Enquiry Committee Report on Grid Disturbance of 2nd January, 2010
Click here to load reader
-
Upload
trinhxuyen -
Category
Documents
-
view
382 -
download
35
Transcript of Enquiry Committee Report on Grid Disturbance of 2nd January, 2010
![Page 1: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/1.jpg)
REPORT OF THE INQUIRY COMMITTEE ON
GRID DISTURBANCE IN NORTHERN REGION
ON
2ND JANUARY 2010
JUNE 2010
![Page 2: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/2.jpg)
- i -
Content
Chapter Description Page No.
Chapter 1. Introduction 1
Chapter 2. Overview of northern regional grid 4
Chapter 3. Description of the disturbance 5
3.1 Antecedent Condition 5
3.2 Power supply positions
6
3.3 Frequency profile
6
3.4 Weather conditions
7
3.5 Brief details of the disturbance
7
Chapter 4. Phenomena of Tripping of Transmission Line during fog
9
Chapter 5 Analysis of the grid disturbance at 03:01 hrs of 2nd January, 2010
11
5.1 Tripping of the EHV transmission system before the grid disturbance at 0301 hrs of 2nd January, 2010.
11
5.2 Tripping events in the system prior to system disturbance at 03:01 hrs.
12
5.2.1 Auto-restarts on the Rihand Dadri HVDC bipole and tripping on the night of 1st January, 2010.
12
5.2.2 Complete blackout of 400/220 kV Muradnagar substation at 2339 hrs of 1st January, 2010
13
5.2.3 Complete outage of Panipat (thermal) stage-ii thermal power station at 01:55 hrs of 2nd January, 2010.
14
5.2.4 Outage of 400 kV Bus-I at Ballabgarh (PG) substation at 0255 hrs.
16
5.2.5 Efforts to reduce the import of North-West part of the system
18
5.3 Sequence of events leading to a split in the 18
![Page 3: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/3.jpg)
- ii -
system at 0301 hrs.
5.3.1 Tripping of 400 kV Bawana-Abdullapur-2 and radial operation of Jhakri HPS.
19
5.3.2 Tripping of complete Ropar TPS 20
5.3.3 Tripping of 400 kV Khedar-Moga ckt. On over-current protection.
21
5.3.4 Low voltages in Punjab system. 22
5.3.5 Separation and collapse of Punjab/ North Haryana/ HP/ UT Chandigarh and J&K system.
24
5.4 Main causes of disturbance 25
Chapter 6 Analysis of grid disturbance at 21:54 hrs on 2nd January 2010.
27
6.1 Antecedent conditions
27
6.2 Events starting from 2144 hrs leading to the disturbance at 2154 hrs.
28
6.2.1 Tripping of 400 kV Bamnauli-Ballabhgarh Ckt.-2(at Ballabhgarh end)
29
6.2.2 Tripping of 400 kV Bamnauli-Ballabhgarh ckt.-I 31
6.2.3 Feeding of Fault by Ballabhgarh-Bamnauli-II Line
33
6.2.4 Voltage dip observed around delhi system. 35
6.2.5 Tripping of 400 kV lines from Bawana to Haryana System from remote end leading to (N-4) contingency.
35
6.2.6 Tripping of 220 kV ckts. from Rajasthan towards Haryana leading effectively to an (N-6) contingency.
36
6.2.7 Tripping of 400 kV Dadri-Panipat ckt.-2 leading to an (N-7) contingency.
37
6.2.8 Effect on the NR grid on account of above tripping.
38
6.3 Nature of the sustained fault in the system fed from 400 kv Bamnauli substation and how did it get finally cleared in about two minutes.
39
![Page 4: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/4.jpg)
- iii -
6.3.1 Possibility of fault in the 220 kV network around 400/200 kV Bamnauli?
40
6.3.2 Why didn’t the fault get cleared from Bawana end on distance protection at least in Zone-2 or Zone-3?
6.3.3 Even if the distance protection at Bawana could not sense the fault, shouldn’t the directional earth fault relay at Bawana sensed this fault much earlier rather than a trip at the ends remote to Bawana?
41
6.3.4 How did the fault finally get cleared? 41
6.4 Sequence of events after clearance of the fault on 400 kV Bamnauli- Ballabgarh ckt.2: (timings as per NRLDC SoE unless otherwise stated).
41
6.5 Main causes of the disturbance 44
Chapter 7 Defense mechanism in the Grid 46
7.1 Defense mechanism available in the Northern Regional (NR) grid.
46
7.2 Recommended Settings for Load Relief 46
7.2.1 UFR setting in Northern Region as recommended by NRPC
47
7.2.2 df/dt setting in Northern Region as recommended by NRPC
47
7.2.3 Under Voltage Load Shedding (UVLS) in NR 48
7.2.4 System Protection System (SPS) 49
7.3 Performance of the defense mechanism in above disturbance
49
7.3.1 Performance of UFR and df/dt scheme at 03.01 hrs of 2nd Jan 2010
50
7.3.2 Performance of UFR and df/dt scheme at 21.54 hrs of 2nd Jan 2010
51
7.4 Performance of ULVS 52
7.5 What could be possible reasons for inadequate relief from UFRs, and df/dt relays
55
Chapter 8 Restoration of the system
57
![Page 5: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/5.jpg)
- iv -
8.0 General 57
8.1 Restoration after event at 0301 hrs
57
8.1.1 Challenges experienced in reaching the hydro
stations during restoration
57
8.1.2 Bottlenecks experienced in extending start up
to thermal stations
57
8.1.3 Issues during Black start of hydro units 58
8.1.4 Issues in BBMB system 58
8.1.5 Railway traction supply 58
8.2 Restoration Sequence of the incidence at 0301
hrs
59
8.3 Restoration after event at 2154 hrs
59
8.4 Restoration Sequence of the incident at 21:54
hrs
60
8.5 Supply interruption to Railways and its restoration
62
Chapter 9. Corrective measures taken to overcome the crisis during foggy winter period.
65
9.1 Tripping of line during Fog 65
9.2 Auto recloser during foggy weather 65
9.3 Crisis Management Group (CMG) 66
9.4 Actions taken before the onset of winter during 2009-10
66
9.4.1 Replacement of Insulators 66
9.4.2 Cleaning of Insulators 67
9.4.3 Shutdown of lines permitted by NRLDC in order to facilitate insulators replacement/ cleaning
67
9.4.4 Mock Black Start Trial 67
9.4.5 Real time Monitoring of Humidity and Temperature of different locations and the weather forecast from different agencies
68
![Page 6: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/6.jpg)
- v -
9.4.6 Deployment of additional manpower during the night shifts
68
9.5 Others measures for enhancing the reliability of the grid
68
9.5.1 Monitoring of Under Frequency Load Shedding (UFRLS), Under Voltage Load Shedding (UVLS)
68
9.5.2 Protection Audit for up gradation of Protection System in Northern Grid
69
9.5.3 Availability of real time data from different generation stations and substations
Chapter 10. Review of implementation of recommendation
of enquiry committee on grid incident of 27th
January, 2007 and 7th/9th march, 2008.
70
Chapter 11. Recommendations 72
1 Implementation of Recommendations of Inquiry
Committee on Grid Incident of 27th Jan 2007
and 7th & 9th March 2008
72
2 Replacement of existing insulators by Polymer/
Antifog Insulators
73
3 Cleaning of Insulators 74
4 Maintenance of System Elements
74
5 Maintenance of System Elements around
NAPS
75
6 Monitoring Mechanism 75
7 Alertness during foggy condition 75
8 Railway Supply Reliability 76
9 Protection Coordination 77
10 Requirement to change the CT ratio to higher
range
78
11 Functioning of RTU and data telemetry facilities 78
12 Adequate back-up power supply by at wide
band communication node/ repeater stations
78
13 Effectiveness of defense mechanism and
adequacy of safety net
79
14 Healthiness of DR/EL and time synchronization 79
![Page 7: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/7.jpg)
- vi -
15 Commissioning of additional 400 kV links to
take care of fog related tripping
80
16 Reactive Power Management 80
17 Pollution control 81
18 Chemical analysis of deposit on Insulators
Strings
81
19 Pollution mapping 81
20 Other Issues 82
Annexure No. Annexure Description
Annexure 1/ I Minutes of the meeting of crisis management Group
(CMG)
Annexure 1/ II Minutes of the meeting of crisis management Group (CMG)
Annexure 1/ III Central Electricity Authority order for constituting Committee
Annexure 1/ IV The minutes of this meeting convened by Joint Secretary (Trans), MOP, Govt. of India on 18th January, 2010.
Annexure 3/ I Plot of temperature and humidity for 27th Dec 2009 to 7th Jan 2010
Annexure 3/ II Plot of load profile of 1st, 2nd & 3rd Jan 2010 with respect to 31st Dec 2009
Annexure 3/ III The breakup of loss of generation during the two incidents of grid disturbance on 2nd Jan 2010
Annexure 4/ I The Mechanism of flash over during the occurrence of fog and factors contributing to increased pollution levels (The extract from the grid incident on 27.01.2007 and 7/9th March, 2008)
Annexure 5/ I The list of lines which tripped right from the night hours of 1st January 2010
Annexure 5/ II The Sequence of Events (SoE) recorded at NRLDC SCADA System
![Page 8: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/8.jpg)
- vii -
Annexure 6/ I The Sequence of Events (SoE) recorded at NRLDC
Annexure 7/ I Line tripping details submitted by PSEB
Annexure 7/ II UFR and df/dt report from PSEB
Annexure 7/ III UFR and df/dt report from BBMB
Annexure 7/ IV Analysis report submitted by Haryana
Annexure 7/V UFR report from HVPNL
Annexure 7/VI Detail of UFR and df/dt report from HP
Annexure 7/VII Report of BBMB
Annexure 7/VIII Analysis report of BBMB
Annexure 8/ I Restoration Sequence of the incidence at 0301 hrs
Annexure 9/ I Review of the progress of replacement of the porcelain insulators by polymer/antifog insulators
Annexure 9/ II Cleaning of Insulators
Annexure 9/ III The list of line shutdowns approved by NRLDC and availed by the constituents from 1st September 2009 to 31st December 2009
Annexure 9/ IV UFR relief ( With ref. to 14th TCC/ 15th NRPC)
Annexure 9/ V Protection Audit for up gradation of Protection System ( With ref. to 14th TCC/ 15th NRPC)
Annexure 9/ VI The extract minutes of 24th Unified Scheme Monitoring Group (USMG) meeting of NRPC held on 24th August 2009
Annexure 10/ I The Minutes of Insulators replacement monitoring meeting.
Annexure 10/ II The Minutes of Insulators replacement monitoring meeting.
Annexure 10/ III Review of progress of Insulators replacement.
Annexure 10/ IV The report of Pollution severity testing done by CPRI
Annexure 10/ V Pollution measurement got done by POWERGRID
![Page 9: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/9.jpg)
- viii -
Annexure 10/ VI A brief status on the implementation of recommendations
of the enquiry committees on Grid Disturbances in NCR
![Page 10: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/10.jpg)
- ix -
Exhibit No. Exhibit Description
Exhibit-2/ I The Map indicating 400 kV and above lines in NR
Exhibit-5/ I The power map of Haryana
Exhibit-5/ II The Numerical relay output of this line at Ballabgarh end
Exhibit-5/ III DR output of this circuit at Abdullapur end
Exhibit-5/ IV Power map of Punjab
Exhibit-5/ V The Tabular Trends for the Ropar TPS, the units 3, 4, 5
and 6 synchronization
Exhibit-5/ VI The output from the Data Acquisition System (DAS) of Ropar TPS, the units 3, 4, 5 and 6
Exhibit-5/ VII the REL 670 Numerical Relay output of this line at Khedar end
Exhibit-5/VIII The Numerical Relay outputs of 400 kV Jhakri-Nalagarh-2 at Jhakri
Exhibit-5/ IX The Numerical Relay output at Malerkotla
Exhibit-5/ X The pictorial representation of the axis of separation of Punjab/North Haryana/HP/UT Chandigarh/J&K system from the main NEW grid.
Exhibit-6/ I The Numerical Relay output at Ballabgarh end
Exhibit-6/ II The Numerical Relay output at Ballabgarh end
Exhibit-6/ III The Numerical Relay output at Bahadurgarh
Exhibit-6/ IV Timing as per Hissar EL
Exhibit-6/ V DR and EL output of Abdullapur end
Exhibit-6/ VI DR and EL output of Abdullapur end
Exhibit-6/ VII MICOM P437 Numerical Relay of AREVA make
Exhibit-6/ VIII REL 511 Output at Bamnauli
Exhibit-6/ IX Numerical Relay and EL output of Hissar & Bawana
![Page 11: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/11.jpg)
- x -
Exhibit-6/ X Numerical Relay output at Dadri
Exhibit-6/ XI EL and Numerical relay output at Abdullapur
Exhibit-6/ XII EL and Numerical relay output at Malerkotla
Exhibit-6/ XIII The axis of separation of Punjab/Haryana/HP/J & K
system from rest of the grid
Exhibit- 7/1 Historical Tabular Trend of Ropar
![Page 12: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/12.jpg)
- xi -
EXECUTIVE SUMMARY
Northern Region (NR) experienced a partial grid disturbance on 2nd January, 2010 at 0301 Hrs in which power supply in Punjab, North Haryana, HP, J&K & UT Chandigarh sub system was affected. This was followed by another partial disturbance almost on the similar pattern, during late evening Hrs. on the same day i.e. 2nd January, 2010 at 2154 Hrs. Central Electricity Authority (CEA) vide its order dated 08-01-2010 constituted a Committee comprising the following to inquire into the grid incident and ascertain the cause of grid disturbance and suggest remedial measures to avoid recurrence of such incident. The Inquiry Committee in its first meeting co-opted the members from CEA, BBMB, POWERGRID, HPGCL, PSEB, HPSEB for this committee. The Inquiry Committee had held three meetings and two separate meetings of expert were also held to analyze the incidents and preparation of the report.
A brief summary of the Report is given below:
Northern Region (NR) experienced a partial grid disturbance on the night of 1st & 2nd January, 2010 at 0301 Hrs in which power supply in Punjab, North Haryana, Himachal Pradesh, Jammu & Kashmir & UT Chandigarh sub system was affected. This was followed by another partial disturbance almost on the similar pattern, during late evening Hrs. on the same day i.e. 2nd January, 2010 at 2154 Hrs.
1. Morning incident
The morning incident was initiated due to outage of large numbers of 220 kV and 400 kV lines particularly in the North-West part of the region due to fog related tripping. There was an unintended and unexpected operation of over current protection on 400 kV Khedar-Moga circuit which caused severe voltage drop in Punjab/ North Haryana system (below 360 kV) on account of heavy loading (more than 800 MW) on 400 kV Dadri-Malerkotla line leading to high reactive power losses of the order of 1,000 MVAR. This has resulted into tripping of 400 kV Dadri-Malerkotla line and other 220 kV lines and isolated Punjab/ North Haryana/ HP/ UT Chandigarh and J&K system from rest of the NEW grid. Due to isolation from the grid, there was deficit of 1850-1900 MW in the
1 Shri S.M. Dhiman Member (GO&D), CEA Chairman 2 Shri Y.K. Raizada Director (Tech), RRVPNL Member 3 Shri R.P. Singh Director (Elec), SJVNL Member 4 Shri A.K. Aggarwal Member Secretary, NRPC Member Convener 5 Shri V.K. Agrawal General Manager, NRLDC Member 6 Shri Anil Kumar Gupta Executive Director, PTCUL Member
![Page 13: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/13.jpg)
- xii -
separated system and it collapsed leading to a loss of about 7500 MW. The separated system had split into several parts as NJHPS, Panipat-II and Ropar had islanded from the main system as separate pockets.
2. Evening incident
At around 2144 Hrs, the earth wire of 400 kV Bamnauli-Ballabhgarh ckt-II snapped and fell on R-phase. The R phase pole of the circuit breaker struck at Ballabhgarh end and LBB was operated to clear the fault. The fault was not cleared from Bamnauli end, and was fed for about 2 minutes.
The LBB protection at Bamnauli was not in operation probably it was disabled by operators to avoid any unwanted operation during the switching. Feeding of fault for about 2 minute caused severe voltage drop around Delhi system and caused tripping of some important lines from Bawana substation feeding Haryana system. This led to more than 1600 MW power flow to North-West part of the grid from Bawana getting disrupted and led to increase in flow on other parallel paths from Dadri NTPC , Ballabhgarh (220 kV) and through Rajasthan system. The lines from Rajasthan system feeding Haryana tripped on overload and further depleted the transmission network.
400 kV Dadri-Panipat ckt-II tripped on operation of Zone-5.Thus, within a minute the system experienced multiple contingency.
At around 2149 hrs 400 kV Hissar-Bawana was restored from Hissar end providing some relief to the congested Dadri-Panipat and Dadri-Malerkotla sections. However, this line tripped on earth fault within 25 secs due to damage of B phase jumper at location no. 35.
400 kV Dadri-Panipat –I tripped on distance protection on transient fault. The line failed to auto- reclose at Dadri end as the loading of the line was of the order of 1800 A.
With the above tripping, at about 2154 hrs, Punjab/Haryana/HP/J & K system separated from rest of the grid (barring a small portion of HP system which remained connected with the Uttarakhand power system radially and small portion of Faridabad and Gurgaon areas connected to Ballabgarh which survived) and collapsed within a few seconds on account of low frequency and failure of the defense mechanism. The detailed recommendations of the Committee to avoid reoccurrence of such disturbance in future and for safe and secure operation of the Grid are elaborated at Chapter-11 of the Report. The major recommendations are as given below: -
Replacement of existing insulators by Polymer/ Antifog Insulators and also to identify additional line for replacement of porcelain insulator with polymer which are getting frequently affected due to fog in winter season.
Railways to make arrangement for additional supply point(s) for the traction system to enhance the reliability and also to replace all porcelain insulators of 132 kV and 220 kV lines with polymer insulators
Increasing alertness during foggy conditions.
![Page 14: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/14.jpg)
- xiii -
Protection coordination and Audit by third party in NR Effectiveness of defense mechanism and adequacy of safety net Ensuring functioning of RTU and data telemetry facilities Planning/Commissioning of additional 400 kV links to take care of fog related
tripping. Reactive Power Management to be ensured Pollution control near the line corridor.
MS, NRPC & Member Convener of the Inquiry Committee made the presentation before CEA on 03.06.2010. The report and its recommendations were discussed in detail. CEA accepted the report submitted by the inquiry committee and directed that an action plan may be formulated by NRPC for implementation of the recommendations of the committee by the concerned utilities in a time bound manner.
------------------------------------------------
![Page 15: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/15.jpg)
- 1 -
CHAPTER 1 INTRODUCTION 1.1 Northern Region (NR) experienced a partial grid disturbance on the night of 1st & 2nd
January, 2010 at 0301 Hrs in which power supply in Punjab, North Haryana, Himachal Pradesh, Jammu & Kashmir & UT Chandigarh sub system was affected this was followed by an other partial disturbance almost on the similar pattern, during late evening Hrs. on the same day i.e. 2nd January, 2010 at 2154 Hrs. The meeting of the Crisis Management Group (CMG) was held on 2nd January in the NRLDC control room and again full meeting was held on 4th January, 2010. Decisions taken in these meetings for immediate implementation of corrective measures by the power utilities of Northern Region was issued and also placed on the NRPC website. A copy of the minutes of the meeting is enclosed at Annexure-1/ I and 1/ II.
1.2 The Central Electricity Authority vide their order no. CEA/5-41 (07) / Secy-2009 dated
08-01-2010 (Annexure-1/ III) constituted a Committee comprising the following to inquire into the grid incident and ascertain the cause of grid disturbance and suggest remedial measures to avoid recurrence of such incident:
1 Shri S.M. Dhiman Member (GO&D), CEA Chairman 2 Shri Y.K. Raizada Director (Tech), RRVPNL Member 3 Shri R.P. Singh Director (Elec), SJVNL Member 4 Shri A.K. Aggarwal Member Secretary, NRPC Member
Convener 5 Shri V.K. Agrawal General Manager, NRLDC Member 6 Shri Anil Kumar Gupta Executive Director, PTCUL Member
1.3 Following officers of the constituents of the NRPC were designated as nodal officers of
the respective organizations, who were to facilitate collection of information required by the Committee for the purpose of analysis.
i) Sh. Mir Quasim, CE (SO), PDD, J&K ii) Sh. V.K. Gupta, CE (SO), PSEB iii) Sh. H.R. Satija. CE (SO), HVPNL iv) Sh. B.B. Sharma, GM, (OM), DTL v) Sh. B. Sharma, GM (NR-I), POWERGRID vi) Sh. P.K. Pal, GM (P&O), Powerlinks Transmission Ltd. vii) Sh. S Parameshwaran, CE, (O&M), NHPC viii) Sh. Rajesh Kr. Jain, Director, Ministry of Railway ix) Sh. Suneel Grover, Director, (PR & CERC), HPSEB x) Sh. P.P. Francis, AGM (OS), NTPC xi) Sh. Sawinder Singh, Senior Executive Engineer, BBMB
1.4 The Terms of reference of the Committee are as under:
![Page 16: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/16.jpg)
- 2 -
i) To analyze the causes and circumstances leading to tripping of lines on 2nd January, 2010 partially affecting power supply in Northern Region.
ii) To suggest remedial measures to avoid recurrence of such disturbances in future, taking into consideration the recommendations of the similar Committees constituted earlier.
iii) To review the restoration of system following the disturbances and suggest measures for improvement in this regard.
iv) Other relevant issues concerning safe and secure operation of the grid. 1.5 The NRPC in its communication to the constituents of the NR requested for submitting
the information related to grid incident along with DR and EL to NRPC Secretariat. The first meeting of the Committee was held on 12th Jan 2010 at NRPC, New Delhi. A detailed presentation of the events during the above incidents was made by the NRLDC and thereafter the action taken by the constituents was also discussed. The Committee decided to co-opt the following as members of this committee.
i) Sh. Ajay Talegaonkar- Director(GM Division) CEA, New Delhi ii) Sh. R S Lamba- Director (PR) BBMB, Chandigarh iii) Sh. Jagmohan Sharma, GM, POWERGRID (NR-II), Jammu iv) Sh. Rakesh Bansal, SE, HPGCL, Panchkula, Haryana v) Sh. V K Gupta Chief Engineer(SO) PSEB vi) Sh. Suneel Grover Director (PR & CERC), HPSEB, Shimla
Meanwhile, the Honourable Central Electricity Regulatory Commission (CERC) vide its order dated 14th January 2010 has directed the CTU and NRLDC to carry out a detailed study of the grid disturbance which occurred on 2.1.2010 and submit a report containing the reasons for grid disturbance, preventive steps taken so far and the suggested remedial measures by 30.1.2010. This report was submitted to the Commission by NRLDC.
On this issue, a meeting was also convened by Joint Secretary (Trans), MoP, Govt. of India on 18th January, 2010 at Shram Shakti Bhawan, New Delhi and the subject matter along with the remedial measures were discussed. A copy of the minutes of this meeting is enclosed at Annexure-1/ IV.
The second meeting of the committee was held on 18.02.10 in which NRLDC made a detailed presentation. The committee deliberated on the protection system, defense mechanism and concerns of railways. In order to analyses the poor performance of UFR and df/dt relays, it was decided that constituents would submit the relay wise data to NRPC secretariat by 28th Feb 2010. The committee analyzed the information of data supplied by the constituents and NRLDC on its SCADA system. The third meeting was held on 10th March 2010, wherein deliberations were made on reliability of railway supply, tripping of Panipat & Ropar TPS, effectiveness of UFRs & df/dt relays and tripping of Delhi sub system. It was decided that a separate meeting of experts would be held to analyze the tripping of Panipat TPS, Ropar TPS,
![Page 17: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/17.jpg)
- 3 -
effectiveness of UFR & df/dt relays and tripping at Bamnauli sub-station during Grid disturbance of 2nd January 2010. As the complete information was not received from the constituents, NRPC secretariat took the matter with them again. The information from the constituents was received in March/April 2010. The details received were further deliberated in a small group of experts in April 2010.
![Page 18: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/18.jpg)
- 4 -
CHAPTER 2 OVERVIEW OF NORTHERN REGIONAL GRID 2.0 OVERVIEW OF NORTHERN REGIONAL GRID
2.1 Northern Region is the largest in geographical area amongst the five regions in the country covering approximately 31% of the area and having largest number of constituents (9 States/UT, 4 Central Generating Companies, one Central Transmission Utility, POWERLINKS and Bhakra Beas Management Board). It has largest sized hydro unit (250 MW at Tehri/ Nathpa Jhakri) in the country. Northern Grid has an installed generating capacity of about 42,190 MW as on 31.03.2010. The Thermal-Hydro (including renewable) mix is of the order of 62:38.
2.2 Northern Region has country’s first High Voltage Direct Current (HVDC) long distance transmission system in the country (2x750 MW, + 500 kV Rihand-Dadri HVDC bipole) and first HVDC back-to-back interconnection with Western Region (2x250 MW back-to-back HVDC station at Vindhyachal). It has 1 x 500 MW HVDC back- to –back interconnection with Eastern Region at Pusauli. NR has country’s first and only 400 kV Static VAR Compensators (SVC’s) (2x + 140 MVAR SVC at Kanpur).
2.3 The large Coal pithead thermal power stations are located in the extreme Southeastern part of the Regional Grid constituting generation capacity of around 7000 MW against which normal generation level is 5500-6000 MW.
2.4 Major generating stations including Super Thermal Power Stations of NTPC at Rihand and Singrauli are located in the eastern part of the grid. Due to such concentration of generation in the eastern part of the grid and major load centers in the central and western part of the grid there is bulk active power transmission from eastern to western part over long distances.
2.5 To handle this bulk transmission of power, a point to point high voltage DC line viz. HVDC Rihand-Dadri bipole with capacity of 1500 MW exists and operates in parallel with thirteen 400 kV AC transmission lines connecting Eastern part (Eastern UP subsystem) with Rest of Grid besides under lying 220 kV network.
2.6 With the commissioning of 400 kV Muzzafarpur (ER) –Gorakhpur (NR) D/C line in August, 2006, Northern grid got synchronized with the Western Region (WR), Eastern Region (ER) & North Eastern Region (NER). Since then NR, WR, ER and NER grids (i.e. Central Grid) are operating in synchronous mode. 765 kV Bina-Gwalior-Agra line (charged at 400 kV) was commissioned on 31st March 2007 and provides direct AC interconnection of Northern Region with Western region. 400 kV Kankroli-Zerda line was synchronized on 22nd April 2009.
2.7 The operation of the entire Northern Regional grid is co-ordinated in real time by the Northern Regional Load Despatch Centre (NRLDC) and eight State Load Despatch Centres (SLDCs).
The Map indicating 400 kV and above lines in NR is enclosed at Exhibit- 2/I.
![Page 19: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/19.jpg)
- 5 -
CHAPTER 3 Description of the Disturbance
3.1 Antecedent Condition
Power system network conditions during the evening peak hours of 1st Jan 2010
were normal. Low ambient temperature (below 100 C) and high relative humidity
(above 90 %) were observed throughout the region. Plot of temperature and
humidity for 27th Dec 2009 to 7th Jan 2010 is attached at Annexure-3 / I. Situation
was under alert condition as it has been experienced that such atmospheric
conditions are favorable for fog /smog formation and tripping of transmission lines
may occur due to flashover. Regional summary and other details during evening
peak hours of 1st & 2nd Jan 2010 are tabulated below.
Table 1: Regional Summary
Sl No.
Description Units 1900 hrs 1st Jan-10
0300 hrs 2nd Jan- 10
1900 hrs 2nd Jan- 10
0300 hrs 3rd Jan- 10
1 System Frequency Hz 49.87 50.64 49.82 50.13 2 Regional Load MW 27560 11736 26268 18356 3 Net Inter Regional
Import MW 2245 672 2238 954
4 Flow on HVDC Rihand-Dadri Bipole
MW 1100 800 1100 800
5 Flow on HVDC Back to back at Vindhyachal (+ve Import)
MW -200 -200 -450 -300
6 Kanpur 17.1 15.1 16.0 14.8 7 Minto
Road 17.1 9.1 11.3 9.9
8 Hisar 13.4 8.0 10.6 10.1 9
Ambient temperature
at
Patiala
0 Celsius
11.8 11.1 11.3 12.9 10 Kanpur ~100 ~100 95 97 11 Minto
Road 64 ~100 ~100 ~100
12 Hisar 85 ~100 ~100 ~100 13
Relative Humidity
Patiala
%
99 99 90 98
![Page 20: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/20.jpg)
- 6 -
3.2 Power supply positions
Table 2: Power Supply Position in all constituent States
SL No.
States Own Generation
Import from Grid
Demand Met
Over Drawl
Own Generation
Import from Grid
Demand Met
Over Drawl
1900 Hrs of 1st Jan 2010 1900 Hrs of 2nd Jan 2010 1 Punjab 2525 1822 4347 111 2105 2293 4398 705 2 Haryana 2158 2423 4581 1109 1292 2231 3523 10273 Rajasthan 3258 2351 5609 279 3187 2463 5650 578 4 Delhi 1009 1802 2811 -378 989 1918 2907 -336 5 Uttar Pradesh 3703 2803 6506 -665 3407 2819 6228 -623 6 Uttara-khand 434 601 1035 -11 456 646 1102 28 7 Himachal
Pradesh 145 827 972 -241 187 746 933 -252
8 Jammu & Kashmir
372 1137 1509 -173 566 760 1326 -476
9 Chandigarh 0 190 190 -5 0 203 203 19
3.3 Frequency Profile
It would be seen from the frequency profile below that the frequency remained
above 50.5 Hz between 0200-0300 hours.
Figure ‐1: Frequency Profile of 02nd Jan‐10
![Page 21: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/21.jpg)
- 7 -
This was primarily on account of the disruption in load fed from several 220 kV
substations on account of tripping of 220 kV lines. Even then the generating stations in
the entire NEW grid could have back down generation in a pro-active manner (barring
the generators in the North West part) as per the frequency linked dispatch guidelines
and ensure that the frequency does not go much beyond 50 Hz. This action was
obviously inadequate.
3.4 Weather conditions
3.4.1 The prevalence of foggy conditions in the Northern Region during the winter months
(late in the night or early in the morning) is a common phenomenon. The foggy
condition prevails during the period from December to February which occurs also
in March, in case the winter period gets extended.
3.4.2 The weather forecasting sensors has been installed at few grid sub-station/ SLDCL
(DTL SLDC at Minto Road, Hisar GSS, Panki GSS of POWERGRID ) in Northern
Region for online monitoring of weather parameters like temperature and relative
humidity. The pattern of temperature and relative humidity as recorded at Delhi and
Hisar in the first week of Jan.2010 is shown graphically in Annexure-3/I.
3.4.3 The foggy condition occurs during winter when relative humidity (RH) exceeds 85-90
per cent and the temperature falls below 15-17˚ C. Under these conditions,
condensation take place and condensation on the pollution laden insulators results
in flash-over and tripping of transmission lines.
Dense fog condition was reported on 2nd Jan.2010 in Delhi, Haryana, Punjab,
Western UP and northern part of Rajasthan. The relative humidity was about 100
per cent and temperature was below 14˚ C.
3.4.4 It has been reported in the News paper that the worst fog of the decade has occurred
in Jan.2010. 172 hours of fog has been reported in the month of Jan.2010. The
earlier record of the decade was 168 hours in Jan.2003 and 179 hours in Dec.1998.
3.5 Brief details of the disturbance
Based on the initial information as obtained from SCADA system at NRLDC and the
information received from the constituents, the brief details of these incidents are as
follows:
![Page 22: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/22.jpg)
- 8 -
Table 3: Disturbance Summary
S. No.
Date and time of
disturbance
Antecedent system
size (NR) (MW)
Generation loss * MW
Load affected
(MW)
Areas affected
1. 02.01.2010 at 03:01 hrs.
20000 4046 7500 Punjab, North Haryana, HP, J & K and UT Chandigarh
2. 02.01.2010 at 21:54 hrs.
25000 5159 9000 Punjab, Haryana, HP, J & K ,UT Chandigarh and North/West Delhi
*- The generation loss does not include the loss of generation due to backing down.
The above figures have been worked out considering 31st Dec 2009 as a normal
day. The drop in demand met on account of the disturbed conditions has been
worked out based on the load curves pattern of a normal day i.e. 31st Dec 2009.
Plot of load profile of 1st, 2nd & 3rd Jan 2010 with respect to 31st Dec 2009 is
attached at Annexure-3/II. On account of disturbance in the grid the estimated
quantum of energy not served from 1st to 3rd Jan 2010 is as summarized below.
Table 4: Energy Not Served
Sl. No
Date Estimated quantum of energy not served (in MWh)
1 1st Jan 2010
3600
2 2nd Jan 2010
112000
3 3rd Jan 2010
43000#
# - For Sundays, it has been observed from past data for Northern Region that the
energy consumption is 12 MU lower than on working days and this factor has been
used while working out the energy not served on 3rd Jan 2010 on account of the
disturbances on 2nd Jan 2010.The breakup of loss of generation during the two
incidents of grid disturbance on 2nd Jan 2010 is attached at Annexure-3/III.
![Page 23: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/23.jpg)
- 9 -
CHAPTER 4 Phenomenon of Tripping of Transmission Lines during fog
4.1 Fog is defined as an obscurity near the surface layer of the atmosphere which is
caused by a suspension of water droplets and associated with visibility less than 1000
meters. Under favorable atmospheric conditions, the fog becomes so much dense
that even one can not see an object beyond 25m in normal vision causing severe
disruption to aviation, railway, and surface transport. Longer nights in peak winter also
help in significant fall of air temperature near surface due to which water vapors get
sufficient cooling required for dense fog formation. The pollution and aerosols which
acts as additional source of Cloud Condensation Nuclei upon which water droplets
form are sufficiently available and increasing day by day along Northern plains and
may be another reason for increasing in frequency of fog occurrences over the region
especially at NCR Delhi. Because of dense fog near ground surface severely
disrupting incoming solar radiation and persistence of very high humidity at lower level
near surface for prolonged hours from late night till late forenoon of the next day, many
incidents of tripping of electric power lines occur in the region affecting the life of
common people very much.
4.2 The dust and other pollutants in the air settle on the insulators which under dry
conditions do not impact the operation of the lines. However, during the occurrence of
high relative humidity levels / fog conditions, the wetting of the surface of insulators /
formation of water droplets on the surface of the insulators takes place which
dissolves the chemicals present in the pollutants already settled on the insulators
resulting in a creation of conditions conducive for the flow of leakage currents. These
leakage currents result in heating of the insulators and initiates drying up of areas of
the insulators having higher density of current leading to formation of dry ring on the
smallest diameter part of the porcelain insulator. The voltage across the dry band
could be high enough to ionize the air and result in flash over across it. This results in
higher leakage current which accelerate the process of further formation of dry
patches and the small flash over grows into the flash over across the insulators and
the process culminates in flash over across the entire insulators resulting in tripping of
the line on line to ground fault. The phenomenon typically occurs from say 2200 hours
to 0800 hours when the temperature falls below 15 degree centigrade and the Relative
Humidity (RH) increases beyond the 85-90% range.
![Page 24: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/24.jpg)
- 10 -
4.3 At the time of design of the transmission lines in NCR of Delhi and other parts of
NCR, the normal pollution levels were taken into consideration. However, the
pollution levels have gone up considerably high due to reasons indicated below
which has caused the problem of tripping:
(a) Increased construction activity commensurate with the development;
(b) Pollution from vehicular traffic;
(c) Burning of agricultural waste;
(d) Burning of Baggasse
(e) Pollution from Brick Kilns;
(f) Industrial activity.
4.4 The increase in the pollution levels due to vehicular traffic particularly from diesel
driven vehicle needs special mention. The diesel fumes which settle on the
insulators are sticky and difficult to wash with water jet spray. The unchecked
emissions from such vehicles could be a cause of concern. The emission norms
for the vehicles particularly the diesel vehicles need to be enforced effectively
particularly in respect of trucks and buses. The deposit on insulators due to Bird
dropping is another factor of pollutant.
4.5 The Mechanism of flash over during the occurrence of fog and factors
contributing to increased pollution levels have been discussed in detail in the
report of the Inquiry committee constituted for grid incident on 27.01.2007 and
7/9th March, 2008. The relevant extract from the report are reproduced as
Annexure- 4 / I.
![Page 25: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/25.jpg)
- 11 -
CHAPTER 5 Analysis of the grid disturbance at 03:01 hrs of 2nd Jan.2010
5.1 Tripping of the EHV transmission system before the grid disturbance at 0301
hours of 2nd January 2010:
The list of lines which tripped right from the night hours of 1st January 2010 is
enclosed at Annexure- 5/I. The Sequence of Events (SoE) recorded at NRLDC
SCADA system is enclosed at Annexure- 5/II. It would be seen from the list that by
0230 hours of 2nd January 2010, the transmission network was depleted to a great
extent. (13 x 400 kV lines and 62 x 220 kV lines out). This situation worsened by
0255 hours of 2nd January 2010 with 14 x 400 kV lines and 79 x 220 kV lines went
out. The same is illustrated graphically in Fig 1 and Fig 2 below. This list does not
include the 400 kV lines (5 Nos.) which were kept off to control high voltages in
certain pockets within the region.
Fig 2: Graph indicating the number of outages in the 400 kV and above transmission
system
Figure 2 : Cumulative outage in the 400 kV transmission systems
![Page 26: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/26.jpg)
- 12 -
Figure-3 Cumulative Outage in 220 kV transmission systems
In respect of 400 kV systems above, it would be seen that efforts were made to
restore the lines immediately after the tripping took place. However in respect of the
220 kV system, the cumulative net number of lines at any point of time which were
out kept mounting suggesting that the Mean Time To Restore (MTTR) was quite
high.
There were several events of multiple contingencies before the system separation
and collapse of sub-system at 0301 hours. These are described below.
5.2 Tripping Events in the system prior to system disturbance at 03:01 hrs.
Some of the tripping events in the system prior to the system disturbance are
described as under.
5.2.1 Auto-restarts on the Rihand Dadri HVDC bipole and tripping on the night of 1st
January 2010:
Pole-1 of Rihand-Dadri HVDC bipole had eight autorestarts starting from 1942
hours to 2219 hours (1942, 1956, 2006, 2009, 2021, 2029, 2141 and 2219 hours).
0
20
40
60
80
100
120
0:15 0:30 0:45 1:00 1:15 1:30 1:45 2:00 2:15 2:30 2:45 3:00
N
O
O
F
2
2
0
k
V
L
I
N
E
S
TIME ‐ 2nd January 2010
Cumulative Outages in the 220kV transmission system in Northern Region on 2nd January 2010
Cumulative No. ofline trippings/ autoreclosures
Cumulative No. oflines Restored
80 No. of 220 kV lines were out at 03.00 HRS
Net No. of Lines out
![Page 27: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/27.jpg)
- 13 -
The fault locator reading in these cases was in the range of 127-128 km from Dadri.
However Pole-1 did not trip and power flow continued uninterrupted.
Pole-2 of Rihand-Dadri HVDC had two auto-restarts at 1952 and 2031 hours
followed by tripping at 2221 hours on DC differential protection at Dadri. In the two
auto-restarts on Pole-2, the fault locator reading was 132 and 122 km. respectively
from Dadri. Pole-2 was restored at 2321 hours.
The above auto-restarts or tripping of Pole-2 of Rihand-Dadri HVDC bipole for one
hour (from 2221 hrs. to 2321 hrs.) did not result in any contingency as the power
demand in the region was low and Pole-2 of Rihand-Dadri HVDC bipole had got
restored much before the other lines in the corridor viz. 400 kV Bareilly-Mandaula
D/C lines started auto-reclosing. It however gives an indication of the inclement
weather conditions in Western UP areas right from the late evening hours of 1st
January, 2010. It has also been ascertained that though in the stretch around Dadri
the insulator replacement work has been completed, the auto-reclosure / tripping
were in the sections beyond Dadri in the Mainpuri jurisdiction, where the insulators
were not replaced with the polymer type of the insulators. This further justifies the
requirement of replacement of the porcelain insulators in all the critical locations on
priority basis.
5.2.2 Complete blackout of 400/220 kV Muradnagar substation at 2339 hours of 1st
January 2010.
400/220 kV Muradnagar substation is a vital substation in the National Capital
Region (NCR) located in Uttar Pradesh. It has five (5) 400 kV lines and five (5) 220
kV lines emanating from the substation. The 400/220 kV transformation capacity
available here is 795 MVA. However the 220 kV system is effectively radial as
several 220 kV loops have been kept open to control over-loading of the 400/220 kV
InterConnecting Transformers (ICTs). The tripping of the 400 kV transmission
system at Muradnagar occurred in the following sequence.
22:43 hrs 400 kV Muradnagar-Agra(UP) tripped.
22:44 hrs 400 kV Muradnagar-Dadri (NTPC) tripped.
23:12 hrs 400 kV Muradnagar-Panki tripped.
23:13 hrs 400 kV Muradnagar-Muzaffarnagar tripped from latter end only.
23:39 hrs 400 kV Muradnagar-Moradabad tripped from former end only.
![Page 28: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/28.jpg)
- 14 -
With the above tripping, approximately 300 MW load was lost in the western UP
system. Impact on the grid was however not very significant. The above tripping
occurred primarily due to line faults. During the tripping of lines emanating from
Muradnagar, some instances of protection system mis-operations also came to the
fore. These are as under:
i. A fault on 400 kV Muradnagar-Agra at 2211 hours, prior to this black out
event, also had caused the tripping of 400 kV Muradnagar-Muzaffarnagar
line also at the far end on Zone-1 over-reach. Fortunately there was a
successful auto-reclosure of the line at Muzaffarnagar.
ii. Series capacitor on 400 kV Panki-Muradnagar line at Muradnagar end got
bypassed at 2211 hours for the above fault on 400 kV Muradnagar-Agra line
at 2211 hours.
iii. A fault on 400 kV Muradnagar-Panki line led to the 400 kV Muradnagar-
Muzaffarnagar line tripping at the latter end on over-reach.
The above protective system mis-operations might be investigated in detail by
UPPCL with respect to the relay settings. No Disturbance Recorder (DR) or
Numerical Relay outputs or Event Logger (EL) outputs have been submitted by
UPPCL for the above tripping and the above instances of misoperation have been
reproduced from UPPCL’s analysis. Protection Sub Committee of NRPC may look
into the above incident to identify the appropriate relay settings.
The sequence of restoration of 400 kV Muradnagar substation is as under on 2nd
January 2010
00:01 400 kV Muradnagar-Moradabad restored.
00:10 400 kV Muradnagar-Agra restored (but tripped again at 0028 hours
and could be restored only at 0726 hours)
00:15 400 kV Muradnagar-Panki restored
01:02 400 kV Muradnagar-Muzaffarnagar restored.
11:20 400 kV Muradnagar-Dadri (NTPC) restored.
5.2.3 Complete outage of Panipat (Thermal) Stage-II Thermal Power Station at 01:55
hours of 2nd January 2010:
Panipat (Thermal) Stage-II TPS, Haryana has four units (2 x 210 MW + 2 x 250
MW) adding to 920 MW capacity. There are eleven (11) 220 kV circuits to evacuate
power from this station. Please refer the power map of Haryana enclosed at Exhibit-
5/I for a better understanding. The 220 kV network around Panipat Stage-II got
![Page 29: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/29.jpg)
- 15 -
progressively depleted during the early morning hours of 2nd January 2010 due to
the following important line trips on fault:
As per following detail due to fog related tripping
sl.no Time Name of line Flag at end
A (HVPNL)
Flag at end
B (PTPS)
Remark
1 0140 220 kV Rohtak-
PTPS-ckt II
No tripping at
Rohtak
DPR AGT
Zone 1
(12.6 km)
Disc insulator
found
damaged at
tower no 37
2 0142 220 kV Nissing -
PTPS- cktI
DPR Y phase Y phase AR
L/O, FL
14.33
3 0150 220 kV Rohtak-
PTPS-ckt I
Earth fault No tripping
4 0150 220 kV Sonipat
PTPS-ckt I
B phase
fault
ABC zone -
1
5 0150 220 kV Saffidon
PTPS-ckt I
Main DPR
REL 611 Trip
CB, RYB, FL
91.5 %
No tripping
6 0150 220 kV Saffidon
PTPS-ckt II
Main 1 trip all
Auto L/O CB
rcd, YB trip
Main –II
Rozoa R. N
trip
No tripping
7 0150 220 kV Saffidon
PTPS-ckt III
Main –I Zone
I trip all, A/R
LO, FL 52.7
No tripping
As given above, at about 0150 Hrs 7 evacuation lines were out. Panipat TPS Stage-
II was weakly connected to rest of the grid. Large number of above tripping ideally
should have led to automatic backing down of generation by Panipat TPS Stage-II
suo-motu or on the intervention of SLDC Haryana. Subsequently, 220 kV Jind-
![Page 30: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/30.jpg)
- 16 -
Hisar IA D/C line tripped on distance protection with overload alarm leading to
islanding of the power station and tripping of the units on over speed. This led to a
loss of 220 kV supply at 220 kV Jind, Safidon, Nissing and Rohtak (approximately
500 MW load) and 920 MW generation at Panipat Stage-II.
The outage of Panipat Stage-II generation in the North West part of the grid and the
220 kV network depletion in Haryana system placed the system in a state of higher
alertness. The tripping beyond 0155 hours in Haryana 220 kV system also resulted
in loss of the 220 kV parallel path from 220 kV Hisar to 220 kV Abdullapur via 220
kV Hisar-Narwana-Kaithal-Pehowa-Shahbad-Tepla-Abdullapur route. (This link got
broken at 220 kV Kaithal-Pehowa section by 0255 hours).
The depletion of the Haryana 220 kV network could not be visualized adequately
owing to non-availability of real time data from a number of HVPNL stations. No
detailed report on the above incident with DR/EL and numerical relay outputs have
been forwarded by HVPNL and the above sequence had to be derived only from the
list of line tripping submitted by HVPNL without any analysis as to whether these
tripping were in order or not.
5.2.4 Outage of 400 kV Bus-I at Ballabgarh (PG) substation at 0255 hours:
At 0255 hours, there was an R-B-N phase fault on 400 kV Ballabgarh-Bamnauli-2
line. At that point of time this was the only infeed to Bamnauli and was feeding a
radial load of approximately 300 MW to south west Delhi. This fault was sensed by
the distance protection at Ballabgarh. However while all the poles of the 400 kV
Bus-2 breaker opened, R-pole of the 400 kV Bus-1 breaker of the Bamnauli feeder
at Ballabgarh did not open leading to operation of the Local Breaker Backup (LBB)
of this breaker and this isolated 400 kV Bus-1 at Ballabgarh. (Please refer sketch
below for Ballabgarh substation for ease of understanding). No proper DR or EL
output is available from 400/220 kV Bamnauli substation for the above tripping.
As the 400 kV Ballabgarh (PG) substation has a breaker and half switching scheme
and all tie breakers were in service, this outage of 400 kV Bus-1 through tripping of
all breakers connected to this bus did not lead to any further element outage. The
other elements continued to remain connected with the grid through the tie breaker
or 400 kV Bus-2 breakers.
![Page 31: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/31.jpg)
- 17 -
Figure-4: Single Line Diagram (SLD) of 400 kV Ballabgarh substation
The Numerical relay output of this line at Ballabgarh end is enclosed at Exhibit-5/II.
It is seen that while the fault has been cleared within 250 ms (corresponding to
distance protection operation plus LBB timer), the R-pole also opened three
seconds later, apparently on Pole Discrepancy (PD). Even after the LBB operation
the trip command generated is failing to trip on bus bar trip command. Obviously,
the Trip circuit is OPEN. However, PD trip do occur as the trip logic is generated
locally in the CB panel. Apart from this blackout at Bamnauli at 0255 hours,
400/220 kV Bamnauli substation had also suffered a blackout earlier from 0222
hours to 0240hrs.
1430
33
ICT ‐ 4
KANPUR BAMNAULI‐I BHIWADI
400kV BUS‐I
400kV BUS‐II
32
31 26
27
13 15 10 12 1 3
28
29
30 25
26
7
8
9 4
5
6
BUS
REACTOR
M.BAGH G.NOIDA
ICT ‐ 3 ICT ‐ 1 ICT ‐ 2
MAINPURI‐II MAINPURI ‐ I AGRA BAMNAULI‐II
FACTS
![Page 32: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/32.jpg)
- 18 -
5.2.5 Efforts to reduce the import of North-West part of the system
Thus apart from the 220 kV and 400 kV line tripping occurring in the system as
stated earlier, the above events brought out the weaknesses in the protective
system and also placed the system in a state of emergency. NRLDC had to take
actions by way of making efforts to reduce the import of the North West part of the
system (Punjab/Haryana/HP/J & K) by way of increasing generation in this part
(Chamera-1 and Jhakri) and reducing the load in order to enhance the system
security.
