1/23
W P 1 6 0 0
Microprocessor Based Escalator&Moving Walk Controller
User ManualVer1.04
& e f Subject to change without notice
Wuxi WIPO Electronic Co.,Ltd
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
2/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
1
Preface
Microprocessor Based Escalator & Moving Walk Controller WP1600is the main controller specially
designed for Escalator & Moving Walk, applied for normal motor drive control system, and VVVF drive
control system. It is functionally featured as following:
1. With high capacity control code memorizer applied for PC controller acts together with ST
Microelectronics CPU for upgrading programs conveniently according to the specific requirement.
2. Fault & operation module applied CanBus LAN Serial Communication with speed up to 125Kbit/S,
High-spped data transmission, real-time control and quick response.
3.LED display with high brightness is applied for function setting. Such as port polarity setting, clock
setting, speed setting, stop/start time setting, password setting.
4.Inside blackbox function following up the lift running & recording the time of running, code of faults
leads to the poWPrful maintenance.
5.Supporting multi-remote display drive to show the running direction and code of faults.
6.SMT technology delivers reliable quality and small & delicate appearance to PCBs with lowpoWPr-consumption. It is a valuable green electronic product.
7.With unique anti-interference technology. All the components WPre selected strictly to guarantee
the quality.
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
3/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
2
Contests
CHAPTER 1 MAIN CONTROLLER WP1600
.. 3
1.1(WP1600) IN PICTURE3
1.2(WP1600)EXTERNAL DIMENSIONS. 4
1.3(WP1600)DIMENSION DRAWING OF MOUNTING. 4
1.4 ELECTRIC SPECIFICATION. 4
1.4.1 supply input J12. 4
1.4.2 switching input5
1.4.3 switching output. 5
1.4.4 input principle. 6
1.4.5 output principle
... 61.5 PORT DESCRIPTION: INPUTS J1J2J3J4J5J6J7 7
INPUT PORTS DESCRIPTION7
1.6 PORT DESCRIPTION: OUTPUTS J8J9J10J11 8
OUTPUT PORTS DESCRIPTION8
1.7OUTPUT PORT:J14. 9
1.8 SUPPLY INPUT:J12.. 9
SUPPLY INPUT DESCRIPTION.. 9
CHAPTER 2: OPERATION AND FAULT DISPLAY MODULE WP1600-01 ... 10
2.1WP1600-01IN PICTURE.. 102.2WP1600-01EXTERNAL DIMENSION.10
2.3WP1600-01DIMENSION DRAWING OF MOUNTING... 10
2.4WP1600-01PORT DESCRIPTION. 11
CHAPTER 3: CONFIGURATION OF MAIN CONTROLLER.. 12
3.1GENERAL VIEW...12
3.2PARAMETERS SETTING... 14
CHAPTER 4: MAIN CONTROLLER ADJUSTMENT..19
4.1 BEFORE THE ADJUSTMENT. 19
4.2 INSPECTION RUNNING19
4.3RUNNING NORMALLY.. 19
4.4OPERATION OF OIL PUTTING19
4.5APTITUDE RUNNING FUNCTION... 20
CHAPTER 5: FAMILIAR FAULT AND TROUBLESHOOTING. 21
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
4/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
3
Chapter 1 : Main Controller (WP1600)
1.1( WP1600) in picture and description of interface
Table 1.1 Description of the outside interface
No. Code Item Remarks
1 J1 Input/output port 1 Switching input / providing output supply
2 J2 Input port 2 Switching input
3 J3 Input port 3 Switching input
4 J4 Input port 4 Switching input
5 J5 Input port 5 Switching input
6 J6 Input port 6 Switching input
7 J7 Input port 7 Switching input
8 J8 Output port 8 Switching output
9 J9 Output port 9 Switching output
10 J10 Output port 10 Switching output
11 J11 Output port 11 Switching output (backup for expanding)
12 J14 Output port 12 Connect with another display board
13 J15 Short circuit port Match with resistance
14 J12 PoWPr supply input 5V and 24V separately
15 BT1 3V lithiumbattery2032
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
5/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
4
1.2 External Dimensions
Unit Width Length Thickness
mm 181 108
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
6/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
5
1.4.2 Switching input
Input Open collector inputsphoto-electricity Isolation
Level 0 0~2mA
Current SignalLevel 1 4.5~8mA
Level 0 18~24V DCVoltage Signal
Level 1 0~5V DC
Digital signal filtering delay 30mS
Signal responding frequency 330Hz
1.4.3 Switching output
There are two types of switching output: transistor output and relay output. Their electric
specifications show as follows.
