Factory Line - Panasonic · Factory Line 60: 3P 60A 300V + 2P 20A 300V with ground. ... Built-in...

6
350 39 58 24 26 20 54 14 21 8 58 24 26 20 54 14 21 39 8 Joiner pin Duct cover 250 25 25 123 64 66 72 400 25 111 122 250 25 66 72 1.000 58 54 20 24 Factory Line 100/60 Product guide (Plug lever is green.) Factory Line Factory Line 100/60 main unit (cream-gray finish: Munsell 5Y7.2/1.4) Factory Line 100: 3P 100A 300V + 2P 20A 300V with ground. Factory Line 60: 3P 60A 300V + 2P 20A 300V with ground. Conductor equipped ducts. The upper 3 conductors are for the 3-phase 3-wire circuit or the single phase 3-wire circuit. The lower 2 conductors are for the single phase circuit. Attaches a joiner-pin protect cap. Galvanized steel core PVC resin housing and copper conductors. [Warning] Use Factory Line 60 main units at the standard length. Cat. No. Length (mm) Weight (kg) Factory Line 100 DH2411 1,000 3.3 DH2412 2,000 6.6 DH2413 3,000 9.9 Factory Line 60 DH2311 1,000 3.1 DH2312 2,000 6.1 DH2313 3,000 9.1 Cat. No. Weight (kg) DH2799 0.06 Cat. No. Weight (kg) DH2422 2.4 Cat. No. Weight (kg) DH2425 2.0 Duct cover For Factory Line 100/60 and 30systems. Protect from entering foreign bodies or dusts into main unit. Length 1m. Made of PVC resin. Factory Line 60 auxiliary main unit (cream-gray finish) For Factory Line 60 system. 3P 60A 300V + 2P 20A 300V with ground. Feed-in caps can only set at the female end of the Factory Line 60 main unit In case supplying power at the male end, use this unit for gender changing. Galvanized steel core PVC resin housing and copper conductors. [Warning] Use this unit at the standard length. Feed-in cap (cream-gray finish) For Factory Line 100/60 system. 3P 100A 300V + 2P 20A 300V with ground. Supplying power at an end of the main unit. Epoxy coating galvanized steel housing. Feed-in cap with breaker (cream-gray finish) For Factory Line 100 system. 3P 100A 200V +2P 20A 300V with ground. (3P 100A N-BAK-100 with built-in breaker) Knockout diameter Side surface 38.8 dia. ×1 With 38pressure terminals Factory Line 100 Factory Line 60 Knockout diameter Upper surface φ38.8 ×1 φ21.5 ×1 Side surface φ38.8 ×1 <Main specifications> Rated voltage: AC 100V * Power supply to lower conductors is AC 100V. Measurable ampere: 30~100 [Arms] Function: 60A Rated/100A Switchover switch, reset function, external output (no voltage, a contact) Cat. No. Weight (kg) DH2310 3.3 Cat. No. Weight (kg) DH2421 1.1 Cat. No. Weight (kg) DH2424K1 3.1 Center feed-in joiner (cream-gray finish) For Factory Line 100/60 system. 3P 100A 300V + 2P 20A 300V with ground. Supplying power between main units and connecting them. Epoxy coating galvanized steel housing. Knockout diameter Upper surface 38.8 dia. ×1 21.5 dia. ×1 Side surface 38.8 dia. ×1 Solderless terminals not required Knockout diameter Upper surface φ 38.8 ×1 φ 21.5 ×1 Side surface φ 38.8 ×1 Solderless terminals not required Feed-in cap with current monitor (cream-gray finish) For Factory Line 100/60 systems. 3P 100A 300V +2P 20A 100V with ground. 3-color LED (light emitting diode) displays the approximate current value through the 3-wire circuits in 3 levels. (Compatible with single phase 3-wire and 3-phase 3-wire circuits) Equipped with external contacts (no voltage, a contact), enabling contact signal transmission. Can be incorporated into systems for warning lamps or PLC (Programmable Logic Controller) to prevent breaker trip by warnings.

Transcript of Factory Line - Panasonic · Factory Line 60: 3P 60A 300V + 2P 20A 300V with ground. ... Built-in...

350

ℓ 39

5824

26

20

54

1421

8

5824

2620

54 1421

ℓ 39

8

Joiner pin

Duct cover

25025 25 123

6466

72

400 25

111

122

250 25

6672

1.000

58

54

20

24

Factory Line 100/60

Product guide(Plug lever is green.)

