ETC Installation Guide Unison Echo ® Occupancy Sensor Echo Occupancy/Vacancy Sensor Page 1 of 12 Electronic Theatre Controls, Inc. Corporate Headquarters Middleton, Wisconsin, USA Tel +608 831 4116 Service: (Americas) [email protected] London, UK Tel +44 (0)20 8896 1000 Service: (UK) [email protected] Rome, IT Tel +39 (06) 32 111 683 Service: (UK) [email protected] Holzkirchen, DE Tel +49 (80 24) 47 00-0 Service: (DE) [email protected] Hong Kong Tel +852 2799 1220 Service: (Asia) [email protected] Web: www.etcconnect.com Copyright © 2016 ETC. All Rights Reserved. Product information and specifications subject to change. ETC intends this document to be provided in its entirety. 7186M2180 Rev C Released 2016-02 Overview The Echo Occupancy/Vacancy Sensor is a ceiling mounted sensor that utilizes passive infrared (PIR) technology, providing reliable vacancy and occupancy detection for lighting control. The sensor provides automatic configuration of vacancy (auto-off) or occupancy (auto-on/off) functionality based on other connected control stations. When manual control stations are present, the sensor will only perform vacancy actions. Each sensor is available in white or black finish. Lens masks are provided to allow customized occupancy detection fields as required by each installation. Custom Configuration This document guides you through the installation and local configuration of the Echo Occupancy/Vacancy Sensor. For more detailed information about custom configuration options available for the Echo Occupancy/Vacancy Sensor using EchoAccess, reference the EchoAccess Mobile App integrated help system. Note: To use the configuration settings applied using EchoAccess, DIP switch 2 must be enabled. Reference DIP Switch Settings on page 7. The Occupancy/Vacancy Sensor provides 360 degree coverage of the installed location and is available in three models: E-OCC-SR- Occupancy/Vacancy Sensor with small room lens covers 450 sq. ft. at 8 ft./ 800 sq. ft. at 10 ft. E-OCC - Occupancy/Vacancy Sensor with standard room lens covers 1,800 sq. ft. at 8 ft./ 3,000 sq. ft. at 10 ft. E-OCC-HC - Occupancy/Vacancy Sensor with high ceiling lens covers 300 sq. ft. at 10 ft./ 7,000 sq. ft. at 40 ft.

Transcript of ETC Installation Guide - Imagine Light · ETC Installation Guide Occupancy/Vacancy Sensor Echo...

Page 1: ETC Installation Guide - Imagine Light · ETC Installation Guide Occupancy/Vacancy Sensor Echo Occupancy/Vacancy Sensor Page 3 of 12 Electronic Theatre Controls, Inc. conditions,

ETC Installation GuideUnison Echo® Occupancy Sensor

OverviewThe Echo Occupancy/Vacancy Sensor is a ceiling mounted sensor that utilizes

passive infrared (PIR) technology, providing reliable vacancy and occupancy

detection for lighting control. The sensor provides automatic configuration of

vacancy (auto-off) or occupancy (auto-on/off) functionality based on other

connected control stations. When manual control stations are present, the

sensor will only perform vacancy actions.

Each sensor is available in white or black finish. Lens masks are provided to

allow customized occupancy detection fields as required by each installation.

Custom ConfigurationThis document guides you through the installation and local configuration of

the Echo Occupancy/Vacancy Sensor. For more detailed information about

custom configuration options available for the Echo Occupancy/Vacancy

Sensor using EchoAccess, reference the EchoAccess Mobile App integrated

help system.

Note: To use the configuration settings applied using EchoAccess, DIP switch 2 must be enabled. Reference DIP Switch Settings on page 7.

The Occupancy/Vacancy Sensor provides 360

degree coverage of the installed location and is

available in three models:

• E-OCC-SR- Occupancy/Vacancy Sensor with

small room lens covers 450 sq. ft. at

8 ft./ 800 sq. ft. at 10 ft.

• E-OCC - Occupancy/Vacancy Sensor with

standard room lens covers 1,800 sq. ft. at

8 ft./ 3,000 sq. ft. at 10 ft.

