FIRE ALARM COVER SHEET FA0.0 Seal: GWWO INC. 800 WYMAN PARK DRIVE, SUITE 300 BALTIMORE, MARYLAND 21211, 4103321009 C 2012 GWWO INC. I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A DULY LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF A MARYLAND, LICENSE NUMBER , EXPIRATION DATE Revisions: Job No. Scale Date Drawing Title Sheet Drawn Checked Approved Drawing Number Of Date/Time Stamp File Path KEYNOTES LISTED ON THIS SHEET ARE FOR CONVENIENCE ONLY. REFER TO SHEET CS.2 FOR COMPLETE LIST 1/8" = 1'90" PORT CANAVERAL WELCOME CENTER CANAVERAL PORT AUTHORITY 1124 RC TC EA No. Date Description N 8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD 21045 410975092246 (BALT) 410975092588 (FAX) AUGUST 6 2012 CONSTRUCTION SET Seal: 1 8/06/12 CONSTRUCTION SET FIRE ALARM SYSTEM PROJECT NOTES FIRE ALARM SYSTEM ABBREVIATIONS A ALHPA9NUMERIC ACT ACOUSTICAL CEILING TILE AFF ABOVE FINISHED FLOOR AHU AIR HANDLING UNIT DACT DIGITAL ALARM COMMUNICATOR TRANSMITTER EOL END OF LINE RESISTOR ETR EXISTING TO REMAIN FA FIRE ALARM FAA FIRE ALARM ANNUNCIATOR PANEL FACP FIRE ALARM CONTROL PANEL HVAC HEATING, VENTILATION AND AIR CONDITIONING IDC INITIATING DEVICE CIRCUIT LCD LIQUID CRYSTAL DISPLAY LED LIGHT EMITTING DIODE MAX MAXIMUM MIN MINIMUM MT METAL TILE N.C. NORMALLY CLOSED (CONTACT) N.O. NORMALLY OPEN (CONTACT) NAC NOTIFICATION APPLIANCE CIRCUIT NIC NOT IN CONTRACT NTS NOT TO SCALE PL PLASTER POC POINT OF CONNECTION RA RETURN AIR (HVAC) RTU ROOF TOP UNIT RX REMOVE EXISTING DEVICE SA SUPPLY AIR (HVAC) SLC SIGNALING LINE CIRCUIT SPL HIDDEN SPLINE (CEILING) TYP TYPICAL UNO UNLESS NOTED OTHERWISE WP WEATHER PROOF 1. THE SCOPE OF WORK SHALL BE TO PROVIDE A NEW EMERGENCY VOICE AND ALARM COMMUNICATION SYSTEM (EVAC) FOR PORT CANAVERAL WELCOME CENTER BUILDING, HEREAFTER REFERRED TO AS THE PROJECT. ALARM FROM THE EVAC SHALL EVACUATE THE ENTIRE BUILDING. 2. THESE DRAWINGS ARE CONCEPTUAL AND ARE INTENDED TO SHOW GENERAL SYSTEM CONFIGURATION AND PERFORMANCE. NOT ALL NECESSARY DEVICES AND COMPONENTS ARE SHOWN. CONTRACTOR SHALL PROVIDE ALL DEVICES AND COMPONENTS FOR A FULLY FUNCTIONAL, CODE COMPLIANT SYSTEM. 3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PREPARING SHOP DRAWINGS, OBTAINING PERMITS, AND FOR FURNISHING AND INSTALLING ALL MATERIALS AND EQUIPMENT REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. ANY MODIFICATIONS TO APPROVED SHOP DRAWINGS SHALL BE COORDINATED WITH THE OWNER. 4. ALL REFERENCES TO THE ENGINEER SHALL MEAN KOFFEL ASSOCIATES, INC. 5. ALL REFERENCES TO THE OWNER SHALL MEAN CANAVERAL PORT AUTHORITY. 6. THE CONTRACTOR SHALL COORDINATE BETWEEN MECHANICAL, ELECTRICAL, AND OTHER TRADES TO FACILITATE AN INSTALLATION WHICH IS CONSISTENT WITH THE BUILDING DESIGN AND OVERALL GOAL OF CONTINUOUS OPERATION. ANY CONDITIONS FOUND ON9SITE THAT RESULT IN DEVIATIONS IN THE DESIGN DOCUMENTS MUST BE APPROVED BY THE ENGINEER AND OWNER. 7. FIRE ALARM AND DETECTION SYSTEM DESIGN AND INSTALLATION SHALL COMPLY WITH 9 FLORIDA BUILDING CODE, 2010 EDITION 9 NFPA 70, NATIONAL ELECTRICAL CODE, 2008 EDITION 9 NFPA 72, NATIONAL FIRE ALARM CODE, 2007 EDITION 9 FLORIDA FIRE PREVENTION CODE, 2010 EDITION 9 ALL MANUFACTURER'S REQUIREMENTS AND ALL APPLICABLE LOCAL AND STATE CODES AND REGULATIONS 9 ALL EQUIPMENT SHALL BE LISTED FOR USE ON COMMERCIAL FIRE ALARM SYSTEMS 8. ALL AREAS PROVIDED WITH FIRE ALARM EQUIPMENT SHALL BE ASSUMED TO BE PROVIDED WITH A MINIMUM AMBIENT TEMPERATURE OF 40 DEGREES AND BE FREE OF EXCESSIVE DUST PARTICLES OR HUMIDITY LEVELS, UNLESS NOTED OTHERWISE. 9. REFER TO THE FIRE ALARM OPERATIONAL MATRIX ON SHEET FA94.0 FOR SYSTEM FUNCTION REQUIREMENTS. 10. ALL NEW FIRE ALARM SYSTEM WIRING SHALL BE IN CONDUIT. SIZE OF CONDUIT AND PERCENT FILL SHALL BE DETERMINED BY THE INSTALLING CONTRACTOR AND SHALL BE IN ACCORDANCE WITH NFPA 70, THE NATIONAL ELECTRIC CODE, 2008 EDITION. 11. SYSTEM CIRCUITS SHALL CONFORM TO THE FOLLOWING: SYSTEM RISER: CLASS A SIGNALING LINE CIRCUITS: CLASS B NOTIFICATION APPLIANCE CIRCUITS: CLASS B INITIATING DEVICE CIRCUITS: CLASS B 12. ALL ADDRESSABLE CONTROL MODULES AND ADDRESSABLE MONITOR MODULES SHALL BE LOCATED WITHIN 3 FEET OF THE ASSOCIATED NON9INTELLIGENT DEVICE MONITORED OR CONTROLLED. 13. ALL FIRE ALARM CONDUIT AND JUNCTION BOXES SHALL BE INSTALLED AS HIGH AS POSSIBLE. IN NO CASE SHALL ANY PORTION OF THE FIRE ALARM WIRING BE INSTALLED BELOW THE BOTTOM HORIZONTAL PLANE OF LIGHTING FIXTURES, WITH THE EXCEPTION OF DROPS TO INDIVIDUAL FIRE ALARM DEVICES AND PANELS. IN AREAS WITH SUSPENDED CEILINGS ALL FIRE ALARM CONDUIT SHALL BE CONCEALED. PROVIDE ACCESS PANELS FOR ALL CONCEALED FIRE ALARM DEVICES AND JUNCTION BOXES, WHERE REQUIRED. 14. PROVIDE AN EMERGENCY VOICE ALARM COMMUNICATIONS SYSTEM WITHIN AREA OF WORK. ALL AUDIBLE SPEAKER AND VISUAL STROBE NOTIFICATION DEVICES SHALL BE WALL MOUNTED AT 96 INCHES ABOVE THE FINISHED FLOOR OR CEILING MOUNTED, PER NFPA 72. NOTIFICATION DEVICES SHALL BE INSTALLED NOT TO INTERFERE WITH EQUIPMENT. 15. A FULL ACCEPTANCE TEST OF ALL NEW FIRE ALARM SYSTEM COMPONENTS IS REQUIRED AS PART OF THIS PROJECT. THIS SHALL INCLUDE A FUNCTIONAL TEST OF 100% OF NEW INITIATING DEVICES, AS WELL AS A TEST OF ALL INPUT/OUTPUT FUNCTIONS. THE CONTRACTOR SHALL ALSO TEST ALL NETWORK AND REPORTING CONDITIONS. INSTALLING CONTRACTOR SHALL PROVIDE ALL MATERIALS AND TECHNICAL SUPPORT TO PERFORM ACCEPTANCE TEST IN ACCORDANCE WITH NFPA 72. 16. APPLY FOR, PAY FOR, AND OBTAIN ANY PERMITS, INSPECTIONS, AND TESTING REQUIRED FOR THIS WORK. 17. UTILIZE WEATHERPROOF DEVICES IN AREAS EXPOSED TO THE OUTSIDE ENVIRONMENT. INCLUDE WEATHERPROOF BACKBOXES AND CONDUIT. FIRE ALARM SYSTEM SYMBOLS FIRE ALARM CONTROL PANEL FIRE ALARM ANNUNCIATOR PANEL (SUBSCRIPT DENOTES TYPE) FIRE ALARM TRANSMITTER FIRE ALARM COMMUNICATOR FIRE ALARM TRANSPONDER PANEL DIGITAL ALARM COMMUNICATOR BOOSTER POWER SUPPLY VOICE EVACUATION SYSTEM CONTROL PANEL ADDRESSABLE INPUT MODULE (MONITOR MODULE) ADDRESSABLE OUTPUT MODULE (CONTROL MODULE) ISOLATOR MODULE NAC POWER EXTENDER PANEL END OF LINE DEVICE VOICE EVACUATION SYSTEM REMOTE MICROPHONE CONTROL PANEL BATTERIES FIREFIGHTER'S SMOKE CONTROL PANEL ULTRAVIOLET/INFRARED FLAME DETECTOR AUDIBLE NOTIFICATION APPLIANCE VISIBLE NOTIFICATION APPLIANCE (SUBSCRIPT DENOTES CANDELA RATING) COMBINATION AUDIBLE/VISIBLE APPLIANCE (SUBSCRIPT DENOTES CANDELA RATING) ROTATING BEACON ALARM BELL WATER MOTOR GONG ELECTRO9MAGNETIC DOOR HOLDER FIRE DAMPER SMOKE DAMPER COMBINATION FIRE/SMOKE DAMPER REMOTE TEST STATION ADDRESSABLE RELAY MODULE AMPLIFIER FIRE ALARM ZONE BOUNDARY RATE COMPENSATION HEAT DETECTOR COMBINATION FIXED TEMPERATURE AND RATE OF RISE HEAT DETECTOR ELEVATOR RECALL HEAT DETECTOR GAS DETECTOR SMOKE DETECTOR ELEVATOR RECALL SMOKE DETECTOR IONIZATION SMOKE DETECTOR BEAM SMOKE DETECTOR 9 TRANSMITTER BEAM SMOKE DETECTOR 9 RECEIVER SMOKE DETECTOR WITH SOUNDER BASE SPOT TYPE VEWFD SMOKE DETECTOR UNDER FLOOR SMOKE DETECTOR ABOVE CEILING SMOKE DETECTOR CRAH/CRAC UNIT SMOKE DETECTOR DUCT SMOKE DETECTOR (SUPERSCRIPT DENOTES SUPPLY OR RETURN) FLAME DETECTOR ULTRAVIOLET FLAME DETECTOR INFRARED FLAME DETECTOR FIRE ALARM TERMINAL CABINET FLOW SWITCH PRESSURE SWITCH WATER PRESSURE SWITCH LOW AIR PRESSURE SWITCH HIGH AIR PRESSURE SWITCH COMBINATION HIGH/LOW AIR PRESSURE SWITCH TAMPER SWITCH VALVE WITH TAMPER SWITCH SUPPRESSION SYSTEM ACTIVATION (SUBSCRIPT DENOTES SYSTEM TYPE) SUPPRESSION SYSTEM ABORT SWITCH (SUBSCRIPT DENOTES SYSTEM TYPE) FIRE ALARM MANUAL PULL STATION FIRE SERVICE TELEPHONE FIRE SERVICE TELEPHONE JACK HEAT DETECTOR FIXED TEMPERATURE HEAT DETECTOR RATE OF RISE HEAT DETECTOR R F P J XX LH HA LA XX BATT FATC W FACP ANN FTR FAC FATP DACT BPS EVAC AIM AOM ISO NAC EOL MIC UV/IR IR UV X C A U V SB E BR BT I E R/F R/C XX C XX C C FSCP RT ARM AMP CE - 001

Transcript of FIRE ALARM SYSTEM SYMBOLS - Skanska · florida building code, 2010 edition 9 nfpa 70, national...