5.3 Sequence of events leading to a split in the system at 0301 hours
The Sequence of events leading to a split in the system at 0301 hours is further
elaborated in this section. If we look into the transmission network connecting the
affected area which finally separated from rest of the grid and collapsed at 0301
hrs., the following 400 kV/220 kV links form the separating corridor and in this the
line sections going out have been highlighted.
400 kV Links
1. 400 KV Hisar- Fathehabad-Moga-Jallandhar
2. 400 KV Hisar –Khedar-Moga-Jallandhar
3. 400 KV Hisar- Patiala-Nalagarh-Jhakri-Abdullapur
4. 400 KV Hisar- Kaithal-Nalagarh-Jhakri-Abdullapur
5. 400 KV Hisar- Bhiwani- Dehar-220 kV Ganguwal
6. 400 kV Panipat-Dehar-220 kV Ganguwal
7. 400 KV Patiala-Malerkotla-Dadri
220 KV Links
1. 220 kV Panipat-Dhulkote-Ganguwal D/C
2. 220 KV Panipat-Kurukshetra-Jagadhari-Ganguwal
3. 220 KV Hisar-Sangrur-1
4. 220 KV Hisar-Sangrur-2
Hence looking specifically into the affected area, as antecedent conditions the
transmission network across the axis of separation was already depleted due to
outage of following ckts:
![Page 33: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/33.jpg)
- 19 -
Table 5: Lines that were already out in the Axis of Separation
S.No Name of line Status at 0253 hours
1 400 kV Hisar-Patiala Out since 0507 hours of 1st Jan 2010
2 400 KV Jhakri-Nalagarh-1 Opened at 2050 hours of 1st Jan 2010
3 400 kV Panipat-Dehar Tripped at 0001 hours of 2nd Jan 2010
4 400 kV Hisar-Kaithal Tripped at 0136 hours of 2nd Jan 2010
5 400 kV Bhiwani-Dehar Tripped at 0151 hours of 2nd Jan 2010
6 220 kV Panipat-Dhulkote-1 Tripped at 0207 hours of 2nd Jan 2010
7 220 kV Panipat-Dhulkote-2 Tripped at 0227 hours of 2nd Jan 2010
8 400 kV Fatehabad-Moga Tripped at 0229 hours of 2nd Jan 2010
9 220 kV Panipat-Kurukshetra Tripped at 0236 hours of 2nd Jan 2010
As would be seen from the above, six (6) 400 kV and three (3) 220 kV links in this
cross section were out with six lines going out in rapid succession between 0136
hours to 0236 hours.
5.3.1 Tripping of 400 KV Bawana-Abdullapur-2 and radial operation of Jhakri HPS:
At 02:54:57:125 (as per NRLDC Sequence of Events log) hours, 400 kV Bawana-
Abdullapur-2 tripped on Y-phase to ground fault, 100 km from Abdullapur. The fault
was cleared by tripping of the Y-pole breaker. The Y-pole autoreclosed immediately
after the 1 second dead time but all three phases tripped at 02:54:58:378 due to
persistent fault. DR output of this circuit at Abdullapur end is enclosed at Exhibit-
5/III. As a result of this tripping, the Jhakri and Yamuna Nagar TPS remained
connected with the grid only through 400 kV Jhakri-Nalagarh-Patiala link (on
account of the tripping in Haryana system explained in para 5.2.3 above). With this,
the power flow across the depleted axis feeding Punjab/ North Haryana/ HP /J & K/
UT Chandigarh system at 0255 hours was as under:
i. 400 kV Dadri-Malerkotla : 590 MW
ii. 400 kV Jhakri-Nalagarh-2 : 410 MW
iii. 400 kV Hisar-Khedar-Moga : 640 MW
iv. 220 kV Hisar-Sangrur-1 : 110 MW
v. 220 kV Hisar-Sangrur-2 : 110 MW
Total : 1860 MW
400 kV Jhakri-Nalagarh-2 was essentially a radial feed to the North West part of the
grid during the above instance on account of loss of connectivity between 220 kV
Hisar and Abdullapur due to outages in the 220 kV HVPNL system. This aspect
![Page 34: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/34.jpg)
- 20 -
could however could not be visualized adequately on account of non-availability of
real time data from the HVPNL system, more so when several contingencies kept
happening in close succession (the tripping of 400 kV Bus-1 at Ballabgarh
described at para 5.2.4 above occurred within three seconds of this tripping).
5.3.2 Tripping of Complete Ropar TPS
Around this instant, another contingency occurred in the Punjab system. Ropar TPS
(RTP) in Punjab has an installed generating capacity of 1260 MW (6 x 210 MW).
The power station has ten (10) 220 kV lines for evacuation and all the six generating
units were operating during the night hours. (Please refer power map of Punjab at
Exhibit-5/IV). The 220 kV transmission systems were tripping progressively as
under on 2nd January 2010 unless mentioned otherwise:
0111/1st Jan 2010 220 kV RTP-Sahnewal
0155 220 kV RTP-Govindgarh-4
0223 220 kV RTP-Govindgarh-1
0251 220 kV RTP-Govindgarh-2
0254 220 kV RTP-Jamsher
Ropar TPS was therefore left with only the following 220 kV lines for evacuation:
220 kV RTP-Kohara
220 kV RTP-Govindgarh-3
220 kV RTP-Goraya
220 kV RTP-Mohali-1
220 kV RTP-Mohali-2
The generation at Ropar TPS at 0255 hours was 977 MW (net). Around 0256 hours,
220 kV Mohali-Rajpura D/C and 220 kV Ganguwal-Mohali circuits have reportedly
tripped and effectively making the 220 kV RTP-Mohali D/C radial. At the same
instance, the power station has got islanded (possibly on account of line trips
beyond Goraya and Govindgarh) and the units have reportedly tripped on over-
speed. As per the output from the Historical Tabular Trending of Ropar TPS, the
units 3, 4, 5 and 6 have got islanded at 02:56:31 hours and within the next two
seconds, the frequency has shot up to 55 Hz leading to tripping of the units on over-
speed.
![Page 35: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/35.jpg)
- 21 -
The Tabular Trends for these units (which appear to be time synchronized) is
enclosed at Exhibit-5/V. In respect of units 1 and 2, the output from the Data
Acquisition System (DAS) of these units are enclosed at Exhibit-5/VI. This output
also indicates that the units have tripped on over-speed.
It might be seen from the above that adequate backing down of generation had not
been carried out by Ropar TPS/SLDC Punjab despite the 220 kV network in Punjab
getting depleted, leading to the above outage.
5.3.3 Tripping of 400 kV Khedar-Moga ckt. on over-current protection
The above outage of Ropar TPS resulted in a deficit in the North West pocket
comprising Punjab/North Haryana/HP/J & K system. The next event as per the
Sequence of Events recorded at NRLDC is the tripping of 400 kV Khedar-Moga line
at 02:56:32:389. As per the REL 670 Numerical Relay output of this line at Khedar
end (which is time synchronized and enclosed at Exhibit-5/VII), the current on this
line just before tripping was 1.3 kA or 1300 amps and the power flow was of the
order of 880 MVA (3 x 225 kV x 1.3 kA). As mentioned in para 5.3.1 above, the
power flow on this line at 0255 hours was 640 MW and the increase in power flow to
880 MVA was mainly on account of tripping of Ropar TPS at 02:56:31 hours.
The above power flow of 1.3 kA and 880 MVA is much less than the thermal rating
of this circuit which is 2.6 kA (1800 MVA) at 100 C ambient temperature. Therefore
the tripping of this line at this power flow of 880 MW is not in order. It is observed
from the relay output that the tripping has occurred on account of overcurrent
protection which has reportedly been set at 1.0 kA.
Over-current protection on 400 kV lines is not a desirable feature. In fact section 2
of the CBIP Publication no. 274 ‘Manual on Protection of Generators, Generator
Transformers and 220 kV and 400 kV networks’ has not recommended any such
protection for 400 kV lines. Over current protection even where it is currently applied
220kV and below, it is applied as a short circuit protection and not as a protection
against over loading. In the lower voltage systems also, it is preferable to use
distance protection itself as back up. Even where O/C back up protection is applied,
its setting should be such that it cannot operate under any contingency loading
situation also. In case such a feature has been enabled, it can lead to unintended
operations or surprises during a contingency and can aggravate the situation
leading to a widespread failure. In the Northern region, existence of such a
![Page 36: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/36.jpg)
- 22 -
protection on one of the 400 kV sections in the Delhi ring main system had led to a
grid disturbance on 12th October 2007 and a blackout in Punjab/Haryana/HP/J & K
system. After this disturbance, the Protection sub-committee of NRPC specifically
directed all the utilities to block the over-current protection on 400 kV lines. It
appears that the requisite checks had not been done during commissioning of the
line on 31st July 2009, which was done as an interim arrangement by Loop-In-and
Loop Out (LILO) of 400 kV Hisar-Moga line at Khedar. This arrangement was
required in connection with the commissioning of units at Rajiv Gandhi Thermal
Power Station (RGTPS). HVPNL now vide letter dated 16th Feb., 2010 informed that
overload current setting on the distance protection of 400 kV Khedar-Moga and
Khedar-Hisar lines at Khedar has been disabled w.e.f. 03.01.2010.
5.3.4 Low voltages in Punjab System
The above unintended tripping of 400 kV Khedar-Moga led to severe drop in
voltages in Punjab/North Haryana system (below 360 kV) on account of heavy
loading (>800 MW) on the 400 kV Dadri-Malerkotla line leading to high reactive
power losses of the order of 1000 MVAR.
While the operator at NRLDC could observe this low voltage of the order of 360 kV,
the high MW loading did not appear on the screen on account of the 1000:1 Current
Transformer (CT) ratio adopted at both ends of this line, which led to the values
getting frozen at around 600 MW. Remedial actions for improving the voltage in this
area were taken such as taking out the bus reactor at Malerkotla. Generators in this
area was also advised to increase their generation
While the reactive power flows on transmission lines are not monitored very closely,
as the same is not very significant under normal line loading conditions, the same
assumes great importance when the transmission network is loaded heavily. After
the incident, the Historical Data Replay at NRLDC revealed high MVAR drawn by
the 400 kV Dadri-Malerkotla line from both ends between 0256 to 0301 hours. This
is illustrated in Fig 4.
![Page 37: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/37.jpg)
- 23 -
-800
-600
-400
-200
0
200
400
600
800M
W/M
VA
R
Flow on 400kV Dadri-Malerkotla line on 2nd Jan 2010
Heavy MVAR of the order of 500 MVAR from each end was flowing into the line for about 5 minutes.
MW recorded at Dadri NTPC
MW recorded at Malerkotla
MVAR recorded at Dadri NTPC
MVAR recorded at Malerkotla
+ve means export and –ve means import
Figure 5: Flow on 400 kV Dadri- Malerkotla line on 2nd January 2010
Initially this seemed to suggest an un-cleared fault on the line. Subsequently,
through off-line simulation, it was seen that the high reactive power drawn by the
line would occur at high level of MW loadings. In this case, while the SCADA data
shows that the MW values had frozen at around 550 MW, the actual power flow on
400 kV Dadri-Malerkotla line would have been much above 1000 MW. The reactive
power drawn by the line vis-à-vis line current is illustrate graphically below in Fig 5.
The Historical Data Recording (HDR) also indicates that the flow on 220 kV Hisar-
Sangrur D/C initially increased from 220 MW to 380 MW and thereafter to 690 MW.
The voltage at Sangrur and Hisar also dipped by 25 kV-30 kV on account of approx.
360 MVAR reactive power losses on this line.
The reactive power requirements under such a situation would have to be met from
the generators nearby such as Dadri NTPC, Lehra Mohabat TPS, GNDTP, Yamuna
Nagar TPS, Chamera-I and Jhakri HPS. Outage of the generating units at Ropar
TPS and Panipat TPS Stage-II in this incident caused a shortfall in dynamic reactive
reserves available leading to a higher voltage drop. Under Voltage Load Shedding
(UVLS) assumes great importance in such situations. Absence of this defense plan
can lead to a situation of voltage collapse.
![Page 38: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/38.jpg)
- 24 -
Fig 6: Reactive power losses on 400 kV Dadri-Malerkotla line with increase in
loading
5.3.5 Separation and collapse of Punjab / North Haryana / HP / UT Chandigarh and J
& K System:
The next set of cascade tripping as per the NRLDC Sequence of Events (SOE) is as
under:
03:01:41:459 220 kV Hisar-Sangrur-2 tripped from Sangrur end.
03:01:42:221 220 kV Hisar-Sangrur-1 tripped from Sangrur end.
03:01:42:705 400 kV Jhakri-Nalagarh-2 tripped. The Numerical Relay outputs
of 400 kV Jhakri-Nalagarh-2 at Jhakri (Exhibit-5/VIII) shows a
sharp dip in voltage to zero with the current of the order of 1.2
kA).
03:01:43:484 400 kV Dadri-Malerkotla tripped. The Numerical Relay output at
Malerkotla Exhibit-5/IX shows the voltage dipping to 270 kV
phase to phase and the current of the order of 2.6 kA just
before tripping). EL at Malerkotla end also enclosed.
‐200
0
200
400
600
800
1000
1200
1400
1600
1800
2000
50 250 500 750 1000 1250 1500 1750 2000 2250 2500
MVAR
Ampere
MVAr flow on 400 kV Dadri‐Malerkotla line vis‐a‐vis line current in Ampere (S/C, 297 km, Twin Moose, 63 MVAr line reactor at Malerkotla end)
Net MVAR @ 400 kV
Net MVAR @ 360 kV
Thermal limit : 2221 Ampere
ACSR Twin Moose, 65 degree conductor design temperatureAge >10 years, 15 degree Ambient temperature
If the line is loaded upto its thermal limit the MVAr flow on the line would be 1400 MVAR
![Page 39: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/39.jpg)
- 25 -
This led to separation of the Punjab/North Haryana/HP/UT Chandigarh/J&K system
from the main NEW grid. The axis of separation is pictorially indicated at Exhibit-
5/X. There was a deficit of approximately 1850-1900 MW in this separated portion
and it collapsed leading to a loss of approximately 7500 MW load (including loads
already affected due to prior fog related tripping). A small portion of HP system
remained connected with Uttarakhand system and survived. Within Uttarakhand
system, loss of supply to 220 kV Roorkee substation at 0302 hours from Nara led to
about 110 MW generation at Chilla, Pathri and Mohammadpur getting affected for
25 minutes and about 296 MW getting interrupted for 65 minutes. This incident is
not related to the main incident at 0301 hours.
It would appear that the separated system had itself split into several parts, rather
than remaining a synchronous separated sub system. As already brought out,
Nathpa Jakheri, Panipat-II and Ropar had islanded from the system as separate
pockets.
It would thus be seen that within five minutes of tripping of 400 kV Khedar-Moga
line, tripped reportedly on account of an incorrect relay setting, the systems
separated and collapsed.
In rest of the NEW grid, the frequency shot up to 51.2 Hz and the situation was
controlled by backing down generation at Singrauli, Rihand and Unchahar thermal
power stations. System voltage also shot up on account of the load rejection caused
due to separation of system above. The frequency remained under check mainly
because of the large size of the NEW grid with the flexibility to export more power to
Southern region. The angular separation between the North and West bus at
Vindhyachal HVDC back to back station is indicated in Fig 6/1in chapter 6 of this
report.
5.4 Main causes of the disturbance
It has been observed that the disturbances were initiated during the foggy weather
conditions due to outage of a number of transmission elements, more particularly in
the North West part of the region. On the basis of analysis of event the main
attributes for the grid disturbance at 03.01 hrs can be identified as:
Depletion of transmission network due to heavy fog / smog conditions;
![Page 40: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/40.jpg)
- 26 -
Unintended and unexpected operation of protective system/switchgear of
some of the critical transmission elements in already depleted network;
Operator’s inability to adequately comprehend the situation in certain
cases as a result of which the system conditions were aggravated
Non availability of defense mechanism for such contingency.
![Page 41: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/41.jpg)
- 27 -
CHAPTER 6 Analysis of the grid disturbance at 21:54 hours on 2nd Jan.2010
6.1 Antecedent conditions:
Chapter-5 of this report indicates the sequence of events culminating in the
disturbance at 0301 hours of 2nd January 2010. As would be seen from Chapter-8 of
this report, the last of the thermal units at Ropar TPS in Punjab were synchronized
by 1800 hours while in Haryana, the units at Yamuna Nagar TPS were
synchronized at 2100 and 2121 hours only.
The Northern Region was meeting a demand of 25400 MW at 2100 hrs. of 2nd Jan
2010 which was about 1300 MW less than on a normal day. This was primarily the
effect of the grid disturbance at 0301 hrs. As far as the transmission network was
concerned, all the trunk transmission lines were restored barring the 400 kV
Bhiwadi-Hisar line which went under breakdown at 0542 hrs. of 2nd Jan 2010 due to
bending of a tower cross arm at location no. 134.
Following are the 400 KV/220 KV links separating the affected area from the rest of
the grid during this incident. (Part of HP system remained connected through
Uttrakhand system)
400 KV Links
1. 400 KV Bhiwadi-Hisar
2. 400 KV Bawana-Hisar
3. 400 KV Bawana-Bahadurgarh-Bhiwani-Hisar
4. 400 kV Bawana-Abdullapur D/C
5. 400 KV Dadri-Malerkotla
6. 400 KV Dadri-Panipat Ckt#1 & Ckt#2
220 KV Links
1. 220 kV Khetri-Hisar
2. 220 KV Khetri-Charkhi Dadri D/C
3. 220 KV Ballabgarh-Charkhi Dadri
4. 220 KV Samaypur-Charkhi Dadri
In view of the fact that the thermal units in Punjab were synchronized only during
the evening or early night hours, the power flow across the above section was
![Page 42: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/42.jpg)
- 28 -
higher than on a normal day. At 21:44 hours just before the tripping commenced,
the power flow across the above cross section was as under:
1. 400 KV Bhiwadi-Hisar 0 MW
2. 400 KV Bawana-Hisar 538 MW
3. 400 KV Bawana-Bahadurgarh 521 MW
4. 400 kV Bawana-Abdullapur D/C 543 MW
5. 400 KV Dadri-Malerkotla 419 MW
6. 400 KV Dadri-Panipat D/C 684 MW
7. 220 kV Khetri-Hisar 146 MW
8. 220 KV Khetri-Charkhi Dadri D/C 370 MW
9. 220 KV Ballabgarh-Charkhi Dadri 124 MW
10. 220 KV Samaypur-Charkhi Dadri 123 MW
Total 3468 MW
The subsequent sections describe the sequence of events leading to the separation
along the above axis and collapse of the Punjab/Haryana/HP/J & K system. The
Sequence of Events (SoE) recorded at NRLDC is enclosed at Annexure-6/I.
6.2 Events starting from 2144 hrs leading to the disturbance at 2154 hrs.
For the sake of understanding please refer Fig 6/1 and Fig 6/2 below.
![Page 43: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/43.jpg)
- 29 -
Figure 7: Sketch of 400 kV Delhi ring main system 6.2.1 Tripping of 400 KV Bamnauli-Ballabgarh Ckt.-2 (at Ballabgarh end)
The first event recorded in the Sequence of Events at NRLDC was the tripping of
400 kV Bamnauli-Ballabgarh-2 at 21:44:09:255 (at Bamnauli end) and at
21:44:09:288 at Ballabagarh end. The Numerical Relay output at Ballabgarh end of
this line indicates a R-phase to ground fault on the line. (Exhibit-6/I). Although Main-
1 protection operates at this end, the fault is seen for a period of 300 msec (15
cycles). It is seen from the NRLDC SOE that the fault is apparently cleared from
Ballabgarh end only after operation of the Local Breaker Backup (LBB) of 400 kV
Bus-1. This has happened as the 400 kV Bus-1 breaker of Bamnauli-2 circuit at
Ballabgarh end has failed to open after operation of distance protection. In fact the
Numerical Relay output shows that the R-pole of this breaker has opened 3
seconds after the occurrence of fault (apparently on Pole Discrepancy protection,
inherent in the CB, the logic being derived in the CB marshalling box) although the
fault was cleared in 300 msec due to 400 kV Bus-1 trip.
Figure 8: Single Line Diagram (SLD) of 400 kV Ballabgarh substation
DR of Ballabgarh – Bamnauli – II
1430
33
ICT ‐ 4
KANPUR BAMNAULI‐IBHIWADI
400kV BUS‐I
400kV BUS‐II
32
31 26
27
13 15 10 12 1 3
28
29
30 25
26
7
8
9 4
5
6
BUS
REACTOR
M.BAGH G.NOIDA
ICT ‐ 3ICT ‐ 1 ICT ‐ 2
MAINPURI‐II MAINPURI ‐ I AGRA BAMNAULI‐II
FACTS
![Page 44: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/44.jpg)
- 30 -
Figure 9: DR of Ballabgarh - Bamnauli - II, Ballabgarh end 21.45hrs 02.01.2010
With reference to Figure 9: DR of Ballabgarh - Bamnauli - II, Ballabgarh end 21.45hrs 02.01.2010 the following can be inferred. Single Phase Protection Trip Command Issued at 21.44.09.270 to R-phase Pole of
Bus-1 & Bus-2 Breakers While R-phase pole of Bus-2 Breaker opens correctly, Bus-1 Breaker fails to trip (see
the Tie CB trace in Figure ) Breaker Fail Protection (LBB) of Bus-1 Breaker (1052) operates correctly after 200ms
and trips all other Breakers connected to Bus-1 as well as the other poles of the line Breakers (see CB status trace). Fault cleared
LBB protection operation of 1052 sends Direct Trip command to Bamnauli end of Ballabgarh – Bamnauli – II (DT send not recorded).
Y&B phase voltage recover after currents are interrupted by Ballabgarh Bus-1 trip (line energised from Bamnauli)
Bamnauli end Breaker Y&B poles open correctly on DT received. Indicated by the vanishing voltage (after 2 ½ cycles of current interruption) in Y&B phases
Note the difference in behavior of R phase voltage, which instead of recovering goes very low. Till Bus-1 isolation the voltage seen in DR was of Ballabgarh bus and after fault clearing the voltage from remote end. The low magnitude of voltage actually does
![Page 45: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/45.jpg)
- 31 -
not vanish at all and continues at the normal frequency. This is the voltage at the fault point on the line as seen by CVT at Ballabgarh end!
After 3 seconds the R pole (1052R) also opens, evidently on Pole Discrepancy (PD) Protection, which is locally generated in the CB, using the position mismatch of the R, Y & B poles from the respective aux. contacts.
It can thus be concluded that the CB 1052R was fully operational and capable of tripping (it tripped too!) but did not receive the primary trip command, most likely due to an open trip circuit. An identical LBB operation and Bus-1 tripping had occurred in the morning of the same day at 0255hrs also. Efforts should have been made by all concerned to check the CB and setting right the problem before putting the CB back in service in morning itself. It was only necessary to check the protection trip function of this breaker. Until the cause of LBB operation was identified, the Breaker could have been kept out of service. This was the second Breaker in the Double Breaker arrangement available for this circuit and would not have had any implication whatsoever other than reducing the reliability. 6.2.2 Tripping of 400 KV Bamnauli-Ballabgarh Ckt.-I With reference to Figure 10: DR of Ballabgarh - Bamnauli - I at Ballabgarh end the following can be inferred. Bus-1 Breaker of Ballabgarh – Bamnauli – I (152) at Ballabgarh end tripped on Bus-1
LBB operation (by 1052R) The R-phase current increase seen may be easily mistaken as a fault of about 3 ½
cycles. But it is certainly not a fault, but a depiction of the conditions seen by Bamnauli – I for the fault on Bamnauli – II. For a fault, the increase in current would be accompanied by reduction in voltage. Here the voltage also is seen to be increasing.
As Bus-1 tripping (seen in Figure 10: DR of Ballabgarh - Bamnauli - I at Ballabgarh end, as opening of TIE CB – 152) isolated the Bamnauli – II fault from Ballabgarh bus. This allows Ballabgarh bus voltage (seen as line voltage) to recover.
![Page 46: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/46.jpg)
- 32 -
Figure 10: DR of Ballabgarh - Bamnauli - I at Ballabgarh end
The voltage could not fully recover as Ballabgarh – Bamnauli – I is continuing to feed
the R-phase fault on Ballabgarh – Bamnauli – II, through Bamnauli bus bars and the STUCK Breaker (of the latter circuit) at Bamnauli. The fault current feeding over Bamnauli – I also increases now as the forcing voltage at Ballabgarh has increased.
The tripping of the Bus-2 CB (352) happens after about 7 cycles. This is not a delayed opening but a prompt opening on receipt of Direct Trip Command. This DT command receipt is recorded in the SOE at Ballabgarh, the relevant portion of which is pasted below:
![Page 47: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/47.jpg)
- 33 -
From Figure 10: DR of Ballabgarh - Bamnauli - I at Ballabgarh end it can be seen that the current in all the three phases vanish before the opening of Main CB (352). This current interruption can only take place if the CB at Bamnauli end opens. Without doubt the CB at Bamnauli of this line opened at this time (DTL claims with the evidence of system control event log, that the Breaker opened at Bamnauli end on DT). Note that the voltages recover fully on this event
Main CB (352) trips on DT (not recorded in DR; may not be wired) about 3 ½ cycles after current interruption and with that the line voltage vanishes, confirming our inference of CB opening at Bamnauli, earlier
Thus it can be positively concluded that there was no fault on this line and had tripped on DT at either end, which is not logically explainable, with the available facts. 6.2.3 Feeding of Fault by Ballabgarh – Bamnauli – II line One REL 511 numerical distance protection relay is wired only for data acquisition purposes at Bamnauli end of Bamnauli – Ballabgarh – II, by DTL, though the Main Protections are Micro-mho. The analogue DR from this relay is available (though time drift is very large), which is pasted below as 11
Figure 11: DR at Bamnauli end of Bamnauli - Ballabgarh - II
The said DR corroborates the conclusions drawn above.
![Page 48: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/48.jpg)
- 34 -
A fault on R-phase (seen as an increased current and reduced voltage in R-phase, not
shown in the said color convention though) can be seen and is never interrupted (including another record, both together has recording of 2 seconds)
On expiry of about 14-15 cycles, the fault current increases in R-phase. This corresponds to the Bus-1 tripping and fault clearing at Ballabgarh. The increase in fault feeding from Ballabgarh – Bamnauli – I (explained in the previous section) causes the fault current contribution to sum up and flow into the Ballabgarh – II fault
Following LBB operation at Ballabgarh, the line gets Direct Trip command and Y & B phases duly opens, while R-phase remains ON.
Summarily, it is inferred that R-phase to ground fault in Ballabgarh – Bamnauli – II circuit, cleared from Ballabgarh
end by LBB protection. Breaker failed to open at Bamnauli end and LBB protection failed to function, probably because it was disabled.
Reportedly, only Bus-1 CB (352) was in service at the time of the incident. Bus-2 CB (452) had been reportedly isolated following a series of erratic operations.
352 had since been restored in service and is since performing correctly, as reported. Thus either 352R failed to open during the incident, trip circuit open circuit was
corrected and the CB tested to find its functioning proper, when tested or, 452 was restored in service in the evening but failed to open. DTL operators have made no mention of any restoration of 452 in their logs, reportedly. Former appears to be more likely.
LBB protection at Bamnauli was probably disabled by the operator at Bamnauli, to avoid any unwanted operation during switching. This is a common practice among operators who do not appreciate the importance of LBB protection in the integrated system currently in vogue. The practice from the older small independent systems’ era is continuing.
Bamnauli end of Ballabgarh – Bamnauli – II receiving DT from other end on LBB operation is logical. DT receipt by either ends of Ballabgarh – Bamnauli – I line defies logic. This could have been a case of spuriously generated DT command.
Based on the timings of the CB opening at either end, it may be possible that the bus-1 trip command to 152 caused DT to Bamnauli (which should be transmitted only if 352 is already open). It is also plausible the CB tripping at Bamnauli end (on DT) does return a DT command (this is normally not so arranged to avoid the vicious loop). The two probabilities is best ruled out by an end to end coordinated testing. The incident of LBB operation at Ballabhgarh end due to stuck of R phase was also reported in the morning incident. Efforts should have been made by concerned to check the CB and setting right the problem before putting the CB back in service in morning itself.
![Page 49: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/49.jpg)
- 35 -
6.2.4 Voltage dip observed around Delhi System
The above events might seem to suggest that the faults on both the 400 kV circuits
between Ballabgarh and Bamnauli have been cleared successfully from both ends.
However, the power system experienced severe low voltages. Voltage dropped to
critically low level at various nearby 400 kV BUS as given below:
These are apparently telemetered voltages (most likely R-Y) and R-phase voltage
dip would have been much more.
Voltage drop up to 66 kV are seen within a second. The following tripping took
place.
6.2.5 Tripping of 400 KV lines from Bawana to Haryana System from remote end
leading to (N-4) contingency
Time Event
21:44:15:750 400 kV Bahadurgarh-Bawana trips from Bahadurgarh (PG)
end only on directional earth fault available in Main-1
protection. (timings as per Event Logger at Bahadurgarh;
21:44:15:435 as per the Numerical Relay output at
Bahadurgarh). Both these outputs enclosed at Exhibit-6/III.
Neutral current observed on this line is of the order of 500
amps.
21:44:19:717 400 kV Hisar-Bawana trips from Hisar end only on Main-2
![Page 50: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/50.jpg)
- 36 -
protection operation B-phase. Timings as per NRLDC SOE
which is time synchronized. Timing as per Hisar EL
21:44:19:610. The directional earth fault element appears to
have picked up considering that neutral current on this line
was 778 amps. Both these outputs are enclosed at Exhibit-
6/IV.
21:44:20:956 400 kV Abdullapur-Bawana-2 trips from Abdullapur end.
Timings as per NRLDC SoE. DR and EL output for this tripping
from Abdullapur end enclosed at Exhibit-6/V. This indicates
that the line has tripped on Main-1 protection. It is seen from
the DR that the neutral current is of the order of 284 amps
leading to the directional earth fault element picking up.
21:44:21:009 400 kV Abdullapur-Bawana-1 trips from Abdullapur end.
Timings as per NRLDC SoE. DR and EL output for this tripping
from Abdullapur end enclosed at Exhibit-6/VI. This indicates
that the line has tripped on Main-1 protection. It is seen from
the DR that the neutral current is of the order of 491 amps
leading to the directional earth fault element picking up.
The above tripping has led to more than 1600 MW power flow to the North West
part of the grid from Bawana getting disrupted and this had to flow on the other
parallel paths from Dadri NTPC (400 kV system), Ballabgarh (PG) 220 kV system
and through the Rajasthan system. This was effectively an (N-4) contingency
occurring within a minute (before any operator actions could be initiated) for which
the power system has not been planned. This led to heavy loading on the 220 kV
lines from Rajasthan system towards Haryana and the tripping as explained below
occurred as per the SoE recorded at NRLDC.
The heavy loading on the 400 kV Dadri-Malerkotla and Dadri-Panipat D/C sections
could not be visualized by the operator at NRLDC as the values got frozen on
account of the current crossing 1000 amps and the 1000/1 CT ratio adopted for
measurement.
6.2.6 Tripping of 220 kV ckts. from Rajasthan towards Haryana leading effectively to
an (N-6) contingency.
Time Event
![Page 51: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/51.jpg)
- 37 -
21:44:26:360 220 kV Hisar-Khetri trips from Khetri end. The relays settings
might be checked to ensure that any conservative ‘overcurrent’
settings are eliminated after ascertaining the reasons for
tripping.
21:44:36:419 220 kV Charkhi Dadri-Khetri-1 trips from Khetri end. The relays
settings might be checked to ensure that any conservative
‘overcurrent’ settings are eliminated after ascertaining the
reasons for tripping.
21:44:36:436 220 kV Charkhi Dadri-Khetri-2 trips from Khetri end. The relays
settings might be checked to ensure that any conservative
‘overcurrent’ settings are eliminated after ascertaining the
reasons for tripping after ascertaining the reasons for tripping.
6.2.7 Tripping of 400 KV Dadri-Panipat ckt.-2 leading to an (N-7) contingency
At this same instance, the 400 kV Dadri-Panipat-2 line has also tripped. This has
not appeared in the NRLDC SoE but is derived from the Historical data Recording
(HDR) facility. The Numerical Relay output available from Dadri NTPC indicates that
the line has tripped on operation of Main-2 protection which is MICOM P437
Numerical Relay of AREVA make (Exhibit-6/VII). On examining the output, it is
observed that the tripping has occurred on account of Zone-5 which got activated at
21:44:36:831 as per this relay timings (this timing is GPS synchronized) and
matches with the above sequence of tripping at Bawana/Rajasthan system.
Zone-5 tripping at Dadri NTPC end is clearly an unwanted operation. Zone-5 ought
to have been blocked, but remained activated by mistake in the process of disabling
Zone-4 to Zone-8 of the relay was disabled following the investigation into the
unwanted operation of the relay on 12.10.2007.Despite this, it appears that a
comprehensive check of all potential threat to the system from such unintended
operations was not done leading to the present tripping on Zone-5.
A similar threat from other numerical relays in the system cannot be ruled out
completely and a comprehensive check has to be made by all utilities to see that all
unintended settings or features available in Numerical Relays are blocked or
disabled. As seen in Chapter-5 of the report, unintended tripping of 400 kV Khedar-
Moga line had occurred during the early morning hours of 2nd Jan 2010 on account
of the ‘overcurrent’ feature being enabled at Khedar end. NTPC informed that they
have blocked Zone -5 setting.
![Page 52: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/52.jpg)
- 38 -
6.2.8 Effect on the NR grid on account of above tripping
Thus within a minute, the system experienced an (N-7) contingency which was an
unprecedented event for which the system has not been planned. Above tripping
led to only the following elements connecting Punjab/Haryana/HP/J & K system to
rest of the grid from 21:44:37 hours.
400 kV Dadri-Malerkotla (tripped at Malerkotla end only)
400 kV Dadri-Panipat-1 (Earth fault, Zone-1) auto-reclosure did not happen
as the relay had blocked auto reclosure due to the over loading before the
fault.
220 kV Samaypur-Charkhi Dadri
220 kV Ballabgarh-Charkhi Dadri
The exact MW power flow on the above 400 kV lines could not be adequately
visualized at NRLDC as the analog readings became suspect on account of the
1000/1 Current Transformer (CT) ratio adopted for various 400 kV lines. The
operator at NRLDC could however see the drop in bus voltages mentioned in
6.2.3 above which would have been on account of two factors:
Reactive power requirement to feed the high active power flows on the
above 400 kV and 220 kV lines.
An un cleared fault at Bamnauli indicated by the 1600-1800 MVAR (with
low MW value) flowing on the 400 kV Bawana-Bamnauli D/C section.
The reactive power requirements under such a situation would have to be met from
the generators nearby such as Dadri NTPC, Lehra Mohabat TPS, Ropar TPS,
GNDTP, Yamuna Nagar TPS, Panipat TPS, Chamera-I and Jhakri HPS. Under
Voltage Load Shedding (UVLS) assumes great importance in such situations.
Absence of this defense plan can lead to a situation of voltage collapse.
The Historical Data Recording (HDR) at NRLDC indicates that low voltage and high
MVAR flow on the 400 kV Mandaula-Bawana-Bamnauli D/C section occurred from
21:44:09 to 21:46:00 hours or approximately two (2) minutes. NRLDC immediately
directed for emergency load shedding in Punjab/Haryana system.
The analysis of this period is covered in the next paragraph.
![Page 53: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/53.jpg)
- 39 -
6.3 Nature of the sustained fault in the system fed from 400 kV Bamnauli
substation and how did it get finally cleared in about two (2) minutes:
As stated above, the SCADA system at NRLDC indicated heavy reactive power
flows in and around Dadri NTPC. Fig 6/3 below indicates snapshot from the
Historical Data Recording (HDR) facility at NRLDC taken at 21:45:02 hours is
indicated below which shows the low voltages (in box) and heavy MVAr flow on 400
kV Bawana-Bamnauli D/C line towards Bamnauli (978 and 996 MVAr each on Ckt 1
and Ckt 2). 400 kV Bamnauli voltage displayed here is incorrect. For a better
understanding of the event, it is also suggested that the Single Line Diagram of
400/220 kV Bamnauli substation at Fig 6/4 is referred.
Figure 9: Snapshot from the SCADA system of NRLDC at 21:45:02 hours
The heavy MVAR flow coming from Bawana towards Bamnauli can flow either
towards Ballabgarh at 400 kV or through the 400/220 kV 4 x 315 MVA ICTs at
Bamnauli depending on where the uncleared fault is prevailing. It is seen from the
![Page 54: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/54.jpg)
- 40 -
SoE at NRLDC that ICTs 3 and 4 have tripped immediately after the fault on the 400
kV Bamnauli-Ballabgarh section described in section 4.2.1 and 4.2.2 above. DTL
has stated that the ICTs have tripped on directional over current. As per the SoE,
the following tripping have taken place at Bamnauli.
21:44:10:225 220 kV Bamnauli-Dwarka-1 trips from Dwarka end on directional
earth fault
21:44:10:270 220 kV Bamnauli-Dwarka-2 trips from Dwarka end on directional
earth fault
21:44:11:290 220 kV Bamnauli-Mehrauli D/C trips from Mehrauli end
21:44:13:725 ICT-3 at Bamnauli opens from 220 kV side
21:44:15:172 ICT-4 at Bamnauli opens from both sides
21:44:38:515 220 kV Bamnauli-Najafgarh D/C trips from Bamnauli end
(reportedly on distance protection as per DTL)
6.3.1 Possibility of fault in the 220 kV network around 400/220 kV Bamnauli ?
At this stage only elements connected at 220 kV Bamnauli were the 400/220 kV,
315 MVA ICTs 1 and 2, 220 kV Bamnauli-Mehrauli D/C line (charged from Bamnauli
end only), 220 kV Bamnauli-Dwarka D/C (charged from Bamnauli end only) and 220
kV Bamnauli-Naraina D/C line. Any uncleared fault on the 220 kV sections would
have resulted in 400/220 kV ICTs 1 and 2 clearing the fault on directional over-
current (as 1600-1800 MVAR from Bawana would have flown through these two
ICTs of 630 MVA only).
Hence an uncleared fault in the 220 kV network for nearly two minutes is ruled out.
So that leaves only the 400 kV Bamnauli-Ballabgarh D/C section as the likely
candidates for an uncleared fault from Bamnauli end.
6.3.2 Why didn’t the fault get cleared from Bawana end on distance protection at
least in Zone-2 or Zone-3?
Since the fault has occurred 35 km from Bamnauli towards Ballabgarh and the
nature of the fault is an earth wire snapping and hanging, there is a possibility that
the fault is an arcing high impedance fault and beyond the reach of the distance
protection at Bawana.
![Page 55: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/55.jpg)
- 41 -
6.3.3 Even if the distance protection at Bawana could not sense the fault,
shouldn’t the directional earth fault relay at Bawana sensed this fault much
earlier rather than a trip at the ends remote to Bawana?
Yes, it should have happened but it is reported that the 400 kV Mandaula-Bawana-
Bamnauli-Ballabgarh section does not have a directional earth fault relay at
Mandaula, Bawana and Bamnauli ends. This has been recommended for 400 kV
lines by the CBIP Technical Publication no. 274 and also by the Protection sub-
committee of NRPC. This explains why neither 400 kV Mandaula-Bawana D/C did
not trip at Mandaula end nor 400 kV Bawana-Bamnauli D/C did not trip at Bawana
end.
6.3.4 How did the fault finally get cleared?
The high MVAR flow on 400 kV Bawana-Bamnauli D/C line has disappeared around
21:46 hours indicating that the fault has been cleared. However there was no
evidence of any switching operation on 400 kV Mandaula-Bawana-Bamnauli section
which was the only infeed to the fault. So how did the fault finally get cleared.
General Manager (O & M), DTL’s report dated 18th January 2010 states ‘On
patrolling, Bamnauli-Ballabgarh lines, it has been observed that the earth wire
between Tower No. 270 (35 km. from Bamnauli end), Tower no. 277 (37 km. from
Bamnauli) were found burnt and broken. Disc insulators of three towers i.e. Tower
No. 272 & 273, (Disc insulators of Ckt II) & Tower No. 276 (Disc insulator of Ckt.I &
Ckt.II) were found cracked.’ Fault clearing by fusing of conductor is highly unlikely.
Probably operators at Bamnauli gave a trip command.
Thus the fault appears to have been cleared by burning of the snapped earth wire
and not due to any switching operation. This is also evident from the fact that 400
kV Bamnauli-Ballabgarh-2 was restored at 2309 hours of the same night and held
okay. However, this also raises another concern that without ascertaining the nature
of fault (which must have been known only the next day after patrolling), the system
was restored and could have had a bearing on public safety.
6.4 Sequence of events after clearance of the fault on 400 kV Bamnauli-Ballabgarh
Ckt 2: (Timings as per NRLDC SoE unless otherwise stated)
21:48:55:185 400 kV Hisar-Bawana closed from Hisar end providing some
relief to the congested Dadri-Panipat & Dadri-Malerkotla
![Page 56: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/56.jpg)
- 42 -
sections.
21:49:20:414 400 kV Hisar-Bawana trips, autorecloses and again trips on
line fault from both ends (it tripped on B-phase to ground
fault, B-phase jumper was found damaged at loc. No. 35).
Numerical Relay and EL output enclosed at Exhibit-6/IX.
21:51:42:929 220 kV Ballabgarh-Charkhi Dadri trips from Ballabgarh end
on distance protection (all three phases). The line went under
breakdown. The Historical Data of this line flow becomes
suspect before the tripping. Special Energy Meter (SEM) data
suggests that the flow would have been of the order of 350
MW.
21:52:08:684 400 kV Abdullapur-Bawana-1 closed from Abdullapur end
providing some relief to the congested Dadri-Panipat & Dadri-
Malerkotla sections.
21:53:00:331 Dehar-1 hydro unit taken out as part of generation schedule.
21:53:39:095 220 kV Samaypur-Dadri trips from Samaypur end on distance
protection. (all three phases). The Historical Data of this line
flow becomes suspect before the tripping. Special Energy
Meter (SEM) data suggests that the flow would have been of
the order of 350 MW.
21:53:58:582 400 kV Dadri-Panipat-1 trips from both ends on distance
protection, R-phase to ground fault, Zone-1 at Dadri NTPC
end. Numerical Relay output enclosed at Exhibit-6/X. The
reason for this fault needs to be established. The lline failed
to reclose at Dadri end as the pre trip loading on the line was
of the order of 1800A, which had generated a A/R BLOCK.
(see the A/R Block trace in DR) The fault would have been
transient in nature considering the fact that this line was
restored at 2325 hours, the same day. This line might have
been carrying 1200-1800 amps for nearly ten (10) minutes,
which although less than the thermal limit might have resulted
in clearance related issues, which does not crop up under
normal loading conditions. Likely cause tree infringement
21:54:00:649 400 kV Abdullapur-Bawana-1 tripped from Bawana end on Y-
phase to ground fault. It tripped at Abdullapur end much later
at 21:54:04:826 on pole discrepancy. EL and Numerical relay
output at Abdullapur enclosed at Exhibit-6/XI.
21:54:00:765 400 kV Dadri-Malerkotla line tripped at Malerkotla end on
![Page 57: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/57.jpg)
- 43 -
distance protection, apparently due to power swing. EL and
Numerical relay output for this trip enclosed at Exhibit-6/XII.
This output shows extremely low voltages 320 kV and 3.2 kA
current in each phase.
With the above tripping, the Punjab/Haryana/HP/J & K system separated from rest
of the grid (barring a small portion of HP system which remained connected with the
Uttarakhand power system radially and small portion of Faridabad and Gurgaon
areas connected to Ballabgarh which survived) and collapsed within a few seconds
on account of low frequency and failure of the defense mechanism which has been
explained in Section 5. The axis of separation is enclosed at Exhibit-6/XIII.
In rest of the NEW grid, the frequency shot up from 50 Hz to 51 Hz and a few 400
kV line tripped on reported over voltage (O/V) protection as given below.
Fortunately the system survived. Since no generating unit was in operation at
RAPS-C nuclear power station, no unit tripping occurred at this station. However,
primary response through the governing system would definitely have helped the
situation further, else secondary collapses in the unaffected system on account of
high frequency and high voltage cannot be ruled out.
Transmission line Time of tripping Time of
restoration
400 kV Agra-Auraiya-I 21:54 22:35
400 kV Agra-Auraiya-I 21:54 22:21
400 kV Balia-Patna-I 21:55 22:22
400 kV Gorakhpur-Gorakhpur-I 21:55 22:00
400 kV Kankroli-RAPP-C-I 21:55 22:00
400 kV Kankroli-RAPP-C-II 21:55 22:00
400 kV Kota-RAPP-C 21:55 22:00
400 kV Lucknow-Bareilly-II 21:55 22:47
400 kV Gorakhpur-
Muzaffarpur-I
21:55 03-Jan-2010
The angular separation between the North and West 400 kV bus at Vindhyachal
during the entire day is shown in Fig 6/5 below which shows a sharp spike in the
angular difference at the two instances of separation. Positive sign of angle
indicates that North bus is leading while negative sign shows that West bus is
leading. Visualization of angular separation between buses would also be made
![Page 58: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/58.jpg)
- 44 -
possible in Northern region through the synchrophasor technology. As part of
adopting this technology, NRLDC is already going ahead with a pilot project
involving four (4) Phasor Measurement Units (PMUs) being installed at Vindhyachal
HVDC back to back station, Kanpur, HVDC Dadri and 400 kV Moga substations.
This would provide a parallel means of real time monitoring independent of the
Energy Management System (EMS).
Fig 11: Angular separation between North & West bus at Vindhyachal HVDC back to
back
In Delhi system, a small portion of east Delhi and generating units at Pragati had got
islanded due to tripping of 220 kV Wazirabad-Geeta Colony D/C line. The Pragati units
tripped. This incident was not related to the main incident above although the timing was
similar. Likewise, supply disruption at seventeen (17) 220 kV substations occurred some of
which were not related to the main incident above. At 2157 hours, the operator at 400/220
kV Bawana substation is reported to have opened the 400 kV Mandaula D/C lines on
noticing arcing in the switchyard. This led to supply disruption in all the 220 kV substations
fed from 400 kV Bawana and Bamnauli sub stations.
6.5 Main causes of the disturbance
On the basis of analysis of event the main attributes for the grid disturbance at
21.54 hrs can be identified as:
Unintended and unexpected operation of protective system/switchgear of
some of the critical transmission elements as well as non operation of some
of the protective system in already depleted network;
3:01 hrs, ‐4.7 degree
9:53 hrs, ‐34.73 degree
-50
-40
-30
-20
-10
0
10
20
00:02 02:02 04:02 06:02 08:02 10:02 12:02 14:02 16:02 18:02 20:02 22:02
An
gle
Time
Profile of Angular Separation Between 400 kV North & West bus at HVDC Vindhyachal Back to Back S/S on 2nd Jan 2010
Instant of Grid Disturbance in Punjab,North Haryana, HP, J & K and
Instant of Grid Disturbance in Punjab, Haryana,Part of Delhi, HP, J & K and
![Page 59: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/59.jpg)
- 45 -
Operator’s inability to adequately comprehend the situation in certain cases.
Inadequacy of safety net.
![Page 60: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/60.jpg)
- 46 -
CHAPTER 7 Defense mechanism in the Grid
7.1 Defense mechanism available in the Northern Regional (NR) grid.
In order to protect the interconnected power system against the system related
contingencies like low frequency, sudden dip in frequency and voltage collapse,
Regional Power Committee (RPCs) throughout the Indian power system have
recommended for installation of under frequency (UFR), rate of change of
frequency(df/dt) and under voltage relay based load shedding (UVLS) schemes in the
Northern Region.
A report on under frequency load shedding scheme based on the input received from
the respective state utilities was updated and is available on the NRPC website. Apart
from the setting recommended for Northern Regional Power System, the major
decisions taken regarding operation of UFR and DF/DT relays in the NRPC meeting
are as under.
a) As decided in the 7th NRPC meeting held on 21-12-2007 adequate load relief was
to be provided by installing 30% additional UFRs, to compensate the manual load
shedding on feeders connected to UFRs.
b) The UFRs installed in the system should be tele-metered and mapped to SCADA
system (as per decision of the 14th NRPC meeting held on 19th Sept, 2009)
c) Constituent States have been requested to supply data on load relief through
UFRs, rotational load shedding scheme and manual load shedding on typical days
and time in each month when frequency falls below 48.8 Hz.
