Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
-
Upload
clide050793 -
Category
Documents
-
view
232 -
download
0
Transcript of Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
1/36
8/27/20
2013 Eaton. All rights reserved.
Equipment Short-Circuit CurrentRating and Available Fault Current
Dan Neeser Field Application Engineer
Eatons Bussmann Business
2 2013 Eaton. All rights reserved.
Agenda
Interrupting Rating & Series Rating
Short-Circuit Current Ratings
Maximum Fault Current Marking
Fault Current Calculations
UL 508A Industrial Control Panels
Supplement SB - SCCR
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
2/36
8/27/20
3 2013 Eaton. All rights reserved.
Interrupting Rating
NECArticle 100 Definition Highest current an OVERCURRENT DEVICE
(fuse or circuit breaker) is rated to safely interrupt.
Self protection rating only
NEC 110.9 Interrupting Rating.
Requires the overcurrent device to have an
interrupting rating not less than the maximum
available fault current.
The maximum fault current must be calculated and
varies based on system size/location.
Similar Requirements in OSHA 1910.303(b)(4)
4 2013 Eaton. All rights reserved.
Interrupting Rating NEC 110.9: Device interrupting rating MUST
be equal to or greater than the maximum
available fault current.
Chapter 1 Video Clips - Interrupting Rating
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
3/36
8/27/20
5 2013 Eaton. All rights reserved.
1st
Determine available short-circuit
current (Isca) at lineside
terminals of each OCPD.
2nd
Apply OCPDs with adequate
Interrupting Rating.
Isca 3
MM
MSB
Isca 1
Isca 4 Isca 5
Isca 6
Isca 2
Interrupting Rating - Proper Application
6 2013 Eaton. All rights reserved.
Must select circuit breaker with interrupting rating adequate for
point of application varies by voltage and circuit breaker type.
Interrupting Rating - Proper Application
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
4/36
8/27/20
7 2013 Eaton. All rights reserved.
High Interrupting rating of current-limiting fuses at full voltage reduces
concerns about proper interrupting rating at point of application
I.R. - Proper Application
8 2013 Eaton. All rights reserved.
A combination of:
- Circuit breakers / circuit breakers
OR
- Fuses / circuit breakers
that can be applied at available fault levelsabove the interrupting rating of the load side
circuit breaker, but not above that of the mainor line side device.
Downstream device will ALWAYS be a circuit breaker
Series Rated Systems
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
5/36
8/27/20
9 2013 Eaton. All rights reserved.
Series Rated
Combination
65,000 A.I.R.200A Circuit Breaker
65,000 A.I.R.
ISC=65,000 A
20A Circuit Breaker
ISC=65,000 A
10,000 A.I.R.
Series Rated Systems: CB-CB
10 2013 Eaton. All rights reserved.
Series Rated
Combination
200,000 A.I.R.
ISC=200,000 A
20A Circuit Breaker
ISC=300,000 A
10,000 A.I.R.
Series Rated Systems: Fuse-CB
LPJ 400 SP
300,000 A.I.R.
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
6/36
8/27/20
11 2013 Eaton. All rights reserved.
Series Rated Systems
NEC 240.86(A) Selected Under EngineeringSupervision in Existing Installations The series rated combination devices must be selected
by licensed, professional engineer.
Requires Documentation and Stamp.
Series combination rating and upstream device must befield marked on end use equipment.
Downstream circuit breaker must remain passive.
NEC 240.86(B) Tested Combinations
The combination of line side and load side devices mustbe tested and marked on the end-use equipment(panelboards & switchboards).
12 2013 Eaton. All rights reserved.
Series Rated Systems
Additional Limitations and Requirements
Labeling Requirements
Manufacturer NEC 240.86(B)
Field Marking NEC 110.22(B)&(C)
Motor Contribution Limitations
NEC 240.86(C)
Motor FLA cannot exceed 1% of IR of protected CB.
