Fiber Optic Cables

20
Specification ETS03-01-07 Ver 2 Ergon Energy Corporation Limited ABN 50 087 646 062 Ergon Energy Corporation Limited Technical Specification for Optic Fibre Cable ETS03-01-07

description

Specifications Regarding Fibre Optics

Transcript of Fiber Optic Cables

  • Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    Ergon Energy Corporation Limited

    Technical Specification for Optic Fibre Cable

    ETS03-01-07

  • Technical Specification for Optic Fibre Cable

    i Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    Contents 1. Purpose and Scope ...................................................................................................... 1

    2. References .................................................................................................................... 1

    2.1 Applicable Standards .......................................................................................... 1

    3. Drawings ....................................................................................................................... 1

    4. Environment ................................................................................................................. 2

    4.1 Aerial optical fibre cables will be exposed to the following environmental conditions: ...................................................................................................................... 2

    4.2 Underground optical fibre cables will be exposed to the following environmental conditions: ...................................................................................................................... 2

    5. Design and Construction ............................................................................................ 3

    5.1 General ............................................................................................................... 3

    5.2 Optical Fibre Requirements ................................................................................ 3

    5.3 Cable Requirements ........................................................................................... 4

    5.4 Drawings ............................................................................................................. 5

    6. Performance and Testing ............................................................................................ 5

    6.1 Tests ................................................................................................................... 5

    6.2 Routine Test ........................................................................................................ 5

    6.3 All Dielectric Self Supporting (ADSS) Optical Fibre Cable .................................. 5

    6.4 Underground Optical Fibre Cable ....................................................................... 6

    6.5 Tests after Delivery ............................................................................................. 6

    6.6 Test Certificates .................................................................................................. 6

    7. Risk Assessment ......................................................................................................... 7

    8. Quality Assurance ........................................................................................................ 7

    8.1 Purchasers Policy ............................................................................................... 7

    8.2 Documentary Evidence ....................................................................................... 7

    9. Samples ........................................................................................................................ 7

    9.1 Production Samples ............................................................................................ 7

    10. Packaging and Marking ............................................................................................... 7

    10.1 General ............................................................................................................... 7

    10.2 Lagging ............................................................................................................... 8

    10.3 Drum Durability ................................................................................................... 8

  • Technical Specification for Optic Fibre Cable

    ii Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    10.4 Drum Surface Treatment .................................................................................... 8

    10.5 Marking of Drums ................................................................................................ 8

    10.6 Fixing of Cable End ............................................................................................. 9

    10.7 Quarantine Requirements ................................................................................... 9

    11. Service Performance ................................................................................................... 9

    12. Reliability ...................................................................................................................... 9

    12.1 Service Life ......................................................................................................... 9

    12.2 Evidence in Support of Reliability ...................................................................... 10

    13. Training ....................................................................................................................... 10

    14. Environmental Considerations ................................................................................. 10

    15. Information To Be Provided ...................................................................................... 10

    15.1 Specific Technical Requirements ...................................................................... 10

    15.2 Checklist of Supporting Documentation ............................................................ 10

    15.3 Fibre Information ............................................................................................... 10

    15.4 Information on Cable ......................................................................................... 11

    15.5 Cable Installation Information ............................................................................ 12

    16. Appendix A.1 Drum and Packaging Details .......................................................... 13

    17. Attachment 1 Cable Performance - All Cables ..................................................... 14

    18. Attachment 1 Cable Performance - All Cables (cont'd) ....................................... 15

    19. Attachment 2 Technical Details Fibre Performance .......................................... 16

    20. Attachment 3 Technical Documentation Checklist .............................................. 17

  • Technical Specification for Optic Fibre Cable

    Page 1 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    1. Purpose and Scope

    This specification sets out the requirements for the manufacture, testing and delivery of optical fibre cables for use on the electricity distribution network in a totally exposed environment. Items covered by this technical specification, are listed as follows:

    ITEM No.