The load relief by UFR should not be counted for those feeders which are already on
manual load shedding of statutory power cuts. As UFRs are the defense mechanism
for the system and it should be ensured that whenever required, these operate
successfully.
7.2 Recommended Settings for Load Relief
![Page 61: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/61.jpg)
- 47 -
Settings recommended for Northern Region Power System by Northern Region Power
Committee (NRPC) are described below.
7.2.1 UFR setting in Northern Region as recommended by NRPC
Three stages of under frequency relay (at 48.8 Hz, 48.6 Hz and 48.2 Hz) based load
shedding have been recommended. State wise load relief envisaged from UFR relays
based load shedding scheme in Northern Region are given at table below.
Load relief in MW STATES Peak MW
Met 2008-09 48.8 Hz 48.6 Hz 48.2 Hz Total
Punjab 7309 180 220 400 800
Haryana 4791 110 140 350 600
Rajasthan 6101 120 150 425 695 Delhi 4034 110 140 350 600 UP 8248 190 240 475 905 Uttarakhand 1267 30 30 100 160 HP 1014 20 20 75 115 J & K 1380 40 50 75 165 Chandigarh 279 0 10 0 10 TOTAL 29504 800 1000 2250 4050
Table 6: State wise planned Load Relief from UFR in NR
7.2.2 df/dt setting in Northern Region as recommended by NRPC
Protection against sudden dip in frequency has also been recommended in three
stages. Stage-I of df/dt scheme is to protect the combined ‘N-E-W’ grid from loss of
generation of a large power station and stage-II of the df/dt is to protect the split grid
from loss of generation of a large power station in NR, WR, ER. The recommended
setting for these two stages are as summarized at table below.
![Page 62: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/62.jpg)
- 48 -
In addition to this, stage-III (or stage –IV) of df/dt have also been recommended to
protect the individual regional grid / state grid from loss of generation in the event of
isolation.
Setting of df/dt relay NR WR ER
STAGE - 1 2000 MW at 0.1 Hz/Sec. at 49.9Hz.
2000 MW at 0.1 Hz/Sec. at 49.9Hz
800MW (600MW ER+ 200MW SR) at 0.125 Hz/Sec. at 49.9Hz.
STAGE- 2 2000 MW at 0.2 Hz/Sec. at 49.9Hz.
2000 MW at 0.2 Hz/Sec. at 49.9Hz.
Nil
Table 7: Recommended df/dt relay setting in NEW grid
Load relief in MW STATES Stage-I
49.9Hz& 0.1Hz/sec
Stage-II 49.9Hz& 0.2Hz/sec
Stage-III 49.9Hz& 0.3Hz/sec
Total
Punjab 430 490 490 1410 Haryana 280 310 310 900 Rajasthan 330 370 370 1070 Delhi 250 280 280 810
UP 500 280 280 1060 Uttarakhand 70 70 70 210
HP 50 70 70 190 J & K 90 90 90 270 Chandigarh 0 50 50 100 TOTAL 2000 2010 2010 6020
Table 8: State wise planned Load Relief from df/dt relays in NR
7.2.3 Under Voltage Load Shedding (UVLS) in NR
![Page 63: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/63.jpg)
- 49 -
After the synchronization of Northern Region power system with central grid in August
2006, during its 3rd meeting in November 2006, NRPC have recommended for
installation of Under Voltage relay based load shedding. The state utilities have been
advised to adopt a setting in the range of 180-190 kV voltage with 5-10 seconds delay.
7.2.4 System Protection System (SPS)
To avoid the overloading and thereby possible tripping of parallel AC lines , an SPS
has been provided in Rihand Dadri HVDC bipolar line which activates when one or
both pole of Rihand- Dadri trips. Based on the loading & tripping of pole(s) , the load is
shed in Delhi, UP, Haryana, Punjab and Rajsathan , generation is reduced at Rihand
Singrauli complex and ramp down of power flow at Vindhyachal HVDC BTB.
An SPS has also been provided at 400kV Mujaffarpur – Gorakhpur D/C inter-regional
link, which trips equivalent load in the states of Northern Region.
Another SPS has been proposed for Balia- Bhiwadi HVDC line, which would also
ensure shedding of load in NR and reduction in generation at Rihand Singrauli complex
and Kahalgoan (ER) on its activation.
7.3 Performance of the defense mechanism in above disturbance
During the instance of grid disturbance at 03.01 hrs. due to failure of auxiliary supply at
microwave communication system, the telemetry from a large portion of the affected
system was not available and therefore the real time data from this portion was not
available. For the disturbance at 21:54 hrs., the frequency data has been derived from
the Historical Tabular Trend of Ropar TPS unit 3-6 enclosed at Exhibit- 7/I.
However, as the relief from UFR and df/dt relays is generally envisaged from the load
at lower level voltages (say 132, 66 and 33 KV). The telemetry for most of such
locations is also not available. Even through the constituents in 14th NRPC meeting
held on 19th September, 2009 agreed to make arrangement for telemetry to register the
relief from UFR & df/dt relays.
![Page 64: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/64.jpg)
- 50 -
7.3.1 Performance of UFR and df/dt scheme at 03.01 hrs of 2nd Jan 2010
7.3.1.1 PSEB has submitted that due to foggy condition in Punjab area the tripping were
observed on various 220KV lines since 31st December, 2009. The detail of line tripping
as submitted by PSEB is given in their report enclosed at Annexure 7/I.
As described in the analysis of the grid disturbances under Para 5.3.2, the tripping of
complete Ropar TPS occurred prior to the grid disturbance at 0255 Hrs on 2nd January,
2010. Ropar TPS was generating about 973 MW. 5 out of the 10 evacuation lines
from Ropar TPS were our prior to the incidence. Even onward network from feeding
stations of Govindgarh & Sahnewal was also depleted. Under the depleted network
condition and further tripping of Mohali-Rajpura (both circuits) & Ganguwal-Mohali
circuits around 0255 Hrs, frequency rose to 55.3 Hz due to islanding of Ropar TPS.
The machine trips thereafter on generator over speed. After tripping of Ropar TPS and
prior to grid failure at 0301 Hrs, PSEB generation was 650 MW and drawal from the
grid 600 MW (against schedule of 513 MW) for meeting a load of 1250 MW. PSEB
submitted that at the time of grid failure, the frequency dropped was so steep in the
sub-system that the deficit of 600 MW in Punjab could not be sustained and PSEB own
generation of 650 MW was lost. PSEB reported that at this instant a relief of about 232
and 72 MW by df/dt operation at 0301 hrs. Additionally 72 MW relief was provided by
UFR operation in BBMB System at Jamalpur and Jallandhar. The details of UFR and
df/dt report from PSEB and BBMB system is enclosed at Annexure- 7/II and 7/III
respectively.
7.3.1.2 SLDC, Haryana submitted that 63 number of 220 KV lines of Haryana trip, 15
number of lines trip due to failure of conventional disk insulators under heavy fog and 1
number of line due to anti fog insulator. A copy of analysis report submitted by
Haryana is enclosed at Annexure 7/IV
![Page 65: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/65.jpg)
- 51 -
UFR report from HVPNL is placed at Annexure- 7/V. The planned load was 230 MW
for stage –I ( flat 48.8 Hz). The feeders on which stage –I of UFRs have been installed
had a load of 127 MW only at 0200 Hrs and 49 MW at 0300 Hours just prior to the
system separation. This indicates non availability of load on the feeders due to
massive tripping by Fog and inclement weather conditions.. During the incident of 0301
Hrs the df/dt did not operate in Haryana system.
7.3.1.3 SLDC, Himachal Pradesh reported that a load relief of about 115 MW was planned
by UFR operation and 190 MW by df/dt relays. The relief obtained was of the order of
20 MW ( at 48.8 Hz) and 64 MW by df/dt (at 0.1 Hz/s) relay operation at 0301 Hrs. In
addition due to depleted network/ grid failure, UFR & df/dt relay could not be operated
which otherwise could have provided load relief of 40 MW and 79 MW respectively.
The details of UFR and df/dt report from HP is enclosed at Annexure-7/VI.
7.3.2 Performance of UFR and df/dt scheme at 21.54 hrs of 2nd Jan 2010
One second interval SCADA data of the Ropar TPS indicates (pl refer Ropar Historical
Tabular Trend data at Exhibit -7/I ) that frequency touched the minimum level of 45.5
Hz at the instance of blackout at 21.54 hrs of 2nd Jan 2010 and the rate of change of
frequency (df/dt) was of the order of 1.8 Hz/sec. The frequency and df/dt plots for the
2154 hours incident are shown in Figure 12.
![Page 66: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/66.jpg)
- 52 -
Figure-12: Frequency and rate of change of frequency plot
7.3.2.1 PSEB submitted that generation prior to the grid disturbance was about 2212 MW
while a load of 3200 MW was being met through drawal of 1000 MW against schedule
of 900 MW. At the time of grid failure, the frequency has dropped sharply in this
subsystem to about 45.64 Hz. And the deficit of about 1000 MW in Punjab alone could
not be sustained and the available generation of 2200 MW was lost. At this instant a
relief of about 295 MW was provided by UFR operation and 153 MW by df/dt relay
operation.
7.3.2.2 SLDC, Haryana reported that due to failure/ tripping of 400 KV transmission
system/ lines, 12 number of 220 KV line of Haryana along with Panipat TPS &
Yamunanagar TPS tripped at 2155 Hrs. However transmission lines in Gurgaon and
Faridabad area of NCR along with generation at Faridabad TPS and Faridabad,
Gurgaon station remain intact. No disc insulator failure occurred during this incidence.
The details of operation of UFR & df/dt relays indicate that the load relief of about 10
MW was provided by UFR operation and 37 MW provided by df/dt (at 0.1 Hz/s) relays
operation at 2155 Hrs at 220 kV Jorian and Sirsa sub stations of HVPNL.
BBMB reported a load relief of 150 MW at Jamalpur and Jallandhar at 2154 hrs. BBMB
has also stated that wherever UFRs and df/dt relays have not operated it might be due
to inherent features of relays during extreme conditions.
7.3.2.3 Himachal Pradesh reported a load relief of 20 MW by operation of UFRs installed
in the firm’s premises (GACL Dharlaghat and ACC Barmana).These firms have
segregated fixed load, 10 MW each, which trips on operation of flat UFRs. HPSEB
reported a relief of 55 MW by df/dt (at 0.1 Hz/s) operation. Due to depleted network/
grid failure, UFR & df/dt relay could not be operated which otherwise could have
provided additional load relief of 29 MW and 27 MW respectively.
7.4 Performance of UVLS
![Page 67: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/67.jpg)
- 53 -
During the incident of 0301 hours in the early morning of 2nd Jan 2010, system
voltages dipped to critically low level due to very high loading of transmission
system in the depleted network. There was heavy inrush of power flow on the 400 kV
Dadri- Malerkotla and 220 kV Hisar-Sangrur D/C line due to outage of parallel circuits
interlinking the affected area with main grid. The reactive power flow/loss on 400 kV
Dadri-Malerkotla (Figure 5 Chapter-5 of this report) and 220 kV Hisar Sangrur was of
the order of 1000 MVAR and 360 MVAR respectively.
Plot of voltage profile at Dadri (Th), Malerkotla, Srinagar and Kishenpur during the grid
disturbance at 03.01 hrs are shown in Figure 13 and 14. It has been observed that dip
in voltage at Dadri (Th) was of the order of 30 kV and at Malerkotla was of the order of
67 kV. The voltages at Kishenpur and Srinagar were dipped by 30 kV and at Hisar-
Sangrur dipped by 25 to 30 kV. Such a low voltage profile persisted for about 5
minutes.
Very low voltages were also observed in the National Capital Region also during the
instance of grid disturbance at 21.54 hrs for a fault on 400 kV Ballabgarh-Bamnauli line
and subsequently during heavy inrush of power through the main tie lines between
affected area and the rest of the grid. However no instance of under voltage loads
shedding has been reported in the affected region during either of the incidents.
![Page 68: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/68.jpg)
- 54 -
Figure-13: Voltage Profile at Dadri (Th) & Malerkotla in the morning of 2nd Jan
2010
![Page 69: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/69.jpg)
- 55 -
Figure-14: Voltage Profile at Kishenpur and Srinagar in the morning of 2nd Jan
2010
7.5 What could be possible Reasons for inadequate relief from UFRs, and df/dt
relays
BBMB has reported (copy enclosed at annexure- 7/ VII that the grid collapse on
2nd January, 2010 was due to inability of the collapsed network/multiple tripping in
NR to meet adequately the shortfall of power in the sub-system of NR. The HDR
report generated in respect of BBMB system indicates that the grid incident at 0301
hrs on 2nd January, 2010 occurred at frequency of 50.6 Hz and second incident at
2154 hrs occurred around 50.1 Hz. At this frequency, neither UFR nor df/dt relays
could provide any relief.
In the depleted system/network, when many feeders on which the relays are
installed could be under power cuts or in tripped condition. The operation of UFR
and df/dt relays even at such high frequency could only provide relief to the extent
of loading at that time.
Further, as per the literature of Ms. ABB whose relays are installed, mention that the
various features of relays restrict the operation of relays in extreme conditions, i.e.
the rate of change of frequency not to exceed 70 Hz/sec, minimum trip time of df/dt
is 150 ms and UFR 100 ms and default setting of the relays is 60% of the nominal
voltage.
In addition, voltage at various sub-station of BBMB dipped sharply and with the
feature of under-voltage blocking (in addition to other inherent features of relays
such as time delay etc) provided in UFR and df/dt relays, the operation of relay
was not supposed to take place. BBMB’s analysis report is placed at Annexure-
7/VIII.
The feeder selection for providing the relays is very important. It has been observed
in some cases that the feeders on which relays are installed are OFF for some
![Page 70: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/70.jpg)
- 56 -
periods leaving the system insecure. Likewise, the relays need to be installed on
feeders having significantly high load factors so that relief is available under
different conditions. The areas under UFR should also not be subject to manual
loadshedding. However as all these conditions have been difficult to achieve, NRPC
has recommended for 30% additional relief from the above values so that adequate
relief from UFR load shedding is available most of the time.
A time delay of 200 ms provided in some of the df/dt relays to avoid their
undesirable operation and a sharp dip in voltage after separation of systems has
been suggested as a possible cause for non-operation of many UFR and df/dt
relays particularly in BBMB area.
However irrespective of the frequency at the time of the separation, the frequency in
the islanded sub-system which was an importer of power prior to the separation,
would fall. Based on data available from Ropar TPS, it is evident that system had
survived for 5 to 6 seconds with frequency below 48 Hz being recorded and rate of
change of frequency by any account would be in the range of 1.8 Hz/sec. Thus
both df/dt and UFR relay should have operated, and some relays have really
operated in Punjab system. However the voltage at 220 kV bus has fallen to 184
kV from 225-230 kV. The under voltage blocking in many relays are 30-90% of the
input voltages with default setting at 60%. Since, the voltage at various sub-stations
dipped sharply and with the feature of under-voltage blocking provided in UFR and
df/dt relays the operation of relay probably did not take place. But Voltage being a
local phenomenon, under voltage blocking cannot be sole reason for non operation
of UFRs and df/dt relays in entire affected sub system. It is evident from the fact that
stage _II / III of df/dt relays have operated in Punjab system. So their settings need
to be reviewed. The inquiry committee recommends that defense mechanism in
shape of df/dt and UVRs should be strengthened in NR. Further safety net need to
be strengthened by providing additional SPS at vital part of system like north-west
part of Northern Grid.
![Page 71: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/71.jpg)
- 57 -
CHAPTER 8 Restoration of the system 8.0 General:
The restoration of the system was started immediately following the collapse of the
part of Northern Regional power system. The main objectives which were kept in
consideration at the time of restoration were;
Priority of supply to Railways
Start up supply to thermal stations
Faster restoration
8.1 Restoration after event at 0301 hrs:
The system restoration after this event was impacted due to non availability of
number of 400 kV and 220 kV trunk lines in various corridors on account of foggy
weather conditions. Therefore, the ‘Top down’ approach of restoration from
resources already available in larger system was proving to be difficult and
accordingly ‘Bottom UP’ approach of starting many island was also adopted.
Though, this type of restoration philosophy is accompanied with its own share of
problems as it requires considerable efforts during synchronisation of these sub-
systems or accidentally mixing of supplies of these sub-systems, but under the
given situations it was effectively employed for faster restoration.
8.1.1 Challenges experienced in reaching the hydro stations during restoration
During the time of restoration the following challenging conditions were experienced
in reaching to main hydro stations :
Dehar HPS on account of outage of 400 kV Panipat-Dehar & Bhiwani-
Dehar
Chamera-I HPS and further power stations in J & K on account of outage
of the 400 kV Hisar-Fatehabad-Moga & 400 kV Hisar-Khedar-Moga
sections.
Jhakri HPS on account of 400 kV Bawana-Abdullapur-Jhakri section and
400 kV Hisar-Patiala-Nalagarh-Jhakri sections.
8.1.2 Bottlenecks experienced in extending start up to thermal stations
The bottlenecks were also experienced in extending start up supply to the thermal
power stations as paths were not available. For instance outage of Govindgarh
substation in Punjab, posed a severe constraint in extending start up power through
the 220 kV Ganguwal-Govindgarh route. Similarly, outage of 220 kV Rajpura-Mohali
section posed a constraint in extending start up to Ropar TPS on Patiala(PG)-
Rajpura-Mohali-Ropar section.
![Page 72: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/72.jpg)
- 58 -
8.1.3 Issues during Black start of hydro units
The black starting of hydro units also has its initial share of issues as this requires
calling of additional maintenance crew at these stations. The continuous follow-ups
were made with these stations and finally following units were black started and
provided valuable support in reviving the system as well as in feeding some
important load:
Jhakri 0458 hours
Salal 0542 hours
Chamera-I 0507 hours
Uri 0740 hours
8.1.4 Issues in BBMB system In BBMB system, although the supply was quickly extended to Bhakra from Hisar
on 220 kV Hisar-Sangrur-Jamalpur-Bhakra route by 0340 hours and unit at Bhakra
synchronized, this system tripped several times (0404, 0429, 0509 and 0608 hours).
The system could not hold due to non availability of sufficient load on the system
resulting into unprecedented High Voltage conditions. During two such attempts,
the system tripped resulting into flashover on the Discs at 220kV Bus – II of
Jamalpur. The restoration was again attempted at 06:10 hrs by extending the
supply from Hisar to Sangrur to Jamalpur to Bhakra, however the system again
collapsed due to operation of Bus Bar Protection at Jamalpur at 06:41 hrs.
Thereafter both the Buses at 220kV Jamalpur Sub-Station were unavailable and
consequently the option of extending supplies from 220kV Bhiwani or 220kV Hisar
Sub-Stations was also closed.Ultimately the unit at Bhakra(Left) operated in isolated
mode and could be synchronized with the main system only by 0841 hours on 400
kV Bhiwani-Dehar-220 kV Ganguwal link.
8.1.5 Railway Traction Supply
Railway traction supply on the Delhi-Ambala and Ambala-Amritsar routes were
affected on account of the disturbance. The supply to railways was also affected to
Delhi-Hawarh section from Dhankaur feeding point despite the Dadri (Gas) station
being live, due to tripping of Railways own 220 kV interconnector between Dadri
(Gas) and Dhankaur. The supply to this section was extended from 220 kV Auraiya
section by the Railways itself.
8.2 Restoration Sequence of the incidence at 0301 hrs.:
![Page 73: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/73.jpg)
- 59 -
The broad restoration sequence after the above incident is given at Annexure-8/I
8.3 Restoration after event at 2154 hrs:
Restoration after this event started with ‘Top down’ approach as the transmission
system paths for reaching to the different thermal and hydro station were not under
breakdown as were after the morning incident. Still in order to extend supply to J&K
areas (higher restoration time anticipated as being far away from the healthy part of
the system), the Uri and Salal HEPs were black started for radially feeding limited
supply to Valley and Jammu area respectively. The broad philosophy of restoration
is as given below:
8.3.1 400 KV Dadri-Malerkotla circuit was restored and supply was extended to Punjab
system with start up to Lehra Mohabbat, Bhatinda, to 400 kV Patiala and to Punjab
system and railways.
8.3.2 From Patiala the supply was extended to 400 kV Nalagarh & supplied to
Chandigarh and Jhakri. Later Jhakri supply extended upto Abdullapur and
Haryana/HP system with startup to Yamunanagar also. Abdullapur-Bawana was
also restored.
8.3.3 From Malerkotla supply was extended to 400 kV Ludhiana - 400 kV Jallandhar.
Supply extended to Kishenpur through 400 kV Jallandhar-Chamera-Chemara2-
Kishenpur section.
8.3.4 Punjab system normalised from 400/220 kV interconnection at these stations.
8.3.5 Supply extended to 400 kV Moga/Amritsar also. Simultaneously supply to Moga
was tried through Hisar-Fatehabad-Moga and 400 kV Hisar-Khedar-Moga section
as well as through Punjab’s 220 kV network also.
8.3.6 From Kishenpur supply extended to Salal and Jammu region of J&K restored.
8.3.7 From Kishenpur supply extended to 220 kV Pampore-Wagoora-400 kV Uri and
Valley system of J&K restored.
(The Salal and Uri were also black started with radial load of Jammu and Ziankote
respectively)
8.3.8 Supply extended upto Bhakra on from Charkhi Dadri- Panipat- Dhulkote-
Ganguwal - Bhakhra and supply to Railways & Panipat (T) extended from Panipat.
![Page 74: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/74.jpg)
- 60 -
Afterwards supply extended from Bhakra to Punjab system.
8.3.9 400 kV Dadri-Panipat normalised and extended up to Dehar. This supply clubbed
with other restoration supply at Panipat through 400/220 kV ICT and at Dehar
through 400/220 kV ICT and 220 kV Dehar-Ganguwal.
8.3.10 400 kV Mandola-Bawana, 400 kV Ballabgarh-Bamanuli-Bawana and then Bawana
to Hisar, Bawana to Abdullapur, Bawana-Bahadugarh-Bhiwani normalised to
strengthen the revived system.
8.3.11 220 kV Charkhi Dadri –Bhiwani- Hisar-Hisar-IA- Hisar PG and Hisar-Sangrur
section also restored with strengthening at Dadri through 220 kV Khetri- Dadri, at
Hisar through 220 kV Khetri-Hisar and at Hisar (PG) through 400/220 kV ICT and
400 kV Hisar-Patiala.
8.4 Restoration Sequence of the incident at 21:54 hrs:
The broad restoration sequence after the above incident is as follows:
Time (hh:mm) Restored Element/Section/System
22:04:09 Supply extended to Malerkotla on 400 kV Dadri-Malerkotla
22:19:49 400 kV Dadri-Panipat-II restored
22:21:57 Supply to Charkhi Dadri on 220 kV Samaypur-Charkhi Dadri
22:23:38/47 400/220 kv ICTs at Malerkotla taken in service.
22:26:03 Supply to 220 kV Bhiwani on 220 kV Ch. Dadri-Bhiwani
22:30:56 Supply to 220 kV Panipat through 220 kV Ch Dadri-Panipat
22:33:40 Supply to Dhulkote on 220 kV Panipat-Dhulkote-1
22:33:47 Supply to Barnala on 220 kV Barnala-Malerkotla
22:36:22 Supply extended to Chandigarh on 660 kV chandigarh feeders
from Dhulkote
22:37:44 Main Bus-1 at 400 kV Ballabgarh restored.
22:39:04 400/220 kV ICT-2 at Panipat taken in service
22:41:04 Supply extended to Ganguwal on 220 kV Dhulkote-Ganguwal-1
22:43:15/29 400 kV Malerkotla-Patiala and 400 kV Malerkotla-Ludhiana
charged.
22:45:46 220 kV Panipat-Panipat (T) #2 closed and supply to Panipat (T)
22:45:55 Supply to Lehra Mohabbat on 220 kV Barnala-Lehra Mohabat and
then to Bhatinda
![Page 75: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/75.jpg)
- 61 -
Time (hh:mm) Restored Element/Section/System
22:52:27 400 kV Panipat-Dehar restored
22:55:34 220 kV Khetri-Hisar charged
22:55:56/56:06 220 kV Khetri-Dadri I & II charged
22:57:02 400/220 kV ICT # 2 at Patiala restored
22:58:17 220 kV Patiala-Ablowal restored.
22:59:59 Supply extended to Bhakra on 220 kV Ganguwal-Bhakra –IV
23:01:22 400/220 kV ICT at Dehar restored
23:02:13 400 kV Mandola-Bawana-1 restored.
23:03:54 GT # 10 at Bhakra taken in service
23:03:58 400 kV Ballabgarh-Bamnauli -2 restored.
23:07:41 Supply extended to Jamalpur on 220 kV Bhakra-Jamalpur-1
23:07:41 Supply to Nalagarh over 400 kV Patiala-Nalagarh
23:11:41 Supply given to Chandigarh on 220 kV Nalagarh-Chandigarh -2
23:15:49 400 kV Nalagarh-Jhakri 2 line taken in service
23:20:11 Dehar unit # 3 synchronised
23:20:12 132 kV Kotla-Ropar restored
23:24:45 220 kV Hisar-Sangrur –I restored
23:25:21 NJPC –Abdullapur-II closed.
23:27:08 NJPC # 3 synchronised.
23:32:43 400 kV Hisar-Patiala synchronised.
23:35:22 Supply extended to Railways and to Yamuna Nagar
23:38:14 400 kV Hisar-Fatehabad restored
23:42:50 Supply to Pong on 220 kV Pong-Jallandhar-I
23:46: 400 kv Abdullapur-Bawana-I restored.
23:54:26 Uri # 2 started in islanded mode with load at Ziankote
00:01:20 Salal # 4 started in islanded mode with Jammu load
00:09:46 400 kV Mandola-Bawana –II restored.
00:11:49 400 kV Bawana-Hisar charged from Bawana and closed at Hisar at
00:18:34
00:14:27 400/220 kV ICT at Bahadurgarh restored
00:20:57 400/220 kV ICT-1 at Kaithal restored (from 220 kV)
00:20:57 400 kV Hisar-Kaithal restored
00:23:27 400 kV Bahadurgarh-Bawana restored.
00:30:28 400 kV Hisar-Bhiwani restored.
00:43:39 400 kV Jallandhar-Chamera II charged
01:26:11 Chamera 2 unit synchronised.
![Page 76: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/76.jpg)
- 62 -
Time (hh:mm) Restored Element/Section/System
01:27:55 Supply extended to Kishenpur on 400 kV Chamera2-Kishenpur
01:29 Salal island tripped so that it could restored.
01:46:12 Supply extended to Salal on 220 kV Kishenpur-Salal-1
01:53:49 Salal unit # 4 synchronised.
02:42:17 Uri island tripped so that it could restored.
03:13:11 Supply extended to Wagoora through 220 kV Kishenpur-Pampore-
Wagoora line
03:21:38 400 kV Wagoora-Uri-II normalised.
03:29:17 Uri unit # 3 synchronised.
8.5 Supply interruption to Railways and its restoration:
The tripping in Punjab, Haryana system led to the supply interruptions to Railways
in Delhi-Ambala, Ambala-Kalaka, Ambala-Saharanpur, Ambala-Amritsar and
Sirhind-Una sections. Apart from above there were interruptions in Delhi-Howrah
and Saharanpur-Moradabad sections in the morning hours as well but the same
was not related with the 0301 hours grid disturbance.
The supply interruptions as given by Northern Railways authorities are given below
with Remarks on restoration of power supply to the affected sub-stations.
Supply
interruption
time (as
given by
Railways)
Railways
section
Feeding
Sub-220
or 132
Grid Sub-
station
Sub-
station
under
control
Area
Traction
sub-Sub-
station
From To
Remarks
Delhi-
Howrah
220 kV
Dadri (G)
Dadri (G),
NTPC
Dhankore 0020 1320 220 kV Dadri-
Dhankore D/C
owned by
Railways tripped.
Supply to this
section was
extended from 220
kV Auraiya.
![Page 77: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/77.jpg)
- 63 -
Delhi-
Ambala
220 kV
Narela
Delhi Narela 0138
2145
0729
2245
Supply extended
to Narela from
Mandola at 0702
hrs
Delhi-
Ambala
220 kV
Panipat
(Th)
Haryana Diwana 0207
2155
1023
2255
Supply extended
to Diwana on 132
Diwana-e feeder at
0713 hrs
Ambala-
Kalka
220 kV
Dera-
bassi
Punjab Ghaggar 0108
1017
220 kV
Rajpura
Punjab Rajpura 0108 0638
Supply interruption
due to tripping of
lower voltage lines
under foggy
conditions prior to
disturbance and
supply to 400/220
kV Patiala was
extended at 0607
hrs
220 kV
Sahnewal
Punjab Sahnewal 0103
2153
0912
0015
220 kV
Jamsher
Punjab Chiheru 0300
2153
0950
0015
Ambala-
Amritsar
220 kV
Butari
Punjab Butari 0300
2153
1036
0015
Sirhind-Una
section
132 kV
Kuri
Punjab Kurali 0300 0800
132 kV
Anandpur
Sahib
Punjab Anandpur
Sahib
0253 1130
Supply to Punjab
area was extended
at Patiala,
Ludhiana,
Jallandhar at 0617,
0637 and 0506 hrs
respectively,
however, due to
massive tripping/
non holding of
lines in foggy
conditions in 220
kV network,
delayed the supply
extension.
Moradabad-
Sahranpur
section
220 kV
Roorkee
Uttrakhand Roorkee 0310 0358 Local temporary
problem
![Page 78: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/78.jpg)
- 64 -
Ambala-
Sahranpur
section
400/220
kV
Abdullapur
ISTS, NR Jagadhari 0300 0545 Supply was
extended to
Abdullapur
substation by 0510
hrs.
![Page 79: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/79.jpg)
- 65 -
CHAPTER 9 Corrective measures to over come the crisis during foggy winter period 9.1 Tripping Of Lines During Fog
Line tripping during dense winter fog conditions was hitherto a common feature in
Northern region. The winter of 2002-03, 2005-06, 2006-07, 2007-08 had witnessed
several tripping on the EHV transmission system in Northern Region. Historically,
these tripping occurred mainly between mid-December to mid-February every year.
However, during the winter of 2007-08, the Northern Region witnessed tripping on the
EHV transmission system on two consecutive days viz. 7th, 8th and 9th March 2008
which led to a large section of consumers getting affected. The total numbers of
tripping of 400kV and 220kV lines were 201 [including 82 Auto Reclosures (A/R)] on
27th January, 2007 and 351(including 60 AR) on 7th March, 2008 respectively.
During 2nd Jan., 2010 disturbance, 211 tripping (including 11 A/R) were observed on
220 kV lines and 59 tripping (including 27 A/R) in 400kV lines.
The comparative summary is given below:
Disturbance
date
Tripping on
400 kV and
above
A/R 400
kV
Tripping on
220 kV
A/R 220
kV
total
27th Jan 2007 45 82 74 0 201
7th March 2008 88 60 203 0 351
9th March 2008 76 95 101 1 273
2nd Jan 2010 32 27 200 11 270
9.2 Auto Re-closure During Foggy Weather
Even if the transmission lines which trip are restored, they either trip later or
autoreclose several times during the night. While the fault currents are not very large
during most of these faults, repeated circuit breaker operations leads to stress on the
equipments. In case of the Rihand Dadri HVDC bipole, there is a facility of operating
at reduced voltages, say +/- 400 kV instead of +/- 500 kV whenever such auto
restarts are frequent. This helps in keeping the transmission system up, albeit at
reduced power transfer capacity.
![Page 80: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/80.jpg)
- 66 -
In case of 220 kV and 400 kV AC system, at times there are requests from the
substation operating personnel to keep the single pole Auto-reclosure facility out of
service when such flashovers are frequent. This becomes a difficult proposition when
the network itself gets depleted and it is this Auto-reclosure facility which helps in
averting a separation and possible collapse of systems.
Fault on the electrical network is a common phenomenon which can lead to system
instability, if not cleared immediately. High speed protective systems are installed on
the transmission network to ensure that faults are cleared in lesser than 100
milliseconds. However, during foggy season, large scale cross country faults
occurring in the transmission system, there is possibility that primary protection may
mis-operates. This leads to the back-up protective systems coming into play.
Obviously the back up protective systems take a longer time to clear the fault,
typically beyond 250 milliseconds and lead to more than the single faulted element
going out. This leads to the power system going quickly from a normal state to a state
of emergency and immediate efforts are necessary to bring back the system to
normalcy.
9.3 Crisis Management Group of NR
A Crisis Management Group (CMG) was constituted at the level of Member (Grid
Operation and Distribution), CEA to monitor the long-term measures required to
minimize such large scale tripping of the EHV transmission system. The following
measures were decided:
Replacing the porcelain insulators in heavily polluted or vulnerable areas with
either polymer or antifog insulators having a higher creepage distance.
Hotline washing of insulators either through helicopters or otherwise.
Intensive manual cleaning of insulators prior to the onset of winter
9.4 Actions taken before the onset of winter during 2009-10:
Since the winter period happens to be a critical time for the NR Grid, particularly in view
of the tripping of the lines due to flashover / failure of insulators under foggy weather
conditions, a number of actions were taken before the onset of winter of 2009-10, with
specific details as follows:
9.4.1 Replacement of Insulators
Under the long term measure in order to avert the large scale tripping of the EHV lines
during winter period, it was decided to replace the porcelain insulators in case of a
number of lines by polymer /antifog insulators. This progress is continuously being
![Page 81: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/81.jpg)
- 67 -
monitored by RPC forum in different meetings and Crisis Management Group
constituted under the Chairmanship of Member (GO&D), CEA is continuously being
apprised of the progress in the matter. The latest details as appearing in the minutes of
the special meeting held on 16.12.2009 at NRPC to review the progress of replacement
of the porcelain insulators by polymer/antifog insulators are given at Annexure-9/I.
9.4.2 Cleaning of Insulators
Since replacement of all the requisite porcelain insulators on the identified lines in
heavily polluted stretches by polymer insulators is a long drawn process, it was decided
that as intermediate measures in respect of some of the sections, cleaning of insulators
shall also be undertaken. While envisaging the cleaning of insulators, during the last
winter some of the critical sections of the important lines owned by POWERGRID were
cleaned using hotline washing through helicopter. This year also certain sections
under Kanpur and Mainpuri jurisdiction were identified for cleaning using the helicopter
and the details are given at Annexure-9/II.
9.4.3 Shutdown of lines permitted by NRLDC in order to facilitate insulators
replacement / cleaning
NRLDC co-ordinated a number of line outages between June to mid-December 2009
for the above activities in connection with ensuring reliability of the transmission system
during winters. The list of line shutdowns approved by NRLDC and availed by the
constituents from 1st September 2009 to 31st December 2009 is enclosed at Annexure-
9/III.
9.4.4 Mock Black Start Trial
The mock black start exercise was also conducted as per the following schedule to
ensure preparedness of all agencies in case of an emergency or partial blackout in any
part of the grid. Table 12: Mock Black start exercise dates
400 kV AC bypass at Vindhyachal
HVDC Back to Back station
15th October, 2009
Nathpa Jhakri HEP 21st October, 2009
Dadri GPS 24th October, 2009
Salal HEP 29th October, 2009
Tehri HEP 9th October, 2009
Bhakra HEP 1st December,
2009
![Page 82: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/82.jpg)
- 68 -
The above exercise was proved to be of extreme importance during system restoration
in respect of both the above incidences.
9.4.5 Real time Monitoring of Humidity and Temperature of different locations and
the weather forecast from different agencies:
After the tripping experienced in the winter of Dec 2007, it was observed that there
was a strong co-relation between fog related tripping and the ambient
temperature/Relative Humidity. A large number of weather transducers were
installed by POWERGRID at a number of sub-stations in the region so that real time
monitoring of the weather parameters could be possible.
Further, in order to anticipate the intensity of fog and weather conditions, NRLDC
had also arranged to get hourly weather forecast data (updated thrice a day) from
M/s SKYMET for different locations viz. Delhi, Panki and Hisar. The agency has
also been providing the weather data for the current day as well as for the next day
at 15 minutes interval and the same is being used extensively in planning the grid
operational measures.
The six hourly fog forecast report issued by the Indian Meteorological Department
(IMD) at 0530, 1130, 1730 and 2330 hours every day for the Indira Gandhi
International Airport (IGIA), New Delhi is also being closely monitored daily. A link to
this forecast is also provided on NRLDC’s website. A high alert is sounded on days
when the visibility is expected to go below 50 metres.
9.4.6 Deployment of additional manpower during the night shifts
In order to tackle the contingency situation additional manpower is being deployed
in the NRLDC Control Room. This deployment is from the officers working in
different departments of NLDC/ NRLDC. The prime objective is to ensure that the
communication facilities, real time data servers, off-line computer systems are
available round the clock and in case of any multiple contingency in the grid, the
monitoring and follow-up with different agencies does not suffer adversely.
9.5 Other measures for enhancing the reliability of the grid
In order to enhance the reliability of the grid the following measures are also being
taken up consistently in the different fora of NRPC.
9.5.1 Monitoring of Under Frequency Relay Load Shedding (UFRLS), Under Voltage
Load Shedding (UVLS)
Provision of under frequency and under voltage load shedding is a part of defense
mechanism. Continuous emphasis is being laid by NRLDC in the RPC forum for
ensuring that defense mechanism in the form of Under Frequency Relay Load
![Page 83: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/83.jpg)
- 69 -
Shedding (UFRLS), Under Voltage Load Shedding (UVLS) and System Protection
Schemes (SPS) and their smooth functioning. The issue of providing of requisite
relief during emergency by way of operation of under frequency and df/dt relays was
emphasized in the last Technical Co-ordination sub-Committee (TCC)/ Northern
Regional Power Committee (NRPC) meeting held on 23rd and 24th December, 2009
and the extracts of minutes are enclosed at Annexure-9/IV.
9.5.2 Protection Audit for upgradation of Protection System in Northern Grid.
The issues in regard to deficiencies in the Protection System are regularly being
flagged in the Protection sub-Committee Meeting of NRPC and in order to upgrade
protection in Northern Grid the subject of Protection Audit in whole of the region was
also deliberated. Extracts from the minutes of the last TCC / NRPC meetings in this
regard are enclosed at Annexure-9/V.
9.5.3 Availability of real time data from different generating stations and sub
stations
The issue in regard to non-availability of real time data from some of the
Generating stations and grid sub-stations is also being highlighted at different
fora. The extracts in this regard from the minutes of 24th Unified Scheme Monitoring
Group (USMG) meeting of NRPC held on 24th August 2009 are enclosed at
Annexure-9/VI.
![Page 84: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/84.jpg)
- 70 -
CHAPTER 10 Review of implementation of recommendation of enquiry committee
on grid incident of 27th January, 2007 and 7th/9th March, 2008.
10.1 In order to expedite the implementation of recommendations of enquiry committee for grid disturbance on 27.1.07, a meeting was taken by Secretary (P), MoP on 9th March 08 and Chairperson CEA on 30th April 08 with the States of Northern Region for replacement of porcelain insulators with polymer/antifog insulators having higher creepage distance on transmission lines in the pollution affected areas.
POWERGRID, DTL, BBMB, UP, HVPN, have identified the line sections where insulators have to be replaced and taking action on the same. The progress is being monitored by NRPC on regular basis. The minutes of the above meetings are placed at Annexure –10/I & 10/II.
10.2 The transmission lines were identified by POWERGRID for replacement of insulators with polymer insulators in Phase-I, II & III. Other constituents have also identified lines for replacement of porcelain insulators by polymer/antifog types. The latest status of replacement were circulated along with the minutes of the meeting taken by MS, NRPC on 5th Feb 2010 are given in Annexure–10/III.
10.3 The committee feels that there was need to comply fully with implementation of the
recommendations of the committee specially the replacement of porcelain insulators by Polymer/ anti fog insulators by constituents.
10.4 The STUs and CTU was to carry out chemical analysis of deposit of insulator
strings at different locations of 400 kV and 220 kV transmission lines where strings were posing frequent problems due to pollution flash over. Based upon the investigation, the power utilities were to identify the stretches of the line and also classify pollution level along the length of the transmission line.
POWERGRID submitted that the pollution severity measurements were carried out on insulator strings at different location of 400kV transmission lines where strings were posing problems due to pollution flashover. The report of testing done by CPRI is placed at Annexure – 10/IV. Further, POWERGRID reported in their letter dated 1st May, 2009 that pollution test and chemical analysis including presence of hydro carbons of pollutants accumulated on insulators were also carried out from Central Power Research Institute, Banglore, Shri Ram Institute for Industrial Research, New Delhi, Indian Institute of Toxicology Research, Luckhnow. Insulators sample were obtained from POWERGRID system and also from UPPTCL for conducting the requisite test. The results of these tests are highlighted in the enclosed Annexure – 10/V.
![Page 85: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/85.jpg)
- 71 -
Report shows the results of the brush wash method at different locations (Refer Tables 1 of the Report. In general, the results show that the bottom surface ESDD of the string has higher accumulation of pollution compared to top surface. The measurement was done in Meerut-Mainpuri-Dadri-Mandola-Panipat—Ballabgarh stretches at 14 locations and found that pollution level is in light and medium zone. CPRI’s chemical analysis states that pollutant contains predominantly ferrous contents.
Contaminations of alkalis were also present predominantly. The average ESDD of the string is compared with the pollution levels, which are specified in IEC 815.
10.5 A brief status on the implementation of recommendations of the enquiry committees
on Grid Disturbances in NCR is given at Annexure-10/VI 10.6 Some of the recommendations where the action requires are listed in the Para 11.1 of the recommendations of this committee.
![Page 86: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/86.jpg)
- 72 -
CHAPTER 11 Recommendations
The recommendations of Northern Regional Committee (NRPC) Enquiry Committee constituted by CEA on grid incident in Northern Region in January 2010 are given as under. The incident of multiple lines tripping in the early morning of 2nd Jan 2010 was similar to
past several incidents during winter foggy nights such as that of 27th Jan 2007, 7th & 9th
March 2008. NRPC Enquiry Committee constituted by CEA had thoroughly analyzed
those major incidents of 27th Jan 2007, 7th & 9th March 2008 and given their
recommendations. These recommendations were found to be very effective in averting
similar incident.
This committee also finds that the recommendations of the previous committee reports are comprehensive and re- emphasizes their implementation in totality.
1. Implementation of Recommendations of Inquiry Committee on Grid Incident of 27th January, 2007 and 7th & 9th March 2008.
The recommendations of the earlier inquiry committee which need to be complied immediately are:-
Classification of pollution levels of lines / line stretches by measurement of
ESDD on insulator. (Action: CTU, STUs)
Notifications by the respective State Government that no brick kiln or any
industrial unit or biomass or diesel based power plant having chimney height up
to 30 meters be set up within 0.5 km of the 220 kV or higher voltage
transmission lines. (Action: State Utilities, State Govts.)
Review of pollution standard in respect of smoke emission from Chimneys of
brick kiln or any industrial unit or biomass power with height upto 30 meters so
as to reduce level of emission of suspended particulate matter.
(Action: State Utilities, State Govts.)
Pollution control of diesel vehicle entering NCR area. (Action: State Govts.)
![Page 87: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/87.jpg)
- 73 -
Pollution Mapping of the Country (Action: POWERGRID)
Railway supply reliability To meet any such eventuality where essential services like Railways get
affected alternative supply points should be made available to Railway. Railway
has suggested having 132 kV supply points at Mehrawal (near Aligarh) and
Shikohabad. The supply points are being taken as an alternative measure in
case of NTPC supply failure from Dadri/ Auriaya. Railway may also prepare
plan identifying additional supply points required by them from state
transmission and distribution utilities in Northern Region. The tariff and O&M
related issues could be sorted out separately. Also, action plan for ensuring
reliable power supply to Railways may be implemented.
(a) Seasonal cleaning of insulators before onset of foggy weather i.e. in the
month of Oct.-Nov. every year to be ensured and report sent to NRPC
periodically.
(b) Replacement of insulators of 132kV/ 220 kV lines by polymer/ antifog
insulators in the areas where insulator failure during foggy weather hass
taken place.
(Action: Railways, STUs/DISCOMS)
Developing a fog forecasting model for power system in NR-
NRLDC reported that Weather Data from many 400 kV stations are available in
the SCADA, Based on these data and IMD forecast, NRLDC had been
regularly putting the fog warnings on its website during winter season. Further ,
during peak winter period, NRLDC has also arrangements for getting detailed
weather forecast data from identified important stations of NR.
2. Replacement of existing insulators by Polymer/ Antifog Insulators
The decision has already taken for replacement of existing porcelain insulators of
line passing through areas having high pollution levels with polymer/ antifog
insulators by the concerned utilities. The committee observed that the work of
replacement of existing insulators with polymer/ antifog on the identified lines
![Page 88: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/88.jpg)
- 74 -
passing through high pollution area should be completed by the respective power
utilities.
In addition they should also identify additional lines which are getting frequently
affected due to fog in winter season. The work of replacement of porcelain insulators
with polymer/anti-fog insulators should be carried out on the complete stretches of the
lines especially in case of the critical 400kV and 200kV lines and evacuation lines from
the generating station. The replacement of insulators of these lines with preferably
polymer may be completed before reoccurrence of fog in next winter season (by
Nov, 2010). The respective utilities may prepare a time line and accordingly
coordinate the activities of procurement and implementation of replacement of
insulators so as to avoid shutdowns during peak period/season.
(Action: Concerned Utilities)
3. Cleaning of Insulators
The various utilities had been carrying out cleaning of porcelain insulators of lines
by adopting cold cleaning (manually availing shutdowns) and hot line cleaning
methods. POWERGRID had also adopted hot line washing of insulators using
helicopter. The power utility may also carry out hot line cleaning of insulators
located in sub-stations/ Switchyards of Power Plants by using high- pressure jets.
Committee feels that in view of increasing pollution level in recent past, the
periodicity of cleaning of insulators needs to be increased in very heavy pollution
area in winter season so as to avoid tripping of lines due to fog. The respective
utilities may preferably do the cleaning of insulators using hot line technique
particularly in peak winter season so as to avoid the shutdowns of the line.
Additional efforts should be made to get the porcelain insulators cleaned
immediately where the Auto-reclosure/tripping took place and repeat the
maintenance process every fortnightly.
(Action: Concerned Utilities)
4. Improving the Maintenance of System Elements
The power utilities may carry out the regular maintenance of their system elements.
They should also enhance the maintenance activities of system elements of their
![Page 89: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/89.jpg)
- 75 -
respective system including the maintenance of uninterrupted auxiliary power
supply before the onset of winter season.
(Action: Concerned Utilities)
5. Proper Maintenance of System Elements around NAPS
It has been observed that the transmission lines emanating from Muradnagar and
Moradabad sub-stations including the lines in around Narora Atomic Power Station
(NAPS) area trip frequently. It is recommended that all system elements around NAPS
should be maintained properly. The porcelain insulators of these lines emanating from
Muradnagar and Muradabad (which fall under high pollution zone) may also be
replaced with polymer insulators on priority.
(Action: UPTPCL)
6. Monitoring Mechanism
Tripping affects the reliability and security of the system and there is also a
curtailment on STOA by NRLDC. Consumers, DISCOMS and generating
companies suffer substantial loss though availability of the transmission system is
not substantially affected due to these tripping.
The committee feels that SLDCs and NRLDC may closely monitor the criticality of
lines vis-à-vis shutdown availed for cleaning/replacement of insulators of lines.
NRPC may review the issues/ constraints of those utilities who do not adhere to the
implementation of the recommendations of the committee in a time bound manner
and accordingly take up with the respective State Utilities / Organization for
ensuring its timely implementation or otherwise accountability.
(Action: SLDCs/NRLDC/NRPC)
7. Alertness during foggy condition
7.1 The Committee recommends that at critical locations, the data of Relative
Humidity (RH) and temperature should be captured by the CTU or the
concerned STU/ transmission licensee and made available to the SCADA
system. For wider circulation, NRLDC/ SLDCs shall uplink this data on their
respective websites. All constituents should closely monitor these forecasts and
![Page 90: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/90.jpg)
- 76 -
ensure availability of suitable O&M staff in place and senior officers at all
strategic locations in case forecasted RH exceeds 85-90% and temperature
likely to fall below 15-17 degree Celsius to control the situation and mitigating
for related tripping.
