Ericsson RAN GSM Training
description
Transcript of Ericsson RAN GSM Training
-
Slide 1
Troubleshooting Common
Ericsson GSM Alarms
A step by step guide.
-
Slide 2
Common Ericsson GSM Alarms
MO FLT= OML FAULT
DIGITAL PATH FAULT SUPERVISION
CELL LOGICAL CHANNEL AVAILABILITY SUPERVISION
MO FLT= PERMANENT FAULT
MO FLT= BTS INTERNAL
-
Slide 3
Common Ericsson GSM Alarms
Cont. EXTERNAL ALARMS; see Additional Info
PWR COMMERCIAL;RECT 24V MAINS;BATTERY
CORRELATED LIKE: MO FLT= TS SYNC FAULT
CELL LOGICAL CHANNELS SEIZURE SUPERVISION
CP AP COMMUNICATION FAULT
-
Slide 4
Common Ericsson GSM Alarms
Cont.
MO FLT= LOOP TEST FAILED
LOCAL MODE & OPERATOR CONDITION
-
Slide 5
MO FLT= OML FAULT
A fault exists in the communications link between the BSC and the BTS.
Alarm can come in as either Major or Critical.
Can come in on the CF, TRX, or both.
90% of the time is due to a down or faulty T1.
Can also result from a faulty TRX or loss of communication from the BSC to the TRX.
NOTE:
Prior to troubleshooting this or any other Ericsson alarm, always perform a right
click on the alarm in Netcool and chose the View alarms at this Location
option to view all alarms at this site to see if this could be a secondary affect
caused by power, maintenance, ECT and always search CTS to see if there is an
existing Ticket on the site for this or any related issue.
-
Slide 6
Recommended Troubleshooting
Steps
1. Log into appropriate Complex/BSC and
retrieve an alarm list for the parent RXOTG
by running the RXASP:MO=RXOTG-__;
for the CF listed.
SKCAB07 SCRMCAT021 MO=RXOCF-55 SLOGAN=OML FAULT
The TG number will be the same as the CF listed in the alarm.
-
Slide 7
Connecting to SKCAB07... (Use 'quit' to logoff)
-
Slide 8
-
Slide 9
3. Create a CTS Ticket
Connecting to SKCAB07... (Use 'quit' to l ogoff)
-
the site. If this is the case, the primary DIP may show WO when a portion
of the site is down (when in reality it is the second DIP that has faulted out).
You may need to determine what the secondary DIP is (if it exists) and
status it. It is important to get the correct DIP information to the field / telco
group so the correct circuit will be tested.
-
Slide 10
4. Status the DIP Quality
-
the circuit tests clean and the OML faults are still present then forward the ticket
to the field to have them check the TRXs. If the circuit test clean and the OML
faults clear, wait about 20 minutes and status the site again. If the OML faults
clear then the site has restored and you can close the TT. If the faults return then
send the ticket to the field tech with your troubleshooting notes to have him
investigate the issue.
It is important to note at this point that the CF/TG number are not always the
same as the DIP number. Secondary T1s will have a number different than that
of the TG. There can be 2 or more DIPs assigned to a CF/TG. In these cases
you will need to run a few extra commands to find the correct DIP number to
status and include in your ticket. Consider the following example using the same
commands used on the previous example.
-
Slide 11
-
Slide 12
Status the DIP using the DTSTP
command
-
Slide 13
Status DIP Quality DTQUP
-
Slide 14
RXAPP Command
-
5496/24=229 so 229RB# will be your third DIP. Now we can status all three DIPs
to see which one is faulty.
-
Slide 15
RXAPP Command Cont.
