Fieldbus Solutions With PCS 7 and PROFINET

84
© Siemens AG 2014. All Rights Reserved. Fieldbus Solutions with PCS 7

description

Field bus

Transcript of Fieldbus Solutions With PCS 7 and PROFINET

  • Siemens AG 2014. All Rights Reserved.

    Fieldbus Solutions with PCS 7

  • Siemens AG 2014. All Rights Reserved.

    PROFINET

    FOUNDATION Fieldbus

    PROFIBUS PA

    Active Field Distributor

    PROFIBUS DP

    Fieldbus Solutions with PCS 7

  • Siemens AG 2014. All Rights Reserved.

    Fieldbus Solutions with PCS 7

    PROFIBUS DP

    System bus and open communication system

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 4 2014-08-13 Thomas Bartsch

    Fieldbus solutions with SIMATIC PCS 7

    PROFIBUS supports:

    HART communication

    Fail-safe technology (PROFIsafe)

    Drive integration (PROFIdrive)

    Device profiles

    And much more

    PROFIBUS is the No. 1 field bus system in the world

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 5 2014-08-13 Thomas Bartsch

    Fieldbus solutions with SIMATIC PCS 7

    Untertitel

    Text erste Ebene

    Text zweite Ebene

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 6 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    Fieldbus solutions with SIMATIC PCS 7

    PROFIBUS DP

    System bus of PCS 7 and open communication system

    Link between PCS 7 and PROFIBUS PA and FOUNDATION Fieldbus

    Connects field devices, process instruments, drives, pumps, remote I/O and analyzers

    PROFIsafe integrates safety functionality

    Supports HART protocol

    Installed base of almost 43 million nodes

    Used for more than 10 years already

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 7 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    Technical Overview

    PR

    OF

    IBU

    S D

    P

    S7-400

    Fiber optic

    OLM

    RS485

    (Diagnose)

    Repeater

    Coupler RS485iS

    PA/FF Link

    RS485

    > 100km

    Max. 1,000 m

    PA / FF H1

    Max. 125 DP slaves per single PROFIBUS DP master system

    Electrical networks can be extended with repeaters (segments)

    max. 31 DP slaves per segment

    OLMs (Optical Link Module) for long distances, also provide

    greater EMC stability

    RS485iS coupler for PROFIBUS DP in hazardous areas

    Copper with RS485 and fiber optic use the same communication

    protocol

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 8 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    Physical Properties

    PROFIBUS DP

    Physical-

    Layer Application

    max. segment length

    @ Baud rate

    PROFIBUS

    DP RS 485

    Remote IO

    Intelligent drives

    Intelligent field devices

    1200 m @ 10,000m @ 12 Mbps

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 9 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    PROFIBUS DP development steps

    Functionality

    Cyclic data exchange Diagnostics

    Extensions:

    Acyclic data exchange Alarms

    Extensions:

    Peer slave communication (Publisher/Subscriber) Isochronous mode (equidistance) Time-of-day management and time stamping Upload and download

    DP-V0

    DP-V1

    DP-V2

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 10 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    Central access to all connected devices

    PROFIBUS PA

    M

    PROFIBUS DP

    ES OS

  • Siemens AG 2014. All Rights Reserved.

    PROFINET

    FOUNDATION Fieldbus

    PROFIBUS PA

    Active Field Distributor

    PROFIBUS DP

    Fieldbus Solutions with PCS 7

  • Siemens AG 2014. All Rights Reserved.

    Fieldbus Solutions with PCS 7

    AFD

    Active Field Distributor

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 13 2014-08-13 Thomas Bartsch

    Active field distributors

    Increasing availability

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 14 2014-08-13 Thomas Bartsch

    Automatic bus termination enables

    unique online changeability

    Add new devices

    PROFIBUS PA / FOUNDATION Fieldbus Automatic bus termination

    AFD

    Bus termination

    Enhance line

    Enhance ring M

    There is no need to reserve spare ports of the AFDs !

