIRE OR INJURY, DO NOT INSTALL AN

UNVENTED GAS LOG SET INTO THIS FIREPLACE.

CAUTION: DO NOT USE CHEMICAL GLASS CLEANER ON PAINTED SURFACES AS IT

MAY CAUSE PAINT TO PEEL.

Page 5: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

2

FIREPLACE MAINTENANCE

CREOSOTE

When wood is burned slowly, it produces tar and other organic vapors which combine with expelled moisture to

form a black deposit called creosote. The creosote vapors condense in the relatively cool chimney flue of a

slow-burning fire. As a result, creosote residue accumulates on the flue lining. When ignited, this creosote makes

an extremely hot fire. If the creosote accumulation is large, a creosote fire in the chimney can damage the chimney

and overheat the surrounding wood framing. Creosote formation in a chimney can be minimized by making small

hot fires rather than slow-burning, smouldering fires.

CHIMNEY MAINTENANCE

Regular chimney inspection and maintenance combined with proper operation will help prevent chimney fires.

Keep your chimney clean. Do not allow more than 1/16" (1.6 mm) build up of creosote in your chimney. The

amount of creosote will depend on variables such as frequency of use and type of fire. We recommend that you:

1. Initially inspect the chimney system weekly. From this you will learn how often it will be necessary to clean

your chimney.

2. Have your chimney cleaned by a qualified chimney sweep. If you wish to clean it yourself, we recommend

using a stiff plastic or non-metallic brush. If a metal brush is used, its' size should be slightly smaller than the

flue to avoid damaging the chimney. Do not use a brush that could scratch the stainless steel interior of the

chimney.

3. Do not expect chemical cleaners to keep your chimney clean. The rain cap can be removed for inspection

and/or cleaning of the chimney.

CHIMNEY FIRES

If you are having a chimney fire, follow these steps:

1. Block the fireplace opening with a non-combustible material such as asbestos or a steel sheet. If you have glass

doors, close them.

2. Alert your family of the possible danger.

3. If you require assistance, alert your fire department.

4. If possible, use a dry chemical fire extinguisher, baking soda or sand to control the fire. Do not use water as it

may cause a dangerous steam explosion.

5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to ensure that

sparks and hot embers coming out of the chimney are not igniting the roof.

6. Do not use the fireplace again until your chimney and fireplace have been inspected by a qualified chimney

sweep or fire department inspector.

Page 6: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

3

FIREPLACE INSTALLATION

RECOMMENDATIONS TO THE INSTALLER

1. Before starting your fireplace installation, read these safety tips and installation instructions carefully to be sure

you understand them completely. Failure to follow them could cause a fireplace malfunction resulting in

serious bodily injury and / or property damage.

2. Always check your local building codes. The installation must comply with their regulations.

3. These fireplaces can use an ASHT+ / HT6103+, S-2100+ / HT6000+ or AC chimney system of the inside

diameter recommended by Security Chimneys International Ltd (SE36 and SB36: 7" inside diameter, SB42: 8"

inside diameter)

4. To maintain top efficiency and to prevent build-up of soot and creosote, inspect and clean the chimney

periodically during the heating season.

5. Ensure an adequate supply of combustion air to prevent possible hazards due to poor combustion and to avoid

affecting other fuel burning appliances.

6. Your Security fireplace has been tested and listed to UL and ULC standards, to be installed in accordance with

this brochure by Warnock Hershey International, Inc.

7. These instructions are written to give you an outline for a fast, safe installation and trouble-free operation.

8. Failure to use parts manufactured by Security Fireplace or variations in techniques and construction materials

described in this installation manual may create a serious fire hazard; it may void the Security Fireplace

warranty and will void the WHI listing.

9. The Security fireplace features optional glass doors, outside combustion air kit, blowers and decorative trims

and panels.

10. When selecting the location, the chimney outlet position and the direction of the wind are important factor affecting the chimney performance. To allow a maximum draft and to reduce wind turbulence, the chimney

must:

• Penetrate the highest part of the roof.

• Be installed as far as possible of roof offsets, trees or any other obstructions that may cause wind

turbulence and back drafts in the chimney.

• The least amount of offsets (elbows) possible.

Page 7: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

4

TOOLS AND BUILDING SUPPLIES NORMALLY REQUIRED

Tools should include: If gas pipe is used: Building supplies:

Phillips screwdriver Pipe wrench Framing materials

Slot style screwdriver Pipe cutter Wall finishing materials

Hammer Pipe threader Caulking materials

Saw and/or Sabersaw Pipe joint compound (non-combustible)

Level Pipe key valve Fireplace front

Measuring Tape (overlay material)

Plumb line Hearth extension

Electric drill and bits (non-combustible)

Pliers

Square

CAUTION

The most important areas of concern dealing with the installation of factory built fireplaces are clearances to

combustible materials, secure assembly of component parts, the height of the chimney system, the proper use of

accessory equipment and the techniques employed in using finishing materials applied to fireplace surrounds, hearth

extensions and wall coverings. Each of these topics will be covered in great detail throughout this manual.

