Experimental Study of Polypropylene Fiber-Reinforced Concrete
Prof., Dr. Hamed M. Jassima, Dr. Abdulkader G. Anwar
b
aDepartment of Geotechnical Engineering, Faculty of Engineering, Koya University, Erbil, Iraq. & UK-H, Erbil,
Iraq
bDepartment of Geotechnical Engineering, Faculty of Engineering, Koya University, Erbil, Iraq.
ABSTRACT
_____________________________________________________________________________________ Concrete made with Portland cement has certain characteristics: it is relatively strong in· compression but weak in tension and
tends to be brittle. These two weaknesses have limited its use. Another fundamental weakness of concrete is that cracks start to
form as soon as concrete is placed and before it has properly hardened. These cracks are major cause of weakness in concrete
particularly in large onsite applications leading to subsequent fracture and failure and general lack of durability. The weakness in
tension can be overcome by the use of conventional rod reinforcement and to some extent by the inclusion of a sufficient volume
of certain fibers. Polypropylene is a synthetic hydrocarbon polymer, the fiber of which is made using extrusion processes by hot
drawing the material through a die. This paper deals with the effects of addition of various proportions of polypropylene fiber on
the properties of concrete. This contribution presents the results of an experimental investigation carried out to study the effect of
fiber contents on the compression, tension (splitting test), and flexural tests of polypropylene fiber reinforced concrete (PFRC).
High performance polypropylene fibers of different fiber content were used. Compression cubes (100 mm), tension (Splitting
Test) cylinder (100x 200 mm), and one point bending tests were performed on both control (without fibers) and fibered notched
prismatic concrete specimens of cross section 100 x 100 mm and clear span of 400mm. The results showed that the compression,
tension (Splitting Test), and flexural properties of concrete matrix are significantly not good by the addition of high performance
polypropylene fibers. Out of the three different tests for polypropylene fibers which were used in this study, the different fibers
dosage of (0.0%, 0.5%, 1.0%, and 1.5%) showed not good efficiency in decreasing the flexural strength by (63.5%, 59.8%,
42.6%, and 40.5%) respectively.
Keywords: Polypropylene fibers, Mix proportions, Compressive strength, Splitting strength, Flexural strength, Synthetic
hydrocarbon polymer.
__________________________________________________________________________________
1. INTRODUCTION
Polypropylene fibers are new generation chemical fibers. They are manufactured in large scale and have fourth
largest volume in production after polyesters, Polyamides and acrylics. Polypropylene fibers were first suggested for
use in 1965 as an admixture in concrete for construction of blast resistant buildings meant for the US Corps of
Engineers [1, 2]. Monofilament polypropylene fibers can be used in much lower content than steel fibers. The tensile
strength and other mechanical properties are enhanced by subsequent multi stage drawing. These fibers have low
density of (0.9 g/cc). They are highly crystalline, with high stiffness and excellent resistance to chemical and
bacterial attack. The crystalline of these fibers is about (70%) while the molecular weight is (80,000 to 300,000
gm/mole) [3-7].
Polypropylene Fiber Reinforced Concrete (PFRC) is an embryonic construction material which can be described as a
concrete having high mechanical strength, stiffness and durability. By utilization of polypropylene fibers in concrete
not only optimum utilization of materials is achieved but also the cost reduction is achieved. Concrete has better
resistance in compression while steel has more resistance in tension. Conventional concrete has limited ductility, low
impact and abrasion resistance and little resistance to cracking. A good concrete must possess high strength and low
permeability. Hence, alternative composite materials are gaining popularity because of ductility and strain
hardening. To improve the post cracking behavior, short discontinuous and discrete fibers are added to the plain
concrete. Addition of fibers improves the post peak ductility performance, pre-crack tensile strength, fracture
strength, toughness, impact resistance, flexural strength resistance, fatigue performance etc. The ductility of fiber
Experimental Study of Polypropylene Fiber-Reinforced Concrete
Page 150
reinforced concrete depends on the ability of the fibers to bridge cracks at high levels of strain. Addition of
polypropylene fibers decreases the unit weight of concrete and increases its strength [8-12].
By utilization of polypropylene fibers in concrete not only optimum utilization of materials is achieved but also the
cost reduction is achieved. This paper presents a comprehensive review on various aspects polypropylene fiber
reinforced concrete concerning the behavior, applications and performance of polypropylene fiber reinforced
concrete.