Lack of Selective Coordination
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
7/36
8/27/20
13 2013 Eaton. All rights reserved.
Current Limitation
A current limiting
fuse will clear a
fault within one
half of a cycle. Thermal energy is
proportionate to thesquare of RMScurrent multiplied bythe time (Irms2t)
Mechanical stressesare proportionate to
the square of peakcurrent multiplied bythe time (Ip2t)
14 2013 Eaton. All rights reserved.
Current Limitation
Conductor protection for fault of 45kA/480V (26kA with
conductor) with non-current-limiting device (1 cycle) vs.
current-limiting device (>1/2 cycle)
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
8/36
8/27/20
15 2013 Eaton. All rights reserved.
Short-Circuit Current Ratings
NECArticle 100 Definition
The highest current EQUIPMENT can withstand without extensive
damage (fire or shock hazard).
Also known as component protection
May be based on a specific type of overcurrent device
NEC 110.10 Circuit Impedance, Short-Circuit Current Ratings,
and Other Characteristics.
Requires the equipment to have a short circuit current rating
not less than the maximum available fault current.
The maximum fault current must be calculated and varies
based on system size/location. Similar Requirements in OSHA 1910.303(b)(5)
16 2013 Eaton. All rights reserved.
Motor Starter - SCCR High Fault Test: starter
protected by an instantaneoustrip circuit breaker (MCP) thatonly provides Type 1 protection
High Fault Test: starterprotected by Low-Peak fusesthat provides Type 2 (NoDamage) protection
Fault
480V - 22,000A
Fault
480V - 22,000A
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
9/36
8/27/20
17 2013 Eaton. All rights reserved.
430.8 Marked on motor controllers
440.4(B) Marked on HVAC equipment
409.110(3) Marked on industrial control panels 409.22 Fault current cannot exceed marked SCCR
670.3(A)(4) Marked on industrial machinerycontrol panel 670.5 Fault current cannot exceed marked SCCR
UL 508A, Supplement SB is an approved methodto determine SCCR forindustrial control panelsand industrial machinery control panels
SCCR Marking Requirements
18 2013 Eaton. All rights reserved.
Fault Current Marking Requirement
110.24 Available Fault Current.
(A) Service equipment must be marked with
the maximum available fault current and
date of calculation
(B) If fault current increases due to system
modification, the marking must be updated.
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
10/36
8/27/20
19 2013 Eaton. All rights reserved.
How to Comply?
Service Equipment
Isc = 60,142 A
Isc = 27,532 AIsc = 42,153 A
Max Avail. Fault Curr ent = 58,524 A
Date Determined/Calculated: 9/2010
Isc = 18,752 AIsc = 38,525 A
Required per NEC 110.24
Motor Controller
SCCR = 25kAIndustrial Control Panel
SCCR = 30kA
Industrial Machinery Panel
SCCR = 65kA
HVAC
SCCR = 40kA
All equipment must comply with:
NEC 110.9 (IR) &110.10 (SCCR)
Engineer Calculate
Contractor Label
20 2013 Eaton. All rights reserved.
IR/SCCR Inspection Check-List
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
11/36
8/27/20
21 2013 Eaton. All rights reserved.
Fault Current Calculations
To determine the fault current:
Draw the one-line diagram
Identify sources of short-circuit current (utility,
generation, motors)
Include system component information
(tranformers, conductors, busway, overcurrent
devices are not considered)
Use calculation method (ohmic, per unit, point-to-
point, software)
Use typical fault current values as a reference
only.
22 2013 Eaton. All rights reserved.
Typical Short-Circuit Current Values
Short-Circuit Current at service entrance equipmentvaries by type/size of system: Small residential systems (100A to 200A) 10,000A to
15,000A or less
Small commercial building systems (400A to 800A) 20,000A to 30,000A
Larger commercial and manufacturing building systems(2,000A to 3,000A) - 50,000A to 65,000A
Higher short-circuit currents are possible where lowimpedance (energy-efficient) transformers are used (orwhere larger transformers (kVA) feed multiple services.
