EPB17956
Transcript of EPB17956
7/24/2019 EPB17956
http://slidepdf.com/reader/full/epb17956 1/4
PRODUCT SPECIFICATION
EPB17956
DEP 2014-03-25 Page 1/4
Power Distribution Cable for SignallingSystems
Enhanced unarmoured cables RodentProtected
Construction and testing according standards
NetworkRail NR/L2/ELP/27408 BS EN 60228
BS 7655-1.3 and BS 7655-4.2IEC 60502-1
Rated Voltage
(1)0 6/1kV
Outer sheath colour
BLACK
Conductor Identification
Brown, Black
Marking on the outer sheath
On the outer sheath by embossing on two primarylines with the following information (example) :
Legend 1 (line 1):
CABELTE ELECTRIC CABLE 600/1000 V
NR/L2/ELP/27408 PVC 2x50 Cu YEAR H NMR
“Railway Catalogue number” Property of Network Rail M.M.
Legend 2 (line 2):
CABELTE ELECTRIC CABLE 600/1000 V
NR/L2/ELP/27408 PVC 2x50 Cu YEAR H NMR
“Railway Catalogue number” Property of Network Rail
Year - Year of manufacture
M.M. - Metric Marking (shall be printed)
Line 1 and line 2 are spaced ~180º.The distance between the end of one element of markingand the beginning of the next identical element of markingis ≤ 550mm.
(1) - Whilst the rated voltage is 600/1000V, the reinforced
insulation thickness permits an insulation level suitable for
voltages 1000/1730V (Uo/U).
CU/XLPE/FGT/PVC
Circular conductors schematic design
Shaped conductors schematic design
1 – ConductorStranded copper conductor s, circular (≤ 16mm
2) or
shaped (> 16mm2), class 2, according to
BS EN 60228.
2 – Insulation
XLPE type GP 8 according to BS 7655-1.3.The two insulated conductors are stranded.
3 – Bedding (only in circular conductors design)
PVC.
4 – Identification tapePolypropylene tape with a printed legend: “Property of Network Rail CABELTE YEAR”, applied over the
stranded cores.Thickness = 50µm | Minimum width = 5mm.
5 – Rodent protection
Fibreglass tape, helically applied with a minimumoverlap of 15%. Weaving design: plain weave 1/1
(272 tex). Nominal thickness of tape = 0,65mm.
Optional tape - Polypropylene plastic tape appliedunder the fiber glass tape, helically with overlap.
Nominal thickness of the tape =0,05mm
6 – Outer sheath
PVC type 9 according to BS 7655-4.2.
7 – Fillers
PVC.
5
4
2
1
6
4
3
2
1
5
6
7
7/24/2019 EPB17956
http://slidepdf.com/reader/full/epb17956 2/4
PRODUCT SPECIFICATION
EPB17956
DEP 2014-03-25 Page 2/4
Technical Characteristics
Cable designation CU/XLPE/FGT/PVC CU/XLPE/FGT/PVC CU/XLPE/FGT/PVC CU/XLPE/FGT/PVC CU/XLPE/FGT/PVC CU/XLPE/FGT/PVC CU/XLPE/FGT/PVC CU/XLPE/FGT/PVC
Voltage U0/U (kV) 0,6/1 0,6/1 0,6/1 0,6/1 0,6/1 0,6/1 0,6/1 0,6/1
Nº of cores x conductor size (mm2) 2x10 2x16 2x25 2x35 2x50 2x70 2x95 2x120
Conductor class and material Cu Class 2 Cu Class 2 Cu Class 2 Cu Class 2 Cu Class 2 Cu Class 2 Cu Class 2 Cu Class 2
Conductor nºwires x diam. of wire (mm) 7 x 1,36 7 x 1,75 7 x 2,22 19 x 1,60 19 x 1,80 19 x 2,20 19 x 2,54 36 x 2,14
Max. cond. dc resist. at 20°C (Ω/km) 1,83 1,15 0,727 0,524 0,387 0,268 0,193 0,153
Nominal core to core capacitance (F/km) 0,117 0,130 0,168 0,183 0,201 0,231 0,259 0,293
Nominal core to earth capacitance (F/km) 0,119 0,135 0,160 0,175 0,194 0,218 0,243 0,265
Zero sequence impedance (Ω/km) (1) 2,38+j2,31 1,52+j2,28 0,98+j2,25 0,72+j2,22 0,54+j2,20 0,39+j2,17 0,30+j2,15 0,25+j2,13
Positive sequence impedance (Ω/km) (1) 2,33+j0,124 1,47+j0,117 0,93+j0,110 0,67+j0,106 0,49+j0,100 0,34+j0,0968 0,25+j0,0939 0,20+j0,0920
Negative sequence impedance (Ω/km) (1) 2,33+j0,124 1,47+j0,117 0,93+j0,110 0,67+j0,106 0,49+j0,100 0,34+j0,0968 0,25+j0,0939 0,20+j0,0920
Inductance (mH/km) 0,393 0,372 0,350 0,337 0,318 0,308 0,299 0,293
Reactance (Ω/km) 0,124 0,117 0,110 0,106 0,100 0,0968 0,0939 0,0920
Impedance (cos = 0,8) (Ω/km) 1,87 1,17 0,745 0,538 0,400 0,280 0,205 0,166
Insulation material XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8
Insulation nom. thickness (mm) 2,0 2,0 2,0 2,0 2,0 2,0 2,0 2,0
Core identification colours BR-BK BR-BK BR-BK BR-BK BR-BK BR-BK BR-BK BR-BK
Sheath material PVC 9 PVC 9 PVC 9 PVC 9 PVC 9 PVC 9 PVC 9 PVC 9
Sheath min. average thickness (mm) 2,4 2,4 2,4 2,6 2,7 2,9 3,0 3,2
Rodent protection FGT FGT FGT FGT FGT FGT FGT FGT
Internal identifying tape Yes Yes Yes Yes Yes Yes Yes Yes
Approximate overall diameter (mm) 23 25 24 26 28 31 33 36
Bend Radius (mm) 92 150 192 208 224 248 264 288
Weight of cable (kg/km) 700 880 860 1060 1390 1840 2380 2880
Maximum drum length (m) (2) 5000 5000 3500 4000 3500 2500 1750 1500
Maximum pulling force – per cond. (daN) 50 80 125 175 250 350 475 600
BR - Brown
BK - Black
FGT- Fibre Glass Tape(1) Should be take only as approx. value. It is assumed that cable is installed in the ground ( earth resistivity 100Ω.m).
(2) These values may suffer slight changes.
7/24/2019 EPB17956
http://slidepdf.com/reader/full/epb17956 3/4
PRODUCT SPECIFICATION
EPB17956
DEP 2014-03-25 Page 3/4
Current carrying capacity according to BS 7671: