FINAL CONSTRUCTION REPORT
NYSERDA
RESIDENTIAL PERFORMANCE CHALLENGE
HOUSE #4
INVERNESS GARDENS – MILLER HOMES
DECEMBER 2011
Submitted to:
NYSERDA
17 Columbia Circle
Albany, NY 12203
Submitted by:
HOMEPIC Team
CDH Energy Corp.
PO Box 641
Cazenovia, NY 13035
315-655.1063
and
Syracuse Center of Excellence in Energy and Environmental Systems
Northeast Green Building Consulting
Camroden Associates
Building Performance Contractors Association of New York
HomePIC Team 2 December 2011
Figure 1. Two-Unit Model at Inverness Gardens (Astilbe Path)
This 2-unit model townhome was built by Miller Homes in September 2011. The house was part
of the 2011 Syracuse Parade of Homes. This model has 2-story units with a loft option. The left
side is the finished model unit while the right side was left unfinished to highlight the
construction and insulation details. The unfinished side was also open during Parade of Homes
to educate the public about the energy efficiency improvements available in these units. As part
of the re-design process we worked with the builder’s architect to revise the plans for the 2-story
unit with loft (1984 sq ft) that was built at this site. In addition, the efficiency improvements
were also included into the plans for the 1-story (1582 sq ft) unit and the 2-story without loft
(1841 sq ft).
The major energy efficiency improvements incorporated into these homes included the Superior
Walls precast foundation system with 2.5” of insulation in the basement as well as the exterior
walls with 2” of exterior foam and 2x6” with 24” OC framing. The wall cavities were filled with
BIBS blown fiberglass. The cathedral ceiling used blown fiberglass, closed cell spray foam, and
2” exterior rigid foam under the roof deck. Blown fiberglass was used in the attic.
The key construction details are summarized in the following section. Table 2 compares the
originally proposed improvements to the actual implemented features. Table 3 summarizes the
costs of the implemented improvements. During construction we worked with the contractor and
recommended additional measures that could be implemented to better adjust to constructability.
In many respects the final design was better than we originally proposed.
HomePIC Team 3 December 2011
Table 1. Energy Performance Ratings for each Window Type
Window Type U-Factor SHGC Visible Transmittance
Double Hung 0.22 0.23 0.37
Slider 0.30 0.20 0.38
Basement 0.28 0.35 0.52
Cathedral Ceiling with 2” Rigid Foam, Spray Foam, and BIBS
Baffles Spray Foamed In Place for Ventilation in Attic
Figure 2. Photos Showing Exterior and Ceiling Insulation Details
The cathedral ceiling with 2x12” with 24” OC framing has 2” exterior rigid foam beneath the
roof deck. In addition, 3” of closed cell spray foam and BIBS blown fiberglass were installed
from below as shown in Figure 2. The design called for the end walls at the gable ends to be
offset by 2” so the exterior foam was not required on the walls for the attic and garage. The
approach eliminated the expense of unnecessary foam board and still allowed the garage and
attic exterior sheathing to be flush with the exterior foam.
EXTERIOR FOAM
CLOSED CELL SPRAY FOAM
BIBS
EXTERIOR FOAM INSTALLED FLUSH WITH OSB IN UNINSULATED
GARAGE AND ATTIC
2” FOAM WITH TAPED SEAMS
HomePIC Team 4 December 2011
Figure 3. Photos Showing Basement Construction, Insulation, and Sealing Details.
A Superior Wall® pre-cast, insulated, and modular foundation system was chosen over the CMU
foundation (Figure 3) in order meet the tight time-schedule for the Parade of Homes. 2” rigid
foam was installed under the entire basement floor.
XI® SUPERIOR WALL 2” RIGID FOAM
BENEATH BASEMENT FLOOR
SPRAY FOAM ON RIM JOISTS
HomePIC Team 5 December 2011
Figure 4. Photos Showing Truss Design and Insulation Choices for Second Floor Walls Adjoining Attic Space.
The top two photos in Figure 4 show that the roof trusses were designed to leave space to install
2” rigid foam on the second floor to attic walls. Then the rigid foam was sealed with closed cell
foam shown in the bottom two photos. This completely sealed the second floor from the
unconditioned attic space.
2” FOAM INSTALLED
CLOSED CELL SPRAY FOAM
SPACE LEFT FOR 2” FOAM
INSTALLATION
HomePIC Team 6 December 2011
Figure 5 shows the details of the tray ceiling in the master bedroom. Closed cell foam seals and
insulates the unconditioned side of the tray ceiling and all of the second floor rim joists to
maintain the conditioned envelope.
Figure 5. Photos Showing Tray Ceiling and 2nd Floor Rim Joist Insulation
The photo in Figure 6 shows a common occurrence in stick framed, residential construction
inaccessible corners are created by the end studs on every corner wall. In this case a jack and
king stud on the left meets a stud on right to form a void that is difficult to insulate. The 2” of
exterior foam and sealing techniques used in the construction of this home reduced the impact of
these empty corners. However, the plans had called for a different stud corner arrangement, as
shown by the drawing on the right side of the Figure that was intended to eliminate this issue.
SIDES OF TRAY CEILING IN MASTER BEDROOM
SECOND FLOOR RIM JOISTS INSULATED ON
BOTH SIDES
HomePIC Team 7 December 2011
Figure 6. Photo Showing Empty Space Created by Studs in Corners
Mechanical Systems
The mechanical system is a Combi unit that uses a tankless water heater to provide both water
heating and space heating. Potable (domestic) hot water is piped to a hot water coil in the air
handler that also provides cooling to the house. In addition, the system also included a solar
water heating system with a 120 gallon tank. The 94% efficient Rheem RTGH-95DVN
condensing, direct vent, tankless unit is shown in Figure 7. The 2.5 ton Rheem air handler has a
cooling coil installed in the cabinet and a heating coil installed immediately downstream. The
system is shown schematically in Figure 8.
Figure 7. Photos Showing DHW and Space Heating Equipment
HEATING COIL
AIR HANDLER
WHOLE HOUSE VENTILATION CONTROLLER
EMPTY CORNER STUD
CAVITY
STUD ARRANGEMENT CALLED FOR IN PLANS
HomePIC Team 8 December 2011
Figure 8. Schematic of DHW and Space Heating System (Monitoring Pts Shown as Red)
Ventilation is provided by a fresh air intake on the return side of the air handler. A damper is
installed on the intake duct which is controlled by the Honeywell controller. The controller
operates the AHU fan and damper fan to supply the desired amount of ventilation. The
controller was set to operate the fan and damper for 36 minutes out of every hour (60% of the
time) to provide ventilation to the home. When the AHU operated with damper open, the
measured ventilation flow was 86 cfm; therefore, the average ventilation across each hour was
52 cfm. The controller also closes the damper when heating and cooling operation are required
for more than 36 minutes of each hour to limit over ventilation. Figure 9 shows where damper
control is located in the fresh air intake duct in the basement. The bottom-left photo in Figure 9
also shows the electric ionizing air cleaner that was installed in the air handler return duct.
