■ Transmission Earthing Devices
THE FIVE GOLDEN RULES
■ STAGE 1
Switch off the circuit
THE FIVE GOLDEN RULES
■ STAGE 2
Lockout & Tagout
THE FIVE GOLDEN RULES
■ STAGE 3
Checking the absence of nominal voltage
THE FIVE GOLDEN RULES
■ STAGE 4
Earthing
THE FIVE GOLDEN RULES
■ STAGE 5
Delimit & Protect the working area
Transmission Earthing Devices
WHY ?• Secure the operators on the network • Secure the network equipments
WHEN ?
• Before working on a network which must be switching off • Immediately after performing the nominal voltage checking
HOW?
• Compliance with 5 golden rules • Creating a connection between the conductor and earth (s) conductors (s) phase in
respecting the order of installation / removal • Using earthing equipments that conforms to all relevant standards:
IEC / EN 61230: Temporary Mobile Grounding devices IEC / EN 61138: Lead copper cable for temporary mobile grounding devices EN 50508: Insulating sticks IEC / EN 60855-1 & CEI/EN61235: Insulating tube for live line working
• By following the minimum approach distance during installation of the line clamps
Composition of the earthing device
3 x
Composition of the earthing device
3 x
How to determinate the adapted earthing device ?
1. Voltage range ?
2. Environnement: Substation ou Overheadline ?
3. Type of earth conductors?
4. Shape :
5. Dimension Mini Maxi (mm): Diameter, thikness, width
6. Type of line conductors ?
7. Shape:
8. Dimension Mini Maxi (mm): Diameter, thikness, width
Lenght of the earthing copper cable
Lenght = distance max between the line conductor and the earth conductor + 2m maxi
Short circuiting intensity
Short circuiting intensity ?
How long time ?
Max temperature increase ?
Short circuiting intensity
CABLE CUIVRE / COPPER CABLE
Section câbleCable section(mm²)
Echauffement du câble à la fin du ccWarm up cable at the end of short-circuit
Iccmax pourMax short-circuit with
Poids/mWeight/m
(kg)
50 700 °C 13,2 kA / 1 s 0,5
Short circuiting intensity
CABLE CUIVRE / COPPER CABLE
CABLE CUIVRE / COPPER CABLE
Section câbleCable section(mm²)
Echauffement du câble à la fin du ccWarm up cable at the end of short-circuit
Iccmax pourMax short-circuit with
Poids/mWeight/m
(kg)
120 700 °C 31,7 kA / 1 s 1,3