(Action: CTU,STUs,NRLDC,SLDCs)
7.2 All the staff manning SLDC/sub-station/generating station should be sensitized
about the situations during foggy conditions. Effective and experienced
personnel should be made available particularly at important stations during
foggy nights. Operators at all sub-stations, generating stations, etc shall follow
the instructions of NRLDC/SLDCs immediately during contingency condition.
(Action: All concerned constituents)
7.3 During the foggy condition or otherwise when the grid is critical, SLDCs may
ensure the loading of major trunk line is controlled with adequate safety margin.
NRLDC may reduce loading of lines in North- west part of NR system during
foggy weather period. The operators at SLDCs may follow the instructions of
NRLDC to reduce the drawal from the grid, maintain the system parameters
particularly the voltages at the grid sub-stations. All the utility must be prepared
to meet even more N-2 contingency under such operating condition of the grid.
(Action: SLDCs, NRLDC)
8. Railway Supply Reliability
Railways may make arrangement for additional supply point(s) for the traction
system at Panipat and other important locations for traction supply. Replace all
porcelain insulators of 132 kV and 220 kV lines with polymer insulators and
enhance the maintenance of their system elements and also cleaning of porcelain
insulators of lines.
(Action: Railways)
9. Protection Coordination
![Page 91: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/91.jpg)
- 77 -
The gravity of the incidence was compounded due to unintended and unexpected
operation of the protection system (Refer para-5.3.3). While at some of the locations
in the grid even the desired protection did not operate (refer Paras 6.3.4 of the
Report). This issues was further aggravated in winter foggy conditions when many
lines frequently auto-closed, tripped, restored after tripping, kept open in winter
nights due to low hydro generation and lesser demand in the grid.
Necessary coordination and checking of protection setting need to be ensured so
that the system operator’s efforts during handling contingencies is not adversely
affected on account of such unintended protective relay operations.
Further directional earth fault relays, wherever not provided, must be provided in the
400 kV system to ensure adequate back up protection in cases where the primary
protection fails to operate and the fault is beyond Zone-3 at the remote end buses.
This might be implemented immediately for the 400 kV Delhi ring main system.
The protection schemes on the 400 kV Ballabgarh-Bamnauli D/C line might be
thoroughly checked along with circuit breaker to ensure that fault are cleared in time
and unintended tripping do not take place.
BBMB may also review the philosophy of keeping tie-breaker in non-auto mode as it
leads to outage of the auto- reclosure facility when the main breaker is taken out of
service.
UPPTCL may check the relay settings of their system for proper operation of
protective system, particularly in & around Muradnagar Sub-station and NAPP
areas.
Committee recommends that each utility should get the protection study and audit
done through third parties. To begin with, the pilot scheme for carrying out such
study/ audit may be taken up as decided in the 15th NRPC meeting held on 24th
December, 2009. One pilot protection scheme could be for the 400 kV Delhi ring
main system including generating plant in and around Delhi and second for Western
UP system in and around Narora Atomic Power System.
(Action: All concerned constituents)
![Page 92: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/92.jpg)
- 78 -
10. Requirement to change the CT ratio to higher range:
Line flow measurements at control centre level were hampered in many cases due
to 1000:1 Current Transformer (CT) ratio adopted in case of 400 KV lines. The
telemetered value in such cases got freezed as soon as the power flow exceeded
a certain range (say 692 MW). Please refer Para 5.3.3 , 6.2.4 and 6.2.6 in this
regard. Hence the CT ratio needs to be changed to higher value, say 2000:1 for all
the 400 kV interconnecting lines where there is a possibility of having the flow
increased beyond 692 MW. Further for the lines having Quad Moose or Bersimis
sections with still higher flow, the CT ratio would need to be changed to still higher
value. The setting as recommended by NRLDC in its communication to the
constituents may be made immediately.
(Action: All constituents)
11. Functioning of RTU and data telemetry facilities:
For satisfactory real time operation of the grid, it is essential that all RTUs and data
telemetry facility should be functioning in the generation stations/grid sub-stations.
This facility should be planned and commissioned along with the commissioning of
new generating station/grid substation.
Remote Terminal Units (RTUs)/ Sub-station Automation System (SAS) provided in
all newly commissioned generating stations and substations, especially at Khedar,
Rosa, DCRTP (Yamunanagar), Chhabra, Barsingar Lignite, Jallipa Kapurdi, Dadri
(NTPC), Kota, Suratgarh etc should be integrated and made operational
immediately. The non-reporting RTUs should be integrated with the system
immediately.
(Action: All utilities)
12. Adequate back-up power supply at wide band communication
node/ repeater stations:
The real time data is being transmitted to regional load dispatch centre from
different SLDCs/Control Centers on wideband communication network which is
having communication node/repeater stations on the route. It has been observed
that whenever there are incidences of grid supply failure some of these
![Page 93: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/93.jpg)
- 79 -
nodes/repeater stations are not able to function properly due to failure of back up
power supply at these locations.
The respective utility should make adequate arrangement for back up power
supply and for its upkeep at all the communication node/repeater stations so as to
ensure the availability of backup power supply in the event of grid disturbances
and no interruption of data during the critical period.
(Action: All utilities)
13. Effectiveness of defense mechanism and adequacy of safety net
The performance of defense mechanism such as Under Frequency Relays (UFRs),
df/dt relays, Under Voltage Relays (UVRs) and System Protection Schemes (SPS)
is being regularly deliberated in the various OCC and NRPC meetings. The State
utility should ensure this defense mechanism should be full- proof, telemetered with
SCADA system and periodically tested to ensure its high quality performance. . The
inquiry committee recommends that settings of existing UFR and df/dt should be
reviewed. The inquiry committee also recommends that defense mechanism
should be further strengthened in NR
(Action:SLDCs, State Utilities,NRLDC, NRPC)
14. Healthiness of DR/EL and time synchronization
All the recording equipment at the generating station and sub-station which are
important for analysis of grid incidents and must be time synchronized using
GPS. The triggering of DR/EL, numerical relays for different analogue and digital
inputs must be tested periodically so as to ensure its functioning at the time of any
major tripping.
Clear labeling of DR/EL and Numerical Relay outputs which indicate the substation
name, feeder, date and time correctly is also important so as to facilitate proper
analysis of events in the system. All the constituents may ensure these features are
made functional / provided in their all 400kV & 220kV Grid sub-stations.
(Action: All Utilities)
![Page 94: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/94.jpg)
- 80 -
15. Planning and Commissioning of additional 400 kV links to take care of fog
related tripping:
The additional links in the affected corridor (central to western part of the grid) such
as 400 kV Meerut-Kaithal D/C have been planned and are being executed. These
links would definitely provide for enhanced transfer capability in the corridor.
However, considering the heavy flow from Rajasthan towards Haryana/Punjab from
220 kV Khetri substation mentioned in Chapter 6. of the report, an additional
corridor from North Rajasthan to Punjab/Haryana such as from Suratgarh to Moga
could be very useful. Similarly Loop-In and Loop-out (LILO) of the 400 kV Dehar-
Bhiwani and Dehar-Panipat lines at Patiala and Panchkula 400 kV substations
respectively would also strengthen the system and provide additional flexibility
during the winter period.
(Action: CTU/STUs)
16. Reactive Power Management:
Steady state low and high voltages have been occurring on seasonal basis in the
Northern region. During the period June to September, inadequate level of shunt
capacitors has already led to a decrease in the transfer capability. The need for
installing adequate shunt capacitors as recommended by the NRPC has already
been emphasized in various meetings/forum. In this incident, antecedent voltages
were satisfactory and were therefore not a direct contributor to the grid
disturbances. Nevertheless, there should be no slippage in the shunt capacitor
installation programmed by all utilities in the Northern region.
Steady state high voltage in the transmission system associated with large remote
hydro power stations in Himachal Pradesh, Uttarakhand and J&K is also a serious
issue when the plants are closed during the winter night off-peak hours. In the 15th
NRPC meeting held in Chandigarh on 24th Dec 2010, the constituents of Northern
region have approved installation of bus reactors at fifteen (15) locations by
POWERGRID. Installation and commissioning of these facilities needs to be
expedited in the interest of system security.
These two grid disturbances have also brought out the need for adequate dynamic
reactive power reserves. In both the instances, there was a sudden requirement of
![Page 95: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/95.jpg)
- 81 -
1500-3000 MVAr in the grid on account of heavy line loading post-contingency and
/or sustained fault. These could only be met partially from the generating stations
which led to a sharp drop in voltages and picking up of some distance relays.
Dynamic reactive power reserves in the form of Static VAR Compensators (SVCs),
Synchronous condenser capability in existing and new Hydro stations therefore
needs to be examined closely in the interest of system security.
(Action: CTU, STUs, GENCOS)
17. Pollution control
The pollution level is increasing every year not only in NCR area but also in the
states of Haryana and Punjab. With a view to control the pollution due to brick kilns,
industrial units, biomass/ diesel based power plans, diesel based vehicle etc., the
Committee recommends that the respective State Governments should strictly
enforce the pollution check and ensure pollution causing establishments are not in
the vicinity of the existing transmission lines. The State Transmission Utilities and
Central Transmission Utilities may also ensure the route of the new proposed line
may not pass through such establishments.
(Action: State Govt., CTU, STUs)
18. Chemical analysis of deposit on Insulators Strings
POWERGRID has done the analysis of deposit on insulators of transmission line. It
is suggested that all the state transmission utilities may also get the similar analysis
regarding deposits on insulators strings in respect of their transmission lines. The
pollution causing factors are on increase and also being reported in other locations
of transmission lines as well. It is therefore suggested that all the STUs and CTU
may get this analysis of deposits on insulators of lines preferably done every year.
(Action: CTU, STUs)
19. Pollution mapping
POWERGRID has taken up with CPRI for getting the pollution mapping done for
the entire country. In the 15th NRPC meeting held on 24th December, 2009 it was
informed that CPRI had submitted the proposal for the approval to MoP. The
committee recommends that the pollution mapping may be completed by
POWERGRID in association with CPRI after getting the requisite approval.
(Action-POWERGRID)
![Page 96: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/96.jpg)
- 82 -
20. Other issues
(a) The time synchronization of disturbance recorders and event loggers should be
checked and wherever required their clock shall be reset.
(b) PLCC equipments for direct tripping need be tested periodically to avert false
tripping. Wherever the protection schemes have not operated from both ends,
cause need to be investigated on each & every occurrence and protection scheme
may be set right.
(c) All the incidences of tripping of lines including auto-reclosure of lines, sub-station,
generating station shall be analyzed by the concerned utility and details of these
tripping and analysis report shall be sent to the NRPC and NRLDC along with
disturbance recorder and event logger print-outs, relay flag indications, UVLSRs,
UFRs & df/dt relays etc.
(Action: Concerned Utilities)
![Page 97: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/97.jpg)
Acknowledgement
The committee gratefully acknowledges the cooperation extended . by the officials of DTL,HVPNL,HPGCL, PSEB (now Punjab Powercom and Transco), RVPNL, UPPTCL, HPSEB, NTPC, NHPC, BBMB, NRLDC, Railways and POWERGRID in the cgllection & submission of information pertaining to Grid incident and its analysis. The committee places on record its appreciation of the assistance provided by the following nodal officers:
i) Sh. Mir Quasim, CE (SO), PDD, J&K ii) Sh. V.K. Gupta, CE, (SO), PSEB iii) Sh. H.R. Satija. CE (SO), HVPNL iv) Sh. B.B. Sharma, GM, (OM), DTL v) Sh. B. Sharma, GM (NR-I), POWERGRID vi) Sh. P.K. Pal, GM (P&O), PowerlinksTransmission Ltd. vii) Sh. S Parameshwaran, CE, (O&M), NHPC viii) Sh. Rajesh Kr. Jain, Director, Ministry of Railway ix) Sh. Suneel Grover, Director, (PR & CERC), HPSEB x) Sh. P.P. Francis, AGM (OS) , NTPC xi) Sh. Sawinder Singh, Senior Executive Engineer, BBMB
The committee also places on record its appreciation of the assistance provided by Sh. P.P. Francis, AGM (OS), NTPC, Shri S R Narasimhan, DGM, NRLDC, Shri Rajesh Kumar, Manager, NRLDC, Shri PS Mhaske, SE, and Shri Vikram Singh, EE, NRPC in helping in the analysis and preparation of the report.
S.no Name of member Desi nation 1 Sh.·Rakesh Bansal SE, HPGCL
2 Sh. Ajay Talegaonkar Director(GM Division) CEA
3 Sfl. R S Lamba . ~
Direetor (PR) -B-BMB
4 . Sh. Jagmohan Sharma GM, POWERGRID (NR-II)
5 Sh. Suneel Grover Director (PR & CERC), HPSEB
6 Sh. V K Gupta Chief Engineer(SO) PSEB
7 Shri R.P. Singh Director (Elec), SJVNL
8 Shri V.K. Agrawal General Manager, NRLDC
9 Shri A.K. Aggarwal Member Secretary, NRPC
10 Shri Anil Kumar Gupta Executive Director, PTCUL
11 Shri Y.K. Raizada Director (Tech), RRVPNL
12 Shri S.M. Dhiman Member (GO&D), CEA and Chairman of In ui Committee
![Page 98: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/98.jpg)
Annexure-I Northern Regional Power Committee
18-A Shaheed Jeet Singh Marg, Qutab Institutional Area, New Delhi-110016
No. SE(O)/CMG/2010 Dated 02-01-2010 Summary record of discussions of the meeting of Crisis Management Group (CMG) was held on 02-01-2010 at 11:00 hrs in NRLDC, New Delhi.
1. Meeting of the Crisis Management Group was held at NRLDC. Member (GO&D) CEA, Director (Operations) POWERGRID, Member Secretary (NRPC), Executive Director (NLDC) POWERGRID and General Manager (NRLDC) participated in the meeting.
2. The members reviewed the situation in the grid arisen from the simultaneous tripping of multiple transmission
elements in the system following heavy fog and inclement weather in the Northern Region on the night/early morning hou rs o f 01/02 Januar y, 20 10. H umidity was al most 100% a nd te mperature less tha n 10 degree Celsius.
3. As a r esult most o f th e generating s tations in t he no rth western part o f N orthern Re gion including ther mal
generating stations at Ropar, Bhatinda, Lehra Mohabbat, Panipat and Yamuna Nagar tripped. Approximately 6000 MW load was affected in Western part of Northern Region. Railway supply from Dadri, Panipat, Narela and Punjab system got affected due to outage of 220/132 kV lines.
4. Western UP system particularly Muradnagar got affected. 400/220 kV Bamnauli substation in Delhi also got affected for some time.
5. The flash report issued by NRLDC is enclosed.
6. Power supply to Railways which was affected due to their own network in western UP was normalised at 7:20 hrs. All traction has been restored. Many of the Hydro stations like Uri, Salal, Jhakri and Bhakra successfully black started and gradually synchronised with the Grid. All the power stations have got the start up supply. All the 400 kV S/S charged. Su pply was restored in most of the affected areas. Load being met in NR is 20,000 MW at 11:00 hrs. Power supply is in the process of normalization with the picking up of thermal generation.
7. Railways is advised to restore its earlier interconnection with UP system as a back up as already decided earlier so that in the event of emergency it can be switched over. This is particularly important for Dadri feeder (as it is prone to inter ruptions under foggy weather). Further, UPPCL is also requested to extend all assistance for expeditious restoration arrangement for back up supply.
8. In view of the fog forecasted for the next few days in the Northern Region, all load dispatch centres are advised to be on high alert.
9. All con trol centres and EHV s ub-stations are adv ised to strengt hen the manpower, especi ally during n ight
hours.
10. The next meeting along with other members of the group would be held on 04-01-2010 at 16:00 hrs in NRPC, Delhi.
Encl: a/a
(A K Aggarwal) Member Secretary
To: 1. All members of CMG 2. All SLDCs of NR and Member (Electrical) Railway Board 3. CMDs of Transmission Utilities of NR
Copy for information to: 1. JS (OM), MoP, New Delhi 2. PPS to Chairperson, CEA 3. PPS to Chairman, NRPC
![Page 99: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/99.jpg)
POWER GRID CORPORATION OF INDIA LIMITED NORTHERN REGION LOAD DESPATCH CENTRE, NEW DELHI
Flash Report dated …02.01.2010 , 0500 hrs
• Due to heavy fog power System of J&K, Punjab, Himachal and Haryana (except South Haryana) has suffered heavily due to simultaneous outage of multiple transmission elements connecting this system with the rest of Northern Grid.
• Humidity is 100 % and temperature is less than 10 degree centigrade. Fog further developing. • Following main transmission lines connecting Punjab/Haryana/J&K system with rest of grid are out.
o 400 kV Mandola-Bareli D/C HVDC Rihand Dari-Pole-1 o 400 kV Dadri-Malerkotla 400 kV Panipat-Dehar-Bhiwani o 400 kV Bawana-Abdullapur D/C 400 kV Bawana-Bamnauli D/C o 400 kV Ballabgarh-Bamnauli-I 400 kV Bhiwadi-Hisar o 400 kV Abdullapur-Jhakri-I 400 kV Hisar-Patiala o 400 kV Hisar-Kaithal 400 kV Hisar-Khedar-Moga-Kishenpur o 400 kV Moga-Jallundhar-Chamera-I 400 kV Moga-Kishenpur-Chamera-II o 400 kV Kishenpur-Wagoora-Uri- D/C 400 kV Kishenpur-Dulhasti o 220 kV Ballabgarh-Charkhi 220 kV Samaypur-Charkhi-Dadri o 220 kV Nalera-Panipat T/C 220 kV Panipat-Dhulkote o 220 kV Khetri-Hisar 220 kV Sangrur-Ludhiana D/C o 220 kV Dhulkote-Ganguwal
As a result thermal generating Stations at Ropar, Bhatinda, Lehra Mohabbat, Panipat, Yamunanagar are out. Aproximately 6000 MW load is affected in Western part of Northern Region is affected. Railway supply from Dari, Panipat, Narela and Punjab system has been affected due to outage of 220 kV / 132 kV lines. NRLDC control room is in touch with Railway officials. Rest of N_E_W grid along with U.P. Rajasthan, Delhi, Uttarakhand is in integrated operation. Hydro stations at Chamera, Jhakri, Salal and BBMB have blackstarted. Restoration is in progress. All power stations, Load Despatch Centres, substations are in alert mode.
D.G.M (Grid Management) NRLDC
Distribution: as per list 1. SLDC-PSEB/HVPNL/HPSEB/RRVPNL/UPPCL/DTL/PTCUL/PDD J&K/UT Chandigarh 2. NPSD/WRLDC/NERLDC/SRLDC/ERLDC 3. NTPC-NR Lucknow, NTPC-NCR Noida, NHPC Faridabad, THDC Tehri, SJVNLJhakri, BBMB Chandigarh,
NAPS, RAPS-A, RAPS-B 4. ED(NR-I)/ED(NR-II)/ED(SO),POWERGRID 5. Director (Operation), POWERGRID 6. Member Secretary NRPC/Member (GO) CEA/Director (OM) Ministry of power
![Page 100: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/100.jpg)
I'OWER GRID CORPO RATION OF INDI,\ LIMITED NORTHERN REGION WAD DESPATCH CENTRE, NEW DELHI
.lash Rtport dated ... 03.01.2010, 0600 HI'S
Ue~vy spark was reported in [he ~OO tV SawIIIlll Sub·station at 21.45 hrs and all lines emanating from Sawana tripp:<!. Th is followed in Ihe cascade tripping of [he 0I1ler lints listed brlow.
• Apan from above mentiorn..'d 400 kV linei, number of no kV lines also [ripped.
, .'
• As II resu lt of tri pping of above llIent ioned lines. power supply in I'unjab/lhryanafJ&KIHPIDTL ~em ,,"'ere aff(('!ro. Rest of the NR grid comprising V.P. Rajasthan. Delhi. Uunrakhand rem ~i ned unaffected in intcgrmed opcrntion wilh ncw grid.
Incident has resu lted inro loss of genernuon along wnh los~ of 100II as laoolnlciJ lxlvw.
![Page 101: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/101.jpg)
l Oll 01 Ot~OI G&ne<IUon l oad ... UW MW
Central SectOf 900 Pl.l1 eb "00 "00 He ani '" '"'" "' '" "" '" '" "'" """ '", ''''' :111 .. orlRag1Otla1
""" """ ''''' • Supply 10 affccted mi l ..... By H'OCt ion frvrn Panipal. Narela and Punjab ..... en: reslored 00
hig~t priority within an hour
• Hydro stat ions at Uri and Sala l have blad·Slarted and operated in islanded mode. Now operating in inte&:mtro mode wit h rest of Ihe grid.
• At tile time of writing tiloe report NR wa~ n>e<:tin &: 22fXlO MW and major thermal generation:; ha>'e been re~l\'I~d exCtpt 600 MW in Punjab and 200 MW in Haryana.
D.G,M (Grid Management)
NRLDC
Distribution: ~ ver list I . SLDC· PSEBII I VPNUllPSEBfRR VPNUUPPClJDTlJI>TCULIPOD J& KfUT ChandigartJ 2. NPS DlWRLDCfNERU)CfSRLDCIERLOC 3. Nll'C· NR Lucknow. NTf'(:. NCR Noida, NHPC Faridabad. TIIDC Tehri. SJVNUhakri,
BBMB Chandigartl, NAI'S, RA ps·A. RAPS· B 4. ED(NR· IlIED(NR· II)lED(SO).POWERGRI D 5. Director (o,:.,r:ltion). POWERGRID 6. Member Sccrelary NRPC/Membcr (GO) CEAlDin:<.:IOT (OM) Ministry of JlO"'cr
![Page 102: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/102.jpg)
Annexure-I/II
Tel.- 26967840,42,26967990,26868681 Fax 26865206, 26567341
E mail [email protected]
Government of India Northern Regional Power Committee
(An ISO 9001:2000 Certified Organisation) 18-A, Shaheed Jeet Singh Marg, Katwaria Sarai, New Delhi-110016
No. NRPC/SE (O)/CMG/2010 Dated: 07-01-2010
To
(As per list enclosed)
Sub: Meeting of Crisis Management Group (CMG) of Northern Region held on 04-01-2010 at
NRPC, New Delhi. The minutes of the meeting is enclosed for information and necessary action. It is requested that the decisions taken by CMG may be implemented u nder intimation to th is o ffice. Min utes of the meeting are also available on website of NRPC (http://nrpc.gov.in). (AK Rajput) Superintending Engineer (O) Copy to: Members of Crisis management Group
1. Sh. S.M Dhiman, Member (GO&D), CEA -Chairman 2. Sh. R N Nayak, Director (O) POWERGRID -Member 3. Sh. R G Yadav, ED (Engg), POWERGRID -Member 4. Sh. S K Soonee, ED (SO), POWERGRID -Member 5. Sh. V K Aggarwal, GM, NRLDC -Member 6. Sh. A K Kaul, Director (O), DTL -Member 7. Sh. Niraj Gulati, Director (Tech), HVPNL -Member 8. Sh. Ashok Kumar, ED (TR), UPPTCL -Member 9. Sh. A K Aggarwal, Member Secretary, NRPC -Member Convener
Special invitee 1. Sh. A K Saxena, Director (O&M) MoP 2. Member (Power), BBMB 3. Member (Transmission), PSEB, Patiala 4. Member (Electrical) Railway Board , 011- 23385100, 23304661,23385086 / Director (Electrical),
Railway Board, New Delhi, 011- 23387045, 5. Executive D irector & CEO, Po werlinks Tran smission Lim ited, New Del hi, Fax-011 -
66306377/66306375 6. CED, North Central Railway, Allahabad, 0532-2223211, 2230204,
Copy for information to: 1. JS (OM), MoP, New Delhi/ 2. PPS to Chairperson, CEA 3. PPS to Chairman, NRPC 0191-2545447, 2546206
![Page 103: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/103.jpg)
List of addresses: 1. Sh. B.R.Sharma, IAS, Chairman,NRPC and Principal Secretary Govt. of J&K , Civil Secretariat,
Shrinagar (J&K) , (Fax 0194- 2452352) 2. Sh. Subhash Chandra Negi, IAS, Chairman, HPSEB, Vidyut Bhawan, Shimla-171004, (Fax 0177-
2658984) 3. Chief Engineer, UT of Chandigarh, Chandigarh-160066, (Fax 0172-2637880) 4. Sh. Rajendra Kumar, IAS, Chairman & Managing Director, DTL, N.Delhi-110002, (Fax No.-23234640) 5. Sh. R. K. Gaur, Managing Director, IPGCL, Rajghat, N. Delhi-110002, (Fax -23275039) 6. Sh. B.C. Mathur, General Manager (SLDC), DTL, New Delhi-110002, (Fax -23221069) 7. Sh. Arup Ghosh, COO, NDPL, New Delhi-110009 (Fax- 27468023) 8. Mrs. Jyoti Arora, IAS, Managing Director, HVPNL, Panchkula-134109, (Fax 0172-2560640) 9. Chief Engineer (SO&C), SLDC, HVPNL, Sewah, Panipat , (Fax -0172-2560622) 10. Sh. Sanjeev Kaushal, IAS, MD, HPGCL, Panchkula-134109, (Fax 0172-2560136, 2565042) 11. Sh. Anurag Agarwal, IAS, Managing Director, DHBVN, Hisar, (Fax. 01662-223153) 12. Sh. H. S. Brar, Chairman, PSEB, Patiala-147001, (Fax- 0175-2213199) 13. CMD, RRVPNL, Jaipur-302005, (Fax -0141-2740168) 14. Chief Engineer (LD), SLDC, Heerapura, Jaipur-302024, (Fax -0141-2740920) 15. Dr.S.K.Calla, CMD, RRVUNL, Jaipur-302005, (Fax -0141-2740633) 16. Sh. K.C.Gupta, Director (Tech.), Jaipur VVNL, Jaipur0302005, (Fax. 0141-27448836) 17. Sh. T. Panda, Managing Director, PTCUL, Dehradun-248001, (Fax- 0135-2762460) 18. Sh. T. Panda, Managing Director, SLDC, PTCUL , Rishikesh, (Fax -0135-2451160) 19. Sh. R. P. Thapliyal, Managing Director, UJVNL, Dehradun-248001, (Fax- 0135-2761549) 20. Sh. J.M.Lal, Managing Director, UPCL, Dehradun-248001, (Fax -0135-2768867) 21. Sh. Navneet Sehgal , IAS, CMD, UPPCL, Lucknow-226001, (Fax- 0522-2288410) 22. Sh. A K singh, Chief Engineer (Transmission), UPPCL, Lucknow-226001, (Fax- 0522-2287880) 23. Sh. Alok Tandan, Managing Director, UPRVUNL, Lucknow-226001, (Fax -0522-2288410) 24. Managing Director, Madhyanchal Vidyut Vitaran Nigam Ltd, Lucknow-226001, (Fax -0522-2208737) 25. Chairman, BBMB, Chandigarh-160019, (Fax- 0172-2549857/2652820) 26. Sh. D.P. Bhargava, Director (Technical), NHPC, Faridabad-121003,m (Fax -0129-227413) 27. Sh. I. J. Kapoor, Director (Commercial), NTPC, New Delhi-110003, (Fax -24368417) 28. Executive Director (Operation), NPCIL, Mumbai-400094, (Fax 022-25563350) 29. Sh. R. P. Singh, Director (Electrical), SJVNL, Shimala-171009, (Fax- 0177-2673283) 30. Sh. S. K. Shukla, Director (Technical), THDC, Rishikesh-249201, (Fax -0135-2431520) 31. Sh. Kanti Prasad, Jt. President, J. P. Hydro Power Ltd, Kinnaur-172104, (Fax 0178-6232354) 32. Sh. Satish Jindal, Director & Sr. V.President, JSWPTC, New Delhi, -66, (Fax 41619674)
![Page 104: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/104.jpg)
Summary Record of 4th Meeting of Crisis Management Group held at NRP C, New Delhi on 4th Jan, 2010 List of participants is enclosed at Annexure-I
1. Member (GO&D), CEA and Ch airman of Crisis Management Group (CMG) welcomed the participants and stated that this meeting had been called to formulate strategy to mitigate the tripping o f system elements in Northern Regi on dur ing foggy winter. He st ated that simultaneous tripping of m ultiple tran smission elements occurred on 2nd Ja nuary, 2010 a t 0301 Hrs and again at 2157 Hrs resulting in interruption of around 6000-7500 MW load in J&K, P unjab, Ha ryana, Ch andigarh, H imachal Prad esh, Delhi a nd We stern U. P. He requested NRLDC to make a brief presentation of these two incidences.
2. The representative of NRLDC stated that during the incident which occurred at 0301 Hrs on
2nd Ja nuary 2010 a nd again a t 2157 Hrs of 2nd Ja nuary, 2 010 s imultaneous tripping of multiple transmission elements to ok p lace. Th is resulted in lo ss of lo ad of around 60 00-7500 MW in Ja mmu & Ka shmir, Pun jab, Haryan a, Chandigarh, Hima chal Prad esh, Delhi and W estern Ut tar Pr adesh. He stated that m ost of the generating stations i n the North-Western part of Northern Region including thermal generating stations at Ropar, Bhatinda, Lehra Mohabbat, Panipat and Yamuna Nagar tripped. The railway supply f rom Dadri and Panipat got affected due to outage of their 220 kV and 132 kV feeding lines of Railways. A copy of the flash report issued by NRLDC on 02-01-2010 & 3-01-2010 and summary record of the discussions of the meeting of CMG held on 2nd January, 2010 is enclosed at Annexure II&III respectively.
3. Representative of NRLDC stated that the following important 400 kV lines supplying power
to Haryana, Punjab and other areas of Northern part of NR had tripped in a s hort span of about 3-5 minutes at 0256 Hrs on 2nd Jan, 2010
• Moga-Khedar (POWERGRID) • Abdullapur-Bawana (POWERGRID) • Moga-Fathehabad (POWERGRID) • Hisar-Kaithal (POWE RGRID) • Bhiwadi-Hisar ( POWERGRID) • Hisar-Patiala (POWE RGRID) • Bamnauli-Bawana I &II (DTL) • Ballabgarh-Bamnauli I &II (DTL)
![Page 105: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/105.jpg)
Because of th e tri pping of the above li nes the lo ading o n 400 kV D adri-Malerkotla line increased (both in MW as well as MVAR terms). T he MVAR flow on this l ine increased excessively and voltage dropped drastically. This 400 kV li nk connecting Punjab, BBMB, HP, and J & K system too tripped at 0301 Hrs and the supply was affected.
NRLDC further informed that on 2nd January, 2010 at 2154 hours, heavy spark was reported in 400 kV Bawana s ub-station of DTL and all lin es em anating f rom the re tri pped. As a result of tripping of the lines power supply in Punjab, Haryana, J&K, Himachal Pradesh and Delhi system was affected. Approximately 7500 MW load was affected in these States.
4. Director (O), DTL stated that there was a spark at Bawana sub-station and 400 kV Bawana- Bahadurgarh, Bawana-Hisar and Bawana-Abdullapur lines tripped. Other lines at Bawana sub-station were hand tripped. 5. ED (SO), NLDC a ppreciated t he b lack s tart of hydro generators particularly NJHPS,
Chamera HPS, Sa lal HPS a nd stated that hydro stations had helped in quick restoration of the system. However, there was further scope of improvement in providing reactive support as per the capability curve of hydro units. He emphasized that provision of FGMO may be ensured on the generating units.
He st ated that as per the IEGC , all the utilities h ave to submit the det ails of trippi ng and
related information along with disturbance recorders (DRs) and event loggers (ELs) output to the RLDC. In the absence of these details it is not possible to analyse the exact cause of the failure and behavior of the system during the incident. He stated that under voltage load shedding relays (UVLSRs) should be in place at least on those 400 kV & 220 kV stations which are supplying the radial 220 kV & 132 kV feeders.
He opined that outage impact would have been less severe, particularly in Punjab, Haryana, and in J &K area, had the defense mechanism in the form of under-voltage relays, UFRs & df/dt relays operated optimally.
6. GM, NRLDC enquired regarding the tripping of the lines emanating from Muradnagar sub-
station of UP. The representative of UPPTCL informed that heavy fog was there and the line tripping sta rted a t midnight and continued a s the time pr ogressed. Due to progressive tripping of the lines the system weakened at Muradnagar. UPPTCL was requested to submit detailed report by 8th Jan, 2010.
![Page 106: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/106.jpg)
7. O n a query f rom POWE RGRID r egarding the performance of polymer i nsulators, a representative of POWERGRID confirmed that no flashover had been observed at locations where polymer insulators had been installed in the lines. He further informed that though they had c leaned t he porcelain i nsulators, but th e f lashover ha d occurred a t porcelain insulators of lines. He clarified that the cold cleaning of porcelain insulators had been done on the transmission lines.
8. A representative of Railway Board informed that they had replaced 1248 porcelain insulator
strings with polymer insulator strings on 132 kV section of lines feeding the traction system. In balance portion of the 132 kV lines and all 220 kV lines cleaning of porcelain insulators had been done by them.
He f urther inf ormed t hat flashover had occurred a t f ew l ocations of 220 kV and 132 kV transmission l ines fed fro m Dad ri an d Siarsaul thus affecting the power supply to th e traction system. Railways restored the supply to traction system through alternate source i.e. by ex tending sup ply fro m Pank i and Phaphund. He also in formed that trac tion su pply to Panipat and towards Punjab area was a ffected due to bursting of lightning arrester (LA) of their 25 kV traction system.
9. Representative of HVPNL in formed that one of the strings got punctured on the Daultabad-
Luna Majra 220 kV Line of 13 km stretch on which porcelain insulators had been replaced with anti-fog insulators.
10. Represen tative of PSEB informed that on Jamalpur-Dhandari Kal an l ine, three anti-fog
insulator strings failed. This area falls under high pollution zone.
11. Representative of BBMB informed that they had provided about 3,000 anti-fog insulator strings on th eir lin es an d during th is period o f incidence, two string s have failed out of
which one was located near a dyeing factory in Ludhiana.
12. MS, NRPC emphasized that STUs and CTU should review its pollution zoning and provide polymer insulators on heavy and very heavy pollution stretches as recommended by Enquiry Committee on Grid Incident of 27th Jan, 2007.
13. After the deliberations, the following decisions were taken by the Crisis Management Group for implementation by the respective utilities.
I. All th e incidences o f tripping of lines including a uto-recloser of l ines, sub-station,
generating station shall be analyzed by the concerned utility and details of these tripping and
![Page 107: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/107.jpg)
analysis shall be sent to the NRPC and NRLDC along with disturbance recorder and event logger print-outs, relay flag indications, UVLSRs, UFRs & df/dt relays etc., by 8th January, 2010.
(Action: SLDCs, STUs and CTU) II. All th e staf f manning SLDC/sub-station/generating s tation should be sensitized abo ut
situations during fog gy condi tions. Effect ive an d experienced personn el sh ould b e made available particulary at important stations during foggy nights. Operators at all sub-stations, generating stations, etc shall follow the instructions of NRLDC/SLDCs immediately during contingency condition.
(Action: All concerned constituents) III. Remote Term inal Unit s (RTUs)/S ub-station Automation System (SAS) provided in all
newly c ommissioned generating stations and su bstations, es pecially a t Khedar, R osa, DCRTP (Yamnanagar), Chhabra, Barsingsar Lignite, Jallipa Kapurdi, Dadri (NTPC), Kota, Suratgarh etc should be integrated and made operational immediately. The non-reporting RTUs should be integrated with the system immediately.
(Action: Concerned utility) IV. Action s hould be taken to e nhance the m aintenance a ctivities of system e lements of th e
respective grid in cluding the m aintenance of un interrupted auxi liary power sup ply. Additional efforts should be made to get the porcelain insulators cleaned immediately where the auto-reclosure/tripping took place and repeat the maintenance process every fortnightly.
(Action: CTU & STUs) V. Manual hot line washing of porce lain insulators should be carried out in case of constraints
in getting the shutdowns. (Action: By CTU, STUs)
VI. All the tra nsmission lin es em anating from Muradnagar and M oradabad sub-stations including the lines in and around Narora Atomic Power Station (NAPS) area and all other system elements should be maintained properly. The porcelain insulators of these lines may also be replaced with polymer insulators on priority.
(Action: UPPTCL) VII. Railways ma y m ake a rrangement f or additional supply point(s) f or the t raction s ystem at
Panipat and o ther important locations. Replace all porcelain insulators of 132 kV and 220 kV lines with polymer insulators and also enhance the maintenance of their system elements and also cleaning of porcelain insulators of lines.
(Action: Railways) VIII. Data of relative humidity and temperature from all critical locations should be captured and
made available to the SCADA system and also uplink this data on their respective websites. (Action: STUs, CTU, SLDCs, NRLDC)
![Page 108: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/108.jpg)
IX. HVPNL, PSEB and DTL, UPPTCL may replace the porcelain insulators of their 220 kV and 132 kV lines wi th Poly mer/antifog (high cre epage dist ance) esp ecially passing th rough pollution prone areas.
(Action: Concerned utilities) X. I dentify n ew li nes/locations w hich are frequently af fected by t he f og related t ripping.
Prioritize the replacement of porcelain insulators of these locations/lines with polymer/anti-fog insulators.
(Action: concerned utilities) XI. The pollution causing installations near transmission lines may be got removed. For this the
matter may be taken up with the District Magistrate/State Government. (Action: Concerned utilities)
Meeting ended with thanks to the Chair.
![Page 109: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/109.jpg)
Annexure-I
List of participants for the Meeting of Crisis Management Group: 04-01-2010 NRPC Delhi Sh S M Dhiman, Member (GO&D), CEA in Chair
Name (S/Sh) Designation Mobile E-mail POWERGRID R.N.Nayak Di r (O) 9811422111 S.K.Soonee ED, NLDC R.G. Yadav ED (OS) 9810647755 [email protected] Bhaskar Sharma GM 9958555761 [email protected] R.K. Singh Manager 9873918545 [email protected] S.Rasool Ch ief Mgr 9873549223 [email protected] NRLDC V. K. Agrawal GM D.K. Jain DGM 9910344127 [email protected] Rajiv Porwal Chief Mgr 9871581133 [email protected] Rajesh Kumar Manager 9811397471 [email protected] UPPTCL D C Jain CE(TW) 9412749801 V.K. Agarwal Advisor to CE 9412749817 POWERLINKS Suresh Sachdev ED &CEO 9810190547 [email protected] P.K. Pal GM (P&O) 9415009321 [email protected] DTL A.K. Kaul Director (O) 9540040614 [email protected] B.B. Sharma G.M (O&M) 9540040610 Railways Rajesh Kr. Jain Director 9910487331 [email protected] PSEB V.K. Gupta CE (SO) 9646518001 N.K. Sharma SE 9646118204 BBMB R S Lamba Dy CE/PR 9417216058 Sawinder Singh Sr Ex Er 9646140207 HVPN H.R. Satija CE/SO & Coml 9357156160 [email protected] N.K. Makkar Xen 9466219042 NRPC A.K. Aggarwal MS A.K. Rajput SE (O) Sarita Sewak EE(O) Vikram Singh EE(O) 9868893051 [email protected]
![Page 110: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/110.jpg)
7.l~~\1~·f f:·~"~;.rr:: r)Ti\i.rc.~~:~ J
:"::·~3r}~u:'1 Llf·\~~rt ~\I./ ~\utr'\";' i{~
1,Ti~1 J1'~F{ ; ~i.f~r ;:'n frJ,r~,,~ i~;;::(~n ' 1: 00613 '>.<'r11' Trrr' r' ~ ,11 .. J ~ "" .!1 I
9001-2uOO)
O'J!ed 08 ,0 1-2G! 0
~~~!'-, Congtitution of a Co:nrnlttee to fH'Hlui,e. ,~nt(J piirlial Ul'id disturbances thal occurri?d in NO"th • .!ln Re~Jio/l OJ! 2'''' Janu,iuy; 2'110
T,'Y;~. separate 0rjd iJ!'C,iurb,~lncl~'~ U(,";.i'IEel (;I, :~r,( JanuHfV, 201 n partidllv ,+:"',,-ung the nov'i(?( ~UPP!'i iii !Jli-) NO(1heril Rf,qnn In PlJr::;l.lanfX~ of POWI:;I" .;::,j'-;"·lfl:'<~ tu the /;'Jtnofltj :,l'Kler $'''l't(XI ~':)(i) 01' thE, Electriclj'/ J\ct 2003 ;~
"<.:P.~ flitted i..>:'impnsing ()f fOI!Cli!l:ng n:18 1 !l~)eIS IS hereby C()(1s\ituted to enquil e Lit;) ; ::-- :llJo\:e grad dlsiurt;,}nce\3-
n :~h S.M Ohiman Mf~'Ir:t.cr ~C:;(Jt~D!CEj~- C.hairf'!i-w !I;~" Sh Y , K Rail:ar18, DIrest,,)( !TE:~ch), !~aJaslhan F\~aJYa Vidyut Prasar'-ir)
Nigam Ltd --l\.1e rT'ter ii~ Sh RP Slngl., Drect<.'r, ifJeclri,':a/j :::;;::,(I"lj ,Ial \lIdYltl Nigam Ltd· Mernt .. ,;( r.rl Sh. J\,K AWdr1rwai M;::;i i',br:i Si'cr.:::tai y, North~m RegIonal Power
Gornrr:i:ti7i;. -Member C0I1VPIK'1
'.it SI! V 1\ A~Jfawal Ger1eral rvi;lila~~!,,! l\kll~hi=,fIl r~89ional L.,).qd De~pa:ch Centre- Iv1e.;nbt:i
,;j: Sf1 I~i;:i i-\uliia:' r'>T,t;" E',;':',cuti'jf- D;;f~;:h,)(, PO'del Tmn:3I1"1iss:f"n CU(Pol;::;tion of Utt3rClk i i31i(l Ud -- M8rr\L~t~r
I) -fu a;'laiy";e ttJ(~ caus:.=s and r;jrClJrnstartCI:-S leadi){J to tripping of hnes em 2';; ,!af'lII:;j;Y 2C)1 C pai1 oily .3rfect!n~~ pC'Jwer supp;yln Nort:?ern Region
I',! f'J s\J~J9<3st li",mettai m,j:;lSUfeS Ie av'~rcJ leCUnE:PCf; of SUet1 dlsturb"l'1ces In Illture, lakin9 wto ,~()"'sldtH';;:itl(;ll UIH r~)i,:.)nlfl\Gildati;)ns of the s:rndar Cornn;itlees (~f)n~tltu!erj earlle:
Ii!) To 16'/IBW ti'lf~ re';ro,'atIOfl of S'y'Gif. 'ITI h::l1( 'Wif1~j 111", I.kj1umance::> ant! ,sugqe<;[ '1' €lflSUlf)S for Il,nprpvemcnt II) 1/"11') k~JjfCi
![Page 111: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/111.jpg)
Fr om:
<:;.()J!'Y .. with the (egI.lEl&L_~~.1~!l~ aV~~J~.bIO_ .. 9fl~f_~~~~_~::.on~_f:~r..I]~~£!...JtIp. S!torgsnid I2l1rnose : ,
/\r!dlt:o'1al Me1~b~r(Elect: i\~ali :-!O(l'ti N,) 11~, FWIV.f8;! :iDarcl i~ai! tit18'1ap New Delhi - 110 001
2 Ch(1i1Tnan 6. Managing Director, N rh.: !.k, NT:')C f3113wan, Core 7 S.::OPE (';cJlnpfex, 1-lnstltli~jolial Area, LOLli ;~>:;i:'Hj ",Ievv ['e!iH-11(j()C);1
,I (,;1',lIrtnan & MarJa9in~ D,rectix, I\lr'IP(' :.1.1 NHP(-:; ()fflce Complr::>: Sf'!cio'. :L; r t:llidaLad - 1::'1 1)03 (Haryarld)
'I CIJ8lfrtlan & Managrng D!rector, PoWerC;ij{! Co,,:.,'-;'/ dtior! af India Ltd, Piol 1'10 -~~ Scctor-29, New IFFCO Ch()'I<'V:\. Cl.ilg8on - '!:?2 D01
~~ l:lrairrnan, j '-,\/"f!d,ni,s Yr:1';<;nl'(, I ii', L: i ,'til; ~")I ~"~j :::1::: 1I'il\~)~i l~fl'i\lifl~1 id. !.1rl1 dl,)uilli.'a ~~[)<ld hJ'>'J [<",Ii,; i :'';'i::
t3 1 hfl M~"ug,rs; D1re<:I,or. Powe;- TI::-:in~;lnlsi;,lon Curl-,oration of Uttaraf;han,; Ltd, 7-G, Lanel, Vasanl Villar E nclaVI;;, De"~radu.1
6. Principal Secreta,)! to Govt, Power Deve!opment Departme~',t CIvil Secretariat, Jarnrnu (J&I\) .
;' Chairman, HPSEB, VidYllt Bhawan, Sntrilia - 111 004
:1 Chatrman & Managing Director. [Jt~!I';j -I ran~;c,j Ltd, Shakti 8hawan, Kolt.l '(t>ad ITO New Deihi -- i 'lO 00/
1rj Maria~~ing Dir.ector, Haryana Vidyw Prasaran NI9EHll Ltd,. Sh2lkti Citlaw'ln Sector -8, Pant'hkulC't .. ' 134009
!! Chairman. 8hakra 8eas Manaoerllent Board. Madhya Marg, Sector 198 Chandigarh - 160-0'19
£QtrilQr info.!!!,ation to '
PS to Secreiary (Power), iVlIniSfry fit Pmr\.t-r Shram Sllaktl 8tl<lw.:m Raie Marg, New DEllhi SA. to Chaiq,i(:rSOIl, GEl-,
•
F, "-
![Page 112: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/112.jpg)
,I f I)lio'," 119 offlcelS ot the c(jr!~:.:!tl~Il($ of the? ''It::.(~'C are hereby rle~l!jnated 2i~S Ii.:dat officers Gf th(: resp8ct!v8 organll:Jtions :.'vhf) will faCilitate co!lp.ctjo~) of ji'lt.'1 ()laton r'eqtlii'(,d ":11 tiVcl C>~:lr'rnltti:e '('I' iI'.'" Pli:~)(J:>i":l Qf anal,'sis
Ij ~';Ir ~;~:- (,Iuasir~l CE iSO', PDU. J,~.i<' II), St-, V K C:icpta. CE iSOl. PSE8 Iii; -~:\I~. H R ~~alila CE (SO!. H\/i)~,:L j',,~ Sf R fJ·. Snarn1a, CM ,OM), eEL \;1 Sf< n Sharrna. GT\,;! ':I\JF~-II, F'i)iPif:-F«d<Ii_1 oil) ~;t, P ~< F'aL C:,1\'j (P&O) Povverln!<'j Tli:1I1",'";iS';'(:- Ltd
-Jli) Sn::.; r:'aramesr·\Nz:ari. Cillet 1::.nqw,et1i (()id'!.; NHPC:: vii.) [-)h RaJe5!1 Kr jain, Directcr fv1inisrry 01 !:;a!:way
I)(j ~;I!I1it Grover Dire(!0f (PFI (';. Ct:HC) f-H::-JSFB :.) Sh P F). FrancIs, OCiM (OS) i~TPC }'") Siln Sawinder Singh, S':.mior r:,..:~cutl\;!? En~~lne(~, 88MB
.-. -i-I~E' TA/OA and otiler expenses cil the men-,bt's ()f Ole Committee as well as n.x1al officers shall be borne byttk resl:>8ctlve ,:jrgal1lzations
t: -r he CommitLee shall sLlbrnit its f{tp(l(! '.t/ilbi!) two rnonlhs fron~ Ihe 'ssue a= thi$ order
7 This I""'as approval of Chairperson, CEA
~~h SM. Dilimari Member (GO(~D",C(;j\
(~1i;,··-~~-i-:::.---~-·~ (Naresh 13hil~;dCt\li
Director (Adm ,"j
lei No 011 .. 2f3'1C183G9
SI', Y K Raizada, Director (Tech), tzajasU-:;,m Raila V~C:V,H Pras3rall NH]8ffl Ltrj, V,dyut Shavano .Jyoti NafJ31, ,Ja,'pat!) ,)AIPU~~- 3Cl2 DOE)
j ~h R P Sin~Jh; .Qirector (ElectriCal), (-;8t!UJ ,Ial Vidyut Nigam Ltd, -liltrnfeo Building New Shimla - 171 OW;
4S11, A K. Agarwal. Member SecretarYNRPC. 18-/\, SJSS Mar{l Katwwi8 Saral New Delhl~ 110016
5 Sh_ VK Agrawal, GM, tIJRLDC.: 8·A SJS~; r,,1drt,:.l. Katwaria Saral N~'I'J Oelh1110016.
A- Ani' I<.umar Gupta, EO (Projects), F'!';wel Tra.-,smission C()rporation of UUarakhand Ltd: Project OffiCI:', F'-' ,,:::UI U(i~1 S/'Iawan. Can)fH1S, I<anwall HoarJ, Oehradun .