Page 1: FIRE ALARM SYSTEM SYMBOLS - Skanska · florida building code, 2010 edition 9 nfpa 70, national electrical code, 2008 edition nfpa 72, national fire alarm code, 2007 edition 9 florida

FIRE ALARMCOVER SHEET FA0.0

Seal:

GWWO INC.

800 WYMAN PARK DRIVE, SUITE 300

BALTIMORE, MARYLAND 21211, 410�332�1009

C 2012 GWWO INC.

I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THATI AM A DULY LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF A MARYLAND,

LICENSE NUMBER , EXPIRATION DATE

Revisions:

Job No.

Scale

Date

Drawing Title

Sheet

Drawn

Checked

Approved

Drawing Number

OfDa

te/T

ime S

tam

pF

ile P

ath

KEYNOTES LISTED ON THIS SHEET ARE FOR CONVENIENCEONLY. REFER TO SHEET CS.2 FOR COMPLETE LIST

1/8" = 1'90"

PORT CANAVERALWELCOME CENTER

CANAVERAL PORT AUTHORITY

1124 RC

TC

EA

No. Date Description

N

8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD 21045

410975092246 (BALT) 410975092588 (FAX)

AUGUST 6 2012

CONSTRUCTION SET

Seal:

1 8/06/12 CONSTRUCTION SET

FIRE ALARM SYSTEM PROJECT NOTES

FIRE ALARM SYSTEM ABBREVIATIONS

A ALHPA9NUMERIC

ACT ACOUSTICAL CEILING TILE

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

DACT DIGITAL ALARM COMMUNICATOR

TRANSMITTER

EOL END OF LINE RESISTOR

ETR EXISTING TO REMAIN

FA FIRE ALARM

FAA FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

HVAC HEATING, VENTILATION AND AIR

CONDITIONING

IDC INITIATING DEVICE CIRCUIT

LCD LIQUID CRYSTAL DISPLAY

LED LIGHT EMITTING DIODE

MAX MAXIMUM

MIN MINIMUM

MT METAL TILE

N.C. NORMALLY CLOSED (CONTACT)

N.O. NORMALLY OPEN (CONTACT)

NAC NOTIFICATION APPLIANCE CIRCUIT

NIC NOT IN CONTRACT

NTS NOT TO SCALE

PL PLASTER

POC POINT OF CONNECTION

RA RETURN AIR (HVAC)

RTU ROOF TOP UNIT

RX REMOVE EXISTING DEVICE

SA SUPPLY AIR (HVAC)

SLC SIGNALING LINE CIRCUIT

SPL HIDDEN SPLINE (CEILING)

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

WP WEATHER PROOF

1. THE SCOPE OF WORK SHALL BE TO PROVIDE A NEW EMERGENCY VOICE

AND ALARM COMMUNICATION SYSTEM (EVAC) FOR PORT CANAVERAL

WELCOME CENTER BUILDING, HEREAFTER REFERRED TO AS THE

PROJECT. ALARM FROM THE EVAC SHALL EVACUATE THE ENTIRE

BUILDING.

2. THESE DRAWINGS ARE CONCEPTUAL AND ARE INTENDED TO SHOW

GENERAL SYSTEM CONFIGURATION AND PERFORMANCE. NOT ALL

NECESSARY DEVICES AND COMPONENTS ARE SHOWN. CONTRACTOR

SHALL PROVIDE ALL DEVICES AND COMPONENTS FOR A FULLY

FUNCTIONAL, CODE COMPLIANT SYSTEM.

3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PREPARING SHOP

DRAWINGS, OBTAINING PERMITS, AND FOR FURNISHING AND INSTALLING

ALL MATERIALS AND EQUIPMENT REQUIRED FOR A COMPLETE AND

OPERATIONAL SYSTEM. ANY MODIFICATIONS TO APPROVED SHOP

DRAWINGS SHALL BE COORDINATED WITH THE OWNER.

4. ALL REFERENCES TO THE ENGINEER SHALL MEAN KOFFEL ASSOCIATES,

INC.

5. ALL REFERENCES TO THE OWNER SHALL MEAN CANAVERAL PORT

AUTHORITY.

6. THE CONTRACTOR SHALL COORDINATE BETWEEN MECHANICAL,

ELECTRICAL, AND OTHER TRADES TO FACILITATE AN INSTALLATION WHICH

IS CONSISTENT WITH THE BUILDING DESIGN AND OVERALL GOAL OF

CONTINUOUS OPERATION. ANY CONDITIONS FOUND ON9SITE THAT

RESULT IN DEVIATIONS IN THE DESIGN DOCUMENTS MUST BE APPROVED

BY THE ENGINEER AND OWNER.

7. FIRE ALARM AND DETECTION SYSTEM DESIGN AND INSTALLATION SHALL

COMPLY WITH

9 FLORIDA BUILDING CODE, 2010 EDITION

9 NFPA 70, NATIONAL ELECTRICAL CODE, 2008 EDITION

9 NFPA 72, NATIONAL FIRE ALARM CODE, 2007 EDITION

9 FLORIDA FIRE PREVENTION CODE, 2010 EDITION

9 ALL MANUFACTURER'S REQUIREMENTS AND ALL APPLICABLE LOCAL

AND STATE CODES AND REGULATIONS

9 ALL EQUIPMENT SHALL BE LISTED FOR USE ON COMMERCIAL FIRE

ALARM SYSTEMS

8. ALL AREAS PROVIDED WITH FIRE ALARM EQUIPMENT SHALL BE ASSUMED

TO BE PROVIDED WITH A MINIMUM AMBIENT TEMPERATURE OF 40

DEGREES AND BE FREE OF EXCESSIVE DUST PARTICLES OR HUMIDITY

LEVELS, UNLESS NOTED OTHERWISE.

9. REFER TO THE FIRE ALARM OPERATIONAL MATRIX ON SHEET FA94.0 FOR

SYSTEM FUNCTION REQUIREMENTS.

10. ALL NEW FIRE ALARM SYSTEM WIRING SHALL BE IN CONDUIT. SIZE OF

CONDUIT AND PERCENT FILL SHALL BE DETERMINED BY THE INSTALLING

CONTRACTOR AND SHALL BE IN ACCORDANCE WITH NFPA 70, THE

NATIONAL ELECTRIC CODE, 2008 EDITION.

11. SYSTEM CIRCUITS SHALL CONFORM TO THE FOLLOWING:

SYSTEM RISER: CLASS A

SIGNALING LINE CIRCUITS: CLASS B

NOTIFICATION APPLIANCE CIRCUITS: CLASS B

INITIATING DEVICE CIRCUITS: CLASS B

12. ALL ADDRESSABLE CONTROL MODULES AND ADDRESSABLE MONITOR

MODULES SHALL BE LOCATED WITHIN 3 FEET OF THE ASSOCIATED

NON9INTELLIGENT DEVICE MONITORED OR CONTROLLED.

13. ALL FIRE ALARM CONDUIT AND JUNCTION BOXES SHALL BE INSTALLED AS

HIGH AS POSSIBLE. IN NO CASE SHALL ANY PORTION OF THE FIRE ALARM

WIRING BE INSTALLED BELOW THE BOTTOM HORIZONTAL PLANE OF

LIGHTING FIXTURES, WITH THE EXCEPTION OF DROPS TO INDIVIDUAL FIRE

ALARM DEVICES AND PANELS. IN AREAS WITH SUSPENDED CEILINGS ALL

FIRE ALARM CONDUIT SHALL BE CONCEALED. PROVIDE ACCESS PANELS

FOR ALL CONCEALED FIRE ALARM DEVICES AND JUNCTION BOXES, WHERE

REQUIRED.

14. PROVIDE AN EMERGENCY VOICE ALARM COMMUNICATIONS SYSTEM

WITHIN AREA OF WORK. ALL AUDIBLE SPEAKER AND VISUAL STROBE

NOTIFICATION DEVICES SHALL BE WALL MOUNTED AT 96 INCHES ABOVE

THE FINISHED FLOOR OR CEILING MOUNTED, PER NFPA 72. NOTIFICATION

DEVICES SHALL BE INSTALLED NOT TO INTERFERE WITH EQUIPMENT.

15. A FULL ACCEPTANCE TEST OF ALL NEW FIRE ALARM SYSTEM

COMPONENTS IS REQUIRED AS PART OF THIS PROJECT. THIS SHALL

INCLUDE A FUNCTIONAL TEST OF 100% OF NEW INITIATING DEVICES, AS

WELL AS A TEST OF ALL INPUT/OUTPUT FUNCTIONS. THE CONTRACTOR

SHALL ALSO TEST ALL NETWORK AND REPORTING CONDITIONS.

INSTALLING CONTRACTOR SHALL PROVIDE ALL MATERIALS AND

TECHNICAL SUPPORT TO PERFORM ACCEPTANCE TEST IN ACCORDANCE

WITH NFPA 72.

16. APPLY FOR, PAY FOR, AND OBTAIN ANY PERMITS, INSPECTIONS, AND

TESTING REQUIRED FOR THIS WORK.

17. UTILIZE WEATHERPROOF DEVICES IN AREAS EXPOSED TO THE OUTSIDE

ENVIRONMENT. INCLUDE WEATHERPROOF BACKBOXES AND CONDUIT.

FIRE ALARM SYSTEM SYMBOLS

FIRE ALARM CONTROL PANEL

FIRE ALARM ANNUNCIATOR PANEL

(SUBSCRIPT DENOTES TYPE)

FIRE ALARM TRANSMITTER

FIRE ALARM COMMUNICATOR

FIRE ALARM TRANSPONDER PANEL

DIGITAL ALARM COMMUNICATOR

BOOSTER POWER SUPPLY

VOICE EVACUATION SYSTEM CONTROL PANEL

ADDRESSABLE INPUT MODULE

(MONITOR MODULE)

ADDRESSABLE OUTPUT MODULE

(CONTROL MODULE)

ISOLATOR MODULE

NAC POWER EXTENDER PANEL

END OF LINE DEVICE

VOICE EVACUATION SYSTEM

REMOTE MICROPHONE

CONTROL PANEL BATTERIES

FIREFIGHTER'S SMOKE CONTROL PANEL

ULTRAVIOLET/INFRARED FLAME DETECTOR

AUDIBLE NOTIFICATION APPLIANCE

VISIBLE NOTIFICATION APPLIANCE

(SUBSCRIPT DENOTES CANDELA RATING)

COMBINATION AUDIBLE/VISIBLE APPLIANCE

(SUBSCRIPT DENOTES CANDELA RATING)

ROTATING BEACON

ALARM BELL

WATER MOTOR GONG

ELECTRO9MAGNETIC DOOR HOLDER

FIRE DAMPER

SMOKE DAMPER

COMBINATION FIRE/SMOKE DAMPER

REMOTE TEST STATION

ADDRESSABLE RELAY MODULE

AMPLIFIER

FIRE ALARM ZONE BOUNDARY

RATE COMPENSATION HEAT DETECTOR

COMBINATION FIXED TEMPERATURE

AND RATE OF RISE HEAT DETECTOR

ELEVATOR RECALL HEAT DETECTOR

GAS DETECTOR

SMOKE DETECTOR

ELEVATOR RECALL SMOKE DETECTOR

IONIZATION SMOKE DETECTOR

BEAM SMOKE DETECTOR 9 TRANSMITTER

BEAM SMOKE DETECTOR 9 RECEIVER

SMOKE DETECTOR WITH SOUNDER BASE

SPOT TYPE VEWFD SMOKE DETECTOR

UNDER FLOOR SMOKE DETECTOR

ABOVE CEILING SMOKE DETECTOR

CRAH/CRAC UNIT SMOKE DETECTOR

DUCT SMOKE DETECTOR (SUPERSCRIPT

DENOTES SUPPLY OR RETURN)

FLAME DETECTOR

ULTRAVIOLET FLAME DETECTOR

INFRARED FLAME DETECTOR

FIRE ALARM TERMINAL CABINET

FLOW SWITCH

PRESSURE SWITCH

WATER PRESSURE SWITCH

LOW AIR PRESSURE SWITCH

HIGH AIR PRESSURE SWITCH

COMBINATION HIGH/LOW

AIR PRESSURE SWITCH

TAMPER SWITCH

VALVE WITH TAMPER SWITCH

SUPPRESSION SYSTEM ACTIVATION

(SUBSCRIPT DENOTES SYSTEM TYPE)