RBLT3-2167 8 UNDEF IDLE YESRBLT3-2168 9 UNDEF IDLE YES
RBLT3-2169 10 UNDEF IDLE YESRBLT3-2170 11 UNDEF IDLE YESRBLT3-2171 12 UNDEF IDLE YESRBLT3-2172 13 UNDEF IDLE YESRBLT3-2173 14 UNDEF IDLE YESRBLT3-2174 15 UNDEF IDLE YES
RBLT3-2175 16 UNDEF IDLE YESRBLT3-2176 17 UNDEF IDLE YESRBLT3-2177 18 UNDEF IDLE YESRBLT3-2178 19 UNDEF IDLE YESRBLT3-2179 20 UNDEF IDLE YESRBLT3-2181 22 UNDEF IDLE YES
RBLT3-2183 24 UNDEF IDLE YESRBLT3-5496 287 UNDEF IDLE YESRBLT3-5497 288 UNDEF IDLE YESRBLT3-5498 289 UNDEF IDLE YESRBLT3-5499 290 UNDEF IDLE YESRBLT3-5500 291 UNDEF IDLE YES
RBLT3-5501 292 UNDEF IDLE YESRBLT3-5502 293 UNCONC SPEECH/DATA YESRBLT3-5503 294 UNDEF IDLE YESRBLT3-5504 295 UNDEF IDLE YESRBLT3-5505 296 UNDEF IDLE YESRBLT3-5506 297 UNDEF IDLE YES
RBLT3-5507 298 UNDEF IDLE YESRBLT3-5508 299 UNDEF IDLE YESRBLT3-5509 300 UNDEF IDLE YESRBLT3-5510 301 UNDEF IDLE YESRBLT3-5511 302 UNDEF IDLE YESRBLT3-5512 303 UNDEF IDLE YES
RBLT3-5513 304 UNDEF IDLE YESRBLT3-5514 305 UNDEF IDLE YESRBLT3-5515 306 UNDEF IDLE YESRBLT3-5516 307 UNDEF IDLE YESRBLT3-5517 308 CONC TRXC SIGNAL NO 2 3 4 5RBLT3-5518 309 CONC TRXC SIGNAL NO 0 1
RBLT3-5519 310 CONC CF/TRXC SIGNAL NO 62 6 8 9 10
Look at the result printout and find the range of RBLT or RBLT3 devices listed.
Usually it is easy to tell if there is more than one DIP assigned because the RBLT
range will have a noticeable skip in the numbering. In this case, the devices start
with RBLT3-1560 through 1583 (first DIP). Then jumps to RBLT3-2160 through
2183 (second DIP). Then Jumps again to RBLT3-5496 through 5513 (third DIP).
To find the DIP number form these devise ranges simply divide any number in
the device range by 24 and that will give you your DIP number. 1560/24=65 so
60RB3 is your first DIP. Then
2160/24=90, so 90RB3 is your second DIP.
-
5496/24=229 so 229RB3 will be your third DIP. Now we can status all three DIPs
to see which one is faulty
-
Slide 16
Status DIP 65RB3
-
Slide 17
Status DIP 229RB3
-
Slide 18
-
Slide 19
-
Slide 20
DIGITAL PATH FAULT SUPERVISION
Indicates A T1 is down or is above the
error threshold.
Can be either a T1 to a cell site or a
Switch DIP.
Usually accompanied be an OML Fault Alarm.
Comprised of 24 devices, 1 for each DSO.
DIGITAL PATH FAULT SUPERVISION DIP=81RB3; FUALT=AIS
-
Slide 21
Recommended Troubleshooting
Steps
1. Log into the appropriate Complex/BSC
and status the DIP using the
DTSTP:DIP=____; (81RB3 in this case)
Command to check and see if the DIP is
down or taking errors.
