Page 1 Page 1 Page 1 Page 1 Page 1 IPC FEC ® FEC FC34-FST HE01 Version 0.1 as of 17.06.99 The CPU I/O Module The CPU I/O Module The CPU I/O Module The CPU I/O Module The CPU I/O Module FEC FC34-FST FEC FC34-FST FEC FC34-FST FEC FC34-FST FEC FC34-FST A member of the Festo group Powerful AMD processor Powerful AMD processor Powerful AMD processor Powerful AMD processor Powerful AMD processor AM186 (20 Mhz, 2 Mips) with 16-bit memory access, 512 Kbytes of RAM Flash disk Approx. 100 Kbytes free Ethernet 10BASE T Telnet, TFTP, TCP/IP, Web Server

Transcript of fec_fc34

Page 1: fec_fc34

Page 1Page 1Page 1Page 1Page 1IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

The CPU I/O ModuleThe CPU I/O ModuleThe CPU I/O ModuleThe CPU I/O ModuleThe CPU I/O ModuleFEC FC34-FSTFEC FC34-FSTFEC FC34-FSTFEC FC34-FSTFEC FC34-FST

A memberof the Festogroup

• Powerful AMD processorPowerful AMD processorPowerful AMD processorPowerful AMD processorPowerful AMD processor

AM186 (20 Mhz, 2 Mips) with 16-bit memory access, 512Kbytes of RAM

• Flash disk

Approx. 100 Kbytes free

• Ethernet 10BASE T

Telnet, TFTP, TCP/IP, Web Server

Page 2: fec_fc34

Page 2FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

ContentsContentsContentsContentsContents

Foreword ...................................................................................................................................... 7

Customer service experience ........................................................................ 7About this manual ......................................................................................... 8FEC FC34-FST - The Control CPU ................................................................... 8CE Confirmation ............................................................................................ 9Important installation instructions ............................................................... 9User safety and device protection ................................................................ 10Warnings ....................................................................................................... 10

Installation and use ..................................................................................................................... 11

Area of use .................................................................................................... 11Scope of delivery .......................................................................................... 11The dimensions of the FEC ............................................................................ 12Start-up requirements .................................................................................. 13

Page 3: fec_fc34

Page 3Page 3Page 3Page 3Page 3IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

FEC components ........................................................................................... 14During installation ........................................................................................ 16During mounting ........................................................................................... 17The COM Programming Interface .................................................................. 18Example connection (FC34 to external computer) ........................................ 19Writing and testing a program ...................................................................... 20Operation and testing ................................................................................... 20Expanding the FEC’s to 40 I/O channels ....................................................... 22COM and EXT interface pin assignment ........................................................ 24Example crossover cable connection ............................................................ 25Network connector (TP) pin assignment ...................................................... 26Networking of two FEC’s ............................................................................... 27Network configuration with 10BASE T .......................................................... 28Network communication ............................................................................... 29Field PC Net Communication ......................................................................... 30TCP/IP communication ................................................................................. 31Festo Windows applications for TCP/IP communication. ............................. 31Remote expansion. ....................................................................................... 31During wiring ................................................................................................. 32

Page 4: fec_fc34

Page 4FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Transistor output wiring diagram ................................................................. 34Relay output wiring diagram ......................................................................... 35Output behaviour if overload/short circuit occurs ....................................... 36Important notes ............................................................................................ 37Limited PC compatibility ............................................................................... 39Software requirements ................................................................................. 40Differences to industry standard PC ............................................................. 41Additional features compared to industry standard PC ............................... 41

Special functions ......................................................................................................................... 42

RUN/STOP switch ......................................................................................... 42Status LED ..................................................................................................... 42Fast counters ................................................................................................. 42Interrupt inputs ............................................................................................. 43Incremental encoder ..................................................................................... 43The timer function ......................................................................................... 44Extension interface/remote expansion ......................................................... 44

Page 5: fec_fc34

Page 5Page 5Page 5Page 5Page 5IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Ethernet network .......................................................................................... 45

Fault fixing ................................................................................................................................... 47

Troubleshooting information ........................................................................ 47What do I do if….. .......................................................................................... 47Error word ..................................................................................................... 50List of error numbers generated by system .................................................. 50

Programming ............................................................................................................................... 52

Programming in AWL and KOP ...................................................................... 53The Command Interpreter (CI) ...................................................................... 53Operands ....................................................................................................... 54Summary of residual operands ..................................................................... 56Drivers and modules ..................................................................................... 57Multitasking/program execution .................................................................. 57PLC programming languages ........................................................................ 58

Page 6: fec_fc34

Page 6FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Error handling ............................................................................................... 58Network communication ............................................................................... 59

Appendix: Command Interpreter (CI) ........................................................................................... 61

Access to command interpreter (CI) ............................................................. 61Command structure: ..................................................................................... 63Commands .................................................................................................... 64Parameters .................................................................................................... 65CI example ..................................................................................................... 67

Appendix: General ....................................................................................................................... 68

Manual change status ................................................................................... 68Hardware change status ............................................................................... 68Technical data ............................................................................................... 69Ordering information .................................................................................... 73

Page 7: fec_fc34

Page 7Page 7Page 7Page 7Page 7IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

ForewordForewordForewordForewordForeword

Customer service experience

As far as we are concerned, our company’sreputation as an innovative source of ideasrepresents confirmation of our standards andalso an obligation to maintain them. Our repu-tation is based on communicating with ourcustomers and carefully monitoring the mar-ket.

Our customers make extremely high demandswith regard to reliability, service life, flexibili-ty, ease of operation and environmental com-patibility. They also expect expert advice, ra-pid service, qualified support and product trai-ning.

We have been providing software, hardware,service and information for industrial PC’s andautomation equipment for 15 years. Reliabledelivery and service are combined with a con-tinuously expanding product range and ever-decreasing intervals between new innovati-ons.

Our target is customer satisfaction. Our custo-mers’ success, and therefore our own, is basedon consistent quality management, a uniquerange of products and highly motivated staffwho are full of ideas.