Factory Line ■Factory Line 100/60 main unit (cream-gray finish: Munsell 5Y7.2/1.4)Factory Line 100: 3P 100A 300V + 2P 20A 300V with ground.Factory Line 60: 3P 60A 300V + 2P 20A 300V with ground.Conductor equipped ducts. The upper 3 conductors are for the 3-phase3-wire circuit or the single phase3-wire circuit.The lower 2 conductors are for thesingle phase circuit.Attaches a joiner-pin protect cap.Galvanized steel core PVC resinhousing and copper conductors.[Warning]Use Factory Line 60 main units atthe standard length.

Cat. No. Length ℓ (mm) Weight (kg)

Factory Line100

DH2411 1,000 3.3DH2412 2,000 6.6DH2413 3,000 9.9

Factory Line60

DH2311 1,000 3.1DH2312 2,000 6.1DH2313 3,000 9.1

Cat. No. Weight (kg)

DH2799 0.06

Cat. No. Weight (kg)

DH2422 2.4

Cat. No. Weight (kg)

DH2425 2.0

■Duct coverFor Factory Line 100/60 and 30systems.Protect from entering foreign bodies or dusts into main unit.Length 1m. Made of PVC resin.

■Factory Line 60 auxiliary  main unit (cream-gray finish) For Factory Line 60 system. 3P 60A 300V + 2P 20A 300V with ground. Feed-in caps can only set at the female end of the Factory Line 60 main unit In case supplying power at the male end, use this unit for gender changing. Galvanized steel core PVC resin housing and copper conductors.[Warning]Use this unit at the standard length.

■Feed-in cap (cream-gray finish)For Factory Line 100/60 system. 3P 100A 300V + 2P 20A 300V with ground. Supplying power at an end of the main unit.Epoxy coating galvanized steel housing.

■Feed-in cap with breaker  (cream-gray finish) For Factory Line 100 system. 3P 100A 200V +2P 20A 300V with ground.(3P 100A N-BAK-100 with built-in breaker)

Knockout diameter

Side surface38.8 dia.×1

With 38㎟ pressureterminals

◦Factory Line 100

◦Factory Line 60

Knockout diameterUpper surfaceφ38.8×1 φ21.5×1

Side surfaceφ38.8×1

<Main specifications> Rated voltage: AC 100V * Power supply to lower conductors  is AC 100V.Measurable ampere: 30~100 [Arms]Function: 60A Rated/100A

Switchover switch, reset function, external output (no voltage, a contact)

Cat. No. Weight (kg)

DH2310 3.3

Cat. No. Weight (kg)

DH2421 1.1

Cat. No. Weight (kg)

DH2424K1 3.1

■Center feed-in joiner (cream-gray finish)For Factory Line 100/60 system. 3P 100A 300V + 2P 20A 300Vwith ground. Supplying power between main units andconnecting them. Epoxy coating galvanized steel housing.

Knockout diameterUpper surface38.8 dia.×1 21.5 dia.×1

Side surface38.8 dia.×1

Solderless terminals not required

Knockout diameterUpper surfaceφ38.8×1 φ21.5×1

Side surfaceφ38.8×1

Solderless terminals not required

■Feed-in cap with current monitor  (cream-gray finish) For Factory Line 100/60 systems. 3P 100A 300V +2P 20A 100V with ground.●3-color LED (light emitting diode) displays the

approximate current value through the 3-wire circuits in 3 levels. (Compatible with single phase 3-wire and 3-phase 3-wire circuits)

●Equipped with external contacts (no voltage, a contact), enabling contact signal transmission.

Can be incorporated into systems for warning lamps or PLC (Programmable Logic Controller) to prevent breaker trip by warnings.

244.5210

244.5

210

72

25

19

9065

3212

34 52

6365

20

59

48 30

M10×200

80

φ10.5hole

80

200120

6742

58

7662 φ6.2hole

61

35

25

Factory Line 100/60

Product guide(Plug lever is green.)

Cat. No. Weight (kg)

DH2431 0.1

Cat. No. Weight (kg)

DH2423K 0.06

Cat. No. Weight (kg)

DH2451 0.18

Cat. No. Weight (kg)

DH85 1.85

■Joiner (cream-gray finish)For Factory Line 100/60 system. 2P 20A 300V with ground.Connecting lower conductors and ground lines of main units electrically. Cannot supply power with this part.

■End cap (cream-gray finish)For Factory Line 100/60 system.Closing an end of the main unit.Resin molding.

Cat. No. Weight (kg)

DH2453 0.03

Cat. No. Weight (kg)

DH2452K1 0.03

■Ceiling direct-mounting hangerFor Factory Line 200, 100/60 systems.Mounting main unit directly to the ceiling.Stainless steel hanger.[Caution]①Main unit cannot fasten directly to the building structure without using hangers.②Suspending weight must be below  196N(20kgf)  on each hanger.