    AFD AFD AFD AFD

    DP Link / FF Link

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 15 2014-08-13 Thomas Bartsch

    Architectures with Active Field Distributor

    Line architecture

    Automatic bus termination by the last AFD

    Line architecture with redundant couplers

    AFS connects a bus line segment to two feeding

    field device coupler FDC 157

    Ring architecture with bus coupler and media

    redundancy

    Advantages

    Automatic bus termination

    Ease and safe installation

    Reduce unplanned plant downtimes

    Extendable and repairable during operation

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 16 2014-08-13 Thomas Bartsch

    Revised version of 4 channel field distributor with automatic bus termination

    Active Field Distributor for PROFIBUS PA & FF-H1

    PR

    OF

    IBU

    S P

    A /

    FF

    -H1

    8 channel version for most competitive channel price

    6 channel field barrier for intrinsically safe applications

    New Mechanical Design

    Bigger connectors (M12 M16)

    All connectors relocated to bottom side

    Screw terminal instead of spring terminal

    AFD8 (01/2013)

    (6ES71570AG820XA0)

    AFDiS

    (6ES71570AG830XA0)

    AFD4 (01/2013)

    (6ES71570AG810XA0)

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 17 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    Active Field Distributor

    Comparison

    Current version New product line

    Feature AFS AFD AFS

    (redesign)

    AFD4

    01 / 2013

    AFD8

    01/2013 AFDiS

    Spurs 4 4 8 6

    Direct grounding l l l l l l

    Grounding bar l l l l

    Automatic bus termination l l l l

    Coupler redundancy l l l l l l

    Ring redundancy l l l l

    Short-circuit-proof spurs 60mA 60mA 60mA 40mA / 60mA

    Electronic chatter suppression l l l

    Status LEDs l l l l l l

    Trunk cover with auto switch-off l l l

    Degree of protection IP65 IP65 IP66 IP66 IP66 IP66

    Operating temperature range - 25 70 - 25 70 - 40 70 - 40 70 - 40 70 - 40 70

    Approved for hazardous area

    (Device / Spurs) zone 2 / Ex e zone 2 / Ex e zone 2 / Ex ic zone 2 / Ex ic zone 1 / Ex ia

    Integrated repeater l

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 18 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    SIMATIC Fieldbus Calculator

    Planning of Fieldbus Segments

    PROFIBUS PA

    FOUNDATION Fieldbus H1

    http://support.automation.siemens.com/WW/view/en/53842953

  • Siemens AG 2014. All Rights Reserved.

    PROFINET

    FOUNDATION Fieldbus

    PROFIBUS PA

    Active Field Distributor

    PROFIBUS DP

    Fieldbus Solutions with PCS 7

  • Siemens AG 2014. All Rights Reserved.

    Fieldbus Solutions with PCS 7

    PROFIBUS PA

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 21 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    PROFIBUS PA

    Overview

    PROFIBUS DP

    PROFIBUS PA (Ex)

    PROFIBUS PA 31 devices

    64

    devices

    9 devices

    123 devices

    Max. 7872 Devices

    DP Interface module IM153-2 (12Mbps to 31.25 kbps)

    Slave on PROFIBUS DP (one address), Master on PROFIBUS PA

    Can be used redundant (H-System)

    Max.. 244 bytes of I/O data (1 AI Value = 5 Byte)

    Up to 64 PA devices

    DP/PA coupler for PROFIBUS PA segment

    Integrated Power supply - (Ex Option: Class 1, Div. 1, ZONE 0)

    Up to 31 (9 Ex) PA devices

    Max 5 couplers per link

    Total number of devices on one PROFIBUS Master system

    Up to 123 DP Slaves

    DP/PA Link is one DP Slave -> 123 x 64 = max. 7872 PA devices

    DP/PA Link

    Interface module

    IM153-2

    DP/PA coupler

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 22 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    PROFIBUS PA features

    Cost and space savings

    Less instruments using multivariable devices

    Less wiring

    Less I/O cards

    Less controller logic

    420mA PROFIBUS PA

    PROFIBUS PA

    420mA

    Digital

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 23 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    PROFIBUS PA features

    Free choice of devices due to open standard

    Interchangeability

    Devices can be operated in device manufacturer independent

    mode according PA Profiles e.g.

    counting

    pressure

    flow

    level

    Interoperability

    Universal device description independent from DCS or device

    manufacturer GSD

    EDD

    Download from

    manufacturer parameterize

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 24 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    PROFIBUS PA features

    Conventional 420mA

    technology

    P A D 420mA D

    A

    0...50 bar 0...10 bar A

    D

    PROFIBUS PA

    PA-

    Interface

    PROFIBUS PA

    A D

    P 8.928

    0...50 bar

    8.9

    0...10 bar

    Higher Accuracy

    Less conversions

    32 bit resolution, digital transmission

    No application specific measuring ranges

    8.928

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 25 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    PROFIBUS PA features