• E-OCC-HC - Occupancy/Vacancy Sensor

with high ceiling lens covers 300 sq. ft. at

10 ft./ 7,000 sq. ft. at 40 ft.

Echo Occupancy/Vacancy Sensor Page 1 of 12 Electronic Theatre Controls, Inc.

Corporate Headquarters Middleton, Wisconsin, USA Tel +608 831 4116 Service: (Americas) [email protected] London, UK Tel +44 (0)20 8896 1000 Service: (UK) [email protected] Rome, IT Tel +39 (06) 32 111 683 Service: (UK) [email protected] Holzkirchen, DE Tel +49 (80 24) 47 00-0Service: (DE) [email protected] Hong Kong Tel +852 2799 1220 Service: (Asia) [email protected]: www.etcconnect.com Copyright © 2016 ETC. All Rights Reserved. Product information and specifications subject to change. ETC intends this document to be provided in its entirety.7186M2180 Rev C Released 2016-02

Page 2: ETC Installation Guide - Imagine Light · ETC Installation Guide Occupancy/Vacancy Sensor Echo Occupancy/Vacancy Sensor Page 3 of 12 Electronic Theatre Controls, Inc. conditions,

ETC Installation GuideOccupancy/Vacancy Sensor

Wire SpecificationSensors connect to the EchoConnect communication bus. EchoConnect is a

bidirectional protocol that uses one pair of wires (data + and data -) for both

data and power. ETC recommends using Belden 8471 (or approved equal)

Class II wire. The total combined length of an EchoConnect wire run (using

Belden 8471, or equal) may not exceed 1,640 feet (500m).

Installation EnvironmentOccupancy/Vacancy Sensors are intended for installation to a finished ceiling

surface, ceiling tile mounted, attached to a round fixture junction box or

single-gang RACO switch box.

The sensor operates in ambient temperatures of 0°C to 40°C, with a maximum

of 90% non-condensing humidity.

ETC recommends paying special attention to the installation environment:

• The sensor must have an unobstructed view of the room. Do not mount

behind or near tall cabinets, shelves, hanging light fixtures, etc.

• Do not install the sensor within eight feet from an HVAC airflow duct/

vent.

• Install the sensor where it cannot easily sense movement in areas

outside of the intended space, such as hallways, glass partitions, or

adjacent rooms. If the installation location cannot avoid these

Note: All control wiring should be installed and terminated by a qualified installer and should follow standard wiring installation practices.

Leave approximately 10 inches (254mm) of wiring in the back box for connection to allow slack for future service needs.

Note: ETC requires that all sensors be grounded. Pull an additional 14 AWG (1.5mm2) wire for grounding when control wires are not installed in grounded metal conduit.

Note: - When using Category5 (or equivalent) cable on the EchoConnect communication bus, please note the following:- Cat5 wiring must be terminated using EchoConnect Cat5 Termination Kit and must be installed using a bus topology. Refer to the installation guide that is provided with the Cat5 Termination Kit (7186A1207) for information to terminate Cat5 wiring.- Not all topologies are supported using Cat5; careful planning is required to ensure the proper termination kits are available and the wire is pulled appropriately.

Echo Occupancy/Vacancy Sensor Page 2 of 12 Electronic Theatre Controls, Inc.

Page 3: ETC Installation Guide - Imagine Light · ETC Installation Guide Occupancy/Vacancy Sensor Echo Occupancy/Vacancy Sensor Page 3 of 12 Electronic Theatre Controls, Inc. conditions,

ETC Installation GuideOccupancy/Vacancy Sensor

conditions, portions of the lens can be masked to block the sensor view

of these undesired areas. Reference Lens Masking on page 10.

Parts and SuppliesThe following parts and supplies are included with the Occupancy/Vacancy

Sensor ordered:

InstallationThe Occupancy/Vacancy Sensor is provided with a twist-lock mounting plate

that can be mounted to a junction box, finished ceiling, or soft ceiling tile.

