Page 1 of 35 1 Nursery Lane C S Stokes and Associates Limited Fire Risk Assessment 1 Nursery Lane Following the Grenfell fire the Council has been working to make sure all our housing meets the most stringent standards of fire safety. We have been cooperating with fire risk assessment professionals and the London Fire Brigade to review our buildings and fire procedures. 1 Nursery Lane has received an overall rating of ‘medium’ in the most recent Fire Risk Assessment. This is a normal risk rating for residential housing blocks of this size. Once the risks identified by the most recent assessment have all been addressed the block will likely remain a medium risk. We will continue to manage these risks.

Transcript of Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk...

Page 1: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 1 of 35 1 Nursery Lane C S Stokes and Associates Limited

Fire Risk Assessment – 1 Nursery Lane

Following the Grenfell fire the Council has been working to make sure all our housing

meets the most stringent standards of fire safety. We have been cooperating with fire

risk assessment professionals and the London Fire Brigade to review our buildings and

fire procedures.

1 Nursery Lane has received an overall rating of ‘medium’ in the most recent Fire

Risk Assessment. This is a normal risk rating for residential housing blocks of this

size. Once the risks identified by the most recent assessment have all been

addressed the block will likely remain a medium risk. We will continue to manage

these risks.

Page 2: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 2 of 35 1 Nursery Lane C S Stokes and Associates Limited

REGULATORY REFORM (FIRE SAFETY) ORDER 2005

Fire Risk Assessment for:

1 Nursery Lane,

London W10 6QD

for The Tenants Management Organisation

(TMO) of the Royal Borough of Kensington and Chelsea

TMO Property reference number UPRN S217009580001

By Carl Stokes on the 31st

July 2017

Suggested review date in August 2018 with a new FRA in Aug 2018 or before, if any significant changes have taken place, in or adjacent to this building

DATE REASON FOR REVIEW BY WHOM OUTCOME

Area(s) covered by this fire risk assessment: All the common parts of the buildings, the staircase enclosures, staircase landings, the corridors, the residents communal areas ie the lounges, laundry, bin storage area, the office, the electrical rooms, the boiler room, the lift motor room, the roof space where the cold water tanks are located, the generator and other plant rooms, the corridor storage cupboards/rooms, the externally accessed gardeners storage areas and the gardens surrounding this property.

Area(s) not covered: All the private residential apartments, the external roofs, any confined spaces, the other roof space areas of this building apart from the cold water tanks are located and any other part of the building not identified above.

The significant findings and action plan of this Fire Risk Assessment are inserted next with this document continuing on page 2.

Page 3: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 3 of 35 1 Nursery Lane C S Stokes and Associates Limited

It is the policy of the TMO to take all reasonable steps to protect all relevant persons including residents, employees, visitors, contractors, any members of the public or any other persons who are lawfully on the premises, from potential injury and damage to their health which might arise whilst they are on these premises. When entrusting tasks to an employee their capabilities are taken into account as regard to Health and Safety so far as they relate to fire aspects. The aim of the fire risk assessment is to comply with The Regulatory Reform (Fire Safety) Order 2005.

The occupier takes the duties imposed by the Equality Act very seriously and seeks to ensure that all reasonable adjustments are made to enable people with disabilities to be treated fairly and not to be placed at any substantial disadvantage as required by The Regulatory Reform (Fire Safety) Order 2005.

Page 4: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 4 of 35 1 Nursery Lane C S Stokes and Associates Limited

Responsible Person:

Chief Executive of the Royal Borough of Kensington and Chelsea

Building Owners/ Landlord: The Council of The Royal Borough of Kensington and Chelsea

Person Consulted during the Assessment:

The premises manager, staff within the building and resident’s of this building.

Assessment completed by:

Mr C Stokes, ACIArb, FPA Dip FP (Europe), Fire Eng (FPA), NEBOSH, FIA BS

5839 Part 1 System Designer, BS 5839 Part 6, Competent Engineer BS 5266, Fire Risk Assessment training course, recognised by the IFE. 19 years Fire Safety experience with local Fire Authority, in enforcement and auditing roles, 8 years as an independent fire risk assessor. Member of the construction industry CPD certification Service for 14 years. Professional indemnity insurance cover provided by Hiscox. Enhanced CRB checked.

H M Government Guide used: Sleeping Accommodation

Any other guides that may be relevant: Building Regulations 2010 Approved Document B (Volume 2) inc FPA information Managing Agents management policy’s, procedures and associated documentation

Any other legislation that could make requirements for fire precautions in the building. The Equality Act 2010

Building Information

This fire risk assessment was carried out when the building was in normal use and only a visual inspection has been undertaken of the buildings structure and no invasive structural investigation was undertaken to complete the risk assessment. If there was any concern about hidden structural damage or lack of structural integrity of the buildings structure this will be raised with the landlords and commented upon within the following report. As far as I am aware the construction and any refurbishments of this building have gone through the Building Regulations process. Information has been gathered from the buildings occupants and employees of TMO and from an analysis of documents provided by TMO, there is some external timber cladding on this building.

Page 5: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 5 of 35 1 Nursery Lane C S Stokes and Associates Limited

Description of the building; This is a purpose built 2 storey hollow square shaped standalone sheltered residential apartment building, it is two floor levels at the front and left hand side, ground and 1st floor levels and ground floor level only on the right hand side and at the rear of this building. There are cold water tanks etc in the enclosed roof space of the two storey part and some plant. This residential building is situated at the end of a short public road and contains 35 purpose built sheltered residential apartments with associated communal areas. All of the flats are accessed from the internal protected corridors of this building apart from flat 35 which has its own independent entrance/exits from its own garden area at the front of the building. The public road is to the front of this building with the enclosed resident’s only garden areas on both sides and at the rear, there is also a central garden area accessed from the ground floor corridors. The exit gates from the garden come back out on to the public road are secured locked shut to reduce the risk of burglary etc after advice from the Metropolitan Police. This building stands in its own site and it is not attached to any other buildings with enough distance between this building and adjacent properties calculated to meet Building Regulation approval therefore minimising and preventing any fire spread to adjacent premises. It is considered unlikely that a fire in this building would compromise other nearby buildings. There were no apparent unusual structural features either externally or internally observed at the time of the assessment and there are no high voltage luminous tubes for signs etc in or on this building. The access arrangements to this building have been considered and the arrangements appear to conform to Part B5 of Approved Document B of the Building Regulations. Any changes to road layout etc away from these premises are outside the control of the responsible person.

Construction of the Building; This is a traditional brick, block and concrete constructed building with tiled pitched or sloping roofs, there are two protected staircases, one at each end of the 2 storey part of the building and a central accommodation staircase, which is open into the entrance lobby area at its base. The walls of the central staircase, the protected staircase enclosures and the corridors mostly being painted plaster over it is assumed brickwork or concrete, there is some wallpaper on the walls as well. The staircase and floors of this building are constructed of concrete. The externally accessed boiler room and the generator room are fire separated from the remainder of this building. There appears to be no hidden voids apart from the normal service duct and sanitary ones, in this building or sandwich panels used. There are no apparent unusual elements of building construction that were considered to add a significant additional contribution to the fire risk.

Use and Layout of the Building; This is a purpose built residential accommodation building which is occupied by older persons, the residents are independent with this being classed as a warden assisted scheme. There maybe staff in this building for some hours of each day during the normal working day, Monday to Friday but there are no permanent staff on site 24 hours a day. This is not a residential care home and there is no nursing

Page 6: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 6 of 35 1 Nursery Lane C S Stokes and Associates Limited

care given within this building. The communal areas in the building on the ground floor level, these areas are designed so that the residents can meet each other and have group activities, there are also ancillary areas such as a laundry, an office, a kitchen off the recreation room and a day room. At the front of the building externally accessed there is a bin storage area, the boiler room and the stand by generator room. The individual flats have fire rated self closing entrance doors with letter boxes in them in the lower half of the door. There is a lift in this building which gives access to both floor levels, the lift motor room is located in a room off the ground floor entrance hall area. The TMO have plans/drawings showing the layout of this building, none are attached to this fire risk assessment.

The evacuation strategy for this building; For the residents of the dwellings within this building:

There is a commercial fire alarm system installed within the common parts this building which extends into the hallway areas of the dwellings, this is a BS 5839 Part 1 fire alarm system. There is a heat detector and a sounder of the Part 1 system in the hallway area of each dwelling. Within the dwellings themselves there is a domestic BS 5839 Part 6 hardwired heat detector in the kitchen of each flat, some flats also have domestic detectors/sounders in each lounge/bedroom area, please see section 17 below for more information on this buildings installed fire alarm systems. For the residents of this building there is a “stay put” evacuation strategy, so even if the commercial fire alarm system activates this means the residents can remain within their own dwelling during a fire incident unless the fire is in that dwelling or it is otherwise affected. In which case they should immediately evacuate the dwelling and the building and call the Fire and Rescue Service. If there is a fire in a resident’s dwelling then this dwelling will be evacuated and also the flats adjacent to it. The Fire and Rescue Service or RBKC employees will arrange for a general evacuation of the building at anytime if this is appropriate. Additionally, any residents’ who prefers to evacuate the building once they hear the fire alarm system can do so at any time. There are fire action notices displayed next to each of this buildings fire alarm system break glass call points describing the actions to undertaken if the buildings fire alarm system activates. TMO has also provided information to all residents via letters and briefing sheets of ‘what to do in the event of an emergency’ and articles on fire safety advice and emergency procedures are included in the resident’s magazine called “Link”. Also article’s are provided reminding tenants that they must not store items in communal areas nor cause obstructions to the means of escape, these articles are produced in the 7 major languages which have been selected as being most likely to meet the needs of the residents. Fire drills or other emergency evacuation exercises are not carried out/undertaken by the residents of this building. As far as it is known having asked the person named above, there have no fires in this building in the last 2 years, there are 4 recorded false activations of the buildings fire alarm system so far this year. The fire alarm system in this building is remotely monitored by a receiving centre (CAS) via a dedicated “redcare” telephone, who have a policy and procedure if the fire alarm and warning system in the building activates. The emergency pull cords

Page 7: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 7 of 35 1 Nursery Lane C S Stokes and Associates Limited

located within each of the dwellings of this building and those in the common parts of this building are remotely monitored by Tunstall/CAS, Tunstall call CAS who implement their procedure for that incident.