    Central configuration, parameterization and diagnostics

    PROFIBUS PA

    M

    PROFIBUS DP

    OS ES

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 26 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    Seamless integration into PCS 7 asset management

    Detailed diagnostics

    via device manager

    Available views:

    I&M Alarm Diagnostic Parameters Change Report Maintenance

    Asset

    Management

    IH alarm

    IH warning

    IH requirement

    Out of order

    Status unknown

    passivated

    Replacement value

    Operator reaction

    Device status OK

    Simulation

    Config. changed

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 27 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    15ms

    Acyclic

    20ms

    10ms 15ms

    10ms

    10ms

    0,5ms

    0,5ms

    cyclic

    80 msec

    2 msec 0,5ms 0,5ms

    acyclic

    Engineering

    Station

    PROFIBUS PA 31,25 kBit/s

    PROFIBUS DP up to 12 MBit/s

    ES

    Industrial Ethernet

    S7 41x

    SIMATIC PDM

    PROFIBUS PA features

    High performance for fast control loops

    Simple calculation formula for PROFIBUS PA

    cycle time = app. 10 ms x number of devices

    + 1.3 ms (for each additional cyclic value)

    + 10 to 20ms (for acyclic class-2 master services)

    DP/PA Link

    DP up-link PA

    Coupler

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 28 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    PROFIBUS PA features

    Process safety support with PROFISafe

    IEC 61508/11:

    The whole communication path to the field device is failsafe now!

    No fail-safe-I/Os required, less cabling

    420 mA

    PROFIsafe on PROFIBUS DP

    S7 41x F_PA_DI

    F_PA_AI

    PROFIsafe on PROFIBUS DP and PA

    S7 41x

    DP/PA-Link ET200M

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 29 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    Conventional setup for high available and fail-safe applications

    PR

    OF

    IBU

    S D

    P

    High available and fail-safe

    measurement (e.g. 2 out of 3)

    Safe communication up to the I/O card

    Safety and high availability requires multiple I/O cards

    2oo3

    F-Remote I/O

    Todays architecture

    S7 41x HF

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 30 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    Cost saving architecture for high available and fail-safe applications

    PR

    OF

    IBU

    S D

    P

    2oo3

    1oo2

    DP/PA Link, redundant

    Safe communication down to the field device

    Safety and high availability on one segment

    Allows combination of standard and PROFISafe devices

    Tomorrows architecture S7 41x HF

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 31 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    PROFIBUS PA enables

    Fast and easy installation because of bus-powering and automatic bus termination

    Prevention of unexpected plant downtimes due to scalable redundancy concept

    Early fault recognition and preventive maintenance due to enhanced diagnostics and asset management

    support

    Cost- and space saving configurations as a real alternative to conventional technologies (4 20mA,

    HART, fail-safe etc.)

    Complete hardware configuration change in run without production downtimes (including modifications on

    trunk line)

    PROFIBUS and PROFIBUS PA are state-of-the-art and fit for the future

  • Siemens AG 2014. All Rights Reserved.

    PROFINET

    FOUNDATION Fieldbus

    PROFIBUS PA

    Active Field Distributor

    PROFIBUS DP

    Fieldbus Solutions with PCS 7

  • Siemens AG 2014. All Rights Reserved.

    Fieldbus Solutions with PCS 7

    FOUNDATION Fieldbus

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 34 2014-08-13 Thomas Bartsch

    FOUNDATION Fieldbus

    Seamless system integration (such as PROFIBUS PA, HART, I/O) via high speed system backbone

    Central configuration & parameterization

    Complete asset management support via PCS 7 Maintenance Station / PDM

    H.I.S.T (Host Interoperability Test) certified Host according FF-569

    Device tag & address assignment

    Configuration of Link Master devices

    Block tag configuration

    Standard & enhanced Blocks

    Function block linkage configuration

    Device description service

    Control In The Field

    Redundancy on all levels

    Redundant controller

    Redundant backbone

    Redundant linking device / Link Master

    FF-H1 coupler / ring redundancy

    AS 41x HF

    PR

    OF

    IBU

    S D

    P S

    yste

    m b

    ackb

    on

    e

    ET200iSP

    ET200M HF

    PROFIBUS PA

    Engineering

    Station

    Maintenance /

    OS Server

    Multi Client

    Drives

    PA Link

    FF Link

    FOUNDATION Fieldbus

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 35 2014-08-13 Thomas Bartsch

    FF Link

    PA Link

    Linking device hardware platform

    IM 153-2

    DP Link

    +

    Field Device Coupler

    FDC 157

    DP Slave PA Master

    Manchester encoding Bus powering

    IM 153-2 FF

    FF Link

    +

    DP Slave FF Link Master

    Manchester encoding Bus powering

    FF Stack

    The FF Linking device is based on the same hardware

    platform as the well proven SIMATIC PA Link

    Link = IM153-2 + Field Device Coupler

    Field Device Coupler

    FDC 157

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 36 2014-08-13 Thomas Bartsch

    FF Link quantity structures

    Property Value / Comment

    Links per DP master system 123 (typ. 30 to 40)

    Link Master per link 1 LAS (1 backup link master in redundant configuration)

    Segments per link 1

    I/O channels per link 40AI, 40AO, 40DI, 40DO

    I/O data per link 244 bytes input / 244 bytes output (AI,AO = 5 bytes, DI/DO = 2 bytes)

    Bus power per segment 1000 mA at 30V

    Devices per segment 31 (typ. 8 to 10 due to FF cycle time)

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 37 2014-08-13 Thomas Bartsch

    No 3rd party components required

    FOUNDATION

    Fieldbus - H1

    M

    SIMATIC FF Link

    Power conditioner FF-H1 Link Master

    Field Devices

    SIMATIC NET

    FF-H1 type A cable

    (yellow and blue)

    Active Field Distributor

    (junction box with

    automatic bus termination)

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 38 2014-08-13 Thomas Bartsch

    Hardware configuration workflow

    Add & configure

    Configure FF Link

    2

    Add & configure devices 3 Import additional DDs

    via PDM

    Device Integration

    Manager

    1

    Connect device I/O data

    to process image of

    controller

    4

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 39 2014-08-13 Thomas Bartsch

    APL fieldbus channel drivers

    Connect process image with application via

    generic fieldbus channel

    driver included in

    PCS 7 APL

    FbAnIn

    FbAnOu

    FbDiIn

    FbDiOu

    Module drivers can be generated automatically

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 40 2014-08-13 Thomas Bartsch

    FF-blocks connected to process image are automatically managed by the system

    In addition FF-blocks can be manually interconnected to establish Control In The

    Field loops (PDM Connection Editor)

    FF communication schedule generation

    FOUNDATION Fieldbus H1

    PID_1

    BKCAL_IN

    IN

    AI_1

    OUT

    AO_1

    CAS_IN

    BKCAL_OUT

    OUT OUT

    AI

    PID AO

    Macro cycle

    Additional devices

    configured for

    cyclic data exchange

    with the controllers process image

    3 1 2 31

    30

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 41 2014-08-13 Thomas Bartsch

    Fieldbus parameter settings

    Automatic or

    custom settings

    Retry Factor

    Timing settings for

    address and device tag

    change procedure

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 42 2014-08-13 Thomas Bartsch

    Schedule and macro cycle are

    automatically determined by the system

    according the following conditions:

    Interconnections (process image and

    CIF)

    Device type specific timings

    Fieldbus communication parameters

    settings

    User defined conditions (max cycle time,

    ratio between cyclic and acyclic

    communication)

    Macrocycle configuration

    Macro cycle

    (400 ms)

    Acyclic portion

    (70% = 280ms)

    Reserve

    (64ms)

    Cyclic

    communication

    (56ms)

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 43 2014-08-13 Thomas Bartsch

    Link master assignment

    Control In The Field applications keep on running without controller or linking device !

    DP/FF-Link is implicitly loaded as primary link master at default

    Master IM153-2 is Link Active Scheduler (LAS)

    Standby IM153-2 is backup LM (in redundant configuration)

    Optionally, field devices can be assigned to be backup link master as well

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 44 2014-08-13 Thomas Bartsch

    Online views

    Maintenance

    Station

    PDM

    Complete Device Management support via

    SIMATIC PDM

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 45 2014-08-13 Thomas Bartsch

    Software Package

    PCS 7 V8.0 Update 1 or higher

    PDM V8.0 Servicepack 1 or higher

    FF Communication is now integrated into PDM

    Universal Solution for FF and PROFIBUS PA

  • Siemens AG 2014. All Rights Reserved.

