![Page 1: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/1.jpg)
Filtration Standards and Applications
Arkansas Chapter of ASHRAEDecember 6 & 7, 2006
![Page 2: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/2.jpg)
Outline
Important Aspects of Particulate FiltersParticulate Filter Test StandardsLocal Codes & RequirementsApplication Summary
Discussion on Gaseous Contaminants and Gas Phase Filter Test Standards and Applications Are Saved For Another Time
![Page 3: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/3.jpg)
Why Filter?
Remove Dust, Dirt, & MicrobialsKeep Equipment & Systems Clean
Reduce Maintenance CostReduce Energy Cost
Keep the Indoor Environment CleanImprove HealthImprove Cleanliness
![Page 4: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/4.jpg)
What is This?
![Page 5: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/5.jpg)
What is That?
![Page 6: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/6.jpg)
What To Filter?
10 - 100Pollen Grain
100 100 -- 150150Human Hair (Diameter)Human Hair (Diameter)<100Dust
2 - 10Fungal & Bacteria Spores0.4 – 5Individual Bacteria0.003 – 0.06Viruses<5<5Respirable ParticlesRespirable ParticlesParticle Size (µm)Particle
Excerpted from 2005 ASHRAE Handbook – Fundamentals, Chapter 12
![Page 7: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/7.jpg)
Filtration Methods
StrainingInertial ImpingementInterceptionDiffusionElectrostatic
All Methods Are Used in Capturing Particles in Most Filters; However, Filters are Typically Designed with a Dominant Method
![Page 8: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/8.jpg)
Straining
• The Particle is Larger Than the Opening Between Media Fibers
• A Dominant Method of Particulate Removal in Low Efficiency Air Filters (Pleated Prefilters)
![Page 9: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/9.jpg)
Inertial Impingement
• A Large, Dense Particle Collides with the Fibers and Attaches to the Media
• Adhesives or Tackifiers Can Be Used to Enhance Capture Efficiency
• A Dominant Method of Particulate Removal in Low Efficiency Air Filters (Flat Panel Prefilters)
![Page 10: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/10.jpg)
Interception
• Particle Follows Airstream at Lower Velocities and Contacts Fiber Through Weak Intermolecular attractions (Van Der Waals Forces)
• The Dominant Method of Particulate Removal in Medium Efficiency Air Filters (Bags and Extended Surface Final Filters)
![Page 11: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/11.jpg)
Diffusion
• Small Particles Collide with the Air Molecules and Move in An Erratic Path (Brownian Movement) and Attaches to the Media Fibers
• The Dominant Method of Particulate Removal in High Efficiency Air Filters (HEPA Filters)
![Page 12: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/12.jpg)
Electrostatic Effects
• An Electrostatic Charge Is applied to the Fiber that Can Produce an Attracting Force if the Particle is of Opposite Charge
• Passive (One-Time, Initial) and Regenerative Charges
• The Dominant Method of Particulate Removal in Metal Panel Prefilters and Some Room Purifiers
![Page 13: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/13.jpg)
Effects of Filtering
Restricts AirflowAdded Pressure Drop Requires Energy
Requires Space and CostRequires Additional Equipment / FramesReplacement Additional Maintenance
![Page 14: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/14.jpg)
Is It Worth It?
“60% of the Service Calls on Air Conditioning Units Could Be Reduced if the Dirt Was Removed From the Airstream Before The Components.”