Commercial buildings directly connected to utility gridsystem 200,000A or greater
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
12/36
8/27/20
23 2013 Eaton. All rights reserved.
Short-Circuit Current Factors
Typicallyhighest atservice point
Decreases indownstreamequipment(due toimpedance oftransformers
andconductors)
24 2013 Eaton. All rights reserved.
Calculation Example
480V/3000A Service supplied from 2500 kVA
Transformer
Find Isc at Transformer Secondary & Service
Equipment480V, 3000A Service Equipment
Service Transformer
2500 kVA
13.2kV 480V
5% Impedance
7 600 Cu kcmil/phase
25 Feet in PVC
Isc = 60,142 A
Isc = 58,524A
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
13/36
8/27/20
25 2013 Eaton. All rights reserved.
IFLA =KVA X 1000
EL-L X 1.732
KVA = KVA of TransformerEL-L = Secondary Phase to Phase voltage
Calculation Example
Step One: Calculate Secondary FLA of
Transformer (3 phase)
26 2013 Eaton. All rights reserved.
2500 KVA Transformer
13.2kV - 480V, 3 Phase
Z = 5%
ISC
IFLA =2500 X 1000
480 X 1.732
IFLA = 3007 A
Calculation Example
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
14/36
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
15/36
8/27/20
29 2013 Eaton. All rights reserved.
480V
Switchgear
7 600 Cu kcmil/phase
25 Feet in PVCISC = 60,140A
Calculation Example
Calculate Short Circuit Current at 480V
Switchgear
30 2013 Eaton. All rights reserved.
ISC 480V SWGR = ISC X Mult
Calculation Example
Isc known from previous calculation
Calculate multiplier for Cable
Step One: Calculate f value
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
16/36
8/27/20
31 2013 Eaton. All rights reserved.
f =1.732 X L X ISC
C X EL-L
L = Length of conductor
ISC = Short-circuit current at beginning of circuit
C = C Value Constant for Cable
From Table. Multiply by # of runs
EL-L = Phase to Phase Voltage
Calculation Example
Step One: Calculate f value
32 2013 Eaton. All rights reserved.
Calculation Example
C Value 600 kcmil, CU, PVC = 28,033
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
17/36
8/27/20
33 2013 Eaton. All rights reserved.
f =
1.732 X 25 X 60,140
7 X 28,033 X 480= 0.0276
Calculation Example
Step One: Calculate f Value
L = 25 Feet
ISC = 60,140 A
C = 7 X 28,033 - See C Value Table
EL-L = 480V
34 2013 Eaton. All rights reserved.
Mult =1
1 + f
Step Two: Use Calculated f Value
Calculate Multiplier
Calculation Example
Mult = = 0.973111 + 0.0276
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
18/36
8/27/20
35 2013 Eaton. All rights reserved.
ISC 480V SWGR = ISC X Mult
ISC 480V SWGR = 60,140 X .9731
ISC 480V SWGR = 58,522 A*
* Add motor contribution if present
Calculation Example
Calculate Short Circuit Current at 480V
Switchgear
36 2013 Eaton. All rights reserved.
What if the System Changes?
480V, 4000A Service EquipmentService Transformer
3000 kVA
13.2kV 480V
5% Impedance
9 600 Cu kcmil/phase
25 Feet in PVC
Isc = 72,171 A
Isc = 70,587A
480V, 3000A Service EquipmentService Transformer
2500 kVA
13.2kV 480V4% Impedance
7 600 Cu kcmil/phase
25 Feet in PVC
Isc = 75,178 A
Isc = 72,667A
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
19/36
8/27/20
37 2013 Eaton. All rights reserved.
Cooper Bussmann Short-Circuit Calculator
New version
Apple or Android Apps
Web (run from homepage)
Old version
Download for Window XP
38 2013 Eaton. All rights reserved.