SUPPRESSION SYSTEM ABORT SWITCH

(SUBSCRIPT DENOTES SYSTEM TYPE)

FIRE ALARM MANUAL PULL STATION

FIRE SERVICE TELEPHONE

FIRE SERVICE TELEPHONE JACK

HEAT DETECTOR

FIXED TEMPERATURE HEAT DETECTOR

RATE OF RISE HEAT DETECTOR

R

F

P

J

XX

LH

HA

LA

XX

BATT

FATC

W

FACP

ANN

FTR

FAC

FATP

DACT

BPS

EVAC

AIM

AOM

ISO

NAC

EOL

MIC

UV/IR

IR

UV

X

C

A

U

V

SB

E

BR

BT

I

E

R/F

R/C

XX

C

XX

C

C

FSCP

RT

ARM

AMP

CE

- 001

Page 2: FIRE ALARM SYSTEM SYMBOLS - Skanska · florida building code, 2010 edition 9 nfpa 70, national electrical code, 2008 edition nfpa 72, national fire alarm code, 2007 edition 9 florida

WOMEN

110

MEN

107

STORAGE

106

FIRECOMMAND

CENTER

104

LOBBY

101

GIFT SHOP

100

FAMILY

108

CAFE

111

ELEVATOR 1 ELEVATOR 2

STAIR B

JAN

105

CORRIDOR

103

STAIR A

SPRINKLERRISER ROOM

113

P

P30

C

EVAC

BATT

FSCP

PP

75

C

P

75

E

6

P

75

C

75

C

30C

75

C

75

C

15

C

AIM AIM

AIM

10

9

8

7

NAC

AMP

9

1

3

4

2

5

ARM

12 12ARMARM

14

AIM AIM

13

12

ARM

12

ARM

ARM

OPEN TOBELOW

EXHIBIT

200

ROOF TYPE 2BELOW

EXHIBIT

200

ELEVATOR 1 ELEVATOR 2STAIR B

STAIR AROOF TYPE 2BELOW

ROOF TYPE 2 BELOW

GLASS CANOPY BELOW,SEE A6.9

TY

P, S

LO

PE

1/4

" P

ER

FT

SLO

PE

E

95P P

6

10

AIM AIM

15

9

9

11

95

75 75

12 12ARMARM

17

16

18

FIRE ALARMGROUND AND

SECOND FLOORPLAN

FA1.0

1/8" = 1'*0"FA1.0

GROUND FLOOR * FIRE ALARM1

1/8" = 1'*0"FA1.0

SECOND FLOOR * FIRE ALARM2

Seal:

GWWO INC.

800 WYMAN PARK DRIVE, SUITE 300

BALTIMORE, MARYLAND 21211, 410�332�1009

C 2012 GWWO INC.

I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THATI AM A DULY LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF A MARYLAND,

LICENSE NUMBER , EXPIRATION DATE

Revisions:

Job No.

Scale

Date

Drawing Title

Sheet

Drawn

Checked

Approved

Drawing Number

OfDa

te/T

ime S

tam

pF

ile P

ath

KEYNOTES LISTED ON THIS SHEET ARE FOR CONVENIENCEONLY. REFER TO SHEET CS.2 FOR COMPLETE LIST

1/8" = 1'*0"

PORT CANAVERALWELCOME CENTER

CANAVERAL PORT AUTHORITY

1124 RC

TC

EA

No. Date Description

N

8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD 21045

410*750*2246 (BALT) 410*750*2588 (FAX)

AUGUST 6 2012

CONSTRUCTION SET

Seal:

1 8/06/12 CONSTRUCTION SET

GENERAL NOTES

1. REFER TO ARCHITECTURAL PLANS FOR CEILING TYPES AND HEIGHTS.

2. PROVIDE NEW ADDRESSABLE DUCT SMOKE DETECTORS FOR NEW AIR

HANDLING UNITS (AHU) OVER 2,000 CFM IN THE SUPPLY AND RETURN DUCTS.

CONTRACTOR IS RESPONSIBLE FOR VERIFYING LOCATIONS AND QUANTITIES.

PROVIDE A REMOTE TEST SWITCH ALONG AN ACCESSIBLE WALL IN THE

IMMEDIATE VICINITY OF EACH DETECTOR. PROVIDE CONTROL MODULES TO

SHUT DOWN AHU UPON DETECTOR ACTIVATION.

CONSTRUCTION NOTES (THIS SHEET ONLY)

PROVIDE AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM WITH

INTEGRATED AMPLIFIERS AND DIGITAL ALARM COMMUNICATOR IN THE FIRE

COMMAND CENTER. COORDINATE FINAL WALL LOCATION WITH OWNER

PRIOR TO INSTALLATION. PROVIDE SMOKE DETECTION ABOVE PANELS.

PROVIDE FIRE FIGHTER'S SMOKE CONTROL PANEL WITHIN THE FIRE

COMMAND CENTER. COORDINATE FINAL WALL LOCATION WITH OWNER

PRIOR TO INSTALLATION. PROVIDE SMOKE DETECTION ABOVE PANELS.

PROVIDE NOTIFICATION APPLIANCE CIRCUIT POWER EXTENDER PANELS FOR

THE FIRST AND SECOND FLOOR AS REQUIRED. MULTIPLE PANELS ARE

ANTICIPATED.

PROVIDE AMPLIFIERS. MULTIPLE SUPPLY CABINETS ARE ANTICIPATED.

PROVIDE EXTERIOR DOOR SIGNAGE INDICATING FIRE COMMAND CENTER

LOCATION.

PROVIDE SMOKE DETECTION FOR ELEVATOR RECALL AND ELEVATOR

HOISTWAY PRESSURIZATION SYSTEM. WALL MOUNT DETECTOR WHERE

CEILING MOUNTING IS NOT FEASIBLE.

PROVIDE EXTERIOR DOOR SIGNAGE INDICATING RISER ROOM LOCATION.

PROVIDE NEW ADDRESSABLE TAMPER SWITCH AND FLOW SWITCH FOR

GROUND FLOOR SPRINKLER ZONE. REFER TO SHEET FP5.0 FOR LOCATION

DETAILS.

PROVIDE NEW ADDRESSABLE SMOKE DETECTOR ADJACENT TO STAIR

ENTRANCE. WALL MOUNT DETECTOR WHERE CEILING MOUNTING IS NOT

FEASIBLE. PROVIDE CONTROL MODULES TO ACTIVATE STAIR

PRESSURIZATION SYSTEMS AND FIRE SHUTTERS.

PROVIDE FIRE ALARM APPLIANCES AND DETECTION DEVICES THROUGHOUT

THE BUILDING IN ACCORDANCE WITH NFPA 72. ALL AUDIBLE FIRE ALARM

NOTIFICATION APPLIANCES SHALL BE FIRE ALARM SPEAKERS PROVIDING

INTELLIGIBILITY IN ACCORDANCE WITH NFPA 72.

PROVIDE TWO*WAY COMMUNICATION SYSTEM AT ELEVATOR LANDING.

SYSTEM MUST INCLUDE COMMUNICATION CAPABILITY WITH FIRE COMMAND

CENTER, AUDIBLE AND VISUAL SIGNALS, AND DIRECTIONS FOR USE. REFER

TO ELECTRICAL DRAWINGS FOR MORE INFORMATION.

PROVIDE NEW ADDRESSABLE SMOKE DETECTORS FOR CLOSURE OF

SMOKE AND FIRE/SMOKE DAMPERS. PROVIDE CONTROL MODULES TO

CLOSE DAMPERS UPON HVAC DETECTOR ACTIVATION. POSITION DETECTOR

AND MODULE WITHIN 3 FEET OF DAMPER.

PROVIDE TAMPER SWITCH AND FLOW SWITCH FOR MAIN BUILDING RISER.

PROVIDE TAMPER SWITCH FOR MAIN STANDPIPE VALVE.

PROVIDE TAMPER SWITCH AND FLOW SWITCH FOR SECOND FLOOR

SPRINKLER ZONE.

MONITOR FIRE PUMP RUNNING, PHASE REVERSEL, LOSS OF POWER.

MONITOR FIRE PUMP VALVES.

MONITOR BACKFLOW PREVENTER VALVES.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

8 0 8 16

SCALE OF FEET1/8" = 1'*0"

16

17

18

AIM

AIM

AIM

AIMAIMAIMAIMAIM

AIMAIM

NTSFA1.0

PREFABRICATED PUMP HOUSE3

1

1 CE

- 001

Page 3: FIRE ALARM SYSTEM SYMBOLS - Skanska · florida building code, 2010 edition 9 nfpa 70, national electrical code, 2008 edition nfpa 72, national fire alarm code, 2007 edition 9 florida

AUDITORIUM

300

EXHIBIT

305

WOMEN

306

MEN

304

ROOF TYPE 2 BELOW

ELEVATOR 1 ELEVATOR 2

STAIR B

STAIR A

VESTIBULE

301

VESTIBULE

309

AV

307

AV

303

CORRIDOR

308CORRIDOR

302

SEE A7.3

FOR SSWINDOWTYPE

P P

AIM AIM

E

2

30

C

30

C

1

4 4

375

C

75

C

515

C

15

C

6 6ARM ARM

75

C

75

C

6ARM

PRE"FUNCTIONROOM

404

WOMEN

407

MEN

403

CATERINGKITCHEN

405

STORAGE

406

STAIR A

STAIR B

ELEVATOR 1 ELEVATOR 2VESTIBULE

409

VESTIBULE

401

CORRIDOR

408

CORRIDOR

402

SEE SHEET K.1

TERRACE

410

1/4" PER FT

FUNCTIONROOM

400

TYP.

1

75

C

75

C

75

C

75

C

PP

E

2

AIM AIM

30

C

30

C

3

4 4

5

30

C

NAC

7

ARM

6

ARMARM

ARM

ARM

66

6

6

FIRE ALARMTHIRD AND

FOURTH FLOORPLAN

FA2.0

1/8" = 1'"0"FA2.0

THIRD FLOOR " FIRE ALARM1

1/8" = 1'"0"FA2.0

FOURTH FLOOR " FIRE ALARM2

Seal:

GWWO INC.

800 WYMAN PARK DRIVE, SUITE 300

BALTIMORE, MARYLAND 21211, 410�332�1009

C 2012 GWWO INC.

I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THATI AM A DULY LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF A MARYLAND,

LICENSE NUMBER , EXPIRATION DATE

Revisions:

Job No.

Scale

Date

Drawing Title

Sheet

Drawn

Checked

Approved

Drawing Number

OfDa

te/T

ime S

tam

pF

ile P

ath

KEYNOTES LISTED ON THIS SHEET ARE FOR CONVENIENCEONLY. REFER TO SHEET CS.2 FOR COMPLETE LIST

1/8" = 1'"0"

PORT CANAVERALWELCOME CENTER

CANAVERAL PORT AUTHORITY

1124 RC

TC

EA

No. Date Description

N

8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD 21045

410"750"2246 (BALT) 410"750"2588 (FAX)

AUGUST 6 2012

CONSTRUCTION SET

Seal:

1 8/06/12 CONSTRUCTION SET

GENERAL NOTES

1. REFER TO ARCHITECTURAL PLANS FOR CEILING TYPES AND HEIGHTS.

2. PROVIDE NEW ADDRESSABLE DUCT SMOKE DETECTORS FOR NEW AIR

HANDLING UNITS (AHU) OVER 2,000 CFM IN THE SUPPLY AND RETURN DUCTS.

CONTRACTOR IS RESPONSIBLE FOR VERIFYING LOCATIONS AND QUANTITIES.

PROVIDE A REMOTE TEST SWITCH ALONG AN ACCESSIBLE WALL IN THE

IMMEDIATE VICINITY OF EACH DETECTOR. PROVIDE CONTROL MODULES TO

SHUT DOWN AHU UPON DETECTOR ACTIVATION.

CONSTRUCTION NOTES (THIS SHEET ONLY)

PROVIDE FIRE ALARM APPLIANCES AND DETECTION DEVICES THROUGHOUT

THE BUILDING IN ACCORDANCE WITH NFPA 72. ALL AUDIBLE FIRE ALARM

NOTIFICATION APPLIANCES SHALL BE FIRE ALARM SPEAKERS PROVIDING

INTELLIGIBILITY IN ACCORDANCE WITH NFPA 72.

PROVIDE SMOKE DETECTION FOR ELEVATOR RECALL AND ELEVATOR

HOISTWAY PRESSURIZATION SYSTEM. WALL MOUNT DETECTOR WHERE

CEILING MOUNTING IS NOT FEASIBLE.

