ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT...

33
ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE

Transcript of ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT...

Page 1: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

ENTERPRISE ENERGY MANAGEMENT SYSTEM

Jason Kutch, P.E.

Malcolm Drane, P.E.

UTILITY METERINGAT PURDUE

Page 2: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

2

AGENDA

• Organizational roles• Comprehensive Energy Master Plan (CEMP) goals• Metering program• Enterprise Energy Management (EEM) System• Benchmarking buildings• Project identification

Page 3: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

3

METERING

ARC FLASH

HIGH VOLTAGE

PM & C

ENGINEERING

LOW VOLTAGE

MaintenanceBLDG DEPUTIES

BLDG OCCUPANTS

BLDG CONTROLS

UTILITIES DISTRIBUTION

ADACENT PROJECTS

ORGANIZATIONAL ROLESTHE TEAM

Page 4: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

4

• Maintain meters• Add points and validation• Maintain users• View Screen creation• Set up alarms for points• Create/maintain predictive analytics models• Manage Web Configuration• History maintenance

ORGANIZATIONAL ROLES

Page 5: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

5

CEMP GOALS

• Plan was developed in 2012• Analyze production, distribution, and demand– Included metering all campus buildings– Controls optimization of building automation

systems (BAS)– System wide review of chilled water

• i.e. chiller operation, building pumps

Page 6: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

6

CEMP GOALS

• Effective Energy Management• Energy Savings Opportunities• Fiscally sustainable plan system wide• Education and Collaboration• Energy-Conscious and Environmentally responsible

culture• 10 year recurring energy and cost savings

Page 7: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

7

METERING PROGRAM• Purdue Produced utilities– Chilled Water– Electricity– Domestic Water– Steam Condensate

• Easily identify issues– Broken valve– Control deficiencies– Low delta T, high flows– Simultaneous heating and cooling

Page 8: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

METERING PROGRAM

2012• $2.3M, 43 Buildings• Master plan developed

2013• $2M• Approx. 40 buildings

2014• $2M• Approx. 40 buildings

2015

• $1M• Over 140 buildings by

2015

Page 9: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

9

METERING PROGRAM

Domestic Water Main

Domestic Water irrigation

Steam Condensate

Temperature

Supply & Return Temperature

Chilled Water

Power

Lighting

DCCP

Ethernet

ARCHITECTURE

Page 10: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

10

METERING PROGRAM

• High accuracy• Low maintenance• Low pressure drop• Smart meter verification

METER SELECTION CRITERIA

Page 11: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

11

METERING PROGRAM• Chilled and Domestic Water meters

– Inline electromagnetic– +/- 0.5 % accuracy– No moving parts or obstructions– No mechanical maintenance

• Steam Condensate meters– Vortex Shedding– +/- 1 % accuracy– No moving parts– No mechanical maintenance

• Highly accurate RTD’s – Chilled Water– Steam Condensate

MECHANICAL METERS

Page 12: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

12

METERING PROGRAMINSTALLATION GUIDELINES

Page 13: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

13

METERING PROGRAMINSTALLATION GUIDELINES

Page 14: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

14

METERING PROGRAMChilled Water Domestic Water Steam Condensate

FlowTotal GallonsSupply TempReturn TempBTU/HRTonsTotal TNHR

FlowTotal GallonsDaily Total Gallons

FlowTotal GallonsDaily Total GallonsTemperature

DATA POINTS

Page 15: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

15

METERING PROGRAM

Selection Criteria – Low Maintenance– Revenue Grade Metering– High Precision Meter

• Minimum of 0.06% accuracy– Metering Form Selection

• (Form 5 vs. Form 9)– Waveform capture– Advanced Trending and data storage– Modbus Communication