Page 8: fec_fc34

Page 8FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

About this manual

We would like to thank you for choosing to buythe FEC FC34-FST module. We are pleased towelcome you as one of our customers.

Please read through this manual carefully bebefore beginning with the installation. The FECFC34-FST module is designed to be a low-cost,versatile industrial controller that is quick andeasy to install and can be operated by person-nel with limited experience of programmablecontrollers.

This manual contains text, diagrams and ex-planations that show the reader how the mo-dule is correctly installed and safely used andoperated. Before installing the module the

contents of this manual must have been readand understood. If in doubt about the operati-on or use of the module, please contact yournearest BECK IPC GmbH office.

FEC FC34-FST - The Control CPU

Pure control technology, 12 inputs, 8 outputswith status LED, network, with fast counterinputs, with connection facility for an FST-PLCas an I/O module (direct switching of 230 V !).All of this fits into an FC34-FST!

Page 9: fec_fc34

Page 9Page 9Page 9Page 9Page 9IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

CE Confirmation

Manufacturer BECK IPC GmbH declares in soleresponsibility that the product

FEC FC34-FST

complies with directive 89/336/EWG in har-monisation with the following standards:

Noise immunity EN 50082-2

Emitted interference EN 50081-2

This is a class A device. It can cause transmis-sion interference in built-up areas. In this caseit is the responsibility of the user to take ap-

propriate measures and bear any costs incur-red by problems of this nature.

Important installation instructions

A shielded cable must be used. Cables with abraided shield (80% coverage) are suitable.The shield should be connected at the moduleend over a large area and have low resistance.

The device complies with protection class III.

Please only use power supplies that guaran-tee safe separation of the operating voltage asper IEC742/EN60742/VDE055, PELV with atleast 4 kV of insulation strength. Switchingpower supplies with safety insulation as perEN60950/VDE 0805 are permitted.

Page 10: fec_fc34

Page 10FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

User safety and device protection

This manual is intended for the use of trainedspecialists when installing the FEC FC34-FSTmodule. Safety guidelines are defined in theEuropean directives for machinery, low volta-ge and EMC. Throughout this manual, symbolsare used to highlight information relating tothe user’s personal safety and the safeguar-ding of the machine’s integrity. Whenever anyof these symbols are encountered, the asso-ciated note should be read and understood.

Warnings

• The identified danger couldpossibly cause damage to per-sons or property.

• Point of further interest or moredetailed explanation.

Page 11: fec_fc34

Page 11Page 11Page 11Page 11Page 11IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Installation and useInstallation and useInstallation and useInstallation and useInstallation and use

Area of use

The FEC FC34-FST is an FEC component thathas been designed for process control.

Scope of delivery

The scope of delivery of the module includes:

• one FEC FC34-FST module

Up-to-date information such as example pro-grams and/or drivers etc. can be obtainedfrom Internet address

http://www.beck-ipc.com

Page 12: fec_fc34

Page 12FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

The dimensions of the FEC

RUN STOP

EXT. COM

130,0

53,0

122,54,

0

80,0

35,0

0 1 02 13 24 35 6 7

OUT

S1S0IN

RUN

POWER

SENSORSUPPLY

POWER

40 1 2 3 1210 11 13

24V 0V

24V 0V

FC-34

C0 0 1 2

0 1 2

75

C+

6

3

3

4

4

5

5

6

6

7

7

C-

TP

Page 13: fec_fc34

Page 13Page 13Page 13Page 13Page 13IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Start-up requirements

• One FEC FC34-FST module (scope of deli-very)

• PS1 PSE4 power supply

• SM14 connecting cable between FEC FS34-FST and external computer, consisting of anull modem cable (PS1 ZK11) and an ad-apter cable (PS1 ZK36).

• External computer such as PC, laptop,toetc. with a free COM port (preferably aWindows system).

• Module-specific software with drivers an-dexample programs. This software can bedownloaded from Internet address

http://www.beck-ipc.com

The software is also available on CD.

Page 14: fec_fc34

Page 14FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

FEC components

RUN STOP

EXT. COM

0 1 02 13 24 35 6 7

OUT

S1S0IN

RUNPOWER

SENSORSUPPLY

POWER

40 1 2 3 1210 11 13

24V 0V

24V 0V

FC-34

C0 0 1 2

0 1 2

75

C+

6

3

3

4

4

5

5

6

6

7

7

C-

TP

1 2 3

9 10 11 12 13 14 15

4

5

8

7

6

1 Sensor supply 24 V DC 100 mA

3 RUN/STOP switch4 Analog potentiometer (trimmer)5 Link/traffic LED for network activity6 Power LED (power supply LED indicator)7 10BASE T network connection8 RUN LED (LED indicator for run/error)9 Power supply 24 V DC

10 Power supply 0 V11 Function earth12 Relay/transistor supply 24 V DC13 Relay/transistor supply 0 V DC14 Connector for expansions (EXT)15 Serial interface (COM)

2 Sensor supply 0 V

Page 15: fec_fc34

Page 15Page 15Page 15Page 15Page 15IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

RUN STOP

EXT. COM

0 1 02 13 24 35 6 7

OUT

S1S0IN

RUNPOWER

SENSORSUPPLY

POWER

40 1 2 3 1210 11 13

24V 0V

24V 0V

FC-34

C0 0 1 2

0 1 2

75

C+

6

3

3

4

4

5

5

6

6

7

7

C-

TP

16

17

30 31 32 33 34 35 36 37 38

18

2519

20 22 24 28

23 2921

26

27

30 Common earth A0

32 Relay output A0.133 Transistor output A0.234 Transistor output A0.335 Transistor output A0.436 Transistor output A0.537 Transistor output A0.638 Transistor output A0.7

31 Relay output A0.0

16 Input E0.0

20 Input E0.422 Input E0.624 Common earth E025 Input E1.027 Input E1.229 Common earth E1

17 Input E0.118 Input E0.2 19 Input E0.3

21 Input E0.523 Input E0.7

26 Input E1.128 Input E1.3

Page 16: fec_fc34

Page 16FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

During installation

When you are installing the FEC FC34-FSt mo-dule, please pay attention to the ambient con-ditions in which the device will normally beoperating.

Please do not install the FEC FC34-FST module

••••• in areas that are subjected to excessiveamounts of dust, oil spray, conductive dustor corrosive gas;

••••• in areas that are subjected to shock orvibration;

••••• in areas that are subjected to high tempe-ratures, direct sunlight, moisture or rain;

••••• near high voltage devices or cables.

Page 17: fec_fc34

Page 17Page 17Page 17Page 17Page 17IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

During mounting

Always install the device as far away as possi-ble from high voltage devices and large powersupplies.

Please ensure that no pieces of wire,fillings or swarf fall into the devicewhen you are drilling holes or con-necting wires.

Do not install the device immediately above aheat-generating source, such as a heater, cur-rent converter or high wattage resistor.

If the ambient temperature in the switch cabi-net is above 55ºC, a ventilator must be instal-led in order to provide external ventilation.

Page 18: fec_fc34

Page 18FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

The COM Programming Interface

Connect the FEC FC34-FST module to the de-velopment computer using the SM14 connec-ting cable. In order to do this, connect one endof the cable to the socket marked COM. Con-nect the other end to a free serial interface onyour development computer.

Page 19: fec_fc34

Page 19Page 19Page 19Page 19Page 19IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Example connection (FC34 to external com-puter)

1

2

3

1 FEC FC34

3 External PC (Laptop)2 SM14 connecting cable

Page 20: fec_fc34

Page 20FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Writing and testing a program

Write a program using a PC that is equippedwith the Festo FSTIPC/FEC program.

Check the program. A syntax check is carriedout automatically as soon as you load theproject from the programming device into theFEC. Existing program errors that are found bythe syntax check must be rectified before theproject can be loaded.

In order to test the wiring or the output de-vices, each output can be forced on and offusing the programming device whilst the FECFC34-FST is not running a program.

A loaded program is run by setting the RUN/STOP switch to RUN. The status LED changescolour from orange (or red) to green.

Operation and testing

Current: ON, FEC FC34-FST: STOP

The FEC FC34-FST module is fitted with aninternal RUN-STOP switch. A so-called remoteRUN/STOP switch can be used as an additio-nal option. This remote RUN/STOP switch is anexternal switch that is connected to one of themodule’s inputs. If this facility is to be used,this input can be defined in the configurationas an additional RUN/STOP switch.

Page 21: fec_fc34

Page 21Page 21Page 21Page 21Page 21IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Current: ON, FEC FC34-FST: RUN

If the RUN/STOP switch is set to RUN (if noremotely operated RUN/STOP switch is beingused), the status LED turns green and themodule starts program execution. The timer,counter and data register settings can be defi-ned as an additional RUN/STOP switch in theconfiguration.

If the RUN/STOP switch is set to STOP (even ifa remotely operated RUN/STOP switch is beingused) the status LED turns orange (or red if anerror has occurred).

Flags or digital outputs can be modified duringoperation using CI commands. However, thesevalues may be changed again by the program.

Page 22: fec_fc34

Page 22FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Expanding the FEC’s to 40 I/O channels

The RUN/STOP switch on the remote unit (FECFC20/30 without its own control program) mustalways be set to STOPSTOPSTOPSTOPSTOP.

It should be ensured that the remote unit doesnot have any files called “PROJECT.RUN” andSTARTUP.BAT” in the directory on drive B (de-livery state).

Procedure for checking the memory contents:

• Start FSTIPC

• Utilities › Program execution › Host ‹-› IPCfile transfer

• F1: from PC

• F7: Enter IPC drive “B”

• Check whether the “PROJECT.RUN” and“STARTUP.BAT” directories are present.

• If yes, delete both files using F1

• Press F8: Exit to exit terminal program

• Switch FEC FC20/30 off and on again

Expansion cables should only be connectedand disconnected when the power is switchedoff.

Page 23: fec_fc34

Page 23Page 23Page 23Page 23Page 23IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

The power supply for the master/remote sy-stem must be provided from the same voltagesource and should be on the same fuse. Theuse of separate power supplies for the masterand the remote is not permitted.

Page 24: fec_fc34

Page 24FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

COM and EXT interface pin assignment

1

2

3

4

5

6

Pin no.

2 23 34 45 5

1 1Signal name

+5 V

TXDGND

RXDCTS

6 6 RTS

Page 25: fec_fc34

Page 25Page 25Page 25Page 25Page 25IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Example crossover cable connection

RUN STO P

EXT. COM

RUN STO P

2

1

4

0 1 02 13 24 35 6 7

OU T

S1S0IN

RUN

POWER

SENSORSUPPLY

POWER

40 1 2 3 1210 11 13

24 V 0V

24 V 0V

FEC-FC30C0 0 1 2

0 1 2

75

C+

6

3

3

4

4

5

5

6

6

7

7

C-

5

3

EXT. COM

0 1 02 13 24 35 6 7

OU T

S1S0IN

RUN

POW ER

SENSORSUPPLY

POW ER

40 1 2 3 1210 11 13

24 V 0V

24 V 0V

FC-34

C0 0 1 2

0 1 2

75

C+

6

3

3

4

4

5

5

6

6

7

7

C-

T P

2

1 The FEC FC20 or FEC FC30 inputsand outputs can be added tothose of the FEC FC34 using aFEC KSD4 crossover cable, whe-reby it is important to note thatthe FEC FC34 must be used asthe master and the FEC FC20 orFEC FC30 must be used as a sla-ve (remote unit). Drive B on theremote unit must not contain anapplication program.

1 Local sensor supply +24 V DC

3 Crossover cable FEC KSD44 FEC FC34 as (master)5 FEC FC30 as slave (remote)

2 Local voltage supply +24 V DC

Page 26: fec_fc34

Page 26FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Network connector (TP) pin assignment

2

1

3

4

5

6

7

8

Pin no.

