Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus...

59
Bid No.: 1086-18 Project Name: Prop 39 Lighting Projects Phase II Date: June 5, 2017 ADDENDUM NO. 1 _______________________________________________________________________________________ This Addendum forms a part of the Contract Documents and modifies the original Bidding Documents and previous Addenda as noted below. Acknowledge receipt of this Addendum in the space provided in the Bid Form. Failure to do so may subject Bidder to disqualification. Changes and/or Clarifications of the contract and specifications are as follows: A. CHANGES TO CONTRACT ITEM 1: ADD to 00 71 00-5 Item 12 as follows: 12. Schedule Coordination: A portion of the work will take place during the academic year between August 16, 2017 and completion of the project. Interior work during this period will be limited to the hours of 3:00 pm to 10:00 pm. ITEM 2: ADD to 00 52 13-50 11 “Agreement”: 11. Classification of Contractor’s License: Electrical (C) License B. CHANGES TO PROJECT MANUAL ITEM 1: REPLACED Appendix A with Attached Appendix A dated 6/5/17 C. RESPONSE TO BIDDER QUESTIONS 1. Would it be possible to get the excel of the lighting matrix for this phase as we did with the last phase? Response: Yes. The district will post the lighting matrix bid document on the District website. The bid will be based on the PDF document provided in the bid docs and not the excel file. D. SITE ELECTRICAL PLANS (REFERENCE) Fairfield-Suisun Unified School District 2490 Hilborn RoadFairfield, California 94534 Telephone (707) 399-5148 FAX: (707) 399-5162 www.fsusd.org “Fairfield-Suisun Unified School District is a premier learning community that empowers each student to thrive in an ever-changing world.”

Transcript of Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus...

Page 1: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

Bid No.: 1086-18 Project Name: Prop 39 Lighting Projects Phase II Date: June 5, 2017

ADDENDUM NO. 1 _______________________________________________________________________________________ This Addendum forms a part of the Contract Documents and modifies the original Bidding Documents and previous Addenda as noted below. Acknowledge receipt of this Addendum in the space provided in the Bid Form. Failure to do so may subject Bidder to disqualification.

Changes and/or Clarifications of the contract and specifications are as follows:

A. CHANGES TO CONTRACT

ITEM 1: ADD to 00 71 00-5 Item 12 as follows:

12. Schedule Coordination: A portion of the work will take place during the academic year between August 16, 2017 and completion of the project. Interior work during this period will be limited to the hours of 3:00 pm to 10:00 pm.

ITEM 2: ADD to 00 52 13-50 11 “Agreement”:

11. Classification of Contractor’s License: Electrical (C) License

B. CHANGES TO PROJECT MANUAL

ITEM 1: REPLACED Appendix A with Attached Appendix A dated 6/5/17

C. RESPONSE TO BIDDER QUESTIONS

1. Would it be possible to get the excel of the lighting matrix for this phase as we did with the last phase? Response: Yes. The district will post the lighting matrix bid document on the District website. The bid will be based on the PDF document provided in the bid docs and not the excel file.

D. SITE ELECTRICAL PLANS (REFERENCE)

Fairfield-Suisun Unified School District

2490 Hilborn Road• Fairfield, California 94534 Telephone (707) 399-5148 FAX: (707) 399-5162 www.fsusd.org

“Fairfield-Suisun Unified School District is a premier learning community that empowers each student to thrive in an ever-changing world.”

Page 2: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

ADDENDUM NO. 1 #1086-18 PROP 39 LIGHTING PROJECTS PHASE II

Page 2 of 2 ITEM 1: Original electrical design plans are available on the Fairfield-Suisun Unified School District Website. Contract scope is based upon the contract documents, these plans are being provided for reference only:

A. Nelda Mundy Elementary School

AE3.1, BE3.1, CE3.1, DE3.1, E1.1, E6.1, EE3.1, FE3.1 (Plans are labeled “Vintage Valley Elementary School”)

B. Laurel Creek Elementary School E3, E5, E6, E8, E10, E13, E15

Page 3: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

PacificWest Energy Solutions, Inc. 18543 Devonshire Street #128 Main 800-310-9080 Northridge, CA 91324 Page 1 of 7 www.PacWestES.com

Appendix A

Project Intent The project will replace or retrofit lighting systems with new high efficiency LED interior and exterior lighting technology with new ON/OFF occupancy sensor controls, as needed. Designated fixtures will have battery backup for emergency lighting. Lights will connect to existing manual switches and circuits. It is the contractor’s responsibility to provide all materials and labor to complete the design intent whether included in the project documentation or not.

Scope of Work The work under this section of the specifications consists of furnishing all labor, equipment and materials necessary for and reasonably incidental to the complete installation of the LED Lighting Systems as herein described including such minor details not specifically mentioned or shown as may be necessary to complete the system, ready for successful operation, and subject to the terms and conditions of the Contract.

All work under this Section shall be done in accordance with the best modern practice, using first grade equipment and material new and previously unused. Workmanship and neat appearance of the installation shall be of the same level of importance as its efficiency. Should any conflicts occur, the Engineer shall be immediately notified.

Contractor shall provide turn-key installation services for a complete, fully commissioned, and operational system(s) per the Project Scope of Work as follows. All system(s) shall operate in accordance to drawings, specifications, and/or performance requirements.

LIGHTING # Name City State 1 Laurel Creek Elementary Fairfield, CA 2 Nelda Mundy Elementary Fairfield, CA 3 Matt Garcia Career & College Academy Fairfield, CA

Planning ♦ Submittals shall be furnished by the contractor and approved by the engineer and

District prior to the ordering of any equipment. Unapproved materials will not be used inthis work.

♦ Contractor shall provide a schedule for completion of the work within one week ofcontract award showing activity at each site and compliance with the contracted timeline.

Demolition ♦ Existing lamps, ballasts, and other equipment will be removed and existing electrical

connections, controls and other connections disconnected for reuse with the newequipment.

♦ The contractor will dispose of, or recycle as necessary, all equipment removed. Duringremoval of equipment, care shall be taken to avoid unnecessary damage to any existingmaterials intended for reuse.

Addendum #1 6/5/17

Page 4: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

PacificWest Energy Solutions, Inc. 18543 Devonshire Street #128 Main 800-310-9080 Northridge, CA 91324 Page 2 of 7 www.PacWestES.com

♦ Any existing materials (wiring, etc.) damaged during the work that compromises suitability for reuse shall be replaced with new materials.

♦ Coordinate and provide lamp and ballast disposal/recycle service. Installation

♦ Contractor will provide (furnish and install) all necessary equipment to complete a fully functional system.

♦ Provide site supervision and coordination of installation activities. ♦ Contractor to clean all work areas at the end of each work shift. ♦ Contractor to clean fixtures and lenses during lamp replacement.

Contractor shall provide the following services:

♦ Provide turn-key Lighting installation for systems at the facilities listed above. Detailed unit locations, quantities, types, and requirements provided in the documents, specifications, and/or performance requirements.

♦ Provide Equipment Submittals for approval prior to procurement and applicable Material Safety Data Sheets, upon request.

♦ Remove and recycle or dispose as required all lamps, ballasts and other items made obsolete.

♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

♦ New Occupancy Sensors to be mounted on ceiling near center of room. Offset as required to avoid existing obstructions. Where 2 are used in a room, mount along centerline of room’s long axis, inset 10’ from end walls.

♦ See provided manufacturer data for wiring diagrams related to installation of multiple switch packs, occupancy sensors, switch leg combinations.

♦ Secure all new EMT with ½” EMT 1-hole straps on maximum 6 foot centers. ♦ Reuse existing electrical disconnects, fuses, controls, sensors, switches, conduit, and

wiring, if in good condition. ♦ Install new electrical disconnects, fuses, controls, sensors, switches, conduit, wiring, and

required electrical or structural upgrades. ♦ Install all necessary equipment, materials, appurtenances, etc. needed for a complete,

fully commissioned, and operational system. ♦ Disconnect and properly secure existing controls, sensors, and/or wiring prior to Lighting

unit removal. Reconnect and commission controls, sensors, and/or wiring after Lighting unit installation.

♦ Provide proper removal, disposal, recycling, and associated coordination of all equipment, materials, appurtenances, etc. to be removed, replaced, or decommissioned.

♦ Provide disposal and recycling documentation, upon request. ♦ Repair and/or replace surrounding architectural finishes associated with the Scope of

Work damaged and/or demolished by Contractor during the performance of the Project. Repairs may include but are not limited to caulking, flashing, insulating, patching, painting, and/or sealing.

♦ Comply to all applicable current Client, local, state, and federal codes, regulations, and standards.

Page 5: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

PacificWest Energy Solutions, Inc. 18543 Devonshire Street #128 Main 800-310-9080 Northridge, CA 91324 Page 3 of 7 www.PacWestES.com

♦ Maintain equipment manufacturer required operational and performance specifications. ♦ Provide site supervision and coordination of installation activities. ♦ Perform system start-up and provide commissioning documentation. ♦ Provide one (1) operations & maintenance manual with complete warranty information. ♦ Conduct four (4) hours of onsite training for operations, maintenance requirements, and

warranty process. ♦ Assist with application of rebates and incentives through Utility Provider(s) and

coordination of applicable measurement & verification activities. The District reserves rights to all rebates.

Specifications Basis of design is RAB, Lithonia, Satco, Energy Focus, Keystone, Phillips, Williams, and Columbia LED product lines including:

♦ RAB BOA Flush Mount LED Strip ♦ RAB FFLED18/26 Stem Mount Flood ♦ RAB WP1/WP2 Series Wall-Pack ♦ RAB VanLED Series Vandal-proof Canopy Mount ♦ Lithonia TWS LED Wall Luminaire ♦ Satco Line Driven Screw-In LED Lamps ♦ Energy Focus Linear Flourescent Retrofit LED Lamps ♦ Keystone Direct Drive Tube LED ♦ Phillips A-Shape Dimmable LED Lamps ♦ Phillips Linear FluxStream Strip ♦ Phillips SML Surface Modular LED ♦ Phillips Stonco WPM LED Wall Pack ♦ Williams Surface or Pendant Mount Wrap ♦ Columbia Ceiling Mount/Recessed LED Troffer ♦ Columbia LCL Lensed LED Striplight

Please refer to the following attachments: ♦ Lighting Design ♦ Manufacturer Specifications Sheets

Page 6: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

PacificWest Energy Solutions, Inc. 18543 Devonshire Street #128 Main 800-310-9080 Northridge, CA 91324 Page 4 of 7 www.PacWestES.com

Total Fixture Counts

Laurel Creek Elementary Replacement Summary Nelda Mundy Replacement Summary

Qty Model # Qty Model # 84 WP2LED24NPC 1963 LEDFLT8-840-415-228F 4 Satco 9390 48 KT-LED12T8-36GC-840-D 1 WPM-LED-36L-530-NW-UNV 31 WP130NPC 89 Total 25 Satco S9396

25 FSS440L840-UNV-DIM Matt Garcia Career & College Academy Replacement Summary 2 14.5A19/LED/827

2 BOA4S-20D10-40N-W Qty Model # 1 10.5A19/LED/827 118 LJT24-40LWG-FSA12-EU 2097 Total 89 LJT24-40LWSM-FSA12-EU 18 39-8-L60/840 Qty Misc Items 15 1SML32L8XX-4-TFA-02F-DIM 31 DT-305 Ceiling Sensor 13 FFLED18 37 BZ-250 Power Pack 7 TWS-1-50K-120-PE 5 VANLED20N 1 Satco S8909

266 Total

Qty Misc Items 16 DT-305 Ceiling Sensor 19 BZ-250 Power Pack

Page 7: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

# Facility Bldg Room Area Type Fixture Qty Fixture Description Fixture Description Model Number Max Watts Min Lumens per Watt Min CRI Color

Temperature Accessories New Sensor New Relay Packs

1 Laurel Creek Elementary Exterior Exterior Exterior 84 1L 70W HPS N/A Wall

Pack Prismatic 1L 24W LED Wall Pack WP2LED24NPC 24 115 83 4,000 120V Button Photocell

2 Laurel Creek Elementary Exterior Exterior Exterior 4 1L 70W HPS N/A Recessed

Clear 1L 18W Screw-In LED Satco 9390 20 113 74 4,000 Base Reducer Scoket

3 Laurel Creek Elementary Exterior Exterior Exterior 1 1L 100W HPS N/A Wall

Pack Prismatic 1L 33W LED Wall Pack WPM-LED-36L-530-NW-UNV 33 93 70 4,000

1 Nelda Mundy Elementary Main 700 Class (Elementary) 16 3L 28W 48" T8 2x4

Recessed Parabolic 3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

2 Nelda Mundy Elementary Main 701 Class (Elementary) 16 3L 28W 48" T8 2x4

Recessed Parabolic 3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

3 Nelda Mundy Elementary Main 702 Class (Elementary) 16 3L 28W 48" T8 2x4

Recessed Parabolic 3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

4 Nelda Mundy Elementary Main 703 Class (Elementary) 16 3L 28W 48" T8 2x4

Recessed Parabolic 3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

5 Nelda Mundy Elementary Main 704 Class (Elementary) 12 3L 28W 48" T8 2x4

Recessed Parabolic 3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

6 Nelda Mundy Elementary Main Storage Class (Elementary) 1 3L 28W 48" T8 2x4

Recessed Parabolic 3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones Ceiling Dual 2

7 Nelda Mundy Elementary Main 705 Class (Elementary) 12 3L 28W 48" T8 2x4

Recessed Parabolic 3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones Ceiling Dual 2

8 Nelda Mundy Elementary Main 706 Class (Elementary) 16 3L 28W 48" T8 2x4

Recessed Parabolic 3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

9 Nelda Mundy Elementary Main 707 Class (Elementary) 16 3L 28W 48" T8 2x4

Recessed Parabolic 3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

10 Nelda Mundy Elementary Main 708 Class (Elementary) 16 3L 28W 48" T8 2x4

Recessed Parabolic 3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

11 Nelda Mundy Elementary Main Storage Storage 2 2L 28W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

12 Nelda Mundy Elementary Main Storage Storage 2 2L 28W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

13 Nelda Mundy Elementary Main Unisex Restroom 1 2L 28W 48" T8 1x4 Wall

Mount Direct/Indirect2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

14 Nelda Mundy Elementary Main Unisex Restroom 1 2L 28W 48" T8 1x4 Wall

Mount Direct/Indirect2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

15 Nelda Mundy Elementary Main Girl's Restroom 9 2L 28W 48" T8 1x4 Wall

Mount Direct/Indirect2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

16 Nelda Mundy Elementary Main Boy's Restroom 9 2L 28W 48" T8 1x4 Wall

Mount Direct/Indirect2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

17 Nelda Mundy Elementary Main Storage Storage 1 2L 28W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

18 Nelda Mundy Elementary Portable P1 Class (Elementary) 10 4L 32W 48" T8 2x4

Recessed Prismatic4L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

19 Nelda Mundy Elementary Portable P2 Class (Elementary) 10 4L 32W 48" T8 2x4

Recessed Prismatic4L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

20 Nelda Mundy Elementary Portable P3 Class (Elementary) 12 2L 32W 48" T8 2x4

Recessed Prismatic2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

21 Nelda Mundy Elementary Portable P4 Class (Elementary) 12 2L 32W 48" T8 2x4

Recessed Prismatic2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

22 Nelda Mundy Elementary MPR MPR Lobby Accent

Lighting 8 2L 32W 48" T8 Strip N/A 1L 31W LED 1x4 Strip FSS440L840-UNV-DIM 31 133 80 4,000

23 Nelda Mundy Elementary MPR MPR Gym 20 1L 400W MH N/A Pendant

Prismatic 1L 100W Screw-In LED Satco S9396 100 120 80 5,000 4

24 Nelda Mundy Elementary MPR Storage Storage 2 2L 28W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

25 Nelda Mundy Elementary MPR Storage Storage 2 2L 28W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

26 Nelda Mundy Elementary MPR MPR Gym 2 2L 32W 48" T8 1x4 Ceiling

Mount Prismatic2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

27 Nelda Mundy Elementary MPR Storage Storage 2 2L 28W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

28 Nelda Mundy Elementary MPR Stage Stage 7 4L 32W 48" T8 2x4 Ceiling

Mount Opaque4L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

29 Nelda Mundy Elementary MPR Hallway Hallway 4 2L 32W 48" T8 1x4 Ceiling

Mount Prismatic2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

30 Nelda Mundy Elementary MPR Kitchen Kitchen 5 4L 32W 48" T8 2x4

Recessed Opaque4L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

31 Nelda Mundy Elementary MPR Kitchen Kitchen 2 1L 100W Incand N/A Ceiling

Mount Prismatic 1L 14.5W Screw-In LED 14.5A19/LED/827 15 103 80 2,700

32 Nelda Mundy Elementary MPR Storage Storage 2 2L 28W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

33 Nelda Mundy Elementary Library Main Area Library/Media 8 6L 32W 48" T8 1x8 Pendant

Direct/Indirect6L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

PacificWest Energy Solutions, Inc.18543 Devonshire Street #128Northridge, CA 91324 Page 1of 5

Main 800-310-9080www.PacWestES.com

Page 8: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

# Facility Bldg Room Area Type Fixture Qty Fixture Description Fixture Description Model Number Max Watts Min Lumens per Watt Min CRI Color

Temperature Accessories New Sensor New Relay Packs

34 Nelda Mundy Elementary Library Main Area Library/Media 8 6L 25W 36" T8 1x6 Pendant

Direct/Indirect6L 12W 48" Tube LED, Direct

Wire KT-LED12T8-36GC-840-D 12 104 83 4,000

35 Nelda Mundy Elementary Library Closet Elec/Mech 1 2L 32W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

36 Nelda Mundy Elementary Library Closet Elec/Mech 1 2L 32W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

37 Nelda Mundy Elementary Library Closet Elec/Mech 1 2L 32W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

38 Nelda Mundy Elementary Main 600 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

39 Nelda Mundy Elementary Main 601 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

40 Nelda Mundy Elementary Main 602 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

41 Nelda Mundy Elementary Main 603 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

42 Nelda Mundy Elementary Main 604 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

43 Nelda Mundy Elementary Main 605 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

44 Nelda Mundy Elementary Main 606 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

45 Nelda Mundy Elementary Main 607 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

46 Nelda Mundy Elementary Main 608 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

47 Nelda Mundy Elementary Main Boy's Restroom 9 2L 32W 48" T8 1x4 Wall

Mount Direct/Indirect2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

48 Nelda Mundy Elementary Main Closet Elec/Mech 1 2L 32W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

49 Nelda Mundy Elementary Main Girl's Restroom 9 2L 32W 48" T8 1x4 Wall

Mount Direct/Indirect2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

50 Nelda Mundy Elementary Main 500 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

51 Nelda Mundy Elementary Main 501 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

52 Nelda Mundy Elementary Main 502 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

53 Nelda Mundy Elementary Main 503 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

54 Nelda Mundy Elementary Main 504 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

55 Nelda Mundy Elementary Main 505 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

56 Nelda Mundy Elementary Main 506 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

57 Nelda Mundy Elementary Main 507 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

58 Nelda Mundy Elementary MPR Closet Office (Private) 2 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones Ceiling Dual 1

59 Nelda Mundy Elementary MPR Closet Storage 3 2L 32W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

60 Nelda Mundy Elementary MPR Closet Storage 1 2L 32W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

61 Nelda Mundy Elementary MPR Boy's Restroom 6 2L 32W 48" T8 1x4 Wall

Mount Direct/Indirect2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

62 Nelda Mundy Elementary MPR Girl's Restroom 6 2L 32W 48" T8 1x4 Wall

Mount Direct/Indirect2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

63 Nelda Mundy Elementary MPR Closet Storage 2 2L 32W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

64 Nelda Mundy Elementary MPR Closet Storage 2 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones Ceiling Dual 1

PacificWest Energy Solutions, Inc.18543 Devonshire Street #128Northridge, CA 91324 Page 2of 5

Main 800-310-9080www.PacWestES.com

Page 9: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

# Facility Bldg Room Area Type Fixture Qty Fixture Description Fixture Description Model Number Max Watts Min Lumens per Watt Min CRI Color

Temperature Accessories New Sensor New Relay Packs

65 Nelda Mundy Elementary MPR Music Class Class (Elementary) 7 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

66 Nelda Mundy Elementary Admin Main Office Office (Open) 6 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

67 Nelda Mundy Elementary Admin Main Office Hallway 1 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones Ceiling Dual 1

68 Nelda Mundy Elementary Admin Main Office Display Case 2 1L 34W 48" T12 1x4 Strip

N/A1L 17W LED 1x4 Ceiling

Mount BOA4S-20D10-40N-W 17 120 80 4,000

69 Nelda Mundy Elementary Admin Main Office Accent Lighting 17 2L 32W 48" T8 Strip N/A 1L 31W LED 1x4 Strip FSS440L840-UNV-DIM 31 133 80 4,000

70 Nelda Mundy Elementary Admin Supply Storage 3 2L 32W 48" T8 1x4 Ceiling

Mount N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

71 Nelda Mundy Elementary Admin Server Elec/Mech 1 2L 32W 48" T8 1x4 Ceiling

Mount N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

72 Nelda Mundy Elementary Admin Nurse's Workroom 3 2L 32W 48" T8 2x4

Recessed Parabolic 12C2L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstoness Ceiling Dual 1

73 Nelda Mundy Elementary Admin Nurse's Office (Private) 3 2L 32W 48" T8 2x4

Recessed Parabolic 12C2L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

74 Nelda Mundy Elementary Admin Nurse's Restroom 1 2L 32W 48" T8 1x4 Wall

Mount Direct/Indirect2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

75 Nelda Mundy Elementary Admin Admin Office (Private) 4 4L 32W 48" T8 2x4

Recessed Parabolic 24C4L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

76 Nelda Mundy Elementary Admin Lobby Lobby 5 2L 32W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

77 Nelda Mundy Elementary Admin Admin Hallway 13 2L 32W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

78 Nelda Mundy Elementary Admin Conference Conference 6 2L 32W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

79 Nelda Mundy Elementary Admin Lounge Break 3 4L 32W 48" T8 2x4

Recessed Parabolic 24C4L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

80 Nelda Mundy Elementary Admin Lounge Break 2 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

81 Nelda Mundy Elementary Admin Lounge Break 6 4L 32W 48" T8 1x8 Pendant

Louvre4L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

82 Nelda Mundy Elementary Admin Lounge Break 3 2L 32W 48" T8 1x4 Pendant

Louvre2L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

83 Nelda Mundy Elementary Admin Psychologist Office (Private) 2 4L 32W 48" T8 2x4

Recessed Parabolic 24C4L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

84 Nelda Mundy Elementary Admin Staff Office (Private) 2 4L 32W 48" T8 2x4

Recessed Parabolic 24C4L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

85 Nelda Mundy Elementary Admin Workroom Workroom 2 4L 32W 48" T8 2x4

Recessed Parabolic 24C4L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

86 Nelda Mundy Elementary Admin Staff Restroom 1 2L 32W 48" T8 1x4 Wall

Mount Direct/Indirect2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

87 Nelda Mundy Elementary Admin Staff Restroom 1 2L 32W 48" T8 1x4 Wall

Mount Direct/Indirect2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

88 Nelda Mundy Elementary Admin Storage Storage 1 2L 32W 48" T8 1x4 Ceiling

Mount N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

89 Nelda Mundy Elementary Main 401 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

90 Nelda Mundy Elementary Main 401 Restroom 1 4L 32W 48" T8 2x4 Ceiling

Mount Prismatic4L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones

91 Nelda Mundy Elementary Main 401 Restroom 1 4L 32W 48" T8 2x4 Ceiling

Mount Prismatic4L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

92 Nelda Mundy Elementary Main 401 Storage 2 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

93 Nelda Mundy Elementary Main 401 Storage 2 2L 32W 48" T8 1x4 Ceiling

Mount N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstones Ceiling Dual 1

