description

When specified correctly fire protection materials preserve property and can save lives. With so many products available and so much at stake, gaining expert advice on choosing the right products is vital

Transcript of Fire Protection

Page 1: Fire Protection

Fire Protection

Page 2: Fire Protection

... the choice of industry experts for over 35 years...

When specified correctly fire protection materials preserve property and can save lives. With so many products available and so much at stake, gaining expert advice on choosing the right products is vital.

The range of fire protection products supplied by SIG Technical Insulation covers fire protection materials suitable for the entire construction process. This guide features information on fire protection products from major manufacturers and includes products for structural steel, partitioning, ductwork, wall and roof linings, ceilings and intumescent fire stopping.

We also stock a wide range of ancillary items such as fixings and steel angles.

Fire Protection is a specialist market and you need suppliers who have the experience and technical expertise to give you tailored advice on products and applications. We can advise you on which metal systems to use or which fixings and fastenings you need for your boards and panels for example.

As our experts are on hand to support you, we can help you select the exact products for your application, first time, every time.

This product range and expertise is backed up by our fleet of specialist delivery vehicles, so we ensure your products are delivered exactly when and where you want them. Efficient scheduling means the risks of damage and loss are greatly reduced and our fleet of Moffett Mounty off-loading vehicles provide the ideal solution for sites with limited availability for off-loading facilities or difficult access.

2

Page 3: Fire Protection

Part B LegislationFire safety legislation can be confusing but it’s essential that it’s adhered to as not following this legislation can cost lives.

The Building Regulations Part B is split into two different volumes which focus on fire safety: Volume 1 covers dwelling houses and Volume 2 covers all other buildings.

Part B assesses the reaction to fire and fire resistance. Elements such as heat emission, ignitability, toxic gas and smoke emission are caused by the reaction to fire. Fire resistance and firestopping deal with the ability of a material to withstand fire exposure. SIG Technical Insulation specialise in supplying fire resistance and firestopping products which comply with Part B after the following assessments:

• Stability – load-bearing capability and structural collapse• Integrity – flame puncture• Fire insulation – heat transfer

Fire resistance covers a number of categories including protection of building structure; service protection; penetration seals and large barriers; and linear fire-stops and cavity barriers.

Fire resistance and firestopping which adheres to Part B will ultimately save lives as it achieves:

• Safe evacuation of the building• Time for the emergency services to fight fires safely and

efficiently• Reduced losses to property, rebuilding costs and business

down-time• Fire containment in cells or compartments to slow the

spread of fire

All the products which SIG Technical Insulation supplies comply with Part B legislation and our team are experts in this.

For more information, please visit www.sigtechnicalinsulation.co.uk 3

Page 4: Fire Protection

Third Party CertificationThird Party Certification is a voluntary certification scheme which includes verification of the test evidence and type of application or use of the product.

The Certification also includes a regular audit of the factory QA system to check the products supplied to the contractor are the same design or formulation as the original test samples.

There are multiple benefits to having Third Party Certification including:

• Shows customers your company is regularly assessed by an impartial third party

• Demonstrates you are meeting minimum quality and environmental requirements

• Makes it easier for you to gain impartial feedback and monitor your business

• Helps you to comply with legal obligations

Depending on the level of claims being made, CE Marking is enabled via a Third Party Certification body acting as a Notified Body to agreed European procedures. It should be noted that CE Marking is not a ‘quality mark’ but uses harmonised European classification and fire testing procedures. Voluntary third party product certification schemes are ‘product quality’ schemes and invariably include more checking procedures than required for CE Marking.

A Third Party Association for installers is a process whereby the contracting company employs appropriately trained staff to design and install the required passive fire protection system. Their work is independently audited by site inspections from the third party organisation and a full record system is required as part of the scheme. The use of such accredited schemes is recognised in the Building Regulations, Approved Document B (Use of Guidance; Independent certification schemes).

In the section detailing ‘Use of Guidance; Materials and Workmanship – Independent certification schemes:

The text suggests that savings are available to reduce the costs of Building Control/Approved Inspectors where third party certificated products and installers are being used on site. This publication is intended to enhance that process.

It should be noted that all ASFP Contractor members are required to be subject to Third Party Certification as a condition of membership of ASFP.

For more information, please visit www.sigtechnicalinsulation.co.uk4

Page 5: Fire Protection

Firestopping IntroductionThe aim of fire stopping is to control the spread of fire with fire resisting compartments which subdivide a building, allowing the fire to be contained.

However, fire can spread through concealed cavities between firestopping floors and doors, such as through the holes made in floors and walls, either for services or by design.

Firestopping ensures the materials used to connect floors and doors are fire resistant and maintain the fire rating of the material they are passing through.

Different types of doors and floors require specific firestopping systems and each system needs to be understood so it’s suitable for its application.

Our experts will take the confusion out of fire stopping and give you the peace of mind that every aspect of your structure is protected from fire.

For more information, please visit www.sigtechnicalinsulation.co.uk 5

Page 6: Fire Protection

Fire Protection Overview

6

Page 7: Fire Protection

7

Copyright Promat 2013

Page 8: Fire Protection

Fire Stopping Products

Ablative coated batts are slabs of high density rock wool with a white endothermic, ablative coating.ApplicationDesigned to stop the spread of fire through openings in fire resistant walls and floors which are used for the passage of buildings and communications services.

Intumescent Fire and Acoustic Sealant is supplied in either 310/600ml foils or 5 litre tubs and has excellent adhesion to most types of surfaces. The sealant cures in air to form a non-hardening, tack-free seal, preventing the passage of smoke, toxic gases and fire.ApplicationIntumescent Fire and Acoustic Sealant is suitable for sealing small gaps and holes in applications requiring up to 240 minutes fire resistance.

Loadbearing Fire Compound is a specially formulated gypsum based compound, which is mixed with water to be trowelled or poured around service penetrations.When set, Loadbearing Fire Compound becomes a hard material with a white matt finish. The actual surface finish of the set product is dependent upon treatment at the time of application.ApplicationLoadbearing Fire Compound is used to provide a fire seal around service penetrations in walls and floors. The formless nature of the fire compound prior to setting allows it to be introduced between services and so create a complete void free seal, including around bunches of cables.

Ablative Coated Batts

Intumescent Fire and Acoustic Sealant

Loadbearing Fire Compound

For more information, please visit www.sigtechnicalinsulation.co.uk8

Page 9: Fire Protection

For more information, please visit www.sigtechnicalinsulation.co.uk

Fire Resistant Silicone Sealant is a one part alkoxy cure silicone with excellent unprimed adhesion to most building surfaces.ApplicationApplication of Fire Resistant Silicone Sealant is a simple process as the product is extruded from a cartridge loaded into a standard sealant gun. The depth of the joint will depend on the gap to be filled and the fire rating required (see Fire Rating).

Fire Resistant Silicone Sealant(310ml)

High Pressure Exerting Mastic is an easy to apply waterborne acrylic emulsion sealant containing graphite. It expands at temperatures above 135º C sealing around various penetrations and services to prevent the passage of smoke and flames.ApplicationHigh Pressure Exerting Mastic is recommended for use where a flexible and durable fire resistant seal is required.Suitable applications include:• Combustible and non-combustible pipes• Cables (single cables or bunches of cables)• Other permanent services• Suitable for masonry walls

High Pressure Exerting Mastic (310ml Cartridge)

9

Page 10: Fire Protection

Fire Protection Products

Ultra Universal Pipe Wrap is an innovative and cost effective product for the fire stopping of plastic pipe penetrations, replacing traditional products already on the market, such as Pipe Collars. The product reinstates the fire rating of a construction and prevents fire spread from one compartment to another.ApplicationUltra Universal Pipe Wrap is suitable for use on plastic pipes for all walls and floors.

Insulated Fire Sleeves provide thermal, noise and fire benefits with an added intumescent effect. Use of Insulated Fire Sleeves makes a complex task simple.ApplicationInsulated Fire Sleeves are intended for use on Copper, Mild Steel, Polypropylene and PVC pipes and can provide 1⁄2, 1 and 2 hour fire resistance.

Expansion Joint Strips are highly compressible, flexible, fire resistant seals which are used where movement joints are formed in the structure of a building.ApplicationExpansion Joint Strips are ideal for sealing movement joints at junctions between compartment walls and floors and within walls and floors. Their flexibility makes them suitable for use in a variety of configurations.

Universal Pipe Sleeve is a revolutionary product incorporating the performance benefits of Ultra Universal Pipe Wrap, as well as a wider scope of application. This provides a cost effective fire stop for all plastic pipes, moving away from traditional products already on the market, such as Pipe Collars and Pipe Wraps.ApplicationUltra Universal Pipe Sleeve is a unique scored wrap, flexible and easy to install on both phenolic insulated and plastic pipes.