2. EXPERIMENTAL PROGRAM
Experimental work was made to prepare polypropylene fiber reinforced concrete, and study their mechanical
properties and flexural resistance. A total of seventy two (72) specimens were casted and tested. We have three types
of specimens (cube, cylinder and prism) , whereby the dimensions of the cubes are (100) mm, for cylinders
(100x200) mm and for prisms (100x100x500) mm. Polypropylene fiber reinforced concrete and unreinforced (plain)
concrete mixes were used throughout the experimental work. In order to do the experimental work and studying the
mechanical behavior of polypropylene fiber reinforced concrete (PFRC), many tests had been done such as:
workability (slump), sieve analysis, compressive strength, splitting tensile strength and flexural strength test.
In the present investigation, three (3) main parameters were chosen to study the mechanical properties of
polypropylene fiber reinforced concrete (PFRC). Full details of these group parameters are listed in table 1.
The main test variables are:
1. Age of test.
2. Content of polypropylene fiber.
3. Type of test.
Table 1 - Considered parameters of (PFRC).
2.1 Materials Properties
The materials that were used for polypropylene fiber reinforced concrete (PFRC) throughout the experimental work
are (cement, sand, gravel, water and polypropylene fiber).
2.1.1 Cement
Ordinary Portland cement from (mass) factory conforming to Iraqi standard specifications (IQS 5/1984) [13] was
used throughout this investigation. The physical properties and chemical compositions are given in tables 2 and 3.
Group No. Fiber Content
%
Type of Test
Compression Test Tensile Test Flexural Test
7 days 28 days 7 days 28 days 7 days 28 days
1 0.00
C1 C4 T1 T4 F1 F4
C2 C5 T2 T5 F2 F5
C3 C6 T3 T6 F3 F6
2 0.50
C7 C10 T7 T10 F7 F10
C8 C11 T8 T11 F8 F11
C9 C12 T9 T12 F9 F12
3 1.00
C13 C16 T13 T16 F13 F16
C14 C17 T14 T17 F14 F17
C15 C18 T15 T18 F15 F18
4 1.50
C19 C22 T19 T22 F19 F22
C20 C23 T20 T23 F20 F23
C21 C24 T21 T24 F21 F24
Experimental Study of Polypropylene Fiber-Reinforced Concrete
Page 151
Table 2 - Chemical composition and main compounds of the cement
Table 3 - Physical properties of Portland cement
Physical properties OPC Limitation of IQS 5/1984
Fineness m2/kg 320 ≥230
Initial setting (Vicat Method) min. 100 ≥45 min
Final setting (Vicat Method) hr:min. 5:30 ≤ 10 hrs
Compressive strength (MPa)
3-days
7-days
17.1
26.8
≥15
≥23
2.1.2 Fine Aggregate Washed natural sand obtained from (Bucket) region in Erbil Governorate was used throughout this work. The results
of the sieve analysis of the sand are given in table 4, and conformed to the limits specified by B.S 882: 1992 [14]
grading requirement (M) was used.
Table 4 - Grading of fine aggregate
Sieve size (mm) Percentage by mass passing B.S 882:1992 Limiting
10 100 100
5 94.8 89-100
2.36 87 60-100
1.18 78.2 30-100
0.6 61.2 15-100
0.3 24.5 5-70
0.15 5.2 0-15
2.1.3 Coarse Aggregate
Washed natural Gravel obtained from (Bucket) region in Erbil Governorate was used throughout this work. Table 5
shows the grading of coarse aggregate used and conformed to the limits specified by B.S 882: 1992 [14].
Chemical Components % by weight
Limitation of IQS 5/1984 OPC
CaO 64.2 -----
MgO 2.1 ≤ 5
SiO2 21.01 -----
SO3 2.0 ≤ 2.8
Fe2O3 2.8 -----
Al2O3 4.86 -----
Loss on ignition 2.05 ≤ 4
Main Compounds
C3S 30.5 -----
C2S 35.3 ----- C3A 9.1 -----
C4AF 11.7 -----
Experimental Study of Polypropylene Fiber-Reinforced Concrete
Page 152
Table 5 - Grading of coarse aggregate
Sieve size (mm) Percentage by mass passing B.S 882:1992 Limiting
14 100 100
10 90.3 85-100
5 20.1 0-25
2.36 1.5 0-5
2.1.4 Water
Tap water was used for mixing and curing the samples for all experimental programs.