-
Slide 22
Status DIP
Connecting to RVCAB08... (Use 'quit' to logoff)
-
Slide 23
2.Find the SNTwith DTDIP
Command
-
Slide 24
-
Slide 25
109RA3 RALT3-2616&&-2639 4378RB3 RBLT3-1872&&-1895 5179RB3 RBLT3-1896&&-1919 5280RB3 RBLT3-1920&&-1943 5381RB3 RBLT3-1944&&-1967 5482RB3 RBLT3-1968&&-1991 5583RB3 RBLT3-1992&&-2015 5684RB3 RBLT3-2016&&-2039 5785RB3 RBLT3-2040&&-2063 5886RB3 RBLT3-2064&&-2087 5987RB3 RBLT3-2088&&-2111 6088RB3 RBLT3-2112&&-2135 6189RB3 RBLT3-2136&&-2159 6290RB3 RBLT3-2160&&-2183 6391RB3 RBLT3-2184&&-2207 6492RB3 RBLT3-2208&&-2231 6593RB3 RBLT3-2232&&-2255 6694RB3 RBLT3-2256&&-2279 6795RB3 RBLT3-2280&&-2303 6896RB3 RBLT3-2304&&-2327 6997RB3 RBLT3-2328&&-2351 7098RB3 RBLT3-2352&&-2375 7199RB3 RBLT3-2376&&-2399 726RTG3 RTGLT3-144&&-167 817RTG3 RTGLT3-168&&-191 828RTG3 RTGLT3-192&&-215 83
SNT EQLEV PROT SDIP SUBSNT DEFPST SNTP MODEETM3-2 1 2ETM3 0 XM-0-0-6 2176
1 XM-0-0-17 0END
3. Status the SNT for the DIP's and their Device ranges
NTCOP:SNT=EMT3-2; Cont.
Now that we have found our DIP and its device range (located to the right of the
DIP number in the printout) we can status this device range. The devise range
numbers are the numeric value configured in the switch and the site for all 24
devises connected to that DIP.
Note: Some data (DIPS) were removed from this printout for spacing reasons.
-
Slide 26
4.Status the DIPs Device Range STDEP:DEV=RBLT3-1944&&-1967
-
Slide 27
5. Find the Site and TG.
RXMDP:MOTY=RXOTS,DEV=RBLT3-1952;
-
Slide 28
6. Status the TG to get the site ID
-
Slide 29
7. Verifying the TG has a down T1.
RXMSP:MO=RXOTG-79,SUBORD;
-
would create a CTS ticket to send to Telco with the DTSTP, RXASP, and the
RXMSP along with the correct ED path for the circuit to be tested.
Looking at this we see that not all the timeslots are in order or on the same
radio. This is done to split the rescores from the different T1s to each sector for
redundancy purposes.
-
Slide 30
7. RXMSP:MO=RXOTG-79,SUBORD; Cont.RXOTS-79-6-6 OPER 0000 0000 0840 DIS UNCONFRXOTS-79-6-7 OPER 0000 0000 0840 DIS UNCONFRXOTX-79-6 OPER 0000 0000 0000 ENA ENARXOTRX-79-7 OPER 0000 0000 STARXORX-79-7 OPER 0000 0000 0000 ENA ENARXOTS-79-7-0 OPER 0000 0000 0000 ENA ENARXOTS-79-7-1 OPER 0000 0000 0000 ENA ENARXOTS-79-7-2 OPER 0000 0000 0000 ENA ENARXOTS-79-7-3 OPER 0000 0000 0000 ENA ENARXOTS-79-7-4 OPER 0000 0000 0000 ENA ENARXOTS-79-7-5 OPER 0000 0000 0000 ENA ENARXOTS-79-7-6 OPER 0000 0000 0840 DIS UNCONFRXOTS-79-7-7 OPER 0000 0000 0840 DIS UNCONFRXOTX-79-7 OPER 0000 0000 0000 ENA ENARXOTS-79-9-0 OPER 0000 0000 0000 ENA ENARXOTS-79-9-1 OPER 0000 0000 0840 DIS UNCONFRXOTS-79-9-2 OPER 0000 0000 0840 DIS UNCONFRXOTS-79-9-3 OPER 0000 0000 0840 DIS UNCONFRXOTS-79-9-4 OPER 0000 0000 0840 DIS UNCONFRXOTS-79-9-5 OPER 0000 0000 0840 DIS UNCONFRXOTS-79-9-6 OPER 0000 0000 0840 DIS UNCONFRXOTS-79-9-7 OPER 0000 0000 0840 DIS UNCONFRXOTX-79-9 OPER 0000 0000 0000 ENA