EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor...

15
MECHANICAL/ELECTRICAL ENGINEER: ARCHITECTURAL ENGINEERING CONSULTANTS 40801 US HIGHWAY 6 & 24, SUITE 214 EAGLE-VAIL, CO 81620 P.O. BOX 8489 AVON, CO 81620 Tel. 970 748-8520 Fax 970 748-8521 MECHANICAL CONTACT - DAVID DENIO E-mail: [email protected] ELECTRICAL CONTACT - CHUCK LANGSTON E-mail: [email protected] EAGLE COUNTY REGIONAL AIRPORT Administration Office Remodel 219 ELDON WILSON ROAD, GYPSUM INDEX TO DRAWINGS PROJECT DESCRIPTION PROJECT TEAM CODE ANALYSIS OCCUPANCY MAX. ALLOWABLE HEIGHT 65'-0" CONSTRUCTION TYPE FIRE SPRINKLERS ± 6,540' ABOVE SEA LEVEL SITE ELEVATION ZONE DISTRICT EAGLE COUNTY REGIONAL AIRPORT PUD NO. OF STORIES TWO VICINITY MAP OWNER: EAGLE COUNTY P.O. BOX 850 EAGLE, CO 81631-0850 ARCHITECT: MENENDEZ ARCHITECTS, P.C. 715 W.MAIN ST., SUITE 104 ASPEN, CO 81611 Tel. 970 544-4851 Fax 970 544-1915 E-mail: [email protected] CONTACT: LUIS MENENDEZ A-1 A-2 A-3 A-4 A-5 A-6 S1.1 S2.1 S3.1 M1.0 M2.0 E1.0 E1.1 E2.0 E3.0 TITLE SHEET EXISTING & PROPOSED FLOOR PLANS EXISTING RC PLAN & PROPOSED RC PLAN WALL SECTION, DETAILS ASSEMBLIES, DETAILS SCHEDULES, INTERIOR ELEVATIONS GENERAL NOTES, SHEET INDEX, KEYPLAN AND LEGEND PARTIAL ROOF AND FLOOR FRAMING PLAN FRAMING AND FOUNDATION DETAILS SPECS, SCHEDULES & SEQUENCE HVAC PLAN ELECTRICAL LEGEND, SPECS, AND DETAILS ELECTRICAL ONE-LINE & PANEL SCHEDULES POWER & SYSTEMS PLAN LIGHTING AND RCP PLAN SETBACKS 50' FROM COOLEY MESA ROAD, F.A.A. REGULATIONS FROM CENTER-LINE OF RUNWAY ALL WORK SHALL BE EXECUTED IN CONFORMANCE WITH THE 2003 INTERNATIONAL BUILDING CODE AND WITH ALL OTHER RULES, REGULATIONS AND ORDINANCES GOVERNING THE PLACE OF BUILDING. CONTRACTOR SHALL BRING TO THE ATTENTION OF THE ARCHITECT ANY CONFLICTS BETWEEN THE REQUIREMENTS OF THE BUILDING CODE AND THE DRAWINGS. ALL WORK SHALL BE PERFORMED TO THE HIGHEST STANDARDS OF CRAFTSMANSHIP BY JOURNEYMEN OF THE APPROPRIATE TRADES. ALL DIMENSIONS NOTED TAKE PRECEDENCE OVER SCALE. DIMENSIONS NOTED WITH "N.T.S." DENOTES NOT TO SCALE. CONTRACTOR IS HEREBY NOTIFIED ASSUMPTIONS HAVE BEEN MADE ABOUT THE CONSTRUCTION METHODS, SYSTEMS AND MATERIALS ORIGINALLY USED IN THE BUIILDING. THE CONTRACTOR, IN THE COURSE OF PERFORMING INVASIVE TESTING DURING CONSTRUCTION, SHALL VERIFY THE ACCURACY OF THE ASSUMPTIONS AND NOTIFY THE ARCHITECT OF ANY DISCREPANCIES. CONTRACTOR SHALL VERIFY THE DIMENSIONS AND CONDITIONS OF ALL AFFECTED AREAS OF EXISTING STRUCTURE/SITE AND SHALL REPORT TO THE ARCHITECT, IN WRITING, ANY DISCREPANCIES BETWEEN ACTUAL EXISTING CONDITIONS AND THE DRAWINGS. CONTRACTOR SHALL TAKE REASONABLE MEASURES TO LOCATE AND MARK ALL UNDERGROUND UTILITIES IN AREAS SUBJECT TO EXCAVATION, TRENCHING OR BORING PRIOR TO COMMENCING WORK. ARCHITECT IS NOT RESPONSIBLE IN ANY WAY FOR THE MEANS, METHODS, SEQUENCE, PROCEDURES, TECHNIQUES OR SCHEDULING OF CONSTRUCTION OR FOR JOB SAFETY. THESE DUTIES ARE THE RESPONSIBILITY OF THE CONTRACTOR. ALL BUILDING COMPONENTS SHALL BE INSTALLED PER MANUFACTURER'S RECOMMENDATIONS. CONTRACTOR SHALL iNSTRUCT EACH OF THE SUBCONTRACTORS TO BECOME THOROUGHLY FAMILIAR WITH ALL OF THE DRAWINGS. WHEREVER EXISTING CONDITIONS MAY HAVE A BEARING ON THE EXPEDITIOUS PERFORMANCE OF THE WORK, THE SUBCONTRACTOR SHALL VISIT THE JOB SITE AND PERSONALLY INSPECT AND VERIFY THE SITE FOR COMPARISON WITH THE DRAWINGS. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, FOR ARCHITECT APPROVAL, FOR THE FOLLOWING ITEMS PRIOR TO PERFORMANCE OF THE WORK: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. GENERAL NOTES STRUCTURAL ENGINEER: GLENWOOD STRUCTURAL AND CIVIL, INC. 812 PITKIN AVENUE GLENWOOD SPRINGS, CO 81601 Tel. 970 928-0135 Fax 970 928-9804 E-mail: [email protected] CONTACT: ADOLFO GORRA OWNER'S REPRESENTATIVE: EAGLE COUNTY PROJECT MANAGEMENT DEPARTMENT P.O. BOX 850 590 BROADWAY EAGLE, CO 81631-0850 Tel. 970 328-8780 E-mail: [email protected] CONTACT: MR. RICK ULLOM AUTOMATIC FIRE SPRINKLER SYSTEM NOTES INTERIOR REMODEL OF EXISTING AIRPORT ADMINISTRATION OFFICES. 1. 1 2 3 4 5 6 7 8 9 10 11 REMOVE DESIGNATED PARTITIONS, COMPONENTS, BUILDING EQUIPMENT AND FIXTURES. CONFORM TO ALL APPLICABLE CODES RELATING TO DEMOLITION AND HAZARDOUS MATERIALS. ERECT AND MAINTAIN TEMPORARY BARRIERS AND SECURITY DEVICES. ERECT AND MAINAIN TEMPORARY PARTITIONS TO PREVENT SPREAD OF DUST. PREVENT MOVEMENT OF STRUCTURE. PROVIDE BRACING AND SHORING AND DESIGN OF SAME BY QUALIFIED PROFESSIONAL. PROTECT EXISTING STRUCTURE, FINISHES, EQUIPMENT, ETC. WHICH ARE NOT TO BE DEMOLISHED. DEMOLISH AND REMOVE COMPONENTS IN AN ORDERLY AND CAREFUL MANNER. DISCONNECT AND CAP/ABANDON UTILITIES AS NECESSARY. REMOVE DEMOLISHED MATERIALS FROM SITE AS WORK PROGRESSES AND DISPOSE IN AN APPROVED AND LEGAL MANNER. LEAVE AREAS OF WORK IN CLEAN CONDITION. MAINTAIN EGRESS AND ACCESS AT ALL TIMES. DEMOLITION NOTES BUILDING IS FIRE SPRINKLERED; MODIFY SYSTEM IN SUBJECT SPACES, PER CODE REQUIREMENTS, FOR NEW LAYOUT. SEE ADDITIONAL NOTES AT LEFT MODIFY EXISTING FIRE SPRINKLER SYSTEM TO SERVE THE PROPOSED IMPROVEMENTS TO MEET CURRENT CODE REQUIREMENTS. FIRE SPRINKLER IMPROVEMENTS SHALL BE DESIGN/BUILD BY CONTRACTOR WITH QUALIFIED SUBCONTRACTOR. SUBMIT DESIGN/DRAWINGS TO BUILDING AND FIRE DEPARTMENTS FOR APPROVAL. 1 2 SECOND FLOOR IS ALL OFFICE SPACE - B OCCUPANCY FIRST FLOOR IS COMBINATION OF VEHICLE STORAGE - S-2 OCCUPANCY AND OFFICE SPACE - B OCCUPANCY III-B BETWEEN NEW SECOND FLOOR OFFICE AND FIRST FLOOR STORAGE - 2 HOURS, REDUCED TO 1-HOUR FOR FIRE SPRINKLERS SEPARATION REQUIREMENT SITE Sheet number: Sheet title: Project: Print Date: Drawn By: Issue: Date: Revision: Date: BID SET 07/02/15 MT EAGLE COUNTY AIRPORT ADMINISTRATION OFFICE REMODEL A-1 TITLE SHEET 7/6/15 715 W. Main Street, Suite 104 Aspen, Colorado 81611 voice: 970.544.4851 email: [email protected]

Transcript of EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor...

Page 1: EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor framing plan framing and foundation details specs, schedules & sequence hvac plan

MECHANICAL/ELECTRICAL ENGINEER:

ARCHITECTURAL ENGINEERING CONSULTANTS

40801 US HIGHWAY 6 & 24, SUITE 214

EAGLE-VAIL, CO 81620

P.O. BOX 8489

AVON, CO 81620

Tel. 970 748-8520 Fax 970 748-8521

MECHANICAL CONTACT - DAVID DENIO

E-mail: [email protected]

ELECTRICAL CONTACT - CHUCK LANGSTON

E-mail: [email protected]

EAGLE COUNTY REGIONAL AIRPORT Administration Office Remodel

219 ELDON WILSON ROAD, GYPSUM

INDEX TO DRAWINGS

PROJECT DESCRIPTION PROJECT TEAM CODE ANALYSIS

OCCUPANCY

MAX. ALLOWABLE HEIGHT 65'-0"

CONSTRUCTION TYPE

FIRE SPRINKLERS

± 6,540' ABOVE SEA LEVELSITE ELEVATION

ZONE DISTRICT EAGLE COUNTY REGIONAL AIRPORT PUD

NO. OF STORIES TWO

VICINITY MAP

OWNER:

EAGLE COUNTY

P.O. BOX 850

EAGLE, CO 81631-0850

ARCHITECT:

MENENDEZ ARCHITECTS, P.C.

715 W.MAIN ST., SUITE 104

ASPEN, CO 81611

Tel. 970 544-4851 Fax 970 544-1915

E-mail: [email protected]

CONTACT: LUIS MENENDEZ

A-1

A-2

A-3

A-4

A-5

A-6

S1.1

S2.1

S3.1

M1.0

M2.0

E1.0

E1.1

E2.0

E3.0

TITLE SHEET

EXISTING & PROPOSED FLOOR PLANS

EXISTING RC PLAN & PROPOSED RC

PLAN

WALL SECTION, DETAILS

ASSEMBLIES, DETAILS

SCHEDULES, INTERIOR ELEVATIONS

GENERAL NOTES, SHEET INDEX,

KEYPLAN AND LEGEND

PARTIAL ROOF AND FLOOR FRAMING

PLAN

FRAMING AND FOUNDATION DETAILS

SPECS, SCHEDULES & SEQUENCE

HVAC PLAN

ELECTRICAL LEGEND, SPECS, AND

DETAILS

ELECTRICAL ONE-LINE & PANEL

SCHEDULES

POWER & SYSTEMS PLAN

LIGHTING AND RCP PLAN

SETBACKS 50' FROM COOLEY MESA ROAD,

F.A.A. REGULATIONS FROM CENTER-LINE OF RUNWAY

ALL WORK SHALL BE EXECUTED IN CONFORMANCE WITH THE 2003 INTERNATIONAL BUILDING CODE AND WITH ALL OTHER RULES,

REGULATIONS AND ORDINANCES GOVERNING THE PLACE OF BUILDING. CONTRACTOR SHALL BRING TO THE ATTENTION OF THE ARCHITECT

ANY CONFLICTS BETWEEN THE REQUIREMENTS OF THE BUILDING CODE AND THE DRAWINGS.

ALL WORK SHALL BE PERFORMED TO THE HIGHEST STANDARDS OF CRAFTSMANSHIP BY JOURNEYMEN OF THE APPROPRIATE TRADES.

ALL DIMENSIONS NOTED TAKE PRECEDENCE OVER SCALE. DIMENSIONS NOTED WITH "N.T.S." DENOTES NOT TO SCALE.

CONTRACTOR IS HEREBY NOTIFIED ASSUMPTIONS HAVE BEEN MADE ABOUT THE CONSTRUCTION METHODS, SYSTEMS AND MATERIALS

ORIGINALLY USED IN THE BUIILDING. THE CONTRACTOR, IN THE COURSE OF PERFORMING INVASIVE TESTING DURING CONSTRUCTION, SHALL

VERIFY THE ACCURACY OF THE ASSUMPTIONS AND NOTIFY THE ARCHITECT OF ANY DISCREPANCIES.

CONTRACTOR SHALL VERIFY THE DIMENSIONS AND CONDITIONS OF ALL AFFECTED AREAS OF EXISTING STRUCTURE/SITE AND SHALL

REPORT TO THE ARCHITECT, IN WRITING, ANY DISCREPANCIES BETWEEN ACTUAL EXISTING CONDITIONS AND THE DRAWINGS.

CONTRACTOR SHALL TAKE REASONABLE MEASURES TO LOCATE AND MARK ALL UNDERGROUND UTILITIES IN AREAS SUBJECT TO

EXCAVATION, TRENCHING OR BORING PRIOR TO COMMENCING WORK.

ARCHITECT IS NOT RESPONSIBLE IN ANY WAY FOR THE MEANS, METHODS, SEQUENCE, PROCEDURES, TECHNIQUES OR SCHEDULING OF

CONSTRUCTION OR FOR JOB SAFETY. THESE DUTIES ARE THE RESPONSIBILITY OF THE CONTRACTOR.

ALL BUILDING COMPONENTS SHALL BE INSTALLED PER MANUFACTURER'S RECOMMENDATIONS.

CONTRACTOR SHALL iNSTRUCT EACH OF THE SUBCONTRACTORS TO BECOME THOROUGHLY FAMILIAR WITH ALL OF THE DRAWINGS.

WHEREVER EXISTING CONDITIONS MAY HAVE A BEARING ON THE EXPEDITIOUS PERFORMANCE OF THE WORK, THE SUBCONTRACTOR SHALL

VISIT THE JOB SITE AND PERSONALLY INSPECT AND VERIFY THE SITE FOR COMPARISON WITH THE DRAWINGS.

CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, FOR ARCHITECT APPROVAL, FOR THE FOLLOWING ITEMS PRIOR TO PERFORMANCE OF THE

WORK:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

GENERAL NOTES

STRUCTURAL ENGINEER:

GLENWOOD STRUCTURAL AND CIVIL, INC.

812 PITKIN AVENUE

GLENWOOD SPRINGS, CO 81601

Tel. 970 928-0135 Fax 970 928-9804

E-mail: [email protected]

CONTACT: ADOLFO GORRA

OWNER'S REPRESENTATIVE:

EAGLE COUNTY

PROJECT MANAGEMENT DEPARTMENT

P.O. BOX 850

590 BROADWAY

EAGLE, CO 81631-0850

Tel. 970 328-8780

E-mail: [email protected]

CONTACT: MR. RICK ULLOM

AUTOMATIC FIRE SPRINKLER SYSTEM NOTES

INTERIOR REMODEL OF EXISTING AIRPORT ADMINISTRATION OFFICES.

1.

1

2

3

4

5

6

7

8

9

10

11

REMOVE DESIGNATED PARTITIONS, COMPONENTS, BUILDING EQUIPMENT

AND FIXTURES.

CONFORM TO ALL APPLICABLE CODES RELATING TO DEMOLITION AND

HAZARDOUS MATERIALS.

ERECT AND MAINTAIN TEMPORARY BARRIERS AND SECURITY DEVICES.

ERECT AND MAINAIN TEMPORARY PARTITIONS TO PREVENT SPREAD OF

DUST.

PREVENT MOVEMENT OF STRUCTURE. PROVIDE BRACING AND SHORING

AND DESIGN OF SAME BY QUALIFIED PROFESSIONAL.

PROTECT EXISTING STRUCTURE, FINISHES, EQUIPMENT, ETC. WHICH ARE

NOT TO BE DEMOLISHED.

DEMOLISH AND REMOVE COMPONENTS IN AN ORDERLY AND CAREFUL

MANNER.

DISCONNECT AND CAP/ABANDON UTILITIES AS NECESSARY.