For employees/contractors working in this building:

There is a simultaneous evacuation strategy is in place for RBKC employed cleaners etc or any contractors working in this building, but not for the staff members responsible for this building. If they are in the building. All cleaners/ contractors etc are advised that upon hearing the fire alarm or discovering a fire they must leave the building immediately by the nearest available safe exit route and go to the assembly point. If there are members of staff in the building, that person will call the Fire and Rescue Service if there is a fire in the building, giving details of the location of the fire and if any persons are missing or unable to escape. The person will then await the arrival of the Fire Service to assist them with any additional information that may be requested. The staff member will assist the residents as needed and carry out the fire warden tasks as trained and instructed, these tasks could be identifying the location of a fire, assisting residents to more away from the fire if appropriate and providing information to the emergency services. Any person in a common part of the building who cannot evacuate can take refuge in a residents room/dwelling and follow the procedure above as detailed for a resident. The CAS employee will inform the Fire Service of any fire alarm system activation if there are no staff on site.

Number of individual private dwellings in this building:

35

Methodology, for the completion of this fire risk assessment The adopted risk assessment methodology has been developed in line with guidance from the Health and Safety Executive (5 steps to risk assessment) and PAS79. The assessment involves: • Gathering relevant information for the building, occupants, processes and past fire

history etc. • Identifying hazards and determining measures to eliminate or control identified fire hazards.

• Determining existing physical fire protection measures and identifying any short comings.

• Discussions with occupiers and employees to determine the effectiveness of fire safety procedures and management policies.

• Subjective assessment of the likelihood of fire occurring. • Subjective assessment of likely consequences to the occupants of a fire event. • Assess fire risk and tolerability. • Document the significant findings from the fire risk assessment. • Formulating an action plan with the aim being to reduce the fire risk, from the

significant findings with both physical and procedural controls,

Page 8: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 8 of 35 1 Nursery Lane C S Stokes and Associates Limited

• Formulating a checking procedures to oversee the “actions to be taken” in the significant findings.

• Formulating a time schedule for reviewing the assessment. The type and scope of this Fire Risk Assessment is as defined by the Fire Safety in Specialised Housing guidance document as a Type 1 assessment, ie Common parts only, non destructive. But there is some over lap into a Type 3 assessment because questions have been asked and answers given about the electrical and heating installations within the flats along with testing and maintenance regimes, also the fire alarm systems installed etc.

The following rational is adhered to for the completion of this fire risk assessment From The Building Regulations, Section 1 of B1, Means of Escape from Flats, of Approved Document B Fire Safety (Volume 2) Incorporating Insurers Requirements for Property Protection.

2.3 The provisions for means of escape for flats are based on the assumption that:

a. the fire is generally in a flat; b. there is no reliance on external rescue (e.g. by a portable ladder); c. measures in Section 8 (B3) provide a high degree of compartmentation and

therefore a low probability of fire spread beyond the flat of origin, so that simultaneous evacuation of the building is unlikely to be necessary; and

d. although fires may occur in the common parts of the building, the materials and construction used there should prevent the fabric from being involved beyond the immediate vicinity (although in some cases communal facilities exist which require additional measures to be taken).

From BS 9991: 2011 Fire safety in the design, management and use of residential buildings – Code of practice, section 0.2 Flats and maisonettes, General principles.

The provisions for means of escape for flats or maisonettes are based on the assumptions that: (the same as the Building Regulations apart from the end of a.)

a. fire will occur within the flat or maisonette (e.g. not in a stairwell); b. there can be no reliance on external rescue (e.g. a portable ladder); c. the flat or maisonette will have a high degree of compartmentation and

therefore there will be a low probability of fire spread beyond the flat or maisonette of origin, so simultaneous evacuation of the building is unlikely to be necessary; and

d. where fires do occur in the common parts of the building, the materials and construction used in such areas will prevent the fire from spreading beyond the immediate vicinity (although in some cases communal facilities exist which require additional measures to be taken).

Page 9: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 9 of 35 1 Nursery Lane C S Stokes and Associates Limited

Information for Londoners living in high rise properties, this information is provided by the London Fire and Civil Defence Service (LFB ‘s web site)

If you live in a flat or maisonette Flats and maisonettes are built to give you some protection from fire. Walls, floors and doors will hold back flames and smoke for a time. If there's a fire outside of your flat, in another part of the building, you're usually safer staying in your flat unless heat or smoke is affecting you.

Important relevant information

This reviewed Fire Risk Assessment (FRA) supersedes any previous FRA’s in their entirety because of new guidance documents that have been provided by Government Departments and enforcement agencies since the original FRA’s were compiled. In particular the fire safety guidance document produced by the Local Government Group Fire safety in purpose-built blocks of flats dated July 2011 and the amendment of September 2011. This also includes determinations issued by the Secretary of State concerning the Fire Safety Order in particular the one about the retrospective fitting of cold smoke seals on fire rated doors. The reports, including the Coroner’s ones issued after the Lakanal House fire (Camberwell London) , Shirley Heights fire (Southampton) and the Prestatyn maisonette fire (North Wales) have been studied and where relevant any information contained within these reports has been incorporated into this FRA.

Any other relevant information on this premises

An audit, under The Regulatory Reform (Fire Safety) Order 2005 (FSO) was undertaken in this building by Fire Safety Inspecting Officer Miles Essex of the London Fire Brigade, on the 18th June 2013. A letter was issued after this audit, dated the 3rd July 2013 stating that there was no failure to comply with the FSO in the building or in the documentation seen at the time of the audit. A copy of this letter is held by the TMO Health and Safety team based at The Network Hub 300 Kensal Road, There have been no further written or verbal comments received from LFB as far as I know in connection with this premises and no follow up inspection has been undertaken by an LFB officer or operational crews. This information has been checked with the TMOs Health and Safety team.

Page 10: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 10 of 35 1 Nursery Lane C S Stokes and Associates Limited

FIRE RISK ASSESSMENT FOR: 1 Nursery Lane, London W10 6QD

The following simple risk level estimator is based on a more general health and safety risk level estimator of the type contained in BS 18004 2008:

Potential consequences of

fire ⇒

Likelihood of fire

Slight harm

Moderate harm

Extreme harm

Low

Trivial risk

Tolerable risk

Moderate risk

Medium

Tolerable risk

Moderate risk

Substantial risk

High

Moderate risk

Substantial risk

Intolerable risk

Taking into account the fire prevention measures observed at the time of this risk assessment, it is considered that the hazard from fire (likelihood of fire) at these premises is:

Low Medium X High

In this context, a definition of the above terms is as follows:

Low: Unusually low likelihood of fire as a result of negligible potential sources of ignition.

Medium: Normal fire hazards (e.g. potential ignition sources) for this type of occupancy, with fire hazards generally subject to appropriate controls (other than minor shortcomings).

High: Lack of adequate controls applied to one or more significant fire hazards, such as to result in significant increase in likelihood of fire.

Taking into account the nature of the building and the occupants, as well as the fire protection and procedural arrangements observed at the time of this fire risk assessment, it is considered that the consequences for life safety in the event of fire would be:

Slight harm X Moderate harm Extreme harm

In this context, a definition of the above items is as follows:

Slight harm: Outbreak of fire unlikely to result in serious injury or death of any occupant.

Moderate harm: Outbreak of fire could foreseeably result in injury (including serious injury) of one or more occupants, but it is unlikely to involve multiple fatalities.

Extreme harm: Significant potential for serious injury or death of one or more occupants.

Page 11: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 11 of 35 1 Nursery Lane C S Stokes and Associates Limited

Accordingly, it is considered that the risk to life from fire at these premises is:

Trivial Tolerable X Moderate Substantial Intolerable

Comments:

The risk to the occupants of this premises is considered to be tolerable.

A suitable risk based control plan should involve effort and urgency that is proportional to risk.

Risk level Action and timescale

Trivial No action is required and no detailed records need be kept.

Tolerable No major additional controls required. However, there might be a need for improvements that involve minor or limited cost.

Moderate

It is essential that efforts are made to reduce the risk. Risk reduction measures should be implemented within a defined time period.

Where moderate risk is associated with consequences that constitute extreme harm, further assessment might be required to establish more precisely the likelihood of harm as a basis for determining the priority for improved control measures.

Substantial

Considerable resources might have to be allocated to reduce the risk. If the building is unoccupied, it should not be occupied until the risk has been reduced. If the building is occupied, urgent action should be taken.