![Page 15: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/15.jpg)
How to Value DifferencesDust Removal Efficiency
The Percentage of Airborne Particulate the Filter Will Remove (ASHRAE Standards 52.1 and 52.2 Handle this Differently and Both are Applicable)
Dust Holding CapacityThe Amount of Dust the Filter Will Hold To a Maximum Resistance Value (ASHRAE Standard 52.1 Only)
Filter ResistanceAs a Function of Airflow & Dust Load
![Page 16: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/16.jpg)
Test Standards
Particulate Filter Test StandardsASHRAE Standard 52.1 - 1992ASHRAE Standard 52.2 – 1999UL Standard 900 (Flammability)US Military Standard MIL-STD-282 DOP Method for HEPA FiltersInternational (CEN EN 779:1993, Others)
![Page 17: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/17.jpg)
ASHRAE Standard 52.1 - 1992
Atmospheric Dust Spot Efficiency TestASHRAE Dust Weight Arrestance TestASHRAE Dust Holding Capacity Test
![Page 18: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/18.jpg)
Atmospheric Dust Spot Efficiency Test
The Dust Spot Test Measures the Ability of a Filter to Reduce Soiling of Fabrics and Building Interior Surfaces using Unconditioned Outside AirVariety and Variability of Atmospheric Dust May Cause the Same Filter to Test at Different Dust Spot Efficiencies at Different Locations
![Page 19: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/19.jpg)
ASHRAE Standard 52.1 – 1992Test Apparatus
![Page 20: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/20.jpg)
ASHRAE Dust Weight Arrestance Test
The ASHRAE Dust Weight Arrestance Test Measures The Amount of Dust (By Weight Fraction) The Filter Will CaptureRequires High Degree of Standardization of Testing ApparatusMore Suited for Low to Medium Efficiency Air Filters
![Page 21: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/21.jpg)
ASHRAE Dust Holding Capacity Test
Measured Amounts of ASHRAE Dust are Used to Artificially Load the Filters in Hours and Not MonthsASHRAE Dust is Not Atmospheric Dust; So, Results May Vary Greatly in Actual Installations
![Page 22: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/22.jpg)
ASHRAE Standard 52.1 Actual Test Report Excerpt
![Page 23: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/23.jpg)
Why a 52.2?
Needed a Means to Measure Removal Efficiency by Particle SizeNeeded more Mandatory (Code) LanguageNeeded More Reliable and Verifiable Results
![Page 24: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/24.jpg)
ASHRAE Standard 52.2 – 1999Test Apparatus
![Page 25: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/25.jpg)
ASHRAE Standard 52.2 - 1999
Twelve (12) Ranges of Particle Counts are Taken Over a Range of Particles Six (6) Times for a Total of Seventy Two (72) Data PointsFor Each Measurement, the Filtration Efficiency is Stated as a Ratio of Downstream-to-Upstream Particle Count
![Page 26: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/26.jpg)
Result? MERV
The Lowest Values then Determine the Composite Minimum Efficiency Curve
![Page 27: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/27.jpg)
This Table Excerpted from ASHRAE Standard 52.2 - 1999
![Page 28: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/28.jpg)
This Table Excerpted from ASHRAE Standard 52.2 - 1999
![Page 29: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/29.jpg)
52.1 and 52.2 Coexist52.1
Used for MERV 1-4 filtersMany Local Standards Reference 52.1 and Dust Spot Efficiency TestsDust Holding Capacity Has Merit
52.2Gaining PopularitySome Manufacturers Test New Products Only Using 52.2Table E-1 is a Good Crossover Reference ChartNow You Have Met MERV
![Page 30: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/30.jpg)
Next Steps for Filter TestingASHRAE Standard 52.2
Addendum A: Reference Filter Check; (Approved and Included)Addendum B: Incorporating Elements of 52.1 Into 52.2 (Waiting for More Data…)Addendum C: Conditioning Step (Waiting for More Data…)
Global Standards for Filter Testing (ISO)?ASHRAE Journal Article, August, 2006, Page 58
![Page 31: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/31.jpg)
UL Standard 900
The UL 900 Standard is Designed to Determine Combustibility and the Amount of Smoke Generated for Air Filter Units Under Test A Methane Flame is Ignited on the Upwind Side of the Filter, Resulting in a Direct Flame Against the Filter, Which is Maintained For Three (3) Minutes
![Page 32: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/32.jpg)
UL Standard 900 (Cont.)