Determine the installation method and follow the detailed instructions:

• See “Junction Box Installation” on page 4.

• See “Soft Ceiling Tile Installation” on page 5.

• See “Lens Masking” on page 10.

• Soft ceiling tile adaptor • 2 each screws, 6-32 x 3/4” and 1 3/4”

• EchoConnect & ESD groundwire pigtails

• 3 lens masks

Note: - Follow all local code requirements for terminating wire.- Use appropriately sized wire nuts (not provided) to secure each termination.

Note: The EchoConnect pigtail is only required when the sensor is installed in series with other stations or sensors. If you are not continuing the data run, direct termination on the control board is recommended.

Echo Occupancy/Vacancy Sensor Page 3 of 12 Electronic Theatre Controls, Inc.

Page 4: ETC Installation Guide - Imagine Light · ETC Installation Guide Occupancy/Vacancy Sensor Echo Occupancy/Vacancy Sensor Page 3 of 12 Electronic Theatre Controls, Inc. conditions,

ETC Installation GuideOccupancy/Vacancy Sensor

Junction Box Installation

a: Strip each wire to the appropriate length, depending on

the wire nut or other termination used (wire nuts are not

provided).

b: Twist the data - (typically black) EchoConnect wire, the

black lead from the EchoConnect pigtail, and any

continuing EchoConnect (typically black) wire together

and secure with a wire nut.

c: Repeat the above steps for the data + (typically white)

EchoConnect wire and the ESD ground wire.

Step 3: Orient the smooth side of the mounting plate to the junction

box and pull the EchoConnect wires (or terminated pigtail)

from the junction box through the provided holes near the

center of the mounting plate.

Step 4: Secure the mounting plate to the junction box using the

screws provided (both short and long screws are provided for

convenience).

Step 5: Strip each wire 5/16” (8mm) and terminate the EchoConnect

(white and black wires) and the ground wire (green/yellow) to

the EchoConnect terminal block located on the sensor

controller. Torque each termination to 3.1-3.5 in-lb.

a: Terminate the white incoming wire to the data +

terminal.

b: Terminate the black incoming wire to the data - terminal.

c: Terminate the green/yellow (ground) wire to the ground

terminal.

Terminate

wires here

Step 1: Pull the Belden 8471 (or

equivalent) and 14 AWG

(2.5mm2) ground wire to the

junction box.

Step 2: If you are installing the sensor in series with other sensors or stations

(continuing the data run), use

the provided EchoConnect

pigtail, ESD ground pigtail

and connectors (not

provided) to make the

terminations. If you are not continuing the data run,

proceed to Step 3.

Echo Occupancy/Vacancy Sensor Page 4 of 12 Electronic Theatre Controls, Inc.

Page 5: ETC Installation Guide - Imagine Light · ETC Installation Guide Occupancy/Vacancy Sensor Echo Occupancy/Vacancy Sensor Page 3 of 12 Electronic Theatre Controls, Inc. conditions,

ETC Installation GuideOccupancy/Vacancy Sensor

Step 6: Attach the sensor to the mounting plate by aligning the tabs

on the sensor with the slots on the mounting plate, then twist

clockwise until the two are secured into place.

Soft Ceiling Tile Installation

Step 1: Pull the Belden 8471 (or equivalent) and 14 AWG (2.5mm2)

ground wire to the installation location.

Step 2: If you are installing the sensor in series with other sensors or stations (continuing the data run), use the

provided EchoConnect pigtail, ESD ground pigtail and

connectors (not provided) to make the terminations. If you are not continuing the data run, proceed

to Step 3.

a: Strip each wire to the appropriate length, depending on

the wire nut or other termination used (wire nuts are not

provided).

b: Twist the data - (typically black) EchoConnect wire, the

black lead from the EchoConnect pigtail, and any

continuing EchoConnect (typically black) wire together

and secure with the wire nut.

c: Repeat the above steps for the data + (typically white)

EchoConnect wire, and for the ESD ground wires.

Step 3: Create a hole for wire pass-through in the ceiling tile by

poking through the center hole or oblong hole of the

mounting plate, then pull the wires through.