94 Nelda Mundy Elementary Main 402 Class (Elementary) 16 3L 32W 48" T8 2x4

Recessed Parabolic 18C3L 15W 48" Tube LED, Direct

Wire, Prismatic Lens Kit LEDFLT8-840-415-228F 15 120 80 4,000 Prismatic Lens Kit, Energy Focus Non-

Shunted Tombstones

95 Nelda Mundy Elementary Main 402 Restroom 1 4L 32W 48" T8 2x4 Ceiling

Mount Prismatic4L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstoness

96 Nelda Mundy Elementary Main 402 Restroom 1 4L 32W 48" T8 2x4 Ceiling

Mount Prismatic4L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstoness

PacificWest Energy Solutions, Inc.18543 Devonshire Street #128Northridge, CA 91324 Page 3of 5

Main 800-310-9080www.PacWestES.com

Page 10: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

# Facility Bldg Room Area Type Fixture Qty Fixture Description Fixture Description Model Number Max Watts Min Lumens per Watt Min CRI Color

Temperature Accessories New Sensor New Relay Packs

97 Nelda Mundy Elementary Main Toy Storage 2 2L 32W 48" T8 1x4 Ceiling

Mount N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstoness Ceiling Dual 1

98 Nelda Mundy Elementary MPR Entry Lobby 5 2L 32W 48" T8 1x4 Strip

N/A2L 15W 48" Tube LED, Direct

Wire LEDFLT8-840-415-228F 15 120 80 4,000 Energy Focus Non-Shunted Tombstoness Ceiling Dual 1

99 Nelda Mundy Elementary Exterior Exterior Exterior 31 1L 70W HPS N/A Wall

Pack Clear 1L 30W LED Wall Pack WP130NPC 30 115 84 4,000 120V Button Photocell

100 Nelda Mundy Elementary Exterior Exterior Exterior 5 1L 400W MH N/A Shoebox

Clear 1L 100W Screw-In LED Satco S9396 100 120 80 5,000

101 Nelda Mundy Elementary Exterior Exterior Exterior 1 1L 70W HPS N/A Ceiling

Mount Clear 1L 10W Screw-In LED 10.5A19/LED/827 11 95 80 2,700

1 Matt Garcia Career & College Academy Admin Office Office (Private) 1 2L 34W 48" T12 1x4 Ceiling

Mount Prismatic1L 30W 1x4 LED Surface

Mount 1SML32L8XX-4-TFA-02F-DIM 30 111 80 3,500 Ceiling Dual 1

2 Matt Garcia Career & College Academy Admin Office Office (Private) 2 2L 34W 48" T12 1x4 Ceiling

Mount Prismatic1L 30W 1x4 LED Surface

Mount 1SML32L8XX-4-TFA-02F-DIM 30 111 80 3,500 Ceiling Dual 1

3 Matt Garcia Career & College Academy Admin Office Office (Private) 1 4L 34W 48" T12 1x4 Ceiling

Mount Prismatic1L 30W 1x4 LED Surface

Mount 1SML32L8XX-4-TFA-02F-DIM 30 111 80 3,500 Ceiling Dual 1

4 Matt Garcia Career & College Academy Admin School Counselor Office (Private) 1 4L 34W 48" T12 1x4 Ceiling

Mount Prismatic1L 30W 1x4 LED Surface

Mount 1SML32L8XX-4-TFA-02F-DIM 30 111 80 3,500 Ceiling Dual 1

5 Matt Garcia Career & College Academy Admin Storage Storage 1 2L 34W 48" T12 1x4 Ceiling

Mount Prismatic1L 30W 1x4 LED Surface

Mount 1SML32L8XX-4-TFA-02F-DIM 30 111 80 3,500 Ceiling Dual 1

6 Matt Garcia Career & College Academy Admin 5 Class (High) 10 2L 34W 48" T12 1x8

Pendant Parabolic 1L 25W 2x4 LED Surface

Mount LJT24-40LWSM-FSA12-EU 25 120 80 4,000 4 fixtures to be mounted with unistrut

7 Matt Garcia Career & College Academy Admin 6 Class (High) 10 2L 34W 48" T12 1x8

Pendant Parabolic 1L 25W 2x4 LED Surface

Mount LJT24-40LWSM-FSA12-EU 25 120 80 4,000 4 fixtures to be mounted with unistrut

8 Matt Garcia Career & College Academy Admin 7 Class (High) 11 2L 34W 48" T12 1x8

Pendant Parabolic 1L 25W 2x4 LED Surface

Mount LJT24-40LWSM-FSA12-EU 25 120 80 4,000 4 fixtures to be mounted with unistrut

9 Matt Garcia Career & College Academy Admin 8 Class (High) 10 2L 34W 48" T12 1x8

Pendant Parabolic 1L 25W 2x4 LED Surface

Mount LJT24-40LWSM-FSA12-EU 25 120 80 4,000 4 fixtures to be mounted with unistrut

10 Matt Garcia Career & College Academy Admin Women's Restroom 4 2L 34W 48" T12 1x4 Ceiling

Mount Prismatic1L 30W 1x4 LED Surface

Mount 1SML32L8XX-4-TFA-02F-DIM 30 111 80 3,500 Ceiling Dual 1

11 Matt Garcia Career & College Academy Admin Custodial Storage 1 2L 34W 48" T12 1x4 Ceiling

Mount Prismatic1L 30W 1x4 LED Surface

Mount 1SML32L8XX-4-TFA-02F-DIM 30 111 80 3,500 Ceiling Dual 1

12 Matt Garcia Career & College Academy Admin Men's Restroom 3 2L 68W 96" T12 1x8

Pendant N/A61W 8' LED Surface Mount with Cable Suspension Kit 39-8-L60/840 61 98 82 4,000

Cable Suspension Kit, Lateral Movement

Brace Ceiling Dual 3

13 Matt Garcia Career & College Academy Admin 4 Class (High) 10 2L 34W 48" T12 2x4 Ceiling

Mount Prismatic1L 25W 2x4 LED Surface

Mount LJT24-40LWSM-FSA12-EU 25 120 80 4,000 4 fixtures to be mounted with unistrut

14 Matt Garcia Career & College Academy Admin 3 Class (High) 10 2L 34W 48" T12 2x4 Ceiling

Mount Prismatic1L 25W 2x4 LED Surface

Mount LJT24-40LWSM-FSA12-EU 25 120 80 4,000 4 fixtures to be mounted with unistrut

15 Matt Garcia Career & College Academy Admin 2 Class (High) 10 2L 34W 48" T12 2x4 Ceiling

Mount Prismatic1L 25W 2x4 LED Surface

Mount LJT24-40LWSM-FSA12-EU 25 120 80 4,000 4 fixtures to be mounted with unistrut

16 Matt Garcia Career & College Academy Admin 1 Class (High) 10 2L 34W 48" T12 2x4 Ceiling

Mount Prismatic1L 25W 2x4 LED Surface

Mount LJT24-40LWSM-FSA12-EU 25 120 80 4,000 4 fixtures to be mounted with unistrut

17 Matt Garcia Career & College Academy Admin Attendance Office Office (Open) 6 4L 32W 48" T8 2x4 Ceiling

Mount Prismatic1L 25W 2x4 LED Surface

Mount LJT24-40LWSM-FSA12-EU 25 120 80 4,000 4 fixtures to be mounted with unistrut

18 Matt Garcia Career & College Academy Admin Nurse's Office (Private) 2 4L 32W 48" T8 2x4 Ceiling

Mount Prismatic1L 25W 2x4 LED Surface

Mount LJT24-40LWSM-FSA12-EU 25 120 80 4,000 Ceiling Dual 1

19 Matt Garcia Career & College Academy Admin Server Elec/Mech 1 2L 32W 48" T8 1x4 Ceiling

Mount N/A1L 30W 1x4 LED Surface

Mount 1SML32L8XX-4-TFA-02F-DIM 30 111 80 3,500 Ceiling Dual 1

20 Matt Garcia Career & College Academy Admin Hallway Hallway 3 2L 32W 48" T8 1x4 Ceiling

Mount Prismatic1L 30W 1x4 LED Surface

Mount 1SML32L8XX-4-TFA-02F-DIM 30 111 80 3,500 Ceiling Dual 1

21 Matt Garcia Career & College Academy Admin Matt Garcia Foundation Conference 6 2L 32W 48" T8 2x4 Ceiling

Mount Prismatic 1L 25W 2x4 LED Recessed LJT24-40LWG-FSA12-EU 25 120 80 4,000 Ceiling Dual 2

22 Matt Garcia Career & College Academy Main 1 Class (Middle) 9 2L 32W 48" T8 2x4 Ceiling

Mount Prismatic 1L 25W 2x4 LED Recessed LJT24-40LWG-FSA12-EU 25 120 80 4,000

23 Matt Garcia Career & College Academy Portable Girl's Restroom 2 2L 32W 48" T8 2x4

Recessed Prismatic 1L 25W 2x4 LED Recessed LJT24-40LWG-FSA12-EU 25 120 80 4,000 Ceiling Dual 1

24 Matt Garcia Career & College Academy Portable Unisex Restroom 1 2L 32W 48" T8 2x4

Recessed Prismatic 1L 25W 2x4 LED Recessed LJT24-40LWG-FSA12-EU 25 120 80 4,000 Ceiling Dual 1

25 Matt Garcia Career & College Academy Portable Closet Storage 1 2L 32W 48" T8 2x4

Recessed Prismatic 1L 25W 2x4 LED Recessed LJT24-40LWG-FSA12-EU 25 120 80 4,000 Ceiling Dual 1

26 Matt Garcia Career & College Academy Portable Boy's Restroom 2 2L 32W 48" T8 2x4

Recessed Prismatic 1L 25W 2x4 LED Recessed LJT24-40LWG-FSA12-EU 25 120 80 4,000 Ceiling Dual 1

27 Matt Garcia Career & College Academy Portable 9 Class (Middle) 12 2L 32W 48" T8 2x4

Recessed Prismatic 1L 25W 2x4 LED Recessed LJT24-40LWG-FSA12-EU 25 120 80 4,000

28 Matt Garcia Career & College Academy Portable 10 Class (Middle) 12 2L 32W 48" T8 2x4

Recessed Prismatic 1L 25W 2x4 LED Recessed LJT24-40LWG-FSA12-EU 25 120 80 4,000

29 Matt Garcia Career & College Academy Portable 11 Class (Middle) 12 2L 32W 48" T8 2x4

Recessed Prismatic 1L 25W 2x4 LED Recessed LJT24-40LWG-FSA12-EU 25 120 80 4,000

30 Matt Garcia Career & College Academy Portable 12 Class (Middle) 13 2L 32W 48" T8 2x4

Recessed Prismatic 1L 25W 2x4 LED Recessed LJT24-40LWG-FSA12-EU 25 120 80 4,000

31 Matt Garcia Career & College Academy Portable 13 Class (Middle) 12 2L 32W 48" T8 2x4

Recessed Prismatic 1L 25W 2x4 LED Recessed LJT24-40LWG-FSA12-EU 25 120 80 4,000

32 Matt Garcia Career & College Academy Portable 14 Class (Middle) 12 2L 32W 48" T8 2x4

Recessed Prismatic 1L 25W 2x4 LED Recessed LJT24-40LWG-FSA12-EU 25 120 80 4,000

33 Matt Garcia Career & College Academy Portable MPR Dining 24 2L 32W 48" T8 2x4

Recessed Prismatic 1L 25W 2x4 LED Recessed LJT24-40LWG-FSA12-EU 25 120 80 4,000

34 Matt Garcia Career & College Academy Exterior Exterior Exterior 13 1L 50W HPS N/A Flood

Clear 1L 18W LED Flood FFLED18 18 89 80 4,000

35 Matt Garcia Career & College Academy Exterior Exterior Exterior 2 1L 50W HPS N/A Wall

Pack Clear 1L 19W LED Wall Pack TWS-1-50K-120-PE 19 53 67 5,000

PacificWest Energy Solutions, Inc.18543 Devonshire Street #128Northridge, CA 91324 Page 4of 5

Main 800-310-9080www.PacWestES.com

Page 11: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

# Facility Bldg Room Area Type Fixture Qty Fixture Description Fixture Description Model Number Max Watts Min Lumens per Watt Min CRI Color

Temperature Accessories New Sensor New Relay Packs

36 Matt Garcia Career & College Academy Exterior Exterior Exterior 2 1L 50W HPS N/A Wall

Pack Prismatic 1L 19W LED Wall Pack TWS-1-50K-120-PE 19 53 67 5,000

37 Matt Garcia Career & College Academy Exterior Exterior Exterior 3 1L 70W HPS N/A Wall

Pack Prismatic 1L 19W LED Wall Pack TWS-1-50K-120-PE 19 53 67 5,000

38 Matt Garcia Career & College Academy Exterior Exterior Exterior 5 1L 50W HPS N/A Ceiling

Mount Opaque 1L 20W LED Canopy VANLED20N 20 113 74 4,000

39 Matt Garcia Career & College Academy Exterior Exterior Exterior 1 1L 100W HPS N/A Barn

Light N/A 1L 30W Screw-In LED Satco S8909 30 120 85 5,000

PacificWest Energy Solutions, Inc.18543 Devonshire Street #128Northridge, CA 91324 Page 5of 5

Main 800-310-9080www.PacWestES.com

Page 12: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

 

 

 

Fairfield‐Suisun Unified School District 

Bid B:  

Laurel Creek Elementary, Nelda Mundy Elementary, Matt 

Garcia Career and College Academy 

Manufacturer’s Specifications 

 Model Number Page 10.5A19/LED/827 2 14.5A19/LED/827 4 1SML32L8XX-4-TFA-02F-DIM 6 39-8-L60/840 9 BOA4S-20D10-40N-W 11 FFLED18 13 FSS440L840-UNV-DIM 15 KT-LED12T8-36GC-840-D 21 LEDFLT8-840-415-IT3F 23 LJT24-40LWG-FSA12-EU 25 LJT24-40LWSM-FSA12-EU 25 S8909 29 S9390 31 S9396 33 TWS-1-50K-120-PE 35 VANLED20N 37 WP130NPC 39 WP2LED24NPC 41 WPM-LED-36L-530-NW-UNV 43 DT-305 Ceiling Sensor 45 BZ-250 Power Pack 47

Page 13: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

A-Shape LED10.5A19/LED/827 ND 120V 6/1

Philips A-shape Dimmable LED lamps are the smart LED alternative to standardincandescents. The unique lamp design provides omi-directional light with excellentdimming performance.

Product data

General Information

Cap-Base E26 [ Single Contact Medium Screw]

Nominal Lifetime (Nom) 10950 h

Switching Cycle 50000X

Technical Type 10.5-75W

Light Technical

Color Code 827 [ CCT of 2700K]

Initial lumen (Nom) 1000 lm

Luminous Flux (Rated) (Nom) 1000 lm

Color Designation Warm White (WW)

Correlated Color Temperature (Nom) 2700 K

Luminous Efficacy (rated) (Nom) 95.24 lm/W

Color Consistency ANSI

Color Rendering Index (Nom) 80

LLMF At End Of Nominal Lifetime (Nom) 70 %

Operating and Electrical

Input Frequency 60 Hz

Power (Rated) (Nom) 10.5 W

Lamp Current (Nom) 180 mA

Wattage Equivalent 75 W

Starting Time (Nom) 0.5 s

Warm Up Time To 60% Light (Nom) 0.5 s

Power Factor (Nom) 0.5

Voltage (Nom) 120 V

Temperature

T-Case Maximum (Nom) 100 °C

Controls and Dimming

Dimmable No

Mechanical and Housing

Bulb Finish Frosted (FR)

Approval and Application

Suitable For Accent Lighting No

Product Data

Order product name 10.5A19/LED/827 ND 120V

EAN/UPC - Product 046677462987

Order code 462985

Numerator - Quantity Per Pack 1

Numerator - Packs per outer box 6

Material Nr. (12NC) 929001219324

Datasheet, 2017, January 10 data subject to change

LightingLighting

Page 14: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

Net Weight (Piece) 0.052 kg

Dimensional drawing

C

D

Bulb A19 120V 10W-75W 100D 2700K E26 ND

Product D C

10.5A19/LED/827 ND 120V 61 mm 107 mm

Photometric data

200 400300 500 6000

40

80

20

60

700 800

100

[nm]

Inte

nsity (

%)

sl16535 2015-12-09

Basic bulb 1 x 10.5W 2700K E26A60

1 x 1000 lm

Light output ratio 1.01Service upward 0.76Service downward 0.25

CIE flux code 8 28 58 25 101

UGRcen (4Hx8H, 0.25H) 21

Polar intensity diagram

(cd/1000lm) 0o

180o

60oo

60

90oo

90

120oo

120

150oo

150

50

50

100

100

150

150

200

200γ

Utilisation factor table

Ceiling mounted

Room

Index

k

Reflectances (%) for ceiling, walls and working plane (CIE)

0.60

0.80

1.00

1.25

1.50

2.00

2.50

3.00

4.00

5.00

0.80

0.50

0.30

0.33

0.42

0.49

0.56

0.61

0.70

0.76

0.80

0.86

0.90

0.80

0.50

0.10

0.31

0.39

0.45

0.51

0.56

0.62

0.67

0.70

0.75

0.78

0.70

0.50

0.30

0.29

0.37

0.43

0.49

0.54

0.61

0.66

0.70

0.75

0.79

0.70

0.50

0.20

0.28

0.36

0.41

0.47

0.51

0.58

0.63

0.66

0.71

0.74

0.70

0.50

0.10

0.28

0.35

0.40

0.45

0.49

0.55

0.59

0.62

0.66

0.69

0.70

0.30

0.10

0.21

0.28

0.33

0.38

0.43

0.49

0.54

0.57

0.62

0.65

0.50

0.30

0.10

0.16

0.21

0.25

0.29

0.32

0.37

0.41

0.44

0.48

0.50

0.50

0.10

0.10

0.12

0.17

0.21

0.25

0.28

0.33

0.37

0.40

0.45

0.48

0.30

0.30

0.10

0.11

0.14

0.17

0.20

0.22

0.26

0.29

0.31

0.34

0.36

0.30

0.10

0.10

0.08

0.11

0.14

0.17

0.19

0.23

0.26

0.28

0.32

0.34

0.00

0.00

0.00

0.01

0.02

0.03

0.04

0.05

0.07

0.09

0.10

0.12

0.13

Quantity estimation diagramnr. of luminaires

0

30

60

90

120

)2

(m10 30 50 70 90

300 lx

500 lx

750 lx

hroom: 2.8 mReflectances: 0.70, 0.50, 0.20Maintenance factor: 1.0

Ceiling mounted

UGR diagram

4.0

4.0

8.0

8.0

12.0

12.0

16.0

16.0

m

m

X

Y

hroom: 2.8 m

Refl: 0.70 0.50 0.20

Ceiling mounted

: viewed endwise

: viewed crosswise

Y : Parallel to viewing dir.

19

19

22

22

25

25

Luminance Table

)2

(cd/m

0.0 15.0 30.0 45.0 60.0 75.0 90.0

45.0

50.0

55.0

60.0

65.0

70.0

75.0

80.0

85.0

90.0

Plane

Cone

3880

4344

4875

5471

6140

6906

7766

8785

9941

11314

3880

4344

4875

5471

6140

6906

7766

8785

9941

11314

3880

4344

4875

5471

6140

6906

7766

8785

9941

11314

3880

4344

4875

5471

6140

6906

7766

8785

9941

11314

3880

4344

4875

5471

6140

6906

7766

8785

9941

11314

3880

4344

4875

5471

6140

6906

7766

8785

9941

11314

3880

4344

4875

5471

6140

6906

7766

8785

9941

11314

General Uniform Lighting

CalcuLuX Photometrics 4.5 Philips Lighting B.V. Page: 1/1

A-Shape LED

© 2017 Philips Lighting Holding B.V. All rights reserved. Philips Lighting reserves the right to make changes in specifications

and/or to discontinue any product at any timewithout notice or obligation and will not be liable for any consequences resulting

from the use of this publication.

www.lighting.philips.com

2017, January 10 - data subject to change

Page 15: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

A-Shape LED14.5A19/LED/827 ND 120V 6/1

Philips A-shape Dimmable LED lamps are the smart LED alternative to standardincandescents. The unique lamp design provides omi-directional light with excellentdimming performance.

Product data

General Information

Cap-Base E26 [ Single Contact Medium Screw]

Nominal Lifetime (Nom) 10950 h

Switching Cycle 50000X

Technical Type 14.5-100W

Light Technical

Color Code 827 [ CCT of 2700K]

Initial lumen (Nom) 1500 lm

Luminous Flux (Rated) (Nom) 1500 lm

Color Designation Soft White

Correlated Color Temperature (Nom) 2700 K

Luminous Efficacy (rated) (Nom) 103.4 lm/W

Color Consistency <6

Color Rendering Index (Nom) 80

LLMF At End Of Nominal Lifetime (Nom) 70 %

Operating and Electrical

Input Frequency 60 Hz

Power (Rated) (Nom) 14.5 W

Lamp Current (Nom) 234 mA

Wattage Equivalent 100 W

Starting Time (Nom) 0.5 s

Warm Up Time To 60% Light (Nom) 0.5 s

Power Factor (Nom) 0.8

Voltage (Nom) 120 V

Temperature

T-Case Maximum (Nom) 95 °C

Controls and Dimming

Dimmable No

Mechanical and Housing

Bulb Finish Frosted (FR)

Approval and Application

Suitable For Accent Lighting Yes

Energy Consumption kWh/1000 h 14.5 kWh

Product Data

Order product name 120V A19 E26 14.5W 2700K

EAN/UPC - Product 046677455682

Order code 455683

Numerator - Quantity Per Pack 1

Numerator - Packs per outer box 6

Datasheet, 2017, February 1 data subject to change

LightingLighting

Page 16: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

Material Nr. (12NC) 929001134904

Net Weight (Piece) 0.051 kg

Dimensional drawing

C

D

Bulb A19 120V 14.5W 150D 2700K E26 ND

Product D C

120V A19 E26 14.5W 2700K 61.0 mm 107.4 mm

Photometric data

200 400300 500 6000

40

80

20

60

700 800

100

[nm]

Inte

nsity (

%)

sl16535 2014-12-03

Basic bulb 1 x 14.5W 2700K E27A60 / 929001134900

1 x 1500 lm

Light output ratio 1.00Service upward 0.75Service downward 0.25

CIE flux code 8 28 59 25 100

UGRcen (4Hx8H, 0.25H) 23

Polar intensity diagram

(cd/1000lm) 0o

180o

60oo

60

90oo

90

120oo

120

150oo

150

50

50

100

100

150

150

200

200γ

Utilisation factor table

Ceiling mounted

Room

Index

k

Reflectances (%) for ceiling, walls and working plane (CIE)

0.60

0.80

1.00

1.25

1.50

2.00

2.50

3.00

4.00

5.00

0.80

0.50

0.30

0.33

0.41

0.48

0.55

0.61

0.69

0.75

0.79

0.85

0.90

0.80

0.50

0.10

0.31

0.39

0.45

0.51

0.55

0.62

0.66

0.70

0.74

0.77

0.70

0.50

0.30

0.29

0.36

0.42

0.48

0.53

0.61

0.66

0.69

0.75

0.78

0.70

0.50

0.20

0.28

0.35

0.41

0.47

0.51

0.58

0.62

0.65

0.70

0.73

0.70

0.50

0.10

0.28

0.34

0.40

0.45

0.49

0.55

0.59

0.62

0.66

0.69

0.70

0.30

0.10

0.21

0.27

0.33

0.38

0.42

0.49

0.53

0.57

0.62

0.65

0.50

0.30

0.10

0.16

0.20

0.25

0.29

0.32

0.37

0.41

0.43

0.47

0.50

0.50

0.10

0.10

0.12

0.17

0.20

0.25

0.28

0.33

0.37

0.40

0.44

0.47

0.30

0.30

0.10

0.10

0.14

0.17

0.20

0.22

0.26

0.28

0.30

0.33

0.36

0.30

0.10

0.10

0.08

0.11

0.14

0.17

0.19

0.23

0.26

0.28

0.31

0.34

0.00

0.00

0.00

0.01

0.02

0.03

0.04

0.05

0.07

0.09

0.10

0.12

0.14

Quantity estimation diagramnr. of luminaires

0

20

40

60

80

)2

(m10 30 50 70 90

300 lx

500 lx

750 lx

hroom: 2.8 mReflectances: 0.70, 0.50, 0.20Maintenance factor: 1.0Ceiling mounted

UGR diagram

4.0

4.0

8.0

8.0

12.0

12.0

16.0

16.0

m

m

X

Y

hroom: 2.8 m

Refl: 0.70 0.50 0.20

Ceiling mounted

: viewed endwise

: viewed crosswise

Y : Parallel to viewing dir.

22

22

25

25

Luminance Table

)2

(cd/m

0.0 15.0 30.0 45.0 60.0 75.0 90.0

45.0

50.0

55.0

60.0

65.0

70.0

75.0

80.0

85.0

90.0

Plane

Cone

5986

6706

7487

8388

9395

10531

11836

13332

15076

17111

5986

6706

7487

8388

9395

10531

11836

13332

15076

17111

5986

6706

7487

8388

9395

10531

11836

13332

15076

17111

5986

6706

7487

8388

9395

10531

11836

13332

15076

17111

5986

6706

7487

8388

9395

10531

11836

13332

15076

17111

5986

6706

7487

8388

9395

10531

11836

13332

15076

17111

5986

6706

7487

8388

9395

10531

11836

13332

15076

17111

General Uniform Lighting

CalcuLuX Photometrics 4.5 Philips Lighting B.V. Page: 1/1

A-Shape LED

© 2017 Philips Lighting Holding B.V. All rights reserved. Philips Lighting reserves the right to make changes in specifications

and/or to discontinue any product at any timewithout notice or obligation and will not be liable for any consequences resulting

from the use of this publication.

www.lighting.philips.com

2017, February 1 - data subject to change

Page 17: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

Surface_Modular_LED_1x4 08/16 page 1 of 3

Ordering guide Example: 1SML42L840-4-FA-02F-UNV-DIM

Width Family Lumen Package1 Color Length Door Frame Lens Voltage Driver Options

1 SML – 4 – – – –

1 1' SML Surface Modular LED

22L 2200lm32L 3200lm42L 4200lm50L 5000lm

830 3000K, 80CRI

835 3500K, 80CRI

840 4000K, 80CRI

850 5000K, 80CRI

4 4' FA Flat Aluminum

RA Regressed Aluminum

TFA Tamper Resistant Flat Aluminum

02F Pattern 12, .100" nominal diffuse 50%

12F DB-12, .125" nominal diffuse 50%

19F DB-19, .156" nominal diffuse 50%

56F .187", nominal DR high impact acrylic diffuse 50%

120 277 347 UNV Universal

Voltage 120-277V

DIM 0-10V dimming

SDIM Step dimming to 40% input power

XDIM2 MarkX phase dimming

F1 3/8" flex, 3 wire, 18 gauge 6'

F2 3/8" flex, 4 wire, 18 gauge 6'

F1/D 3/8" twin flex, 3 wire, 18 gauge 6', for dimmable luminaires

F2/5W 3/8" single flex, 5 wire, 18 gauge 6', for dimmable luminaires

EMLED3 Integral emergency battery pack

1W 1-way gasket between lens & door frame (not avail. for RA door frame)

2W 1-way & gasket between door frame & housing

3W 2-way & gasket betweem housing & ceiling (field installed)

GLR Fusing, fast blow

Project:

Location:

Cat.No:

Type:

Lamps: Qty:

Notes:

Surface

Surface Modular LED 1x4

2200, 3200, 4200, or

5000 lumens

The Philips Day-Brite / Philips CFI Surface Modular LED luminaire is a

shallow body, surface mounted premium grade luminaire with a variety of

door frames and lens options available.

Accessories (order separately)• TPDTH Tamper proof driver, Torx T-15 head pin drive and handle (required with TR option)• CS-400 Rigid canopy• CS-500 42° top swivel canopy• CS-12 12" Stem• CS-18 18" Stem• CS-24 24" Stem• CS-30 30" Stem• CS-36 36" Stem• CS-48 48" Stem

Footnotes1 Nominal lumens delivered2 XDIM option requires 120V or 277V to be specified3 Philips Bodine BSL310 1100 nominal lumens

Luminaire Catalog Number Input Power Efficacy

1x4

1SML32L840 29.7 111.9

1SML42L840 39.2 109.6

1SML50L840 47.4 108.2

Energy data

Page 18: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

Surface_Modular_LED_1x4 08/16 page 2 of 3

Application

• High efficacy long life solid state lighting platform.

• General lighting distribution is excellent for ambient lighting.

• High CRI source provides excellent color rendering, 80 CRI minimum.

• LEDs are an excellent source for use with controls since frequent switching does not affect the life of the light source.

Construction/Finish• Surface or pendant mounting requires 2

stems.

• 4" deep metal sided unit.

• Housing is multi-stage phosphate treated for maximum corrosion resistance and painted after fabrication with white polyester powder coating.

• K.O.’s provided in ends allow individual or continuous row mounting.

Electrical• Standard 0–10V dimming.

• Driver and LED boards are accessible from below. LED boards are individually replace-able if required.

• Five-year luminaire limited warranty includ-ing LED boards and driver. Visit www.philips.com/warranties for complete warranty infor-mation.

• High efficiency LEDs have 50,000 hour rated life (defined by testing at 70% lumen maintenance (L70)), based on 25°C ambient operating temperature.

• cETLus listed to UL and CSA standards, suit-able for damp location.

• Many luminaire components, such as reflectors, refractors, lenses, sockets, lampholders, and LEDs are made from various types of plastics which can be adversely affected by airborne contaminants. If sulfur based chemicals, petroleum based products, cleaning solutions, or other contaminants are expected in the intended area of use, consult factory for compatibility.

Enclosure• Mitered corner door frames painted after

fabrication with a choice of Flat Aluminum, Regressed Aluminum, or Tamper Resistant Flat Aluminum.

• Door frames standard with guide post spring loaded latches.

• Prismatic acrylic pattern 12 lens standard (02F). Other lenses optional.

• Can be hinged and latched from either side.

• TFA Door latches secured with 2 Torx head pin drive screws

• Special screwdriver required for TFA door, catalog #TPDTH sold separately

• #56F Lens withstands impact of 70 ft lbs. at 75°F. with the lens supported on all four edges.

1SML Surface Modular LED luminaire 1x42200, 3200, 4200, or 5000 lumens

CandlepowerAngle End 45 Cross

0 1586 1586 1586 5 1560 1577 1584 15 1491 1504 1504 25 1343 1339 1322 35 1113 1080 1029 45 825 763 683 55 501 430 380 65 290 244 244 75 164 150 166 85 63 55 62

Light DistributionDegrees Lumens % Luminaire 0-30 1187 35.7 0-40 1857 55.8 0-60 2839 85.3 0-90 3327 100.0 0-180 3327 100.0

Average LuminanceAngle End 45° Cross 45 4071 3764 3368 55 3044 2615 2311 65 2397 2016 2012 75 2207 2016 2234 85 2505 2213 2477

Catalog No. 1SML32L840-4-FA-02F-UNV-DIM

Test No. 36646

S/MH 1.1

Lamp Type LED

Lumens 3327

Input Watts 30

Comparative yearly lighting energy cost per 1000 lumens – $2.14 based on 3000 hrs. and $.08 pwr KWH.

The photometric results were obtained in the Philips Day-Brite laboratory which is NVLAP accredited by the National Institute of Standards and Technology.

Surface Modular LED 1x4 3200 nominal delivered lumens LER – 112

Coefficients of UtilizationEFFECTIVE FLOOR CAVITY REFLECTANCE 20 PER (pfc=0.20)pcc 80 70 50pw 70 50 30 70 50 30 50 30RCR0 118 118 118 115 115 115 111 1111 110 105 102 107 103 100 98 952 101 93 86 97 92 85 88 823 93 82 76 91 81 75 79 724 85 75 67 83 73 66 70 655 80 68 59 78 67 58 65 576 73 61 53 71 60 53 58 527 68 56 47 67 56 47 54 468 65 52 44 63 51 44 50 429 59 47 40 58 46 40 46 3910 56 44 36 56 44 36 42 35

Dimensions

Photometry

12-3/16 (309 mm)

4-1/16 (104 mm)

24"

48"(1219mm)

3"

3"

4-1/16"

4-5/16"

7/8" K.O.

11/16" DIA. K.O. (4)

DIMPLEW/.30"HOLE (4)2" K.O.

Page 19: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

Surface_Modular_LED_1x4 08/16 page 3 of 3

1SML Surface Modular LED luminaire 1x42200, 3200, 4200, or 5000 lumens

CandlepowerAngle End 45 Cross

0 2039 2039 2039 5 2006 2028 2037 15 1918 1933 1934 25 1728 1722 1699 35 1431 1391 1323 45 1061 984 878 55 686 594 508 65 373 315 313 75 211 192 213 85 81 71 78

CandlepowerAngle End 45 Cross

0 2424 2424 2424 5 2384 2411 2421 15 2279 2299 2298 25 2054 2048 2019 35 1701 1653 1578 45 1263 1169 1051 55 817 708 624 65 444 375 374 75 251 229 255 85 96 85 96

Light DistributionDegrees Lumens % Luminaire 0-30 1526 35.5 0-40 2388 55.6 0-60 3670 85.4 0-90 4298 100.0 0-180 4298 100.0

Light DistributionDegrees Lumens % Luminaire 0-30 1814 35.4 0-40 2842 55.4 0-60 4380 85.3 0-90 5132 100.0 0-180 5132 100.0

Average LuminanceAngle End 45° Cross 45 5232 4854 4331 55 4173 3614 3090 65 3076 2602 2586 75 2837 2591 2869 85 3238 2829 3133

Average LuminanceAngle End 45° Cross 45 6227 5767 5182 55 4967 4305 3796 65 3667 3094 3089 75 3382 3086 3432 85 3846 3386 3830

Catalog No. 1SML42L840-4-FA-02F-UNV-DIM

Test No. 36647

S/MH 1.1

Lamp Type LED

Lumens 4298

Input Watts 39

Comparative yearly lighting energy cost per 1000 lumens – $2.18 based on 3000 hrs. and $.08 pwr KWH.

The photometric results were obtained in the Philips Day-Brite laboratory which is NVLAP accredited by the National Institute of Standards and Technology.

Catalog No. 1SML50L840-4-FA-02F-UNV-DIM

Test No. 36648

S/MH 1.1

Lamp Type LED

Lumens 5132

Input Watts 47

Comparative yearly lighting energy cost per 1000 lumens – $2.22 based on 3000 hrs. and $.08 pwr KWH.

The photometric results were obtained in the Philips Day-Brite laboratory which is NVLAP accredited by the National Institute of Standards and Technology.

Surface Modular LED 1x4 4200 nominal delivered lumens

Surface Modular LED 1x4 5000 nominal delivered lumens

LER – 110

LER – 108

Coefficients of UtilizationEFFECTIVE FLOOR CAVITY REFLECTANCE 20 PER (pfc=0.20)pcc 80 70 50pw 70 50 30 70 50 30 50 30RCR0 118 118 118 115 115 115 111 1111 110 105 102 107 103 100 98 952 101 93 86 97 92 85 88 823 93 82 76 91 81 75 79 724 85 75 67 83 73 66 70 655 80 68 58 78 67 58 65 576 73 61 53 71 60 53 58 527 68 56 47 67 55 47 54 468 64 52 44 63 51 42 50 429 59 47 40 58 46 40 46 3910 56 44 36 56 44 36 42 35

Coefficients of UtilizationEFFECTIVE FLOOR CAVITY REFLECTANCE 20 PER (pfc=0.20)pcc 80 70 50pw 70 50 30 70 50 30 50 30RCR0 118 118 118 115 115 115 111 1111 110 105 102 107 103 100 98 952 101 93 86 97 92 85 88 823 93 82 76 91 81 75 79 724 85 75 67 83 73 66 70 655 80 68 58 77 67 58 64 576 73 60 53 71 60 53 58 527 68 56 47 67 55 47 54 468 64 52 44 63 51 42 50 429 59 47 40 58 46 40 46 3910 56 44 36 55 44 35 42 35

© 2016 Philips Lighting Holding B.V. All rights reserved.Philips reserves the right to make changes in specifications and/or to discontinue any product at any time without notice or obligation and will not be liable for any consequences resulting from the use of this publication.philips.com/luminaires

Philips Lighting North America Corporation200 Franklin Square Drive, Somerset, NJ 08873 Tel. 855-486-2216

Philips Lighting Canada Ltd.281 Hillmount Rd, Markham, ON, Canada L6C 2S3 Tel. 800-668-9008

Page 20: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

H.E. Williams, Inc. Car thage, Missouri www.hew.com 417-358-4065

CATALOG #: TYPE:

PROJECT: NOTES:

WrapsPage 1 of 2

SURFACE OR PENDANT MOUNT WRAP 39

FEATURESXX Designed for surface or suspended

applications.XX Diffuser is secured continuously along

luminaire sides.XX Individual or continuous row mounting.XX Tool-less wireway access and diffuser

replacement.XX LED technology provides high efficacy and

energy efficiency.XX Minimum 82 CRI; 3000K, 3500K, 4000K, or

5000K CCT.XX This fixture is proudly made in the USA.

EXAMPLE 39 - 4 - L52/835 - A - OPTIONS - DIM - UNV t t t t t t t t SERIES NOMINAL LUMEN CRI/ SHIELDING OPTIONS DRIVER VOLTAGE LENGTH PACKAGE CCT

LED

CROSS SECTIONS

ORDERING INFORMATIONSERIES

39 Surface or Pendant Mount Wrap39W Wide Surface or Pendant Mount Wrap

NOMINAL LENGTH4 4’8 8’

LED PACKAGEEXAMPLE: L52/835

LUMEN PACKAGE

NOMINAL LUMENS MINIMUM CRI & CCT

AVERAGE SYSTEM

WATTAGE4’

830 = 82 CRI, 3000K835 = 82 CRI, 3500K840 = 82 CRI, 4000K850 = 82 CRI, 5000K

L30 3,000 25L52 5,200 51L84 8,400 84

8’L60 6,000 61

L104 10,400 105L168 16,800 168

Nominal lumens based on 3500K CCT, actual lumens may vary.

SHIELDINGA Frosted ribbed acrylic

OPTIONSEM/10WLP Low-profile 10-watt emergency LED driver

(120V-277V only)(L__) Additional lower lumen packages available.

Specify in increments of 100 nominal lumens. Option must be specified with next higher lumen package. Example: 8,000 nominal lumens = 39-4-L84/835-(L80)

C2_ Two circuit quick-connect wiring harness (See Information section for complete quick-connect offering. Units ordered with quick-connect contain one endplate for continuous row mounting)

ACCESSORIES (shipped separately)See back and Technical Info for mounting accessories details.SS-12 Single stem and canopy, 12”SWS-12 Swivel stem and canopy, 12”ACF(Y12)24 24” adjustable Y aircraft cable with canopiesACF(Y12)48 48” adjustable Y aircraft cable with canopiesACF(Y12)96 96” adjustable Y aircraft cable with canopiesMSA Myers sway adapter

DRIVERAdditional dimming drivers available, see Technical Info.DRV Driver prewired for non-dimming applicationsDIM Driver prewired for 0-10V low voltage dimming

applications

VOLTAGE120 120V277 277VUNV 120-277V347 347V (not available with EM drivers)

4”

10-3/16”

39 Shown

4”

12-1/16”

39W Shown

39 Shown

Page 21: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

H.E . W ill iams, Inc . C ar thage, Missour i w w w.hew.com 417-35 8 - 4 0 6 5Information contained herein is subject to change without notice.

Wraps Page 2 of 2 HEW70534JL REV.08/24/16

39 SURFACE OR PENDANT WRAP

LED

SPECIFICATIONSHousing – 22-gauge die-formed C.R.S. and riveted construction.Shielding – Frosted ribbed acrylic.Finish – 92% minimum average reflective white polyester powder coat bonded to phosphate-free, multi-stage pretreated metal. All parts painted after fabrication to facilitate installation, increase efficiency, and inhibit corrosion.Electrical – High quality mid-power LED boards. Rated for 50,000 hours at 85% lumen maintenance (L85). Mounting – Surface or suspended.Labels – ccSAuS certified as luminaire suitable for dry or damp locations.Warranty – 5-year limited fixture warranty, see hew.com/warranty.

IMPORTANT:Electrostatic sensitive unit. Observe precautions when handling.

LED Product Partner

DLC qualified products listed at www.designlights.org

The U.S. Department of Energy’s Lighting Facts® Program has verified product performance based on industry-standardized testing. For details, see H.E. Williams 39 series at www.lightingfacts.com.

PHOTOMETRY39W-4-L52/835-A-DIM-UNV Report #: 19087.0; 07/28/15 | Total Luminaire Output: 5198 lumens; 51.1 WattsEfficacy: 101.7 lm/W | 84.3 CRI; 3531K CCT

0° 90°45°

100°

120°

140°160°180°

0° 20° 40°

60°

80°

90°

CAND

LEPO

WER

DIS

TRIB

UTIO

N

Vertical Angle

Horizontal Angle ZonalLumens0º 45º 90º

0 1981. 1981. 1981.5 1992. 1990. 1991. 190.015 1879. 1884. 1888. 533.925 1669. 1678. 1681. 776.335 1435. 1454. 1462. 911.545 1119. 1153. 1172. 890.255 771. 821. 857. 733.165 484. 548. 615. 545.975 230. 323. 403. 338.485 59. 168. 245. 175.390 0. 100. 164.95 0. 64. 121. 67.3105 0. 25. 57. 26.6115 0. 0. 29. 9.5125 0. 0. 0. 0.135 0. 0. 0. 0.145 0. 0. 0. 0.155 0. 0. 0. 0.165 0. 0. 0. 0.175 0. 0. 0. 0.185 0. 0. 0.

LUM

EN S

UMM

ARY

Zone Lumens % Fixture

0 - 30 1500. 28.90 - 40 2412. 46.40 - 60 4035. 77.60 - 90 5095. 98.090 - 120 103. 2.090 - 150 103. 2.090 - 180 103. 2.00 - 180 5198. 100.0

FIXTURE DETAILSBACK VIEW

A

C

ø2” KO

ø7/8” KO6”

B

10-3/16” (39)12-1/16” (39W)

NominalLength

A(Overall)

B(Stem/Cable O.C.)

C (Surface Mounting Holes)

3’ 36-1/16” 31” 28”4’ 48-1/16” 43” 40”8’ 96-1/16” 91” 88”

MOUNTING OPTIONS

SS-12 SWS-12

Page 22: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

BOA4S-20D10-40N-W

Upscaledesign,high-endperformance,undeniablevalue.BOAisdesignedwithproprietaryopticsthatdelivermaximumlumensandconcealtheLEDlightsourcesbehindthelenstocreateapleasingdimensionalilluminancewithsoftblendedbeamedges.

Color:White Weight:13.7lbs

Project: Type:

PreparedBy: Date:

DriverInfoType: ConstantCurrent120V: 0.16A208V: 0.12A240V: 0.11A277V: 0.10AInputWatts: 17WEfficiency: N/A

LEDInfoWatts: 20WColorTemp: 4000KColorAccuracy: 83CRIL70Lifespan: 100000Lumens: 1559Efficacy: 91LPW

TechnicalSpecificationsListingsULListing:Suitablefordamplocations.Recommendedforindooruseonly.

IESNALM-79&LM-80Testing:RABLEDluminaireshavebeentestedbyanindependentlaboratoryinaccordancewithIESNALM-79andLM-80,andhavereceivedtheDepartmentofEnergy"LightingFacts"label.

ElectricalDrivers:120-277V,0-10Vdimmingdownto10%,93.7%powerfactor,1kVsurgeprotection

DimmingDriver:Driverincludesdimmingcontrolwiringfor0-10Vdimmingsystems.Requiresseparate0-10VDCdimmingcircuit.Dimsaslowas10%.

Optical

Reflector:40°reflector

Aperture:2.5"

Construction

Housing:Precisionextrudedaluminum

Lens:High-transmission,microprismaticacryliclensforsmoothlightdistributionanduniformity

Finish:Formulatedforhigh-durabilityandlonglastingcolor.

GreenTechnology:MercuryandUVfree.RoHScompliantcomponents.PolyesterpowdercoatfinishformulatedwithouttheuseofVOCortoxicheavymetals.

Mounting:Fordirectceilingandwallmounting

LEDCharacteristics

LEDs:DiscreetLEDsonPCBboard

Lifespan:100,000-hourLEDlifespanbasedonIESLM-80resultsandTM-21calculations.

ColorConsistency:3-stepMacAdamEllipsebinningtoachieveconsistentfixture-to-fixturecolor.

ColorStability:LEDcolortemperatureiswarrantiedtoshiftnomorethan200KinCCTovera5yearperiod

ColorUniformity:RAB'srangeofCCT(CorrelatedColorTemperature)followstheguidelinesoftheAmericanNationalStandardforSpecificationsfortheChromaticityofSolidStateLighting(SSL)Products,ANSIC78.377-2015.

OtherWarranty:RABwarrantsthatourLEDproductswillbefreefromdefectsinmaterialsandworkmanshipforaperiodoffive(5)yearsfromthedateofdeliverytotheenduser,includingcoverageoflightoutput,colorstability,driverperformanceandfixturefinish.

CaliforniaTitle24:BOAcompliaswith2013CaliforniaTitle24buildingandelectricalcodesasacommercialindoorfixtureforgeneralspaceswhenusedwithavacancysensorand0-10Vdimmingcontrol.SelectavacancysensorusingcatalognumberLVS800.0-10Vdimmerprovidedbyothers.

CountryofOrigin:DesignedbyRABinNewJerseyandassembledinCalifornia.

BuyAmericanActCompliant:ThisproductisaCOTSitemmanufacturedintheUnitedStates,andiscompliantwiththeBuyAmericanAct.

RecoveryAct(ARRA)Compliant:Thisproductcomplieswiththe52.225-21"RequiredUseofAmericanIron,Steel,andManufacturedGoods--BuyAmericanAct--ConstructionMaterials(October2010).

GSASchedule:SuitableinaccordancewithFARSubpart25.4.

Needhelp?Techhelpline:(888)RAB-1000Email:[email protected]:www.rabweb.comCopyright©2014RABLightingInc.AllRightsReservedNote:Specificationsaresubjecttochangeatanytimewithoutnotice

Page1of2

Page 23: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

BOA4S-20D10-40N-W

Dimensions Features

Offersacleanflushmountdirectlytoaceilingorawall

3-stepbinningforcolorconsistency

0-10Vdimmingstandard

100,000-HourLEDlifespan

OrderingMatrix

Family Length Mount Watts Dimming Reflector ColorTemp Finish

BOA 4=4ft S=Surface 20=20W

40=40WD10=Dimmable 40=40°Reflector Y=3000K(Warm)

YN=3500K(WarmNeutral)N=4000K(Neutral)

B=BlackW=WhiteS=Silver

Needhelp?Techhelpline:(888)RAB-1000Email:[email protected]:www.rabweb.comCopyright©2014RABLightingInc.AllRightsReservedNote:Specificationsaresubjecttochangeatanytimewithoutnotice

Page2of2

Page 24: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

FFLED18

RectangularshapedLEDfloodlightdesignedtoreplace70WMetalHalide.PatentPendingairflowtechnologyensureslongLEDanddriverlifespan.Useforbuildingfacadelighting,signlighting,LEDlandscapelightingandinstant-onsecuritylighting.