    PROFINET

    FOUNDATION Fieldbus

    PROFIBUS PA

    Active Field Distributor

    PROFIBUS DP

    Fieldbus Solutions with PCS 7

  • Siemens AG 2014. All Rights Reserved.

    Fieldbus Solutions with PCS 7

    PROFINET

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 48 2014-08-13 Thomas Bartsch

    Installation Base of PROFINET

    Over 5.9 Mio nodes are already installed

    Controller

    Remote IO

    Drives

    Displays

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 49 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    Imagine: a PROFIBUS installation with

    a higher availability

    a higher scalability of the redundancy

    PROFINET has the answers to all these requirements!

    more than one master in the network

    Webserver functionality

    electrical ring installation

    more than 126 connections / devices on the same network

    graphic visualization and automatic identification of the topology

    complete commissioning with automatic addressing and naming

    easy and fast device exchange

    100% investment protection for the future by integration of existing fieldbus technologies (proxy technology)

    flexible topologies, which follows the installation of your plant (Line, Star, Tree and Ring)

    very high data rate over high distances without need of separate repeaters

    big data rates (e.g. data base, pictures, printer, webcam) over the same cable

    wireless communication (also high available)

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 50 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    PROFINET in Process Automation

    Architectures

    Topologies

    Line

    Ring

    Tree

    Mixed

    Media and cable length

    Copper

    max. 100m between two devices

    Fiber optics

    50 m 16 km

    Wireless

    Industrial WLAN (IEEE 802.11)

    Bluetooth (IEEE 802.15.2)

    Ringstruktur

    Linienstruktur

    Baumstruktur

    Sternstruktur

    Wireless

    Glas/POF

    PROFINET

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 51 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    Comparison of the addressing

    Individual and manual

    addressing of each

    station

    Easy addressing by controller

    with support of engineering

    system

    Automatic detection of the

    topology

    Visualization of the topology Easy device exchange

    Fast commissioning

    Prevention of address conflicts

    Automatic addressing of the station by the controller

    Engineering of stations by the engineering station

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 52 2014-08-13 Thomas Bartsch

    Standardization

    Key features of PROFINET in the Process Automation

    Configuration in Run (CiR)

    DCS

    Remote I/O Proxy

    Time synchronization & stamping System Master Clock

    (GPS, DCF77, )

    Controller 1 Controller 2 Controller 3

    Proxy

    Device Device

    Backup

    Clock Master

    PROFINET IO System Redundancy

    Redundant Controller

    Primary Backup

    Redundant Network

    Device with

    redundant

    connectivity

    Device with

    singular

    connectivity

    Complete fieldbus integration

    DCS

    HART

    PROFIBUS PA

    FF H1

    PROFIBUS DP

    DeviceNet

    PROFINET

    Already standardized

    System Redundancy

    Released

    Released

    In PI Review PNIO Media Redundancy

    Released Sept. 2012

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 53 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    Integration of existing fieldbus technologies

    DCS

    PROFIBUS PA

    FF H1

    PROFIBUS DP

    PROFINET

    HART

    AS-Interface

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 54 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    Integration of PROFIBUS-DP in PROFINET

    Proxy

    PROFINET

    PROFIBUS DP Transparent communication

    between PROFINET und PROFIBUS-DP

    IE/PB Link (Proxy) represents the

    PROFIBUS-Devices on PROFINET at a single

    controller

    The IE/PB Link is a PROFINET device on

    Ethernet and DP-Master on PROFIBUS

    Cyclic and acyclic communication

    100% Investment protection for the future

    Step-by-step from PROFIBUS DP to

    PROFINET

    IE/PB Link

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 55 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    Integration of PROFIBUS-PA in PROFINET

    Proxy

    PROFINET

    PROFIBUS DP

    DP/PA Coupler for connection of

    PROFIBUS-PA field devices

    Connection of up to 31 PA field devices per

    DP/PA Coupler

    Cyclic and acyclic communication

    PROFIBUS PA

    DP/PA Coupler

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 56 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    Combination of PROFINET and PROFIBUS

    Coexistence of PROFIBUS and PROFINET

    No additional CPs for PROFIBUS

    Easy migration from PROFIBUS to PROFINET

    Migrate step by step

    PROFINET and PROFIBUS can be used at the same time on the Controller

    Less Hardware required!