In this house the builder also provided ventilation in the garage. The continuous duty exhaust
fan operates at low speed but jumps to high speed when the garage door opens. This system was
intended to provide the ventilation of vehicle exhaust and maintains the garage under negative
pressure. In the winter of 2011, the negative pressure (-10 Pa) caused some moisture from under
the slab to condense on the lower portions of the garage wall and discolor the paint. The garage-
slab-to-foundation interface was sealed to eliminate this problem.
TSHS
Electric Air
Cleaner/Ionizer
Heating Coil Tankless Heater
Solar Tank
Outdoor Air
Supply Air
TSHW
TWH
TWC
SRP
TWS
SDHW
TSHR
TSHM Return/ Space
Air
SV
Ventilation Damper
Space Heating Loop
Space Heating Pump
Mixing
Valve Mixing Valve
AHU Fan
WAHU
HomePIC Team 9 December 2011
Figure 9. Photos Showing Ventilation and Air-Cleaning System
An indirect, flat plate collector solar hot water system was installed with a 120 gallon storage
tank to boost the inlet water temperatures to the DHW system. As shown by Figure 8, the solar
tank can only provide heating when there is a water draw (and not in the space heating mode).
VENT DUCT THOUGH SILL
VENTILATION DAMPER
ELECTRIC IONIZING AIR CLEANER IN RETURN DUCT
EXHAUST FAN IN GARAGE
HomePIC Team 10 December 2011
Figure 10. Storage Tanks for Solar Thermal System Installed in Basement
Design Summary
Table 2 compares the baseline design to the proposed design and finally to the actual, as-built
details. Table 3 summarizes the incremental costs of the implemented improvements compared
to the baseline design.
120 GALLON SOLAR HOT WATER
STORAGE TANK
HomePIC Team 11 December 2011
Table 2. Summary of Baseline, Proposed and Actual Design Details
Base Design Proposed Design As Built Details
Walls
Vinyl Siding, 1-1/2”
exterior foam, 2x6”
framing w/ Fiberglass
batts R29
Vinyl Siding, 2”Exterior
Foam, 2x6” framing w/ dense
packed cellulose R30
Vinyl Siding, 2” Exterior Foam,
2x6” framing, BIBS blown in
fiberglass R33
2nd
Floor
Knee Walls 2x4” framing w/
fiberglass batts R13
2” Exterior Foam, 2x6”
framing w/ dense packed
cellulose R30
2” Exterior Foam and Closed Cell
foam 2nd
floor to attic walls
Garage
(Exterior) Vinyl Siding, 2x6”
framing
Vinyl Siding, 2x6” framing Vinyl Siding, 2x6” framing
Attic 2x12 rafters frame with
Fiberglass batts R38
2x12 rafters frame with 16”
cellulose R49
2x12 rafters frame with blown
cellulose R60
Cathedral
Ceiling R38 Fiberglass Batts Blown Fiberglass with 2”
Exterior Foam above roof
deck R58
BIBS, Closed Cell foam, and
Exterior Foam beneath roof deck
R67
Basement
Walls 10” CMU w/ 5’ Hanging
Blown in Fiberglass R10
10” CMU, 2.5” white
Thermax R15
Superior Walls Xi Foundation
System with 2.5” Dow® Extruded
Polystyrene Insulation R15
Basement
Floor Uninsulated poured
concrete floor
2” Rigid Foam under poured
concrete floor R10
2” Rigid Foam under poured
concrete floor R10
Windows U=0.33 Low E Argon
double hung
Super Seal Windows U = 0.20 DH: Triple glazed, Low E, U = 0.22,
SHGC = 0.23
Slider: Double glazed, Low E Argon
filled, U = 0.30, SHGC = 0.20
Basement: Double glazed, Low E
Argon/air filled, U=0.28, SHGC=0.35
Rim/Band
Joists 6” Fiberglass batts w/ 1-
1/2” Ext Foam R 29
3” Closed Cell foam in Band
joists w/ 2” ext Foam R32
3” Closed Cell foam in Band joists
w/ 2” ext Foam R32
Garage-to-
house Wall 2x6 framing w/ Fiberglass
batts R19
2”Exterior Foam, 2x6”
framing w/ dense packed
cellulose R33
2” Exterior Foam, 2x6” framing,
BIBS system blown in fiberglass.
Air Tightness
& Thermal
Bypass
5 ACH50 (with basement)
2 ACH50 (with basement)
Various air sealing and
thermal bypass improvements
1.79 ACH50 with basement
(actual)
Heating/
Cooling 90% Natural Gas Furnace
13 SEER AC Unit
94% Natural Gas Furnace
13 SEER AC Unit
95% Rheem tankless water heater
and heating coil Combi System
13 SEER 2.5 ton AC unit
Ventilation Exhaust Only Ventilation HRV Fantech SH704 run 24
hours, 36 watts, 55 cfm
Fresh Air Ventilation with damper.
Honeywell Whole House
Ventilation Control.