Electric specifications of transistor output:
Output form Transistor outputJ11
Load voltage DC 24V DC
Resistance load Single output 100mA, whole output 400mA *note 1Load current
Inductive load 20mA
Note 1On the port J11, the summation of all the transistor output current cannot 400 mA
Electric specifications of relay output:
Output form Relay OutputJ8J9J10
AC 250V ACLoad Voltage
DC 110V DC
Inductive load 3 ALoad Current
Resistance load 5 A
Electric service life 3,000,000 timesService life
Mechanical service life 10,000,000 times
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
7/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
6
1.4.4 Input principle:
1.4.5 Output principle:
Transistor output
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
8/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
7
Relay output
1.5 Port description: inputs J1 J2 J3 J4 J5 J6 J7
Port No. Relative component Remarks
P1 Testing motor speed
P2 Testing left armrest speed
P3 Testing right armrest speed
Impulse input, working frequencyunder 50Hz
24- Supply 24V-
J1
24+ Supply 24V+
Provide supply 24V to photocouplefor testing speed
P4Inspection signals
N/C signals (normal:N/C,inspection:N/O.)
P5 Going up signals Going-up: press close input
P6 Going down signals Going-down: press close input
P7 Oil pump operation button Put the oil by manual
J2
P8 Contactor conglutinationinspection
N/C signalsrunning:N/O, stop:N/C
P9 Brake traveling switch inspectionN/O/N/C can be selected throughthe menu
P10 Safety loop relay
P11 Drive chain break off
P12 Apron left-upside
Including P11~P29 relative switch,phase relay, hot relay, emergency
switch all safty loop connect:
close,fault anywhere: break off
J3
P13 Apron right-upside
P14 Gear left-upside
P15 Gear right-upside
J4
P16 Armrest entrance left-upside
All the switch inputs in safety loop,when the switch activated, therelative input was lightened.
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
9/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
8
P17 Armrest entrance right-upside
P18 Step stop upside
P19 Apron left-underside
P20 Apron right-underside
P21 Gear left-undersideP22 Gear right-underside
J5
P23 Armrest entrance left-underside
P24 Armrest entrance right-underside
P25 Left traction chain break off
P26 Right traction chain break off
P27 Step underside break off
J6
P28 Left armrest break off
P29 Right armrest break off
P30 Upside entrance sensor input
P31 Underside entrance sensor inputUsed for the inputs driving by modeof VVVF & energy -saving
P32 Backup input 1 Backup for function expanding
J7
CM6 Common input P1-P32 commonly use CM624V-
1.6 Port description: outputs J8 J9 J10 J11
Port No. Relative component Remarks
T1 Star contactor Using as supply input contactor(VVVF)
T2 Triangle contactor Running contactor
CM1 Signals output: common port 1 T1T2 commonly use CM1
T3 Going-up contactor Going-up contactor
J8
T4 Going-down contactor Going-down contactor
CM2 Signals output: common port 2 T3T4 commonly use CM2
T5 Brake contractor 1
T6 Brake contractor 2
T7 Cooling oilpump valve contactor
J9
CM3 Signals output: common port 3 T5T7 commonly use CM3
T8 Alarm bell When there is fault, it alarm.
CM4 Signals output: common port 4 T8 CM4 independent connection
NC Empty
NC Empty
J10
NC Empty
J11C1 Going-up contactor output
control (VVVF)
VVVF speed control (transistor output)
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
10/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
9
C2 Going-down contactor outputcontrol (VVVF)
C3 High-speed output (VVVF)
C4 Low-speed output (VVVF)
CM5 Signals output: common port 5 C1C4 commonly use CM524+
J8,J9,J10 are relay outputs, J11 is transistor output.
1.7 Port description: output J14
Port No. Relative component Remarks
CANL CAN interface -
CANH CAN interface +Note the interface polarity.
24+ 24V DC supply output +J14
24- 24V DC supply output -
Supplying 200mA current.
