FIREPLACE MODELS
SB36 - SE36
SB42
Installation and Operating
Instructions
This installation manual will help
you to obtain a safe, efficient,
dependable installation for your fireplace
and chimney system. Please read and
understand these installation instructions
before beginning your installation.
Warning: Do not attempt to modify or
alter the construction of the fireplace or
its components. Any modification or
alteration of construction may void the
warranty, listings and approvals of this
system. In such a case, Security
Chimneys International will not be
responsible for damages.
SAVE THESE INSTRUCTIONS
FOR FUTURE REFERENCE.
2125 Monterey St., Laval, Quebec, Canada H7L 3T6 Tel.: (450) 973-9999
SE36
SB36
SB42
• Hot! Do not touch! The glass and surfaces of this appliance
will be hot during operation and
will retain heat for a while after
shutting off the appliance.
Severe burn may result.
• Carefully supervise children in the same room as appliance.
• If small children are present in the home, it
is recommended that this appliance be used
with a fire screen kit.
Listed to standards :
UL-127, ULC-S610
This appliance has been
certified as being exempt from
EPA 40 CFR 60 standard
i
CERTIFICATION
LABEL
iii
TABLE OF CONTENTS
Page
Safety Rules .............................................................................................................................. 1
Fireplace Maintenance Creosote ............................................................................................................................... 2
Chimney Maintenance ......................................................................................................... 2
Chimney Fires ..................................................................................................................... 2
Fireplace Installation
Recommendations ............................................................................................................... 3
Tools and Building Supplies ............................................................................................... 4
Fireplace Installation Procedure .......................................................................................... 4
Locating the Fireplace ......................................................................................................... 4
Adjacent Walls .................................................................................................................... 4
Enclosure ............................................................................................................................. 5
Facing and Mantel ............................................................................................................... 5
Hearth Extension Requirements .......................................................................................... 6
Outside Air Installation ....................................................................................................... 7
Chimney Installation
General Notes .................................................................................................................... 10
Straight Installation ........................................................................................................... 11
Offset Installation ................................................................................................................ 13
Angled Wall Radiation Shield (Insulated Radiation Shield) .............................................. 17
Universal Roof Support Installation .................................................................................... 18
Universal Offset Support Installation .................................................................................. 18
Chimney Chase and Multiple Terminations ........................................................................ 19
Parts and Components ............................................................................................................ 20
Door Handle Installation (Model SE36) ................................................................................ 22
Fireplace Dimensions .............................................................................................................. 23
1
SAFETY RULES FOR OPERATING YOUR
FIREPLACE MODEL SB36, SE36, SB42
� When in operation, a fireplace will draw air out of the house. If an outside air kit for the
fireplace is not installed, it may be necessary to leave a window or door open a little while using
the fireplace.
WARNING: When doors are installed on the fireplace, it should be operated with the doors fully
opened or fully closed. If the doors are left partly open, smoke may be drawn into
the room.
� Only use Security Chimneys International Ltd glass doors.
� Always keep the firescreen or the door closed and the damper opened when using the fireplace.
Keep the damper closed when the fireplace is not in use.
� When cleaning your fireplace, ashes should be placed in a metal container with a tight-fitting lid.
The closed container of ashes should be placed on a non-combustible floor or on the ground, well
away from all combustible materials, pending final disposal. If the ashes are disposed of by
burial in soil or otherwise locally dispersed, they should be retained in the closed container until
all cinders have thoroughly cooled.
CAUTION: Never leave children unattended when there is a fire burning in the fireplace.
CAUTION: This fireplace has been tested with Security Chimneys International Ltd wood
grates. They must always be used.
CAUTION: Keep combustible material at least 48" away from the front of the fireplace
opening.
CAUTION: Never use gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter fluid or
similar liquid to start or "freshen up" a fire in this fireplace. Keep all such liquid
well away from the fireplace at all times.
WARNING: This fireplace has provisions for the installation of a gas pipe and is intended only
for connection to a decorative gas appliance incorporating an automatic shutoff
device and complying with ANSI Z21.60-M96/CGA 2.26-M96, Standard for
Decorative Gas Appliances for Installation in Solid-Fuel Burning Fireplaces.
WARNING: THIS FIREPLACE HAS NOT BEEN TESTED WITH AN UNVENTED GAS LOG
SET. TO REDUCE RISK OF FIRE OR INJURY, DO NOT INSTALL AN
UNVENTED GAS LOG SET INTO THIS FIREPLACE.
CAUTION: DO NOT USE CHEMICAL GLASS CLEANER ON PAINTED SURFACES AS IT
MAY CAUSE PAINT TO PEEL.
2
FIREPLACE MAINTENANCE
CREOSOTE
When wood is burned slowly, it produces tar and other organic vapors which combine with expelled moisture to
form a black deposit called creosote. The creosote vapors condense in the relatively cool chimney flue of a
slow-burning fire. As a result, creosote residue accumulates on the flue lining. When ignited, this creosote makes
an extremely hot fire. If the creosote accumulation is large, a creosote fire in the chimney can damage the chimney
and overheat the surrounding wood framing. Creosote formation in a chimney can be minimized by making small
hot fires rather than slow-burning, smouldering fires.