Intolerable Building (or relevant area) should not be occupied until the risk is reduced.

(Note that, although the purpose of this section is to place the fire risk in context, the above approach to fire risk assessment is subjective and for guidance only. All hazards and deficiencies identified in this report should be addressed by implementing all recommendations contained in the following action plan. The fire risk assessment should

be reviewed regularly.)

A fire risk assessment has been carried out for this building and the significant findings produced. By implementing the actions of the significant findings the risks or hazards will be lowered and therefore making the building safer for its occupants. If appropriate the significant findings should be passed on to any other occupiers in the building so that co-ordinated actions can be taken and visa versa, this also applies to any significant findings from any reviews etc that are undertaken.

You should consider the potential increased risk and hazard of any significant change before the change is introduced, it is usually more effective to minimise a risk or hazard beforehand than trying to achieve it after the event.

Page 12: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 12 of 35 1 Nursery Lane C S Stokes and Associates Limited

FIRE HAZARDS AND THEIR ELIMINATION OR CONTROL 1. ELECTRICAL SOURCES OF IGNITION YES NO N/A

Are reasonable measures taken to prevent fires of

electrical origin? X

Are fixed installation periodically inspected and tested? X

If appropriate, is portable appliance testing carried out? X

If any electrical appliances are present, are trailing leads/ adapters suitably limited and sockets not overloaded? X

Comments or observations:

According to the contractor’s label on the buildings electrical supply/distribution boards located in the electrical rooms of this building the last 5 year electrical fixed wiring check on the common parts electrical fixed wiring was undertaken on the 11th

July 2015. The retest date on these Stewards Electrical Limited contractor’s test labels is July 2020. There were no outstanding items indicated on this contractor’s label. These same test and retest dates are on all of the electrical supply/distribution boards seen. The main electrical room appears to be the one located on the ground floor level next to flat number 1, but there are other electrical rooms dotted around this building, these have the individual dwellings electrical meters located within them as well as landlords electrical boards etc. The landlord’s electrical supply/distribution boards and other associated electrical components appear to be industry standard items and are were appropriate housed in standard metal lockable containers. The Estates Service Assistants (ESA’s) and the schemes managers carry out regular visual inspections of the lighting system which is the main electrical installation in the common parts of this building and which is on a different electrical circuit from the apartment’s ones. Some of the lighting units are combined normal and emergency lighting units. The inspections also encompass the electrical rooms. There are no electrical supply boards on display on the common parts of this building. If there is any damage or remedial work is needed this is reported and repair’s or replacement lighting units are installed by a contractor on a responsive defect reporting procedure. Any defects can also be reported at any time by the schemes employees or a resident direct to the TMO’s 24 hour help line. There are wall mounted electrical sockets in the corridors of this building. There are portable electrical appliances in the communal lounge and day room as well in the kitchen, these are Portable Alliance Tested (PAT) by an external contractor with an asset register of all the items and records kept. Testing is not carried out on any resident’s private electrical items within their flats and as far as I know personnel electrical items are not used in the common parts this building. The PAT labels attached to these portable electrical appliances in this building had a last test date of the 2nd February 2017 on them and a retest date of February 2018. The office is equipped with all the types of electrical appliances that would normally be found in an office, computers, copier etc and a fan etc these items are PAT at the same time as the ones in the communal areas.

Page 13: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 13 of 35 1 Nursery Lane C S Stokes and Associates Limited

X

X

The use of trailing leads or multi plugs is restricted in this building and they are only used where necessary, there are no solar thermal or photovoltaic systems on or attached to this building. Contractors or workmen employed by RBKC and TMO are required to use only electrical equipment that is fit for purpose, in a good condition and appropriately inspected and maintained. TMO does not carry out checks on these items of equipment and it is assumed that electrical items of equipment brought into the building by other contractors or workmen are also suitable and in a good condition as again the TMO does not carry out checks on these items of equipment.

There is no recent history of major electrical power supply failures for this building. 2. SMOKING YES NO N/A

Are reasonable measures taken to prevent fires as

a result of smoking? X

Is the smoking ban suitable enforced, in the common parts

with “No Smoking” notices displayed at the entrance(s)? X

If located are the external smoking areas appropriately

sited with suitable receptacles provided? X

Does the no smoking policy appeared to be observed at the time of the inspection?

Comments or observations:

The residents are allowed to smoke within their own private individual dwellings but this is discouraged, residents are not allowed to smoke in the common parts of this building or in the communal areas of this building. At the time of this risk assessment there were no indications that the no smoking policy was being abused. This building is fitted with a BS 5839 Part 1 fire alarm and warning system in the common parts and this fire alarm system extends into the hallways of the residential dwellings. Please see section 17 below for more information on the buildings fire alarm system. At the time of this risk assessment there were no indications that smoking was being undertaken in the common parts of the parts of this building, “No Smoking” signage is displayed as you enter this building. The staff smoke outside the main entrance doors of this building on the public path, this is not a designated smoking area, but there were no piles of discarded used smoking materials seen at the time of this assessment.

3. ARSON YES NO N/A

Does basic security against arson by outsiders appear reasonable?

Are combustible and waste materials kept away

from the outside of the premises? X

Are the external refuse containers/rubbish bins suitably

secured against an external arson attack? X

Page 14: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 14 of 35 1 Nursery Lane C S Stokes and Associates Limited

YES NO N/A

Is the refuse storage area kept reasonably tidy and the

amount of waste material kept to a minimum? X Comments or observations:

There is an electrically operated door entry control system on the front entrance door to restrict entry to the building to authorised personnel only, keys or key fobs are used by the residents and an intercom system for visitors to the building. At the base of each end staircase there is a final exit door, both staircases exit into the garden area, there are gates from the garden back onto the public road, but these gates are padlocked shut. Please see the significant findings regarding this subject. The main entrance/exit door is opened from the inner face by a push button to the side of the door on the wall. This device is used every time by persons leaving the building. The doors at the base of the two end staircases are fitted with push bar to open devices so no keys are needed to open these exit doors when leaving this building and they can be opened in a single action. I am told that the main entrance/exit door with the push buttons fails safe to the open position if there is an electrical power failure in this building. There is a standard green manual over ride switch on the wall by the main entrance door so that this door can be manually opened if required. The front entrance door, the ground floor level alternative exit doors and the staircase exit doors are all fitted with self closing devices so that these doors close automatically thus maintaining the security of the building. These self closing devices were tested and all worked correctly at the time of this assessment. There is a fireman’s switch override device fitted to the front entrance door of this building which did not work when tested at the time of this visit. Combustible and waste materials are kept away from the exterior of the premises as far as possible this includes the garden areas. The bin storage area for the building is located on the round floor near to the laundry room, there is a refuse chute hatch in the lobby area by the exit door for the residents to use to place rubbish in the bins. This bin store is accessed externally from the road. The bin area is fire separated from the remainder of the building by the toilet wall and a self closing fire rated door to the lobby area, the hatch in the bin room wall onto the lobby area is metal. But the fire line is the toilet wall and the lobby door. The recycling bins with lids are located outside the front of this building, these are for the use of the residents of this building, these are industry standard metal bins. The area on the floor around these recycling bins was clear and in a tidy state at the time of this assessment as was the internal bin storage area. From the information provided bin storage area fires have not been a problem in the general area of this building, the gardens of the site are secured and to minimise the amount of waste the refuse is collected regularly by the local council.

4. PORTABLE HEATERS & HEATING INSTALLATIONS YES NO N/A

Is the use of portable heaters avoided as far as

practicable, in the areas covered? X Are fixed heating boilers/installations subject to regular maintenance, including any gas supply? X

Page 15: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 15 of 35 1 Nursery Lane C S Stokes and Associates Limited

YES NO N/A

Are suitable measures taken to keep combustible Xmaterials and waste away from boilers or heaters?

Are gas safety checks carried out in the building? X

Comments or observations:

Portable heaters are not used in the common parts of this building, there were no portable heaters seen at the time of this assessment. The central gas boiler which provides the heating and hot water for this building is located in the boiler room which is externally accessed from the road. This boiler provides the heating for the common parts and the flats in this building via a fixed heating system with water filled radiators. This boiler also provides the hot water for flats in this building. The gas supply for this central boiler and any other gas appliances in this building are on a planned preventive maintenance and servicing programme which also includes annual servicing of any gas appliances. The last service according to the serving book in the boiler room was on the 5th January 2017. There were no items of storage or waste in this boiler room at the time of this assessment, the boiler room is fire separated from the remainder of this building. At the time of this risk assessment there were no leaks of oil/lubricant or other types of liquid from the boilers or the associated machinery seen on the floor. Access to this boiler room is restricted to authorised persons only because of the type of key needed to access the room. There gas shut off valve is located just inside the boiler room. There is a small wall mounted electrical water heater fitted over the sink in the kitchen, this electrical water heater provides the hot water for this kitchen sink, the water heater is wired directly into the buildings electrical wiring via a fused electrical socket. There is a gas meter and a shut off valve in a wall cupboard in the kitchen.