Ultra Universal Pipe Wrap

Insulated Fire SleevesExpansion Joint Strips

Ultra Universal Pipe Sleeve

For more information, please visit www.sigtechnicalinsulation.co.uk10

Copyright Promat 2013

Page 11: Fire Protection

For more information, please visit www.sigtechnicalinsulation.co.uk

Intumescent Pillows have been tested to BS 476:part 20 to provide up to 4 hours fire protection to metal services and cables passing through fire resisting compartment floors and walls. ApplicationUnder fire conditions, Intumescent Pillows expand several times their original volume to form an effective seal around service penetrations.Intumescent Pillows are suitable for use with:• Metal pipework• Cable trays• Electrical trunking (inside and outside)

Multi-Cable Firestop has been developed to effectively seal cable bunches in electrical trunking and cable trays, where they pass through fire rated walls and floors. Tested to BS476 Part 20, Multi-Cable Firestop will provide up to 4 hours fire protection.ApplicationMulti-Cable Firestop is a compressible fire retardant foam which is laminated both sides with a graphite based intumescent polymer. Multi-Cable Firestop is supplied in sections measuring 60mm wide x 30mm thick x 1000mm long.

Fire Pillows

Multi-Cable Firestop

Speedline Putty Pads are intumescent, mouldable putty pads designed to easily fit socket boxes to reduce sound travel through dry walls. The pads also provide fire resistance while maintaining the acoustic integrity of the wall. The strong, malleable putty avoids accidental tearing or puncturing, while offering flexibility during fitting.Permitted to be used as a mechanism of sealing electrical service penetrations such as sockets in Robust Detail timber frame and metal frame separating walls.ApplicationSpeedline Putty Pads are cost effective, easy to use and reduce waste. The putty pad is supplied as a one-size-fits-all strip on a reel, suitable for single and double sockets in both residential and commercial applications.Speedline Putty Pads also offer optional application methods, suitable for use inside the socket or externally.

Speedline Putty Pads

11

Page 12: Fire Protection

Ablative Coated Batts are designed for sealing around service penetrations in multiple substrates, as well as void filling. Used as a ‘head-of-wall’ barrier to extend the fire resistance and acoustic performances of masonry walls that finish at suspended ceiling height, up to the concrete soffit above.

Voids of up to 20m in length and 1.2m in height can be sealed. In addition, blank seals of up to 2880mm x 2400mm can be formed in either dry walls or masonry walls, or up to 600mm x 600mm in concrete floors.

Standard sizesLength mm Width mm Thickness mm

1200 600 601200 600 50

ROCKWOOL 50mm Ablative Coated BattHead of Wall Acoustic Data

Gap RwFull scale blank wall test 3m x 2.9m wide x 240mm thick 58

50mm Ablative Coated Batt 300mm deep at head of wall - Single layer - full wall width 3750mm Ablative Coated Batt 300mm deep head of wall - Double layer-full wall width, fitted into wall flush both sides 48

ROCKWOOL 60mm Ablative Coated BattHead of Wall Acoustic Data

Gap RwFull scale blank wall test 2.92m x 3.87m wide 53

60mm Ablative Coated Batt 100mm head of wall - Single layer - full wall width 3860mm Ablative Coated Batt 100mm head of wall - Double layer - full wall width & air gap 60mm 52

60mm Ablative Coated Batt 300mm head of wall - Single layer - full wall width 3360mm Ablative Coated Batt 300mm head of wall - Double layer - full wall width & air gap 60mm 50

60mm Ablative Coated Batt 300mm head of wall - Double layer - full wall width with RWA45 (50mm) in the 60mm gap between batts 52

Ablative Coated Batt

For more information, please visit www.sigtechnicalinsulation.co.uk

General benefits:• Excellent fire resistance from single thickness Batt• Suitable for sealing large wall and floor voids containing most commonly used services• Can be used as a blank seal and a head of wall seal• Tested for use in masonry and dry wall constructions• Lightweight and simple installation• Maintenance free• 180kg/m3 density base material provides additional benefits of a smoke and acoustic seal• Tested for air tightness

12

Page 13: Fire Protection

Ablative Coated Batt

For more information, please visit www.sigtechnicalinsulation.co.uk

Typical Performance ROCKWOOL 60mm Ablative Coated Batt

Service Type60 Minutes 90 Minutes 120 Minutes

Integrity Insulation Integrity Insulation Integrity InsulationBlank seal up to 1200mm x 600mm ˇ ˇ ˇ ˇ ˇ ˇ

Blank seal up to 2.4m x 2.8m* ˇ ˇ ˇ ˇ

Single/bunched cables ≤61mm ˇ ˇ ˇ C ˇ CBunched cables ≤100m with High Pressure Mastic ˇ ˇ

Cable trays ≤480mm ˇ ˇ ˇ C ˇ CSteel pipes ≤168mm lagged with Fire Tube ˇ ˇ ˇ ˇ ˇ ˇ

Steel pipes ≤168mm unlagged ˇ ˇ ˇ

Copper pipes ≤108mm lagged with Fire Tube ˇ ˇ ˇ ˇ

Copper pipes ≤108mm unlagged ˇ ˇ ˇ

Circular steel duct ≤360mm lagged with Fire Duct ˇ ˇ ˇ ˇ ˇ ˇ

Square steel duct ≤400mm lagged with Fire Duct ˇ ˇ ˇ ˇ ˇ ˇ

PVC & HDPE Pipes ≤40mm with High Pressure Mastic ˇ ˇ

PP & HDPE Pipes ≤160mm with Fire Sleeve ˇ ˇ

PVC ≤110mm with Fire Sleeve ˇ ˇ ˇ ˇ ˇ ˇ

ABS ≤110mm with Fire Sleeve ˇ ˇ ˇ ˇ

Fire Dampers 1000 x 1000mm ˇ ˇ ˇ

*See Rockwool Technical Manual for specific sizes and maximum fire ratings. Apertures over 1.2m x 1.2m require Fire Pro Glue to seal between the batts. Head of Wall applications have been assessed for up to 1.2m x 20m for 60 minutes Integrity and insulation performance using ablative acoustic sealant.✓ C using 1mm thick coatback along 100mm of service item either side of the seal

Ablative Coated Batts are manufactured by a number of suppliers, including Promat UK Limited and ROCKWOOL® Limited

13

Page 14: Fire Protection

Loadbearing Fire Compound is ideal for use around pipes and ducts where these penetrate compartment or separating walls or floors. Even when fully cured Loadbearing Fire Compound permits the provision of additional or replacement services without the need to replace the complete installation, yet still retaining its strength properties.

General benefits:• Smoke seal• Good acoustic barrier• Suitable for making good around most types of service penetrations• Loadbearing (see Loadbearing table for details)• Simple installation• No smoke emission• Maintenance free• Unaffected by humidity• Suitable for floors in riser cupboards etc

Loadbearing Fire Compound

For more information, please visit www.sigtechnicalinsulation.co.uk

Performance in masonry (non-reinforced) supporting walls

Minimum compound thickness

Maximum aperture dimensions

Fire resistance (min)Integrity Insulation

75mm 1000 x 400mm 60 6075mm 600 x 400mm 120 12075mm 400 x 400mm 240 240

100mm 1200 x 600mm 60 60100mm 800 x 600mm 120 120100mm 600 x 600mm 240 240

Non-reinforced sealsFirestop compound

Thickness in mm Fire rating in hours Maximum opening width x any linear length mm Load bearing capacity in kn

75mm 2 500mm 2.5kn (UDL)100mm 4 750mm 2.5kn (UDL)

Simply reinforced sealsFirestop compound

Thickness in mm Fire rating in hours Maximum opening width x any linear length mm Load bearing capacity in kn

100mm 4 Up to 1500mm 2.5kn (UDL)Load bearing performance in line with BS6399 for workspaces and cupboards (This is general guidance, advice from Rockwool Technical should always be obtained)

Performance in masonry (reinforced) floors

Minimum compound thickness

Maximum aperture dimensions

Fire resistance (min)Integrity Insulation

75mm 1000 x 400mm 60 6075mm 600 x 400mm 120 12075mm 400 x 400mm 240 24075mm 800 x 800mm 360 360

100mm 1400 x 1200mm 60 60100mm 1400 x 1000mm 120 120100mm 1200 x 1000mm 240 240100mm 1000 x 1000mm 360 360

1. For steel and copper pipe penetrations, integrity performance only2. For plastic pipe penetrations, use in conjunction with Ultra Universal Pipe Wrap

14

Page 15: Fire Protection

In addition to Rockwool Fire Compound, SIG Technical Insulation also offer Promat Promaseal Extra Strength, which offers excellent fire resistance, strength, versatility and acoustic performance:

For more information, please visit www.sigtechnicalinsulation.co.uk

Acoustic performanceThickness of Compound (mm) Weighted Sound Reduction Index (Rw)

75 39db100 46db150 51db

Coverage of compoundThickness of Compound (mm) Number of bags/m2

75 3.15100 4.20150 6.30

Ratio: A bag of compound to 10 litres water (3:1) volume. Vary to suit site conditions

Typical PropertiesFlexural Strength Frupture at 28 days

Compound: Water ratio 2.5:1 5.2 N/mm2

Compressive Strength at 28 daysCompound: Water ratio 2.5:1 - pourable 14.0 N/mm2

Compound: Water ratio 3.0:1 - stiff 21.0 N/mm2

* Compound: water ratio by volumeFire Performance

Depth of seal (mm) Insulation (mm) Integrity (mm)Cables & Pipework through

floors (EN 1366-3) 100 231 240

Ductwork Dampers through floors through walls

(BS 476 Part:20)9082

225164

240240

Loadbearing Capacity at 48 hoursUn-reinforced floor seal, mix ratio 2.5:1

Span of Seal (mm) Span/Depth Ratio (100mm deep floor seal)

Tensile Failure Pressure (kN/m2) (one way spanning) *Safe Working Load (kN/m2)

90012001500

9:112:115:1

302515

1085

15

Loadbearing Fire Compound

Page 16: Fire Protection

Intumescent Acrylic Sealant is suitable for most applications but Silicone Sealant would be required for service temperatures over 70°C or where increased joint movement capability is needed.