CHIMNEY MAINTENANCE
Regular chimney inspection and maintenance combined with proper operation will help prevent chimney fires.
Keep your chimney clean. Do not allow more than 1/16" (1.6 mm) build up of creosote in your chimney. The
amount of creosote will depend on variables such as frequency of use and type of fire. We recommend that you:
1. Initially inspect the chimney system weekly. From this you will learn how often it will be necessary to clean
your chimney.
2. Have your chimney cleaned by a qualified chimney sweep. If you wish to clean it yourself, we recommend
using a stiff plastic or non-metallic brush. If a metal brush is used, its' size should be slightly smaller than the
flue to avoid damaging the chimney. Do not use a brush that could scratch the stainless steel interior of the
chimney.
3. Do not expect chemical cleaners to keep your chimney clean. The rain cap can be removed for inspection
and/or cleaning of the chimney.
CHIMNEY FIRES
If you are having a chimney fire, follow these steps:
1. Block the fireplace opening with a non-combustible material such as asbestos or a steel sheet. If you have glass
doors, close them.
2. Alert your family of the possible danger.
3. If you require assistance, alert your fire department.
4. If possible, use a dry chemical fire extinguisher, baking soda or sand to control the fire. Do not use water as it
may cause a dangerous steam explosion.
5. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check outside to ensure that
sparks and hot embers coming out of the chimney are not igniting the roof.
6. Do not use the fireplace again until your chimney and fireplace have been inspected by a qualified chimney
sweep or fire department inspector.
3
FIREPLACE INSTALLATION
RECOMMENDATIONS TO THE INSTALLER
1. Before starting your fireplace installation, read these safety tips and installation instructions carefully to be sure
you understand them completely. Failure to follow them could cause a fireplace malfunction resulting in
serious bodily injury and / or property damage.
2. Always check your local building codes. The installation must comply with their regulations.
3. These fireplaces can use an ASHT+ / HT6103+, S-2100+ / HT6000+ or AC chimney system of the inside
diameter recommended by Security Chimneys International Ltd (SE36 and SB36: 7" inside diameter, SB42: 8"
inside diameter)
4. To maintain top efficiency and to prevent build-up of soot and creosote, inspect and clean the chimney
periodically during the heating season.
5. Ensure an adequate supply of combustion air to prevent possible hazards due to poor combustion and to avoid
affecting other fuel burning appliances.
6. Your Security fireplace has been tested and listed to UL and ULC standards, to be installed in accordance with
this brochure by Warnock Hershey International, Inc.
7. These instructions are written to give you an outline for a fast, safe installation and trouble-free operation.
8. Failure to use parts manufactured by Security Fireplace or variations in techniques and construction materials
described in this installation manual may create a serious fire hazard; it may void the Security Fireplace
warranty and will void the WHI listing.
9. The Security fireplace features optional glass doors, outside combustion air kit, blowers and decorative trims
and panels.
10. When selecting the location, the chimney outlet position and the direction of the wind are important factor affecting the chimney performance. To allow a maximum draft and to reduce wind turbulence, the chimney
must:
• Penetrate the highest part of the roof.
• Be installed as far as possible of roof offsets, trees or any other obstructions that may cause wind
turbulence and back drafts in the chimney.
• The least amount of offsets (elbows) possible.
4
TOOLS AND BUILDING SUPPLIES NORMALLY REQUIRED
Tools should include: If gas pipe is used: Building supplies:
Phillips screwdriver Pipe wrench Framing materials
Slot style screwdriver Pipe cutter Wall finishing materials
Hammer Pipe threader Caulking materials
Saw and/or Sabersaw Pipe joint compound (non-combustible)
Level Pipe key valve Fireplace front
Measuring Tape (overlay material)
Plumb line Hearth extension
Electric drill and bits (non-combustible)
Pliers
Square
CAUTION
The most important areas of concern dealing with the installation of factory built fireplaces are clearances to
combustible materials, secure assembly of component parts, the height of the chimney system, the proper use of
accessory equipment and the techniques employed in using finishing materials applied to fireplace surrounds, hearth
extensions and wall coverings. Each of these topics will be covered in great detail throughout this manual.
PLEASE GIVE EACH OF THESE INSTRUCTIONS SPECIAL ATTENTION AS YOU PROGRESS WITH
YOUR INSTALLATION.
FIREPLACE INSTALLATION PROCEDURE
1. Move the fireplace into desired position.
2. Install the outside air assembly (if required).
3. Install the hearth extension. Make sure the gap between the fireplace and the hearth extension is sealed.
4. If using an AC chimney, remove the radiation ring on top of the fireplace. (See Figure 6).
LOCATING THE FIREPLACE
Do not place the fireplace on carpeting, vinyl or other
soft surface floor covering. It may however, be
directly placed on flat wood, plywood, particle board
or other hard surface materials.
ADJACENT WALLS
A wall perpendicular to and in front of the fireplace
front facing must be at least 18" (460 mm) from the
fireplace opening. A wall at 45° to the front facing
and starting at the fireplace's outer edge is permitted.
Projections within this area are permitted.
(See Figure 1).