ENARXOTRX-79-10 OPER 0000 0000 STARXORX-79-10 OPER 0000 0000 0000 ENA ENARXOTS-79-10-0 OPER 0000 0000 0840 DIS UNCONFRXOTS-79-10-1 OPER 0000 0000 0840 DIS UNCONFRXOTS-79-10-2 OPER 0000 0000 0840 DIS UNCONFRXOTS-79-10-3 OPER 0000 0000 0840 DIS UNCONFRXOTS-79-10-4 OPER 0000 0000 0840 DIS UNCONFRXOTS-79-10-5 OPER 0000 0000 0840 DIS UNCONFRXOTS-79-10-6 OPER 0000 0000 0840 DIS UNCONFRXOTS-79-10-7 OPER 0000 0000 0840 DIS UNCONFRXOTX-79-10 OPER 0000 0000 0000 ENA ENAEND
-
Slide 31
MO FLT= BTS INTERNAL
A fault has occurred in the CF or in one or
more of the MOs
Can occur in the CF, TRX, RXOTX, RXORX
Usually presents in Netcool as a Major
Can sometimes be restored remotely
MO FLT= BTS INTERNAL 2 alarms: RXOTX-195-0 RXOTX-195-1
-
Slide 32
Recommended Troubleshooting
Steps1. Retrieve alarm printout from parent RXOTG
RADIO X-CEIVER ADMINISTRATION
MANAGED OBJECT ALARM SITUATIONS
MO RSITE ALARM SITUATION
RXOTG-195 LA0166
RXOCF-195 LA0166 BTS INT UNAFFECTED
RXOTX-195-0 LA0166 BTS INT AFFECTED
RXOTX-195-1 LA0166 BTS INT AFFECTED
END
Determine if the fault is service-affecting or if any other MOs are in alarm by
looking at the alarm list for the parent RXOTG. If it shows BTS INT
UNAFFECTED, this will generally not be service-affecting and will not warrant a
critical ticket on the RXOCF itself
If any other MOs show AFFECTED alarm situations, then troubleshoot them
appropriately. The fault codes reflected by the RXOCF will aid in determining the
problems on any subordinate MOs.
When the RXOTX or RXORX show BTS INT AFFECTED, it is out of service
(blocked). Usually the RXOCF or the parent RXOTRX will show a BTS INT
UNAFFECTED but will not be blocked. However, because the TX and RX are
-
blocked, from an operational standpoint the TRX is out of service as well since it
has no operating transmit or receive function.
Look the fault code up in the maintenance manual fault list to determine what it
means. The manual may also direct you to pull the fault codes from the parent
MOs that are showing unaffected faults to help further isolate the problem.
2) Retrieve the fault code(s) for the RXOCF
-
Slide 33
2. Retrieve the fault code(s) RXMFP:MO=RXOTG-195,SUBORD,FAULTY;
-
Slide 34
2. Retrieve the fault code(s) Cont.
40
MO BTSSWVER
RXOTX-195-0 ER A-G04-R08-V01
RU RUREVISION RUSERIALNO
0
RUPOSIT ION RULOGICALID
STATE BLSTATE INTERCNT CONCNT CONERRCNT LASTFLT LFREASON
NOOP BLO 00000
FAULT CODES CLASS 1B4
MO BTSSWVER RXOTX-195-1 ER A-G04-R08-V01
RU RUREVISION RUSERIALNO0
RUPOSIT ION RULOGICALID
STATE BLSTATE INTERCNT CONCNT CONERRCNT LASTFLT LFREASONNOOP BLO 00000
FAULT CODES CLASS 1B
4END
2) Retrieve the fault code(s) for the MO
Note: The actual faults are listed at the end of the printout. From here we can
see that the fault in on RXOTX-195-0 and 195-1. The fault code is 1B4. We can
now reference our documentation to see what the fault is and what actions are
required.