Exhaust fan in garage
HomePIC Team 12 December 2011
Table 3. Summary of Incremental Cost Differences
Units Quanity Unit Cost Total Cost Notes
Exterior Walls
2" Dow Styrofoam Wallboard ft2 2272 1.22$ 2,780.00$ 71 Sheets (4x8)
Sill Flashing ft 133 1.10$ 146.67$ $80 in material
BIBS ft21138 1.00$ 1,138.39$
Deduct for Tyvek ft21138 0.36$ (409.82)$
Deduct for FG Batts ft21138 0.65$ (739.95)$
2,915.28$
Basement Walls and Floor
Superior Walls with 2.5" Continuous Foam ft2 1427 8.80$ 12,554.50$ Actual Cost From Invoice
Deduct for CMU Foundation ft2 1427 7.50$ (10,702.00)$ From Invoice Estimate
2" Foam Under Slab ft2 1697 1.14$ 1,931.23$
Deduct for 5' Hanging FG batt ft2 1011 0.50$ (505.34)$
3,278.40$
Rim/Band Joists, Framed Floors, Shed roofs
Closed Cell Rim/Band Joist & Shed/Floor ft2 204 3.50$ 713.62$
Other Misc Spray Foam ft2 200 3.50$ 700.00$
Deduct for FG Rim/Band/Dam Joist ft2 204 0.65$ (132.53)$
1,281.09$
Ceiling
R60 Cellulose in Attic Floor ft2 1376 1.80$ 2,476.80$
BIBS in Cathedral Ceiling ft2 460 1.00$ 460.00$
2" Exterior Foam in Cathedral Ceiling ft2 460 1.22$ 562.85$
Closed Cell Spray Foam ft2 460 3.50$ 1,610.00$
Deduct for R38 FG in Ceiling ft2 1836 1.15$ (2,111.40)$
2,998.25$
Windows
Energy Star, Triple Glazed, Low E 1 8,601.00$ 8,601.00$ From Invoice Estimate
Deduct for Estar Double Glazed 1 5,923.00$ (5,923.00)$ From Invoice Estimate
2,678.00$
Heating and Ventilation
Hybrid System w/ 95% Condensing Tankless Unit 1 13,529$ 13,529.00$ From Invoice Estimate
Deduct for 90% Efficient Gas Furnace 1 5,300$ (5,300.00)$ From Invoice Estimate
Deduct for 0.63 EF Water Heater 1 1,200$ (1,200.00)$
Garage Ventilation 1 464$ 464.00$ Actual Cost From Invoice
7,493.00$
NET Total 20,644.02$
Inverness Gardens 2 Story with Loft Costs
HomePIC Team 13 December 2011
Energy Performance
The energy use and savings predicted by REM/Rate for this house is shown in Table 4. The
heating load for the house with the proposed improvements is 37% of the baseline design and the
final, as-built design is 50% that of the baseline design.
Table 4. Summary of Energy Use and Savings
Space
Heating
(MMBtu/yr)
Peak Space
Heating
(MMBtu/h)
Fuel for Space
Heating
(MMBtu/yr)
Fuel for Water
Heating
(MMBtu/yr)
Relative
Fuel
Annual
Cost
Cost
Savings
Baseline 66.1 38.3 75.1 18.8 100% 1,409$ -$
Proposed Improvements 31.3 21.8 34.2 0.6 37% 522$ 887$
As-built Improvements 43.8 27.8 46.6 0.4 50% 705$ 704$
Inverness Gardens 2 Floor With Loft Design
The house was rated according to the Energy Star requirements. The HERS Index for the house
was 52 and the NY HERS Score was 89.6. Savings are primarily due to air tightness and added
insulation.
Thermal images, using a Fluke TiR3FT, were taken of the duplex on December 2, 2011, in the
morning before sunrise. The stud bays built into the Superior Wall panels are clearly visible
through the variation of heat transfer. Slightly more heat loss is evident at the inside corner of
the foundation wall (surface 14-15°F warmer).
Figure 11. Thermal Images Showing Foundation Wall and Slider Doors Near Deck
DOWNSPOUT
DECK JOIST
FOUNDATION INSIDE CORNER
HomePIC Team 14 December 2011
Figure 12. Thermal Image of End of Unit
The foam-to-sheathing (or OSB) transition is slightly visible from the infrared image shown
above. In Figure 13 it is apparent the model unit on the left side heated while the unfinished
unit on right side is unheated.
Figure 13. Thermal Image of Building from Front (Only Left-Side Unit is Heated)
FOAM-TO-OSB TRANSITION
HomePIC Team 15 December 2011
Figure 14. Thermal Image of Unheated Side (Foundation is slightly warmer)
Figure 15. Thermal Image of Building showing Front Door Area
HomePIC Team 16 December 2011
Figure 16. Thermal Image of Front Windows
Figure 17. Thermal Image of Both Front Door Areas
HomePIC Team 17 December 2011
Figure 18. Thermal Image of Superior Wall at Rear of Building (at center of building)
Figure 19. Thermal Image of Superior Wall (AC Unit Shown)
AIR LEAKAGE REPORT
Date: November 30, 2011 Rating No.: 0061-0206c.blg
Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.
Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757
Property: 4964 Astilbe Path Rater's Name: James E. Hammel
Address: Liverpool, NY 13088 Rater's No.: R 0061
Builder's Name: Troy Adams
Weather Site: Syracuse, NY Rating Type: Confirmed Rating
File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Whole House InfiltrationBlower door test
Heating CoolingNatural ACH: 0.13 0.11ACH @ 50 Pascals: 1.79 1.79CFM @ 25 Pascals: 714 714CFM @ 50 Pascals: 1120 1120Eff. Leakage Area: [sq.in] 61.5 61.5Specific Leakage Area: 0.00018 0.00018ELA/100 sf shell: [sq.in] 0.90 0.90
Duct Leakage Leakage to Outside Units Supply/ReturnCFM @ 25 Pascals: 25CFM25 / CFMfan: 0.0115CFM25 / CFA: 0.0104CFM per Std 152: N/ACFM per Std 152 / CFA: N/ACFM @ 50 Pascals: 39Eff. Leakage Area: [sq.in] 2.15Thermal Efficiency: N/ATotal Duct Leakage Units CFM25Total Duct Leakage: 50.00
Ventilation Mechanical: Balanced Sensible Recovery Eff. (%): 0.0 Total Recovery Eff. (%): 0.0 Rate (cfm): 115 Hours/Day: 11.0 Fan Watts: 25.0Cooling Ventilation: Natural Ventilation
ASHRAE 62.2 - 2010 Ventilation Requirements
For this home to comply with ASHRAE Standard 62.2 - 2010 Ventilation and Acceptable Indoor Air Quality in Low-RiseResidential Buildings, a minimum of 54 cfm of mechanical ventilation must be provided continuously, 24 hours per day. Alternatively, an intermittently operating mechanical ventilation system may be used if the ventilation rate is adjustedaccordingly. For example, a 108 cfm mechanical ventilation system would need to operate 12 hours per day, as long as thesystem operates to provide required average ventilation once each hour.
BUILDING FILE REPORT
File Name: 4964 Astilbe Path Liverpool M&A Homes Model Date: November 30, 2011
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Property/Builder: Rating Building Name: Duplex Model Home Org. Name: James E. Hammel, Inc.
