EP018

4
50 Hz Water-Source Heat Pumps

description

The award winning Tranquility Large (TLV) Series raises the bar for water-source heat pump efficiencies, features and application flexibility.

Transcript of EP018

Page 1: EP018

50 Hz Water-Source Heat Pumps

Page 2: EP018

The award winning Tranquility Large (TLV) Series raises the bar for water-source heat pump efficiencies, features and application flexibility.

Not only does the Tranquility Large Series exceed ASHRAE 90.1 efficiencies, but it also uses EarthPure® (HFC-410A) zero ozone depletion refrigerant, making it an extremely environmentally-friendly option. Tranquility Large Series is eligible for additional LEED® (Leadership in Energy and Environmental Design) points because of the “green” technology design.

tranquility large (tlV) SerieS

Condensate overflow is one of the 8 standard safeties provided by the microprocessor controls in all TLV Series units

Dual compressor refrigeration circuit in TLV 168-300 equipment single compressor refrigeration circuit in TLV 084-150

Optional insulated water/refrigerant circuits allow extended range operation (ground loop applications)

Belt drive blowers with high efficiency motors and multiple pulley adjustments

Wide variety of vertical configurations

Large capacity up to 87.97 kW

Galvanized steel cabinet with baked-on epoxy powder finish on all access panels

Page 3: EP018

unit Features• Vertical sizes 084 (24.6 kW) through 300 (87.9 kW)

• Unit configuration can be ordered with, or converted to

front or back return and top, front, or back discharge.

Field conversion uses all existing parts including panels

and belts

• Electrical box can be field converted to be on front or

back of unit

• Electric power can enter from any side of unit

• Water and drain can be connected to either side

• Dual refrigeration circuits (TL168, 192, 240, 300)

• Exceeds ASHRAE 90.1 efficiencies

• TXV metering device

• Extended range (-6.7 to 48.9°C) operation

• Microprocessor controls standard (optional DXM and/

or DDC controls)

• LonWorks, BACnet, Modbus and Johnson N2

compatibility options for DDC controls

• Unit Performance Sentinel performance

monitoring system

tranquility large (tlV) SerieS

Performance and SpecificationsAHRI/ISO/ASHRAE 13256-1 Data

Dimensional Data

Vertical ModelOverall Cabinet

W D H

084 -150 cm 134.9 86.4 200.7

168 -300 cm 270.9 86.4 200.7

Vertical Model

Volts Hz Phase

084 - 300 380/420 50 3

Voltage Options

Model

Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump

Cooling 30 ºC Heating 20 ºC Cooling 15 ºC Heating 10 ºC Cooling 25 ºC Heating 0 ºC

Capacity WATTS

EER W/W

Capacity WATTS

COPCapacity WATTS

EER W/W

Capacity WATTS

COPCapacity WATTS

EER W/W

Capacity WATTS

COP

TLV084 22,011 4.9 26,876 5.3 23,681 6.7 22,128 4.7 22,098 5.3 17,526 4.0

TLV096 24,971 4.8 31,008 5.2 27,521 6.6 25,205 4.6 25,147 5.1 19,343 3.8

TLV120 31,653 4.8 38,189 5.3 35,961 6.7 30,481 4.6 31,770 5.1 24,414 3.9

TLV150 40,064 4.5 48,652 5.1 45,926 6.4 39,918 4.5 40,709 4.9 30,774 3.8

TLV168 44,021 4.9 53,751 5.3 47,362 6.7 44,256 4.7 44,197 5.3 35,053 4.0

TLV192 49,941 4.8 62,016 5.2 55,041 6.6 50,410 4.6 50,293 5.1 38,687 3.8

TLV240 63,306 4.8 76,377 5.3 71,923 6.7 60,961 4.6 63,540 5.1 48,828 3.9

TLV300 80,129 4.5 97,304 5.1 91,852 6.4 79,836 4.5 81,419 4.9 61,547 3.8

Cooling capacities based upon 27°C DB, 19°C WB entering air temperature.Heating capacities based upon 20°C DB, 15°C WB entering air temperature.All ratings based upon operation at lower voltage of dual voltage rated models.Note 1 - All TLV084 ratings at 1321 l/s with sheave settings at 3.5 turns open.Note 1 - All TLV096 ratings at 1510 l/s with sheave settings at 3.5 turns open.Note 1 - All TLV120 ratings at 1888 l/s with sheave settings at 3.5 turns open.

Page 4: EP018

100 C l i m a t e M a s t e r Wa t e r- S o u rc e H e a t i n g a n d C o o l i n g S y s t e m s

C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S

P a c k a g e d U n i t sR e v. : 1 / 0 6 / 0 9 B

Revision History

Date Item Description5 Nov, 2008 Various TC Data Added16 Oct, 2008 Line Voltage Two Notes Added Below Tables and 460 Vac Note9 Sept, 2008 CXM Control Pressure Testing Note Updated

30 June, 2008 Low Volt Wiring Shut-Off Valve Note Added4 June, 2008 Various Added 460 Vac Note to Electrical Tables21 May, 2008 CXM Control Added Pressure Testing Language Note26 Nov, 2007 Line Voltage Added TS 50Hz Electrical Data14 Sep, 2007 Various Added Data for TS Size 006, 009, 01230 July, 2007 Various Updated Metric InformationMay 23, 2007 Various Added Data for TT Size 072May 23, 2007 Various Updated TS Size 018 for Rev B20 Nov, 2006 Added International Warranty20 Nov, 2006 Added GS, GR, GC 50Hz Service Data20 Nov, 2006 Added ClimaDry Reheat Option Information20 Nov, 2006 Added GS, GR, GC 50Hz Electrical Data11 July, 2005 Various Updated Low Temperature Limit Verbiage11 July, 2005 All First Published

97B0045N02

ClimateMaster works continually to improve its products. As a result, the design and speci cations of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for speci c information on the current design and speci cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products.

The management system governing the manufacture of ClimateMaster’s products is ISO 9001:2000 certi ed.

© ClimateMaster, Inc. 2005

*97B0045N02*

7300 S.W. 44th Street

Oklahoma City, OK 73179

Phone: 405-745-6000

Fax: 405-745-6058

climatemaster.com

ISO 9001:2000Certified

Quality: First & Always

R

MA

NU

FAC

TUR

ER

CERTIFIED TO ARI AS COMPLY

ING

WIT

H

ISOSTANDARD 132

56

-1

HEAT PUMPS

WAT

ERTO

AIRBRINETO

AIR

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at +1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products.

EP018 © ClimateMaster, Inc. 2010 Created: 31 August, 2010

7300 S.W. 44th StreetOklahoma City, OK 73179Phone: +1-405-745-6000