Intumescent Fire and Acoustic Sealant

For more information, please visit www.sigtechnicalinsulation.co.uk

CoverageEach cartridge/sausage is intended to provide the following application rates:

Joint size (mm) Depth of sealant (mm) Yield per cartridge (m) Yield per sausage (m)10 10 3.10 5.9020 15 1.03 1.9530 20 0.51 0.95

Aerated concrete/Blockwork walls

Min wall width (mm)

Max. joint width (mm)

Sealant Depth (mm) Backing

Fire ResistanceType of Seal Integrity Insulation

150 10 10 Polyethylene foam backing rod Single 200 166150 10 10 Polyethylene foam backing rod Double 265 265150 15 15 Polyethylene foam backing rod Single 227 227150 15 15 Polyethylene foam backing rod Double 265 230150 30 30 Polyethylene foam backing rod Single 240 233150 30 30 Polyethylene foam backing rod Double 265 265200 50 25 Ethafoam backing rod Single 245 82

Aerated concrete floors

Min floor depth (mm)

Max. joint width (mm)

Sealant Depth (mm) Backing

Fire ResistanceType of Seal Seal location Integrity Insulation

230 50 25 Ethafoam backing rod Single Bottom 155 105250 30 15 Ethafoam backing rod Single Bottom 243 65250 20 10 Polyethylene foam backing rod Single Top 155 47250 25 15 Polyethylene foam backing rod Single Top 240 73250 50 25 Polyethylene foam backing rod Single Top 240 92

Note: other performances are available - please contact your local branch of SIG Technical Insulation for details

Acoustic PerformanceWeighted Sound Reduction index (Rw) of up to 57db.Dependant on:• Type of construction• Type of seal backing• Size of joint

Smoke SealIntumescent Fire and Acoustic Sealant will inhibit the passage of smoke

Intumescent Fire and Acoustic Sealant is manufactured by a number of suppliers, including Promat UK Limited and ROCKWOOL® Limited

ROCKWOOL® Intumescent Fire and Acoustic Sealant must be used on ROCKWOOL® Ablative Coated Batts

16

Page 17: Fire Protection

Fire Resistant Silicone Sealant is designed to be used in joints with high movement capability or where they are formed between dissimilar substrates, eg. steel and masonry.

Fire Resistant Silicone Sealant (310ml)

For more information, please visit www.sigtechnicalinsulation.co.uk

CoverageFire Resistant Silicone Sealant is available in 310ml cartridges. One cartridge will provide the following coverage rates:

Joint size (mm) Metres per litre6 x 6 27.759 x 6 18.50

12 x 9 9.2518 x 12 4.7525 x 10 4.0

Fire ratingJoint Size

(mm)Sealant

Depth (mm) Backing material Dimensions Single or dual seal

Integrity (in mins)

Insulation(in mins)

15 10 PE 25mm diameter Single 240 12015 10 Mineral wool (density 90kg/m2) 15mm thick x 10mm depth Dual 240 24025 15 PE 30mm diameter Single 240 12040 25 Mineral wool (density 90kg/m2) 40 x 25mm depth Dual 240 240

ColoursWhite

SpecificationOnce installed, Fire Resistant Silicone Sealant should provide up to 4 hours of fire protection in all joints up to 40mm.Installation must be fully in accordance with manufacturer’s instructions.The quantity contained in each cartridge is 310ml.Once installed the sealant can offer up to 25 years service (if correctly applied).

Fire Resistant Silicone Sealant is manufactured by a number of suppliers, including Promat UK Limited and ROCKWOOL® Limited

17

Page 18: Fire Protection

Performance & propertiesProvides up to 4 hours fire protection in joints up to 30mm

High Pressure Exerting Mastic (310ml)

For more information, please visit www.sigtechnicalinsulation.co.uk

Fire resistance in 2 hour plasterboard wallService

penetrationHole size

(mm) Design of joint Depth of sealant/mineral wool (mm)

Fire integrity (mins)

55mm diameter HDPE/PVC pipe 100 x 100 25mm annular joint in Patrice fixed coated panel

(50mm thick) on both sides of wall 40 120

110mm HDPE/PVC pipe 150 x 150 25mm annular joint in Patrice fixed coated panel on both sides of wall 40 120

Fire resistance in 150mm thick masonry wallService

penetration Hole size (mm) Design of joint Depth of sealant/mineral wool (mm)

Fire integrity (mins)

Fire insulation (mins)

Cable tray (150 x 25mm) 200 x 100 Sealant/mineral wool/sealant 40/50 120 120

Cable bunch (100mm diameter) 150 diameter Sealant/mineral wool/sealant 40/50 120 120

PVC pipe (110mm) 162 diameter Sealant/mineral wool/sealant 40/50 120 120ABS (50mm) 150 diameter Sealant/mineral wool/sealant 40/50 120 120

Fire resistance in concrete floorsService

penetrationHole size

(mm) Design of joint Depth of sealant/mineral wool (mm)

Fire integrity (mins)

110mm HDPE/PVC pipe 160 Mineral wool shutter 125mm thick/sealant (Mineral wool shutter removed before test) 75 90

18

Page 19: Fire Protection

Ultra Universal Pipe Wrap

For more information, please visit www.sigtechnicalinsulation.co.uk 19

Ultra Universal Pipe Wrap is capable of expanding over 30 times its thickness to crush and close off the pipe in a fire situation, forming a solid char and preventing the passage of fire and smoke to the adjacent compartment.

Ultra Universal Pipe Wrap is suitable for use on plasticpipes for all walls and floors.

DimensionsLength: 1000mmWidth: 130mmThickness: 2.1mmPack qty: 5

Performance Benefits• Provides fire rating of up to 4 hours to BS-EN 1366-3*• Provides integrity & insulation• One size fits all pipes• Suitable for use with any ablative coated batt• One wrap can replace two collars• Quick and easy to cut and install• Minimal waste• The pipe wrap is solid and stable even when fully expanded• Environmentally friendly – halogen free*Not recommended for use below -5°C

Applications: One Size Fits All and VersatileScope of types of penetrations and required number of laps with Ultra Universal Pipe Wrap.

Types of pipes and maximum diameters covered (mm)PVC MDPE & HDPE ABS PP

Φ =< 115 115 < Φ =< 170 Φ =< 110 Φ =< 115 Φ =< 110

60 Min.

Wall

1 lap 2 laps 1 lapFloor

120 Min.

WallFloor

Inte

grity

CAD Details: Simple and Easy to Install

Ultra Universal Pipe Wrap can be used in conjunction with Rockwool ablative coated batts and loadbearing compound as a recognised system

Ultra

Page 20: Fire Protection

Ultra Universal Pipe Wrap

For more information, please visit www.sigtechnicalinsulation.co.uk

Applications: Wall/Floor SectionDrywall = 100-125 Concrete Wall = 100-125 Fire Batt (Single Layer) Floor => 100mm

Gap15mm

Centred Sealant

Wrap

Gap15mm

Centred Sealant

Wrap

Sealant

Gap30mm

Gap30mm

Centred FireCompound

Gap30mm

Centred FireCompound

Tightlyfitting

FireCompound

Centred Bottomed

Sealant

Tightlyfitting

Centred

Gap30mm

FireCompound

Bottomed

Gap15mm

Centred Sealant

Wrap

Gap15mm

Centred Sealant

Wrap

Sealant

Gap30mm

Gap30mm

Centred FireCompound

Gap30mm

Centred FireCompound

Tightlyfitting

FireCompound

Centred Bottomed

Sealant

Tightlyfitting

Centred

Gap30mm

FireCompound

Bottomed

Gap15mm

Centred Sealant

Wrap

Gap15mm

Centred Sealant

Wrap

Sealant

Gap30mm

Gap30mm

Centred FireCompound

Gap30mm

Centred FireCompound

Tightlyfitting

FireCompound

Centred Bottomed

Sealant

Tightlyfitting

Centred

Gap30mm

FireCompound

Bottomed

Gap15mm

Centred Sealant

Wrap

Gap15mm

Centred Sealant

Wrap

Sealant

Gap30mm

Gap30mm

Centred FireCompound

Gap30mm

Centred FireCompound

Tightlyfitting

FireCompound

Centred Bottomed

Sealant

Tightlyfitting

Centred

Gap30mm

FireCompound

Bottomed

Drywall = 125-130 Concrete Wall = 125-130 Fire Batt (Double Layer) Floor => 150mm

