Experience With Use of C57.139 LTC DGA Guide IEEE TRANSFORMER COMMITTEE MEETINGS JOHN PRUENTE OCTOBER 23, 2011 DIR. ENG. TECHNICAL SUPPORT © SPX Transformer Solutions, Inc. 2012

Transcript of Experience With Use of C57.139 LTC DGA...

Page 1: Experience With Use of C57.139 LTC DGA Guidegrouper.ieee.org/groups/transformers/subcommittees/fluids/C57_139/... · UZD DGA Study ‐Background • Began with request from Midwest

Experience With Use of C57.139 LTC DGA GuideIEEE TRANSFORMER COMMITTEE MEETINGS JOHN PRUENTEOCTOBER 23, 2011 DIR. ENG. TECHNICAL SUPPORT

© SPX Transformer Solutions, Inc. 2012

Page 2: Experience With Use of C57.139 LTC DGA Guidegrouper.ieee.org/groups/transformers/subcommittees/fluids/C57_139/... · UZD DGA Study ‐Background • Began with request from Midwest

Outline of Presentation

• Background of UZD DGA Study

• Summary of Data Reviewed

• Results of Study to Date

• Suggestions for Revisions / Additions  to C57.139 Guide for Consideration 

2

Page 3: Experience With Use of C57.139 LTC DGA Guidegrouper.ieee.org/groups/transformers/subcommittees/fluids/C57_139/... · UZD DGA Study ‐Background • Began with request from Midwest

UZD DGA Study ‐ Background• Began with request from Midwest utility in March 2010• Too many “false positives” with code 4 DGA results from oil lab.• Utility needed a better way to analyze and use DGA data as a predictive 

maintenance tool.• Grown to include 5 utilities located  in different regions around the United 

States:– Northeast – North Central – South Central– North Western– South Western 

• Utility selection criteria– Have 50+ UZD’s in service– Sample LTC for DGA annually (minimum)– Have historical DGA database to work with

3

Page 4: Experience With Use of C57.139 LTC DGA Guidegrouper.ieee.org/groups/transformers/subcommittees/fluids/C57_139/... · UZD DGA Study ‐Background • Began with request from Midwest

UZD DGA Study Objectives• Determine calculated DGA limits for each utility population based on the 

C57.139 guide applied to the historical data.• Verify limits by correlating DGA diagnosis to maintenance inspection “as 

found “ condition.• Develop SPX Waukesha endorsed universal UZD DGA criteria for use by 

UZD owners (if possible).• Develop a more consistent approach and analysis method (algorithm) for 

UZD DGA. • Investigate “false positives” and identify a way to recognize them at the 

analysis stage.• Identify most effective next steps to be taken when a UZD is outside the 

norms.• Identify which maintenance activities are most critical for the UZD model.• Learn as much as possible about operational performance of the UZD 

model LTC.   

4

Page 5: Experience With Use of C57.139 LTC DGA Guidegrouper.ieee.org/groups/transformers/subcommittees/fluids/C57_139/... · UZD DGA Study ‐Background • Began with request from Midwest

Results to Date

• Represents 12% of Population (approx. 6500 units sold)

5

Utility Geographic Region # of UZD's # Samples Oldest Sample

A North Central US 134 780 Apr‐95

B South Central US 265 1988 Jan‐00

C Northeastern US 57 444 Jan‐91

D Northwestern US 212 2197 Apr‐95

E Southwestern US 116 930 Nov‐02

784  6339

Table 1 : Summary of UZD Populations by Utility in Study

Page 6: Experience With Use of C57.139 LTC DGA Guidegrouper.ieee.org/groups/transformers/subcommittees/fluids/C57_139/... · UZD DGA Study ‐Background • Began with request from Midwest

Results to Date

6

Maintenance Item Utility A Utility B Utility C Utility  D Utility E

# of Operations N/A N/A50K / 100K*** 

or 12 yrs50K**

Time Based 3 yrs

DGA ResultCode 4 or 4*

TASABased on Internal 

CriteriaBased on 

Internal CriteriaCode 3, 4, or 4*

TASABased on 

Internal Criteria

Oil Sample Rate Annual* Annual* Annual* Annual* Annual*

Infra Red Scan Annual* Bi‐Annual* As Needed Annual* As Needed

Oil Replaced at Maintenance YesReuse (Large Vol)Replace (Small 

Vol)yes

≈50% based on oil condition

Yes

Oil Filter Operation 24/7Based on LTC Operation

Periodic(Time Based)