2 23 34 45 5

1 1Signal name

TD+

RD+TD-

--

7 76 6 RD-

-8 8 -

Page 27: fec_fc34

Page 27Page 27Page 27Page 27Page 27IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Networking of two FEC’s

11

88

1 Pin 1

3 Pin 34 Pin 45 Pin 56 Pin 6

2 Pin 2TD+TD-

no usedRD+

no usedRD-

7 Pin 7 8 Pin 8 no used

no used

Page 28: fec_fc34

Page 28FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Network configuration with 10BASE T

9

9

9

10

1111

11

10 Hub (star distributor)9 FEC FC34

11 Twisted pair cable

Page 29: fec_fc34

Page 29Page 29Page 29Page 29Page 29IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Network communication

FEC FC34-FST module network communicati-on is supported by two drivers: the Field PCNet driver and the TCP/IP driver. In order touse these drivers the following must be obser-ved:

For Field PCNet functionality (only with the3.43 ms timer) the following files must bepresent in directory FBLIB.FEC:

• mpme • mprcv• mpregt • mpstat• mpsucc • mpver• mpxmit

In the RUNTIME.FEC directory:

• fpcniof.exe• fpcnudp.com• fpcnudp.dsc• tmr13_3.com• fpcnudpd.hlp (German version)• fpcnudpg.hlp (English version).

Max. segment length:Max. number of transceivers per segment:

Min. distance between transceivers:

100 m

Segment lengths

hub-dependent

any

Page 30: fec_fc34

Page 30FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

For TCP/IP functionality (Internet) (alsowith the 4.58 ms default timer) the follo-wing files must be present in theRUNTIME.FEC directory:

• tcpipdrv.exe• tcpipdrv.dsc (tcpipfec.dsc)• tcpip_d.hlp (German version)• tcpip_gb.hlp (English version)

If required the TCP/IP modules can also beused (IP_IP, IP_ALIVE etc.).

Update files can be found on the enclosed datamedium.

Field PC Net Communication

Field PC Net is used to network several stati-ons. Each station has its own project. Enter the”FPCNUDP” driver in each project using thedriver configuration tool.

The system can be configured from these sta-tions using the Field PC Net configuration tool(a constituent of Festo Software Tool). Definethe components to be transferred and save theproject.

Page 31: fec_fc34

Page 31Page 31Page 31Page 31Page 31IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

TCP/IP communication

The FEC FC34-FST module can be linked (net-worked) to the in-house network using theTCP/IP driver. The FEC FC34-FST can then beaccessed by other computers using the TCP/IPprotocol. To do this, enter the ”TCPIPDRV”(”TCPIPFEC”) driver in the driver configurationtool.

Festo Windows applications for TCP/IPcommunication.

In order to carry out TCP/IP communicationbetween the FEC FC34-FST and external com-puters you need a program on the external

computer that creates a DDE interface to anExcel application. This program is called the”IPC DATA Server” and is installed from Win-dows folder ”Festo Software”. Another usefulprogram is called ”IPC TCPIP Application”. Thisprogram contains a facility for carrying outsmall tests using TCP/IP communication andsending CI (Command Interpreter) commandsto FST computers with TCP/IP functionality.

Remote expansion.

If you would like to expand the FEC FC34-FST itis possible to use the FEC FC20-FST or FECFC30-FST as a remote expansion.The followingitems must be observed:

Page 32: fec_fc34

Page 32FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

• The FEC FC34-FST may not be the slave.

• The default 4.58 ms timer must be loadedon the FEC FC34-FST. The remote expansi-on will not work with the 3.43 ms timer.

• The remote expansion cannot currently beused at the same time as network operati-on.

During wiring

Install the input and output signal wires inseparate cable conduits and avoid bunchingthem together.

Do not use the same multi-core cable for wi-ring the signal inputs and outputs.

Page 33: fec_fc34

Page 33Page 33Page 33Page 33Page 33IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

If the power supply terminals are wronglyconnected, a short circuit betweenthe incoming direct current wiresand the power supply cable or ashort circuit within the outgoing wires can cause considerable damage to the module.

Warning

Before switching on the power, check the po-wer supply and earth connections and the in-coming and outgoing connections.

Please ensure that none of the installationscrews are loose. Make sure that no screwterminals for external connections are loose.There must be no visible damage to externalconnections.

Caution:

Please ensure that the power is switched offbefore you replace cables or carry out otherwork.

If you need to measure the maximum insulati-on voltage and the insulating resistance of theFEC FC34-FST module, disconnect the inco-ming and outgoing wires and the power cablefrom the module and carry out the measure-ments across all the terminals and the earthterminal using a common point.

Page 34: fec_fc34

Page 34FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Transistor output wiring diagram

+5 VC+

OutputOUT 2 ... OUT 7

C-

1) Analog current restriction to 4 A / 200 ms Analog short circuit/overload protection, thermal only

KS1)

+24 V

0 V

Lam

p m

otor Po

wer

sup

ply

externalinternal

Page 35: fec_fc34

Page 35Page 35Page 35Page 35Page 35IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Relay output wiring diagram

+5 VC+

OutputOUT 0 ... OUT 1

C-

KS

+24 V

0 V

Pow

er s

uppl

y

internal extern

C0

Page 36: fec_fc34

Page 36FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Output behaviour if overload/short circuitoccurs

Transistor outputs A0.2 to A0.7 are indepen-dently protected against short circuits andoverloads.

If short circuit or overload current is applied,the switching transistor heats up. The over-heating fuse switches the output concernedoff, meaning that the switching transistor cancool down again. Subsequently the outputconcerned is reactivated. If overload current isstill present after reactivation, the processstarts again from the beginning.

The process cycle time depends on the magni-tude of the load. If there is only a minimaloverload, the cycle time can be up to severalminutes, and if there is a major overload thistime may be less than 1 second.

Page 37: fec_fc34

Page 37Page 37Page 37Page 37Page 37IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Important notes

• The maximum signal voltage atthe digital inputs may not exceedthe supply voltage

• Do not connect any of the unusedterminals.

• If loads such as forward/back-ward motor contactors are pre-sent that may be dangerous ifthey are switched on simultane-ously, external locking mecha-nisms and programmable locksshould be provided in order toprevent such loads from beingactivated simultaneously.

• For EMERGENCY STOP functionsthe output loads should be swit-ched off using a switch outsidethe module that disconnects thecurrent from the output termi-nals.