Color:Bronze Weight:4.8lbs

Project: Type:

PreparedBy: Date:

DriverInfoType: ConstantCurrent120V: 0.2A208V: 0.15A240V: 0.13A277V: 0.11AInputWatts: 23WEfficiency: 78%

LEDInfoWatts: 18WColorTemp: 5000KColorAccuracy: 72CRIL70Lifespan: 100000Lumens: 2,310Efficacy: 100LPW

TechnicalSpecificationsListingsULListing:SuitableForWetLocations.Suitableforgroundmounting.

IESNALM-79&LM-80Testing:RABLEDluminaireshavebeentestedbyanindependentlaboratoryinaccordancewithIESNALM-79andLM-80,andhavereceivedtheDepartmentofEnergy"LightingFacts"label.

DLCListed:ThisproductisontheDesignLightsConsortium(DLC)QualifiedProductsListandiseligibleforrebatesfromDLCMemberUtilities.DLCProductCode:P0000170B

Optical

Lifespan:100,000-hourLEDlifespanbasedonIESLM-80resultsandTM-21calculations.

NEMAType:NEMABeamSpreadof7Hx6V

Construction

IPRating:IngressProtectionratingofIP66fordustandwater

Airflow:Airflowtechnologyheatsinkforsuperiorcooling.

AmbientTemperature:Suitableforusein104°F(40°C)ambienttemperatures.

ColdWeatherStarting:Minimumstartingtemperatureis-40°F(-40°C)

ThermalManagementHousing:Die-castaluminumhousing,lensframeandmountingarm.

Mounting:Heavy-dutymountingarmwith"O"ringseal&stainlesssteelscrew.

Reflector:Semi-specularanodizedaluminum.

Gaskets:High-temperaturesiliconegaskets.

Finish:Formulatedforhigh-durabilityandlonglastingcolor.

GreenTechnology:MercuryandUVfree.RoHScompliantcomponents.PolyesterpowdercoatfinishformulatedwithouttheuseofVOCortoxicheavymetals.

LEDCharacteristics

LEDs:Multi-chip,high-output,long-lifeLEDs

ColorConsistency:7-stepMacAdamEllipsebinningtoachieveconsistentfixture-to-fixturecolor.

ColorStability:LEDcolortemperatureiswarrantiedtoshiftnomorethan200KinCCTovera5yearperiod.

ColorUniformity:RAB'srangeofCCT(CorrelatedColorTemperature)followstheguidelinesoftheAmericanNationalStandardfor(SSL)Products,ANSIC78.377-2015.

Electrical

Driver:ConstantCurrent,Class2,100-277V,50-60Hz,100-277VAC0.4Amps.

THD:9.5%at120V,9.9%at277V

PowerFactor:99.4%at120V,96.2%at277V

SurgeProtection:6kV

Other

CaliforniaTitle24:SeeFFLED18/PC,FFLED18/PCS,FFLED18/PC2orFFLED18/PCS2fora2013CaliforniaTitle24compliantmodel.

Warranty:RABwarrantsthatourLEDproductswillbefreefromdefectsinmaterialsandworkmanshipforaperiodoffive(5)yearsfromthedateofdeliverytotheenduser,includingcoverageoflightoutput,colorstability,driverperformanceandfixturefinish.

Patents:TheFFLEDdesignisprotectedbyU.S.Pat.D643,147,CanadaPat.140798,ChinaPat.ZL201130171304.1,MexicoPat.36757andpendingpatentinTaiwan.

Needhelp?Techhelpline:(888)RAB-1000Email:[email protected]:www.rabweb.comCopyright©2014RABLightingInc.AllRightsReservedNote:Specificationsaresubjecttochangeatanytimewithoutnotice

Page1of2

Page 25: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

FFLED18

TechnicalSpecifications(continued)OtherAmericanBureauofShipping(ABS):ForuseonMobileOffshoreDrillingUnits(MODU)andshippingvessels.

Equivalency:Equivalentto70WMetalHalide.

Dimensions Features

UltraefficientLEDandopticaldesign

Replaces70WMHfloodlights

100,000hourlifebasedonLM-80tests

NEMAtype-7Hx6V

Air-flowtechnologyheatsink

5-yearwarranty

OrderingMatrix

Family Watts ColorTemp Finish Photocell

FFLED 18=18W Blank=5000K(Cool)

Y=3000K(Warm)N=4000K(Neutral)

Blank=BronzeW=White

Blank=NoPhotocell/PC=120VButton/PC2=277VButton

Needhelp?Techhelpline:(888)RAB-1000Email:[email protected]:www.rabweb.comCopyright©2014RABLightingInc.AllRightsReservedNote:Specificationsaresubjecttochangeatanytimewithoutnotice

Page2of2

Page 26: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

FluxStream_Strip 03/17 page 1 of 6

Project:

Location:

Cat.No:

Type:

Lumens: Qty:

Notes:

Linear

FluxStream strip

2', 3', 4' and 8'

Philips Day-Brite / CFI FluxStream LED Strip is a high performing

luminaire delivering smooth diffuse light ideal for light industrial,

commercial and residential applications with the unparalleled energy

efficiency of Philips LED lighting.

Accessories (order separately)• FSSD2L - 2' Diffuse replacement lens• FSSD3L - 3' Diffuse replacement lens• FSSD4L - 4' Diffuse replacement lens (order two for 8' models)• FSSWG4 - 4' wire guard (order two for 8' models)• FSTH - Sliding hanger bracket (set of two)• LSXR10 - Low bay PIR motion sensor, 120-277V• LSXR10ADC - Low bay PIR motion sensor with photocell and hi/lo trim dimming, 120-277V• (See last page for details and more options)

General notesMany luminaire components, such as reflectors, refractors, lenses, sockets, lampholders, and LEDs are made from various types of plastics which can be adversely affected by airborne contaminants. If sulfur based chemicals, petroleum based products, cleaning solutions, or other contaminants are expected in the intended area of use, consult factory for compatibility.

Ordering guide Example: FSS440L840-UNV-DIM

Series Length

(nominal)

Lumens2

(nominal)

Color temp.

(K)

Voltage Driver Options

FSS

FSS FluxStream Strip

2 2' length 20L 2000 lumens30L 3000 lumens

830 80 CRI, 3000K

835 80 CRI, 3500K

840 80 CRI, 4000K

8503 80 CRI, 5000K

UNV Universal voltage 120-277V

1204 120V2774 277V347 347V

DIM 0-10V 1% dimmingSDIM5,6 Step dimming to

40% input powerXDIM4,5,6 MarkX phase

dimmingDALI7 DALI

EMLED5,8 Factory wired Philips Bodine BSL310LP integral emergency pack. Nominal 1100lm

LSXR10 120-347V motion sensor, factory installed on end capLSXR10ADC 120-347V motion sensor with photocell and hi/lo trim

dimming, factory installed on end capDAYOCC9,10 Integral sensor, daylighting and occupancy, Philips

EasySense SNS102 PAF Paint after fabrication (white)BK Matte black paint colorST Satin aluminum paint color

3 3' length 30L 3000 lumens

4 4' length 40L 4000 lumens55L 5500 lumens70L 7000 lumens

8 8' length1 80L 8000 lumens110L 11000 lumens140L 14000 lumens

1. 8' is tandem (2) 4' lenses with single piece 8' body.2. Nominal delivered lumens at 25C ambient.3. Not available in 3' model.4. XDIM option must be specified with 120V or 277V option only.5. Not available in 2' or 3' model.6. Not available in 4' 70L model or 8' 140L model.7. DALI available up to 80L models only, consult factory for other options.8. EMLED on 8' models illuminates 4' section in emergency mode.9. Specify DIM driver with DAYOCC option.10. Not available in 8' 110L or 140L models.

- - -

Page 27: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

FluxStream_Strip 03/17 page 2 of 6

FSS FluxStream strip LED2', 3', 4' and 8'

Features

• Compact design for installation in tight spaces

• Frosted acrylic diffuser provides wide light distribution and superior glare control

• Diffuser and LED plate snap into place allowing tool-free access to LED boards and driver

• 2', 3', 4' and 8' tandem lengths available to accommodate many field applications

• Up to 100,000 hour predicted L70 LED lumen maintenance provides long service life to reduce maintenance costs

• Can be surface mounted on ceilings or walls, or suspended via chain, pendants or cables

• Wall mountable - ADA compliant

• Ideal for cold applications (-20°C)

• Continuous row mounting using standard end caps. No extra parts needed

• 7/8" knock out provided at each end and on base of luminaire

•Multiple driver options available with 0-10v as standard

• Enclosed lens minimizes penetration of dust, insects, and other debris into the LED compartment.

• 8' tandem unit is two 4' optical assemblies with a center mullion on a single full length chassis.

• Integral controls options include sensor mounted in control module extension mounted on fixture end (see dimension drawing). Controls are commissioned via intuitive Philips app on a Droid smartphone either through NFC or an IR blaster.

• Fluxstream luminaires are Designlights Consortium® qualifed. Please see the DLC QPL list for exact catalog numbers (http://www.designlights.org/QPL).

• 5 year manufacturer's limited warranty Visit www.philips.com/warranties for complete warranty information.

Finish

• Baked white acrylic matte high reflectance paint finish

Shielding

• Contoured frosted acrylic lens

Electrical

• LED boards and drivers are RoHS (Restriction of Hazardous Substances) compliant. Total system life rated at 50,000 hours. Predicted L70 lifetime based on LED manufacturer’s supplied LM-80 data and in-situ laboratory testing.

Materials

• Heavy gauge cold rolled steel housing, LED plate, and end caps

DAYOCC

• Integrated fixture mount Philips EasySense sensor featuring daylight and PIR occupancy sensing

• Compatibility with Philips Advance Xitanium SR Sensor Ready LED drivers

• Features automatic or manual on/off scenarios for code compliance and to realize full energy savings potential

• Basic grouping to a wireless switch via an IR interface with the Philips Field App

• Self-powered single rocker switch Illumra #ZBT-S1AWH (sourced by others), up to 40 luminaires may be grouped to a single switch

• Recommended maximum spacing of 25ft between luminaires, and closest luminaire to wall switch

Labels

• cETLus listed

• Suitable for damp locations

Page 28: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

FluxStream_Strip 03/17 page 3 of 6

FSS FluxStream strip LED2', 3', 4' and 8'

Fixture Lumens Wattage Efficacy

FSS220L 2000lm 17W 123lm/w

FSS330L 3000lm 26W 119lm/w

FSS440L 4000lm 31W 133lm/w

FSS455L 5500lm 45W 129lm/w

FSS470L 7000lm 58W 126lm/w

Performance data

Dimensions

7/8" Dia. K.O.

1-1/2"(38mm)

3"(76mm)

2-1/2"(64mm)

8 FT

4 FT

3 FT

2 FT

44-3/4"(1137mm)

33-1/2"(851mm)

22-1/2"(572mm)

44-3/4"(1137mm)

7/8" Dia. K.O. 7/8" Dia. K.O.9/16" Dia. K.O.

1/4" Dia. Hole

3/4" (19mm)1-3/8" (35mm)2-3/8" (60mm)

7/8" Dia. K.O.9/16" Dia. K.O.

1/4" Dia. Hole1/4" Dia. Hole

9/16" Dia. K.O. 7/8" Dia. K.O.

22-3/8"(568mm)

3/4" (19mm)1-3/8" (35mm)2-3/8" (60mm)

1/4" Dia. Hole9/16" Dia. K.O.

1/4" Dia. Hole9/16" Dia. K.O.

89-1/2"(2273mm)

7/8" Dia. K.O.9/16" Dia. K.O.

1/4" Dia. Hole15-3/4"

(400mm)

3/4" (19mm)1-3/8" (35mm)2-3/8" (60mm)

7/8" Dia. K.O.9/16" Dia. K.O.

1/4" Dia. Hole

3/4" (19mm)1-3/8" (35mm)2-3/8" (60mm)

7/8" Dia. K.O.

1-1/2"(38mm)

3"(76mm)

2-1/2"(64mm)

8 FT

4 FT

3 FT

2 FT

44-3/4"(1137mm)

33-1/2"(851mm)

22-1/2"(572mm)

44-3/4"(1137mm)

7/8" Dia. K.O. 7/8" Dia. K.O.9/16" Dia. K.O.

1/4" Dia. Hole

3/4" (19mm)1-3/8" (35mm)2-3/8" (60mm)

7/8" Dia. K.O.9/16" Dia. K.O.

1/4" Dia. Hole1/4" Dia. Hole

9/16" Dia. K.O. 7/8" Dia. K.O.

22-3/8"(568mm)

3/4" (19mm)1-3/8" (35mm)2-3/8" (60mm)

1/4" Dia. Hole9/16" Dia. K.O.

1/4" Dia. Hole9/16" Dia. K.O.

89-1/2"(2273mm)

7/8" Dia. K.O.9/16" Dia. K.O.

1/4" Dia. Hole15-3/4"

(400mm)

3/4" (19mm)1-3/8" (35mm)2-3/8" (60mm)

7/8" Dia. K.O.9/16" Dia. K.O.

1/4" Dia. Hole

3/4" (19mm)1-3/8" (35mm)2-3/8" (60mm)

–DAYOCC control module extension

3"(76mm)

Configuration Ambient

FSS470L -20°C to 30°C

FSS8110L -20°C to 35°C

FSS8140L -20°C to 25°C

EMLED option Minimum 0°C

All others -20°C to 40°C

Ambient temperature data

Page 29: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

FluxStream_Strip 03/17 page 4 of 6

FSS FluxStream strip LED2', 3', 4' and 8'

Photometry

Candlepower

Angle End 45 Cross Back-450 644 644 644 6445 635 641 646 64115 610 618 626 61825 520 567 585 56735 451 474 495 47445 371 403 432 40355 284 324 362 32465 191 243 288 24375 96 167 218 16785 18 105 155 105

Catalog No. FSS220L840-UNV-DIM

Test No. 37164

S/MH 1.2

Lamp Type LED

Lumens 2034

Input Watts 17

Comparative yearly lighting energy cost per 1000 lumens – $1.95 based on 3000 hrs. and $.08 pwr KWH.

The photometric results were obtained in the Philips Day-Brite laboratory which is NVLAP accredited by the National Institute of Standards and Technology.

Photometric values based on test performed in compliance with LM-79.

Coefficients of Utilization

EFFECTIVE FLOOR CAVITY REFLECTANCE 20 PER (pfc=0.20)pfc = 20Ceil 80 70 50Wall 70 50 30 70 50 30 50 30RCR0 118 118 118 114 114 114 108 1081 106 100 94 102 96 93 92 882 95 86 79 92 83 77 80 733 86 76 67 83 73 66 69 634 79 67 57 77 65 56 61 555 72 59 50 69 57 50 55 476 67 54 45 65 52 44 50 417 61 48 40 59 47 39 45 388 57 44 35 56 42 34 41 349 54 40 32 53 40 32 38 3010 51 38 30 49 37 29 35 29

2' FluxStream strip LED, 2000 nominal delivered lumens LER - 123

Average LuminanceZone End 45° Cross45 15155 12916 1295555 14048 11583 1185965 12449 10173 1078175 9646 8758 983985 4206 7611 9181

Light DistributionDegrees Lumens % Luminaire0-30 493 24.20-40 790 38.90-60 1391 68.40-90 1910 93.990-180 124 6.10-180 2034 100

Candlepower

Angle End 45 Cross Back-450 982 982 982 9825 966 978 980 97815 927 943 948 94325 849 869 884 86935 738 772 795 77245 609 655 690 65555 435 505 554 50565 293 356 414 35675 148 232 301 23285 28 129 201 129

Catalog No. FSS330L840-UNV-DIM

Test No. 37132

S/MH 1.3

Lamp Type LED

Lumens 3045

Input Watts 26

Comparative yearly lighting energy cost per 1000 lumens – $2.02 based on 3000 hrs. and $.08 pwr KWH.

The photometric results were obtained in the Philips Day-Brite laboratory which is NVLAP accredited by the National Institute of Standards and Technology.

Photometric values based on test performed in compliance with LM-79.

3' FluxStream strip LED, 3000 nominal delivered lumens LER - 119

Average LuminanceZone End 45° Cross45 16859 14162 1382355 14686 12197 1213865 13174 10098 1037675 10412 8269 911085 4882 6455 7980

Light DistributionDegrees Lumens % Luminaire0-30 759 24.90-40 1241 40.80-60 2187 71.80-90 2918 95.890-180 127 4.20-180 3045 100

Coefficients of Utilization

EFFECTIVE FLOOR CAVITY REFLECTANCE 20 PER (pfc=0.20)pfc = 20Ceil 80 70 50Wall 70 50 30 70 50 30 50 30RCR0 118 118 118 115 115 115 109 1091 107 101 96 103 98 93 93 902 96 88 81 93 85 79 81 763 88 77 68 84 75 67 70 654 80 68 58 78 66 57 63 565 73 60 51 70 58 51 56 486 68 55 45 66 53 45 51 447 63 48 40 60 47 40 46 398 58 45 36 56 44 35 42 349 55 40 33 53 40 33 39 3210 51 38 30 50 38 30 36 29

Page 30: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

FluxStream_Strip 03/17 page 5 of 6

FSS FluxStream strip LED2', 3', 4' and 8'

Photometry

Candlepower

Angle End 45 Cross Back-450 1272 1272 1272 12725 1250 1265 1277 126515 1199 1221 1237 122125 1098 1130 1157 113035 957 1005 1044 100545 791 860 910 86055 606 690 758 69065 382 481 598 48175 194 326 416 32685 36 196 289 196

Catalog No. FSS440L840-UNV-DIM

Test No. 37259

S/MH 1.3

Lamp Type LED

Lumens 4130

Input Watts 31

Comparative yearly lighting energy cost per 1000 lumens – $1.80 based on 3000 hrs. and $.08 pwr KWH.

The photometric results were obtained in the Philips Day-Brite laboratory which is NVLAP accredited by the National Institute of Standards and Technology.

Photometric values based on test performed in compliance with LM-79.

Coefficients of Utilization

EFFECTIVE FLOOR CAVITY REFLECTANCE 20 PER (pfc=0.20)pfc = 20Ceil 80 70 50Wall 70 50 30 70 50 30 50 30RCR0 118 118 118 114 114 114 108 1081 106 101 95 103 97 93 92 892 95 86 80 93 84 78 80 753 86 76 67 83 73 66 69 644 80 67 57 77 65 56 61 555 72 59 51 70 57 50 56 476 68 54 45 65 53 44 50 427 63 48 40 59 47 39 46 388 57 44 35 56 44 34 41 349 54 40 32 53 40 32 38 3010 51 38 30 49 37 29 35 28

4' FluxStream strip LED, 4000 nominal delivered lumens LER - 133

Average LuminanceZone End 45° Cross45 16754 14171 1384755 15678 12712 1261865 13207 10415 1137575 10615 8873 955085 5052 7511 8720

Light DistributionDegrees Lumens % Luminaire0-30 986 23.90-40 1614 39.10-60 2886 69.90-90 3905 94.690-180 225 5.40-180 4130 100

Candlepower

Angle End 45 Cross Back-450 1788 1788 1788 17885 1757 1777 1792 177715 1685 1715 1736 171525 1544 1585 1623 158535 1346 1408 1462 140845 1113 1202 1271 120255 852 960 1055 96065 575 712 828 71275 272 443 610 44385 50 259 389 259

Catalog No. FSS455L840-UNV-DIM

Test No. 37262

S/MH 1.3

Lamp Type LED

Lumens 5759

Input Watts 45

Comparative yearly lighting energy cost per 1000 lumens – $1.86 based on 3000 hrs. and $.08 pwr KWH.

The photometric results were obtained in the Philips Day-Brite laboratory which is NVLAP accredited by the National Institute of Standards and Technology.

Photometric values based on test performed in compliance with LM-79.

Coefficients of Utilization

EFFECTIVE FLOOR CAVITY REFLECTANCE 20 PER (pfc=0.20)pfc = 20Ceil 80 70 50Wall 70 50 30 70 50 30 50 30RCR0 118 118 118 115 115 115 108 1081 106 101 95 103 97 93 93 892 95 86 80 93 84 78 80 753 86 76 68 83 73 66 69 644 80 67 57 77 66 56 61 555 72 59 51 70 58 50 56 476 68 54 45 65 53 44 50 427 63 48 40 60 47 39 46 388 57 44 35 56 44 34 41 349 54 40 32 53 40 32 38 3010 51 38 30 49 37 29 36 29

4' FluxStream strip LED, 5500 nominal delivered lumens LER - 129

Average LuminanceZone End 45° Cross45 23558 19796 1934755 22047 17697 1757465 19887 15425 1574975 14898 12084 1402385 7023 9926 11749

Light DistributionDegrees Lumens % Luminaire0-30 1384 240-40 2264 39.30-60 4043 70.20-90 5478 95.190-180 281 4.90-180 5759 100

Page 31: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

FluxStream_Strip 03/17 page 6 of 6

FSS FluxStream strip LED2', 3', 4' and 8'

Photometry

Candlepower

Angle End 45 Cross Back-450 2211 2211 2211 22115 2176 2199 2217 219915 2088 2124 2148 212425 1914 1966 2010 196635 1672 1750 1813 175045 1379 1502 1580 150255 1058 1204 1317 120465 714 898 1041 89875 339 592 776 59285 63 344 524 344

Catalog No. FSS470L840-UNV-DIM

Test No. 37265

S/MH 1.3

Lamp Type LED

Lumens 7275

Input Watts 58

Comparative yearly lighting energy cost per 1000 lumens – $1.90 based on 3000 hrs. and $.08 pwr KWH.

The photometric results were obtained in the Philips Day-Brite laboratory which is NVLAP accredited by the National Institute of Standards and Technology.

Photometric values based on test performed in compliance with LM-79.

4' FluxStream strip LED, 7000 nominal delivered lumens LER - 126

Average LuminanceZone End 45° Cross45 29203 24745 2405055 27371 22192 2193865 24688 19451 1979375 18540 16135 1782585 8824 13174 15831

Light DistributionDegrees Lumens % Luminaire0-30 1714 23.60-40 2809 38.60-60 5028 69.10-90 6879 94.690-180 396 5.40-180 7275 100

Coefficients of Utilization

EFFECTIVE FLOOR CAVITY REFLECTANCE 20 PER (pfc=0.20)pfc = 20Ceil 80 70 50Wall 70 50 30 70 50 30 50 30RCR0 118 118 118 114 114 114 108 1081 106 100 95 103 97 93 92 892 95 86 79 92 83 78 80 733 86 76 67 83 73 66 69 634 79 67 57 77 65 56 61 555 72 59 50 69 57 48 55 476 67 54 44 65 52 44 50 417 61 47 40 59 46 39 45 388 57 44 35 56 42 34 40 349 54 40 32 52 40 32 38 3010 51 37 29 49 37 29 35 28

© 2017 Philips Lighting Holding B.V. All rights reserved. Philips reserves the right to make changes in specifications and/or to discontinue any product at any time without notice or obligation and will not be liable for any consequences resulting from the use of this publication. philips.com/luminaires

Philips Lighting North America Corporation200 Franklin Square Drive, Somerset, NJ 08873Tel. 855-486-2216

Philips Lighting Canada Ltd.281 Hillmount Rd, Markham, ON, Canada L6C 2S3Tel. 800-668-9008

Accessories

Accessory Catalog Code

Description

FSTH Sliding hanger bracket (pair)SV5F12 12" Stem and canopy kit

White stem and canopy kit, 1/4" trade size (1/2" O.D.) locknuts included. Works with 9/16" k.O. on base of housing.