-
Slide 35
3. Reference the Fault code Fault No. AO TX I1B: 4
Fault name: TX antenna VSWR limits exceeded
Related fault:
SO CF I2A:8 VSWR limits exceeded
SO CF RU:40 Antenna
Description: When VSWR at CDU output exceeds the class 2 limit defined in IDB with OMT (default value: 1.8), the fault SO CF I2A:8 arises with RU map "Antenna". When VSWR exceeds the class 1 limit (default value: 2.2), the fault AO TX I1B:4 arises on TX.
Possible reasons:
Faulty IDB
Faulty CDU
TX antenna/feeder faulty or disconnected
Pfwd/ Prefl cables faulty
Measurement receiver in TRU/CU (in some cases) faulty.
Action
Reference the fault code given from our documentation to view the fault and see
what are the next steps to take. From our documentation we can see that this is
a VSWR alarm
Fault Internal 1A 4 TX Antenna VSWR Limits Exceeded
This fault means that the VSWR (voltage standing wave ratio) on the transmit
antenna or antenna feeder is too high. To keep the reflected power from burning
up the transmitter or power amplifiers, the transmitter is shut down. The RXOCF
will usually also show unaffected fault internal 2A 8 as well.
This fault is NOT remote-repairable. Even if it is a bogus alarm, generally any
blocking/deblocking of TX, TRX, CF, etc will only remove the alarm for a short
period of time, and it will return on the next periodic VSWR measurement.
-
Cut a ticket to the field with RXASP and RXMFP printout and explanation that TX
has high VSWR. The radio is out of service.
-
Slide 36
CELL LOGICAL CHANNEL
AVAILABILITY SUPERVISION
Generated to inform you that a number of
available channels have fallen below defined
limits.
Usually accompanied or correlated with additional alarms for the MOs that have
caused the channel failures.
Can present as a Critical or Major in Netcool.
Can also be caused by a down T1.
CELL LOGICAL CHANNEL AVAILABILITY SUPERVISION CELL=SD0379Y; CHTY PE=TCH
-
Slide 37
Recommended Troubleshooting
Steps
1. Right click on the alarm in Netcool and
chose the View Alarms At This Locationoption to see if there are secondary or
correlated faults that may be causing the
Alarm.
1A. If there are no secondary or correlated
alarms, search CTS on the site for
previously opened tickets.
Usually these are accompanied by secondary and/or correlated alarms. These
can come in as Major or Critical alarms. If you do find a secondary alarm, no
matter the severity, troubleshoot that alarm as instructed before moving on to the
next step. If there are no other issues at the site then we will proceed to find the
correct TG for the site in the alarm.
-
Slide 38
2. Find the correct TG correlated
with the alarm.
Connecting to SDCAB09... (Use 'quit' to logoff)
-
Slide 39
3. Status the Alarm Situation on the
TG.
-
Slide 40
4. Run RXMFP command to get
the fault codes.
-
Slide 41
4. Run RXMFP command to get
the fault codes. Cont.MO BTSSWVER RXOTX-91-4 ERA-G04-R08-V01
RU RUREVISION RUSERIALNO0
RUPOSITION RULOGICALID
STATE BLSTATE INTERCNT CONCNT CONERRCNT LASTFLT LFREASONNOOP BLO 00000
FAULT CODES CLASS 1B2
MO BTSSWVER RXOTX-91-5 ERA-G04-R08-V01
RU RUREVISION RUSERIALNO0
RUPOSITION RULOGICALID
STATE BLSTATE INTERCNT CONCNT CONERRCNT LASTFLT LFREASONNOOP BLO 00000
FAULT CODES CLASS 1B2
END