PLEASE GIVE EACH OF THESE INSTRUCTIONS SPECIAL ATTENTION AS YOU PROGRESS WITH

YOUR INSTALLATION.

FIREPLACE INSTALLATION PROCEDURE

1. Move the fireplace into desired position.

2. Install the outside air assembly (if required).

3. Install the hearth extension. Make sure the gap between the fireplace and the hearth extension is sealed.

4. If using an AC chimney, remove the radiation ring on top of the fireplace. (See Figure 6).

LOCATING THE FIREPLACE

Do not place the fireplace on carpeting, vinyl or other

soft surface floor covering. It may however, be

directly placed on flat wood, plywood, particle board

or other hard surface materials.

ADJACENT WALLS

A wall perpendicular to and in front of the fireplace

front facing must be at least 18" (460 mm) from the

fireplace opening. A wall at 45° to the front facing

and starting at the fireplace's outer edge is permitted.

Projections within this area are permitted.

(See Figure 1).

WALL FIREPLACE

45o

OPENING

18" (460 mm)

Figure 1

Page 8: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

5

ENCLOSURE

1. WARNING: Do not place loose insulation or any other material in the space around the fireplace or the

chimney. Insulation placed on or around the fireplace or chimney may cause adjacent wood to overheat and

catch on fire. (Security Chimneys International recommends that you install the fireplace against a finished

wall).

2. IN CANADA, the fireplace must be installed against a finished wall. It must not be installed against a vapour

barrier or exposed insulation

3. The fireplace is zero clearance. Combustible material like wood, plywood, particle board or drywall can be in

direct contact with the fireplace wall or the fireplace top spacer. Two inch (50 mm) clearance to combustibles

must be kept around the chimney.

4. Do not block the fireplace's hot air vents or air inlets as this will cause the fireplace to overheat.

FACING AND MANTEL

The fireplace should be framed using 2" x 3"

(50 mm x 75 mm) or heavier lumber. Figures 6 and 7

show the general framing layout.

Combustible materials must be installed flush with the

fireplace facing. It may not project out in front of the

fireplace. (See Figure 2)

Non-combustible materials such as brick, stone or

ceramic tile may project in front of and / or on the

fireplace facing.

WARNING: The header should rest on top of the metal spacers (See Figure 2). Do not alter the spacers or notch the header to fit

around them. Do not block the air inlet or outlet as this will cause the fireplace to overheat. A wood mantle, if

installed, must be at least 48" (1.2 m) above the base of the fireplace. (See Figure 3a)

COMBUSTIBLE MATERIAL

JOIST 2" X 3" (50MM X 75MM)

SPACER WRONG WAY

FIREPLACE

Figure 2

Page 9: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

6

HEARTH EXTENSION REQUIREMENTS

A non-combustible hearth extension must be built in front of the fireplace and extend out on both sides.

Hearth extensions must be constructed according to the following guidelines:

1. A layer of sheet metal 0.018" (0.45 mm) thick or 3/8" (9 mm) thick millboard or any other material

(tiles, marble or granite) with equivalent heat resistance may be used. Check with your local building

authority before installation to determine what other materials are acceptable in your area.

2. The hearth extension should be secured to the floor and must extend a minimum of 1" (25 mm) under

the unit (Figure 3a).

3. On a raised base or raised hearth, a "Z" shape piece of metal must be fabricated to join from under the

fireplace to the hearth extension. This piece of metal must cover the entire width of the fireplace.

This ‘Z’ shaped piece replaces the 1” extension under the unit described in the point #2 thereover

(figure 3b). Hearth extension must respect the same minimal dimensions as a fireplace installed

directly on the floor (figure 3a).

Figure 3b

Fireplace

Bande en ‘Z’

Figure 3a

Page 10: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

7

OUTSIDE AIR INSTALLATION FOR FIREPLACE AND AC CHIMNEY

During operation, the fireplace requires air for combustion and draws air out of the house. It may starve other fuel

burning appliances such as gas or oil furnaces. As well, exhaust fans and fan driven appliances may compete for air,

causing a negative pressure in the home and resulting in smoke entering the home from the fireplace. This situation

is aggravated in modern airtight houses. To overcome this potential problem, we recommend installing an

OUTSIDE AIR assembly and glass doors.

The fireplace's outside air control should be open when the fireplace is being used. The outside air control is located

behind the fireplace's lower louver. Pull this lever to open.