Class 1 Air FiltersNo Flames or Sparks May Pass Through the Filter and Only a Small Amount of Smoke Can Be Generated
Class 2 Air FiltersLimited Flaming and Sparking are Acceptable and a Larger Amount of Smoke May be Generated
![Page 33: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/33.jpg)
US Military Standard MIL-STD-282 For HEPA Filters
Reserved For a Later Date
![Page 34: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/34.jpg)
Codes and Requirements2003 Arkansas Mechanical Code2005 Arkansas Hospital Rules & RegulationsAmerican Institute of Architects (AIA) Guidelines for Design and Construction of Health Care FacilitiesJoint Commission: A Guide To Managing Indoor Air Quality in Health Care OrganizationASHRAE Standard 62.1 - 2004Proposed ASHRAE Standards 170P & 180P
![Page 35: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/35.jpg)
2003 Arkansas Mechanical Code
Section 605 Air Filters Requires:Heating and Air Conditioning Equipment to be Provided with Approved Air FiltersFilters to Be Installed in the Return Air System, Upstream of Any Heat Exchanger or CoilFilters to be Listed and Labeled
![Page 36: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/36.jpg)
2005 Arkansas Hospital Rules and Regulations
References ASHRAE Standard 52.1 Values & AIA Guidelines for Design and Construction of Health Care Facilities
![Page 37: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/37.jpg)
This Table Excerpted from Section 74, 2005 Rules and Regulations for Hospitals and Related Institutions in Arkansas
![Page 38: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/38.jpg)
AIA Guidelines for Design and Construction of Health Care Facilities
References ASHRAE Standard 52.1Requires a Manometer across each filter Bed Having a Required Efficiency of 75% or moreFor Individual Room Units, a Minimum of 68% Weight Arrestance Filters Are to Be Used (ASHRAE 52.1)
This Table Excerpted from Section 7.31 of the 2001 Edition of AIA Guidelines for Design and Construction of Health Care Facilities
![Page 39: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/39.jpg)
NFPA Standard 90ARequires Filters To be Renewed or Cleaned when the Resistance to Airflow has Increased to Two Times the Original Resistance or When the Resistance Has Reached a Value of Recommended Replacement by the Manufacturer.…Avoid Gaps Between Filter Sections,
This Information Excerpted from Annex B: Maintenance of the 2002Edition of NFPA Standard 90A
![Page 40: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/40.jpg)
Joint Commission: A Guide To Managing Indoor Air Quality in Health Care Organization
Composite Filter Banks with a Final Filter Efficiency of at Least 95% Removal of Particles of 1 Micron Size is the Critical Quality TargetDoes This Contradict Current 2005 Arkansas Hospital Rules and Regulations?
This Information Excerpted from A Guide To Managing Indoor Air Quality in Health Care Organization, 1997
![Page 41: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/41.jpg)
ASHRAE Standard 62.1-2004Section 5.9 States That the Minimum of a MERV 6 Filter Must Be Used and It Should Be Located Upstream of Cooling Coils and Wetted SurfacesSection 7.1 States That During Construction Measures Should be Taken to Prevent Construction-Generated Contaminants From Spreading to Occupied Spaces
![Page 42: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/42.jpg)
Proposed ASHRAE Standards 170P and 180P
170P: Ventilation of Health Care Facilities
180P: Standard Practice for Inspection and Maintenance of Commercial Building HVAC Systems
![Page 43: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/43.jpg)
Application – Apply Right Filter
Minimum MERV 6 Prefilter Rating In Non-Health Care SettingsMinimum MERV 8 Prefilter Rating In Health Care Settings
![Page 44: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/44.jpg)
Application - System Efficiency
System Efficiency Starts With the Frame / Housing
![Page 45: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/45.jpg)
Application – System Efficiency (Cont.)
System Efficiency Continues With Eliminating Bypass
![Page 46: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/46.jpg)
Application – System Efficiency (Cont.)
![Page 47: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/47.jpg)
Application – Consider New Technology
![Page 48: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/48.jpg)
Questions?
![Page 49: Filtration Standards and Applications - ASHRAE …arkansasashrae.org/images/downloads/Meeting_Notes/dec...AIA Guidelines for Design and Construction of Health Care Facilities References](https://reader030.fdocuments.us/reader030/viewer/2022021704/5b2c56ca7f8b9abe2a8befea/html5/thumbnails/49.jpg)