Www.ict.csiro.au End-2-End QoS Internet Presented by: Zvi Rosberg 3 Dec, 2007 Caltech Seminar.
Fire protection – Combustible Shielding in Instrumental Buildings Daniel Rosberg - WSP AB Dan...
-
Upload
henry-long -
Category
Documents
-
view
216 -
download
0
Transcript of Fire protection – Combustible Shielding in Instrumental Buildings Daniel Rosberg - WSP AB Dan...
![Page 1: Fire protection – Combustible Shielding in Instrumental Buildings Daniel Rosberg - WSP AB Dan Madsen – Grontmij AB Fredrik Jörud – ESS AB.](https://reader034.fdocuments.us/reader034/viewer/2022050714/56649d215503460f949f6b0d/html5/thumbnails/1.jpg)
Fire protection – Combustible Shielding in Instrumental Buildings
Daniel Rosberg - WSP ABDan Madsen – Grontmij AB
Fredrik Jörud – ESS AB
![Page 2: Fire protection – Combustible Shielding in Instrumental Buildings Daniel Rosberg - WSP AB Dan Madsen – Grontmij AB Fredrik Jörud – ESS AB.](https://reader034.fdocuments.us/reader034/viewer/2022050714/56649d215503460f949f6b0d/html5/thumbnails/2.jpg)
2
Planning and Building Act (ESS-0002382) Natural Fire => roof steel members No resistance & pillars 60 minutes
OK
![Page 3: Fire protection – Combustible Shielding in Instrumental Buildings Daniel Rosberg - WSP AB Dan Madsen – Grontmij AB Fredrik Jörud – ESS AB.](https://reader034.fdocuments.us/reader034/viewer/2022050714/56649d215503460f949f6b0d/html5/thumbnails/3.jpg)
3
Radiation Protection Act (ESS-0001051)
• “As far as reasonable practical, non- combustible materials should be used in installations”
• “Detect and extinguish quickly those fires that do start”
![Page 4: Fire protection – Combustible Shielding in Instrumental Buildings Daniel Rosberg - WSP AB Dan Madsen – Grontmij AB Fredrik Jörud – ESS AB.](https://reader034.fdocuments.us/reader034/viewer/2022050714/56649d215503460f949f6b0d/html5/thumbnails/4.jpg)
4
General Safety Objectives (ESS-000004) Ionization radiation
> 1 mSv to public within a return time of 10 000 years
> 20 mSv to public within a return time of 1 000 000 years
Demonstrate how to avoid:
> 100 mSv to public within a return time of 10 000 000 years
![Page 5: Fire protection – Combustible Shielding in Instrumental Buildings Daniel Rosberg - WSP AB Dan Madsen – Grontmij AB Fredrik Jörud – ESS AB.](https://reader034.fdocuments.us/reader034/viewer/2022050714/56649d215503460f949f6b0d/html5/thumbnails/5.jpg)
Recommendation to limit loss of property (ESS- 0001126)
> 7 M€ => AUT SUPPRESSION
> 50 M€ => AUT SUPPRESSION + ANALYSIS
![Page 6: Fire protection – Combustible Shielding in Instrumental Buildings Daniel Rosberg - WSP AB Dan Madsen – Grontmij AB Fredrik Jörud – ESS AB.](https://reader034.fdocuments.us/reader034/viewer/2022050714/56649d215503460f949f6b0d/html5/thumbnails/6.jpg)
6
Purpose: Evaluate how to handle the combustible shielding to meet requirements
![Page 7: Fire protection – Combustible Shielding in Instrumental Buildings Daniel Rosberg - WSP AB Dan Madsen – Grontmij AB Fredrik Jörud – ESS AB.](https://reader034.fdocuments.us/reader034/viewer/2022050714/56649d215503460f949f6b0d/html5/thumbnails/7.jpg)
7
SUMMARY
Install sprinkler in caveInstall sprinkler in hall ceilingAllow only redesign of 1 instrument
simultaneously OR apply 5 m safety distanceKeep HGV on 10 m distance to unprotected
fire load Keep field offices/labs on 2 m distance to
unprotected fire load