WALL FIREPLACE
45o
OPENING
18" (460 mm)
Figure 1
5
ENCLOSURE
1. WARNING: Do not place loose insulation or any other material in the space around the fireplace or the
chimney. Insulation placed on or around the fireplace or chimney may cause adjacent wood to overheat and
catch on fire. (Security Chimneys International recommends that you install the fireplace against a finished
wall).
2. IN CANADA, the fireplace must be installed against a finished wall. It must not be installed against a vapour
barrier or exposed insulation
3. The fireplace is zero clearance. Combustible material like wood, plywood, particle board or drywall can be in
direct contact with the fireplace wall or the fireplace top spacer. Two inch (50 mm) clearance to combustibles
must be kept around the chimney.
4. Do not block the fireplace's hot air vents or air inlets as this will cause the fireplace to overheat.
FACING AND MANTEL
The fireplace should be framed using 2" x 3"
(50 mm x 75 mm) or heavier lumber. Figures 6 and 7
show the general framing layout.
Combustible materials must be installed flush with the
fireplace facing. It may not project out in front of the
fireplace. (See Figure 2)
Non-combustible materials such as brick, stone or
ceramic tile may project in front of and / or on the
fireplace facing.
WARNING: The header should rest on top of the metal spacers (See Figure 2). Do not alter the spacers or notch the header to fit
around them. Do not block the air inlet or outlet as this will cause the fireplace to overheat. A wood mantle, if
installed, must be at least 48" (1.2 m) above the base of the fireplace. (See Figure 3a)
COMBUSTIBLE MATERIAL
JOIST 2" X 3" (50MM X 75MM)
SPACER WRONG WAY
FIREPLACE
Figure 2
6
HEARTH EXTENSION REQUIREMENTS
A non-combustible hearth extension must be built in front of the fireplace and extend out on both sides.
Hearth extensions must be constructed according to the following guidelines:
1. A layer of sheet metal 0.018" (0.45 mm) thick or 3/8" (9 mm) thick millboard or any other material
(tiles, marble or granite) with equivalent heat resistance may be used. Check with your local building
authority before installation to determine what other materials are acceptable in your area.
2. The hearth extension should be secured to the floor and must extend a minimum of 1" (25 mm) under
the unit (Figure 3a).
3. On a raised base or raised hearth, a "Z" shape piece of metal must be fabricated to join from under the
fireplace to the hearth extension. This piece of metal must cover the entire width of the fireplace.
This ‘Z’ shaped piece replaces the 1” extension under the unit described in the point #2 thereover
(figure 3b). Hearth extension must respect the same minimal dimensions as a fireplace installed
directly on the floor (figure 3a).
Figure 3b
Fireplace
Bande en ‘Z’
Figure 3a
7
OUTSIDE AIR INSTALLATION FOR FIREPLACE AND AC CHIMNEY
During operation, the fireplace requires air for combustion and draws air out of the house. It may starve other fuel
burning appliances such as gas or oil furnaces. As well, exhaust fans and fan driven appliances may compete for air,
causing a negative pressure in the home and resulting in smoke entering the home from the fireplace. This situation
is aggravated in modern airtight houses. To overcome this potential problem, we recommend installing an
OUTSIDE AIR assembly and glass doors.
The fireplace's outside air control should be open when the fireplace is being used. The outside air control is located
behind the fireplace's lower louver. Pull this lever to open.
The OUTSIDE AIR assembly for fireplaces and air cooled chimneys is mandatory in some areas. Check with your
local building authority for the requirements in your area.
If the outside air assembly on the AC chimney is not installed, provide a supply of fresh air with an air intake in the
enclosure.
The outside air assembly must be installed according to the following guidelines: (see Figures 4 & 5)
1. The maximum length of insulated flexible duct 4" ID. (100 mm) is 20 ft (6.1 m). If a longer duct is required,
use a 6" ID. insulated (150 mm) flexible duct. The maximum length is 40 ft (12 m).
2. The duct and register may be installed above or below floor level.
3. The outside air register must not be installed more than 10 feet (3050mm) above the base of the appliance.
4. The outside air assembly must come from outside the house. It must not draw air from the attic, the basement,
or a garage.
5. Locate the outside register where it will be well away from automobile exhaust fumes, or other vents.
6. The outside air register should be installed where it is not likely to be blocked by snow or exposed to extreme
wind.
8
Figure 4 Figure 5
TYPICAL INSTALLATIONS
Figure 6a Figure 6b
OUTSIDE AIR REGISTER
PLASTIC COVERED INSULATION
ALUMINUM TAPE
FLEXIBLE ALUMINUM DUCT
WALL
OPEN SIDE DOWN
PLASTIC COVERED INSULATION
OUTSIDE AIR CONNECTOR
FIREPLACE
ALUMINUM TAPE
FLEXIBLE ALUMINUM DUCT
2 " MIN. CLEARANCE
PLYWOOD OR DRYWALL
2" X 3" FRAME
CAP STORM COLLAR
ROOF SUPPORT
FLASHING
ATTIC RADIATION SHIELD
FIRESTOP
ASHT+ CHIMNEY
RADIATION RING
9
Figure 7
AC MODEL (AIR COOLED INSULATED, GALVALUME CHIMNEY)
ACFA (F) (FLASHING)
ACST (ROOF SUPPORT)
ACRSA (ATTIC RADIATION SHIELD)
ACRS (RADIATION SHIELD)
AIR COOLED CHIMNEY STARTING PIECE
FIRE GRATE (STANDARD)
GLASS DOOR (OPTIONAL)
FIRE SCREEN (STANDARD)
COOLING AIR KIT FOR AIR COOLED CHIMNEY ACZI
COMBUSTION AIR KIT UZI (OPTIONAL)
10
CHIMNEY INSTALLATION
GENERAL NOTES
1. The Security fireplaces are listed only with Security Chimneys International Ltd systems. Do not connect the
fireplace to a masonry chimney, chimney liner, or other brand of metal chimney.