This port used for besides display boardmax. 4pcs, and also can provide 24V voltage( from 24+ to
24-), 200mA. current to the other equipment (such as photocouple for testing speed).
1.8 port description: supply input J12
Port No. Relative component Remarks
5V+
5V-5V DC supply
FG Grounded port
24V+
J12
24V-24V DC supply
Note: the polarity of the connection, dont connect contrarily.
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
11/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
10
Chapter 2: Operation and fault display module WP1600-01
2.1 WP1600-01 in picture:
WP1600-01 display side WP1600-01 component side
2.2 WP1600-01 External dimension:
2.3 WP1600-01 installation dimensions drawing:
Unit Width Length Thickness
mm 576 772
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
12/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
11
2.4 WP1600-01 port description:
Port Description
JI CAN used for short circuit port of resistance matching
J2 CAN interface and supply input
Operation & fault display moduleWP1600-01is used for Escalator & Moving Walk controller to
display the running direction. Fault code module, it is used with Escalator & Moving Walk main
controllerWP1600. The controller can work with 4 pcs operation & fault display module
WP1600-01at most. Regarding to the port J1, when there is one piece of WP1600-01 in the
controller, it will be short connected with port J1used for resistance matching to reduce CAN bus
signals reflection.if there is more than one piece of WP1600-01, one of them should be short
connected with J1, others are not. J2 is supply input and CAN-BUS input, please note the polarity of
the supply and CAN-BUS avoiding to destroy it.
LED display screen used super two-colours display module, fresh colour, high brightness, far
optical distance. The display figure can be set in the main controller by users themselves. Default figure:
big arrowhead, small arrowhead, rolling arrowhead etc. All of them can be set in the main controller.
On the display board, port J4 is used to set the installation place of the display module, if J4 was
short connected, this module will be installed on the top of the Escalator, if not, it will be in the bottom.
This port deside the right display information.
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
13/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
12
Chapter 3: Configuration of the main controller
3.1 General view:
Microprocessor Based Escalator & Moving Walk Controller should configure with some
parameters to work WPll. It will use LED display and keyboard to finish these configurations.Menu operation screen(located on the left-underside of the controller) show as below:
Including 4 LED display, 4 touch button.
ESC---------Exit UP----------up DOWN-------down OK------------confirm
Note menu operation should be do under stop status, otherwise, it is not be alloWPd.
Menu catalogue is as follows:
Main
menuFirst menu Menu function setting description Default
FUN1 F1-1 Brake traveling switch inspect N/O,N/C selection setting: 0---N/C, 1---N/O. 0
F1-2 Under VVVF drive& energy-saving control, upside entrance inductive switch input
setting: 0---N/C, 1---N/O.
0
F1-3 Under VVVF drive& energy-saving control, underside entrance inductive switch
input setting: 0---N/C, 1---N/O.
0
FUN2 F2-1 Under automaticly putting the oil, time interval setting scope: 09999min 120
F2-2 Under automaticly putting the oil, time setting scope:09999 sec 60
F2-3 Brake contactor run to the Up(Down) contactor, delaying time setting
scope:09999 MSEL
1000
F2-4 Star contactor running time setting scope:09999 MSEL 1000
F2-5 System clock setting scope:00:0023:59 06:00
F2-6 Lift stop automaticly time setting scope:00:0023:59 88:88
F2-7 Lift start automaticly time setting scope:00:0023:59 88:88
F2-8 Before lift start, the time setting of the bell scope:099sec 1S
ESC UP DOWN OK
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
14/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
13
F2-9 Under mode of VVVF, the delaying time of output in the leisure energy-saving
running scope:1-99sec
30
F211 Under aptitude running, no one use the lift, delaying time to stop the lift
scope:1-99sec
60
F2-0 System default: all the parameters will be back to the default set by manufacture
Main
menuFirst menu Menu function setting description Default
FUN3 F3-1 Motor speed setting Unit: impulse interval time counting value
Value = 0, cancel this speed control.
180
F3-2 Left armrest speed setting Unit: impulse interval time counting value
Value = 0, cancel this speed control.
180
F3-3 Right armrest speed setting Unit: impulse interval time counting value
Value = 0, cancel this speed control.