    ITEM DESCRIPTION STOCK CODE

    Fibre Optic Underground Cable with Termite Protection: 1 Single Mode 12 Fibres 0104766

    2 Single Mode 36 Fibres 0104441

    3 Single Mode 48 Fibres 0104440 All Dielectric Self Supporting (ADSS) Overhead Optical Fibre Cable:

    4 Single Mode 12 Fibres Short Span (0 150m) 0104765

    5 Single Mode 36 Fibres Short Span (0 - 150m) 0104444

    6 Single Mode 36 Fibres Long Span (150m 500m) 0104443

    7 Single Mode 48 Fibres Short Span (0 - 150m) 0104442

    8 Single Mode 48 Fibres Long Span (150m 500m) 0104439

    2. References

    2.1 Applicable Standards The optical fibre cables shall be designed, manufactured and tested in accordance with the relevant parts of the following Standards and all amendments issued from time to time except where varied by this specification.

    STANDARD TITLE AS/ACIF

    S008:2006 Requirements for Customer Cabling Products.

    ITU Recommendation

    G.652

    Characteristics of a Single-Mode Optical Fibre Cable (Zero Water Peak)

    ANSI TIA-598C Optical Fibre Colour Coding AS 1049 Telecommunications Cable Insulation, Sheath & Jacket.

    AS 2857 - 1986 Timber drums for insulated electric cables and bare conductors

    AS 3983 Metal drums for insulated electric cables and bare conductors

    ISO 9002 Quality systems - Model for quality assurance in production, installation and servicing

    3. Drawings

    There are no drawings attached to this specification.

  • Technical Specification for Optic Fibre Cable

    Page 2 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    4. Environment

    4.1 Aerial optical fibre cables will be exposed to the following environmental conditions:

    DESCRIPTION CONDITION

    Temperatures Not exceeding 45oC as determined by a shaded thermometer (Summer day time)

    Minimum -5C (Winter night time)

    Solar Radiation Level 1100 watts per square metre with high ultraviolet content

    Precipitation Tropical summer storms with gust wind speeds above 160km/h and an annual rainfall in excess of 1500mm

    Atmospheric classifications Areas of coastal salt spray and / or industrial pollution with equivalent salt deposit densities in the range of 2.0 3.0 g/m2

    4.2 Underground optical fibre cables will be exposed to the following

    environmental conditions:

    DESCRIPTION CONDITION

    Installation Installed directly buried in fine grain bedding material, or, in PVC conduits at a nominal depth of up to 1000 mm, with cable ends rising up concrete or timber poles and exposed to direct sunlight.

    Ambient Air Temperatures Not exceeding 45oC as determined by a shaded thermometer (Summer day time)

    Minimum -5C (Winter night time)

    Ambient Ground Temperatures Not exceeding 30oC

    Altitude Not exceeding 500 metres above sea level

    Humidity 90% high humidity combined with a high temperature (35oC) followed by a sudden drop in temperature of up to 10oC

    Exposed sections of underground optical fibre cables will be subject to the service conditions described in Clause 4.1 above.

  • Technical Specification for Optic Fibre Cable

    Page 3 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    5. Design and Construction

    5.1 General 5.1.1 Metal Free

    The offered cables shall be completely metal free and shall comply with the product approval requirements of AS/ACIF S008:2006.

    5.1.2 Standard product range It is preferred that the cables be part of or become part of the standard product range produced by the manufacturer.

    5.1.3 ITU-T Recommendation The optical fibre cable as specified shall have single mode optical fibres in accordance with ITU-T Recommendation G.652.

    5.1.4 Outside diameter Short span The outside diameter of the ADSS Short Span cable shall be between 14mm and 14.99mm.

    5.1.5 Outside diameter Long Span The outside diameter of the ADSS Long Span cable shall be between 18mm and 18.99mm.

    5.2 Optical Fibre Requirements 5.2.1 Fibre Type

    The optical fibres will be single mode fibres with the following characteristics.

    5.2.2 Fibre Characteristics Single Mode: The characteristics of each single mode optical fibre in the optical fibre cable will adhere to the ITU-Ts recommendation G.652 and as follows: Transmission wavelength 1310 nm and suitable for 1550 nm Mode field diameter 9.2 +- 0.4m at a transmission

    wavelength of 1310 nm. Attenuation Not greater than 0.40 dB/km at an

    optical wavelength of 1310 nm and 0.30 dB/km at 1550 nm

    Point Discontinuity Not greater than 0.1 db at 1310 and 1550 nm.

