ERM - WordPress.com · increased detection is recommended by BS 6266 and/or BS 7273. A choice of...

46
TM0061 Page 1 of 46 Issue 2.01 ERM MANUAL TM0061

Transcript of ERM - WordPress.com · increased detection is recommended by BS 6266 and/or BS 7273. A choice of...

  • TM0061 Page 1 of 46 Issue 2.01

    ERMMANUAL

    TM0061

  • TM0061 Page 2 of 46 Issue 2.01

    PROPRIETARY RIGHTS NOTICE

    The information contained in this manual is the property of Kidde Fire Protection Services Limited andmay not be reproduced or transmitted in any form or by any means, electronic, mechanical,photocopying, recording or otherwise, nor stored in any retrieval system of any nature without theexpress written authority of Kidde fire Protection Services Limited.

    © Copyright 2002 Kidde Fire Protection Services Ltd

  • TM0061 Page 3 of 46 Issue 2.01

    Preliminary Pages

    AMENDMENT INCORPORATION RECORD

    AmendmentNumber

    Brief Description of Content

    1 Chapter 2 page 2 Clause 2.1.1.3

    2 Chapter 2 page 2 Clause 2.1.1.3

    3 Various amendments to Chapter 3

    4 Appendix A2Compatibility with Vega Control & IndicatingEquipment.

    5 Various Amendments

    6

    7

    8

    9

    10

  • TM0061 Page 4 of 46 Issue 2.01

    Preliminary Pages

    AMENDMENT INCORPORATION RECORD

    AmendmentNumber

    Brief Description of Content

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

  • TM0061 Page 5 of 46 Issue 2.01

    Preliminary Pages

    TABLE OF CONTENTS

    Chapter Page

    1. INTRODUCTION 9

    1.1 INTRODUCTION 9

    1.2 EXTINGUISHANT RELEASE MODULE 9

    1.3 SYSTEM OVERVIEW 11

    1.3.1 Fire Detection Control Panel 11

    1.3.2 Extinguishant Release Module 12

    1.3.3 Power Supply 12

    1.3.4 Status Indicators 13

    2. TECHNICAL SPECIFICATION 15

    2.1 EXTINGUISHANT RELEASE MODULE 15

    2.1.1 Outputs 15

    2.1.2 Monitored Inputs 17

    2.1.3 Unmonitored Inputs 18

    2.2 STATUS INDICATOR 19

    2.3 ENVIRONMENTAL 20

    3. INSTALLATION AND COMMISSIONING 21

    3.1 GENERAL 21

    3.1.1 Standards 21

    3.1.2 Static Sensitive Devices 21

  • TM0061 Page 6 of 46 Issue 2.01

    Preliminary Pages

    TABLE OF CONTENTS

    Chapter Page

    3.2 INSTALLATION 22

    3.2.1 Conventional Control Panel Interface 22

    3.2.2 Addressable Control Panel Interface 23

    3.2.3 Addressable Loop Interface 24

    3.3 COMMISSIONING 30

    3.3.1 Preliminary Cautions 30

    3.3.2 Initial Power Up 31

    4. CONTROLS AND INDICATORS 34

    4.1 FUNCTION OF CONTROLS AND INDICATORS 34

    4.1.1 Extinguishant Release Module 34

    4.1.2 Status Indicator 38

    4.1.3 Manual Extinguishant Release Break Glass 39

    4.2 OPERATING INSTRUCTIONS 39

    5. MAINTENANCE 41

    5.1 ROUTINE MAINTENANCE 41

    5.2 FAULT FINDING 41

    APPENDIX

    A.1 EXTINGUISHANT RELEASE MODULES 43

    A.2 VEGA CONTROL PANEL INTERFACE TO ERM 44

  • TM0061 Page 7 of 46 Issue 2.01

    Preliminary Pages

    LIST OF ILLUSTRATIONS

    Figure Page

    1-1 System Overview 13

    2-1 Terminal Board 19

    3-1 Addressable Loop Interface - Typical Example 25

    3-2 Typical System Installation 25

    3-3 ERM pcb - Wiring Diagram 28

    3-4 Status Indicator - Wiring Diagram 29

    4-1 ERM pcb 37

    4-2 Status Indicator pcb 38

    4-3 Manual Extinguishant Release Break Glass 39

    4-4 Vega panel connected to a single ERM unit 45

  • TM0061 Page 8 of 46 Issue 2.01

    THIS PAGE IS INTENTIONALLY BLANK

  • TM0061 Page 9 of 46 Issue 2.01

    CHAPTER 1

    INTRODUCTION

    1. INTRODUCTION

    The Extinguishant Release Module (ERM) forms an integral part of an approved fire detectioncontrol panel. Its microprocessor control contributes to the distributed intelligence. The designincludes safety features which reduce the chances of an accidental discharge. It is compatiblewith all forms of extinguishant formats.

    The ERM has been designed, manufactured and tested under the stringent requirements of BritishStandard (BS) 5750 Part 1.

    The ERM has been designed to meet the following standards:

    BS 7273 Parts 1 and 2.

    BS 6226.

    BS 5306 Parts 0 and 4.

    EN 55022.

    EN 54 Current Draft.

    Pre EN BCYG-2A Final Draft.

    1.2 EXTINGUISHANT RELEASE MODULE

    The ERM consists of two components: the display module and the printed circuit board (PCB).

    The display module has; a polycarbonate membrane fascia, a status indicator pcb, a manualextinguishant release unit, an AUTOMATIC/MANUAL keyswitch and LEDs complete withslider inserts for the appropriate text.