The OUTSIDE AIR assembly for fireplaces and air cooled chimneys is mandatory in some areas. Check with your

local building authority for the requirements in your area.

If the outside air assembly on the AC chimney is not installed, provide a supply of fresh air with an air intake in the

enclosure.

The outside air assembly must be installed according to the following guidelines: (see Figures 4 & 5)

1. The maximum length of insulated flexible duct 4" ID. (100 mm) is 20 ft (6.1 m). If a longer duct is required,

use a 6" ID. insulated (150 mm) flexible duct. The maximum length is 40 ft (12 m).

2. The duct and register may be installed above or below floor level.

3. The outside air register must not be installed more than 10 feet (3050mm) above the base of the appliance.

4. The outside air assembly must come from outside the house. It must not draw air from the attic, the basement,

or a garage.

5. Locate the outside register where it will be well away from automobile exhaust fumes, or other vents.

6. The outside air register should be installed where it is not likely to be blocked by snow or exposed to extreme

wind.

Page 11: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

8

Figure 4 Figure 5

TYPICAL INSTALLATIONS

Figure 6a Figure 6b

OUTSIDE AIR REGISTER

PLASTIC COVERED INSULATION

ALUMINUM TAPE

FLEXIBLE ALUMINUM DUCT

WALL

OPEN SIDE DOWN

PLASTIC COVERED INSULATION

OUTSIDE AIR CONNECTOR

FIREPLACE

ALUMINUM TAPE

FLEXIBLE ALUMINUM DUCT

2 " MIN. CLEARANCE

PLYWOOD OR DRYWALL

2" X 3" FRAME

CAP STORM COLLAR

ROOF SUPPORT

FLASHING

ATTIC RADIATION SHIELD

FIRESTOP

ASHT+ CHIMNEY

RADIATION RING

Page 12: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

9

Figure 7

AC MODEL (AIR COOLED INSULATED, GALVALUME CHIMNEY)

ACFA (F) (FLASHING)

ACST (ROOF SUPPORT)

ACRSA (ATTIC RADIATION SHIELD)

ACRS (RADIATION SHIELD)

AIR COOLED CHIMNEY STARTING PIECE

FIRE GRATE (STANDARD)

GLASS DOOR (OPTIONAL)

FIRE SCREEN (STANDARD)

COOLING AIR KIT FOR AIR COOLED CHIMNEY ACZI

COMBUSTION AIR KIT UZI (OPTIONAL)

Page 13: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

10

CHIMNEY INSTALLATION

GENERAL NOTES

1. The Security fireplaces are listed only with Security Chimneys International Ltd systems. Do not connect the

fireplace to a masonry chimney, chimney liner, or other brand of metal chimney.

2. The chimney models HT6103+ and HT6000+ of Oliver MacLeod, division of Security Chimneys International

Ltd are respectively equivalent to models ASHT+ and S-2100+.

3. In areas with continuous temperatures below 00 F (-18

0 C) the use of an exterior chimney increases the

likelihood of operating problems such as low draft, high rate of creosoting and poor start-up characteristics.

Exterior chimneys are also prone to down-drafting and flow reversal. Installations which are located low in the

house such as in a basement, in combination with outside chimneys, are especially prone to flow reversal. In

cold areas, air cooled chimneys should not be used in an exterior installation.

4. A chimney venting a fireplace shall not vent any other appliance.

5. The minimum system height, including the fireplace is the following:

Table 1

FIREPLACE MODEL SE36 / SB36 SB42

CHIMNEY MODEL ASHT+ / HT6103+, S-2100+ / HT6000+ or AC

VERTICAL INSTALLATION 4.57 m (15’) 4.57 m (15’)

ONE OFFSET 5.49 m (18’) 5.49 m (18’)

TWO OFFSETS 6.10 m (20’) 6.10 m (20’)

NOTE : A maximum of 2 offsets is allowed.

6. In altitude, add 18" (450 mm) to the chimney for every 2000 ft. (600 m) above sea level.

WARNING:

In cold areas, an air cooled chimney may generate large amounts of water due to condensation. This water will

accumulate on top of the fireplace and may cause corrosion. Security Chimneys International Ltd cannot be

held responsible for condensation and corrosion problems. In cold climates, Security Chimneys International

recommends the use of ASHT+ / HT6103+ or S-2100+ / HT6000+ chimneys.

7. All chimney installations must include at least

one support. The maximum length of chimney

that can be supported by the fireplace is 6 ft. (1.8

m) for S-2100+ / HT6000+, 10 ft. (3m) for ASHT+

/ HT6103+ or 26 ft. (8 m) for AC.