Gap15mm

Centred Sealant

Wrap

Gap15mm

Centred Sealant

Wrap

Sealant

Gap30mm

Gap30mm

Centred FireCompound

Gap30mm

Centred FireCompound

Tightlyfitting

FireCompound

Centred Bottomed

Sealant

Tightlyfitting

Centred

Gap30mm

FireCompound

Bottomed

Gap15mm

Centred Sealant

Wrap

Gap15mm

Centred Sealant

Wrap

Sealant

Gap30mm

Gap30mm

Centred FireCompound

Gap30mm

Centred FireCompound

Tightlyfitting

FireCompound

Centred Bottomed

Sealant

Tightlyfitting

Centred

Gap30mm

FireCompound

Bottomed

Gap15mm

Centred Sealant

Wrap

Gap15mm

Centred Sealant

Wrap

Sealant

Gap30mm

Gap30mm

Centred FireCompound

Gap30mm

Centred FireCompound

Tightlyfitting

FireCompound

Centred Bottomed

Sealant

Tightlyfitting

Centred

Gap30mm

FireCompound

Bottomed

Gap15mm

Centred Sealant

Wrap

Gap15mm

Centred Sealant

Wrap

Sealant

Gap30mm

Gap30mm

Centred FireCompound

Gap30mm

Centred FireCompound

Tightlyfitting

FireCompound

Centred Bottomed

Sealant

Tightlyfitting

Centred

Gap30mm

FireCompound

Bottomed

Through fl oor penetrations Ultra Universal Pipe Wrap can be utilised at 65mm to give the required fi re performance.

Installation: One Size Fits All and Versatile

Apply the wrap aroundthe pipe, and tape over it.

Measure the required length for the pipe and cut the wrap

Flush

Yes Yes No

Overlapped Open

Drywall/Concrete Wall/Masonry Wall

Slide the wrap into the wall Fill the annular space with fire rated sealant or fire compound*Fire compound cannot be used on drywall.

Fire Compound

Sealant

1.

Wall2. 3. or

Inte

grity

60 M

in12

0 M

in

20

Page 21: Fire Protection

Ultra Universal Pipe Wrap

For more information, please visit www.sigtechnicalinsulation.co.uk 21

Ultra Universal Pipe Sleeve is a unique scored wrap,flexible and easy to install on both phenolic insulated andplastic pipes.

DimensionsLength: 1000mmWidth: 130mmThickness: 2.1mmPack qty: 5

Performance Benefits• Provides a Fire Rating of : 2 hours, BS-EN 1366-3• Eliminates condensation and maintains vapour layer• One size fits all phenolic insulated pipework and plastic pipes• ‘No cut back’ of phenolic insulation is required• Unique scored sleeve, soft and easy installation• Cost effective• One sleeve can replace two collars• Solid and stable, even when fully expanded• Suitable for use with any ablative coated batt• Minimal waste• Environmentally friendly – halogen free

Applications: Scope for Insulated PipeInsulation is limited only for Phenolic insulation.

Pipe O.D.

(mm)

InsulationThickness

(mm)Drywall120 min.

Batt*1 60 min

(T=50mm)

Batt*2 120 min.

(T=60mm)

Batt*3 120 min.

(T=100mm)

Concrete wall

120 min.

Concrete floor

120 min.

Copper

15 15 ˇ ˇ ˇ ˇ ˇ ˇ

42 15 ˇ ˇ ˇ ˇ ˇ ˇ

108 15 ˇ ˇ ˇ ˇ ˇ ˇ

108 40 ˇ ˇ ˇ ˇ ˇ ˇ

Steel168 15 ˇ ˇ ˇ ˇ ˇ ˇ

168 40 ˇ ˇ ˇ ˇ ˇ ˇ

Batt*1: Thickness = 50mm, Density 160kg/m3

Batt*2: Thickness = 60mm, Density 180kg/m3

Batt*3: Thickness = 100mm <50mm*2>, Density 160kg/m3

*Terms and Condition

Page 22: Fire Protection

Ultra Universal Pipe Sleeve

For more information, please visit www.sigtechnicalinsulation.co.uk

Applications: Installation for Insulated Pipe

Cross Section

The reinforced foil tape needs to be appliedon the following locations.

1. Over the UPS / intumescent wrap.

2. Directly over the phenolic tube itself at theboth sides of the wall, upper side of fl oor.

Gap15mm

ReinforcedFoil Tape

Centred

Dry Wall

Sealant

UPS

Sealant Copper orSteel pipePhenolic

Insulation

Gap30mm

Centred

Concrete Wall

FireCompound

Tightlyfitting

Centred

Fire Batt Concrete Floor

Gap30mm

FireCompound

Bottomed

Phenolic Insulation

Hard Char

Copper or Steel Pipe

Reinforced Foil TapeUltra UniversalPipe Sleeve

22

Page 23: Fire Protection

Ultra Universal Pipe Sleeve

For more information, please visit www.sigtechnicalinsulation.co.uk 23

Ultra Universal Pipe Wrap/ Sleeve can be used in conjunction with Promaseal Extra Strength Compound as a recognised system

Fire stopping service penetrations through concrete floors - Promaseal Fire Compound with plastic pipe penetration

· Up to 240 minutes fire resistance in concrete floors. Refer to CERTIFIRE CERTIFICATE OF APPROVAL No CF 425.

· Promat Technical Services must always be consulted for specific advice where penetrations are involved.

3· The seal must be installed in floors or walls which are minimum 100mm thick, or the the thickness of the seal, whichever is greater. The minimum density for the concrete of the floor or wall is 780kg/m 3and for walls made of concrete blocks is 600kg/m .

· Penetrating services must be rigidly supported no further than 500mm from the seal faces on both sides of the seal.

3· Rock wool slab (minimum 50mm thick x 140kg/m ) may be used as permanent shuttering for pouring the compound into the opening and around penetrations.

· Plastic pipe penetrations should be firestopped with Promaseal Pipewrap, available in a range of sizes up to 160mm plastic pipe diameter.

· Promaseal Pipewraps are folded around the pipe and secured into position using the adhesive tab.

· The Promaseal Pipewrap is then slid along the pipe and positioned to tight-fit into the prepared opening.

· The Promaseal Pipewrap must then be grouted into position using Compound.

NOT FOR PRODUCTION DESIGN SKETCH ONLYDO NOT SCALE VIEW TOLERANCES General ± 1mm DIMENSIONS IN mmA3 LANDSCAPE

Gap 30mm

Concrete fl oor or wall thickness 150mm<

Rockwool slab (minimum 50mm x 140kg/m3)

Bottomed Ultra Universal Pipe Wrap/Sleeve

Promat Promaseal Fire Compound

Penetrating services = Plastic pipes

CAD Details: Simple and Easy to Install

Ultra Universal Pipe Sleeve can be used in conjunction with Rockwool ablative coated batts and loadbearing compound as a recognised system

“ SIG have brought to market a new and useful Universal Pipe Wrap and Sleeve, it has been tested on both plastic pipes and around some insulation materials as an integrity fi re barrier, making it a handy versatile type of product.Rockwool have looked at the testing of this product in some detail, based on this we see it as suitable option solution for plastic pipes and some insulated pipes that pass through Rockwool coated batts”

“ These are very often problem applications for fi restopping purposes, and this seems to be a nice simple one stop type solution”

Bob WestcombeRockwool UK FireProtection Manager

Testimonial

Ultra Pipe Sleeve(130 mm wide)

Page 24: Fire Protection

Insulated Fire Sleeves

For more information, please visit www.sigtechnicalinsulation.co.uk

For insulated pipes, it is necessary to remove the insulation at point of penetration to enable standard pipe collars to close plastic pipes. This removal of insulation results in condensation on cold pipes and loss of thermal performance on hot pipes.

Insulated Fire Sleeves combats this problem by providing both fire stopping and thermal insulation.

General benefits:• Quick, simple and accurate installation• Maintains pipe insulation at penetration points• Supplied with integral vapour barrier• No mastic or ancillaries required• Excellent thermal and acoustic insulation• Non-combustible

DimensionsInsulated Fire Sleeves are supplied 300mm long. They are manufactured to fit a range of standard pipe sizes, from 17mm to 169mm O.D. and standard thicknesses of 25mm to 100mm.For un-insulated pipes, a thickness of 25mm is required to maintain the fire rating. Insulated Fire Sleeves should be installed to the same thickness as the pipe insulation (min 25mm thick).

Service TemperaturesInsulated Fire Sleeves are used to fire stop pipe work operating at temperatures between 0°C and 180°C. At low temperatures, care should be taken to maintain the vapour barrier.