    The LEDs are labelled via four text inserts supplied with each unit:

  • TM0061 Page 10 of 46 Issue 2.01

    DESIGNATION DESIGNATION DESIGNATION DESIGNATION

    DISCHARGE DISCHARGE DISCHARGE DISCHARGE

    1st STAGE 1st STAGE 1st STAGE 1st STAGE

    2nd STAGE 2nd STAGE 2nd STAGE 2nd STAGE

    DISABLED DISABLED DISABLED DISABLED

    ABORT ABORT

    HOLD HOLD

    AUTO/MANUAL AUTO/MANUAL AUTO/MANUAL AUTO/MANUAL

    MANUAL ONLY MANUAL ONLY MANUAL ONLY MANUAL ONLY

    The text inserts can be typed on an individual basis therefore enabling multi-language capability.

    In addition text can be allocated to identify the protected area.

    The AUTOMATIC/MANUAL ONLY keyswitch allows the operator to select the desired modeof operation. The keyswitch is spring-biased, non-removable in the left and right hand operatedpositions. It is only removable in the central parked position. This configuration allows themode of operation to be switched from automatic to manual and to be controlled from numeroussources such as the main ERM, status indicators and door interlocks.

    The pcb accepts the following inputs from the main fire control panel: 1st stage, 2nd stagesilence and reset. This information is transformed using the on-board processor. The pcbincorporates numerous inputs and outputs which depending upon their importance, aremonitored.

    The manual extinguishant units are constructed of yellow thermoplastic with a micro-switchwhich is held operated by the edge of the glass. This has increased protection against accidentaloperation by means of a hinged transparent polycarbonate cover.

    The ERM is controlled via the basic commands of the main fire control panel which enables thesilencing of the audible alarms and resetting of alarm condition.

    It is of robust construction, precise with information and simple to use. The 2 wire datatransmission to status indicators has been designed to save cable on installation.

  • TM0061 Page 11 of 46 Issue 2.01

    1.3 SYSTEM OVERVIEW

    The range of fire detection and extinguishant control panel will be configured utilising threemajor components housed within the same enclosure. This will enable systems to be engineeredto meet specific requirements on an individual basis or standard configuration panels to meet thegeneral requirements of the market. The major components are: fire detection control panel,ERM and power supply.

    A system overview is shown in Figure 1-1.

    1.3.1 Fire Detection Control Panel

    The detection system should meet the minimum requirements of BS 5839 Part 1 1988, unlessincreased detection is recommended by BS 6266 and/or BS 7273. A choice of detectionmediums are available to suit the requirements of the protected risk, these are conventional andanalogue addressable.

    The current range of control panels, i.e. Sirius Antares and Procyon, have been accredited by theLoss Prevention Council Certification Board as meeting the requirements of BS 5839 Part 41988. The Vega control panel may also be used to interface with the ERM unit refer to Appendix4.2.

    1.3.1.1 Sirius

    A range of conventional fire detection panels are available in : 2-, 4-, 8-, 16-, and 32 zone formatscomplete with an integral power supply unit. The panels offer the following as a minimumstandard:

    1. Two reverse polarity monitored sounder circuits.

    2. Two sets of volt-free change-over auxiliary contacts for common alarm conditions.

    3. One set of volt free change-over contacts for common fault condition.

    4. 0 V outputs for common fault and zonal repeat.

    The panels are compatible with the products (point and beam detection) of the worlds leadingdetector manufacturers.

    1.3.1.2 Antares

    A two loop analogue addressable control panel which can be configured utilising Apollo,Hochiki or Nittan protocol offering a wide range of detection devices.

    NOTE The Nittan protocol does not have Loss Prevention Council approval with this panel.This panel offers the following as a minimum standard:

  • TM0061 Page 12 of 46 Issue 2.01

    1. Two reverse polarity monitored sounder circuits.

    2. Two sets of volt-free change-over auxiliary contacts for common alarm conditions.

    3. One set of volt-free change-over contacts for common fault conditions.

    4. A protected output (common, normally open) acting on common alarm and manualsound.

    5. 0 V 100 mA outputs for : pre-alarm, alarm repeat, buzzer repeat, fault repeat, auxiliaryrepeat and manual repeat.

    6. 0 V input terminals to activate the external fault and integral sounder circuits.

    1.3.1.3 Procyon

    A 4-, 8-, 12-, or 16- loop analogue addressable control panels which can be configured utilisingApollo, Hochiki or Nittan protocol offering a wide range of detection devices.

    NOTE The Nittan protocol does not have Loss Prevention Council approval with this panel.

    This panel offers the following as a minimum standard:

    1. Four reverse polarity monitored sounder circuits.

    2. Four sets of volt-free change-over auxiliary contacts for common alarm conditions.

    3. A protected output (common, normally open). Active on common alarm and manualsound.

    4. 0 V 100 mA outputs for: repeat, buzzer repeat, fault repeat, auxiliary repeat and manualrepeat.

    5. 0 V input terminals to activate the external fault and integral sounder circuits.

    1.3.2 Extinguishant Release Module

    An ERM is required for each area of extinguishant connected to the control panel.

    1.3.3 Power Supply

    The full range of power supplies offered have been accredited by the Loss Prevention CouncilCertification Board as meeting the requirements of BS 5839 Part 4 1988.

    The Sirius range of control panels have an integral power supply which after reviewing theloading of the system may be capable of supplying the required load for the ERM.

  • TM0061 Page 13 of 46 Issue 2.01

    The Antares and Procyon control panels will have to be powered by the standard Regulus powersupplies in the 4 or 10 Amp formats depending upon the system load requirements.1.3.4 Status Indicators

    A status indicator can be supplied as an optional addition to ERM, these are of the sameconstruction as the ERM display modules, but do not include the ERM main pcb.