2.1.5 Reinforcement
Addition of polypropylene fiber as shown in figure 1 to concrete greatly affects the mechanical properties of
(PFRC), and this effect of polypropylene fiber on the mechanical properties of (PFRC) depends on the followings:
1-The aspect ratio of the fiber length is equal to (50) as shown in table 6.
2- Shape of the fiber.
3- Density of the fiber.
4- Surface condition of the fiber.
5- Chemical compositions of the fiber.
Fig. 1 - Polypropylene fiber used
Table 6 - Aspect ratio of polypropylene fiber
Type of fiber Length(mm) Diameter(mm) Aspect ratio
Polypropylene 50 1 50
2.2 Mix Design The design of concrete mix cannot be based on the same parameters that are used for polypropylene fiber mix. The
mix proportions used are based on experiments carried out on the work of others in the field. After many trials, the
mix proportion by weight (kg/m3) was achieved and used in this investigation (1.0:1.8:2.1:0.55) (cement: sand:
gravel: water cement ratio) for polypropylene fiber mix. The workability was measured by slump test according to
ASTM C143-86 [15-17]. The results of the slump tests are given in table 7.
Table 7 - Slump results for concrete with polypropylene fiber
Mix Slump (mm) Remarks
1.0:1.8:2.1:0.55 180 without fiber
1.0:1.8:2.1:0.55 40 with fiber
Experimental Study of Polypropylene Fiber-Reinforced Concrete
Page 153
2.3 Mixing, Casting and Curing:- All the mixes were batched in a tilting pan type mixer of (0.04m3) capacity as shown in figure 2. First half of dry
sand was mixed (30 seconds), then half quantity of cement was added to the mixer and mixed for (30 seconds), then
after half quantity of water was dispersed gradually for (30 seconds), and the remaining sand was added to the mixer
and mixed for (30 seconds), and the remaining cement was added to the mixer and mixed for (30 seconds) and
finally the remaining water was added to the mix and mixed for (30 seconds). The mixer was stopped when a good
homogeneous mix was produced. The mix was poured in two layers into the molds.
Each layer was compacted by electrical vibrator. The specimens were left in the laboratory for 24 hours after casting,
then they were remolded and the specimens were marked and stored in a water pool (tank) until time of testing (7
days) and (28 days), and finally they were taken out from the tank and placed in dry place at room temperature
before testing in the concrete laboratory [18-20].
Fig. 2 - Tilting pan type concrete mixer
2.4 Control Specimens Since it was necessary to carry out test on each sample, it was important to make (cubes, cylinders and prisms) from
the plain concrete as a reference to determine the compressive, tensile and flexural strength of them and also they
were used for comparison. The specimens have been air dried for 24 hours, then kept in a water tank for 28 days at
room temperature of about (20° C) and finally taken out from the water tank and kept in the open at room
temperature before testing them. For each group in compression loading three specimens were made. The
compression test was carried out on cubes (100x100x100) mm, cylinders (100x200) mm and prisms (100x100x500)
mm. Figure (3) shows the compression and flexural testing machines.
Fig. 3 - The compression and flexural testing machines
Experimental Study of Polypropylene Fiber-Reinforced Concrete
Page 154
3. TEST RESULTS AND DISCUSSION
The discussions of test results for the control specimens (compression, tension, and flexural tests) are summarized in
tables 8, and 9, and figures 4 to 9.
3.1 Test Results for the Control Specimens
In the tables 8 and 9, the test results and the average results for the compression, tension, and flexural tests for 7 and
28 days for the different polypropylene fiber contents are shown.
Table 8 - Results of control specimens
Table 9 - Average results of control specimens
Group No. Fiber Content
(%)
Type of Test
Compressive Strength
(MPa)
Tensile Strength
(MPa)
Flexural Strength
(MPa)
7 days 28 days 7 days 28 days 7 days 28 days
1 0.00 19.51 49.33 2.23 4.22 2.96 4.84
2 0.50 25.35 40.21 2.58 3.38 3.57 4.73
3 1.00 24.95 39.23 2.26 3.14 3.21 4.22
4 1.50 21.93 37.61 2.18 3.00 3.12 4.16
3.2 Compression Test The results of the compressive strength as shown in figure 4 are calculated using the following law:
(1)
Where:
P= the applied force (N).