    Cable Cut-off Wavelength < 1260 nm Zero dispersion 1312 +/- 10nm Dispersion Slope at Zero dispersion Wavelength

    0.093ps/(nm2-km)

    Optical cladding diameter 125 m 1.0m Life span Greater than 35 years

    5.2.3 Fibre Coatings

    The secondary coating is required to be a tight UV Acrylate coating and shall be easily removed by mechanical means for jointing purposes. Preference is likely to be given to fibres, which have a primary buffer coating of 250 15 micron low modulus UV, cured

  • Technical Specification for Optic Fibre Cable

    Page 4 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    Acrylate material. Thus Tenderers are encouraged to offer prices for totally UV cured Acrylate coated fibres where possible. Tenderers may offer more than one primary, buffer coating material. In such cases Tenderers should provide as much information as possible regarding the physical, mechanical, and transmission performance of such fibres, with particular regard to the relative susceptibility to hydrogen degradation compared with UV Acrylate coated fibre.

    5.2.4 Identification of Individual Fibres The colours of individual fibres and tubes as well as other cable components shall allow for the unique identification of individual fibres within the cable and shall be in accordance with AS/ACIF S008:2006.

    5.2.5 Factory Joints The fibres shall not be jointed within any un-installed cable length without prior approval by the Purchaser. Where such approval is given, there shall be a maximum of one (1) joint allowed in any continuous length. This joint shall have a two way average splice loss of less than 0.2 dB at 1310 nm and 1550 nm.

    5.2.6 Point Loss in Un-Installed Cable

    For the un-installed optical fibre cable there shall be no point loss (of any cause) in any single fibre, whose average two way attenuation exceeds 0.01 dB at 1310 nm and 1550 nm.

    5.3 Cable Requirements 5.3.1 Moisture Exclusion

    As the cable may be subjected to total water immersion, the cable shall comply with the requirements for water penetration specified in Clause 25, Method F5B of IEC60794-1-2 to prevent the ingress of moisture and other impurities to the optical fibres. Dry core water blocking techniques shall be used for all cables.

    5.3.2 Cable Configuration The configuration of the cable shall be such that it is arranged in tubes of twelve (12) fibres. Filler tubes will be used as required.

    5.3.3 Cable Sheathing The cable sheath shall consist of material compatible with the hauling of cable

    through ducts and shall be resistant to insect and termite attack. The cable sheath shall be resilient to ageing and embrittlement from heat and

    ultraviolet radiation such that the life expectancy of the cable is a minimum of 35 years.

    The entire cable shall consist of electrically insulating material. Distance markings shall be provided on the cable (in metres) in order to assist

    possible fault location in the future. A cable number and Ergon Energy name shall be provided on the cable. Long Span ADSS cable shall be marked with the words LONG SPAN. The markings are to be legible and indelible and shall not reduce the effectiveness

    of the cable in resisting insect and termite attack.

    5.3.4 Cable Design The cable is to be of non-metallic construction.

  • Technical Specification for Optic Fibre Cable

    Page 5 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    The cable will incorporate a strength member of glass reinforced plastic or equivalent.

    The optical fibres shall not be constrained firmly against other fibres, strength members, moisture barrier compound or any other cable components in order that the fibre strain is de-coupled from the strain in other components when the cable is under tension.

    The preferred construction type is "Loose Tube".

    5.3.5 Cable Mechanical Requirements The cable must be able to withstand a directly applied long term crush loads of 1 kN per 100 mm without increase in optical attenuation for any fibre or any decrease in the integrity of the optical fibre cable over its designated lifetime. Test method as per IEC 60794-1.

    5.4 Drawings Tenderers shall provide detailed drawings of the cross-section of the items offered.

    6. Performance and Testing

    6.1 Tests 6.1.1 Standards Cables shall be tested in accordance with the requirements of the relevant Australian Standards.

    6.2 Routine Test 6.2.1 Attenuation The attenuation of the fibre shall be tested using a 1310 nm & 1550 nm light source at one end of the fibre and an optical level metre at the other end. 6.2.2 Continuity Continuity shall be tested at 1310 nm & 1550 nm by measuring backscattered light using an Optical Time Domain Reflectometer (OTDR), which is adjusted to see the whole length of the fibre. This measurement shall be done from both ends of each fibre.