    There are three types of status indicator:

    1. LEDs only

    2. LEDs and AUTOMATIC/MANUAL keyswitch.

    3. LEDs, AUTOMATIC/MANUAL keyswitch and manual extinguishant release breakglass.

    All three types can be supplied boxed or unboxed.

    A maximum of five status indicators can be connected to the ERM. The status indicator boardconnects to the main ERM via a two-core cable. The information is transferred in an RS422format which is decoded via the on-board processor PIC16C55 to illuminate the relevantindications.

    Figure 1-1 System Overview

  • TM0061 Page 14 of 46 Issue 2.01

    THIS PAGE IS INTENTIONALLY BLANK

  • TM0061 Page 15 of 46 Issue 2.01

    CHAPTER 2

    TECHNICAL SPECIFICATION 2. EXTINGUISHANT RELEASE MODULE

    The ERM pcb is constructed on a double-side board and uses the Motorola 68HC711E9 IC toprocess the operational and control data. The program and data space is contained wholly on themicrocontroller. Specific software is required to control the inputs and outputs of the processor. The software is written in C and compiles to the IC source code.

    Correct operation of the program is monitored by the watch-dog circuit. If the program shouldfail to stimulate the watch-dog at least once every 42 ms, the processor would perform a reset,therefore restoring the correct operation.

    If a fault condition occurs on either of the two sounder circuits, the release of the extinguishantwill be inhibited.

    There are two distinct types of input onto the ERM board:

    1. Monitored Inputs.

    2.1 UNMONITORED INPUTS

    All the input and output terminals will accommodate conductors of cross-sectional area between1.0 and 2.5mm.

    2.1.1 Outputs

    2.1.1.1 Sounder Circuit 1

    This reverse monitored sounder circuit is rated at 2.5 Amp and operates in two distinct modes.

    1. A pulsed mode of operation which can be configured to operate as an audible indicationof 1st stage.

    2. An intermittent mode of operation which will give an audible indication of the operationof the hold switch.

  • TM0061 Page 16 of 46 Issue 2.01

    2.1.1.2 Sounder Circuit 2

    This reverse monitored sounder circuit is rated at 2.5 Amp and operates in two distinct modes.

    1. A pulsed mode of operation to indicate that extinguishant release is imminent.

    NOTE This as a different pulse frequency to sounder circuit 1.

    2. A constant mode of operation to indicate that the extinguishant agent has been released.

    2.1.1.3 Actuator Output

    Due to the low resistance of the various types of actuators it is only possible to providemonitoring of the circuits for open circuit conditions. The circuit provides 24 V d.c in theoperated state to initiate the release of the extinguishant and the output to the actuator is rated at2 Amps.

    Compatible actuators:

    Control Head K62454.

    Control Head K62844.

    Solenoid K62422B.

    Solenoid B6793-709. Note: When using this solenoid a suppression diode must be fitted.

    2.1.1.4 Display/Status Indicator Output

    This RS422 communication link provides a two wire connection which updates the condition ofthe status LEDs, i.e discharged, 1st stage, 2nd stage, disabled, abort, hold, auto/manual andmanual only.

    2.1.1.5 24 V Output

    This is a fused output rated at 1.6 Amps and is used to provide the operational power for thestatus indicators.

    2.1.1.6 Fault Output

    This is a common fault indication which provides a 0 V output in a fault condition which willbe connected to the main control panel.

    2.1.1.7 1st and 2nd Stage Outputs

    These are 0 V outputs rated at 100 mA and activate in sympathy with the 1st and 2nd stageinputs.2.1.2 Monitored Inputs

  • TM0061 Page 17 of 46 Issue 2.01

    These inputs are taken externally to the control panel and therefore it is essential that the circuitsare monitored for open - and short-circuit fault conditions. The monitoring of the inputs isaccomplished by means of an end-of-line resistor.

    2.1.2.1 Hold

    The operation of this input, at the extinguishant release imminent stage, will stop theextinguishant release timer and activate the alarm circuit 1 in an intermittent mode. Upon releaseof the switch the extinguishant release timer will then restart.

    If the switch is operated and an alarm condition does not exist the panel will respond with a faultcondition.

    NOTE The hold switches must be of a non-latching type.

    2.1.2.2 Abort

    The operation of the input will block the release of the extinguishant by causing the panel toinitiate the disablement mode. The extinguishant can only be released by resetting the panel andrestarting the release program.

    2.1.2.3 Pressure Monitor

    This input connects to a pressure switch located on the extinguishant cylinders and will monitorfor leakages of the extinguishant that will impair the effectiveness of the extinguishant agent.

    2.1.2.4 Discharged

    This circuit connects to a flow switch usually connected to the manifold of the release pipe andgives and actual confirmation that the extinguishant has been released. Operation of this inputwill also cause the sounder circuit 2 to operate in a constant mode and the released LED on thedisplay module will illuminate.

    2.1.2.5 Manual Release

    This circuit is in parallel from the manual release located on the display unit. Activation of thiscircuit will cause the release timer to activate and unless inhibited will initiate a release.

    2.1.2.6 Automatic/Manual Key Switch

    This circuit selects the desired mode of operation from automatic and manual release of theextinguishant to manual only release. The state of change will be reflected by the LEDindications located on the display and associated status indications.

    2.1.3 Unmonitored Inputs

  • TM0061 Page 18 of 46 Issue 2.01

    These inputs are for internal use within the control panel and therefore monitoring is notrequired.

    2.1.3.1 Sounder Circuit 1 and 2

    These inputs require a 0 V input to externally operate the sounder circuits.

    NOTE The sounder circuits will operate in a continuous mode if activated fromtheseinputs.

