F-Gaz Regulation - Implementation in France
-
Upload
unep-ozonaction -
Category
Technology
-
view
3.086 -
download
1
Transcript of F-Gaz Regulation - Implementation in France
UNEP - Budapest
Gérald CAVALIER,
19th of October 2011
F-Gaz regulationImplementation in France
І Content
• Cemafroid in a few words
– Independent cold chain expertise
French F-Gaz implementation
– Overview of French regulations
– The main requirements
DATAFLUID a centralized computing system
– A public platform
– Link between all actors
• Conclusion
Cemafroid in a few words and data
ІCemafroid : refrigeration experts
• 60 years of history
– 1950 creation of Antony laboratory
– 1970 Antony official ATP test station for UN
– 1980 creation of Cemagref
– 2000 creation of Cemafroid by Cemagref
– 2010 creation of Cemafroid group, TECNEA
and Cemafroid formation
• An independant company owned by:
– Cemagref : public research center
– PERIFEM distribution technical association
– TRANSFRIGOROUTE France association
– Cemafroid Staff : TECNEA
• Income : 4,1 M€ in 2010
– +25% in 2010
In a few words and data
Essais 36%
Cerification 27%
Expertise
6%
DSP 31%
Répartition du CA 2009
274 495 €
1 006 164 €
992 739 €
1 133 733 €
1 552 306 €1 638 676 €
1 862 312 €
2 148 042 €
2 240 860 €
3 310 000 €
4 030 000 €
- €
500 000 €
1 000 000 €
1 500 000 €
2 000 000 €
2 500 000 €
3 000 000 €
3 500 000 €
4 000 000 €
4 500 000 €
2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010
CA annuel du Cemafroid
Arras• Service public
Bordeaux• Tests
Antony•Direction• Tests• Certification• Expertise
ІCemafroid• More than 40 staff
– 32 technical experts
• 3 locations
– Cestas (Bordeaux) (33)
– Fresnes (94) & Antony(92)
(Paris)
– Arras (62)
Staff, equipment,
and locations
• Laboratories and equipments
Fresnes
ІCemafroid activities
-Cemafroid Performance
-PIEK Certification
-Tests Centers
-Certificate of Capability
-F-Gas
-Measuring equipment
-Performance
-Conformity
-Qualification
-Calibration
-Verification
-Comparative tests
-Validation
-Audit
-Technical assistance
-F-Gas
-Carbon Footprint
-Energy optimization
-Competent Authority
-Datafrig
-ATP
-Innovation
-Cold Chain & Hygiene
-Metrology & Instrumentation
-Cold, Security and Environment
Certification of products,
services and companiesTests, Calibration, Verification Expertise, Counsels
Public Service Training
ІLe Cemafroid
• Laboratories accreditation
– Tests : Cofrac Essais ISO 17025,
– Tests : WHO/OMS – PQS
– Verifications : Cofrac Étalonnage ISO 17025
• Designation
– UNO – UNECE : ATP Test Station and ATP
Competent Authority
– Ministeries : Agriculture, Health, Defense,
Environment, Industry, …
• Networks
– IIF, Transfrigoroute, CEN, ISO,
– AFF, SFSTP, CNM,
Accreditations
F-Gaz implementation
French regulations
ІF-Gaz regulation• Concerns
– CFC - HCFC - HFC –
– All equipments including
– refrigerated transport,
– cars air conditionning…
• Obligations:
– Etancheity Controls over 2 kg
– Companies certification
• To buy and manipulate any F-Gazes
– Staff certification
• Even for etancheity control
– Traceability of all operations
• Load, installation, controls…
– Reporting and control
• stocks, leakages, usage, …
Framework
ІF-Gaz regulationFrench system overview
Opérateur /
Company siteOrganisme agréé
Ministery
Agrément
Attestation d’aptitude
Evaluation body Certification body
COFRAC
Accreditation
Certification
Equipment owner or user, PAC, refrigeration device, Air conditionning, car…
Control
StaffEquipment
F-Gaz
distributor
ADEMEreport
report
Leakage
report
Ministery
local authority
ІF-Gaz regulation in FranceCategories of operators
Etancheity
control
Maintenance
Support
Installation F-Gaz
recovery
Catégorie I All equipments refrigeration, air conditionning heat pumps
Catégorie II All equipments
refrigeration,
AC, HP
All equipments refrigeration, AC, HP with less
than 3kg F-Gaz
Catégorie III All equipments
refrigeration,
AC, HP with
less than 3kg
F-Gaz
Catégorie IV All equipments
refrigeration,
AC, HP
Catégorie V All equipments for air conditionning for vehicles
(cars, trucks, bus, all equipments going on the road)
ІF-Gaz regulation
Operator
Certified people working for certified
companies
Attestation d’aptitude /
Staff certificate
Attestation de capacité
/ Company certificate
ІF-Gaz regulation
Operators
Agrément
Company certificate
Condition n°1 :
Equipment
since 4th of July 2009
Charge station
Bottles
Leakage detector
Flexibles and obturators
Manometers; thermometres
Identification devices
List linked with the activity of the company
Vérifié selon la
norme NF EN 35421
Conforme à la NF
EN 14624Précision 5%...