8. The chimney must extend at least 3' (915 mm)

above its point of contact with the roof and at least

2 feet (610 mm) higher than any wall, roof or

building within 10' (3 m) of it. (see Figure 8)

9. If the chimney extends higher than 5' (1500 mm)

above the roof, it must be secured using a roof

brace or guide wires.

10. A rain cap must be installed on top of the chimney.

Failure to install a rain cap may cause the fireplace

to corrode and operate inefficiently.

11. Cut and frame square holes in all floors and the

roof to provide 2" (50 mm) of clearance between

the chimney and any combustible material. Do not

fill this 2" (50 mm) space with any material. (See

Figure 9)

12. Portions of the chimney which may extend

through accessible spaces must be enclosed to

avoid contact or damage to the chimney.

Figure 8

10’

(3000mm)

2’ min.

(610mm) 3’ min.

(915mm)

Page 14: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

11

STRAIGHT INSTALLATION

Cut and frame the holes in the ceiling, floor and roof where the chimney will pass. Use a plumb bob to line up the

center of the holes. See Table 2 for the hole sizes and Table 3 for the roof hole sizes

Table 2

From below, install a firestop in each floor through

which the chimney passes. At the attic level, install an

attic radiation shield from above. (Figures 10a - l0b).

Note: In cold climate locations, we recommend the

installation of an insulated radiation shield (RSI) where

the chimney penetrates the house's thermal barrier,

instead of a firestop. See details on page 15 (Insulated

Radiation Shield).

Place the first chimney length on the fireplace (A

starting section should be the first chimney length used

with the AC chimney).

Lock it into place. Continue installing chimney lengths

until you reach the desired height.

Put the roof support in place (Refer to page 16).

Put the roof flashing in place (sec fig. 11a & 11b). Seal

the joint between the roof and the flashing with roofing

pitch. For sloping roofs, place the flashing under the

upper shingles and on top of the lower shingles.

Nail the flashing to the roof using roofing rails.

Place the storm collar over the chimney and the

flashing, and caulk this joint, using silicone caulking.

Tighten it with the bolt supplied. Install the chimney

cap.

CHIMNEY

SQUARE HOLE DIMENSIONS

36" 42"

ASHT+ / HT6103+ 340 mm (13 3/8") 365 mm (14 3/8")

S-2100+ / HT6000+ 380 mm (15") 406 mm (16")

AC 380 mm (15") 406 mm (16")

Figure 9

Figure 10a

Figure 10b

ATTIC RADIATION SHIELD

FIRESTOP

ASHT+ / S-2100+ / HT6103+ / HT6000+

ATTIC RADIATION SHIELD

AC RS

AC

Page 15: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

12

ROOF DOWN SLOPE HOLE SIZE

• CROSS SLOPE HOLE SIZE Fit the rain cap to the top of the chimney. Secure it tightly in place.

Figure11a Figure 11b

Table 3

SLOPE ASHT+ / HT6103+ S-2100+ / HT6000+ AC

7" 8" 7" 8" 7" 8"

* 13 3/8" (340 mm) 14 3/8" (365 mm) 15" (380 mm) 16" (406 mm) 15" (380 mm) 15" (380 mm)

2/12 4/12 6/12 8/12

10/12 12/12

13 5/8" (345 mm) 14 1/4" (360 mm) 15" (380 mm) 16 1/4" (413 mm) 17 1/2" (445 mm) 19" (483 mm)

14 5/8" (371 mm) 15 1/4" (387 mm) 16 1/8" (410 mm) 17 3/8" (441 mm) 18 3/4" (476 mm) 20 3/8" (518 mm)

15 3/8" (390 mm) 16 1/8" (410 mm) 16 7/8" (430 mm) 18 1/4" (465 mm) 19 5/8" (500 mm) 21 3/8" (545 mm)

16 1/4" (413 mm) 16 7/8" (429 mm) 17 7/8" (454 mm) 19 1/4" (489 mm) 20 7/8" (530 mm) 22 5/8" (575 mm)

15 3/8" (390 mm) 16 1/8" (410 mm) 16 7/8" (430 mm) 18 1/4" (465 mm) 19 5/8" (500 mm) 21 3/8" (545 mm)

15 3/8" (390 mm) 16 1/8" (410 mm) 16 7/8" (430 mm) 18 1/4" (465 mm) 19 5/8" (500 mm) 21 3/8" (545 mm)

CHIMNEY

COLLAR

SPACER

FLASHING

AIR-COOL CHIMNEY ROOF FLASHING INSTALLATION

Page 16: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

13

OFFSET INSTALLATION

The minimum chimney height (including fireplace) when using elbows is:

FIREPLACE MODEL SE36 / SB36 SB42

CHIMNEY MODEL ASHT+ / HT6103+, S-2100+ / HT6000+, AC ASHT+ / HT6103+, S-2100+ / HT6000+, AC

Vertical installation 15’ (4.57 m) 15’ (4.57 m)

2 Elbows 18’ (5.49 m) 18’ (5.49 m)

4 Elbows 20’ (6.10 m) 20’ (6.10 m)

Table 4

NOTE: A maximum of 2 offsets is allowed.