SV5F18 18" Stem and canopy kitSV5F24 24" Stem and canopy kitSV5F36 36" Stem and canopy kitSV5F48 48" Stem and canopy kit

FKR-126 Chain hanger set (pair)Includes two 5' heavy duty link chains with "V" hooks. Attaches to base of housing.

DACHxx Adjustable cable hanger kit (single)

Works with 1/4" hole on base of housing or FSTH hanger bracket.

xx=cable length in inches, enter 48" to 180" lengths in 12" increments

DACHxx-1-SC Adjustable cable hanger kit with white straight 18/3 cord (single)

DACHxx-1-CC Adjustable cable hanger kit with white coiled 18/3 cord (single)DACHxx-2-SC Adjustable cable hanger kit with white straight 18/4 cord (single)

DACHxx-2-CC Adjustable cable hanger kit with white coiled 18/4 cord (single)

DACHxx-1D-SCAdjustable cable hanger kit with white straight 18/5 cord with dimming leads (single)

LSXR10 Low bay pir motion sensor (120-277v)LSXR10ADC Low bay pir motion sensor with photocell and hi/lo trim dimming (120-277v)FSSWG4 4' Wire guard (order two for 8' models)FSSD2L 2' Diffuse replacement lensFSSD3L 3' Diffuse replacement lensFSSD4L 4' Diffuse replacement lens (order two for 8' models)

SensorChain

CableBracket Stem Wire guardLSXR

Page 32: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

KT-LED12T8-36GC-840-DT8 LED LAMP

12W T8 LED | 4000K | >83 CRI | High Efficiency

DESCRIPTION

• Replacement for Conventional Fluorescent Lamp• 50,000+ Hour Lifetime • Environmentally Friendly: No Mercury Used• Instant Startup• Frosted Lens Eliminates Pixelation• UL Classified

• Operating Temperature: -20ºC/-4ºF to 45ºC/113ºF• Integral Driver (Isolated), Eliminates the Need

for External Driver or Ballast• 100+ Lumens per Watt• Improved Lamp Durability with Shatterproof Coated Glass• ETL Santiation Listed NSF/ANSI Standard 2 - Food Equipment

PRODUCT FEATURES

LAMP TYPE: Linear

BULB TYPE: T8 LED

BASE TYPE: G13 (Medium Bi-Pin)

WATTAGE: 12W

COLOR TEMPERATURE: 4000K

COLOR RENDERING INDEX (CRI): >83

WARRANTY: 5 Years

Page 1 of 2

Keystone Technologies • 208 Progress Drive, Montgomeryville, PA 18936 • Phone (800) 464-2680 • Fax (888) 966-0556 • www.keystonelamp.com

Specifications subject to change. Last revised on 8.24.15

OPERATING SPECIFICATIONS

RATED LIFEL70 (Hours) 50,000

PHOTOMETRIC CHARACTERISTICSColor Temperature (CCT) 4000K

Luminous Flux 1250 lm

Color Rendering Index (CRI) >83

Efficacy 104 lm/W

Beam Angle 240º

Visible Light Area 325º

ELECTRICAL CHARACTERISTICS Input Voltage Power Consumption Power Factor Input Current

120-277Vac 12W >0.90.108A @ 120V0.043A @ 277V

60.8

121.6

182.4

243.2

304.6

21

SPECTRAL DISTRIBUTION

POLAR CANDELA DISTRIBUTIONMaximum Candela = 1248.55Located at Horizontal Angle = 0, Vertical Angle 0

1. Violet Vertical Plane through Horizontal Angles (90-270)

2. Green Vertical Plane through Horizontal Angles (0-180)

Wavelength (nm)

Flux

(W

/nm

)

350 425 500 575 650 725 800

1.0

0.8

0.6

0.4

0.2

0.0

Flux (W/nm)

Page 33: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

ORDERING INFORMATIONORDER CODE PACKAGING STYLE PACK QTY. ITEM STATUS

KT-LED12T8-36GC-840-D-CP Carton Pack (Egg Crate Packaging) 25 Quick Ship

KT-LED12T8-36GC-840-D-DP Distributor Pack (Individual Cartons) 12 Quick Ship

Keystone Technologies • 208 Progress Drive, Montgomeryville, PA 18936 • Phone (800) 464-2680 • Fax (888) 966-0556 • www.keystonelamp.com

Specifications subject to change. Last revised on 8.24.15

KT-LED12T8-36GC-840-DT8 LED LAMP

Page 2 of 2

PHYSICAL CHARACTERISTICS LAMP DIMENSIONS

A (Illuminated Length) 32.36”

B (Body Length) 35.19”

C (Diameter) 1.10”

NOMINAL LENGTH: 36” BASE TYPE: G13 (Medium Bi-Pin)

C

B

A

Connect wires directly to these terminals

Typical Non-Shunted Lampholder

CAUTION: Use only non-shunted lampholders. Do not install product in a fixture with shunted lampholders (found in all fixtures using instant start bal-lasts). If the current lampholders are shunted, remove them and replace them with non-shunted lampholders. Make new con-

nections directly to terminals as indicated above.

Keystone can provide any style replacement lampholders. Call us at 800-464-2680.

WIRING DIAGRAMS1. Cut all existing connections to ballast as shown below and remove ballast.

Typical Ballast Configurations:PROGAM START

LINE

NEUTRAL

YELLOW

YELLOW RED

RED

BLUE

BLUE

LAMP

LAMP

BALLAST

PREHEAT WITH STARTER

LINE BLACK

BALLAST

LAMP

S

CAUTION: INSTANT START BALLAST WITH SHUNTED SOCKETS.

INSTANT START

LINE

NEUTRAL

BLUE

BLUE

RED

LAMP

LAMP

BALLAST

NEUTRAL

POWER SOURCELINE

NEUTRAL

LINE

Direct Drive LED Tube

Direct Drive LED Tube

Direct Drive LED Tube

Direct Drive LED Tube

No Live Connection

2. Re-wire fixture as shown below (maximum of 4 LED tubes per fixture).

CATALOG NUMBER BREAKDOWN

KT-LED12T8-36GC-840-D-CPKeystone

TechnologiesLED Lamp Nominal

Length (Inches)

Lamp Type

800 Series

Shatter- Proof

Coated Glass

Wattage Color Temp.

Packaging Style

Direct Drive Series

Page 34: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

Intellitube Linear Fluorescent Retrofit LED LampFor: T8 lamp replacement

Product SpecificationsLength

Body

Lens

Connection

Input voltage

Driver

Available colors

2’, 3' & 4' versions available

Oval extruded aluminum / polycarbonate lens

Clear (striated) or frosted available

Medium bi-pin (g13) end cap

100-277vac, 50/60hz

Integrated LED driver for Direct Wire modeExternal electronic ballast for Direct Fit mode

Zen - Warm 3500KFocused - Neutral 4000K Brilliant - Cool 5000K

CRI >80

Dimming

Lifetime

Environmental Requirements

Regulatory

Application

Direct Fit: compatible with dimming ballastDirect Wire: non-dimmable

Rated life of 50,000 hours (L70)

Operating temp: -20 to +50°C Storage temp: -30 to +60°C Working humidity: 30% to 85%Storage humidity: 10% to 90%Non-corrosive environments

UL, cUL, FCC, **DLC

UL tested for dry and damp locations

ENLIGHTEN AND INSPIRE

Features and Benefit

• Proprietary Universal Design - Direct Fit or Direct WireApplications

• Direct Fit for plug-and-play replacement of a fluorescent lamp

• Direct Wire for highest efficiency and lowest energy cost

• Quick and simple lighting upgrade

• Eliminate time-consuming maintenance

• Enjoy a brighter and better quality of light

• UV-free, IR-free, Mercury-free and Flicker Free

• Achieve your ROI in as little as 12 months

• Compatible with over 90% of instant start and select program

Start Ballasts ( visit energyfocus.com for compatibility list)

PRODUCT LINE LAMP TYPE COLOR TEMP LENGTH WATTAGE SERIES LENS

LEDFL LED Tube T8 Lamp 2’/ 24” 08 -IT3 C Clear

4’/ 48” 13-IT3B F Frosted

15

INTELLITUBE® SERIES ORDERING GUIDE

3’/ 36” 11

*835 Zen (3500K)

840 Focused (4000K)

*850 Brilliant (5000K)

Energy Focus , Inc. 32000 Aurora Road, Suite B, Solon, OH 44139 800.327.7877 // energyfocus.com © 2016 All Rights Reserved. Energy Focus, Inc. reserves the right to change specifications for product improvement without prior notice.

18

Intellitube® is a universal all-in-one lamp that offers both Direct Fit and

Direct Wire functions. In Direct Fit mode, it serves as a one-for-one

replacement of an existing fluorescent lamp. In the event of a ballast

failure, Intellitube® in Direct Wire mode can offer superior efficiency and

eliminate the expense of replacing the ballast.

Direct Wire Mode: LED tube lamp requires single end power only; wiring to one side of the fixture is sufficient. Ensure lamp end labeled “INPUT” is installed to the live circuit and must use non-shunted lamp holders.

* Extended lead times apply** DLC qualification only applies to 2' and 4' versions. 3' Intellitube is NOT DLC qualified

Page 35: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

Intellitube Series

PART NUMBER DIMENSION POWER LUMINOUS FLUX EFFICACY VOLTAGE POWER FACTOR

DIRECT WIRE

LEDFLT8-8XX-208-IT3C (24”) 2’ 8W 1040 lm 130 lm/W 100-277 VAC

LEDFLT8-8XX-208-IT3F (24”) 2’ 8W 960 lm 120 lm/W 100-277 VAC

LEDFLT8-8XX-413-IT3C (48”) 4’ 13W 1715 lm 130 lm/W 100-277 VAC

LEDFLT8-8XX-413-IT3F (48”) 4’ 13W 1615 lm 120 lm/W 100-277 VAC

LEDFLT8-8XX-415-IT3C (48”) 4’ 15W 1950 lm 130 lm/W 100-277 VAC

LEDFLT8-8XX-415-IT3F (48”) 4’ 15W 1800 lm 120 lm/W 100-277 VAC

LEDFLT8-8XX-418-IT3C (48”) 4’ 18W 2340 lm 130 lm/W 100-277 VAC

LEDFLT8-8XX-418-IT3F (48”) 4’ 18W 2160 lm 120 lm/W 100-277 VAC

DIRECT FIT

LEDFLT8-8XX-208-IT3C (24”) 2’ 11.3W 1325 lm 118 lm/W 100-277 VAC

LEDFLT8-8XX-208-IT3F (24”) 2’ 11.3W 1250 lm 111 lm/W 100-277 VAC

LEDFLT8-8XX-413-IT3C (48”) 4’ 16.6W 1960 lm 118 lm/W 100-277 VAC

LEDFLT8-8XX-413-IT3F (48”) 4’ 16.6W 1875 lm 112 lm/W 100-277 VAC

LEDFLT8-8XX-415-IT3C (48”) 4’ 16.9W 2090 lm 123 lm/W 100-277 VAC

LEDFLT8-8XX-415-IT3F (48”) 4’ 16.9W 1890 lm 112 lm/W 100-277 VAC

LEDFLT8-8XX-418-IT3C (48”) 4’ 17.3W 2175 lm 125.5 lm/W 100-277 VAC

LEDFLT8-8XX-418-IT3F (48”) 4’ 17.3W 2010 lm 116 lm/W 100-277 VAC

BATTERY PACK COMPATIBILITY

ACCESSORIES

Philips Bodine Emergency Battery Pack in Direct Fit installations (model no. ELI-S-20)Energy Focus Emergency Battery Pack in Direct Wire installations (model no. LEDES-PWR25-90M)

Single lampholder, no wires (Model no. LEDFLSLH-G13NS-SBOG)Pair of two (2) lampholders, one with 3’ wires (Model no. LEDFLSLH-G13NS-SNETGW)Single lampholder, with 3’ wires (Model no. LEDFLSLH-G13NS-SBOGW)

Data reflects DLC listing measurements. Consult EFOI Compatibility List for specific ballast data

LEDFLT8-8XX-208-IT3BC 3AV10086

LEDFLT8-8XX-208-IT3BF 3AV10186

LEDFLT8-8XX-413-IT3BC 3AV10136

LEDFLT8-8XX-413-IT3BF 3AV10136

LEDFLT8-8XX-415-IT3BC 3AV10156

LEDFLT8-8XX-415-IT3BF 3AV10156

LEDFLT8-8XX-418-IT3BC 3AV10186

LEDFLT8-8XX-418-IT3BF 3AV10186

BUY AMERICAN UL PART NUMBER

Energy Focus , Inc. 32000 Aurora Road, Suite B, Solon, OH 44139 800.327.7877 // energyfocus.com © 2016 All Rights Reserved. Energy Focus, Inc. reserves the right to change specifications for product improvement without prior notice.

LEDFLT8-8XX-311-IT3F (36”) 3’ 11W 1350 lm 120 lm/W 100-277 VAC

>0.9

>0.9

>0.9

>0.9

>0.9

>0.9

>0.9

>0.9

>0.9

LEDFLT8-8XX-311-IT3F (36”) 3’ 11W 1250 lm 110 lm/W 100-277 VAC

>0.9

>0.9

>0.9

>0.9

>0.9

>0.9

>0.9

>0.9

>0.9

LEDFLT8-8XX-311-IT3BF 3AV10116

Page 36: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

EXAMPLE L JT24-35MLG-FSA12-EUORDERING INFORMATION

FEATURES• Full distribution LED troffer• Direct replacement of fluorescent 2x4• Long-life, 60,000 hour LEDs at L80 reduce life cycle

maintenance costs• Four LED color choices and 80 CRI• Many shielding choices• Two door frame choices• Metal to metal light leak protection on all four sides of

shielding frame• Fixed output, step dimming (high/low/off), 0-10V dimming,

0-10V dimming-dim to dark drivers available• Hinged optical system allows easy access to LED modules and

electrical from below the ceiling• All models standard with IC rating• DesignLights Consortium® (DLC) qualified with many

configurations qualifying for DLC Premium; see www.designlights.org

• Five year warranty

CONSTRUCTIONLuminaire housing, end caps, and reflectors are die-formed code-gauge cold-rolled steel. Optical system hinges from either side for easy access to LED module and electrical components. Mechanical light trap prevents light leaks.

FINISHAll metal parts processed with a multi-stage phosphate bonding treatment and finished with a high reflectance baked white enamel.

SHIELDINGLens is high transmission pattern #12 acrylic (A12) for light diffusion without compromise to light output. Other shielding may be specified. If desired shielding media is not shown in ordering guide, contact your local Hubbell Lighting representative.

INSTALLATIONAn access plate is furnished with each recessed fixture for fast wiring connections without the necessity to open the fixture or wireway.

CEILING COMPATIBILITYDesigned for recessed installation in standard inverted tee grid ceilings (G). Four integral T-bar clips standard. Also available for recessed installation in hard ceilings (G with FK accessory), surface mount at ceiling plane (SM), or cable mount suspension below ceiling plane (CM). For compatibility with specific ceilings contact your Hubbell Lighting representative.

CERTIFICATIONAll luminaires are built to UL 1598 and 2108 standards, and bear appropriate CSA labels. Damp location labeling is standard. Emergency equipped fixtures labeled UL924. Adheres to LM79, LM80 and TM21 industry standards. IC rating is standard on all models. DesignLights Consortium® (DLC) and DLC Premium qualified. Please refer to the DLC website for specific product qualifications at www.designlights.org.

WARRANTYFive year warranty. (Terms and Conditions Apply)

LUMEN OUTPUTXW Extra Low WattVW Very Low WattMW Medium Low WattLW Low Watt

ML Medium LumenHL High LumenVL Very High LumenXL Extra High Lumen

See Product Availability Table Below

– – – –LJT 24

SIZE 24 2' × 4'

VOLTAGEU 120V-277V

COLOR TEMP30 3000K35 3500K40 4000K50 5000K

MODELLJT LED Lensed

Troffer

CEILING TYPEG Grid1

SM Surface Mount

CM Cable Mount2

U

DOORFS White

Flush SteelFA White

Flush Aluminum

OPTIONSC388 3-Wire FlexC488 4-Wire FlexC588 5-Wire Flex

ELL14 Emergency Battery Pack Installed, 1400 Lumens5,6

GLR Fast Blow FuseGTD Generator Transfer

DeviceG1 Single Gasketing

(Door to Housing)G2 Double Gasketing

(G1 and Lens to Door)G3 Triple Gasketing

(G2 and Housing to Ceiling)

CP Chicago Plenum

ACCESSORIES(ORDER SEPARATELY)

FK24 2' × 4' Single Flange Kit

CM48Y2SC3F-KIT 48" Cable Mount Kit for 2' wide CM ceiling type, 3 Wire Feed Cord

SHIELDINGA12 Pattern 12 Acrylic

LensA12125 Pattern 12 Acrylic

Lens, 0.125" Nominal

A12F Pattern 12 Frosted Acrylic Lens

A12125F Pattern 12 Frosted Acrylic Lens, 0.125" Nominal

A19 Pattern 19 Acrylic Lens, 0.156" Nominal

A19F Pattern 19 Frosted Acrylic Lens 0.156"

1 For hard ceilings use flange kit accessory.2 Order hanger accessories separately.3 Not available with XL lumen output.4 50 watt and below.5 For compatibility with Dual-Lite LiteGear®

inverters in lieu of installed battery pack, contact Hubbell Lighting Representative.

6 Not available with Surface Mount.Damp label—standard.IC rating—standard.

DRIVERE Fixed Output

ESD Step DimmingED 0-10V Dimming

ED1 0-10V 1% Dimming

EDD 0-10V Dimming, Dim to Dark3

LUTH Hi-lume 1% EcoSystem LED driver with Soft-on, Fade-to-Black dimming technology 4

LUT5 5-Series EcoSystem LED driver 4

DRIVER AVAILABILITY TABLEXW VW MW LW ML HL VL XL

E X X X X X X X XESD X X X X XED X X X X X X X X

ED1 X X X X X X X XEDD X X X X X X X X

LUTH X X X X X X X XLUT5 X X X X X X X X

LJT242' × 4' LED Troffer

LED / LJT24Page 1/3 Rev. 02/15/17

© 2017 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Catalog No.

Project Name Type

Date

PROJECT INFORMATION

Page 37: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

Product Availability

Lumen Package Lumens Input Watts LPW

LJT24-50XWG-FSA12-EU 2919 20 145

LJT24-40XWG-FSA12-EU 2681 20 133

LJT24-35XWG-FSA12-EU 2640 20 131

LJT24-30XWG-FSA12-EU 2563 20 127

LJT24-50VWG-FSA12-EU 3806 27 142

LJT24-40VWG-FSA12-EU 3495 27 130

LJT24-35VWG-FSA12-EU 3441 27 128

LJT24-30VWG-FSA12-EU 3341 27 125

LJT24-50MWG-FSA12-EU 4297 31 140

LJT24-40MWG-FSA12-EU 3946 31 129

LJT24-35MWG-FSA12-EU 3886 31 127

LJT24-30MWG-FSA12-EU 3772 31 123

LJT24-50LWG-FSA12-EU 4720 34 139

LJT24-40LWG-FSA12-EU 4334 34 127

LJT24-35LWG-FSA12-EU 4268 34 126

LJT24-30LWG-FSA12-EU 4144 34 122

LJT24-50MLG-FSA12-EU 5218 38 136

LJT24-40MLG-FSA12-EU 4792 38 125

LJT24-35MLG-FSA12-EU 4718 38 123

LJT24-30MLG-FSA12-EU 4581 38 119

LJT24-50HLG-FSA12-EU 6017 45 133

LJT24-40HLG-FSA12-EU 5526 45 122

LJT24-35HLG-FSA12-EU 5441 45 120

LJT24-30HLG-FSA12-EU 5286 45 117

LJT24-50VLG-FSA12-EU 8191 59 138

LJT24-40VLG-FSA12-EU 7522 59 127

LJT24-35VLG-FSA12-EU 7407 59 125

LJT24-30VLG-FSA12-EU 7192 59 121

LJT24-50XLG-FSA12-EU 9763 73 134

LJT24-40XLG-FSA12-EU 8966 73 123

LJT24-35XLG-FSA12-EU 8829 73 121

LJT24-30XLG-FSA12-EU 8571 73 117

LJT242' × 4' LED Troffer

LED / LJT24Page 2/3 Rev. 02/15/17

© 2017 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 38: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

PHOTOMETRIC DATA

Luminaire LJT24-40LWG-FSA12-EULJT LED, Lensed Troffer2' X 4' LED with A12 pattern acrylic prismed lens

Ballast XI040C110V054BST1Ballast Factor 1.00Lamp LEDFixture Lumens 4334Watts 34.00Mounting RecessedShielding Angle 0º = 90 90º = 90Spacing Criterion 0º = 1.19 90º = 1.19Luminous Opening in feet

Length: 3.92 Width: 1.92 Height: 0.00

Luminaire LJT24-40MLG-FSA12-EULJT LED, Lensed Troffer2' X 4' LED with A12 pattern acrylic prismed lens

Ballast XI040C110V054BST1Ballast Factor 1.00Lamp LEDFixture Lumens 4792Watts 38.40Mounting RecessedShielding Angle 0º = 90 90º = 90Spacing Criterion 0º = 1.19 90º = 1.19Luminous Opening in feet

Length: 3.81 Width: 1.80 Height: 0.00

Luminaire LJT24-40HLG-FSA12-EULJT LED, Lensed Troffer2' X 4' LED with A12 pattern acrylic prismed lens

Ballast XI054C150V054BST1Ballast Factor 1.00Lamp LEDFixture Lumens 5526Watts 45.20Mounting RecessedShielding Angle 0º = 90 90º = 90Spacing Criterion 0º = 1.18 90º = 1.18Luminous Opening in feet

Length: 3.81 Width: 1.80 Height: 0.00

INDOOR CANDELA PLOT

INDOOR CANDELA PLOT

INDOOR CANDELA PLOT

ENERGY DATATotal Luminaire Efficiency 100.0%

Total Lumens per Watt 127ANSI/IESNA RP-1-2004 Compliance

Noncompliant

Comparative Yearly Lighting Energy Cost per 1000 Lumens

$1.89 based on 3000 hrs. and $0.08 per KWH

ENERGY DATATotal Luminaire Efficiency 100.0%

Total Lumens per Watt 125ANSI/IESNA RP-1-2004 Compliance

Noncompliant

Comparative Yearly Lighting Energy Cost per 1000 Lumens

$1.90 based on 3000 hrs. and $0.08 per KWH

ENERGY DATATotal Luminaire Efficiency 100.0%

Total Lumens per Watt 122ANSI/IESNA RP-1-2004 Compliance

Noncompliant

Comparative Yearly Lighting Energy Cost per 1000 Lumens

$1.95 based on 3000 hrs. and $0.08 per KWH

LUMINAIRE DATA

LUMINAIRE DATA

LUMINAIRE DATA

Test 16399 Test Date 06/28/2016

Test 16402 Test Date 06/27/2016

Test 16405 Test Date 06/28/2016

ZONAL LUMEN SUMMARYZone Lumens %Lamp %Fixt.0-30 1456 33.6 33.60-40 2317 53.5 53.50-60 3680 84.9 84.90-90 4334 100.0 100.00-180 4334 100.0 100.0

ZONAL LUMEN SUMMARYZone Lumens %Lamp %Fixt.0-30 1609 33.6 33.60-40 2562 53.5 53.50-60 4069 84.9 84.90-90 4792 100.0 100.00-180 4792 100.0 100.0

ZONAL LUMEN SUMMARYZone Lumens %Lamp %Fixt.0-30 1870 33.8 33.80-40 2975 53.8 53.80-60 4704 85.1 85.10-90 5526 100.0 100.00-180 5526 100.0 100.0