REMOVE DEMOLISHED MATERIALS FROM SITE AS WORK PROGRESSES

AND DISPOSE IN AN APPROVED AND LEGAL MANNER.

LEAVE AREAS OF WORK IN CLEAN CONDITION.

MAINTAIN EGRESS AND ACCESS AT ALL TIMES.

DEMOLITION NOTES

BUILDING IS FIRE SPRINKLERED; MODIFY SYSTEM IN SUBJECT SPACES, PER CODE REQUIREMENTS, FOR NEW LAYOUT. SEE ADDITIONAL NOTES AT LEFT

MODIFY EXISTING FIRE SPRINKLER SYSTEM TO SERVE THE PROPOSED IMPROVEMENTS TO MEET CURRENT CODE REQUIREMENTS.

FIRE SPRINKLER IMPROVEMENTS SHALL BE DESIGN/BUILD BY CONTRACTOR WITH QUALIFIED SUBCONTRACTOR. SUBMIT

DESIGN/DRAWINGS TO BUILDING AND FIRE DEPARTMENTS FOR APPROVAL.

1

2

SECOND FLOOR IS ALL OFFICE SPACE - B OCCUPANCY

FIRST FLOOR IS COMBINATION OF VEHICLE STORAGE -

S-2 OCCUPANCY AND OFFICE SPACE - B OCCUPANCY

III-B

BETWEEN NEW SECOND FLOOR OFFICE AND

FIRST FLOOR STORAGE - 2 HOURS, REDUCED TO

1-HOUR FOR FIRE SPRINKLERS

SEPARATION REQUIREMENT

SITE

Sheet number:

Sheet title:

Project:

Print Date:

Drawn By:

Issue: Date: Revision: Date:

BID SET 07/02/15

MT

EAGLE COUNTY AIRPORT

ADMINISTRATION OFFICE

REMODEL

A-1

TITLE SHEET

7/6/15

715 W. Main Street, Suite 104 Aspen, Colorado 81611voice: 970.544.4851 email: [email protected]

Page 2: EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor framing plan framing and foundation details specs, schedules & sequence hvac plan

12

3

4

5

8

7

9

W5

W2

W1

W5

W5

W5

W5

W1

W3

W4

W4

1

A-4

1

A-4

6A-6

1N

2EA-6

W1

A-6

1N

3EA-6

2N

A-6

W1

6'-0"

± 15'-4

3/8

"3 5

/8"

3'-10

"3 5

/8"

3 5

/8"

18'-1 7/8

"3 5

/8"

1'-9

"3 5

/8"

3'-1 1/2" 3 5/8"

12'-1 1/2" 3 5/8"

EQ. (±9'-6 1/4") 3 5/8" EQ. (± 9'-6 1/4" ) 9'-9 3/4"3 5/8"

3'-6

"3 5

/8"

± 6

'-8

5/8

"

FROM EXISTING

PARTITION

3 5/8"

ALIGN

A

1

2

3

5

1

4

5

B D

A DC

A

1

2

3

5

1

4

5

B D

A DC

2'-0

"

EXIS

TIN

G

CM

U R

.O.

6'-8"

2'-0

"

± 6

'-4

5/8

"

(R.O

.)

10"± 8'-4 1/4" R.O.4"

6"5'-8"6"

1 1/

2"

MASONRY R.O. 6'-8"

± 1 1/2"

4" ± 9'-1 1/8" R.O. 4"

ALIGN F.O.S. WITH FACE

OF MASONRY OPENING

± 2'-5 3/4"

(R.O.)

4"

EXISTING PARTITION TO REMAIN

EXISTING PARTITION TO BE REMOVED

PROPOSED PARTITION, ALL NEW PARTITIONS

SHALL EXTEND 6" ABOVE SUSPENDED CLG.

TYPICAL NON-STRUCTURAL STEEL STUD

SHALL BE 362S125-30

WALL TYPE LEGEND

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

FINISH ENDS OF CMU WALL WITH DRYWALL TO

MATCH ADJOINING SURFACES.

FRAME-IN EXISTING OPENING. FINISH TO MATCH

ADJOINING SURFACES.

FINISH AND PATCH AREAS OF NEW WORK

(WALLS, FLOOR AND CEILING) TO BLEND

SEAMLESSLY WITH EXISTING CONSTRUCTION,

TYPICAL.

EXISTING STOREFRONT PARTITION TO REMAIN.

NEW STOREFRONT PARTITION TO MATCH EXISTING

IN MANUFACTURER (KAWNEER), STYLE/MODEL

AND FINISH.

CHANGE IN FLOORING MATERIAL.

INSULATE ALL NEW PARTITIONS AND FRAMED-IN

OPENINGS FOR SOUND WITH FIBER BATT

INSULATION, FULL DEPTH OF STUD CAVITY, AND

SEAL PERIMETER WITH ACOUSTICAL SEALANT,

TYPICAL.

EXISTING DOOR TO REMAIN, ALL DOORS WITH A

DOOR SYMBOL INDICATE NEW DOOR, SEE DOOR

SCHEDULE.

DASHED LINE INDICATES EXISTING ROOF

OVERHANG ABOVE.

DASHED RECTANGLE INDICATES OBSERVATION

DECK SHAFT OPENING ABOVE.

EXISTING LADDER TO REMAIN.

FIX EXISTING GARAGE DOOR IN PLACE AND SEAL.

REMOVE SECTION OF TRACK AND OPERATOR

THAT CONFLICTS WITH NEW CONSTRUCTION.

RESILIENT CHANNEL ON THIS SIDE OF WALL, SEE

WALL ASSEMBLIES.

NEW 3/4" STEEL FURRING WITH DRYWALL FINISH

OVER EXISTING CMU WALL. WEST AND NORTH

WALLS OF CHASE.

NEW 18" DEEP FIXED, BUILT-IN PAINT-GRADE

SHELVING.

NEW STEEL COLUMN AND BEAM ABOVE, SEE

STRUCTURAL

KEYNOTES

PROPOSED SECOND FLOOR PLANSCALE: 1/4" = 1'-0"4

DN.

EXISTING/DEMO SECOND FLOOR PLANSCALE: 1/4" = 1'-0"3

DECK

KITCHENETTE

CHASE

STORAGE

AVIATION DIRECTOR

CONFERENCE

ROOM

STAIR 2

PROJECT

COORDINATOR

ADMIN. ASST.

BADGING

ADMIN. MGR.ASST. AVIATION

DIRECTOR

RECEPTION

MEN'S

TOILET ROOM

WOMEN'S

TOILET ROOM

STAIR 1

ELECTRICAL

ROOM

OPEN TO BELOW

DN.

DECK

CONFERENCE

ROOM

BADGING

ELECTRICAL

ROOM

KITCHENETTE

STORAGE

STAIR 2

ASST. AVIATION

DIRECTOR

ADMIN. MGR.

AVIATION

DIRECTOR

RECEPTION

MARKETING

ADMIN. ASST.

STORAGE

ROOM

MEN'S

TOILET ROOM

WOMEN'S

TOILET ROOM

STAIR 1

OPEN TO BELOW

OPERATIONS

MANAGER

CHASE

REMOVE ALL COMPONENTS/FIXTURES SHOWN

DASHED, TYPICAL.

REMOVE EXISTING DOOR AND FRAME.

REMOVE EXISTING CARPET THROUGHOUT SECOND

FLOOR.

GARAGE DOOR TO REMAIN BUT TRIM TRACK TO

ALLOW FOR NEW CONSTRUCTION. FIX GARAGE

DOOR IN PLACE.

REMOVE AND RELOCATE EXISTING MECHANICAL

EQUIPMENT PER MECHANICAL PLANS.

EXISTING DUCT TO REMAIN, SEE MECHANICAL.

REMOVE UPPER CABINETS ALONG NORTH WALL.

REMOVE EXISTING WOOD BASE IN AREAS OF

NEW WORK.

REMOVE PORTION OF EXISTING RESILIENT

FLOORING AT STAIR 2 THAT WILL BECOME

HALLWAY.

REMOVE EXISTING STOREFRONT AND REUSE TO

NEW SIZE IF IN GOOD CONDITION.

REMOVE EXISTING ROOF INSULATION ON THIS

AREA AND REPLACE WITH NEW ROOF INSULATION

D1

D2

D3

D4

D5

D6

D7

D8

D9

D10

D11

DEMOLITION KEYNOTES

PROPOSED PARTIAL FIRST FLOOR PLANSCALE: 1/4" = 1'-0"2

EXISTING/DEMO PARTIAL FIRST FLOOR PLANSCALE: 1/4" = 1'-0"1

STORAGE STORAGE

HALLWAY

PROJECT

COORDINATOR

DN. DN.

EXISTING CMU PARTITION TO REMAIN

14

14

D1

D1

D2

D2 D2

D3

D3

D3

D4

D5

D6

D6

D7

2

1

3

3

3

3

4

5

5

5

6

7

7

7

7

7

7

9

9

10

11

12

13

13

13

13

13

8

8

8

8

OPEN OFFICE

CLOSET

D9

D10

OPEN OFFICE

D11

15

16

1

5/8" FROM EDGE

OF LANDING

Sheet number:

Sheet title:

Project:

Print Date:

Drawn By:

Issue: Date: Revision: Date:

BID SET 07/02/15

LM & MT

EAGLE COUNTY AIRPORT

ADMINISTRATION OFFICE

REMODEL

A-2

EXISTING & PROPOSED

FLOOR PLANS

7/6/15

715 W. Main Street, Suite 104 Aspen, Colorado 81611voice: 970.544.4851 email: [email protected]

Page 3: EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor framing plan framing and foundation details specs, schedules & sequence hvac plan

1

A-4

EQ. EQ. EQ. EQ.

A

1

2

3

5

1

4

5

B D

A DC

A

1

2

3

5

1

4

5

B D

A DC

EQ

.EQ

.

PROPOSED SECOND FLOOR REFLECTED CEILING PLANSCALE: 1/4" = 1'-0"2

CONFERENCE

ROOM

BADGING

KITCHENETTE

STORAGE

ASST. AVIATION

DIRECTOR

ADMIN.

MGR.

AVIATION

DIRECTOR

RECEPTION

STORAGE

STAIR 1

EXISTING SECOND FLOOR REFLECTED CEILING PLANSCALE: 1/4" = 1'-0"1

OPEN TO BELOW

KITCHENETTE

CHASE

STORAGE

AVIATION

DIRECTOR

CONFERENCE

ROOM

STAIR 2

RECEPTION

MEN'S

TOILET ROOM

WOMEN'S

TOILET ROOM

STAIR 1

ELEC. RM.

MEN'S

TOILET ROOM

WOMEN'S

TOILET ROOM

ELEC. RM.

STAIR 2

CHASE

SYMBOLS LEGEND

EXISTING 2' x 4' FLUORESCENT LIGHT

FIXTURE TO BE REMOVED

EXISTING SUPPLY AIR DIFFUSER TO REMAIN

OR TO BE REMOVED AND REINSTALLED AT

SAME LOCATION, SEE MECHANICAL PLAN

EXISTING RETURN AIR DIFFUSER TO REMAIN

OR TO BE REMOVED AND REINSTALLED AT

SAME LOCATION, SEE MECHANICAL PLAN

EXISTING SMOKE DETECTOR TO REMAIN

RECESSED DOWNLIGHT, SEE ELECTRICAL

PLAN

NEW 2' x 4' TROFFER LIGHT FIXTURE, SEE

ELECTRICAL PLANS

PROPOSED RETURN AIR DIFFUSER, SEE

MECHANICAL PLAN

KEYNOTES

1

2

3

4

SECURE SUSPENSION SYSTEM/WIRE/ROD

HANGERS, ETC. FOR THE CEILING TILES OR

GYPSUM BOARD TO STRUCTURAL MEMBERS OR

FRAMING MEMBERS ONLY. NEVER ATTACH THE

SUSPENDED STEEL FRAMING TO THE ROOF

DECKS OR TO THE DUCTS, PIPES AND CONDUITS.

INSTALL EDGE MOLDING AND TRIM AT PERIMETER

OF ACOUOSTICAL CEILING WHERE NECESSARY

TO CONCEAL EDGES OF ACOUSTICAL CEILING

TILES.

APPLY ACOUSTICAL SEALANT IN A CONTNUOUS

RIBBON FORM WHERE CEILING MEETS THE

VERTICAL WALLS.

LOCATE ELECTRICAL DEVICES, LIFE SAFETY

DEVICES AND THE SPRINKLER HEAD AT THE

CENTER OF THE ACOUSTICAL CELING TILES,

UNLESS OTHERWISE NOTED.

ACOUSTICAL CEILING

CRITERIA

1

2

3

4

5

6

7

8

TO FACILITATE INSTALLATION OF NEW

MECHANICAL SYSTEM REMOVE AND REPLACE

EXISTING SUSPENDED ACOUSTICAL BOARD AND

GRID CEILING THROUGHOUT SECOND FLOOR

EXCEPT AT STAIR AND ELECTRICAL ROOM.

NEW DRYWALL SOFFIT, SEE WALL SECTION.

NEW DRYWALL CEILING, SEE WALL SECTION.

EXISTING DRYWALL CEILING TO REMAIN.

EXISTING SUSPENDED ACOUSTICAL BOARD AND

GRID CEILING TO REMAIN. REPLACE ALL DAMAGED

OR MISSING TILES.

EXISTING EXIT SIGN TO BE REMOVED AND

REPLACED, SEE ELECTRICAL PLAN, TYPICAL.

EXISTING ELECTRICAL DEVICE, REMOVE AND

REINSTALL IF ACTIVE. FOR BIDDING PURPOSES,

ASSUME ALL DEVICES ARE ACTIVE. PRIOR TO

RE-INSTALLATION CONFIRM WITH OWNER IF

DEVICE IS NEEDED. PROVIDE CREDIT FOR ANY

DEVICES NOT REINSTALLED. TYPICAL.

NEW SUSPENDED ACOUSTICAL BOARD AND GRID

CEILING, TYPICAL.

E

N

NPROPOSED SUPPLY AIR DIFFUSER, SEE

MECHANICAL PLAN

S

APPROXIMATE LOCATION OF EXISTING FIRE

SPRINKLER HEAD, MODIFY EXISTING

SYSTEM TO NEW FLOOR PLAN LAYOUT

AND CODE REQUIREMENTS AS

DESIGN-BUILD.

HALLWAY

PROJECT

COORDINATOR

OPERATIONS

MANAGER

MARKETING

ADMIN. ASST.

E

E

NEW SMOKE DETECTOR, SEE ELECTRICAL

PLAN

P

BADGING

PROJECT

COORDINATOR

ADMIN. ASST.

ASST. AVIATION

DIRECTOR

ADMIN. MGR.

EXISTING EXHAUST FAN TO REMAIN

8

8

8

8

8

8

6

6

7

7

7

supply

supply

supply

supply

return

s s

return

supply

s

exit

supply

supply

supply

return

supply

supply

exit

s

return

s

s

sp

sp

s

s

supply

supply

s

sp

E E E

E E E

E E E

E E E

E

E E

E

E E

EE

exit

s

return

s

s

supply

return

exit

supply

s

supply

supply

s s

s

s s

sp

R

N

return

return

N

supply

N

N

return

N

return

supply

N

supply

N

supply

N

N

return

1

1

2

3

4

4

4

5

5

Sheet number:

Sheet title:

Project:

Print Date:

Drawn By:

Issue: Date: Revision: Date:

BID SET 07/02/15

LM & MT

715 W. Main Street, Suite 104 Aspen, Colorado 81611voice: 970.544.4851 email: [email protected] fax: 970.544.1915

EAGLE COUNTY AIRPORT

ADMINISTRATION OFFICE

REMODEL

7/6/15

A-3

EXISTING RCP,

PROPOSED RCP

Page 4: EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor framing plan framing and foundation details specs, schedules & sequence hvac plan

± 8

'-0

" (M

ATC

H E

XIS

TIN

G)

6"

DIAGONAL BRACING TO

STRUCTURE ABOVE

7

A-4

NEW SUSPENDED ACOUSTICAL BOARD

AND GRID CEILING

NEW WALL FINISH MATERIAL, SEE

INTERIOR ROOM FINISH SCHEDULE,

TYPICAL

NEW STEEL STUDS AT 16" O.C.

NEW FIBER BATT INSULATION

NEW FLOOR FINISH MATERIAL, SEE

INTERIOR ROOM FINISH SCHEDULE

FLOOR SUBSTRATE (CONCRETE

OR WOOD)

RESILIENT CHANNELS AT 16" O.C.,

WHERE OCCURS

INSULATION

NOT SHOWN

INSULATION

NOT SHOWN

5/8" DRYWALL

HEADER

5/8" DRYWALL

HOLLOW METAL

DOOR FRAME

DOOR

HOLLOW METAL

DOOR FRAME

5/8" DRYWALL

DOOR

5/8" DRYWALL

INSULATION

NOT SHOWN

INSULATION

NOT SHOWN

5/8" DRYWALL

HEADER

5/8" DRYWALL

HOLLOW METAL

DOOR FRAME

DOOR

HOLLOW METAL

DOOR FRAME

5/8" DRYWALL

DOOR

5/8" DRYWALL

RESILIENT CHANNELS

AT 16" O.C.