Test Data

Pipe DescriptionCompartment Construction

2h Batt 2h Blockwork 12h Plasterboard 2h Solid FloorCopper Ø 15-160mm ˇ ˇ ˇ

Mild Steel Ø 15-160mm ˇ ˇ ˇ

Polypropylene Ø 15-26mm ˇ ˇ ˇ ˇ

PVC Ø 15-80mm ˇ ˇ

Insulated Fire Sleeves are available from a number of suppliers, including: ROCKWOOL® Limited, Tenmat and PFC Corofil

24

Page 25: Fire Protection

Expansion Joint Strips

For more information, please visit www.sigtechnicalinsulation.co.uk 25

Expansion Joint Strips consist of layers of intumescent material bonded to class O foam and have been successfully fire tested and assessed to provide up to 240 minutes in joints, walls and floors.

Expansion Joint Strips are available from a number of suppliers, including: Promat UK Limited, ROCKWOOL® Limited and Polyseam.

Typical properties

Strip size Maximum joint width in mm (g)

Minimum seal width in mm (t)

Minimum seal depth in mm (d)

Integrity(minutes)

4009053 10 12 12 1204009055 20 29 12 1204009039 25 32 20 1204009040 35 53 20 1204009041 50 61 35 1204009042 75 90 50 1204009043 100 126 100 1204009044 120 147 125 1204009045 150 170 100 120

Application technique: Compressed into gap/joint such that the multi-layers/banding are visible.

Copyright Promat 2013

Page 26: Fire Protection

Intumescent Pillows

For more information, please visit www.sigtechnicalinsulation.co.uk

Intumescent Pillows are simply packed tightly in between penetrating services and the wall. In a floor, pillows are additionally supported by means of a mesh support system.

General benefits:• Simple to install• Easy to remove and reinstate whilst changing services• Maintenance free• Dry system

Pillow SizesPillow size (mm) Approximate number

300 x 200 x 30 165 per m2 opening300 x 150 x 30 220 per m2 opening300 x 100 x 30 330 per m2 opening300 x 50 x 30 660 per m2 opening

Performance in masonry supporting walls

Method of support/installation

Maximum aperture dimensions

Fire resistance (min)Integrity Insulation

Friction fitted 850 x 850mm 120 120Friction fitted 600 x 600mm 240 120

Minimum density of masonry supported walls - 650kg/m3 300mm bag length to be laid horizontally in wall void. Bags should be laid centrally within wall thickness.

Performance in concrete floors

Method of support/installation

Maximum aperture dimensions

Fire resistance (min)Integrity Insulation

Wire basket 850 x 850mm 120 120Wire basket 600 x 600mm 240 120

300mm bag length to be laid vertically in floor void.

Performance in masonry supporting walls

Method of support/installation

Maximum aperture dimensions

Fire resistance (min)Integrity Insulation

Friction fitted 850 x 850mm 120* 120*

*Product performance is dependent on matching performance of plasterboard wall system. Void in plasterboard should be fully ‘framed out’ with steel studs or similar 300mm bag length to be laid horizontally in wall void. Bags should be laid centrally within wall thickness.

Fire Pillows are available from a number of suppliers, including Promat UK Limited and ROCKWOOL® Limited

26

Page 27: Fire Protection

Multi-Cable Firestop

For more information, please visit www.sigtechnicalinsulation.co.uk 27

General benefits:• Simple to install• Cables can be easily added or removed• No de-rating of cables required• Maintenance free• Dry system

Fire Rating

Services and support

Surrounding penetration

seat

Width of fire stop for each Coated Batt

(mm)

Maximum void height (mm)

(no. of fire stop plies)

Fire resistance integrity (min)Seat in a masonry

wall

Seat in a plasterboard

wall

Seat in a concrete

floorCables

secured to appropriately

supported perforated steel

cable trays/ladders (max.

width 150mm)

Single 60mm ROCKWOOL®

Ablative Coated Batt

Double 60mm ROCKWOOL®

Ablative Coated Batt

60

60

25 (1)55 (2)80 (3)

25 (1)55 (2)80 (3)

180120120

240240240

606060

180120n/a

240240n/a

Cables within PVC

trunking (maximum

100 x 100mm)

Double 60mm ROCKWOOL®

Ablative Coated Batt with no air

gap

60 180 (1) 240 60 -

Page 28: Fire Protection

Speedline Putty Pads

For more information, please visit www.sigtechnicalinsulation.co.uk

Speedline Putty Pads comply with building regulations Part E and Part B.

With a fire rating of two hours in dry walls (to BS476 part 20), Speedline Putty Pads also achieve an acoustic rating of up to 69dB Rw, ensuring that the safety and performance of the drywall construction are maintained.

General benefits:• Maintains acoustic integrity of the wall• Use in PVC & Metal boxes• Provides 2 hour fire resistance• Robust Details compliance in timber frame & metal frame separating walls• Easy to use• Fast to fit• Minimal waste• Easy to stock: one reel fits all• Reduced damage on site and in transit• Cost effective – labour and time saving

SIG also produces a wide variety of bespoke insulation products to customer specification and also manufactures a range of fire, thermal and acoustic products.

Fire Stop StripFor medium size linear gaps in buildings.

Fire Stop BlocksFor apertures in buildings, especially the flutes of metal profiles.

Wall Cavity Fire BarrierFire Barrier Slab & Strip For all cavity walls and curtain walls, horizontal and vertical use.

Raised Access Floor Fire BarrierFor the voids beneath Raised Access Floors.

Partition Head Fire BarrierFor large gaps above partitions and masonry walls.

FireFloor System 2Fire protection system for timber floors.

Cavity Fire CloserTo close masonry cavities, especially around door and window openings.

Party Wall Fire CloserSemi-rigid mineral wool to polythene DPC Cavity Closers for the junctions of party walls.

Horizontal Fire CloserWith polythene DPC Cavity Tray and up to 2 hour fire rating. Includes support fixings.

Ventilated Rainscreen Fire BarrierPolythene enclosed mineral wool barrier for rainscreen systems.

28

Page 29: Fire Protection

Fire Duct System

For more information, please visit www.sigtechnicalinsulation.co.uk 29

Fire resistant ducts are the best way to ensure fire safety in HVAC installations as they provide performance from beginning to the end of the duct system lifetime. Rockwool, Isover, Knauf and Promat provide solutions for metal ventilation ducts that secure fire resistance as well as meeting thermal and acoustic requirements.

Fire Duct products can be used to provide fire protection to horizontal, vertical, rectangular, circular, ventilation and smoke extract steel ductwork fully in accordance with BS 476 – 24, ducts ‘Type A’ and ‘Type B’, ‘Fire outside duct’ and ‘Fire inside duct’.

Fire Duct SlabSize: 1200 x 2000mmThicknesses: 40 & 90mmFacing: reinforced aluminium foilSurface spread of flame: Class 1 to BS 476–7Non-combustibility: Class A1 to BSEN 13501-1(wall & ceiling linings)Thermal conductivity: 0.035 W/mK at 10°C

Fire Duct sectionDiameters: 60 to 356mmThicknesses: 40 and 90mm*Facing: reinforced aluminium foil

Fire Duct PSMFire Duct PSM is made of Fire Duct Slab with factorymachined grooves to suit specific duct diameters.Diameters: 406mm and aboveThicknesses: 40 and 90mm*Facing: reinforced aluminium foil* Some thicknesses of Fire Duct Section and Fire Duct PSMare not available for certain duct diameters

Hanger sectionsDiameter: 17mmThicknesses: 30, 40, 50 & 60mmFacing: reinforced aluminium foil

Notes to picture opposite1. Circular steel duct to DW/1442. Fire Duct Section/Fire Duct PSM3. M10 steel drop rods at 1500mm maximum centres4. Fire Duct Slab/Section - protection to hanger system5. 30 x 30 x 3mm minimum steel angle bearer

Page 30: Fire Protection

Fire resistancePerformance summary – Fire Duct Slab, Section and PSM

Thermal Conductivity Chart

Fire resistance (hours) Duct type

Required fire duct thickness

(mm)Joint options

Hangar protection Max duct size for mitre joint glued system

(mm)Fire duct

Slab (mm)Hangar

section (mm)½ HVAC & Smoke extract 40 BC 40 17 x 30 1500 x 1500½ Kitchen extract 40 BC 40 17 x 30 1500 x 15001 HVAC & Smoke extract 40 BC 40 17 x 40 1000 x 10001 Kitchen extract 90 ABC 40 17 x 40 1500 x 1500

1½ HVAC & Smoke extract 90 ABC 40 17 x 50 1200 x 12002 HVAC & Smoke extract 90 ABC 40 17 x 60 1000 x 1000

Knauf Rocksilk PyroDuct SlabRocksilk PyroDuct Slab is fully tested and certified to provide up to 2 hours fire protection to HVAC steel ductwork. It can be used in horizontal ducts, vertical ducts, ducts passing through compartment walls and floors and kitchen extracts. Rocksilk PyroDuct Slab is suitable for applications above clean rooms, within air plenums or for aesthetic purposes.

ThermalRocksilk PyroDuct has a thermal conductivity of 0.037 W/mK.