PROVIDE NEW ADDRESSABLE TAMPER SWITCH AND FLOW SWITCH FOR

SPRINKLER ZONE. REFER TO SHEET FP5.0 FOR LOCATION DETAILS.

PROVIDE NEW ADDRESSABLE SMOKE DETECTOR ADJACENT TO STAIR

ENTRANCE. WALL MOUNT DETECTOR WHERE CEILING MOUNTING IS NOT

FEASIBLE. PROVIDE CONTROL MODULES TO ACTIVATE STAIR PRESSURIZATION

SYSTEMS.

PROVIDE TWO"WAY COMMUNICATION SYSTEM AT ELEVATOR LANDING. SYSTEM

MUST INCLUDE COMMUNICATION CAPABILITY WITH FIRE COMMAND CENTER,

AUDIBLE AND VISUAL SIGNALS, AND DIRECTIONS FOR USE. SEE ELECTRICAL

DRAWINGS FOR MORE INFORMATION.

PROVIDE NEW ADDRESSABLE SMOKE DETECTORS FOR CLOSURE OF SMOKE

AND FIRE/SMOKE DAMPERS. PROVIDE CONTROL MODULES TO CLOSE DAMPERS

UPON HVAC DETECTOR ACTIVATION. POSITION DETECTOR AND MODULE WITHIN

3 FEET OF DAMPER.

PROVIDE NOTIFICATION APPLIANCE CIRCUIT POWER EXTENDER PANEL AS

REQUIRED. FIELD COORDINATE LOCATION.

1

2

3

4

5

6

7

8 0 8 16

SCALE OF FEET1/8" = 1'"0"

CE

- 001

Page 4: FIRE ALARM SYSTEM SYMBOLS - Skanska · florida building code, 2010 edition 9 nfpa 70, national electrical code, 2008 edition nfpa 72, national fire alarm code, 2007 edition 9 florida

ELEVATORCONTROL

ROOM

504

STAIR A

STAIR BELEVATOR 2ELEVATOR 1

MECHANICAL

502

ROOF TYPE 2 BELOW

RESTROOM

506

CORRIDOR

501

EXHIBIT

500

ELECTRICAL

503

IT

505

ELECTRICAL

507

L1

1

AIM AIM

75

C

75

C

E

E

2

2

P P

15

C

15

C

75

30

15

C

E

2

AOM

AIM

x56

44

3

5

7

8

8

ARM ARM

30

ARM

ARM

8

8ARM

8

ROOF TYPE 2 BELOW

STAIR A

STAIR B

ELEVATOR 2ELEVATOR 1

WORK ROOM

607

MEN

603

HARBORMASTER

601

STORAGE

604

INDOOROBSERVATION

600

WOMEN

605

JAN

606

STOR

602

DD.1

DD 1

75

C

75

C

E

2

P P

AIM AIM

15

C

15

C

15

C

15

C

4 4

3

7

8

8

ARM

ARM

NAC

915

C

15

C

8ARM

ARM

8

ARM

8

ARM8

1/8" = 1')0"FA3.0

FIFTH FLOOR ) FIRE ALARM1

1/8" = 1')0"FA3.0

SIXTH FLOOR ) FIRE ALARM2

FIRE ALARMFIFTH AND SIXTH

FLOOR PLAN FA3.0

Seal:

GWWO INC.

800 WYMAN PARK DRIVE, SUITE 300

BALTIMORE, MARYLAND 21211, 410�332�1009

C 2012 GWWO INC.

I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THATI AM A DULY LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF A MARYLAND,

LICENSE NUMBER , EXPIRATION DATE

Revisions:

Job No.

Scale

Date

Drawing Title

Sheet

Drawn

Checked

Approved

Drawing Number

OfDa

te/T

ime S

tam

pF

ile P

ath

KEYNOTES LISTED ON THIS SHEET ARE FOR CONVENIENCEONLY. REFER TO SHEET CS.2 FOR COMPLETE LIST

1/8" = 1')0"

PORT CANAVERALWELCOME CENTER

CANAVERAL PORT AUTHORITY

1124 RC

TC

EA

No. Date Description

N

8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD 21045

410)750)2246 (BALT) 410)750)2588 (FAX)

AUGUST 6 2012

CONSTRUCTION SET

Seal:

1 8/06/12 CONSTRUCTION SET

GENERAL NOTES

1. REFER TO ARCHITECTURAL PLANS FOR CEILING TYPES AND HEIGHTS.

2. PROVIDE NEW ADDRESSABLE DUCT SMOKE DETECTORS FOR NEW AIR

HANDLING UNITS (AHU) OVER 2,000 CFM IN THE SUPPLY AND RETURN DUCTS.

CONTRACTOR IS RESPONSIBLE FOR VERIFYING LOCATIONS AND QUANTITIES.

PROVIDE A REMOTE TEST SWITCH ALONG AN ACCESSIBLE WALL IN THE

IMMEDIATE VICINITY OF EACH DETECTOR. PROVIDE CONTROL MODULES TO

SHUT DOWN AHU UPON DETECTOR ACTIVATION.

CONSTRUCTION NOTES (THIS SHEET ONLY)

PROVIDE FIRE ALARM APPLIANCES AND DETECTION DEVICES THROUGHOUT

THE BUILDING IN ACCORDANCE WITH NFPA 72. ALL AUDIBLE FIRE ALARM

NOTIFICATION APPLIANCES SHALL BE FIRE ALARM SPEAKERS PROVIDING

INTELLIGIBILITY IN ACCORDANCE WITH NFPA 72.

PROVIDE SMOKE DETECTION FOR ELEVATOR RECALL AND ELEVATOR

HOISTWAY PRESSURIZATION SYSTEM. WALL MOUNT DETECTOR WHERE

CEILING MOUNTING IS NOT FEASIBLE.

PROVIDE NEW ADDRESSABLE TAMPER SWITCH AND FLOW SWITCH FOR

SPRINKLER ZONE.

PROVIDE NEW ADDRESSABLE SMOKE DETECTOR ADJACENT TO STAIR

ENTRANCE. WALL MOUNT DETECTOR WHERE CEILING MOUNTING IS NOT

FEASIBLE. DETECTOR SHALL ACTIVATE STAIR PRESSURIZATION SYSTEMS.

PROVIDE HEAT DETECTION WITHIN 2 FT OF ALL SPRINKLERS IN ELEVATOR

MACHINE ROOM.

PROVIDE CONTROL MODULES FOR ELEVATOR RECALL AND SHUNT TRIP.

INCLUDE MODULES FOR: PRIMARY RECALL FLOOR, ALTERNATE RECALL FLOOR,

HAT FLASH, SHUNT TRIP AND MONITOR SHUNT TRIP POWER.

PROVIDE TWO)WAY COMMUNICATION SYSTEM AT ELEVATOR LANDING. SYSTEM

MUST INCLUDE COMMUNICATION CAPABILITY WITH FIRE COMMAND CENTER,

AUDIBLE AND VISUAL SIGNALS, AND DIRECTIONS FOR USE. REFER TO

ELECTRICAL DRAWINGS FOR MORE INFORMATION.

PROVIDE NEW ADDRESSABLE SMOKE DETECTORS FOR CLOSURE OF SMOKE

AND FIRE/SMOKE DAMPERS. PROVIDE CONTROL MODULES TO CLOSE DAMPERS

UPON HVAC DETECTOR ACTIVATION. POSITION DETECTOR AND MODULE WITHIN

3 FEET OF DAMPER.

PROVIDE NOTIFICATION APPLIANCE CIRCUIT POWER EXTENDER PANEL AS

REQUIRED. FIELD COORDINATE LOCATION.

1

2

3

4

5

6

7

8

9

8 0 8 16

SCALE OF FEET1/8" = 1')0"

CE

- 001

Page 5: FIRE ALARM SYSTEM SYMBOLS - Skanska · florida building code, 2010 edition 9 nfpa 70, national electrical code, 2008 edition nfpa 72, national fire alarm code, 2007 edition 9 florida

OBSERVATION

700

STAIR A

ELEVATOR 1 ELEVATOR 2 STAIR B

VESTIBULE

701

1

75WP

P P

WP WP

2

4

ARM ARM

66

ARM

7

E, WP

E2 5

E5 2

75WP

3

15

WP

15

WP

ARM

8

1/8" = 1'�0"FA4.0

SEVENTH FLOOR � FIRE ALARM1

FIRE ALARMSEVENTH

FLOOR ANDDETAILS

FA4.0

Seal:

GWWO INC.

800 WYMAN PARK DRIVE, SUITE 300

BALTIMORE, MARYLAND 21211, 410�332�1009

C 2012 GWWO INC.

I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THATI AM A DULY LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF A MARYLAND,

LICENSE NUMBER , EXPIRATION DATE

Revisions:

Job No.

Scale

Date

Drawing Title

Sheet

Drawn

Checked

Approved

Drawing Number

OfDa

te/T

ime S

tam

pF

ile P

ath

KEYNOTES LISTED ON THIS SHEET ARE FOR CONVENIENCEONLY. REFER TO SHEET CS.2 FOR COMPLETE LIST

1/8" = 1'�0"

PORT CANAVERALWELCOME CENTER

CANAVERAL PORT AUTHORITY

1124 RC

TC

EA

No. Date Description

N

8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD 21045

410�750�2246 (BALT) 410�750�2588 (FAX)

AUGUST 6 2012

CONSTRUCTION SET

Seal:

1 8/06/12 CONSTRUCTION SET

N/AFA4.0

FIRE ALARM MATRIX2

GENERAL NOTES

1. REFER TO ARCHITECTURAL PLANS FOR CEILING TYPES AND HEIGHTS.

2. PROVIDE NEW ADDRESSABLE DUCT SMOKE DETECTORS FOR NEW AIR

HANDLING UNITS (AHU) OVER 2,000 CFM IN THE SUPPLY AND RETURN DUCTS.

CONTRACTOR IS RESPONSIBLE FOR VERIFYING LOCATIONS AND QUANTITIES.

PROVIDE A REMOTE TEST SWITCH ALONG AN ACCESSIBLE WALL IN THE

IMMEDIATE VICINITY OF EACH DETECTOR. PROVIDE CONTROL MODULES TO

SHUT DOWN AHU UPON DETECTOR ACTIVATION.

3. PROVIDE NEW ADDRESSABLE SMOKE DETECTORS FOR CLOSURE OF SMOKE

AND FIRE/SMOKE DAMPERS. PROVIDE CONTROL MODULES TO CLOSE

DAMPERS UPON HVAC DETECTOR ACTIVATION.

CONSTRUCTION NOTES (THIS FLOOR ONLY)

PROVIDE FIRE ALARM APPLIANCES AND DETECTION DEVICES THROUGHOUT

THE BUILDING IN ACCORDANCE WITH NFPA 72. ALL AUDIBLE FIRE ALARM

NOTIFICATION APPLIANCES SHALL BE FIRE ALARM SPEAKERS PROVIDING

INTELLIGIBILITY IN ACCORDANCE WITH NFPA 72.

PROVIDE HOISTWAY SMOKE DETECTION FOR ELEVATOR RECALL AND

ELEVATOR HOISTWAY PRESSURIZATION SYSTEM. WALL MOUNT DETECTOR

WHERE CEILING MOUNTING IS NOT FEASIBLE.

OPEN TO OUTSIDE.

PROVIDE TWO�WAY COMMUNICATION SYSTEM AT ELEVATOR LANDING. SYSTEM

MUST INCLUDE COMMUNICATION CAPABILITY WITH FIRE COMMAND CENTER,

AUDIBLE AND VISUAL SIGNALS, AND DIRECTIONS FOR USE. REFER TO

ELECTRICAL DRAWINGS FOR MORE INFORMATION.

PROVIDE HOISTWAY HEAT DETECTION WITHIN 2 FEET OF SPRINKLERS TO

INITIATE SHUNT TRIP OF ELEVATOR POWER.

PROVIDE RELAY MODULE FOR STAIR PRESSURIZATION FAN START. LOCATE

WITHIN 3 FEET OF FAN. PROVIDE DUCT DETECTOR FOR FAN. DETECTOR MUST

SIGNAL SUPERVISORY. DETECTOR MUST NOT CLOSE DAMPER.

PROVIDE RELAY MODULE FOR ELEVATOR PRESSURIZATION FAN START. LOCATE

WITHIN 3 FEET OF ROOF FAN. PROVIDE DUCT DETECTOR FOR FAN. DETECTOR

MUST SIGNAL SUPERVISORY. DETECTOR MUST NOT CLOSE DAMPER.