RESILIENT CHANNELS

AT 16" O.C.

INSULATION

NOT SHOWN

5/8" DRYWALL

STEEL BASE TRACK

5/8" DRYWALL

RESILIENT CHANNELS

AT 16" O.C., WHERE

OCCURS

FLOOR SUBSTRATE (PLYWOOD OR

CONCRETE)

1/4

"

CONTINUOUS BEAD OF

ACOUSTICAL SEALANT,

BOTH SIDES OF WALL

FLOOR FINISH MATERIAL

BASE NOT SHOWN

1"1"

4SCALE: 3" = 1'-0"

INTERIOR DOOR HEAD

3SCALE: 3" = 1'-0"

INTERIOR DOOR JAMB

2SCALE: 3" = 1'-0"

INTERIOR DOOR HEAD

5SCALE: 3" = 1'-0"

INTERIOR DOOR JAMB

SCALE: 3" = 1'-0"7

TYPICAL WALL TO FLOOR

SCALE: 3" = 1'-0"8

DETAIL

SCALE: 3/4" = 1'-0"6

TYPICAL INTERIOR PARTITION

F1

ELEV. 100'-0"

T.O. CONC. SLAB

ELEV. ±111'-10"

(ALIGN WITH TOP OF

EXIST. CONCRETE)

T.O. SHEATHING

± 11'-

10"

ELEV. 120'-0"

JOIST BEARING

20

'-0

"

± 8

'-0

"

(MA

TC

H E

XIS

TIN

G)

(VER

IFY

)

6'-9

"

2'-0"

1"

SCALE: 1/2" = 1'-0"

WALL SECTION1

EXISTING ROOF TO REMAIN

METAL DECK TO REMAIN

EXISTING TRUSS TO REMAIN

EXISTING SOFFIT TO REMAIN

WALL FINISH TO REMAIN

EXISTING CMU WALL TO REMAIN

EXISTING STEEL BEAM TO REMAIN

EXISTING FAUX HEADER TO REMAIN

EXISTING GARAGE DOOR

TO REMAIN, FIX IN PLACE

NEW PLYWOOD FLOOR SHEATHING,

SEE STRUCTURAL

NEW SUSPENDED ACOUSTICAL BOARD

AND GRID CEILING

OPERATIONS MANAGER

OFFICENEW R-13 FIBER BATT INSULATION

NEW WALL FINISH MATERIAL, SEE

INTERIOR ROOM FINISH

SCHEDULE, TYPICAL

NEW FLOOR FINISH MATERIAL, SEE

INTERIOR ROOM FINISH SCHEDULE

NEW 5/8" DRYWALL

STORAGE

NEW PLYWOOD WEB JOIST, SEE

STRUCTURAL

NEW R-19 FIBER BATT INSULATION

ONE LAYER OF TYPE 'X'

DRYWALL

EXISTING CONCRETE SLAB ON

GRADE TO REMAIN

NEW 3 5/8" STEEL

JOISTS AT 16" O.C.

NEW 5/8" DRYWALL

NEW STEEL STUDS AT

16" O.C.

NEW 1 1/2" WALL FURRING AT 16" O.C.

REMOVE EXISTING ROOF INSULATION

AND REPLACE WITH NEW INSULATION

NEW UNFACED, FORMALDEHYDE FREE FIBER BATT INSULATION

FULL DEPTH OF STEEL BAR JOISTS AND THERMAL BLOCK (±21"

OF INSULATION, ±R-65).

NEW CONTINUOUS THERMAL

BLOCK AT BOTTOM CHORD

NEW CONTINUOUS VAPOR BARRIER,

SEAL TO WALLS

NEW ROOF INSULATION SYSTEM ABOVE

OPERATIONS MANAGER AND PROJECT

COORDINATOR OFFICES SHALL BE SIMPLE SAVER

SYSTEM BY THERMAL DESIGN INCLUDING SYSEAL

FABRIC, STEEL SUPPORT STRAPS, FASTENERS &

SEALANTS.

FILL THE ENTIRE SPACE BETWEEN THE BAR JOISTS

AS WELL AS THE ENTIRE DEPTH OF THE BAR JOIST

WITH UNFACED FORMALDEHYDE FREE FIBER BATT

INSULATION TO ASSURE THE HIGHEST IN PLACE

R-VALUES AND TO HELP AVOID POSSIBLE

CONDENSATION PROBLEMS.

THE INSULATION SHALL REST ON THE LINER

FABRIC/VAPOR BARRIER BETWEEN THE JOISTS.

THE INSULATION SHALL FIT TIGHTLY TOGETHER

AROUND THE JOIST CHORDS.

A CONTINUOUS 1" THICK x WIDTH OF BOTTOM

CHORD TYPE II EXPANDED POLYSTYRENE (EPS)

THERMAL BLOCK SHALL BE INSTALLED TO THE

BOTTOM CHORD OF ALL BAR JOISTS BETWEEN

THE LINER FABRIC/VAPOR RETARDER AND THE

JOIST.

SEAL LINER FABRIC/VAPOR RETARDER AGAINST

WALLS AND ALL PENETRATIONS.

1

2

3

4

5

6

NEW ROOF INSULATION

Sheet number:

Sheet title:

Project:

Print Date:

Drawn By:

Issue: Date: Revision: Date:

BID SET 07/02/15

LM & MT

EAGLE COUNTY AIRPORT

ADMINISTRATION OFFICE

REMODEL

A-4

WALL SECTION, DETAILS

7/6/15

715 W. Main Street, Suite 104 Aspen, Colorado 81611voice: 970.544.4851 email: [email protected]

Page 5: EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor framing plan framing and foundation details specs, schedules & sequence hvac plan

FRAMED FLOOR (1-HR. 55 TO 59 STC SOUND)

FINISH FLOORING MATERIAL, SEE INTERIOR ROOM FINISH SCHEDULE

GA FILE NO. FC 5106

BASE LAYER 1/2" TYPE X GYPSUM WALLBOARD APPLIED AT RIGHT ANGLES TO RESILIENT

CHANNELS 16" O.C. WITH 11/4" TYPE S DRYWALL SCREWS 12" O.C. RESILIENT CHANNELS

APPLIED AT RIGHT ANGLES TO MINIMUM 91/2" DEEP WOOD I-JOISTS, WITH MINIMUM 11/4" DEEP

X 11/2" WIDE FLANGES AND MINIMUM 3/8" WEBS, 24" O.C. WITH 11/4" TYPE W DRYWALL

SCREWS. FACE LAYER 1/2" TYPE X GYPSUM WALLBOARD APPLIED AT RIGHT ANGLES TO

CHANNELS WITH 15/8" TYPE S DRYWALL SCREWS 12" O.C. FACE LAYER END JOINTS

LOCATED MIDWAY BETWEEN CHANNELS AND ATTACHED TO BASE LAYER WITH 11/2" TYPE G

SCREWS 12" O.C. EDGE JOINTS OFFSET 24" FROM BASE LAYER EDGE JOINTS. WOOD

I-JOISTS SUPPORTING 5/8" ORIENTED STRAND BOARD APPLIED AT RIGHT ANGLES TO I-

JOISTS WITH 8D COMMON NAILS 12" O.C.

STC AND IIC TESTED BOTH WITH AND WITHOUT VINYL FLOOR COVERING AND WITH 31/2"

GLASS FIBER INSULATION IN JOIST SPACES. THIRD LAYER OF 1/2" OR 5/8" TYPE X GYPSUM

WALLBOARD REQUIRED TO ACHIEVE 1 HOUR FIRE RESISTANCE RATING WHEN GLASS FIBER

INSULATION IS USED.

TYPICAL INTERIOR WALL

INTERIOR WALL FINISH MATERIAL, SEE

INTERIOR ROOM FINISH SCHEDULE

3 5/8" STEEL STUDS AT 16" O.C.

FIBER BATT INSULATION (FORMALDEHYDE FREE,

FOR SOUND), FULL DEPTH OF STUD CAVITY

INTERIOR WALL FINISH MATERIAL, SEE

INTERIOR ROOM FINISH SCHEDULE

EXISTING CMU WALL WITH FURRING

(BOTH SIDES)

NEW INTERIOR WALL FINISH MATERIAL, SEE

INTERIOR ROOM FINISH SCHEDULE

NEW 1 1/2" FURRING CHANNELS AT 16" O.C.

NEW FIBER BATT INSULATION (FORMALDEHYDE FREE,

FOR SOUND)

EXISTING CMU

NEW FIBER BATT INSULATION (FORMALDEHYDE FREE,

FOR SOUND) IF EXISTING DRYWALL IS REMOVED

EXISTING 1 1/2" FURRING CHANNEL (VERIFY), TO REMAIN

EXISTING INTERIOR WALL FINISH MATERIAL, SEE

INTERIOR ROOM FINISH SCHEDULE

EXISTING CMU WALL WITH FURRING

EXISTING CMU

NEW FIBER BATT INSULATION (FOR SOUND)

NEW 1 1/2" FURRING CHANNEL

NEW INTERIOR WALL FINISH MATERIAL, SEE

INTERIOR ROOM FINISH SCHEDULE

INSULATION

NOT SHOWN

5/8" DRYWALL

HOLLOW METAL

DOOR FRAME

DOOR

5/8" DRYWALL

INSULATION

NOT SHOWN

5/8" DRYWALL

DOOR

5/8" DRYWALL

4" M

IN.

1/4

"

SH

IM

METAL L-TRIM

INSULATION

NOT SHOWN

5/8" DRYWALL

HEADER

DOOR

5/8" DRYWALL

HEMMED ANGLE MOLDING, TYPICAL

AT CEILING TO WALL

NEW SUSPENDED ACOUSTICAL

BOARD AND GRID CEILING, SEE

REFLECTED CEILING PLANNEW 3 5/8" STEEL

STUDS AT 16" O.C.

METAL L-TRIM

INSULATION

NOT SHOWN

5/8" DRYWALL

HEADER

5/8" DRYWALL

NEW SUSPENDED ACOUSTICAL

BOARD AND GRID CEILING, SEE

REFLECTED CEILING PLANNEW 3 5/8" STEEL

STUDS AT 16" O.C.

METAL L-TRIM

1/2" S

HIM

INSULATION

NOT SHOWN

5/8" DRYWALL5/8" DRYWALL

1/4

"

SH

IM

METAL L-TRIM

1/2" S

HIM

CARPET

1/4

" S

HIM

STOREFRONT FRAME

INTERIOR WALL (1-HR)

GA FILE NO. WP 1072

ONE LAYER 5/8" TYPE 'X' GYPSUM

WALLBOARD OR GYPSUM VENEER BASE

APPLIED PARALLEL OR AT RIGHT ANGLES

TO EACH SIDE OF 3 5/8" STEEL STUDS OR

2x WOOD STUDS AT 16" O.C. WITH 1" TYPE

'S' DRYWALL SCREWS 8" O.C. AT

VERTICAL JOINTS AND 12" O.C. AT FLOOR

AND CEILING RUNNERS AND

INTERMEDIATE STUDS.

JOINTS STAGGERED 24" ON EACH SIDE

AND ON OPPOSITE SIDES.

FIBER BATT INSULATION (FORMALDEHYDE

FREE, FOR SOUND), FULL DEPTH OF STUD

CAVITY

INTERIOR WALL WITH RESILIENT

CHANNELS

INTERIOR WALL FINISH MATERIAL, SEE

INTERIOR ROOM FINISH SCHEDULE

1/2" SINGLE LEG RESILIENT CHANNEL AT 16" O.C.,

PERPENDICULAR TO STUDS (SCREW ATTACHMENT)

3 5/8" STEEL STUDS AT 16" O.C.

FIBER BATT INSULATION (FOR SOUND) FULL DEPTH

OF STUD CAVITY

INTERIOR WALL FINISH MATERIAL, SEE

INTERIOR ROOM FINISH SCHEDULE

INSULATION

NOT SHOWN

5/8" DRYWALL

HOLLOW METAL

DOOR FRAME

DOOR

5/8" DRYWALL

RESILIENT CHANNELS

AT 16" O.C.

1"1"

INSULATION

NOT SHOWN

5/8" DRYWALL

HOLLOW METAL

DOOR FRAME

DOOR

5/8" DRYWALL

RESILIENT CHANNELS

AT 16" O.C.

1"3" M

IN.

4" M

IN.

HEMMED ANGLE MOLDING, TYPICAL

AT CEILING TO WALL

STOREFRONT FRAME

STOREFRONT FRAME

STOREFRONT FRAME

STOREFRONT FRAME

3" M

IN.

3" M

IN.

W3SCALE: 3" = 1'-0"

WALL ASSEMBLY (PLAN VIEW)

W2SCALE: 3" = 1'-0"

WALL ASSEMBLY (PLAN VIEW)

W1SCALE: 3" = 1'-0"

WALL ASSEMBLY (PLAN VIEW)

W4SCALE: 3" = 1'-0"

WALL ASSEMBLY (PLAN VIEW)

W5SCALE: 3" = 1'-0" SCALE: 3" = 1'-0"4

STOREFRONT DOOR HEAD

SCALE: 3" = 1'-0"5

STOREFRONT DOOR JAMB

SCALE: 3" = 1'-0"6

STOREFRONT HEAD

SCALE: 3" = 1'-0"7

STOREFRONT JAMB

SCALE: 3" = 1'-0"10

INTERIOR DOOR JAMB TO WALL

SCALE: 3" = 1'-0"11

INTERIOR DOOR JAMB TO WALL

SCALE: 3" = 1'-0"9

STOREFRONT WINDOW HEAD

SCALE: 3" = 1'-0"8

STOREFRONT SILL

SCALE: 3" = 1'-0"F1

FLOOR ASSEMBLY

SCALE: 3" = 1'-0"2

DOOR JAMB

SCALE: 3" = 1'-0"3

DETAIL

WALL ASSEMBLY (PLAN VIEW)

Sheet number:

Sheet title:

Project:

Print Date:

Drawn By:

Issue: Date: Revision: Date:

BID SET 07/02/15

MT

EAGLE COUNTY AIRPORT

ADMINISTRATION OFFICE

REMODEL

A-5

ASSEMBLIES, DETAILS

7/6/15

715 W. Main Street, Suite 104 Aspen, Colorado 81611voice: 970.544.4851 email: [email protected]

Page 6: EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor framing plan framing and foundation details specs, schedules & sequence hvac plan

5

A-5

4

A-5

6

A-5

7

A-5

8

A-5

8

A-5

7

A-5

SIM.

6

A-5

8

A-5

6

A-5

7

A-5

SIM.

SIM.

SIM.

5" 5"

5"

10"

7'-0

"

3'-0"

7'-0

"

3'-0"

1 3/4" 1 3/4"± 4'-10 1/2" ± 5'-7 3/8"1 3/4" 1 3/4"± 3'-0" 3'-0"1 3/4" 1 3/4"

± 8'-3 3/4" ± 9'-0 5/8"

1 3/4

"± 2

'-2 1/2

"1 3/4

"± 4

'-6

"1 3/4

"

(MA

TC

H E

XIS

T.)

(MA

TC

H E

XIS

T.)

(MA

TC

H E

XIS

T.)

(MA

TC

H E

XIS

T.)

7'-1 3/4

"

1 3/4" 3'-0 3/8" 1 3/4" 3'-0 3/8"

± 6'-4 3/8"

1 3/4

"± 2

'-2 1/2

"1 3/4

"± 4

'-6

"1 3/4

"

(MA

TC

H E

XIS

T.)

(MA

TC

H E

XIS

T.)

7'-1 3/4

"

1 3/4

"± 2

'-2 1/2

"1 3/4

"± 4

'-6

"1 3/4

"

7'-1 3/4

"

± 2'-0"

REFRIGERATOR

SPACE FOR 24"

WIDE REFRIG.

± 8 5/8"

4 1/2"

1 3/4

"± 2

'-2 1/2

"1 3/4

"± 4

'-6

"1 3/4

"

(MA

TC

H E

XIS

T.)

(MA

TC

H E

XIS

T.)

7'-1 3/4

"

(FIT DOOR) (FIT DOOR)

± 2'-3 3/4" 1 3/4"

4 1/2" ± 2'-5 1/2"

(VERIFY)

1HALLWAY

SCALE: 1/2" = 1'-0"

NORTH

2HALLWAY

SCALE: 1/2" = 1'-0"

EAST

4DOOR TYPES

TYPE 'A' TYPE 'B'

SCALE: 1/2" = 1'-0"

NEW CORNER JAMB OR

MODIFY EXISTING

3KITCHENETTE

SCALE: 1/2" = 1'-0"

EAST

WIDEN REFRIGERATOR

SPACE BY REMOVING

AND REPLACING

DRAWER CABINET

DASHED LINE INDICATE

EXISTING BANK OF

DRAWERS

REPLACE DRAWERS CABINET A

NEW BASE CABINET, WITH ADJ.