2. The chimney models HT6103+ and HT6000+ of Oliver MacLeod, division of Security Chimneys International
Ltd are respectively equivalent to models ASHT+ and S-2100+.
3. In areas with continuous temperatures below 00 F (-18
0 C) the use of an exterior chimney increases the
likelihood of operating problems such as low draft, high rate of creosoting and poor start-up characteristics.
Exterior chimneys are also prone to down-drafting and flow reversal. Installations which are located low in the
house such as in a basement, in combination with outside chimneys, are especially prone to flow reversal. In
cold areas, air cooled chimneys should not be used in an exterior installation.
4. A chimney venting a fireplace shall not vent any other appliance.
5. The minimum system height, including the fireplace is the following:
Table 1
FIREPLACE MODEL SE36 / SB36 SB42
CHIMNEY MODEL ASHT+ / HT6103+, S-2100+ / HT6000+ or AC
VERTICAL INSTALLATION 4.57 m (15’) 4.57 m (15’)
ONE OFFSET 5.49 m (18’) 5.49 m (18’)
TWO OFFSETS 6.10 m (20’) 6.10 m (20’)
NOTE : A maximum of 2 offsets is allowed.
6. In altitude, add 18" (450 mm) to the chimney for every 2000 ft. (600 m) above sea level.
WARNING:
In cold areas, an air cooled chimney may generate large amounts of water due to condensation. This water will
accumulate on top of the fireplace and may cause corrosion. Security Chimneys International Ltd cannot be
held responsible for condensation and corrosion problems. In cold climates, Security Chimneys International
recommends the use of ASHT+ / HT6103+ or S-2100+ / HT6000+ chimneys.
7. All chimney installations must include at least
one support. The maximum length of chimney
that can be supported by the fireplace is 6 ft. (1.8
m) for S-2100+ / HT6000+, 10 ft. (3m) for ASHT+
/ HT6103+ or 26 ft. (8 m) for AC.
8. The chimney must extend at least 3' (915 mm)
above its point of contact with the roof and at least
2 feet (610 mm) higher than any wall, roof or
building within 10' (3 m) of it. (see Figure 8)
9. If the chimney extends higher than 5' (1500 mm)
above the roof, it must be secured using a roof
brace or guide wires.
10. A rain cap must be installed on top of the chimney.
Failure to install a rain cap may cause the fireplace
to corrode and operate inefficiently.
11. Cut and frame square holes in all floors and the
roof to provide 2" (50 mm) of clearance between
the chimney and any combustible material. Do not
fill this 2" (50 mm) space with any material. (See
Figure 9)
12. Portions of the chimney which may extend
through accessible spaces must be enclosed to
avoid contact or damage to the chimney.
Figure 8
10’
(3000mm)
2’ min.
(610mm) 3’ min.
(915mm)
11
STRAIGHT INSTALLATION
Cut and frame the holes in the ceiling, floor and roof where the chimney will pass. Use a plumb bob to line up the
center of the holes. See Table 2 for the hole sizes and Table 3 for the roof hole sizes
Table 2
From below, install a firestop in each floor through
which the chimney passes. At the attic level, install an
attic radiation shield from above. (Figures 10a - l0b).
Note: In cold climate locations, we recommend the
installation of an insulated radiation shield (RSI) where
the chimney penetrates the house's thermal barrier,
instead of a firestop. See details on page 15 (Insulated
Radiation Shield).
Place the first chimney length on the fireplace (A
starting section should be the first chimney length used
with the AC chimney).
Lock it into place. Continue installing chimney lengths
until you reach the desired height.
Put the roof support in place (Refer to page 16).
Put the roof flashing in place (sec fig. 11a & 11b). Seal
the joint between the roof and the flashing with roofing
pitch. For sloping roofs, place the flashing under the
upper shingles and on top of the lower shingles.
Nail the flashing to the roof using roofing rails.
Place the storm collar over the chimney and the
flashing, and caulk this joint, using silicone caulking.
Tighten it with the bolt supplied. Install the chimney
cap.
CHIMNEY
SQUARE HOLE DIMENSIONS
36" 42"
ASHT+ / HT6103+ 340 mm (13 3/8") 365 mm (14 3/8")
S-2100+ / HT6000+ 380 mm (15") 406 mm (16")
AC 380 mm (15") 406 mm (16")
Figure 9
Figure 10a
Figure 10b
ATTIC RADIATION SHIELD
FIRESTOP
ASHT+ / S-2100+ / HT6103+ / HT6000+
ATTIC RADIATION SHIELD
AC RS
AC
12
ROOF DOWN SLOPE HOLE SIZE
• CROSS SLOPE HOLE SIZE Fit the rain cap to the top of the chimney. Secure it tightly in place.