A= the sectional area (mm2).
Group No. Fiber Content
(%)
Type of Test
Compressive Strength
(MPa)
Tensile Strength
(MPa)
Flexural Strength
(MPa)
7 days 28 days 7 days 28 days 7 days 28 days
1 0.00 19.35 48.62 2.16 3.55 2.63 4.60
18.65 51.49 2.13 4.63 3.24 5.15
20.54 47.89 2.40 4.47 3.00 4.77
2 0.50 26.83 40.27 2.68 3.02 3.42 4.94
24.05 41.31 2.60 3.48 3.43 4.31
25.18 39.05 2.46 3.63 3.85 4.95
3 1.00 26.35 39.43 2.30 3.25 3.28 4.41
25.88 41.88 2.12 3.05 3.03 4.26
22.62 36.37 2.37 3.13 3.33 4.00
4 1.50 22.08 37.80 2.03 3.06 3.18 4.21
22.29 38.67 2.23 2.97 3.10 4.12
21.41 36.35 2.27 2.96 3.09 4.15
Experimental Study of Polypropylene Fiber-Reinforced Concrete
Page 155
= the compression stress (N/mm2).
The results were taken for the average three cube samples (100 mm) according to BS 1881: Part 116 Testing
Concrete: method for determination of compressive strength of concrete cubes standards [21]. The results for the
compression strength are taken for 7 and 28 days for different polypropylene fiber content (0.00%, 0.50%, 1.00%,
and 1.50%) which are shown in table 8.
Fig. 4 - Compressive strength test
It is observed from the figures 5, 6 and table 9 that the cube compressive strength decreased up to 1.5 % fiber
content. The cube compressive strength was observed as 40.21 MPa for 0.5% of fibers, 39.23 MPa for 1% of fibers
and 37.61 MPa for 1.5% fiber content in the concrete at 28 days. There is a reduction in slump with the increase in
fiber content, especially beyond 1.5% dosage. However, the compressive strength for controlled mix at 28 days was
observed as 49.33 MPa.
Fig. 5 - Effect of various contents of fibers on the compressive strength
Experimental Study of Polypropylene Fiber-Reinforced Concrete
Page 156
Fig. 6 - Compressive strength of different fiber content for 7 and 28 days tests
All things considered, it appears that at low dosage rates (0.5% to 1%) the addition of polypropylene fibers does not
significantly detract from, and even improve the compressive strength. Higher dosage rates however decrease the
strength of concrete matrix due to higher volumes of fibers interfering with the cohesiveness of the concrete matrix
[22-25].
3.3 Tension Test (Splitting Test) The results for the splitting tensile strength as shown in figure 7 are calculated by using the following law:
(2)
Where:
p = the applied force (N).
D= the diameter of cylinder test (mm).
L= the length of the specimen (mm).
t= the tensile stress (N/mm2).
The results were taken for the average three samples (100 mm x 200 mm) cylinder according to ASTM C496 and BS
1881: Part 2 Methods of Testing Concrete standard was used [26].The results for the splitting tensile strength are
taken for 7 and 28 days for different polypropylene fiber content (0.00%, 0.50%, 1.00%, and 1.50%) ratios and
shown in table 8.
Fig. 7 - Splitting tensile strength test
0
10
20
30
40
50
60
0.00 0.50 1.00 1.50
7days 19.51 23.35 24.95 21.93
28days 49.33 40.21 39.23 37.61
Co
mp
ress
ive
Str
ength
(M
Pa)
Fiber Content %
7days
28days
Experimental Study of Polypropylene Fiber-Reinforced Concrete
Page 157
It is observed from figures 8, 9 and table 9 that the Split tensile strength was decreased for fiber ratios up to 1.5 %
fiber content. The split tensile strength values at 28 days were observed as 3.37 MPa for 0.5% of fibers, 3.14 MPa
for 1% of fibers and 3.00 MPa for 1.5% fiber content in the concrete. There is a reduction in slump with the increase
in fiber content, especially beyond 1.5% dosage. However, the split strength for controlled mix at 28 days was
observed as 3.88 MPa [24, 25, and 27-29].