5. PLANT and FIXED EQUIPMENT YES NO N/A

Does the plant look in good working order? X

Is combustible material kept away from the plant

or equipment? X Comments or observations:

There is a planned maintenance programme of inspections for the lift machinery and plant for the hydraulic lift within the building which is carried out by a third party contractor(Express Lift Services Limited). The records kept centrally in the “Hub” in Kensal Road but there is a record book kept in the lift motor room to aid the service

engineers. The last service date in the lift record book was the 10th July 2017, there were no adverse comments from the lift engineer at the time of this last service about the operation of this lift. The lift motor room and other items of plant are located in a purpose built ground floor level room, this lift motor room is accessed off the corridor with restricted accessed to this room to authorised persons only. At the time of the risk assessment there did not appear to be any leaks of oil or other types of liquid from any plant or machinery and there was no storage of any kind in this lift motor room.

Page 16: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 15 of 35 1 Nursery Lane C S Stokes and Associates Limited

X

There is a standby diesel generator located in an externally accessed ground floor level room at the front of the building next to the boiler room, I have been told that this standby generator is now not used and it will I am told be removed or mothballed if not removed from site. Please see the significant findings sheets reference more information about this standby diesel generator.

6. COOKING and LAUNDRY FACILITIES) YES NO N/A

Are reasonable measures taken to prevent fires

as a result of cooking? X Is there a suitable design and layout of the cooking area? X

Are reasonable measures taken to prevent fires if any

laundry facilities are located in the building? X

Are any filters changed or cleaned on a regularly basis if

fitted in any cooker hoods or tumble dryers in laundries? X

Are any filters changed and ductwork cleaned on a regular basis in any kitchen/laundry extract systems?

Are there suitable extinguishing appliances available? X

Comments or observations:

There is a kitchen area located off the ground floor level recreational/lounge area, this kitchen is used by staff mostly as the residents would use their own kitchens in their flats. If communal meals etc are to be cooked/provided then staff undertake these cooking duties. In the kitchen is an electrical slot in cooker, a toaster, a kettle, a microwave, a dishwasher and two fridge/freezers. There is no extraction system in this kitchen, there is an openable window. As the amount of cooking is minimal then natural ventilation in this area is sufficient to dispel any cooking fumes. The kitchen is also used by the staff members to provide themselves with hot drinks and snacks, at the time of the risk assessment this kitchen area was clean and tidy. The kitchen is separated from the lounge area by a set of double doors, these do not have self closing devices fitted to them. This is because this kitchen is part of the lounge/dining area, I have classed the kitchen and lounge area as one room or compartment. This area is fire separated from the corridor At the time of the risk assessment the kitchen was free of any waste or combustible items of storage as was the lounge area. Kitchens are located in each residential dwelling with the occupier being responsible for the maintenance of these domestic cooking areas. There is a laundry room on the ground floor opposite the lounge, this contains two washing machine and two dryers, these are available for use by any resident of this building unsupervised to launder their clothes. As far as I know there are no washing machines or tumble dryers in the individual flats. The laundry is fire separated from the remainder of the building and the appliances used are a standard washers and tumble dryers. The laundry area was free of piles of clothes etc or plies of unwashed laundry at the time of this assessment.

Page 17: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 16 of 35 1 Nursery Lane C S Stokes and Associates Limited

Both the kitchen and the laundry are fitted with suitable automatic fire detection which is part of the buildings system to give early warning to a fire situation and fire fighting equipment is provided in the corridor outside of these rooms.

7. LIGHTNING YES NO N/A

If a lightning protection system is installed on the building Xdoes it look in good condition?

Comments or observations:

There is not a lightning protection system installed in or on this building.

8. HOUSEKEEPING YES NO N/A Is the standard of housekeeping in the building adequate? X

Is there an avoidance of unnecessary amounts of

combustible materials or waste? X Is there an avoidance of inappropriate storage of

combustible materials or waste in escape routes, X

staircases or around rubbish chutes (if any in the building)? Is there an avoidance of inappropriate storage of

combustible materials or waste in cupboards or stores etc? X

Are any soft furnishing etc in corridors kept to a minimum,

do not raise the fire loading or cause an obstruction? X Are routine preventive checks carried to see that

the housekeeping/cleaning routines are working? X

Comments or observations:

The TMO has decided that the policy on items in the common parts of this building will be a “managed” one. This is because the structural elements of this building are concrete and brick ie non combustible, this means that items can be in the common parts, but the amount and type of items is monitored by regular managers inspections. So wheel chairs could be left in the entrance hall lobby area or in the corridors but not electric buggies/mobility scooters and definitely not mobility scooters on charge. The cleaners ensure that any quantities of waste and combustible material are removed from the building to the bin room or the external recycling bins. Therefore not allowing a build up of any combustible waste materials or rubbish in the common parts of this building. The garden area of this building was clear of any waste or rubbish at the time of this assessment. The lift motor room, the boiler room and the electrical rooms/cupboards were all empty of storage at the time of this assessment, the cupboards off the corridors have storage in them. At the time of this assessment the means of escape routes, the staircases and their landings, as well as the internal protected corridors were clear of any combustible items or storage.

Page 18: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 17 of 35 1 Nursery Lane C S Stokes and Associates Limited

The corridor at the rear of this building is very wide and there chairs and a tables located here as well as soft furniture and tables and chairs in the entrance hall/lobby area. There are no ignition sources near these items except for electrical sockets and the width of the corridors is large enough not to restrict the width of the means of escape route nor add unduly to the fire loading of these areas. Mostly where any furniture is located it is positioning against the wall so as not to be a trip hazard or obstruction, there are no items in the staircase enclosures. There are two staircases at the ends of the 2 storey part of this building and exit doors also from the ground floor level areas, which go directly to open air, so having chairs and tables in the corridors etc is low risk and I believe that no further action is needed on this issue. The HM Government guide, Sleeping Accommodation allows soft furnishings and furniture to be located in the means of escape routes and none of the furniture or the covering was damaged or ripped etc. There is automatic smoke detection in the corridors and two directions of travel, so these items in the corridors etc are in accordance with the H M Government guide. There are also bookcases in the corridors, I have used the same criteria as above in deciding that these book cases are low risk and no action is needed on this item. The purpose built bin did not have any bulk storage in it at the time of this risk assessment with all rubbish in the bins. The electrical rooms contain the electrical supply boards for the building these were empty apart from the electrical components and a small amount of storage, spare light bulbs etc which I believe is acceptable as the rooms were in a tidy state and the amounts of storage was minimal. In the far left hand side corner of the central garden area there is a maintenance room, there is a small amount of storage here mostly on purpose built racking, the items stored here are like those found in any DIY retailers. There is some paint which is mostly water based and a small amount of white spirits etc which are used for cleaning purposes. The access to this room is restricted and the room is fire separated from the remainder of the building, the quantities of items stored here are small and all materials are kept in their manufactures containers etc. There is also a gardeners store externally accessed and located near to flat number 1, this store is fire separated from the remainder of the building and contain gardening tools/equipment, along with plant pots etc, no fuel is kept in here. The gardeners store was in a tidy condition but the maintenance room could be tidied up. Residents have not introduced any items into the common parts of the building, apart from some residents do have door mats outside their flat doors, these are low risk and did not appear to cause an obstruction or be a trip hazard. Most of the flooring in this building is carpet and there are no curtains and blinds at the windows of the staircases, where carpeted the carpet was well fitted with no signs of any damage. Where there are other types of flooring in the shower and toilet areas no areas were seen to be damaged.

9.HAZARDS INTRODUCED BY OUTSIDE CONTRACTORS & BUILDING WORK

Are fire safety conditions imposed on outside contractors?

If contractors carry out lone working are there suitable precautions taken?

YES NO N/A

X

X

Page 19: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 18 of 35 1 Nursery Lane C S Stokes and Associates Limited

YES NO N/A

Is there satisfactory control over works carried out in the

building by outside contractors (including “hot work” permits)? X

If there are in house maintenance personnel, are suitable precautions taken, including use of hot work permits? X

Comments or observations:

Only authorised contractors, who have to provide method statements and schedules of work or TMO employees carry out work for the TMO in this building, the TMO has policies and procedures for contractors or in house employees carrying out work in their buildings, including “hot work” or other permit work. These policies and procedures are kept under review and altered as and when necessary or in the light of new information. If any contractors or tradesmen are employed by a leaseholder or tenant directly and the TMO is not informed then the TMO has no control over these contractors or tradesmen and these persons are outside the control of the TMO. According to the TMO policies contractors employed by the TMO or TMO employees are advised on procedures to undertake when lone working takes place. TMO instructed contractors or tradesmen are advised that when work is carried out that waste and building materials should not be allowed accumulate and obstruct or block exits and escape routes nor should final exit doors be propped or wedge open to aid the workmen. If openings are created in fire resisting partitions or compartments suitable preventive measures must be put in place to maintain the fire separation within the building until these openings are closed again. Care must also be taken to prevent false alarms of the fire alarm system by dust etc from the work being undertaken. It is assumed that any tools or items of equipment used and owned by any contractors or tradesmen and brought onto the premises are suitable for the work to be undertaken and in a good state of repair. No checks or inspections are undertaken on any items of equipment or tools of any contractors or tradesmen. No construction, refurbishment or maintenance work was being carried out in the common parts of this building at the time of this assessment nor were there any contractors on site working in the common parts of this building.

10. DANGEROUS SUBSTANCES YES NO N/A

If dangerous substances are, or could be, used, has a risk assessment been carried out, as required by the Dangerous Substances and Explosive Atmospheres XRegulations 2002?