    6.2.3 Recording The overall attenuation and the OTDR traces shall be recorded and shall form part of the test certificates.

    6.3 All Dielectric Self Supporting (ADSS) Optical Fibre Cable

    6.3.1 Type Tests 6.3.1.1 Graph

    Tenderers shall provide a graph of cable strain versus fibre strain. 6.3.1.2 Results of Type Testing

    Results of type testing previously carried out on the same ADSS type offered shall be provided at time of tendering.

    6.3.1.3 Breaking Load Test Following completion of the stress/strain test, the tension shall be increased until breakage load and the load at which the ADSS or fitting began to yield under tension shall be recorded.

  • Technical Specification for Optic Fibre Cable

    Page 6 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    6.3.1.4 Crushing Force Test A sample of the optical fibre core shall be subjected to a lateral crushing force, which shall be slowly increased from zero. The transmission characteristics of the optical fibres shall be continuously monitored. A graphical plot of transmission loss versus lateral force shall be prepared. The lateral force shall be increased until the change in transmission loss of the optical fibres exceeds 0.1dB, test method as per IEC60794-1.

    6.3.2 Routine Tests The optical fibre attenuation and continuity for each fibre of each cable drum length shall be measured and recorded prior to shipment from the manufacturing plant. The test results shall include date of test, drum number, drum length and names of test personnel.

    6.4 Underground Optical Fibre Cable

    6.4.1 Type Tests 6.4.1.1 Results of Type Testing

    Results of type testing previously carried out on the same underground type cable offered shall be provided at time of tendering.

    6.4.1.2 Breaking Load Test

    Following completion of the stress/strain test, the tension shall be increased until breakage load and the load at which the underground cable began to yield under tension shall be recorded.

    6.4.1.3 Crushing Force Test

    A sample of the optical fibre core shall be subjected to a lateral crushing force, which shall be slowly increased from zero. The transmission characteristics of the optical fibres shall be continuously monitored. A graphical plot of transmission loss versus lateral force shall be prepared. The lateral force shall be increased until the change in transmission loss of the optical fibres exceeds 0.1dB, test method as per IEC60794-1.

    6.4.2 Routine Tests

    The optical fibre attenuation and continuity for each fibre of each cable drum length shall be measured and recorded prior to shipment from the manufacturing plant. The test results shall include date of test, drum number, drum length and names of test personnel.

    6.5 Tests after Delivery The cables may be subject to tests after delivery at Ergon Energys expense. Ergon Energy reserves the right to reject all cables not in conformance with this Specification or the successful Tenderer's guaranteed parameters. All rejected cables shall be replaced by the successful Tenderer at the successful Tenderers expense.

    6.6 Test Certificates 6.6.1 Supply of Test Certificates

    Test certificates shall be supplied by the successful Tenderer for all tests required by this Specification. Payment under the Contract shall not become due and payable unless and until test certificates are received by Ergon Energy in accordance with the following:

  • Technical Specification for Optic Fibre Cable

    Page 7 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    6.6.1.1 Type Test Certificates

    All type tests shall be completed and certificates submitted as part of the tender response.

    6.6.1.2 Routine Test Certificates

    Routine test certificates shall be submitted prior to the dispatch of the cable from the manufacturing plant.

    7. Risk Assessment

    There is no requirement for manufacturer provided safety risk assessments for the items covered by this specification.

    8. Quality Assurance

    8.1 Purchasers Policy It is the Purchasers policy to procure goods, equipment and services from sources that demonstrate the ability to supply quality products.

    8.2 Documentary Evidence Documentary evidence shall be provided concerning the level of quality system certification associated with the Tenderer and/or Manufacturer. This documentation shall include the Capability Statement associated with the Quality System Certification.

    9. Samples

    9.1 Production Samples When requested, production samples of each item offered shall be submitted to assist in the evaluation of the offer. Each sample shall be delivered freight free, suitably packaged and labelled with the following information:

    Name of Supplier and this Contract No.