• If you connect an EMERGENCYSTOP circuit, please be sure tocomply with local wiring and safe-ty regulations.

• Connecting a power surge sup-pressor parallel to an inductiveload reduces the generation ofelectrical interference.

Page 38: fec_fc34

Page 38FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

• The supply voltage is not protec-ted against reverse polarity.Check the polarity of the supplyvoltage before starting up.

Page 39: fec_fc34

Page 39Page 39Page 39Page 39Page 39IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Limited PC compatibility The AM186ES/ED chip set that is used in theFEC FC34-FST module is only PC compatible toa limited extent.

Component If yesPC compatible x86 core8250 UART-FIFO

� 80186-

n/a8254 PIT8259 PIC

--

CMOS RAM6845 CRTC

-n/a

8042 KEYB8272 FDC

n/an/a

If no Workaround (SW)

IDE n/aFC34� NE2000MAC

Status LEDDL MiniBIOSBIOS

Power on LED �

AMD-specific

AMD-specificAMD-specific

XT

Fossil driverSerial port DMAPS1 service interrupt

Flash memoryRemote consoleRemote consoleFlash disk

PDS1 service interrupt

Packet driverPS1 service interrupt

Page 40: fec_fc34

Page 40FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Software requirements

BIOS: Datalight MiniBIOS

DOS: Datalight ROM-DOS 5.0 (equivalentto MS-DOS 5.0); no INT 2Fh support

Function TaskSub funct.

10h 0Eh11h12h14h

TTY char outputGet equipmentGet memory sizeSerial I/0(Fossil-Treiber)

16h 016h 116h 219h1Ah 01Ah 11Ch

Ready TTY charGet TTY statusGet TTY flagsReboot systemGet tick countSet tick countTimer tick (DOS = 55 ms) FST = 13ms)

Page 41: fec_fc34

Page 41Page 41Page 41Page 41Page 41IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Differences to industry standard PC

••••• Datalight MiniBIOS with reduced BIOS sup-port (see previous page for list of BIOSfunctions

••••• Datalight ROM DOS (equivalent to MS-DOS5.0)

••••• No keyboard and video controller/videoRAM available

••••• Standard I/O diverted to a terminal usingserial interface (DOS INT 21 and BIOS INT10)

••••• Approx. 480 Kbytes of free RAM available

••••• On-board flash disk (approx. 100 KB free)

••••• Programming of ”On-chip peripherals”(PIC, timer, UART) completely differentfrom standard PC

••••• Different IRQ number assignments

Additional features compared to industrystandard PC

••••• Service interrupt support of FC34 functions(digital I/O, counters, Ethernet network,status LED).

Page 42: fec_fc34

Page 42FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Special functionsSpecial functionsSpecial functionsSpecial functionsSpecial functions

RUN/STOP switch

The RUN/STOP switch is used to influence theexecution of the application program. If theswitch is set to RUN the program is executed,and if it is on STOP the program is halted.

Status LED

The status LED indicates the current programexecution status:

Fast counters

Inputs E1.2 and E1.3 can be independentlyconfigured as fast counter inputs and used tocount counter pulses up to a frequency of 2kHz. The counters are 16-bit (0 to 65535) andare configured and evaluated using the provi-

Green

Orange

Red if an error has occurred

if the program is running correctlyif the application program has been stopped or has terminated

Page 43: fec_fc34

Page 43Page 43Page 43Page 43Page 43IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

ded program library. Inputs that are configu-red as counters can also be read in as normaldigital inputs.

Interrupt inputs

Inputs E1.0 and E1.1 can be individually confi-gured as interrupt inputs. Like the counterinputs, the interrupt inputs can be softwareconfigured and high level language user routi-nes used for interrupt handling. Inputs thatcan be configured as interrupt inputs can alsobe read in as normal digital inputs.

Incremental encoder

The FEC FC34-FST has a 16-bit software incre-mental encoder (see AB direction detection)that can process counter pulses of up to 200Hz. Connection takes place using the two in-terrupt inputs E1.0 and E1.1. An optional refe-rence switch can be connected using inputE0.7.

The incremental encoder is configured andevaluated using the program library.

Page 44: fec_fc34

Page 44FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

The timer function

The FEC FC34-FST has an extremely flexibletimer function that makes it possible to confi-gure up to 32 32-bit timers. The time base foreach timer can be adjusted in multiples of 4.58ms using a configurable 16-bit distributor. Thismeans that times ranging from 4.58 ms to(theoretically) several years can be measured.

The timers are configured and evaluated usingthe program library.

Extension interface/remote expansion

The FEC FC34-FST module has an extensioninterface via which the FC20/FC30 module canbe connected as a remote expansion or anotherserial device with max. 115 Kbaud can be ac-tuated.

In order to connect an FC20/FC30 as a remoteexpansion you require an FEC KSD4 cable. Theremote expansion is configured and actuatedusing the provided program library. The mo-dule (FEC FC34-FST) on which the remotefunction is software-activated acts as a masterstation and contains the control program. Themaster station has read/write access to the

Page 45: fec_fc34

Page 45Page 45Page 45Page 45Page 45IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

inputs and outputs and the RUN/STOP switchon the remote and slave stations. The slavestation cannot have its own control program.

Since both stations are connected via a TTLinterface, this may only be implemented usingan original FEC KSD4 cable (max. 30 cm). If thecable is any longer, reliable operation of theremote connection is no longer guaranteed. Ifstrong EMC radiation is present, both of theconnected stations should be installed in ascreened switch cabinet.

If a serial device is to be connected to theextension interface, please remember that theinterface produces TTL signals and is not gal-vanically separated. If you wish to convert thesignal to a level of 24 V, for example, you mustdo this yourself using suitable hardware de-pending on the application.

The extension interface is actuated by a supp-lied driver and the provided program library.

Ethernet network

The FEC FC34-FST has network functions thatcan be used using the 8-pin RJ45 connector(10Base T).

Page 46: fec_fc34

Page 46FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

The communication interface can used by theuser for TCP/IP communication or in a compre-hensive network (particularly for ST - so-calledField PC Net communication).