Comments or observations:

There are no dangerous substances stored or used in the common parts of this building, this risk assessment has not taken into account any substances that may be within any domestic dwelling, but there are clauses in the tenancy agreements to restrict such substances. I asked at the time of this assessment and there are no residents who use oxygen

Page 20: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 19 of 35 1 Nursery Lane C S Stokes and Associates Limited

X

therapy and there is no storage of oxygen cylinders etc within any of the dwellings of this premises that could assist fire growth. Please see section 13 below for more information on this subject. This risk assessment has considered the small quantities of substances that are used or stored in the building, for instance those used for cleaning purposes, but only to the extent necessary to determine the adequacy of the general fire precautions.

11. PEST CONTROL YES NO N/A

Is there suitable control of any pest infestations? X

Comments or observations:

This building does not have any problems at the present time with rats, pigeons, squirrels or other rodents or insects, but this issue is kept under review to mitigate any damage that these types of vermin could cause to the fabric or structure of the buildings and electrical cabling or wiring. If droppings or guano are noticed then action can be taken to inform the pest control company employed by TMO to monitor the pest situation and measures will be taken to eradicate the problem.

FIRE PROTECTION MEASURES

12. MEANS OF ESCAPE FROM FIRE YES NO N/A It is considered that the building is provided with

reasonable means of escape in case of fire? X

Is the design of the escape routes adequate? X

Is there suitable protection of escape routes? X

Are the escape routes unobstructed? X

Are the escape routes suitable for buildings occupancy? X

Do the escape routes lead to suitable final exits? X

Are there reasonable travel distances, both in a single and alternative direction, if applicable?

Are travel distances in dead ends suitably limited? X

Are travel distances suitable for disabled people? X

Is there adequate provision of final exits? X

Are exits easily and immediately openable where

necessary? X

Page 21: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 20 of 35 1 Nursery Lane C S Stokes and Associates Limited

X

YES NO N/A

Where necessary do the fire exits open in direction

of escape route? X

Do the final exit doors have appropriate securing devices? X

Do the dwelling entrance doors appear to be fire rated? X

Are any other doors protecting the escape route suitably X fire rated and in a good condition?

Where appropriate are any fire doors fitted with self closing devices and do these function correctly?

Are store and cupboard fire doors kept locked shut?

X

Where appropriate are the doors/flaps to rubbish chutes

or the fire doors to the rubbish chute rooms suitable? X

Is the floor covering suitable to prevent slips, trips and

falls? X Comments or observations:

This building appears to have been constructed in accordance with the Building Regulations at the time of construction with the layout of the building including the travel distances, the escape routes, the width of escape routes and the number of exits appropriate for the present use. The main entrance door and the exit by the laundry lead out onto the public road all of the other means of escape route exit doors go into the garden area. Please see The significant findings sheets regarding this issue. The final exit doors from this building open in the direction of travel. There is a push button to release the securing devices of the front entrance/exit door which is suitable for the residents and DDA compliant with “push bar to open devices” fitted to the other exit doors. The main entrance door fails safe to open in a power cut, I am told. All of the exits from the building apart from the ones on the front face onto the public road lead into the enclosed garden area, from here you can leave the site via the garden gates. The local Metropolitan Police crime prevention officer has advised that these garden gates are kept secure at all times to prevent burglars gaining easy access to the building. This poses a problem that you cannot exit the garden unless you have keys to the gates and it has been decided that residents will not be given keys to the gates in case they wonder off. The garden is large enough to enable any persons in the garden to move away from the building in the first instance, if there was an emergency, to a safe distance away from the building and then for a member of staff to unlock the gates. By having the garden as a secure area the residents feel safe and the area is controlled and restricted to only authorised persons. There was adequate protection for the means of escape route with no visual damage observed during the assessment, the apartment entrance doors are not marked as 30 minute fire rated doors. But they are 44mm thick timber doors which are fitted with over head self closing devices, they have a letter box and a flap in the lower quarter to half of the door. The locking mechanism of the flat entrance doors is

Page 22: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 21 of 35 1 Nursery Lane C S Stokes and Associates Limited

“Yale” lock, this is easily openable by persons who are exiting the flats as it opens the door in a single action and no key is required. The corridor sub division doors are 30 minute fire rated doors fitted with self closing devises and strips and seals and held open by electromagnetic hold open/release devices (EMRs) wired in to the buildings fire alarm system, when the manual over ride switch was activated on each of these doors, the door was released and the self closing device shut the door fully. The doors to the other rooms located off the corridors are also standard 30 minute fire doors either kept locked shut or fitted with self closing devices. The fire rated door to the ground floor office/reception in the entrance lobby area does not have a self closing device fitted to it. There are no self closing devices fitted to the double doors separating the kitchen from the lounge area, I do not believe that self closing devices need to be fitted to these doors as I have classed this as one compartment. The lounge is fire separated from the corridor and the remainder of the building. Some of the cold smoke seals on the fire doors of this building have painted on them as a result of decorating work which has been undertaken, the amount of paint on the cold smoke seals is minimal so I believe that the seal will still function correctly. But this has been pointed out to the manager who will inform any decorators in the future not to put paint on the cold smoke seals. The electrical room by flat number 1, has a vent in the lower part of the door, there is an intumescent block in this vent, this door was locked shut and were the other corridor cupboard doors. There were no fire doors seen to be damaged at the time of this assessment. At the time of this risk assessment the escape routes were clear of obstructions apart from there were some pots of plants by the windows in the corridors mostly the rear one. These plants were located in the corners or against the walls of the building and did not appear to be an obstruction or could cause a trip hazard in an emergency so I believe are acceptable and in accordance with the managed policy on items on the means of escape routes. There are pictures and notice boards on the walls of the entrance hall, in the corridors these are low risk and I believe no further action is needed on this issue. Where fitted in the fire doors or in the screens the glazing is Georgian wired fire rated glass. At the time of this risk assessment the escape routes in the building ie the staircases and the corridors were clear of obstructions with the flooring materials on the escape routes suitable to prevent slips, trips and falls during evacuation, there were no signs of any damage to the floors or any unevenness. The staff and the caretakers/ESAs carry out checks and report any deficiency’s to the “Hub” so repairs can be undertaken. At the time of the risk assessment the flooring materials on the escape routes within the common parts of the building appeared suitable to prevent slips, trips and falls during evacuation, there were no signs of any damage to the floors or any unevenness. The ESA’s/caretakers carry out checks and report any deficiency’s to the “Hub” so repairs can be undertaken. When this building was constructed it was not a requirement under the Building Regulations standards at the time to have cold smoke seals fitted to fire doors changes to the Building Regulation standards are not retrospective. Over time some fire doors in the building have been replaced, so therefore have smoke seals fitted, the fire doors that do not have smoke seals are close fitting and shut tight. If these fire doors are to be replaced, repaired or any refurbishment work carried out that

Page 23: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 22 of 35 1 Nursery Lane C S Stokes and Associates Limited

involves these fire doors, then they will either be upgraded with smoke seals fitted to the door or in the surrounding frame or replaced with doors that already have smoke seals fitted. This stance on cold smoke seals is backed up by the Secretary of State’s determination issue in May 2012. If any of the apartments in this building are leaseholder apartments, this is unlikely but could happen, rather than tenanted apartments then the entrance door of the flat is demised to the leaseholder. The TMO does not have any control over or legal powers to intervene if the leaseholder changes the flat entrance door. The lease agreement clearly defines that the entrance door is demised to the leaseholder so if there is an issue over the conformity of the flat’s entrance door to either the standards required of the Fire Safety Order or the Building Regulations this is a private matter between the leaseholder and the enforcement authority. There have been meetings on this subject between the TMO and the local LFB fire safety team leaders, minutes of these meeting are held by the TMO Health and Safety team manager along with the relevant policies and procedures. If the apartment is a tenanted one with a TMO tenant not a leaseholder then the TMO has control and will undertake any appropriate actions needed.

13. DISABLED PEOPLE YES NO N/A It is considered that the building is provided with reasonable arrangements for means of escape for Xdisabled people?

Comments or observations:

At the time of the risk assessment there was no evidence of any resident within the dwellings of this premises who suffers from sensory impairment to such a level that would prevent them from hearing the domestic fire alarm system within their apartment if it activated or loud knocking on their entrance door to warn them of a fire. If any TMO members of staff think that a resident is in need of any extra help or assistance they can have Personal Emergency Evacuation Plan (PEEPs) drawn up for them. Alternatively “person centred fire risk assessments” could be undertaken for specific residents when it is identified that they may need them. Please see the significant findings sheets for more information on this subject. The TMO have a comprehensive programme to gathering information about tenants including any disabilities and their physical ability and mobility to respond to any emergency situations. This information has been entered on a “TP Tracker system” and is held centrally. The additional information will be used to assess if residents may require additional devices to provide them with early warning of smoke/fire in their home and/or development of a Personal Emergency Evacuation Plan (PEEPs). Regular inspections of the flats are undertaken so that hoarding tendencies and also medical problems can be identified at an early stage and then reports etc are written on the tenants and help given to them if needed. Within each dwelling there are emergency pull cords in each room/area, in the bedsit/lounge area, in the kitchen, the bathroom and in a few cases in the entrance hall/lobby area. Occupants of the dwellings could also have pendants around their necks. The Tunstall and CAS operators who remotely monitor these systems or the Tunstall control centre have a policy and procedure to follow if a call system or pendant is operated. This policy is specific to that tenant/client, this can be from undertaking a call back to the person to immediately alerting the emergency services