Poke the adapter through the ceiling tile, then bend

it over for a secure fit.

EchoConnect pigtail

and connectors

(optional use)

Terminate

wires here

Echo Occupancy/Vacancy Sensor Page 5 of 12 Electronic Theatre Controls, Inc.

Page 6: ETC Installation Guide - Imagine Light · ETC Installation Guide Occupancy/Vacancy Sensor Echo Occupancy/Vacancy Sensor Page 3 of 12 Electronic Theatre Controls, Inc. conditions,

ETC Installation GuideOccupancy/Vacancy Sensor

Step 4: Orient the smooth side of the mounting plate to the finished

side of the ceiling tile and align and insert the soft ceiling tile

adapter through the holes provided near the center of the

mounting plate. Reference the graphic on the previous page.

Step 5: Poke the tines of the adapter through the ceiling tile, then

bend each tine over in opposite directions for a secure fit on

the unfinished side of the ceiling tile.

Step 6: Strip each wire 5/16” (8mm) and terminate the EchoConnect

(white and black wires) and ground wire (green/yellow) to the

EchoConnect terminal block located on the sensor control

board. Torque each termination to 3.1-3.5 in-lb.

a: Terminate the white incoming wire to the data +

terminal.

b: Terminate the black incoming wire to the data - terminal.

c: Terminate the green/yellow (ground) wire to the labeled

ground terminal.

Sensor ConfigurationThe Echo Occupancy/Vacancy Sensor participates in an Echo system using the

configured Space and Address, which are selectable using the rotary switches

on the rear panel of the sensor.

Additional DIP switches and the [Mode] button, also located on the rear

panel, set the sensor functionality and the occupancy detected action.

Set Space and AddressTwo rotary switches on the rear panel of the controller provide for assignment

of the sensor Space and Address. By default, these switches are set to Space 1,

Address 1. Commands are shared by all devices within a given space.

Step 1: Set the Space rotary switch to the desired number (1 thru 16)

for the space you want the sensor to control.

Step 2: Set the Address rotary switch to desired address (1 thru 16) for

the sensor identification in the selected space.

Note: Do not duplicate a device Address within the same Space.

Echo Occupancy/Vacancy Sensor Page 6 of 12 Electronic Theatre Controls, Inc.

Page 7: ETC Installation Guide - Imagine Light · ETC Installation Guide Occupancy/Vacancy Sensor Echo Occupancy/Vacancy Sensor Page 3 of 12 Electronic Theatre Controls, Inc. conditions,

ETC Installation GuideOccupancy/Vacancy Sensor

DIP Switch SettingsDIP switches on the rear panel of the Occupancy/

Vacancy Sensor provide for additional

configuration options including Use Custom

Config, Vacancy Timeout, Enable/Disable PIR

detection LED, and the ability to restore the

sensor to its factory defaults.

DIP Switch 2

DIP switch 2 enables “Custom Config” which instructs the sensor to use

settings that are configured using the EchoAccess Mobile App. This setting is

Off by default.

• When “Custom Config” is set to Off, the default position, local DIP

switch settings for Vacancy Timeout and Enable PIR LED are used.

Sensor actions can be adjusted using the program [Mode] button.

• When “Custom Config” is set to On, all other local DIP switch settings

are ignored. Instead, the settings made by the EchoAccess Mobile App

for Vacancy Timeout, Enable PIR LED, and Occupancy actions are used.

DIP Switch 3&4

DIP switch 3 & 4 set the “Vacancy Timeout” to 5, 15, 30 minutes, or Auto.

See “Vacancy Timeout” on page 9.

• 5 min = Switches 3 and 4 are Off.

• 15 min = Switch 3 is Off and Switch 4 is On (default).

• 30 = Switch 3 is On and Switch 4 is Off.

• Auto = Both switches are On. See “Auto Vacancy Timeout” on page 10.

DIP Switch 5

DIP switch 5 enables/disables the red PIR detection LED. When the switch is

Off, the PIR LED disables unless it is in Walk Test mode. When set to On, the

red PIR LED will illuminate the sensor lens when movement is detected. The

default position is On.