![Page 113: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/113.jpg)
FROM OFPOUER
To,
: l.ll Nl SIRY
\
FnX NO. : A1123Z3a2Gd 2? Jan. ZOL6
.1. Member .(Electrical), Railway Board,. Rail Bhawan, New Delhi.?. Member (pS), CEA3, Member {cO), CEA1. l,lP, flaryana power Generation Corporation, pa_achkula.9. MD, Haryana Vidyut prasaran Niil;_rit d.
*9. Chairman, Up power corporationlii"Gl;-:/. Chairman, Delhi Transmissi" d;;;ti;; Kotla Mars Delhi 2I, Chairman, Rrnjab State Eluctricit;;;;;;;;9. CMD, PGCIL, Gureaon.10, Director (projects), PGCIL, Gurgaon.
of po*er "ueotv to tho R"i-rffiDEffi
F.No. r0/2/20tO-pGGovernment of lndia
Minisry of powerPG Desk
Shrem Shatifi Bhawan, Raf Mare,New Delhi, Jenuary 22,2011
(x.v. c@6iflao)und,er secretary to the Governrrrent of India
Sir,
I am direated to encloee .herewitJr the minutes of the mbetingtaken by shri M. Ravi Ku"{ joll! -s";i#0."q;;irrnietry of poweroa the above subjcct on t8.r.2o1o ut d.6ir 'pii',^i1,.'i"r",'"ation ardn€cessary action please.
Cow to:Director {OM), Director (Trans}, eS to JS (Trans).
Telefax : 23230264
t1^ fvt"rotc.rr*Uftfiti^t.
ANNEXE - I/IV (page 1 of 7)n .
FROM :MINISTRY OFPOWER
to,
1.
2. ' 3. 4.
, 5. , 6. T 8. 9. 10.
FAX NO. : 01123730264
F.No. lO/2/2010-PG Government of India
!V!inistiy of Power ,
27 Jan. 2010 12:36PM Pl
,PG Desk , , . ,,' . Sbram Shakti Bhawan, Raft Marg,
New Delhi, January 22, 2010
Member (Electrical) , Railway Board, Rail Shawan, New Delhi.
, Member (PS), CEA Member (GO), CEA MD; Ha.yana Power Generation Corporation, Panchkula. MD, Haryana Vidyut Prasaran Nigam Limited. Chairman, UP Power Corporation, Lucknow " ' Chairman; Delhi Transmission Corporation, Kotla Marg, Delhi 2 Chairman, Punjab State Electricity Board, Patiala CMD, PGCIL, Gurgaon.
, Director (Projects), PGeIL, Gurgaon.
Subject: Minutes of the meeting by Joint Secretarv ITransmission).on 18.1.2010 at 3.00 PM to examine thebreakdoWD ofpowersup~ly to the Railways on 2.1.2010. ,
Sir, "
I am ' directed to enclose herewith the minutes' of the meeting taken by Shri !V! , Ravi Kanth. Joint Secretary (Trans) , Ministry of Power on the above subject on 18.1.2010 at 3:00 PM, for information and necessary action please,
CoPY to:
", YOUrs faithfully,
•
· (K~O)- .' Under Secretary to the Government of India
Telefax : 23730264
Director (OM), Director (Tt'an$), PS toJS (!tans) ,
"
![Page 114: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/114.jpg)
aFROI.I : Il INI STRY OFPOUER Fn>: No. : a1123?3A264
1.. \
?1 Ja^. ?A!A 12;36pt'1 p2.)
I
^ t Y:"ti"e was taken by Shri M. Ravi Kanth, Jointlsccretary(Trans), Mt"1.,r]' of power on- Igu January, 2010 at 3.OO pM in thlConference Room of Ministry of power, Sfr"aram Shakti Bhawa", -lt*
.Delhi in connection--with the naiiwjJTrr.tion Supply, Therepresentarives from Haryana po*", o'eie.ation corpo?ldo" itd"IHPGCL), Haryana vidiut _[3qran Nigam Lia,
-
6rverur,y, itn", ir.a"JPoiver Corporation Ltd, (UppCL), oetii ttansco Lta. ibrui,- f.l-"rtt "-Regionai power committe€ (NRpc), cent.at-ptectri"try i-"rt6rr,y'tciiiand.power Gri.d corporarion of India LimiteJ rpdcu,t parucipatei in-trrismeeting. The list of participants is arurexed..
2. Joint Selretarv (Tran-s) welcomed all the participants ande,mphasized the impoitance of the meeting, which has been called as per1:-l]l"Tt:"s of Secretary (power) to ai#"". ",.,a-=";;;;;;-.fii*:T"rg: to ensure powel lu.pqtr ro Railways tracUoilna .i,"fl*,..'.igrid incidences like that of 2"d january, 20 16.
1. - Joint Secretary glans) expressed his ser.
t]'re absence pr. 'i#e!"ntative from naiiway" ;';i:L::H,"f t".tHf;Ethat the mecting has primarily been calledio i_prou. the power supplyto Railways Tlacbion a'd to avoid ,-""ra.rrrr* ol-".rct, problems and thenon-participarion of Rai_lways l; ;;;;i;;' i" ;'fi"-.;;; H;ii:concern,
4. Executive Director (System. Operation), pGCIL expressed that theTragtign has atways been girren the^trigheJ'pri*,ty i" Jv"i.i-o;;;d;;and detailed proccdure his been "p.it o;'i"-rhi, n..L.udon'ifuT-oicvery region. On 2nd January, 2010,.the Up system was heaithy;;J;iefrorts were made to .o::g lh._lly;, :"eety i; iuil*.y; ;;l;; plil.rr".HoY."o::I: delay in complete ,estoration' ias paruy aJlected bv . nonavailability of certain elements feedrng Railways f;;i;''-'".. ,r rrurr
5., .. Director (operations), pGCIL explained that Railways are graduallvwinding up the earlier sources of 'supply-""a u*t"iai"g-ri;.*.:;;through their own feeders which arc r"dfi-il;;.", a"."Ly'i.iri,"vfeeding points become dependent o" o'u ";;;;, tne reliabiliry of t'esupply reduces. .
-1-
ANNEXE - I/IV (page 2 of 7), . ,
'-
FROM :MINISTRY OFPOWER FAX NO. :01123730264 27 Jan. 2010 12: 36PM P2
f ./ . / . . Minutes of .the meeting by Joint Secretary (Transmission) on
18.1.2010 at 3.00 PM to examine the breakdown of power supply to the Railways 011 2.1.2010.
A Meeting was taken by Shri M. Ravi Kanth, Joint · Secretary (Trans). Ministry of Power on 18th January, 2010 at .3.00 PM in the Conference Room of Ministry of Power, Sharam Shakti Bhawan, New
.. Delhi in . connection with the Railways Traction Supply, . The representatives from Haryana Power Generation Corporation Ltd. (HPGCL), Haryana Vidyut ?rasaran Nigam Ltd. (HVPNL), Uttar Pradesh Power Corporation Ltd. (UPPCL), Delhi Transco Ltd. (DTL) , Northern Regional Power Comniittee (NRPC), Central Electricity Authority (CEA) and Power Grid Corporation of India Limited (PGCIL) participated in this meeting. The list of participants is annexed.. .
2. Joint Secretary (Trans) welcomed all the partlClpants and emphasized the importance of the meeting, which has been called as per . the directions or Secretary (Power) to discuss and suggest the remedial measures to ensure power supply to Railways Traction and avoidance of grid incidences like·that of 2nd January, 2010.
3 , Joint Secretary (Trans) expressed his serious concern regarding the absence of a representative from Railways 'in the meeting. He stated that the meeting has primarily been called to improve the power supply · to Railways Traction and to avoid recurrence of such problems and the non-participation of Railways in the meeting is a matter of serious concern.
4. ;Executive Director (System Operation), PGCIL expressed that the Traction has always been given the highest priority in system operation
. and detailed procedure has been spelt out in the Restoration Plan .of every region. On 2 nd January, 2010, 'the UP system was healthy and all efforts were made tqextend the power supply to Railways o·rl top priority. However, delay in complete restoration was parUy affected by . non availability of certain elements feeding Railways Traction. .
5. Director (Operations), PGelL explained that Railways are gradually winding up the earlier sources of . supply and extending the same through their .own feeders which are radial in nature. As many Railway · feeding points become dependent on one source, the reliability of the supply reduces . ..
- 1 -
![Page 115: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/115.jpg)
FROII : IlINISTRY OFPOJERl - t.FFX f.10. :611237JA264 27 Ja^. 2A!A t?i3lpl
9. Chief Engineer, CEA. also explained. that this change inarrangement by Railways is bcing 'aorr" because of commercialconsiderations arrd compromising wilh the reliabili[ "a;d;ilAi;;;contingencies . will effect public intirests.
10' It wis decided !o qirccl Member {E}ectrica.l), Railways omphasizing, for .b€tter retiability during fog "orraiUo""-*Jto tal<e all the steps toavoid recr:rredce of the pro-ble;s that occurreJon Z"a Janua:y, 2Oi6.- --
I 1. Regardiog the tripping of lines, replacement and cleaning ofinsuldtors and changing oi irrsrrlatoi" tioo, porcelain ,o ;;,fi";:Director, HVPNL explJin€a that they have J.*; ora..J I pruiiii?oireplacembnt of the insulators by anti-fog and future repracement wourdbe through porymel insurators. rurthe-r, i3 was decid'ed r;t-r"-;;;;flashovers/de-capping are not controlled ,,'i ifr" f.J;";;;;;,"-,h;efforrs shall be made to replace the existing insur"tor* -oiry .i,iih ;Jffi;insulators.
t 2. Director, DTL also- confrrmed . thl they lare in the process of
Silfffi'$.";:11:,:I" ftnolrmer i, neuri 'rung-rd"';y iffi;#
3
ANNEXE - I/IV (page 3 of 7)
FROM :MINISTRY OF POWER FAX NO. : Ell 1 2373El254 27 Jan. 2El10 12:37PM P3
.Ii . // : " , I'
,f .j' .• 6 . , Member , Secretary, - NRPC emphasized that in the eartier
'l ' disturbances, ", similar recommendations , to Railws.ys have since , been ,.. "made in March, 2008. However, no efforts have been made by Railways.
. . . . . . . ' ..
, 7. AdVisor; UPPCL explained that they would be able to supply from Aligarh. He also emphasized that the earlier supply paints like Panki etc. have been Withdrawn by Railways. , "
- , 8. Director, HVPNL explained that from Panipat, Railways have their own feeders. HVPNL is ready to extend the new source of supply from the upcoming stati011 in Haryana. '
9. Chief ' Engineer, CEA also explained \hat this change in arrangement by ' Railways is being , done , because 'of commercial considerations ,and compromising with the, reliability of supply during
, ,contingencies. Will effect public interests. '
.10. It was decided to direct Member (Electrical), RailwayS emphasizing (or better reliability during fog conditions and to take all the steps to ' avoid recUrrerice of the problems that occurred on 2nd January, 2010.
11. Regarding the tripping of lines, replacement and cleaning of insulators ' and , changing of insulators from porcelain to polymer, Director, HVPNL explained that they have already ordered / planned for replacement of. the insulators by anti-fog and future replacement would be through pOlymer ' insulators. Further, it was decided that in case flashovers/de-capping are not controlled and the faults continue; the -efforts shall be made to replace the existing insulators only with polymer ' insulators. -
i2 . ' [)irector,DTL also confIrmed that they are in the process of changing the insulators to polymer in Delhi Ring Main by taking the shutdown of one line at a time. ' ,
13. Director (OM), MOP emphasized that the Cost Benefit ':Analysis of changing all the irisulators should be done in the light of securityC"of supply -during contingency. It Was transpired that still iilarge iiumber-of insulator strings have to ,be replaced by polymer insulators and cleaning , is -alsore-quired to be carried out at some of the rei:riaining triticei ' locations . This is a phenomena acrOss all the utilities and considering ,
. the reliability of transmission system requires immediate attention;
- 2 -
<I
"
"
i I , , i
! I
I I
![Page 116: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/116.jpg)
FROtl : IiINI9TRY OFPOJER Fex No. : a1123?3A254 ?? Jan. $tO t?':3?pn p4
15. Regar{ing adequate bacl< up power supply at widebandcommunication node / repe,ater "t"rions, it was Tmpnasized that theconstituents should make Ltt "or"g"_;rri, ;.;;; visibility of the datais ensured.
19 Joint S€cret4ry (Trans), MOp emphasized that trained manpowerat contr- ol-cenrres / sub-stations. should be aug-"tila by all the utilitiesl*:-l:tr,j::ing the night and earty -"r*G;;;;., ;h"" A; ffiil;'maJemum lmpact.
rl
I
18. Director, HVPNL assured that the Khedar RtU would becommissioned immediately.
19. . Joint Secretary (Trans),.MOp emphasizcd t}lat all the new stationsshould have their RTUs commissioned "" prtrititr"i".
20' Director (oM), Mop also. raised the issue of proper deience oranlike underfrequenry relays, undervoltage rer.vi-ai/Ai .JiIi" _;"#; |#jof such emergent situation in tfre Event-J' ;y ;;;;;;; #;;ll?,T3?.:J:.j,*r:.-,::t lf1 q, u:re,uuritii. ".;a t" ,lfu.J,i,ril.Jipriority to keep the defence.plan a*"V. _ "p.."Uj".
i
I
,l
ANNEXE - I/IV (page 4 of 7)
FR01 : f1INI STRY OFP()JER
I: . ! i
FAX NO. : 0112373026~ 27 Jan. 2010 12 : 37PM P4
.'"
.'I
it . ii .
: .. .~. .... '. '/
,';/ '. 14. . On ~.'" 'enqUiry ' regarding ' the requisite . changes ' in .. Current Transfonner (CT) ratio of different lines, by Joint Secretary (Trans) MOP,
.. Director (Operations), PGCIL confirmed that the same. has been ·taken up. It was Slso agreed that the same will be taken care by other constituents alsO in their areas in consultation with RLDC.
. '. " ,
15. Regardingac;!equate bacl( up p<lwersupplyat . widebarid comml,lnication node. I repeater stations, it was emphasized that the . constituents should make all arrangements so ' that visibility of the data is ensured.
"
16. Joint Secretary (Trans). MOP emphasized that trained . manpower at control centres / sub-stations should be augmented by all the utilities . particularly during the night and early morning hours. when fog has the maximum impact. . -
. 17. During '. the discussions, it also transpired that at a number of grid sub-stations / generating stations, particUlarly whiCh have . come out recently. Remote Terminal Units ~ (RTUs) , have . not been
. . commissioned. This is leading to blind operation by the load dispatchers ' . and the real time operation is severely affected.' . .
. ' ," . ' .
18. Director, HVPNL. assured that the !<hedar RTU would be . commissioned immediately.
19. Joint Secretary (Trims), MOP emphasized that alL the new stations should have their RTUs commissioned on priority basis.
20. Director (OM), MOP also r aised the issue of proper defence plan ' like underfrequency relays, undervoltage relays, dfl dtrelays to take care of such emergent situation in the event of any contingency. Joint Secretary, MOP reiterated that fill the utilities need to accord highest ' priority to keep the defence plan always in operation.
21. MembeTSecretary, NRPC explained that for the new ·" capacitors. 20% of the cost would be paid from the Reactive Pool Account of NRPC
. and the same is being monitored byNRPC. '. .
, 3 '
'.
. '
., \
.. !
., . I
I
, ' 1 , . , . . ,
\
.: ·· ···S···"·--. . : . . ;
.; . ' :...",
I I I I I I I
![Page 117: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/117.jpg)
FRO14
'.: I'IINISTRY OFPOUER: .: Fcx No' :81123?34254 z? Ja^. zara 12:3Bpl'1 p5
,'!'iiil 22- Director, HVPNL and the reDr€senrrriv- ^r rrEr.!/rr -!-- , ., I,' g"i-glatio; .i-iii'ipii-ai'lffi XrlT,"t"Tj'nor.HPGCL cited the loee of,', :.:y:. rh;;" h.;:-bb; ff#.;;;J .-i""'"Xli :;o[tfr$?r"""*?T,o, ff, BBMB. rhere havt bbil i;;1!J.ii.i6'.T'B'B'ffi To6'fr$?t.'H?Tlffstatibn for even hieher than lO "-;b=er;ti;es m Jaruary, 2010 itself.Similar incidentsiad rr".p.pr"J ""iri;r-il;: A sratement showing thefiffi|f .?t,ffnRings
has'6..; h;;;; lr.-, uy the . representatiie o-f
trippines on the zrh tFjjt'1""-:t-:fMB'
-lt,was -""hd d;-th;;;.;
l _21 Joint. S:cretary, MOp_ _ directed that NRPC along with therepresentadve from cEA, NRPC, pcCIL, eBile u"a Uppcl"*;;;;rni;Task Force ro visit aI the a_bove ;L-_'.;;;;".;;L.
"*r,,o", of BBMB.Muradnagar and Mau oi uF ana;ied:rilHi" measures to avoidreoccurrence of outages a1 thgse aii_.atio"r,' which have serious;:1Tffiffi;on the securit5r "r tn* g.ta. ilii'"i.v u" 1.". ;; ;"ffi::
' 25. Member Secretary, NRpC explained that a Committee hae sincebeen consdruted bv cEA t9-e" r"r'o:ri"ie1;j irf the incidence of 2,,dJanuary, 20 I O unier _trr. c1i{"iarJ,p li'ilJ*uer (Grid operations}.: cFA' Thb crisis *"rr^u:T:l! Group.formed as per rhe directions of Mophad also met on 2nd January as wil as on 4o ianuary, 2OlO to review.the situation.
?9. . _Dyring the discussions, it also.emerged that fog affected areas asidentified eariier have be-en increased "i-i,r?rirr,iil Region as welr as inother regions arso. Therefore, th"-;"il";;;iioi po.""r"i' insurator withpolymer should be revieitid t;-;;h;;",ttuenr inctudi.nc pecll,immediately and wheiever polymer t"";i;t ;;;;e not been pianned buttrippin gs/ fl ashovers are. inirJ;;g ;;;';i""#.. in pollution / densiwof fog level, the same "t* ,r.rj ii t. ,in..ihth polymer insulatorsbefore next winter to avoid Grid ai.-*ri*5._. "' '
27. Director (Tracls) observed that whilc therc are adequatesuggestions for taking care of ,rr"." ."""i""iiti,titiJy i-pt"ro..tt"tili"br ,r,. sug*estions. :s what is required is
trippinss on the Zrh,8th, 16th."Jl?1rr "ij*r"*"#Olr / u.r eJ !, anllarv ?O1n
Irl
I
I
.tI'1
-4-
ANNEXE - I/IV (page 5 of 7)
....
FROM :MINISTRY OFPOWER FAX NO. :01 123730264 27 Jan. 2010 12:3BPM PS
' .. ~ . . p r; . ,I' :
'':/ !
·22. Director, HVPNL and the representative of HPGCLcited the 108s of. . generation atPanipat dunng the last few days due to tripping at Panipat
. BBMB . . There have been forced outages at BBMB400 KV Panipat .sub. . station for even higher than 10 number ohimes in January, 2010 itself . .. Similar inCidents had happened earlier also. A statement showing the ...
number of trippings has been handed over by the representative of HVPNL of the Substations of BBMB. It was noted that there were trippings on the 7th, 8th, 16th and 17th of January 2010 . .
23. · . Director (Operations), PGCIL · also. cited the · examples of Muradnagarand Mau sub~stations of UP becoming deaq.-very frequently .
... DTL confirmed that complete outage · of BAWANA SIS has been . .. addressed and it. is expected that this problem at Bawana would not
occur again.
24. Joint . Secretary, MOP directed that . NRPC along with the . representative from CEA, NRPC, PGeIL, B8MB and· UPPCL may form a · Task Force to . visit all the above sub-stations; viz. Panipat ofBBMB, Muradnagar and Mau of UP and suggest remedial measures to avoid reoccurrence of outages . at these sub-stations, · which have serious repercussions on the secUrity of the grid. This may be done in a timebound manner.
: 25 . . Member Secretary, NRPCexplained that .a Committee has .since been constituted by CEA to go into the details 'of the incidence of 2nd .
January, 2010 under the Chairmanship of Member (Grid Operations), CEA. The Crisis Management Group formed as per the directions of MOP . had also met on 2n4 January as well as on 4th January, 2010 to review
. the ·situation . . .
26. During the discussions, it also emerged that fog affected areas lis identified earlier . have · been increasedm Northern Region as well as in other regions also'. Therefore, the replacement of porcelain insulator with ·polymer should be revisited by ~ch constituent includipg PGCIL . immediately and wherever polymer insulators have not been planned but ·
. . trippings/flashovers are increasing due to increase in pollution/density of fog level, . the same also need to be replaced with polymer insulators before next winter to avoid Grid disturbances.
27. Director (Trans) observed . that while . there are adequate · suggestions for taking care of these eventualities what is required is timely imp1ementation of the suggestions.
- 4 -
. .
. 1 . ·1
!
'. . " ...... .
·····CC··· ·
. 1 I ,
. , 1
. ,
i
\ I I I I I I
![Page 118: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/118.jpg)
FRO'1 :l'llNlSTRf Fft ER FAX NO. :41123?36A64 A? Ja^. 26!@ 1Z:3BFtt p6. ;: .... I.1,-. ., ,,.-,::r;1-i;1.1i1-;i,,;;.. : ,....,.... :.,.,.,t - ,-.". -:-.- ,
''''..'.:;l : . ' . .' . tl.,. li i:. 'j:. . !: i. .'.: :': .: ..ii:t . '., . . ,.'.1i: -" ",1,; ""' , ..' :...;.-..,'.
ii 7a, concluding the discussions, &e Joint secreary, lrop *itratea:', ".: ! . the ncacssit5r :lTar?,T1"*C g:.H4 atcrtress by all thc co"troi
""r,tn 17'i 's'b'stations and ar orc uriliueiin No*rrernlnceio;;r;; of thcadverse weather
"o"aiuo". ""J-.i"re. r.-s b"t"s-d;d;;" ,j;;;'' wintcr. He arso emphasised tirc oeea.rEr-ffiidil.iiJ-I"p".ttor". . installadon to avoid lovr voltage in the forthcoming summer.
IThemcetinlendedwithaVoteofThankstotheChair. - :,,, . r i
'j .r ,: . r': :lI
+**.r*rrri I
ANNEXE - I/IV (page 6 of 7)-' I
. ' , - .
FAX NO. :01123730264 27 Jan. 2010 12: 38PM P6
" :, '~ -. '
. i: .....
... . .. , '; " , ~ ..
"
', ' - . " ...• .. . , '. . ':
", . "f I- : , '.' ;' . .
/1 28.~chidingthe discussions, the joint Secr~,MoP rei~rated _,:. the n~ssity of maintaining the high alertness by ,all the control centres!
.. /i' ' -sub-stations" and all the utilities in Northern . Region' in vieW or the : adverse weather conditions and , severe fog being experienced during
. . winter: He also emphasised the l\eed for expediting. the capacitors . 'installation to avoid low voltage in the forthcoming summer.
The meeting erided with a Vote of Than'ks to the Chair • ...•
'. ' . ,
, , . ~, .,
" . i
'. '
••••••••••
;;.
, "
, ,
. c·· ·
.•. , .... .... . ....
. ~ " . .: " .~ .
· : ":, . ~ . . . , '_ . ; .
. ; . " , . : "
· . ' ..... , ',. -<::. " ',
", ;
;., - ~\ .' , .. :" ..
. , . ' :" ,
. . . ~ .
" .
.... .
., . " ,
.... ~.:''''''' '' . . : ."
. " . : .' ." . :",
",' . , '
. : . ", :. >
'. ". : , ' • I ""· .. ' " :' " , "
, : . ~ .-.
. - · . ~ ' :: . .....
5 . ~ : , " ..
. , . '~ . . . ' .. ~ .
, . . . -.-'
.. ' '," " -~.
: .,. .' ~:.' . ~' .
," '" .
'~. '.' .'
. ~ .
" "
. .' /' ....
" "
"
~' . .
" . .
"
. " :,,'
.. ... : .
'". ' .. " :, '
' ,' .. ··t ' ., .
i
I . \ , 1
:\ ' . '
',' . I
I '.:\
.. ' 1 'I 1
" \ . .. !
. . 1
I , i
! .: , -i
. ;
. -':' \
I ;
. ....
'.'
![Page 119: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/119.jpg)
Mlnistry of pover
l.2.34.
101lt2l3
'r,.14r1516'17
| 47L23?3A264:I'lINISTRY OFPOUERFROt'l
.;Fnx N0.
LTST OF.PARTTCIPAITTS
6
ANNEXE - I/IV (page 7 of 7)
- .'
.::' ...
, . '
. . ',
FAX NO. :011237302&4 27 Jan . 2010 12:39PM P7 " "."
, . . " '. ' , .~ . . " .~ ' .....
. . ~ . I
'I '" MiDutes of the meeting by J8 !TraPS) on 18.1.2010 at a.CON ,"
to examine the breakdown of poWer wpply to the Railways on, 2.1.2010 '
LIST OF PARTICIPANTS
S/Shri . ,.,
Ministry of Power . ' . .
1. M. Ravi Kanth, Joint Secretary (Tr~s) " 2. , Malaya Srivastava. Director (Trans) 3 AK Saxena. Director (OM) ' 4, "K.V. Gopala Rao. Under Secretary (PG)
CEA
' 5. ' , , 'RaVinder. Chief Engineer (SP&PA) 6. , , RK Grover. Chief Engineer JGM)
7 ' 8
9
RN Nayak. Director IOperations) " SK Soonee. ED (SO&NLDC)
AK Agarwal. Member Secretary, NRPC , "
, States .. :-
10 , AK Kaul, Director (Operations). Delhi Transc,o 11 ' BB Sharina, OM (O&M). Delhi Trasnco
, 12 DC Jain. CE (TW), UPPTCL , 13 , VK A!;iarwal. UPPl'CL ,
(,, 14 VB Choudhary. Director (Projects) HVPNL 15 , JS Batra. SE. HVPNL '" 16 Sanjeev Gupta"Xen. HPGCL
' 17 , ' SC Vashishta. CE, HPGC1
, . -.",.,
" ", " ' ",
-', ,' - . "
. . '. "';'
, "
,
in the ' Chair.
" '
. "," . . . '.:
, 1 , ,
I , I
: . :., '" .. i I
.',. ~: . '. .' . ~. .
" .' 1
.- ," .
" '1
J
... ,. .. .. ,\
" . ,
'" . . .. : .. ; .......... .
,:. . .. ..
-. "; '::" .. ' ' " .
'·:8 '
,
, j
i ," . . "
,i
'1
\
![Page 120: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/120.jpg)
Chaper -2 _ EXHIBIT - 2/I (page1 of 1)
"","0 ~ 400 kV UNS'MTCHEO A~ 765 IN TRANSMISSION UNES - TRF2x~ODtWA IN UHE RrACTOR NORTHERN = B~ ~ BUS
THERIUL 400 W SWITCHED ""'" _ 500 kV UHE
IIUS/UNE RE'ACTOR
'" [j] 33 kV SWITCHED C~ ''''' I!<I WESTERN
OJSR<ACTOR POWERGRID SUB-STATION @ 400 leV lRANSWlSSlON UNES
• f-MlC BACK TO BACK -[)j(J-B8MB SUB-STATION
¢ 220 leV lRANSM1SS1ON UNES
• STATIC VAR COWPENSATOR STATES SUB-STATION SYC I: BUS/UNE REACTOR RATING IN WAR
![Page 121: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/121.jpg)
Chapter 3-Annexure 3/1
120.00
100.00
80.00
60 .00 ,
4 0.00
20 .00
0 .00
'"
100
"
..
.. "
o
HUMDITY vs TEMPERATURE OF DELHI FOR DECEMBER -2009 JAN UARY 2010
.. ,...-
t ftr1 ~ ..............
W t' I
fI ~ ~ ~
\ \ rW\ r\ \.. \ /\ J', "'-J ~ HUMD TEMP
" " ,
DATE SCROLL
HUMDITY v~ TEMPERATURE OF HISSAR FOR DECEMBER -2009 JANUARY 2010
" .... 11\ )1 !" rt
I I I
l
t\ 1\ 1\ ~
I
\ \ /' .... I\.. N I~ ~ V -" " 30 31 ,
DATE SCROLL
50.00
4 5.00
4 0.00
35.00
30.1lIl
! ".®
~ 20 .1Rl
15.00
10.00
5.00
0 .00
50
.. "
10
, o
![Page 122: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/122.jpg)
NRLDC Annexure-1
(Page 1 of 2)
Details of load and generation affected in Northern Region on 2nd
January 2010
Note:
The above figures have been worked out considering 31st
Dec 2009 as a normal day and the drop
in demand met on account of the disturbed conditions has been worked out based on the above
load curves.
For Sundays, it has been observed from past data for Northern Region that the energy
consumption is 12 MU lower than on working days and this factor has been used while working
out the Energy Not Served on 3rd
Jan 2010 on account of the disturbances on 2nd
Jan 2010.
Chapter 3- ANNEXE - 3 /II
![Page 123: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/123.jpg)
NRLDC Annexure-1
(Page 2 of 2)
Loss of generation during disturbances in Northern Region on
2nd January 2010
S. no Station 0302 hrs. 2154 hrs.
MW loss MW loss
1 Bhakra 369 802
2 Dehar 0 305
3 Pong 0 60
4 Bsiul 0 0
5 Salal 30 35
6 Chamera-1 180 0
7 Chamera-2 0 0
8 Dulhasti 0 261
9 Uri 104 103
10 Jhakri 240 162
11 Punjab(T) 1585 1684
12 Punjab(H) 112 418
13 Haryana(T) 1278 873
14 Haryana(H) 0 0
15 HP hydro 36 248
16 J & K hydro 10 10
17 Baglihar 102 198
Total 4046 5159
Thermal 2863 2557
Hydro 1183 2602
Chapter 3-ANNEXE - 3/III
![Page 124: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/124.jpg)
Annex – 4/1
POLLUTION FLASH OVER MECHANISM
(Extracts from the Report of the Inquiry Committee on Grid
Incident in Northern Region on 27th
January, 2007) 6.5 Pollution Flashover Mechanism : Wind drives airborne contaminant particles onto the
outdoor insulator surfaces. Insulators near coastal areas are contaminated by wind driven salt and those inland, by wind driven soil dust, fertilizer deposits, industrial emissions, fly ash and construction activities, etc. Depending on proximity to highways and traffic, the wear of car tyres produces a slick, tar-like carbon deposit on the insulator’s surface. It is inland pollution which is relevant to flashovers of line insulators in northern region and consequent the trippings of number of EHV lines.
6.6.1 The pollution level in some of the stretches of any transmission line can increase
during its service life due to other progressive developments taking place in the vicinity of the transmission lines. The increase in levels is predominant in areas where:
(i) Industrial development has taken place after line construction (Fig-1)
Fig-1: Pollution Deposits On Insulator Strings Due To Industrial Emissions
(ii) A surge in agricultural activities using chemical fertilizers have taken place
(iii) Burning of agricultural waste is carried out after harvesting (Fig-2.)
![Page 125: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/125.jpg)
Fig-2: Burning of Agricultural Waste
(iv) Brick kilns are in operation near to transmission lines (Fig-3a&b.)
Fig-3a: Smoke from Brick Kilns polluting Transmission Line
Fig-3b: Smoke from Brick Kilns polluting Transmission Line
(v) The normal soil itself has soluble conductive ingredients and there are dust storms and fewer showers (Fig-4.).
![Page 126: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/126.jpg)
Fig-4: Dust Accumulation On Insulators
(vi) There is change in climatic pattern with less magnitude and frequency of rain
(vii) Birds are nesting on the transmission towers and its excreta falling and accumulating on insulator strings(Fig-5.)
Fig-5: Deposits On Insulator Surface Due To Bird Droppings
(viii) Increased vehicular traffic is observed with consequent vehicular emissions
(ix) Conductive fog conditions prevails due to increase in atmospheric pollution
6.6.2 In the Northern Region, all round developments are taking place in all sectors viz.,
industrial, agricultural, automobile and infrastructure sectors like road, rail etc. All these progressive developments and related construction activities gradually increase the risk of more and more stretches of transmission lines getting exposed to higher and higher pollution over the years during the course of its service life. The type of pollution experienced by Northern Region lines as reported by the Utilities are pollution on account of smoke from brick kilns, refineries, sugar mills, burning of agriculture waste, fertilizer, dust, salty soils, automobile emissions.
6.6.3 The flashover process develops in the phases as under:
i) Insulators operating in polluted atmosphere collect pollutants on insulator surfaces. Deposition of pollutants on insulator surface depends on many factors e.g. shape of insulator, nature of voltage (i.e. AC or DC), location, angle of inclination of insulator, wind, rain etc. The continuous depositing and cleaning by
![Page 127: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/127.jpg)
rain and wind produces a seasonal variation of the pollution on the insulator surfaces. The performance of the insulator itself is not altered significantly by the presence of dry contaminant because the electrical strength of a dry polluted insulator is close to that of a c1ean insulator. The pollutant particles are of both soluble and non soluble nature and contaminates the insulator surfaces.
ii) Porcelain and glass are easily wetable. Moisture in the form of fog, mist, drizzle,
light rain or dew impinging on the insulator surface wets the pollution layer, dissolving the salts and soluble electrolytes produce a thin conducting layer on the insulator surface.
iii) Wetting of the contamination layer and consequent formation of a conductive
layer on the insulator surface causes flow of leakage current through the surface when the insulator is under energized state. The leakage current flow generates heat due to I2R losses and it heats the conductive layer. Surface deposit and wetting of deposit is not uniform. In the area of higher current (density around pin) the heat dissipated would be greater and therefore moisture dries more rapidly at these locations leading to the formation of dry bands. These dry bands have higher resistance than of other areas which are still moist. Due to the high resistance, the voltage drop across the dry band also would be more and sometimes become sufficient enough to create an electric arc across the most stressed dry band. Arc short circuit the dry band and heat generated keeps the bands dry and contributes to the overall drying process. Due to short circuiting by the arc the resistance of the dry band is quite low and therefore the leakage current increases further and leading to formation of other dry bands. Arc propagates along the insulator surface. In many cases arc extinguishes while in some cases flashover of insulator unit ( unit 6) take place and the line trips.
![Page 128: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/128.jpg)
Fig-6 :Flashover of a single insulator unit under pollution
v) When one insulator unit has flashed over, as explained above, the leakage current flow along other insulator units in the string increases and the dry band arcing gets accelerates and progresses to other insulator units leading to arc cascading on the complete insulator string resulting in insulator string flashover ( figure 7) and line tripping.
![Page 129: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/129.jpg)
Fig -7 : Complete Flashover of an Insulator String under Pollution
6.7 It has been observed that DC flashover voltages are lower than the AC under the same
operating conditions. More pollutants are attracted to an insulator under DC voltage than AC and it is higher on positive polarity. Also, due to absence of current zero in DC, the propagation of arc is easier than in AC and its arc quenching is more difficult.
6.8 Once a pollution flashover takes place on a string, it can repeat. As such wherever
pollution flashover is observed at any location in a day of heavy fog that location be considered as of concern.
6.9 The severity (degree) of the pollution is characterized by the equivalent salt deposit
density (ESDD). It is measured by periodically washing down the pollution from selected insulators with distilled water and measuring the conductivity of the collected water by determining and equivalent amount of salt in mg., which produces the same conductivity. This value is divided by the surface area of the insulator from where the pollution was washed to determine the applicable ESDD level.
![Page 130: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/130.jpg)
6.9.1 Typical ranges for pollution severity in terms of ESDD (in mg/cm2 of insulated surface) for inland pollution and salinity (in kg/cum) as provided in IEC 60815 “Guide For the Selection of Insulators in Polluted Conditions” is as under.
Table - Pollution levels and creepage distances
Pollution level
Equivalent salt deposit density
Salt fog method
Minimum nominal specific creepage distance
Category
(mg/sq. cms) (kg/cub.meters) (mm/kV) Light < 0.06 < 14 16 Medium > 0.06 & < 0.20 > 14& < 40 20 Heavy > 0.20 & < 0.60 > 40 &< 160 25 Very heavy
>0.60 > 160 31
Notes: 1.This table is based on table II & III of IEC – 60815 with appropriate changes
made by the committee. 2. For actual creepage distance manufacturing tolerances, as permissible under
IEC-273, 305,433 or 730, is applicable. 2. Specific creepage distance in mm/kV is ratio of creepage distance measured
between phase to earth and r.m.s. phase to phase value of highest voltage for the equipment / line.
3. In case of exceptionally high pollution level, a specific nominal creepage distance higher than 31 kV/mm may be adopted based on service experience and /or on laboratory test results however before that practicability of washing or greasing may be considered.