PROVIDE NEW ADDRESSABLE SMOKE DETECTORS FOR CLOSURE OF SMOKE

AND FIRE/SMOKE DAMPERS. PROVIDE CONTROL MODULES TO CLOSE DAMPERS

UPON HVAC DETECTOR ACTIVATION. POSITION DETECTOR AND MODULE WITHIN

3 FEET OF DAMPER.

1

2

3

4

EVAC / FACP

WITH AMPS

BATT

TRANSMITTER

FSCP120 VAC

FATCAIMAIMAIMAIMAIMAIMAIMAIMAIMEOL

FATCNAC

753015

15

EOL

EOL

FATCNAC

753015

15

EOL

EOL

E

P AIM AIMS

RT

R

RT

ARM

CLOSE

STAIR

SHUTTER

GROUND

TYPICAL NOTIFICATION APPLIANCE CIRCUIT

TYPICAL SECOND FLOOR

THROUGH OBSERVATION DECK

E

P AIM AIMS

RT

R

RT

ARM

PRIMARY ELEV.

RECALL

ARM

ALT. ELEV.

RECALL

ARM

ELEV. FIRE HAT

ARM

SHUNT TRIP

CONTROL

ARM

CLOSE SMOKE

DAMPER

ARM

INITIATE SHAFT

PRESSURIZE

EOLTYPICAL NOTIFICATION APPLIANCE CIRCUIT

TYPICAL ADDRESSABLE SIGNALING LINE CIRCUIT

UTILITY YARD MONITORING

N/AFA4.0

CONCEPTUAL FIRE ALARM RISER3

1 2

4

3

567

8

5

6

7

AIM

10

9

FIFTH FLOOR MACHINE ROOM ONLY AT EACH

DAMPER

AT ROOF

TOP UNITS

EOL

NOTE:

ILLUSTRATED DEVICES AND APPLIANCES MAY

REPRESENT MULTIPLE SYSTEM COMPONENTS.

CONSTRUCTION NOTES (THIS DETAIL ONLY)

PROVIDE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM.

PROVIDE SMOKE DETECTORS FOR COMBINATION SMOKE/FIRE DAMPERS.

REFER TO MECHANICAL DRAWINGS FOR LOCATIONS.

MONITOR FSCP FOR MANUAL OVERRIDE CONDITION.

EXTEND FIRE ALARM TERMINAL CABINET TO THE FIRE PUMP HOUSE

APPROXIMATELY 100 FT FROM THE BUILDING. REFER TO CIVIL DRAWINGS FOR

LOCATION.

PROVIDE MONITORING FOR BACKFLOW PREVENTER CONTROL VALVES AND

TEST HEADER ADJACENT TO FIRE PUMP HOUSE. USE WEATHERPROOF DEVICES

AND CONDUIT. REFER TO CIVIL DRAWINGS FOR LOCATION.

PROVIDE MONITORING FOR FIRE PUMP (LOSS OF POWER, PHASE REVERSAL,

AND PUMP RUN.

PROVIDE MONITORING FOR EMERGENCY GENERATOR.

PROVIDE CLASS A STROBE NAC RISER LOOP, EACH LEG SHALL BE SEPARATED

IN ACCORDANCE WITH NFPA 72

PROVIDE CLASS A SLC RISER LOOP. EACH LEG OF THE RISER SHALL BE

SEPARATED IN ACCORDANCE WITH NFPA 72.

PROVIDE TAMPER SWITCHES ON ALL CONTROL VALVES IN PUMP ROOM. EACH

VALVE SHALL HAVE SEPARATE ADDRESS.

PROVIDE CLASS B SPEAKER CIRCUITS FROM AMPS IN FIRE COMMAND CENTER.

RUN A SEPARATE SPEAKER CIRCUIT TO EACH FLOOR.

MONITOR TWO�WAY COMMUNICATION PANEL AND CIRCUITS FOR SHORT AND

OPEN CONDITIONS.

DACT TRANSMITTER.

1

2

3

9

10

8

7

6

5

4

11

12

13

11

NAC RETURN TO CONTROL PANEL

SLC RETURN TO CONTROL PANEL

95

SPEAKER CIRCUIT

STROBE CIRCUIT

AIM

13

AIM

AIM

TWO�WAY

COMMUNICATION PANEL

12

TO ELEVATOR LOBBY/AREA OF RESCUE ASSISTANCE STATIONS

8

8 0 8 16

SCALE OF FEET1/8" = 1'�0"

CE

- 001

Page 6: FIRE ALARM SYSTEM SYMBOLS - Skanska · florida building code, 2010 edition 9 nfpa 70, national electrical code, 2008 edition nfpa 72, national fire alarm code, 2007 edition 9 florida

SPRINKLERCOVER SHEET FP0.0

Seal:

GWWO INC.

800 WYMAN PARK DRIVE, SUITE 300

BALTIMORE, MARYLAND 21211, 410�332�1009

C 2012 GWWO INC.

I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THATI AM A DULY LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF A MARYLAND,

LICENSE NUMBER , EXPIRATION DATE

Revisions:

Job No.

Scale

Date

Drawing Title

Sheet

Drawn

Checked

Approved

Drawing Number

OfDa

te/T

ime S

tam

pF

ile P

ath

KEYNOTES LISTED ON THIS SHEET ARE FOR CONVENIENCEONLY. REFER TO SHEET CS.2 FOR COMPLETE LIST

1/8" = 1':0"

PORT CANAVERALWELCOME CENTER

CANAVERAL PORT AUTHORITY

1124 RC

TC

EA

No. Date Description

N

8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD 21045

410:750:2246 (BALT) 410:750:2588 (FAX)

AUGUST 6 2012

CONSTRUCTION SET

Seal:

1 8/06/12 CONSTRUCTION SET

FIRE SUPPRESSION ABBREVIATIONSABD AUTOMATIC BALL DRIP

ACT ACOUSTICAL CEILING TILE

AFF ABOVE FINISHED FLOOR

AS AUTOMATIC SPRINKLER

ATR ALL THREAD ROD

BFP BACKFLOW PREVENTER

BOB BOTTOM OF BEAM

CB CONCRETE BEAM

CI CAST IRON

COL COLUMN

CONC CONCRETE

DN DOWN

DP DRY PENDENT (SPRINKLER)

DS DRY SIDEWALL (SPRINKLER)

EC EXTENDED COVERAGE (SPRINKLER)

ETR EXISTING TO REMAIN

EXP EXPOSED (NO CEILING)

FDC FIRE DEPARTMENT CONNECTION

GALV GALVANIZED

GYP GYPSUM WALL BOARD (SHEETROCK)

HSW HORIZONTAL SIDEWALL (SPRINKLER)

HT HIGH TEMPERATURE (SPRINKLER)

IT INTERMEDIATE TEMP. (SPRINKLER)

ITC INSPECTORS TEST CONNECTION

MAX MAXIMUM

MIN MINIMUM

MT METAL TILE

NIC NOT IN CONTRACT

NS NON:SPRINKLERED

NTS NOT TO SCALE

PL PLASTER (CEILING)

POC POINT OF CONNECTION

PRV PRESSURE REGULATING VALVE

QR QUICK RESPONSE (SPRINKLER)

RX REMOVE EXISTING DEVICE

SCH SCHEDULE

SPL HIDDEN SPLINE (CEILING)

SR STANDARD RESPONSE (SPRINKLER)

STL STEEL

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

EXTENDED COVERAGE PENDENT SPRINKLER; ON DROP NIPPLE

PENDENT SPRINKLER; ON DROP NIPPLE (SUBSCRIPT "HT"

DENOTES HIGH TEMPERATURE)

SPRINKLER CAGE;

SHOWN ON UPRIGHT SPRINKLER

HYDRAULIC REFERENCE NODE

ORDINARY HAZARD GROUP 1

NON:SPRINKLERED AREA

FULLY SPRINKLERED AREA

PARTIALLY SPRINKLERED AREA

ZONE BOUNDARY

PRESSURE REGULATING VALVE

PRESSURE RELIEF VALVE

PRESSURE GAUGE

ALARM CHECK VALVE

FIRE DEPARTMENT CONNECTION,

FLUSH TYPE

SIDEWALL SPRINKLER

UPRIGHT SPRINKLER

(SUBSCRIPT "IT" DENOTES INTERMEDIATE

TEMPERATURE)

HOSE VALVE

PIPE TEE DOWN

FLUSHING CONNECTION OR CAP

CONTROL VALVE

CHECK VALVE

OS&Y GATE VALVE

BUTTERFLY VALVE

NON:INDICATING CONTROL VALVE

BACKFLOW PREVENTER;

DOUBLE CHECK TYPE

ZONE CONTROL ASSEMBLY

FIRE SUPPRESSION SYSTEM SYMBOLS

NEW SYSTEM PIPING

EXISTING PIPING TO REMAIN

DEMO EXISTING PIPING

POINT OF CONNECTION

MECHANICAL COUPLING

PIPE HANGER

SYSTEM RISER

DRAIN RISER

PIPE ELBOW DOWN

OH1

AS

AS

NS

XX

ZCA

OWNER'S INFORMATION CERTIFICATE

NOYES

WILL THERE BE ANY STORAGE OR PRODUCTS

OVER 12 FT (3.5 M) IN HEIGHT?

WILL THERE BE ANY STORAGE OF PLASTIC,

RUBBER, OR SIMILAR PRODUCTS OVER 5 FT (1.3

M) HIGH EXCEPT AS DESCRIBED ABOVE?

THIS FORM HAS BEEN COMPLETED BY KOFFEL

ASSOCIATES ON BEHALF OF THE OWNER BASED ON

INFORMATION PROVIDED BY THE OWNER AND HIS

AGENTS.

I CERTIFY THAT I HAVE KNOWLEDGE OF THE INTENDED

USE OF THE PROPERTY AND THAT THE ABOVE

INFORMATION IS CORRECT.

SIGNATURE OF OWNER'S REPRESENTATIVE OR AGENT

DATE: JUNE 6, 2012

KOFFEL ASSOCIATES, INCNAME OF OWNER'S REPRESENTATIVE OR AGENT

COMPLETING CERTIFICATE.

CONSULTING ENGINEERRELATIONSHIP AND FIRM OF AGENT

NOYES

INDICATE WHETHER ANY OF THE FOLLOWING

SPECIAL MATERIALS ARE INTENDED TO BE

PRESENT:

FLAMMABLE OR COMBUSTIBLE LIQUIDS

AEROSOL PRODUCTS

NITRATE FILM

PYROXYLIN PLASTIC

COMPRESSED OR LIQUEFIED GAS

CYLINDERS

LIQUID OR SOLID OXIDIZERS

ORGANIC PEROXIDE FORMULATIONS

IDLE PALLETS

INDICATE WHETHER THE PROTECTION IS

INTENDED FOR ONE OF THE FOLLOWING

SPECIALIZED OCCUPANCIES OR AREAS:

SPRAY AREA OR MIXING ROOM

SOLVENT EXTRACTION

LABORATORY USING CHEMICALS

OXYGEN:FUEL GAS SYSTEM FOR

WELDING OR CUTTING

ACETYLENE CYLINDER CHARGING

PRODUCTION OR USE OF

COMPRESSED OR LIQUEFIED GASES

COMMERCIAL COOKING OPERATION

CLASS A HYPERBARIC CHAMBER

CLEANROOM

INCINERATOR WASTE HANDLING

SYSTEM

LINEN HANDLING SYSTEM

WATER:COOLING TOWER

YES NO

NOYES

PROPERTY LOCATION:

CANAVERAL PORT AUTHORITY WELCOME CENTER

CAPE CANAVERAL, FLORIDA

NAME OF OWNER:

CANAVERAL PORT AUTHORITY

445 CHALLENGER ROAD

CAPE CANAVERAL, FLORIDA

PHONE: 321:783:7831

EXISTING OR PLANNED CONSTRUCTION IS:

FIRE RESISTIVE OR NONCOMBUSTIBLE

WOOD FRAME OR ORDINARY

(MASONRY WALLS WITH WOOD BEAMS)

UNKNOWN

IS THE SYSTEM INSTALLATION INTENDED FOR ONE

OF THE FOLLOWING SPECIAL OCCUPANCIES:

AIRCRAFT HANGAR

FIXED GUIDEWAY TRANSIT SYSTEM

RACE TRACK STABLE

MARINE TERMINAL, PIER, OR WHARF

AIRPORT ENGINE TEST FACILITY

AIRCRAFT ENGINE TEST FACILITY

POWER PLANT

WATER:COOLING TOWER

NOYES

1. PROVIDE NEW AUTOMATIC SPRINKLER PROTECTION AND AUTOMATIC WET STANDPIPES

THROUGHOUT THE PORT CANAVERAL WELCOME CENTER BUILDING. THIS SYSTEM SHALL BE

SUPPLIED FROM A NEW 8:INCH FIRE MAIN ROUTED TO THE FIRST FLOOR RISER ROOM UNDERNEATH

STAIR B. THE SCOPE OF WORK FOR THE BUILDING SPRINKLER SYSTEM STARTS WHEN THE

PIPE ENTERS THE FIRST FLOOR SLAB.