    PROFIBUS and PROFINET in the Controller

    Flexible system design with PROFIBUS and PROFINET

    PROFIBUS and PROFINET extend each other

    Coexistence of both technologies

    Routing via PROFIBUS interface

    Coexistence of PROFIBUS and PROFINET

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 57 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    Redundancy

    57

    Redundant Controller Primary

    Backup

    Redundant Network

    Device with

    redundant

    connectivity

    Device with

    singular

    connectivity

    Functionality

    Support of system

    redundancy is mandatory for

    PA PROFINET devices in

    CC-B(PA). High Scalability

    High Availability

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 58 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    Terms

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 59 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    Terms and Meanings

    What means System Redundancy

    We need to know first some terms to understand

    PN IO Controller (IOC)

    can be a single or redundant AS 400

    Application Relation (AR)

    Describes the relationship between IOC and the Remote IO or PN devices

    Network Access Point (NAP)

    Means the number of interface in a PN IO Device

    S1/S2 Devices

    S1 only one AR

    S2 two AR possible

    R1/R2 Device

    two AR possible per interface (NAP)

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 60 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    Single System

    AR 1 Application Relation

    Single NAP

    Network Access Point 1 Interface

    Controller

    CPU IOC

    NAP

    PN IO

    AR

    S1 Device

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 61 2014-08-13 Thomas Bartsch

    Single NAP

    Network Access Point

    Redundant Automation System

    PROFINET in Process Automation

    Redundant System and System Redundancy

    AR 1 Application Relation

    AR 2 Application Relation

    1 Interface

    Controller 1

    CPU IOC

    NAP

    PN IO

    AR 1 S2 Device

    Supports System Redundancy

    Controller 2

    CPU IOC

    AR 2

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 62 2014-08-13 Thomas Bartsch

    NAP 2

    Redundant NAP

    Redundant Automation System

    PROFINET in Process Automation

    System Redundancy Redundant System

    AR 1.1 AR 2.1

    2 Interfaces

    Controller 1

    CPU IOC

    NAP 1

    PN IO

    AR 1.1

    R2 Device

    Each NAP has 2 AR

    Controller 2

    CPU IOC

    AR 2.1 AR 1.2 AR 2.2

    AR 1.2 AR 2.1

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 63 2014-08-13 Thomas Bartsch

    Architecture

    PROFINET in Process Automation

    Media Redundancy Protocol (MRP)

    MRP Media Redundancy Protocol

    IEC 61158-5-10 Edition 1.0 2007-12

    Part of the PROFINET standardization

    Based on ring topology - The basic concepts of MRP and HSR (High Speed Redundancy) are identical

    Max. 50 nodes in the ring

    PROFINET IO-Controller

    PROFINET IO-Devices

    Components of the network infrastructure (IE switches, CPs)

    Configuration and diagnostics in STEP7

    200 ms reconfiguration time

    MRP manages Ethernet Ring architecture, independent of the connected participants and there communication relation

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 64 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    Media Redundancy Protocol (MRP)

    PROFINET devices are supporting

    MRP functionality

    Improved plant availability More flexibility Less costs, because of less required components

    MRP on integrated

    PROFINET ports

    Innovation for simplification of the

    system architecture

    One device or controller is Ring-

    Master

    Other devices or masters can take

    over Ring-Master functionality in case

    of a failure

    Industrial Ethernet

    PROFINET

    data

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 65 2014-08-13 Thomas Bartsch

    The Ring-Manager will initiate a

    second communication path on the

    network

    In case of a failure in the network or of

    a device the communication resume

    The communication is now managed

    over the alternative path

    The failure is limited to a damaged

    device

    PROFINET in Process Automation

    Media Redundancy Protocol (MRP)

    Industrial Ethernet

    PROFINET

    data

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 66 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    Media Redundancy Protocol (MRP) Topologie Editor

    Online check of ring configuration in the Topology Editor

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 67 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    Media Redundancy Protocol (MRP) Topologie Editor

    Detection of a lost connection in the Topology Editor

    Industrial Wireless LAN

    Safety

    Flexible Topologien

    Erweiterbarkeit

    Web Tools

    Easy cabling

    Offener Standard

    Medienredundanz

    Ein Kabel fr alles

    Gerte-/ Netzdiagnose

    Energieeffizienz Groe Mengengerste

    Hohe Datenrate

    Geschwindigkeit

    Hohe Przision

    Mageschneiderte

    Anlagenkonzepte

    Optimale Nutzung von

    RessourcenHhere Produktivitt

    Schneller Gertetausch

    Robustheit/Stabilitt

    Easy cablingEinfache Verkabelung

    Schneller Hochlauf

    Flexibilitt Effizienz Performance

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 68 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    PROFINET Diagnostic