4. Specific creepage distance less than 16 mm/kV is not recommended by the Committee.
![Page 131: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/131.jpg)
Date Time DATE TIME
1 220 Ablowal - Bahadurgarh 1 1-Jan-10 22:30:00 2-Jan-10 23:10 Trip
2 220 Muradnagar - Baraut 2-Jan-10 0:03:00 2-Jan-10 17:35:00 Trip
3 220 Malerkotla - ALMOH 1 2-Jan-10 0:10:00 2-Jan-10 1:40:00 Trip
4 220 Muradnagar - Shamli 2-Jan-10 0:11:00 2-Jan-10 18:18:00 Trip
5 220 Panipat - Narela 3 2-Jan-10 0:15:45 2-Jan-10 17:46:00 Trip
6 220 Muradnagar - Khurja 2-Jan-10 0:17:00 2-Jan-10 12:12:00 Trip
7 220 Gobindgarh - Ablowal 1 2-Jan-10 0:20:00 2-Jan-10 11:25:00 Trip
8 220 Muradnagar - Shahibabad 2 2-Jan-10 0:25:00 2-Jan-10 12:18:00 Trip
9 220 Panipat - Narela 1 2-Jan-10 0:39:26 2-Jan-10 0:39:26 A/R
10 220 Jind - Hisar 1 2-Jan-10 0:40:00 2-Jan-10 17:10:00 Trip
11 220 Nissing - Salimpur 1 2-Jan-10 0:40:00 4-Jan-10 0:40:00 Trip
12 220 Panipat - Narela 2 2-Jan-10 0:41:47 2-Jan-10 0:41:47 A/R
13 220 Panipat - Narela 2 2-Jan-10 0:41:47 2-Jan-10 0:41:47 A/R
14 220 Panipat - Narela 1 2-Jan-10 0:41:52 2-Jan-10 0:41:52 A/R
15 220 Panipat - Narela 1 2-Jan-10 0:43:27 2-Jan-10 0:43:27 A/R
16 220 Panipat - Narela 2 2-Jan-10 0:44:24 2-Jan-10 0:44:24 Trip
17 220 Pehowa - Kaithal 1 2-Jan-10 0:45:00 2-Jan-10 0:45:00 Trip
18 220 Panipat - Narela 1 2-Jan-10 0:46:07 2-Jan-10 0:46:07 A/R
19 220 Panipat - Narela 1 2-Jan-10 0:46:08 2-Jan-10 19:22:00 Trip
20 220 Muradnagar -Shahibabad 1 2-Jan-10 0:54:00 2-Jan-10 8:43:00 Trip
21 220 Ch. Dadri - Panipat 1 2-Jan-10 0:59:47 2-Jan-10 1:49:54 Trip
22 220 Panipat - Narela 3 2-Jan-10 1:01:05 2-Jan-10 17:46:00 Trip
23 220 Rajpura - Bahadurgarh 1 2-Jan-10 1:05:00 2-Jan-10 2:05:00 Trip
24 220 Rajpura - Fagganmajra 1 2-Jan-10 1:05:00 2-Jan-10 6:30:00 Trip
25 220 Ganguwal - Mohali 1 2-Jan-10 1:05:00 2-Jan-10 2:05:00 Trip
26 220 RTP - Mohali 1 2-Jan-10 1:05:00 2-Jan-10 2:42:00 Trip
27 220 RTP - Mohali 2 2-Jan-10 1:05:00 2-Jan-10 2:55:00 Trip
28 220 Bawana - DSIDC 1 2-Jan-10 1:06:00 2-Jan-10 1:17:00 Trip
29 220 Ballabgarh Samaypur 1 2-Jan-10 1:07:06 2-Jan-10 1:45:56 Trip
30 220 Mandola - Narela 1 2-Jan-10 1:10:00 2-Jan-10 7:02:00 Trip
31 220 Muradnagar Sikandrabad 2-Jan-10 1:13:00 2-Jan-10 13:43:00 Trip
32 220 G.Noida Noida 1 2-Jan-10 1:15:00 2-Jan-10 16:58:00 Trip
33 220 Bawana - DSIDC 1 2-Jan-10 1:23:00 2-Jan-10 10:20:00 Trip
34 220 Nunamajra - DaultaBad 2 2-Jan-10 1:24:00 2-Jan-10 13:45:00 Trip
35 220 Panipat - Thermal 3 2-Jan-10 1:26:12 2-Jan-10 1:26:12 A/R
36 220 Ganguwal - Jamalpur 2 2-Jan-10 1:28:20 2-Jan-10 1:29:00 A/R
37 220 Bawana - DSIDC 2 2-Jan-10 1:29:00 2-Jan-10 10:20:00 Trip
38 220 Safidon - Narwana 2 2-Jan-10 1:35:00 3-Jan-10 1:10:00 Trip
39 220 Nissing - Salimpur 2 2-Jan-10 1:35:00 2-Jan-10 18:15:00 Trip
40 220 Mandola - Narela 2 2-Jan-10 1:36:00 Trip
TRIPPING DETAIL OF 220kV TRANSMISSION LINES IN NORTHERN REGION ON 2nd JANUARY 2010
Sr. No kVDate & Time of Tripping /
Auto Reclose Time of RestorationName of Line Trip or Auto Reclose(A/R)
Chapter- 5 _ ANNEXE - 5/I (page 1 of 8)
![Page 132: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/132.jpg)
Date Time DATE TIME
41 220 Jamalpur - Dhandari Kalan 1 2-Jan-10 1:37:00 Trip
42 220 Jamalpur - Dhandari Kalan 2 2-Jan-10 1:37:00 Trip
43 220 Rohtak - PTPS 2 2-Jan-10 1:40:00 2-Jan-10 17:15:00 Trip
44 220 PTPS - Nissing 1 2-Jan-10 1:42:00 2-Jan-10 16:00:00 Trip
45 220 Jind - Hisar 1 2-Jan-10 1:43:00 2-Jan-10 17:10:00 Trip
46 220 Kaithal - Nissing 1 2-Jan-10 1:45:00 2-Jan-10 15:15:00 Trip
47 220 Kaithal - Nissing 2 2-Jan-10 1:45:00 3-Jan-10 18:55:00 Trip
48 220 Muradnagar - Loni 2-Jan-10 1:50:00 2-Jan-10 3:16:00 Trip
49 220 Rohtak - PTPS 1 2-Jan-10 1:50:00 2-Jan-10 7:52:00 Trip
50 220 PTPS - Sonipat 1 2-Jan-10 1:50:00 2-Jan-10 10:25 Trip
51 220 Narwana - Safidon 1 2-Jan-10 1:50:00 2-Jan-10 0:20:00 Trip
52 220 PTPS - Safidon 1 2-Jan-10 1:50:00 2-Jan-10 21:20:00 Trip
53 220 PTPS - Safidon 2 2-Jan-10 1:50:00 2-Jan-10 3:36:00 Trip
54 220 PTPS - Safidon 3 2-Jan-10 1:50:00 2-Jan-10 15:25:00 Trip
55 220 Safidon - Jind 1 2-Jan-10 1:50:00 2-Jan-10 13:40:00 Trip
56 220 Mandola - Gopalpur 1 2-Jan-10 1:50:00 2-Jan-10 2:02:00 Trip
57 220 Bawana - Najafgarh 2 2-Jan-10 1:50:00 2-Jan-10 2:37:00 Trip
58 220 Gobindgarh - Ablowal 2 2-Jan-10 1:50:00 2-Jan-10 11:25:00 Trip
59 220 Ch. Dadri - Panipat 1 2-Jan-10 1:50:27 2-Jan-10 1:50:00 A/R
60 220 Ch. Dadri - Panipat 1 2-Jan-10 1:51:30 2-Jan-10 18:59:00 Trip
61 220 Jind - Hisar 2 2-Jan-10 1:54:00 2-Jan-10 3:24:00 Trip
62 220 G1 - RTP 4 2-Jan-10 1:55:00 Trip
63 220 Jind - Saffidon 1 2-Jan-10 1:59:00 2-Jan-10 13:20:00 Trip
64 220 Ballabgarh - Samaypur 1 2-Jan-10 2:01:46 2-Jan-10 2:06:00 Trip
65 220 Malerkotla - Almoh 1 2-Jan-10 2:05:00 3-Jan-10 18:53:00 Trip
66 220 Mandola - Gopalpur 1 2-Jan-10 2:06:00 2-Jan-10 8:49:00 Trip
67 220 Dhulkote Panipat 2 2-Jan-10 2:07:32 2-Jan-10 2:23:14 Trip
68 220 Dhulkote Panipat 1 2-Jan-10 2:07:32 2-Jan-10 19:55:00 TRIP
69 220 Nunamajra Bahadurgarh(PG) 1 2-Jan-10 2:07:00 2-Jan-10 3:05:00 Trip
70 220 Nunamajra Bahadurgarh(PG) 2 2-Jan-10 2:08:00 2-Jan-10 2:53:00 Trip
71 220 Kaithal Narwana 2 2-Jan-10 2:10:00 2-Jan-10 17:05:00 Trip
72 220 Premnagar Bapora 1 2-Jan-10 2:11:00 4-Jan-10 16:26:00 Trip
73 220 Bawana - Shalimarbagh 2 2-Jan-10 2:11:00 2-Jan-10 2:23:00 Trip
74 220 Bawana - Shalimarbagh 1 2-Jan-10 2:12:00 2-Jan-10 2:21:00 Trip
75 220 Bawana - Rohini 2 2-Jan-10 2:14:00 2-Jan-10 11:08:00 Trip
76 220 Badshahpur - Pali 1 2-Jan-10 2:15:00 2-Jan-10 12:55:00 Trip
77 220 Bawana - Rohini 1 2-Jan-10 2:18:00 2-Jan-10 10:36:00 Trip
78 220 G1- RTP 1 2-Jan-10 2:23:00 Trip
79 220 Kaithal - Narwana 1 2-Jan-10 2:24:00 2-Jan-10 17:00:00 Trip
80 220 Sec 52 - Pali 1 2-Jan-10 2:25:00 2-Jan-10 11:10:00 Trip
Time of RestorationTrip or Auto Reclose(A/R)
TRIPPING DETAIL OF 220kV TRANSMISSION LINES IN NORTHERN REGION ON 2nd JANUARY 2010
Sr. No kV Name of LineDate & Time of Tripping /
Auto Reclose
Chapter - 5 _ ANNEXE -5/I (page 2 of 8)
![Page 133: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/133.jpg)
Date Time DATE TIME
81 220 Bamnauli - Najafgarh 1 2-Jan-10 2:25:00 2-Jan-10 5:06:00 Trip
82 220 Bamnauli - Najafgarh 2 2-Jan-10 2:25:00 2-Jan-10 5:06:00 Trip
83 220 Bawana - Shalimarbagh 2 2-Jan-10 2:26:00 2-Jan-10 7:40:00 Trip
84 220 Bawana - Najafgarh 2 2-Jan-10 2:36:00 2-Jan-10 10:47:00 Trip
85 220 Dhulkote - Panipat 2 2-Jan-10 2:27:00 2-Jan-10 20:00:00 Trip
86 220 Panipat - Thermal 2 2-Jan-10 2:29:56 2-Jan-10 4:13:00 Trip
87 220 Samaypur - Badshahpur 2 2-Jan-10 2:33:57 Trip
88 220 Kurukshetra - Panipat 1 2-Jan-10 2:36:17 2-Jan-10 18:29:00 Trip
89 220 Ballabgarh - Samaypur 2 2-Jan-10 2:39:46 2-Jan-10 6:05:00 Trip
90 220 Badshahpur - Samaypur 2 2-Jan-10 2:33:00 2-Jan-10 18:46:00 Trip
91 220 Mandola - Gopalpur 2 2-Jan-10 2:48:00 2-Jan-10 8:28:00 Trip
92 220 Kaithal - Kaithal(PG) 2 2-Jan-10 2:35:00 2-Jan-10 17:50:00 Trip
93 220 Badshahpur - Pali 2 2-Jan-10 2:40:00 2-Jan-10 12:55:00 Trip
94 220 Premnagar - Bapora 1 2-Jan-10 2:50:00 2-Jan-10 11:17:00 Trip
95 220 Premnagar - Bapora 2 2-Jan-10 2:50:00 2-Jan-10 11:17:00 Trip
96 220 Malerkotla - Gobindgarh 1 2-Jan-10 2:50:00 Trip
97 220 G1 - RTP 1 2-Jan-10 2:51:00
98 220 Bhiwani - Bapora 1 2-Jan-10 2:52:00 2-Jan-10 12:01:00 Trip
99 220 GNDTP - Mukatsar 2 2-Jan-10 2:53:00 Trip
100 220 Bhiwani Bapora 2 2-Jan-10 2:53:00 2-Jan-10 12:21:00 Trip
101 220 Bawana - Shalimarbagh 1 2-Jan-10 2:54:00 2-Jan-10 9:38:00 Trip
102 220 Bawana - Shalimarbagh 2 2-Jan-10 2:54:00 2-Jan-10 7:43:00 Trip
103 220 Jamsher - RTP 1 2-Jan-10 2:54:00
104 220 Hisar-IA Hisar (BBMB) 2 2-Jan-10 2:55:00 2-Jan-10 8:30:00 Trip
105 220 Pehowa Kaithal 2 2-Jan-10 2:55:00 2-Jan-10 7:20:00 Trip
106 220 Ganguwal - Mohali 1 2-Jan-10 2:55:00 2-Jan-10 9:50:00 Trip
107 220 Rajpura - Mohali 1 2-Jan-10 2:55:00 2-Jan-10 14:25:00 Trip
108 220 Rajpura - Mohali 2 2-Jan-10 2:55:00 2-Jan-10 14:25:00 Trip
109 220 Kaithal Kaithal(PG) 1 2-Jan-10 2:58:00 2-Jan-10 7:33:00 Trip
110 220 Bhakra - Mahilpur 1 2-Jan-10 3:01:00 Trip
111 220 Hisar(PG) - Fatehabad 2 2-Jan-10 3:02:00 2-Jan-10 3:55:00 Trip
112 220 Ganguwal - Jamalpur 1 2-Jan-10 3:04:54 2-Jan-10 11:41:00 Trip
113 220 Ganguwal - Jamalpur 2 2-Jan-10 3:05:03 2-Jan-10 10:14:35 Trip
114 220 Ballabgarh - Ch. Dadri 1 2-Jan-10 3:05:14 2-Jan-10 3:11:00 Trip
115 220 Muradnagar - Nara 2-Jan-10 3:06:00 2-Jan-10 3:46:00 Trip
116 220 Bamnauli - Najafgarh 1 2-Jan-10 3:12:00 2-Jan-10 3:27:00 Trip
117 220 Ballabgarh - Ch. Dadri 1 2-Jan-10 3:12:59 2-Jan-10 3:12:59 A/R
118 220 Bhiwani - Ch. Dadri 3 2-Jan-10 3:17:06 2-Jan-10 17:00:00 Trip
119 220 Ballabgarh - Samaypur 1 2-Jan-10 3:17:08 2-Jan-10 15:24:00 Trip
120 220 Bhiwani - Ch. Dadri 4 2-Jan-10 3:18:09 2-Jan-10 4:46:00 Trip
Time of RestorationTrip or Auto Reclose(A/R)Sr. No kV Name of Line
Date & Time of Tripping / Auto Reclose
TRIPPING DETAIL OF 220kV TRANSMISSION LINES IN NORTHERN REGION ON 2nd JANUARY 2010
Chapter - 5 _ ANNEXE -5/I (page 3 of 8)
![Page 134: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/134.jpg)
Date Time DATE TIME
121 220 Badshahpur - Samaypur 1 2-Jan-10 3:24:00 2-Jan-10 18:46:00 Trip
122 220 Jind - Saffidon 2 2-Jan-10 3:25:00 2-Jan-10 12:55:00 Trip
123 220 Jind - PTPS 1 2-Jan-10 3:25:00 2-Jan-10 12:55:00 Trip
124 220 Jind - PTPS 2 2-Jan-10 3:25:00 2-Jan-10 16:15:00 Trip
125 220 Jind - Hisar 2 2-Jan-10 3:27:00 2-Jan-10 19:55 Trip
126 220 Hisar - Narwana 1 2-Jan-10 3:27:00 2-Jan-10 5:20:00 Trip
127 220 Bhiwani - Hisar 2 2-Jan-10 3:28:38 2-Jan-10 12:48:00 Trip
128 220 Sec 52 - Pali 2 2-Jan-10 3:30:00 2-Jan-10 24:00 Trip
129 220 Bamnauli - Najafgarh 1 2-Jan-10 3:35:00 2-Jan-10 10:28:00 Trip
130 220 Nunamajra - Bahadurgarh(PG) 1 2-Jan-10 3:37:00 2-Jan-10 7:37:00 Trip
131 220 Nunamajra - Daultabad 1 2-Jan-10 3:37:00 2-Jan-10 19:02:00 Trip
132 220 Hisar - Hisar(I/A) 1 2-Jan-10 3:44:00 2-Jan-10 3:57:00 Trip
133 220 Hisar - Hisar(I/A) 2 2-Jan-10 3:44:00 2-Jan-10 3:57:00 Trip
134 220 Panipat - Thermal 3 2-Jan-10 3:46:00 2-Jan-10 1:27:00 A/R
135 220 Hisar - Khetri 1 2-Jan-10 3:46:12 2-Jan-10 9:28:00 Trip
136 220 PTPS - Sonipat 2 2-Jan-10 3:50:00 2-Jan-10 14:40:00 Trip
137 220 Narwana - Hisar 1 2-Jan-10 3:50:00 4-Jan-10 20:30:00 Trip
138 220 Mandola - Wazirabad 4 2-Jan-10 3:51:00 2-Jan-10 23:55:00 Trip
139 220 Ch Dadri - Samaypur 1 2-Jan-10 3:57:28 2-Jan-10 7:40:00 Trip
140 220 Matana - Bhuna 1 2-Jan-10 4:13:00 2-Jan-10 18:29 Trip
141 220 Narwana - Bhuna 1 2-Jan-10 4:13:00 2-Jan-10 18:05:00 Trip
142 220 Panipat - Thermal 3 2-Jan-10 4:14:00 2-Jan-10 12:00:00 Trip
143 220 Nunamajra - PGCIL 2 2-Jan-10 4:15:00 2-Jan-10 7:03:00 Trip
144 220 Patparganj - IP 1 2-Jan-10 4:15:00 2-Jan-10 4:21:00 Trip
145 220 Patparganj - IP 2 2-Jan-10 4:15:00 2-Jan-10 4:21:00 Trip
146 220 Patparganj - Geeta Colony 2 2-Jan-10 4:15:00 2-Jan-10 4:23:00 Trip
147 220 Ballabgarh - Ch. Dadri 1 2-Jan-10 4:21:00 2-Jan-10 5:43:00 Trip
148 220 Hisar - Sangrur 1 2-Jan-10 4:25:00 2-Jan-10 16:01:00 Trip
149 220 Hisar - Sangrur 2 2-Jan-10 4:25:00 2-Jan-10 5:29:00 Trip
150 220 Bhiwani - Ch. Dadri 1 2-Jan-10 4:28:00 2-Jan-10 5:32:00 Trip
151 220 Bhiwani - Hisar 1 2-Jan-10 4:28:00 2-Jan-10 9:12:00 Trip
152 220 Bhiwani - Hisar 2 2-Jan-10 4:29:00 2-Jan-10 4:36:00 Trip
153 220 Bhakra - Jamalpur 1 2-Jan-10 4:29:00 2-Jan-10 5:07:00 Trip
154 220 Bhiwani - Hisar 2 2-Jan-10 4:37:00 2-Jan-10 Trip
155 220 220 KV Panipat - Thermal - III 3 2-Jan-10 4:38:00 2-Jan-10 4:38:00 Trip
156 220 Bhiwani - Hisar 1 2-Jan-10 4:42:00 2-Jan-10 4:52:00 Trip
157 220 220 KV Panipat - Thermal - III 3 2-Jan-10 4:47:00 2-Jan-10 17:47:00 Trip
158 220 Bhiwani - Ch. Dadri 2 2-Jan-10 4:48:00 2-Jan-10 6:11:00 Trip
159 220 Bhiwani - Hisar 1 2-Jan-10 4:53:00 2-Jan-10 9:11:00 Trip
160 220 Ballabgarh - Ch. Dadri 1 2-Jan-10 4:57:00 2-Jan-10 Trip
TRIPPING DETAIL OF 220kV TRANSMISSION LINES IN NORTHERN REGION ON 2nd JANUARY 2010
Sr. No kV Name of LineDate & Time of Tripping /
Auto Reclose Time of RestorationTrip or Auto Reclose(A/R)
Chapter - 5 _ ANNEXE -5/I (page 4 of 8)
![Page 135: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/135.jpg)
Date Time DATE TIME
161 220 Jamalpur - Sangrur 2 2-Jan-10 5:07:00 2-Jan-10 5:36:00 Trip
162 220 Bhiwani - Ch. Dadri 4 2-Jan-10 5:09:00 2-Jan-10 5:34:00 Trip
163 220 Bamnauli - Mehrauli 1 2-Jan-10 5:10:00 2-Jan-10 16:44:00 Trip
164 220 Bhiwani Ch. Dadri 3 2-Jan-10 5:19:00 2-Jan-10 5:33:00 Trip
165 220 Patparganj - IP 2 2-Jan-10 5:20:00 2-Jan-10 5:58:00 Trip
166 220 Bhiwani Ch. Dadri 4 2-Jan-10 5:37:00 2-Jan-10 5:44:00 Trip
167 220 Patparganj - IP 1 2-Jan-10 5:40:00 2-Jan-10 5:52:00 Trip
168 220 Patparganj - Geeta Colony 2-Jan-10 5:40:00 2-Jan-10 5:52:00 Trip
169 220 Mandola - Geeta Colony 1 2-Jan-10 5:40:00 2-Jan-10 5:50:00 Trip
170 220 Geeta Colony - Wazirabad 1 2-Jan-10 5:40:00 2-Jan-10 5:52:00 Trip
171 220 Bhiwani Ch. Dadri 1 2-Jan-10 5:43:00 2-Jan-10 5:46:00 Trip
172 220 Pehowa - Shahbad 2 2-Jan-10 5:46:00 2-Jan-10 7:37:00 Trip
173 220 Jorian Shahbad 2 2-Jan-10 5:51:00 2-Jan-10 13:42:00 Trip
174 220 Hisar - Narwana 1 2-Jan-10 5:58:00 4-Jan-10 20:30:00 Trip
175 220 Bhiwani - Ch. Dadri 1 2-Jan-10 5:58:00 2-Jan-10 6:38:00 Trip
176 220 Jamalpur - Sangrur 2 2-Jan-10 6:08:00 2-Jan-10 11:47:00 Trip
177 220 Jamalpur - Sangrur 1 2-Jan-10 6:08:00 2-Jan-10 6:19:00 Trip
178 220 Ablowal - Rajla 2-Jan-10 6:30:00 2-Jan-10 16:35:00 Trip
179 220 Jamalpur Mahilpur 1 2-Jan-10 6:33:00 Trip
180 220 PTPS Nissing 2 2-Jan-10 6:40:00 2-Jan-10 15:40:00 Trip
181 220 Jamalpur - Jalandhar 1 2-Jan-10 6:41:00 2-Jan-10 11:47:00 Trip
182 220 Bhakra - Jamalpur 1 2-Jan-10 6:41:00 2-Jan-10 11:47:00 Trip
183 220 Bamnauli - Najafgarh 1 2-Jan-10 6:47:00 2-Jan-10 8:35:00 Trip
184 220 Bamnauli - Najafgarh 2 2-Jan-10 6:52:00 2-Jan-10 7:35:00 Trip
185 220 Bamnauli - Najafgarh 2 2-Jan-10 6:52:00 2-Jan-10 7:35:00 Trip
186 220 Ballabgarh - Samaypur 2 2-Jan-10 6:52:00 2-Jan-10 7:01:00 Trip
187 220 Ballabgarh - Ch. Dadri 1 2-Jan-10 7:02:00 2-Jan-10 7:16:00 Trip
188 220 Bamnauli - Najafgarh 1 2-Jan-10 7:04:00 2-Jan-10 7:28:00 Trip
189 220 Bamnauli - Najafgarh 2 2-Jan-10 7:04:00 2-Jan-10 7:28:00 Trip
190 220 Kashmiri Gata - Wazirabad 1 2-Jan-10 7:10:00 2-Jan-10 7:19:00 Trip
191 220 Kashmiri Gata - Wazirabad 2 2-Jan-10 7:10:00 2-Jan-10 7:19:00 Trip
192 220 Geeta Colony - Wazirabad 1 2-Jan-10 7:10:00 2-Jan-10 7:21:00 Trip
193 220 Geeta Colony - Wazirabad 2 2-Jan-10 7:10:00 2-Jan-10 7:21:00 Trip
194 220 Geeta Colony - Patparganj 1 2-Jan-10 7:10:00 2-Jan-10 7:21:00 Trip
195 220 Geeta Colony - Patparganj 2 2-Jan-10 7:10:00 2-Jan-10 7:21:00 Trip
196 220 Mandola - Wazirabad 1 2-Jan-10 7:10:00 2-Jan-10 7:23:00 Trip
197 220 Mandola - Wazirabad 2 2-Jan-10 7:10:00 2-Jan-10 7:16:00 Trip
198 220 Mandola - Wazirabad 3 2-Jan-10 7:10:00 2-Jan-10 7:18:00 Trip
199 220 GNDTP Mukatsar 2 2-Jan-10 7:27:00 Trip
200 220 Ch. Dadri - Samaypur 1 2-Jan-10 7:28:00 2-Jan-10 7:40:00 Trip
TRIPPING DETAIL OF 220kV TRANSMISSION LINES IN NORTHERN REGION ON 2nd JANUARY 2010
Sr. No kV Name of LineDate & Time of Tripping /
Auto Reclose Time of RestorationTrip or Auto Reclose(A/R)
Chapter - 5 _ ANNEXE -5/I (page 5 of 8)
![Page 136: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/136.jpg)
Date Time DATE TIME
201 220 Ch. Dadri - Samaypur 1 2-Jan-10 7:28:00 2-Jan-10 7:40:00 Trip
202 220 Mohali - Rajpura 2 2-Jan-10 7:35:00 2-Jan-10 16:35:00 Trip
203 220 GNDTP - Mukatsar 2 2-Jan-10 7:45:00 Trip
204 220 GNDTP - Lehra 2 2-Jan-10 7:57:00 Trip
205 220 Bamnauli -Mehrauli 2 2-Jan-10 8:24:00 2-Jan-10 8:35:00 Trip
206 220 Bhiwani - Ch. Dadri - I 1 2-Jan-10 8:28:00 2-Jan-10 10:52:00 Trip
207 220 Verpal - Wadalagranthian 1 2-Jan-10 10:15:00 2-Jan-10 19:25:00 Trip
208 220 Verpal - Wadalagranthian 2 2-Jan-10 10:15:00 3-Jan-10 13:26:00 Trip
209 220 Ch Dadri - Panipat 1 2-Jan-10 10:56:00 2-Jan-10 18:59:00 Trip
210 220 Shahbad - Pehowa 2 2-Jan-10 11:15:00 2-Jan-10 11:45:00 Trip
211 220 Kaithal - Kaithal(PG) 1 2-Jan-10 11:15:00 3-Jan-10 14:07:00 Trip
TRIPPING DETAIL OF 220kV TRANSMISSION LINES IN NORTHERN REGION ON 2nd JANUARY 2010
Sr. No kV Name of LineDate & Time of Tripping /
Auto Reclose Time of RestorationTrip or Auto Reclose(A/R)
Chapter - 5 _ ANNEXE -5/I (page 6 of 8)
![Page 137: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/137.jpg)
Date Time DATE TIME
1 400 DADRI - MURADNGR 1-Jan-10 22:44:00 2-Jan-10 11:20:00 Trip
2 400 PANKI - MURADNGR 1-Jan-10 23:12:00 2-Jan-10 1:15:00 Trip
3 400 ABDULLAPUR BAWANA - 1 1-Jan-10 23:54:00 1-Jan-10 23:54:00 A/R
4 400 Dehar Panipat - 1 2-Jan-10 0:00:39 2-Jan-10 0:00:39 A/R
5 400 Dehar Panipat - 1 2-Jan-10 0:00:43 2-Jan-10 11:06:00 Trip
6 400 MUZAFNGR-V.PRAYAG-II 2-Jan-10 0:24:00 2-Jan-10 0:24:00 AR
7 400 MUZAFNGR-MATORE 2-Jan-10 0:24:00 2-Jan-10 0047:00 Trip
8 400 AGRA-MURADNGR 2-Jan-10 0:28:00 2-Jan-10 7:26:00 Trip
9 400 BAWANA MANDOLA - 1 2-Jan-10 0:34:00 2-Jan-10 0:34:00 A/R
10 400 ABDULLAPUR BAWANA - 2 2-Jan-10 0:43:00 2-Jan-10 2:18:00 Trip
11 400 MALERKOTLA PATIALA - 1 2-Jan-10 0:53:00 2-Jan-10 0:58:00 A/R
12 400 MALERKOTLA Ludhiana - 1 2-Jan-10 0:55:00 2-Jan-10 0:55:00 A/R
13 400 ABDULLAPUR BAWANA - 1 2-Jan-10 0:56:00 2-Jan-10 0:56:00 A/R
14 400 ABDULLAPUR BAWANA - 1 2-Jan-10 0:58:00 2-Jan-10 8:21:00 Trip
15 400 MALERKOTLA DADRI - 1 2-Jan-10 1:06:00 2-Jan-10 1:06:00 A/R
16 400 BAWANA BAMNAULI - 2 2-Jan-10 1:08:00 2-Jan-10 1:08:00 A/R
17 400 BAMNAULI BAWANA - 1 2-Jan-10 1:10:00 2-Jan-10 1:18:00 Trip
18 400 MUZAFNGR-MATORE 2-Jan-10 1:21:00 2-Jan-10 2:27:00 Trip
19 400 BAMNAULI BAWANA - 1 2-Jan-10 1:26:00 2-Jan-10 1:35:00 Trip
20 400 BAMNAULI BAWANA - 2 2-Jan-10 1:27:00 2-Jan-10 1:27:00 A/R
21 400 BAMNAULI BALLABGARH - 1 2-Jan-10 1:27:00 2-Jan-10 1:42:00 Trip
22 400 MALERKOTLA PATIALA - 1 2-Jan-10 1:30:00 2-Jan-10 1:30:00 A/R
23 400 MALERKOTLA PATIALA - 1 2-Jan-10 1:32:00 2-Jan-10 1:32:00 A/R
24 400 NALAGARH PATIALA - 1 2-Jan-10 1:32:00 2-Jan-10 1:32:00 A/R
25 400 HISAR KAITHAL - 1 2-Jan-10 1:36:00 2-Jan-10 14:31:00 Trip
26 400 BAMNAULI BAWANA - 1 2-Jan-10 1:37:00 2-Jan-10 10:04:00 Trip
27 400 MALERKOTLA PATIALA - 1 2-Jan-10 1:47:00 2-Jan-10 1:47:00 A/R
28 400 Dehar Bhiwani - 1 2-Jan-10 1:51:07 2-Jan-10 7:10:00 Trip
29 400 BAWANA BAMNAULI - 2 2-Jan-10 1:52:00 2-Jan-10 1:52:00 A/R
30 400 MALERKOTLA PATIALA - 1 2-Jan-10 1:52:00 2-Jan-10 1:52:00 A/R
31 400 NALAGARH PATIALA - 1 2-Jan-10 1:52:00 2-Jan-10 1:52:00 A/R
TRIPPING DETAIL OF 400kV TRANSMISSION LINES IN NORTHERN REGION ON 2nd JANUARY 2010
Sr. No kV Name of Line
Date & Time of Tripping / Auto Reclose Time of Restoration Trip or Auto
Reclose(A/R)
Chapter - 5 _ ANNEXE -5/I (page 7 of 8)
![Page 138: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/138.jpg)
Date Time DATE TIME
32 400 BAMNAULI BALLABGARH - 1 2-Jan-10 1:53:00 2-Jan-10 7:25:00 Trip
33 400 BAWANA BAMNAULI - 2 2-Jan-10 1:55:00 2-Jan-10 1:55:00 A/R
34 400 BAWANA BAMNAULI - 2 2-Jan-10 1:57:00 2-Jan-10 1:57:00 A/R
35 400 BAMNAULI BALLABGARH - 2 2-Jan-10 1:57:00 2-Jan-10 2:40:00 Trip
36 400 BAWANA BAMNAULI - 2 2-Jan-10 2:08:00 2-Jan-10 2:08:00 A/R
37 400 BAWANA BAMNAULI - 2 2-Jan-10 2:09:00 2-Jan-10 2:09:00 A/R
38 400 MALERKOTLA PATIALA - 1 2-Jan-10 2:10:00 2-Jan-10 2:10:00 A/R
39 400 NALAGARH PATIALA - 1 2-Jan-10 2:10:00 2-Jan-10 2:10:00 A/R
40 400 BAMNAULI BAWANA - 2 2-Jan-10 2:22:00 2-Jan-10 9:46:00 Trip
41 400 MOGA FATEHABAD - 1 2-Jan-10 2:29:00 2-Jan-10 21:19:00 Trip
42 400 MALERKOTLA PATIALA - 1 2-Jan-10 2:51:00 2-Jan-10 2:51:00 A/R
43 400 NALAGARH PATIALA - 1 2-Jan-10 2:51:00 2-Jan-10 2:51:00 A/R
44 400 BAWANA ABDULLAPUR - 2 2-Jan-10 2:55:00 2-Jan-10 5:29:00 Trip
45 400 BAMNAULI BALLABGARH - 2 2-Jan-10 2:55:00 2-Jan-10 4:22:00 Trip
46 400 ABDULLAPUR BAWANA-II - 2 2-Jan-10 2:55:00 2-Jan-10 5:47:00 Trip
47 400 MOGA Khedar - 1 2-Jan-10 2:56:00 2-Jan-10 11:59:00 Trip
48 400 MALERKOTLA DADRI - 1 2-Jan-10 3:01:00 2-Jan-10 12:28:00 Trip
49 400 MUZAFNGR-MATORE 2-Jan-10 3:02:00 2-Jan-10 3:26:00 Trip
50 400 MUZAFNGR-V.PRAYAG-I 2-Jan-10 3:05:00 2-Jan-10 5:25:00 Trip
51 400 MURADNAGAR-MUZFNGR 2-Jan-10 3:12:00 2-Jan-10 17:42:00 Trip
52 400 MURADNAGAR-ROORKEE 2-Jan-10 3:12:00 2-Jan-10 9:40:00 Trip
53 400 BAWANA MANDOLA - 1 2-Jan-10 3:22:00 2-Jan-10 3:32:00 Trip
54 400 MOGA HISAR - 1 2-Jan-10 3:32:00 2-Jan-10 18:37:00 Trip
55 400 HISAR Bhiwadi - 1 2-Jan-10 4:06:00 2-Jan-10 4:06:00 A/R
56 400 BAWANA MANDOLA - 1 2-Jan-10 4:41:00 2-Jan-10 4:43:00 Trip
57 400 HISAR BHIWADI - 1 2-Jan-10 4:42:00 2-Jan-10 4:42:00 A/R
58 400 HISAR BHIWADI - 1 2-Jan-10 5:42:00 2-Jan-10 16:37:00 Trip
59 400 JALLANDHAR CHAMERA - 2 2-Jan-10 6:35:00 2-Jan-10 6:47:00 Trip
TRIPPING DETAIL OF 400kV TRANSMISSION LINES IN NORTHERN REGION ON 2nd JANUARY 2010
Sr. No kV Name of Line
Date & Time of Tripping / Auto Reclose Time of Restoration Trip or Auto
Reclose(A/R)
Chapter - 5 _ ANNEXE -5/I (page 8 of 8)
![Page 139: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/139.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From RTUS Reporting to SLDCsANNEX-5/II
Part-1
'02-01-2010 '00:00:39.568 DEHAR PS CB F_3(PANPT) STTS OPEN GOOD Valid
'02-01-2010 '00:00:39.578 DEHAR PS CB F_4(PANPT) STTS OPEN GOOD Valid
'02-01-2010 '00:00:39.589 PANIPAT CB F_7(D_THM-2 & DEHAR TIE) STTS OPEN GOOD Valid
'02-01-2010 '00:00:59.105 PONG CB E_04(H01) STTS CLOSED GOOD Valid
'02-01-2010 '00:05:57.120 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '00:05:57.120 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '00:05:59.166 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '00:05:59.166 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '00:10:12.727 MURADNGR-1 CB F_06(AGRA1) STTS CLOSED GOOD Valid
'02-01-2010 '00:11:46.775 MURADNGR-1 CB E_01(SHMLI) STTS OPEN GOOD Valid
'02-01-2010 '00:11:48.599 SAHARANPUR CB E_03(SHMLI-1) STTS OPEN GOOD Valid
'02-01-2010 '00:11:51.976 KHARA CB E_81(H01) STTS OPEN GOOD Valid
'02-01-2010 '00:13:17.005 MUR2N_UP CB E_03(KHURJ-1) STTS OPEN GOOD Valid
'02-01-2010 '00:13:17.043 KHURJA CB E_01(MUR2N-1) STTS OPEN GOOD Valid
'02-01-2010 '00:13:17.854 MUR2N_UP CB E_03(KHURJ-1) STTS CLOSED GOOD Valid
'02-01-2010 '00:14:02.444 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '00:14:05.464 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '00:15:45.632 PANIPAT CB E_07(NAREL-3) STTS BETWEEN Bad Valid
'02-01-2010 '00:15:46.376 PANIPAT CB E_07(NAREL-3) STTS OPEN GOOD Valid
'02-01-2010 '00:15:54.693 BHIWANI CB F_5(DEHAR BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 '00:16:14.809 BHIWANI CB F_2(DEHAR BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 '00:17:39.595 DEHAR PS CB F_7(BHIWN) STTS CLOSED GOOD Valid
'02-01-2010 '00:17:43.653 DEHAR PS CB F_8(BHIWN) STTS CLOSED GOOD Valid
'02-01-2010 '00:18:17.867 GRKPR_PG CB F_4(MUZAF-2 BUS-1) STTS OPEN BAD TIME
'02-01-2010 '00:18:19.869 GRKPR_PG CB F_5(MUZAF-2BUS-2) STTS OPEN BAD TIME
'02-01-2010 '00:18:21.890 GRKPR_PG CB (F_51) MUZ1 TCSC STTS CLOSED BAD TIME
'02-01-2010 '00:18:22.921 GRKPR_PG CB (F_50) MUZ1 FSC STTS CLOSED BAD TIME
'02-01-2010 '00:18:23.961 GRKPR_PG CB (F_50) MUZ1 FSC STTS OPEN BAD TIME
'02-01-2010 '00:18:24.869 GRKPR_PG CB F_5(MUZAF-2BUS-2) STTS OPEN BAD TIME
'02-01-2010 '00:18:25.083 GRKPR_PG CB F_5(MUZAF-2BUS-2) STTS CLOSED BAD TIME
'02-01-2010 '00:18:26.106 GRKPR_PG CB F_4(MUZAF-2 BUS-1) STTS CLOSED BAD TIME
'02-01-2010 '00:18:26.867 GRKPR_PG CB F_4(MUZAF-2 BUS-1) STTS OPEN BAD TIME
'02-01-2010 '00:18:27.140 GRKPR_PG CB F_4(MUZAF-2 BUS-1) STTS OPEN BAD TIME
'02-01-2010 '00:18:28.140 GRKPR_PG CB F_5(MUZAF-2BUS-2) STTS OPEN BAD TIME
'02-01-2010 '00:18:30.211 GRKPR_PG CB F_4(MUZAF-2 BUS-1) STTS OPEN BAD TIME
'02-01-2010 '00:18:30.213 GRKPR_PG CB F_5(MUZAF-2BUS-2) STTS OPEN BAD TIME
'02-01-2010 '00:18:37.854 BRELY_PG CB F_7(MANDU-1 BUS-1) STTS OPEN
'02-01-2010 '00:18:37.856 BRELY_PG CB F_8(MANDU-1 & REACTOR TI STTS OPEN
'02-01-2010 '00:18:39.066 BRELY_PG CB F_7(MANDU-1 BUS-1) STTS CLOSED
'02-01-2010 '00:18:40.187 BRELY_PG CB F_8(MANDU-1 & REACTOR TI STTS CLOSED
'02-01-2010 '00:18:46.890 GRKPR_PG CB (F_51) MUZ1 TCSC STTS CLOSED BAD TIME
'02-01-2010 '00:19:33.935 MUR2N_UP CB E_03(KHURJ-1) STTS OPEN GOOD Valid
'02-01-2010 '00:20:33.085 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '00:20:34.623 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '00:21:45.923 BRELY_PG CB F_8(MANDU-1 & REACTOR TI STTS OPEN
'02-01-2010 '00:21:45.938 BRELY_PG CB F_7(MANDU-1 BUS-1) STTS OPEN
'02-01-2010 '00:21:46.235 BRELY_PG CB F_7(MANDU-1 BUS-1) STTS OPEN
'02-01-2010 '00:21:46.244 BRELY_PG CB F_8(MANDU-1 & REACTOR TI STTS OPEN
'02-01-2010 '00:21:47.135 BRELY_PG CB F_7(MANDU-1 BUS-1) STTS CLOSED
'02-01-2010 '00:21:48.259 BRELY_PG CB F_8(MANDU-1 & REACTOR TI STTS CLOSED
'02-01-2010 '00:23:05.921 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '00:23:32.615 NUNAMAJRA CB E_10(BHADR-2) STTS BETWEEN Bad Valid
'02-01-2010 '00:24:08.200 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '00:24:08.506 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '00:24:28.180 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '00:25:00.280 MURADNGR-1 CB E_08(SHIBD-2) STTS OPEN GOOD Valid
'02-01-2010 '00:25:00.289 SAHIBABAD CB E_06(MUR1N-2) STTS OPEN GOOD Valid
'02-01-2010 '00:25:25.095 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '00:25:25.095 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '00:25:33.166 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '00:25:33.166 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '00:27:05.040 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '00:27:05.077 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '00:28:46.628 MURADNGR-1 CB F_06(AGRA1) STTS OPEN GOOD Valid
'02-01-2010 '00:28:47.379 MURADNGR-1 CB F_06(AGRA1) STTS CLOSED GOOD Valid
'02-01-2010 '00:28:47.418 MURADNGR-1 CB F_06(AGRA1) STTS BETWEEN Bad Valid
'02-01-2010 '00:28:51.207 MURADNGR-1 CB F_06(AGRA1) STTS OPEN GOOD Valid
'02-01-2010 '00:29:52.726 BRELY_PG CB F_8(MANDU-1 & REACTOR TI STTS OPEN
'02-01-2010 '00:29:52.759 BRELY_PG CB F_7(MANDU-1 BUS-1) STTS OPEN
'02-01-2010 '00:29:52.775 BRELY_PG CB F_7(MANDU-1 BUS-1) STTS OPEN
'02-01-2010 '00:29:52.776 BRELY_PG CB F_8(MANDU-1 & REACTOR TI STTS OPEN
'02-01-2010 '00:29:53.934 BRELY_PG CB F_7(MANDU-1 BUS-1) STTS CLOSED
'02-01-2010 '00:29:55.060 BRELY_PG CB F_8(MANDU-1 & REACTOR TI STTS CLOSED
'02-01-2010 '00:30:25.307 BHAKRA DAM CB E_15(H04) STTS BETWEEN Bad Valid
'02-01-2010 '00:32:10.413 PANIPAT CB E_13(NAREL-1) STTS BETWEEN Bad Valid
'02-01-2010 '00:32:11.255 PANIPAT CB E_13(NAREL-1) STTS CLOSED GOOD Valid
'02-01-2010 '00:36:02.597 DEHAR PS CB F_3(PANPT) STTS CLOSED GOOD Valid
'02-01-2010 '00:36:08.740 DEHAR PS CB F_4(PANPT) STTS CLOSED GOOD Valid
'02-01-2010 '00:37:43.726 FATEHPUR CB E_09(ALHAC) STTS OPEN GOOD InvRTU
1 of 18
Chapter - 5 _ ANNEXE -5/II (page 1 of 18)
![Page 140: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/140.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From RTUS Reporting to SLDCsANNEX-5/II
Part-1
'02-01-2010 '02:38:58.234 DHULEKOTE CB E_4 STTS OPEN GOOD Valid
'02-01-2010 '02:38:58.246 DHULEKOTE LINE E_DHULK_PANPT1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '02:39:46.733 SAMAYUR CB E_02(BLBGH-2) STTS OPEN GOOD Valid
'02-01-2010 '02:41:29.588 NISSING CB E_11(SALEM-2) STTS BETWEEN Bad Valid
'02-01-2010 '02:41:41.050 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '02:41:41.050 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '02:41:43.156 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '02:41:43.156 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '02:44:14.894 SUNAM CB E_3(DHURI-1) STTS CLOSED GOOD Valid
'02-01-2010 '02:45:38.075 DHANDARI CB E_2(LALTN-2) STTS CLOSED GOOD Valid
'02-01-2010 '02:46:19.045 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '02:46:57.296 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '02:47:10.668 SAMAYUR CB E_01(BLBGH-1) STTS CLOSED GOOD Valid
'02-01-2010 '02:47:23.921 SIMBHOLI CB E_03(SHATB-1) STTS OPEN GOOD Valid
'02-01-2010 '02:47:23.927 SHATABDINAGAR CB E_03(SBHLI-1) STTS OPEN GOOD Valid
'02-01-2010 '02:47:48.990 BALLABGARH CB E_09(SMYUR-1) STTS CLOSED GOOD Valid
'02-01-2010 '02:52:54.020 NUNAMAJRA CB E_12(ROTAK-2) STTS OPEN GOOD Valid
'02-01-2010 '02:53:27.132 SAHNEWAL CB E_07(RAILY-2) STTS BETWEEN Bad Valid
'02-01-2010 '02:53:38.997 KAITHAL CB E_10(NISNG-1) STTS CLOSED GOOD Valid
'02-01-2010 '02:54:29.547 ABLOWAL CB E_6(PATRA) STTS CLOSED GOOD Valid
'02-01-2010 '02:55:09.408 PEHOWA CB E_09(KTHAL-2) STTS BETWEEN Bad Valid
'02-01-2010 '02:55:09.450 KAITHAL CB E_11(KAITH-1) STTS OPEN GOOD Valid
'02-01-2010 '02:55:10.456 PEHOWA CB E_09(KTHAL-2) STTS CLOSED GOOD Valid
'02-01-2010 '02:56:29.278 GORAYA LINE E_GORAY_JMSHR PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '02:56:29.309 GORAYA CB E_51(JMSHR) STTS OPEN GOOD Valid
'02-01-2010 '02:56:51.843 NUNAMAJRA CB E_11(ROTAK-1) STTS OPEN GOOD Valid
'02-01-2010 '02:57:09.090 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '02:57:09.090 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '02:57:11.166 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '02:57:11.166 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '02:57:37.075 NUNAMAJRA CB E_10(BHADR-2) STTS CLOSED GOOD Valid
'02-01-2010 '02:58:57.744 NARWANA LD E_BHUNA_NARWN PRT PROTECTION OK GOOD Valid
'02-01-2010 '02:58:57.779 NARWANA LD E_BHUNA_NARWN PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '02:58:58.170 NARWANA LD E_BHUNA_NARWN PRT PROTECTION OK GOOD Valid
'02-01-2010 '02:58:58.195 NARWANA LD E_BHUNA_NARWN PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '02:58:58.221 NARWANA LD E_BHUNA_NARWN PRT PROTECTION OK Bad Valid
'02-01-2010 '02:59:04.431 NARWANA LD E_BHUNA_NARWN PRT PROTECTION OK GOOD Valid
'02-01-2010 '02:59:05.760 NUNAMAJRA CB E_09(BHADR-1) STTS CLOSED GOOD Valid
'02-01-2010 '02:59:37.061 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '02:59:37.061 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '02:59:39.166 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '02:59:39.166 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '02:59:43.832 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '02:59:45.842 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '03:00:01.140 GORAYA CB E_52(T4) STTS OPEN GOOD Valid
'02-01-2010 '03:00:32.467 NARWANA CB E_03(BHUNA) STTS CLOSED GOOD Valid
'02-01-2010 '03:00:49.115 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '03:00:49.115 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '03:00:51.156 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '03:00:51.156 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '03:00:53.329 PIPLI CB E_02(PANPT) STTS INVALID Bad Valid
'02-01-2010 '03:00:53.634 PIPLI CB E_02(PANPT) STTS CLOSED GOOD Valid
'02-01-2010 '03:01:06.824 GORAYA CB E_50(GGSTP) STTS OPEN GOOD Valid
'02-01-2010 '03:01:39.286 BHIWANI XFMR_P FE_T1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:01:39.297 BHIWANI CB E_06(T1) STTS BETWEEN Bad Valid
'02-01-2010 '03:01:39.325 BHIWANI CB F_1(ICT-1 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '03:01:39.332 BHIWANI CB F_4(ICT-1 BUS2) STTS OPEN GOOD Valid
'02-01-2010 '03:01:41.459 SANGRUR CB E_04(HISAR-2) STTS OPEN GOOD Valid
'02-01-2010 '03:01:41.607 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:01:41.895 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:01:42.061 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:01:42.221 SANGRUR CB E_03(HISAR-1) STTS OPEN GOOD Valid
'02-01-2010 '03:01:42.343 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:01:42.443 JAGADHRI LINE E_JGDRI_PIPLI PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:01:42.456 JAGADHRI CB E_1 STTS BETWEEN Bad Valid
'02-01-2010 '03:01:42.474 JAGADHRI CB E_2 STTS OPEN GOOD Valid
'02-01-2010 '03:01:42.506 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION TRIP Bad Valid
'02-01-2010 '03:01:42.531 JAGADHRI LINE E_JGDRI_PIPLI PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:01:42.573 PIPLI CB E_02(PANPT) STTS INVALID Bad Valid
'02-01-2010 '03:01:42.693 PIPLI CB E_02(PANPT) STTS CLOSED GOOD Valid
'02-01-2010 '03:01:42.732 PIPLI CB E_02(PANPT) STTS OPEN GOOD Valid
'02-01-2010 '03:01:49.216 DEHAR PS XFMR_P FE_T1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:01:49.241 BHAKRA DAM CB E_35(G6) STTS OPEN GOOD Valid
'02-01-2010 '03:01:49.249 DEHAR PS CB F_01(T1) STTS OPEN GOOD Valid
'02-01-2010 '03:01:49.269 DEHAR PS CB E_07(T1) STTS OPEN GOOD Valid
'02-01-2010 '03:01:51.727 BUTARI CB E_1(JLNDR) STTS OPEN GOOD Valid
'02-01-2010 '03:01:52.011 MAHILPUR CB E_4(JMSHR-2) STTS OPEN GOOD Valid
'02-01-2010 '03:01:56.987 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:02:42.915 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION OK GOOD Valid
6 of 18
Chapter - 5 _ ANNEXE -5/II (page 6 of 18)
![Page 141: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/141.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From RTUS Reporting to SLDCsANNEX-5/II
Part-1
'02-01-2010 '01:01:53.176 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '01:01:53.176 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '01:01:57.265 GHTP CB E_8(GNDTP-2) STTS BETWEEN GOOD Valid
'02-01-2010 '01:04:47.313 MUR2N_UP CB E_03(KHURJ-1) STTS OPEN GOOD Valid
'02-01-2010 '01:04:48.155 MUR2N_UP CB E_03(KHURJ-1) STTS CLOSED GOOD Valid
'02-01-2010 '01:07:06.859 BALLABGARH CB E_09(SMYUR-1) STTS BETWEEN Bad Valid
'02-01-2010 '01:07:33.132 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '01:07:33.132 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '01:07:37.176 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '01:07:37.176 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '01:08:59.798 MUR2N_UP CB E_03(KHURJ-1) STTS OPEN GOOD Valid
'02-01-2010 '01:09:00.656 MUR2N_UP CB E_03(KHURJ-1) STTS CLOSED GOOD Valid
'02-01-2010 '01:10:44.150 SAHNEWAL CB E_06(GGSTP-1) STTS OPEN GOOD Valid
'02-01-2010 '01:14:44.398 MUR2N_UP CB E_04(KHURJ-2) STTS OPEN GOOD Valid
'02-01-2010 '01:15:32.823 GHTP__PS CB E_9 STTS ???????????????? GOOD Valid
'02-01-2010 '01:18:21.348 NUNAMAJRA CB E_10(BHADR-2) STTS CLOSED GOOD Valid
'02-01-2010 '01:21:25.713 PEHOWA LINE E_KTHAL_PHOWA1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '01:21:26.181 PEHOWA LINE E_KTHAL_PHOWA1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '01:21:26.449 PEHOWA LINE E_KTHAL_PHOWA1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '01:22:07.465 SAHIBABAD CB E_04(MUR1N-1) STTS OPEN GOOD Valid
'02-01-2010 '01:22:51.875 GHTP CB E_10(MNSA2-2) STTS BETWEEN GOOD Valid
'02-01-2010 '01:26:03.006 NUNAMAJRA CB E_10(BHADR-2) STTS BETWEEN Bad Valid
'02-01-2010 '01:26:12.666 PANIPAT CB E_06(PANTH-3) STTS BETWEEN Bad Valid
'02-01-2010 '01:26:12.997 PANIPATTPS CB E_08(PANPT-3) STTS BETWEEN Bad Valid
'02-01-2010 '01:26:13.715 PANIPAT CB E_06(PANTH-3) STTS CLOSED GOOD Valid
'02-01-2010 '01:27:29.460 PEHOWA CB E_08(KTHAL-1) STTS CLOSED GOOD Valid
'02-01-2010 '01:27:43.510 PEHOWA LINE E_KTHAL_PHOWA1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '01:27:43.568 PEHOWA CB E_08(KTHAL-1) STTS OPEN GOOD Valid
'02-01-2010 '01:28:20.526 MISS GANGUWAL CB E_05(JAMAL-2) STTS BETWEEN Bad Valid
'02-01-2010 '01:28:20.549 JAMALPUR CB E_12(GANGL-2) STTS OPEN GOOD Valid
'02-01-2010 '01:28:21.394 JAMALPUR CB E_12(GANGL-2) STTS CLOSED GOOD Valid
'02-01-2010 '01:28:21.818 MISS GANGUWAL CB E_05(JAMAL-2) STTS OPEN GOOD Valid
'02-01-2010 '01:29:39.978 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '01:29:40.288 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '01:29:40.401 MAHINDERGARH CB E_05 STTS BETWEEN Bad Valid
'02-01-2010 '01:29:42.973 PANIPATTPS CB E_08(PANPT-3) STTS CLOSED GOOD Valid
'02-01-2010 '01:29:44.099 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '01:30:13.581 GOBINDGAR2 CB E_6(GOBIO-2) STTS BETWEEN Bad Valid
'02-01-2010 '01:30:15.542 SAHNEWAL CB E_07(RAILY-2) STTS CLOSED GOOD Valid
'02-01-2010 '01:31:42.787 NUNAMAJRA CB E_10(BHADR-2) STTS CLOSED GOOD Valid
'02-01-2010 '01:31:49.443 MUR2N_UP CB E_03(KHURJ-1) STTS OPEN GOOD Valid
'02-01-2010 '01:33:05.149 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '01:33:05.149 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '01:33:07.156 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '01:33:07.156 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '01:33:46.569 ABLOWAL CB E_3(GOBIO-1) STTS OPEN GOOD Valid
'02-01-2010 '01:34:16.761 GHTP CB E_3(BAJAK-1) STTS BETWEEN GOOD Valid
'02-01-2010 '01:34:17.124 NUNAMAJRA CB E_10(BHADR-2) STTS BETWEEN Bad Valid
'02-01-2010 '01:34:54.368 ABLOWAL CB E_3(GOBIO-1) STTS CLOSED GOOD Valid
'02-01-2010 '01:36:19.310 GOBINDGAR2 LINE E_GOBIN_GOBIO2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '01:36:19.329 GOBINDGAR2 CB E_6(GOBIO-2) STTS OPEN GOOD Valid
'02-01-2010 '01:36:19.358 GOBINDGAR2 LINE E_GOBIN_GOBIO2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '01:36:20.345 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '01:36:25.752 DHANDARI CB E_2(LALTN-2) STTS OPEN GOOD Valid
'02-01-2010 '01:36:25.837 DHANDARI CB E_1(JAMAL-2) STTS BETWEEN Bad Valid
'02-01-2010 '01:36:25.855 DHANDARI LINE E_DHNDR_JAMAL1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '01:36:25.867 JAMALPUR CB E_10(DHNDR-1) STTS OPEN GOOD Valid
'02-01-2010 '01:36:25.875 DHANDARI CB E_3(JAMAL-1) STTS OPEN GOOD Valid
'02-01-2010 '01:36:25.910 JAMALPUR CB E_16(DHNDR-2) STTS OPEN GOOD Valid
'02-01-2010 '01:36:25.988 DHANDARI LINE E_DHNDR_JAMAL1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '01:36:26.661 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '01:36:26.694 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '01:36:26.723 MAHINDERGARH CB E_05 STTS BETWEEN Bad Valid
'02-01-2010 '01:36:30.109 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '01:37:58.223 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '01:38:27.011 NARWANA LINE E_NARWN_SFDON2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '01:38:27.048 NARWANA CB E_06(SFDON-2) STTS OPEN GOOD Valid
'02-01-2010 '01:38:34.420 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '01:38:57.427 SAHIBABAD CB E_02(GAZIT-1) STTS CLOSED GOOD Valid
'02-01-2010 '01:38:57.444 SAHIBABAD CB E_87(T2) STTS CLOSED GOOD Valid
'02-01-2010 '01:39:18.057 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '01:39:18.154 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '01:41:41.336 NUNAMAJRA CB E_10(BHADR-2) STTS CLOSED GOOD Valid
'02-01-2010 '01:43:41.053 PEHOWA CB E_08(KTHAL-1) STTS CLOSED GOOD Valid
'02-01-2010 '01:43:41.128 PEHOWA CB E_08(KTHAL-1) STTS OPEN GOOD Valid
'02-01-2010 '01:45:51.329 BALLABGARH CB E_09(SMYUR-1) STTS CLOSED GOOD Valid
'02-01-2010 '01:46:08.585 KAITHAL CB E_09(NISNG-2) STTS OPEN GOOD Valid
'02-01-2010 '01:46:08.904 NISSING CB E_06 STTS BETWEEN Bad Valid
'02-01-2010 '01:46:08.912 KAITHAL LINE E_KTHAL_NISNG1 PRT PROTECTION TRIP GOOD Valid
3 of 18
Chapter - 5 _ ANNEXE -5II (page 3 of 18)
![Page 142: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/142.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From RTUS Reporting to SLDCsANNEX-5/II
Part-1
'02-01-2010 '01:46:08.926 KAITHAL CB E_10(NISNG-1) STTS OPEN GOOD Valid
'02-01-2010 '01:46:09.466 NISSING CB E_08(KTHAL-1) STTS BETWEEN Bad Valid
'02-01-2010 '01:46:16.845 MISS GANGUWAL CB E_05(JAMAL-2) STTS CLOSED GOOD Valid
'02-01-2010 '01:46:51.008 NUNAMAJRA CB E_10(BHADR-2) STTS BETWEEN Bad Valid
'02-01-2010 '01:47:58.470 SAHIBABAD CB E_86(T1) STTS CLOSED GOOD Valid