The standard settings are:

Interrupt 3

Port 0x300

Page 47: fec_fc34

Page 47Page 47Page 47Page 47Page 47IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Fault fixingFault fixingFault fixingFault fixingFault fixing

Troubleshooting information

Please ensure that the installation instruc-tions in the manual have been correctly follo-wed. Check whether the FEC has been connec-ted using undamaged cables that comply withthe relevant standards. Furthermore, youshould also make sure that the FEC is beingprovided with the correct supply voltage.

What do I do if…..

Problem

The FEC FC34-FST module doesn’t react.

Remedy

Restart the module. Disconnect the power sup-ply to the module for several seconds.

Problem

No green status LED when the RUN/STOPswitch is set to RUN.

Page 48: fec_fc34

Page 48FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Remedy

Check whether an executable program hasbeen integrated into the FEC FC34-FST modu-le.

Problem

The status LED goes green as soon as the RUN/STOP switch is set to RUN, but the programdoes not start working.

Remedy

Perform the following test: check your remoteRUN/STOP switch settings (configured in theprogramming software). This RUN/STOPswitch may be set to “STOP”.

Problem

The status of the I/O control LED does notcorrespond with the actual output status.

Page 49: fec_fc34

Page 49Page 49Page 49Page 49Page 49IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Remedy

Check whether the output device is workingcorrectly. Check whether the required voltageis present at the output terminals.

Problem

The operating status of the input device doesnot correspond with the status of the I/O con-trol LED’s for this input.

Remedy

Check that the input device is working correct-ly, check for loose contacts or other irregulari-ties.

An input that is switched on or off within a timeperiod that is shorter than the operating cycleor the module sampling time may not be de-tected.

Problem

Status LED is red.

Remedy

This indicates a program error or an internalerror. The error number can be read out usingthe CI (Command Interpreter test system in theFEC FC34-FST module) in the FSTIPC/FEC soft-ware package or the service unit (optional).

Page 50: fec_fc34

Page 50FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Error word

At present there is no automatic detection oferrors in the connected inputs and outputs. Inapplications where this can lead to problems,appropriate measures must be taken (an addi-tional program with a function test, externalsignal detection, signal feedback etc.). Suita-ble additional error numberscould also be produced in theapplication program.

List of error numbers generated by system

The following error numbers are currently ge-nerated by the FEC FC24-FST module opera-ting system:

No.Program 0 not found at start6Program not found7

Error text

9 Unable to start programI/0 error11

34 Arithmetic error (zero division)Illegal module call36

57 Project not found

Page 51: fec_fc34

Page 51Page 51Page 51Page 51Page 51IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

If an error handling program is activated whenan error occurs, this must be defined in theconfiguration. The error program is a programwritten by the user in the form of a list ofinstructions or a contact plan. This programshould not be active during normal operation(see FSTIPC/FEC software documentation formore information).

The FEC FC34-FST module also allows an erroroutput to be set if an error occurs. If this facilityis being used, the output must also be speci-fied in the configuration

Page 52: fec_fc34

Page 52FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

ProgrammingProgrammingProgrammingProgrammingProgramming

The Festo FST run-time kernel FSTPCR22.EXEfor the FEC FC34-FST module is already instal-led and is started automatically. This containsPLC characteristics that are always required.The kernel is also responsible for loading andrunning the user program. Other parts of a PLCoperating system can be subsequently loadedinto the FEC FC34-FST module as modulesand/or drivers together with a user project.This is done using a development computer(e.g. standard PC or laptop) and the Festo FSTsoftware. The development computer shouldbe connected to the COM port of the FEC FC34-FST module via a null modem cable (see abo-ve).

The characteristics of the IPC PLC operatingsystem and the FST software for producingindustrial PC PLC programs are described indetail in the manuals supplied with the FSTsoftware. Here is a brief description of thecontents thereof:

Page 53: fec_fc34

Page 53Page 53Page 53Page 53Page 53IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Programming in AWL and KOP

The AWL (instruction list) and KOP (contactplan) are programmed in accordance with theFesto FST software rules. A description of theFST software can be found in the relevant do-cumentation accompanying the software. Ma-nuals containing a detailed description of howto program instruction lists and contact plansare also available. More information can beobtained from your nearest Festo branch.

The Command Interpreter (CI)

All FESTO controllers have a command inter-preter. It is usually referred to as the “CI”. TheCI is a man-machine interface (MMI). However,it is also frequently used manually because ithas an extremely easy-to-use interface. CI com-mands are a constituent of the Festo softwaretool. They are entered on the developmentcomputer and transferred to the FEC FC34-FSTmodule via the link to the FEC as a PLC stationusing a COM port. The results are also transfer-red to the development computer by the mo-dule, where they are displayed. The CI can alsobe operated using a terminal or a terminalemulator via the serial interface (COM). Thecommand interpreter on the serial interface(COM) is also used by the FST software for

Page 54: fec_fc34

Page 54FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

many other tasks. The different program com-ponents of the FST software handle communi-cation with the connected industrial PC auto-matically and provide considerably better,more convenient user interfaces.

Access to the controller can be password pro-tected. If a password has been specified, allwrite access and driver access is blocked in theCI.

Operands

The FEC has the following operands, which canbe accessed using the FST software or the CI.

Page 55: fec_fc34

Page 55Page 55Page 55Page 55Page 55IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

OperandEW0 to EW1 with EA0.0 to EA0.7

AW0 with EA0.0 to EA0.7FW and FFI for each programMW0 to MW9999 with Mx.0 to Mx.15R0 to R255FE0 to FE255, FE32 to FE38 for each programT0 to T255 (and TV and TW for each TE, TA timer)

Input wordRange

Z0 to Z255 (and ZV and ZW for each counter)P0 to P63PS0 to PS63BAF0 to BAF99 (predefined by Festo)BAP0 to BAP99 (can be user-defined)

Error wordInitialisation flagFlag wordsRegistersFunction unitsTimersCountersProgramsProgram statusFunction modulesProgram modules

Output word

Page 56: fec_fc34

Page 56FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Summary of residual operands

Operand Operand numberOutput word (AW)Register (Rx)Timer selection (TV)Counter (Zx)Counter selection (ZV)

0 to 1

0 to 1270 to 127

Counter word (ZW)Flag word (MW)

0 to 1270 to 255

0 to 1270 to 127

Page 57: fec_fc34

Page 57Page 57Page 57Page 57Page 57IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Drivers and modules

The programming of drivers and modules isdescribed in the FST IPC 3.2 manual.