2. THE SCOPE OF WORK ALSO INCLUDES PROVIDING A PREFABRICATED EXTERNAL FIRE PUMP

HOUSE. PROVIDE EQUIPMENT AND PERSONNEL TO ACCEPT DELIVERY OF PUMP HOUSE AND

INSTALL ON:SITE WITH CRANE. PUMP HOUSE SHALL BE PLACED IN PREVIOUSLY PERMITTED

LOCATION. REFER TO SITE CIVIL DRAWINGS. REFER TO SPECIFICATION 213113, ELECTRICAL DRIVE

CENTRIFUGAL FIRE PUMPS, FOR MORE DETAILED INFORMATION. GENERAL CONTRACTOR SHALL

COORDINATE WITH SPRINKLER CONTRACTOR.

3. STANDPIPE HOSE OUTLETS SHALL BE ON THE INTERMEDIATE LANDINGS. STANDPIPE AND

SPRINKLER RISERS WILL BE COMBINED IN THE LOCATIONS SHOWN.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR PREPARING SHOP DRAWINGS OBTAINING PERMITS AND

FOR FURNISHING AND INSTALLING ALL MATERIALS AND EQUIPMENT REQUIRED FOR A COMPLETE

AND OPERATIONAL SYSTEM AS DESCRIBED IN THE PROJECT SPECIFICATIONS AND CONTRACT

DRAWINGS.

5. ALL REFERENCES TO THE ENGINEER SHALL MEAN KOFFEL ASSOCIATES.

6. ALL REFERENCES TO THE OWNER SHALL MEAN THE CANAVERAL PORT AUTHORITY.

7. ALL REFERENCES TO THE AUTHORITY HAVING JURISDICTION (AHJ) SHALL MEAN THE STATE OF

FLORIDA AND THE CANAVERAL PORT AUTHORITY.

8. INSTALLATION OF ALL SPRINKLER AND STANDPIPE SYSTEM PIPING AND COMPONENTS SHALL BE IN

ACCORDANCE WITH THE FOLLOWING:

• NFPA 13, INSTALLATION OF SPRINKLER SYSTEMS, 2007 EDITION

• NFPA 14, INSTALLATION OF STANDPIPE AND HOSE SYSTEMS, 2008 EDITION

• FLORIDA FIRE PREVENTION CODE, 2010 EDITION

• FLORIDA BUILDING CODE, 2010 EDITION

• THE MANUFACTURER'S REQUIREMENTS AND PROJECT SPECIFICATIONS

• ALL APPLICABLE STATE CODES AND REGULATIONS

9. SPRINKLER SPACING AND HYDRAULIC DESIGN CRITERIA HAS BEEN DETERMINED BY NFPA 13 FOR

THE HAZARD PROTECTED. THE FOLLOWING DESIGN CRITERIA APPLIES:

OFFICES, AUDITORIUM, STAIRS, RESTROOMS : LIGHT HAZARD AT 0.10 GPM/SQ.FT OVER 1,500 SQ.FT,

100 GPM OUTSIDE HOSE DEMAND.

MECHANICAL ROOMS, ELECTRICAL ROOMS, EXHIBIT SPACES, STORAGE ROOMS : ORDINARY

HAZARD GROUP I AT 0.15 GPM/SQ.FT OVER 1,500 SQ.FT, 250 GPM OUTSIDE HOSE DEMAND.

PER SECTION 11.2.3.2.3 OF NFPA 13, A REDUCTION IN THE DESIGN AREA UP TO 40% IS PERMITTED

BASED ON CEILING HEIGHT WHERE LISTED QUICK RESPONSE SPRINKLERS ARE UTILIZED.

10. THE FOLLOWING WATER SUPPLY DATA IS AVAILABLE:

STATIC PRESSURE : 68 PSI

RESIDUAL PRESSURE : 54 PSI

FLOW : 1230 GPM

LOCATION : HYDRANT A:14 NEAR DAVE NISBET

DATE OF TEST : NOVEMBER 2, 2011

SOURCE : CITY OF COCOA, FLORIDA

SEE THE CIVIL DRAWINGS FOR THE LOCATION AND FURTHER DETAILS ON THE WATER SUPPLY AND

UNDERGROUND PIPE ROUTING. CONTRACTOR SHALL PERFORM ANOTHER FLOW TEST TO VERIFY

RESULTS ONCE NEW HYDRANTS ARE INSTALLED OR PRIOR TO SIZING FIRE PUMP.

11. ALL WORK SHALL BE COORDINATED WITH THE OWNER AND THEIR DESIGNATED PROJECT MANAGER.

12. ALL MATERIALS SHALL BE LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY FOR USE

ON COMMERCIAL FIRE PROTECTION SYSTEMS.

13. SPRINKLERS TYPES SHALL BE AS INDICATED IN THE PROJECT SPECIFICATIONS. CORROSION

RESISTANT SPRINKLERS SHALL BE INSTALLED IN AREAS SUBJECT TO HIGH HUMIDITY, INCLUDING

EXTERIOR AREAS, OR OTHER CORROSIVE ENVIRONMENTS.

14. SPRINKLER AND STANDPIPE SYSTEM PIPE AND FITTINGS SHALL MEET THE FOLLOWING CRITERIA:

o PIPE SIZES 2" AND SMALLER: SCHEDULE 40, BLACK STEEL, MEETING ASTM A53 SPECIFICATIONS,

CONNECTED WITH THREADED FITTINGS.

o PIPE SIZES 2:1/2" AND LARGER: SCHEDULE 10, BLACK STEEL, MEETING ASTM A135 OR A795

SPECIFICATIONS, CONNECTED WITH LISTED GROOVED COUPLINGS.

15. PIPE FITTINGS SHALL INCLUDE:

o THREADED FITTINGS FOR SCHEDULE 40 PIPE SHALL CONFORM WITH SECTION 6.4 (4.3) OF NFPA

13 (NFPA 14).

o ROLL GROOVED FITTINGS FOR SCHEDULE 10 PIPE SHALL BE UL LISTED. COUPLING SHALL

COMPLY WITH ASTM A536, AND A183 SPECIFICATIONS WITH GRADE E, TYPE A GASKETS. ALL

COMPONENTS SHALL BE FROM A SINGLE MANUFACTURER.

16. PROVIDE AN ISOLATION VALVE FOR EACH STANDPIPE AT THE BULK FEED CONNECTION.

17. ALL NECESSARY CONNECTIONS TO THE FIRE ALARM SYSTEM SHALL BE MADE BY AND

COORDINATED WITH THE FIRE ALARM CONTRACTOR. SYSTEM ACCEPTANCE TESTS SHALL BE

CONDUCTED BY THE FIRE ALARM CONTRACTOR AND THE OWNER.

18. AUXILIARY DRAINS ARE NOT SHOWN ON THESE DRAWINGS. LOCATIONS OF AUXILIARY DRAINS

SHALL BE DETERMINED BY CONTRACTOR WHERE A CHANGE IN PIPING DIRECTION PREVENTS

DRAINAGE OF THE SYSTEM PIPING THROUGH THE MAIN DRAIN VALVE. SIGNS SHALL BE PROVIDED

TO INDICATE AUXILIARY DRAINS. AUXILLARY DRAINS SHALL NOT BE LOCATED IN PUBLIC AREAS,

FOR EXAMPLE CORRIDORS OR WAITING AREAS.

19. UPON COMPLETION OF EACH OPERATIONAL PORTION OF THE SYSTEM INSTALLATION, HYDROSTATIC

TESTING SHALL BE CONDUCTED IN ACCORDANCE WITH NFPA 13 AND WITNESSED BY THE AHJ.

20. ALL FIRE SUPPRESSION WORK SHALL BE INSPECTED BY THE OWNERS DESIGNATED

REPRESENTATIVE

21. ALL HANGERS SHALL BE LISTED FOR USE WITH SPRINKLER SYSTEMS. HANGER INSTALLATION AND

SPACING SHALL BE IN ACCORDANCE WITH NFPA 13.

22. PENETRATION OF FIRE:RATED ASSEMBLIES SHALL BE SEALED BY THE CONTRACTOR WITH A LISTED

THROUGH:PENETRATION SYSTEM APPROPRIATE FOR THE RATING OF THE WALL PENETRATED.

COORDINATE THESE LOCATIONS WITH THE LIFE SAFETY PLANS.

23. AT ROOF LEVEL, DO NOT SUPPORT SPRINKLER PIPE FROM BOTTOM CHORDS OF ROOF BAR JOIST

OR FROM ROOF DECKING. SUPPORT OF SPRINKLER PIPE FROM TOP CHORDS OF ROOF BAR JOIST

OR I:BEAM IS ACCEPTABLE.

24. ALL SPRINKLER SYSTEM PIPING AND HANGERS SHALL BE CONCEALED WHEREVER POSSIBLE.

PROVIDE ACCESS PANELS FOR ALL VALVES, WHERE REQUIRED.

SPRINKLER SYSTEM PROJECT NOTES

IT

HT

CE

- 001

Page 7: FIRE ALARM SYSTEM SYMBOLS - Skanska · florida building code, 2010 edition 9 nfpa 70, national electrical code, 2008 edition nfpa 72, national fire alarm code, 2007 edition 9 florida

WOMEN

110

MEN

107

STORAGE

106

FIRECOMMAND

CENTER

104

LOBBY

101

GIFT SHOP

100

FAMILY

108

CAFE

111

ELEVATOR 1 ELEVATOR 2

STAIR B

JAN

105

CORRIDOR

103

STAIR A

SPRINKLERRISER ROOM

113

OH1

OH1

OH1

1

4"

212"

21

2"

4"

4"

212"

2

6

7 7

4

5

8

4"

3

9

4"

10

11

12

10

1

1

1

1

EXHIBIT

200

EXHIBIT

200

ELEVATOR 1 ELEVATOR 2STAIR B

STAIR A

1

212"

212"

OH1

OH1

3

4

4"

4

ZCA

10

1010

1

1 1

SPRINKLERGROUND AND

SECOND FLOORPLAN

FP1.0

1/8" = 1'*0"FP1.0

GROUND FLOOR * SPRINKLER1

1/8" = 1'*0"FP1.0

SECOND FLOOR * SPRINKLER2

Seal:

GWWO INC.

800 WYMAN PARK DRIVE, SUITE 300

BALTIMORE, MARYLAND 21211, 410�332�1009

C 2012 GWWO INC.

I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THATI AM A DULY LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF A MARYLAND,

LICENSE NUMBER , EXPIRATION DATE

Revisions:

Job No.

Scale

Date

Drawing Title

Sheet

Drawn

Checked

Approved

Drawing Number

OfDa

te/T

ime S

tam

pF

ile P

ath

KEYNOTES LISTED ON THIS SHEET ARE FOR CONVENIENCEONLY. REFER TO SHEET CS.2 FOR COMPLETE LIST

1/8" = 1'*0"

PORT CANAVERALWELCOME CENTER

CANAVERAL PORT AUTHORITY

1124 RC

TC

EA

No. Date Description

N

8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD 21045

410*750*2246 (BALT) 410*750*2588 (FAX)

AUGUST 6 2012

CONSTRUCTION SET

Seal:

1 8/06/12 CONSTRUCTION SET

GENERAL NOTES

1. ALL AREAS LIGHT HAZARD UNLESS INDICATED AS ORDINARY HAZARD (OH1).

2. CONTRACTOR SHALL MAKE PROVISIONS TO ENSURE ADEQUATE DRAINAGE OF

ALL PIPING. AUXILIARY DRAINS SHALL BE PROVIDED IN ACCORDANCE WITH THE

REQUIREMENTS OF NFPA 13.

CONSTRUCTION NOTES (THIS SHEET ONLY)

PROVIDE WET PIPE SPRINKLER PROTECTION THROUGHOUT THE BUILDING IN

ACCORDANCE WITH NFPA 13. ALL PIPING SHALL BE ABOVE CEILING.