180
FUN4 F4-1 The type of lift poWPr control setting: 0VVVF, 1Y/ 1
F4-2 Parameters setting of the controller running status monitor scope: 07 7
F4-3 Display mode of the outside display figure setting: 0-big arrowhead, 1-small
arrowhead, 2-step arrowhead, 3-rotated arrowhead
0
F4-4 Oil putting equipment selection: 0motor, 1electromagnetic valve. 1
F4-5 Running direction selection of poWPr on automatic: 0going up, 1going down 0
F4-6 Self-learning of the lift speed: 0----run normally, 1----self-learn. 0
F4-7 Under VVVF control, output speed ratio betWPen high-speed and low-speed. 5
F4-8 The ability of the lift aptitude running: 0---NO, 1---YES. 0
FUN5 F5-1 Popedom password of the lift maintain time scope: 0-99999999 00000000
F5-2 Maintain time of the lift scope: 0-9999 hour 0
FUN6 Fault inquiry, it can store 4 fault records.
FUN7 Show the edition of the software.
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
15/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
14
3.2 Parameters setting description:
When the controller is poWPr on, pressOK to enter the menu setting:
1PressUP or DOWN to turn the pages to select the menu.2 If there is submenu under ths menu, pressOK to enter the next menu.3 If there is no submenu, pressOK to enter the function parameters setting.4Anytime you can pressESC to back to the last menu without saving.5Entering the parameters setting, the place you want to set will flash, indicate that it can be
revised. UP can change the number, DOWN changes the digit.
6After revised, press OK to save the settings, and finish with YES. ( If you set the wrongnumber, it will show ERR.) And then back to the last menu.
7All the input datas should be algorism data.3.2-1 FUN1 Menu description:
FUN1 includes 3 submenus to finish the polarity setting of the hardware inputs.
1F1-1 Brake traveling switch inspection N/O, N/C selection: 0---N/C (stopclose; runbreak
off), 1---N/O (stopbreak off; run--close)
2F1-2F1-3 Used for the polarity setting of the VVVF inductive inputs, please check the
menu catalogue for some details.
3.2-2 FUN2 Menu description:
FUN2 includes 9 submenus to finish the time setting :
1F2-1F2-4 please check the parameters description of catalogue.2F2-5 system clock setting, the first two digits on the LED display are hours (scope:0-23), the
next two are minutes(scope:0-59).
3F2-6 escalator stop automaticly time setting: the format of the time is XX:XX such as 18:00,means that the escalator stop at 6:00 pm. If you want to cancel this function, yue can set the
number beyond the scope 00:0023:59. (But because of the safety criterion, it will not be
provided).
4F2-7 escalator start automaticly time setting: the format of the time is XX:XX such as 06:00means that the escalator start at 6:00 am. If you want to cancel this function, yue can set the
number beyond the scope 00:0023:59. (But because of the safety criterion, it will not be
provided).
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
16/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
15
5F2-8 the bell setting before escalator start: please check the catalogue for some details.6F2-9 UP/DOWN inductive ertrance fault inspection delay time, means that when it goes up,
the upside inductive ertrance inspect the inputs, after the delay time reach to max, the
underside inductive ertrance still cannot inspect the inputs, it will show fault. When it goes
down, in the contrary.
7F2-0 system default setting: all the parameters set same with it set by manufacturer. Thedetails show as follows:
Entering to the menu F2-9, press OK, the display will show REAL, means that are you sure all of
them back to the default?, then press OK to confirm and save it. Press ESC to quit without any
changes.
3.2-3 FUN3 Menu description:
FUN3 includes 3 submenus:
Motor speed setting, left armrest speed limit setting and right armrest speed limit setting, these three
settings are used to test the escalator speed. Show the detailed setting as below:
1. Set F4-6 is1(self-learning)under inspection mode to start the escalator.
2. After inspection running, pressUP or DOWN to turn the pages, LED display will show
the parameters monitored currently, the parameters including:
RUN----------------------total running time parameter
STP----------------------- total leisure time parameter
NSP-----------------------motor speed impulse counting value parameter
USP-----------------------left armrest speed impulse counting value parameter
DSP-----------------------right armrest speed impulse counting value parameter
CLOC--------------------system clock
STU-----------------------running status parameter
NSPC---------------------motor speed time counting value parameter
USPC---------------------left armrest speed time counting value parameter
DSPC-------------------- right armrest time counting value parameter
Record the relative value of these three parameters by researchingNSPCUSPC
DSPC
.
