Fire Rated and Special Application Enclosures for Hazardous Areas
-
Upload
abtech-ltd -
Category
Engineering
-
view
300 -
download
5
Transcript of Fire Rated and Special Application Enclosures for Hazardous Areas
Specialised Enclosures for
Hazardous Areas
Fire Rated Enclosures
Standard Fire RatingsAvailable on Abtech Stainless and GRP rangesIEC331 Fire Test• 750°C for 3 hours followed by visual inspection• Then 5kV insulation resistance testBS6387 Fire Test - 3 separate tests1. Fire alone: Category C
• Flame at 950°C for 3 hours, cables powered
2. Fire with Water: Category W• Flame at 650°C for 15 minutes then flame and
water spray for 15 minutes
3. Fire with Mechanical shock: Category Z• Flame at 950°C with mechanical shock applied
at 15s intervals for 15minutes
• Note: All fire rated enclosures must be fitted with ceramic terminals
Extreme Fire Resistance Test
• 19kV High Voltage Enclosure (HVJB) coated with K-Mass™ fireproofing• 1100°C for 1 hour
• Tested in accordance with HC fire curve NEK 606
• Under conditions as specified in ASTM E1725 (Section 4) & ASTM E1529 (Section 5)
• Independent test carried out by Intertek and witnessed by Worley Parsons
Preparation for the Test
Fitted with ceramic pillars, side plates and phase separators. Clad with K-Mass™
19kV DC applied for 1 minute without breakdown prior to test
1100°C for 1 hour
• Required furnace temperature reached after 7min and 44 seconds. The test then began
• A constant 4kVDC voltage was maintained for the duration of the test• Leakage was monitored throughout the test • There was no breakdown
After the Test
Some cooling down is required!
Positive Result• Maximum recorded
temperature within the box was 349°C
• After cool down 19kV DC was re-applied and the enclosure passed
Special Application Enclosures
Nautilus IP68• Stainless Steel 316 Enclosure• IP68 to EN60529
• 100m for 5 days • 50m for 14 days
• ATEX & IECEx • Ex e, Ex ia or Ex ib certified• Terminal box only• Ambient temperature -50°C to
+55°C• Hinged cover with handle and
lifting eye straps fitted as standard
SSD Enclosure• Stainless Steel Ex d Enclosure• Used for containing transformers,
circuit breakers, motor controls, PLC’s etc
• ATEX & IECEx IIB or IIB+H2 certified• Ambient range -20°C to +55°C• Can be fitted with pushbuttons,
selector switches & windows• Custom sizes available:
• Almost any size dictated by surface area: from 560cm² to 18000cm²
• Maximum voltage 660V ac 120V dc
Combined Ex e & Ex d Enclosures
• Link SX (Ex e) and SSD (Ex d) enclosures: • Ex d Isolator enclosure
with Ex e high voltage enclosure• HMI display (Ex d) with
Ex e terminal connections
Camera & Instrument Housing• Stainless Steel 316 Ex d Enclosure with toughened glass window• ATEX & IECEx certified• Ingress protected to IP66/67 to EN60529• Custom mounting brackets to suit installed device• Maximum device voltage 60V dc
High Voltage Enclosures
Ex-Rated High Voltage Enclosures
• Ex certified HV range based on SX enclosure• From 3.3kV up to 45kV and
3.2kA• Suitable for -50°C• Typical applications:
• Umbilical connection• Down hole pumps• Water injection pumps• Fire suppression systems• Temporary power supply
connections
HV Splitter Box• A unique solution for the
termination of offshore umbilical cables or onshore distribution systems • The power conductor
compartment houses the HV cables • A separate control
compartment is used for terminating fibre optic or control cables• Ex e or Ex e op is• Other ratings same as HVJB
series