Choosethreephaseor
singlephasesystem
Calculating available fault current and creating 110.24 labels has never been easier!
1 2 3
ClickonAddtomy
System
Selectacomponent
youwanttoadd
Create a System
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
20/36
8/27/20
39 2013 Eaton. All rights reserved.
SelectAdd
Transformer
Calculating available fault current and creating 110.24 labels has never been easier!
1 2 3
Ifyou
have
aknown
primary
fault
currentyoucanaddithere. Ifnot,
selectassumeinfinite
Entervalues
into
the
appropriatefields
Add a Transformer
40 2013 Eaton. All rights reserved.
AfteraddingaTransformer,
youwillbeaskedifyouwant
toaddmotorcontribution
Calculating available fault current and creating 110.24 labels has never been easier!
1 2 3
Youcancompleteaquickcalculation
byselectinga%ofyour
transformersFLAoradditmanually
Addthese
calculationstoyour
system
Add Motor Contribution
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
21/36
8/27/20
41 2013 Eaton. All rights reserved.
SelectAdd
To
MySystem
Calculating available fault current and creating 110.24 labels has never been easier!
1 2 3
AddConductor
RunorBussRun
Addthecorrectvalues
andAddToSystem
Add Other Components
42 2013 Eaton. All rights reserved.
Viewsystemoneline
diagram
Calculating available fault current and creating 110.24 labels has never been easier!
1 2 3
Emailoneline
diagram
Selectaspecificfaultto
createalabel
System Summary
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
22/36
8/27/20
43 2013 Eaton. All rights reserved.
Selectafaultandclick
onCreateLabel
Calculating available fault current and creating 110.24 labels has never been easier!
1 2
Entertheemailaddress, projectname,
faultname,andlabelsize,thenSendLabel
Create a Label
44 2013 Eaton. All rights reserved.
TaponFuse
SizingDiagram
Sizing fuses for mains , feeders, and branch ci rcuits has never been easier!
1 2 3
Taponthecircuit
toprotect
Review eachsectionandthefuse
suggestionsfortheselectedlocation
Fuse Sizing
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
23/36
8/27/20
45 2013 Eaton. All rights reserved.
Calculating available fault current and creating 110.24 labels has never been easier!
TheUserguide
providesuseful
informationaboutFC2
Thereisauserguide
selectionatthebottom
ifeachpage
Basedonwhereyou
areintheapp,youwill
beprovidedaspecific
overviewofFC2s
functionality
WhiletheFC2isvery
intuitive,theremaybe
additionalquestions
ThereisaContactUs
selectionatthe
bottomofeachpage
Fromthislocation,
youcanselecttosend
anemailfortechnical
assistanceor
customerservice
support
User Guide & Contact Us
46 2013 Eaton. All rights reserved.
Cooper Bussmann FC2 Web Version - Example
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
24/36
8/27/20
47 2013 Eaton. All rights reserved.
How to Determine SCCR?
Short-Circuit Current Rating (SCCR)
Can be established by testing during the listing
and labeling process
OR
Can be determined using an approved
(calculation) method
UL 508A Supplement SB is an approved method
(industrial control panels and industrial machinery
control panel)
AHJ Approved Method
NRTL field evaluation can also be used.
48 2013 Eaton. All rights reserved.
Industrial Control Panel SCCR
Industrial Control Panel.
An assembly of two or more components consisting of one of the
following:
1)power circuit components only, such as motor controllers,
overload relays, fused disconnect switches, and circuit breakers;
2)control circuit components only, such as push buttons, pilot
lights, selector switches, timers, switches, and control relays;
3)a combination of power and control circuit components. These
components, with associated wiring and terminals, are mounted
on, or contained within, an enclosure or mounted on a subpanel.The industrial control panel does not include the controlled
equipment.
48
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
25/36
8/27/20
49 2013 Eaton. All rights reserved.
UL 508A Supplement SB
What Needs to be Analyzed per UL 508A,
Supplement SB?
