    Reference Guide for Building Operation, Maintenance & Recordkeepin(Fire Safety Director Continuing Education)

    Graduation Test Reference Guide Defining Individuals Qualified as to whom can Perform

    Inspection, Testing and Maintenance for Fire Alarm System & OtherRelated SystemsS-95 C of F S-95 - Supervision for Fire alarm Systems & other related systems W-26 C of F W-26 - Maintenance and Testing Of Smoke Detectors City Wide

    to the equipment manufacturer’s published instructions1 After initial acceptance and reacceptance functionally tested.2  The visual inspection shall be made to ensure that there are no changes that affect

    equipment performance.3  Must be performed by an Authorized Technician. 

    May be performed by Components 

    S-95 C of F

    I. VISUAL INSPECTION2 

    Frequency1  WEEKLY (52) 1 Fuses

    Interfaced equipment

    Lamps and LEDs

    Control equipment: Fire Alarm SystemsUnmonitored for Alarm supervisory and

     Trouble Signals

    Primary (main) power supply

    Yes 

    Lead-acid

    Nickel-cadmium

    Primary (dry cell)

    Batteries

    Sealed Lead-acid

    Yes 

    MONTHLY (12) 1 Lead-acidBatteries Primary (dry cell)

    Yes 

    QUARTERLY (4) 1 Supervisory signal and waterflow initiating devices Yes 

    Radiant energy fire detectors

    Supervisory signal devices

    Other Initiating devices

    Waterflow devices

    Yes 

    SEMIANNUALLY (2) 1 Nickel-cadmiumBatteries Sealed lead-acid

    Yes 

    Emergency voice alarm communications equipment

    Remote annunciators

    Alarm Notification appliance Supervised Yes Interface equipment

    Central station transmitters

    Air sampling

    Duct detectors

    Electromechanical releasing devices

    Fire extinguishing system(s) orsuppression system(s) switches

    Fire alarm boxes

    Other Initiating devices

    Smoke detectors (excluding one- andtwo-family dwellings)

    Yes 

    ANNUALLY (1) 1 

  • 8/17/2019 Fire Alarm Reference Guide.pdf

    2/3

     

    Fuses

    Interfaced equipment

    Lamps and LEDs

    Control equipment: Fire Alarm SystemsMonitored for Alarm supervisory and

     Trouble Signals

    Primary (main power supply

    Yes 

    II. TEST3 

    Frequency1  MONTHLY (12) 1 Engine-Driven Generator — Central Station Facilities and Fire Alarm Systems Yes3 Batteries — Fire Alarm Systems Primary type (dry cell) - Age test Yes3 

    QUARTERLY (4) 1 Functions

    Fuses

    Interfaced equipment

    Lamps and LEDs

    Primary (main) power supply

    Control Equipment — Building SystemsNot Connected to a Supervising Station

     Transponders

    Yes3 

    Initiating Devices Supervisory signal devices (exceptvalve tamper switches)

    SEMIANNUALLY (2) 1 Discharge test (30 minutes)Load voltage test

    Lead-acid type

    Specific gravity

    Nickel-cadmium type Load voltage test

    Batteries —Fire AlarmSystems

    Charger test (Replacebattery within 5 yearsafter manufacture or morefrequently as needed.)

    Load voltage test

    Yes3 

    Radiant energy fire detectors

    Waterflow devices

    Initiating Devices

    Valve supervisory switches

    Yes3 

    ANNUALLY (1) 1 Lead-acid type Charger test (Replace

    battery as needed.)

    Charger test (Replacebattery as needed.)

    Nickel-cadmiumtype

    Discharge test (30 minutes)

    Charger test (Replacebattery within 5 years after

    manufacture or morefrequently as needed.)

    Batteries — Fire AlarmSystems

    Sealed lead-acidtype

    Discharge test (30 minutes)

    Yes3 

    Functions

    Fuses

    Interfaced equipment

    Lamps and LEDs

    Primary (main) power supply

    Control Equipment — Building

    Systems Connected toSupervising Station

     Transponders

    Yes3 

    Emergency Voice/Alarm Communications Equipment Yes3

     Remote Annunciators Yes3 Duct detectors

    Electromechanical releasing device

    Fire extinguishing system(s) orsuppression system(s) switches

    Fire–gas and other detectors

    Heat detectors

    Fire alarm boxes

    Initiating Devices

    System smoke detectors — functionaltest

    Yes3 

  • 8/17/2019 Fire Alarm Reference Guide.pdf

    3/3

     

    Smoke detectors — sensitivity testingin other than one- and two-familydwellings

    Single- and multiple-station smokealarms

    Single- and multiple-station heatalarms

    Audible devices

    Audible textual notification appliances

    Alarm Notification Appliances

    Visible devices

    Yes3 

    Central Station Transmitters Yes3