Owner's Name: M&A Homes, Inc. Address: 21 North Street
Property Address: 4964 Astilbe Path City, St, Zip: Baldwinsville, NY 13027
City, St, Zip: Liverpool, NY 13088 Phone No: 315 638 1757
Phone No: Website:
Builder's Name: Troy Adams Rater's Name: James E. Hammel
Phone No: 315 480 9878 Rater's Email: [email protected]
Email Address: pipefish@yahoo Rater's ID: R 0061
Model: Two Story Townhouse
Development: Invernness Gardens Rating Date: 11/11/11
Rating Type: Confirmed Rating
Reason: New Home
Rating No.: 0061-0206c.blg
Registry ID:
General Building Information Area of Cond. Space(sq ft): 2415
Volume of Cond. Space: 37475
Year Built: 2011
Housing Type: Duplex, single unit
Level Type(Apartments Only): None
Floors on or Above-Grade: 2
Number of Bedrooms: 3
Foundation Type: Conditioned basement
Enclosed Crawl Space Type: N/A
Thermal Boundary Location: N/A
Foundation Wall Info: 1 2 3
Name To Garage To Ambient To Ambient
Library Type Superior Wall # 2 Superior Wall # 2 Superior Wall # 2
Length(ft) 20.0 41.5 23.2
Total Height(ft) 9.0 9.0 9.0
Depth Below Grade(ft) 7.0 4.0 7.0
Height Above Grade(ft) 2.0 5.0 2.0
Location Cond->garage/grnd Cond->ambient/grnd Cond->ambient/grnd
Uo Value (wall, airfilm, & soil) 0.070 0.081 0.070
Uo Value (wall assembly only) 0.148 0.148 0.148
BUILDING FILE REPORT
Duplex Model Home Page 2
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Foundation Wall Info: 4 5
Name To Ambient To common
Library Type Superior Wall # 2 Superior Wall # 2
Length(ft) 42.0 52.0
Total Height(ft) 9.0 9.0
Depth Below Grade(ft) 6.0 6.0
Height Above Grade(ft) 3.0 3.0
Location Cond->ambient/grnd Cond -> another cond unit
Uo Value (wall, airfilm, & soil) 0.074 0.074
Uo Value (wall assembly only) 0.148 0.148
Foundation Wall: Superior Wall # 2 Type: Solid concrete or stone
Thickness(in): 10.3
Studs: None
Interior Insulation:
Continuous R-Value: 12.5
Frame Cavity R-Value: 0.0
Cavity Insulation Grade: 1
Ins top: 0.3 ft from top of wall
Ins Bottom: 0.3 ft from bottom of wall
Exterior Insulation:
R-Value: 0.0
Ins top: 0.0 ft from top of wall
Ins bottom: 0.0 ft from bottom of wall
Note:
Slab Floor Info: 1
Name Insulated Cellar Fl
Library Type R10P
Area(sq ft) 1731
Depth Below Grade(ft) 6.0
Full Perimeter(ft) 179
Exposed Perimeter(ft) 128
On-Grade Perimeter(ft) 0
BUILDING FILE REPORT
Duplex Model Home Page 3
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Slab Floor: R10P Slab Covering Carpet
Perimeter Insulation (R-Value): 10.0
Perimeter Insulation Depth (ft): 0.3
Under-Slab Insulation (R-Value): 0.0
Under-Slab Insulation Width (ft): 0.0
Slab Insulation Grade: 1
Radiant Slab: No
Note:
Frame Floor Info: 1
Name Total
Library Type R34,LDF1,10-16
Area (sq ft) 23
Location Btwn cond & ambient
Uo Value 0.032
BUILDING FILE REPORT
Duplex Model Home Page 4
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Frame Floor: R34,LDF1,10-16Information From Quick Fill Screen:
Continous Insulation R-Value 0.0
Cavity Insulation R-Value 33.9
Cavity Insulation Thickness (in.) 9.2
Cavity Insulation Grade 1.0
Joist Size (w x h, in) 1.5 x 9.3
Joist Spacing (in oc) 16.0
Framing Factor - (default) 0.1300
Floor Covering HARDWOOD
Note:
Layers Paths
Cavity Framing GradeInside Air Film 0.920 0.920 0.920
Floor covering 0.680 0.680 0.680
Subfloor 0.820 0.820 0.820
Cavity ins 33.900 0.000 0.000
Continuous ins 0.000 0.000 0.000
Framing 0.000 11.500 0.000
0.000 0.000 0.000
Outside Air Film 0.920 0.920 0.920
Total R-Value 37.240 14.840 3.340
U-Value 0.027 0.067 0.299
Relative Area 0.870 0.130 0.000
UA 0.023 0.009 0.000
Total Component UA: 0.032
Total Component Area: 1.0
Component Uo: 0.032
BUILDING FILE REPORT
Duplex Model Home Page 5
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Rim and Band Joist: 1 2 3
Name To Garage 1 st floor Ambient Commen
Area(sq ft) 20.0 106.0 52.0
Continuous Ins 10.0 10.0 10.0
Framed Cavity Ins 24.0 24.0 24.0
Cavity Ins Thk(in) 4.0 4.0 4.0
Joist Spacing 24.0 16.0 16.0
Insulation Grade 1 1 1
Location Cond -> garage Cond -> ambient Cond -> another cond unit
Uo Value 0.031 0.032 0.032
Rim and Band Joist: 4
Name 2 nd floor Ambient
Area(sq ft) 28.0
Continuous Ins 10.0
Framed Cavity Ins 24.0
Cavity Ins Thk(in) 4.0
Joist Spacing 16.0
Insulation Grade 1
Location Cond -> ambient
Uo Value 0.032
Above-Grade Wall: 1 2 3
Name To Garage To Ambient 1st To Ambient 2nd
Library Type BIB FG1,6-24,+10Foam BIB FG1,6-24,+10Foam BIB FG1,6-24,+10Foam
Gross Area(sq ft) 180.00 960.30 290.00
Exterior Color Medium Medium Medium
Location Cond -> garage Cond -> ambient Cond -> ambient
Uo Value 0.034 0.034 0.034
Above-Grade Wall: 4 5
Name Knee Walls common
Library Type BIB.FGG,4-24,+2"Foam BIB.FGG,4-16
Gross Area(sq ft) 560.00 652.00
Exterior Color Medium Medium
Location Cond -> attic Cond -> another cond unit
Uo Value 0.042 0.079
BUILDING FILE REPORT
Duplex Model Home Page 6
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Above-Grade Wall: BIB FG1,6-24,+10FoamInformation From Quick Fill Screen:
Standard Wood Frame
Continuous Insulation (R-Value) 10.0
Frame Cavity Insulation (R-Value) 22.0
Frame Cavity Insulation Thickness (in) 5.5
Frame Cavity Insulation Grade 1
Stud Size (w x d, in) 1.5 x 5.5
Stud Spacing (in o.c.) 24.0
Framing Factor - (default) 0.1988
Gypsum Thickness (in) 0.5
Note:
Layers Paths
Cavity Framing GradeInside Air Film 0.680 0.680 0.680
Gyp board 0.450 0.450 0.450
Air Gap/Frm 0.000 0.000 0.000
