Fgt Al Data Sheet
Transcript of Fgt Al Data Sheet
-
7/24/2019 Fgt Al Data Sheet
1/3
PRODUCT SPECIFICATION
EPB18132
DEP 2011-12-09 Page 1/3
Power Distribution Cable forSignalling Systems
Enhanced unarmoured cablesRodent Protected
Construction and testing according standards
NetworkRail NR/L2/ELP/27408BS EN 60228
BS 7655-1.3 and BS 7655-4.2IEC 60502-1
Rated Voltage
0,6/1kV
Outer sheath colour
BLACK
Conductor Identification
Brown, Black
Marking on the outer sheath
On the outer sheath by embossing on two primary
lines with the following information (example) :
Legend 1 (line 1):
CABELTE ELECTRIC CABLE 600/1000 VNR/L2/ELP/27408 PVC 2x50 Al YEAR H NMR
Railway Catalogue number Property of Network Rail M.M.
Legend 2 (line 2):
CABELTE ELECTRIC CABLE 600/1000 V
NR/L2/ELP/27408 PVC 2x50 Al YEAR H NMR
Railway Catalogue number Property of Network Rail
Year - Year of manufacture
M.M. - Metric Marking (shall be printed)
Line 1 and line 2 are spaced ~180.
The distance between the end of one element of marking
and the beginning of the next identical element of marking
is 550mm.
SAC/XLPE/FGT/PVC
Circular conductors schematic design
Shaped conductors schematic design
1Conductor
Solid Aluminium Conductors (SAC), circular( 35mm2) or shaped (> 35mm2), class 1,
according to BS EN 60228.
2InsulationXLPE type GP 8 according to BS 7655-1.3.The two insulated conductors are stranded.
3Identification tapePolypropylene tape with a printed legend:Property of Network Rail CABELTE YEAR,applied over the stranded cores.Thickness = 50m | Minimum width = 5mm.
4Bedding (only in circular conductors design)
PVC.
5Rodent protectionFibreglass tape, helically applied with a minimum
overlap of 15%. Weaving design: plain weave 1/1
(272 tex). Nominal thickness of tape = 0,65mm.
6Outer sheathPVC type 9 according to BS 7655-4.2.
5
3
2
1
6
4
3
2
1
5
6
-
7/24/2019 Fgt Al Data Sheet
2/3
PRODUCT SPECIFICATION
EPB18132
DEP 2011-12-09 Page 2/3
Technical Characteristics
Cable designation SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC
Voltage U0/U (kV) 0,6/1 0,6/1 0,6/1 0,6/1 0,6/1 0,6/1 0,6/1
N of cores x conductor size (mm2) 2x16 2x25 2x35 2x50 2x70 2x95 2x120
Conductor class and material Al Class 1 Al Class 1 Al Class 1 Al Class 1 Al Class 1 Al Class 1 Al Class 1
Max. cond. dc resist. at 20C (/km) 1,91 1,20 0,868 0,641 0,443 0,320 0,253
Nominal core to core capacitance (F/km) 0,125 0,141 0,153 0,184 0,217 0,243 0,271
Nominal core to earth capacitance (F/km) 0,130 0,150 0,165 0,179 0,205 0,228 0,247
Zero sequence impedance (/km) (1) 2,50+j2,29 1,59+j2,26 1,16+j2,24 0,87+j2,22 0,62+j2,19 0,46+j2,16 0,37+j2,14
Positive sequence impedance (/km) (1) 2,45+j0,100 1,54+j0,0936 1,11+j0,0898 0,82+j0,0864 0,57+j0,0820 0,41+j0,0792 0,32+j0,0770
Negative sequence impedance (/km) (1) 2,45+j0,100 1,54+j0,0936 1,11+j0,0898 0,82+j0,0864 0,57+j0,0820 0,41+j0,0792 0,32+j0,0770
Inductance (mH/km) 0,319 0,298 0,286 0,275 0,261 0,252 0,245
Reactance (/km) 0,100 0,0936 0,0898 0,0864 0,0820 0,0792 0,0770
Impedance (cos = 0,8) (/km) 1,96 1,23 0,890 0,660 0,457 0,332 0,264
Insulation material XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8
Insulation nom. thickness (mm) 2,0 2,0 2,0 2,0 2,0 2,0 2,0
Core identification colours BR-BK BR-BK BR-BK BR-BK BR-BK BR-BK BR-BK
Sheath material PVC 9 PVC 9 PVC 9 PVC 9 PVC 9 PVC 9 PVC 9
Sheath min. average thickness (mm) 2,4 2,4 2,6 2,7 2,9 3,0 3,2
Rodent protection FGT FGT FGT FGT FGT FGT FGT
Internal identifying tape Yes Yes Yes Yes Yes Yes Yes
Approximate overall diameter (mm) 25 27 29 27 29 32 34
Bend Radius (mm) 200 216 232 216 232 256 272
Weight of cable (kg/km) 660 810 970 810 1010 1220 1450
Maximum drum length (m) (2) 4000 3000 3000 3000 2000 1500 1500
Maximum pulling forceper cond. (daN) 48 75 105 150 210 285 360
BR - BrownBK - Black
FGT- Fibre Glass Tape
(1) Should be take only as approx. value. It is assumed that cable is installed in the ground (earth resistivity 100.m).(2) These values may suffer slight changes.
-
7/24/2019 Fgt Al Data Sheet
3/3
PRODUCT SPECIFICATION
EPB18132
DEP 2011-12-09 Page 3/3
Technical Characteristics (cont.)
Cable designation SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC
Voltage U0/U (kV) 0,6/1 0,6/1
N of cores x conductor size (mm2) 2x150 2x185
Conductor class and material Al Class 1 Al Class 1
Max. cond. dc resist. at 20C (/km) 0,206 0,164
Nominal core to core capacitance (F/km) 0,307 0,321
Nominal core to earth capacitance (F/km) 0,269 0,284
Zero sequence impedance (/km) (1) 0,32+j2,12 0,26+j2,11
Positive sequence impedance (/km) (1) 0,27+j0,0751 0,21+j0,0738
Negative sequence impedance (/km) (1) 0,27+j0,0751 0,21+j0,0738
Inductance (mH/km) 0,239 0,235
Reactance (/km) 0,0751 0,0738
Impedance (cos = 0,8) (/km) 0,217 0,175
Insulation material XLPE GP8 XLPE GP8
Insulation nom. thickness (mm) 2,0 2,0
Core identification colours BR-BK BR-BK
Sheath material PVC 9 PVC 9
Sheath min. average thickness (mm) 3,4 3,6
Rodent protection FGT FGT
Internal identifying tape Yes Yes
Approximate overall diameter (mm) 36 39
Bend Radius (mm) 288 312
Weight of cable (kg/km) 1680 1950
Maximum drum length (m) (2) 1400 1200
Maximum pulling forceper cond. (daN) 450 555
BR - BrownBK - Black
FGT- Fibre Glass Tape
(1) Should be take only as approx. value. It is assumed that cable is installed in the ground (earth resistivity 100.m).(2) These values may suffer slight changes.