ELECTRIC METERS

Page 16: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

16

ELECTRIC METERS

• Current Transformers (CT’s)– Revenue Grade Accuracy

• 0.3% Accurate

– Core Selection• Split vs. Solid

– Sizing Considerations• Physical Size• CT Ratio • CT Rating Factor

– Low end Current

COMPONENTS

Page 17: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

17

METERING PROGRAMElectrical

VoltageCurrentPower (kVA)Energy (kWh)Demand Power (kVA/kW)Peak Demand PowerPower Factor

DATA POINTS

Page 18: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

18

METERING PROGRAM

• Centralized data• No manual meter reads• Ease of maintenance• Less traffic on BAS• Simple integration into EEM• Flexibility

DATA CONCENTRATOR CONTROL PANEL (DCCP)

Page 19: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

19

METERING PROGRAM• Design /

Fabrication Process

• Components• Benefits– Flexibility– Expandability– Maintainability

DCCP

Page 20: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

20

METERING PROGRAM

• Building Number– 1085 – ELLT

• Service– DW – domestic water

• Unique Instrument Number– 01 – meter one of domestic water

meters• Instrument Type

– ME – mechanical type• Size (inches x 100)

– 0200 – 2 inch meter

UNIQUE IDENTIFIERS

Page 21: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

21

METERING PROGRAM

• Commissioning process:– Custom program– Validate Installation– Custom Spanning

DCCP

Page 22: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

22

EEM SYSTEM• Enterprise Energy Management System - What

is it?– Real-time performance management and

predictive analytics software• EEM System software– Data historian– Predictive analytics– Electronic billing

Page 23: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

23

EEM SYSTEM• Connected systems

to EEM– Power plant– Building Automation

System (BAS)– Data Concentrator

Control Panel (DCCP)– Legacy Meters

Page 24: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

24

EEM SYSTEM

Power Plant

BAS

Utility Meters

Legacy Meters

Interfaces

EEM Historian Web Server

PC application Web application

ARCHITECTURE

Page 25: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

25

EEM View Screen

kW

Page 26: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

26

EEM View Screen

Page 27: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

27

EEM View Screen

Page 28: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

28

EEM View Screen

Page 29: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

29

BENCHMARKING BUILDINGS

JNSN KCTR KNOY LAMB LWSN LYNN MACK MANN MCUT ME MGL MRGN MTHW0

5000

10000

15000

20000

25000

30000July 2014 EUI

Elec. Steam

CW

EUI (

Btu/

sf/m

onth

)

Page 30: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

30

BENCHMARKING BUILDINGS

Page 31: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

31

PROJECT IDENTIFICATION

7/1/2

013

7/11/2

013

7/21/2

013

7/31/2

013

8/10/2

013

8/20/2

013

8/30/2

013

9/9/2

013

9/19/2

013

9/29/2

013

10/9/2

013

10/19/2

013

10/29/2

013

11/8/2

013

11/18/2

013

11/28/2

013

12/8/2

013

12/18/2

013

12/28/2

013

1/7/2

014

1/17/2

014

1/27/2

014

2/6/2

014

2/16/2

014

2/26/2

014

3/8/2

014

3/18/2

014

3/28/2

014

4/7/2

014

4/17/2

014

4/27/2

014

5/7/2

014

5/17/2

014

5/27/2

014

6/6/2

014

6/16/2

014

6/26/2

014

7/6/2

014

7/16/2

014

7/26/2

0140

500

1000

1500

2000

2500

3000

0

5

10

15

20

25

30

35

40Mann Hall CW and SC UsageCW Ton-hrSC MMBtu

Chill

ed W

ater

(ton

-hrs

)

Stea

m (M

MBt

u)

Page 32: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

32

PROJECT IDENTIFICATION

Page 33: ENTERPRISE ENERGY MANAGEMENT SYSTEM Jason Kutch, P.E. Malcolm Drane, P.E. UTILITY METERING AT PURDUE.

33

CONTACT

• Jason M. Kutch, P.E.– Mechanical Engineer; [email protected]

• Malcolm E. Drane, P.E.– Electrical Engineer; [email protected]

QUESTIONS?