Transcript of Fire Protection Hydraulic Calculation
![Page 1: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/1.jpg)
Fire Protection
Hydraulic Calculations(Wet and Dry Systems)BSSI 1001
John Willden, P.Eng.
![Page 2: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/2.jpg)
Hydraulic Equations
where: Q = USGPM AOP = Area of Sprinkler operations
1500 – 3000 ft2 for light hazard
Density = USGPM/ft2 or water/square foot
Q AOP Density for first sprinkler flow
![Page 3: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/3.jpg)
Hydraulic Equations
where: Q = USGPM K=sprinkler factor p=pressure in psig
Q K p
2Qp for first sprinkler pressureK
![Page 4: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/4.jpg)
Hydraulic Equations
where: Pf = pressure drop per foot (psig/ft)
Q = USGPM pipe flow F = friction factor from table
PF = total pressure loss
1.85fP FQ LPP fF
![Page 5: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/5.jpg)
Hydraulic Example
Ordinary Hazard group 1 we get 0.15 USGPM/ft2
If each sprinkler is covering 130 ft2 we have:
Q =Q = Q = Q =
P =P = P = P = P = Q =
10 ft 10 ft 10 ft 10 ft
1 in1 in1¼ in1½ in
P = Q =
16 ft
![Page 6: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/6.jpg)
Hydraulic Example
Q = Area x Density = 130 ft2 x 0.15 USGPM = 19.5 USGPM
Q =Q = Q = Q =
P =P = P = P = P = Q =
10 ft 10 ft 10 ft 10 ft
1 in1 in1¼ in1½ in
P = Q =
16 ft
![Page 7: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/7.jpg)
p = (Q/K)2
= (19.5/5.65)2
= 11.91 psig
Hydraulic Example
Q = 19.5Q = Q = Q =
P =P = P = P = P = Q =
10 ft 10 ft 10 ft 10 ft
1 in1 in1¼ in1½ in
P = Q =
16 ft
![Page 8: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/8.jpg)
pf = FC120 x Q1.85
= 5.10 x 10-4 x 19.51.85
= 0.124 psig/ft
Hydraulic Example
Q = 19.5Q = Q = Q =
P =11.91P = P = P = P = Q =
10 ft 10 ft 10 ft 10 ft
1 in1 in1¼ in1½ in
P = Q =
16 ft
![Page 9: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/9.jpg)
Pf = pf x L = 0.124 x 10 ft
= 1.24 psig
Hydraulic Example
Q1 = 19.5Q2 = Q3 =
Q4 =
P1 =11.91P2 =
P3 = P4 = P5 = Q5 =
10 ft 10 ft 10 ft 10 ft
1 in1 in1¼ in1½ in
P = Q =
16 ft
![Page 10: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/10.jpg)
P2 = Pf + P1
= 1.24 + 11.91= 13.15 psig
Hydraulic Example
Q1 = 19.5Q2 = Q3 =
Q4 =
P1 =11.91P2 =
P3 = P4 = P5 = Q5 =
10 ft 10 ft 10 ft 10 ft
1 in1 in1¼ in1½ in
P = Q =
16 ft
![Page 11: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/11.jpg)
Q2 = K P2 + Q1
= 5.65 13.15 + 19.5= 20.49 + 19.5= 39.99 USGPM
Hydraulic Example
Q1 = 19.5Q2 = Q3 =
Q4 =
P1 =11.91P2 =13.15
P3 = P4 = P5 = Q5 =
10 ft 10 ft 10 ft 10 ft
1 in1 in1¼ in1½ in
P = Q =
16 ft
![Page 12: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/12.jpg)
Hydraulic Example
Q1 = 19.5Q2 =39.99 Q3 =
Q4 =
P1 =11.91P2 =13.15
P3 = P4 = P5 = Q5 =
10 ft 10 ft 10 ft 10 ft
1 in1 in1¼ in1½ in
P = Q =
16 ft Now you try the next sprinkler
![Page 13: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/13.jpg)
wet systems are always full of water they sprinkle when a head opens
TO SPRINKLERS
CHECK VALVE
ALARM VALVE(SPRINKLER VALVE)
INDICATING VALVE
SIAMESE CONNECTION(FIRE DEPARTMENT
CONNECTION)
FROM SERVICE MAIN
![Page 14: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/14.jpg)
Details of Wet System
© 1997, The Viking Corporation
![Page 15: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/15.jpg)
dry systems are full of compressed air they bleed off the air and sprinkle when a head
opensTO SPRINKLERS
FIRE DEPARTMENT CHECK VALVE
ALARM VALVE(DRY SPRINKLER VALVE)
INDICATING VALVE
SIAMESE CONNECTION(FIRE DEPARTMENT
CONNECTION)
FROM SERVICE MAIN
CHECK VALVE
![Page 16: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/16.jpg)
Dry Pipe System
© 1997, The Viking Corporation
![Page 17: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/17.jpg)
TO SPRINKLERS
CHECK VALVES
ALARM VALVE(PREACTION SPRINKLER VALVE)
INDICATING VALVE
SIAMESE CONNECTION(FIRE DEPARTMENT
CONNECTION)
FROM SERVICE MAIN
CHECK VALVE
preaction systems are full of compressed air until a fire is detected
then they fill with water to get ready
![Page 18: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/18.jpg)
TO SPRINKLERS
CHECK VALVE
ALARM VALVE(PREACTION SPRINKLER VALVE)
INDICATING VALVE
SIAMESE CONNECTION(FIRE DEPARTMENT
CONNECTION)
FROM SERVICE MAIN
CHECK VALVE
deluge systems are empty and the sprinkler heads are open
they all come on at once when a fire is detected
![Page 19: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/19.jpg)
Sprinkler Heads three major types
of sprinkler heads upright pendant sidewall
dry type
http://www.vikingcorp.com/databook/sprinklers/
![Page 20: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/20.jpg)
Sprinkler Arrangements Tree systems
Only one path to each sprinkler head
Grid systems At least two
paths to each sprinkler head
![Page 21: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/21.jpg)
Loop systems There are two paths to
each sprinkler head but the system can also be used to circulate heating or cooling water
Sprinkler Arrangements – cont’d
pendant
upright
![Page 22: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/22.jpg)
Typical Alarm Valve
![Page 23: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/23.jpg)
Parts of Alarm Valve
![Page 24: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/24.jpg)
Fire Protection Symbolspendent head – hangs downupright head – stands upsidewall head – sticks out sidewaysupright (elevation view)pendent (elevation view)siamese connection – fire departmentcheck valve
![Page 25: Fire Protection Hydraulic Calculation](https://reader034.fdocuments.us/reader034/viewer/2022050621/577c85ca1a28abe054be80bf/html5/thumbnails/25.jpg)
Fire Protection SymbolsALARM VALVE (wet)ALARM VALVE (dry)ALARM VALVE (preaction)ALARM VALVE (deluge)flushing connection (flanged)flushing connection (cap)open stem and yoke valve (OS & Y)
FC
FC