Fire Fighting Pupms Data Sheet

18

Transcript of Fire Fighting Pupms Data Sheet

Page 1: Fire Fighting Pupms Data Sheet
Page 2: Fire Fighting Pupms Data Sheet

MINISTRY OF ENERGY IRAN POWER DEVELOPMENT COMPANY

I.P.D.C.

Client Doc. No.: TSM/AL-28/FF-M-31-DL0-001 Rev. 0

Contractor Doc. No.: File No.:

MAPNA GROUP

SE Code: MF Code: Page 1 of 15

PROJECT: ARDEBIL-EXT. GAS TURBINE POWER PLANT

IN HOUSE REVISION DOCUMENT REVISION D

C

B

A

0 0 ISUUED FOR APPROVAL SAP SEP. 2009 M.N. SEP. 2009 S.R. SEP. 2009

REV. DESCRIPTION DESG. DATE CHK. DATE APP. DATE REV. DESCRIPTION DESG. DATE CHK. DATE APP. DATE

FIRE FIGHTING SYSTEM

PUMPS DATA SHEETS

Page 3: Fire Fighting Pupms Data Sheet

MINISTRY OF ENERGY IRAN POWER DEVELOPMENT COMPANY

I.P.D.C.

Client Doc. No.: TSM/AL-28/FF-M-31-DL0-001 Rev. 0

Contractor Doc. No.: File No.:

MAPNA GROUP

SE Code: MF Code: Page 2 of 15

PROJECT: ARDEBIL-EXT. GAS TURBINE POWER PLANT REVISION REVISION PAGE

0 A B C D E F G REMARKS PAGE

0 A B C D E F G REMARKS

1 X 54 2 X 55 3 X 56 4 X 57 5 X 58 6 X 59 7 X 60 8 X 61 9 X 62

10 X 63 11 X 64 12 X 65 13 X 66 14 X 67 15 X 68 16 69 17 70 18 71 19 72 20 73 21 74 22 75 23 76 24 77 25 78 26 79 27 80 28 81 29 82 30 83 31 84 32 85 33 86 34 87 35 88 36 89 37 90 38 91 39 92 40 93 41 94 42 95 43 96 44 97 45 98 46 99 47 100 48 101 49 102 50 103 51 104 52 105 53 106

Page 4: Fire Fighting Pupms Data Sheet

MINISTRY OF ENERGY IRAN POWER DEVELOPMENT COMPANY

I.P.D.C.

Client Doc. No.: TSM/AL-28/FF-M-31-DL0-001 Rev. 0

Contractor Doc. No.: File No.:

MAPNA GROUP

SE Code: MF Code: Page 3 of 15

PROJECT: ARDEBIL-EXT. GAS TURBINE POWER PLANT TABLE OF CONTENT PAGE 1.  MAIN DIESEL FIRE PUMP............................................................................................................................................................4 

2.  MAIN ELECTRICAL FIRE PUMP ...............................................................................................................................................10 

3.  JOCKEY ELECTRICAL PUMP ...................................................................................................................................................14 

 

Page 5: Fire Fighting Pupms Data Sheet

PAGE OF

CONTRACT No. :

DOC. No. : TSM/AL-28/FF-M-31-DL0-001 DATE

PREPARED BY : CHECKED BY :

REVISION

1 APPLICABLE TO: ○ PROPOSAL ● PURCHASE ◘ AS BUILT

2 FOR UNIT

3 SITE SERVICE

4 NO. REQ. TYPE

5 MANUFACTURER MODEL TAG NO.

6 NOTE: ○ INDICATES INFORMATION COMPLETED BY PURCHASER □ BY MANUFACTURER ◘ BY MANUFACTURER OR PURCHASER

7

9 □ DIESEL ENGINE POWER ( RATED/MAX. ) KW ● ALTITUDE M

10 SPEED: 1770 ● AMBIENT TEMPERATURE , NORMAL °C

11 ○ VARIABLE SPEED FROM 600 TO 2400 RPM MAXI. MINI. °C

12 ● CONSTANT SPEED 1760 RPM ● RELATIVE HUMIDITY: MAX/MIN %

13 ■ OVERSPEED 2112 RPM ○ UNUSUAL CONDITIONS:

14 ■ MAX ALLOWABLE WORKING SPEED 2400 RPM INSTALLATION:

15 OVER LOAD : ● INDOOR ○ HEATED ○ UNDER ROOF

16 ■ SITE POWER KW ○ OUTDOOR ● UNHEATED ○ PARTIAL SIDES

17 ■ SPEED 1760 RPM ○ GRADE ○ MEZZANINE ●18 ◘ FREQUENCY- TIME ● ELECTRICAL AREA CLASSIFICATION:

19 ◘ RATED VOLTAGE ESTABLISHMENT TIME SEC CLOR OF WATER: 2184 PPM20 ◘ FULL LOAD ESTABLISHMENT TIME SEC

21 □ max. sound level 110dB (REV A) RPM

22 DIRECTION OF ROTATION (VIEW FROM COUPLING SIDE) ■ CW □ CCW COOLING WATER:

23 TEMP. INLET 15 °C TEMP. RETURN 35 °C

24 ○ ISO ● NFPA-20 ○ ASME / ANSI PRESS. INLET BARG DESIGN BARG

25 ○ OTHER ● UL/FM MIN RETURN MAX ALLOW DP BARG

26 STEAM:

27 ● SHOP INSPECTION PRESSURE:MIN / MAX BARG

28 ● BY CONTROL AGENCY TEMPERATURE:MIN / MAX °C

29 TEST

30 STANDARD SHOP TEST ○ ○31 HYDROSTATIC TEST ○ ○ ELECTRIC SUPPLY (FOR BATTERY CHAGER):

32 MECHANICAL RUNNING & PERFORMANCE TEST ○ ○33 STARTING SYSTEM TEST ○ ○34 NOISE LEVEL TEST ○ ○35 SURFACE TEMPERATURE TEST ○ ○36 OVERSPEED TRIP DEVICE TEST ○ ○37

38 ● POLYURETHANE ,RED COLOR RAL 3000 39 □ OTHER ( PLEASE SPECIFY ) FUEL OIL: Kg/KW. Hr

40 LUBE OIL: LIT

41 ○ DOMESTIC ○ EXPORT ○ EXPORT BOXING REQUIRED INSTRUMENT AIR: M3/Hr

42 ○ OUTDOOR STORAGE MORE THAN 6 MONTHS STARTING AIR: M3/TIM

43 COOLING WATER: M3/MIN

44 BASE PLATE / SKID UNIT x SPECIAL TOOLS

45 FOUNDATION BOLTS WIRING & INSTRUMENTATION x ◘ AIR STARTING46 ENGINE FITTING BOLTS x BATTERY & CHARGER x ◘ NUMBER OF TANKS ONE

47 FLYWHEEL & GUARD x LOCAL CONTROL PANEL x □ CAPACITY M3/H

48 EXHAUST SILENCER x FUEL INTERCONNECTING PIPING □ PRESSURE BAR

49 COUPLING AND GUARD x WALKWAYS, LADDERS □ NUMBER OF STARTS

50 COUPLING BOLTS x SPEED GOVERNING SYSTEM x ◙ ELECTRIC STARTING51 AIR DUCTING & SUPPORT TURBOCHARGING SYSTEM □ VOLTAGE 24 V □ POWER KW