Fig. 8 - Effect of various contents of fibers on the splitting strength
Fig. 9 - Splitting strength of different fiber contents for 7 and 28 days tests
3.4 Flexural Test (Rupture Test)
The results of the flexural strength as shown in figure 10 were calculated by using the following law:
(3) Where:
p = the applied force (N).
L= the length of the specimen (mm).
b = the width of prism test (mm).
d = the depth of prism test (mm).
0
1
2
3
4
5
0.00 0.50 1.00 1.50
7days 2.23 2.58 2.26 2.18
28days 4.22 3.38 3.14 3
Ten
sile
Str
ength
(M
Pa)
Fiber Content %
7days
28days
Experimental Study of Polypropylene Fiber-Reinforced Concrete
Page 158
r = the flexural stress (N/mm2).
Fig. 10 - Flexural strength test
The results for the average three samples (100 mm x 100 mm x 500 mm) prisms were taken according to ASTM
C1609 standard [30]. The results for the flexural strength are taken for 7 days and 28 days for different
polypropylene fiber content (0.00%, 0.50%, 1.00%, and 1.50%) ratios which are shown in table 8. It is observed from figures 11, 12 and table 9 that the flexural strength was decreased with fiber content up to 1.5 %.
The flexural strength values at 28 days were observed as (4.72) MPa for 0.5% of fibers, (4.22) MPa for 1% of fibers
and (4.16) MPa for 1.5% fiber content in the concrete. There is a reduction in slump with increase in fiber content,
especially beyond 1.5% dosage. However, the flexural strength for controlled mix at 28 days was observed as (4.84)
MPa [24, 25, and 31-32].
Fig. 11 - Effect of various contents of fibers on the flexural strength
Experimental Study of Polypropylene Fiber-Reinforced Concrete
Page 159
Fig. 12 - Flexural strength of different fiber contents for 7 and 28 days tests
4. CONCLUSIONS AND SUGGESTIONS FOR FUTURE WORK According to the outcomes of this research, the following conclusions can be made:
1- The comparison between the different values of compressive strength of concrete for (7 and 28 days) shows a
decrease gradually due to the addition of polypropylene fiber from 0.00% to 1.5%. There is a decrease in
compressive strength as compared with normal plain concrete (without fibers). Thus the percentages of
compressive strength decreases are: (152.8, 58.6, 57.2, and 71.5), for fiber content percent (0.00%, 0.50%,
1.00%, and 1.50%).
2- The compressive strength values for (7 days) according to fiber content of (0.50%, 1.00%, and 1.50%)
decrease in the percentage of (29.9%, 27.8%, and 12.4%) respectively.
3- The compressive strength values for (28 days) according to fiber content of (0.50%, 1.00%, and 1.50%)
decrease by the percentages of (18.4%, 20.47%, and 23.75%) respectively.
4- The comparison between tensile strength values of concrete for (7 & 28 days) shows a gradual decrease due
to the addition of polypropylene fiber from 0.00% to 1.5%. There is a decrease in tensile strength as
compared with normal plain concrete (without fibers). Thus the percentage tensile strength decreases are:
(73.99%, 31.1%, 38.3%, and 48.5%), for fiber content percent of (0.00%, 0.50%, 1.00%, and 1.50%)
respectively.
5- The tensile strength values for (7 days) according to fiber contents of (0.50%, 1.00%, and 1.50%) show a
decrease of (15.17%, 1.34%, and 2.67%) respectively.
6- The tensile strength values for (28 days) according to fiber content of (0.50%, 1.00%, and 1.50%) decrease by
the percentages of (13.14%, 19.07%, and 22.68%) respectively.
7- The comparison between flexural strength values of concrete for (7 and 28 days) shows a gradual decrease
with the addition of polypropylene fiber. There is a decrease in flexural strength as compared to normal plain
concrete (without fibers). Thus the percentages of flexural strength decreases are: (63.5%, 59.8%, 42.56%,
and 40.54%), for fiber content percentages of (0.00%, 0.50%, 1.00%, and 1.50%) respectively.
8- The flexural strength values for (7 days) according to fiber content values of (0.50%, 1.00%, and 1.50%)
decrease by the percentages of (20.6%, 8.44%, and 5.4%) respectively.