3. Stopenter the menuFUN3 then enter to the submenu
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
17/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
16
F3-1----------record the relative value of NSPC, and save it.
F3-2--------record the relative value of USPC, and save it.
F3-3--------- record the relative value of DSPC, and save it.
4. If using VVVF drive mode, you should set the speed ratio of output betWPen high-speed
and low-speed to the menu F4-7.
3.2-4 FUN4 Menu description:
FUN4 includes 6 submenus to set the system control parameters.
1 F4-1 is the setting reference menu catalogue which set the type of the escalator poWPrcontrol, when set Y/, the drive mode is star/triangle drive; when select VVVF drive,
ourput: the star contactor output change into VVVF contactor output 1; triangle contactor
output change into VVVF contactor output 2; output C1 or T3 works as the VVVF control
up contactor, C2H or T4 works as the VVVF control down contactor,C3 works as the
VVVF control high-speed output, C4 works as the VVVF control low-speed outputP30
P31works as speed adjustment .Note: Please select the right drive type according to
the different drive mode.
2 F4-2 Parameters setting of controller running status monitor, used after escalator start,LED display the current parameters, value: 0-----7:
0------ poWPr-saving mode, LED sleep, brightless
1------monitor the total running time, unit is hour, max. value is 9999 hours, beyond 9999
hours,it will recount the number from 0, running time data will not lost even poWPr off.
2------PoWPr on, escalator non-running using time, unit is hour, max. value is 9999
hours, beyond 9999 hours,it will recount the number from 0, running time data will lost if it
is poWPr off.
3------Motor speed
4------Left armrest speed
5------ Right armrest speed
6------System clock
7------Running direction. Such asUPDNSTOP.
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
18/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
17
3F4-3 display mode of outside display figure, which match with the operation&fault display
module.
WP1600-01display mode setting, parameter from 0 to 3.
0------big arrowhead to display the running direction
1------small arrowhead to display the running direction
2------step arrowhead to display the running direction
3------rotated arrowhead to display the running direction
4F4-4 oil-putting equipment selection 0 or 1:
0------motor drive oil-putting mode, when manual oil-putting signal exits, or auto/half-auto
signals exit, oil-putting control output T7 works all the time, if the signals disappear, outputs stop.
1------electromagnetic valve drive oil-putting mode, when manual oil-putting signal exits, or
auto signals exit, oil-putting control output T7 works 1 second & stops 3 seconds, output circularly till the
signals disappear.
5F4-5 running direction of starting the escalator automaticly: 0-------Up, 1-------Down.
6F4-6 self-learning: is the speed setting of the self-learning. 0----cancel self-learning, 1---
start self-learning. If stop the escalator, this parameters will back to 0cancel self-learning. So
everytime you want to set this speed, you should select 1.
3.2-5 FUN5 Menu description:
FUN5 includes 2 submenus to set the system maintenance time limit.
Password8digitsto limit setting the maintenance time random. Only one know the
passwordcan do it. Default: 00000000.
Maintenance time4digitsDefault:0000. If it is set 0, there is no any limit, if not, such as set
0002, the system can run 2 hours at most, after that, system enter into maintenance status(all
the escalator functions are invalid), finishing it, you should set 0 again to resume all the
functions.
The setting method show as follows:
1. F5-1 popedom password setting
(1) Enter menu F5-1, press OK, LED display CD01 (input the ability operation
password[Note1]higher 4 digits), then display0000
, start to input.
(2) Input the ability operation password the higher 4 digits, press OK, LED display CD02
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
19/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
18
(input the ability operation password the loWPr 4 digits), then display 0000, start to
input.
(3) Input the ability operation password the loWPr 4 digits, press OK, if the input 8 digits
ability operation password is unconformity with the former one, it will display ERR, and
let you input again, if it is conformity, displayYES, then SET, set the next new
popedom password.
(4) LED displaySD01input the higher 4 digits of the new password, then display
0000, start to input.
(5) Input the higher 4 digits of the new password, press OK, LED display SD02input
the loWPr 4 digits of the new password, then display0000
, start to input.
