FIL SP TH in Rev 00- 06_08
-
Upload
jvaldivie1 -
Category
Documents
-
view
22 -
download
3
Transcript of FIL SP TH in Rev 00- 06_08
![Page 1: FIL SP TH in Rev 00- 06_08](https://reader035.fdocuments.us/reader035/viewer/2022081816/552b44db550346ef478b464b/html5/thumbnails/1.jpg)
∗ = MPA NRW 550035 0 89-03 550035 0 89-05 # = test report RNE – CETIAT N° 920393/6 A 920393/6 B 920393/6 C
Tecnologie di Filtrazione s TECHNICAL CHARACTERISTICS MEDIA = Glass fibre paper SEPARATORS = Hot melt gluing. SEALANT = Two components cold moulded polyurethane. FRAME = Full plastics. EFFICIENCY ∗ #
CODE EUROVENT 4/5 CLASSIFICATION
AVERAGE EFFICIENCY, Em % 0,4µm CEN - EN 779
EN 779 CLASSIFICATION
TH EU9 95 ≤ Em F9 WORKING TEMPERATURE = 80°C RELATIVE HUMIDITY = 90% max. FIRE RESISTANCE = This filter can be incinerated without the emission
of toxic gases and dust in town incinerators. SPECIAL MODELS = Final code : _ _ 2 R = Two side protective grids version
Final code : _ _ 0 G = Eight grids version
Neoprene gasket version on request
FIL SP RIGID POCKETS TH
TYPICAL APPLICATIONS
High efficiency air filtration in reduced dimensions and high flow filtering units applications Thanks to its construction and high filtering surface, the ERISFIL filters have a longer clogging time than standard flat pockets, moreover there is no risk of loss of clogged dusts, as well as glass fibres.
ADVANTAGES
Strong and rigid construction that permits an easy and quick installation.
Compact project with reduced volume (292 mm width, 25 mm flange)
High filtering surface and long clogging time.
Increasing efficiency during the utilisation.
![Page 2: FIL SP TH in Rev 00- 06_08](https://reader035.fdocuments.us/reader035/viewer/2022081816/552b44db550346ef478b464b/html5/thumbnails/2.jpg)
L
D
W25
FIL
SP T
H
Pressure drop as a function of the air flow rate (clean device)
0255075
100125150175200225250275
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500Air flow rate (m3/s)
Pres
sure
dro
p (P
a)
SP30 SP29 SP32SP31
CODE Dimensions W x L x D
Flow rate
Filtering surface
Initial pressure drop Volume Weight
mm m3/h m2 Pa m3 kg
SP 29 TH 00 402 x 593 x 292 3300 11,80 230 0,084 4,00
SP 30 TH 00 288 x 593 x 292 2250 8,5 230 0,060 3,15
SP 31 TH 00 491 x 593 x 292 4100 14,5 230 0,102 4,50
SP 32 TH 00 593 x 593 x 292 5000 18,0 230 0,123 5,50
Recommended final pressure drop ≤ 600 Pa Maximum final pressure drop ≤ 1000 Pa
Subject to change without prior notice
Freudenberg Tecnologie di Filtrazione
20017 Mazzo di Rho (MI) Italy – Via Risorgimento, 34 – Tel 0039 02 9346681 – Fax 0039 02 93904394 UNI EN ISO 9001 – 2000 N° 156/05