After arriving at the location requiring the elbow, proceed as follows:

1. Install the first elbow. Turn it in the required direction. For ASHT+ / HT6103+ and S-2100+ / HT6000+

chimneys, fasten it with the three (3) ½" (12 mm) metal screws provided. For AC, attach the elbow to the

surrounding framing using the straps already attached to the elbow.

2. Install the necessary lengths to achieve the required offset. Lock the chimney lengths together (for ASHT+ /

HT6103+ and S-2100+ / HT6000+ chimneys, secure them using three (3) ½" (12 mm) screws). If the offset

length is made of two (2) chimney lengths, use an offset support halfway up the offset. If penetrating a wall,

install a wall radiation shield.

3. Use another elbow to turn the chimney vertically. Again, secure the elbow using three (3) ½" (12 mm) metal

screws for ASHT+ / HT6103+ and S-2100+ / HT6000+. For AC, attach the elbows to the surrounding framing,

using the straps already attached to the elbow.

4. Use a plumb bob to line up the center of the hole. Cut a hole for the chimney in the cei1ing. Frame this hole

using 2" x 4" (50 x 100 mm) wood.

5. From below, install a radiation shield in this opening. (Upward for ASHT+ / HT6103+ and S-2100+ /

HT6000+. Downward for AC. See Figure 10).

Note: When using a support on ASHT+ / HT6103+ and S-2100+ / HT6000+, it may be necessary to cut

slots in the upper portion of the radiation shield so it will fit around the support brackets.

6. For ASHT+ / HT6103+ and S-2100+ / HT6000+ chimneys, a support must be used on the first 15' section.

7. Continue with the regular installation.

Note - With ASHT+ / HT6103+ or S-2100+ / HT6000+ chimneys: An 8" length of chimney should be used

before an elbow can be installed. If an 8" length of chimney cannot be used, the radiation ring on the fireplace

will have to be cut to allow room for the elbow.

Note - With AC chimneys: An ACSB starting section must be used before installing an elbow. For those

situations where an offset is needed at the beginning, the ACSBO, a starting section with a built-in 4" (100 mm)

offset, is available.

Note: - 45° insulated elbow listed to ULC Standard S- 610 only, not for use in US.A.

In U.S.A. use 15° and 30° elbows only.

Page 17: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

14

Table 5

CHIMNEY 7-8” ELBOW DEVIATION

& HEIGHT ONE LENGTH BETWEEN ELBOWS TWO LENGTHS BETWEEN ELBOWS

8” 12” 18” 24” 36” 48” 8” & 48” 12” & 48” 18” & 48” 24” & 48” 36” & 48” 48” & 48”

Secure TempASHT+

Nova TempHT6103+

15º DEVIATION

3 5/16" (84mm)

4 5/16" (110mm)

5 7/8" (149mm)

7 7/16" (189mm)

10 1/2" (267mm)

13 5/8" (346mm)

15 3/8" (391mm)

16 7/16" (418mm)

18" (457mm)

19 1/2" (495mm)

22 5/8" (575mm)

25 3/4" (654mm)

HEIGHT 15 11/16" (398mm)

19 9/16" (497mm)

25 3/8" (645mm)

31 3/16" (792mm)

42 3/4" (1086mm)

54 3/8" (1381mm)

60 15/16" (1548mm)

64 13/16" (1646mm)

70 9/16" (1792mm)

76 3/8" (1940mm)

87" (2210mm)

99 9/16" (2529mm)

30º DEVIATION

7 7/16" (189mm)

9 7/16" (240mm)

12 7/16" (316mm)

15 7/16" (392mm)

21 7/16" (545mm)

27 7/16" (697mm)

30 13/16" (783mm)

32 13/16" (833mm)

35 13/16" (910mm)

38 13/16" (986mm)

44 13/16" (1138mm)

50 13/16" (1291mm)

HEIGHT 20"

(508mm) 23 ½"

(597mm) 28 11/16" (729mm)

33 7/8" (860mm)

44 1/4" (1124mm)

54 11/16" (1389mm)

60 9/16" (1538mm)

64 " (1627mm)

69 1/4" (1759mm)

74 7/16" (1891mm)

84 13/16" (2154mm)

95 1/4" (2419mm)

45º DEVIATION

10 5/16" (262mm)

13 3/16" (335mm)

17 3/8" (441mm)

21 5/8" (549mm)

30 1/8" (765mm)

38 5/8" (981mm)

