Rich Walke
UL Codes and Regulatory Services
Fire-Resistance Test
Standards for
Elements and
Assemblies
![Page 2: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/2.jpg)
22
Fire-Resistance-Rated Construction
![Page 3: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/3.jpg)
3
Fire-Resistance-Rated Construction
Code
Requirements
for
Fire-Resistance-
Rated
Construction
![Page 4: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/4.jpg)
4
Code Requirements
• IBC Section 703.2 – Fire-resistance ratings
shall be determined in accordance with
ANSI/UL 263 or ASTM E119
• LSC 8.2.3.1 – The fire resistance of
structural elements and building
assemblies shall be determined in
accordance with test procedures set forth
in ANSI/UL 263 or ASTM E119
![Page 5: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/5.jpg)
5
Fire Resistance
• Expressed as an Hourly Time Period
• Ratings range from 1/2 to 4 hours
• Containment of Fire to Room or Floor of
Origin, and Structural Fire Resistance
![Page 6: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/6.jpg)
6
Fire-Resistance-Rated Construction
Establishing
Fire-Resistance
Ratings
![Page 7: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/7.jpg)
7
Standards
• ANSI/UL 263
• ASTM E119
• NFPA 251 (Withdrawn)
![Page 8: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/8.jpg)
8
Building Components
• Columns
• Beams
• Floor/Ceilings or Roof/Ceilings
• Walls
![Page 9: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/9.jpg)
9
Temp
(ºF)
Time (Hr)
Time - Temperature Curve
![Page 10: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/10.jpg)
10
Columns
• Sample size – Minimum 9 ft
• Tested unloaded
![Page 11: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/11.jpg)
11
![Page 12: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/12.jpg)
12
![Page 13: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/13.jpg)
13
Conditions of Acceptance – Columns
• 1000ºF / 1200ºF
![Page 14: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/14.jpg)
14
![Page 15: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/15.jpg)
15
![Page 16: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/16.jpg)
16
Beams
• Sample size – Minimum 12 ft
• Load applied – Per design
![Page 17: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/17.jpg)
17
![Page 18: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/18.jpg)
18
![Page 19: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/19.jpg)
19
![Page 20: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/20.jpg)
20
![Page 21: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/21.jpg)
21
![Page 22: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/22.jpg)
22
![Page 23: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/23.jpg)
23
Conditions of Acceptance – Beams
• Support load
• 1100ºF / 1300ºF
![Page 24: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/24.jpg)
24
Floor/Ceiling or Roof/Ceilings
• Sample size – 180 sq ft / 12 ft
• Load applied – Per design
180 sq ft12 ft
![Page 25: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/25.jpg)
25
![Page 26: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/26.jpg)
26
![Page 27: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/27.jpg)
27
![Page 28: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/28.jpg)
28
![Page 29: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/29.jpg)
29
![Page 30: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/30.jpg)
30
![Page 31: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/31.jpg)
31
![Page 32: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/32.jpg)
32
![Page 33: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/33.jpg)
33
![Page 35: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/35.jpg)
35
Conditions of Acceptance
Floor/Ceilings or Roof/Ceilings
• Support load
• Flame passage
• 250ºF / 325ºF
• Support temperatures
![Page 36: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/36.jpg)
36
![Page 37: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/37.jpg)
37
Walls
• Sample size - 100 sq ft / 9 ft
• Load applied - Per design
100 sq ft9 ft
![Page 38: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/38.jpg)
38
![Page 39: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/39.jpg)
39
![Page 40: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/40.jpg)
40
![Page 41: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/41.jpg)
41
![Page 42: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/42.jpg)
42
![Page 43: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/43.jpg)
43
![Page 44: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/44.jpg)
44
Conditions of Acceptance – Walls
• Flame passage
• 250ºF / 325ºF
• Support load
• Hose stream
![Page 45: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/45.jpg)
45
Where Can I Find The
Most Current Listing?
