Protection Coordination
Prepared By:
Syed Faraz IqbalApp. Engr. (Electrical)
CONTENTS
Introduction to Protection Coordination
Selective Coordination
Data Required for Coordination Study
Protection Coordination at FFC-MM
Anomalies in Protection Coordination Scheme
Recommendations
PROTECTION COORDINATION
Protective device coordination is the process of determining the "best fit" timing of current
interruption when abnormal electrical conditions occur.
The goal is to minimize an outage to the smallest extent possible.
Successful system design hinges on coordination of each relaying scheme.
SELECTIVE COORDINATION
ISOLATION of a faulted circuit from the remainder of the installation is MANDATORY in today's modern
electrical systems.
Power BLACKOUTS CANNOT be tolerated.
A properly engineered system will allow ONLY the protective device nearest the fault to open, leaving
the remainder of the system undisturbed and preserving continuity of service.
SELECTIVE COORDINATION
The faulted circuit is isolated by the selective operation of only that overcurrent protective device
closest to the overcurrent condition.
[1] The National Electrical Code, NFPA 70, The National Fire Protection Association, Inc., 2005 Edition.
“Localization of an overcurrent condition to restrict outages to the circuit or equipment affected, accomplished by the choice of overcurrent
protective devices and their ratings or settings.”[1]
Not Affected
B
C
D
Also Opens
Also Opens
Opens
Branch CircuitFault
A
B
C
D
Opens
Not Affected
Not Affected
Not Affected
De-EnergizedPortion of System Fault
De-EnergizedPortion of SystemA
Selectively Coordinated SystemNon Selective System
DATA REQUIRED
Single-line
diagram
System voltage levels
Impedances
Short-circuit and load
current data
Data required for
coordination study
G G G
124 AC 124 BC
42-G1A 42-G1B 42G2
124 DE
TG-701A6.3 KV10000 KVA, 14%
TG-701B6.3 KV10000 KVA, 14%
MG-7026.3 KV1900 KVA
52B
M
24
M
52A
152 CD 152 C1D1
MP 601C MP 604
TR1A-46.3/0.38kV2000 kVA, 6.25%
TR1B-46.3/0.38kV
2000 kVA, 6.25%
FFC-MM POWER SYSTEM
FOR LINE TO LINE FAULT OF 6000 AMPS ON LV BUSBAR:
G
124 AC42-G1A
TG-701A6.3 KV10000 KVA, 14%
52A
TR1A-42000 KVA, 6.25%
51
50
50
51
51
3000/1
200/1
1000/1
O/C Relay of 52A will pick up & trip the CB in 5 seconds.
O/C Relay of MV CB will pick up & trip the CB in 18
seconds.
O/C Relay of 42-G1A will NOT pick up as per IDMT
curves
Inst O/C Relay of 52A will NOT pick up as per IDMT
curves
FAULT AT LV BUSBAR
FOR LINE TO LINE FAULT OF 18000 AMPS (Pickup Current of Inst. O/C Relay 50 of 52A) ON LV BUSBAR:
G
124 AC42-G1A
TG-701A6.3 KV10000 KVA, 14%
52A
TR1A-42000 KVA, 6.25%
51
50
50
51
51
3000/1
200/1
1000/1
O/C Relay of 52A will pick up & trip the CB in 0.42
seconds.
O/C Relay of MV CB will pick up & trip the CB in 1.3
seconds.
O/C Relay of 42-G1A will pick up & trip the CB in 90
seconds.
FAULT AT LV BUSBAR
Inst. O/C Relay of 52A will also pick
up in 0.1 seconds and block the automatic changeover
FOR LINE TO LINE FAULT OF 43350 AMPS ON LV BUSBAR:
G
124 AC42-G1A
TG-701A6.3 KV10000 KVA, 14%
52A
TR1A-42000 KVA, 6.25%
51
50
50
51
51
3000/1
200/1
1000/1
O/C Relay of 52A will pick up & trip the CB in 0.42
seconds.
O/C Relay of MV CB will pick up & trip the CB in
0.42 seconds.
O/C Relay of 42-G1A will pick up & trip the CB in 3.8
seconds.
FAULT AT LV BUSBAR
Inst. O/C Relay of 52A will also
pick up in 0.1 seconds and block the automatic changeover
FOR LINE TO LINE FAULT OF 48000 AMPS (TR1A-4 Short Circuit Level) ON LV BUSBAR:
G
124 AC42-G1A
TG-701A6.3 KV10000 KVA, 14%
52A
TR1A-42000 KVA, 6.25%
51
50
50
51
51
3000/1
200/1
1000/1
O/C Relay of 52A will pick up & trip the CB in 0.42
seconds.
O/C Relay of MV CB will pick up & trip the CB in
0.36 seconds.
O/C Relay of 42-G1A will pick up & trip the CB in 2.7
seconds.
FAULT AT LV BUSBAR
Inst O/C Relay of MV CB will NOT pick up as per IDMT
curves
Inst. O/C Relay of 52A will also
pick up in 0.1 seconds and block the automatic changeover
OBSERVATION # 01
On Occurrence Of Short Circuit Fault On LV Busbar,
The LV Incoming Circuit Breaker 52A will
trip until FaultCurrent Level
of app. 43KA as opposed to the current
understanding that MV CB always trips in case
of Short Circuit Fault On LV Busbar
FOR LINE TO LINE FAULT OF 275 AMPS ON MV SIDE OF T/F:
G
124 AC
42-G1A
TG-701A6.3 KV10000 KVA, 14%
51
50
51
67A
1000/1
1000/1
200/1
TR1A-46.3/0.38kV2000 kVA, 6.25%
FAULT AT MV SIDE OF T/F
O/C Relay of MV CB will pick up & trip the CB in 50 seconds.