    Device failure

    Maintenance

    cable

    Diagnostic information of Topology Editor

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 69 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    System Architectures with S1 Devices and PCS 7 V8.1

    Controller

    With IOC

    S1 - Device

    S1 - Device

    Controller

    With IOC

    S1 - Device

    S1 - Device

    MRP

    S1 Devices

    e.g. ET 200M, ET 200SP, IE/PB Link PNIO (MRP with Switch), Simocode, Sinamics

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 70 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    System Architectures with S1 Devices and Switches and PCS 7 V8.1

    Controller

    With IOC

    S1 - Device

    S1 - Device

    MRP

    S1 Devices

    e.g. ET 200M, ET 200SP, IE/PB Link PNIO, Simocode, Sinamics

    Controller

    With IOC

    S1 - Device

    S1 - Device

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 71 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    System Architectures with S2 Devices and PCS 7 V8.1

    Redundant Controller

    With IOC

    S2 - Device

    S2 - Device

    S2 Devices

    e.g. ET 200M, Simocode (new version 2014)

    Redundant Controller

    With IOC

    S2 - Device

    S2 - Device

    MRP

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 72 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    System Architectures with S2 Devices and Switches and PCS 7 V8.1

    Redundant Controller

    With IOC

    S2 - Device

    S2 - Device

    MRP

    S2 Devices

    e.g. ET 200M, Simocode (new version 2014)

    Redundant Controller

    With IOC

    S2 - Device

    S2 - Device

  • Siemens AG 2014. All Rights Reserved.

    Products

    PROFINET in Process Automation

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 74 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    PROFINET in Process Automation

    PROFINET as Fieldbus in PCS 7

    PCS 7 Standard with PROFINET

    AS 410

    AS 414-3IE and AS 416-3IE

    PROFINET Interface integrated into CPU

    AS 414-3, 416-2/4, 417-4

    CP 443-1

    Possible IO

    ET 200SP Standard modules with PCS 7 V8.1

    ET 200M with IM 153-4 PNIO HF

    All modules

    IE/PB Link PN IO with DP/PA - Link

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 75 2014-08-13 Thomas Bartsch

    PROFINET

    FOUNDATION

    Fieldbus

    PROFIBUS PA

    Active Field

    Distributor

    PROFIBUS DP

    PROFINET in Process Automation

    PROFINET as Fieldbus in PCS 7

    PCS 7 High available and safety related automation systems

    AS 410H,

    AS 412H, AS 414H, AS 416H, AS 417H

    AS 410 F/FH,

    AS 412F/FH, AS 414F/FH,

    AS 416F/FH, AS 417F/FH

    Integrated PN-Interface

    Possible IO on PROFINET

    ET 200SP Standard modules with PCS 7 V 8.1

    ET 200M with IM 153-4 PNIO HF

    F-DI Namur only on PROFIBUS

    Architecture with Switches

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 76 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    PROFINET in PCS 7 V8.02

    Industrial Ethernet, plant bus

    PCS 7 OS server

    PROFINET, field bus

    ET 200M PN

    IE/PB-Link

    PROFIBUS DP

    Zone 2 Zone 1

    AFDiS

    PROFIBUS PA

    AFD

    PA-Koppler

    PCS 7

    AS 410-5H

    SIMOCODE PN

    PAC 3200/4200 PN

    SINAMICS PN

    Fault-tolerant

    automation systems

    Weighing systems

    Comprehensive diagnostics and easier commissioning support via standard Ethernet mechanisms (Plug & Play)

    Improved performance due to higher bus

    transmission rate (100 Mbit)

    Improved robustness

    Free customizable flexible plant

    topologies

    100% investment protection and backward compatibility for fieldbus installations (reuse of I/O modules)

    Cost effective architecture for system

    redundancy (Red. Controller, Single IM)

    PROFIBUS & PROFINET in one System

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 77 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    PROFINET in PCS 7 V8.1

    Second PROFINET IO Controller on CPU410-5H

    (without 443-1 -> optimized costs)