Multitasking/program execution

The module’s PLC operating system has multi-tasking capability. It can sequentially workthrough the processing cycles (tasks) of sever-al programs. During the execution of aprogram’s tasks the other programs are notrunning. However, the programs are executedso quickly and the change to the next program(task change) is so rapid that the programsseem to be running synchronously. This isknown as pseudo-parallel program execution.

A PLC application can contain up to 64 pro-grams that can also be synchronously execut-ed. Program 0 is automatically started after

Page 58: fec_fc34

Page 58FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

start-up. These in turn (i.e. any program) canactivate, stop or reset other programs usingthe P/PS tool or modules.

PLC programming languages

In FST-IPC control programs can be formulatedin the form of contact plans and instructionlists (with integrated interface programming).Program development is supported by a user-friendly editor, and another tool checks thesyntax of the programs.

Error handling

Errors can occur at any time in an automatedsystem, whereby a distinction should be madebetween programming errors and system er-rors. An example of a programming error is azero division, and an example of a system erroris an I/O module failure.

The FST IPC PLC operating system detects manyerrors and deals with them in a defined man-ner. The user is provided with a facility forparticipating in error handling and possibly insolving the problem. This is done using theerror word (FW) and the error program.

Page 59: fec_fc34

Page 59Page 59Page 59Page 59Page 59IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Network communication

FEC FC34-FST module network communicationis supported by two drivers: the Field PC Netdriver and the TCP/IP driver. In order to usethese drivers the following must be observed:

For Field PCNet functionality (only with the3.43 ms timer) the following files must be pre-sent in the FBLIB.FEC directory:

• mpme• mpregt• mpsucc• mprcv• mpstat• mpver• mpxmit

In the RUNTIME.FEC directory:

• fpcniof.exe• fpcnudp.com• fpcnudp.dsc• tmr13_3.com• fpcnudpd.hlp (German version)• fpcnudpg.hlp (English version).

For TCP/IP functionality (Internet) (also withthe 4.58 ms default timer) the following filesmust be present in the RUNTIME.FEC directo-ry:

• tcpipdrv.exe• tcpipdrv.dsc (tcpipfec.dsc)• tcpip_d.hlp (German version)• tcpip_gb.hlp (English version).

Page 60: fec_fc34

Page 60FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

On request the TCP/IP modules can also beused (IP_IP, IP_ALIVE etc.).

Field PC Net communication

Field PC Net is used to network several stati-ons. Each station has its own project. Enter the”FPCNUDP” driver each project using the driverconfiguration tool.

The system can be configured from these sta-tions using the Field PC Net configuration tool(a constituent of Festo Software Tool). Definethe components to be transferred and save theproject. More information can be found in the“Field PC Net configuration tool” document.

TCP/IP communication

The FEC FC34-FST module can be connected tothe in-house network using the TCP/IP driver.The FEC FC34-FST can then be accessed byother computers using the TCP/IP protocol. Todo this, enter the ”TCPIPDRV” (”TCPIPFEC”)driver in the driver configuration tool.

Page 61: fec_fc34

Page 61Page 61Page 61Page 61Page 61IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

The command interpreter is a constituent ofthe FEC operating system and represents itsuser interface.

The CI is used for:

• Testing, service, diagnosis and start-up,• Uploading and downloading files

The command interpreter (CI) provides moni-toring functions for the entire control system.

In the case of programs and operands the usercan

start and stop programs individually or dis-play all programs display and modify operands.

Access to command interpreter (CI)

If a dialog device is connected to the FEC theuser must proceed as follows in order to ac-cess the CI:

Appendix: Command Interpreter (CI)Appendix: Command Interpreter (CI)Appendix: Command Interpreter (CI)Appendix: Command Interpreter (CI)Appendix: Command Interpreter (CI)

Page 62: fec_fc34

Page 62FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

• Connect FEC to power supply• Switch on dialog device• Access CI:

The dialog device should be set to the correctbaud rate (default 9600 baud). The baud rateis automatically measured after a BREAK si-gnal or after switching on the power if thesystem memory does not contain a valid baudrate.

Input format

CTRL T CTRL T CTRL T CTRL T CTRL T

The CI replies with:

The CI can still be accessed if the controllerdisplays an error. However, this error must beremedied before any other task can be perfor-med.

IPCVm.n(m.n = operating system no.)

›_

Page 63: fec_fc34

Page 63Page 63Page 63Page 63Page 63IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Command structure:

A complete command always consists of aletter for identifying the command, nearly al-ways a parameter and sometimes a parametervalue.

The command is not case-sensitive and mustbe terminated with ‹CR›.

Input format

‹CI Letter›[‹Parameter› [Parameter value]]

Page 64: fec_fc34

Page 64FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Delete wrong entries

Wrong entries can be deleted with Backspace(CTRL H) before confirming with ‹CR›.

Commands

The following list contains a selection of theFEC command interpreter commands

Command letter and command Description = display operandsD = DISPLAY Display contents/status/operands

M = MODIFY = modify operandsR = RUN = start or continue Start programS = STOP Stop programX = EXIT Exit CI

Page 65: fec_fc34

Page 65Page 65Page 65Page 65Page 65IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Parameters

Various parameters must be entered depen-ding on the operands with which a command isto be used.