O/C Relay of 42-G1A will NOT pick up as per IDMT
curves
Directional O/C Relay of 124 AC will NOT pick up as per
IDMT curves
FOR 6.3KV MAXIMUM SHORT CIRCUIT LEVEL CURRENT (22000 AMPS):
G
124 AC
42-G1A
TG-701A6.3 KV10000 KVA, 14%
51
50
51
67A
1000/1
1000/1
200/1
TR1A-46.3/0.38kV2000 kVA, 6.25%
O/C Relay of MV CB will pick up & trip the CB in 0.28
seconds.
O/C Relay of 42-G1A will pick up & trip the CB in 0.42
seconds.
Directional O/C Relay of 124 AC will NOT sense the fault
current.
Inst. O/C Relay of MV CB will also pick up and trip the CB in 0.03 seconds.
Inst. O/C Relay of MV CB will NOT pick up as per IDMT
curves
FOR LINE TO LINE FAULT OF 4000 AMPS (Pickup Current of Inst. O/C Relay 50 of MV CB) ON MV SIDE OF T/F:
G
124 AC
42-G1A
TG-701A6.3 KV10000 KVA, 14%
51
50
51
67A
1000/1
1000/1
200/1
TR1A-46.3/0.38kV2000 kVA, 6.25%
O/C Relay of MV CB will pick up & trip the CB in 0.28
seconds.
O/C Relay of 42-G1A will pick up & trip the CB in 1.6
seconds.
Directional O/C Relay of 124 AC will NOT sense the fault
current
Inst. O/C Relay of MV CB will also pick up and trip the CB in 0.03 seconds.
FOR LINE TO LINE FAULT OF 1467 AMPS ON BUSBAR ‘A’:
G
124 AC
42-G1A
TG-701A6.3 KV10000 KVA, 14%
511000/1
67A
1000/1
124 BC 124 DE
GTG-701B6.3 KV10000 KVA, 14%
51
GMG-7026.3 KV1900 KVA
152 CD
42-G1B 42-G267B
1000/1
152 C1D1
1000/1
51 500/1
FAULT AT BUSBAR ‘A’
O/C Relay of 42-G1A & 42G1-B will pick up & trip the respective
CB’s in 20 seconds.
Directional O/C Relays on Busbar ‘A ‘ & Busbar ‘B’ will not sense the fault current.
Both Directional O/c Relays ‘67A’ & ‘67B’ in accordance
with their CT polarity are sensing the Fault Current
in the same direction as opposed to the required
scheme of sensing the Fault Current
in opposite directions.
OBSERVATION # 02
FOR LINE TO LINE FAULT OF 1467 AMPS ON BUSBAR ‘B’:
G
124 AC
42-G1A
TG-701A6.3 KV10000 KVA, 14%
511000/1
67A
1000/1
124 BC 124 DE
GTG-701B6.3 KV10000 KVA, 14%
51
GMG-7026.3 KV1900 KVA
152 CD
42-G1B 42-G267B
1000/1
152 C1D1
1000/1
51 500/1
FAULT AT BUSBAR ‘B’
Directional O/C Relay on Busbar ‘A’ will pick up & trip 124AC in 8
seconds.
Directional O/C Relay on Busbar ‘B’ will pick up & trip 124BC in 8
seconds.
O/C Relay of 42-G1B will pick up & trip the CB in 20
seconds.
FOR LINE TO LINE FAULT OF 1467 AMPS ON BUSBAR ‘C’:
G
124 AC
42-G1A
TG-701A6.3 KV10000 KVA, 14%
511000/1
67A
1000/1
124 BC 124 DE
GTG-701B6.3 KV10000 KVA, 14%
51
GMG-7026.3 KV1900 KVA
152 CD
42-G1B 42-G267B
1000/1
152 C1D1
1000/1
51 500/1
FAULT AT BUSBAR ‘C’
Directional O/C Relay on Busbar ‘A’ will pick up & trip 124AC in 8
seconds.
Directional O/C Relays on Busbar ‘B’ will not sense the
fault current.
O/C Relay of 42-G1B will pick up & trip the CB in 20
seconds.
FOR LINE TO LINE FAULT OF 1467 AMPS ON CABLE LINK:
G
124 AC
42-G1A
TG-701A6.3 KV10000 KVA, 14%
511000/1
67A
1000/1
124 BC 124 DE
GTG-701B6.3 KV10000 KVA, 14%
51
GMG-7026.3 KV1900 KVA
152 CD
42-G1B 42-G267B
1000/1
152 C1D1
1000/1
51 500/1
FAULT AT CABLE LINK
Directional O/C Relay on Busbar ‘A’ will pick up & trip 124AC in 8
seconds.
Directional O/C Relays on Busbar ‘B’ will not sense the
fault current.
O/C Relay of 42-G1B will pick up & trip the CB in 20
seconds.
O/C Relay of 152CD will pick up & trip the CB in 5
seconds.`
U/V Relay of 124DE will pick up & open the CB.
RECOMMENDATIONS
An extensive audit is needed to be carried out to check the Dot Notation of Current Transformers.
Secondary Current Injection Test should be planned in order to determine the correct behavior of Directional Relays in case of occurrence of fault on MV Busbars .
QUESTIONS………..?
External Wiring of Phase Fault detection relay CR
Pickup Current for Inst O/C Relay (50) of LV Busbar CB
TR1A-4 Short Circuit Level Current