    Contract Item Numbers

    Any supporting data on features or characteristics

    10. Packaging and Marking

    10.1 General 10.1.1 Damage Free

    It is the appointed supplier's responsibility to ensure that the fibre optic cable is delivered on site damage free. Storage, packaging, delivery to site and all other aspects of cable protection are the responsibility of the Tenderer.

  • Technical Specification for Optic Fibre Cable

    Page 8 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    10.1.2 Drum standards Optical fibre cables may be supplied on either timber drums or steel drums complying with the requirements of AS 3983.

    10.1.3 Standard for Timber Drums Operational difficulties are anticipated with the use of cable drums manufactured in accordance with AS 2857-1996. Hence this specification is based on cable supplied on timber drums manufactured in accordance with the requirements of superseded standard AS 2857-1986.

    10.1.4 Drum sizes Optical fibre cables shall be supplied on drum sizes and in the lengths as detailed in Appendix A.1 to this specification.

    10.1.5 Length The cable shall be in one (1) length on each drum.

    10.1.6 Winding The cable shall be wound in such a way as to preclude the possibility of chafing or damage to the cable during winding and transport. The winding tension shall be as low as possible, being only as high as that required to minimise movement of cable between adjacent layers.

    10.2 Lagging

    The cable shall be protected by external lagging to ensure that it is delivered undamaged giving due consideration to the methods and distance of transportation and handling. Sheet form wrapping alone is NOT acceptable.

    10.3 Drum Durability All drums must be of suitable quality and robustness to withstand a minimum of months twenty-four (24) exposure to all types of weather conditions during outdoor storage without deterioration.

    10.4 Drum Surface Treatment Drum surface treatment to protect against weather, the environment, galvanic action, and corrosion is required. Suppliers shall state the type of surface treatment applicable to drums for each item.

    10.5 Marking of Drums 10.5.1 Standard

    The marking of information on the cable drum shall be in accordance with Clause 16.3 of AS / NZS 5000.1. In addition, the following information shall be provided indelibly and legibly marked directly on the flanges:

    a) The name Ergon Energy and the relevant stores stock code.

    b) Contract number.

    c) Order release authority or purchasing order number. d) Manufacturer's traceability number derived from Manufacturers first letter,

    hyphen, batch number, hyphen, drum number for this batch.

  • Technical Specification for Optic Fibre Cable

    Page 9 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    10.5.2 Size and location Marking at least 25 mm high shall be located on both outside flange surfaces near the spindle.

    10.5.3 Direction of rolling Drums shall be marked with the preferred direction of rolling.

    10.5.4 Additional Information to be provided The following information shall also be provided:

    ERGON ENERGY

    All Dielectric Optical Fibre Cable

    Contract No.

    Purchase Order Number

    10.6 Fixing of Cable End

    The inner end of the cable shall be secured to the drum to ensure that the end will not flick off the drum barrel when the cable is being run out.

    10.7 Quarantine Requirements Should the items offered be supplied from overseas manufacturers, then it is mandatory that all conditions and inspections required by the Australian Quarantine Act be met and that all these costs be included in the tendered price. In particular, timber crates must be fumigated with methyl bromide with a concentration of 48 grams per cubic metre for 24 hours at 21 C. The supplier shall ensure that the procedure does not produce any deleterious effects to the cable or the drums.

    11. Service Performance

    Suppliers shall state: (a) the period of service achieved by the items offered within Australian service

    conditions;

    (b) Australian electricity supply authorities who have a service history of the items offered; AND

    (c) Contact names and phone numbers of relevant employees of those supply authorities who can verify the service performance claimed.

    12. Reliability

    12.1 Service Life Suppliers are required to comment on the reliability of the cables and the performance of the materials offered for a service life of 35 years under the specified system and environmental conditions.

  • Technical Specification for Optic Fibre Cable

    Page 10 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    12.2 Evidence in Support of Reliability Such comments shall include evidence in support of the reliability and performance claimed including information on Failure Mode and Effect Analysis.

    13. Training

    Training material in the form of drawings, instructions and/or audio visuals may be required to be provided for the items accepted under the offer. Tenders shall state the availability of training materials which should include but is not limited to the following topics:

    Handling Storage Application (particularly in areas of heavy coastal pollution) Installation Maintenance Environmental performance Electrical performance Mechanical performance Disposal

    14. Environmental Considerations

    Suppliers are required to comment on the environmental soundness of the design and the materials used in the manufacture of the items offered. In particular, comments should address such issues as recyclability and disposability at the end of service life.