Thickness (mm) Length (mm) Width (mm) Slabs per pack Area per pack (m2)90 1200 600 2 1.4445 1200 600 4 2.88

Fire Duct System

For more information, please visit www.sigtechnicalinsulation.co.uk30

Page 31: Fire Protection

Fire Duct System

For more information, please visit www.sigtechnicalinsulation.co.uk 31

ISOVER solutions for providing fire resistance in HVAC using ULTIMATE mineral wool. U Protect solutions provide an easy to install and lightweight efficient solution for fire resistance in HVAC to BS 476: Part 24.Insulation Product Range

Product Thickness (mm) Width (mm) Length (mm) Slabs per pack m2 per pack Packs per pallet m2 per pallet

ULTIMATE™ Protect Slab

4.0 Alu 1

60 600 1200 6 4.32 12 51.8480 600 1200 5 3.60 12 43.20

100 600 1200 4 2.88 12 34.56ULTIMATE™ Protect Wired Mat 4.0 Alu 1

75 600 4000 2 4.80 18 86.40

120 600 2500 2 3.00 18 54.00

For rectangular ducts use U Protect 4.0 Alu 1 Slab and for circular ducts use U Protect 4.0 Alu Wired Mat. *Smoke extraction requires 2 hours fire protection. Note that for rectangular ducts these insulation thicknesses should be increased from 80mm as shown in the table to 90mm.

Declared Thermal Conductivity • 0.033 W/mK at 10 °C mean temperature.• 0.035 W/mK at 50 °C mean temperature.

• 0.040 W/mK at 100 °C mean temperature.• 0.047 W/mK at 150 °C mean temperature

Choose the insulation thickness Choose the appropriate thickness from the table below by selecting the desired duct type, fire rating, duct orientation and fire location.

Isover ULTIMATE™ Protect thickness table

Rect

angu

lar D

uct

Fire location Fire class Duct orientation1 hour 2 hourFire inside duct

Inside 60mm 80mm* Horizontal80mm 100mm Vertical

Fire outside duct

Outside 60mm 80mm* Horizontal60mm 80mm* Vertical

In case both fire locations needs to be covered

Both 60mm 80mm* Horizontal80mm 100mm Vertical

Use of 1 product for both duct orientationsOutside 60mm 80mm* BothInside 80mm 100mm

Use of 1 product for all casesBoth 80mm 100mm Both

Circ

ular

Duc

t

Fire location Fire class Duct orientation1 hour 2 hourFire inside duct

Inside 75mm 120mm Horizontal75mm 120mm Vertical

Fire outside duct

Outside 75mm 120mm Horizontal75mm 120mm Vertical

In case both fire locations needs to be covered

Both 75mm 120mm Horizontal75mm 120mm Vertical

Use of 1 product for both duct orientationsOutside 75mm 100mm BothInside 75mm 120mm

Use of 1 product for all casesBoth 75mm 120mm Both

Page 32: Fire Protection

For more information, please visit www.sigtechnicalinsulation.co.uk32

Fire Duct System

PROMATECT® -L500 PROMATECT® - L500 is a non-combustible low density calcium silicate board, used for the construction of fire resistant ducts. It is a Class O product as defined in the Building Regulations.

Thickness (mm) Length x Width (mm)Approx weight (kg/m2)

Dry With approx 5% moisture20 2500 x 1200 10.0 10.525 2500 x 1200 12.5 13.130 2500 x 1200 15.0 15.835 2500 x 1200 17.5 18.440 2500 x 1200 20.0 21.050 2500 x 1200 25.0 26.352 2500 x 1200 26.0 27.460 2500 x 1200 30.0 31.5

Page 33: Fire Protection

33

Tunnel Liner and Ductliner

PassiveTecTM Tunnel Liner Our 30mm Tunnel Liner board has passed the most demanding tunnel test currently available. Tested at the Efectis laboratory in the Netherlands, it has achieved 3 hours against the RWS temperature curve, 3 hours against the HCM temperature curve and 4 hours against the ISO 834 temperature curves. These test standards cover all of the highest specifications likely to be required in tunnel lining fire protection.

The PassiveTecTM board has a uniquely high insulation performance hence it achieves more than the required standard of protection. In addition it is extremely stable when exposed to moisture or water. This is critical in the tunnel lining area where leakage and flash floods can occur regularly. Our team of fire engineers are ready to conduct specific tests as required by tunnel construction projects.

CertificationRWS 1350 Certified 180 mins

HCM Certified 180 mins

ISO 834 Certified 240 mins

Lineal thermal expansion a (°K-1) - 3,1x 10-5 (long) and- 4,1x 10-5 (tran)

Density 900 kg/m3 ± 10 %

Water diffusion resistance µ:3,5

Determination of compression behavior. Breaking load (N) 25213

CertificationBS EN1366 pt 1 & Pt 8 Certified

Type B Vertical : CLASSIFICATION: EI 120 (ve i→o)Type A Vertical : CLASSIFICATION: EI 120 (ve i→o) S

Type B Horizontal : CLASSIFICATION: EI 120 (ho i→o)Type A Horizontal: CLASSIFICATION: EI 180 (ho i→o) S

Type C : El 120 (ho) S 1500 Multi

Thermal conductivity (W/mk) 0,29Thermal resistance (m2.K/W) 0,1

Lineal thermal expansion a (°K-1) - 3,1x 10-5 (long) and- 4,1x 10-5 (tran)

Electrical surface resistance [kΩ] 5,1

PassiveTecTM Ductliner Our 30mm Ductliner board has achieved the highest standard of smoke evacuation and extraction duct protection. It is the only magnesium oxide board on the market with both EN 1366 part 1 and part 8 accreditation. At 30mm it is also thinner than any other competing solutions for 2 hours which is a huge advantage in the congested plenums. We are proud to have passed the smoke extraction standard at the maximum pressure level

Tested at European accredited laboratories that ensure compliance across the EU.

PassiveTecTM is a proven high performance range of Fibre Reinforced Magnesium boards owned by SIG and PFP Fire Systems. Its range of applications will be expanded further during 2014 but in the meantime offers two principal solutions prevalent in construction and infrastructure projects. www.passivetec.com

• Thinnest board to give 2 hours protection to EN1366 Pt 8• Saves space and therefore can reduce construction costs

• Very competitively priced system for contractors• Extremely durable

For more information, please visit www.sigtechnicalinsulation.co.uk

Page 34: Fire Protection

34

Firemac FM Blue

Firemac FM Blue is a non-combustible composite board with a fibre-reinforced cement core, and outer facings of perforated galvanised steel mechanically bonded to the core, used to provide fire protection and protect life and buildings.

Firemac FM Blue systems provide robust wall, ceiling, building services enclosures and ductwork systems to give fire resistance of up to 4 hours and blast resistance of up to 14kPa.

Applications• Vertical & horizontal barriers, all either insulated or uninsulated• Ventilation, smoke extract & kitchen extract ductwork• Enclosures for building services

Specific applications include:• Vertical & horizontal barriers forming escape routes and refuge areas• Enclosures & barriers around hazardous areas• Equipment protection• Document protection• Warehouse compartmentation• Service shafts • Electrical transformer & switch gear rooms

General Technical DataBoard thickness 8.5mm -1mm + 2mm

Standard board sizes 2000mm x 1200mm & 2400mm x 1200mm Combustibility Non-combustible

Classification to BS EN 13501-1 A1 Building regulations classification Class O

Effective density (composite) 2400kg/m³ (approx.) Approx. weight (composite) 19.2kg/m²

Moisture content (composite) 7.6% (approx.) Water absorption (composite, oven-dried to saturated) 15.5% (approx.)

Flexural strength Frupture (average) 300N/mm² Modulus of elasticity E (average) 195GPa

Impact strength to BS 5669: Part 1: 1989 Exceeds 980N/m Loadbearing capacity 10kN/m²

Max. point ‘load’ with 600mm span 980kg Max. point ‘load’ with 1200mm span 600kg

Thermal conductivity (λ) 38°C 0.40

If any data is being used for structural calculations contact Firemac to ensure the relevant data is up-to-date.

Firemac FM Blue has been installed across a range of industrial and commercial builds including transport and infrastructure projects, power stations, office blocks, communication and asset protection.

Firemac FM Blue is distributed solely through SIG and is supported by a full range of test evidence and assessments including BS 476: Parts 20, 22 and 24, BS EN 1364 - Parts 1 and 2, and UL263. In addition, the board is produced under a Third Party Certification scheme. Full details are available upon request.

For installers full training in the installation of Firemac FM Blue will be given, alongside ongoing site inspections and comprehensive technical support.

For more information, please visit www.sigtechnicalinsulation.co.uk

Page 35: Fire Protection

For more information, please visit www.sigtechnicalinsulation.co.uk 35

Structural Steel

Building regulations stipulate the period of fire resistance required for any element of building structure. Beams and columns require at least the same standard of fire protection as that required by any element they support.

The temperature rise of structural steelwork under fire test conditions provides a method of computing fire protection thicknesses based on accepted empirical formulae. The rate of increase in temperature of a steel cross section is determined by the ratio of the heated surface area (A) to the volume (V).

This ratio (A/V) has units of m-1 and is known as the section factor.

The section factor is a measure of the rate at which a steel element will increase in temperature. The higher the value of the section factor, the faster the element will heat up and therefore the thicker fire protection required to satisfy a stipulated fire protection period.

How to Specify Promat VERMICULUX® (up to 240 minutes – A/V 17 – 260m-1)Promat VERMICULUX® is a lightweight non-combustible board specially designed to provide fire protection to structural steelwork. Up to 240 minutes fire resistance can be achieved depending on thickness of material used and the dimensions of the beam or column being protected. Promat VERMICULUX® can be installed prior to the building being weather tight.

Promat PROMATECT®-250 (up to 120 minutes – A/V 17 – 260 m-1)Promat PROMATECT®-250 is a non-combustible mineral bound light weight board. It has smooth matt upper surface and is off-white in appearance.

Promat PROMATECT®-250 provides a high degree of strength, dimension stability, and fire protection to structural steelwork. Up to 120 minutes fire resistance can be achieved depending on thickness of material used and the dimensions of the beam or column being protected.

Thickness (mm) Dimensions (mm) Stack Quantities Can Stack be Split?20 1220 x 1220 40 N25 1220 x 1220 30 N30 1220 x 1220 26 N35 1220 x 1220 22 Y40 1220 x 1220 20 Y45 1220 x 1220 17 Y50 1220 x 1220 15 Y55 1220 x 1220 14 Y60 1220 x 1220 13 Y

Thickness (mm) Dimensions (mm) Stack Quantities Can Stack be Split?12 2500 x 1200 30 N15 2500 x 1200 30 N18 2500 x 1200 25 N20 2500 x 1200 25 N22 2500 x 1200 25 N25 2500 x 1200 20 N30 2500 x 1200 15 N

Page 36: Fire Protection

For more information, please visit www.sigtechnicalinsulation.co.uk36

Structural Steel

Glasroc F FIRECASEUsed predominantly as part of the British Gypsum FireCase and GypLyner encase structural steel encasement system, giving up to 180 minutes fire protection.

It has a high quality, white smooth surface finish, ideally suited as a self finish or to receive direct decoration with most paint finishes. Can also be tiled and plastered directly.

• Staple fixes (up to 25mm) or screw fixed• 3 or 4 sided protection• Steel angles or solders• GypLyner encase with FireLine is also available

Promat TD Board®/Rocksilk FireTech/ Rockwool BeamcladA high density, resilient and non-combustible rock mineral wool slab, which offers up to 240 minutes fire protection. It is available un-faced or faced with a Bright Class ‘O’ reinforced aluminium foil.

General benefits:• Quick, clean and dry installation process• Quick and simple installation of noggins• Choice of fixing systems• Moisture tolerant• Can accommodate decorative finishes

Thickness (mm) Dimensions (mm) Stack Quantities15 2400 x 1200 3220 2000 x 1200 4025 2000 x 1200 3030 2000 x 1200 20

Promat TD Board®

Thickness (mm) Dimensions (mm) Stack Quantities Can Stack be Split?25 2000 x 1200 45 N30 2000 x 1200 40 N35 2000 x 1200 32 N40 2000 x 1200 30 N

Page 37: Fire Protection

For more information, please visit www.sigtechnicalinsulation.co.uk 37

Structural Steel

Rocksilk FireTech (UN-FACED / FOIL FACED)Thickness (mm) Dimensions (mm) Stack Quantities

20 1800 x 1200 5625 1800 x 1200 4530 1800 x 1200 3635 1800 x 1200 3240 1800 x 1200 2845 1800 x 1200 2550 1800 x 1200 2260 1800 x 1200 18

Rocksilk FireTech Dry Fix Noggin SlabAn easy to cut, rock mineral wool slab, with superior fire resistant properties for use as the fixing noggin in the fire protection of structur-al steel work.

Thickness (mm) Dimensions (mm) Stack Quantities30 1800 x 1200 3635 1800 x 1200 3240 1800 x 1200 2845 1800 x 1200 2550 1800 x 1200 2260 1800 x 1200 18

Rockwool BeamcladThickness (mm) Dimensions (mm) Stack Quantities

25 2000 x 1200 4530 2000 x 1200 4035 2000 x 1200 3240 2000 x 1200 3050 2000 x 1200 2460 2000 x 1200 20

Page 38: Fire Protection

For more information, please visit www.sigtechnicalinsulation.co.uk38

Fire Barrier Systems

Fire Barrier systems help to prevent fire and smoke spread within roof and ceiling voids for all general conditions encountered on site.

The vertically hung Fire Barriers are capable of achieving both integrity and insulation protection periods from 15 to 120 minutes, and the friction fitted Fire Barrier Slab will also provide 60 minutes integrity and insulation.

Rockwool Fire BarrierDimensions:1000mm x 600mm x 100mm

Standard width 1 metre thickness (mm) Length (m)50 460 3-5

Description, performances & properties

Product Fire performance Integrity (mins) Insulation (mins) Specification

½ hour Cavity Barrier 60 15 1 layer 50mm

½ hour 60 30 1 layer 60mm Fire Barrier foil faced overlapped joints

1 hour Fire Barrier 60 60 2 layers 50mm Fire Barrier staggered vertical joints

1½ hour Fire Barrier 90 90 2 layers 50mm Fire Barrier staggered vertical joints

2 hour Fire Barrier 120 120 2 layers 60mm Fire Barrier foil faced separated by 40mm airspace

1 hour Fire Barrier Slab 240 60 100mm foil faced slab

Acoustic performanceThe correct use of Fire Barrier within structural cavities and voids will reduce the level of transmitted sound

Room to room attenuation Rw dBTypical lay-in grid suspended ceiling 30

As above, with 50mm ROCKWOOL® Fire Barrier 42Applied as 2, but ROCKWOOL® Fire Barrier foil faced 44

Applied as 2, but two thickness of 50mm ROCKWOOL® Fire Barrier - both foil faced 50ROCKWOOL® Fire Barrier Slab foil faced both faces 50

If ceiling is plasterboard, add between 2-3 db

Note: values are approximate

Page 39: Fire Protection

For more information, please visit www.sigtechnicalinsulation.co.uk 39

Fire Barrier Systems

Culimeta Saveguard Fire BarriersCulimeta Saveguard Fire Barriers are developed to offer flexible, lightweight, non-respirable and easy to install product for all types of installations.

Product Name

Fire Specification Product Dimensions Fixing MethodIdentification

ColourIntegrity (min)

Insulation (min)

Width (cm)

Length (m)

Thick (mm)

PackArea

StapleGun Staples

Firehalt 30/30 30 30 120 7 8 8.4m2 R31 12mm White

Firehalt 60/30 60 30 120 7 8 8.4m2 R31 12mm White

Firehalt 120/30 (Gold)

120 30 120 7 8 8.4m2 R31 12mm Green

Firehalt 120/60 120 60 120 5 16 6.0m2 R31 12mm Green/White

FIREHALT FIREHALT has bought two new products to the lightweight fire barrier/fire curtain market that are exclusively available through your local branch of SIG. These are:

Firehalt SF90 Product DescriptionSF90 is an ultra-lightweight fabric smoke and flame curtain that is totally non combustable and has a full 90 min fire rating when tested to BS476 p20/22.

InstallationSupplied in handy sized rolls 120cm wide by 25m long which like all the other FIREHALT products utilises standard fixing components that are inexpensive and readily available. 12mm metal staples are used to join panels together vertically andhorizontally.

Firehalt 30/30 Product DescriptionTo help you cope with an increasingly competitive market FIREHALT has developed a lightweight fire rated cavity barrier that still offers a full 30 mins Insulation value when tested to BS476 p20/22.

InstallationEach pack weighs little more than 16kg but provides 8.4sqm of product. In line with other products in the range it is quick to install using standard components such as 50mm stud and 25mm metal angle, and can be fixed from one side.

Page 40: Fire Protection

For more information, please visit www.sigtechnicalinsulation.co.uk

Culimeta-Saveguard Smoke and Flame Curtains Culimeta-Saveguard offer two Fire Curtains that are flexible, lightweight and easy to install.

ProductName

Fire Specification Product Dimensions Fixing MethodIdentification

ColourIntegrity (min)

Insulation (min)

Width (cm)

Length (m)

Thick (cm)

Pack Area (cm)

Staple Gun Staples

Firehalt SF90 90 0 120 25 2 30m² R31 6 -12 White

Firehalt SF 120 0 120 25 2 30m² R31 6 -12 Green

40

Fire Barrier Systems

Brush seal Introducing BRUSHSEAL - a unique product specifically designed to be used in conjunction with Firehalt barriers and curtains.

• Simple and quick to install• Will fit any size or shape of service penetration• Suitable for uneven surfaces such as cable trays• Requires no expensive mastics or adhesives• Provides a neat & professional finish

Brushseal is fixed to the penetration service rather than the barrier and is therefore straightforward and quick to fit. System will also add stability to the barrier.