Cavity ins/Frm 22.000 6.875 1.030
Continuous ins 10.000 10.000 10.000
Ext Finish 0.940 0.940 0.940
0.000 0.000 0.000
Outside Air Film 0.170 0.170 0.170
Total R-Value 34.240 19.115 13.270
U-Value 0.029 0.052 0.075
Relative Area 0.801 0.199 0.000
UA 0.023 0.010 0.000
Total Component UA: 0.034
Total Component Area: 1.0
Component Uo: 0.034
BUILDING FILE REPORT
Duplex Model Home Page 7
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Above-Grade Wall: BIB.FGG,4-24,+2"FoamInformation From Quick Fill Screen:
Standard Wood Frame
Continuous Insulation (R-Value) 10.0
Frame Cavity Insulation (R-Value) 14.0
Frame Cavity Insulation Thickness (in) 3.5
Frame Cavity Insulation Grade 1
Stud Size (w x d, in) 1.5 x 3.5
Stud Spacing (in o.c.) 24.0
Framing Factor - (default) 0.1988
Gypsum Thickness (in) 0.5
Note:
Layers Paths
Cavity Framing GradeInside Air Film 0.680 0.680 0.680
Gyp board 0.450 0.450 0.450
Air Gap/Frm 0.000 0.000 0.000
Cavity ins/Frm 14.000 4.375 1.030
Continuous ins 10.000 10.000 10.000
Ext Finish 0.940 0.940 0.940
0.000 0.000 0.000
Outside Air Film 0.170 0.170 0.170
Total R-Value 26.240 16.615 13.270
U-Value 0.038 0.060 0.075
Relative Area 0.801 0.199 0.000
UA 0.031 0.012 0.000
Total Component UA: 0.042
Total Component Area: 1.0
Component Uo: 0.042
BUILDING FILE REPORT
Duplex Model Home Page 8
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Above-Grade Wall: BIB.FGG,4-16Information From Quick Fill Screen:
Standard Wood Frame
Continuous Insulation (R-Value) 0.0
Frame Cavity Insulation (R-Value) 15.0
Frame Cavity Insulation Thickness (in) 3.5
Frame Cavity Insulation Grade 3
Stud Size (w x d, in) 1.5 x 3.5
Stud Spacing (in o.c.) 16.0
Framing Factor - (default) 0.2300
Gypsum Thickness (in) 0.5
Note:
Layers Paths
Cavity FramingInside Air Film 0.680 0.680
Gyp board 0.450 0.450
Cavity ins/Frm 15.000 4.375
Continuous ins 0.000 0.000
Ext Finish 0.940 0.940
0.000 0.000
0.000 0.000
Outside Air Film 0.170 0.170
Total R-Value 17.240 6.615
U-Value 0.058 0.151
Relative Area 0.770 0.230
UA 0.045 0.035
Total Component UA: 0.079
Total Component Area: 1.0
Component Uo: 0.079
BUILDING FILE REPORT
Duplex Model Home Page 9
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Window Information: 1 2 3
Name 1st Front 1st Rear 1st left
Library Type U:0.22, SHGC:0.25 U:0.22, SHGC:0.25 U:0.22, SHGC:0.25
U-Value 0.220 0.220 0.220
SHGC 0.250 0.250 0.250
Area(sq ft) 33.00 143.20 125.80
Orientation North South East
Overhang Depth 4.0 1.0 1.0
Overhang To Top 1.0 1.0 9.0
Overhang To Bottom 6.5 8.0 15.0
Interior Winter Shading 0.85 0.85 0.85
Interior Summer Shading 0.70 0.70 0.70
Adjacent Winter Shading Complete None Some
Adjacent Summer Shading Complete None Some
Wall Assignment AGWall 2 AGWall 2 AGWall 2
Window Information: 4 5
Name 2nd Front 2nd Left
Library Type U:0.22, SHGC:0.25 U:0.22, SHGC:0.25
U-Value 0.220 0.220
SHGC 0.250 0.250
Area(sq ft) 50.00 30.00
Orientation North East
Overhang Depth 1.0 1.0
Overhang To Top 1.0 4.0
Overhang To Bottom 6.0 9.0
Interior Winter Shading 0.85 0.85
Interior Summer Shading 0.70 0.70
Adjacent Winter Shading Complete Some
Adjacent Summer Shading Complete Some
Wall Assignment AGWall 3 AGWall 3
Window: U:0.22, SHGC:0.25 U-Value: 0.220
Solar Heat Gain Coefficient: 0.250
Note:
Door Information: 1 2
Name Front Garage
Opaque Area(sq ft) 15.0 21.0
Library Type Steel-polyurethane Steel-polyurethane
Wall Assignment AGWall 2 AGWall 1
Uo Value 0.283 0.283
BUILDING FILE REPORT
Duplex Model Home Page 10
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Door: Steel-polyurethane R-Value of Opaque Area: 2.6
Storm Door: No
Note:
Roof Information: 1 2
Name Flat ceiling Cathedral
Library Type R60,BFG20" R55, Hybred Adams******
Gross Area(sq ft) 1401.00 372.00
Color Medium Medium
Radiant Barrier No No
Type(Attic) Attic Attic
Uo Value 0.016 0.022
Clay or Cement Tiles: No No
Sub Roof Ventilation: No No
BUILDING FILE REPORT
Duplex Model Home Page 11
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Ceiling: R60,BFG20"Information From Quick Fill Screen:
Continous Insulation (R-Value) 48.0
Cavity Insulation (R-Value) 12.0
Cavity Insulation Thickness (in) 3.5
Cavity Insulation Grade 1
Gypsum Thickness (in) 0.500
Bottom Chord/Rafter Size(w x h, in) 1.5 x 3.5
Bottom Chord/Rafter Spacing (in o.c.) 24.0
Framing Factor - (default) 0.1100
Ceiling Type Attic
Note: quick-fill by MP 12/15/05
Layers Paths
Framing Cavity GradeInside Air Film 0.610 0.610 0.610
Gyp board 0.450 0.450 0.450
Cavity Ins/Frm 4.375 12.000 0.000
Continuous ins 48.000 48.000 48.000
0.000 0.000 0.000
0.000 0.000 0.000
0.000 0.000 0.000
Outside Air Film 0.610 0.610 0.610
Total R-Value 54.045 61.670 49.670
U-Value 0.019 0.016 0.020
Relative Area 0.110 0.890 0.000
UA 0.002 0.014 0.000
Total Component UA: 0.016
Total Component Area: 1.0
Component Uo: 0.016
BUILDING FILE REPORT
Duplex Model Home Page 12
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Ceiling: R55, Hybred Adams******Information From Quick Fill Screen:
Continous Insulation (R-Value) 10.0
Cavity Insulation (R-Value) 45.5
Cavity Insulation Thickness (in) 11.5
Cavity Insulation Grade 1
Gypsum Thickness (in) 0.500
Bottom Chord/Rafter Size(w x h, in) 1.5 x 7.3
Bottom Chord/Rafter Spacing (in o.c.) 16.0
Framing Factor - (default) 0.1412
Ceiling Type Attic
Note: quick-fill by MP 12/15/05
Layers Paths
Framing Cavity GradeInside Air Film 0.610 0.610 0.610
Gyp board 0.450 0.450 0.450