52 EXHAUST DUCTING & SUPPORT INLET AIR FILTER & SUPPORT x ◘ BATTERY ◘ NO. OF BATTERY : 2 SETS

53 PROTECTION DEVICE DAY FUEL TANK x ◙ BATTERY CHARGER YES

54 STARTING SYSTEM x OVERSPEED SAFETY DEVICE x STARTING:

55 BARRING SYSTEM OIL COOLER x ● LOCAL

56 ANTIVIBRATION DEVICE WATER COOLER x ● MANUAL ● AUTO/MANUAL SELECTOR SWITCH

57 SAFETY GUARD FOR FLYWHEEL & FAN FUEL COOLER ○ REMOTE:

58 HEAT EXCHANGER x ● MANUAL ○ AUTO

59 REMARKS:

60

STARTING SYSTEM

ALL CHECKS TO BE DURING STRING TEST . *)Information must be given by manufacturer

PAINTING

■ UTILITY CONSUMPTION

SHIPMENT

ACCESSORIES PROVIDED BY MANUFACTURER

HERTZ

AC 220 1 50

CONTROL AC / DC VOLTS PHASE

APPLICABLE CODE & STANDARDS

SHOP TEST - INSPECTION

NON-WIT WIT

39.5 -37

AVAILABLE UTILITIES

96

SAFE AREAUNDER GRADE

OPERATING CONDITIONS SITE DATA1340

TWO CLARKE JW6H-UF60 *

268

ARDEBIL EXT. G.T.P.P. ARDEBIL EXT. FIRE FIGHTING

S.R.

0 APPR. BY :

SI UNITS S.P.

15

DIESEL ENGINE4

SEP 2009M.N.

DATA SHEET

Page 6: Fire Fighting Pupms Data Sheet

PAGE OF

CONTRACT No. :

DOC. No. : DATE

PREPARED BY : CHECKED BY :

REVISION

61 ○ CONTINUOUS USE ● EMERGENCY USE AIR FILTER: ◙ SINGLE ◘ DUPLEX

62 CYCLE: ◘ 2 STROKE ■ 4 STROKE ◘ DRY ◘ OIL BATH

63 □ SINGLE ACTING □ DOUBLE ACTING ◘ TURBOCHARGING AIR COOLER:

64 CYLINDER ARRANGEMENT ◘ IN-LINE □ VEE □ TYPE □ NUMBER

65 ■ NUMBER OF CYLINDERS 6 □ MANUFACTURER

66 ■ CYLINDER BORE X STROKE Φ X mm ◘ PIPING ◘ EXPANSION JOINTS

67 EXHAUST & SUCTION VALVE:

68 ◘ ONE FOR EACH CYLINDER ◙ TWO FOR EACH CYLINDER

69 □ MAIN EFFECTIVE PRESS. BARG

70 □ MAX. CYLINDER PRESS. BARG FRAME CRANKSHAFT FORGED STEEL

71 □ PISTON SPEED M/S @ RATED SPEED CYLINDER CAST IRON CAMSHAFT STEEL HARDENED

72 ■ COMPRESSION RATIO LINERS ALLOY IRON PLATEAU CONNECTING ROD FORGED STEEL ALLOY

73 COOLING SYSTEM: ◘ AIR ◘ AIR/ WATER COOLED TIE-ROD FORGED STEEL ALLOY CROSSHEADS

74 ◙ WATER ◘ WATER / WATER COOLED CYLINDER-HEAD CAST IRON PISTONS STEEL CROWN AL.S.

75 □ COOLING WATER TANK CAPACITY: M3CROSSHEAD PISTON RINGS TOP-PLASMA COATED

76 WATER PUMP: ◘ SHAFT DRIVEN ◘ MOTOR DRIVEN VALVES SECOND,TAPERED CAST IRON.3RD CHROMIUM FACED

77 ◙ TURBOCHARGER ◘ SUPER CHARGER ◘ NORMALLY ASPIRATED EXHAUST SPARK ARRESTER

78 □ NUMBER OIL COOLER: TUBES SHELL

79 ■ MANUFACTURER □ MODEL OIL FILTER ELEMENTS OIL HEATING COIL

80 □ PRESSURE RATIO OIL LUBRICATING PIPING BEFORE / AFTER FILTER

81 □ SPEED 1760 RPM BOLTING *

82 POWER TRANSMISSION:

83 □ FLEXIBLE COUPLING ◘ RIGID COUPLING ◘ V-BELT ◘ MANUAL ◘ ELECTRICAL ◘ HYDRAULIC

84

85 ◘ SPLASH SYSTEM ◘ PRESSURE SYSTEM

86 LUBE OIL FILTER: ◙ SINGLE ◘ DUPLEX ■ ENGINE PIPE OUTLET ■ SPARKED ARRESTER

87 OIL COOLER: ■ SILENCER

88 ◘ SINGLE ◘ DUPLEX ■ EXPANSION JOINT

89 ◘ SHELL & TUBE TYPE ◘ PLATE TYPE

90 ◘ RADIATOR TYPE FUEL SUPPLY TO ENGINE BY : ● GRAVITY ○ PUMP

91 ◙ OIL HEATER ◘ SINGLE ◘ DUPLEX

92 TYPE: ■ ELECTRICAL ◘ OTHER FUEL OIL SUPPLY PUMP: ◘ SHAFT DRIVEN ◘ MOTOR DRIVEN

93 ■ POWER 2.5 KW ◘ EXPLOSION PROOF FILTER: ◘ SINGLE ◘ DUPLEX

94 ○ STEAM COIL ◘ FUEL SHUT OF VALVE

95 CONSUMPTION KG/H FUEL TANK CAPACITY: 440 GALLONS96 FLANGES IN/ * / RATING IN/ OUT / ◘ FIXED TO THE SET ◙ SEPARATED

97 MINIMUM STARTING OIL TEMPERATURE °C ● FUEL CHARACTERISTICS:

98 □ PUMPS: KIND OF FUEL: GASOIL

99 TYPE KINEMATIC VISCOSITY AT 100 °F CST

100 FLOW LIT/MIN FLASH / POUR / CLOUD POINT C

101 DRIVER SULPHUR 1 WT%

102 SPEED RPM ASH WT%

103 POWER KW WATER AND SEDIMENTS VOL%

104 MATERIAL SPECIFIC GRAVITY AT 60/60F

105 AUXILIARY PUMP: CARBON RESIDUE WT%

106 ◘ PRELUBE ◘ STARTING ◘ STAND BY CETANE INDEX

107 □ FUEL TO AIR RATIO

108 □ SPECIFIC FUEL CONSUMPTION

109 ACIDITY mgKOH/gr

110 REMARKS:

111

*)Information must be given by manufacturer

LUBRICATIONEXHAUST SYSTEM

FUEL

MAIN AUXILIARY

INJECTION PUMP:

3.8

< 0.01

APPR. BY : S.R.

■ MATERIAL

BARRING SYSTEM

DIESEL ENGINE5 15

Lit./KW

DATA SHEET TSM/AL-28/FF-M-31-DL0-001 SEP.2009

SI UNITS S.P. M.N.

