Reference Guide for Building Operation, Maintenance & Recordkeepin(Fire Safety Director Continuing Education)
Graduation Test Reference Guide Defining Individuals Qualified as to whom can Perform
Inspection, Testing and Maintenance for Fire Alarm System & OtherRelated SystemsS-95 C of F S-95 - Supervision for Fire alarm Systems & other related systems W-26 C of F W-26 - Maintenance and Testing Of Smoke Detectors City Wide
to the equipment manufacturer’s published instructions1 After initial acceptance and reacceptance functionally tested.2 The visual inspection shall be made to ensure that there are no changes that affect
equipment performance.3 Must be performed by an Authorized Technician.
May be performed by Components
S-95 C of F
I. VISUAL INSPECTION2
Frequency1 WEEKLY (52) 1 Fuses
Interfaced equipment
Lamps and LEDs
Control equipment: Fire Alarm SystemsUnmonitored for Alarm supervisory and
Trouble Signals
Primary (main) power supply
Yes
Lead-acid
Nickel-cadmium
Primary (dry cell)
Batteries
Sealed Lead-acid
Yes
MONTHLY (12) 1 Lead-acidBatteries Primary (dry cell)
Yes
QUARTERLY (4) 1 Supervisory signal and waterflow initiating devices Yes
Radiant energy fire detectors
Supervisory signal devices
Other Initiating devices
Waterflow devices
Yes
SEMIANNUALLY (2) 1 Nickel-cadmiumBatteries Sealed lead-acid
Yes
Emergency voice alarm communications equipment
Remote annunciators
Alarm Notification appliance Supervised Yes Interface equipment
Central station transmitters
Air sampling
Duct detectors
Electromechanical releasing devices
Fire extinguishing system(s) orsuppression system(s) switches
Fire alarm boxes
Other Initiating devices
Smoke detectors (excluding one- andtwo-family dwellings)
Yes
ANNUALLY (1) 1
-
8/17/2019 Fire Alarm Reference Guide.pdf
2/3
Fuses
Interfaced equipment
Lamps and LEDs
Control equipment: Fire Alarm SystemsMonitored for Alarm supervisory and
Trouble Signals
Primary (main power supply
Yes
II. TEST3
Frequency1 MONTHLY (12) 1 Engine-Driven Generator — Central Station Facilities and Fire Alarm Systems Yes3 Batteries — Fire Alarm Systems Primary type (dry cell) - Age test Yes3
QUARTERLY (4) 1 Functions
Fuses
Interfaced equipment
Lamps and LEDs
Primary (main) power supply
Control Equipment — Building SystemsNot Connected to a Supervising Station
Transponders
Yes3
Initiating Devices Supervisory signal devices (exceptvalve tamper switches)
SEMIANNUALLY (2) 1 Discharge test (30 minutes)Load voltage test
Lead-acid type
Specific gravity
Nickel-cadmium type Load voltage test
Batteries —Fire AlarmSystems
Charger test (Replacebattery within 5 yearsafter manufacture or morefrequently as needed.)
Load voltage test
Yes3
Radiant energy fire detectors
Waterflow devices
Initiating Devices
Valve supervisory switches
Yes3
ANNUALLY (1) 1 Lead-acid type Charger test (Replace
battery as needed.)
Charger test (Replacebattery as needed.)
Nickel-cadmiumtype
Discharge test (30 minutes)
Charger test (Replacebattery within 5 years after
manufacture or morefrequently as needed.)
Batteries — Fire AlarmSystems
Sealed lead-acidtype
Discharge test (30 minutes)
Yes3
Functions
Fuses
Interfaced equipment
Lamps and LEDs
Primary (main) power supply
Control Equipment — Building
Systems Connected toSupervising Station
Transponders
Yes3
Emergency Voice/Alarm Communications Equipment Yes3
Remote Annunciators Yes3 Duct detectors
Electromechanical releasing device
Fire extinguishing system(s) orsuppression system(s) switches
Fire–gas and other detectors
Heat detectors
Fire alarm boxes
Initiating Devices
System smoke detectors — functionaltest
Yes3
-
8/17/2019 Fire Alarm Reference Guide.pdf
3/3
Smoke detectors — sensitivity testingin other than one- and two-familydwellings
Single- and multiple-station smokealarms
Single- and multiple-station heatalarms
Audible devices
Audible textual notification appliances
Alarm Notification Appliances
Visible devices
Yes3
Central Station Transmitters Yes3