Ministery
Organisme agréé
Opérateur /
Company site
ІF-Gaz regulation
Minister
Organisme agréé
Opérateur /
Company site
Agrément
Attestation de capacité /
company certificate
Personnal certificate
Evaluation body
Certification
bodyCOFRAC
Accreditation
Certification
Condition n°2
Competent staffSince 5th of July 2011
ІF-Gaz regulation
Agreement
Company certificate
Condition n°3
F-Gaz containement and
treaceabilitySince 4th of July 2009
Operation traceability
Operation report
F-Gaz annual Reporting
Etancheity certificate
Ministery
Organisme agréé
Opérateur/
Company site
ІF-Gaz regulationPeriodical controls
F-Gaz load Controls
> 2 kg Once a year
> 30 kg Every 6 month
> 300 kg Every 3 month
When a ambiance detector is installed frequency can be devided by 2
DATAFLUIDES
A centralised computing system
Datafluides®
First contact with
« Organismes Agrees »
Direct acces to
regulation
Last news
Private acces for
certificate
management
Public list of
operators
Declare company
elements
Siège social
Région 1
Région 2
Région 3
SIRET 1
SIRET 2
SIRET 3
SIRET 4
SIRET 5
SIRET 7
Accès selon profils à
Datafluides
Declare staff
Affect the staff to the
sites
Move people from one
site to another
Declare their
certification
Withdraw them.
Overview of demand
ІF-Gazes operators
French figures January 2011
40%
2%1%1%
56%
Cat 1 Cat 2 Cat 3 Cat 4 Cat 5
• Companies certificates :
« Attestation de capacité »
– Catégorie I à IV : 11 208
– Catégorie V: 16 291
– Some 70%
• People certificates :
« Attestation d’aptitude »
– Catégorie 1: 13 836
– Catégorie 2: 19 721
– Some 33%
ІDATAFLUIDES fonctionalities
OR
GA
NIS
ME
AG
RE
E
Anonyme
Opérateur
candidat
Abonnement à consultations détaillées Consultation espace public Inscription, choix d’un organisme agréé,
demande de devis, renseignement pré-dossier
Création compte opérateur candidat
Validation commande valant
demande d’attestation
Invitation à renseigner le
dossier de candidature
Envoi devis
Renseignement dossier de
candidature
Recevable
Edition attestation, et enregistrement
statut sur DATAFLUIDES
Si non
Demande complément
d’information
Saisie annuelle fiche fluides
Renouvellement
Suspension
Audit dans les 5 ans Si défavorable
Opérateur
habilité
Opérateur
candidat
HABILITATION
Si non
Suspension
HABILITATION
French disposal system
and its funding
ІThe French disposal system
• Collect and recycle and destroy F-Gazes
– In the frame of a national convention
– Managed by professional associations
• Collect system
• Equipments owned and operated by
distributors
• Treatment
• Done by the distributors and producers
• Payment
• A fee on each F-Gaz kg distributed
• a payment for dedicated bottles rental
• A payment of a prime for collect
Since 1993
ІThe French disposal system
A new system
Eco-organisme
Eco-fluides
Distributeurs de
fluides
MEDDTL
ADEME
Opérateurs attestés
manipulant des fluides
frigorigènes Flux de fluides
Flux financiers
Flux de données
Flux d’informations
Audits de contrôle
Organisations
professionnelles
Conclusion
ІConclusion
• F-Gaz issues are transversal
– No reason to exclude some activities
– Neither actors
• Process is long to implement
– Step by step process is necessary
– Control is also imperative
– international harmonization should increase
• A global computing tool online is a plus
– For everybody
– Cost and time saving project
– Traceability insurance
ІThank you for your attention !
For more detailled information, please contact us :
Gérald CAVALIER
Cemafroid
5, avenue des Prés,
94 266 Fresnes cedex France
www.cemafroid.fr
Tel : 01 49 84 84 84
Independent expertise and testing for cold chain