CHARACTERISTICS AIR INLET SYSTEM0

*

116 127

15.7 : 1

*

Page 7: Fire Fighting Pupms Data Sheet

PAGE OF

CONTRACT No. :

DOC. No. : TSM/AL-28/FF-M-31-DL0-001 DATE

PREPARED BY : CHECKED BY :

REVISION

112 □ FLOW: □ SERVICE COOLING

113 □ AIR TEMPERATU INLET / OUTLET / °C □ FLUID WATER

114 □ WATER TEMPERATU INLET / OUTLET / °C □ FLOW

115 □ TEST PRESSURE BAR □ OPERATING TEMPERATU INLET / OUTLET 25/60 °C

116 □ FOULING FACTOR M2H °C / kcal □ WATER TEMPERATU INLET / OUTLET 25/60 °C

117 □ TOTAL AREA m2 □ TEST PRESSURE

118 □ TUBES: DIAMETER mm m □ FOULING FACTOR

119 PLUNGER: □ TOTAL AREA

120 □ INLET / OUTLET: □ SHELL: DIAMETER MM □ LENGTH

121 □ DRAIN / VENT: □ TUBES: NUMBER PER SHELL

122 FAN: □ DIAMETER MM □ THICKNESS

123 □ NO. REQ'D: SET(S)

124 □ CAPACITY NM3/MIN ■ INLET / OUTLET

125 ◘ SUCTION TYPE ◘ PUSHER TYPE □ DRAIN / VENT

126 ◘ SHAFT DRIVEN ◘ MOTOR DRIVEN MATERIAL:

127 □ SPEED: RPM □ SHELL ■ TUBES

128 □ MATERIAL: □ SHELL SHEETS □ BAFFLES

129 □ POWER: k w □ CHANNEL-SHELL FLANGES □ CHANNEL

130 BLADES:

131 ◘ FIXED PITCH ◘ VARIABLE DIAMETER m

132 ◘ MANUAL ◘ AUTOMATIC

133 POWER TRANSMISSION:

134 ◘ RIGID COUPLING ◘ V-BELT HEIGHT UNDER HOOK M

135 □ BELTS: TYPE NUMBER OVERALL DIMENSION (L X W X H) M

136 □ MOTOR: TYPE DIMENSIONS FOR MAINTENANCE M

137 POWER Kw SPEED RPM

138

139 ALARM ● DIFFERENTIAL PRESSURE SWITCH ON FILTER

140 LOW LUB OIL PRES. ● ○ ● ENGINE SPEED INDICATOR

141 HIGH ENGINE WATER TEMP. ● ○ ● TACHOMETER

142 HIGH COOLING WATER TEMP. LEAVING THE PRESSURE GAUGES:

143 ENGINE JACKETS ● ○ ○ LUBE OIL ● COOLING WATER ● BOOST AIR

144 LOW & HIGH FUEL LEVEL IN FUEL OIL DAILY TANK ● ○ TEMPERATURE GAUGES:

145 ○ ● ● COOLING WATER ● LUBE OIL

146 LOW LUB OIL LEVEL SUMP. ● ○ ● EXHAUST GAS TEMPERATURE GAUGE (UP STREAM OF TURBO CHARGER)

147 BATTERY CHARGER FAILURE ● ○ ● THERMOMETER AND THERMOWELL FOR EACH CYLINDER

148 HIGH CHARGED AIR TEMP. IN TURBOCHARGER

149 AND INTER-COOLED ENGINE ● ○ HEAVIEST PART FOR ERECTION * KG

150 ● ○ HEAVIEST PART FOR MAINTENANCE * KG

151 OVERSPEED ○ ● WEIGHT OF ENGINE ONLY * KG

152 WEIGHT OF THE SET * KG

153 WEIGHT OF RADIATOR: EMPTY/WITH LIQUID / * KG

154 WEIGHT OF WATER COOLED EXCHANGER : * KG

155 ALLOWABLE LOAD ON WALKWAYS * KG

156 REMARKS:

157

158

159

160

161

162This document is the property of MAPNA who will safeguard its rights according to the civil and penal provisions of the law

INSTRUMENTATION SHUTDOWN

■ WEIGHTS

/ / /

■ DIMENSIONS

CU-IN

DIAMETER SERIAL FACE

* / * / THREADED

/ / /

FLANGES

DIAMETER RATING FACE

/ / /

BAR

LENGTH

M3/H

M2H °C / kcal

0 APPR. BY : S.R.

M3/H

DIESEL ENGINE6 15

MM

M

M

DATA SHEET SEP.2009

SI UNITS S.P. M.N.

AIR COOLED EXCHANGER (N/A) WATER COOLED EXCHANGER

Page 8: Fire Fighting Pupms Data Sheet

PAGE OF

CONTRACT No. :

DOC. No. : DATE

PREPARED BY : CHECKED BY :

REVISION

163

164

165

166

167

168

169

170

171

172

173

174

175

176

177

178

179

180

181

182

184

185

186

187

188

189

190

191

192

193

194 - INSPECTION AND TESTING

195 - PRESERVATION AND EXPORT BOXING

196

197

198

199

200201

202

203

204

205206

207

208

209

- DIESEL ENGINE LUBRICATING SYSTEM

- DOCUMENTATION

- OTHER COMPLEMENTARY ACCESSORIES FOR PROPER OPERATION OF ENGINE

- DIESEL ENGINE WITH AUXILIARIES AND LIFTING POINTS

- LIFTING FRAME AND SLINGS FOR ALL EQUIPMENT ON COMBINED BASEPLATE ( NOT REQUIRED STATED BY VENDOR )

- SPARE PARTS FOR COMMISSIONING & 2 YEARS

6- AUTOMATIC SHUTDOWN SHALL BE INITIATED BY ENGINE OVERSPEED ONLY .

7- THE CONTROLLER SHALL MEET THE REQUIREMENTS OF BOTH THE PRIME ELECTRICAL AND THE EMERGENCY

STARTING/SHUTDOWN SYSTEM .THE CONTROLLER SHALL ARRANGE THAT ,UPON RECEIPT OF A STARTING SIGNAL ,

START UP USING THE PRIME STARTING SYSTEM SHALL BE ATTEMPTED .

MOUNTED ELEMENTS

- DIESEL ENGINE INSTRUMENTATION AND CONTROLS ,PROTECTION AND ALARMS

- INTERCONNECTING POWER AND CONTROL WIRING/CABLING BETWEEN ALL EQUIPMENTS WITHIN BASEPLATE/CABINETS

OVER AN 8 HOUR PERIOD .

- SPECIAL TOOLS ( NOT REQUIRED STATED BY VENDOR )

SUPPORT STAND AND MOUNTING FEET

- DIESEL ENGINE AIR INTAKE FILTERS WITH AIR SHUT-OFF VALVES

- EXHAUST PIPING ,FLEXIBLE CONNECTIONS ,SILENCERS WITH RAIN CAPS ,SPARK ARRESTER ,AND INSULATION ON ENGINE

- DIESEL ENGINE COOLING SYSTEM (HEAT EXCHANGER)

- DIESEL ENGINE ELECTRIC STARTING SYSTEMS WITH BATTERY CHARGER

8- SCOPE OF SUPPLY INCLUDES :

OR ALTERNATOR SUPPLIED WITH THE ENGINE .

4- BATTERIES SHALL BE LEAD ACID TYPE .

5- DAILY FUEL TANK SHALL BE SIZED IN ACCORDANCE WITH NFPA-20 FOR CONTINUOUS OPERATION AT 150% RATED FLOW

2- MAXIMUM BRAKE HORSEPOWER SHALL COVER ANY FLOW FROM SHUT-OFF TO 150% RATED FLOW .ENGINE RATING

CONDITIONS AND DEDUCTIONS SHALL MEET NFPA-20 REQUIREMENTS .

3- TWO MEANS OF RECHARGING STORAGE BATTERIES SHALL BE PROVIDED .THE SECOND MEANS SHALL BE THE GENERATOR

APPR. BY : S.R.

GENERAL NOTES

1- THE WHOLE PACKAGE SHALL BE FULLY COMPLIANT WITH NFPA-20 .

0

DATA SHEET TSM/AL-28/FF-M-31-DL0-001 JUN.2009

SI UNITS S.P. M.N.