UL Product iQ on
www.ul.com
![Page 46: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/46.jpg)
4646
Breaches in Fire-Resistance-Rated
Construction
• Penetrations
• Joint Systems
• Opening Protectives
• Ducts and Air Transfer Openings
![Page 47: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/47.jpg)
47
Breaches in Fire-Resistance-Rated
Construction Cont.
Do breaches really impact the performance
of a fire-resistance-rated assembly?
Absolutely!!!
![Page 48: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/48.jpg)
48
Breaches in Fire-Resistance-Rated
Construction Cont.
• Unsealed or improperly sealed breaches cost lives and
property!
• MGM Grand, Las Vegas, NV – Fire confined to 1st floor.
Eighty-four fatalities, most on upper floors.
• Hilton Hotel, Las Vegas, NV – Fire spread from 8th to 23rd
floor in 25 minutes at exterior of building. Eight fatalities.
• First Interstate Bank, Los Angeles, CA – Fire spread from
12th to 16th floor through improperly protected penetrations
and through unprotected perimeter joint. One fatality.
• One Meridian Plaza, Philadelphia, PA – Fire spread from
22nd to 30th floor through improperly protected penetrations
and through perimeter joint. Three fatalities.
![Page 49: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/49.jpg)
49
IBC Requirements
• IBC – Breaches shall be protected
•Section 714 – Penetrations
•Section 715 – Fire-Resistant Joint Systems
•Section 716 – Opening Protectives
•Section 717 – Ducts and Air Transfer Openings
![Page 50: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/50.jpg)
50
LSC Requirements
• LSC – Breaches shall be protected
•Penetrations
•Joint Systems
•Opening Protectives
•Ducts and Air Transfer Openings
![Page 51: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/51.jpg)
51
Code Requirements
• Each type of breach has a unique fire test
standard associated with it which
compliments ANSI/UL 263 and ASTM
E119
• Where breach occurs in, through or
between assemblies intended to restrict the
movement of smoke, the code also sets
limits on the leakage through the breach
![Page 52: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/52.jpg)
52
Where Can I Find The
Most Current Listing?
UL Product iQ on
www.ul.com
![Page 53: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/53.jpg)
5353
Fire Resistive Construction
UL’s
Product iQ
Online Directory
![Page 54: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/54.jpg)
54
Product iQ – UL’s New Online Directory
• Replaces the old Online Certifications
Directory which was developed in 1999
• Helps you achieve code compliance
• Is continuously updated
• Requires registration to create user account
• Basic Service – no charge for use
![Page 55: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/55.jpg)
55
Product iQ – UL’s New Online Directory
• Paid Subscription Service provides more
features
•Save Searches
•Tags and Groups
•Confirmation Letters
• Same listing information as the old platform
• No impact on testing results or
certifications
• https://iq.ulprospector.com/en/
![Page 56: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/56.jpg)
56
UL Product iQ – www.ul.com
Scroll to the bottom of the page
![Page 57: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/57.jpg)
57
UL Product iQ
![Page 58: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/58.jpg)
58
UL Product iQ Cont.
![Page 59: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/59.jpg)
59
UL Product iQ Cont.
![Page 60: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/60.jpg)
60
UL Product iQ Cont.
![Page 61: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/61.jpg)
61
UL Product iQ Cont.
![Page 62: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/62.jpg)
62
UL Product iQ Cont.
![Page 63: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/63.jpg)
63
UL Product iQ Cont.
Smart Search
![Page 64: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/64.jpg)
64
UL Product iQ Cont.
iQ Plus Search
![Page 65: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/65.jpg)
65
UL Product iQ Cont.
iQ Plus Search
![Page 66: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/66.jpg)
66
Questions / Comments
![Page 67: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall](https://reader036.fdocuments.us/reader036/viewer/2022071506/6126e3cb6149be01a50ac8ad/html5/thumbnails/67.jpg)
6767
Thank You for Attending!!!
Rich Walke