Figure11a Figure 11b
Table 3
SLOPE ASHT+ / HT6103+ S-2100+ / HT6000+ AC
7" 8" 7" 8" 7" 8"
* 13 3/8" (340 mm) 14 3/8" (365 mm) 15" (380 mm) 16" (406 mm) 15" (380 mm) 15" (380 mm)
2/12 4/12 6/12 8/12
10/12 12/12
13 5/8" (345 mm) 14 1/4" (360 mm) 15" (380 mm) 16 1/4" (413 mm) 17 1/2" (445 mm) 19" (483 mm)
14 5/8" (371 mm) 15 1/4" (387 mm) 16 1/8" (410 mm) 17 3/8" (441 mm) 18 3/4" (476 mm) 20 3/8" (518 mm)
15 3/8" (390 mm) 16 1/8" (410 mm) 16 7/8" (430 mm) 18 1/4" (465 mm) 19 5/8" (500 mm) 21 3/8" (545 mm)
16 1/4" (413 mm) 16 7/8" (429 mm) 17 7/8" (454 mm) 19 1/4" (489 mm) 20 7/8" (530 mm) 22 5/8" (575 mm)
15 3/8" (390 mm) 16 1/8" (410 mm) 16 7/8" (430 mm) 18 1/4" (465 mm) 19 5/8" (500 mm) 21 3/8" (545 mm)
15 3/8" (390 mm) 16 1/8" (410 mm) 16 7/8" (430 mm) 18 1/4" (465 mm) 19 5/8" (500 mm) 21 3/8" (545 mm)
CHIMNEY
COLLAR
SPACER
FLASHING
AIR-COOL CHIMNEY ROOF FLASHING INSTALLATION
13
OFFSET INSTALLATION
The minimum chimney height (including fireplace) when using elbows is:
FIREPLACE MODEL SE36 / SB36 SB42
CHIMNEY MODEL ASHT+ / HT6103+, S-2100+ / HT6000+, AC ASHT+ / HT6103+, S-2100+ / HT6000+, AC
Vertical installation 15’ (4.57 m) 15’ (4.57 m)
2 Elbows 18’ (5.49 m) 18’ (5.49 m)
4 Elbows 20’ (6.10 m) 20’ (6.10 m)
Table 4
NOTE: A maximum of 2 offsets is allowed.
After arriving at the location requiring the elbow, proceed as follows:
1. Install the first elbow. Turn it in the required direction. For ASHT+ / HT6103+ and S-2100+ / HT6000+
chimneys, fasten it with the three (3) ½" (12 mm) metal screws provided. For AC, attach the elbow to the
surrounding framing using the straps already attached to the elbow.
2. Install the necessary lengths to achieve the required offset. Lock the chimney lengths together (for ASHT+ /
HT6103+ and S-2100+ / HT6000+ chimneys, secure them using three (3) ½" (12 mm) screws). If the offset
length is made of two (2) chimney lengths, use an offset support halfway up the offset. If penetrating a wall,
install a wall radiation shield.
3. Use another elbow to turn the chimney vertically. Again, secure the elbow using three (3) ½" (12 mm) metal
screws for ASHT+ / HT6103+ and S-2100+ / HT6000+. For AC, attach the elbows to the surrounding framing,
using the straps already attached to the elbow.
4. Use a plumb bob to line up the center of the hole. Cut a hole for the chimney in the cei1ing. Frame this hole
using 2" x 4" (50 x 100 mm) wood.
5. From below, install a radiation shield in this opening. (Upward for ASHT+ / HT6103+ and S-2100+ /
HT6000+. Downward for AC. See Figure 10).
Note: When using a support on ASHT+ / HT6103+ and S-2100+ / HT6000+, it may be necessary to cut
slots in the upper portion of the radiation shield so it will fit around the support brackets.
6. For ASHT+ / HT6103+ and S-2100+ / HT6000+ chimneys, a support must be used on the first 15' section.
7. Continue with the regular installation.
Note - With ASHT+ / HT6103+ or S-2100+ / HT6000+ chimneys: An 8" length of chimney should be used
before an elbow can be installed. If an 8" length of chimney cannot be used, the radiation ring on the fireplace
will have to be cut to allow room for the elbow.
Note - With AC chimneys: An ACSB starting section must be used before installing an elbow. For those
situations where an offset is needed at the beginning, the ACSBO, a starting section with a built-in 4" (100 mm)
offset, is available.
Note: - 45° insulated elbow listed to ULC Standard S- 610 only, not for use in US.A.
In U.S.A. use 15° and 30° elbows only.