7 15

DIESEL ENGINE

Page 9: Fire Fighting Pupms Data Sheet

PAGE OF

CONTRACT No. :

DOC. No. : DATE

PREPARED BY : CHECKED BY :

REVISION

1 APPLICABLE TO: ● PROPOSAL ○ PURCHASE ◘ AS BUILT

2 FOR UNIT

3 SITE SERVICE

4 NO. REQ. PUMP SIZE TYPE CENTRIFUGAL/HORIZONTAL5 MANUFACTURER MODEL TAG NO.

6 NOTE: ○ INDICATES INFORMATION COMPLETED BY PURCHASER □ BY MANUFACTURER ◘ BY MANUFACTURER OR PURCHASER

7 LIQUID

8 PUMPING TEMP. (°C) NORMAL

9 MAXIMUM

10 MINIMUM

11 RELATIVE DENSITY

12 VAPOR PRESSURE @ MAXIMUM TEMP. (bara) ■ HYDRAULIC TEST PRESSURE (barg)

13 VISCOSITY (CENTIPOISE) ■ DESIGN PRESSURE (barG):

14 ● CAPACITY (m3 / h) RATED ■ MAXIMUM ALLOWABLE WORKING PRESSURE AT RATED TEMP.(barG): 1815 ● DISCHARGE PRESSURE (barg) □ SHUTT-OFF PRESSURE (barG):

16 ● SUCTION PRESSURE (barg) MAX/RATED / FLOW RATE / HEAD CURVE SUPPLIED : ● A02-11272517 ● DIFFERENTIAL HEAD (m) □ DRIVER SPEED (rpm) 177018 ● DIFFERENTIAL PRESSURE (bar) □ EFFICIENCY AT RATED CAPACITY : 7619 ● □ EFFICIENCY AT 150% RATED CAPACITY : 8620 ● □ MIN. CONTINUOUS FLOW (m3 / h) MECHANICAL 100m3/h21 ● THERMAL < 100 m3/h22 □ RATED POWER (KW): *23 LOCATION : □ MAX. HEAD WITH RATED IMPELLER (m):

24 ● INDOOR ○ HEATED ● UNDER ROOF □ MAX. POWER WITH RATED IMPELLER (KW):

25 ○ OUTDOOR ● UNHEATED ○ PARTIAL SIDES □ REQUIRED NPSH AT 150% RATED CAPACITY (m) :

26 ○ GRADE ○ MEZZANINE ◘ COOLING / HEATING PIPING : MATERIAL

27 ● ELECTRICAL AREA CLASSIFICATION TUBE □ PIPE ■28 CL GR DIV THREADED ■ FLANGED □29 ○ WINTERIZATION REQ'D ○ TROPICALIZATION REQ'D SEAL WELDED □ SOCKET - WELDED □30 SITE DATA : ◘ AUXILIARY PIPING: MATERIAL

31 ○ ALTITUDE (m) BAROMETER (mbara)

32 ○ RANGE OF AMBIENT TEMPS: MIN/MAX / CASING MOUNTING *

33 ○ RELATIVE HUMIDITY: MAX./MIN. (%) CENTERLINE □ BRACKET □34 UNUSUAL CONDITIONS (2.1.23) ○ DUST ○ FUMES NEAR CENTERLINE □ IN -LINE □35 CHLORIDE CONTENT: 2184PPM FOOT ■36 ○ UTILITY CONDITIONS: VERTICAL □ SUMP □37 STEAM: DRIVERS HEATING VERTICAL BARREL □ OTHERS □38 MIN (bar) (barg) CASING SPLIT:* AXIAL ■ RADIAL □39 MAX (bar) (barg) CASING TYPE*

40 ELECTRICITY: DRIVERS CONTROL HEATING SHUTDOWN SINGLE VOLUTE □ DOUBLE VOLUTE ■41 VOLTAGE 230 230 DIFFUSER □ STAGGERED □42 HERTZ 50 50 IMPELLER MOUNTING:*

43 PHASE 1 1 BETWEEN BEARINGS ■ OVERHUNG ◘44 COOLING WATER:

45 TEMP. RETURN

46 (barg) DESIGN

47 PRESS. RETURN (barg) MAX ALLOW DP

100

209

NPSH AVAILABLE@150%RATED CAPACITY(mwc) 8.

107

HEAD LOSS FROM TANK TO PUMP SUCTION (mwc) 1.755

MINIMUM AVAILABLE STATIC SUCTION HEAD (mwc) 1.4

18

11.0YES

SUCTION

27

8"BALANCE DRUM

STEEL

SAFE AREA

4.9STEEL

● SITE AND UTILITY DATA

(°C)

@ PUMP TEMP.

10

8601340

(°C)

-37 39.5

(°C)

10(barg)

(°C)

1/2"VENT PRESSURE GAUGEDRAIN

1/2" _1/2"CIRCULATING RELIEF VALVE

(barg)

60

(°C)

4

96

TEMP. INLET

(°C)

25 (°C)

PRESS. INLET

100.4 0.05

4801

401

0.1

RAW WATERCONSTRUCTION

10x8 M

0.999

*

150#FF

10"DISCHARGE

FACING

SIDELOCATION

150#

SIDEFF

SIZE

RATING@ PUMP TEMP.

NOZZLES

ARDEBIL

PATTERSON

15

TWO

PURCHASER'S REQUIREMENTS

MAIN DIESEL FIRE PUMPDATA SHEET

SI UNITS

ARDEBIL EXT. G.T.P.P.

FIRE FIGHTING

APPR. BY :0

GENERAL

15

SEP.2009TSM/AL-28/FF-M-31-DL0-001

S.P.

8

M.N.

S.R.

Page 10: Fire Fighting Pupms Data Sheet

PAGE OF

CONTRACT No. :

DOC. No. : DATE

PREPARED BY : CHECKED BY :

REVISION

48 ■ NUMBER OF STAGES: BARREL / CASE IMPELLER

49 □ BALANCING METHOD: WEAR RINGS BASE / SKID

50 ■ IMPELLER DIAMETER (mm) SHAFT SLEEVE

51 RATED STUFFING BOX TROTTLE BUSHING

52 MIN. BEARING HOUSING

53 MAX. REMARKS

54 COUPLING:

55 ■ TYPE: MFR: □ WEIGHTS56 ◘ SPACER LENGTH: WEIGHT OF PUMP (kg)

57 ◘ MATERIAL WEIGHT OF BASEPLATE (kg)

58 WEIGHT OF MOTOR (kg)

59 ■ BASEPLATE TYPE: TOTAL WEIGHT (kg) *

60 GROUTING HOLE:

61 REMARKS

62 PUMP LENGTH (m):

63 MINIMUM SUBMERGENCE (m):

64 MAXIMUM SUCTION HEIGHT (m):

65 ■ PACKING: MANUFACTURER COLUMN PIPE: FLANGED THREADED

66 TYPE LINE SHAFT: OPEN ENCLOSED

67 SIZE / MODEL GUIDE BUSHING LUBRICATOR:

68 ◘ MECHANICAL SEAL API CLASS CODE PUMP THRUST (N) UP DOWN

69 MANUFACTURER AT MIN. FLOW

70 SIZE / MODEL

71 ■ GLAND : TYPE / MODEL

72 QUENCH ◘ FLUSH ◘73 DRAIN ◘ VENT ◘74 MATERIAL:

75 ■ SEAL FLUSH PIPING PLAN REQUIRED

76 CARBON STEEL □ STAINLESS STEEL □

77 TUBE ■ PIPE □

78 THREADED □ FLANGED □

79 SEAL WELDED □ SOCKET - WELDED □

80 REMARKS

81 ● POLYURETHANE ,RED COLOR RAL 3000

82 □ OTHERS ( PLEASE SPECIFY )

8384 BEARING TYPE 1 NO. * *)Information must be given by manufacturer

85 RADIAL. ■ AXIAL □

86 BEARING TYPE 2 NO. *87 RADIAL. ■ AXIAL □

88 LUBRICATION TYPE:

89 GREASE ■ RING OIL ◘90 OIL MIST ◘ FLOOD ◘91 FLINGER ◘ PRESSURE ◘929394 ○ ANSI B73.1-1978 ANSI B73.2-197595 ● UL/FM ● NFPA-209697 NON -WIT WIT

98 HYDROSTATIC ○ ●99 PERFORMANCE ○ ●100 NPSH ○ ●101 COMPLETE UNIT TEST ● ○102

- PUMP STOP POINT :

PAINTING

15

M.N.