All power circuit components (SB 4.1)
Feeder and branch circuit components that supply power to
loads (motors, lighting, heating and appliances)
Includes disconnect switches, fuses, circuit breakers, load
controllers, overload relays, power distribution/terminal
blocks, bus bars, etc.
Control circuit components are not required to be
analyzed Pushbuttons, pilot lights, selector switches, timers, control
relays, etc.
50 2013 Eaton. All rights reserved.
Power vs. Control Circuits
Control circuit components
dont have to be analyzed
Power
Transformer
Control Transformer
*
*Control Circuit, but
affects SCCR
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
26/36
8/27/20
51 2013 Eaton. All rights reserved.
UL 508A Supplement SB
How to Determine Component SCCR (SB4.2.2)? The SCCR marked on the component or on instructions.
The SCCR determined by the voltage rating of thecomponent and the assumed short circuit current fromTable SB4.1.
or
The SCCR for a load controller, motor overload relay, orcombination motor controller that has been investigatedin accordance with the performance requirements,including short circuit test requirements for standard faultcurrents or high fault currents specified in the Standardfor Industrial Control Equipment, UL 508, and describedin the manufacturers procedure.
52 2013 Eaton. All rights reserved.
UL 508A Supplement SB
What are the Rules (Sweep 1)?
Lowest component SCCR limits
assembly SCCR unless:
Combination ratings can be used to
increase branch circuit component ratings
(SB 4.2.2)
Component with marked/specified OCPD
Check with component manufacturer for
combination ratings
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
27/36
8/27/20
53 2013 Eaton. All rights reserved.
Combination Ratings - Branch
Use combination
ratings with
specified/marked
OCPD to fix low rated
branch components
Component SCCR OCPD I.R.
Combination ratings of overcurrent protective devices and components can be used
Nameplate
480
SCCR:
Voltage:
100kA
54 2013 Eaton. All rights reserved.
Combination Ratings - Contactor
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
28/36
8/27/20
55 2013 Eaton. All rights reserved.
Combination Ratings - MMP
OL Protection Only
Fuse or Circuit Breaker Required for
SC Protection
Suitable for Group Installations
Straight Ratings (480V)
56 2013 Eaton. All rights reserved.
Combination Ratings Type E/F
Combination Motor Controller
SC & OL Protection
Line Side Adapters Required
Slash Ratings (480/277V)
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
29/36
8/27/20
57 2013 Eaton. All rights reserved.
Combination Ratings - ASD
200kA with Class CC/J/T Fuse
Suitable for Group Installations
65kA with Type E CMC (480/277V)
58 2013 Eaton. All rights reserved.
Combination Ratings - Feeder
Use UL Listed powerdistribution block with highSCCR when used withspecified fuses or circuitbreakers and required loadside conductors
Must have feeder circuitspacing (Listed PDB) if infeeder circuit
Nameplate
480
SCCR:
Voltage:
100kA
Component SCCR OCPD I.R.
Combination ratings of PDBs is cost effective fix
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
30/36
8/27/20
59 2013 Eaton. All rights reserved.59
Combination Ratings - PDBs
PDBFS220 (4 14 Load Side
Conductors) 100kA with 175A
Class J fuse or less
60 2013 Eaton. All rights reserved.
UL 508A Supplement SB
What are the Rules (Sweep 1)?
Lowest component SCCR limits assembly
SCCR unless:
Feeder components are used that limit the short-
circuit current reducing the need for higher branch
circuit component SCCR (SB 4.3)
Current limiting overcurrent protective devices
Transformers rated 10kVA or less
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
31/36
8/27/20
61 2013 Eaton. All rights reserved.
Feeder Circuit
Branch
Circuit
Branch
Circuit
Feeder vs. Branch Circuits
62 2013 Eaton. All rights reserved.