Tel 864 678 1000 701 Millennium Blvd. Greenville, SC 29607

LUMINAIRE: LJT24-40LWG-FSA12-EU LJT LED, Lensed Troffer 2' X 4' LED with A12 pattern acrylic prismed lens Data scaled from test 16.01603BALLAST: XI040C110V054BST1BALLAST FACTOR: 1.00LAMP: LedFIXTURE LUMENS: 4334WATTS: 34.00MOUNTING: RecessedSHIELDING ANGLE: 0º = 90 90º = 90SPACING CRITERION: 0º = 1.19 90º = 1.19LUMINOUS OPENING IN FEET

LENGTH: 3.92WIDTH: 1.92HEIGHT: 0.00

TEST #16399DATE: 6/28/2016

TOTAL LUMINAIRE EFFICIENCY = 100.0TOTAL LUMENS PER WATT = 127

ANSI/IESNA RP-1-2004 COMPLIANCE: NONCOMPLIANTCOMPARATIVE YEARLY LIGHTING ENERGY COST PER 1000 LUMENS = $1.89

BASED ON 3000 HRS. AND $.08 PER KWH

ZONAL LUMENSZONE LUMENS % LAMP % FIXTURE0-300-400-600-900-180

1456 33.6 33.62317 53.5 53.53680 84.9 84.94334 100.0 100.04334 100.0 100.0

INDOOR CANDELA PLOT

Horiz 0-180

1000

2000

0 15 30 45

90

75

60

0.0 45.0 90.0

CANDELA/SQ MAVERAGE LUMINANCEANGLE 0.0 22.5 45.0 67.5 90.0

03040455055606570758085

2730 2730 2730 2730 27302525 2543 2525 2520 25222250 2261 2257 2248 22532067 2087 2075 2053 20411882 1882 1878 1816 17911668 1651 1611 1528 15091470 1413 1299 1279 12871303 1184 1049 1130 11781196 1066 924 1100 11831205 1072 961 1160 13151318 1120 1120 1351 15241411 1280 1329 1641 1756

ZONAL CAVITY METHODCOEFFICIENTS OF UTILIZATION (%)EFFECTIVE FLOOR CAVITY REFLECTANCE = 20%

RC 0%80% 70% 50% 30% 10%RW 70% 50% 30% 10% 70% 50% 30% 10% 50% 30% 10% 50% 30% 10% 50% 30% 10% 0%

RCR

0123456789

10

119 119 119 119 116 116 116 116 111 111 111 106 106 106 102 102 102 100110 105 101 98 107 103 99 96 99 96 93 95 92 90 91 89 87 85101 93 87 81 98 91 85 80 88 83 79 84 80 77 81 78 75 7393 83 75 69 90 81 74 69 78 72 67 76 70 66 73 69 65 6385 74 66 60 83 73 65 59 70 64 58 68 62 58 66 61 57 5579 67 58 52 77 66 58 52 64 57 51 62 56 51 60 55 50 4873 61 52 46 71 60 52 46 58 51 46 56 50 45 55 49 45 4368 55 47 41 66 55 47 41 53 46 41 52 45 40 50 45 40 3864 51 43 37 62 50 42 37 49 42 37 48 41 37 46 41 36 3560 47 39 34 58 46 39 34 45 38 33 44 38 33 43 37 33 3156 43 36 31 55 43 36 31 42 35 30 41 35 30 40 34 30 29

RCR = ROOM CAVITY RATIO RC = EFFECTIVE CEILING CAVITY REFLECTANCE RW = WALL REFLECTANCE

THE DATA IN THIS REPORT ARE BASED ON ABSOLUTE MEASUREMENTS.ANSI/IESNA RP-1 COMPLIANCE IS BASED ON ABSOLUTE MEASUREMENTS.THIS TEST RUN IN ACCORDANCE WITH CURRENT I.E.S.N.A. PUBLISHED PROCEDURES.

APPROVED BY:______________Tel 864 678 1000 701 Millennium Blvd. Greenville, SC 29607

LUMINAIRE: LJT24-40LWG-FSA12-EU LJT LED, Lensed Troffer 2' X 4' LED with A12 pattern acrylic prismed lens Data scaled from test 16.01603BALLAST: XI040C110V054BST1BALLAST FACTOR: 1.00LAMP: LedFIXTURE LUMENS: 4334WATTS: 34.00MOUNTING: RecessedSHIELDING ANGLE: 0º = 90 90º = 90SPACING CRITERION: 0º = 1.19 90º = 1.19LUMINOUS OPENING IN FEET

LENGTH: 3.92WIDTH: 1.92HEIGHT: 0.00

TEST #16399DATE: 6/28/2016

TOTAL LUMINAIRE EFFICIENCY = 100.0TOTAL LUMENS PER WATT = 127

ANSI/IESNA RP-1-2004 COMPLIANCE: NONCOMPLIANTCOMPARATIVE YEARLY LIGHTING ENERGY COST PER 1000 LUMENS = $1.89

BASED ON 3000 HRS. AND $.08 PER KWH

ZONAL LUMENSZONE LUMENS % LAMP % FIXTURE0-300-400-600-900-180

1456 33.6 33.62317 53.5 53.53680 84.9 84.94334 100.0 100.04334 100.0 100.0

INDOOR CANDELA PLOT

Horiz 0-180

1000

2000

0 15 30 45

90

75

60

0.0 45.0 90.0

CANDELA/SQ MAVERAGE LUMINANCEANGLE 0.0 22.5 45.0 67.5 90.0

03040455055606570758085

2730 2730 2730 2730 27302525 2543 2525 2520 25222250 2261 2257 2248 22532067 2087 2075 2053 20411882 1882 1878 1816 17911668 1651 1611 1528 15091470 1413 1299 1279 12871303 1184 1049 1130 11781196 1066 924 1100 11831205 1072 961 1160 13151318 1120 1120 1351 15241411 1280 1329 1641 1756

ZONAL CAVITY METHODCOEFFICIENTS OF UTILIZATION (%)EFFECTIVE FLOOR CAVITY REFLECTANCE = 20%

RC 0%80% 70% 50% 30% 10%RW 70% 50% 30% 10% 70% 50% 30% 10% 50% 30% 10% 50% 30% 10% 50% 30% 10% 0%

RCR

0123456789

10

119 119 119 119 116 116 116 116 111 111 111 106 106 106 102 102 102 100110 105 101 98 107 103 99 96 99 96 93 95 92 90 91 89 87 85101 93 87 81 98 91 85 80 88 83 79 84 80 77 81 78 75 7393 83 75 69 90 81 74 69 78 72 67 76 70 66 73 69 65 6385 74 66 60 83 73 65 59 70 64 58 68 62 58 66 61 57 5579 67 58 52 77 66 58 52 64 57 51 62 56 51 60 55 50 4873 61 52 46 71 60 52 46 58 51 46 56 50 45 55 49 45 4368 55 47 41 66 55 47 41 53 46 41 52 45 40 50 45 40 3864 51 43 37 62 50 42 37 49 42 37 48 41 37 46 41 36 3560 47 39 34 58 46 39 34 45 38 33 44 38 33 43 37 33 3156 43 36 31 55 43 36 31 42 35 30 41 35 30 40 34 30 29

RCR = ROOM CAVITY RATIO RC = EFFECTIVE CEILING CAVITY REFLECTANCE RW = WALL REFLECTANCE

THE DATA IN THIS REPORT ARE BASED ON ABSOLUTE MEASUREMENTS.ANSI/IESNA RP-1 COMPLIANCE IS BASED ON ABSOLUTE MEASUREMENTS.THIS TEST RUN IN ACCORDANCE WITH CURRENT I.E.S.N.A. PUBLISHED PROCEDURES.

APPROVED BY:______________

Tel 864 678 1000 701 Millennium Blvd. Greenville, SC 29607

LUMINAIRE: LJT24-40MLG-FSA12-EU LJT LED, Lensed Troffer 2' X 4' LED with A12 pattern acrylic prismed lens Data scaled from test 16.01605BALLAST: XI040C110V054BST1BALLAST FACTOR: 1.00LAMP: LedFIXTURE LUMENS: 4792WATTS: 38.40MOUNTING: RecessedSHIELDING ANGLE: 0º = 90 90º = 90SPACING CRITERION: 0º = 1.19 90º = 1.19LUMINOUS OPENING IN FEET

LENGTH: 3.81WIDTH: 1.80HEIGHT: 0.00

TEST #16402DATE: 6/27/2016

TOTAL LUMINAIRE EFFICIENCY = 100.0TOTAL LUMENS PER WATT = 125

ANSI/IESNA RP-1-2004 COMPLIANCE: NONCOMPLIANTCOMPARATIVE YEARLY LIGHTING ENERGY COST PER 1000 LUMENS = $1.90

BASED ON 3000 HRS. AND $.08 PER KWH

ZONAL LUMENSZONE LUMENS % LAMP % FIXTURE0-300-400-600-90

0-180

1609 33.6 33.62562 53.5 53.54069 84.9 84.94792 100.0 100.04792 100.0 100.0

INDOOR CANDELA PLOT

Horiz 0-180

1100

2200

0 15 30 45

90

75

60

0.0 45.0 90.0

CANDELA/SQ MAVERAGE LUMINANCEANGLE 0.0 22.5 45.0 67.5 90.0

03040455055606570758085

3313 3313 3313 3313 33133068 3085 3068 3050 30572735 2746 2741 2723 27232513 2535 2526 2479 24772288 2286 2281 2198 21662044 2006 1957 1850 18281786 1714 1582 1538 15631586 1434 1281 1363 14221464 1290 1115 1326 14411461 1292 1164 1401 15951600 1365 1374 1636 18621765 1549 1603 1981 2143

ZONAL CAVITY METHODCOEFFICIENTS OF UTILIZATION (%)EFFECTIVE FLOOR CAVITY REFLECTANCE = 20%

RC 0%80% 70% 50% 30% 10%RW 70% 50% 30% 10% 70% 50% 30% 10% 50% 30% 10% 50% 30% 10% 50% 30% 10% 0%

RCR

0123456789

10

119 119 119 119 116 116 116 116 111 111 111 106 106 106 102 102 102 100110 105 101 98 107 103 99 96 99 96 93 95 92 90 91 89 87 85101 93 87 81 98 91 85 80 88 83 79 84 80 77 81 78 75 7393 83 75 69 90 81 74 69 78 72 67 76 70 66 73 69 65 6385 74 66 60 83 73 65 59 70 64 58 68 62 58 66 61 57 5579 67 58 52 77 66 58 52 64 57 51 62 56 51 60 55 50 4873 61 52 46 71 60 52 46 58 51 46 56 50 45 55 49 45 4368 55 47 41 66 55 47 41 53 46 41 52 45 40 50 45 40 3864 51 43 37 62 50 42 37 49 42 37 48 41 37 46 41 36 3560 47 39 34 58 46 39 34 45 38 33 44 38 33 43 37 33 3156 43 36 31 55 43 36 31 42 35 30 41 35 30 40 34 30 29

RCR = ROOM CAVITY RATIO RC = EFFECTIVE CEILING CAVITY REFLECTANCE RW = WALL REFLECTANCE

THE DATA IN THIS REPORT ARE BASED ON ABSOLUTE MEASUREMENTS.ANSI/IESNA RP-1 COMPLIANCE IS BASED ON ABSOLUTE MEASUREMENTS.THIS TEST RUN IN ACCORDANCE WITH CURRENT I.E.S.N.A. PUBLISHED PROCEDURES.

APPROVED BY:______________Tel 864 678 1000 701 Millennium Blvd. Greenville, SC 29607

LUMINAIRE: LJT24-40MLG-FSA12-EU LJT LED, Lensed Troffer 2' X 4' LED with A12 pattern acrylic prismed lens Data scaled from test 16.01605BALLAST: XI040C110V054BST1BALLAST FACTOR: 1.00LAMP: LedFIXTURE LUMENS: 4792WATTS: 38.40MOUNTING: RecessedSHIELDING ANGLE: 0º = 90 90º = 90SPACING CRITERION: 0º = 1.19 90º = 1.19LUMINOUS OPENING IN FEET

LENGTH: 3.81WIDTH: 1.80HEIGHT: 0.00

TEST #16402DATE: 6/27/2016

TOTAL LUMINAIRE EFFICIENCY = 100.0TOTAL LUMENS PER WATT = 125

ANSI/IESNA RP-1-2004 COMPLIANCE: NONCOMPLIANTCOMPARATIVE YEARLY LIGHTING ENERGY COST PER 1000 LUMENS = $1.90

BASED ON 3000 HRS. AND $.08 PER KWH

ZONAL LUMENSZONE LUMENS % LAMP % FIXTURE0-300-400-600-900-180

1609 33.6 33.62562 53.5 53.54069 84.9 84.94792 100.0 100.04792 100.0 100.0

INDOOR CANDELA PLOT

Horiz 0-180

1100

2200

0 15 30 45

90

75

60

0.0 45.0 90.0

CANDELA/SQ MAVERAGE LUMINANCEANGLE 0.0 22.5 45.0 67.5 90.0

03040455055606570758085

3313 3313 3313 3313 33133068 3085 3068 3050 30572735 2746 2741 2723 27232513 2535 2526 2479 24772288 2286 2281 2198 21662044 2006 1957 1850 18281786 1714 1582 1538 15631586 1434 1281 1363 14221464 1290 1115 1326 14411461 1292 1164 1401 15951600 1365 1374 1636 18621765 1549 1603 1981 2143

ZONAL CAVITY METHODCOEFFICIENTS OF UTILIZATION (%)EFFECTIVE FLOOR CAVITY REFLECTANCE = 20%

RC 0%80% 70% 50% 30% 10%RW 70% 50% 30% 10% 70% 50% 30% 10% 50% 30% 10% 50% 30% 10% 50% 30% 10% 0%

RCR

0123456789

10

119 119 119 119 116 116 116 116 111 111 111 106 106 106 102 102 102 100110 105 101 98 107 103 99 96 99 96 93 95 92 90 91 89 87 85101 93 87 81 98 91 85 80 88 83 79 84 80 77 81 78 75 7393 83 75 69 90 81 74 69 78 72 67 76 70 66 73 69 65 6385 74 66 60 83 73 65 59 70 64 58 68 62 58 66 61 57 5579 67 58 52 77 66 58 52 64 57 51 62 56 51 60 55 50 4873 61 52 46 71 60 52 46 58 51 46 56 50 45 55 49 45 4368 55 47 41 66 55 47 41 53 46 41 52 45 40 50 45 40 3864 51 43 37 62 50 42 37 49 42 37 48 41 37 46 41 36 3560 47 39 34 58 46 39 34 45 38 33 44 38 33 43 37 33 3156 43 36 31 55 43 36 31 42 35 30 41 35 30 40 34 30 29

RCR = ROOM CAVITY RATIO RC = EFFECTIVE CEILING CAVITY REFLECTANCE RW = WALL REFLECTANCE

THE DATA IN THIS REPORT ARE BASED ON ABSOLUTE MEASUREMENTS.ANSI/IESNA RP-1 COMPLIANCE IS BASED ON ABSOLUTE MEASUREMENTS.THIS TEST RUN IN ACCORDANCE WITH CURRENT I.E.S.N.A. PUBLISHED PROCEDURES.

APPROVED BY:______________

Tel 864 678 1000 701 Millennium Blvd. Greenville, SC 29607

LUMINAIRE: LJT24-40HLG-FSA12-EU LJT LED, Lensed Troffer 2' X 4' LED with A12 pattern acrylic prismed lens Data scaled from test 16.01607BALLAST: XI054C150V054BST1BALLAST FACTOR: 1.00LAMP: 144 Nichia NSFL757GT-V1FIXTURE LUMENS: 5526WATTS: 45.20MOUNTING: RecessedSHIELDING ANGLE: 0º = 90 90º = 90SPACING CRITERION: 0º = 1.19 90º = 1.18LUMINOUS OPENING IN FEET

LENGTH: 3.81WIDTH: 1.80HEIGHT: 0.00

TEST #16405DATE: 6/28/2016

TOTAL LUMINAIRE EFFICIENCY = 100.0TOTAL LUMENS PER WATT = 122

ANSI/IESNA RP-1-2004 COMPLIANCE: NONCOMPLIANTCOMPARATIVE YEARLY LIGHTING ENERGY COST PER 1000 LUMENS = $1.95

BASED ON 3000 HRS. AND $.08 PER KWH

ZONAL LUMENSZONE LUMENS % LAMP % FIXTURE0-300-400-600-90

0-180

1870 33.8 33.82975 53.8 53.84704 85.1 85.15526 100.0 100.05526 100.0 100.0

INDOOR CANDELA PLOT

Horiz 0-180

1300

2600

0 15 30 45

90

75

60

0.0 45.0 90.0

CANDELA/SQ MAVERAGE LUMINANCEANGLE 0.0 22.5 45.0 67.5 90.0

03040455055606570758085

3847 3847 3847 3847 38473572 3592 3556 3543 35383178 3194 3155 3153 31472908 2932 2906 2861 28262632 2647 2600 2510 24472340 2299 2206 2104 20552040 1949 1783 1755 17671786 1634 1419 1552 16121657 1469 1248 1519 16381674 1480 1334 1613 18371817 1573 1582 1880 21241981 1801 1801 2377 2467

ZONAL CAVITY METHODCOEFFICIENTS OF UTILIZATION (%)EFFECTIVE FLOOR CAVITY REFLECTANCE = 20%

RC 0%80% 70% 50% 30% 10%RW 70% 50% 30% 10% 70% 50% 30% 10% 50% 30% 10% 50% 30% 10% 50% 30% 10% 0%

RCR

0123456789

10

119 119 119 119 116 116 116 116 111 111 111 106 106 106 102 102 102 100110 105 101 98 107 103 99 96 99 96 93 95 92 90 91 89 88 86101 93 87 82 98 91 85 81 88 83 79 85 80 77 82 78 75 7393 83 75 69 90 81 74 69 78 72 68 76 71 66 73 69 65 6385 74 66 60 83 73 65 59 71 64 59 68 63 58 66 61 57 5579 67 59 52 77 66 58 52 64 57 52 62 56 51 60 55 51 4873 61 52 46 72 60 52 46 58 51 46 56 50 45 55 49 45 4368 55 47 41 67 55 47 41 53 46 41 52 45 41 50 45 40 3964 51 43 37 62 50 43 37 49 42 37 48 41 37 47 41 37 3560 47 39 34 58 46 39 34 45 38 34 44 38 33 43 37 33 3156 43 36 31 55 43 36 31 42 35 31 41 35 31 40 35 30 29

RCR = ROOM CAVITY RATIO RC = EFFECTIVE CEILING CAVITY REFLECTANCE RW = WALL REFLECTANCE

THE DATA IN THIS REPORT ARE BASED ON ABSOLUTE MEASUREMENTS.ANSI/IESNA RP-1 COMPLIANCE IS BASED ON ABSOLUTE MEASUREMENTS.THIS TEST RUN IN ACCORDANCE WITH CURRENT I.E.S.N.A. PUBLISHED PROCEDURES.

APPROVED BY:______________

Tel 864 678 1000 701 Millennium Blvd. Greenville, SC 29607

LUMINAIRE: LJT24-40HLG-FSA12-EU LJT LED, Lensed Troffer 2' X 4' LED with A12 pattern acrylic prismed lens Data scaled from test 16.01607BALLAST: XI054C150V054BST1BALLAST FACTOR: 1.00LAMP: 144 Nichia NSFL757GT-V1FIXTURE LUMENS: 5526WATTS: 45.20MOUNTING: RecessedSHIELDING ANGLE: 0º = 90 90º = 90SPACING CRITERION: 0º = 1.19 90º = 1.18LUMINOUS OPENING IN FEET

LENGTH: 3.81WIDTH: 1.80HEIGHT: 0.00

TEST #16405DATE: 6/28/2016

TOTAL LUMINAIRE EFFICIENCY = 100.0TOTAL LUMENS PER WATT = 122

ANSI/IESNA RP-1-2004 COMPLIANCE: NONCOMPLIANTCOMPARATIVE YEARLY LIGHTING ENERGY COST PER 1000 LUMENS = $1.95

BASED ON 3000 HRS. AND $.08 PER KWH

ZONAL LUMENSZONE LUMENS % LAMP % FIXTURE0-300-400-600-90

0-180

1870 33.8 33.82975 53.8 53.84704 85.1 85.15526 100.0 100.05526 100.0 100.0

INDOOR CANDELA PLOT

Horiz 0-180

1300

2600

0 15 30 45

90

75

60

0.0 45.0 90.0

CANDELA/SQ MAVERAGE LUMINANCEANGLE 0.0 22.5 45.0 67.5 90.0

03040455055606570758085

3847 3847 3847 3847 38473572 3592 3556 3543 35383178 3194 3155 3153 31472908 2932 2906 2861 28262632 2647 2600 2510 24472340 2299 2206 2104 20552040 1949 1783 1755 17671786 1634 1419 1552 16121657 1469 1248 1519 16381674 1480 1334 1613 18371817 1573 1582 1880 21241981 1801 1801 2377 2467

ZONAL CAVITY METHODCOEFFICIENTS OF UTILIZATION (%)EFFECTIVE FLOOR CAVITY REFLECTANCE = 20%

RC 0%80% 70% 50% 30% 10%RW 70% 50% 30% 10% 70% 50% 30% 10% 50% 30% 10% 50% 30% 10% 50% 30% 10% 0%

RCR

0123456789

10

119 119 119 119 116 116 116 116 111 111 111 106 106 106 102 102 102 100110 105 101 98 107 103 99 96 99 96 93 95 92 90 91 89 88 86101 93 87 82 98 91 85 81 88 83 79 85 80 77 82 78 75 7393 83 75 69 90 81 74 69 78 72 68 76 71 66 73 69 65 6385 74 66 60 83 73 65 59 71 64 59 68 63 58 66 61 57 5579 67 59 52 77 66 58 52 64 57 52 62 56 51 60 55 51 4873 61 52 46 72 60 52 46 58 51 46 56 50 45 55 49 45 4368 55 47 41 67 55 47 41 53 46 41 52 45 41 50 45 40 3964 51 43 37 62 50 43 37 49 42 37 48 41 37 47 41 37 3560 47 39 34 58 46 39 34 45 38 34 44 38 33 43 37 33 3156 43 36 31 55 43 36 31 42 35 31 41 35 31 40 35 30 29

RCR = ROOM CAVITY RATIO RC = EFFECTIVE CEILING CAVITY REFLECTANCE RW = WALL REFLECTANCE

THE DATA IN THIS REPORT ARE BASED ON ABSOLUTE MEASUREMENTS.ANSI/IESNA RP-1 COMPLIANCE IS BASED ON ABSOLUTE MEASUREMENTS.THIS TEST RUN IN ACCORDANCE WITH CURRENT I.E.S.N.A. PUBLISHED PROCEDURES.

APPROVED BY:______________

LJT242' × 4' LED Troffer

LED / LJT24Page 3/3 Rev. 02/15/17

© 2017 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 39: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

2' × 4' 2-Lamp Lay-In SideEnd

A: 7/8" Diameter knockoutK: 2" × 3" through hole for access plate.

NOTE: All dimensions are in inches; dimensions and specifications are subject to change without notice. Please consult factory or check sample for verification.

Type G

For lay-in installation in exposed grid ceilings. Maximum tee widths of 1" and maximum tee heights of 2" allowed.

CEILING COMPATIBILITY

24"

A K

31/8"

4½" 3" 35/32"

48"

33/32"

DIMENSIONAL DATAFK24 Flange Kit

For hard ceiling applications order FK24 flange kit. Flange kit wires directly into concealed ceiling opening for a clean, finished appearance.