Page 24: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 23 of 35 1 Nursery Lane C S Stokes and Associates Limited

and a range of other procedures in between including calling an on duty staff member. There are regular updates of the client’s needs etc provided to the CAS operators who follow up on the Tunstall calls. I was told that calls from the Tunstall system can also be directed through to a mobile telephone if a staff member is on site. On the wall of the entrance hall area there is an information box with any information on residents who may need assistance, this list and their dwelling is regularly up dated. Part of the information contained within this information box is if there are any oxygen cylinders located within any of the dwellings of this building. At the time of this assessment there were no residents that needed to use oxygen cylinders for medical reasons or the free standing oxygen machines, if in the future any residents require theses items then this fire risk assessment will be amended. If there is only one resident who requires oxygen cylinders I have spoken with the manager and suggested that it is probably more sensible to have any oxygen cylinders that this resident requires stored within their flat. This is because all the cylinders will be in one place rather than one cylinder here and another there. If a lot of residents require oxygen cylinders then there will probably be a central storage area with only one or two cylinders in each flat. I would recommend through that a suitable storage rack or storage system is provided for the storage of any oxygen cylinders, they should not be just stood on the floor where they could be knocked over. The hydraulic lift installed in this building is not an evacuation or fire fighting lift but it is on different electrical sub circuit and could be used as part of an evacuation strategy, this is in line with current thinking from the International Organisation for Standardisation (ISO). It is now recognised that lifts can help persons with restricted mobility and other problems to evacuate buildings with relative ease and also significantly reduce general evacuation time even if they are not evacuation lifts. If the lift is to be used to aid in the evacuation process from the building then its use would be under the control of the Fire and Rescue Service if they are on site or under the control of the residents or perhaps TMO/RBKC staff if the fire service are not yet in attendance. There are no “Evac” chairs provided in this building. This is because of the construction of the building and the number of compartments and sub compartments within it, also this is not a fully staffed building 24 hours a day, so there are no staff to use an evac chair. This is a normal residential building which happens to have employees working in it at certain times of the day. If any members of staff are in the building they could help to undertake an evacuation and make certain any residents are in a safe location/refuge as well as contacting the fire and rescue service etc.

14. MEASURES TO LIMIT FIRE SPREAD AND DEVELOPMENT

It is considered that there is:

A reasonable standard of compartmentation provided?

A reasonable limitation of the fire loading in the means of escape routes/corridors that might promote fire spread?

The wall and ceiling linings are in a good condition?

YES NO N/A

X

X

X

Page 25: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

YES NO N/A

Page 24 of 35 1 Nursery Lane C S Stokes and Associates Limited

X

If fitted, is any fire rated glazing in good condition? X

Where necessary are fire dampers provided to protect the means of escape against fire, smoke and combustion Xproducts in the early stages of a fire?

If fitted, is the ductwork of any mechanical ventilation

system cleaned and any filters changed regularly? X

Comments or observations:

This building appears to have appropriate fire separation and compartmentation and from a visual inspection of the structure of the building there appeared to be no areas that raised concern about structural damage to the building or fire stopping issues. There were no obvious signs that in the areas covered that bad workmanship would mean that the fabric or fire integrity was or could be compromised. No invasive structural investigation was undertaken to complete this risk assessment and there were no visible breaches of the compartment or wall and ceilings linings at the time of this risk assessment, apart from the areas mentioned on the significant findings sheets. There are ceiling tiles on a grid system in the corridors, I looked above some of these ceiling tiles and in the areas looked at there were no breaches of the wall linings above the ceiling tiles. The roof space areas over the two storey part of this building is accessed via a loft hatch in the 1st floor level electrical cupboard ceiling, there are other loft hatches in the ceilings of the 1st corridors but the main access is in the electrical room. The roof space areas appear to be a common roof void, with no or limited sub divided/compartmentation. The fire loading of the common parts of the building was considered to be good, please see the sections on “housekeeping” and “arson” for more information on this subject. There is fire rated glazing in the fire doors and in the screens of the lounge onto the corridor, this was in a good condition at the time of this assessment with no cracks or damaged pieces noticed in this Georgian wired glass. From information provided there are no fire dampeners in this building and natural ventilation is used for the corridors and staircases etc via openable windows. In the first floor corridor ceilings there are open ventilation shafts/ducts which go directly to open air at roof level, where there are louvered panels. These are just shafts up through the ceiling and any hot gases or smoke from a fire will filter up these shafts, the openings in the ceiling were not blocked or obstructed in anyway at the time of this assessment. This way of ventilating the corridors relies on natural ventilation and a full evaluation should be undertaken before this system is replaced with automatic or mechanical ventilation systems. Please see section 19 below for more information on this subject.

15. EMERGENCY ESCAPE LIGHTING YES NO N/A

If any is fitted, is the emergency lighting system currently installed in the building, to a reasonable standard?

Page 26: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

YES NO N/A

Page 25 of 35 1 Nursery Lane C S Stokes and Associates Limited

X

Is there adequately normal or borrowed lighting to back X

up any fitted emergency lighting system installed?

Where necessary, does the emergency lighting cover

any external escape routes? X

If fitted, are all emergency lighting units, clean and

visually in a good condition? X Comments or observations:

There is an emergency lighting system installed in this building, as a minimum there are emergency lighting units installed to cover the means of escape routes and stairwells of this building, including in the boiler and some other areas. Please see the significant findings sheets regarding if any of the lights in this building are backed up from the stand by emergency generator. The external areas of the building would be illuminated by borrowed light from the street lighting during the hours of darkness so in the event of a supply systems fail in the building the exterior lighting would still function as it is on a different sub circuit. Therefore not having external emergency lighting presents a low risk to the residents and no further action is needed concerning escape lighting on the exterior of the building. As I have stated in the significant findings sheets some of the lights in this building may have been backed up from the stand by emergency generator, this is an item that needs to be checked out and additional self contained emergency lighting units installed if required. Any installation should be to the requirements of BS 5266 Part 1. The emergency lighting system in this building was not checked as part of this assessment. Where installed system consists of self contained units, not a centralised battery system. The neon indicator lights are visible on the emergency lighting units. The glare limits of the emergency lighting units are with-in the acceptable ranges of BS 5266 and the colour of the light produced is white , there are no twin pack lighting units in use.

16. FIRE SAFETY SIGNS AND NOTICES YES NO N/A

Is there suitable pictogram fire signage in this building? X

Are any signs displayed clearly legible, fixed securely in

position and unobstructed? X

If necessary, are there pictogram fire safety notices in the building with the assembly point indicated?

Comments or observations:

There was industry standard pictogram emergency escape signage in the building, this signage is suitably located, positioned and it is in accordance with the required guidance. The signage is not obstructed and it is displayed so that it can easily be seen by the occupants of this building.

Page 27: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 26 of 35 1 Nursery Lane C S Stokes and Associates Limited

There is pictogram fire action notices displayed next to most of this buildings fire alarm break glass call points, these are bespoke pictogram fire action notices which state that there is a stay put policy for the residents of this building if the fire alarm system sounds. That is unless their dwelling is affected by smoke or flames. The fire assembly point is written on these fire action notices, this is outside the front of this building. The fire action notices are also be the buildings emergency action plan in line with the guidance in the H M Government risk assessment guides, as this is a non complex building. The assembly point is marked on these notices. There is a push bar to open signs on the secondary exit doors and a press button is used to open the main entrance/exit door of this building, this button has press on it. This door fails safe to open if there is a power cut I am told this main entrance door is used every time by a person leaving the building. Pictogram signage is used so that the fire action message can be understood by occupants who have limited English language skills or who do not speak English. In the ground floor level entrance hall area near to the office there is a box on the wall which contains information for the fire service on residents that may need assistance to evacuate the building. A “premises information box”. This box and the information contained within it has been placed here at the request of the LFB fire officer in charge of fire safety. There were long discussions about the information that was needed and the result was that a list of flats numbers would be provided of residents who would defiantly need help to evacuate. This list of flat numbers is reviewed on a monthly basis by the manager and up dated as required along with information of any resident who has medical gas cylinders, oxygen etc within their dwelling. The Fire Service has access to this box.

17. MEANS OF GIVING WARNING IN CASE OF FIRE YES NO N/A

Is a suitable manually operated electrical fire alarm Xsystem provided in the common parts of the building?

Does it have automatic fire detection, if required? X

Is the system suitable for the occupancy and fire risk? X

If the system extends into the private flats is it suitable?

X

Has remote transmission of the system been considered? X

Comments or observations:

There is a “mixed” fire alarm and warning system installed in this building, this means that there is a British Standard 5839 Part 1 system covering the common parts of this building, the means of escape routes etc and in the roof space areas. There is a heat detector and sounder of this Part 1 system installed within each dwellings hallway as well. In the kitchens of each of the dwellings there is a domestic heat detector/sounder installed this is an electrically power detector wiring into the dwellings fixed electrical wiring. This is a standard and recognised fire alarm system installation, some flats have a domestic detector/sounder in each lounge/bedsit area as well. The BS 5839 Part 1 fire alarm and warning system is this building includes manually operated break glass call points, automatic fire detection and audible warning devices in accordance with British Standard 5839 Part 1 at the time of installation.