Cavity Ins/Frm 9.125 45.500 0.000
Continuous ins 10.000 10.000 10.000
0.000 0.000 0.000
0.000 0.000 0.000
0.000 0.000 0.000
Outside Air Film 0.610 0.610 0.610
Total R-Value 20.795 57.170 11.670
U-Value 0.048 0.017 0.086
Relative Area 0.141 0.859 0.000
UA 0.007 0.015 0.000
Total Component UA: 0.022
Total Component Area: 1.0
Component Uo: 0.022
Mechanical Equipment: General Number of Mechanical Systems: 2
Heating SetPoint(F): 68.00
Heating Setback Thermostat: Not Present
Cooling SetPoint(F): 78.00
Cooling Setup Thermostat: Not Present
BUILDING FILE REPORT
Duplex Model Home Page 13
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Intg: Int. Heat/DHW SystemType: Combined Appliance
DistributionType: Hydronic w/ air
Fuel Type: Natural gas
Rated Output Capacity (kBtuh): 100.0
Space Heating Efficiency: 0.89 CAafue
DHW Heating Efficiency: 0.89 CAef
Auxiliary Electric: 60 Watts
Note: Location: Conditioned area
Performance Adjustment: 100
% Space Heat Load Served: 100
% DHW Heat Load Served: 100
Number Of Units: 1
Cooling Equipment: ACC, 18K, 13 SEER System Type: Air conditioner
Fuel Type: Electric
Rated Output Capacity (kBtuh): 18.0
Seasonal Equipment Efficiency: 13.0 SEER
Sensible Heat Fraction (SHF): 0.70
Note: Location: Conditioned area
Performance Adjustment: 100
Percent Load Served: 100
Number Of Units: 1
BUILDING FILE REPORT
Duplex Model Home Page 14
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Duct System Information: Name Supply/Return
Heating System Int. Heat/DHW
Cooling System ACC, 18K, 13 SEER
Supply Area(sq ft) 489.0
Return Area(sq ft) 452.8
Conditioned Floor Area(sq ft) 2415.0
# of Registers 5 Duct Leakage
Qualitative Assessment - Not Applicable
Duct Leakage to Outside: 25.00 CFM @ 25 Pascals
Supply Duct Leakage - Not Applicable
Return Duct Leakage - Not Applicable
Total Duct Leakage: 50.00 CFM @ 25 Pascals
Duct Tightness Test: Rough-In Test - w/o Air Handler
Duct Information: 1 2
Type Supply Return
Percent Area 100.0 100.0
R-Value 0.0 0.0
Location Conditioned space Conditioned space
Infiltration and Mechanical VentilationWhole House Infiltration
Measurement Type: Blower door test
Heating Season Infiltration Value: 1120 CFM @ 50 Pascals
Cooling Season Infiltration Value: 1120 CFM @ 50 Pascals
Shelter Class 2
2009 IECC Verification: Tested
Mechanical Ventilation for IAQ
Type: Balanced
Rate(cfm): 115
Sensible Recovery Efficiency(%): 0.00
Total Recovery Efficiency(%): 0.00
Hours per Day: 11.00
Fan Power (watts): 25.00
Ventilation Strategy for Cooling
Cooling Season Ventilation: Natural Ventilation
BUILDING FILE REPORT
Duplex Model Home Page 15
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Lights and Appliances Simplified Audit
Oven/Range Fuel Type: Electric
Clothes Dryer Fuel Type: Natural gas
Percent Fluorescent - Pin-Based: 0.00
Percent Fluorescent - CFL: 61.00
Refrigerator KWh: 775
Dishwasher EF: 0.46
Ceiling Fan CFM / Watt: 0.00
BUILDING FILE REPORT
Duplex Model Home Page 16
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Mandatory RequirementsIECC Requirements
Verified IECC 04: false
Verified IECC 06: false
Verified IECC 09: false
Verified IECC 12: false
Verified IECC NY: true
ENERGY STAR Version 2 Checklist
Thermal Bypass Checklist: true
ENERGY STAR Products: true
ENERGY STAR Version 3 Checklists
Thermal Enclosure Checklist: false
HVAC System Quality Installation Contractor Checklist: false
HVAC System Quality Installation Rater Checklist: false
Water Management System Builder Checklist: false
Indoor airPlus Verification Checklist: false
ENERGY STAR Version 3 Appliances
Has Refrigerators: true
Number Of Refrigerators: 1
Has Ceiling Fans: false
Number Of Ceiling Fans: 0
Has Exhaust Fans: true
Number Of Exhaust Fans: 3
Has Dishwashers: true
Number Of Dishwashers: 1
ENERGY STAR Version 3 Basements
Basement Wall Area 50% Below Grade: false
Basement Floor Area: 0
Number of Basement Bedrooms: 0
Active Solar System Type: DHW & space heating
Loop Type: Liquid, indirect
Type: Double glazing, flat black
Orientation: South
Area(sq ft): 64.0
Tilt(degrees): 45.0
Volume(cu ft/gal): 120.0
FUEL SUMMARY
Date: November 30, 2011 Rating No.: 0061-0206c.blg
Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.
Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757
Property: 4964 Astilbe Path Rater's Name: James E. Hammel
Address: Liverpool, NY 13088 Rater's No.: R 0061
Builder's Name: Troy Adams
Weather Site: Syracuse, NY Rating Type: Confirmed Rating
File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Duplex Model Home
Annual Energy Cost ($/yr) Natural gas $ 601
Electric $ 1321
Annual End-Use Cost ($/yr) Heating $ 581
Cooling $ 76
Water Heating $ 4
Lights & Appliances $ 1262
Photovoltaics $ -0
Service Charges $ 408
Total $ 2331
Annual End-Use Consumption Heating (Therms) 558
Heating (kWh) 157
Cooling (kWh) 411
Water Heating (Therms) 4
Lights & Appliances (Therms) 45
Lights & Appliances (kWh) 6490
Annual Energy Demands (kW) Heating 0.1
Cooling 1.1
Water Heating (Winter Peak) 0.0
Water Heating (Summer Peak) 0.0
Lights & Appliances (Winter Peak) 0.6
Lights & Appliances (Summer Peak) 1.2
Total Winter Peak 0.6
Total Summer Peak 2.4
Utility Rates: Electricity: NIMO Elect 1/10*************0***0*******
Gas: NIMO Gas 1/10*************0***0*******
EQUIPMENT SIZING SUMMARY
Date: November 30, 2011 Rating No.: 0061-0206c.blg
Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.
Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757
Property: 4964 Astilbe Path Rater's Name: James E. Hammel
Address: Liverpool, NY 13088 Rater's No.: R 0061
Builder's Name: Troy Adams
Weather Site: Syracuse, NY Rating Type: Confirmed Rating
File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Duplex Model HomeHEATING Calculated Peak Load (kBtu/hr) 29.3 Sizing Factor (%) 100.0
HEATING EQUIPMENT CAPACITY (kBtu/hr) Required 29.3 Specified 100.0
COOLING Calculated Peak Load (kBtu/hr) 14.1 Sensible 10.6 Latent 3.5 Sizing Factor (%) 100.0
COOLING EQUIPMENT CAPACITY (kBtu/hr) Required Total 14.1 Specified Total 18.0
Required Sensible 10.59 Specified Sensible 12.60
Required Latent 3.48 Specified Latent 5.40
PERFORMANCE SUMMARY
Date: November 30, 2011 Rating No.: 0061-0206c.blg
Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.
Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757
Property: 4964 Astilbe Path Rater's Name: James E. Hammel
Address: Liverpool, NY 13088 Rater's No.: R 0061
Builder's Name: Troy Adams
Weather Site: Syracuse, NY Rating Type: Confirmed Rating
File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Duplex Model Home
Annual Load (MMBtu/yr) Heating 49.7 Cooling 5.1 Water Heating 0.3
Annual Consumption (MMBtu/yr) Heating 56.3 Cooling 1.4 Water Heating 0.4 Lights & Appliances 26.6 Photovoltaics -0.0 Total 84.8
Annual Energy Cost ($/yr) Heating $ 581 Cooling $ 76 Water Heating $ 4 Lights & Appliances $ 1262 Photovoltaics $ -0 Service Charges $ 408 Total $ 2331
Design Loads (kBtu/hr) Space Heating 29.3 Space Cooling 14.1
Utility Rates: Electricity: NIMO Elect 1/10*************0***0******* Gas: NIMO Gas 1/10*************0***0*******
PERFORMANCE SUMMARY
Date: November 30, 2011 Rating No.: 0061-0206c.blg
Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.
Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757
Property: 4964 Astilbe Path Rater's Name: James E. Hammel
Address: Liverpool, NY 13088 Rater's No.: R 0061
Builder's Name: Troy Adams
Weather Site: Syracuse, NY Rating Type: Confirmed Rating
File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
01020304050
Hea
t
Coo
l
Wat
er H
eatin
g
MMBtu/yr
Annual Load
020406080
100
Hea
ting
Coo
ling
Wat
er H
eatin
g
Ligh
ts &
App
Pho
tovo
ltaic
s
Tota
l
MMBtu/yr
Annual Consumption
0
500
1000
1500
2000
2500
Hea
ting
Coo
ling
Wat
er H
eatin
g
Ligh
ts &
App
Pho
tovo
ltaic
s
Ser
vice
Cha
rge
Tota
l
$/yr
Annual Energy Cost
Duplex Model Home
PERFORMANCE SUMMARY
Duplex Model Home Page 2
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
0
10
20
30
Spa
ce H
eatin
g
Spa
ce C
oolin
g
KBtu/Hr
Design Loads Utility Rates: Electricity: NIMO Elect 1/10*************0***0*******
Gas: NIMO Gas 1/10*************0***0*******
PERFORMANCE FACTORS
Date: November 30, 2011 Rating No.: 0061-0206c.blg
Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.
Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757
Property: 4964 Astilbe Path Rater's Name: James E. Hammel
Address: Liverpool, NY 13088 Rater's No.: R 0061
Builder's Name: Troy Adams
Weather Site: Syracuse, NY Rating Type: Confirmed Rating
File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Duplex Model Home
Normalized Loads (Btu/sf shell area/DD) Heating: 1.07 Cooling: 5.14
Normalized Consumption (kBtu/sf floor area/yr) Heating: 23.3 Cooling: 0.6 Water Heating: 0.2 Lighting: 2.3 Appliances: 8.8 Photovoltaics: -0.0 Total w/o PV: 35.1 Total: 35.1
Normalized Consumption (Btu/sf floor area/DD) Heating: 3.4 Cooling: 4.0
Normalized Costs ($/sf floor area/yr) Heating: $ 0.241 Cooling: $ 0.031 Water Heating: $ 0.002 Lighting: $ 0.124 Appliances $ 0.399 Photovoltaics $ -0.000 Total: $ 0.796
Normalized Design Loads (Btuh/sf shell area/DD) Heating: 0.0006 Cooling: 0.0141
Normalization Factors Floor Area: 2415 Shell Area: 6812 Heating Degree Days (B65): 6789 Cooling Degree Days (B74): 147
EMISSIONS REPORT
Date: November 30, 2011 Rating No.: 0061-0206c.blg
Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.
Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757
Property: 4964 Astilbe Path Rater's Name: James E. Hammel
Address: Liverpool, NY 13088 Rater's No.: R 0061
Builder's Name: Troy Adams
Weather Site: Syracuse, NY Rating Type: Confirmed Rating
File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Total Emissions
Duplex Model Home
Type of EmissionsCarbon Dioxide (CO2) - tons/year 6.4
Sulfur Dioxide (SO2) - lbs/year 17.3
Nitrogen Oxides (NOx) - lbs/year 15.4
Emissions By End-Use
Duplex Model HomeCarbon Dioxide (CO2) - tons/yearHeating 3.4Cooling 0.2Water Heating 0.0Lights & Appliances 2.8Photovoltaics 0.0
Sulfur Dioxide (SO2) - lbs/yearHeating 0.4Cooling 1.0Water Heating 0.0Lights & Appliances 15.9Photovoltaics 0.0
Nitrogen Oxide (NOx) - lbs/yearHeating 8.5Cooling 0.4Water Heating 0.1Lights & Appliances 6.5Photovoltaics 0.0
Site-to-source energy multipliers and air emission data were taken from the US EPA eGRID2007 database.