(6) Input the loWPr 4 digits of the new password, press OK, LED display YES, means
password set successfully.
Note 1: Ability operation password is the former popedom password.
2. F5-2 Maintenance time setting:
1Enter menu F5-2, press OK, LED display CD01 (input the ability operation
password[Note1]higher 4 digits), then display 0000, start to input.
2Input the ability operation password the higher 4 digits, press OK, LED display
CD02 (input the ability operation password the loWPr 4 digits), then display 0000, start
to input.
3Input the ability operation password the loWPr 4 digits, press OK, if the input 8 digits
ability operation password is unconformity with the former one, it will display ERR, and let
you input again, if it is conformity, displayYES, then SET, set the next maintenance
time.
4Input the time, press OK to finish the set.
Note After setting the password, please keep it in your mind, never forget.
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
20/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
19
Chapter 4: Main controller adjustment
4.1 Before the adjustment:
1 Inspect all the output/input wires connecting right.
2Inspect the lift parameters set right or not.
4.2 Inspection running:
The condition under inspection running:
1Safety loop normalP10 is lighten.
2Contactor conglutination testing input normal, stop(P8 is lighten), run(P8 isnt lighten)
3Brake traveling switch testing input normal.
After start the escalator, observe the sequence is right or not, output is right or not (indication LED
lighten).
Using Y/ drive, the sequence is: Up Down signal input Delay Brake contactoropen Delay UpDowncontactor open Star contactor open Inspection running.
Using VVVF drive, the sequence is: Up Down signal input Delay Brake contactor
open Delay output contactor 1 & 2 open together UpDowncontactor open Fast car and
slow car contactor open(under self-learning, only fast car open) Inspection running.
4.3 Running normally:
The condition under running normally:
1Safety loop normalP10 is lighten.
2Contactor conglutination testing input normal, stop(P8 is lighten), run(P8 isnt lighten)
3Brake traveling switch testing input normal.
After start the escalator, observe the sequence is right or not, output is right or not (indication LED
lighten).
Using Y/ drive, the sequence is: UpDownsignal input Delay Alarm bell ring Delay Brake
contactor open Delay UpDowncontactor open Star contactor open Delay Star contactor
close Triangle contactor open running normally.
Using VVVF drive, the sequence is: Up Down signal input Delay Brake contactor
open Delay output contactor 1 & 2 open together UpDowncontactor open Fast car
contactor open
running normally.
4.4Oil-putting operation:
Oil-putting button input port input signals, oil-putting control output port output signals, the
sequenceof output show as below:
1Under motor drive oil-putting mode, when manual oil-putting signal exits, oil-putting controloutput T7 works all the time(LED lighten), if the signals disappear, outputs stop.
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
21/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
20
2Under electromagnetic valve drive oil-putting mode, when manual oil-putting signal exits,
oil-putting control output T7 works 1 second & stops 3 seconds, output circularly till the signals
disappear. When time of automatic oil-putting interval is up, it is also do it as the above sequence.
When the time of automatic oil-putting is up, stop putting the oil, T7 doesnt output(LED go out.)
3Half-auto oil-putting: After escalator running, keep the Up/Down key switch in the status of going
up or input status of going down 8 seconds, system will come to oil-putting status automaticly.
Using this mode, please note that keep the key input status conformity with the running
direction, otherwise, escalator will stop.
4.5 Aptitude running function:
This function mainly used for Moving Walk system, not suitable for Escalator.
Suitable for Y/ drive and VVVF drive. Working mode: after lift running, if no one use it, it will use
time set in advance(F211). If it is Y/ drive mode, the lift will stop at once. But if it is under VVVF mode,
no one use it, the delay stopping time(F211) is more than delay time of leisure energy-saving running
output(F2-9). The lift firstly enter to the slow speed running, till the time of stop delay is up, it will stop.
But if the delay stopping time(F211) is less than delay time of leisure energy-saving running
output(F2-9), the lift will stop at once. After than, when there is passenger, it will start automaticly or
change into high-speed running from low-speed, according the direction passenger entered(judging by
the two inductive port on the entrance). Under running, if the key switch works 3 times continuously(in 3
seconds), and keep consistent with the running direction, lift will keep this running direction till stop it.
This function should be carefully used by customer according the fact.