Flange kit rough in dimensions for single unit only: 243/8" × 483/8"

For flanged fixtures in row configurations, the FKCR adapter bracket kit is required in addition to the FK24 kit. Order one less FKCR than the total number of fixtures in row. (Example: Row of two, order (2) FK24 & (1) FKCR)

Row cut out dimensions using FK24 & FKCR adapters:Width 243/8", Length [48" × (# in row)] + 3/8". Example: (48" × 2) + 3/8"= 963/8"

FKCR

SideEnd

DIMENSIONAL DATA - SURFACE MOUNT (SM) AND CABLE MOUNT (CM)

NOTE: All dimensions are in inches; dimensions and specifications are subject to change without notice. Please consult factory or check sample for verification.

445/8"

33⁄4"

49" 25"

5"

43⁄4"

1½" Thru Hole

123/8"

123/8"14"

End ViewSide View

4½" x 5" Mounting Collar (SM only). For Cable Mount (CM) a 2" x 3" access plate with (2) 7/8" K.O.s provided in place of Mounting Collar shown.

SURFACE MOUNT

Order SM ceiling type. Mounting collar required for surface mounting. (4) Mounting knock-outs, 1⁄4" to 1⁄2" provided as shown, marked "A".

CABLE MOUNT

Order CM ceiling type. Access plate supplied for cable mounting or suspension. Use CM48Y2C3F-KIT 48" cable mount kit. Includes 3 wire feed cord. For other wiring needs, contact Hubbell Lighting representative. Mounting knock-outs, 1⁄4" to 1⁄2", provided as shown, marked "A".

Mounting Holes: (4) 1⁄4–½"

DIA KOs (A)

LJT242' × 4' LED Troffer

LED / LJT24Page 4/3 Rev. 02/15/17

© 2017 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 40: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

S890930W/LED/HID/WP/5K/E39/100-277V30 watt LED Hi-lumen, omni-directional lamp for commercial fixture applications; 5000K; Mogul base; 100-277 volts

FeaturesHigh Lumen Omni-directional LED for for use in wall pack, canopy, shoe box, or cobra head fixtureReplaces HID, CFL, and IncandescentBallast by-pass - Direct wire only 100V - 277VUL approved for totally enclosed fixturesBase up, base down or horizontal operationDLC qualifiedEmits no UV light / Contains no mercury (Hg)5 year limited warrantycULus listed

              Minimum Compartment Size     Length      Width      Depth       8 inch       8 inch     11 inch

Optional accessory: In-line surge protector 80-929

S8909

Item Number Product Line UPC Input Voltage Watts HID Equivalent Base ANSI Base

S8909 Hi-Pro 045923089091 100 - 277 30 150W Mogul E39

Lamp CodeDimmable/Non-

DimmableFinish

MOL In Inches

MOD In Inches

Initial Lumens

Average Rated Hours

Kelvin Temp

30W/LED/HID/WP/5K/E39/100-277V Non-Dimmable White 8-11/16'' 3-9/16'' 4300 50000 5000

Color CRIBeam Spread

DegOperating Temperature Pack Package Type DLC ID: RoHS Compliant

Natural Light 85 180-29C (-20F) to a maximum of

+60C (+140F)12 Box

P19R7R69DLC Search

Yes

UL or ETL Listed UL Classification Warranty

Yes cULus - Damp Location Rated 5 Year Limited

Page 41: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.
Page 42: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

S939018W/LED/HID/5000K/100-277V E2618 watt - LED HID Replacement; 5000K; Medium base; 100-277 volts

FeaturesHigh Lumen Omni-directional LED for Industrial / Commercial applicationsReplaces HID, CFL, and IncandescentBallast by-pass - Direct wire only 100V - 277VUL approved for totally enclosed fixturesDamp location - IP65 ratedFor outdoor & indoor useBase up, base down or horizontal operationEmits no UV light / Contains no mercury (Hg)5 year limited warrantycULus listed

Additional Technical SpecificationsPower Factor >0.9Operating temperature range -20°C to 65°COperating Frequency 50-60HzWorking Voltage AC90-305V

Minimum lamp compartment dimensions:

152mm x 152mm x 216mm (5.98" x 5.98" x 8.5")

Optional accessory: In-line surge protector 80-929

S9390

Item Number

Product Line

UPCInput

VoltageWatts

Incandescent Equivalent

Fluorescent Equivalent

HID Equivalent

S9390 Hi-Pro 045923093906 100 - 277 18 120W 32W 70W

BaseANSI Base

Lamp CodeDimmable/Non-

DimmableFinish

MOL In Inches

MOD In Inches

Initial Lumens

Medium E26 18W/LED/HID/5000K/100-277V E26 Non-Dimmable White 6-7/8'' 2-3/4'' 2400

Average Rated Hours

Kelvin Temp

Color CRIBeam Spread

DegOperating Temperature Pack Package Type

Page 43: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

50000 5000 Natural Light 80+ 300-20C (-4F) to a maximum of

+65C (+149F)48 Box

RoHS Compliant UL or ETL Listed Warranty

Yes Yes 5 Year Limited

Page 44: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

S9396100W/LED/HID/5000K/100-277V/EX39100 watt - LED HID Replacement (up to 400W); 5000K; Mogul extended base; 100-277 volts

FeaturesHigh Lumen Omni-directional LED for Industrial / Commercial applicationsReplaces HID, CFL, and IncandescentBallast by-pass - Direct wire only 100V - 277VUL approved for totally enclosed fixturesDamp location - IP65 ratedFor outdoor & indoor useDLC QualifiedBase up, base down or horizontal operationEmits no UV light / Contains no mercury (Hg)5 year limited warrantyClassified under UL 1598CSafety chain included

Additional Technical SpecificationsPower Factor >0.9Operating temperature range -20°C to 65°COperating Frequency 50-60HzWorking Voltage AC90-305V

Minimum lamp compartment dimensions:

235mm x 235mm x 440mm (9.25" x 9.25" x 17.3")

Optional accessory: In-line surge protector 80-929

S9396

Item Number

Product Line

UPCInput

VoltageWatts

Incandescent Equivalent

Fluorescent Equivalent

HID Equivalent

S9396 Hi-Pro 045923093968 100 - 277 100 500W 150W 400W

BaseANSI Base

Lamp CodeDimmable/Non-

DimmableFinish

MOL In Inches

MOD In Inches

Initial Lumens

Page 45: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

Mogul Extended

EX39100W/LED/HID/5000K/100-

277V/EX39Non-Dimmable White 9-5/8'' 5.87'' 13300

Average Rated Hours

Kelvin Temp

Color CRIBeam Spread

DegOperating Temperature Pack Package Type

50000 5000 Natural Light 80+ 300-20C (-4F) to a maximum of

+65C (+149F)4 Box

DLC ID: RoHS CompliantUL or ETL

ListedUL Classification Warranty

Search under: S9396A or P93FAQCD or PE62TJJCDLC Search

Yes Yes cULus - Damp Location Rated 5 Year Limited

Page 46: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

TWS LED

Series Performance Package Color Temperature Voltage Control Options Finish

TWS LED P1 1476 lumens 50K 5000K 1 120 120V 2 PE Photoelectric cell, button type

(blank) Dark bronze

TWS LEDLED Wall Luminaire

Ordering Information EXAMPLE: TWS LED P1 50K 120 PE

NOTES

1 Corrected color temperature (CCT) shown is nominal per ANSI C78, 377-2008.

2. 120V driver operates on 120V.

Catalog Number

Notes

Type

One Lithonia Way • Conyers, Georgia 30012 • Phone: 800.279.8041 • www.lithonia.com© 2013-2017 Acuity Brands Lighting, Inc. All rights reserved.

Hit the Tab key or mouse over the page to see all interactive elements.

Introduction

The popular TWS luminaire is now available with long-lasting, energy-efficient LED technology. Featuring a classic dayform, the TWS LED offers a traditional appearance and is powered by advanced LEDs.

The TWS LED luminaire is powerful yet energy efficient, capable of replacing up to a 70W HPS or 100W MH wall pack while saving up to 80% in energy costs. With long-life LEDs, the TWS LED eliminates frequent lamp and ballast replacements associated with traditional technologies.

Width: 6-3/4”(17.2 cm)

Height: 10-7/8”(27.7 cm)

Depth: 5-5/16”(13.5 cm)

Weight: 3.19 lbs(1.45 kg)

Specifications

H

WD

AccessoriesOrdered and shipped separately.

TWSWG Wire Guard

FEATURES & SPECIFICATIONS INTENDED USE

The TWS LED combines traditional wall pack design with high-output LEDs to provide an energy-efficient, low maintenance LED wall pack suitable for replacing up to 70W HPS or 100W MH fixtures. The traditional shape helps maintain building aesthetics when replacing only a portion of your building’s wall packs. TWS LED is for outdoor applications such as personnel doors, loading areas, driveways and parking areas.

CONSTRUCTION Back plate is die-cast aluminum. Front cover is impact-resistant polycarbonate which is fully gasketed. All electronics are protected in the upper housing. Housing is sealed against moisture and environmental contaminants.

FINISH UV stabilized polycarbonate front cover has dark bronze color which provides superior resistance to corrosion and weathering and that can withstand extreme climate changes without cracking or peeling.

OPTICS Protective polycarbonate lens covers the LEDs. Prismatic front cover and precision-molded reflector for superior uniformity and fixture spacing. Light engine is available in 5000K (70 min. CRI).

ELECTRICAL Light engine consists of two high-powered, long-life, high-efficacy LEDs mounted on an internal aluminum heat sink to maximize heat dissipation and promote long life (L95/100,000 hours at 40°C). Driver and integral photocell operate at 120V and are fully enclosed in the upper housing. There are no user serviceable parts.

INSTALLATION Back housing easily mounts to any recessed junction box. With all electronics in upper housing the open lower section makes wiring easy. Mount on any vertical surface. Not recommended in applications where a sprayed stream of water can come in direct contact with polycarbonate lens.

LISTINGS UL Certified to US and Canadian safety standards for wet-location mounting higher than 4 feet off the ground.

Rated for -40°C to 40°C ambient temperature.

WARRANTY 5-year limited warranty. Complete warranty terms located at: www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx.

Note: Actual performance may differ as a result of end-user environment and application All values are design or typical values, measured under laboratory conditions at 25 °C. Specifications are subject to change without notice.

Page 47: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

Lumen values are from photometric tests performed in accordance with IESNA LM-79-08. Data is considered to be representative of the configurations shown, within the tolerances allowed by Lighting Facts. Actual performance may differ as a result of end-user environment and application.

PerformancePackage CCT System

Watts

50K(5000K, 67 CRI)

Lumens B U G LPW

P1 5000K 25W 1,476 1 3 1 60

Performance Data

To see complete photometric reports or download .ies files for this product, visit the Lithonia Lighting TWS LED homepage. Tested in accordance with IESNA LM-79 and LM-80 standards Photometric Diagrams

One Lithonia Way • Conyers, Georgia 30012 • Phone: 800.279.8041 • www.lithonia.com© 2013-2017 Acuity Brands Lighting, Inc. All rights reserved.

TWS LED

Rev. 01/31/17

Lumen OutputUse these factors to determine relative lumen output for average ambient temperatures from 0-40°C (32-104°F).

Lumen Ambient Temperature (LAT) Multipliers

Ambient Lumen Multiplier0°C 32°F 1.03

10°C 50°F 1.02

20°C 68°F 1.01

25°C 77°F 1.0030°C 86°F 0.99

40°C 104°F 0.98

Projected LED Lumen MaintenanceData references the extrapolated performance projections in a 40°C ambient, based on 10,000 hours of LED testing (tested per IESNA LM-80-08 and projected per IESNA TM-21-11).

To calculate LLF, use the lumen maintenance factor that corresponds to the desired number of operating hours below. For other lumen maintenance values, contact factory.

Operating Hours 0 25,000 50,000 55,000 100,000

Lumen Maintenance Factor 1.0 0.98 0.97 0.97 0.95

Electrical LoadCurrent (A)

LED Package

System Watts 120

P1 25W 0.26

Test

No

. LTL

2267

2S t

este

d in

acc

ord

ance

with

IE

SNA

LM

-79-

08.

LEGEND

0.2 fc

0.5 fc

1.0 fc

2.0 fc

TWS LED 1 50K 120 PE. Mounting height - 10’

Lighting Facts Labels

Page 48: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

VANLED20N/D10

Low-profilevandal-resistantfixturecoversthefootprintofmosttraditionalcanopylights.Availableinflatordroplens.

Color:Bronze Weight:12.0lbs

Project: Type:

PreparedBy: Date:

DriverInfoType: ConstantCurrent120V: 0.30A208V: 0.20A240V: 0.17A277V: 0.15AInputWatts: 22WEfficiency: 92%

LEDInfoWatts: 20WColorTemp: 4000KColorAccuracy: 74CRIL70Lifespan: 100000Lumens: 2,312Efficacy: 106LPW

TechnicalSpecificationsListingsULListing:Suitableforwetlocations.

IESNALM-79&LM-80Testing:RABLEDluminaireshavebeentestedbyanindependentlaboratoryinaccordancewithIESNALM-79andLM-80,andhavereceivedtheDepartmentofEnergy"LightingFacts"label.

DLCListed:ThisproductisontheDesignLightsConsortium(DLC)QualifiedProductsListandiseligibleforrebatesfromDLCMemberUtilities.DLCProductCode:PT4V38X8

Electrical

Driver:Class2,ConstantCurrent,100-277V,50-60Hz,500mA

THD:6.1%at120V,10.1%at277V

DimmingDriver:Driverincludesdimmingcontrolwiringfor0-10Vdimmingsystems.Requiresseparate0-10VDCdimmingcircuit.Dimsaslowas10%.

Construction

MaximumAmbientTemperature:Suitableforusein104°F(40°C)ambienttemperatures

ColdWeatherStarting:Minimumstartingtemperatureis-40°F(-40°C)

Housing:Die-castaluminumhousingandlensframewith(4)1/2"NPSsideconduitentriesandweatherproofrearwireplugandaccessplate

Mounting:Ceilingmounttorecessedjunctionwithknockouttemplateordirectytoceilingsurface,utilizingsideconduitentrypoints.

IPRating:IngressProtectionratingofIP66fordustandwater

Lens:Vandal-resistantpolycarbonatetexturedopaqueforlowglaredroplens

Reflector:Semi-specular,vacuum-metalizedpolycarbonate

Gaskets:High-temperaturesiliconegaskets

Finish:Ourenvironmentallyfriendlypolyesterpowdercoatingsareformulatedforhigh-durabilityandlong-lastingcolor,andcontainnoVOCortoxicheavymetals.

GreenTechnology:MercuryandUVfree.RoHScompliantcomponents.PolyesterpowdercoatfinishformulatedwithouttheuseofVOCortoxicheavymetals.

LEDCharacteristics

LEDs:DiscreetLEDsonPCBboard

ColorStability:RABLEDsexceedindustrystandardsforchromaticstability.

ColorUniformity:RAB'srangeofCCT(CorrelatedColorTemperature)followstheguidelinesoftheAmericanNationalStandardforSpecificationsfortheChromaticityofSolidStateLighting(SSL)Products,ANSIC78.377-2015.

Other

Warranty:RABwarrantsthatourLEDproductswillbefreefromdefectsinmaterialsandworkmanshipforaperiodoffive(5)yearsfromthedateofdeliverytotheenduser,includingcoverageoflightoutput,colorstability,driverperformanceandfixturefinish.Seeourfullwarranty

CountryofOrigin:DesignedbyRABinNewJerseyandassembledintheUSAbyRAB'sIBEWLocal3workers.

BuyAmericanActCompliant:ThisproductisaCOTSitemmanufacturedintheUnitedStates,andiscompliantwiththeBuyAmericanAct.

RecoveryAct(ARRA)Compliant:Thisproductcomplieswiththe52.225-21"RequiredUseofAmericanIron,Steel,andManufacturedGoods--BuyAmericanAct--ConstructionMaterials(October2010).

GSASchedule:SuitableinaccordancewithFARSubpart25.4.

CaliforniaTitle24:SeeVANLED20/PCS,VANLED20/PCS2orVANLED20MSfora2013CaliforniaTitle24compliantmodel.

Replacement:Replacesupto70WMetalHalide.

Needhelp?Techhelpline:(888)RAB-1000Email:[email protected]:www.rabweb.comCopyright©2014RABLightingInc.AllRightsReservedNote:Specificationsaresubjecttochangeatanytimewithoutnotice

Page1of2

Page 49: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

VANLED20N/D10

Dimensions Features

Fitsthefootprintofoldercanopylights

VandalresistantandUVresistantlens

Ultra-highefficiency

Clean,contemporary,low-profiledesign

Availablewithdroplensorflatlens

IP66rated,keepsdust,bugsandwaterout

Photoandmotionsensoroptionsavailable

OrderingMatrix

Family Watts ColorTemp Lens Finish Voltage Dimming

VANLED 10=10W20=20W40=40W52=52W65=65W75=75W

Blank=5000K(Cool)

Y=3000K(Warm)N=4000K(Neutral)

Blank=DroplensF=Flatlens

Blank=BronzeW=White

Blank=120-277V/480=480V(10W&20Wnot

available)

Blank=NoDimming/D10=Dimmable(10W&20Wnot

available)

Needhelp?Techhelpline:(888)RAB-1000Email:[email protected]:www.rabweb.comCopyright©2014RABLightingInc.AllRightsReservedNote:Specificationsaresubjecttochangeatanytimewithoutnotice

Page2of2

Page 50: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

WP1LED30N

Affordable30WLEDwallpackwithtraditionallook.100,000hourL70lifespan.5-YearWarranty.

Color:Bronze Weight:4.4lbs

Project: Type:

PreparedBy: Date:

DriverInfoType: ConstantCurrent120V: 0.25A208V: 0.16A240V: 0.14A277V: 0.12AInputWatts: 30WEfficiency: N/A

LEDInfoWatts: 30WColorTemp: 4000KColorAccuracy: 84CRIL70Lifespan: 100000Lumens: 3392Efficacy: 115LPW

TechnicalSpecificationsListingsULListing:Suitableforwetlocations.Wallmountonly.

IESNALM-79&LM-80Testing:RABLEDluminaireshavebeentestedbyanindependentlaboratoryinaccordancewithIESNALM-79andLM-80,andhavereceivedtheDepartmentofEnergy"LightingFacts"label.

DLCListed:ThisproductisontheDesignLightsConsortium(DLC)QualifiedProductsListandiseligibleforrebatesfromDLCMemberUtilities.DLCProductCode:PXC78HW2

Electrical

Driver:ConstantCurrent,Class2,700mA,50/60Hz.100-277V,4kVsurgeprotection

Optical

BUGRating:B1U3G3

Construction

ThermalManagement:Superiorthermalmanagementwithdie-castaluminumheatsink

MaximumAmbientTemperature:Suitableforusein104°F(40°C)ambienttemperatures

ColdWeatherStarting:Minimumstartingtemperatureis-40°F(-40°C)

Housing:Precisiondie-castaluminumhousing.

Mounting:Housinghasthree(3)conduitentrypointsandknockoutpatternforjunctionboxordirectwallmounting.Hingeddoorforeasyre-assembly.

Lens:High-impact,prismatic,UV-stabilizedpolycarbonaterefractorlens

Reflector:High-glosswhitealuminum

Gaskets:High-temperaturesiliconegaskets.

Finish:Formulatedforhigh-durabilityandlonglastingcolor.

GreenTechnology:MercuryandUVfree.RoHScompliantcomponents.PolyesterpowdercoatfinishformulatedwithouttheuseofVOCortoxicheavymetals.

LEDCharacteristics

ColorStability:LEDcolortemperatureiswarrantiedtoshiftnomorethan200KinCCTovera5yearperiod.

ColorUniformity:RAB'srangeofCCT(CorrelatedColorTemperature)followstheguidelinesoftheAmericanNationalStandardforSpecificationsfortheChromaticityofSolidStateLighting(SSL)Products,ANSIC78.377-2015.

Other

Warranty:RABwarrantsthatourLEDproductswillbefreefromdefectsinmaterialsandworkmanshipforaperiodoffive(5)yearsfromthedateofdeliverytotheenduser,includingcoverageoflightoutput,colorstability,driverperformanceandfixturefinish.Seeourfullwarranty

CountryofOrigin:DesignedbyRABinNewJerseyandassembledintheUSAbyRAB'sIBEWLocal3workers.

BuyAmericanActCompliant:ThisproductisaCOTSitemmanufacturedintheUnitedStates,andiscompliantwiththeBuyAmericanAct.

RecoveryAct(ARRA)Compliant:Thisproductcomplieswiththe52.225-21"RequiredUseofAmericanIron,Steel,andManufacturedGoods--BuyAmericanAct--ConstructionMaterials(October2010).

GSASchedule:SuitableinaccordancewithFARSubpart25.4.

Needhelp?Techhelpline:(888)RAB-1000Email:[email protected]:www.rabweb.comCopyright©2014RABLightingInc.AllRightsReservedNote:Specificationsaresubjecttochangeatanytimewithoutnotice

Page1of2

Page 51: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

WP1LED30N

Dimensions Features

CoversfootprintoftraditionalHIDwallpacks

WP1LEDreplacesupto100WMH

100,000-HourLEDlifespan

OrderingMatrix

Family Watts ColorTemp Finish Voltage Photocell

WP1LED 30 N 30=30W Blank=5000K(Cool)

Y=3000K(Warm)N=4000K(Neutral)

Blank=BronzeW=White

Blank=120-277V/480=480V

/PC=120VButton/PCS=120VSwivel/PC2=277VButton/PCS2=277VSwivel/PCS4=480VSwivel

Needhelp?Techhelpline:(888)RAB-1000Email:[email protected]:www.rabweb.comCopyright©2014RABLightingInc.AllRightsReservedNote:Specificationsaresubjecttochangeatanytimewithoutnotice

Page2of2

Page 52: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

WP2LED24Y/PCS2

Affordable37Wand24WLEDwallpackswithtraditionallook.100,000hourL70lifespan.5-YearWarranty.

Color:Bronze Weight:9.6lbs

Project: Type:

PreparedBy: Date:

DriverInfoType: ConstantCurrent120V: N/A208V: 0.13A240V: 0.11A277V: 0.09AInputWatts: 25WEfficiency: 96%

LEDInfoWatts: 24WColorTemp: 3000KColorAccuracy: 83CRIL70Lifespan: 100000Lumens: 2874Efficacy: 115LPW

TechnicalSpecificationsListingsULListing:Suitableforwetlocations.Wallmountonly.

IESNALM-79&LM-80Testing:RABLEDluminaireshavebeentestedbyanindependentlaboratoryinaccordancewithIESNALM-79andLM-80,andhavereceivedtheDepartmentofEnergy"LightingFacts"label.

DLCListed:ThisproductisontheDesignLightsConsortium(DLC)QualifiedProductsListandiseligibleforrebatesfromDLCMemberUtilities.DLCProductCode:PTHT3AXQ

Electrical

Driver:ConstantCurrent,Class2,450mA,50/60Hz.100-277V,4kVsurgeprotection

Photocell:277VSwivelPhotocellIncluded.Photocelliscompatiblewith208V-277V.

Optical

BUGRating:B1U3G3

Construction

ThermalManagement:Superiorthermalmanagementwithdie-castaluminumheatsink

MaximumAmbientTemperature:Suitableforusein104°F(40°C)ambienttemperatures

ColdWeatherStarting:Minimumstartingtemperatureis-40°F(-40°C)

Housing:Precisiondie-castaluminumhousing.

Mounting:Die-castbackboxwithfour(4)conduitentrypointsandknockoutpatternforjunctionboxordirectwallmounting.Hingeddoorforeasyre-assembly.

Lens:Prismatic,heat-resistantborosilicateglass

Reflector:High-glosswhitealuminum

Gaskets:High-temperaturesiliconegaskets.