    ET 200SP: The low-cost Remote I/O

    SIMOCODE PRO V PN Release 2014

    with System Redundancy

    Integration of Drives via PN

    Industrial Ethernet, plant bus

    PCS 7 OS server

    PROFINET, field bus

    ET 200M PN

    IE/PB-Link

    PROFIBUS DP

    Zone 2 Zone 1

    AFDiS

    PROFIBUS PA

    AFD

    PA-Koppler

    PCS 7

    AS 410-5H

    PAC 3200/4200 PN

    SINAMICS PN

    Fault-tolerant

    automation systems

    Weighing systems

    SIMOCODE PN

    ET 200SP PN

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 78 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    SIMOCODE pro with PROFINET

    SIMOCODE pro

    with PROFINET

    Functionality

    Benefit

    Integrated two port switch with support of MRP

    In preparation: redundant connection on high available controller over PROFINET

    Communication based on open industry standard OPC UA and diagnostic over integrated web server

    Expandable with failsafe module with PROFIsafe

    Supply of energy measured value over PROFIenergy

    In preparation: Higher availability with PROFINET redundancy functions

    In preparation: No need of Y-Link for connection on redundant system

    Simplified operation and monitoring

    Client and location-independent diagnostic

    Easy implementation of Safety- (PROFIsafe) and Energy management (PROFIenergy) concepts

    More

    Integration of SIMOCE pro PN with full functionality with PCS 7 V8 Advanced Process Library (APL)

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 79 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    ET 200SP

    New AI HART module Tool-free connection system

    due to push-in terminals

    Enhanced product performance Reduced variety of parts

    due to function compression

    Power modules to create load groups

    integrated into the system 50% smaller footprint

    ET 200SP

    Simple to use smaller in size stronger in performance

    with PROFINET, replacing ET 200S

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 80 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    CPU 410-5H

    Flexible scalable PO (from 100 PO to 2600 PO)

    Memory

    48MB Load-, 16MB Code- and 16MB data memory

    IO-Range

    16.000 Byte Input and 16000 Byte Output

    Performance

    10ms cycle time

    Functionality

    HF-CPU (Process Safety & High Availability)

    High precision time stamping

    Interfaces

    DP-Master with max. 96 DP-Slaves

    Up to 10 additional external DP-Master

    2x PN IO Controller with 250 Devices each or 2x Ethernet

    or 1x Ethernet & 1x PN IO Controller

    Conformal Coating

    Individual configurations possible

    Technical Details

  • Siemens AG 2014. All Rights Reserved.

    Advantages

    PROFINET in Process Automation

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 82 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    The way from PROFIBUS to PROFINET

    PROFINET: The perfect combination of two

    worlds with additional value

    PROFIBUS know-how can be easy used for

    PROFINET

    PROFINET has advantages compared to

    PROFIBUS

    Partly shift to PROFINET with a existing

    PROFIBUS installation

    PROFINET is a worldwide established and

    reliable standard

    New projects can already start today with

    PROFINET

    PROFIBUS is the most established fieldbus and PROFINET is the further

    development based on standard Ethernet

    The low costs for the change from PROFIBUS to PROFINET are a investment

    protection for the customer

    Flexible topologies, Scalable redundancy, Performance, Robust installation,

    Wireless, Web, Multi-Master, Shared Device, Media redundancy and many more

    Step-by-step change from PROFIBUS communication modules, whereby the cabling

    of the I/O modules is still used. A proxy is used to connect the remaining devices.

    and using therefore the innovative concepts of the system architectures

    which is accepted and used in all branches and markets

    The time is ready for PROFINET!

  • Siemens AG 2014. All Rights Reserved.

    Industry Sector Page 83 2014-08-13 Thomas Bartsch

    PROFINET in Process Automation

    Advantages of PROFINET

    Higher performance with higher data rate (100Mbit)

    PROFINET is well proven since many of years in factory automation and motion control

    Seamless Integration from ERP/MES level to field level (horizontal integration)

    Detailed diagnostic and easier commissioning due to Ethernet mechanisms (Plug & Play)

    Complete Commissioning by automatic naming and addressing

    Easier and faster device exchange

    Higher scalability of the system redundancy

    Higher robustness

    More flexible topologies (Line, Star, Tree and Ring)

    PROFINET is the future system backbone for PCS 7

    100% investment protection for the future due to integration of existing fieldbus technologies (Proxies)

    PROFINET is a worldwide established standard in the industry based on standard Ethernet