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
22/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
21
Chapter 5: Familiar faults & troubleshooting
Code Fault Cause Troubleshooting
P-01 Motor speedunconformity Motor fault Inspect the motor, testing speed part, ¶meterssetting, if hardware is bad, replace the bad parts.
P-02Left armrest speedunconformity
Left armrest testing speed faultInspect left armrest testing speed part, & parameterssetting, if hardware is bad, replace the bad parts.
P-03Right armrest speedunconformity
Right armrest testing speed faultInspect right armrest testing speed part, ¶meters setting, if hardware is bad, replace thebad parts.
C-05Up&Dn signalsappear together
Touchpoint/input wire faultInspect up/dn switch and input wire, if the switch isbad, replace it.
P-05Up-buttonconglutination
After lift running, button wasnt bereleased.
Inspect UP button is bad or not, replace it.
P-06Down-buttonconglutination
After lift running, button wasnt bereleased.
Inspect DOWN button is bad or not, replace it.
P-08 Contactorconglutination
Contactor/input wire fault Inspect input wire and contactor, if the contactor isbad, replace it.
P-09Brake traveling switchno action
Brake contactor/input wire faultInspect input wire and brake contactor, if thecontactor is bad, replace it.
P-10 Safety loop fault Safety loop/relay/input wire faultInspect input wire and safety relay, if the relay is bad,replace it.
P-11 Drive chain break off Drive chain break offInspect input wire and drive chain, if drive chainbreak off , replace it.
P-12 Apron left-upside Apron left-upsideInspect input wire and apron left-upside, replace thebad one.
P-13 Apron right-upside Apron right-upsideInspect input wire and apron right-upside, replace thebad one.
P-14 Gear left-upside Gear left-upside Inspect input wire and gear left-upside, replace thebad one.
P-15 Gear right-upside Gear right-upsideInspect input wire and gear right-upside, replace thebad one.
P-16Armrest entranceleft-upside
Armrest entrance left-upsideInspect input wire and armrest entrance left-upside,replace the bad one.
P-17Armrest entranceright-upside
Armrest entrance right-upsideInspect input wire and armrest entrance right-upside,replace the bad one.
P-18Step stop upside Step stop upside Inspect input wire and step upside, replace the bad
one.
P-19 Apron left-underside Apron left-undersideInspect input wire and armrest entranceleft-underside, replace the bad one.
P-20 Apron right-underside Apron right-underside
Inspect input wire and armrest entrance
left-underside, replace the bad one.
P-21 Gear left-underside Gear left-undersideInspect input wire and armrest entranceleft-underside, replace the bad one.
P-22 Gear right-underside Gear right-undersideInspect input wire and armrest entranceleft-underside, replace the bad one.
P-23Armrest entranceleft-underside
Armrest entrance left-undersideInspect input wire and armrest entranceleft-underside, replace the bad one.
P-24Armrest entranceright-underside
Armrest entrance right-undersideInspect input wire and armrest entranceleft-underside, replace the bad one.
P-25Left traction chainbreak off
Left traction chain break off Inspect input wire and traction left chain, replace thebad one.
P-26Right traction chain
break off
Right traction chain break off Inspect input wire and traction right chain, replace the
bad one.P-27
Step underside breakoff
Step underside break off Inspect input wire and step underside, replace thebad one.
-
7/31/2019 Escalator&Moving Walk Controller_ ZXK1600_ User Manual
23/23
WIPO Electronic Microprocessor Based Escalator&Moving Walk Controller WP1600 user manual
22
P-28 Left armrest break off Left armrest break offInspect input wire and left armrest, replace the badone.
P-29Right armrest breakoff
Right armrest break offInspect input wire and right armrest, replace the badone.
P-30Upside entrancesensor input
Upside entrance sensor input Inspect input wire and up touchpoint, replace the badone.
P-31 Underside entrancesensor input
Underside entrance sensor input Inspect input wire and down touchpoint, replace thebad one.
NUSEFunction limit
If the maintenance time is up, or clock doesnt work, please check the clock chip, set thefunction using limit time 0. If the clock show the wrong number, take down thebattery(poWPr off), put it again after few seconds. PoWPr on, enter into the menu F2-0,reset the default.
If there is any fault when escalator is running, stop it at once.