Use of CL Devices - OCPD
CL Device must be in the feeder circuit
For CL Fuses or Circuit Breakers Use PEAK Let-through, Not RMS Let-Through (more
conservative)
Fuses - cannot use manufacturer specific fuse data only tables based on performance requirements fromUL 248 (more conservative - apply to allmanufacturers)
Circuit Breakers - must be Listed and marked current-limiting and use published let-thru curves (most circuit
breakers are not CL) Can only raise downstream BRANCH circuit
components (not overcurrent protective devices fuses/circuit breaker IR or Combination motorcontrollers SCCR)
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
32/36
8/27/20
63 2013 Eaton. All rights reserved.
Fuse LT UL vs Manufacturer
LPJ-100SP
UL Limits 50kA = 12kA
100kA = 14kA
200kA = 20kA
Manufacturer LetThrough Curves Ip LT:
50kA = 9kA
100kA = 12kA
200kA = 14kA
Irms LT: 50kA = 4kA
100kA = 5kA
200kA = 6kA
64 2013 Eaton. All rights reserved.
Current limitingfeeder OCPDcan be used to
increase branchcomponentSCCR.
Component SCCR OCPD I.R.
Use of CL OCPD can only fix components
F
B
Use of CL Devices - OCPD
Nameplate
480
SCCR:
Voltage:
14kA
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
33/36
8/27/20
65 2013 Eaton. All rights reserved.
Use of CL Devices - Transformers
CL Device must be in the feeder circuit
For Transformers If 10kVA with secondary devices (components and
overcurrent devices) of 5kA or higher, apply the IRof the primary overcurrent protective device
If 5kVA (120V Secondary) with secondary devices(Components and overcurrent devices) of 2kA orhigher, apply the IR of the primary overcurrent
protective device
66 2013 Eaton. All rights reserved.
Component SCCR OCPD I.R.
10 kVA
Use of CL Devices - Transformers
Transformers can be used tolimit the short-circuit currentavailable
If 10kVA & sec comp = 5kA+ If 5kVA/120V & sec comp = 2kA+ Then assign entire circuit I.R. of
primary overcurrent device
Use of Small Transformers (10kVA or less) can increase secondary component/OCPD ratings
Nameplate
480
SCCR:
Voltage:
200kA
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
34/36
8/27/20
67 2013 Eaton. All rights reserved.
UL 508A Supplement SB
What are the Rules (Sweep 2)?
Lowest overcurrent protective device interrupting
rating (or SCCR for some devices) always limits
assembly SCCR
All Feeder and branch circuit overcurrent devices
Tested series combination ratings or series ratings
(fuse-circuit breaker or circuit breaker-circuit breaker)
are NOT allowed.
Branch circuit overcurrent devices tapped from the feeder
circuit supplying a control circuit. Supplemental protective devices protecting the control
circuit transformer in a motor branch circuit.
68 2013 Eaton. All rights reserved.
Overcurrent Protection Devices
Branch Circuit Protective Devices
Fuses
Circuit Breakers
Application Limited Devices
Supplemental Protectors/Fuses
Not suitable for branch circuitprotection (protecting a load)
Can only be used in control circuits
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
35/36
8/27/20
69 2013 Eaton. All rights reserved.
Why High SCCR?
NEC & Equipment standards only require the
SCCR to be marked
NEC requires the marked value to be adequate
for the maximum available fault current
Although not required, high SCCR is often
preferred
Flexibility of application
Multiple installations
Fault current unknown
Insufficient SCCR can delay installation
70 2013 Eaton. All rights reserved.
Fix It - Solutions
High I.R. Protective
Devices
Class R
Class J
Class J Drive Fuse
Class T
Class CC
CubeFuse
High Speed
High IR/CL CBs
-
8/12/2019 Equipment Short-Circuit Current Rating and Available Fault Current - SW IAEI.243212239
36/36
8/27/20
71 2013 Eaton. All rights reserved.
Fix It - Solutions
High SCCR Components
2013 Eaton. All rights reserved.
Questions?