SAI SINDHU SPONGE IRON PVT LTD8 MW CAPTIVE POWER PLANT AT TADIPATRI
FAULT LEVEL CALCULATION
HIQ POWER ASSOCIATES PRIVATE LIMITED, CHENNAI
G
Y
D
11 KV bus
33 KV bus
DETAILS:1. Transformer - 8.6MVA, 11/33 KV, 8.5%
2. Generator - 8.0MW, 10.0 MVA
33Kv Grid SS
ACSR,O/H line
Isolater
11KV XLPE cable
1
SAI SINDHU SPONGE IRON PVT LTD8 MW CAPTIVE POWER PLANT AT TADIPATRI
FAULT LEVEL CALCULATION IN 11KV BUS BAR
I. Fault level at 33 KV: -
Fault level at 33KV Bus = 1000 MVA (considered)
Let the base MVA = 8.6 MVA
% Impedance of the system at source = 8.6/1000 = 0.0086 P.U = Z1
II. Fault level at 8.6MVA Transformer
Transformer KVA = 8600KVA
Voltage rating = 33KV/11KV
Impedance of the transformer = 10% = 0.1 P.U =Z2
III. Fault level at 10.0 MVA Generator
Sub transient Reactance of the Generator = 12. % (Considered)
Generator MVA = 10.0 MVA
Base MVA for generator = 8.6 MVA
Impedance of the Generator
= 0.12X (8.6 / 10)
= 0.1032 P.U = Z3
TOTAL FAULT IN 11KV BUS: -
Z1 and Z2 are in series
Total P.U in Transformer end (Z0) = Z1 +Z2
HIQ POWER ASSOCIATES PRIVATE LIMITED, CHENNAI
Z2 Z1
Z3
2
SAI SINDHU SPONGE IRON PVT LTD8 MW CAPTIVE POWER PLANT AT TADIPATRI
= 0.0086 + 0.1
= 0.1086
P.U in 11KV Bus = Z0 XZ3 /Z0+Z3
= (0.1086 X 0.1032) / (0.1086 + 0.1032)
= 0.0529 P.U
Fault MVA in 11KV End = 8.6/0.0529
= 162 MVA
Fault Current = 162/(1.732X11)
= 8.5 KA
FAULT LEVEL CALCULATION IN 415V BUS BAR
IV. Fault level at 11 KV: -
Actual fault level at 11KV Bus = 162 MVA Let the base MVA = 2.0 MVA
% Impedance of the system at source = 2.0/162 = 0.0123 P.U =Z4
V. Fault level at 2.5MVA Transformer
Transformer KVA = 2000KVA
Voltage rating = 11KV/0.433KV
Impedance of the transformer = 7%
= 0.07 P.U =Z5
TOTAL FAULT IN 415V BUS: -
Z4 and Z5 are in series
Total P.U in Transformer end (Z0) = Z4+Z5
= 0.0123 + 0.07
HIQ POWER ASSOCIATES PRIVATE LIMITED, CHENNAI
3
SAI SINDHU SPONGE IRON PVT LTD8 MW CAPTIVE POWER PLANT AT TADIPATRI
= 0.0823
Fault MVA in 415V End = 2.0/0.0823
= 24.3 MVA
Fault Current = 24.3/(1.732X0.433)
= 32.4 KA
Fault in motor end = 8 KA
Total Fault in 415V end = 40.4 KA
HIQ POWER ASSOCIATES PRIVATE LIMITED, CHENNAI
4