2005 EPACT ENERGY EFFICIENT HOME TAX CREDIT
Date: November 30, 2011 Rating No.: 0061-0206c.blg
Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.
Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757
Property: 4964 Astilbe Path Rater's Name: James E. Hammel
Address: Liverpool, NY 13088 Rater's No.: R 0061
Builder's Name: Troy Adams
Weather Site: Syracuse, NY Rating Type: Confirmed Rating
File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Normalized, Modified End-Use Loads (MMBtu/year)2004 IECC
50% Target As Designed
Heating: 32.9 31.6
Cooling: 6.2 4.3
Total: 39.0 35.9
Envelope Loads (MMBtu/year)2004 IECC
90% Target As Designed
Heating: 59.1 47.2
Cooling: 11.1 5.4
Total: 70.2 52.6
This home MEETS the requirements for the residential energy efficiency tax credits underSection 1332, Credit for Construction of New Energy Efficient Homes, of the Energy Policy Act of 2005.
As demonstrated above, this dwelling unit has a projected level of annual heating and cooling energy consumption that is at least 50% below theannual level of heating cooling energy consumption of a reference dwelling in the same climate zone, and the building envelope componentsimprovements alone account for at least 10% of those savings. The projected heating and cooling energy savings above have been calculated in themanner prescribed in Section 2.02 of Notice 2006-27 of the Internal Revenue Service. Field inspections of the dwelling unit performed by theundersigned eligible certifier during and after the completion of construction have confirmed that all features of the home affecting such heatingand cooling energy consumption comply with the design specifications provided to the undersigned certifier.
Building FeaturesCeiling Flat: R-60, R-56 Slab: R-10.0 Edge, R-0.0 Under
Vaulted Ceiling: NA Duct: Uninsulated
Above Grade Walls: R-32, R-24 Window: U-Value = 0.220, SHGC = 0.250
Foundation Walls: R-12.5 Integrated: Natural gas, Htg eff 0.89 CAafue. DHW eff 0.89 CAef.
Exposed Floor: R-34 Cooling: Air conditioner, Electric, 13.0 SEER.
This report provides information useful in determining whether the home qualifies for Energy Efficiency Tax Credits.It is not valid for tax purposes, as homes must be inspected and approved by a certified HERS rater in order to qualify.
ENERGY STAR VERSION 2 HOME REPORT
Date: November 30, 2011 Rating No.: 0061-0206c.blg
Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.
Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757
Property: 4964 Astilbe Path Rater's Name: James E. Hammel
Address: Liverpool, NY 13088 Rater's No.: R 0061
Builder's Name: Troy Adams
Weather Site: Syracuse, NY Rating Type: Confirmed Rating
File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Normalized, Modified End-Use Loads (MMBtu/year)ENERGY STAR As Designed
Heating: 52.6 31.6
Cooling: 9.9 4.3
Water heating: 9.9 0.1
Lighting & Appliances: 23.8 26.5
Total: 96.1 62.5
HERS Index: 80 52NY HERS Score: 84.0 89.6
ENERGY STAR Mandatory Requirements
X Thermal Bypass Inspection Checklist X ENERGY STAR Products
X Ductwork Requirements X ENERGY STAR Scoring Exceptions
This home MEETS OR EXCEEDS the energy efficiency requirements for designation as an EPA ENERGY STAR Qualified Home.
Pollution PreventedType of Emissions Reduction
Carbon Dioxide (CO2) - tons/yr 5.0
Sulfur Dioxide (SO2) - lbs/yr 4.7
Nitrogen Oxides (NOx) - lbs/yr 12.3
Energy Cost Savings ($/year)Heating: $428
Cooling: $137
Water Heating: $218
Lights & Appliances: $138
Total: $920
The energy savings and pollution prevented are calculated by comparing the Rated Home to the Reference Home as defined inthe "Mortgage Industry National Home Energy Rating Systems Standards" as promulgated by the Residential Energy ServicesNetwork (RESNET) . In accordance with these guidelines, building inputs affecting setpoints, infiltration rates, window shadingand the existence of mechanical systems may have been changed prior to calculating loads.
4964 Astilbe Path
Liverpool, NY 13088
5 Stars PlusConfirmed Rating
Rating Number: 0061-0206c.blgCertified Energy Rater: James E. Hammel
Rating Date: 11/11/11Rating Ordered For: M&A Homes, Inc.
Estimated Annual Energy CostConfirmed Rating
Use MMBtu Cost Percent Heating 54.2 $563 24%
Cooling 1.5 $79 3%
Hot Water 0.4 $4 0%
Lights/Appliances 26.5 $1253 54%
Photovoltaics -0.0 $-0 -0%
Service Charges $408 18%
Total $2307 100%
This home meets or exceeds the minimumcriteria for all of the following:
TITLECompanyAddressCity, State, ZipPhone #Fax #
Uniform Energy Rating System1 Star 1 Star Plus 2 Stars 2 Stars Plus 3 Stars 3 Stars Plus 4 Stars 4 Stars Plus 5 Stars 5 Stars Plus0-19 20-39 40-49 50-59 60-69 70-79 80-81 81-82 83-85 86-100
Energy Efficient
NY HERS Score: 89.6 / HERS Index: 52General Information
Conditioned Area: 2415 sq. ft. HouseType: Duplex, single unitConditioned Volume: 37475 cubic ft. Foundation: Conditioned basement
Bedrooms: 3Mechanical Systems Features
Integrated Htg/DHW: Natural gas, Htg eff 0.89 CAafue. DHW eff 0.89 CAef.Cooling: Air conditioner, Electric, 13.0 SEER.
Duct Leakage to Outside: 25.00 CFM.Ventilation System: Balanced: 115 cfm, 25.0 watts.
Programmable Thermostat: Heating: No Cooling: No
Building Shell FeaturesCeiling Flat: R-60, R-56 Exposed Floor: R-34
Vaulted Ceiling: NA Window Type: U:0.22, SHGC:0.25Above Grade Walls: R-32, R-24 Infiltration:
Foundation Walls: R-12.5 Rate: Htg: 1120 Clg: 1120 CFM50Slab: R-10.0 Edge, R-0.0 Under Method: Blower door test
Lights and Appliance FeaturesPercent Fluorescent Pin-Based: 0.00 Clothes Dryer Fuel: Natural gas
Percent Fluorescent CFL: 61.00 Range/Oven Fuel: ElectricRefrigerator (kWh/yr): 775.00 Ceiling Fan (cfm/Watt): 0.00
Dishwasher Energy Factor: 0.46
The Home Energy Rating Standard Disclosure for this home is available from the rating provider.
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.