    15. Information To Be Provided

    15.1 Specific Technical Requirements The specific technical requirements for the items offered shall be as stated in Attachment 1 of this specification. The supplier shall provide all details requested by Attachment 1 and shall guarantee such data.

    15.2 Checklist of Supporting Documentation

    Attachment 2 details a checklist of supporting technical documentation which is required to be submitted with the offer.

    15.3 Fibre Information

    15.3.1 Fibre Characteristics The Tenderer is required to supply the following: (a) A graph of attenuation versus wavelength over the range of 700 nm to 1700

    nm for single mode fibres. (b) A typical graph of fibre attenuation for the 1310 nm & 1550 nm wavelength

    for single mode fibres for the temperature range of 5oC to 75oC. (c) Details for the strength of the fibres. (d) A graph of attenuation verses cable strain for each cable offered. (e) Information on the chromatic dispersion co-efficient in ps/km/nm with

    respect to zero dispersion wavelength in the region of 1310 nm and 1550 nm for single mode fibre.

  • Technical Specification for Optic Fibre Cable

    Page 11 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    (f) Information on the Dispersion Slope at Zero Dispersion Wavelength in ps/(nm2-m)

    15.3.2 Fibre Performance Tenderers shall provide information regarding the physical, mechanical, and transmission performance of fibres, with regard to the relative susceptibility to hydrogen degradation.

    15.3.3 Field Jointing Tenderers shall provide details of their fibres performance to different jointing techniques (including arc fusion and mechanical spicing), preferably in the form of histograms showing minimum obtainable splice losses.

    15.4 Information on Cable 15.4.1 Moisture Exclusion

    Full details of the water blocking compound shall be supplied by the Tenderer, including the method of removing the compound prior to cleaving and splicing.

    15.4.2 Cable Sheathing The Tenderer must include in the tender documents information detailing the design and performance of the sheath and jacket of the cables offered to demonstrate that the cable is adequate for a 35 year service life time. The information should include

    The material used as the outer sheath. Effectiveness of resisting pest attack as described in Clauses 4.1 and 4.2. The thickness of the outer sheath. Resistance to environmental stress cracking and thermal and ultraviolet radiation

    ageing.

    15.4.3 Cable Design The Tenderer is to provide details of the design of the cable. The documentation provided will include a cross section of the cable, nominating the materials used on the drawing and any other relevant information.

    15.4.4 Material Properties The Tenderer shall supply a full listing of the material components used in the cable with details on toxicity and safe handling of the materials.

    15.4.5 Fibre Colours Tenderers are required to supply details of the colour of fibres.

    15.4.6 Fibre Tube Colours Tenderers are required to supply details of the colour of fibres tubes

    15.4.7 Vibration Testing The Tenderer will supply results of vibration resistance tests.

    15.4.8 Service Lifetime The Tenderer will supply information to support a cable life time of 35 years for the environmental conditions listed in Clause 4.1. Details as to potential damage to fibres caused by cable materials with particular reference to hydrogen producing agents will be included.

  • Technical Specification for Optic Fibre Cable

    Page 12 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    15.4.9 Sag-Strain Characteristics for Aerial Cables The fibre optic cable must have sag-strain characteristics to enable its installation onto existing power poles while maintaining clearances to low and high voltage mains and statutory clearances. The Tenderer shall supply stringing chart(s) or tables showing optical fibre strain and sag-tension information for the following conditions:

    Range of spans 0-250 m in steps of 20 m.

    Range of cable tensions 0-100% of the maximum recommended cable tension.

    Range of temperatures 5C to +75C in steps of 5C.

    Tenderer to indicate the constant horizontal tension (@ 15C no wind). The Tenderer shall supply details of all assumptions used in calculating stringing chart(s) or tables.

    15.5 Cable Installation Information The Tenderer will nominate any special requirements that Ergon Energy will need to adhere to during the installation of the fibre to ensure that the cable is installed damage free and the lifetime of the installation is not unnecessarily reduced.