DIP Switch 8

DIP switch 8 provides a “Restore Defaults at Boot” function. The factory

defaults are restored by setting this DIP switch On, and cycling power to the

station. The default position is Off.

Note: DIP switches 1, 6, and 7 are not currently used and are reserved for future development. Leave them at their default Off setting.

Echo Occupancy/Vacancy Sensor Page 7 of 12 Electronic Theatre Controls, Inc.

Page 8: ETC Installation Guide - Imagine Light · ETC Installation Guide Occupancy/Vacancy Sensor Echo Occupancy/Vacancy Sensor Page 3 of 12 Electronic Theatre Controls, Inc. conditions,

ETC Installation GuideOccupancy/Vacancy Sensor

Power Up and TestPower Up

All EchoConnect terminations in the system must be made before applying

power to the system and sensor. When the sensor is powered up, the PIR LED

illuminates for one minute for calibration and warm-up, and then returns to

normal operation.

ConfigurationSensor configuration for Basic config mode (DIP switch 2 set to Off) can be

accomplished locally on the sensor using the other available DIP switches,

[MODE] button and LED, and the Auxiliary button. See Preset below, and

Vacancy Timeout on page 9 for local configuration instructions.

PresetThe [MODE] button and LED found on the rear panel of the sensor sets the

sensor into “Program Mode.” Both the [MODE] button and LED, and the

Auxiliary “A” button are used for configuration of the occupancy detected

action.

The “A” button and Mode LED are used to program the preset that is

activated with an occupancy detected state change. The Mode LED blinks to

indicate the current preset number used.

Note: The occupancy detected action only matters when using the sensor without manual wall station controls. When manual wall stations are present in the space, the sensor will only control the vacancy action (manual on).

Echo Occupancy/Vacancy Sensor Page 8 of 12 Electronic Theatre Controls, Inc.

Page 9: ETC Installation Guide - Imagine Light · ETC Installation Guide Occupancy/Vacancy Sensor Echo Occupancy/Vacancy Sensor Page 3 of 12 Electronic Theatre Controls, Inc. conditions,

ETC Installation GuideOccupancy/Vacancy Sensor

Step 1: Press and hold the [MODE] button for 3 seconds to enter

“Program Mode.” Program Mode allows adjustment of the

preset that activates for occupancy detection. By default, this

is Preset 1. The “A” button, located on the front of the sensor,

blinks to indicate the preset number controlled by the

occupancy action.

Step 2: Press and release the “A” button the number of times to set

the new preset. (For example: press and release ten times to

set Preset 10.) The “A” button blinks the number of the preset

used for the occupancy event action.

Step 3: Press and release the [MODE] button to save the current

setting. The Mode/Sensor count LED turns off and the “A”

button again blinks out the saved preset index.

Step 4: Attach the sensor to the mounting plate by aligning the tabs

on the sensor with the slots on the mounting plate, then twist

clockwise until the two are locked into place.

Vacancy TimeoutVacancy timeout is the amount of time the sensor waits to take action after no

movement is detected. By default, vacancy timeout is set to 15 minutes

(indicated by DIP switch 3 set to Off and 4 set to On). When the vacancy

timeout ends, the grace period begins.

When the sensor detects vacancy, the vacancy timeout period begins. If the

sensor does not detect occupancy again during the vacancy timeout period,

the lights turn off and a 30 second grace period begins.

Auxiliary

button

Walk Test

button

MODEbutton

MODELED

rear panel view

Echo Occupancy/Vacancy Sensor Page 9 of 12 Electronic Theatre Controls, Inc.

Page 10: ETC Installation Guide - Imagine Light · ETC Installation Guide Occupancy/Vacancy Sensor Echo Occupancy/Vacancy Sensor Page 3 of 12 Electronic Theatre Controls, Inc. conditions,

ETC Installation GuideOccupancy/Vacancy Sensor

Grace PeriodThe sensor features a 30 second grace period after a vacancy timeout occurs.