SHELF, TO MATCH EXISTING

NORTH

LOCATIONMARK TYPE WIDTH HEIGHT THICKNESS MATERIAL HARDWARE

1 CONFERENCE ROOM

FINISH FRAME FINISH HEAD JAMB SILL COMMENTS

DOOR TYPES:

DOOR SCHEDULE

REV.

2

3 STAIR 2

4 OPERATIONS MANAGER

5 PROJECT COORDINATOR

6

7

8

AVIATION DIRECTOR

ADMIN. MGR.

STORAGE

TYPE 'A': SINGLE LITE STILE AND RAIL WOOD DOOR: MARSHFIELD, OR EQUIVALENT, STILE AND RAIL SERIES, DESIGN K-6010 WITH W-8 MOULDING. FACTORY GLAZED WITH 1/4" CLEAR TEMPERED GLASS. FINAL WOOD VENEER SELECTION TO

BE DETERMINED BUT FOR BIDDING USE PLAIN SLICED WHITE MAPLE CLEAR. FIELD STAIN. SEE DOOR STYLE DRAWING AT LEFT.

TYPE 'B': FLUSH WOOD DOOR: MARSHFIELD, OR EQUIVALENT, SIGNATURE SERIES WOOD BASED PARTICLEBOARD CORE. FINAL WOOD VENEER SELECTION TO BE DETERMINED BUT FOR BIDDING USE PLAIN SLICED WHITE MAPLE CLEAR. FIELD

STAIN . SEE DOOR STYLE DRAWING AT LEFT.

TYPE 'C': FIRE RATED FLUSH WOOD DOOR: MARSHFIELD, OR EQUIVALENT, SIGNATURE SERIES WOOD BASED PARTICLEBOARD CORE, 60 MINUTE FIRE RATED. FINAL WOOD VENEER SELECTION TO BE DETERMINED BUT FOR BIDDING USE PLAIN

SLICED WHITE MAPLE CLEAR. FIELD STAIN . SEE DOOR STYLE DRAWING AT LEFT.

A STEEL, TYPE 13'-0" 7'-0" 1 3/4" PRIME AND PAINT

STEEL, TYPE 12'-4" 7'-0" 1 3/4"

STEEL, TYPE 23'-0" 7'-0" 1 3/4"

3'-0" 7'-0" 1 3/4"

ALUMINUM3'-0" 7'-0" 1 3/4" FACTORY PAINT

3'-0" 7'-0" 1 3/4"

A 3'-0" 7'-0" 1 3/4" PRIME AND PAINT

B 3'-0" 7'-0" 1 3/4" PRIME AND PAINT

4/A-4 5/A-4 & 2/A-5 - -

CONFERENCE ROOM B

B

A

A

A

WOOD

WOOD

WOOD & GLASS STAIN

STAIN

STAIN

STAIN

STAIN

STAIN

STAIN

PRIME AND PAINT

PRIME AND PAINT

PRIME AND PAINT

PRIME AND PAINT

ROOM FINISH SCHEDULE

ROOMREV

FLOORS

MTRL BASENORTH

MTRL FIN. MTRL FIN.

EAST

WALLS

SOUTH WEST

CEILINGS

MTRL FIN. COMMENTS

MTRL FIN. MTRL FIN.

OPEN OFFICE (INCLUDES RECEPTION,

BADGING, ADMIN. ASST. & MARKETING)

RM #

NOTE 1 NOTE 2 DW NOTE 1 ACT - -

NOTES:

CONFERENCE ROOM

ASSISTANT AVIATION DIRECTOR

FINISH MATERIALS SPECIFICATIONSDESCRIPTIONREV SIZE COMMENTSMARK MANUF./MTRL. MANF'R # COLOR SIZE

1.

2.

3.

AVIATION DIRECTOR

PROJECT COORDINATOR

OPERATIONS MANAGER

NOTES:

1.

PATCH, OR REPLACE (CONTRACTOR'S OPTION), EXISTING DRYWALL ON PARTITIONS TO REMAIN AND NEW DRYWALL ON NEW PARTITIONS.

PATCH, OR REPLACE (CONTRACTOR'S OPTION), EXISTNG DRYWALL ON PARTITIONS TO REMAIN AND NEW DRYWALL OVER NEW FURRING ON EXISTING EXPOSED CMU WALL AT CHASE.

PATCH, OR REPLACE (CONTRACTOR'S OPTION), EXISTING DRYWALL.

ETR EXISTING TO REMAIN - - - - - -- -

PAINT PAINT ULTRA SPEC 500 N 537 (LOW SHEEN)

AND N539 (SEMI GLOSS)

LINEN WHITE - -BENJAMIN MOORE

TYPICAL NOTES:

1.

2.

3.

REMOVE AND REPLACE AS MUCH DRYWALL FINISH AS NEEDED TO EXECUTE PROPOSED WORK. CONTRACTOR'S DISCRETION TO LEAVE OR REPLACE ANY AND ALL EXISTING DRYWALL ON WALL SURFACES WHERE NEW WORK IS MINIMAL. ANY

EXISTING DRYWALL THAT REMAINS MUST BLEND SEAMLESSLY WITH NEW DRYWALL. PATCH/REPAIR ANY IMPERFECTIONS/DAMAGE TO EXISTING DRYWALL THAT REMAINS AND TEXTURE TO BLEND SEAMLESSLY WITH NEW DRYWALL.

PAINT ALL EXISTING WOOD WINDOW CASING/TRIM (WINDOWS ARE ALUMINUM, DO NOT PAINT WINDOWS).

PAINT ALL EXISTING WOOD DOORS, FRAMES AND CASING TO REMAIN.

NOTE 3 NOTE 3DWDW - -

NOTE 3 PAINT NOTE 3 PAINT - -

ACT - -

DW GYPSUM DRYWALL - - - - 5/8"AMERICAN GYPSUM TEXTURE TO MATCH EXISTING.

NOTE 3 PAINT DW PAINT NOTE 3 PAINT

CARPET CARPET GL 149 WAVELENGTH BILLOW - 665 - -MOHAWK GROUP

ADMINISTRATIVE MANAGER - -

PAINT PAINTPAINTPAINT

PAINT PAINT PAINT PAINT

PAINT PAINT PAINT - -

ACT ACOUSTICAL CEILING TILE (NEW) CIRRUS TEGULAR #534 PANELS

W/ PRELUDE XL 15/16" TEE SYSTEM

WHITE 2'x4'ARMSTRONG

ACT (E) ACOUSTICAL CEILING TILE (EXISTING

TO REMAIN)

EXISTING EXISTING 2'x4'EXISTING REPLACE ANY AND ALL DAMAGED TILES AND GRID WITH NEW TILES

AND GRID TO MATCH EXISTING.

STORAGE ROOM

KITCHENETTE

CARPET VB

ACT

ACT - -PAINT PAINT PAINT PAINT

ACT - -PAINT

PAINT PAINT ACT

PAINT PAINT ACT

ETR ETR PAINTETRPAINTETR ETR

VCT PAINT PAINTPAINTDW PAINT - -ACT

9

ASST. AVIATION DIRECTOR

WOOD & GLASS

WOOD & GLASS

WOOD & GLASS

WOOD & GLASS

WOOD & GLASS

WOOD

A 3'-0" 7'-0" 1 3/4" STAIN

PAINT

PRIME AND PAINT

HALLWAY

VCT VINYL COMPOSITION TILE MATCH EXISTING MATCH EXISTING 12x12MATCH EXISTING MATCH VCT AND VINYL BASE IN EXISTING WOMEN'S TOILET ROOM.

VB COLOR INTEGRATED VINYL BASE COVE PROFILE STD. COLOR, TBD 4" TALLARMSTRONG

DW DW ACT - -PAINT PAINT PAINT PAINT

4/A-4 5/A-4, 11/A-5 - -

2/A-4 3/A-4, 10/A-5 - -

4/A-4 5/A-4, 11/A-5 - -

4/A-5 5/A-5 - -

4/A-5 5/A-5 - -

2/A-4 3/A-4, 10/A-5 - -

2/A-4 3/A-4, 10/A-5 - -

2/A-4 3/A-4 - -

STAIR 2

WOMEN'S TOILET ROOM

MEN'S TOILET ROOM

ELECTRICAL ROOM

STAIR 1

STORAGE

ETR ETR & VINYL ETRETR & GWB PAINT PAINTETR & GWB ETR ETR

ETR ETR ETR ETRETR ETR ETR

ETR ETR ETR ETRETR ETR ETR

ETR ETR ETR - - - -ETRETR - - ETR - - ETR - -

ETR ETR ETR - - - -ACT (E)ETR - - ETR - - ETR - -

ETR ETRETR ETR ETR

DW

DW

DW

DW

DW

DW

DW

DW

DW

DW

DW

DW

DW

DW

DW

DW

DW

DW

CLOSET DW DW ACT - -PAINT PAINT PAINT PAINTDW DW

NEW VINYL BASE AT STAIR LANDING SHALL

MATCH EXISTING.

DRYWALL AT SOFFIT CEILING AND CEILING ON

OTHER SIDE OF NORTH WALL, PAINT.

DRYWALL AT SOFFIT CEILING AND CEILING ON

OTHER SIDE OF NORTH WALL, PAINT.

PAINT PAINTNOTE 3 DW

NOTE 3

PAINT PAINTPAINT FINISH FRAMED-IN OPENING TO MATCH EXISTING.

PAINTPAINT PAINTPAINT PAINT

PAINTPAINT PAINTPAINT PAINT

PAINTPAINT PAINTPAINT PAINT

PAINTPAINT PAINT

PRIMER AND PAINT COATS AND THICKNESSES: LATEX PRIMER 1.4 TO 1.7 DRY MILS. INTERMEDIATE: ACRYLIC PAINT; 1.5 TO 1.7 DRY MILS. FINISH COAT: ACRYLIC PAINT 1.5 TO 1.7 DRY MILS; 1.5 TO 1.7 DRY MILS. SHEEN: LOW SHEEN (EGGSHELL)

THROUGHOUT EXCEPT AS NOTED. TOILET ROOMS, KITCHENETTE, AND INTERIOR DOORS AND FRAMES: SEMI-GLOSS.

PRIMER PRIMER ULTRA SPEC 500 N534 - - - -BENJAMIN MOORE

SEE NOTE 1 BELOW.

SEE NOTE 1 BELOW.

VB

VB

VB

VB

VB

VB

VB

VB

VB

VB

VB

CARPET

CARPET

CARPET

CARPET

CARPET

CARPET

CARPET

CARPET

CARPET

DOOR FRAME TYPES:

TYPE '1': DOUBLE RABBET NON-RATED STEEL FRAME. CECO, OR EQUIVALENT, SERIES BQ, 18 GAUGE.

TYPE '2': DOUBLE RABBET 60-MINUTE RATED STEEL FRAME. CECO, OR EQUIVALENT, SERIES BQ, 18 GAUGE (VERIFY GAUGE WITH FIRE RATING REQUIREMENT).

STEEL, TYPE 1

STEEL, TYPE 1

ALUMINUM

STEEL, TYPE 1

STEEL, TYPE 1

HARDWARE SCHEDULE:

HARDWARE SET 1: (DOOR 1)

HINGES: STANLEY 5 KNUCKLE CB FULL MORTISE HINGE: CB191-32D

LATCH SET: BEST ACCESS SYSTEMS CYLINDRICAL LOCK, PASSAGE FUNCTION: 9K-3-0-N-16-C-S3-626

WALL STOP: IVES WS447-US26D (SATIN CHROME)

ACOUSTIC SEAL SET: PEMKOSTCSET-1A (GASKETING: S773BL (SINGLE ROW) AND S44BL (SINGLE ROW), DOOR

BOTTOM: PDB411AE, CORNER PAD: ACP112BL

PASSAGE

HDWE SET

1

HARDWARE SET 2: (DOOR 2)

HINGES: STANLEY 5 KNUCKLE CB FULL MORTISE HINGE: CB191-32D

LATCH SET: BEST ACCESS SYSTEMS CYLINDRICAL LOCK, PASSAGE FUNCTION: 9K-3-0-N-16-C-S3-626

WALL STOP: IVES WS447-US26D (SATIN CHROME)

HARDWARE SET 3: (DOOR 3)

HINGES: STANLEY 5 KNUCKLE CB FULL MORTISE HINGE: CB191-32D

LATCH SET: BEST ACCESS SYSTEMS CYLINDRICAL LOCK, PROVIDE SAME FUNCTION AS EXISTING LATCH SET

WALL STOP: IVES WS447-US26D (SATIN CHROME)

GASKET: SMOKE SEAL AT HEAD AND JAMBS

DOOR BOTTOM: PEMKO 411 ARL AUTOMATIC DOOR BOTTOM

CLOSER: LCN CLOSERS, 1260 SERIES. HINGE PULL SIDE MOUNTING. POWDER COAT FINISH.

HARDWARE SET 4: (DOORS 4 & 7)

HINGES: STANLEY 5 KNUCKLE CB FULL MORTISE HINGE: CB191-32D

LATCH SET: BEST ACCESS SYSTEMS CYLINDRICAL LOCK, OFFICE FUNCTION: 9K-3-7-B-16-C-S3-626

WALL STOP: IVES WS447-US26D (SATIN CHROME)

ACOUSTIC SEAL SET: PEMKOSTCSET-1A (GASKETING: S773BL (SINGLE ROW) AND S44BL (SINGLE ROW), DOOR

BOTTOM: PDB411AE, CORNER PAD: ACP112BL

PASSAGE

LOCKSET

LOCKSET

LOCKSET

LOCKSET

LOCKSET

2

3

4

5

5

4

6

7

HARDWARE SET 5: (DOORS 5 & 6)

HINGES: STANLEY 5 KNUCKLE CB FULL MORTISE HINGE: CB191-32D

LATCH SET: BEST ACCESS SYSTEMS CYLINDRICAL LOCK, OFFICE FUNCTION: 9K-3-7-B-16-C-S3-626

WALL STOP: IVES WS447-US26D (SATIN CHROME)

GASKET: ACOUSTIC GASKETING/WEATHERSTRIPPING AT JAMBS AND HEAD BY STOREFRONT SUPPLIER

DOOR BOTTOM: PEMKO PDB411AE

HARDWARE SET 6: (DOOR 8)

HINGES: STANLEY 5 KNUCKLE CB FULL MORTISE HINGE: CB191-32D

LATCH SET: BEST ACCESS SYSTEMS CYLINDRICAL LOCK, OFFICE FUNCTION: 9K-3-7-B-16-C-S3-626

FLOOR STOP: IVES FS410-US26D (SATIN CHROME) DECORATIVE FLOOR STOP

ACOUSTIC SEAL SET: PEMKOSTCSET-1A (GASKETING: S773BL (SINGLE ROW) AND S44BL (SINGLE ROW), DOOR

BOTTOM: PDB411AE, CORNER PAD: ACP112BL

LOCKSET

HARDWARE SET 7: (DOOR 9)

HINGES: STANLEY 5 KNUCKLE CB FULL MORTISE HINGE: CB191-32D

LATCH SET: BEST ACCESS SYSTEMS CYLINDRICAL LOCK, STOREROOM FUNCTION: 9K-3-7-RZ-16-C-S3-626

FLOOR STOP: IVES FS410-US26D (SATIN CHROME) DECORATIVE FLOOR STOP

HARDWARE SET 8: EXISTING MEN'S AND WOMEN'S TOILET ROOM DOORS TO REMAIN - REPLACE EXISTING LATCH

SETS TO MATCH NEW ONES

LATCH SET: BEST ACCESS SYSTEMS CYLINDRICAL LOCK, PRIVACY FUNCTION: 9K-3-0-L-16-C-S3-626

HARDWARE SET 9: EXISTING ELECTRICAL ROOM DOOR TO REMAIN - REPLACE EXISTING LATCH

SET TO MATCH NEW ONES

LATCH SET: BEST ACCESS SYSTEMS CYLINDRICAL LOCK, STOREROOM FUNCTION: 9K-3-7-RZ-16-C-S3-626

SEE HARDWARE SCHEDULE BELOW FOR NEW LATCH SETS FOR EXISTING DOORS TO REMAIN

1/4" CLEAR TEMPERED GLASS

TYPICAL

ALUMINUM STOREFRONT FRAME,

TYPICAL

NEW END PANEL, TO MATCH

EXISTING, WHERE UPPER

CABINETS REMOVED

EXISTING UPPER CABINETS

TO REMIAN

EXISTING BASE

CABINET TO REMAIN

EXISTING CORNER CABIENT

TO REMAIN

Sheet number:

Sheet title:

Project:

Print Date:

Drawn By:

Issue: Date: Revision: Date:

BID SET 07/02/15

MT

EAGLE COUNTY AIRPORT

ADMINISTRATION OFFICE

REMODEL

A-6

SCHEDULES, INTERIOR

ELEVATIONS

7/6/15

715 W. Main Street, Suite 104 Aspen, Colorado 81611voice: 970.544.4851 email: [email protected]

Page 7: EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor framing plan framing and foundation details specs, schedules & sequence hvac plan
Page 8: EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor framing plan framing and foundation details specs, schedules & sequence hvac plan
Page 9: EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor framing plan framing and foundation details specs, schedules & sequence hvac plan
Page 10: EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor framing plan framing and foundation details specs, schedules & sequence hvac plan

RADIANT FLOOR SUPPLY

RADIANT FLOOR RETURN

NOTE: ALL SYMBOLS SHOWN ON LEGEND

ARE NOT NECESSARILY USED.