  • Technical Specification for Optic Fibre Cable

    Page 13 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    16. Appendix A.1 Drum and Packaging Details

    UNDERGROUND CABLE

    Drum Designation Cable Code Nominal Length

    (m/drum) Timber Metal

    1600/1100/1100 1600/800/1000 SM 36 4000 SM 48 4000 SM 12 4000 OVERHEAD CABLE

    Drum Designation Cable Code Nominal Length

    (m/drum) Timber Metal

    1600/1100/1100 1600/800/1000 SM 36 4000 SM 48 4000 SM 12 4000

  • Technical Specification for Optic Fibre Cable

    Page 14 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    17. Attachment 1 Cable Performance - All Cables

    NOTE: A separate schedule is to be provided for each item offered except for details common to all items which only needs to be provided once.

    PARTICULARS UNITS ITEM No.

    Manufacturer's Name and Address

    Place of Manufacture

    Cable Details:

    Nominal Overall Diameter mm

    Calculated Breaking Load kN

    Maximum permissible cable tension kN

    Effective Cross Sectional Area mm2

    Effective Modulus of Elasticity GPa

    Coefficient of Linear Expansion per oC

    Nominal Mass kg/km

    Maximum permissible cable strain % strain

    Guaranteed strain free window % strain

    Minimum permissible cable bending radius

    No tension

    mm

    Maximum permissible tension mm Minimum permissible radius of stringing sheaves

    mm

    SIGNATURE OF TENDERER: _________________________________

  • Technical Specification for Optic Fibre Cable

    Page 15 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    18. Attachment 1 Cable Performance - All Cables (cont'd)

    PARTICULARS UNITS ITEM No.

    Packaging Details:

    Type of Drum

    AS 2857-1986 Drum Designation

    AS 3983-1991 Drum Designation

    Spindle Hole Diameter mm

    Method of Lagging

    Length of Conductor per Drum m

    Gross Mass of Drum, Conductor and Protective External Lagging

    kg

    Mass of Drum and Conductor kg

    Drum Surface Treatment:

    Barrel:

    Drum Surface Treatment:

    Internal Surface of Flanges

    Metal Drum: Protection Against Weather or Environment

    SIGNATURE OF TENDERER: _________________________________

  • Technical Specification for Optic Fibre Cable

    Page 16 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    19. Attachment 2 Technical Details Fibre Performance

    NOTE: A separate schedule is to be provided for each item offered except for details common to all items which only needs to be provided once.

    PARTICULARS UNITS ITEM No.

    SINGLE MODE: Mode field diameter at 1310 nm m

    and Tolerance %

    Attenuation (at zero fibre tension)

    At 1310 nm

    dB/km

    At 1550 nm dB/km Maximum permissible fibre strain % strain

    Fibre Proof test strain % strain

    Attenuation (at Maximum permissible fibre strain)

    At 1310 nm

    dB/km

    At 1550 nm dB/km Optical cladding diameter m

    and Tolerance %

    Dispersion

    1270 to 1340 nm

    ps/km.nm

    1550 nm ps/km.nm Dispersion Slope at Zero Dispersion Wavelength

    ps/(nm2-km)

    Maximum continuous operating temperature C

    Minimum bending radius for coated optical fibre

    Under no tension

    mm

    Under maximum tension mm SIGNATURE OF TENDERER: _________________________________

  • Technical Specification for Optic Fibre Cable

    Page 17 of 17 Specification ETS03-01-07 Ver 2

    Ergon Energy Corporation Limited ABN 50 087 646 062

    20. Attachment 3 Technical Documentation Checklist

    CLAUSE Ref.

    PARTICULARS UNITS

    Have full and comprehensive details been submitted WITH the tender documents associated with each of the following items?

    5.4 Drawings of conductor cross-section Yes/No

    8.2 Quality systems of BOTH the SUPPLIER and the MANUFACTURER

    Yes/No

    11 Service Performance Yes/No

    12 Reliability Yes/No

    13 Training materials Yes/No

    14 Environmental considerations Yes/No

    15 Completed Attachment 1 and Attachment 2 Yes/No NAME OF TENDERER: ADDRESS OF TENDERER: SIGNATURE: FOR AND ON BEHALF OF TENDERER DATE: ______________________