Page 28: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 27 of 35 1 Nursery Lane C S Stokes and Associates Limited

Small cupboards of less than 1 meter squared do not need to have automatic detection fitted in them, this is as specified in the British Standard on the siting of detection. But there are no smoke detectors of the buildings fire alarm system in the ground floor cleaners cupboard or in the externally accessed maintenance room. By the lift on the first floor level there are wall mounted smoke detectors, automatic smoke detectors can be wall mounted as part of the British standard, but please see the significant findings sheets reference this issue. There is a layout diagram displayed next to the fire alarm control panel which is located in the entrance lobby area, showing the presently installed fire alarm system. There are no areas within the building where the back ground noise would be that high that there would be a requirement to fit visual alarms (flashing beacons) to supplement the audible fire alarm warning signal. The installed fire alarm system in this building was not checked as part of this assessment. Not sound level readings were taken as part of this assessment. The fire alarm system is tested weekly on, with the test records up to date at the time of this assessment this buildings fire alarm system is remotely monitored by CAS. The corridor doors in these buildings are fitted with electromagnetic hold open/release (EMR) devices wired directly into the fire alarm system, the EMRs operated correctly when the manual over ride switch was activated and the door was released. The EMRs and the hold open self closing devices are not on a timer so the doors remain in the open position unless the buildings fire alarm system activates and releases them. There is the appropriate signage on the facing side of each of these fire doors. There is a “Stay Put” evacuation strategy in place for the residential flats in this building and this is considered to be acceptable.

18. PORTABLE FIRE EXTINGUISHING APPLIANCES YES NO N/A

Is there reasonable provision of portable fire extinguishers? X

Are all the fire extinguishing appliances readily accessible? X

Comments or observations:

The current types, numbers and the locations of portable fire fighting equipment are suitable for the current building occupancy and use and were visible, none were obstructed in any way at the time of this assessment. There are portable fire fighting appliances provided within the common parts of this building as well as in other areas, like the kitchen, lift motor room, the electrical room, the boiler room etc. It is not known if any portable fire fighting equipment has been purchased by any residents for their own private dwellings, in news letters to the residents there have been fire safety articles contains basic instructions in relation to the safe use of portable fire fighting equipment. if any residents have purchased portable fire fighting equipment, then this will be for their own person used and beyond the control of the TMO. With the coming into force of BS 5306 Part 8 2012 the principles of the 2000 document in regard to dry powder fire extinguishers being used/discharged in a confined space have now been extended to cover all types of buildings. The BS 5306 Part 8 2000 document only previously commented on they use in hospitals, old people’s homes and hotels this is because of the sudden reduction of visibility which may temporarily jeopardise any escape, rescue or other emergency action.

Page 29: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 28 of 35 1 Nursery Lane C S Stokes and Associates Limited

X

X

Previously water based extinguishers were the preferred option in hospitals, old people’s homes and hotels, now dry powder fire extinguishers should not normally be specified for use indoors in any building unless mitigated by a Health and Safety assessment. The fire extinguisher engineer may comment further on this issue when he next undertakes the annual servicing of the fire extinguishers as there is a dry powder fire extinguisher located in the boiler room.

19. FIXED FIRE SYSTEMS AND FIRE EQUIPMENT YES NO N/A

Type of fixed system: X

Ventilation Shafts Comments or observations:

There are ventilation shafts in the ceilings of the first floor level corridor, these openings in the ceilings are covered with a mesh grill. These ventilation shafts use natural air flow and have no mechanical or forced air systems attached to them as far as I know. At the roof level of the shafts there are louvered vents which are wind shielded. At the time of this assessment none of the grills and the louvered vents of the ventilation system were obstructed or appeared to be blocked or damaged, this was a visual inspection only from the corridor.

MANAGEMENT OF FIRE SAFETY

20. PROCEDURES AND ARRANGEMENTS YES NO N/A Are there routine in- house fire safety inspections and checks carried out, with records kept?

Are appropriate fire procedures in place with a suitable

record of the fire safety arrangements ? X

Are there suitable arrangements for summoning and

meeting the fire and rescue service, including providing Xrelevant information and any likely hazards?

Are there suitable policies and procedures in place for contractors and “lone workers?

Comments or observations:

The schemes manager, the deputy manager etc or employees/caretakers, Estates Services Assistants (ESAs) walk around this building on a daily basis and there are defect reporting policies and procedures in place so that any discrepancies or damage can be repaired or items replaced. The Fire and Rescue service can be called at any time if there is an emergency situation by a resident or by the CAS monitoring centre if the buildings fire alarm system activates. There are also Tunstall pull cards in the common parts of this building as well as in the dwellings, these pull cords are all monitored by Tunstall and the CAS monitoring centre. CAS have policies and procedures for calling the fire service in when the pull cords are activated if the fire service are required.

Page 30: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 29 of 35 1 Nursery Lane C S Stokes and Associates Limited

If there is an employee within the building they would meet Fire Service on their arrival. If there are only tenants/occupants within the building they would meet the Fire Service on their arrival as would be the situation for a fire in any private dwelling. There are defect reporting policies and procedures in place so that any discrepancies or damage can be repaired or items replaced. Any resident can ring the TMO 24 hour help line at any time to report any defects in this building, damaged lights etc or any items that are damaged. The Health and Safety Advisor of the TMO has regular liaison meetings with the local fire and rescue service commander to pass on information and arrange familiarisation visits if needed or requested. As far as I can tell and from information I have been given the policies and procedures are subject to reviewing at set intervals or are altered if new or relevant information becomes available.

21. TRAINING YES NO N/A

Are TMO employees given adequate fire safety instruction

and training on induction and adequate periodic X“refresher training” at suitable intervals, with records kept?

Is the content of the staff training provided suitable, with Xpractical instruction on fire fighting equipment?

Comments or observations:

The fire safety and emergency procedures for the building are as described on the fire action notices that are displayed n this building, any visitors to the building sign in and out so a record can be kept of who is in the building. The staff in this building are employed by RBKC and are provided with induction training which includes fire training and periodic “refresher training” at regular intervals, these records are kept by the scheme manager I am told. I have not seen these training records. A fire warden is also the nominated persons and by being recorded as a fire warden you are also the nominated person. All TMO employees receive induction training which includes fire training and periodic “refresher training” at regular intervals, any records of this training are kept by the Human Resources (HR) department at 300 Kensal Road North Kensington. ESA’s/caretakers, wardens and office managers receive training to be fire marshals/ wardens by a third party fire training company the fire warden are also the nominated persons and by being recorded as a fire warden you are also the nominated person, training records again kept by the HR department. The topics and areas covered by the training packages are available from either TMO‘s HR or the Health and Safety team or direct from the training provider. I have been shown copies of the training documents and they appear to cover all the areas and topics that are mentioned in the H M Government risk assessment guidance booklets. The practical training involves using the types of portable fire fighting appliances currently provided in the TMO buildings. If anybody receiving this training does not use English as their first language this fact is taken into account so that they comprehend the information given to them. Prior to moving into this building all residents are issued with a handbook which includes fire safety advice, they are also given a copy of the LFBs Home Fire Safety leaflet and a letter informing them what to do in a fire situation.

Page 31: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 30 of 35 1 Nursery Lane C S Stokes and Associates Limited

X

They are given a tour of the building by a Housing/Neighbourhood Officer, there is no documentary evidencing required by TMO for the issuing of the handbook. Contractors are reported by TMO to be required to have a construction phase plan which should be agreed before work commences and be acted upon including provision of a suitable number and type of fire extinguishers and someone trained to use them as part of the fire safety arrangements for the project where appropriate. Fire drills are not undertaken in this building because there are no permanent members of staff, the managers can be switched between buildings. Contractors could be in this building but this is covered under section 9 above and the evacuation procedure is as specified in building evacuation strategy above and on the fire action notices displayed.

22. CO-OPERATION WITH ANY OTHER EMPLOYERS YES NO N/A

If this building is shared with other occupiers is fire risk

Information co-ordinated between occupiers? X

Have you received appropriate information on other occupiers fire risks and general fire precautions?

Comments or observations:

This is a single occupied residential building.

23. TESTING AND MAINTENANCE YES NO N/A

Is the structure of the premises adequately maintained? X Is there weekly testing and six monthly servicing of fire detection and fire alarm system, with records kept? X

Is there a monthly visual and annual testing of the emergency escape lighting, with records kept? X

Is there a monthly visual and annual maintenance of the

fire extinguishing appliances, with records kept? X

Is there a monthly testing and annual servicing and maintenance of any smoke and or automatic opening Xvents along with any associated equipment/devices, with records kept?

Is there routine checks of final exit doors and/or security fastenings, with records kept? X

Is there periodic inspection of any external escape staircases and gangways, with records kept? X

Six monthly inspections and annual testing of any wet

or dry rising mains, with records kept? X

Page 32: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 31 of 35 1 Nursery Lane C S Stokes and Associates Limited

Monthly inspections of switches and annual testing of the fire fighting/evacuation lifts, with records kept?

Weekly inspections and annual testing of the sprinkler installations, with records kept?

Annual inspection and test of lightning protection system, with records kept?

Monthly and annual testing and servicing, under load of any back up/stand by generators, with records kept?