Page 41: Fire Protection

Cladding and Curtain Walling

For more information, please visit www.sigtechnicalinsulation.co.uk

Cavity Barriers for Curtain Wall FacadesProduct Thickness Fire Rating

AIM Cavity Fire Barrier 75 mm 60 minAIM Fire Barrier Slab 100 mm 120 min

Rockwool SP 60 Firestop Slab 75 mm 60 minRockwool SP 120 Firestop Slab 90 mm 120 min

CW-FS Cavity Barriers 90 mm 60 minCW-FS Cavity Barriers 120 mm 120 mm

General benefits:• Easy to cut and install• Ensures site tolerances are accommodated• Independently tested to provide 2 hours of fire resistance• Resists the passage of smoke – aluminium foil• Faced on both sides• Suitable for cavity widths up to 400mm• Easy site storage and handling• Quality assured to BS EN ISO 9001

Slabs are designed to be cut on-site, to produce cavity fire stops of 1000mm length and in widths to suit individual cavity sizes.

Fixing Brackets are required for the installation. They are supplied in two standard types, Small Fixing Brackets designed for cavities up to, and including 100mm wide and Large Fixing Brackets for cavities over 100mm and up to 400mm wide.Brackets are supplied in cardboard boxes, flat packed, and are designed to be easily re-profiled by hand on site. Fixing Brackets should be cut on site as necessary to allow at least 75% penetration of the Firestop.

41

Page 42: Fire Protection

Cladding and Curtain Walling

For more information, please visit www.sigtechnicalinsulation.co.uk42

Fire Performance and Product thicknessApplication Fire Rating (mins) Thickness (mm)Horizontal 30/30 75Horizontal 60/60 90

Vertical 30/30 75Vertical 60/60 90Vertical 120/120 120

Cavity Barriers in Rainscreen Facades

AIM Ventilated Rainscreen Barrier Plus (VRB Plus)Product DescriptionThe AIM VRB Plus offers an effective fire barrier for ventilated cavities over 60mm up to 300mm in its standard form. The AIM VRB offers a superior fire rating and allows a continuous ventilation space of up to 44mm. This provides excellent ventilation behind the cladding whilst leaving sufficient room for easy installation of the cladding panels.

ApplicationPolythene enclosed to give weather resistance in a semi exposed application

SpecificationThickness – 75mmWidth – Total cavity size less 44mmLength – 1000mmMax Air Gap – 44mm• Polythene enclosed to give weather resistance in a semi exposed application• Tested and assessed by Chiltern International Fire

AIM Ventilated Rainscreen Fire Barrier (Lite) VRB LiteProduct DescriptionThe AIM VRB Lite, offers an effective fire barrier for ventilated cavities of up to 300mm. VRB Lite is simple and cost effective to install, allowing a continuous ventilation space of up to 25mm. VRB Lite has been tested to the general principles of the more stringent BS EN 1363-1 standard.

ApplicationPolythene enclosed to give weather resistance in a semi exposed application

SpecificationThickness – 75mmWidth – Total cavity size less 25mmLength – 1000mmMax Air Gap – 25mm• Polythene enclosed to give weather resistance in a semi exposed application• Tested and assessed by Chiltern International Fire

Horizontal Cavity Barrier Lamatherm CW–RSH incorporates a continuous bonded intumescent strip to the leading edge and encapsulated in a weather resistant polymer film. In the event of exposure to fire, this expands and fully seals the designed ventilation gap formed at the time of installation between barrier and the rear of the cladding.

Vertical Cavity Barrier For vertical barriers within rainscreen systems, it is generally acceptable to fully fill the void. Our Lamatherm CW–RSV product is specifically intended for use in this manner. As a full fill barrier system, the integral intumescent strip is not required. The front edge is finished as standard in a plain aluminium foil.

Alternatively, the product is optionally available with a factory applied DPC pre-bonded to this surface.

Page 43: Fire Protection

Masonry WallMasonry walls within the external fabric of a building are typically formed by an inner and outer masonry leaf which forms a void for installation of a thermal insulation layer. Such situations will typically form a hidden cavity within the fabric of a building and potentially form a ready route for spread of flame and smoke within this hidden void. In these instances it is necessary to install cavity barriers to limit the spread of flame within this hidden void. It is imperative the selection of products are suited to the intended application and proven to perform having undergone independent testing in line with current standards.

AIM Wall Cavity Fire Barrier & Fire Barrier SlabsProduct DescriptionAIM Wall Cavity Barrier is made from foil faced high density Rockwool stone wool. The barrier prevents the passage of flame and smoke within the cavity it fills for the period of fire rating, specified below.

ApplicationSuitable for use in all cavity walls, as well as for fire stopping between a curtain wall system and a concrete floor slab.

SpecificationLengths: 1000mm (Available cut to size or in slabs)Foil Facing (with AIM logo)Cavity widths: 50 - 600mm (barrier to be compressed by about 5%)

• No mastics or sealants required• Tested to BS 476 part 20 and assessed by Warrington Fire Research Centre• Non-combustible to EN15301-1 and classified A1• Faced with Class O reinforced aluminium foil for enhanced smoke resistance• Ozone depletion potential of zero; no CFCs or HCFCs used in manufacture

For more information, please visit www.sigtechnicalinsulation.co.uk 43

Cladding and Curtain Walling

Page 44: Fire Protection

All rights reserved. No part of this publication may be reproduced or transmitted in any form, or by any means, electronic or mechanical including photocopy, recording or any information storage and retrieval system, without permission in writing from SIG Technical Insulation. No information contained within this publication can be used to compile any other printed or electronic directory or mailing list. Whilst every effort has been made to ensure accuracy, the publisher does not, under any circumstances, accept responsibility for errors or omissions and no representation or warranty is made in relation to the suitability of a product for a specific application. Copying of the images contained in this publication, in any form without the author’s permission, is an unlawful act under the Copyright Designs and Patent Act 1988.

For full technical advice, thermal calculations and support, please contact your local SIG Technical Insulation branch

ScotlandAberdeenBroadfold RoadBridge of DonAberdeenAB23 8EETel: 01224 771 566Fax: 01224 770 319

Glasgow95 Westburn DriveCambuslangGlasgowG72 7NATel: 0141 643 3600Fax: 0141 641 2426

TynesideTynesideFederation Business ParkSt Omers RoadDunstonNE11 9HRTel: 0191 226 6730Fax: 0191 226 6731

North West LiverpoolHornhouse LaneKnowsley Industrial ParkLiverpoolL33 7YQTel: 0151 547 5295Fax: 0151 547 5296 ManchesterBlock 1River ParkRiver Park RoadEastlandsManchesterM40 2XPTel: 0161 438 7262Fax: 0161 370 5879 Newton-Le-WillowsSunbeam StNewton-Le-WillowsLancashireWA12 8NGTel: 01925 225 252Fax: 01925 229 700

North EastChesterfieldUnit 1 Sheepbridge CentreChesterfieldS41 9RXTel: 01246 269 537Fax: 01246 261 725

LeedsIntermezzo DrivePontefract RoadLeeds LS10 1RUTel: 0113 385 7777Fax: 0113 385 7778

MidlandsBirminghamApollo ParkRounds Green RoadOldburyWest Midlands B69 2DFTel: 0121 665 3060Fax: 0121 544 8026

Leicester Unit E BraunstoneIndustrial Estate139 Scudamore RoadLeicesterLE3 1UQTel: 0116 232 5000Fax: 0116 232 5001

AngliaBedfordTelford WayBedfordMK42 0PQTel: 01234 761 490Fax: 01234 761 499

NorwichUnit 27White Lodge Business ParkNorwichNR4 6DQTel: 01603 226 005Fax: 01603 226 000

LondonLondon East – Beckton19-21 Alpine WayLondon Industrial ParkBecktonLondonE6 4LATel: 020 7473 9310Fax: 020 7473 9311

London West – RuislipUnit 4 Victoria Road Retail ParkCrown Road South RuislipLondonHA4 0AFTel: 020 8839 4290Fax: 020 8839 4301

South WestBristolUnit 200/300 North Bristol ParkNorth WayFiltonBristol BS34 7QHTel: 0117 931 3420Fax: 0117 931 3425

Plymouth87 St Modwen RoadParkway Industrial EstateMarsh MillsPlymouth PL6 8LHTel: 01752 675 417Fax: 01752 675 418

SwanseaUnits 37-38 CwmduTrading EstateFforestfachSwanseaSA5 8JFTel: 01792 588 461Fax: 01792 583 849

South EastHeathrowBlackthorne RoadPoyle Trading EstateColnbrookSloughSL3 0DUTel: 01753 687 272Fax: 01753 681 623

OxfordUnit 5 Curbridge Business ParkDowns RoadWitneyOxonOX29 7WJTel: 01993 700 993Fax: 01993 708 993

PortsmouthUnit 2 Quadra Sharps ClosePorstmouthPO3 5PSTel: 023 9269 6733Fax: 023 9266 1406