CHILLED WATER RETURN

CHILLED WATER SUPPLY

HEATING WATER RETURN

HEATING WATER SUPPLY

MECHANICAL LEGEND

MEDIUM PRESSURE NATURAL GAS

SNOWMELT RETURN

SNOWMELT SUPPLY

GAS

HWS

T

A

B

HWR

CWS

CWR

SMS

SMR

RFS

RFR

G

MPG

PIPE RISER

PIPE DROP

PIPE TAKEOFF (FROM BOTTOM OF MAIN)

PIPE TAKEOFF (FROM TOP OF MAIN)

PIP END CAP

PIPE CONTINUATION

PIPE EXPANSION GUIDE

PIPE UNION

PIPE ANCHOR

FLEXIBLE PIPE CONNECTION

PIPE EXPANSION JOINT

POINT OF NEW CONNECTION

AIR VENT

PLUG VALVE

CHECK VALVE

BALL VALVE

BALANCING VALVE

BUTTERFLY VALVE

PRESSURE REDUCING VALVE

STRAINER

PRESSURE - TEMP. TAP

PRESSURE GAUGE

2-WAY CONTROL VALVE

3-WAY CONTROL VALVE

SUPPLY GRILLE

RETURN GRILLE

EXHAUST AIR

SUPPLY AIR

RETURN AIR

OUTDOOR AIR

SUPPLY AIR DAMPER

RETURN AIR DAMPER

SUPPLY DIFFUSER

OA

RA

SA

EA

RAD

SAD

SG

RG

SD

RETURN DIFFUSERRD

TRANSFER GRILLETG

TRANSFER DIFFUSERTD

THERMOSTAT

FIRE/SMOKE DAMPER

FIRE DAMPER

MOTOR OPERATED DAMPER (MOD)

MANUAL BALANCING DAMPER

TURNING VANES IN 90° ELBOW

??x??

DUCT SIZES ARE NET FREE AREA

1ST NO. IS DUCT WIDTH.

2ND NO. IS DUCT DEPTH.

SECTION THRU SUPPLY AIR DUCT

SECTION THRU RETURN/EXHAUST AIR DUCT

SUPPLY DUCT TURN DOWN

RETURN/EXHAUST DUCT TURN DOWN

CHANGE OF ELEVATION

FLEXIBLE DUCT CONNECTION

R/D

(D) DROP (R) RISE

SENSOR (CALL OUT ON DRAWINGS)

SUPPLY REGISTER/DIFFUSER/LOUVER

NECK SIZE

CFM-S

RETURN REGISTER/DIFFUSER/LOUVER

NECK SIZE

CFM-R

OUTSIDE AIR REGISTER/DIFFUSER/LOUVER

NECK SIZE

CFM-O.A.

EXHAUST REGISTER/DIFFUSER/LOUVER

NECK SIZE

CFM-E

UDOOR UNDERCUT CFM

(A) SECTION CUT LINE

(B) SHEET SHOWN ON

S

SECTION THRU ROUND DUCT

ROUND DUCT TURN DOWN

4-WAY CONTROL VALVE

FLOW REGULATOR VALVE

DIFFERENTIAL BYPASS VALVE

NATURAL GAS PRESSURE REGULATOR

THERMOMETER

M

SEQUENCE OF OPERATION:

FURNACES & CONDENSING UNITS:

THE FURNACES AND CONDENSING UNITS SHALL BE CONTROLLED BY HEATING AND COOLING 7-DAY

PROGRAMMABLE WALL MOUNTED THERMOSTATS.

EF-1:

THE EXHAUST FAN SHALL BE CONTROLLED ACCORDING TO A WALL MOUNTED THERMOSTAT.

MOTORIZED DAMPERS:

WHEN THE SPACE IS OCCUPIED, THE OUTSIDE AIR DAMPERS (MD-2 & MD-4) SHALL OPEN AND THE RETURN AIR

DAMPERS (MD-1 & MD-3) SHALL PARTIALLY CLOSE AS INDICATED IN THE DAMPER SCHEDULE. WHILE UNOCCUPIED,

THE OUTSIDE AIR DAMPERS SHALL CLOSE AND THE RETURN AIR DAMPERS SHALL FULLY OPEN.

MECHANICAL SPECIFICATIONS:

1. GENERAL:

a. FURNISH ALL LABOR, SUPERVISION, MATERIALS, EQUIPMENT AND FACILITIES

NECESSARY TO FURNISH, FABRICATE, DELIVER, STORE AND INSTALL ALL WORK NOTED

ON THE DRAWINGS AND/OR SPECIFIED HEREIN.

b. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL WORK NECESSARY TO MAKE A

COMPLETE SYSTEM WHETHER OR NOT SUCH DETAILS ARE MENTIONED IN THESE

SPECIFICATIONS OR SHOWN ON THE PLANS, BUT WHICH ARE OBVIOUSLY NECESSARY

TO MAKE A COMPLETE SYSTEM, EXCEPTING ONLY THOSE PORTIONS THAT ARE

SPECIFICALLY MENTIONED HEREIN OR PLAINLY MARKED ON THE ACCOMPANYING

DRAWINGS AS BEING INSTALLED UNDER ANOTHER SECTION OF THE SPECIFICATIONS.

2. WORKMANSHIP:

a. THE WORK SHALL BE ACCOMPLISHED IN A THOROUGH AND WORKMAN-LIKE MANNER

SATISFACTORY TO AND MEETING THE APPROVAL OF THE OWNER AND ARCHITECT.

3. MATERIALS:

a. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND THE BEST OF THEIR RESPECTIVE

KIND, FREE FROM ALL DEFECTS AND OF THE MAKE AND QUALITY SPECIFIED.

4. SITE INSPECTION:

a. CONTRACTOR SHALL VISIT THE SITE OF WORK PRIOR TO SUBMISSION OF HIS BID AND

THOROUGHLY FAMILIARIZE HIMSELF WITH THE WORKING CONDITIONS & EXACT NATURE

OF THE WORK.

b. SUBMISSION OF A BID ACKNOWLEDGES FULL RESPONSIBILITY FOR FURNISHING A

COMPLETE AND FUNCTIONAL SYSTEM.

c. NO CHANGES IN CONTRACT WILL BE MADE TO ACCOMMODATE OR ALLOW EXTRA FUNDS

FOR ANY OMISSION WHICH RESULTS FROM A FAILURE TO THOROUGHLY MAKE THE

EXAMINATION.

5. CODES AND PERMITS:

a. ALL MECHANICAL EQUIPMENT, INSTALLATION, ETC., SHALL CONFORM TO THE 2009

INTERNATIONAL MECHANICAL CODE (IMC), 2009 INTERNATIONAL ENERGY

CONSERVATION CODE (IECC) AND ORDINANCES AS INTERPRETED BY THE COUNTY OF

EAGLE BUILDING DEPARTMENT.

b. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS AND INSPECTIONS.

c. COPIES OF ALL PERMITS AND INSPECTION REPORTS SHALL BE SUBMITTED TO THE

ARCHITECT.

6. AS-BUILTS:

a. CONTRACTOR SHALL PROVIDE A COMPLETE SET OF AS-BUILT DOCUMENTS WITH ALL

CHANGES NOTED THEREON AT THE COMPLETION OF THE PROJECT AND PRIOR TO FINAL

ACCEPTANCE AND PAYMENT.

7. GUARANTEE:

a. CONTRACTOR SHALL UNCONDITIONALLY GUARANTEE ALL LABOR AND MATERIALS ON

ALL WORK AGAINST DEFECTS IN WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE

YEAR AFTER COMPLETION.

8. SUBMITTALS:

a. CATALOG INFORMATION AND CUTS OF ALL EQUIPMENT AND DEVICES (WITH ALL

OPTIONS CLEARLY MARKED) SHALL BE SUBMITTED TO THE ARCHITECT FOR REVIEW (SIX

COPIES OF EACH). ELECTRONIC SUBMITTALS PREFERRED.

9. COORDINATION:

a. THE DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO SHOW SCOPE.

b. THE CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER TRADES TO PROVIDE

BEST ARRANGEMENT OF ALL DUCTS, PIPES, CONDUIT, ETC.

10. CUTTING AND PATCHING:

a. ALL CUTTING AND PATCHING REQUIRED OF THE STRUCTURE (NEW OR EXISTING) SHALL

BE PROVIDED UNDER OTHER SECTIONS OF THE WORK.

b. PROVIDE NECESSARY REQUIREMENTS TO THE PROJECT SUPERINTENDENT.

c. X-RAY SLABS PRIOR TO CORING.

11. CLEANUP:

a. UPON COMPLETION OF THE WORK UNDER THIS SECTION, THE CONTRACTOR SHALL

REMOVE ALL SURPLUS MATERIALS, EQUIPMENT AND DEBRIS INCIDENTAL TO THIS WORK

AND LEAVE THE PREMISES CLEAN AND ORDERLY.

12. MECHANICAL IDENTIFICATION

a. EQUIPMENT NAMEPLATES: METAL, WITH DATA ENGRAVED OR STAMPED, FOR

PERMANENT ATTACHMENT ON EQUIPMENT.

13. DUCTWORK:

a. DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH THE 2009 IMC

AND SMACNA STANDARDS.

b. DUCTWORK SHALL BE GALVANIZED STEEL GAUGES TO MEET SMACNA STANDARDS.

DUCTWORK SIZES INDICATED ARE INSIDE TO INSIDE DIMENSIONS.

c. ALL DUCT JOINTS SHALL BE SEALED AIR TIGHT WITH RCD CORP. # 6 MASTIC ADHESIVE

WITH VERSA GRIP OR MESH.

d. ALL FINAL CONNECTIONS TO GRILLES SHALL BE COMPLETED WITH ACOUSTICAL

FLEXIBLE DUCT UNLESS OTHERWISE NOTED ON THE PLANS. MINIMUM LENGTH IS 3',

MAXIMUM LENGTH IS 5'.

e. FLEXIBLE DUCT USED FOR CONDITIONED AIR SHALL BE UL APPROVED, VINYL COATED,

WIRE REINFORCED FIBERGLASS, WITH MAXIMUM THERMAL CONDUCTIVITY OF 0.30

BTU-IN/HR-FT2-°F AND A MAXIMUM LENGTH OF FIVE FEET.

f. DUCTWORK SHALL BE SIZED AT A MAXIMUM VELOCITY OF 1,000 FPM/.08" PRESSURE

DROP PER 100 FEET.

g. EACH MECHANICAL VENTILATION SYSTEM (SUPPLY AND/OR EXHAUST) SHALL BE

EQUIPPED WITH A MEANS OF SHUT-OFF WHEN VENTILATION IS NOT REQUIRED, AND

BACKDRAFT DAMPERS WHICH CAN BE CLOSED ON FAN SHUTDOWN SHALL BE PROVIDED

FOR AIR INTAKES AND/OR DISCHARGES.

h. CLEAN OUT ALL DUCTS PRIOR TO SUPPLY AND RETURN GRILLE INSTALLATION

i. DOUBLE THICKNESS TURNING VANES SHALL BE USED ON ALL DUCT TURNS OF 90°.

14. REFRIGERANT PIPING:

a. REFRIGERANT LINE SETS SHALL BE FURNISHED BY THE CONDENSING UNIT

MANUFACTURER AND BE PRE-INSULATED.

b. REFRIGERANT PIPING CONNECTIONS SHALL BE BRAZED WITH 15% SILL FLOSS. PURGE

PIPING WITH NITROGEN WHILE BRAZING.

c. PROVIDE HANGERS, SUPPORTS AND INSULATION SADDLES AS REQUIRED AND PER ANSI

REQUIREMENTS. PLUMBERS TAPE AND WIRE ARE NOT ACCEPTABLE.

d. REFRIGERANT PIPING INDICATED IS SCHEMATIC ONLY. SIZE PIPING AND DESIGN THE

ACTUAL PIPING LAYOUT, INCLUDING OIL TRAPS, DOUBLE RISERS, SPECIALTIES, AND

PIPE AND TUBE SIZES, TO ENSURE PROPER OPERATION AND COMPLIANCE WITH

WARRANTIES OF CONNECTED EQUIPMENT.

e. EVACUATE THE ENTIRE REFRIGERANT SYSTEM WITH A VACUUM PUMP TO A VACUUM OF

500 MICROMETER FOR A PERIOD OF 12 HOURS PRIOR TO CHARGING.

15. DUCTWORK INSULATION:

a. ALL DUCTWORK SHALL BE INSULATED CONSISTENT WITH THE REQUIREMENTS PER

SECTION 604 OF THE 2009 IMC.

b. INSULATION SHALL BE UL LISTED IN COMPLIANCE WITH A FLAME-SPREAD INDEX NOT

MORE THAN 25 AND SMOKE DEVELOPED INDEX NOT MORE THAN 50, PER THE 2009 IMC.

INSTALLATION SHALL BE IN ACCORDANCE WITH IMC REQUIREMENTS.

c. RECTANGULAR SUPPLY, RETURN & TRANSFER DUCTWORK SHALL BE INTERNALLY LINED

WITH A VAPOR RESISTANT DUCT LINER OF THICKNESSES SPECIFIED BELOW.

d. CONCEALED ROUND, CONCEALED OVAL & OUTDOOR AIR DUCTS SHALL BE EXTERNALLY

WRAPPED WITH FIBERGLASS INSULATION WITH AN EXTERNAL VAPOR BARRIER.

REQUIRED R-VALUES ARE SPECIFIED BELOW.

e. ALL SUPPLY, RETURN & TRANSFER DUCTWORK LOCATED WITHIN THE BUILDING

ENVELOPE SHALL BE INSULATED TO A MINIMUM OF R-4 (1” LINER) UNLESS SPECIFIED

OTHERWISE ON THE PLANS.

f. ALL SUPPLY DUCTWORK LOCATED IN ATTICS OR OTHER UNCONDITIONED SPACES

SHALL BE INSULATED TO A MINIMUM OF R-8 (2” LINER). ALL OTHER DUCTS IN

UNCONDITIONED SPACES SHALL BE INSULATED TO A MINIMUM OF R-6 (1-1/2” LINER).

g. ALL SUPPLY & RETURN DUCTWORK SHALL BE INSULATED TO A MINIMUM OF R-5 (1-1/2”

LINER) WHEN LOCATED IN UNCONDITIONED SPACES AND SHALL BE INSULATED TO A

MINIMUM OF R-8 (2” LINER) AND WEATHERPROOFED WHEN LOCATED OUTSIDE THE

BUILDING.

h. ALL OUTDOOR AIR DUCTS SHALL BE INSULATED TO A MINIMUM OF R-6 WITH A VAPOR

BARRIER.

16. TEMPERATURE CONTROL DEVICES:

a. CONTRACTOR SHALL PROVIDE STAND-ALONE CONTROLS CAPABLE OF MEETING THE

SEQUENCE OF OPERATION DESCRIBED ON SHEET M1.0.

b. THE HVAC SYSTEM SHALL BE PROVIDED WITH 7-DAY PROGRAMMABLE AUTOMATIC

SPACE TEMPERATURE CONTROL DEVICES (THERMOSTATS) AS SHOWN ON THE PLANS.

THE THERMOSTATS SHALL BE CAPABLE OF SCHEDULING OCCUPANCIES AND PROVIDING

SETBACK CAPABILITIES TO MAINTAIN ZONE SETPOINTS DOWN TO 55°F OR UP TO 85°F.

c. CONTROLS SHALL BE CAPABLE OF PROVIDING A DEADBAND OF AT LEAST 5°F BETWEEN

HEATING AND COOLING.

d. THERMOSTATS SHALL HAVE NUMERIC SET POINTS IN °F, ADJUSTABLE SETPOINT STOPS,

AND SHALL BE MOUNTED AT 54" ABOVE FINISHED FLOOR.

e. ALL THERMOSTATS SHALL BE APPROVED BY THE OWNER.

17. GAS APPLIANCE VENTING:

a. ACCEPTABLE VENT MATERIALS, ROUTING, DISTANCE AND TERMINATION LOCATIONS

SHALL COMPLY WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND ALL

REQUIREMENTS IN CHAPTER 8 OF THE 2009 IMC.