YES NO N/A

X

X

X

X

Comments or observations:

There is a fire alarm system installed within this building, according to the Allied Protection fire logbook kept by the buildings fire alarm panel the last test/service of

this buildings fire alarm system was on the 15th June 2017. The occupiers weekly tests were up to date according the managers record sheet. Please see the significant findings sheets reference the installed emergency lighting system in this building and the stand by emergency generator. The last annual emergency lighting test/service was undertaken by Allied again on the 15th June 2017, please see the significant findings sheets regarding this service and the failed emergency lighting units. It is not known if the schemes managers or the TMOs ESAs/caretakers are undertaking the monthly occupier’s tests of the installed emergency lighting system with the results being recorded as proof of testing etc. Please see the significant findings sheets regarding the servicing and maintenance of the fire extinguishers in this building, some are over due servicing others have been serviced twice in 6 months.

Definitions:

Responsible person: The person ultimately responsible for fire safety as defined in the Regulatory Reform (Fire Safety) Order 2005. which is:-

"responsible person" means—

a) in relation to a workplace, the employer, if the workplace is to any extent under his control;

b) in relation to any premises not falling within paragraph (a)— i. the person who has control of the premises (as occupier or otherwise)

in connection with the carrying on by him of a trade, business or other undertaking (for profit or not); or

ii. the owner, where the person in control of the premises does not have control in connection with the carrying on by that person of a trade, business or other undertaking.

"relevant persons" means—

a) any person (including the responsible person) who is or may be lawfully on the premises; ( members of the public in a shop or licensed premises, contractors or visitors in a factory ) and

Page 33: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 32 of 35 1 Nursery Lane C S Stokes and Associates Limited

b) any person in the immediate vicinity of the premises who is at risk from a fire on the premises, but does not include a fire-fighter who is carrying out his duties in relation to a function of a fire and rescue authority under section 7, 8 or 9 of the Fire and Rescue Services Act 2004 (fire-fighting, road traffic accidents and other emergencies). This could include people in flats above a ground floor shop or the staff living over a licensed premises.

Child; Anyone who is not over compulsory school age, i.e. before or just after their 16th birthday. You must, before you employ a child, provide a parent with clear and relevant information on the risks to that child identified by the risk assessment, the measures you have put in place to prevent/protect them from fire and inform any other responsible person of any risks to that child arising from their undertaking.

Combustible materials: A substance that can be burned.

Compartment wall and/or floor: A fire-resisting wall or floor that separates one fire compartment from another.

Competent person: A person with enough training and experience or knowledge and other qualities to enable them properly to assist in undertaking the preventive and protective measures.

Dangerous substances: A substance which because of its physico-chemical or chemical properties and the way it is used or is present at the workplace creates a risk or a substance subject to the Dangerous Substances and Explosive Atmosphere Regulations 2002 (DSEAR). Small quantities of substances are not considered a major hazard for instance DSEAR talks of quantities of 25 litres and more so a few plastic bottles of cleaning materials and other such substances are not relevant and would be normal. For example the local corner shop or supermarket would not record as dangerous substances all the items they sell in their shop, including bleach, white spirit, paint and glue etc.

Material change: An alteration to the premises, process or service which significantly affects the level of risk to people from fire in those premises.

Means of escape: Route(s) provided to ensure safe egress from the premises or other locations to a place of total safety.

Premises: Any place, such as a building and the immediate land bounded by it, any tent, moveable or temporary structure or any installation or workplace.

Significant findings: A feature of the premises or items from which the fire hazards and persons at risk are identified this information comes from completing the fire risk assessment. It can also contain the necessary information, instruction and training needed and how it will be given. From the significant findings can come an:-

An Action plan: The actions you have taken or will take to remove or reduce the chance of a fire occurring or the spread of fire and smoke, including time frames and who will supervise or carry out the work needed.

Page 34: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 33 of 35 1 Nursery Lane C S Stokes and Associates Limited

Travel distance: The actual distance to be travelled by a person from any point with-in the floor area to the nearest storey exit or final exit, taking into account the layout of walls, partitions and fixings in the building. If the building has been constructed in accordance with The Building Regulations and no unauthorised alterations have then place then the travel distances will be satisfactory.

Where necessary: The Order requires that fire precautions (such as fire fighting equipment, fire detection and warning, and emergency routes and exits) should be provided (and maintained) ‘where necessary’. What this means is that the fire precautions you must provide (and maintain) are those which are needed to reasonably protect relevant persons from risks to them in case of fire. This will be determined by the findings of your risk assessment including the preventative measures you have or will have taken.

Who is at Risk in the building: This is a term used in risk assessment documents and the Fire Safety Order 2005, for the purposes of this risk assessment persons who are at risk are deemed to be anybody who is lawfully entitled to be in the building, ie relevant persons, but excluding fire fighters engaged in emergency activities. Please see the definition of "relevant persons" as described above.

Young person: (a) A person aged 16 years, from the date on which he attains that age until and including the 31st August which next follows that date. (b) A person aged 16 years and over who is undertaking a course of full-time education at a school or college which is not advanced education. (c) A person aged 16 years and over who is undertaking approved training that is not provided through a contract of employment.

. REFERENCES:

Fire Safety Design and Management BS 5588-12: 2004. Fire precautions in the design, construction and use of buildings Managing fire safety. Now incorporated in: BS 9999: 2008. Code of practice for fire safety in the design, management and use of buildings and BS 9991:2015.

LACoRS. Housing Fire Safety Guidance (Now Local Government Regulation) Local Government Group Fire safety in purpose-built blocks of flats (July 2011) National Fire Chiefs Council, guide to Fire Safety in Specialised Housing

Fire Detection and Fire Alarm Systems BS 5839-1: 2013. Fire detection and fire alarm systems for buildings - Code of practice for system design, installation, commissioning and maintenance. BS 5839-6: 2013. Fire detection and fire alarm systems for buildings – Code of practice for the design, installation and maintenance of fire detection and fire alarm systems in dwellings. BS 5839-8: 2013. Fire detection and fire alarm systems for buildings - Code of practice for the design, installation, commissioning and maintenance of voice alarm systems.

Page 35: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 34 of 35 1 Nursery Lane C S Stokes and Associates Limited

BS 5839-9: 2011. Fire detection and fire alarm systems for buildings - Code of practice for the design, installation, commissioning and maintenance of emergency voice communication systems.

Fire Extinguishing Appliances BS 5306-1: 2006. Code of practice for fire extinguishing installations and equipment on premises - hose reels and foam inlets. BS 5306-3: 2009. Fire extinguishing installations and equipment on premises - Code of practice for the inspection and maintenance of portable fire extinguishers. BS 5306-8: 2012. Fire extinguishing installations and equipment on premises - Selection and installation of portable fire extinguishers - Code of practice. BS EN 3. Portable fire extinguishers. BS EN 671-3: 2009: Fixed fire-fighting systems. Hose systems. Maintenance of hose reels with semi-rigid hose and hose systems with lay-flat hose. BS 5306-0:2011 Fire protection installations and equipment on premises Part 0: Guide for selection of installed systems and other fire equipment BS EN 1869: 1997. Fire blankets. BS ISO 14520-1:2015 Gaseous fire-extinguishing systems. Physical properties and system design. General requirements

Emergency Lighting BS 5266-1: 2016. Emergency lighting - Code of practice for the emergency lighting of premises. BS 5266-7: 1999 (BS EN 1838: 2013). Lighting applications - Emergency lighting. BS 5266-8: 2004 (BS EN 50172: 2004). Emergency escape lighting systems.

Fire Safety Signs BS ISO 3864-1:2011, Graphical symbols. Safety colours and safety signs. Design principles for safety signs and safety markings BS 5499-4: 2013. Safety signs, including fire safety signs. Code of practice for escape route signing. BS EN ISO 7010:2012+A5:2015. Graphical symbols. Safety colours and safety signs. Registered safety signs. BS 5499-10: 2014. Guidance for the selection and use of safety signs and fire safety notices

Fixed Fire Extinguishing Systems and Equipment BS 5306-2: 1990. Fire extinguishing installations and equipment on premises - Specification for sprinkler systems. BS 9990: 2015. Code of practice for non-automatic fire-fighting systems in buildings. BS EN 12845: 2015. Fixed fire-fighting systems - Automatic sprinkler systems - Design, installation and maintenance.

Miscellaneous BS 476-22: 1987, ‘Fire tests on building materials and structures, methods for determination of the fire resistance of non-load-bearing elements of construction’ BS 7176: 2007 A1 2011. Specification for resistance to ignition of upholstered furniture for non-domestic seating by testing composites. BS 7273-4: 2015. Code of practice for the operation of fire protection measures - Actuation of release mechanisms for doors.

Page 36: Fire Risk Assessment 1 Nursery Lane › sites › default › files › atoms › files...Fire Risk Assessment – 1 Nursery Lane Following the Grenfell fire the Council has been working

Page 35 of 35 1 Nursery Lane C S Stokes and Associates Limited

BS 7671: 2008 A3:2015. Requirements for electrical installations. IEE Wiring Regulations. Seventeenth edition. PAS 79: 2012. Fire risk assessment - Guidance and a recommended methodology. BS 8300:2009 (Amended 2010) Code of Practice for the Design of Buildings and their approaches to meet the needs of disabled people. HM Government Supplementary Guide- Means of Escape for Disabled People.

Lightning BS EN 62305-1: 2011. Protection against lightning. General principles. BS EN 62305-2: 2012. Protection against lightning. Risk management. BS EN 62305-3: 2011. Protection against lightning. Physical damage to structures

and life hazard. BS EN 62305-4: 2011. Protection against lightning. Electrical and electronic

systems within structures.