LOCATION OF EXTERIOR ACCESSED RISER ROOM UNDERNEATH STAIR LANDING.

PROVIDE RISER MANIFOLD AND ASSOCIATED VALVES. PROVIDE SPRINKLER

PROTECTION WITHIN ROOM. REFER TO DETAIL 1 ON FP5.0.

PROVIDE NEW 4*INCH COMBINATION SPRINKLER/ AUTOMATIC STANDPIPE RISER.

REFER TO SHEET FP5.0 FOR DETAILS.

PROVIDE NEW 4*INCH AUTOMATIC STANDPIPE RISER WITH 2.5 INCH FIRE HOSE

VALVE. PROVIDE ADJACENT EXPRESS DRAIN PIPED TO EXTERIOR ON GROUND

FLOOR.

PROVIDE CEMENT BLOCK FOR EXPRESS DRAIN DISCHARGE TO EXTERIOR.

PROVIDE SPRINKLER PROTECTION UNDER THE LOWEST LANDING OF STAIR.

PROVIDE A SIDEWALL SPRINKLER AT THE BOTTOM OF ELEVATOR HOISTWAY 2

FEET ABOVE THE PIT FLOOR.

ROUTE STANDPIPE HORIZONTAL PIPING AROUND VERTICAL OPENING.

FIRST FLOOR ZONE CONTROL ASSEMBLY.

LOCATION OF CEILING BULKHEAD. REFER TO CEILING PLAN ON A2.1.

PROVIDE SPRINKLER PROTECTION ABOVE AND UNDER FEATURE CEILING

PANELS EXCEEDING 4 FT IN LENGTH. REFER TO CEILING PLAN ON A2.1.

PROVIDE SPRINKLER PROTECTION ABOVE AND BELOW CANOPY.

1

2

3

4

5

6

7

8

9

8 0 8 16

SCALE OF FEET1/8" = 1'*0"

FP5.0

1.1

FP5.0

2

10

11

12

1

CE

- 001

Page 8: FIRE ALARM SYSTEM SYMBOLS - Skanska · florida building code, 2010 edition 9 nfpa 70, national electrical code, 2008 edition nfpa 72, national fire alarm code, 2007 edition 9 florida

AUDITORIUM

300

EXHIBIT

305

WOMEN

306

MEN

304

ROOF TYPE 2 BELOW

ELEVATOR 1 ELEVATOR 2

STAIR B

STAIR A

VESTIBULE

301

VESTIBULE

309

AV

307

AV

303

CORRIDOR

308CORRIDOR

302

SEE A7.3

FOR SSWINDOWTYPE

1

212"

212"

21

2"

OH1

23

4"

ZCA

4

1

PRE$FUNCTIONROOM

404

WOMEN

407

MEN

403

CATERINGKITCHEN

405

STORAGE

406

STAIR A

STAIR B

ELEVATOR 1 ELEVATOR 2VESTIBULE

409

VESTIBULE

401

CORRIDOR

408

CORRIDOR

402

SEE SHEET K.1

TERRACE

410

1/4" PER FT

FUNCTIONROOM

400

TYP.

1

OH1

OH1

212"

212"

21

2"

4"

23

ZCA

4 1

SPRINKLERTHIRD AND

FOURTH FLOORPLAN

FP2.0

1/8" = 1'$0"FP2.0

THIRD FLOOR $ SPRINKLER1

1/8" = 1'$0"FP2.0

FOURTH FLOOR $ SPRINKLER2

Seal:

GWWO INC.

800 WYMAN PARK DRIVE, SUITE 300

BALTIMORE, MARYLAND 21211, 410�332�1009

C 2012 GWWO INC.

I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THATI AM A DULY LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF A MARYLAND,

LICENSE NUMBER , EXPIRATION DATE

Revisions:

Job No.

Scale

Date

Drawing Title

Sheet

Drawn

Checked

Approved

Drawing Number

OfDa

te/T

ime S

tam

pF

ile P

ath

KEYNOTES LISTED ON THIS SHEET ARE FOR CONVENIENCEONLY. REFER TO SHEET CS.2 FOR COMPLETE LIST

1/8" = 1'$0"

PORT CANAVERALWELCOME CENTER

CANAVERAL PORT AUTHORITY

1124 RC

TC

EA

No. Date Description

N

8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD 21045

410$750$2246 (BALT) 410$750$2588 (FAX)

AUGUST 6 2012

CONSTRUCTION SET

Seal:

1 8/06/12 CONSTRUCTION SET

GENERAL NOTES

1. ALL AREAS LIGHT HAZARD UNLESS INDICATED AS ORDINARY HAZARD (OH1).

2. CONTRACTOR SHALL MAKE PROVISIONS TO ENSURE ADEQUATE DRAINAGE OF

ALL PIPING. AUXILIARY DRAINS SHALL BE PROVIDED IN ACCORDANCE WITH THE

REQUIREMENTS OF NFPA 13.

CONSTRUCTION NOTES (THIS SHEET ONLY)

PROVIDE WET PIPE SPRINKLER PROTECTION THROUGHOUT THE BUILDING IN

ACCORDANCE WITH NFPA 13. ALL PIPING SHALL BE ABOVE CEILING.

PROVIDE NEW 4$INCH COMBINATION SPRINKLER/ AUTOMATIC STANDPIPE.

REFER TO SHEET FP5.0 FOR DETAILS.

PROVIDE NEW 4$INCH AUTOMATIC STANDPIPE RISER WITH 2.5 INCH FIRE HOSE

VALVE. PROVIDE ADJACENT EXPRESS DRAIN PIPED TO EXTERIOR ON

GROUND FLOOR.

LOCATION OF CEILING BULKHEAD. REFER TO CEILING PLAN ON A2.1.

1

2

3

8 0 8 16

SCALE OF FEET1/8" = 1'$0"

FP5.0

3

FP5.0

4

4

1

CE

- 001

Page 9: FIRE ALARM SYSTEM SYMBOLS - Skanska · florida building code, 2010 edition 9 nfpa 70, national electrical code, 2008 edition nfpa 72, national fire alarm code, 2007 edition 9 florida

ELEVATORCONTROL

ROOM

504

STAIR A

STAIR BELEVATOR 2ELEVATOR 1

MECHANICAL

502

RESTROOM

506

CORRIDOR

501

EXHIBIT

500

ELECTRICAL

503

IT

505

ELECTRICAL

507

1

OH1

212"

212"

21

2"

OH1

OH1

4

OH1

4"

23

OH1

4

4

OH1

ZCA

5

1

STAIR A

STAIR B

ELEVATOR 2ELEVATOR 1

WORK ROOM

607

MEN

603

HARBORMASTER

601

STORAGE

604

INDOOROBSERVATION

600

WOMEN

605

JAN

606

STOR

602

1

OH1

212"

212"

21

2"

OH1

4"

23

OH1

ZCA

5

1

1/8" = 1'$0"FP3.0

FIFTH FLOOR $ SPRINKLER1

1/8" = 1'$0"FP3.0

SIXTH FLOOR $ SPRINKLER2

SPRINKLERFIFTH AND SIXTH

FLOOR PLAN FP3.0

Seal:

GWWO INC.

800 WYMAN PARK DRIVE, SUITE 300

BALTIMORE, MARYLAND 21211, 410�332�1009

C 2012 GWWO INC.

I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THATI AM A DULY LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF A MARYLAND,

LICENSE NUMBER , EXPIRATION DATE

Revisions:

Job No.

Scale

Date

Drawing Title

Sheet

Drawn

Checked

Approved

Drawing Number

OfDa

te/T

ime S

tam

pF

ile P

ath

KEYNOTES LISTED ON THIS SHEET ARE FOR CONVENIENCEONLY. REFER TO SHEET CS.2 FOR COMPLETE LIST

1/8" = 1'$0"

PORT CANAVERALWELCOME CENTER

CANAVERAL PORT AUTHORITY

1124 RC

TC

EA

No. Date Description

N

8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD 21045

410$750$2246 (BALT) 410$750$2588 (FAX)

AUGUST 6 2012

CONSTRUCTION SET

Seal:

1 8/06/12 CONSTRUCTION SET

GENERAL NOTES

1. ALL AREAS LIGHT HAZARD UNLESS INDICATED AS ORDINARY HAZARD (OH1).

2. CONTRACTOR SHALL MAKE PROVISIONS TO ENSURE ADEQUATE DRAINAGE OF

ALL PIPING. AUXILIARY DRAINS SHALL BE PROVIDED IN ACCORDANCE WITH THE

REQUIREMENTS OF NFPA 13.

CONSTRUCTION NOTES (THIS SHEET ONLY)

PROVIDE WET PIPE SPRINKLER PROTECTION THROUGHOUT THE BUILDING IN

ACCORDANCE WITH NFPA 13. ALL PIPING SHALL BE ABOVE CEILING.

PROVIDE NEW 4$INCH COMBINATION SPRINKLER/ AUTOMATIC STANDPIPE.

REFER TO SHEET FP5.0 FOR DETAILS.

PROVIDE NEW 4$INCH AUTOMATIC STANDPIPE RISER WITH 2.5 INCH FIRE HOSE

VALVE. PROVIDE ADJACENT EXPRESS DRAIN PIPED TO EXTERIOR ON GROUND

FLOOR.

DO NOT ROUTE PIPING OVER ELECTRICAL PANELS WITHIN ELECTRICAL

EQUIPMENT ROOM.

LOCATION OF CEILING BULKHEAD. REFER TO CEILING PLAN ON A2.1.

1

2

3

4

8 0 8 16

SCALE OF FEET1/8" = 1'$0"

FP5.0

5

FP5.0

6

5

1

CE

- 001

Page 10: FIRE ALARM SYSTEM SYMBOLS - Skanska · florida building code, 2010 edition 9 nfpa 70, national electrical code, 2008 edition nfpa 72, national fire alarm code, 2007 edition 9 florida

OBSERVATION

700

STAIR A

ELEVATOR 1 ELEVATOR 2 STAIR B

VESTIBULE

701

11

3

22

3

21

7

5

8

10

913

15

11

12

16

22

26

23

24

COUPLING (GUARD NOT SHOWN)

JOCKEY PUMP

AURORA FIRE%PUMP

DRIVER WITH VARIABLE SPEED CAPABILITY

CONTROL PANEL (JOCKEY PUMP)

OS & Y GATE VALVE

ECCENTRIC REDUCER

AIR RELEASE VALVE (PUMP CASING)

SUCTION PRESSURE GAUGE

VARIABLE SPEED DRIVE CONTROL PANEL (FIRE PUMP)

OS & Y GATE VALVE (JOCKEY PUMP SUCTION)

RELIEF VALVE (JOCKEY PUMP LINE)

CHECK VALVE (JOCKEY PUMP LINE)

BUTTERFLY VALVE (HOSE HEADER)

OS & Y GATE VALVE (JOCKEY PUMP DISCHARGE)

WAFER CHECK VALVE

CONCENTRIC INCREASER

BUTTERFLY VALVE (DISCHARGE SIDE)

HOSE VALVE

HOSE HEADER

DISCHARGE PRESSURE GAUGE

23

24

19

20

22

15

16

17

18

11

13

12

10

4

9

8

5

6

2

3

1

WAFER CHECK VALVE (BYPASS LINE)

BUTTERFLY VALVE (BYPASS LINE)25

26

BYPASS LINE AIR RELEASE27

RELIEF VALVE (FIRE PUMP CASING)7

6 4

SUCTION

CONNECTION

DISCHARGE CONNECTION

HOSE HEADER

CONNECTION

27

25

FRONT VIEW

(SIDE VIEW W/O JOCKEY PUMP LINE, CONTROLLERS,

HOSE HEADER CONNECTION)

PLAN VIEW

NOTE: PUMP HOUSE ILLUSTRATION IS TYPICAL

REPRESENTATION FOR CONCEPT PURPOSES. EXACT LAYOUT

OF PREFABRICATED HOUSE SHALL BE ILLUSTRATED ON

CONTRACTOR SHOP DRAWINGS. REFER TO PROJECT CIVIL

DRAWINGS FOR ADDITIONAL INFORMATION.

17

18 19

20

28

AUTOMATIC RELIEF VALVE28

PIPE TO

DRAIN

1/8" = 1'%0"FP4.0

SEVENTH FLOOR % SPRINKLER1

SPRINKLERSEVENTH

FLOOR ANDDETAILS

FP4.0

Seal:

GWWO INC.

800 WYMAN PARK DRIVE, SUITE 300

BALTIMORE, MARYLAND 21211, 410�332�1009

C 2012 GWWO INC.