Parameter Parameter valueMeaningA x.yA WxE x.yEW xF

Output 0.0 to 0.7Output value 0Input 0.0 to 0.7; 1.0 to 1.3Input value 0 to 1; 2 to 255 for trimmers and fast countersError

M x.yMW x

FlagFlag word

0.0 to 9999.150 to 9999

Page 66: fec_fc34

Page 66FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Parameter Parameter valueMeaningP xPS xR x

Program 0 to 63Program status 0 to 63Register 0 to 255

TW xZ x

Timer wordCounter

0 to 255 0 to 255

T xTV x

Timer 0 to 255 Timer preselection 0 to 255

ZV xZW x

Counter preselection 0 to 255 Counter word 0 to 255

Page 67: fec_fc34

Page 67Page 67Page 67Page 67Page 67IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

CI example

Displays

Display status of single-bit operands, output 0.6 DA0.6‹CR› CR reply = 0 or 1Display status of single-bit operands, input 1.2 DE1.2‹CR› CR reply = 0 or 1Display status of timer 20 DT20‹CR› CR reply = 0 or 1Display flag 1000.15 DM1000.15‹CR› CR reply = 0 or 1

ModifyModify contents of registers 0 to 255 MR0‹CR›

CR reply = xxx: 255‹CR›xxx = old value; 255‹CR›Enter new value

Page 68: fec_fc34

Page 68FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Hardware change status

Appendix: GeneralAppendix: GeneralAppendix: GeneralAppendix: GeneralAppendix: General

Manual change status

Version Date Change

0.1 17.06.99 First version

Serial number Hardwareversion

Change

From PMFC34D1-1 H00 First version

Page 69: fec_fc34

Page 69Page 69Page 69Page 69Page 69IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Technical data

Climatic characteristics

• Transportation/storage (IEC 68-2-1/2). . . . : -25ºC to +70ºC• Normal operation (IEC 68-2-1/2). . . . . : 0ºC to +55ºC / 20 G• Temperature change (slow change). . . . . : IEC 68-2-14• Relative humidity (DIN 40040). . . . . . : 75% on 30 days

95% no condensation

Mechanical characteristics

• Weight . . . . . . . . . . : approx. 160 g• Dimensions . . . . . . . . . : 75x21x96 mm• Vibration (sinusoidal oscillation) . . . . . : IEC 68-2-6• Shock test (impact test) (IEC 68-2-6) . . . . : 10 to 150 Hz, 2 G

Page 70: fec_fc34

Page 70FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Electromagnetic characteristics

• Electromagnetic compatibility (EMC). . . . . . : EN 50081/2 as per IEC 1131-2• Electrostatic discharge (ESD). . . . . . . : EN 61000-4-2 as per IEC 801-2• High frequency electromagnetic fields (HFF). . . . : EN 61000-4-3 as per IEC 801-3• Fast transients (BURST). . . . . . . . : EN 61000-4-4 as per IEC 801-4• Wire-conducted HF interference (LHF). . . . . : EN 61000-4-6• Radio interference / interference strength. . . . : EN 55022 / A

Electrical characteristics:

• Maximum current consumption (at 5 V). . . . . : 300 mA (typical)• Power consumption. . . . . . . . . : 1.6 W (typical)

Inputs:

• Galvanic separation . . . . . . . . : Optocoupler• Input voltage . . . . . . . . . . : 24 V DC, input current 7mA

Page 71: fec_fc34

Page 71Page 71Page 71Page 71Page 71IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

• Delay time . . . . . . . . . : 5 ms• Signal display . . . . . . . . : Green LED (after galv. separation)• 2 fast counter inputs . . . . . . . : max. 2 kHz• Incremental encoder . . . . . . . : max. 200 Hz

Outputs:

• Supply voltage . . . . . . . . : +24V ± 20%• Nominal load: . . . . . . . . : 700 mA 24 V DC• Service life: . . . . . . . . : 100,000 hours• Maximum switching frequency: . . . . . : 1 kHz

IEC / VDE safety information

• Protection class: . . . . . . . . : IP 41• Insulation measurement . . . . . . : VDE 0160

Page 72: fec_fc34

Page 72FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

Hardware and software characteristics

• Processor . . . . . . . : AM186 (20 MHZ), (Intel 80186-compatible)• Program memory (compiled) . . . : 256 kBytes flash (read/write cycles › 10,000)• Working storage . . . . . . : 512 kB DRAM, (480 kB free)• Residual data . . . . . . : 2 kB in flash• Program storage (drive B) . . . . : 256 kB in flash memory (approx. 100 kBytes free)• Terminal connection . . . . . : Serial asynchronous TTL (RJ12 connector)

(4-wire, max. 115 kBaud)• Operating status display . . . . : Status LED (green, red, orange)• Operating system . . . . . . : ROM DOS 5.0• Network connection . . . . . : 10BASE T (RJ45)• Network communication display . . . : Link/traffic LED

Page 73: fec_fc34

Page 73Page 73Page 73Page 73Page 73IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99

Ordering information

ModelFesto

order no.Beck

order no.Description

FEC FC34-FST FEC FC34-FSTFEC 12 in/2 relay outputs, 6 trans.outputs,24V DC, Ethernet, 10Base T, FST

PS1 SM14 PS1 SM14ZK36 connecting cable + ZK 11null modem cable

00190587

00188935

FEC KSD4 FEC KSD4Network cable for 2 stations(30 cm) RJ12/RJ12

00183635

PS1 ZK44 PS1 ZK44AW G26 8-core modular cablefor RJ45 (100 metres)

00189682

PS1 ZC24 PS1 ZC24Modular connectorRJ45, 8-pin (10)

00190580

Page 74: fec_fc34

Page 74FEC FC34-FST HE01 Version 0.1 as of 17.06.99IPC FEC®

We try to keep our manuals up to date at alltimes. If you discover descriptions that aredifficult to understand or even contain errors,please inform us, specifying the manual con-cerned and the version number to the follo-wing E-mail address (Internet):

[email protected]@[email protected]@[email protected]

Please also send your suggestions and impro-vements.

We cannot reply to technical queries by E-mail.Please contact your retailer.

More information under:

http://www.beck-ipc.comhttp://www.beck-ipc.comhttp://www.beck-ipc.comhttp://www.beck-ipc.comhttp://www.beck-ipc.com

Page 75: fec_fc34

Page 75Page 75Page 75Page 75Page 75IPC FEC® FEC FC34-FST HE01 Version 0.1 as of 17.06.99