    2.1.3.2 Zone 1 and 2

    These inputs require a 0 V input from the detection control panel from the coincidence (doubleknock crossed zoned) detection circuits to activate the 1st and 2nd stages of the unit.

    These inputs are scanned by the ERM software to protect against transients and after verificationthe input will be processed.

    2.1.1.3 Disabled

    This input requires a 0 V to block the release of the extinguishant agent, this input can beactivated from the lock of mechanism on the extinguishant cylinders or a micro-switch locatedon the control panel door.

    2.1.3.4 Silence Alarms

    This input requires a 0 V input from the fire detection control panel to silence the sounder circuit2 (extinguishant release imminent).

    2.1.3.5 Reset

    This input requires a 0 V input from the fire detection control panel to reset the ERM unit.

    2.1.3.6 Supply

    These terminals accept a 24 V supply to provide the required power for the unit. The operatingvoltage range is 21 to 28 V d.c.

  • TM0061 Page 19 of 46 Issue 2.01

    2.2 STATUS INDICATOR

    Inputs

    Receive data input terminals RX + and RX-.

    Enclosure

    The enclosure is constructed of 1.6mm (16swg) mild steel and has a paint finish of Ash grey,semi-gloss. BS 00A01, which is powder coated prior to baking. The enclosures are designed toafford a degree of protection of IP 52 to BS/EN 60529. Cable entry is via four pre-formed 20mm knock-outs located in the top of the enclosure. The back of the case has three 4 mm indentedholes to enable alignment and securing of the unit.

    On the boxed status indicators (Part Nos. ESI300, ESI200 and ESI100), the terminal board (PartNO. 29-030632-000) will be fitted to terminate external wiring at a convenient point, see Figure2.2.1

    Figure 2.1 Terminal Board (Part No 29-030632-000)

  • TM0061 Page 20 of 46 Issue 2.01

    2.3 ENVIRONMENTAL

    The ERM and status indicators, must form an integral component of the fire detection controlpanel and the proposed panels have all been approved as meeting the requirements of thefollowing tests:-

    Temperature Operating : +40, -10°C.Storage : +40, -10°C.

    Relative Humidity 93%, +2%, -3%.

    Shock and Vibration Operational: 10 to 150 Hz sinusoidal, 0.1g in all threeplanes.Endurance: 10 to 150 Hz sinusoidal, 0.1 g in all threeplanes.

    Electrostatic Discharge 8 kV.

    Electromagnetic Interference 10 V/m, 27 Mhz to 500 Mhz.

    Electrical Fast Transients 1 to 2 kV on power input cables.

    Design and Test Standards Designed and tested under BS 5750 Part 1.

    Approvals Sirius: LPCB BS 5839 Part 4.Antares: LPCB BS 5839 Part 4.Procyon: LPCB BS 5839 Part 4.

    TNO NEN 2535.Vega: LPCB prEN54 parts 2 & 4 (pending).

  • TM0061 Page 21 of 46 Issue 2.01

    CHAPTER 3

    INSTALLATION AND COMMISSIONING 3.1 GENERAL

    The installation of the extinguishant system control panel will vary depending upon whichsystem configuration has been chosen. In all cases, the guide lines given in this chapterMUST be adhered to as a minimum.

    3.1.1 Standards

    Make sure that the fire detection and extinguishant system complies with the current editionsof the :

    1. IEE Wiring Regulations.

    2. The British Standard for fire detection and alarm systems for buildings.

    3. Hong Kong Fire Services Department.

    3.1.2 Static Sensitive Devices

    A static sensitive device is any transistor or integrated circuit which may be permanentlydamaged due to electrostatic potentials and is generally encountered during routine handling,repair and transportation.

    Static electricity is produced almost every time plastics or textiles are stroked or separated.

    Static charges are collected on adjacent conductors and are delivered in the form of sparkspassing between conductors through insulating space or material. The sweat layer on thehuman skin is of a sufficient medium to store induced static charges and deliver them to anyreceptive conductor such as a component or pcb.

    Static discharges can be reduced by adhering to the following guide lines:

    1. Always use conductive or anti-static containers for transportation or storage.

    2. Wear an earth wrist strap when handling static sensitive devices, make sure that agood earth connection is maintained.

    3. Never subject static sensitive devices to a sliding movement over any surface andavoid any direct contact with the pins.

  • TM0061 Page 22 of 46 Issue 2.01

    4. Avoid placing static sensitive devices on plastic or vinyl surfaces.

    5. Minimise the handling of static sensitive devices and pcbs.

    All static sensitive devices are marked accordingly, but it is good engineering practice to treatall components and pcbs with the same degree of protection.

    3.2 INSTALLATION

    See Figures 3.2.1, 3.2.2 and 3.2.3.

    IT IS RECOMMENDED: to remove the chassis, doors and back plates from the fire controlpanel to avoid damage during installation.

    All external cables are to be securely glanded via the 20 mm preformed knock out located in thetop of the control panel enclosure.

    When the cables have been installed, clean the interior of the control panel enclosure making surethat all masonry, debris and drilling swarf has been removed.

    3.2.1 Conventional Control Panel Interface

    The Sirius range of control panels have been enhanced to provide an effective interface with theERM. The Sirius provides local output controls for silence alarms, reset and evacuate with aninput for the fault monitoring from the ERM.

    The interconnection between a 2-zone Sirius and 1 ERM is detailed in Table 3.1.