18. BEFORE STARTING ANY WORK, THE CONTRACTOR FOR THIS SECTION OF THE WORK SHALL

EXAMINE A COMPLETE SET OF DRAWINGS FOR ALL TRADES, INCLUDING ARCHITECTURAL,

STRUCTURAL, HVAC, ELECTRICAL, FIRE PROTECTION AND PLUMBING. DIMENSIONS, SPACE

REQUIREMENTS AND POINTS OF CONNECTION TO ALL EQUIPMENT SHALL BE VERIFIED, AND ANY

MINOR ADJUSTMENTS NECESSARY TO AVOID CONFLICT WITH THE BUILDING STRUCTURE AND

THE WORK OF THE OTHER TRADES SHALL BE MADE. CONTRACTOR SHALL NOTIFY ARCHITECT

IMMEDIATELY IF ANY MAJOR CONFLICTS OCCUR.

19. COORDINATE LOCATIONS OF ALL ROOF AND EXTERIOR WALL OPENINGS WITH ALL RELEVANT

TRADES, AND PROVIDE WATERTIGHT FLASHINGS WHEREVER PENETRATIONS OCCUR. EXACT

LOCATIONS AND SIZES MAY BE DEPENDENT UPON EQUIPMENT SELECTIONS; COORDINATE SIZES

AND LOCATIONS OF ALL OPENINGS WITH APPROPRIATE EQUIPMENT REQUIREMENTS.

20. PERMANENT ACCESS TO EQUIPMENT SHALL BE PROVIDED, AND A MINIMUM OF 30" CLEAR

WORKING SPACE IN FRONT OF ACCESS PANELS TO THE COMPRESSOR, BLOWER ASSEMBLY AND

AIR FILTER SECTION OF THE EQUIPMENT SHALL BE PROVIDED BY GENERAL CONTRACTOR.

21. ALL EQUIPMENT SHALL BE SECURELY FASTENED TO THE BUILDING STRUCTURE WITH CODE

APPROVED VIBRATION ISOLATORS.

22. EACH PIECE OF EQUIPMENT AND ALL SYSTEMS SHALL BE ADJUSTED AND RE-ADJUSTED TO

INSURE PROPER FUNCTION OF ALL CONTROLS, MAINTENANCE OF TEMPERATURE, ADEQUACY OF

FLOWS AND CAPACITIES, ELIMINATION OF NOISE AND VIBRATION, AND SHALL BE LEFT IN PROPER

OPERATING CONDITION.

23. TEST & BALANCING:

a. THE ENTIRE HEATING AND VENTILATING SYSTEM SHALL BE BALANCED BY AN

INDEPENDENT CERTIFIED TEST AND BALANCE COMPANY.

b. 5 COPIES OF THEIR BALANCE REPORTS SHALL BE SUBMITTED TO THE ENGINEER FOR

REVIEW AND APPROVAL. ELECTRONIC DISTRIBUTION PREFERRED.

c. ALL REQUIRED RE-SHEEVING AND ADJUSTING OF EQUIPMENT SHALL BE MADE BY THE

TEST & BALANCE CONTRACTOR.

d. ALL FINAL MEASURED CAPACITIES SHALL BE WITHIN 10% OF THOSE INDICATED ON THE

PLANS.

24. FINAL LOCATION OF GRILLES, REGISTERS & DIFFUSERS SHALL BE PER THE ARCHITECTURAL

PLANS, ELEVATIONS OR AS PER FIELD REQUIREMENTS (UPON ACCEPTANCE BY ARCHITECT).

25. THE GENERAL CONTRACTOR SHALL FURNISH & INSTALL ALL OF THE REQUIRED ACCESS PANELS

IN THE DRYWALL CEILINGS TO GAIN SERVICE ACCESS TO THE EQUIPMENT.

26. ALL EQUIPMENT SHALL BE INSTALLED ACCORDING TO THE MANUFACTURER'S INSTALLATION,

OPERATION & MAINTENANCE MANUAL'S RECOMMENDATIONS ESPECIALLY FOR SERVICE

CLEARANCES.

27. FILTERS:

a. SHALL BE UL RATED AND APPROVED.

b. PRESSURE DROPS SHALL NOT EXCEED .10" STATIC PRESSURE.

28. ELECTRICAL CONNECTIONS:

a. UNLESS OTHERWISE INDICATED ALL MAGNETIC MOTOR STARTERS, THERMAL

OVERLOADS, LOW VOLTAGE THERMOSTATS, CONTROL RELAYS, CONTROL

TRANSFORMERS AND SOLENOID VALVES SHALL BY FURNISHED BY THE MECHANICAL

CONTRACTOR.

b. UNLESS OTHERWISE SPECIFIED, ALL MOTORIZED DAMPERS SHALL BE LOW VOLTAGE.

ALL WIRING AND POWER CONNECTIONS SHALL BE PROVIDED BY THE MECHANICAL

CONTRACTOR.

c. PROVIDE MOTORS AND EQUIPMENT FOR ONLY THOSE CURRENT CHARACTERISTICS

INDICATED ON THE DRAWINGS.

d. IT IS THE INTENT OF THIS DIVISION TO REQUIRE A COMPLETE SYSTEM PER THE

CONTRACT DOCUMENTS.

e. COORDINATE ALL EQUIPMENT REQUIRING ELECTRICAL POWER, REGARDLESS OF

VOLTAGE, WITH OTHER TRADES, SO THAT ALL SYSTEMS ARE COMPLETE AND

OPERATIONAL.

f. ALL THREE PHASE MOTORS SHALL BE PROVIDED WITH PHASE LOSS PROTECTION.

g. ALL SINGLE AND THREE PHASE MOTORS, STARTERS AND DISCONNECTS PROVIDED BY

MECHANICAL CONTRACTOR AND WIRED BY THE ELECTRICAL CONTRACTOR.

29. TEMPORARY HEATING DURING CONSTRUCTION:

a. MECHANICAL EQUIPMENT SHALL NOT BE UTILIZED FOR TEMPORARY HEATING.

b. GAS FIRED TEMPORARY HEAT SHALL BE PROVIDED BY THE GENERAL CONTRACTOR.

of

ww

w.a

ec-va

il.co

m

aP

O B

ox 8

48

9, 4

08

01

U

S H

wy 6

&

2

4, S

te

2

14

, A

vo

n, C

olo

ra

do

, 8

16

20

Mechanical, E

lectrical &

Lighting D

esign S

ervices

Architectural E

ngineering C

onsultants

Telephone: 970-748-8520ce

Drawn By: Checked By:

DATE: ISSUE:

07-02-15BID SET

AEC PROJECT #:

EA

GLE

C

OU

NT

Y A

IR

PO

RT

AD

MIN

IS

TR

AT

IO

N

OF

FIC

E R

EM

OD

EL

GY

PS

UM

, C

O

15050

An O

ffice w

ith LE

ED

™ A

ccredited P

rofessionals

AutoCAD SHX Text
COPYRIGHT 2015 ARCHITECTURAL ENGINEERING CONSULTANTS, INC.
AutoCAD SHX Text
c
Page 11: EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor framing plan framing and foundation details specs, schedules & sequence hvac plan

F

2

F

1

GENERAL NOTES:

1. ALL DUCTWORK DIMENSIONS ARE SHOWN INSIDE TO INSIDE.

2. ALL INTERIOR SUPPLY AND RETURN DUCTWORK SHALL INCLUDE 1" LINER

UNLESS OTHERWISE NOTED. ALL OUTSIDE AIR INTAKE AND ROUND

DUCTWORK SHALL BE WRAPPED WITH 1.5" THICK INSULATION UNLESS

OTHERWISE NOTED.

3. ALL FINAL DUCTWORK CONNECTIONS TO SUPPLY GRILLES (OR PLENUMS)

SHALL BE COMPLETED WITH ACOUSTICAL FLEXIBLE DUCT UNLESS

OTHERWISE NOTED AND A MAXIMUM LENGTH OF FIVE FEET.

4. ALL ROUND DUCT CONNECTIONS TO ROUND DUCTWORK SHALL BE

CONICAL TEES.

5. ALL SQUARE 90 DEGREE ELBOWS SHALL HAVE TURNING VANES.

6. ALL DUCTWORK SHALL BE RUN TIGHT TO UNDERSIDE OF STRUCTURE

WHERE IT EXISTS UNLESS OTHERWISE NOTED.

7. ALL DUCTWORK PASSING THROUGH FIRE-RATED ASSEMBLIES SHALL

INCLUDE FIRE DAMPERS RATED TO MATCH THAT OF THE ASSEMBLY.

8. ALL SUPPLY GRILLES SHALL HAVE AN BALANCING DAMPER UNLESS

OTHERWISE NOTED. IF THE DAMPER IS LOCATED IN AN INACCESSIBLE

LOCATION, CABLE-STYLE DAMPERS (ROTOTWIST OR EQUIVALENT) SHALL

BE INSTALLED AND SHALL BE ADJUSTABLE FROM THE GRILLE FACE.

9. COORDINATE ALL ACCESS PANEL LOCATIONS WITH THE ARCHITECT.

SHEET DETAIL NOTES:

ROUTE TO OUTSIDE AIR TO EXISTING OUTSIDE AIR DUCT IN SPACE.

CAP EXISTING OUTSIDE AIR DUCT WHERE DUCT IS DISCONNECTED

FROM EXISTING EVAPORATIVE COOLER.

TERMINATE FURNACE CONDENSATE DRAINS INDIRECTLY TO NEW

FUNNEL BELOW SINK. CONNECT FUNNEL TO EXISTING WASTE PIPE

SERVING SINK.

TERMINATE WITH WALL TERMINATION KIT (BAYVENT200B). INSTALL

PER MANUFACTURER REQUIREMENTS. MAINTAIN 3' CLEARANCE TO

ANY OPERABLE OPENINGS INTO THE BUILDING AND 10' FROM ANY

MECHANICAL AIR INTAKES. PAINT TERMINATION TO MATCH WALL

COLOR. ENSURE PAINT DOES NOT IMPEDED AIRFLOW.

ROUTE 1" G TO GAS METER. EXISTING GAS PIPING MAY BE REUSED IF

IT IS AT LEAST 1". IF TOTAL DISTANCE EXCEEDS 200', CONTACT

ENGINEER PRIOR TO INSTALLING. ANY ABANDONED GAS PIPE SHALL

BE REMOVED. CONFIRM GAS METER CAN HANDLE AN ADDITIONAL

LOAD OF 50 MBH.

PROVIDE REQUIRED EQUIPMENT CLEARANCES.

ROUTE TO EXISTING GRILLE IN OBSERVATION TOWER FLOOR AND

BALANCE TO 50 CFM (ADJ.).

ROUTE REFRIGERANT PIPING FROM CONDENSING UNIT TO

ASSOCIATED COOLING COIL. SIZE PIPING ACCORDING TO

MANUFACTURER'S REQUIREMENTS.

1

2

12"Ø

12"Ø

10"Ø

8"Ø

8"Ø

6"Ø

6"Ø

6"Ø 9"Ø

10"Ø

12"Ø

6"Ø

8"Ø

6"Ø

8"Ø

8"Ø

6"Ø

E

255-S

24x24

B

255-R

24x24

E

765-R

24x24

E

385-R

24x24

E

380-S

24x24

A

125-S

24x24

E

100-S

24x24

A

105-S

24x24

A

80-S

24x24

A

50-S

24x24

B

140-R

24x24

E

195-S

24x24

E

120-S

24x24

B

100-R

24x24

B

125-R

24x24

B

215-R

24x24

CU

1

CU

2

10"Ø

8"Ø

1

1

T

T

F-1

F-2

FURNACE IN THIS AREA SHALL BE LOWERED

BELOW NEW FLOOR AND MOVED NORTH.

REROUTE FLUE UP AS SHOWN AND ALONG

ROOF TO EXISTING WALL PENETRATION.

SHORTEN SUPPLY DUCT AS NECESSARY.

EF

1

6"Ø

TERMINATE WITH 6" WALL CAP

(SEIHO SX 6 OR EQUIVALENT)

6"Ø12"Ø

12"Ø

10"Ø

12"Ø

16"Ø

12"Ø

16"Ø

10"Ø

14"Ø

6"Ø

M

M

MD

1

MD

2

M

M

MD

3

MD

4

B

70-R

24x24

3

3

3

2" FLUE & COMBUSTION AIR

2" FLUE & COMBUSTION AIR

2" COMBUSTION AIR & 2" VENT,

PROVIDE CONCENTRIC DIRECT

VENT (BAYVENT200B)

COOLING COIL

REFRIGERANT CONNECTION

TO OUTDOOR AIR

CONDENSING UNIT

CONDENSATE ON THE

BOTTOM TO

CONDENSATE AUX. DRAIN

PAN

CONDENSATE DRAIN TO

CONDENSATE AUX. DRAIN PAN

GAS FURNACE

1

2

" GAS CONNECTION

RETURN AIR

SUPPLY AIR

GAS FURNACE HORIZONTAL FLOW DETAIL

NO SCALE

NEOPRENE MOUNTING

BUSHING

ANCHOR TO BAR JOIST

S

FLUID DETECTION SENSOR

AUXILIARY DRAIN PAN

ROUTE DRAIN DOWN INTO AND THRU WALL. DISCHARGE INDIRECTLY

INTO WASTE LINE.

INSULATED RIGID DUCT

AIR

F

LO

W

CLAMP

MANUAL DAMPER,

HANDLE, & LOCK NUT

WORM DRIVE S.S.

Ø TWIST-IN FITTING W/

INSULATED RIGID DUCT

AIR

F

LO

W

CLAMP

MANUAL DAMPER,

HANDLE, & LOCK NUT

WORM DRIVE S.S.

Ø TWIST-IN FITTING W/

ROUND DUCT TAKE-OFF DETAIL

NO SCALE

EXISTING EXHAUST

TO REMAIN

EXISTING EXHAUST

TO REMAIN

TYPICAL LOW PRESSURE

GAS CONNECTION DETAIL

NO SCALE

GAS SHUT

OFF VALVE

TYP.

LOW

PRESSURE

GAS LINE

6" MIN.

DRIP LEG

MECHANICAL

EQUIPMENT

NOTE:ALL EXISTING SUPPLY AND RETURN DUCTWORK SHALL

BE REMOVED. EXISTING EVAPORATIVE COOLER AND FURNACE

SHALL BE REMOVED. EXISTING OUTSIDE AIR DUCT CURRENTLY

SERVING EXISTING EVAPORATIVE COOLER SHALL REMAIN AND

SUPPLY OUTSIDE AIR TO THE NEW FURNACES AS SHOWN.

4

4

2

3

4

" G

3

4

" G

5

5

5

5

5

6"Ø

6

6

CC

2

CC

1

7

7

7

7

7

of

ww

w.a

ec-va

il.co

m

aP

O B

ox 8

48

9, 4

08

01

U

S H

wy 6

&

2

4, S

te

2

14

, A

vo

n, C

olo

ra

do

, 8

16

20

Mechanical, E

lectrical &

Lighting D

esign S

ervices

Architectural E

ngineering C

onsultants

Telephone: 970-748-8520ce

Drawn By: Checked By:

DATE: ISSUE:

07-02-15BID SET

AEC PROJECT #:

EA

GLE

C

OU

NT

Y A

IR

PO

RT

AD

MIN

IS

TR

AT

IO

N

OF

FIC

E R

EM

OD

EL

GY

PS

UM

, C

O

15050

An O

ffice w

ith LE

ED

™ A

ccredited P

rofessionals

NORTH

HVAC PLAN

SCALE: 1/4" = 1'0"

AutoCAD SHX Text
printer
AutoCAD SHX Text
files
AutoCAD SHX Text
files
AutoCAD SHX Text
files
AutoCAD SHX Text
files
AutoCAD SHX Text
files
AutoCAD SHX Text
key system
AutoCAD SHX Text
gasboy
AutoCAD SHX Text
files
AutoCAD SHX Text
A
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
5
AutoCAD SHX Text
1
AutoCAD SHX Text
4
AutoCAD SHX Text
5
AutoCAD SHX Text
B
AutoCAD SHX Text
D
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
C
AutoCAD SHX Text
DN.
AutoCAD SHX Text
DECK
AutoCAD SHX Text
CONFERENCE ROOM
AutoCAD SHX Text
BADGING
AutoCAD SHX Text
ELECTRICAL ROOM
AutoCAD SHX Text
KITCHENETTE
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
STAIR 2
AutoCAD SHX Text
ASST. AVIATION DIRECTOR (CHRIS)
AutoCAD SHX Text
ADMIN. MGR. (ERIN)
AutoCAD SHX Text
AVIATION DIRECTOR (GREG)
AutoCAD SHX Text
RECEPTION
AutoCAD SHX Text
MARKETING
AutoCAD SHX Text
ADMIN. ASST. (JANET)
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
MEN'S TOILET ROOM
AutoCAD SHX Text
WOMEN'S TOILET ROOM
AutoCAD SHX Text
STAIR 1
AutoCAD SHX Text
OPEN TO BELOW
AutoCAD SHX Text
OPERATIONS MANAGER (ALEX)
AutoCAD SHX Text
CHASE
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
PROJECT COORDINATOR (JEFF)
AutoCAD SHX Text
DN.
AutoCAD SHX Text
5/8" FROM EDGE OF LANDING
AutoCAD SHX Text
COPYRIGHT 2015 ARCHITECTURAL ENGINEERING CONSULTANTS, INC.
AutoCAD SHX Text
c
Page 12: EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor framing plan framing and foundation details specs, schedules & sequence hvac plan

equipment, etc. furnish by mechanical - refer to both electrical and

electrical apparatus as shown on single line diagram and

and mechanical drawing for scope and work and additinal infor-

Complete connection of HVAC/Plumbing motor(s), water heater(s),

Fire alarm system will be by electrical contractor.