APPR. BY :

SEP.2009

9

0 S.R.

TSM/AL-28/FF-M-31-DL0-001

S.P.

N/A

N/A

- PUMP START POINT : ELECTRICAL PUMP START POINT MINUS 0.68 bar.g

PRESSURE SWITCH SET POINTS

MANUALLY

N/A

INSPECTION AND TEST

TEST

APPLICABLE STANDARDS

NOTES

STEEL

600600

9292129STEEL

SPECIAL DATA FOR VERTICAL PUMPS

STEEL

1

FELXIBLE

*

400 mm458 mm

444 mm

BEARINGS AND LUBRICATION

BORNZE

MECHANICAL SEAL OR PACKING

YES

SPLIT

1/2" Sq. 5SOFT PACKING

MATERIAL

*

CAST IRON

CAST IRON BRONZE BRONZE STEEL

STAINLESS STEEL(416SS)

MAIN DIESEL FIRE PUMPDATA SHEET

SI UNITS

CONSTRUCTION (CONTINUED)

Page 11: Fire Fighting Pupms Data Sheet

PAGE OF

CONTRACT No. :

DOC. No. : DATE

PREPARED BY : CHECKED BY :

REVISION

103

104 3- AN NPSH TEST IS ALSO REQUIRED AT 150% RATED FLOW .

105 4- FIRE PUMP CONTROLLER SHALL BE PROVIDED FOR EACH FIRE WATER PUMP .ENCLOSURE SHALL BE IP-44 .

106

107

108

109

110

111

112

113

114

115

116

117

118 - MAIN 8"- SIZE RELIEF VALVE IN ACCORDING TO TABLE 2-20 OF NFPA-20 (6" IS REQUIRED WITH 6"X10" WASTE CONE)

119 - 1/2" AUTOMATIC AIR RELEASE VALVE

120 - SPARE PARTS FOR COMMISSIONING & 2 YEARS

121 - SPECIAL TOOLS

122 - OTHER COMPLEMENTARY ACCESSORIES FOR PROPER OPERATION OF PUMP

123 - INSPECTION AND TESTING

124 - PRESERVATION AND EXPORT BOXING

125 - SUCTION & DISCHARGE LINES PRESSURE GAUGES

126

127

128

129

130131

132

133134

135

136

137

138

139

140

141

142

143

144

145

146

147148

149

150

- DOCUMENTATION

- COMBINED MANUAL/AUTOMATIC FIRE PUMP CONTROLLER AND CONTROLLER PANEL

- GAUGE BOARD (s)

- DIESEL ENGINE

- INTERCONNECTING POWER AND CONTROL WIRING/CABLING BETWEEN ALL EQUIPMENTS WITHIN BASEPLATE / CABINETS

- FLEXIBLE COUPLINGS & GUARDS

- COMMON BASEPLATE WITH ANCHOR POINTS ,LIFTING POINTS AND EARTH POINTS

- PUMP

CONTROLLER SHALL BE LOCATEED ON THE COMMON ENGINE & PUMP BASEPLATE .

5- SCOPE OF SUPPLY INCLUDES :

2-STAR ITEM SHOULD BE FILLED BY VENDOR

1- THE WHOLE PACKAGE SHALL BE FULLY COMPLIANT WITH NFPA-20 .

DATA SHEET SEP.2009

SI UNITS S.P. M.N.

GT3/AL-28/FF-M-31-DL0-001

10 15

MAIN DIESEL FIRE PUMP

0 APPR. BY : S.R.GENERAL NOTES

Page 12: Fire Fighting Pupms Data Sheet

PAGE OF

CONTRACT No. :

DOC. No. : DATE

PREPARED BY : CHECKED BY :

REVISION

1 APPLICABLE TO: ● PROPOSAL ○ PURCHASE ◘ AS BUILT

2 FOR UNIT

3 SITE SERVICE

4 NO. REQ. PUMP SIZE TYPE CENTRIFUGAL-HORIZONTAL5 MANUFACTURER MODEL

6 NOTE: ○ INDICATES INFORMATION COMPLETED BY PURCHASER □ BY MANUFACTURER ◘ BY MANUFACTURER OR PURCHASER

7 LIQUID

8 PUMPING TEMP. (°C) NORMAL

9 MAXIMUM

10 MINIMUM

11 RELATIVE DENSITY

12 VAPOR PRESSURE @ MAXIMUM TEMP. (bara) ■ HYDRAULIC TEST PRESSURE (barg)

13 VISCOSITY (CENTIPOISE) ■ DESIGN PRESSURE (barG):

14 ● CAPACITY (m3 / h) RATED ■ MAXIMUM ALLOWABLE WORKING PRESSURE AT RATED TEMP.(barG): 18

15 ● DISCHARGE PRESSURE (barg) □ SHUTT-OFF PRESSURE (barG):

16 ● SUCTION PRESSURE (barg) MAX/MIN / FLOW RATE / HEAD CURVE SUPPLIED : ● A02-8283417 ● DIFFERENTIAL HEAD (m) □ DRIVER SPEED (rpm)

18 ● DIFFERENTIAL PRESSURE (bar) □ EFFICIENCY AT RATED CAPACITY : 8119 ● □ EFFICIENCY AT 150% RATED CAPACITY : 7220 ● □ MIN. CONTINUOUS FLOW (m3 / h) MECHANICAL 100

21 ● THERMAL 100

22 ■ RATED POWER (KW):

23 LOCATION : NPSHA@ 150% RATED FLOW (mwc): □ MAX. HEAD WITH RATED IMPELLER (m): 118

24 ● INDOOR ○ HEATED ● UNDER ROOF ■ MAX. POWER WITH RATED IMPELLER (KW): 379

25 ○ OUTDOOR ● UNHEATED ○ PARTIAL SIDES □ REQUIRED NPSH AT 150% RATED CAPACITY (m) : 7.3

26 ○ GRADE ○ MEZZANINE ◘ COOLING / HEATING PIPING : MATERIAL

27 ● ELECTRICAL AREA CLASSIFICATION TUBE □ PIPE □28 CL GR DIV THREADED □ FLANGED □29 ● WINTERIZATION REQ'D ○ TROPICALIZATION REQ'D SEAL WELDED □ SOCKET - WELDED □30 SITE DATA : ◘ AUXILIARY PIPING: MATERIAL

31 ○ ALTITUDE (m) BAROMETER (mbara)