    Table 3.1 Interconnection - 2 zone Sirius and 1 ERM

    SIRIUS O/P !!!!I/P """"

    ERM

    FR1 (Zone Repeat 1) ! ZONE 1

    FR2 (Zone Repeat 2) ! ZONE 2

    SIL (Silence) ! SIL ALM

    RST (Reset) ! RESET

    FLT (Fault) " COM FLT

    EVA (Evacuate) ! ACT SND 1 or ACT SND 2

    0 V (24 V d.c. supply) ! 0 V (24 V d.c. supply input)

    24 V (24 V d.c. supply) ! 24 V (24 V d.c. supply input)

  • TM0061 Page 23 of 46 Issue 2.01

    3.2.2 Addressable Control Panel Interface

    The Antares and Procyon range of control panels utilise the special 489/490 outputs pcb toprovide the interface with the ERM. The special 489/490 output pcb provides the interface forup to nine ERMs to one addressable control panel.

    The interconnection between an addressable control panel and one ERM is detailed in Table 3.2.

    Table 3.2 Interconnection - Addressable Control Panel and 1 ERM

    Antares Procyon O/P !!!!I/P """"

    ERM

    O/P pcb (29-020555-000):

    ALM RPT (Alarm Repeat)

    MAN ALM (Manual O/P)

    FLT REP (Fault)

    O/P pcb (29-020517-000):

    ALM RPT (Alarm Repeat)

    MAN ALM (Manual O/P)

    FLT REP (Fault)

    !

    !

    !

    ZONE 1

    ACT SND 1 orACT SND 2

    COM FLT

    489/490 O/P pcb:

    More than 1 detector use:terminal 30

    Silence O/P use: terminal26

    Reset O/P use terminal 25

    Set Decode Select Link to 2

    489/490 O/P pcb:

    More than 1 detector use:terminal 22

    Silence O/P use: terminal 18

    Reset O/P use terminal 17

    Set Decode Select Link to 5

    !

    !

    !

    ZONE 2

    SIL ALM

    RESET

    0 V 0 V ! 0 V (24 V d.c.supply input)

    24 V 24 V ! 24 V (24V d.c.supply input)

    3.2.2.1 Detection - Inside the Protected Area

    This is a very basic method of co-incidence detection using default outputs to achieve co-incidence from any of the detectors in the protected area. Upon the first detector operating thealarm repeat output terminal will drive low (0 V) into Zone 1 of the ERM and using the specialoutput on the 489/490 pcb "more than 1 detector operated" driving into Zone 2 of the ERM. Therefore the co-incidence detection is achieved without any programming of the control panel.

  • TM0061 Page 24 of 46 Issue 2.01

    3.2.2.2 Multiple ERMs and/or Detection - Peripheral Areas

    The special output pcb set 489/490 located in the addressable control panel can provide sixteensets of double-knock outputs. Input devices are assigned to a set of outputs via the programmingof the control panel.

    A typical example of how the co-incidence is achieved is given below:

    1st set of outputs All the input devices assigned to the single-knock outputterminal x single-knock will be assigned to the associated double-knock output.terminal x double-knock In the event of an input device operating, the single-knock output

    will drive low (0 V). Upon a second device assigned to the outputset operating the double-knock output will drive low (0 V).

    The above example will provide co-incidence detection from any two devices within theprotected area and will have the capability to accommodate detection in peripheral areas whichwill not vote towards the discharge of the extinguishant.

    3.2.3 Addressable Loop Interface

    Using the addressable input and output modules, an extinguishant interface can be configuredremote from the control panel. This configuration utilises the programmable loop output toachieve the co-incidence. A typical example of the interface is shown in Figure 3.2.3.1.

    All equipment should be installed in the same enclosure, which should have the door fabricatedto accept the ERM display, complete with manual release break glass and auto/manual keyswitchif required, and an enable keyswitch which will give access to the momentary switches forsilence alarms reset.

    The addressable interface will vary dependent upon which protocol is used, but the basicrequirements are:-

    1. Addressable output - for 1st knock.

    2. Addressable output - for 2nd knock.

    3. Addressable input - discharged (alarm signal at main control panel).

    4. Addressable input - fault (fault signal at main control panel).

    The co-incidence is achieved as follows: Half of the detection devices located in the protectedarea will be assigned to the 1st knock output device and the other half assigned to the 2nd knockoutput device. The ERM will require local controls via an enable keyswitch to enable silencealarms and reset of the system. A local 24 V d.c power supply is required for the ERM and mayneed to power the addressable input and output devices.

    IT IS RECOMMENDED: that a local LED indicator is used and a remote indicator located on

  • TM0061 Page 25 of 46 Issue 2.01

    the main control panel fascia.

    Figure 3-1 Addressable Loop Interface - Typical Example

    Figure 3-2 Typical System Installation

  • TM0061 Page 26 of 46 Issue 2.01

    Table 3.3 Key to Figure 3.2

    CABLE TYPE CORE DESIGNATION EXTERNAL (E)OR INTERNAL (I)

    A 7C 1. O V E

    A 7C 2. 24 V E

    A 7C 3. TX + E

    A 7C 4. TX- E

    A 7C 5. ACCESS/INHIBIT E

    A 7C 6. ACCESS/INHIBIT E

    A 7C 7. MANUAL RELEASE E

    B 2C 1. 0 V I

    B 2C 2. 24 V I

    C 3C 1. 0 V I

    C 3C 2. 24V I

    C 3C 3. FAULT I

    D 5C 1. 1ST KNOCK I

    D 5C 2. 2ND KNOCK I

    D 5C 3. SILENCE I

    D 5C 4. RESET I

    D 5C 5. FAULT I

    E 7C 1. 0 V I

    E 7C 2. 24 V I

    E 7C 3. TX+ I

    E 7C 4. TX- I

    E 7C 5. ACCESS/INHIBIT I

    E 7C 6. ACCESS/INHIBIT I

    E 7C 7. MANUAL RELEASE I

  • TM0061 Page 27 of 46 Issue 2.01

    CABLE TYPE CORE DESIGNATION EXTERNAL (E)OR INTERNAL (I)