'02-01-2010 '01:48:16.561 NUNAMAJRA CB E_10(BHADR-2) STTS CLOSED GOOD Valid
'02-01-2010 '01:48:26.968 NUNAMAJRA CB E_10(BHADR-2) STTS BETWEEN Bad Valid
'02-01-2010 '01:48:47.763 PANIPATTPS CB E_27(NISNG-1) STTS BETWEEN Bad Valid
'02-01-2010 '01:49:33.301 PANIPATTPS CB E_21(ROTAK-1) STTS BETWEEN Bad Valid
'02-01-2010 '01:49:54.289 DADRI CB E_05(PANPT) STTS CLOSED GOOD Valid
'02-01-2010 '01:50:27.124 DADRI CB E_05(PANPT) STTS OPEN GOOD Valid
'02-01-2010 '01:50:35.187 PANIPAT CB E_14(DADRI) STTS CLOSED GOOD Valid
'02-01-2010 '01:51:07.656 DEHAR PS LINE F_BHIWN_DEHAR PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '01:51:07.660 DEHAR PS CB F_7(BHIWN) STTS OPEN GOOD Valid
'02-01-2010 '01:51:07.661 DEHAR PS CB F_8(BHIWN) STTS OPEN GOOD Valid
'02-01-2010 '01:51:07.728 BHIWANI CB F_5(DEHAR BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '01:51:07.734 BHIWANI CB F_2(DEHAR BUS-2) STTS OPEN GOOD Valid
'02-01-2010 '01:51:30.425 PANIPAT CB E_14(DADRI) STTS OPEN GOOD Valid
'02-01-2010 '01:51:42.640 PANIPATTPS CB E_15(SONEP-1) STTS BETWEEN Bad Valid
'02-01-2010 '01:52:59.091 NISSING CB E_04(PANTH-1) STTS BETWEEN Bad Valid
'02-01-2010 '01:53:05.242 KAITHAL LINE E_KTHAL_NISNG1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '01:53:26.482 FTEBD_PG LINE F_FTEBD_HISAR2 PRT OPEN
'02-01-2010 '01:54:00.000 FTEBD_PG CB F_1 (MOGA-2 BUS-1) STTS CLOSED BAD QUAL
'02-01-2010 '01:54:06.000 FTEBD_PG LINE F_FTEBD_HISAR2 PRT OPEN BAD QUAL
'02-01-2010 '01:54:12.000 FTEBD_PG LINE F_FTEBD_HISAR2 PRT OPEN BAD QUAL
'02-01-2010 '01:55:08.970 PANIPATTPS CB E_23(SFDON-2) STTS BETWEEN Bad Valid
'02-01-2010 '01:55:09.563 PANIPATTPS CB E_23(SFDON-2) STTS OPEN GOOD Valid
'02-01-2010 '01:55:09.998 PANIPATTPS CB E_22(SFDON-1) STTS OPEN GOOD Valid
'02-01-2010 '01:55:10.042 PANIPATTPS CB E_29(KRNAL) STTS CLOSED GOOD Valid
'02-01-2010 '01:55:13.427 PANIPATTPS CB E_29(KRNAL) STTS BETWEEN Bad Valid
'02-01-2010 '01:55:23.973 PANIPATTPS CB E_25(U5) STTS OPEN GOOD Valid
'02-01-2010 '01:55:48.831 SAHNEWAL CB E_05(GGSTP-2) STTS OPEN GOOD Valid
'02-01-2010 '01:56:00.535 NARWANA LINE E_NARWN_SFDON1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '01:56:00.592 NARWANA CB E_05(SFDON-1) STTS OPEN GOOD Valid
'02-01-2010 '01:56:01.596 NARWANA CB E_05(SFDON-1) STTS CLOSED GOOD Valid
'02-01-2010 '01:56:01.671 NARWANA CB E_05(SFDON-1) STTS BETWEEN Bad Valid
'02-01-2010 '01:56:04.271 NARWANA CB E_05(SFDON-1) STTS OPEN GOOD Valid
'02-01-2010 '01:57:01.687 NARWANA CB E_05(SFDON-1) STTS CLOSED GOOD Valid
'02-01-2010 '01:57:01.765 NARWANA CB E_05(SFDON-1) STTS OPEN GOOD Valid
'02-01-2010 '02:01:13.160 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '02:01:13.160 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '02:01:17.166 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '02:01:17.166 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '02:01:46.850 BALLABGARH CB E_09(SMYUR-1) STTS BETWEEN Bad Valid
'02-01-2010 '02:01:48.176 SAMAYUR CB E_01(BLBGH-1) STTS OPEN GOOD Valid
'02-01-2010 '02:03:27.194 PANIPAT CB F_1(DEHAR) STTS CLOSED GOOD Valid
'02-01-2010 '02:03:31.846 PANIPAT CB F_1(DEHAR) STTS OPEN GOOD Valid
'02-01-2010 '02:03:51.423 PANIPAT CB F_1(DEHAR) STTS CLOSED GOOD Valid
'02-01-2010 '02:06:05.772 ROHTAK CB E_04(PANTH-1) STTS INVALID Bad Valid
'02-01-2010 '02:06:45.078 PANIPAT CB E_18(DHULK-2) STTS OPEN GOOD Valid
'02-01-2010 '02:06:45.086 DHULEKOTE CB E_3 STTS BETWEEN Bad Valid
'02-01-2010 '02:06:45.088 DHULEKOTE CB E_2 STTS BETWEEN Bad Valid
'02-01-2010 '02:06:45.089 DHULEKOTE LINE E_DHULK_PANPT2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '02:06:45.135 DHULEKOTE LINE E_DHULK_PANPT2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '02:06:45.954 DHULEKOTE CB E_3 STTS CLOSED GOOD Valid
'02-01-2010 '02:06:45.987 DHULEKOTE CB E_2 STTS CLOSED GOOD Valid
'02-01-2010 '02:07:32.196 PANIPAT CB E_17(DHULK-1) STTS OPEN GOOD Valid
'02-01-2010 '02:07:32.215 DHULEKOTE CB E_3 STTS BETWEEN Bad Valid
'02-01-2010 '02:07:32.233 DHULEKOTE CB E_4 STTS BETWEEN Bad Valid
'02-01-2010 '02:07:33.379 DHULEKOTE CB E_4 STTS CLOSED GOOD Valid
'02-01-2010 '02:07:33.379 DHULEKOTE CB E_3 STTS CLOSED GOOD Valid
'02-01-2010 '02:08:53.062 PANIPAT CB F_1(DEHAR) STTS OPEN GOOD Valid
'02-01-2010 '02:09:03.514 PANIPAT CB F_1(DEHAR) STTS CLOSED GOOD Valid
'02-01-2010 '02:09:36.539 PANIPAT CB F_1(DEHAR) STTS OPEN GOOD Valid
'02-01-2010 '02:09:47.414 DHULEKOTE LINE E_DHULK_PANPT1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '02:09:47.421 DHULEKOTE CB E_3 STTS OPEN GOOD Valid
'02-01-2010 '02:09:47.423 DHULEKOTE CB E_4 STTS OPEN GOOD Valid
'02-01-2010 '02:09:47.447 DHULEKOTE LINE E_DHULK_PANPT1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '02:10:00.611 KAITHAL CB E_02(NARWN-2) STTS OPEN GOOD Valid
'02-01-2010 '02:10:00.666 NARWANA CB E_02(KTHAL-2) STTS OPEN GOOD Valid
'02-01-2010 '02:10:05.791 NUNAMAJRA CB E_10(BHADR-2) STTS CLOSED GOOD Valid
'02-01-2010 '02:11:48.457 NUNAMAJRA CB E_10(BHADR-2) STTS BETWEEN Bad Valid
'02-01-2010 '02:14:11.354 ABLOWAL CB E_4(GOBIO-2) STTS CLOSED GOOD Valid
'02-01-2010 '02:15:02.514 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '02:15:03.426 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '02:15:18.634 RAJPURA CB E_5(RAILY-1) STTS INVALID GOOD Valid
'02-01-2010 '02:15:19.115 RAJPURA CB E_5(RAILY-1) STTS INVALID GOOD Valid
'02-01-2010 '02:15:19.597 RAJPURA CB E_5(RAILY-1) STTS INVALID GOOD Valid
'02-01-2010 '02:15:20.077 RAJPURA CB E_5(RAILY-1) STTS INVALID GOOD Valid
4 of 18
Chapter - 5 _ ANNEXE -5/II (page 4 of 18)
![Page 143: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/143.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From RTUS Reporting to SLDCsANNEX-5/II
Part-1
'02-01-2010 '02:15:20.558 RAJPURA CB E_5(RAILY-1) STTS INVALID GOOD Valid
'02-01-2010 '02:15:21.040 RAJPURA CB E_5(RAILY-1) STTS INVALID GOOD Valid
'02-01-2010 '02:15:21.521 RAJPURA CB E_5(RAILY-1) STTS INVALID GOOD Valid
'02-01-2010 '02:16:39.045 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '02:16:39.045 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '02:16:45.176 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '02:16:45.176 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '02:17:16.180 NISSING CB E_04(PANTH-1) STTS OPEN GOOD Valid
'02-01-2010 '02:17:51.120 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '02:17:51.120 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '02:17:57.166 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '02:17:57.166 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '02:18:05.943 NUNAMAJRA CB E_09(BHADR-1) STTS OPEN GOOD Valid
'02-01-2010 '02:18:06.054 BHADR_PG CB E_4(MAJRA-1) STTS OPEN
'02-01-2010 '02:19:04.196 SAHNEWAL CB E_02(LALTN-1) STTS OPEN GOOD Valid
'02-01-2010 '02:19:07.087 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '02:19:07.087 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '02:19:11.166 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '02:19:11.186 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '02:20:10.439 DEHAR PS LINE F_BHIWN_DEHAR PRT PROTECTION OK GOOD Valid
'02-01-2010 '02:20:53.571 BHIWANI CB F_5(DEHAR BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 '02:20:54.756 BHIWANI CB F_5(DEHAR BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '02:21:21.246 NISSING CB E_06 STTS CLOSED GOOD Valid
'02-01-2010 '02:21:35.130 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '02:21:35.130 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '02:21:39.166 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '02:21:39.166 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '02:22:57.154 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '02:22:57.154 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '02:22:59.166 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '02:22:59.166 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '02:23:14.437 PANIPAT CB E_18(DHULK-2) STTS CLOSED GOOD Valid
'02-01-2010 '02:23:22.860 MERRUT CB E_03(MEERT-1) STTS OPEN GOOD Valid
'02-01-2010 '02:23:38.953 SUNAM CB E_3(DHURI-1) STTS BETWEEN Bad Valid
'02-01-2010 '02:24:15.152 KAITHAL CB E_01(NARWN-1) STTS OPEN GOOD Valid
'02-01-2010 '02:24:15.421 NARWANA LD E_BHUNA_NARWN PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '02:24:15.436 NARWANA CB E_03(BHUNA) STTS OPEN GOOD Valid
'02-01-2010 '02:24:15.540 NARWANA CB E_01(KTHAL-1) STTS OPEN GOOD Valid
'02-01-2010 '02:26:57.314 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '02:27:00.517 PANIPAT CB E_18(DHULK-2) STTS OPEN GOOD Valid
'02-01-2010 '02:27:00.522 DHULEKOTE CB E_2 STTS BETWEEN Bad Valid
'02-01-2010 '02:27:00.524 DHULEKOTE LINE E_DHULK_PANPT2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '02:27:00.572 DHULEKOTE LINE E_DHULK_PANPT2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '02:27:01.375 DHULEKOTE CB E_3 STTS CLOSED GOOD Valid
'02-01-2010 '02:27:01.409 DHULEKOTE CB E_2 STTS CLOSED GOOD Valid
'02-01-2010 '02:27:05.015 DHULEKOTE LINE E_DHULK_PANPT1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '02:27:05.025 DHULEKOTE CB E_3 STTS OPEN GOOD Valid
'02-01-2010 '02:27:05.043 DHULEKOTE LINE E_DHULK_PANPT1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '02:27:05.387 DHULEKOTE LINE E_DHULK_PANPT2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '02:27:05.405 DHULEKOTE CB E_2 STTS OPEN GOOD Valid
'02-01-2010 '02:27:05.486 DHULEKOTE LINE E_DHULK_PANPT2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '02:27:33.137 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '02:28:46.625 DADRI CB E_05(PANPT) STTS CLOSED GOOD Valid
'02-01-2010 '02:28:48.471 DADRI CB E_05(PANPT) STTS BETWEEN Bad Valid
'02-01-2010 '02:28:49.467 DADRI CB E_05(PANPT) STTS OPEN GOOD Valid
'02-01-2010 '02:29:19.611 FTEBD_PG CB F_2(MOGA-2 & XFMR-1TIE) STTS OPEN
'02-01-2010 '02:29:20.908 FTEBD_PG CB F_2(MOGA-2 & XFMR-1TIE) STTS OPEN
'02-01-2010 '02:31:26.445 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '02:31:30.800 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '02:31:57.202 JAMALPUR CB E_08(T1) STTS OPEN GOOD Valid
'02-01-2010 '02:32:36.959 MURADNGR-1 CB E_08(SHIBD-2) STTS CLOSED GOOD Valid
'02-01-2010 '02:32:39.061 MURADNGR-1 CB E_08(SHIBD-2) STTS OPEN GOOD Valid
'02-01-2010 '02:33:52.105 NUNAMAJRA CB E_09(BHADR-1) STTS CLOSED GOOD Valid
'02-01-2010 '02:33:57.445 SAMAYUR CB E_18(BADSH-2) STTS OPEN GOOD Valid
'02-01-2010 '02:36:17.248 PANIPAT CB E_19(PIPLI) STTS BETWEEN Bad Valid
'02-01-2010 '02:36:17.395 PIPLI CB E_02(PANPT) STTS OPEN GOOD Valid
'02-01-2010 '02:36:17.417 PIPLI CB E_02(PANPT) STTS INVALID Bad Valid
'02-01-2010 '02:36:18.252 PIPLI CB E_02(PANPT) STTS CLOSED GOOD Valid
'02-01-2010 '02:36:18.258 PIPLI CB E_02(PANPT) STTS BETWEEN Bad Valid
'02-01-2010 '02:36:20.358 PIPLI CB E_02(PANPT) STTS OPEN GOOD Valid
'02-01-2010 '02:36:41.050 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '02:36:41.050 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '02:36:47.156 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '02:36:47.156 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '02:37:48.058 NUNAMAJRA CB E_09(BHADR-1) STTS OPEN GOOD Valid
'02-01-2010 '02:38:50.426 DHULEKOTE CB E_3 STTS CLOSED GOOD Valid
'02-01-2010 '02:38:56.917 DHULEKOTE CB E_4 STTS CLOSED GOOD Valid
'02-01-2010 '02:38:58.216 DHULEKOTE LINE E_DHULK_PANPT1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '02:38:58.234 DHULEKOTE CB E_3 STTS OPEN GOOD Valid
5 of 18
Chapter - 5 _ ANNEXE -5/II (page 5 of 18)
![Page 144: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/144.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From RTUS Reporting to SLDCs
'02-01-2010 '02:38:58.234 DHULEKOTE CB E_4 STTS OPEN GOOD Valid
'02-01-2010 '02:38:58.246 DHULEKOTE LINE E_DHULK_PANPT1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '02:39:46.733 SAMAYUR CB E_02(BLBGH-2) STTS OPEN GOOD Valid
'02-01-2010 '02:41:29.588 NISSING CB E_11(SALEM-2) STTS BETWEEN Bad Valid
'02-01-2010 '02:41:41.050 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '02:41:41.050 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '02:41:43.156 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '02:41:43.156 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '02:44:14.894 SUNAM CB E_3(DHURI-1) STTS CLOSED GOOD Valid
'02-01-2010 '02:45:38.075 DHANDARI CB E_2(LALTN-2) STTS CLOSED GOOD Valid
'02-01-2010 '02:46:19.045 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '02:46:57.296 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '02:47:10.668 SAMAYUR CB E_01(BLBGH-1) STTS CLOSED GOOD Valid
'02-01-2010 '02:47:23.921 SIMBHOLI CB E_03(SHATB-1) STTS OPEN GOOD Valid
'02-01-2010 '02:47:23.927 SHATABDINAGAR CB E_03(SBHLI-1) STTS OPEN GOOD Valid
'02-01-2010 '02:47:48.990 BALLABGARH CB E_09(SMYUR-1) STTS CLOSED GOOD Valid
'02-01-2010 '02:52:54.020 NUNAMAJRA CB E_12(ROTAK-2) STTS OPEN GOOD Valid
'02-01-2010 '02:53:27.132 SAHNEWAL CB E_07(RAILY-2) STTS BETWEEN Bad Valid
'02-01-2010 '02:53:38.997 KAITHAL CB E_10(NISNG-1) STTS CLOSED GOOD Valid
'02-01-2010 '02:54:29.547 ABLOWAL CB E_6(PATRA) STTS CLOSED GOOD Valid
'02-01-2010 '02:55:09.408 PEHOWA CB E_09(KTHAL-2) STTS BETWEEN Bad Valid
'02-01-2010 '02:55:09.450 KAITHAL CB E_11(KAITH-1) STTS OPEN GOOD Valid
'02-01-2010 '02:55:10.456 PEHOWA CB E_09(KTHAL-2) STTS CLOSED GOOD Valid
'02-01-2010 '02:56:29.278 GORAYA LINE E_GORAY_JMSHR PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '02:56:29.309 GORAYA CB E_51(JMSHR) STTS OPEN GOOD Valid
'02-01-2010 '02:56:51.843 NUNAMAJRA CB E_11(ROTAK-1) STTS OPEN GOOD Valid
'02-01-2010 '02:57:09.090 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '02:57:09.090 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '02:57:11.166 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '02:57:11.166 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '02:57:37.075 NUNAMAJRA CB E_10(BHADR-2) STTS CLOSED GOOD Valid
'02-01-2010 '02:58:57.744 NARWANA LD E_BHUNA_NARWN PRT PROTECTION OK GOOD Valid
'02-01-2010 '02:58:57.779 NARWANA LD E_BHUNA_NARWN PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '02:58:58.170 NARWANA LD E_BHUNA_NARWN PRT PROTECTION OK GOOD Valid
'02-01-2010 '02:58:58.195 NARWANA LD E_BHUNA_NARWN PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '02:58:58.221 NARWANA LD E_BHUNA_NARWN PRT PROTECTION OK Bad Valid
'02-01-2010 '02:59:04.431 NARWANA LD E_BHUNA_NARWN PRT PROTECTION OK GOOD Valid
'02-01-2010 '02:59:05.760 NUNAMAJRA CB E_09(BHADR-1) STTS CLOSED GOOD Valid
'02-01-2010 '02:59:37.061 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '02:59:37.061 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '02:59:39.166 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '02:59:39.166 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '02:59:43.832 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '02:59:45.842 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '03:00:01.140 GORAYA CB E_52(T4) STTS OPEN GOOD Valid
'02-01-2010 '03:00:32.467 NARWANA CB E_03(BHUNA) STTS CLOSED GOOD Valid
'02-01-2010 '03:00:49.115 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '03:00:49.115 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '03:00:51.156 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '03:00:51.156 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '03:00:53.329 PIPLI CB E_02(PANPT) STTS INVALID Bad Valid
'02-01-2010 '03:00:53.634 PIPLI CB E_02(PANPT) STTS CLOSED GOOD Valid
'02-01-2010 '03:01:06.824 GORAYA CB E_50(GGSTP) STTS OPEN GOOD Valid
'02-01-2010 '03:01:39.286 BHIWANI XFMR_P FE_T1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:01:39.297 BHIWANI CB E_06(T1) STTS BETWEEN Bad Valid
'02-01-2010 '03:01:39.325 BHIWANI CB F_1(ICT-1 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '03:01:39.332 BHIWANI CB F_4(ICT-1 BUS2) STTS OPEN GOOD Valid
'02-01-2010 '03:01:41.459 SANGRUR CB E_04(HISAR-2) STTS OPEN GOOD Valid
'02-01-2010 '03:01:41.607 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:01:41.895 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:01:42.061 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:01:42.221 SANGRUR CB E_03(HISAR-1) STTS OPEN GOOD Valid
'02-01-2010 '03:01:42.343 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:01:42.443 JAGADHRI LINE E_JGDRI_PIPLI PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:01:42.456 JAGADHRI CB E_1 STTS BETWEEN Bad Valid
'02-01-2010 '03:01:42.474 JAGADHRI CB E_2 STTS OPEN GOOD Valid
'02-01-2010 '03:01:42.506 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION TRIP Bad Valid
'02-01-2010 '03:01:42.531 JAGADHRI LINE E_JGDRI_PIPLI PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:01:42.573 PIPLI CB E_02(PANPT) STTS INVALID Bad Valid
'02-01-2010 '03:01:42.693 PIPLI CB E_02(PANPT) STTS CLOSED GOOD Valid
'02-01-2010 '03:01:42.732 PIPLI CB E_02(PANPT) STTS OPEN GOOD Valid
'02-01-2010 '03:01:49.216 DEHAR PS XFMR_P FE_T1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:01:49.241 BHAKRA DAM CB E_35(G6) STTS OPEN GOOD Valid
'02-01-2010 '03:01:49.249 DEHAR PS CB F_01(T1) STTS OPEN GOOD Valid
'02-01-2010 '03:01:49.269 DEHAR PS CB E_07(T1) STTS OPEN GOOD Valid
'02-01-2010 '03:01:51.727 BUTARI CB E_1(JLNDR) STTS OPEN GOOD Valid
'02-01-2010 '03:01:52.011 MAHILPUR CB E_4(JMSHR-2) STTS OPEN GOOD Valid
'02-01-2010 '03:01:56.987 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:02:42.915 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION OK GOOD Valid
6 of 18
Chapter - 5 _ ANNEXE -5/II (page 6 of 18)
![Page 145: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/145.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From RTUS Reporting to SLDCsANNEX-5/II
Part-1
'02-01-2010 '03:02:52.587 PONG CB E_05(H02) STTS OPEN GOOD Valid
'02-01-2010 '03:02:54.345 PONG CB E_13(H06) STTS OPEN GOOD Valid
'02-01-2010 '03:02:57.498 PEHOWA CB E_09(KTHAL-2) STTS OPEN GOOD Valid
'02-01-2010 '03:02:57.521 KAITHAL LINE E_KTHAL_NISNG2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:03:03.378 GORAYA LINE E_GORAY_JMSHR PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:03:03.629 GORAYA LINE E_GORAY_JMSHR PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:03:04.673 GORAYA LINE E_GORAY_JMSHR PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:03:05.101 GORAYA LINE E_GORAY_JMSHR PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:03:10.690 PONG CB E_06(H03) STTS OPEN GOOD Valid
'02-01-2010 '03:03:16.170 GORAYA LINE E_GORAY_JMSHR PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:03:17.990 GHTP CB E_4(BAJAK-2) STTS BETWEEN GOOD Valid
'02-01-2010 '03:03:20.756 MERRUT CB E_03(MEERT-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:03:28.834 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '03:03:31.738 MERRUT CB E_03(MEERT-1) STTS OPEN GOOD Valid
'02-01-2010 '03:03:32.078 MAHINDERGARH CB E_05 STTS BETWEEN Bad Valid
'02-01-2010 '03:03:34.571 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '03:04:12.581 SAHNEWAL CB E_03(T1) STTS OPEN GOOD Valid
'02-01-2010 '03:04:15.569 PONG CB E_01(BAIRA) STTS OPEN GOOD Valid
'02-01-2010 '03:04:18.646 PONG CB E_02(JASOR) STTS OPEN GOOD Valid
'02-01-2010 '03:04:20.939 PONG CB E_10(JLNDR-1) STTS OPEN GOOD Valid
'02-01-2010 '03:04:25.937 PONG CB E_11(JLNDR-2) STTS OPEN GOOD Valid
'02-01-2010 '03:04:34.002 PONG CB E_14(DASYA-1) STTS OPEN GOOD Valid
'02-01-2010 '03:04:37.788 PONG CB E_15(DASYA-2) STTS OPEN GOOD Valid
'02-01-2010 '03:04:45.594 JAMALPUR CB E_15(T6) STTS OPEN GOOD Valid
'02-01-2010 '03:04:47.274 JAMALPUR CB E_14(T5) STTS BETWEEN Bad Valid
'02-01-2010 '03:04:48.768 JAMALPUR CB E_13(T4) STTS OPEN GOOD Valid
'02-01-2010 '03:04:54.673 JAMALPUR CB E_11(GANGL-1) STTS OPEN GOOD Valid
'02-01-2010 '03:04:57.076 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '03:04:57.076 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '03:05:01.166 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '03:05:01.166 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '03:05:03.398 JAMALPUR CB E_12(GANGL-2) STTS OPEN GOOD Valid
'02-01-2010 '03:05:09.077 JAMALPUR CB E_01(SNGRU-2) STTS OPEN GOOD Valid
'02-01-2010 '03:05:12.218 JAMALPUR CB E_02(SNGRU-1) STTS OPEN GOOD Valid
'02-01-2010 '03:05:14.602 BALLABGARH CB E_03(DADRI) STTS OPEN GOOD Valid
'02-01-2010 '03:05:14.650 DADRI CB E_06(BLBGH) STTS BETWEEN Bad Valid
'02-01-2010 '03:05:15.380 JAMALPUR CB E_03(BHAKR-2) STTS OPEN GOOD Valid
'02-01-2010 '03:05:15.734 DADRI CB E_06(BLBGH) STTS CLOSED GOOD Valid
'02-01-2010 '03:05:18.082 JAMALPUR CB E_04(BHAKR-1) STTS OPEN GOOD Valid
'02-01-2010 '03:05:24.285 JAMALPUR CB E_05(JLNDR-1) STTS BETWEEN Bad Valid
'02-01-2010 '03:05:26.858 JAMALPUR CB E_06(JLNDR-2) STTS OPEN GOOD Valid
'02-01-2010 '03:05:32.024 JAMALPUR CB E_09(T2) STTS OPEN GOOD Valid
'02-01-2010 '03:05:32.716 MISS GANGUWAL CB E_05(JAMAL-2) STTS BETWEEN Bad Valid
'02-01-2010 '03:05:33.009 MISS GANGUWAL CB E_05(JAMAL-2) STTS OPEN GOOD Valid
'02-01-2010 '03:05:38.985 DULHA_NH BUS F_B2 LOV CLOSED BAD TIME
'02-01-2010 '03:05:51.316 BHADR_PG CB E_4(MAJRA-1) STTS CLOSED BAD QUAL
'02-01-2010 '03:05:51.316 BHADR_PG CB E_4(MAJRA-1) STTS CLOSED BAD QUAL
'02-01-2010 '03:06:23.852 BHAKRA DAM CB E_14(GANGL-1) STTS OPEN GOOD Valid
'02-01-2010 '03:06:32.619 BHAKRA DAM CB E_17(GANGL-2) STTS BETWEEN Bad Valid
'02-01-2010 '03:06:33.822 DHULEKOTE CB E_6 STTS OPEN GOOD Valid
'02-01-2010 '03:06:39.362 DHULEKOTE CB E_1 STTS OPEN GOOD Valid
'02-01-2010 '03:06:39.608 DHULEKOTE CB E_5 STTS OPEN GOOD Valid
'02-01-2010 '03:06:40.907 BHAKRA DAM CB E_18(GANGL-3) STTS OPEN GOOD Valid
'02-01-2010 '03:07:07.963 DEHAR PS CB E_05(GANGL-2) STTS BETWEEN Bad Valid
'02-01-2010 '03:07:09.910 DEHAR PS CB E_03(GANGL-1) STTS OPEN GOOD Valid
'02-01-2010 '03:07:10.073 RORKE_PG CB F_4 STTS OPEN BAD TIME
'02-01-2010 '03:07:10.079 RORKE_PG CB F_5 STTS OPEN BAD TIME
'02-01-2010 '03:07:10.079 RORKE_PG CB F_4 STTS OPEN BAD TIME
'02-01-2010 '03:07:30.373 MISS GANGUWAL CB E_03(JGDRI- ) STTS OPEN GOOD Valid
'02-01-2010 '03:07:32.275 DEHAR PS CB E_02(T2) STTS OPEN GOOD Valid
'02-01-2010 '03:07:42.021 DEHAR PS CB E_09(KANGO) STTS OPEN GOOD Valid
'02-01-2010 '03:07:46.771 MISS GANGUWAL CB E_04(JAMAL-1) STTS OPEN GOOD Valid
'02-01-2010 '03:08:21.576 JALANDHAR CB E_01(T4) STTS OPEN GOOD Valid
'02-01-2010 '03:08:28.478 JALANDHAR CB E_02(T5) STTS OPEN GOOD Valid
'02-01-2010 '03:09:10.774 JALANDHAR CB E_04(PONG_-1) STTS BETWEEN Bad Valid
'02-01-2010 '03:09:11.751 JALANDHAR CB E_04(PONG_-1) STTS OPEN GOOD Valid
'02-01-2010 '03:09:24.651 BHAKRA DAM CB E_22(GANGL-5) STTS OPEN GOOD Valid
'02-01-2010 '03:09:31.992 BHAKRA DAM CB E_24(MHLPR-2) STTS OPEN GOOD Valid
'02-01-2010 '03:09:34.670 JALANDHAR CB E_05(PONG_-2) STTS BETWEEN Bad Valid
'02-01-2010 '03:09:36.871 BHAKRA DAM CB E_26(GANGL-4) STTS BETWEEN Bad Valid
'02-01-2010 '03:09:43.472 BHAKRA DAM CB E_28(JAMAL-2) STTS OPEN GOOD Valid
'02-01-2010 '03:09:48.213 SANGRUR CB E_09(T3) STTS BETWEEN Bad Valid
'02-01-2010 '03:09:49.028 BHAKRA DAM CB E_29(MHLPR-1) STTS OPEN GOOD Valid
'02-01-2010 '03:09:52.446 BHAKRA DAM CB E_32(JAMAL-1) STTS OPEN GOOD Valid
'02-01-2010 '03:10:19.683 SANGRUR CB E_02(JAMAL-2) STTS BETWEEN Bad Valid
'02-01-2010 '03:10:24.785 SANGRUR CB E_01(JAMAL-1) STTS OPEN GOOD Valid
'02-01-2010 '03:10:27.895 MISS GANGUWAL CB E_06(DHULK-1) STTS OPEN GOOD Valid
'02-01-2010 '03:10:29.306 JALANDHAR CB E_12(JAMAL-2) STTS OPEN GOOD Valid
'02-01-2010 '03:10:31.258 SANGRUR CB E_8(BARNL) STTS BETWEEN Bad Valid
7 of 18
Chapter - 5 _ ANNEXE -5/II (page 7 of 18)
![Page 146: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/146.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From RTUS Reporting to SLDCsANNEX-5/II
Part-1
'02-01-2010 '03:10:32.788 JALANDHAR CB E_11(JAMAL-1) STTS OPEN GOOD Valid
'02-01-2010 '03:10:35.538 JALANDHAR CB E_08(T1) STTS OPEN GOOD Valid
'02-01-2010 '03:10:37.903 MISS GANGUWAL CB E_07(DHULK-2) STTS OPEN GOOD Valid
'02-01-2010 '03:10:44.426 JALANDHAR CB E_09(T2) STTS OPEN GOOD Valid
'02-01-2010 '03:10:48.339 JALANDHAR CB E_10(T3) STTS OPEN GOOD Valid
'02-01-2010 '03:10:52.513 MISS GANGUWAL CB E_17(GOBIN-2) STTS OPEN GOOD Valid
'02-01-2010 '03:10:53.943 BHIWANI XFMR_P FE_T1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:10:54.230 SANGRUR CB E_05 STTS BETWEEN Bad Valid
'02-01-2010 '03:10:54.698 BHIWANI XFMR_P FE_T1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:10:55.085 MISS GANGUWAL CB E_16(GOBIN-1) STTS OPEN GOOD Valid
'02-01-2010 '03:10:55.171 BHIWANI XFMR_P FE_T1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:10:55.641 BHIWANI XFMR_P FE_T1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:10:58.490 BHIWANI XFMR_P FE_T1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:10:59.295 BHIWANI XFMR_P FE_T1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:10:59.626 MISS GANGUWAL CB E_18(MOHLI-1) STTS OPEN GOOD Valid
'02-01-2010 '03:11:00.832 JALANDHAR CB E_6(DASYA-1) STTS BETWEEN Bad Valid
'02-01-2010 '03:11:02.431 BHIWANI XFMR_P FE_T1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:11:02.775 JALANDHAR CB E_6(DASYA-1) STTS OPEN GOOD Valid
'02-01-2010 '03:11:10.708 JALANDHAR CB E_7(DASYA-2) STTS OPEN GOOD Valid
'02-01-2010 '03:11:14.476 JALANDHAR CB E_15(JMSHR-2) STTS OPEN GOOD Valid
'02-01-2010 '03:11:17.804 JALANDHAR LINE E_JLNDR_JMSHR1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:11:17.833 JALANDHAR CB E_14(JMSHR-1) STTS OPEN GOOD Valid
'02-01-2010 '03:11:32.465 JALANDHAR CB E_3(BUTRI) STTS OPEN GOOD Valid
'02-01-2010 '03:11:33.033 SUNAM CB E_3(DHURI-1) STTS BETWEEN Bad Valid
'02-01-2010 '03:11:34.273 NUNAMAJRA CB E_11(ROTAK-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:11:35.612 NUNAMAJRA CB E_10(BHADR-2) STTS BETWEEN Bad Valid
'02-01-2010 '03:11:38.723 SUNAM CB E_3(DHURI-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:12:00.785 MURADNGR-1 CB F_01(MUZA1) STTS OPEN GOOD Valid
'02-01-2010 '03:12:10.920 RORKE_PG CB F_2 STTS OPEN BAD TIME
'02-01-2010 '03:12:10.925 RORKE_PG CB F_1 STTS OPEN BAD TIME
'02-01-2010 '03:12:10.928 RORKE_PG CB F_2 STTS OPEN BAD TIME
'02-01-2010 '03:12:22.004 BHAKRA DAM CB E_25 STTS OPEN GOOD Valid
'02-01-2010 '03:12:41.847 DASUYA LINE E_DASYA_JALAN1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:12:42.210 DASUYA LINE E_DASYA_JALAN1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:12:46.101 DASUYA LINE E_DASYA_JALAN2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:12:46.158 DASUYA CB E_3(JALAN-2) STTS OPEN GOOD Valid
'02-01-2010 '03:12:46.479 DASUYA LINE E_DASYA_JALAN2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:12:59.421 NAKODAR_220 LINE E_JALAN_KJNGA PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:12:59.446 NAKODAR_220 CB E_03(JALAN) STTS OPEN GOOD Valid
'02-01-2010 '03:12:59.994 DADRI CB E_06(BLBGH) STTS BETWEEN Bad Valid
'02-01-2010 '03:13:00.753 DELHI (R.R) CB E_01(NAREL-1) STTS OPEN GOOD Valid
'02-01-2010 '03:13:01.087 DADRI CB E_06(BLBGH) STTS CLOSED GOOD Valid
'02-01-2010 '03:13:05.302 DELHI (R.R) CB E_04(NAREL-2) STTS OPEN GOOD Valid
'02-01-2010 '03:13:09.038 UNNAO CB F_14 STTS CLOSED GOOD Valid
'02-01-2010 '03:14:15.896 PIPLI CB E_01(JGDRI) STTS BETWEEN Bad Valid
'02-01-2010 '03:15:05.237 BHIWANI CB E_08(DADRI-4) STTS BETWEEN Bad Valid
'02-01-2010 '03:15:05.324 BHIWANI LINE E_BHIWN_DADRI4 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:15:05.338 DADRI CB E_14(BHIWN-4) STTS BETWEEN Bad Valid
'02-01-2010 '03:15:05.605 BHIWANI LINE E_BHIWN_DADRI4 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:15:05.927 BHIWANI LINE E_BHIWN_DADRI4 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:15:06.200 BHIWANI LINE E_BHIWN_DADRI4 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:15:06.293 DADRI CB E_14(BHIWN-4) STTS CLOSED GOOD Valid
'02-01-2010 '03:15:06.525 BHIWANI LINE E_BHIWN_DADRI4 PRT PROTECTION TRIP Bad Valid
'02-01-2010 '03:15:07.554 BHIWANI CB E_08(DADRI-4) STTS OPEN GOOD Valid
'02-01-2010 '03:15:24.911 BHIWANI LINE E_BHIWN_DADRI4 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:15:29.304 DHANDARI CB E_6(T2) STTS OPEN GOOD Valid
'02-01-2010 '03:15:34.612 DHANDARI CB E_5(T1) STTS OPEN GOOD Valid
'02-01-2010 '03:16:01.146 REWARI LINE E_DADRI_RWARI PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:16:01.158 REWARI CB E_01(DADRI) STTS BETWEEN Bad Valid
'02-01-2010 '03:16:01.159 REWARI CB E_01(DADRI) STTS OPEN GOOD Valid
'02-01-2010 '03:16:09.653 BALLABGARH CB E_03(DADRI) STTS CLOSED GOOD Valid
'02-01-2010 '03:16:24.115 DHANDARI CB E_50(T5) STTS INVALID Bad Valid
'02-01-2010 '03:16:24.116 DHANDARI XFMR_P EC_T5 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:16:50.175 DHANDARI XFMR_P EC_T5 PRT PROTECTION TRIP Bad Valid
'02-01-2010 '03:16:50.175 DHANDARI LINE E_DHNDR_JAMAL2 PRT PROTECTION OK Bad Valid
'02-01-2010 '03:16:50.175 DHANDARI BUS E_B1 BPT BUSBAR PROT OK Bad Valid
'02-01-2010 '03:16:50.175 DHANDARI XFMR_P EC_T1 PRT PROTECTION OK Bad Valid
'02-01-2010 '03:16:50.175 DHANDARI LINE E_DHNDR_LALTN1 PRT PROTECTION OK Bad Valid
'02-01-2010 '03:16:50.175 DHANDARI LINE E_DHNDR_JAMAL1 PRT PROTECTION OK Bad Valid
'02-01-2010 '03:16:50.175 DHANDARI XFMR_P EC_T2 PRT PROTECTION OK Bad Valid
'02-01-2010 '03:16:50.175 DHANDARI LINE E_DHNDR_LALTN2 PRT PROTECTION OK Bad Valid
'02-01-2010 '03:16:54.535 BHIWANI CB E_07(DADRI-3) STTS BETWEEN Bad Valid
'02-01-2010 '03:16:54.611 DADRI CB E_13(BHIWN-3) STTS OPEN GOOD Valid
'02-01-2010 '03:16:54.631 BHIWANI LINE E_BHIWN_DADRI3 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:16:54.661 DADRI CB E_13(BHIWN-3) STTS BETWEEN Bad Valid
'02-01-2010 '03:16:54.906 BHIWANI LINE E_BHIWN_DADRI3 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:16:55.236 BHIWANI LINE E_BHIWN_DADRI3 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:16:55.372 BHIWANI CB E_07(DADRI-3) STTS CLOSED GOOD Valid
'02-01-2010 '03:16:55.424 DADRI CB E_13(BHIWN-3) STTS CLOSED GOOD Valid
8 of 18
Chapter - 5 _ ANNEXE -5/II (page 8 of 18)
![Page 147: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/147.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From RTUS Reporting to SLDCsANNEX-5/II
Part-1
'02-01-2010 '03:16:55.515 BHIWANI LINE E_BHIWN_DADRI3 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:16:55.843 BHIWANI LINE E_BHIWN_DADRI3 PRT PROTECTION TRIP Bad Valid
'02-01-2010 '03:17:06.911 BHIWANI LINE E_BHIWN_DADRI3 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:17:08.365 BALLABGARH CB E_09(SMYUR-1) STTS BETWEEN Bad Valid
'02-01-2010 '03:17:09.693 SAMAYUR CB E_01(BLBGH-1) STTS OPEN GOOD Valid
'02-01-2010 '03:17:20.917 NUNAMAJRA CB E_12(ROTAK-2) STTS CLOSED GOOD Valid
'02-01-2010 '03:17:24.111 REWARI CB E_01(DADRI) STTS CLOSED GOOD Valid
'02-01-2010 '03:17:24.117 REWARI LINE E_DADRI_RWARI PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:17:28.540 JAGADHRI CB E_5 STTS BETWEEN Bad Valid
'02-01-2010 '03:17:41.303 JAGADHRI CB E_4 STTS OPEN GOOD Valid
'02-01-2010 '03:17:55.751 DADRI CB E_14(BHIWN-4) STTS BETWEEN Bad Valid
'02-01-2010 '03:17:56.585 DADRI CB E_14(BHIWN-4) STTS CLOSED GOOD Valid
'02-01-2010 '03:17:59.718 JAGADHRI CB E_6 STTS BETWEEN Bad Valid
'02-01-2010 '03:18:09.641 BHIWANI LINE E_BHIWN_DADRI4 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:20:03.001 SAHIBABAD CB E_02(GAZIT-1) STTS OPEN GOOD Valid
'02-01-2010 '03:20:05.604 BHIWANI LINE E_BHIWN_DADRI3 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:20:18.261 DULHA_NH LINE F_DULHA_KISHN1 PRT CLOSED BAD TIME
'02-01-2010 '03:20:19.313 DULHA_NH CB F_04(KISHN-2) STTS OPEN BAD TIME
'02-01-2010 '03:20:19.822 NARWANA LINE E_NARWN_SFDON1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:21:02.869 BHAKRA DAM CB E_33(G10) STTS CLOSED GOOD Valid
'02-01-2010 '03:21:39.530 NARWANA LINE E_NARWN_SFDON1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:21:39.569 NARWANA CB E_05(SFDON-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:21:39.650 NARWANA CB E_05(SFDON-1) STTS OPEN GOOD Valid
'02-01-2010 '03:22:05.760 SANGRUR CB E_07(T1) STTS BETWEEN Bad Valid
'02-01-2010 '03:22:08.143 SANGRUR CB E_06(T2) STTS OPEN GOOD Valid
'02-01-2010 '03:22:08.145 SANGRUR CB E_06(T2) STTS BETWEEN Bad Valid
'02-01-2010 '03:22:48.151 SANGRUR CB E_04(HISAR-2) STTS CLOSED GOOD Valid
'02-01-2010 '03:22:57.238 SHATABDINAGAR CB E_02(MEERT) STTS OPEN GOOD Valid
'02-01-2010 '03:22:59.204 ROHTAK CB E_04(PANTH-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:22:59.296 ROHTAK CB E_04(PANTH-1) STTS INVALID Bad Valid
'02-01-2010 '03:23:31.178 BADSHAPUR CB E_07(RWARI) STTS OPEN GOOD Valid
'02-01-2010 '03:23:32.450 SAMAYUR CB E_19(BADSH-1) STTS OPEN GOOD Valid
'02-01-2010 '03:24:14.480 SAHIBABAD CB E_02(GAZIT-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:24:51.141 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '03:24:51.141 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '03:24:55.156 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '03:24:55.156 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '03:25:06.848 MISS GANGUWAL CB E_09(T2) STTS OPEN GOOD Valid
'02-01-2010 '03:25:09.551 MISS GANGUWAL CB E_08(T1) STTS OPEN GOOD Valid
'02-01-2010 '03:26:03.116 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '03:26:03.116 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '03:26:05.146 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '03:26:05.146 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '03:26:19.080 SANGRUR CB E_01(JAMAL-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:27:29.035 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '03:27:31.146 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '03:27:34.181 SANGRUR CB E_02(JAMAL-2) STTS CLOSED GOOD Valid
'02-01-2010 '03:27:51.597 NUNAMAJRA CB E_10(BHADR-2) STTS CLOSED GOOD Valid
'02-01-2010 '03:27:51.623 NUNAMAJRA CB E_10(BHADR-2) STTS BETWEEN Bad Valid
'02-01-2010 '03:28:30.606 KARTARPUR 220 CB E_02(T1) STTS OPEN GOOD Valid
'02-01-2010 '03:28:30.648 KARTARPUR 220 CB E_02(T1) STTS INVALID Bad Valid
'02-01-2010 '03:28:38.470 BHIWANI CB E_02(HISAR-2) STTS OPEN GOOD Valid
'02-01-2010 '03:28:38.474 BHIWANI LINE E_BHIWN_HISAR2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:28:38.509 HISSAR CB E_06(BHIWN-2) STTS BETWEEN Bad Valid
'02-01-2010 '03:28:38.580 HISSAR LINE E_BHIWN_HISAR2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:28:38.744 BHIWANI LINE E_BHIWN_HISAR2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:28:38.885 HISSAR LINE E_BHIWN_HISAR2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:28:39.070 BHIWANI LINE E_BHIWN_HISAR2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:28:39.206 HISSAR LINE E_BHIWN_HISAR2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:28:39.344 BHIWANI LINE E_BHIWN_HISAR2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:28:39.512 HISSAR LINE E_BHIWN_HISAR2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:28:39.604 HISSAR CB E_06(BHIWN-2) STTS CLOSED GOOD Valid
'02-01-2010 '03:28:39.669 BHIWANI LINE E_BHIWN_HISAR2 PRT PROTECTION TRIP Bad Valid
'02-01-2010 '03:28:39.669 HISSAR CB E_06(BHIWN-2) STTS OPEN GOOD Valid
'02-01-2010 '03:28:39.833 HISSAR LINE E_BHIWN_HISAR2 PRT PROTECTION TRIP Bad Valid
'02-01-2010 '03:28:43.112 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '03:28:43.112 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '03:28:44.858 KARTARPUR 220 CB E_01(JALAN) STTS OPEN GOOD Valid
'02-01-2010 '03:28:45.156 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '03:28:45.156 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '03:28:48.941 BHIWANI LINE E_BHIWN_HISAR2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:29:07.699 JAMALPUR CB E_02(SNGRU-1) STTS INVALID Bad Valid
'02-01-2010 '03:29:18.174 JAMALPUR CB E_01(SNGRU-2) STTS CLOSED GOOD Valid
'02-01-2010 '03:30:43.779 KAITHAL CB E_02(NARWN-2) STTS BETWEEN Bad Valid
'02-01-2010 '03:30:43.893 KAITHAL CB E_02(NARWN-2) STTS CLOSED GOOD Valid
'02-01-2010 '03:31:09.087 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '03:31:09.087 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '03:31:15.156 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '03:31:15.156 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
9 of 18
Chapter - 5 _ ANNEXE -5/II (page 9 of 18)
![Page 148: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/148.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From RTUS Reporting to SLDCsANNEX-5/II
Part-1
'02-01-2010 '03:31:16.549 JAMALPUR CB E_13(T4) STTS CLOSED GOOD Valid
'02-01-2010 '03:31:27.529 JIND_220KV CB E_07(T2) STTS OPEN GOOD Valid
'02-01-2010 '03:31:47.638 ABLOWAL CB E_6(PATRA) STTS OPEN GOOD Valid
'02-01-2010 '03:31:59.875 NARWANA LINE E_HISAR_NARWN PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:31:59.919 NARWANA CB E_10(HISAR) STTS OPEN GOOD Valid
'02-01-2010 '03:32:00.491 NARWANA CB E_10(HISAR) STTS CLOSED GOOD Valid
'02-01-2010 '03:32:00.525 NARWANA LINE E_HISAR_NARWN PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:32:03.472 JAMALPUR CB E_03(BHAKR-2) STTS CLOSED GOOD Valid
'02-01-2010 '03:32:23.593 SANGRUR CB E_06(T2) STTS CLOSED GOOD Valid
'02-01-2010 '03:32:23.623 SANGRUR CB E_06(T2) STTS INVALID Bad Valid
'02-01-2010 '03:33:34.685 NUNAMAJRA CB E_10(BHADR-2) STTS CLOSED GOOD Valid
'02-01-2010 '03:33:41.673 ROHTAK CB E_04(PANTH-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:33:41.684 NUNAMAJRA CB E_10(BHADR-2) STTS BETWEEN Bad Valid
'02-01-2010 '03:33:41.762 ROHTAK CB E_04(PANTH-1) STTS INVALID Bad Valid
'02-01-2010 '03:35:02.821 SAHIBABAD CB E_02(GAZIT-1) STTS OPEN GOOD Valid
'02-01-2010 '03:35:03.076 SAHIBABAD CB E_02(GAZIT-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:35:20.486 BARNALA CB E_1(SNGRU) STTS OPEN GOOD Valid
'02-01-2010 '03:35:28.854 SIMBHOLI CB E_03(SHATB-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:35:41.916 NARWANA CB E_02(KTHAL-2) STTS CLOSED GOOD Valid
'02-01-2010 '03:35:41.987 NARWANA CB E_02(KTHAL-2) STTS OPEN GOOD Valid
'02-01-2010 '03:35:44.179 BARNALA CB E_2(GHTP_-1) STTS BETWEEN Bad Valid
'02-01-2010 '03:35:53.357 BARNALA CB E_4 STTS BETWEEN Bad Valid
'02-01-2010 '03:37:24.399 SANGRUR CB E_07(T1) STTS CLOSED GOOD Valid
'02-01-2010 '03:37:38.189 BHAKRA DAM CB E_28(JAMAL-2) STTS CLOSED GOOD Valid
'02-01-2010 '03:38:32.350 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '03:39:07.457 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '03:39:54.333 JAMALPUR CB E_04(BHAKR-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:40:40.778 BHIWANI LINE E_BHIWN_HISAR2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:40:57.502 BHAKRA DAM CB E_32(JAMAL-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:41:40.325 JAMALPUR CB E_09(T2) STTS CLOSED GOOD Valid
'02-01-2010 '03:43:00.419 JAMALPUR CB E_15(T6) STTS CLOSED GOOD Valid
'02-01-2010 '03:43:29.851 NUNAMAJRA CB E_07(DLTBD-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:43:29.884 NUNAMAJRA CB E_07(DLTBD-1) STTS INVALID Bad Valid
'02-01-2010 '03:43:36.616 NUNAMAJRA CB E_07(DLTBD-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:43:36.646 NUNAMAJRA CB E_07(DLTBD-1) STTS INVALID Bad Valid
'02-01-2010 '03:44:24.538 MUZFRNGR-2 CB E_03(RISH2-1) STTS OPEN GOOD Valid
'02-01-2010 '03:44:50.094 NARWANA LINE E_HISAR_NARWN PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:44:50.138 NARWANA CB E_10(HISAR) STTS OPEN GOOD Valid