Cat. No. Weight (kg)

DH2454 0.51

Cat. No. Weight (kg)

DH2457 0.01

■Connection reinforcement fixture (cream-gray finish)For Factory Line 200, 100/60 systems.To keep straight the joint part of the main unit suspended by long bolts. Epoxy coating galvanized steel.

■Earthquake resistant reinforcement fixturesUsed in hanger installations to further strengthen the main unit installation. Can be installed at any time to existing hanger installations. As a guide, we recommend installing it to hangers with a bolt length greater than 500 mm. Stainless steel hanger. [Caution]Cannot be used with ceiling direct-mounting hangers.

■Joiner L (Cream-gray finish) For Factory Line 100/60 systems. 3P 100A 300V +2P 20A 300V with ground. Connecting main unit to L-shapes. With feed-in terminal[Caution]①For Factory Line 100 systems, cut the feed

line side unit to 40 mm for connection. ②For Factory Line 60 systems, auxiliary unit

required on the feed in side.

■Hanger (with earthquake resistant reinforcement  fixtures)For Factory Line 200, 100/60 systems.Attaching main unit directly to the building structure or suspending with supplied bolts. Stainless steel hanger.[Caution]①Main unit cannot fasten directly to the building structure without using hangers.②Suspending weight must be below 196N(20kgf) on each hanger.

■Hanger (with bolt)For Factory Line 200, 100/60 system.Suspending main unit fromthe building structure.Stainless steel hanger andgalvanized bolt (200mm).[Caution]Suspending weight must bebelow 196N(20kgf) on each hanger.

The DH2452K (no earthquake resistant reinforcement fixtures) is also available.

30 30

30

60

2-φ11

60

3030

30

φ11

105

100

69

174

42 38

100 68

150

208

38

φ90

60 15

1,000

φ16 φ16.3

φ13.5

32

66

Anti-swingfixture

Hanger(without bolt)(supplied separately)

100 68

34150 208

100V 100V 200V

Type I Type II Type III

Polarity Indicator

26

Factory Line 100/60

Product guide(Plug lever is green.)

Consider the phase balance when selecting plugs.

Cat. No. Rating Weight (kg)

DH2482K2 3P20A200V with ground0.91

DH2483K2 3P30A200V with ground

Cat. No. Name Weight (kg)

DH2455 Decorative flange 0.1DH2456 Decorative pipe 0.47

Cat. No. Weight (kg)

DL741Y 0.1

■Decorative flange and pipe  (cream-gray finish)For Factory Line 200, 100/60 and 30 systems.Hide the suspension bolt for good appearance.Cut the decorative pipe into the length of the suspension bolt.Melamine coated steel pipe and ABS resin flange.

■Anti-swing fixture (ivory-gray finish)For Factory Line 400, 200, 100/60 and 30 systems.Prevent suspension bolts from swinging.Use 2 pieces if secure both sides.Epoxy coating galvanized steel.

Cat. No. Rating Weight (kg)

DH2492K2 3P60A200V with ground 1.4

■Terminal plugs with breaker (cream-gray finish)For Factory Line 100/60 systems. 3P 20A/30A 200V with ground.Power plug from the upper 3P conductors with Miniature Circuit Breaker. ABS resin housing.

Decorative flange

Decorative pipeφ16ℓ=1m

■Anti-swing fixture  (electro-galvanized) For Factory Line 200, 100/60 and 30 systems. Eliminates need to pass through hanger bolt before processing. Can be fitted to existing bolts to prevent swinging.

For single side DLEF3

For both sides DLEF3W

Cat. No. Name Bolt Weight (kg)

DLEF3 For both sides W3/8 0.07DLEF3W For single sides W3/8 0.13

■Terminal plugs with breaker (cream-gray finish) For Factory Line 100/60 systems. 3P 60A 200V with ground.Built-in breaker (60A: N-BAK-100)Power plug from the upper 3P conductors with Miniature Circuit Breaker.

■Terminal plugs with breaker (cream-gray finish)For Factory Line 100/60 systems. 2P 20A/30A 200V with ground.Built-in breaker (N-BAK-50K)2P Power plug from the upper 3P conductors with Miniature Circuit Breaker. Available in 3 models, Type I, Type II and Type III.

Cat. No. Rating Type Weight (kg)

DH24823K12P20A200V with ground

Type I0.90DH24824K1 Type II

DH24825K1 Type IIIDH24833K1

2P30A200V with groundType I

0.90DH24834K1 Type II DH24835K1 Type III

100

208

150

38

68100

208

150

38

68

42117

105

100

69

100

38145

87

68

27

Factory Line 100/60

Product guide(Plug lever is green.)