9- The flexural strength values for (28 days) according to fiber content values of (0.50%, 1.00%, 1.50%)
decrease by the percentages of (-2.27%, -12.8%, -14.05%) respectively.
5. RECOMMENDATIONS
The following recommendations can be indicated:
1- The use of other type of fibers like polyester, polyethylene, and nylon.
2- The use of multi aspect ratio for other fibers.
3- The study of other materials like lightweight aggregate.
4- The study of the behavior of polypropylene fiber in beams and slabs.
0
1
2
3
4
5
6
0.00 0.50 1.00 1.50
7days 2.96 3.57 3.21 3.12
28days 4.84 4.73 4.22 4.16
Fle
xura
l S
tren
gth
(M
Pa)
Fiber Content %
7days
28days
Experimental Study of Polypropylene Fiber-Reinforced Concrete
Page 160
Acknowledgements The authors wishe to place on record the help provided by the management and the academic teaching and non-
teaching staff of the faculty of engineering at Koya university, in the completion of this study.
REFERENCES [1]. Goldfein, S., “Fibrous Reinforcement for Portland Cement,” Modern Plastics, Vol. 42, No. 8, 1965, pp.
156-160.
[2]. Williamson, G. R., “Response of Fibrous Reinforced Concrete to Explosive Loading,” Technical Report
No. 2-48, Department of the Army, Ohio River Division Laboratory, U. S. Corp of Engineers, Cincinnati,
Ohio, Jan. 1966.
[3]. Majumdar, A. J., “Properties of Fiber Cement Composites,” Proceedings, RILEM Symposium, London,
1975, Construction Press, Lancaster, 1976, pp. 279-314.
[4]. Hannant, D. J., Fibre Cements and Fibre Concretes, John Wiley and Sons, Ltd., New York, 1978, 213 pp.
[5]. Dave, N. J., and Ellis, D. G., “Polypropylene Fibre Reinforced Cement,” The International Journal of
Cement Composites, Vol. 1, No. 1, May 1978, pp. 19-28.
[6]. “Measurement of Properties of Fiber Reinforced Concrete,” ACI JOURNAL, ACI Committee Report
544.2R 78, July 1978.
[7]. Mai, Y. W.; Andonian, R.; and Cotterell, B., “Thermal Degradationof Polypropylene Fibers in Cement
Composites,” International Journal of Composites, Vol. 3, No. 3, Aug. 1980, pp. 149-155.
[8]. Zollo, R. F., Collated Fibrillated Polypropylene Fibers in FRC, SP- 81, American Concrete Institute,
Detroit, 1984, pp. 397-409.
[9]. Zollo, R. F.; Ilter, J. A.; and Bouchacourt, G. B., “Plastic and Drying Shrinkage in Concrete Containing
Collated Fibrillated Polypropylene Fibre,” Third International Symposium on Developments in
FibreReinforced Cement and Concrete, RILEM Symposium FRC 86, Vol. 1, RILEM Technical
Committee 49-TFR, July 1986.
[10]. Rice, E., Vondran, G. and Kunbargi, H., “Bonding of Fibrillated Polypropylene Fibers to Cementitious
Materials,” Materials Research Society Proceedings, Pittsburgh, Vol. 114, 1988, pp. 145-152.
[11]. Morgan, D. R.; McAskill, N.; Richardson, B. W.; and Zellers, R. C., “A Comparative Evaluation of Plain,
Polypropylene Fiber, Steel Fiber, and Wire Mesh Reinforced Shotcrete,” Transportation Research Board,
Washington D. C., Jan. 1989.
[12]. State-of-the-Art Report on Fiber Reinforced Concrete Reported by ACI Committee 544, 1996, PP.66.
[13]. Iraqi Specification No.5:1984 "Cement Portland", 1987, National Center for Structural Laboratory,
Planning Council, pp.21-23.
[14]. B.S.882: 1992 "Aggregate from Natural Sources used in Concrete" British Standard Institute BSI.
[15]. ASTM Designation C 143-86 “Method for Slump of Hydraulic Cement Concrete”, 1989 Annual Book of
ASTM Standard, American Society for Testing and Materials, Philadelphia, Pennsylvania, Section 4, Vol.