43 7/16" (113mm)

46 1/4" (1175mm)

50 1/2" (1283mm)

54 3/4" (1391mm)

63 1/4" (1607mm)

71 11/16" (1818mm)

HEIGHT 17 13/16" (452mm)

20 5/8" (524mm)

24 7/8" (632mm)

29 1/8" (740mm)

37 5/8" (956mm)

46 1/8" (1172mm)

50 15/16" (1294mm)

53 3/4" (1365mm)

58" (1473mm)

62 1/4" (1581mm)

70 3/4" (1797mm)

79 3/16" (2011mm)

CHIMNEY 7-8” ELBOW DEVIATION

& HEIGHT ONE LENGTH BETWEEN ELBOWS TWO LENGTHS BETWEEN ELBOWS

8” 12” 18” 24” 36” 48” 8” & 48” 12 & 48” 18 & 48” 2 4” & 48” 36” & 48” 48” & 48”

Secure TempS2100+

Nova TempHT6000+

15º DEVIATION 3 5/16"

(84mm) 4 5/16"

(110mm) 5 7/8"

(149mm) 7 7/16"

(189mm) 10 1/2"

(267mm) 13 5/8"

(346mm) 15 1/2"

(394mm) 16 1/2"

(419mm) 18 1/16" (459mm)

19 5/8" (498mm)

22 3/4" (578mm)

25 13/16" (656mm)

HEIGHT 16"

(406mm) 19 7/8"

(505mm) 25 11/16" (652mm)

31 1/2" (800mm)

43 1/16" (1094mm)

54 5/8" (1387mm)

61 7/16" (1561mm)

65 1/4" (1657mm)

71 1/16" (1805mm)

76 7/8" (1953mm)

88 1/2" (2248mm)

100 1/16" (2542mm)

30º DEVIATION 7 3/8"

(187mm) 9 3/8"

(238mm) 12 3/8"

(314mm) 15 3/8"

(391mm) 21 3/8"

(543mm) 27 3/8"

(695mm) 30 7/8"

(784mm) 32 7/8"

(835mm) 35 7/8"

(911mm) 38 7/8"

(987mm) 44 7/8"

(1140mm) 50 7/8"

(1292mm)

HEIGHT 20 11/16" (525mm)

24 3/16" (614mm)

29 3/8" (746mm)

34 9/16" (878mm)

44 15/16" (1141mm)

55 5/16" (1405mm)

61 3/8" (1559mm)

64 7/8" (1648mm)

70 1/16" (1780mm)

75 1/4" (1911mm)

35 5/8" (2175mm)

96" (2438mm)

CHIMNEY 7-8” ELBOW DEVIATION

& HEIGHT ONE LENGTH BETWEEN ELBOWS TWO LENGTHS BETWEEN ELBOWS

--- 12” 18” --- 36” 48” --- 12" & 48" 18" & 48" --- 36” & 48” 48” & 48”

AC 7-8"

15º

DEVIATION --- 4 13/16" (122mm)

6 1/8" (156mm)

11" (280mm)

14 1/8" (359mm)

16 7/8" (429mm)

18 7/16" (468mm)

23" (584mm)

26 3/16" (665mm)

HEIGHT --- 27 11/16" (703mm)

33 ½" (851mm)

50 7/8" (1292mm)

65 ½" (1588mm)

72 5/8" (1845mm)

78 7/16" (1992mm)

95 ¾" (2432mm)

107 3/8" (2727mm)

30º

DEVIATION --- 9 3/8" (238mm)

12 3/8" (314mm)

21 3/8" (543mm)

27 3/8" (695mm)

32 5/8" (829mm)

35 5/8" (905mm)

44 5/8" (1134mm)

50 5/8" (1286mm)

HEIGHT --- 25 ¾" (654mm)

31" (878mm)

46 ½" (1181mm)

57" (1448mm)

66" (1676mm)

71 ¼" (1810mm)

86 7/8" (2207mm)

97 ¼" (2470mm)

*** NOTE : With the AC chimney, a starting length o f 6” high must be used on top of the fireplace befo re installing an elbow ***

RISE

OFFSET

Page 18: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

15

Figure 12

Figure 13

AIR COOLED

BRACE

STRAPS

RADIATION SHIELD

STRAPS

SUPPORT

EXTERIOR INSTALLATION NOT RECOMMENDED FOR COLD CLIMATES

RAIN CAP STORM COLLAR

ROOF SUPPORT

FLASHING

WALL BAND

WALL RADIATION SHIELD

RADIATION RING

FRAME 2" X 4"

INSULATED WALL

Page 19: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

16

TYPICAL CHASE INSTALLATION

Figure 14

FLASHING

NON COMBUSTIBLE CHASE TOP

CEILING/FLOOR

SEPARATION

- Must have same fire rating as adjacent ceiling.