24/7Periodic 

(Time Based)

Oil Filter Cartridge Replacement

Pressure Differential

Pressure Differential or 

AnnualAnnual

Pressure Differential

Pressure Differential

Operate LTC Through Neutral If Possible6 Months if Possible

If Possible3,6,9, or 12 

months based on Model

QuarterlyIf Possible

Table 2: Comparison of LTC Maintenance Criteria by Utility in Study* ‐More frequent if problem suspected or critical unit** ‐ 75K if temperature differential monitor installed*** ‐ 100K for vacuum type

Page 7: Experience With Use of C57.139 LTC DGA Guidegrouper.ieee.org/groups/transformers/subcommittees/fluids/C57_139/... · UZD DGA Study ‐Background • Began with request from Midwest

Results to Date

7

Utility A Utility B Utility C Utility D Utility EEquipment Population Size : 134 Equipment Population Size : 265 Equipment Population Size : 57 Equipment Population Size : 212 Equipment Population Size : 116

Variable NAlert Limit (95%)

Alarm Limit (99%)

U1 U2 Variable NAlert Limit (95%)

Alarm Limit (99%)

U1 U2 Variable NAlert Limit (95%)

Alarm Limit (99%)

U1 U2 Variable NAlert Limit (95%)

Alarm Limit (99%)

U1 U2 Variable NAlert Limit (95%)

Alarm Limit (99%)

U1 U2

h2 497 1375 1952 h2 1509 502 842 h2 399 271 390 h2 1770 697 1001 h2 930 331 492

ch4 456 750 1106 ch4 1303 134 231 ch4 379 103 148 ch4 1527 266 381 ch4 930 156 229

c2h6 375 552 816 c2h6 616 35 123 c2h6 109 84 121 c2h6 1148 97 137 c2h6 930 37 56

c2h4 506 2540 3758 c2h4 1466 479 790 c2h4 396 448 639 c2h4 1774 767 1095 c2h4 930 575 860

c2h2 506 6272 9479 c2h2 1573 3724 5874 c2h2 406 2496 3513 c2h2 1817 4171 5979 c2h2 930 5850 8700

THG 367 4194 6083 THG 588 1121 1542 THG 108 1565 2218 THG 1104 1232 1704 THG 878 761 1123

water 505 58 77 water 1967 63 91 water 432 40 55 water 1827 56 76 water 833 46 61

fluidtempc n/a n/a n/a fluidtempc 717 61 82 fluidtempc n/a n/a n/a fluidtempc 1589 53 68 fluidtempc 912 61 79

c2h4/c2h2 525 0.78 1.34 0.88 1.34 c2h4/c2h2 1374 0.19 0.22 0.21 0.26 c2h4/c2h2 358 0.22 0.27 0.21 0.26 c2h4/c2h2 1688 0.36 0.49 0.44 0.63 c2h4/c2h2 909 0.123 0.143 0.136 0.173

n2/o2 544 5.07 9.08 6.46 8.99 n2/o2 1717 4.95 5.86 5.21 6.48 n2/o2 412 2.62 2.81 5.1 7.01 n2/o2 1850 17.77 29.35 18.3 27.6 n2/o2 530 3.69 5.31 3.56 4.38

THG/C2H2 368 1.14 1.97 THG/C2H2 547 0.35 0.44 THG/C2H2 93 0.52 0.69 0.87 1.22 THG/C2H2 1088 0.771 1.133 0.73 1.05 THG/C2H2 130 0.221 0.264 0.26 0.34

Table 2: Comparison of Calculated Limits for UZD Populations by Utility

• No universal limits

• Some population limits extremely low , should not be applied

Page 8: Experience With Use of C57.139 LTC DGA Guidegrouper.ieee.org/groups/transformers/subcommittees/fluids/C57_139/... · UZD DGA Study ‐Background • Began with request from Midwest

Results to Date

• Wide variation in limits between utilities– Differences in maintenance practices

• Length of maintenance cycle 

• Replace vs. reuse oil

• Use of on line filtration

• Desiccant breather maintenance

– Transformer loading

– Frequency of operation

8

Page 9: Experience With Use of C57.139 LTC DGA Guidegrouper.ieee.org/groups/transformers/subcommittees/fluids/C57_139/... · UZD DGA Study ‐Background • Began with request from Midwest

Results to Date

9

• False Positive “Maverick” Units Identified– Ethylene / Acetylene ratio outside calculated limits (>1)

– First noticed at Utility A (< 7% of population)

– Indicative of “Severe Contact Heating” classical DGA diagnosis

– IR Scans while in service and internal inspections revealed no issues

– Further research needed to identify source of elevated Ethylene

– Trend using Duval Triangle 2² to verify stability

“Maverick” Unit “Normal” Unit Unit in “Fault Evolution”

² ‐ Source IEEE Magazine Nov / Dec 2008 – Vol. 24, No.6

Page 10: Experience With Use of C57.139 LTC DGA Guidegrouper.ieee.org/groups/transformers/subcommittees/fluids/C57_139/... · UZD DGA Study ‐Background • Began with request from Midwest

UZD Best Practices

10

• For units flagged outside the DGA norms established – Retest oil to verify trend and rate of change

– Check Duval Triangle 2² trend

– IR scan to check LTC tank temp and look for localized heating

– Check N2/O2 to verify breather open (ratio should be < 4)

– Check for recent change in loading  and / or frequency of operation

– Review past maintenance history for previous problems (repeatingproblem)

• After performing maintenance– Replace old oil with new , clean, filtered oil

– Sample after oil filling and before energization (benchmark)

– Re‐sample again within one week of energization to verify no issues

² ‐ Source IEEE Magazine Nov / Dec 2008 – Vol. 24, No.6

Page 11: Experience With Use of C57.139 LTC DGA Guidegrouper.ieee.org/groups/transformers/subcommittees/fluids/C57_139/... · UZD DGA Study ‐Background • Began with request from Midwest

Summary

11

• Universal DGA limits for UZD LTC’s not possible

• C57.139 Guide works well for given utility / LTC model population

• Application of U1 / U2 limits good start for alert and alarm levels

• Application 95% / 99% limits for key ratios worked well for identifying units outside the norm and with real problems 

• N2/O2 ratio on free breathing LTC’s works well for identifying breathers in need of maintenance

• Identified “Maverick” gassing pattern for UZD’s and method of recognizing it

• Use of Duval Triangle 2² for trending LTC’s headed towards failure very useful

² ‐ Source IEEE Magazine Nov / Dec 2008 – Vol. 24, No.6

Page 12: Experience With Use of C57.139 LTC DGA Guidegrouper.ieee.org/groups/transformers/subcommittees/fluids/C57_139/... · UZD DGA Study ‐Background • Began with request from Midwest

Suggested Changes 

12

• Add suggestion on what to do when calculated limits are too low– Suggest using C2H4/C2H2 boundary limits of Duval Triangle 2:

• <.35 – normal  and in “N” Zone  continue  operation• > .35 and <1.2 – increase sample frequency / trend (Quarterly)• >1.2 and < 4.0 ‐ increase sample frequency / trend  ( Monthly / Weekly)• >4.0 – Consider outage and inspection

– And/or apply Stenestram Ratio¹ limits for UZD, UZE, UZF, or UZG models

• Encourage utilities to correlate calculated limits to LTC inspection observations for refinement of initial limits

¹ ‐ Source ABB Info No. IZSC000498‐AAA en, dated 6‐21‐2004² ‐ Source IEEE Magazine Nov / Dec 2008 – Vol. 24, No.6

Duval Triangle 2 With Suggested C2H4 / C2H2 Limits²

Page 13: Experience With Use of C57.139 LTC DGA Guidegrouper.ieee.org/groups/transformers/subcommittees/fluids/C57_139/... · UZD DGA Study ‐Background • Began with request from Midwest

Suggested Changes • Add use of Duval Triangle 2 for trending , possibly include case study example in Annex C

• Consider adding mention of importance of N2/O2 ratio for Free breathing LTC’s or breath through a desiccant (dryer). 

– Ratio > 8 indicate plugged air path with high degree of confidence

• Add recommendation on how often limits should be recalculated and updated.– Suggest every 5 years or after any major maintenance initiatives involving multiple units of a given 

model are completed

• Add recommendation for replacing oil in LTC when maintenance performed– Due to length of time between maintenance intervals– Filtering used oil does not remove gasses, can cloud after maintenance benchmark

• Recommend “sanity” limits for individual gasses set at 5 – 10 X U2 calculated limit to catch cases where :

– Breather is plugged and gas concentrations increase significantly– Excessive LTC operations due to faulty controller– Mechanical binding causing slow operation and longer than normal arc duration

13