Exp. 3_ Load Test and Equivalent Circuit Determination on Three Phase Squirrel Cage Induction Motor...
-
Upload
sanjay-meena -
Category
Documents
-
view
218 -
download
0
Transcript of Exp. 3_ Load Test and Equivalent Circuit Determination on Three Phase Squirrel Cage Induction Motor...
-
7/30/2019 Exp. 3_ Load Test and Equivalent Circuit Determination on Three Phase Squirrel Cage Induction Motor and (1)
1/9
Indian Institute of Technology Gandhinagar
Department of Electrical Engineering
EE 311 Electrical Machines and Power Electronics Lab. B. Tech.: Electrical, Sem. : V
Date of Exp. : 21st Aug. 2012 Submitted by:
Date of Submission: 28th Aug.2012 Nitya Pawar(10002022)
EXPERIMENT 3: LOAD TEST ON THREE PHASE SQUIRREL CAGE INDUCTION MOTOR AND
EQUIVALENT CIRCUIT DETERMINATION USING NO LOAD AND BLOCKED ROTOR TESTS.
AIM:
1. To conduct load test on 3 squirrel cage induction motor and obtain its performancecharacteristics.
2. Equivalent circuit model determination using OC and SC tests and performance analysis.
APPARATUS REQUIRED:
Sl. No. Apparatus Specification Quantity
1. Rotating Machines
from Test bench
The machines from the Test Bench are to be
configured for running the DC machine as
Generator and the Induction machine as Motor
the prime mover for the DC generator.
1
2 Extension Panel Panel that facilitates having terminals extended
from rotating machinery, power supplies, Load
banks and panel meters.
1
THEORY
A three phase induction motor consists of a stationary stator and rotating rotor separated by
uniform air gap. Two types of rotor used are slip ring rotor and squirrel cage rotor.
When a three phase supply is given to a stator, a revolving magnetic field rotating at
synchronous speed is produced. The lines of force of stator field cut the rotor conductors and
alternating emf is induced in the rotor conductors due to the relative motion between the
stator field and the rotor conductors. The Interaction between the stator magnetic field and the
rotor current carrying conductors causes a force upon the rotor conductors ending them to
turn in the direction of flux.
-
7/30/2019 Exp. 3_ Load Test and Equivalent Circuit Determination on Three Phase Squirrel Cage Induction Motor and (1)
2/9
Torque is produced only when the speed of the rotor is less than N s. When the rotor is loaded
the speeds falls causing an increase in relative motion between stator and rotor conductors,
rotor current and hence the torque in order to cope with the increased load.
With the circuit model developed for the induction motor, the parameters of the circuit can be
obtained from no load and blocked rotor tests. When the machine is run on no load, very little
torque is developed by it. The rotor Branch acts like an open circuit. The slip is near to zero
resulting in infinite impedance on the rotor branch.
When the Machine is prevented from rotating the slip is unity. The elements representing the
magnetising branch Rm and Xm are high impedances much larger than RT and XTR in series. Thus
the equivalent circuit under this condition, the magnetising branch is neglected.
The equivalent circuit under these conditions are shown below.
CIRCUIT DIAGRAM (LOAD TEST)
G
Variable
Power
Supply
A
A
V
V_
Control
1 Supply
Sensors
T & S
Display
T/I
MCB 16 A
L
O
A
DInduction
Motor
R
YB
V
A M L
C V
M L
C V
W1
W23,4
15VAC,
50Hz
R
Y
B
NO LOAD AND BLOCKED ROTOR TEST
Induction
Motor
R
Y B
3PhasePowerSupply
A
V
R
Y
B
B
Y
R3
Auto
Xmer
W1
W2
No
Load or
Blocked
-
7/30/2019 Exp. 3_ Load Test and Equivalent Circuit Determination on Three Phase Squirrel Cage Induction Motor and (1)
3/9
PROCEDURE (LOAD TEST)
1. The Induction Machine is selected and configured as Motor running directly on theIncoming Supply.
2. The DC machine is configured as Generator and the field is kept at minimum initially. TheLoad is not connected to the DC output of the Generator. The DC machine is the load for the
Induction Motor.
3. The Induction Motor is started and brought to rated rpm.4. The DC Machine field is gradually increased till the output voltage reaches the rated voltage
of the Generator.
5. The input supply current, voltage, power and Power factor of the Induction Machine can bemeasured using the required meters.. Also the output of the IM parameters namely the
speed and the Torque are also noted from the Monitoring Panel of the DC machine. The first
set of readings when the Generator is on no load is recorded.
6. The Load on the DC generator is added gradually and the corresponding readings arerecorded for each load step.
7. The above step is repeated till the IM current reaches the rated value.8. Remove the load completely and bring down the DC machine field to minimum.9. Switch off the Induction motor and the main supply.
TABULATION:
Sr.
No.
Supply
Voltage
VL
(Volt)
Line
Current
IL
(Amp.)
Speed
N
(RPM)
I/P
Power
(Watt)
Torque
T
(NM)
O/P
(Watt)
Effici-
ency
(%)
Slip
S
(%)
Power
Factor
(Cos)1 377.22 1.25 1493 356.43 1.1 without excitan .28
2 377.46 1.22 1490 445.47 1.7 Excitation without load .31
3 379.55 1.42 1483 812.25 3.5 539.81 66.45 1.1 .50
4 382.81 1.61 1475 1169.4 5.2 797.68 68.21 1.7 .62
5 381.48 1.83 1469 1497.3 6.9 1054.15 70.40 2.1 .71
6 380.90 2.05 1462 1776.3 8.6 1307.61 73.61 2.5 .77
7 381.72 2.28 1454 2070.5 10.2 1542.40 74.49 3.06 .80
8 379.72 2.46 1447 2308.2 11.7 1760.70 76.28 3.53 .83
-
7/30/2019 Exp. 3_ Load Test and Equivalent Circuit Determination on Three Phase Squirrel Cage Induction Motor and (1)
4/9
CALCULATION
Input to motor : W Watt
Motor output :
% Efficiency :
100% Slip :
Where, Ns = synchronous speed,
N= actual speed
Power factor, cos : MODEL GRAPHS:
T
N
0 Output
pf
0 % Slip
TNm
Observed graph:
1.
0
2
4
6
8
10
12
14
0 250 500 750 1000 1250 1500 1750 2000
Torque
Output Power
Torque v/s Output Power
-
7/30/2019 Exp. 3_ Load Test and Equivalent Circuit Determination on Three Phase Squirrel Cage Induction Motor and (1)
5/9
2.
3.
4.
1445
1450
1455
1460
1465
1470
1475
1480
1485
0 250 500 750 1000 1250 1500 1750 2000
Speend
Output Power
Speed v/s output power
64
66
68
70
72
74
76
78
0 250 500 750 1000 1250 1500 1750 2000
Efficiency
Output Power
Efficiency v/s Output Power
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0 250 500 750 1000 1250 1500 1750 2000
PowerFactor
Output Power
Power Factor v/s Output Power
-
7/30/2019 Exp. 3_ Load Test and Equivalent Circuit Determination on Three Phase Squirrel Cage Induction Motor and (1)
6/9
PROCEDURE( Equivalent Circuit Determination)
NO LOAD TEST
1. The Rotary Bench is configured for the Induction Motor operation. The Motor shaft isdelinked from the DC machine.
2. Using the DOL starter mode the machine is started and made to run under no load.3. The applied voltage, the no load current and the No load power are noted down.BLOCKED ROTOR TEST:
1. Rotary Bench is configured for the Induction Motor operation thro external supply source.2. The external supply source with fed with a Variable 3 phase AC supply ( using an
Autotransformer)
3. The rotor is held/Blocked. The 3 ph voltages to the motor is gradually applied keeping awatch on the stator current. Once the rated current is reached, (with the rotor in blocked
condition) the voltage, current and the power readings are noted. The Voltage to the
machine is brought to zero and the power is switched off.
TABULATION:
No load test:
Sr. No. Volt IO Amp 3 Phase Power Power factor
1 414.26 1,57 278.1 W .137(82.3)
Blocked rotor test:
Sr.
No.
VS Volts IS Amps. WS = Total system
power in Watts
Power factor
1 71.6 2.4 310.5 .59
CALCULATION OF EQUIVALENT CIRCUIT PARAMETERS
In no load the current drawn is primarily by the magnetising branch and the power consumed
by the core loss is too high compared to the loss in the stator resistance. The stator cu loss is
neglected and the input power is consumed at the Rm in meeting the core loss. Hence f or the
data of Input voltage, current and the Power the following circuit parameters are calculated,
Let the applied voltage = Vs Then the current drawn is given by
Is =
+
-------------- (1)
-------------- (2)
From these equations the Rm and Xm are calculated.
-
7/30/2019 Exp. 3_ Load Test and Equivalent Circuit Determination on Three Phase Squirrel Cage Induction Motor and (1)
7/9
In blocked rotor test the rotor is prevented from running and hence the slip of the operation is
unity. Since the current drawn is decided by the resistance and leakage reactance alone, the
measured power is entirely consumed in the stator resistance plus the equivalent resistance of
rotor referred to the stator.
Using the equivalent circuit of this test, the resistive and the reactive component of the stator
and the equivalent rotor component referred to stator can be evaluated as shown below,
------------- (1)
------------- (2) ------------- (3)Assume,
The Stator resistance is measured using a voltmeter and ammeter method employing a
variable DC source. The Equivalent circuit thus determined is shown below.
EQUIVALENT CIRCUIT:
Rs Xls R/s Xlr
XmRm
Rr (1-s)/s
PERFORMANCE CHARACTERISTICS EVALUATION
From the equivalent circuit many aspects of the steady state behaviour of the machine can be
deduced. The most important of all is the speed Torque characteristics of the machine.
-
7/30/2019 Exp. 3_ Load Test and Equivalent Circuit Determination on Three Phase Squirrel Cage Induction Motor and (1)
8/9
In order to estimate the speed torque characteristics let us suppose that a Sinusoidal voltage
is impressed on the machine.
The Current drawn by the circuit is,
Neglecting the magnetising current the air gap power is given by
The mechanical power output P given by (1-s) Pg. The Torque is obtained by the relation,
Overall Torque,
The Torque may be plotted as function of s and t Called Torque Slip characteristics.
0
2
4
6
8
10
12
14
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8
Torque
% slip
Torque v/s % Slip
-
7/30/2019 Exp. 3_ Load Test and Equivalent Circuit Determination on Three Phase Squirrel Cage Induction Motor and (1)
9/9
RESULT AND INFERENCE:
1. The observed curve for efficiency, speed, torque, and power factor v/s output (load)current is found to be similar to the model curve, the curve is not complete as we have
worked out few readings only.
2. The performance characteristic curve of the motor i.e. torque-slip curve is also foundmatching with the model graph given.
3. By calculating equivalent circuit parameters, we now know,Rm=617.08
Xm=462.9
Rs=Rr=26.95
Xs=Sr=22.44
4.