    F C6 1. ACTUATOR E

    F 6C 2. ACTUATOR E

    F 6C 3. EXTINGUISHANT RELEASE E

    F 6C 4. EXTINGUISHANT RELEASE E

    F 6C 5. PRESSURE MONITOR E

    F 6C 6. PRESSURE MONITOR E

    G 2C 1. ABORT E

    G 2C 2. ABORT E

    H 2C 1. HOLD E

    H 2C 2. HOLD E

    I 2C 1. SOUNDER CIRCUIT 2 E

    I 2C 2. SOUNDER CIRCUIT 2 E

    J 2C 1. SOUNDER CIRCUIT 1 E

    J 2C 2. SOUNDER CIRCUIT 1 E

  • TM0061 Page 28 of 46 Issue 2.01

    Figure 3-3 ERM pcb – Wiring Diagram

  • TM0061 Page 29 of 46 Issue 2.01

    Figure 3-4 Status Indicator – Wiring Diagram

  • TM0061 Page 30 of 46 Issue 2.01

    3.3 COMMISSIONING

    (a) Check that all external wiring is correctly identified and using a multimeter check thatthe cables are free from fault condition, i.e earth, open-and short-circuits.

    (b) Re-install the inner chassis into the control panel enclosure.

    (c) Connect the external wiring into their respective terminals and if applicable replacingany end-of-line resistors to the last device on the circuit.

    (d) Prior to the initial power up of the control panel, carry out the following preliminarychecks;

    (i) Check for any visible signs of damage which may been caused duringinstallation.

    (ii) verify that all installation instructions have been adhered to.

    (iii) Physically check that the main pcb is secure in its mounting.

    (iv) Check that the ribbon cable is secure and correctly connected.

    (v) Check that all cable terminations are secured.

    (e) All damage and faults must be rectified before proceeding.

    (f) Prior to connecting any a.c mains supply to the power supply unit, use a multimeter tomake sure that the supply is not present and take precautionary steps to avoidaccidental application of the a.c mains supply.

    (g) Connect the a.c. mains supply cables into the mains input terminals and remove thelocal on board mains fuse.

    3.3.1 Preliminary Cautions

    (a) Prior to the initial power up, make sure that all end-of-line monitoring resistors havebeen installed at the end of each applicable circuit and that the actuator has NOT beenconnected to the cylinders or connect dummy loads across the actuator circuits.

    (b) Make sure that adequate precautions are taken when connecting the a.c mains supplyto the power supply unit.

    (c) Make sure that all relevant personnel are aware of the commissioning procedures and that permission has been granted to sound the audible alarms and/or shut-down plantor electrical supplies.

  • TM0061 Page 31 of 46 Issue 2.01

    3.3.2 Initial Power Up

    The system specification will determine the functional operation of the installation which willbe achievable via the on-board link selects and control switches, refer to Chapter 4.

    Upon initial power up of the associated control panel the ERM will display a processor faultby illuminating LED D3, located on the main pcb and will transmit a fault output to thecontrol panel. The processor fault can be reset by operating SW1, located on the main pcb.

    As a built in safety feature, the ERM will always power up into the "manual only" mode.

    If any faults are on the external circuits they can be easily diagnosed as they are displayed onthe amber seven segment display located on the main pcb, for additional information refer toChapters 4 and 5.2.

    Once the ERM is in the quiescent mode, performance checks on the system configuration canbe made.

    Table 3.4, gives a brief summary of the performance chart. The operation of the ERM isdependent upon the link selects and the input circuits which are utilised.

  • TM0061 Page 32 of 46 Issue 2.01

    Ref I/P #1 I/P #2 Mode Action Result Notes

    1.1 Active Manual Sounder cct 1 pulsed

    1.2 Active Active Manual Sounder cct 1 pulsed

    2.1 Active Manual Sounder cct 1 pulsed

    2.2 Active Active Manual sounder cct 1 pulsed

    2.3 Active Active Auto/Man Select AUTO/MAN Sounder cct 2 pulsed

    2.4 Active Active Auto.Man Timer initiated Sounder cct 2 pulsed

    2.5 Active Active Auto/Man Timer expires Sounder cct 2 constant See Note 1

    3.1 Active Auto/Man Sounder cct 1 pulsed

    3.2 Active Active Auto/Man Timer initiated Sounder cct 2 pulsed

    3.3 Active Active Auto/Man Hold activated Sounder cct 1intermittent

    Release/timerinhibited

    3.4 Active Active Auto/Man Hold de-activatedTimer re-started

    Sounder cct 2 pulsed

    3.5 Active Active Auto/Man Timer expires Sounder cct 2 constant See Note 1

    4.1 Active Auto/Man Sounder cct 1 pulsed

    4.2 Active Active Auto/man Timer initiated Sounder cct 2 pulsed

    4.3 Active Active Auto/Man Abort activated Sounder cct 1 pulsed Release/timerinhibited

    5.1 Active Auto/Man Sounder cct 1 pulsed

    5.2 Active Active Auto/Man Timer initiated Sounder cct 2 pulsed See Note 1

    5.3 Active Active Auto/Man Disable I/P active Sounder cct 1 pulsed See Note 2.Release/timerinhibited

    6.1 Active Manual Sounder cct 1 pulsed

    6.2 Active Active Manual Sounder cct 1 pulsed

    6.3 Active Active Manual Operate manualrelease

    Sounder cct 2 pulsed

    6.4 Active Active Manual Timer initiated Sounder cct 2 pulsed See Note 1

    6.5 Active Active Manual Timer expires Sounder cct 2 constant

    " NOTE 1 Timer Delay set by SW2, refer to Chapter 4.

    " NOTE 2 Disable set by link select or input.

  • TM0061 Page 33 of 46 Issue 2.01

    THIS PAGE IS INTENTIONALLY BLANK

  • TM0061 Page 34 of 46 Issue 2.01

    CHAPTER 4

    OPERATING INSTRUCTIONS 4.1 FUNCTION OF CONTROLS AND INDICATORS

    4.1.1 Extinguishant Release Module

    The controls can be configured by the commissioning engineer to meet the expressrequirements of the specification. Unless otherwise specified the ERM will be despatchedfrom the factory in the default position.

    See Figures 4.1.1.1 and 4.1.1.2 for the ERM pcb and Status Indicator pcb respectively.

    SWITCHES

    SW2

    A horizontal hexadecimal switch that controls the delay timer which is initiated from alarmstage 2 and controls the release of the extinguishant agent.

    Listed below are switch positions and the delay in seconds.

    Switch Position Delay (seconds)

    0 01 52 103 154 205 256 307 358 409 45A 50B 55C 60D 60E 60F 60

  • TM0061 Page 35 of 46 Issue 2.01

    SW3

    A momentary push-button which when operated resets the microprocessor and re-reads anyhardware configuration changes.

    SW1

    A momentary push-button which when operated resets the processor fault D3.

    LINK SELECTS

    These links are to be configured by the commissioning engineer to meet the expressrequirements of the specification. Unless otherwise specified the ERM will be despatchedfrom the factory with the LINKS in the PARK positions.

    NOTE If the LINKS are not required, they should be placed in the PARK position.

    LINE 1 and LINK 2

    In the MADE position, these two links work as a pair to achieve gas release from theactivation of the 1st zonal input.

    LINK 3

    In the MADE position, the delay timer for the extinguishant release will be over-ridden whenthe release has been initiated by a manual release.

    LINK 4

    Affects the control of the ERM after the extinguishant agent has been released.In the MADE position the ERM will accept the reset command from the main fire detectioncontrol panel.In the PARK position, the reset command will only be successful after the flow switch hasbeen reset.

    LINK 5

    In the PARK position, a fault condition on the hold and/or abort input circuits will inhibit therelease of the extinguishant agent.

    LINK 6

    For engineering use only.In the MADE position, the ERM will revert to the disablement mode.

  • TM0061 Page 36 of 46 Issue 2.01

    INDICATORS

    Two LED indicators are provided for fault diagnosis: D3 and D2.

    D3

    An amber Led, which when illuminated, indicates that the processor has been restarted.

    D2

    An amber seven segment display which will indicate the code for individual fault. Multiplefault conditions will automatically scroll.

    The fault codes are:

    Indication Fault Condition1 Pressure monitor2 Hold circuit3 Abort circuit4 Discharge circuit5 Extinguishant released6 Manual release circuit7 Auto/manual circuit8 Sounder circuit 19 Sounder circuit 2A Actuator drive circuitb Actuator circuitb Actuator fuseC 24 V inputd 24 V outputE DisablementF Hold activated fault

    FUSES

    All fuses are 20 mm glass cartridge.

    FUSE RATING (Amps) Protects1 2.5 Sounder circuit 12 2.5 Sounder circuit 23 1.6 Actuator O/P circuit4 1.6 24 V output5 2.5 24 V input (supply)

  • TM0061 Page 37 of 46 Issue 2.01

    Figure 4-1 ERM pcb

  • TM0061 Page 38 of 46 Issue 2.01

    4.1.2 Status Indicator

    See Figure 4.1.2.1

    INDICATORS

    D13

    Which illuminates under a communications fault condition with the main ERM.

    SWITCHES

    SW1

    A momentary push-button, which performs an LED test on the display unit.

    SW2

    A momentary push-button, which performs a processor restart on the display unit.

    JUMPER

    JP1

    a jumper link, which inserts a 100 Ω terminating resistor across the RS422 data link.

    NOTE JP1 must only be inserted in the last status indicator connected to theERM board.

    Figure 4.2 Manual Gas Release Break Glass

  • TM0061 Page 39 of 46 Issue 2.01

    4.1.3. Extinguishant Release Module

    The dual action manual release units are connected to the ERM via a fully monitored circuitand can form part of the main display/status indicator or be mounted as a stand-alone unit.

    The units are constructed of a yellow thermoplastic and have a clear perspex lid to preventaccidental discharge.

    Operating instructions are printed on the perspex lid and the break glass.

    Figure 4-3 Manual Extinguishant Release Break Glass

    4.2 OPERATING INSTRUCTIONS

    The controls which govern the ERM are located on the main fire panel with the exception ofthe AUTO/MANUAL keyswitch.

    Main Fire Panel Control ERM Effect

    SILENCE ALARMS - Will silence the sounder cct 1 only, i.e 1st stage alarmcondition.

    - Silence fault buzzer generated by ERM faults.

    RESET - Will reset the ERM from fault conditions.

  • TM0061 Page 40 of 46 Issue 2.01

    - Will reset the ERM from 1st and 2nd stage alarmconditions.

    - Will silence the sounder cct 2 when the release imminentis being terminated via a reset command.

    SOUNDS ALARMS - Can generate an output to the ERM which could be usedto drive sounder cct 1 or sounder cct 2.

  • TM0061 Page 41 of 46 Issue 2.01

    CHAPTER 5

    MAINTENANCE 5.1 ROUTINE MAINTENANCE

    For routine maintenance, refer to the main fire control panel manual.