14
Table 5
CHIMNEY 7-8” ELBOW DEVIATION
& HEIGHT ONE LENGTH BETWEEN ELBOWS TWO LENGTHS BETWEEN ELBOWS
8” 12” 18” 24” 36” 48” 8” & 48” 12” & 48” 18” & 48” 24” & 48” 36” & 48” 48” & 48”
Secure TempASHT+
Nova TempHT6103+
15º DEVIATION
3 5/16" (84mm)
4 5/16" (110mm)
5 7/8" (149mm)
7 7/16" (189mm)
10 1/2" (267mm)
13 5/8" (346mm)
15 3/8" (391mm)
16 7/16" (418mm)
18" (457mm)
19 1/2" (495mm)
22 5/8" (575mm)
25 3/4" (654mm)
HEIGHT 15 11/16" (398mm)
19 9/16" (497mm)
25 3/8" (645mm)
31 3/16" (792mm)
42 3/4" (1086mm)
54 3/8" (1381mm)
60 15/16" (1548mm)
64 13/16" (1646mm)
70 9/16" (1792mm)
76 3/8" (1940mm)
87" (2210mm)
99 9/16" (2529mm)
30º DEVIATION
7 7/16" (189mm)
9 7/16" (240mm)
12 7/16" (316mm)
15 7/16" (392mm)
21 7/16" (545mm)
27 7/16" (697mm)
30 13/16" (783mm)
32 13/16" (833mm)
35 13/16" (910mm)
38 13/16" (986mm)
44 13/16" (1138mm)
50 13/16" (1291mm)
HEIGHT 20"
(508mm) 23 ½"
(597mm) 28 11/16" (729mm)
33 7/8" (860mm)
44 1/4" (1124mm)
54 11/16" (1389mm)
60 9/16" (1538mm)
64 " (1627mm)
69 1/4" (1759mm)
74 7/16" (1891mm)
84 13/16" (2154mm)
95 1/4" (2419mm)
45º DEVIATION
10 5/16" (262mm)
13 3/16" (335mm)
17 3/8" (441mm)
21 5/8" (549mm)
30 1/8" (765mm)
38 5/8" (981mm)
43 7/16" (113mm)
46 1/4" (1175mm)
50 1/2" (1283mm)
54 3/4" (1391mm)
63 1/4" (1607mm)
71 11/16" (1818mm)
HEIGHT 17 13/16" (452mm)
20 5/8" (524mm)
24 7/8" (632mm)
29 1/8" (740mm)
37 5/8" (956mm)
46 1/8" (1172mm)
50 15/16" (1294mm)
53 3/4" (1365mm)
58" (1473mm)
62 1/4" (1581mm)
70 3/4" (1797mm)
79 3/16" (2011mm)
CHIMNEY 7-8” ELBOW DEVIATION
& HEIGHT ONE LENGTH BETWEEN ELBOWS TWO LENGTHS BETWEEN ELBOWS
8” 12” 18” 24” 36” 48” 8” & 48” 12 & 48” 18 & 48” 2 4” & 48” 36” & 48” 48” & 48”
Secure TempS2100+
Nova TempHT6000+
15º DEVIATION 3 5/16"
(84mm) 4 5/16"
(110mm) 5 7/8"
(149mm) 7 7/16"
(189mm) 10 1/2"
(267mm) 13 5/8"
(346mm) 15 1/2"
(394mm) 16 1/2"
(419mm) 18 1/16" (459mm)
19 5/8" (498mm)
22 3/4" (578mm)
25 13/16" (656mm)
HEIGHT 16"
(406mm) 19 7/8"
(505mm) 25 11/16" (652mm)
31 1/2" (800mm)
43 1/16" (1094mm)
54 5/8" (1387mm)
61 7/16" (1561mm)
65 1/4" (1657mm)
71 1/16" (1805mm)
76 7/8" (1953mm)
88 1/2" (2248mm)
100 1/16" (2542mm)
30º DEVIATION 7 3/8"
(187mm) 9 3/8"
(238mm) 12 3/8"
(314mm) 15 3/8"
(391mm) 21 3/8"
(543mm) 27 3/8"
(695mm) 30 7/8"
(784mm) 32 7/8"
(835mm) 35 7/8"
(911mm) 38 7/8"
(987mm) 44 7/8"
(1140mm) 50 7/8"
(1292mm)
HEIGHT 20 11/16" (525mm)
24 3/16" (614mm)
29 3/8" (746mm)
34 9/16" (878mm)
44 15/16" (1141mm)
55 5/16" (1405mm)
61 3/8" (1559mm)
64 7/8" (1648mm)
70 1/16" (1780mm)
75 1/4" (1911mm)
35 5/8" (2175mm)
96" (2438mm)
CHIMNEY 7-8” ELBOW DEVIATION
& HEIGHT ONE LENGTH BETWEEN ELBOWS TWO LENGTHS BETWEEN ELBOWS
--- 12” 18” --- 36” 48” --- 12" & 48" 18" & 48" --- 36” & 48” 48” & 48”
AC 7-8"
15º
DEVIATION --- 4 13/16" (122mm)
6 1/8" (156mm)
11" (280mm)
14 1/8" (359mm)
16 7/8" (429mm)
18 7/16" (468mm)
23" (584mm)
26 3/16" (665mm)
HEIGHT --- 27 11/16" (703mm)
33 ½" (851mm)
50 7/8" (1292mm)
65 ½" (1588mm)
72 5/8" (1845mm)
78 7/16" (1992mm)
95 ¾" (2432mm)
107 3/8" (2727mm)
30º
DEVIATION --- 9 3/8" (238mm)
12 3/8" (314mm)
21 3/8" (543mm)
27 3/8" (695mm)
32 5/8" (829mm)
35 5/8" (905mm)
44 5/8" (1134mm)
50 5/8" (1286mm)
HEIGHT --- 25 ¾" (654mm)
31" (878mm)
46 ½" (1181mm)
57" (1448mm)
66" (1676mm)
71 ¼" (1810mm)
86 7/8" (2207mm)
97 ¼" (2470mm)
*** NOTE : With the AC chimney, a starting length o f 6” high must be used on top of the fireplace befo re installing an elbow ***
RISE
OFFSET
15
Figure 12
Figure 13
AIR COOLED
BRACE
STRAPS
RADIATION SHIELD
STRAPS
SUPPORT
EXTERIOR INSTALLATION NOT RECOMMENDED FOR COLD CLIMATES
RAIN CAP STORM COLLAR
ROOF SUPPORT
FLASHING
WALL BAND
WALL RADIATION SHIELD
RADIATION RING
FRAME 2" X 4"
INSULATED WALL
16
TYPICAL CHASE INSTALLATION
Figure 14
FLASHING
NON COMBUSTIBLE CHASE TOP
CEILING/FLOOR
SEPARATION
- Must have same fire rating as adjacent ceiling.
- Must be insulated same as adjacent ceiling.
- Local code regulation for ceiling must be applied to
the ceiling floor separation.
i.e. Firestop etc..
NOTE:
- Follow fireplace installation instruction for chase installation.
- Chase wall and floor must be insulated in the same manner as the rest of the
building below the attic.
OFFSET SUPPORT
ROOF SUPPORT
FINISHED WALL
17
ANGLED WALL RADIATION SHIELD (RSM 30°, RSM 45°) OR
INSULATED RADIATION SHIELD (RSMI 30°, RSMI 45°) (See Figure #15)
When traversing a combustible wall with the chimney at a 30º or 45º angle, an angled firestop and / or wall radiation
shield must be installed. Only one is required.
NOTE: 45º ANGLE FOR CANADA ONLY.
In cold climate locations (such as Canada and Northern USA), we recommend that you use the insulated wall
radiation shield since it will maintain the home's thermal barrier.
RSM 30°, 45° and RSMI 30°, 45°
CHIMNEY ANGLE HOLE SIZE
7" ASHT+ (Canada only) 8" ASHT+ (Canada only)
30° 45° 30° 45°
13 3/8 x 33 ¼ (340 x 845 mm) 13 3/8 x 23 ¼ (340 x 591 mm) 14 3/8 x 36 ½ (365 x 927 mm) 14 3/8 x 24 ¾ (356 x 629 mm)
7" S-2100+ (Canada only) 8" S-2100+ (Canada only)
30° 45° 30° 45°
15 x 38 ¼ (380 x 972 mm) 15 x 25 7/8 (380 x 657 mm) 16 x 40 (406 x1016 mm) 16 x 27 ¼ (406 x 692 mm)
7" AC 8" AC
30° 30°
15 x 38 ¼ (380 x 972 mm) 15 x 38 ¼ (380 x 972 mm)
Table 6
Figure 15
DRYWALL
INSULATED WALL
ANGLE WALL RADIATION SHIELD (INSULATED)
18
INSULATED RADIATION SHIELD (RSI)
In cold climate locations, an insulated firestop may be
installed at the ceiling level. This will minimize heat loss
around the chimney at this location.
The insulated radiation shield should be installed from
below and the attic radiation shield installed from above.
UNIVERSAL ROOF SUPPORT INSTALLATION
This support has three possible uses:
1. For ASHT+ / HT6103+ and S-2100+ / H16000+, it must be used on a roof to support the chimney.
2. It may be used on a floor, ceiling or roof above an offset to support the chimney above the offset.
3. It may be used on a floor, ceiling or roof as a supplementary support when the chimney height exceeds 15 ft.
Table 7 gives maximum height of supported chimney.
Note: For the AC chimney, a support section must be used every 40' instead of the roof support.
FOR INSTALLATION INSTRUCTIONS REFER TO THE MANUAL PROVIDED WITH THE ROOF
SUPPORT.
UNIVERSAL OFFSET SUPPORT INSTALLATION
This support is used to support a chimney above an offset. When the chimney offset is used to traverse a wall, this
support may be used on the wall to support the chimney. The maximum height is given in Table 7.
CHIMNEY MAXIMUM HEIGHT OF CHIMNEY SUPPORTED
UNIVERSAL OFFSET SUPPORT UNIVERSAL ROOF SUPPORT
7" ASHT+ / HT6I03+
8" ASHT+ / HT6103+
24’ (7.30 m)
22’ (6.70 m)
29’ (8.84 m)
29’ (8.84 m)
7" S-2100+ / HT6000+
8" S-2100+ / HT6000+
12’ (3.65 m )
10’ (3.10 m )
20’ (6.10 m) 20’ (6.10 m)
7" AC
8" AC
40’ (12.19 m) 40’ (12.19 m)
50’ (15.20 m) 50’ (15.20 m)
Table 7
FOR INSTALLATION INSTRUCTIONS, REFER TO THE MANUAL PROVIDED WITH THE OFFSFT
SUPPORT.
ASHT+ / S-2100+ - HT6103+ / HT6000+
ATTIC RADIATION
SHIELD
RSI
Figure 16
19
CHIMNEY CHASE AND MULTIPLE TERMINATIONS
For the purpose of this manual a chimney chase is considered a part of the chimney system rather than part of the
building. The termination must be placed 18" (460 mm) above the chase.
For installations where more than one chimney is located in the same chase or within the same general area, we
suggest that their terminations be separated by at least 16" (410 mm) horizontally and 18" (460 mm) vertically. This
separation is to prevent smoke migrating from one chimney to another. (See Figure 17).
Figure 17
18" (460mm) 18" (460mm)
18" (460mm)
(410 mm) 16"
(410 mm) 16"
EXTERIOR JACKETING
20
PARTS AND COMPONENTS AC Chimney Part No.
LENGTHS 7" DIA. 8" DIA.
12" length AC 7L12 AC 8L12
18" length AC 7L18 AC 8L18
36" length AC 7L36 AC 8L36
48" length AC 7L48 AC 8L48
15º elbow AC7E15 AC 8E15
30º elbow AC 7E30 AC 8E30
Rain Cap AC 7CPR AC 8CPR
SUPPORTS
Offset support XSO XSO
Support section AC 7SL AC 8SL
Roof support XST XST
Starting section AC 7SB AC 8SB
Starting section with 4" (100 mm) offset AC 7SBO AC 8SBO
FIRESTOPS
Radiation shield ACRS ACRS
Attic radiation shield AC RSA AC RSA
Wall radiation shield 30° AC RSM30 ACRSM30
Insulated wall radiation shield 30° AC RSMI30 AC RSMI30
Roof brace XBS2 XBS2
Wall band XBM XBM
Outside air kit ACZI
(Flex, insulation, outside register and coupling)
Flat roof flashing ACF ACF
Adjustable roof flashing 1/12-7/12 (5° to 30°) AC FA AC FA
8/12 - 12/12 (30°to 45°) AC FB AC FB
12/12-21/12 (54° to 60°) AC FBB AC FBB
Storm collar AC FC AC FC
21
OPTIONAL PARTS
Outside air kit - fireplace UZI
(Flex, insulation and outside register)
Fireplace coupling - for outside register UZIDB or UZIDR
Blower (includes two blowers with magnets & thermostatic control) UZY5
Set of brass doors 36" SRDB36
Set of brass doors 42" SRDB42
Set of black doors 36" SRDN36
Set of black doors 42" SRDN42
Builder doors 36" SDB36
Builder doors 42" SDB42
Brass louvers 36" TLB36
Brass louvers 42" TLB42
COMMON REPLACEMENT PARTS 36” Smoke deflector PR-DF585A
Louver PR-SR15P
Louver pivot PR-PIVOT
Damper with rod PR-SBDAMPER
Facing :
Side PR-SB102
Top PR-SB138
Bottom PR-SB131
Middle PR-SR2178
REPLACEMENT PARTS SE36
Refractory - side PR-SR2135
Refractory - back PR-SR2134
Refractory - bottom PR-SR124
Refractory - front PR-SR114
Fire grate PR-SR2129
Rigid firescreen - right PR-SR2141D
Rigid firescreen - left PR-SR2141G
Folding door - right PR-SR2162D
Folding door - left PR-SR2162G
Door brass finish trim SR2167
Door guide PR-SR2146
Hinges PR-SR2170
Glass PR-SR2158
Handle support PR-SR2165
REPLACEMENT PARTS SB36
Refractory - side PR-SB141
Refractory - back PR-SB142
Refractory - bottom PR-SB143
Fire grate PR-PB01
Firescreen kit U36ZP
Firescreen PR-PE01
Firescreen rod PR-TPE01
Firescreen screws PR-SACSE
Wooden handle PR-C7
Hinges / hardware PR-SBDQ
Glass panel PR-VC03
REPLACEMENT PARTS SB42
Refractory - side PR-SB141
Refractory - back PR-SB127
Refractory - bottom PR-SB128
Fire grate PR-PB01
Firescreen U42ZP
Smoke deflector PR-DF585B
22
FIREPLACE MODEL SE36
INSTALLATION INSTRUCTIONS FOR THE DOOR HANDLE
2 1/4"
23
DIMENSIONS
D C
A B
A B
SB36 & SE36 Inches 40 5/8 43 Metric (cm) 103 109
SB42 Inches 46 5/8 43 Metric (cm) 118 109
A B C D E F SB36 & SE36
Inches 40 3/8 69 1/2 34 3/4 49 1/8 40 3/8 22 3/4 Metric (cm) 102 177 88 125 102 58
SB42 Inches 46 3/8 75 1/2 37 3/4 53 3/8 46 3/8 22 3/4 Metric (cm) 118 192 96 136 118 58
Dimensions include 1/4" tolerance
A B SB36 SE36
Inches 40 1/8 36 Metric (cm) 102 91
SB42 Inches 46 1/8 42 Metric (cm) 117 106
E
F
B
A
12 1/4"
20 1/2"
B
42 1/2"
HEADER
22 1/2"