■Terminal plug A (cream-gray finish)For Factory Line 100/60 systems. 3P 30A 300V with ground.Power outlet for the main unit from the upper 3P conductors.ABS resin housing.

Cat. No. Rating Weight (kg)

DH2481 3P30A300V with ground 0.35

Cat. No. Rating Weight (kg)

DH2491 3P60A300V with ground 0.5

Cat. No. Motor rating Rating Weight (kg)

DH24871K1 0.2kW

3P200V with ground 0.94

DH24872K1 0.4kWDH24873K1 0.75kWDH24874K1 1.0kWDH24875K1 1.5kWDH24876K1 2.2kWDH24877K1 3.7kWDH24878K1 5.5kW

Cat. No. Rating Current sensitivity Weight (kg)

DH24821K1 3P20A200V with ground15mA

0.94DH24831K1 3P30A200V with groundDH24822K1 3P20A200V with ground

30mADH24832K1 3P30A200V with ground

■Terminal plugs with leakage breaker  (cream-gray finish) For Factory Line 100/60 systems. 3P 20A/30A 200V with ground.Built-in leakage breaker (BKW-50S) Available in 2 types with differing current sensitivity and capacity for Power plug from the upper 3P conductors with Miniature Circuit Breaker.

■Terminal plugs with motor breaker  (cream-gray finish)For Factory Line 100/60 systems. For 0.2 kW to 5.5 kW. Built-in motor breaker (BBW-30CM) Power plug from the upper 3P conductors with Miniature Circuit Breaker.

■Terminal plug A (cream-gray finish) For Factory Line 100/60 systems. 3P 60A 300V with ground.Power outlet from the upper 3P conductors.

60 42

3516

51

60 42

3516

51

65 42

3316

64

28

Factory Line 100/60

Product guide(Plug lever is green.)

■Terminal plug B (cream-gray finish)JIS C 8366 For Factory Line 100/60 systems. 2P 15A 300V with ground.Power plug from the lower 2P conductors.ABS resin housing.[Caution]Cannot be used for Factory Line 30 because of the difference in the ground connection.

Cat. No. Rating Weight (kg)

DH2477 Ground 2P15A125V Locking 0.07

Cat. No. Rating Weight (kg)

DH2463 2P15A300V with ground 0.08

Cat. No. Rating Weight (kg)

DH2461 Ground 2P15A125V 0.07

■Locking plug socket (cream-gray finish)JIS C 8366 For Factory Line 100/60 systems. Ground 2P 15A 125V Locking. Locking outlet plug from lower 2P conductors. (100V only) [Caution]Cannot be used for Factory Line 30 because of the difference in the ground connection.

■Plug Socket (cream-gray finish) JIS C 8366 For Factory Line 100/60 systems. Ground 2P 15A 125V. Plug socket from lower 2P conductors. (100V only)[Caution]Cannot be used for Factory Line 30 because of the difference in the ground connection.

(one combination)

Lead wire0.86㎟480㎜

3628

3012 8

14

20480

7

φ19

adapter clamp

■Fluorescent lighting fixture plugJIS C 8366 For Factory Line 100/60 system. 2P 6A 250V with ground.Mounting a fluorescent lighting fixture directly to the main unitand supply power from lower 2P conductors.Consists of clamp-feeder and cramp. Galvanized steel frame.[Caution]Weight must be below 20kg.

Cat. No. Rating Weight (kg)

DH2471 2P6A250V with ground 0.16

Note: Cannot be used for Factory Line 30 becauseof the difference in the ground connection.

65 42

16

approx. 800~1,800

121

90 50

25

6

1056

30

46

29

Factory Line 100/60

Product guide(Plug lever is green.)

■Cord hook (cream-gray finish)For Factory Line 100/60 and 30 systems.Support wiring cables connected to the outlet plug.Polly carbonate resin.[Caution]Suspending weight must be below 5kg on each hanger.

Cat. No. Rating Weight (kg)

DH2462 For twin ground 2P15A125V0.70

DH2464 For twin ground 2P15A125V locking

Cat. No. Weight (kg)

DH2798 0.03

■Reel-type plug socket  (Plug: Cream-gray finish. Socket: Off-white finish) JIS C 8366 For Factory Line 100/60 systems. For twin ground 2P 15A 125V, twin ground 2P 15A 125V locking. Plug socket from lower 2P conductors, and can be lowered to hand level (max. 1.8m from the duct). Lowering up to 3m 9 from the duct available to order. (100V only)[Caution]①Cannot be used for

Factory Line 30 because of the difference in the ground connection.

②To rewind the reel section, press and hold the button, and slowly raise the socket.

Failure to do so may cause damage.