During this grace period, if the sensor detects occupancy, it will turn on or

restore the previous lighting condition.

Auto Vacancy TimeoutThe “Auto” vacancy timeout setting varies vacancy the timeout between

5 and 30 minutes depending on how often it identifies an occupancy trigger

after a vacancy timeout occurs (during the grace period).

Lens MaskingLens masks are provided in the packaging for your convenience, used to block

a section of the lens from detecting occupancy.

PIR DetectionThe PIR detection automatically adjusts its sensitivity to eliminate nuisance

tripping. When the sensor powers on, the red PIR LED illuminates for

approximately 60 seconds to identify “Power Up” state. Sensor configuration

is not allowed. During this time, no events are triggered.

Step 1: As needed, trim the lens

mask to fit the desired

area to be blocked.

Step 2: Gently press down on the

sensor lens, which will

give only slightly, and

insert the lens mask.

Step 3: Rotate the lens mask

around the dome to block

the required area from

occupancy sensing.

Echo Occupancy/Vacancy Sensor Page 10 of 12 Electronic Theatre Controls, Inc.

Page 11: ETC Installation Guide - Imagine Light · ETC Installation Guide Occupancy/Vacancy Sensor Echo Occupancy/Vacancy Sensor Page 3 of 12 Electronic Theatre Controls, Inc. conditions,

ETC Installation GuideOccupancy/Vacancy Sensor

TestOccupancy/Vacancy Sensors offer a Walk Test mode which shortens the

vacancy timer to 10 seconds, allowing for simple and quick verification of the

sensors coverage and range in the installed space.

Enable Walk Test ModeStep 1: Prepare the site for configuration.

a: Make certain the sensor and lighting loads are powered

and connected for control by the Echo controller.

b: You will need direct access to the Occupancy/Vacancy

Sensor in order to place it into Walk Test mode.

Step 2: Press the [Walk Test] button on the front of the sensor to

enable the Walk Test feature at the sensor. A green LED will

begin to flash, indicating Walk Test is enabled and the

vacancy/no vacancy occupancy timer will be shortened to 10

seconds.

Step 3: Move throughout the space including corners and areas that

may specifically be obscured from line of sight to the sensor.

Each time the sensor detects movement, the lens will

illuminate red.

Step 4: Adjust the lens masking, if installed, blocking certain areas of

the installed space from sensor detection. See “Lens Masking”

on page 10.

Step 5: Walk Test mode will automatically exit after five minutes from

the time it was enabled. To manually exit the Walk Test mode,

press either of the buttons on the sensor.

Auxiliary

button

Walk Test

button

Walk-Test mode automatically exits and the

sensor returns to normal operation after 5

minutes and can be manually terminated early by

pressing the [Walk Test] button.

Echo Occupancy/Vacancy Sensor Page 11 of 12 Electronic Theatre Controls, Inc.

Page 12: ETC Installation Guide - Imagine Light · ETC Installation Guide Occupancy/Vacancy Sensor Echo Occupancy/Vacancy Sensor Page 3 of 12 Electronic Theatre Controls, Inc. conditions,

ETC Installation GuideOccupancy/Vacancy Sensor

High Ceiling side view

03.0m10ft

3.0m10ft

6.1m20ft

6.1m20ft

9.1m30ft

9.1m30ft

12.2m40ft

12.2m40ft

0

12.2m40ft

9.1m30ft

6.1m20ft

Small Room side view0

01.5m5ft

1.5m5ft

3.0m10ft

3.0m10ft

4.6m15ft

4.6m15ft

6.1m20ft

6.1m20ft

8ft2.4m

10ft3.0m

12ft3.7m

Large Room side view

0

8ft2.4m

10ft3.0m

12ft3.7m

03.0m

10ft

3.0m

10ft

6.1m

20ft

6.1m

20ft

9.1m

30ft

9.1m

30ft

12.2m

40ft

12.2m

40ft

Echo Occupancy/Vacancy Sensor Page 12 of 12 Electronic Theatre Controls, Inc.