- Must be insulated same as adjacent ceiling.

- Local code regulation for ceiling must be applied to

the ceiling floor separation.

i.e. Firestop etc..

NOTE:

- Follow fireplace installation instruction for chase installation.

- Chase wall and floor must be insulated in the same manner as the rest of the

building below the attic.

OFFSET SUPPORT

ROOF SUPPORT

FINISHED WALL

Page 20: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

17

ANGLED WALL RADIATION SHIELD (RSM 30°, RSM 45°) OR

INSULATED RADIATION SHIELD (RSMI 30°, RSMI 45°) (See Figure #15)

When traversing a combustible wall with the chimney at a 30º or 45º angle, an angled firestop and / or wall radiation

shield must be installed. Only one is required.

NOTE: 45º ANGLE FOR CANADA ONLY.

In cold climate locations (such as Canada and Northern USA), we recommend that you use the insulated wall

radiation shield since it will maintain the home's thermal barrier.

RSM 30°, 45° and RSMI 30°, 45°

CHIMNEY ANGLE HOLE SIZE

7" ASHT+ (Canada only) 8" ASHT+ (Canada only)

30° 45° 30° 45°

13 3/8 x 33 ¼ (340 x 845 mm) 13 3/8 x 23 ¼ (340 x 591 mm) 14 3/8 x 36 ½ (365 x 927 mm) 14 3/8 x 24 ¾ (356 x 629 mm)

7" S-2100+ (Canada only) 8" S-2100+ (Canada only)

30° 45° 30° 45°

15 x 38 ¼ (380 x 972 mm) 15 x 25 7/8 (380 x 657 mm) 16 x 40 (406 x1016 mm) 16 x 27 ¼ (406 x 692 mm)

7" AC 8" AC

30° 30°

15 x 38 ¼ (380 x 972 mm) 15 x 38 ¼ (380 x 972 mm)

Table 6

Figure 15

DRYWALL

INSULATED WALL

ANGLE WALL RADIATION SHIELD (INSULATED)

Page 21: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

18

INSULATED RADIATION SHIELD (RSI)

In cold climate locations, an insulated firestop may be

installed at the ceiling level. This will minimize heat loss

around the chimney at this location.

The insulated radiation shield should be installed from

below and the attic radiation shield installed from above.

UNIVERSAL ROOF SUPPORT INSTALLATION

This support has three possible uses:

1. For ASHT+ / HT6103+ and S-2100+ / H16000+, it must be used on a roof to support the chimney.

2. It may be used on a floor, ceiling or roof above an offset to support the chimney above the offset.

3. It may be used on a floor, ceiling or roof as a supplementary support when the chimney height exceeds 15 ft.

Table 7 gives maximum height of supported chimney.

Note: For the AC chimney, a support section must be used every 40' instead of the roof support.

FOR INSTALLATION INSTRUCTIONS REFER TO THE MANUAL PROVIDED WITH THE ROOF

SUPPORT.

UNIVERSAL OFFSET SUPPORT INSTALLATION

This support is used to support a chimney above an offset. When the chimney offset is used to traverse a wall, this

support may be used on the wall to support the chimney. The maximum height is given in Table 7.

CHIMNEY MAXIMUM HEIGHT OF CHIMNEY SUPPORTED

UNIVERSAL OFFSET SUPPORT UNIVERSAL ROOF SUPPORT

7" ASHT+ / HT6I03+

8" ASHT+ / HT6103+

24’ (7.30 m)

22’ (6.70 m)

29’ (8.84 m)

29’ (8.84 m)

7" S-2100+ / HT6000+

8" S-2100+ / HT6000+

12’ (3.65 m )

10’ (3.10 m )

20’ (6.10 m) 20’ (6.10 m)

7" AC

8" AC

40’ (12.19 m) 40’ (12.19 m)

50’ (15.20 m) 50’ (15.20 m)

Table 7

FOR INSTALLATION INSTRUCTIONS, REFER TO THE MANUAL PROVIDED WITH THE OFFSFT

SUPPORT.

ASHT+ / S-2100+ - HT6103+ / HT6000+

ATTIC RADIATION

SHIELD

RSI

Figure 16

Page 22: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

19

CHIMNEY CHASE AND MULTIPLE TERMINATIONS

For the purpose of this manual a chimney chase is considered a part of the chimney system rather than part of the

building. The termination must be placed 18" (460 mm) above the chase.

For installations where more than one chimney is located in the same chase or within the same general area, we

suggest that their terminations be separated by at least 16" (410 mm) horizontally and 18" (460 mm) vertically. This

separation is to prevent smoke migrating from one chimney to another. (See Figure 17).

