Natural Refrigerants: Future-proof Solutions for Today
eurammon End-Users
“Roche´s commitment to natural refrigerants”
by
Hans Baumann, F. Hoffmann-La Roche AG
Thomas Wolf, F. Hoffmann-La Roche AG
Schaffhausen, 07 October 2011
The Group Directive K6 (Thomas)
Technical applications (Hans)
4
Schaffhausen, 07 October 2011
Group Directive K6
• Directive on Substances Affecting the Ozone Layer and the Climate
• Since 1994
• Directs the implementation of Roche Group Goal
• Over time adjusted and extended scope
• Developed and maintained by Group-SHE
• Monitoring and control of its implementation by Group-SHE
Schaffhausen, 07 October 2011
Group Directive K6
• Goals
• Affected substances: Halons, CFCs, HCFCs, HBFCs, HFCs, PFCs
• 90% of all affected substances must be removed
• 10% exemptions for applications with no market-available solutions
• Remaining 10% only HFCs/PFCs
• Timeline
Legacy Roche sites:
• CFCs/HCFCs/HBFCs:expeditiously, but not later than end of 2015
• HFCs/PFCs: by end 2015
New acquisitions:
• CFCs/HCFCs/HBFCs:appropriate new timeframes
• HFCs/PFCs: appropriate new timeframes
• Schematic implementation scheme
Schaffhausen, 07 October 2011
Group Directive K6
CFCs, HCFCs, HBFCs and Halons HFCs, PFCs
Prohibited in aerosol products manufactured by Roch e or its affiliates
Prohibited in foam products for packaging material
Prohibited in foam products for new thermal insulati on(Insulation material in existing equipment and inst allations may remain in use until the end of its se rvice life)
Use as a solvent in production is prohibited(May be used in laboratories on a small scale in te st methods required by government agencies)
• Schematic implementation scheme
Schaffhausen, 07 October 2011
Group Directive K6
CFCs, HCFCs, HBFCs and Halons HFCs, PFCs
No new equipment No new equipment if inventory exceeds 10% of baseli ne
Expeditious phase-out according to defined deadline s Phase-out according to defined deadlines
Leak rates to be less than 1% Leak rates to be less than 1%
Refilling only after repair or removal of equipment Refilling only after repair or removal of equipment
Drop-in replacement with HFCs in exceptional casesUse as drop-in replacement if this does not cause
inventory to exceed 10% of baseline
Destruction of disposed substances Destruction of disposed substances
Reuse of HCFCs until deadlinesReuse of substances if this does not cause inventor y to
exceed 10% of baseline
Destruction of no longer used equipment Destruction of no longer used equipment
Resale or reuse of equipment if this does not cause inventory to exceed 10% of baseline
Schaffhausen, 07 October 2011
The Group Directive K6 (Thomas)
Technical applications (Hans)
9
The range of technical applications using cooling technology in
the Pharma & Diagnostics business is very broad
High rack warehouse Freezer Cooling room
Lyophilization Soda fountain Lyophilisation unitslab thermostat
Schaffhausen, 07 October 2011 10
Lack of technology using natural refrigerants required
development work for different applications
NH3
30 kW…. 5 MW
CO2
2 kW…. 300 kW
Hydrocarbons*
< 1 kW…approx. 1 kW
(without safety activities)
2 kW…. 50 kW
(safety activities required, EN 378)
(+15°C < T > -100°C)
(T > -60°C)
(T > -50°C)
* e. g. propane, isobutane; ethene
Hydrocarbons*
CO2 Chillers for cold rooms
Air cooled propane chiller unit 2 kW
Lyophilisation usinghydrocarbon
special equipment requiring verylow temperature (< -80°C)
11Schaffhausen, 07 October 2011
Findings & challenges
• NH3 is the most energy efficient refrigerant for large scale applications (e.g. for air conditioning)
• The availability of commercial solutions for small scale equipment is still limited
• For applications with cooling capacities between 2 - 10 kW CO2 based solutions are often the only option due to safety issues
• CO2 based systems have worse energy efficiency for room temperature requirements > 0°C
• The best technology needs to be selected form case to case considering energy efficiency, safety and financial issues
Schaffhausen, 07 October 2011 12