32 ○ RANGE OF AMBIENT TEMPS: MIN/MAX / CASING MOUNTING

33 ○ RELATIVE HUMIDITY: MAX./MIN. (%) CENTERLINE □ BRACKET □34 UNUSUAL CONDITIONS (2.1.23) ○ DUST ○ FUMES NEAR CENTERLINE □ IN -LINE □35 CHLORIDE CONTENTS 2184 PPM FOOT ■36 ○ UTILITY CONDITIONS: VERTICAL □ SUMP □37 STEAM: DRIVERS HEATING VERTICAL BARREL □ OTHERS □38 MIN (bar) (barg) CASING SPLIT: AXIAL ■ RADIAL □39 MAX (bar) (barg) CASING TYPE

40 ELECTRICITY: DRIVERS CONTROL HEATING SHUTDOWN SINGLE VOLUTE □ DOUBLE VOLUTE ◘41 VOLTAGE 6.6KV±10% 230 DIFFUSER □ STAGGERED □42 HERTZ 50(-4%,+2%) 50 IMPELLER MOUNTING:

43 PHASE 3 1 BETWEEN BEARINGS ■ OVERHUNG □44 COOLING WATER:

45 TEMP. RETURN

46 (barg) DESIGN

47 PRESS. RETURN (barg) MAX ALLOW DP

BALANCE DRUM

SEP.2008

SI UNITSTSM/AL-28/FF-M-31-DL0-001

S.P.

NOZZLES

FIRE FIGHTING ARDEBILARDEBIL EXT. G.T.P.P.

11

GENERAL

15

M.N.

CONSTRUCTION

TAG NO PATTERSON

PURCHASER'S REQUIREMENTSDISCHARGE

MAIN ELECTRICAL FIRE PUMPDATA SHEET

0 APPR. BY : S.R.

SUCTION

12x8 MAAONE

1"1/2"

CIRCULATING RELIEF VALVEDRAIN

1/2" 1/2"

VENT PRESSURE GAUGE

150#@ PUMP TEMP.

(°C)

(°C)

- 37 39.5

*

10.0

0.1

YES

N/A(°C)

(°C)

(barg)

N/A

10

● SITE AND UTILITY DATA

TEMP. INLET

N/AN/A (°C)

PRESS. INLET

N/A N/A (barg)

(°C)

96

(°C)

RAW WATER

15 SIZE

0.9991

45 LOCATION

RATING

12"

FF

SIDE

1340

FACING

SAFE AREA

MAX. SOUND LEVEL 85 dB(REV A)

95518

8"

150#

11.8

FF

27

SIDE

0.051470100

0.4

@ PUMP TEMP.1

860

HEAD LOSS FROM TANK TO PUMP SUCTION (mwc) 2.169

MINIMUM AVAILABLE STATIC SUCTION HEAD (mwc) 1.4

NPSH AVAILABLE@150%RATED CAPACITY(mwc) 9.

Page 13: Fire Fighting Pupms Data Sheet

PAGE OF

CONTRACT No. :

DOC. No. : DATE

PREPARED BY : CHECKED BY :

REVISION

48 ■ NUMBER OF STAGES: BARREL / CASE IMPELLER

49 □ BALANCING METHOD: WEAR RINGS BASE / SKID

50 ■ IMPELLER DIAMETER (mm) SHAFT SLEEVE

51 RATED STUFFING BOX TROTTLE BUSHING

52 MIN. BEARING HOUSING

53 MAX. REMARKS

54 COUPLING:

55 ■ TYPE: MFR: □ WEIGHTS56 ◘ SPACER LENGTH: WEIGHT OF PUMP (kg)

57 ◘ MATERIAL WEIGHT OF BASEPLATE (kg)

58 WEIGHT OF MOTOR (kg)

59 ■ BASEPLATE TYPE: TOTAL WEIGHT (kg)

60 GROUTING HOLE:

61 REMARKS

62 PUMP LENGTH (m):

63 MINIMUM SUBMERGENCE (m):

64 MAXIMUM SUCTION HEIGHT (m):

65 ■ PACKING: MANUFACTURER COLUMN PIPE: FLANGED THREADED

66 TYPE LINE SHAFT: OPEN ENCLOSED

67 SIZE / MODEL GUIDE BUSHING LUBRICATOR:

68 ◘ MECHANICAL SEAL API CLASS CODE PUMP THRUST (N) UP DOWN

69 MANUFACTURER AT MIN. FLOW

70 SIZE / MODEL

71 GLAND: TYPE / MODEL

72 QUENCH ◘ FLUSH ◘ ◘ MANUFACTURER

73 DRAIN ◘ VENT ◘ □ □ (RPM)

74 MATERIAL: ◙ HORIZONTAL ◘ VERTICAL

75 ◘ SEAL FLUSH PIPING PLAN REQUIRED ■ FRAME

76 CARBON STEEL □ STAINLESS STEEL □ ◘ SERVICE FACTOR

77 TUBE ■ PIPE □ ◘ KVOLTS/PHASE/HERTZ 6.6KV±10% / / 50(-4%,+2%)

78 THREADED □ FLANGED □ □ CLOCKWISE □ □

79 SEAL WELDED □ SOCKET - WELDED □ ◘ ENCLOSURE

80 REMARKS ◘ STARTING METHOD

81 ◘ LUBE

82 □ VERTICAL THRUST CAPACITY

83 UP (N) DOWN

84 BEARING TYPE 1 NO. BEARINGS (TYPE / NUMBER):

85 RADIAL. ■ AXIAL □ □ RADIAL /86 BEARING TYPE 2 NO. □ THRUST /

87 RADIAL. ■ AXIAL □

88 LUBRICATION TYPE:

89 GREASE ■ RING OIL ◘90 OIL MIST ◘ FLOOD ◘91 FLINGER ◘ PRESSURE ◘929394 ○ ANSI B73.1-1978 ANSI B73.2-197595 ● UL/FM ● NFPA-209697 NON -WIT WIT ● POLYURETHANE ,RED COLOR RAL 3001

98 HYDROSTATIC ○ ● □ OTHERS ( PLEASE SPECIFY )

99 PERFORMANCE ○ ●100 NPSH ○ ●101 COMPLETE UNIT TEST ● ○ *)Information must be given by manufacturer

102

BEARINGS AND LUBRICATION

GREASE

IP 55

3

MOTOR DRIVE

1.0

1470

APPR. BY :

(KW)

COUNTER CLOCKWISE

CAST IRON

0 S.R.MATERIAL

*

(N)

500

ABB/SIEMENS*

ROTATION

1

*

DOL

1000

MAIN ELECTRICAL FIRE PUMPDATA SHEET

SI UNITS

CONSTRUCTION (CONTINUED)

559539584

N/A

N/AN/A

STEEL

*FLEXIBLE

SOFT PACKING

FABRICATED STEEL

MECHANICAL SEAL OR PACKING

BRONZE

1/2 Square/5

12

SEP.2009

S.P.

15

M.N.

TSM/AL-28/FF-M-31-DL0-001

BRONZE* STEEL

STAINLESS STEEL(416SS) STEEL

SPECIAL DATA FOR VERTICAL PUMPS

INSPECTION AND TEST

*

TEST

MANUALLY

DUTY JOCKEY PUMP START POINT MINUS 0.68 bar.gAPPLICABLE STANDARDS

PAINTING

*

*

- PUMP START POINT :

BALLBALL

PRESSURE SWITCH SET POINTS

- PUMP STOP POINT :

NOTES

Page 14: Fire Fighting Pupms Data Sheet

PAGE OF

CONTRACT No. :

DOC. No. : DATE

PREPARED BY : CHECKED BY :

REVISION

103

104

106 CONTROLLER SHALL BE LOCATEED ON THE COMMON ENGINE & PUMP BASEPLATE .

107 3- ONE METERING DEVICE SHALL BE SUPPLIED FOR PUMP CAPACITY IN ACCORDING TO TABLE 2-20 OF NFPA-20 .