Finish:Formulatedforhigh-durabilityandlonglastingcolor.

GreenTechnology:MercuryandUVfree.RoHScompliantcomponents.PolyesterpowdercoatfinishformulatedwithouttheuseofVOCortoxicheavymetals.

LEDCharacteristicsColorStability:LEDcolortemperatureiswarrantiedtoshiftnomorethan200KinCCTovera5yearperiod.

ColorUniformity:RAB'srangeofCCT(CorrelatedColorTemperature)followstheguidelinesoftheAmericanNationalStandardforSpecificationsfortheChromaticityofSolidStateLighting(SSL)Products,ANSIC78.377-2015.

OtherWarranty:RABwarrantsthatourLEDproductswillbefreefromdefectsinmaterialsandworkmanshipforaperiodoffive(5)yearsfromthedateofdeliverytotheenduser,includingcoverageoflightoutput,colorstability,driverperformanceandfixturefinish.Seeourfullwarranty

CountryofOrigin:DesignedbyRABinNewJerseyandassembledintheUSAbyRAB'sIBEWLocal3workers.

BuyAmericanActCompliant:ThisproductisaCOTSitemmanufacturedintheUnitedStates,andiscompliantwiththeBuyAmericanAct.

RecoveryAct(ARRA)Compliant:Thisproductcomplieswiththe52.225-21"RequiredUseofAmericanIron,Steel,andManufacturedGoods--BuyAmericanAct--ConstructionMaterials(October2010).

GSASchedule:SuitableinaccordancewithFARSubpart25.4.

Needhelp?Techhelpline:(888)RAB-1000Email:[email protected]:www.rabweb.comCopyright©2014RABLightingInc.AllRightsReservedNote:Specificationsaresubjecttochangeatanytimewithoutnotice

Page1of2

Page 53: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

WP2LED24Y/PCS2

Dimensions Features

CoversfootprintoftraditionalHIDwallpacks

WP2LEDreplacesupto175WMH

100,000-HourLEDlifespan

OrderingMatrix

Family Watts ColorTemp Finish White Voltage Photocell

WP2LED 24 Y /PCS224=24W37=37W

Blank=5000K(Cool)Y=3000K(Warm)

N=4000K(Neutral)

Blank=BronzeW=White

W=White Blank=120-277V/480=480V(Onlyavailablefor37W)

/PC=120VButton/PCS=120VSwivel/PC2=277VButton

/PCS2=277VSwivel/PCS4=480VSwivel

Needhelp?Techhelpline:(888)RAB-1000Email:[email protected]:www.rabweb.comCopyright©2014RABLightingInc.AllRightsReservedNote:Specificationsaresubjecttochangeatanytimewithoutnotice

Page2of2

Page 54: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

WPM-LED_Spec S 10/16 page 1 of 2

The Philips Stonco LED wallpack medium WPM offers maximum light output for general purpose area and security lighting through a classic glass refractor design. Now available with enhanced Philips LED platforms, WPM LED provides improved energy savings compared to the former LED design.* This versatile luminaire is ideal to match same as existing or retrofit HID legacy designs.

Wall Mount

LED wallpack med WPM

Project:

Location:

Cat.No:

Type:

Qty:

Notes:

Ordering guide example: WPM-LED -36L-530-NW-120-PCB-BZ

Prefix

WPM

Source

LED

LED Quantity, Drive Current

36L-530

Color Temp

NW

Voltage Finish Finish

WPM LED wallpack medium WPM

LED LED 36L-530 36 LEDs, 530mA

NW 4000K UNV 120-277V 50hz or 60hz

120 120V

208 208V

277 277V

APD Automatic Profile Dimming1

PCB Button Photo Control (must specify voltage)

F1 Single Fusing

F2 Double Fusing

F3 Double Fusing, Canadian

BZ Textured bronze

WH Textured white

BK Textured black

DGY Dark grey

1. Automatic profile dimming (ADP) is only available in 120-277V.

Accessories (order separately)

Item

P110A Pencil photocontrol (120V)

P150M Light leveler photocontrol (208-277V)

P105A Button Photo Control Kit (120V)

P105M Button Photo Control Kit (208-277V)

330S Stainless steel wire guard, for WPM

335S Clear Lexan vandal guard, for WPM

32352LED Replacement Lens, for WPM (some field assembly required)

Lumen output of previous WPM LED version - 2,909. Lumen output of current WPM LED version - 3,052. Luminaire input watts of previous WPM LED version - 35. Luminaire input watts of current WPM LED version - 33.

Stocked Luminaire

Item

WPM-LED-36L-530-NW-UNV-BZ

9.2"233mm

17.8"452mm

16.9"430mm

8.4"214mm

225mm8.8"

247mm9.7"

1.8"47mm

443561204200(03-27-14)

Page 55: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

WPM-LED_Spec S 10/16 page 2 of 2

Dimensions

Specifications

WPM LED wallpack mediumWall Mount

Features

The Philips Stonco LED wallpack medium WPM combines enhanced LED performance in a classic luminaire design for general purpose wall mount area and security lighting and can be used to match same as existing installations or retrofit myriad of HID legacy designs. Options include use of energy saving control features such as Automatic Profile Dimming (APD) for even greater savings opportunities and standard surge suppression

Predicted Lumen Depreciation Data

Predicted performance derived from LED manufacturer’s data and engineering design estimates, based on IESNA LM-80 methodology. Actual experience may vary due to LED application conditions. L70 is the predicted time when LED performance depreciates to 70% of initial lumen output. Calculated per IESNA TM21-11. Published L70 hours limited to 6 times actual LED test hours

Housing/Door

One piece die cast aluminum housing provided hinged, removable one piece die cast aluminum door.

Performance

Input Watts: 33W Delivered Lumens: 3,052 lumens. Efficacy: 93 Lumens per watt.

Mounting

Mount over 4" j-box with direct mounting via bolts (by others).

Electrical

Driver efficiency (>90% standard) 50/60Hz available in 120-277V or 347-480V, open/short circuit protection. RoHS compliant. Surge protector standard, 10KA per ANSI/IEEE C62.41.2.

LED

36 LED's. Neutral White (4000K) color temperature. 70 color rendering inx (CRI) (nominal).

Optical Lens System

Borosilicate glass catadioptic refractive design featuring a IES Type 4 distribution. BUG Rating: B2-U2-G1. Cutoff Classification: Non-cutoff.

Finish

Each standard color luminaire receives a fade and abrasion resistant, electrostatically applied, thermally cured, triglycidal isocyanurate (TGIC ) textured polyester powdercoat finish.

Listing

ETL listed to the UL 1598 standard, suitable for Wet Locations. Suitable for use in ambients from -40° to 40°C (-22° to 104°F).

Limited Warranty

WPM LED luminaires feature a 5 year limited warranty.

© 2016 Philips Lighting Holding B.V. All rights reserved.Philips reserves the right to make changes in specifications and/or to discontinue any product at any time without notice or obligation and will not be liable for any consequences resulting from the use of this publication.philips.com/luminaires

Philips Lighting North America Corporation200 Franklin Square Drive, Somerset, NJ 08873 Tel. 855-486-2216

Philips Lighting Canada Ltd.281 Hillmount Rd, Markham, ON, Canada L6C 2S3 Tel. 800-668-9008

Front View Side View

Approximate Luminare Weight:

10.2 Lbs (4.6 Kg)

(192mm)7.3"

(254mm)10.0"

(179mm)7.1"

1.5"(38mm)

12.6"(320mm)

9.1"(231mm)

443561204210

(03-27-14)

(192mm)7.3"

(254mm)10.0"

(179mm)7.1"

1.5"(38mm)

12.6"(320mm)

9.1"(231mm)

443561204210

(03-27-14)

Ordering CodeTotal LEDs

System Current

Color Temp.

Average System

WattageLumen

Output*BUG

RatingEfficacy (LPW)

WPM-LED-36L-530-NW 36 530 mA 4000K 33 3052 B1-U4-G3 93

* Wattage and lumen output may vary by +/- 8% due to LED manufacturer forward volt specification and ambient temperature. Wattage shown is average for 120V through 277V input. Actual wattage may vary by an additional +/- 10% due to actual input voltage. Lumen values based on photometric tests performed in compliance with IESNA LM-79.

LED Wattage and Lumen Values

Ambient Temperature °C

Driver Current

Calculated L70hrs 1,2

L70 per TM21 2,3

Lumen Maintenance @ 60,000hrs

25 °C 530 mA >100,000 >60,000 88%

1. Predicted performance derived from LED manufacturer’s data and engineering design estimates.2. L70 is the predicted time when LED performance depreciates to 70% of initial lumen output.3. Calculated per IESNA TM 21-11. Published L70 hours limited to 6 times actual LED test hours.

Page 56: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

WWW.LEGRAND.US/WATTSTOPPER

WATTSTOPPER®SENSORS

DescriptionThe DT-300 Series Dual Technology Ceiling Sensors combine the benefits of passive infrared (PIR) and ultrasonic technologies to detect occupancy. Sensors have a flat, unobtrusive appearance and provide 360 degrees of coverage.

OperationLow voltage DT-300 Series sensors utilize a Wattstopper power pack to turn lights on when both PIR and ultrasonic technologies detect occupancy. They can also work with a low voltage switch for manual-on operation. PIR technology senses motion via a change in infrared energy within the controlled area, whereas ultrasonic uses 40KHz high frequency ultrasound. Once lights are on, detection by either technology holds them on. When no occupancy is detected for the length of the time delay, lights turns off. DT-300 Series Sensors can also be set to trigger lights on when either technology or both detect occupancy, or to require both technologies to hold lighting on.

Time Delay OptionsThe DT-300 is factory set for a 20 minute time delay, ideal for both energy savings and user satisfaction in most applications. Installers can quickly select other fixed time delays (5, 10, 15 or 30 minutes) via DIP switches. Fixed time delays eliminate the occupant dissatisfaction associated with an automatically adjusted time delay option, and reduce callbacks. Walk-through mode may be enabled for added energy savings in spaces with frequent transient traffic.

ApplicationsDT-300 Series Dual Technology Sensors have the flexibility to work in a variety of applications, where one technology alone could cause false triggers. Ideal applications include classrooms, open office spaces, large offices and computer rooms. The DT-300 Series mounting system makes them easy to install in ceiling tiles or to junction boxes, providing the flexibility to be used in a wide range of spaces.

LOW VOLTAGE DUAL TECHNOLOGY CEILING SENSORS DT-300 SERIES

Architecturally appealing low-profile appearance

Plug terminal wiring for quick and easy installation

Supports automatic or manual-on operation

Walk-through mode increases savings potential

Accepts low-voltage switch input for manual-on operation

Ultrasonic diffusers give more comprehensive coverage

OCCUPANCY & VACANCY

• Advanced control logic based on RISC microcontroller provides:

– Detection Signature Processing eliminates false triggers and provides immunity to RFI and EMI

– Walk-through mode turns lights off three minutes after the area is initially occupied – ideal for brief visits such as mail delivery

– Available with built-in light level sensor featuring simple, one-step setup

• Sensors work with low-voltage momentary switches to provide manual control

• Patented ultrasonic diffusion technology spreads coverage to a wider area

• LEDs indicate occupancy detection

• Uses plug terminal wiring system for quick and easy installation

• Eight occupancy logic options provide the ability to customize control to meet application needs

• Available with isolated relay for integration with BAS or HVAC

• BAA/TAA-compliant models available

• Sensor coverage tested to NEMA Guide Publication WD 7-2000

Features

Page 57: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

Rearhousing

Depluggable terminal

Frontcover

Ceiling

Spring clips (2)

Keyhole slots(for mounting to 4" octagonal box)

Double gang mudringmounting holes

Light level pushbutton

DIP switches

PIR lens

Ultrasonic sensitivitytrimpot

ON

1

2

3

4

5

6

7

8

ECE

Ultrasonic transducercones

Ultrasonic activityLED (Green)

PIR ActivityLED (Red)

Standard

Option 2Option 3

Option 1

Trigger

Option 4Option 5

Initi

alO

ccup

ancy

Mai

ntai

nO

ccup

ancy

Re-

trigg

er(s

econ

dsdu

ratio

n)

Occ

upan

cy L

ogic

Both

Both PIR Both(5)

Either(5)

EitherEitherEitherEither

Either(5)Either(5)

Either

PIR

PIR

PIR(5)

Either(30)Either(5)Either

= ON = OFF

6 7 8

Switch#

Occ

upan

cy L

ogic

= Factory Setting

5 minutes10 minutes15 minutes20 minutes25 minutes30 minutes

30 seconds

1 2 3Time Delay

Test Mode/20 min

5 Minimum PIR Sensitivity

Walk-ThroughEnabledDisabled

4

Maximum

PIR PIR

Settings

Man.Man. PIR Both(30)

Feature

Option 6Option 7

Standard

Option 2Option 3

Option 1

Option 4Option 5Option 6Option 7

Standard

Option 2Option 3

Option 1

Trigger

Option 4Option 5

Initi

alO

ccup

ancy

Mai

ntai

nO

ccup

ancy

Re-

trigg

er(s

econ

dsdu

ratio

n)

Occ

upan

cy L

ogic

Both

Both PIR Both(5)

Either(5)

EitherEitherEitherEither

Either(5)Either(5)

Either

PIR

PIR

PIR(5)

Either(30)Either(5)Either

= ON = OFF

6 7 8

Switch#

Occ

upan

cy L

ogic

= Factory Setting

5 minutes10 minutes15 minutes20 minutes25 minutes30 minutes

30 seconds

1 2 3Time Delay

Test Mode/20 min

5 Minimum PIR Sensitivity

Walk-ThroughEnabledDisabled

4

Maximum

PIR PIR

Settings

Man.Man. PIR Both(30)

Feature

Option 6Option 7

Standard

Option 2Option 3

Option 1

Option 4Option 5Option 6Option 7

36 ft(10.97m)

36 ft x 36 ft(10.97m x 10.97m)

WWW.LEGRAND.US/WATTSTOPPER Pub. No. 14909 Rev. 08/2016

• 24 VDC/VAC• Ultrasonic frequency: 40kHz• Time delays: 5, 10, 15, 20, or 30 minutes, Walk-through/Test

Modes• Sensitivity adjustment: High/low (PIR); variable with trim pot

(ultrasonic) • Built-in light level sensor: 10 to 300 footcandles (107.6 to

3,229.2 lux)• Low-voltage, momentary switch input for manual on or off

operation

• DT-300 contains an isolated relay with N/O and N/C outputs; rated for 1 Amp @ 30 VDC/VAC

• Multi-level Fresnel lens provides 360° coverage• Mounting options: ceiling tile; 4” octagonal J-box, 1.5” deep• Max DT-300s per power pack: B=2 , BZ=3

Max DT-305s per power pack: B=3, BZ=4• Dimensions: 4.50” diameter x 1.02” deep

(114.3mm x 25.9mm) • UL and cUL listed • Five year warranty

Specifications

Wiring & MountingWiring Diagram Ceiling Mounting

Controls & SettingsProduct Controls DIP Switch Settings

Ordering Information

Catalog # Voltage Current Coverage Features DT-300

DT-300-U24 VDC/VAC 43 mA up to 1000 ft2 (92.9 m2 Isolated relay, light level

DT-305 DT-305-U

24 VDC/VAC 35 mA up to 1000 ft2 (92.9 m2

Sensors are white and use Wattstopper power packs. Current consumption can be slightly higher when only one sensor per power pack is used.-U = BAA/TAA compliant; product is compliant with Buy American Act and Trade Agreement Act

CoverageCoverage Pattern

The control technology (occupancy logic) is selectable. The default setting requires both technologies to trigger on, either to hold on, and is recommended for most applications.

Coverage shown is maximum and represents half-step walking motion. Under ideal conditions, coverage for half-step walking motion can reach up to 1000 ft2.

Low Voltage Wires

Control Output

Common

+24VDC

Neutral

Hot

White

Black

Red

Bla

ck

Power Pack

Blu

e

Red

Red

Fixture

BZ-200

**Ground

*To AdditionalSensor(s)

** BZ-200 Power Pack must be grounded to ensure signal integrity,not for safety ground.

Optional Local Off Switch

Fixture

Optional Local Off Switch

DT-300/DT-305Low VoltageOccupancySensor

Page 58: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

WWW.LEGRAND.US/WATTSTOPPER

WATTSTOPPER®SENSORS

DescriptionThe BZ-250 power pack switches lighting or plug loads On and Off in response to low voltage control inputs, and provides up to 225mA at 24VDC to power Wattstopper occupancy sensors. It enables Manual-On sequences of operation, as well as Hold-On, Hold-Off and load shed applications when used with lighting control panels or building automation systems. This device is constructed with environmentally friendly materials and is RoHS-compliant.

OperationThe BZ-250 consists of a high-efficiency switching power supply and a high-current relay. It turns the connected load Off automatically based on occupancy sensor input, and On either automatically based on occupancy, or manually in response to a low-voltage momentary switch. The installer can select Auto-On or Manual-On operation via an actuator switch on the power pack. The BZ-250 also accepts low-voltage Hold-On and Hold-Off inputs for broader applications. The BZ-250 relay can be set to open, close or maintain state prior to loss of power, so that lighting is in the preferred state (On, Off or last state) when power is restored.

Manual-On and Bi-Level SwitchingIncreasingly, energy codes require Manual-On control as well as bi-level switching, and the BZ-250 enables both of these requirements. When used with a low-voltage wall switch, Manual-On operation can be selected while in the field by using the conveniently located actuator switch on the front. Combining switches, power packs and sensors provides easy and cost-effective code-compliant solutions.

ApplicationsThe BZ-250 can control lighting circuits, plug load circuits, self-contained air conditioners, pumps, fans, motors and motorized damper controls. Bi-level switching with Manual-On operation can be achieved using two low-voltage switches, a ceiling sensor and two BZ-250s (one set to Auto-On and one set to Manual-On). The Hold-On input is ideal for overriding an occupancy sensor to force lighting On during normal business hours in retail and commercial facilities. After hours, a time clock signals the BZ-250 to cancel the Hold-On mode, allowing the sensor to resume control. The Hold-Off input can be used for load shedding or security systems.

LIGHTING AND PLUG LOAD FLEX CONTROL POWER PACK BZ-250

High-efficiency, plenum-rated switching power supply

Auto-On or Manual-On operation for code compliance

Low voltage over current protection

120-277VAC and 120-347VAC models

Hold-On and Hold-Off inputs

Load On/Off button to verify wiring

Zero crossing and for reliability and increased product life

Mechanically held latching relay with selectable power loss

operation: On, Off, or last state

POWER PACKS

• Hold-On and Hold-Off inputs integrate with BAS, lighting control panels & other building systems

• Integrates with low-voltage momentary switch to control any 24VDC occupancy sensor

• Field-selectable Auto-On or Manual-On operation • Efficient switching power supply provides optimized current

output based on number of sensors• Includes short circuit and thermal protection• LED indicates status of relay or presence of low-voltage

overcurrent

• UL 2043 plenum rated for cost-effective installation• UL listed for control of lighting and plug loads• Tested to NEMA 410 criteria for electronic ballast and driver

inrush current• 1/2” threaded nipple attaches to standard electrical

enclosures through 1/2” knockouts• 12 AWG wires on the relay for 20A operation• The product meets the materials restrictions of RoHS• BAA/TAA-compliant models available

Features

Page 59: Fairfield-Suisun Unified School District...♦ Replace existing tombstones with Energy Focus Tombstone Lampholders for LED tubes, powered on one end. Must use non-shunted tombstones.

Low VoltageConnections

Line Voltage InTo Load

+24VDC

Common

RedWhiteNeut. BZ-250(A)

AUTO ON

Blu

e

Bla

ck

Red

LightingLoad (A)

Black

Any 3-Wire24VDCSensor

HotRed

Brown

Orange

Control

Low Voltage Wires

RedWhiteNeut. BZ-250(B)

MANUAL ON

Blu

e

Bla

ck

Red

LightingLoad (B)

BlackHot

Red

Brown

Orange Gre

y

Momentary Switch (B)

Low Voltage Wires

Gre

y

Momentary Switch (A)

Ground

Ground

NOTES:• BZ-250 power packs should be

grounded to ensure signal integrity, not for safety ground.

2-wire Push Button

Red24VDC

GreyManual ON

3-wire Momentary, DCC2

Red24VDC

GreyManual ON

InstallJumperWire

Multi-button Switch, LVSW-101Do not use pilot or locator

light connections

Red24VDC

GreyManual ON

S(x)

Com

BZ

OccupancySensor

BZ-250Power Pack

BZ1 BZ2

Hold-ONSignal

BZ3 BZ4

Low Voltage

Line Voltage

BZ

BZ1 BZ2

Hold-OFFSignal

OccupancySensor

BZ-250Power Pack

Low Voltage

Line Voltage

WWW.LEGRAND.US/WATTSTOPPER Pub. No. 43301 Rev. 08/2016

• Input/output voltage:120-277VAC or 120-347VAC, 50/60Hz• Secondary output: 24VDC, 225mA• Low-voltage leads rated for 300 volts• UL-rated 94 V-O plastic enclosure• Power up options: On, Off, previous state• Operating conditions: -4 to 131�F (-20 to 55�C); 5-95% RH,

non condensing • Dimensions: 1.5” x 3” x 2.4”• (37mm x 77mm x 61mm) H x W x D with .6“ L (15mm)

threaded nipple• UL and cUL listed • Five year warranty

Specifications

Installation & Wiring

Installation Diagram Manual-On and Bi-Level Switching

Hold-off & Hold-on Applications

Load Shed (Hold-Off) Application Retail (Hold-On) Application

Load Ratings For a complete listing of Multibutton Low-voltage and Momentary Toggle Switches that will provide Manual-On switching with the BZ-250, please refer to the product cut sheets in the section on Lighting Control Systems.-U = BAA/TAA compliant. Product is compliant with Buy American Act and Trade Agreement Act

Catalog # Input Voltage OutputBallast/ELV/

MLV Incan/LEDE-Ballast

CFL MotorPlug Load

BZ-250 120-277VAC, single phase; 50/60Hz 24VDC, 225mA

20A 16A 1HP 20ABZ-250-UBZ-250-347 120-347VAC, single phase; 50/60Hz 16A 16A 1/4HP 15A

Ordering Information

Low-voltage Momentary Switch Options

Wiring to Occupancy Sensor

1. All Wattstopper power packs should be installed in accordance with state. local, and national electrical codes and requirements. 2. Power packs are designed to attach to existing or new electrical enclosures with .5” 125.40mmJ knockout (check electrical codes in your area). 3. Most applications require UL-listed, 18-22 AWG, 3-conductor, Class 2 cables for low-voltage wiring. For plenum return ceilings use UL-listed plenum-approved cables.

Connect two low-voltage switches, a ceiling sensor and two BZ-250s (one set to Auto-On and one set to Manual-On) for bi-level switching with manual-on operation.

Two-wire Switch Three-wire Switch

Multibutton SwitchDo not use pilot or locator

light connections

During store hours, a signal from a time clock to the BZ-250 holds lights On, regardless of occupancy. After hours, the clock schedule cancels the Hold-On and occupancy sensor control takes over.

The occupancy sensor normally keeps lights On when the space is occupied. When a load shed command is received (from utility meter, BAS, etc.), lights connected to BZ2 are held Off. Remaining lights (connected to BZ1) are still controlled by occupancy.

BZ-250 power packattached to J-box

+24VDC

Common

RedWhiteNeut.BZ-250

Blu

e

Bla

ck

Red

Dry

Con

tact

LightingLoad

Black

5-30 VDC InHold OFF

5-30 VDC InHold ON

Any 3-Wire24VDCSensor

HotRed

Brown

Orange

Gre

y

Control

Momentary Switch (optional)

Low Voltage WiresGround

NOTES:• BZ-250 power packs

should be grounded to ensure signal integrity, not for safety ground.