Complete provision, installation and connection of lighting fixtures,

exit signs and lamps as specified and as shown on drawings.

Complete branch circuit wiring required for the connection of

emergency lighting and exit signs to existing emergency stand

Complete feeder(s) installation as required for new and/or

devices, new control devices, etc. for a complete lighting and

including new panelboards, new conduits, new wires, new wiring

Complete wiring system for new lighting and power as shown,

contract. Electrical work shall include, but not limited to, these major

as indicated on drawing and as specified, as necessary to complete the

SCOPE: Furnish all materials and labor required to execute this work

2.

3.

4.

6.

5. Provide grounding and bonding Facilities.

Complete all electrical demolition as required.

mation.

A.

ELECTRICAL SPECIFICATIONS

1.

drawings.

by power system.

and power system.

b.

a.

items:

A. Contractor shall submit shop drawings for engineer review and approval.

MC cable permitted per local codes. Run hard pipe from panel to local

Lighting fixtures.

Shop drawing submittal shall include:

Panelboard(s).

CONDUIT AND WIRE:

B.

13.

A.

B.

2.

1.

and contractor shall have written approvals from building owner prior

Core drilling and patching of existing building structure required for

Operating, Maintenance and identification instructions manuals, if

electrical work. Core drilling shall follow Building Standard procedures

Applicable codes: National Electric Code (2014)

PERMITS AND FEES: Obtain and pay for all necessary permits, inspec-

tions, examinations and fees or charges necessary for execution and

and to the requirements of Federal, State or other City agencies

Town of Gypsum Electrical Code, pertinent NFPA publications

Conform to the prevailing edition and amendments thereto of the

SHOP DRAWINGS AND SUBMITTAL:

to start of any work.

Test of entire system and work.

REGULATIONS AND CODES:

having jurisdiction.

completion of electrical work.

12.

11.

A.

7.

9.

8.

10.

any.

THE NEW FIRE LIFE SAFETY EQUIPMENT REQUIRED FOR THIS CONTRACT

SHALL BE BY THE SAME MANUFACTURER. ALL FIRE LIFE SAFETY SYSTEM

COMPONENT, EQUIPMENT, DEVICES, ETC. LESS WIRING PROVIDED IN THIS

CONTRACT SHALL BE COMPATIBLE FOR SAID ALARM EQUIPMENT USED AT

THE SITE, AND BE BOTH CFM AND U.L. LISTED FOR SAME.

CONTRACTOR SHALL SUBMIT UNIT PRICES ON F.A. EQUIPMENT AND DEVICES

PRIOR TO BID, CONTRACTOR SHALL VERIFY NEW FIRE LIFE

SAFETY INSTALLATION AND INCLUDE ALL LABOR AND MATERIAL REQUIRED

FOR A COMPLETE AND OPERABLE LIFE SAFETY AND SMOKE CONTROL

SUPPLY & INSTALL NEW EQUIPMENT AND MODIFICATIONS TO EXISTING FIRE ALARM

PROVIDE ALL COSTS FOR LABOR, DESIGN, ENGINEERING,

SYSTEM TO PROVIDE A COMPLETE FIRE ALARM SYSTEM TO MEET LOCAL CODES.

ALL NEW FIRE ALARM EQUIPMENT, DEVICES, WIRING, ETC. REQUIRED AND

WHICH ARE INSTALLED FOR THE FACILITY SHALL MEET

LATEST EDITION OF THE NFPA FIRE LIFE SAFETY CODES AND SHALL MEET

ALL CITY AND STATE FIRE MARSHALL REQUIREMENTS.

THE FIRE ALARM SYSTEM SCOPE OF WORK SHALL INCLUDE, BUT NOT

NECESSARILY BE LIMITED TO THE FOLLOWING:

CALCULATIONS, SHOP DRAWING, ETC. INCLUDING SUBMISSION OF FINAL

FIRE ALARM LIFE SAFETY DRAWING TO THE AUTHORITY HAVING

JURISDICTION FOR REVIEW AND APPROVAL.

PROVIDE ALL COSTS FOR LABOR, MATERIAL, INSTALLATION,

CONNECTION AND EXECUTION OF FIRE LIFE SAFETY ALARM EQUIPMENT,

DEVICES, CONDUIT/WIRING SYSTEM, ETC. AS REQUIRED DUE TO THE

CONSTRUCTION OF THIS FACILITY.

IN THEIR BID.

SYSTEM(S).

3.

2.

B.

A.

1.

ALARM DEVICE LOCATIONS & QUANTITIES PRIOR TO FINAL ROUGHIN.

WITH THE AUTHORITY HAVING JURISDICTION TO DETERMINE FINAL FIRE

AND ARE DIAGRAMMATIC ONLY. THE CONTRACTOR SHALL WALK THROUGH

DRAWINGS HAVE BEEN DEVELOPED FOR BIDDING AND PRICING PURPOSES

4.

WHEN PERMITTED BY THE AUTHORITY HAVING JURISDICTION, COORDINATE WITH

PAINTER TO FINISH THE CEILING MOUNTED SMOKE DETECTORS TO MATCH

RESPECTIVE CEILINGS. REFER TO MANUFACTURER'S INSTRUCTIONS

REGARDING ADDITIONAL FINISHES TO THE SPECIFIC PRODUCT.

5.

N. All cabling shall be bundled and properly secured and terminated.

warranty period shall begin at the point of system acceptance or beneficial

system during this warranty period at no additional cost to the owner. The

free of defects of workmanship or products and will inspect and repair the

from the date of project completion. The contractor warrants the system to be

O. The warranty set forth for this system shall consist of a full three (3) years

use, whichever comes later.

Coordinate numbering scheme with owner.

enclosed within cable trays, raceways or conduit, as specified.

engineer. Cabling shall be in the wall, above the ceiling or where exposed,

M. No exposed wiring will be accepted unless approved in writing by the

Care must be taken to ensure cables are not kinked, bent beyond limit,

including NEC, EIA/TIA 568,569 and 606, and federal, state and local codes.

familiar and install in accordance with all applicable codes and standards,

L. All cable hangers shall be no more than 48" apart. Contractor shall be

Cables are to be kept a minimum of 6" from power lines, electric motors,

K. Cable bends shall be no less than eight times the cable diameter or 1.00".

termination. No more than .5 inches of exposed untwisted pairs shall be

the extent in which each twisted pair is unraveled at the point of its physical

J. All connections of twisted wiring shall be made in such a way as to minimize

length of the run. Splices and bridge taps with cabling are strictly prohibited.

Cabling shall be free from tension at both ends, as well as through out the

I. All wiring shall be protected from moving mechanical or physical contacts.

cable runs exceeding 90 meters and provide solution to meet the 90 meter

H. Route cables so as not to exceed 90 meters in length. Bidder will identify any

the case of "hard" drywall ceilings, adequate support shall be accomplished

independent hangers. Cable "draped" across ceiling tiles is unacceptable. In

G. All cable above the ceiling must be tied and properly supported with

F. Provide plenum rated cable when required by article NEC 300-22.

overloaded, over-cinched, crushed, improperly untwisted, etc.

fluorescent fixtures or heat generating devices.

present at these locations.

Wiring is to be run in cable tray and conduit where specified.

requirement.

where reasonably possible.

patch panel location, and each wall/floor faceplate that has wiring installed.

E. All cables will be labeled with self-laminating labels at each cable end, at each

jacks, match faceplates to power, color coded for voice and data, match to

modular RJ-45, 8 pin, 8 conductor, Hubbell, Leviton, or lucent or equivalent

C. The terminations at the station locations must be Category 6, T568B (AT&T)

B. Data cable will be colored blue. Voice cable will be colored white.

manufacturers include: Berk-Tek, Belden, Lucent or equivalent.

500 Mhz or better category 6, 4 pair UTP as applicable. Acceptable

A. The cabling for voice and data must be continuous, home run, non-spliced,

D. Wall mounted patch panels will be provided.

cable. Outlets will be securely held in place.

B. Cat 6 Wiring Requirements

6.

A. General Requirements

C. Fire Life Safety Scope of Work

& General Conditions

PROVIDE PLENUM RATED CABLE WHEN REQUIRED BY ARTICLE NEC 300-22.

14.

decora style. Finish per owner or architect.

Convenience receptacles will be 20 amp, commercial grade

Light switches will be 20 amp, commercial grade,B.

ELECTRICAL DEVICES

A.

decora style. Finish per owner or architect.

Provide decora style, finish per owner or architect.

Dimming switches will be a minimum of 600w or as noted.C.

15.

Support all electrical equipment independent of accessible ceilings as

required by NEC.

SUPPORT

A.

All mounting heights will conform to ADA guidelines. Typical receptacleD.

heights will be +18"AFF and switch heights will be +46"AFF

unless noted otherwise.

16.

At fire rated wall space electrical boxes at opposite sides of the wall

no less than 24" horizontal distance.

ELECTRICAL BOXES

A.

When phone, TV & power receptacles are shown on plan next to each other.

Locate respective receptacles next to each other on site with no more

B.

than 1" seperating cover plates.

Provide GFI type receptacles at kitchens, bathrooms,

garages, exterior etc. as required by code.

E.

ACCEPTABLE FIRE ALARM SYSTEM MANUFACTURERS ARE SIMPLEX, NOTIFIER,

SILENT KNIGHT & FIRELITE. FIRE ALARM SYSTEMS MUST HAVE PARTS AND SERVICE

AVAILABLE WITHIN 24 HOURS.

7.

8.

H/P HEAT/PHOTOELECTRIC SMOKE DETECTOR

ELECTRICAL LEGEND

(NOT ALL SYMBOLS REQUIRED FOR THIS PROJECT)

RECESSED OR SURFACE DOWNLIGHT

WALL MOUNTED LIGHT FIXTURE

RECESSED FLUOR. LIGHT FIXTURE

SURFACE FLUOR. LIGHT FIXTURE

Aa

Aa

FIXTURE DESIGNATIONS:

UPPER CASE - FIXTURE TYPE

LOWER CASE - SWITCH DESIGNATION

SHADING ON FIXTURE INDICATES EMERG. BATTERY BACKUP

FLUORESCENT STRIP FIXTURE

TRACK LIGHT AS NOTED OR SCHEDULED

WALL WASHER

POLE-MOUNTED FIXTURE

POST (BOLLARD) FIXTURE

CEILING OR WALL MOUNTED EXIT LIGHT

EMERGENCY BATTERY LIGHTS

DUPLEX RECEPTACLE @ 18" UNLESS NOTED

DOUBLE DUPLEX RECEPTACLE @ 18" UNLESS NOTED

SPECIAL OUTLET AS NOTED

FLUSH FLOOR DUPLEX RECEPTACLE

DUPLEX RECEPTACLE HALF-SWITCHED @ 18" UNLESS NOTED

TELE-POWER POLE

JUNCTION BOX IN FLOOR, CEILING OR IN WALL

MULTI-OUTLET PLUG STRIP

COMPUTER/TELEPHONE OUTLET IN FLOOR OR WALL

CONDUIT RUN CONCEALED IN WALL OR ABOVE CEILING

TELEPHONE BACKBOARD

CIRCUIT HOMERUN

CONDUIT RUN BELOW FLOOR OR GRADE

CONDUIT STUB-UP - CAP & MARK

LIGHT SWITCH AT 46" UNLESS NOTED

SUBSCRIPTS:

2 = 2-POLE SWITCH

3 = 3-WAY SWITCH

4 = 4-WAY SWITCH

K = KEY-OPERATED SWITCH

TO = THERMAL OVERLOAD SWITCH

P = SWITCH WITH PILOT LIGHT

DIMMER SWITCH W/ WATTAGE

MAGNETIC MOTOR STARTER

DISCONNECT SWITCH

TRANSFORMER

GROUND

PUSHBUTTON CONTROL STATION

PHOTOELECTRIC CELL

TIME SWITCH

THERMOSTAT AT 60" UNLESS NOTED

DIVISION 15 EQUIPMENT

CIRCUIT BREAKER

MOTOR OUTLET

AUTOMATIC TRANSFER SWITCH

FOOD SERVICE EQUIPMENT

PC

TS

T

ABBREVIATIONS

- ABOVE COUNTERAC

AFF - ABOVE FINISHED FLOOR

- ABOVE FINISHED GRADEAFG

- ALUMINUMAL

- EMERGENCYEM

- GROUNDGND

- GROUND FAULT INTERRUPTERGFI

NIC - NOT IN CONTRACT

NL - NIGHT LIGHT

NTS - NOT TO SCALE

UG - UNDERGROUND

WP - WEATHER PROOF

XFMR - TRANSFORMER

+18" - MOUNTING HEIGHT TO CENTERLINE

OF DEVICE AFF OR AFG

FIRE ALARM SYSTEM

FIRE ALARM CONTROL PANEL

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM PULL STATION

ALARM HORN OR SPEAKER

COMBINATION HORN/STROBE OR SPEAKER/STROBE

THERMAL HEAT DETECTORH

SMOKE/IONIZATION DETECTORI

PHOTOELECTRIC SMOKE DETECTORP

DUCT DETECTOR

SPRINKLER SYSTEM FLOW SWITCH

SPRINKLER SYSTEM TAMPER SWITCH

STROBE

SMOKE/FIRE DAMPER CONNECTION

REMOTE INDICATOR LIGHT

COMMUNICATION SYSTEM

SPEAKER IN CEILING OR WALL

VOLUME CONTROL AT 60" UNLESS NOTED

MICROPHONE OUTLET IN FLOOR BOX OR WALL

CALL-IN SWITCH

PROGRAM BELL

INTERCOM

CLOCK

AMPLIFIER

TELEVISION OUTLET

CONTACT DOOR SWITCH IN JAMB OR HINGE

SECURITY SYSTEM

KEY-OPERATED ACCESS SWITCH

SURVEILLANCE CAMERA

DISTRIBUTION EQUIPMENT SYMBOLS

DISCONNECT SWITCH

FUSES

CIRCUIT BREAKER

CURRENT TRANSFORMER

TRANSFORMER

METER

CU - COPPER

STEP LIGHT

FACP

M = MOTION-OPERATED SWITCH

POP-UP RECEPTACLE

- ELECTRICAL CONTRACTOREC

- AUTHORITY HAVING JURISDICTIONAHJ

- MECHANICAL CONTRACTORMC

- PLUMBING CONTRACTORPC

UTP - UNSHIELDED TWISTED PAIR

- GENERAL CONTRACTORGC

- REFERENCEREF

junction box, and run MC cable from junction box to device.

1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY

SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL

U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND

SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED

ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102

MM) LUMBER SPACED 16 IN. (406 MM) OC WITH NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES

AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM) WIDE BY 1-3/8 IN. (35 MM) DEEP

CHANNELS SPACED MAX 24 IN. (610 MM) OC.

B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE

OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER

TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES

DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 26 IN. (660 MM).

2. THROUGH PENETRANT - ONE CONDUIT INSTALLED EITHER CONCENTRICALLY OR

ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR

TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN. (0 MM) (POINT CONTACT) TO MAX 2 IN. (51

MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.

THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN. (102 MM) DIAM

(OR SMALLER) STEEL ELECTRICAL METALLIC TUBING

3. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. 1-1/4,1-7/8 AND 2-1/2 IN.

(16, 32, 48 AND 64 MM) THICKNESS OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES,

RESPECTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. MIN 1/4 IN. (6 MM)

DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT CONTACT

LOCATION ON BOTH SIDES OF WALL.

THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING

OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE.

THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE

PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED,

AS TABULATED TO THE LEFT.

3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT,

*BEARING THE UL CLASSIFICATION MARKING

PENETRATION THROUGH A FIRE-RATED WALL

T

18

"(1

'6

")

46

"(3

'1

0")

48

"(4

'-0

")80

"(6

'8

")

TYPICAL DEVICE

MOUNTING HEIGHTS

MAIN CIRCUIT BREAKER &

BRANCH CIRCUIT BREAKERS

MAXIMUM MOUNTING HEIGHT

IS 79", MINIMUM IS 18".

THE ELECTRICAL CONTRACTOR WILL PROVIDE A WALK THROUGH WITH THE

OWNER/ARCHITECT PRIOR TO FINAL ROUGHIN AS FOLLOWS:

CONFIRM ALL LOCATIONS FOR LIGHT SWITCHES; ADD THREE WAYS IF

FOUND NECESSARY.