108 4- CONTROL PANEL IS FREE STANDING .

109

109

110

111

112

113

114

115

116

117

118

119

120

121

122

123

124

125

126

127

128

129

130

131132

133

134135

136

137

138

139

140

141

142

143

144

145

146

147

148149

150

SI UNITS

- COMBINED MANUAL/AUTOMATIC FIRE PUMP CONTROLLER AND CONTROLLER PANEL

GENERAL NOTES

S.P. M.N.

0 APPR. BY :

- PUMP

13 15

MAIN ELECTRICAL FIRE PUMP

- * SIZE AUTOMATIC AIR RELEASE VALVE

TSM/AL-28/FF-M-31-DL0-001 SEP.2008DATA SHEET

6- SCOPE OF SUPPLY INCLUDES :

S.R.

5- THE NOMINAL POWER OF ELECTRICAL MOTOR IS SELECTED BAISED ON DERATED CALCULATION FOR 42˚c

1- THE WHOLE PACKAGE SHALL BE FULLY COMPLIANT WITH NFPA-20 .

- SPECIAL TOOLS ( NOT REQUIRED STATED BY VENDOR )

- MOTOR DRIVER

- INTERCONNECTING POWER AND CONTROL WIRING/CABLING BETWEEN ALL EQUIPMENTS WITHIN BASEPLATE/CABINETS

- OTHER COMPLEMENTARY ACCESSORIES FOR PROPER OPERATION OF PUMP

- DOCUMENTATION

- GAUGE BOARD (s)

- * SIZE CIRCULATING RELIEF VALVE

- FLEXIBLE COUPLINGS & GUARDS

- COMMON BASEPLATE WITH ANCHOR POINTS ,LIFTING POINTS AND EARTH POINTS

- INSPECTION AND TESTING

- PRESERVATION AND EXPORT BOXING

- *SIZE METERING DEVICE ON 10" SIZE TEST LINE

- SPARE PARTS FOR COMMISSIONING & 2 YEARS

- SUCTION & DISCHARGE LINES PRESSURE GAUGES

Page 15: Fire Fighting Pupms Data Sheet

PAGE OF

CONTRACT No. :

DOC. No. : DATE

PREPARED BY : CHECKED BY :

REVISION

1 APPLICABLE TO: ● PROPOSAL ○ PURCHASE ◘ AS BUILT

2 FOR UNIT

3 SITE SERVICE

4 NO. REQ. PUMP SIZE TYPE

5 MANUFACTURER MODEL TAG NO.

6 NOTE: ○ INDICATES INFORMATION COMPLETED BY PURCHASER □ BY MANUFACTURER ◘ BY MANUFACTURER OR PURCHASER

7 LIQUID

8 PUMPING TEMP. (°C) NORMAL

9 MAXIMUM

10 MINIMUM

11 RELATIVE DENSITY

12 VAPOR PRESSURE @ MAXIMUM TEMP. (bara) □ HYDRAULIC TEST PRESSURE (barg)

13 VISCOSITY (CENTIPOISE) □ DESIGN PRESSURE (barG):

14 ● CAPACITY (m3 / h) RATED □ MAXIMUM ALLOWABLE WORKING PRESSURE AT RATED TEMP.(barG): 2515 ● DISCHARGE PRESSURE (barg) □ SHUTT-OFF PRESSURE (barG):

16 ● SUCTION PRESSURE (barg) MAX/MIN / FLOW RATE / HEAD CURVE SUPPLIED : ● NO ○17 ● DIFFERENTIAL HEAD (m) □ DRIVER SPEED (rpm) 295018 ● DIFFERENTIAL PRESSURE (bar) □ EFFICIENCY AT RATED CAPACITY : *19 ● □ EFFICIENCY AT 150% RATED CAPACITY : *20 ● □ MIN. CONTINUOUS FLOW (m3 / h) MECHANICAL

21 ● THERMAL

22 □ RATED POWER (KW):

23 LOCATION : □ MAX. HEAD WITH RATED IMPELLER (m): 10 Barg

24 ● INDOOR ○ HEATED ● UNDER ROOF □ MAX. POWER WITH RATED IMPELLER (KW): *

25 ○ OUTDOOR ● UNHEATED ○ PARTIAL SIDES □ REQUIRED NPSH AT 150% RATED CAPACITY (m) : *26 ○ GRADE ○ MEZZANINE ◘ COOLING / HEATING PIPING : MATERIAL

27 ● ELECTRICAL AREA CLASSIFICATION TUBE □ PIPE □28 CL GR DIV THREADED □ FLANGED □29 ● WINTERIZATION REQ'D ○ TROPICALIZATION REQ'D SEAL WELDED □ SOCKET - WELDED □30 SITE DATA : ◘ AUXILIARY PIPING: MATERIAL

31 ○ ALTITUDE (m) BAROMETER (mbara)

32 ○ RANGE OF AMBIENT TEMPS: MIN/MAX CASING MOUNTING (VERTICAL INLINE PUMP)33 ○ RELATIVE HUMIDITY: MAX./MIN. (%) CENTERLINE □ BRACKET □34 UNUSUAL CONDITIONS : ○ DUST ○ FUMES NEAR CENTERLINE □ IN -LINE □35 CHLORIDE CONTENTS 2184 PPM FOOT

36 ○ UTILITY CONDITIONS: VERTICAL ◙ SUMP □37 STEAM: DRIVERS HEATING VERTICAL BARREL □ OTHERS □38 MIN (bar) (barg) CASING SPLIT: AXIAL □ RADIAL ◙39 MAX (bar) (barg) CASING TYPE

40 ELECTRICITY: DRIVERS CONTROL HEATING SHUTDOWN SINGLE VOLUTE □ DOUBLE VOLUTE □41 VOLTAGE 400V±10% DIFFUSER □ STAGGERED □42 HERTZ 50(-4%,+2%) IMPELLER MOUNTING:

43 PHASE 3 BETWEEN BEARINGS □ OVERHUNG ◙44 COOLING WATER :

45 TEMP. RETURN

46 (barg) DESIGN

47 PRESS. RETURN (barg) MAX ALLOW DP

● SITE AND UTILITY DATA *

100

- 37

PURCHASER'S REQUIREMENTSRAW WATER

15

10.0

401

@ PUMP TEMP.

10

1

TWO

SAFE AREA

0.999

NPSH AVAILABLE@150%RATED CAPACITY(mwc) *

(°C)

(°C)

(°C)

96

980

39.5

(°C)

N/A (barg)

(barg)N/A

150 150

6

0.1RATING

(°C)

(°C)N/A

SIDESIDE

HEAD LOSS FROM TANK TO PUMP SUCTION (mwc) 1.821

MINIMUM AVAILABLE STATIC SUCTION HEAD (mwc) *

MAX. SOUND LEVEL 85 dB(REV A)

PRESS. INLET

N/A

TEMP. INLET

N/A(°C)N/A

*

CIRCULATING RELIEF VALVE

*) Information must be given by manufacturer

VENT PRESSURE GAUGEDRAIN

CENTRIFUGAL/VERTICAL

CONSTRUCTION

RF

DN25

RF

DN32LOCATION

NOZZLES

*

14

JOCKEY ELECTRICAL PUMPDATA SHEET

15

SEP.2009TSM/AL-28/FF-M-31-DL0-001

FIRE FIGHTING

SI UNITS

S.R.

S.P.

APPR. BY :0GENERAL

M.N.

ARDEBIL

ARDEBIL G.T.P.P.