04 - 02, pp. 20 - 23.
[16]. ACI 211.1-91 "Standard Practice for Selecting Proportions for Normal, Heavyweight, and Mass Concrete",
American Concrete Institute, Detroit, Michigan, 1996, pp.1-38.
[17]. Osman Gencel a, "Workability and Mechanical Performance of Steel Fiber-Reinforced Self-Compacting
Concrete with Fly Ash" Composite Interfaces 18 (2011) 169–184.
[18]. Ramakrishnan, V.; Gollapudi, S.; and Zellers, R., Performance Characteristics and Fatigue of
Polypropylene Fiber Reinforced Concrete, SP 105, American Concrete Institute, Detroit, 1987, pp. 159-
177.
[19]. Nagabhushanam, M.; Ramakrishnan, V.; and Vondran, G., “Fatigue Strength of Fibrillated Polypropylene
Fiber Reinforced Concrete, Transportation Research Record 1226, National Research Council,
Washington D.C., 1989, pp. 36-47.
[20]. ACI 544.1 R-96 "State-of-the-Art Report on Fiber Reinforced Concrete", American Concrete Institute,
Experimental Study of Polypropylene Fiber-Reinforced Concrete
Page 161
Detroit, Michigan, 1996, pp.1-24.
[21]. British Standard Institution (1983), “BS 1881: part 116: Testing Concrete: method for determination of
compressive strength of concrete cubes”, BSI, London.
[22]. Guirguis, S., and Potter, R. J., “Polypropylene Fibers in Concrete,” Technical Report TR/F90, Cement and
Concrete Association of Australia, May 1985, 21 pp.
[23]. Malisch, W. R., “Polypropylene Fibers in Concrete—What Do the Tests Tell Us?,” Concrete Construction,
Apr. 1986, pp. 363-368.
[24]. T.Ch.Madhavi, L.SwamyRaju, and Deepak Mathur “Polypropylene Fiber Reinforced Concrete – A
Review,” IJETAE Journal, Vol.4, Issue 4, June 2014, pp. 114-119.
[25]. Milind V. Mohod, “Performance of Polypropylene Fiber Reinforced Concrete,” IOSR Journal of
Mechanical and Civil Engineering (IOSR-JMCE) IOSR-JMCE, Vol.12, Issue 1, Jan-Feb.2015, pp. 28-26.
[26]. ASTM Designation C496-96“Standard Test Method for Splitting Tensile Strength of Cylindrical Concrete
Specimens”, 1996 Annual Book of ASTM Standard, American Society for Testing and Materials,
Philadelphia, Pennsylvania.
[27]. Ramakrishnan, V.; Gollapudi, S.; and Zellers, R., Performance Characteristics and Fatigue of
Polypropylene Fiber Reinforced Concrete, SP-105, American Concrete Institute, Detroit, 1987, pp. 159-
177.
[28]. Nagabhushanam, M.; Ramakrishnan, V.; and Vondran, G., “Fatigue Strength of Fibrillated Polypropylene
Fiber Reinforced Concrete,” Transportation Research Record 1226, National Research Council,
Washington D.C., 1989, pp. 36-47.
[29]. Mashima, P., Hannant, D.J. and Keer, J.G., "Tensile Properties of Polypropylene Reinforced Cement with
Different Fiber Orientation", ACI Material Journal, Vol.87, No.2, March-April 1990, pp.172-178.
[30]. ASTM Designation C1609/C1609M, “Standard Test Method for Flexural Performance of Fiber Reinforced
Concrete (Using Beam with Third-Point Loading)”, Annual Book of ASTM Standard, ASTM
International, West Conshohocken, PA, 2011.
[31]. Ramakrishnan, V.; Wu, G. Y.; and Hosalli, G., “Flexural Behavior and Toughness of Fiber Reinforced
Concretes,” Transportation Research Record 1226, National Research Council, Washington D. C., 1989,
pp. 69-77.
[32]. Vondran, G. L.; Nagabhushanam, M.; and Ramakrishnan, V., “Fatigue Strength of Polypropylene Fiber
Reinforced Concretes,” Fiber Reinforced Cements and Concretes: Recent Developments, edited by R. N.
Swamy and B. Barr, Elsevier Applied Science, London and New York, 1990, pp. 533-543.