REVIEW RECEPTACLE LOCATIONS; MOVE AS REQUIRED. PROVIDE

UNIT PRICING IF ADDITIONAL RECEPTACLES ARE REQUIRED.

REVIEW RECEPTACLE LOCATIONS AT COUNTERS AND CONFIRM IF

THOSE RECEPTACLES SHOULD BE ABOVE COUNTER OR BELOW. MOVE

AS REQUIRED.

IN GENERAL CONFIRM POWER AND LIGHTING REQUIREMENTS. THE

ELECTRICIAN SHOULD BE PREPARED TO REWORK SOME DEVICE LOCATIONS.

SIGNIFICANT REWORK SHOULD BE FLAGGED AND UNIT PRICING PROVIDED

AND WRITTEN AUTHORIZATION FOR ADDITIONAL COSTS APPROVED PRIOR

TO PROCEEDING.

+80"AFF

P

+80:AFF

TELEPHONE ONE-

LINE DIAGRAM

TELEPHONE/

COMPUTER ROUGHIN

FIRE ALARM CONTROL PANEL

H

P

NO SCALE

NOTES:

1. ALL WIRE WILL BE SHIELDED. WIRING PER MANUFACTURERS REQUIREMENTS.

2. REFERENCE FLOOR PLANS FOR QUANTITIES.

3. PROVIDE PLENUM RATED WIRE WHERE REQUIRED.

4. FIRE ALARM SYSTEM IS SHOWN AS A DESIGN BUILD SYSTEM. FINAL DESIGN AND

DEVICE QUANTITIES ARE BY THE ELECTRICAL CONTRACTOR.

CONDUCTOR SIZES AND TYPES: For sizes #1/0 AWG and larger, use

coppper THW or aluminum XHHW. For sizes #1 AWG and smaller, use only

copper wire with 600V insulation, types TW, THHN, or THW - stranded in

sizes #8 and larger, solid in sizes #10 and smaller. Control wiring shall be #14,

stranded. Use type THHN for wires entering or passing through fluorescent

lighting fixtures. All motors shall be wired with copper conductors only.

UNO - UNLESS NOTED OTHERWISE

EXTERIOR

HORN

MIN.

#14AWG

FAN

SHUT

OFF

.23A 24VDC

ADA HORN/

STROBE MAX.

15 PER CIRCUIT

ROUTE WIRE AT CEILING PARALLEL OR

PERPENDICULAR TO STRUCTURE. SECURE

TO STRUCTURE AT 4' INTERVALS OR LESS.

STUB UP TO ABOVE

ACCESSIBLE CEILNG

STRUCTURED CABLE

DISTRIBUTION PANEL

(2#CAT 6) 3/4"C

PLENUM RATED WIRE

WHEN REQUIRED

(2) RJ-45 IN

SINGLE

GANG BOX

COLD WATER PIPE

NOT TO SCALE

NOTES:

1. HEIGHTS SHOWN ARE TYPICAL TO CENTERLINE OF BOX

UNLESS NOTED OTHERWISE.

2. DEVICES ABOVE DOORS SHALL BE CENTERED BETWEEN TOP

OF DOOR TRIM AND CEILING LINE.

3. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS

AND NOTED ON ELECTRICAL FLOOR PLANS SHALL GOVERN

OVER THOSE SHOWN ABOVE.

4. FOR CEILING HEIGHTS HIGHER THAN 7'2", INSTALL FIRE ALARM

NOTIFICATION AUDIO AND VISUAL APPLIANCES AT 80"AFF

OTHERWISE INSTALL AT 6" BELOW CEILING.

5. MOUNTING HEIGHTS PER IBC 2009 AND ADA CODES

MAIN TELE/DATA

ROOM

(PULLWIRE)4"C

120V, 1P

BATTERY

BACKUP

DIALER

TELEPHONE

NOT TO SCALE

NO SCALE

FINISHED FLOOR

TYPICAL 8'0" CEILING

Provide tamper proof receptacles at all residential

areas as required by code.

F.

DEMOLITION NOTES:

1. THE ELECTRICAL CONTRACTOR SHALL REMOVE ALL WIRING DEVICES,

LIGHT FIXTURES, ETC., WHICH ARE INDICATED TO BE REMOVED. IN

GENERAL, SYMBOLS WHICH ARE SHOWN ON DEMOLITION PLANS

INDICATE DEVICES WHICH ARE EXISTING, AND WHICH ARE TO REMAIN.

SYMBOLS WHICH ARE SHOWN ON THE PLANS AND WHICH HAVE AN (R)

ADJACENT, INDICATE DEVICES TO BE REMOVED. SYMBOLS WHICH ARE

SHOWN ON THE PLANS AND WHICH HAVE AN (E) ADJACENT, INDICATE

DEVICES THAT ARE EXISTING AND SHALL REMAIN, RE-WORK MY BE

NECESSARY TO CONNECT TO NEW CIRCUIT OR PROVIDE NEW

CONNECTION AS SHOWN IN NEW POWER PLANS. SEE RESPECTIVE

LIGHTING OR POWER PLANS. DEVICES WHICH ARE TO BE REMOVED MAY

REQUIRE REWORKING CONDUIT AND WIRING IN ORDER TO MAINTAIN

SERVICE TO OTHER DEVICES. REMOVED DEVICES SHALL BE PATCHED

OVER AND PAINTED TO MATCH, INCLUDE ALTERNATE PRICING TO

PROVIDE BLANK FACEPLATES INSTEAD OF PATCHING

2. WHERE REMODELING INTERFERES WITH CIRCUITS IN AREAS WHICH ARE

OTHERWISE UNDISTURBED, CIRCUITS SHALL BE REWORKED AS

REQUIRED.

3. EXISTING DEVICES AND CIRCUITING WHICH ARE SHOWN ARE INDICATED

ONLY FOR INFORMATIONAL PURPOSES. THE ELECTRICAL CONTRACTOR

SHALL VISIT THE SITE AND SHALL VERIFY CONDITIONS AS THEY EXIST

AND SHALL REMOVE, RELOCATE AND/OR REWORK ANY ELECTRICAL

EQUIPMENT OR CIRCUITS AFFECTED (WHETHER INDICATED OR NOT) DUE

TO REMOVAL OR REWORKING OF EXISTING WALLS, CEILINGS, ETC. THE

ELECTRICAL CONTRACTOR SHALL FAMILIARIZE HIMSELF WITH ALL WORK

TO BE DONE BY OTHER TRADES BY STUDYING THE ARCHITECTURAL,

STRUCTURAL, MECHANICAL, AND PLUMBING DRAWINGS.

4. COORDINATE THE ROUTING OF ALL CONDUITS WITH THE MECHANICAL

AND PLUMBING CONTRACTORS IN ORDER TO AVOID CONFLICTS WITH

DUCTS, PIPES, ETC.

5. ALL EQUIPMENT, LUMINAIRES, DEVICES, ETC., WHICH ARE REMOVED,

SHALL BE DELIVERED TO THE OWNER FOR DISPOSITION. ALL ITEMS

WHICH ARE REMOVED AND NOT WANTED BY THE OWNER AND WHICH

ARE NOT REUSED SHALL BECOME THE PROPERTY OF THE CONTRACTOR

AND SHALL BE REMOVED FROM THE SITE.

6. THE COST OF CUTTING AND PATCHING NECESSARY FOR THE

INSTALLATION OR REMOVAL OF ELECTRICAL WORK SHALL BE INCLUDED

IN THE ELECTRICAL CONTRACT. COORDINATE WITH THE GENERAL

CONTRACTOR.

7. THE ELECTRICAL CONTRACTOR SHALL REMOVE AND REPLACE LIGHTING

FIXTURES, REWORK, RELOCATE OR REPLACE CONDUIT AND WIRING, AND

DO OTHER WORK REQUIRED BY THE INSTALLATION OF NEW DUCTWORK,

PIPING, ETC., ABOVE EXISTING CEILING. COORDINATE WITH OTHER

CONTRACTORS AND VERIFY THE EXTENT OF THE WORK.

8. ALL LIGHT FIXTURES WHICH ARE INDICATED TO BE RELOCATED SHALL BE

CLEANED, RELAMPED WITH F40WW LAMPS AND RELOCATED IN LOCATION

INDICATED ON ELECTRICAL DRAWINGS.

9. THE ELECTRICAL CONTRACTOR SHALL OBTAIN WRITTEN AUTHORIZATION

FROM THE OWNER (30) CALENDAR DAYS PRIOR TO ANY OUTAGE.

of

ww

w.aec-vail.com

M

echa

nica

l, E

le

ctrica

l &

L

igh

ting

D

esign

S

ervice

s

Architectural E

ngineering C

onsultants

Tele

pho

ne: 97

0-74

8-8

520

Drawn By: Checked By:

DATE: ISSUE:

07-02-15BID SET

AEC PROJECT #:

EA

GLE

C

OU

NT

Y A

IR

PO

RT

AD

MIN

IS

TR

AT

IO

N

OF

FIC

E R

EM

OD

EL

GY

PS

UM

, C

O

15050

An Office with LEED™ Accredited Professionals

Page 13: EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor framing plan framing and foundation details specs, schedules & sequence hvac plan

T

UTILITY

TRANSFORMER

PAD MOUNTED

NO SCALE

NOTE: PROVIDE SHORT CIRCUIT BRACING TO MEET REQUIREMENTS NOTED

AT ONE-LINE, NOTED AS "AIC AVAILABLE". SERIES RATED COMBINATION

ACCEPTABLE, SUBMIT MANUFACTURER'S SERIES RATINGS WITH SHOP

DRAWING REVIEW.

PANEL R1

(1-42)

PANEL R1

(43-84)

100/3

(4 #1 CU, 1 #4 CUG) 2"C

OR (4 #1/0 MCM AL, 1 #2 ALG) 3"C

PANEL

R1A

100/3

PANEL

R1B

HOLY CROSS METER# 95920

MAXIMUM DEMAND OF 37.6KW

MEASURED ON JAN 2014.

NEW WORK

IS CLOUDED

100/3

TVSS

CURRENT TECHNOLOGY

XN100-120/208-3GY

OR EQUIVALENT

400/3

400A FUSES

of

ww

w.aec-vail.com

M

echa

nica

l, E

le

ctrica

l &

L

igh

ting

D

esign

S

ervice

s

Architectural E

ngineering C

onsultants

Tele

pho

ne: 97

0-74

8-8

520

Drawn By: Checked By:

DATE: ISSUE:

07-02-15BID SET

AEC PROJECT #:

EA

GLE

C

OU

NT

Y A

IR

PO

RT

AD

MIN

IS

TR

AT

IO

N

OF

FIC

E R

EM

OD

EL

GY

PS

UM

, C

O

15050

An Office with LEED™ Accredited Professionals

Page 14: EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor framing plan framing and foundation details specs, schedules & sequence hvac plan

GENERAL NOTES:

1. COORDINATE LOCATION OF ALL MECHANICAL EQUIPMENT WITH

MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN. COORDINATE

CONNECTION SIZE WITH MANUFACTURER PRIOR TO ROUGH-IN.

2. ALL DEVICES ARE LOCATED AT +18" AFF UNLESS NOTED OTHERWISE.

3. RE-USE EXISTING JUNCTION BOXES AND CONDUITS IF POSSIBLE.

OUTLETS TO BE REMOVED OR RE-WORKED ARE SHOWN. FOR REMOVED

OUTLETS, CUT AND CAP ALL ABANDONED CONDUCTORS AND CONDUITS

AT PANELS AND PROVIDE BLANK FACEPLATE TO COVER ANY ABANDONED

OUTLETS. RE-WORKED OUTLETS SHALL REMAIN IN EXISTING LOCATIONS,

AND RE-CIRCUIT OR RE-CONNECT AS SHOWN ON PLANS.

SHEET DETAIL NOTES:

PROVIDE CONNECTION FOR PRE-WIRED DESK WORKSTATIONS.

COORDINATE CONNECTION TYPE WITH DESK MANUFACTURER PRIOR

TO ROUGH-IN.

EXISTING OUTLET OR DATA WILL BE UN-USED, NOTED DEVICES AND

WIRING SHALL BE REMOVED AND PATCHED AS NECESSARY.

EXISTING OUTLET SHALL BE RE-WORKED, UPDATE CONNECTION AND

CIRCUITING AS SHOWN ON NEW POWER PLANS.

EXISTING PHONE AND DATA CONNECTION SHOWN IS THROUGH OPEN

WALL WITH BARE WIRE, AND DOES NOT HAVE RJ-45 CONNECTION OR

FACEPLATE. ANY NEW DATA CONNECTIONS SHALL NOT BE THROUGH

THE OPEN WALL, AND WILL INCLUDE FACEPLATES.

EXISTING JUNCTION BOX IS FITTED WITH A BLANK FACEPLATE, UNLESS

OTHERWISE NOTED ALL UN-USED DEVICES SHALL BE REMOVED AND

PATCHED WITH DRYWALL.

LOCATE NEW PANEL R1B IN ELECTRICAL ROOM, ADJACENT TO PANEL

R1A IF THERE IS ADEQUATE SPACE. IF ADEQUATE SPACE IS NOT

AVAILABLE LOCATE IN NEW KITCHEN WALL.

1

AC

MW

AC

GFI

AC

GFI

AC

COFFEE

1

R1B-12

R1B-14

R1B-10

R1B-18,20,22

R1B-24

R1B-26

R1B-28

R1B-30

R1B-32

R1B-16

R1B-2

R1B-4

R1B-6

R1B-8

1

1

1

TV

+60"AFF

AREA WILL

REMAIN AS

EXISTING

R1

R1A

2

(E)

(E)

(E)

3

3

3

3

+5'AFF

+5'AFF

+4'AFF

+4'AFF

+5'AFF

(R)

(R)

+4'AFF

+5'AFF

4

4

5

2

3

3

5

(E)(E)

(E)

(E) (R)

(R)

(R)

(R)

(R)

(R)

3

(E)

(E)

(E)

(E)

AC

GFI

COFEE

UC

FRIDGE

AC

GFI

MW

AC

(E)

(E)

(E)

(E)

3

(E)

(E)

(E)

(E)

(R)

3

3

2

2

2

(R)

(R)

(R)

(R)

(R)

(R)

(R)

(R)

(R)

(R)

(R)

(R)

(R)

(R)

(R)

(R)

2

2

2

2

3

(R) (E) (R) (R)

2 2

2

(R)(R)

(R)

(R)

2

3

(R) (R)

(E)

52

2

2

2

2

2

2

3

5

2

(R)

5

(R)

5

(R)

2

3

3

2

2

2

AC

3

3

3

3

3

FRIDGE

3

3

3

(E)

(E)

3

(E)

(E)

(E)

(E)

3

(E)

3

F

2

F

1

CU

1

CU

2

R1B-1,3

TO

TO

R1B-7,9

R1B-5

R1B-11

R1B

6

6

of

ww

w.aec-vail.com

M

echa

nica

l, E

le

ctrica

l &

L

igh

ting

D

esign

S

ervice

s

Architectural E

ngineering C

onsultants

Tele

pho

ne: 97

0-74

8-8

520

Drawn By: Checked By:

DATE: ISSUE:

07-02-15BID SET

AEC PROJECT #:

EA

GLE

C

OU

NT

Y A

IR

PO

RT

AD

MIN

IS

TR

AT

IO

N

OF

FIC

E R

EM

OD

EL

GY

PS

UM

, C

O

15050

An Office with LEED™ Accredited Professionals

NORTH

NEW POWER & SYSTEMS PLAN

SCALE: 1/4" = 1'0"

NORTH

DEMOLITION POWER & SYSTEMS PLAN

SCALE: 1/4" = 1'0"

Page 15: EXISTING & PROPOSED FLOOR PLANS A-3 EXISTING RC PLAN ... keyplan and legend partial roof and floor framing plan framing and foundation details specs, schedules & sequence hvac plan

A

A

A A

A

A

A

A

A

AA

AAAA

A A A A

AAA

AA A

PP

P

P

P

P

P

P

M

M

B

BB

B

B

SWITCHING

SHALL

REMAIN AS

EXISTING

AREA WILL

REMAIN AS

EXISTING

REUSE

EXISTING

SWITCHING

B

C

D

AREA WILL

REMAIN AS

EXISTING

E

E

SWITCHING

SHALL

REMAIN AS

EXISTING

P

of

ww

w.aec-vail.com

M

echa

nica

l, E

le

ctrica

l &

L

igh

ting

D

esign

S

ervice

s

Architectural E

ngineering C

onsultants

Tele

pho

ne: 97

0-74

8-8

520

Drawn By: Checked By:

DATE: ISSUE:

07-02-15BID SET

AEC PROJECT #:

EA

GLE

C

OU

NT

Y A

IR

PO

RT

AD

MIN

IS

TR

AT

IO

N

OF

FIC

E R

EM

OD

EL

GY

PS

UM

, C

O

15050

An Office with LEED™ Accredited Professionals

NORTH

LIGHTING & RCP PLAN

SCALE: 1/4" = 1'0"