Figure 17

18" (460mm) 18" (460mm)

18" (460mm)

(410 mm) 16"

(410 mm) 16"

EXTERIOR JACKETING

Page 23: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

20

PARTS AND COMPONENTS AC Chimney Part No.

LENGTHS 7" DIA. 8" DIA.

12" length AC 7L12 AC 8L12

18" length AC 7L18 AC 8L18

36" length AC 7L36 AC 8L36

48" length AC 7L48 AC 8L48

15º elbow AC7E15 AC 8E15

30º elbow AC 7E30 AC 8E30

Rain Cap AC 7CPR AC 8CPR

SUPPORTS

Offset support XSO XSO

Support section AC 7SL AC 8SL

Roof support XST XST

Starting section AC 7SB AC 8SB

Starting section with 4" (100 mm) offset AC 7SBO AC 8SBO

FIRESTOPS

Radiation shield ACRS ACRS

Attic radiation shield AC RSA AC RSA

Wall radiation shield 30° AC RSM30 ACRSM30

Insulated wall radiation shield 30° AC RSMI30 AC RSMI30

Roof brace XBS2 XBS2

Wall band XBM XBM

Outside air kit ACZI

(Flex, insulation, outside register and coupling)

Flat roof flashing ACF ACF

Adjustable roof flashing 1/12-7/12 (5° to 30°) AC FA AC FA

8/12 - 12/12 (30°to 45°) AC FB AC FB

12/12-21/12 (54° to 60°) AC FBB AC FBB

Storm collar AC FC AC FC

Page 24: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

21

OPTIONAL PARTS

Outside air kit - fireplace UZI

(Flex, insulation and outside register)

Fireplace coupling - for outside register UZIDB or UZIDR

Blower (includes two blowers with magnets & thermostatic control) UZY5

Set of brass doors 36" SRDB36

Set of brass doors 42" SRDB42

Set of black doors 36" SRDN36

Set of black doors 42" SRDN42

Builder doors 36" SDB36

Builder doors 42" SDB42

Brass louvers 36" TLB36

Brass louvers 42" TLB42

COMMON REPLACEMENT PARTS 36” Smoke deflector PR-DF585A

Louver PR-SR15P

Louver pivot PR-PIVOT

Damper with rod PR-SBDAMPER

Facing :

Side PR-SB102

Top PR-SB138

Bottom PR-SB131

Middle PR-SR2178

REPLACEMENT PARTS SE36

Refractory - side PR-SR2135

Refractory - back PR-SR2134

Refractory - bottom PR-SR124

Refractory - front PR-SR114

Fire grate PR-SR2129

Rigid firescreen - right PR-SR2141D

Rigid firescreen - left PR-SR2141G

Folding door - right PR-SR2162D

Folding door - left PR-SR2162G

Door brass finish trim SR2167

Door guide PR-SR2146

Hinges PR-SR2170

Glass PR-SR2158

Handle support PR-SR2165

REPLACEMENT PARTS SB36

Refractory - side PR-SB141

Refractory - back PR-SB142

Refractory - bottom PR-SB143

Fire grate PR-PB01

Firescreen kit U36ZP

Firescreen PR-PE01

Firescreen rod PR-TPE01

Firescreen screws PR-SACSE

Wooden handle PR-C7

Hinges / hardware PR-SBDQ

Glass panel PR-VC03

REPLACEMENT PARTS SB42

Refractory - side PR-SB141

Refractory - back PR-SB127

Refractory - bottom PR-SB128

Fire grate PR-PB01

Firescreen U42ZP

Smoke deflector PR-DF585B

Page 25: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

22

FIREPLACE MODEL SE36

INSTALLATION INSTRUCTIONS FOR THE DOOR HANDLE

2 1/4"

Page 26: FIREPLACE MODELS SB36 - SE36 SB36 SB42 Installation and ... Info/Security... · 5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to

23

DIMENSIONS

D C

A B

A B

SB36 & SE36 Inches 40 5/8 43 Metric (cm) 103 109

SB42 Inches 46 5/8 43 Metric (cm) 118 109

A B C D E F SB36 & SE36

Inches 40 3/8 69 1/2 34 3/4 49 1/8 40 3/8 22 3/4 Metric (cm) 102 177 88 125 102 58

SB42 Inches 46 3/8 75 1/2 37 3/4 53 3/8 46 3/8 22 3/4 Metric (cm) 118 192 96 136 118 58

Dimensions include 1/4" tolerance

A B SB36 SE36

Inches 40 1/8 36 Metric (cm) 102 91

SB42 Inches 46 1/8 42 Metric (cm) 117 106

E

F

B

A

12 1/4"

20 1/2"

B

42 1/2"

HEADER

22 1/2"