    5.2 FAULT FINDING

    All faults detected by the ERM will transmit 0 V signal to the fire control panel which will beindicated as a general fault condition: visually and audibly.

    The ERM will give a visual indication of the fault on either the amber seven segment display orLED D3. The indications, respective designation and probable cause are given in the Table 5.1.

  • TM0061 Page 42 of 46 Issue 2.01

    Table 5.1 Fault Finding

    Indication Designation Cause

    1 Pressure monitor Open or short circuit condition or 680 Ohm resistormissing from low pressure monitoring circuit.

    2 Hold Open or short circuit condition or 680 Ohm resistormissing from hold monitoring circuit.

    3 Abort Open or short circuit condition or 680 Ohm resistormissing from abort monitoring circuit.

    4 Discharge Open or short circuit condition or 680 Ohm resistormissing from pressure switch on the manifoldextinguishant monitoring circuit.

    5 Extinguishantreleased

    Monitors for a discharged confirmation signal after theactuator circuit has been activated, fault displayed after30 seconds if no discharge signal.

    6 Manual Release Open or short circuit condition or 680 Ohm resistormissing from manual release monitoring circuit.

    7 AUTO/MANUALkeyswitch

    Open or short circuit condition or 680 Ohm resistormissing from auto/man keyswitch monitoring circuit.

    8 Sounder cct 1 Open or short circuit condition or 4k7 Ohm resistormissing from sounder circuit 1, or Fuse 1.

    9 Sounder cct 2 Open or short circuit condition or 4k7 Ohm resistormissing from sounder circuit 2, or Fuse 2.

    A Actuator drive Optical component failure in the actuator drive circuit.

    b Actuator Open circuit or actuator head missing or actuator notwithin the resistance tolerance 10 to 100 Ohm.

    C 24 V input 24 V feed missing or Fuse 5 open circuit.

    d 24 V output Fuse 4 open circuit

    E Disablement Disablement enabled via Link 6 or 0 V input intodisablement terminal.

    F Hold activated If the hold circuit has been activated out of sequence(non-alarm condition).

    LED D3 Processor fault Will illuminate upon initial power up or if the processorre-starts its program can be cleared by operating SW1.

    NOTES All fault conditions latch until cleared by the control panel RESET. Fault conditions will automatically be scrolled on the amber sevensegment display.

  • TM0061 Page 43 of 46 Issue 2.01

    A.1 EXTINGUISHANT RELEASE MODULES

    A-1 Extinguishing Release Module fitted to aDunford Sirius Conventional Detection Fire Control Panel

  • TM0061 Page 44 of 46 Issue 2.01

    A.2 VEGA CONTROL PANEL INTERFACE TO EXTINGUISHANT RELEASE UNIT

    The Vega analogue addressable control panel can be configured utilising Apollo or Hochiki ESPprotocol to enable connection to a wide range of detection devices. The panel offers the followingas a minimum standard:-

    1. One detection loop with 24 zone indications. (expandable to 16 loops, 120 zones)2. Four reverse polarity monitored programmable sounder circuits.3. Four sets of volt-free change over programmable relay contacts.4. 0 volt switching inputs for external fault monitoring and remote silence \ reset functions.5. 0 volt switching outputs to silence and reset remote equipment.6. 2.5 Amp power supply unit.

    The interconnection between the control panel and one ERM is detailed in table 5.2 below.

    Vega Mblc connectionslocated on PCB 44782-K073

    E.R.M connectionslocated on PCB 29-020624-000

    Programmable Relay - REL 1 Zone 1

    Programmable Relay - REL 2 Zone 2

    Evacuate Output - TB7 O/P 6 Act Snd 1 or Act Snd 2 (as required)

    System Reset Output - TB7 O/P 7 RESET

    Silence Alarms Output - TB7 O/P 8 SIL ALM

    External Fault Input - TB7 I/P 5 COM FLT

    Table 5.2

    The 28 Volt dc supply connection should be made direct to the integral power supply charger unitlocated within the control panel.

    The Vega panels programmable relays “REL 1" and “REL 2" are used to initiate the ERM unitduring an alarm condition. These will require on site programming using the engineers softwarepackage Viper. The options available to activate a programmable panel relays are defined withinthe Viper software programme and manual.

    A typical cause \ effect programme would require “REL 1" to be set to operate on a single knockcondition for the specified zone area therefore initiating 1st stage operation on the ERM. “REL2" would be programmed to operate upon the activation of two devices (double knock) withinthe same zone area initiating 2nd stage operation on the ERM unit.

    The above example will provide co-incidence detection from any two devices within the sameprotected zone area. It is also possible using the Viper software to programme relays 1 and 2 toinitiate the ERM by two separate zones which may be located within the one protected area.

  • TM0061 Page 45 of 46 Issue 2.01

    Figure 4-4 details the wiring diagram of a standard Vega panel connected to one ERM unit.

    Figure 4-4

    Multiple ERM units within one Vega control panel

  • TM0061 Page 46 of 46 Issue 2.01

    To enable the Vega control panel to interface with multiple ERM units additional relay outputswill be required within the control panel enclosure. These can be supplied using the Vegamotherboard (44782-K091) installed with either the 8 way relay output card (44782-K092) or16 way open collector output card (44782-K095) The additional programmable panel outputs canthen be internally wired and configured to operate the relevant ERM unit through the panelprogramming.

    A suitable power supply must also be installed within the system to accommodate the increasein current requirements. These are offered as standard on a factory prepared control panel usingmultiple ERM units.

    FigurePageFigure 3-4 Status Indicator – Wiring Diagram

    Exit: Back: