Fan Coils Units Control Wall mounted, 2x2 and 3x3 cassette fancoil units MERCA, SRC and WRC.
Transcript of Fan Coils Units Control Wall mounted, 2x2 and 3x3 cassette fancoil units MERCA, SRC and WRC.
Fan Coils Units ControlWall mounted, 2x2 and 3x3 cassette fancoil units
MERCA, SRC and WRC
2Apr 21, 2023
Internal use only
SLM 3
orCN_WIR
SRC
CN_DSP
Note: Only one application is function at one time, either wireless or wired
Wiring connection
MERCA
6Apr 21, 2023
Internal use only
The PCB has 4 modes selection via jumper:
Model
Configuration
Operating Modes
M1 2 pipes Cooling or Heating(no Auto mode)
M2 2 pipes + Aux. Htr
Cooling or Heating with Aux. Htr (no Auto mode)
M3 4 pipes with Boiler
Cooling only or Boiler (with Auto mode)
M4 4 pipe + Boiler
Cooling or Heating with Boiler water (no Auto mode)
Mode Selection
7Apr 21, 2023
Internal use only
Last Memory
Options for last memory setting is available by setting of J_LST.
Last setting that memorized:1. Mode and on/off status2. Set Temperature 3. Fan Speed 4. DC & AC Swing5. Flap stop coordinate (for DC swing off mode)
For Default setting, power up is “OFF” mode, temperaturesetting is 24 o C, indoor fan speed is High and swing modeis off.
Setting J_LST
With Last Memory Setting Short
Default Setting Open
8Apr 21, 2023
Internal use only
Valve Jumper
Setting Jumper Valve
Valve control Short
Valveless control Open
Valve/Valveless Control Selection
9Apr 21, 2023
Internal use only
Turn ON/OFF
3 ways to turn on / off the system:1. Via ON/Off triggering - pressing emergency ON/Off button or LCD controller ON/OFF button. Override timer setting2. Via delay timer - Delay timer is to simulate the ON/OFF pressing after the set numbers of hours 3. Via real time ON/OFF timer - When the real time ON timer set time matches the internal real time clock, unit will switch on, similar for OFF time. The timer setting are retained so
that similar switching can occur 24 hours later
Temperature setting allowed in COOL, DRY, and HEAT mode Temperature range is 16 o C to 30 o C
Temperature range and setting
10Apr 21, 2023
Internal use only
FAN_P Jumper
This option applied to Cool, Heat and Auto mode (apply only during thermostat off cycle)
Fan Priority Setting
Setting Jumper FAN_P
User set speed or low fan if auto mode is selected
Short
Fan stop when thermostat cuts off
Open
11Apr 21, 2023
Internal use only
Heat JumperSetting Jumper Heat
Heat mode allow to use Short
Bar Heat mode Open
Bar Heat Mode Setting
This setting is to bar user from using Heat mode
12Apr 21, 2023
Internal use only
....
Sleep Mode
• Only available for COOL & HEAT modes -
• This function will increase (cooling mode) or decrease (heating mode) the set temperature with time
• The option can be set or reset by the LCD or LED controller. Activation of Emergency switch will reset this option
14Apr 21, 2023
Internal use only
H M L H M L
Water ValveOFF
Water ValveOFF
Water ValveON
Water ValveON
Ts
Ts+1.0
ºC
Cool Mode - With Water Valve
Water valve will cut in if the Tr >= Ts + 1 C. Water valve cut out if Tr=<Ts. Thermostat cut in or out is decided every 30 seconds. In this mode, indoor fan will follow jumper FAN_PRIO setting.
If jumper FAN_PRIO is ON:-- For manual fan speed setting, indoor fan will run as per user set speed. - In AUTO FAN, the indoor fan speed will run as follows:
Tr: room T°
Ts: T°set
15Apr 21, 2023
Internal use only
Manual fan speed
Auto fan speed
User set speed
(H/M/L)
User set speed
(H/M/L)
SLo
SLo
Ts
- 1.0 C
- 0.5 C
H
SLo
SLo
Ts - 0.5 C - 1.0 C
+1.0 C
- 0.5 C M
L
+0.5 C
L
M
H
Ts
Cool Mode - Without Water Valve
Fan speed decision is made every 30 seconds.Fan speed will run as the following diagram
16Apr 21, 2023
Internal use only
HL LM H
Water ValveON
Water ValveON
Water ValveOFF
Water ValveOFF
Ts
Ts-1.0
ºC
Ts-2.0
M L
Auxiliary Heater /Boiler OFF
Auxiliary Heater /Boiler ON
Tr: room T°
Ts: T°set
Heat Mode - With Water Valve
Water valve will cut in if the Tr =< Ts - 1 C. Water valve cut out if Tr<=Ts. Thermostat cut in or out is decided every 30 seconds.
If jumper FAN_PRIO is ON:-- For manual fan speed setting, indoor fan will run as per
user set speed. - In AUTO FAN, the indoor fan speed will run as follows:
17Apr 21, 2023
Internal use only
User set speed
(H/M/L) User set speed
(H/M/L)
SLo SLo
Ts
+1.5 C +1.0 C
H
SLo
SLo
Ts
+2.0 C
+1.0 C +1.5 C
M
L
- 1.0 C
L
M
H - 2.0 C
Ts
Manual fan speed
Auto fan speed
Heat Mode - Without Water Valve
Fan speed decision is made every 30 seconds.Fan speed will run as the following diagram
18Apr 21, 2023
Internal use only
Force On (Valve) 2 minuteUser set speed indoor fan.
If Auto fan low fan
Check Tr14ºC < Tr < 47ºC
Check Tc
2 minuteconfirm?
Tc > Tr+3ºC(Water not suitable)
No
(Force valve to ON)
9 minuteelapsed?
Yes(Force valve OFF 9 minutes)
No
Yes
OthersCheck Tc
2 minuteconfirm?
Tc > 30ºC(Water not suitable)
No
(Force valve to ON)
9 minuteelapsed?
Yes(Force valve OFF 9 minutes)
No
Yes
Enter into coolingthermostat cycle
Tc < Tr+2ºC Tc < 29ºC
Pipe Water Temperature Sensor (Indoor Coil Sensor)Cool Mode - With Water valve
Water valve and indoor fan at set fan speed will be forced to cut in minimum 2 minutes irrespective of thermostat cycle during power
on reset / change mode/unit recover from fault
19Apr 21, 2023
Internal use only
Force On 2 minuteIndoor fan force Low fan
Check Tr14ºC < Tr < 47ºC
Check Tc
2 minuteconfirm?
Tc > Tr+3ºC(Indoor fan force super low fan)(Water not suitable)
No
Yes
Enter into coolingthermostat cycle
Tr-2ºC < Tc <Tr+2ºC(Indoor fan force low fan)
Tc < Tr-3ºC(fault terminated,LED stop blinking)
OthersCheck Tc
2 minuteconfirm?
No
Tc < 25ºC(fault terminated,
LED stop blinking)
(fault declared, LED blinking)
Tc > 30ºC(Indoor fan force super low fan)
(Water not suitable)
Yes
26ºC < Tc < 29ºC(Indoor fan force low fan)
(fault declared, LED blinking)
Pipe Water Temperature Sensor (Indoor Coil Sensor)Cool Mode - Without Water valve
Indoor fan is forced to run at low speed for at least 2 minutes
irrespective of thermostat cycle during power on reset / change mode / unit recover from fault
20Apr 21, 2023
Internal use only
Force On (Valve) 2 minuteUser set speed indoor fan.
If Auto fan low fan
Check Tr14ºC < Tr < 47ºC
Check Tc
2 minuteconfirm?
Tc < Tr-3ºC(no auxiliary Heater/booster)(Water not suitable)
No
(Force valve to ON)
9 minuteelapsed?
Yes(Force valve OFF 9 minutes)(Auxiliary Heater/booster can be used)
No
Yes
Enter into heatingthermostat cycle
Tr-2ºC < Tc < Tr+2ºC(Auxiliary Heater/booster can be used)
Tc > Tr+3ºC(no Auxiliary Heater/booster)
Others Check Tc
2 minuteconfirm?
Tc<25ºC(no auxiliary Heater/booster)
(Water not suitable)
No
(Force valve to ON)
9 minuteelapsed?
Yes(Force valve OFF 9 minutes)
(Auxiliary Heater/booster can be used)
No
Yes
26ºC < Tc < 29ºC(Auxiliary Heater/booster can be used)
Tc > 30ºC(no Auxiliary Heater/booster)
Pipe Water Temperature Sensor(Indoor Coil Sensor)Heat Mode - With Water valve
Water valve will be forced to cut in minimum 2 minutes irrespective of thermostat cycle during power on reset / change mode / unit recover from fault
21Apr 21, 2023
Internal use only
Force On 2 minuteIndoor fan force Low fan
Check Tr14ºC < Tr < 47ºC
Check Tc
Withbooster?
No
Yes
Enter into heatingthermostat cycle
Tr-2ºC < Tc < Tr+2ºC(Auxiliary heater/booster can be used)(Indoor fan**)
Tc > Tr+3ºC(no auxiliary heater/booster)(fault terminated, LED stop blinking)
OthersCheck Tc
Tc > 30ºC(no auxiliary heater/booster)
(fault terminated, LED stop blinking)
(fault declared, LED blinking)
Yes
(fault declared, LED blinking)
26ºC < Tc < 29ºC(Indoor fan force low fan)
(Indoor fan**)
Indoor fan**Heater ON user set speed / Low fan if AUTO fan selectedHeater OFF low fan
(Auxiliary heater/booster can be used)(Run user set fan speed )
Yes
2 minuteconfirm?
No(Indoor fan force super low fan)
Withbooster?
2 minuteconfirm?No
(Auxiliary heater/booster can be used)(Run user set fan speed )
Yes
No
(Indoor fan force super low fan)
Tc < Tr-3ºC Tc < 25ºC
Pipe Water Temperature Sensor(Indoor Coil Sensor)Heat Mode - Without Water valve
Indoor fan is forced to run at low speed for at least 2 minutes
irrespective of thermostat cycle during power on reset / change mode / unit recover from fault
22Apr 21, 2023
Internal use only
Errors Cool LED
7 Segment Indicator
Rooms sensor error (short/open) 1 blinks E1
Pipe water sensor error (short/open)
2 blinks E2
Water pump error 6 blinks E6
Pipe water temperature fault 5 blinks E5
Fault Diagnostics