I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THATI AM A DULY LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF A MARYLAND,

LICENSE NUMBER , EXPIRATION DATE

Revisions:

Job No.

Scale

Date

Drawing Title

Sheet

Drawn

Checked

Approved

Drawing Number

OfDa

te/T

ime S

tam

pF

ile P

ath

KEYNOTES LISTED ON THIS SHEET ARE FOR CONVENIENCEONLY. REFER TO SHEET CS.2 FOR COMPLETE LIST

1/8" = 1'%0"

PORT CANAVERALWELCOME CENTER

CANAVERAL PORT AUTHORITY

1124 RC

TC

EA

No. Date Description

N

8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD 21045

410%750%2246 (BALT) 410%750%2588 (FAX)

AUGUST 6 2012

CONSTRUCTION SET

Seal:

1 8/06/12 CONSTRUCTION SET

GENERAL NOTES

1. ALL AREAS LIGHT HAZARD UNLESS INDICATED AS ORDINARY HAZARD (OH1).

2. CONTRACTOR SHALL MAKE PROVISIONS TO ENSURE ADEQUATE DRAINAGE OF

ALL PIPING. AUXILIARY DRAINS SHALL BE PROVIDED IN ACCORDANCE WITH THE

REQUIREMENTS OF NFPA 13.

CONSTRUCTION NOTES (THIS DETAIL ONLY)

PROVIDE WET PIPE SPRINKLER PROTECTION AT THE TOP OF THE STAIRS.

PROVIDE PRESSURE GAUGE AT HIGHEST LANDING OF THE STANDPIPES.

PROVIDE SPRINKLER PROTECTION WITHIN OBSERVATION VESTIBULE AND

ELEVATORS WITH COMBUSTIBLE BELTS. EXTEND SPRINKLER PIPING UP FROM

SIXTH FLOOR VIA SHAFT.

1

2

3

NTSFP4.0

ZONE CONTROL ASSEMBLY2

±3

'%0

" T

O 5

'%0"

2%1/2" ANGLE

HOSE VALVE

FLOOR LEVEL

TO

UP

PE

R L

EV

EL

STANDPIPE

PROVIDE 300 LB. PRESSURE

GAUGE AT TOP OF STANDPIPE

NTSFP4.0

TYPICAL STANDPIPE HOSE VALVE DETAIL3

THROUGH PENETRANT: ONE PIPE INSTALLED CONCENTRICALLY OR ECCENTRICALLY

WITHIN THE FIRESTOP SYSTEM. PIPE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF

WALL ASSEMBLY.

FILL MATERIAL: SEALANT % FILL MATERIAL (NOT SHOWN) APPLIED WITHIN THE

ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. BEAD OF FILL MATERIAL SHALL

ALSO BE APPLIED AT THE PIPE/WALL INTERFACE.

SPRINKLER SYSTEM PIPING

RATED FIRE BARRIER

FILL MATERIAL

SCHEDULE 40 BLACK STEEL PIPE

SLEEVE

NOTE: PROVIDE UL LISTED THROUGH%PENETRATION

FIRESTOP SYSTEM AT ALL RATED ASSEMBLIES.

NTSFP4.0

THROUGH WALL PENETRATION4

UP TO 1'%0"

NTSFP4.0

TYPICAL HANGER DETAILS5

ST

EE

L

DIA

ME

TE

R 15'%0"

15'%0"

15'%0"

2"

2 12"

3"& 4"

12'%0"

12'%0"

15'%0"

1"

1 14"

1 12"

MAXIMUM DISTANCE BETWEEN HANGERS

HANGER NOTES:

1. MAXIMUM UNSUPPORTED

ARMOVER LENGTH SHALL NOT BE

GREATER THAN 12"

2. MIN 38" ALL THREAD ROD FOR PIPE

DIAMETERS 4" AND SMALLER

3. PROVIDE SURGE RESTRAINT FOR

ALL HANGERS AS REQUIRED FOR

SYSTEMS IN EXCESS OF 100 PSI

SPAN

DIA

ME

TE

R 5'%0"

4'%0"

4'%0"

2"

2 12"

3"& 4"

5'%0"

5'%0"

5'%0"

1"

1 14"

1 12"

MAXIMUM SPAN OF TRAPEZE MEMBER

NTSFP4.0

PREFABRICATED PUMP HOUSE6

8 0 8 16

SCALE OF FEET1/8" = 1'%0"

FP5.0

7

FLOOR LEVEL

2 1/2" ANGLE

HOSE VALVE

STANDPIPE

3'%0"

TO

5'%0"

TO

UP

PE

R L

EV

EL

PROVIDE 300 LB. PRESSURE

GAUGE AT TOP OF STANDPIPE

1

1

1

1

1

CE

- 001

Page 11: FIRE ALARM SYSTEM SYMBOLS - Skanska · florida building code, 2010 edition 9 nfpa 70, national electrical code, 2008 edition nfpa 72, national fire alarm code, 2007 edition 9 florida

LOBBY

101

CORRIDOR

103

1

5

3

611

10

9

2 4

7

8

EXHIBIT

200

3

1

2

EXHIBIT

500

CORRIDOR

501

3

1

2

FUNCTIONROOM

400

VESTIBULE

401

3

1

2

OBSERVATION

700

3

1

2

INDOOROBSERVATION

600

3

1

2

EXHIBIT

305

CORRIDOR

302

AUDITORIUM

300

3

1

2

GROUND FLOOR12.00'

SECOND FLOOR32.00'

THIRD FLOOR50.00'

FOURTH FLOOR68.00'

FIFTH FLOOR83.00'

SIXTH FLOOR98.00'

TOP OF CONCRETE #OBSERVATION FLOOR112.00'

SPRINKLERRISER ROOM

113

STAIR B

ST#B

CORRIDOR

103

EXHIBIT

200

CORRIDOR

302

CORRIDOR

402

TOP OF CONCRETE #STAIR TOWER # HIGH121.78'

TOP OF CONCRETE #STAIR TOWER # LOW121.33'

ELECTRICAL

503

OBSERVATION FLOOR113.00'

HARBORMASTER

601

2

1

5

6

4

ZCA

ZCA

ZCA

ZCA

7

9

3

8

ZCA

ZCA

4

4

4

4

4

4

4

11

11

11

11

11

10

SPRINKLERDETAILS

FP5.0

Seal:

GWWO INC.

800 WYMAN PARK DRIVE, SUITE 300

BALTIMORE, MARYLAND 21211, 410�332�1009

C 2012 GWWO INC.

I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THATI AM A DULY LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF A MARYLAND,

LICENSE NUMBER , EXPIRATION DATE

Revisions:

Job No.

Scale

Date

Drawing Title

Sheet

Drawn

Checked

Approved

Drawing Number

OfDa

te/T

ime S

tam

pF

ile P

ath

KEYNOTES LISTED ON THIS SHEET ARE FOR CONVENIENCEONLY. REFER TO SHEET CS.2 FOR COMPLETE LIST

1/8" = 1'#0"

PORT CANAVERALWELCOME CENTER

CANAVERAL PORT AUTHORITY

1124 RC

TC

EA

No. Date Description

N

8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD 21045

410#750#2246 (BALT) 410#750#2588 (FAX)

AUGUST 6 2012

CONSTRUCTION SET

Seal:

1 8/06/12 CONSTRUCTION SET

CONSTRUCTION NOTES (THIS DETAIL ONLY)

EXTEND NEW 8#INCH INCOMING WATER SERVICE MAIN TO THIS LOCATION.

REFER TO PROJECT CIVIL DRAWINGS.

APPROXIMATE LOCATION OF FLOOR SLAB PENETRATION.

TO FIRST FLOOR SPRINKLERS.

PROVIDE 6#INCH MAIN BUILDING CONTROL VALVE, CHECK VALVE, AND

APPURTENANCES IN VERTICAL POSITION.

RUN 4#INCH PIPE TIGHT TO RISER ROOM CEILING. RUN PIPE ABOVE MECHANICAL

WATER PIPING.

APPROXIMATE LOCATION OF MECHANICAL EQUIPMENT.

PENETRATE STAIR WALL BELOW INTERMEDIATE LANDING AND CONTINUE TO

CORRIDOR. REFER TO SHEET FP1.0 FOR CONTINUATION.

1

3/16" = 1'#0"FP5.0

1.1

3/16" = 1'#0"FP5.0

STAIR B # SECOND FLOOR PLAN2

3/16" = 1'#0"FP5.0

STAIR B # FIFTH FLOOR PLAN5

3/16" = 1'#0"FP5.0

4

3/16" = 1'#0"FP5.0

STAIR B # SEVENTH FLOOR PLAN7

3/16" = 1'#0"FP5.0

STAIR B # SIXTH FLOOR PLAN6

3/16" = 1'#0"FP5.0

STAIR B # THIRD FLOOR PLAN3

STAIR B # GROUND FLOOR PLAN

2

3

4

5

11

10

9

8

7

6

STAIR B # FOURTH FLOOR PLAN

CONSTRUCTION NOTES (DETAILS 2 � 7)

EXPRESS DRAIN LOCATION. INSTALL ADJACENT TO STANDPIPE. MAINTAIN

EGRESS CLEAR WIDTH ON LANDING.

PROVIDE 4#INCH CLASS I AUTOMATIC SPRINKLER STANDPIPE RISER.

PROVIDE 212#INCH HOSE VALVE ON RISER. INSTALL SO THAT OS&Y VALVE DOES

NOT PROJECT MORE THAN 12#INCHES FROM STANDPIPE. MAINTAIN EGRESS

CLEAR WIDTH ON LANDING.

1

2

3

3/16" = 1'#0"FP5.0

STAIR B # LONGITUDINAL SECTION8

CONSTRUCTION NOTES (THIS DETAIL ONLY)

APPROXIMATE LOCATION OF INCOMING WATER.

EXTEND DRAIN THROUGH EXTERIOR WALL. PROVIDE CEMENT BLOCK FOR

EXPRESS DRAIN DISCHARGE TO EXTERIOR.

PROVIDE SPRINKLER PROTECTION WITHIN RISER ROOM.

PROVIDE 2 ½#INCH HOSE VALVE ON RISER BETWEEN 3 12 FT AND 5FT AFF.

PROVIDE SPRINKLER PROTECTION AT THE TOP OF THE STAIRS.

PROVIDE SPRINKLER PROTECTION IN EXTERIOR ACCESSED MECHANICAL

ROOM.

TO GROUND FLOOR SPRINKLER SYSTEM.

4#INCH FEED TO STAIR A STANDPIPE.

6#INCH MAIN SHUT OFF VALVE, CHECK VALVE AND FLOW SWITCH.

GAUGE.

TO SPRINKLER SYSTEM ON FLOOR.

1

2

3

4

5

6

11

10

9

8

7

ZONE CONTROL ASSEMBLY FOR GROUND FLOOR IN STAIR.

4#INCH COMBINATION SPRINKLER STANDPIPE UP THROUGH INTERMEDIATE

STAIR LANDING.

EXPRESS DRAIN UP THROUGH INTERMEDIATE STAIR LANDING.

EXTEND DRAIN THROUGH EXTERIOR WALL. PROVIDE CEMENT BLOCK FOR

EXPRESS DRAIN DISCHARGE TO EXTERIOR.

BUILDING FOUNDATION WALL

MAINTAIN MIN.

COVER DEPICTED ON

CIVIL DRAWINGS

INSTALL BITUMINOUS COATED

CLASS 50 DIP OR SCH. 40

STEEL SLEEVE THROUGH

BUILDING FOUNDATION WALL

COAT ALL U/G FERROUS METAL

PARTS WITH 2 COATS OF BITUMASTIC

OR COAL TAR EXPOXY (TYP)

COMPACTED SUBGRADE

12" DIP WALL PIPE WITH

INTERGRAL WATER STOP

GROUT WATER TIGHT ALL

AROUND WITH NON#SHRINK,

NON#METALIC GROUT

TIE RODS

EXTEND TIE RODS THROUGH FOUNDATION

WALL, CAULK WATER TIGHT ALL

AROUND

SLEEVE THROUGH

EXISTING SLAB

BUILDING SLAB

EXTEND TIE RODS THROUGH BLIND FLANGE

SET BLIND FLANGE AT 12" AFF

PLUMB AND LEVEL FOR TESTING

OF UNDERGROUND PIPING SYSTEM

3/16" = 1'#0"FP5.0

1.2 WATER SERVICE ENTRANCE

EXTEND UNDERGROUND PIPE. SEE

CIVIL DRAWINGS FOR

CONTINUATION.

CE

- 001