DISCHARGE

SIZE

FACING

BALANCE DRUMSUCTION

@ PUMP TEMP.

15YES0.0650.25

Page 16: Fire Fighting Pupms Data Sheet

PAGE OF

CONTRACT No. :

DOC. No. : DATE

PREPARED BY : CHECKED BY :

REVISION

48 ◘ NUMBER OF STAGES: BARREL / CASE IMPELLER

49 □ BALANCING METHOD: WEAR RINGS BASE / SKID

50 □ IMPELLER DIAMETER (mm) SHAFT SLEEVE

51 RATED STUFFING BOX TROTTLE BUSHING

52 MIN. BEARING HOUSING

53 MAX. REMARKS

54 COUPLING:

55 ◘ TYPE: MFR: □ WEIGHTS56 ◘ SPACER LENGTH: WEIGHT OF PUMP (kg)

57 ◘ MATERIAL WEIGHT OF BASEPLATE (kg)

58 WEIGHT OF MOTOR (kg)

59 □ BASEPLATE TYPE: TOTAL WEIGHT (kg)

60 GROUTING HOLE:

61 REMARKS

62 PUMP LENGTH (m):

63 MINIMUM SUBMERGENCE (m):

64 MAXIMUM SUCTION HEIGHT (m):

65 ◘ PACKING: MANUFACTURER COLUMN PIPE: FLANGED THREADED

66 TYPE LINE SHAFT: OPEN ENCLOSED

67 SIZE / MODEL GUIDE BUSHING LUBRICATOR:

68 ◘ MECHANICAL SEAL API CLASS CODE PUMP THRUST (N) UP DOWN

69 MANUFACTURER AT MIN. FLOW

70 SIZE / MODEL

71 GLAND: TYPE / MODEL

72 QUENCH ◘ FLUSH ◘ ◘ MANUFACTURER

73 DRAIN ◘ VENT ◘ ■ ■ (RPM)

74 MATERIAL: □ HORIZONTAL ◙ VERTICAL

75 ◘ SEAL FLUSH PIPING PLAN REQUIRED □ FRAME

76 CARBON STEEL □ STAINLESS STEEL □ ◘ SERVICE FACTOR

77 TUBE □ PIPE □ ◘ VOLTS/PHASE/HERTZ / /78 THREADED □ FLANGED □ □ CLOCKWISE □ □79 SEAL WELDED □ SOCKET - WELDED □ ◘ ENCLOSURE

80 REMARKS ◘ STARTING METHOD

81 ◘ LUBE

82 □ VERTICAL THRUST CAPACITY

83 UP (N) DOWN

84 BEARINGS (TYPE / NUMBER):

85 BEARING TYPE 1 NO. □ RADIAL /86 RADIAL. □ AXIAL □ □ THRUST /87 BEARING TYPE 2 NO.

88 RADIAL. □ AXIAL □89 LUBRICATION TYPE:

90 GREASE ◘ RING OIL ◘91 OIL MIST ◘ FLOOD ◘92 FLINGER ◘ PRESSURE ◘939495 ○ ANSI B73.1-1978 ANSI B73.2-197596 ● UL/FM ● NFPA-209798 ● POLYURETHANE ,RED COLOR RAL 3000

99 □ OTHERS ( PLEASE SPECIFY )

100101 NON -WIT WIT

102 HYDROSTATIC ○ ●103 PERFORMANCE ○ ●104 NPSH ○ ●105 COMPLETE UNIT TEST ● ○106

BALL

DUTY PUMP STOP POINT MINUS 0.68 bar.g

SHALL BE SUPPLIED .

PUMP PRESSURE SWITCH SET POINTS - DUTY PUMP STOP POINT :

BALL

- DUTY PUMP START POINT :

CHURN PRESSURE + MINIMUM STATIC SUPPLY PRESSURE

- RESERVE PUMP STOP POINT :

APPLICABLE STANDARDS CHURN PRESSURE + MINIMUM STATIC SUPPLY PRESSURE

- RESERVE PUMP START POINT :

DUTY PUMP START POINT MINUS 0.34 bar.g

PAINTING

*)Information must be given by manufacturer

GENERAL NOTES

SS

SS SS

SPECIAL DATA FOR VERTICAL PUMPS

INSPECTION AND TEST TEST

15

CAST IRON

SEP.2009

S.P.

0 S.R.

15

APPR. BY :

TSM/AL-28/FF-M-31-DL0-001

1- SUCTION & DISCHARGE LINES PRESSURE GAUGES

M.N.

MATERIAL

**

*

DIRECT ON LINE

2890-2910

MECHANICAL SEAL OR PACKING

4 (KW)

MOTOR DRIVE

JOCKEY ELECTRICAL PUMPDATA SHEET

SI UNITS

CONSTRUCTION (CONTINUED)

1

BEARINGS AND LUBRICATION

(N)

*

50

ROTATION COUNTER CLOCKWISE

400 3

IP-55

Page 17: Fire Fighting Pupms Data Sheet

Patterson Pump Company Ltd P. O. Box 72083, Helioupolis 16310, Athens, Greece Tel.: +30 210-965-0511 Fax: +30 210-965-1467 E-mail: [email protected]

6 October 2009 MAPNA Power Plants Construction & Development Co. Tehran, Iran Attention : MR. H. A. GOLSORKHI Contract Manager for Mechanical Systems Our Ref. : RRQ-330 Project : ARDEBIL GTPP (Extension Phase)

TECHNICAL CLARIFICATIONS

Dear Mr. Golsorkhi, With regards to your mail of October 5, please see our response below: MAPNA Comments – October 5, 2009 Patterson Response –October 6, 2009 1. The curve of pumps shall be submitted as

per required capacity in data sheets (4200 & 2100 GPM not 4000 & 2000 GPM) and specified operation point on curve.

Please see attached curve for Q = 4200 GPM and Q = 2100 GPM. Please note that pumps are UL listed, FM approved for Q = 4000 GPM and Q = 2000 GPM.

2. Altitude correction factor for ARDEBIL site

shall be considered in selection of diesel pumps.

The derating power for 1340 m is 0.86. Engine site power at 1340 m elevation is : 360 x 0.86 = 310 HP. The max pump power is 280 HP.

3. Fuel daily tank for each diesel pump shall

be considered. Each package is provided with 440 gallon fuel tank.

4. Flow meter for test line and relief valve for

diesel pump shall be considered. One flow meter is provided. One pressure relief valve for each diesel package is provided (total 2 pcs).

5. Below mention tests shall be done under

witness:

a) Standard Shop Test Provided. b) Hydrostatic Test Provided. c) Mechanical Running & Performance

Test Performance test for all main pumps provided. Mechanical running test is done in the field by our Service Engineer. We can perform mechanical running test for pump with diesel engine and controller at the factory for one hour.

Page 18: Fire Fighting Pupms Data Sheet

PATTERSON PUMP COMPANY LTD Technical Clarifications 6 October 2009

Our Ref.: RRQ-330 Page 2 of 2

MAPNA Comments – October 5, 2009 Patterson Response –October 5, 2009

d) NPSH Performance Test If NPSH A > NPSH R by more than 1 m, the NPSH test is not required. Our pumps have NPSH R 3.5 m and NPSH A is over 7 m and the difference is 3.5 m or more. Therefore, no NPSH test is required. Please note that in order for fire pumps to be UL listed and FM approved, they need to have low NPSH R.

Should you require any further clarifications, please do not hesitate to contact our office. On behalf of PATTERSON PUMP COMPANY LTD Very truly yours, ARIS GEORGAKIS Regional Sales Manager vp