'02-01-2010 '03:44:50.704 NARWANA CB E_10(HISAR) STTS CLOSED GOOD Valid
'02-01-2010 '03:44:50.739 NARWANA LINE E_HISAR_NARWN PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:45:05.881 PANIPATTPS CB E_08(PANPT-3) STTS BETWEEN Bad Valid
'02-01-2010 '03:45:06.705 MORADABAD1 CB F_04 STTS CLOSED GOOD Valid
'02-01-2010 '03:45:31.485 KAITHAL CB E_01(NARWN-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:45:31.530 KAITHAL CB E_01(NARWN-1) STTS INVALID Bad Valid
'02-01-2010 '03:46:11.091 SAHIBABAD CB E_86(T1) STTS OPEN GOOD Valid
'02-01-2010 '03:46:12.396 SAHIBABAD CB E_86(T1) STTS CLOSED GOOD Valid
'02-01-2010 '03:46:12.796 SAHIBABAD CB E_86(T1) STTS BETWEEN Bad Valid
'02-01-2010 '03:46:12.880 HISSAR LINE E_HISAR_KHTRI PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:46:12.904 HISSAR CB E_04(KHTRI) STTS OPEN GOOD Valid
'02-01-2010 '03:46:13.172 KHETRI CB E_02(HISAR) STTS OPEN GOOD Valid
'02-01-2010 '03:46:17.627 SAHIBABAD CB E_86(T1) STTS CLOSED GOOD Valid
'02-01-2010 '03:46:45.154 MISS GANGUWAL CB E_02(DEHAR-2) STTS OPEN GOOD Valid
'02-01-2010 '03:46:55.728 MISS GANGUWAL CB E_01(DEHAR-1) STTS OPEN GOOD Valid
'02-01-2010 '03:47:06.196 PANIPATTPS CB E_08(PANPT-3) STTS CLOSED GOOD Valid
'02-01-2010 '03:47:08.900 MISS GANGUWAL CB E_11(BHAKR-4) STTS OPEN GOOD Valid
'02-01-2010 '03:47:10.767 MISS GANGUWAL CB E_12(BHAKR-5) STTS OPEN GOOD Valid
'02-01-2010 '03:47:12.071 MISS GANGUWAL CB E_10 STTS OPEN GOOD Valid
'02-01-2010 '03:47:26.008 MISS GANGUWAL CB E_13(BHAKR-1) STTS OPEN GOOD Valid
'02-01-2010 '03:47:30.890 ABLOWAL CB E_8(PATIA) STTS CLOSED GOOD Valid
'02-01-2010 '03:47:35.382 NARWANA CB E_05(SFDON-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:47:35.464 NARWANA CB E_05(SFDON-1) STTS OPEN GOOD Valid
'02-01-2010 '03:47:44.687 MISS GANGUWAL CB E_15(BHAKR-3) STTS OPEN GOOD Valid
'02-01-2010 '03:47:44.872 MISS GANGUWAL CB E_15(BHAKR-3) STTS BETWEEN Bad Valid
'02-01-2010 '03:47:52.012 SAMAYUR CB E_11(PALLI-1) STTS BETWEEN Bad Valid
'02-01-2010 '03:47:52.990 SAMAYUR CB E_11(PALLI-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:48:35.799 MISS GANGUWAL CB E_14(BHAKR-2) STTS OPEN GOOD Valid
'02-01-2010 '03:49:08.479 BHAKRA DAM CB E_25 STTS INVALID Bad Valid
'02-01-2010 '03:49:08.916 BHAKRA DAM CB E_25 STTS CLOSED GOOD Valid
'02-01-2010 '03:50:02.467 HISSAR CB E_07(SNGRU-1) STTS BETWEEN Bad Valid
'02-01-2010 '03:50:02.534 HISSAR LINE E_HISAR_SNGRU1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:50:02.811 HISSAR LINE E_HISAR_SNGRU1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:50:03.213 HISSAR LINE E_HISAR_SNGRU1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:50:03.487 HISSAR LINE E_HISAR_SNGRU1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:50:03.564 HISSAR CB E_07(SNGRU-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:50:03.904 HISSAR LINE E_HISAR_SNGRU1 PRT PROTECTION TRIP Bad Valid
'02-01-2010 '03:50:21.812 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '03:50:22.683 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '03:50:27.117 HISSAR LINE E_HISAR_SNGRU1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:50:45.898 BHAKRA DAM CB E_26(GANGL-4) STTS CLOSED GOOD Valid
10 of 18
Chapter - 5 _ ANNEXE -5/II (page 10 of 18)
![Page 149: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/149.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From RTUS Reporting to SLDCsANNEX-5/II
Part-1
'02-01-2010 '03:51:14.826 BHAKRA DAM CB E_22(GANGL-5) STTS CLOSED GOOD Valid
'02-01-2010 '03:51:43.743 BHIWA_PG CB F_8 (BALLB ICT-3 TIE) STTS OPEN
'02-01-2010 '03:51:43.746 BHIWA_PG CB F_7 (BALLB BUS-1) STTS OPEN
'02-01-2010 '03:53:03.174 BHIWANI CB E_06(T1) STTS CLOSED GOOD Valid
'02-01-2010 '03:53:12.134 SANGRUR CB E_09(T3) STTS CLOSED GOOD Valid
'02-01-2010 '03:53:13.124 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '03:53:13.124 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '03:53:14.833 SANGRUR CB E_09(T3) STTS BETWEEN Bad Valid
'02-01-2010 '03:53:15.156 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '03:53:15.156 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '03:53:24.501 BHIWANI CB F_1(ICT-1 BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:53:36.608 HISSAR LINE E_HISAR_SNGRU1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:53:40.942 BHIWANI CB F_4(ICT-1 BUS2) STTS CLOSED GOOD Valid
'02-01-2010 '03:54:45.550 NAKODAR_220 CB E_04(T1) STTS OPEN GOOD Valid
'02-01-2010 '03:54:51.573 MISS GANGUWAL CB E_12(BHAKR-5) STTS CLOSED GOOD Valid
'02-01-2010 '03:54:56.408 MISS GANGUWAL CB E_11(BHAKR-4) STTS CLOSED GOOD Valid
'02-01-2010 '03:55:01.879 PANIPATTPS CB E_05(PANPT-2) STTS OPEN GOOD Valid
'02-01-2010 '03:55:10.150 SANGRUR CB E_09(T3) STTS CLOSED GOOD Valid
'02-01-2010 '03:55:12.788 PANIPATTPS CB E_06(U2) STTS BETWEEN Bad Valid
'02-01-2010 '03:55:16.751 PANIPATTPS CB E_3X(U1) STTS BETWEEN Bad Valid
'02-01-2010 '03:55:47.127 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '03:55:47.127 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '03:55:53.146 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '03:55:53.146 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '03:56:25.830 HISSAR CB E_07(SNGRU-1) STTS BETWEEN Bad Valid
'02-01-2010 '03:56:25.909 HISSAR LINE E_HISAR_SNGRU1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:56:26.191 HISSAR LINE E_HISAR_SNGRU1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:56:26.689 HISSAR LINE E_HISAR_SNGRU1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:56:26.931 HISSAR CB E_07(SNGRU-1) STTS CLOSED GOOD Valid
'02-01-2010 '03:56:26.971 HISSAR LINE E_HISAR_SNGRU1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:56:27.474 HISSAR LINE E_HISAR_SNGRU1 PRT PROTECTION TRIP Bad Valid
'02-01-2010 '03:56:38.294 PANKI (T) CB E_U1(U01) STTS OPEN GOOD Valid
'02-01-2010 '03:56:43.955 MISS GANGUWAL CB E_08(T1) STTS CLOSED GOOD Valid
'02-01-2010 '03:56:52.402 NISSING CB E_08(KTHAL-1) STTS OPEN GOOD Valid
'02-01-2010 '03:56:52.460 NISSING CB E_11(SALEM-2) STTS CLOSED GOOD Valid
'02-01-2010 '03:57:28.616 SAMAYUR CB E_07(DADRI) STTS OPEN GOOD Valid
'02-01-2010 '03:57:28.676 DADRI CB E_07(SMYUR) STTS OPEN GOOD Valid
'02-01-2010 '03:57:28.738 DADRI LINE E_DADRI_SMYUR PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:57:29.077 DADRI LINE E_DADRI_SMYUR PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:57:29.428 DADRI LINE E_DADRI_SMYUR PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:57:29.760 DADRI LINE E_DADRI_SMYUR PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:57:30.110 DADRI LINE E_DADRI_SMYUR PRT PROTECTION TRIP Bad Valid
'02-01-2010 '03:57:41.908 DADRI LINE E_DADRI_SMYUR PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:58:00.643 NARWANA LINE E_HISAR_NARWN PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:58:00.690 NARWANA CB E_10(HISAR) STTS OPEN GOOD Valid
'02-01-2010 '03:58:01.239 NARWANA CB E_10(HISAR) STTS BETWEEN Bad Valid
'02-01-2010 '03:58:01.333 NARWANA LINE E_HISAR_NARWN PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:58:04.432 NARWANA LINE E_HISAR_NARWN PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:58:04.475 NARWANA CB E_10(HISAR) STTS OPEN GOOD Valid
'02-01-2010 '03:58:10.131 PONG CB E_08(T1) STTS OPEN GOOD Valid
'02-01-2010 '03:58:15.115 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '03:58:15.115 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '03:58:19.156 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '03:58:19.156 PANKI (T) CB E_U1(U01) STTS OPEN GOOD Valid
'02-01-2010 '03:58:28.426 MISS GANGUWAL CB E_09(T2) STTS CLOSED GOOD Valid
'02-01-2010 '03:58:29.147 HISSAR LINE E_HISAR_SNGRU1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '03:58:51.241 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '03:58:59.104 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '03:59:07.621 DULHA_NH LINE F_DULHA_KISHN1 PRT OPEN BAD TIME
'02-01-2010 '03:59:23.213 DADRI LINE E_DADRI_SMYUR PRT PROTECTION OK GOOD Valid
'02-01-2010 '03:59:48.194 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
11 of 18
Chapter - 5 _ ANNEXE -5/II (page 11 of 18)
![Page 150: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/150.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From Central Sector RTUsANNEX-5/II
Part-2
'02-01-2010 0:17:16.583 MANDAULA CB F_26( BARLEY2TIE) STTS BETWEEN Bad Valid
'02-01-2010 0:17:16.599 MANDAULA CB F_27(BAREILLY-2 BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 0:17:19.619 MANDAULA CB F_27(BAREILLY-2 BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 0:17:19.625 MANDAULA CB F_26( BARLEY2TIE) STTS OPEN GOOD Valid
'02-01-2010 0:18:37.812 MANDAULA CB F_22 (BAREILLY-1 BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 0:18:37.824 MANDAULA CB F_23( BARLEY-MEERT-1 TIE STTS BETWEEN Bad Valid
'02-01-2010 0:18:39.011 MANDAULA CB F_23( BARLEY-MEERT-1 TIE STTS CLOSED GOOD Valid
'02-01-2010 0:18:39.021 MANDAULA CB F_22 (BAREILLY-1 BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 0:21:45.856 MANDAULA CB F_22 (BAREILLY-1 BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 0:21:45.864 MANDAULA CB F_23( BARLEY-MEERT-1 TIE STTS BETWEEN Bad Valid
'02-01-2010 0:21:46.164 MANDAULA CB F_23( BARLEY-MEERT-1 TIE STTS OPEN GOOD Valid
'02-01-2010 0:22:20.921 MANDAULA CB F_22 (BAREILLY-1 BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 0:22:29.344 MANDAULA CB F_23( BARLEY-MEERT-1 TIE STTS CLOSED GOOD Valid
'02-01-2010 0:22:29.386 MANDAULA CB F_23( BARLEY-MEERT-1 TIE STTS OPEN GOOD Valid
'02-01-2010 0:22:36.510 MANDAULA CB F_23( BARLEY-MEERT-1 TIE STTS CLOSED GOOD Valid
'02-01-2010 0:22:36.553 MANDAULA CB F_23( BARLEY-MEERT-1 TIE STTS OPEN GOOD Valid
'02-01-2010 0:22:55.593 MANDAULA CB F_23( BARLEY-MEERT-1 TIE STTS CLOSED GOOD Valid
'02-01-2010 0:23:32.596 MEERUT CB F_12 MUZA1 BUS-2 STTS OPEN GOOD Valid
'02-01-2010 0:23:32.602 MEERUT CB F_11 TEHRI-II & MUZA1 TI STTS OPEN GOOD Valid
'02-01-2010 0:29:52.674 MANDAULA CB F_22 (BAREILLY-1 BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 0:29:52.737 MANDAULA CB F_23( BARLEY-MEERT-1 TIE STTS OPEN GOOD Valid
'02-01-2010 0:30:18.289 MANDAULA CB F_22 (BAREILLY-1 BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 0:30:39.662 MANDAULA CB F_23( BARLEY-MEERT-1 TIE STTS CLOSED GOOD Valid
'02-01-2010 0:34:16.274 MANDAULA CB F_6 (BAWANA MAIN BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 0:34:16.274 MANDAULA CB F_4( BAWANA MAIN BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 0:34:17.454 MANDAULA CB F_4( BAWANA MAIN BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 0:34:18.897 MANDAULA CB F_6 (BAWANA MAIN BUS-2) STTS OPEN GOOD Valid
'02-01-2010 0:35:10.293 MANDAULA CB F_6 (BAWANA MAIN BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 0:43:08.421 ABDULLAPUR CB F_6 (BWANA -2 BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 0:43:08.448 ABDULLAPUR CB F_5 (BWANA-2 NJPC) TIE STTS OPEN GOOD Valid
'02-01-2010 0:43:08.922 ABDULLAPUR LINE F_ABDUL_BWANA2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 0:43:08.932 ABDULLAPUR CB F_6 (BWANA -2 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 0:46:27.050 MEERUT CB F_12 MUZA1 BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 0:46:39.611 MEERUT CB F_11 TEHRI-II & MUZA1 TI STTS CLOSED GOOD Valid
'02-01-2010 0:51:42.299 MANDAULA CB F_22 (BAREILLY-1 BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 0:51:42.306 MANDAULA CB F_23( BARLEY-MEERT-1 TIE STTS BETWEEN Bad Valid
'02-01-2010 0:51:43.488 MANDAULA CB F_23( BARLEY-MEERT-1 TIE STTS CLOSED GOOD Valid
'02-01-2010 0:51:43.498 MANDAULA CB F_22 (BAREILLY-1 BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 0:53:11.386 PATIALA CB F_3 (MALER K BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 0:53:11.399 PATIALA CB F_2(NALAG-MALER K TIE) STTS BETWEEN Bad Valid
'02-01-2010 0:53:12.600 PATIALA CB F_3 (MALER K BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 0:53:13.634 PATIALA CB F_2(NALAG-MALER K TIE) STTS OPEN GOOD Valid
'02-01-2010 0:54:47.813 ABDULLAPUR CB F_6 (BWANA -2 BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 0:54:47.838 ABDULLAPUR LINE F_ABDUL_BWANA2 PRT PROTECTION OK GOOD Valid
'02-01-2010 0:54:49.252 ABDULLAPUR LINE F_ABDUL_BWANA2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 0:54:49.271 ABDULLAPUR CB F_6 (BWANA -2 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 0:55:23.844 MANDAULA CB F_26( BARLEY2TIE) STTS BETWEEN Bad Valid
'02-01-2010 0:55:23.857 MANDAULA CB F_27(BAREILLY-2 BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 0:55:25.907 MANDAULA CB F_27(BAREILLY-2 BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 0:55:25.922 MANDAULA CB F_26( BARLEY2TIE) STTS OPEN GOOD Valid
'02-01-2010 0:56:42.297 ABDULLAPUR LINE F_ABDUL_BWANA1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 0:56:42.316 ABDULLAPUR CB F_2( BAWANA -1 TIE) STTS BETWEEN Bad Valid
'02-01-2010 0:56:42.318 ABDULLAPUR CB F_3 (BAWANA-1 BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 0:56:43.578 ABDULLAPUR CB F_3 (BAWANA-1 BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 0:56:43.586 ABDULLAPUR CB F_2( BAWANA -1 TIE) STTS CLOSED GOOD Valid
'02-01-2010 0:56:43.606 ABDULLAPUR LINE F_ABDUL_BWANA1 PRT PROTECTION OK GOOD Valid
'02-01-2010 0:57:23.396 MANDAULA CB F_22 (BAREILLY-1 BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 0:57:23.399 MANDAULA CB F_23( BARLEY-MEERT-1 TIE STTS BETWEEN Bad Valid
'02-01-2010 0:57:24.600 MANDAULA CB F_22 (BAREILLY-1 BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 0:57:26.283 MANDAULA CB F_23( BARLEY-MEERT-1 TIE STTS OPEN GOOD Valid
'02-01-2010 0:57:33.262 MANDAULA CB F_22 (BAREILLY-1 BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 0:57:54.069 ABDULLAPUR CB F_2( BAWANA -1 TIE) STTS BETWEEN Bad Valid
'02-01-2010 0:57:54.070 ABDULLAPUR CB F_3 (BAWANA-1 BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 0:57:55.332 ABDULLAPUR CB F_3 (BAWANA-1 BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 0:57:55.338 ABDULLAPUR CB F_2( BAWANA -1 TIE) STTS CLOSED GOOD Valid
'02-01-2010 0:57:55.384 ABDULLAPUR LINE F_ABDUL_BWANA1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 0:57:55.401 ABDULLAPUR CB F_3 (BAWANA-1 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 0:57:55.406 ABDULLAPUR CB F_2( BAWANA -1 TIE) STTS OPEN GOOD Valid
'02-01-2010 1:06:31.146 MALERKOTLA CB F_2 DADRI ICT-1 TIE STTS BETWEEN Bad Valid
'02-01-2010 1:06:31.151 MALERKOTLA CB F_3 DADRI MAIN BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 1:06:31.213 DADRI (TH) CB (F_14)MALER MANDULA-1 TI STTS BETWEEN Bad Valid
'02-01-2010 1:06:31.218 DADRI (TH) CB (F_13)MALERK MAIN BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 1:06:32.314 MALERKOTLA CB F_3 DADRI MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 1:06:32.374 DADRI (TH) CB (F_13)MALERK MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 1:06:33.139 MALERKOTLA CB F_2 DADRI ICT-1 TIE STTS CLOSED GOOD Valid
'02-01-2010 1:06:33.488 DADRI (TH) CB (F_14)MALER MANDULA-1 TI STTS CLOSED GOOD Valid
Chapter - 5 _ ANNEXE -5/II (page 12 of 18)
![Page 151: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/151.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From Central Sector RTUsANNEX-5/II
Part-2
'02-01-2010 1:08:06.362 BALLABGARH CB F_50 FACT MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 1:11:12.500 MANDAULA CB E_01(NAREL-1) STTS OPEN GOOD Valid
'02-01-2010 1:18:28.422 PATIALA CB F_2(NALAG-MALER K TIE) STTS CLOSED GOOD Valid
'02-01-2010 1:21:01.785 MEERUT CB F_12 MUZA1 BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 1:21:01.794 MEERUT CB F_11 TEHRI-II & MUZA1 TI STTS BETWEEN Bad Valid
'02-01-2010 1:21:02.806 MEERUT CB F_12 MUZA1 BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 1:21:02.846 MEERUT CB F_11 TEHRI-II & MUZA1 TI STTS CLOSED GOOD Valid
'02-01-2010 1:22:41.361 MANDAULA CB F_22 (BAREILLY-1 BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 1:22:45.072 MANDAULA CB F_22 (BAREILLY-1 BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 1:30:55.297 PATIALA CB F_3 (MALER K BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 1:30:55.309 PATIALA CB F_2(NALAG-MALER K TIE) STTS BETWEEN Bad Valid
'02-01-2010 1:30:56.510 PATIALA CB F_3 (MALER K BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 1:30:57.538 PATIALA CB F_2(NALAG-MALER K TIE) STTS OPEN GOOD Valid
'02-01-2010 1:32:04.868 PATIALA CB F_3 (MALER K BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 1:32:05.064 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP GOOD Valid
'02-01-2010 1:32:05.553 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION OK GOOD Valid
'02-01-2010 1:32:05.738 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP GOOD Valid
'02-01-2010 1:32:06.080 PATIALA CB F_3 (MALER K BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 1:32:06.217 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION OK GOOD Valid
'02-01-2010 1:32:06.396 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP Bad Valid
'02-01-2010 1:32:07.419 NALAGARH CB F_17 PATIA TIE STTS OPEN GOOD Valid
'02-01-2010 1:32:14.331 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP GOOD Valid
'02-01-2010 1:34:33.402 PATIALA CB F_2(NALAG-MALER K TIE) STTS CLOSED GOOD Valid
'02-01-2010 1:34:33.470 PATIALA CB F_2(NALAG-MALER K TIE) STTS OPEN GOOD Valid
'02-01-2010 1:35:54.307 MANDAULA CB E_02(NAREL-2) STTS OPEN GOOD Valid
'02-01-2010 1:36:28.768 KAITHAL CB F_4(HISAR MAIN BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 1:36:28.778 KAITHAL CB F_5 (HISAR ICT-1 TIE) STTS BETWEEN Bad Valid
'02-01-2010 1:36:28.952 HISSAR CB F_21( KAITH MAIN BUS-1) STTS INVALID Bad InvRTU
'02-01-2010 1:36:28.953 HISSAR CB F_21( KAITH MAIN BUS-1) STTS OPEN GOOD InvRTU
'02-01-2010 1:36:28.980 HISSAR CB F_2T (ICT-2 KAITHAL TIE) STTS OPEN GOOD InvRTU
'02-01-2010 1:36:29.742 KAITHAL CB F_4(HISAR MAIN BUS-1) STTS OPEN GOOD Valid
'02-01-2010 1:36:29.755 KAITHAL CB F_4(HISAR MAIN BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 1:36:29.771 KAITHAL CB F_4(HISAR MAIN BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 1:36:29.822 KAITHAL CB F_4(HISAR MAIN BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 1:36:29.872 KAITHAL CB F_5 (HISAR ICT-1 TIE) STTS OPEN GOOD Valid
'02-01-2010 1:36:32.510 KAITHAL CB F_4(HISAR MAIN BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 1:37:09.134 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION OK GOOD Valid
'02-01-2010 1:37:37.037 NALAGARH CB F_17 PATIA TIE STTS CLOSED GOOD Valid
'02-01-2010 1:40:21.368 PATIALA CB F_2(NALAG-MALER K TIE) STTS CLOSED GOOD Valid
'02-01-2010 1:46:51.051 BALLABGARH CB F_3 BAMNL-1 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 1:46:51.083 BALLABGARH CB F_1 BAMNL-1 MAIN BUS-2 STTS OPEN GOOD Valid
'02-01-2010 1:46:52.310 BALLABGARH CB F_3 BAMNL-1 MAIN BUS-1 STTS CLOSED GOOD Valid
'02-01-2010 1:46:59.488 PATIALA CB F_3 (MALER K BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 1:46:59.501 PATIALA CB F_2(NALAG-MALER K TIE) STTS BETWEEN Bad Valid
'02-01-2010 1:47:00.713 PATIALA CB F_3 (MALER K BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 1:47:01.725 PATIALA CB F_2(NALAG-MALER K TIE) STTS OPEN GOOD Valid
'02-01-2010 1:48:14.773 MANDAULA CB E_04(GOPAL-2) STTS BETWEEN Bad Valid
'02-01-2010 1:48:27.060 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 1:48:27.060 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 1:48:28.344 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS CLOSED GOOD Valid
'02-01-2010 1:48:28.345 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 1:52:09.234 BALLABGARH CB F_3 BAMNL-1 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 1:52:10.490 BALLABGARH CB F_3 BAMNL-1 MAIN BUS-1 STTS CLOSED GOOD Valid
'02-01-2010 1:52:10.557 BALLABGARH CB F_3 BAMNL-1 MAIN BUS-1 STTS OPEN GOOD Valid
'02-01-2010 1:52:48.615 PATIALA CB F_3 (MALER K BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 1:52:48.817 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP GOOD Valid
'02-01-2010 1:52:49.301 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION OK GOOD Valid
'02-01-2010 1:52:49.487 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP GOOD Valid
'02-01-2010 1:52:49.827 PATIALA CB F_3 (MALER K BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 1:52:49.969 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION OK GOOD Valid
'02-01-2010 1:52:50.151 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP Bad Valid
'02-01-2010 1:52:51.174 NALAGARH CB F_17 PATIA TIE STTS OPEN GOOD Valid
'02-01-2010 1:52:56.371 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP GOOD Valid
'02-01-2010 1:54:35.399 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION OK GOOD Valid
'02-01-2010 1:55:02.475 NALAGARH CB F_17 PATIA TIE STTS CLOSED GOOD Valid
'02-01-2010 2:03:24.092 HISSAR CB F_21( KAITH MAIN BUS-1) STTS CLOSED GOOD InvRTU
'02-01-2010 2:03:26.037 HISSAR CB F_21( KAITH MAIN BUS-1) STTS OPEN GOOD InvRTU
'02-01-2010 2:05:52.711 MANDAULA CB E_04(GOPAL-2) STTS CLOSED GOOD Valid
'02-01-2010 2:06:05.563 MANDAULA CB F_6 (BAWANA MAIN BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 2:06:05.564 MANDAULA CB F_4( BAWANA MAIN BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 2:06:06.740 MANDAULA CB F_4( BAWANA MAIN BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 2:06:08.183 MANDAULA CB F_6 (BAWANA MAIN BUS-2) STTS OPEN GOOD Valid
'02-01-2010 2:06:38.732 MANDAULA CB F_6 (BAWANA MAIN BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 2:07:20.389 MANDAULA CB E_04(GOPAL-2) STTS BETWEEN Bad Valid
'02-01-2010 2:08:36.456 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 2:08:36.456 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 2:08:37.739 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS CLOSED GOOD Valid
Chapter - 5 _ ANNEXE -5/II (page 13 of 18)
![Page 152: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/152.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From Central Sector RTUsANNEX-5/II
Part-2
'02-01-2010 2:08:37.739 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 2:10:08.496 PATIALA CB F_3 (MALER K BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 2:10:08.716 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP GOOD Valid
'02-01-2010 2:10:09.202 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION OK GOOD Valid
'02-01-2010 2:10:09.397 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP GOOD Valid
'02-01-2010 2:10:09.710 PATIALA CB F_3 (MALER K BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 2:10:09.864 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION OK GOOD Valid
'02-01-2010 2:10:10.050 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP Bad Valid
'02-01-2010 2:10:11.062 NALAGARH CB F_17 PATIA TIE STTS OPEN GOOD Valid
'02-01-2010 2:10:18.401 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP GOOD Valid
'02-01-2010 2:10:38.364 NAPTHA CB F_G3(H03) STTS BETWEEN Bad Valid
'02-01-2010 2:10:38.390 NAPTHA CB F_G3(H03) STTS INVALID Bad Valid
'02-01-2010 2:15:23.997 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION OK GOOD Valid
'02-01-2010 2:17:12.460 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 2:17:12.460 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 2:17:13.723 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS CLOSED GOOD Valid
'02-01-2010 2:17:13.723 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 2:17:47.903 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 2:17:47.903 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 2:17:49.183 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 2:17:49.183 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS CLOSED GOOD Valid
'02-01-2010 2:18:06.054 BAHADURGARH CB E_4(MAJRA-1) STTS CLOSED GOOD Valid
'02-01-2010 2:18:07.556 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 2:18:07.556 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 2:18:08.820 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS CLOSED GOOD Valid
'02-01-2010 2:18:08.820 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 2:19:24.191 ABDULLAPUR CB F_6 (BWANA -2 BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 2:19:24.215 ABDULLAPUR LINE F_ABDUL_BWANA2 PRT PROTECTION OK GOOD Valid
'02-01-2010 2:19:44.546 ABDULLAPUR CB F_5 (BWANA-2 NJPC) TIE STTS CLOSED GOOD Valid
'02-01-2010 2:22:04.784 ABDULLAPUR CB F_6 (BWANA -2 BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 2:22:04.817 ABDULLAPUR CB F_5 (BWANA-2 NJPC) TIE STTS OPEN GOOD Valid
'02-01-2010 2:22:06.024 ABDULLAPUR CB F_6 (BWANA -2 BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 2:28:03.956 ABDULLAPUR CB F_5 (BWANA-2 NJPC) TIE STTS CLOSED GOOD Valid
'02-01-2010 2:28:05.882 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 2:28:05.882 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 2:28:07.164 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 2:28:07.164 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS CLOSED GOOD Valid
'02-01-2010 2:29:19.574 MOGA_ LINE F_FTEBD_MOGA_2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 2:29:19.580 MOGA_ CB F_5 (FTEBD-2 BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 2:29:19.580 MOGA_ CB F_8 (ICT-3 HISAR-2 TIE) STTS BETWEEN Bad Valid
'02-01-2010 2:29:19.606 MOGA_ LINE F_FTEBD_MOGA_2 PRT PROTECTION OK GOOD Valid
'02-01-2010 2:29:20.823 MOGA_ CB F_5 (FTEBD-2 BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 2:29:20.867 MOGA_ LINE F_FTEBD_MOGA_2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 2:29:20.894 MOGA_ LINE F_FTEBD_MOGA_2 PRT PROTECTION OK GOOD Valid
'02-01-2010 2:29:20.920 MOGA_ CB F_5 (FTEBD-2 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 2:29:20.925 MOGA_ CB F_8 (ICT-3 HISAR-2 TIE) STTS OPEN GOOD Valid
'02-01-2010 2:31:06.496 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS OPEN GOOD Valid
'02-01-2010 2:31:06.496 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS OPEN GOOD Valid
'02-01-2010 2:33:53.267 KAITHAL CB E_06(KTHAL-2) STTS BETWEEN Bad Valid
'02-01-2010 2:33:54.597 KAITHAL CB E_06(KTHAL-2) STTS INVALID Bad Valid
'02-01-2010 2:36:43.636 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 2:36:43.636 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS CLOSED GOOD Valid
'02-01-2010 2:36:48.872 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 2:36:48.872 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 2:36:50.148 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS CLOSED GOOD Valid
'02-01-2010 2:36:50.148 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 2:36:56.584 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 2:36:56.584 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 2:36:57.844 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 2:36:57.844 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS CLOSED GOOD Valid
'02-01-2010 2:37:11.611 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 2:37:11.611 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 2:37:12.890 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS CLOSED GOOD Valid
'02-01-2010 2:37:12.890 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 2:38:42.726 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 2:38:42.726 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 2:38:43.982 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS CLOSED GOOD Valid
'02-01-2010 2:38:43.982 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 2:38:45.627 BADARPUR CB E_18(ALWAR) STTS OPEN GOOD Valid
'02-01-2010 2:43:12.447 HISSAR LINE E_FTEBD_HISAR1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 2:43:12.479 HISSAR CB E_L3(FTEBD-1) STTS OPEN GOOD Valid
'02-01-2010 2:46:30.366 HISSAR LINE E_FTEBD_HISAR1 PRT PROTECTION OK GOOD Valid
'02-01-2010 2:48:43.751 MANDAULA CB E_03(GOPAL-1) STTS BETWEEN Bad Valid
'02-01-2010 2:48:59.347 ABDULLAPUR CB F_3 (BAWANA-1 BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 2:48:59.371 ABDULLAPUR LINE F_ABDUL_BWANA1 PRT PROTECTION OK GOOD Valid
'02-01-2010 2:49:00.111 ABDULLAPUR LINE F_ABDUL_BWANA1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 2:49:00.159 ABDULLAPUR CB F_3 (BAWANA-1 BUS-2) STTS OPEN GOOD Valid
Chapter - 5 _ ANNEXE -5II (page 14 of 18)
![Page 153: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/153.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From Central Sector RTUsANNEX-5/II
Part-2
'02-01-2010 2:51:08.596 PATIALA CB F_3 (MALER K BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 2:51:08.792 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP GOOD Valid
'02-01-2010 2:51:09.281 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION OK GOOD Valid
'02-01-2010 2:51:09.467 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP GOOD Valid
'02-01-2010 2:51:09.816 PATIALA CB F_3 (MALER K BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 2:51:09.945 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION OK GOOD Valid
'02-01-2010 2:51:10.130 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP Bad Valid
'02-01-2010 2:51:20.481 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION TRIP GOOD Valid
'02-01-2010 2:51:47.632 BADARPUR CB E_18(ALWAR) STTS CLOSED GOOD Valid
'02-01-2010 2:52:35.885 BADARPUR CB E_18(ALWAR) STTS OPEN GOOD Valid
'02-01-2010 2:54:57.120 ABDULLAPUR CB F_5 (BWANA-2 NJPC) TIE STTS BETWEEN Bad Valid
'02-01-2010 2:54:57.125 ABDULLAPUR CB F_6 (BWANA -2 BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 2:54:58.333 ABDULLAPUR CB F_6 (BWANA -2 BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 2:54:58.363 ABDULLAPUR LINE F_ABDUL_BWANA2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 2:54:58.374 ABDULLAPUR CB F_6 (BWANA -2 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 2:54:58.378 ABDULLAPUR CB F_5 (BWANA-2 NJPC) TIE STTS OPEN GOOD Valid
'02-01-2010 2:55:01.503 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 2:55:01.503 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 2:55:01.687 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS OPEN GOOD Valid
'02-01-2010 2:55:01.687 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS OPEN GOOD Valid
'02-01-2010 2:55:01.734 BALLABGARH CB F_28 MAINPURI-2 MAIN BUS STTS OPEN GOOD Valid
'02-01-2010 2:55:01.736 BALLABGARH CB F_9 ICT-4 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 2:55:01.738 BALLABGARH CB F_25 MAINPURI-1 MAIN BUS STTS OPEN GOOD Valid
'02-01-2010 2:55:01.742 BALLABGARH CB F_21 REACTOR MAIN BUS-1 STTS OPEN GOOD Valid
'02-01-2010 2:55:01.744 BALLABGARH CB F_15 AGRA MAIN BUS-1 STTS OPEN GOOD Valid
'02-01-2010 2:55:01.745 BALLABGARH CB F_18 GNOIDA MAIN BUS-1 STTS OPEN GOOD Valid
'02-01-2010 2:55:01.746 BALLABGARH CB F_6 ICT-1 MAIN BUS-1 STTS OPEN GOOD Valid
'02-01-2010 2:55:01.747 BALLABGARH CB F_23 KANPUR TIE STTS OPEN GOOD Valid
'02-01-2010 2:55:09.366 KAITHAL CB E_05(KTHAL-1) STTS BETWEEN Bad Valid
'02-01-2010 2:55:10.564 KAITHAL CB E_05(KTHAL-1) STTS OPEN GOOD Valid
'02-01-2010 2:56:32.388 MOGA_ CB F_7 (RGTPS & XFMR-4 TIE) STTS OPEN GOOD Valid
'02-01-2010 2:56:32.389 MOGA_ CB F_4 (RGTPS-1 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 2:56:34.004 NALAGARH LINE F_NALAG_PATIA PRT PROTECTION OK GOOD Valid
'02-01-2010 3:01:42.704 NALAGARH CB F_11( NAPTHA-1 ICT-3 TIE STTS OPEN GOOD Valid
'02-01-2010 3:01:42.705 NALAGARH CB F_10( NAPTHA-2 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 3:01:42.711 NAPTHA CB F_L1(NALAG-2) STTS OPEN GOOD Valid
'02-01-2010 3:01:43.058 URI CB F_04 UNIT-G2 STTS OPEN GOOD Valid
'02-01-2010 3:01:43.482 DADRI (TH) CB (F_14)MALER MANDULA-1 TI STTS OPEN GOOD Valid
'02-01-2010 3:01:43.484 DADRI (TH) CB (F_13)MALERK MAIN BUS-2 STTS OPEN GOOD Valid
'02-01-2010 3:01:43.634 NAPTHA CB F_G3(H03) STTS BETWEEN Bad Valid
'02-01-2010 3:01:43.644 NAPTHA CB F_G3(H03) STTS INVALID Bad Valid
'02-01-2010 3:01:43.742 NAPTHA CB F_L5(BASPA-1) STTS OPEN GOOD Valid
'02-01-2010 3:01:48.375 SALAL CB E_10(G3) STTS OPEN GOOD Valid
'02-01-2010 3:01:48.648 PATIALA CB F_3 (MALER K BUS-2) STTS OPEN GOOD Valid
'02-01-2010 3:01:48.898 SALAL BUS E_B1 LOV LOSS OF VOLT GOOD Valid
'02-01-2010 3:01:48.914 SALAL BUS E_B2 LOV LOSS OF VOLT GOOD Valid
'02-01-2010 3:01:49.202 SRINAGAR BUS F_B2 LOV LOSS OF VOLT GOOD Valid
'02-01-2010 3:01:49.228 SRINAGAR BUS F_B1 LOV LOSS OF VOLT GOOD Valid
'02-01-2010 3:01:51.265 CHAMERA II CB F_03(CHM_1- ) STTS BETWEEN Bad Valid
'02-01-2010 3:01:51.278 CHAMERA II CB F_07(KISHN) STTS BETWEEN Bad Valid
'02-01-2010 3:02:35.701 MEERUT CB F_12 MUZA1 BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 3:02:35.712 MEERUT CB F_11 TEHRI-II & MUZA1 TI STTS BETWEEN Bad Valid
'02-01-2010 3:02:36.730 MEERUT CB F_12 MUZA1 BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 3:02:36.761 MEERUT CB F_11 TEHRI-II & MUZA1 TI STTS CLOSED GOOD Valid
'02-01-2010 3:04:19.063 MALERKOTLA CB E_01(T1) STTS OPEN GOOD InvRTU
'02-01-2010 3:04:19.072 MALERKOTLA CB F_1 ICT-1 MAIN BUS-1 STTS OPEN GOOD InvRTU
'02-01-2010 3:04:26.591 MALERKOTLA CB F_4 (ICT-2 MAIN BUS-1) STTS OPEN GOOD InvRTU
'02-01-2010 3:04:26.607 MALERKOTLA XFMR_P 400/220KV ICT-2 PRT PROTECTION TRIP GOOD InvRTU
'02-01-2010 3:04:26.655 MALERKOTLA CB E_04(T2) STTS OPEN GOOD InvRTU
'02-01-2010 3:04:33.995 MALERKOTLA CB F_8( PATIALA & LUDHIANA STTS OPEN GOOD InvRTU
'02-01-2010 3:04:36.245 MALERKOTLA CB F_9 (PATIALA BUS-1I) STTS OPEN GOOD InvRTU
'02-01-2010 3:05:51.316 BAHADURGARH CB E_4(MAJRA-1) STTS CLOSED GOOD Valid
'02-01-2010 3:05:51.316 BAHADURGARH CB E_4(MAJRA-1) STTS CLOSED GOOD Valid
'02-01-2010 3:05:56.426 HISSAR CB E_L4(FTEBD-2) STTS BETWEEN Bad Valid
'02-01-2010 3:05:58.985 HISSAR CB E_L4(FTEBD-2) STTS OPEN GOOD Valid
'02-01-2010 3:07:48.344 BALLABGARH CB F_23 KANPUR TIE STTS CLOSED GOOD Valid
'02-01-2010 3:07:59.755 ABDULLAPUR ZBR F_ABDUL_NPTHA2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 3:07:59.780 ABDULLAPUR CB F_7 (NJPC-2 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 3:08:00.661 NAPTHA CB F_L2(ABDUL-2) STTS BETWEEN Bad Valid
'02-01-2010 3:08:33.899 BALLABGARH CB F_18 GNOIDA MAIN BUS-1 STTS CLOSED GOOD Valid
'02-01-2010 3:09:51.219 BALLABGARH CB F_15 AGRA MAIN BUS-1 STTS CLOSED GOOD Valid
'02-01-2010 3:10:43.626 JALLANDHAR CB F_13 LUDHIANA MAIN BUS-2 STTS OPEN GOOD Valid
'02-01-2010 3:10:52.756 JALLANDHAR CB F_14 LUDHIANA & ICT-2 T STTS OPEN GOOD Valid
'02-01-2010 3:10:55.930 JALLANDHAR CB F_15 ICT-2 MAIN BUS-1 STTS OPEN GOOD Valid
'02-01-2010 3:10:55.942 JALLANDHAR CB E_01(T2) STTS OPEN GOOD Valid
'02-01-2010 3:11:10.779 JALLANDHAR CB F_6(AMRITSAR BUS-2) STTS OPEN GOOD Valid
'02-01-2010 3:11:13.871 JALLANDHAR CB F_5 (MOGA-2 AMRIT TIE) STTS OPEN GOOD Valid
Chapter - 5 _ ANNEXE -5/II (page 15 of 18)
![Page 154: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/154.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From Central Sector RTUsANNEX-5/II
Part-2
'02-01-2010 3:11:17.323 MOGA_ CB F_2 (J NDHER-2 BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 3:11:17.339 MOGA_ CB F_3 (JALANDHER-1 &2 TIE) STTS OPEN GOOD Valid
'02-01-2010 3:11:17.381 JALLANDHAR CB F_4 MOGA-2 BUS-1 STTS OPEN GOOD Valid
'02-01-2010 3:11:20.155 MOGA_ CB F_2 (J NDHER-2 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 3:11:25.738 JALLANDHAR CB F_3 MOGA-1 BUS-2 STTS OPEN GOOD Valid
'02-01-2010 3:11:30.826 JALLANDHAR CB F_2 CHAMERA-1 MOGA-1 TIE STTS OPEN GOOD Valid
'02-01-2010 3:11:30.917 MOGA_ CB F_1 (J DHER-1 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 3:11:33.469 JALLANDHAR CB F_1 CHAMERA-1 BUS-1 STTS OPEN GOOD Valid
'02-01-2010 3:11:39.416 JALLANDHAR CB F_7 CHAMERA-2 MAIN BUS-2 STTS OPEN GOOD Valid
'02-01-2010 3:11:41.935 JALLANDHAR CB F_8 CHAMERA-2 TIE STTS OPEN GOOD Valid
'02-01-2010 3:11:46.458 MOGA_ CB E_05(MOGAN-2) STTS INVALID Bad Valid
'02-01-2010 3:11:53.216 JALLANDHAR CB E_12(T1) STTS OPEN GOOD Valid
'02-01-2010 3:11:53.218 JALLANDHAR CB F_11 ICT-1 TIE STTS OPEN GOOD Valid
'02-01-2010 3:12:13.218 MOGA_ CB F_13 (KISHNPUR-1 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 3:12:15.638 MOGA_ CB F_14( KISHENPUR-1 & RCTR STTS OPEN GOOD Valid
'02-01-2010 3:12:15.692 KISHENPUR CB F_13 MOGA-1 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 3:12:15.699 KISHENPUR CB F_13 MOGA-1 MAIN BUS-1 STTS OPEN GOOD Valid
'02-01-2010 3:12:15.704 KISHENPUR CB F_14 MOGA-1 TIE STTS OPEN GOOD Valid
'02-01-2010 3:12:24.324 MOGA_ CB F_18 (K NPUR-2 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 3:12:25.545 MOGA_ CB F_17 (KISHENPUR-2 TIE) STTS OPEN GOOD Valid
'02-01-2010 3:12:25.597 KISHENPUR CB F_16 MOGA-2 MAIN BUS-2 STTS OPEN GOOD Valid
'02-01-2010 3:12:25.611 KISHENPUR CB F_17 MOGA-2&DULHA-1 TIE STTS OPEN GOOD Valid
'02-01-2010 3:12:39.680 MOGA_ CB E_07(MOGAN-3) STTS OPEN GOOD Valid
'02-01-2010 3:12:41.481 MOGA_ CB E_08(MOGAN-4) STTS BETWEEN Bad Valid
'02-01-2010 3:12:41.869 JALLANDHAR CB E_04(DASYA-1) STTS BETWEEN Bad Valid
'02-01-2010 3:12:42.035 MOGA_ CB E_08(MOGAN-4) STTS OPEN GOOD Valid
'02-01-2010 3:12:46.133 JALLANDHAR CB E_05(DASYA-2) STTS OPEN GOOD Valid
'02-01-2010 3:12:49.291 JALLANDHAR CB E_03(HAM2P-2) STTS OPEN GOOD Valid
'02-01-2010 3:12:52.448 JALLANDHAR CB E_02(HAM2P-1) STTS OPEN GOOD Valid
'02-01-2010 3:12:56.522 JALLANDHAR CB E_15(KARTA) STTS OPEN GOOD Valid
'02-01-2010 3:12:59.476 JALLANDHAR CB E_16(KJNGA) STTS OPEN GOOD Valid
'02-01-2010 3:14:24.790 PATIALA CB F_1 (NALAGARH-2 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 3:14:44.143 PATIALA CB F_9(ICT-1 MAIN BUS-2) STTS OPEN GOOD Valid
'02-01-2010 3:15:02.983 NALAGARH CB F_13( KAITH BUS-1) STTS INVALID Bad Valid
'02-01-2010 3:15:08.375 NALAGARH CB F_14 (KAITH TIE) STTS OPEN GOOD Valid
'02-01-2010 3:15:10.332 NALAGARH CB F_15 (KAITH BUS-2) STTS OPEN GOOD Valid
'02-01-2010 3:15:10.332 KAITHAL CB F_1 (NALAGARH-1)MAIN BUS STTS BETWEEN Bad Valid
'02-01-2010 3:15:10.379 KAITHAL CB F_2(NALAG-ICT-2 TIE) STTS OPEN GOOD Valid
'02-01-2010 3:15:24.411 NALAGARH CB F_18 PATIA BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 3:15:36.743 PATIALA CB F_9 (ICT-2 BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 3:15:44.638 PATIALA CB F_9 (ICT-2 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 3:15:46.679 PATIALA CB E_02(T2) STTS OPEN GOOD Valid
'02-01-2010 3:15:46.683 PATIALA CB F_8 ( LUDHIANA-1&ICT-2 T STTS OPEN GOOD Valid
'02-01-2010 3:15:56.296 NALAGARH CB F_8( NAPTHA-1 B/R TIE) STTS OPEN GOOD Valid
'02-01-2010 3:15:57.936 NALAGARH CB F_9 (B/R BUS-2) STTS OPEN GOOD Valid
'02-01-2010 3:16:10.743 NALAGARH CB F_7( NAPTHA-1 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 3:16:29.479 PATIALA CB E_01(T1) STTS OPEN GOOD Valid
'02-01-2010 3:16:31.370 ABDULLAPUR CB F_9 (ICT-1 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 3:16:33.234 ABDULLAPUR XFMR_P FE_T1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 3:16:33.263 ABDULLAPUR CB E_01(ICT-1) STTS OPEN GOOD Valid
'02-01-2010 3:16:33.264 ABDULLAPUR CB F_8 (NJPC ICT-1 TIE) STTS OPEN GOOD Valid
'02-01-2010 3:16:38.089 NALAGARH CB F_6( ICT-2 MAIN BUS-2) STTS OPEN GOOD Valid
'02-01-2010 3:16:38.861 PATIALA CB E_06(ABLWL) STTS OPEN GOOD Valid
'02-01-2010 3:16:40.631 ABDULLAPUR ZBR F_ABDUL_NPTHA1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 3:16:40.686 ABDULLAPUR CB F_4 (NJPC-1 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 3:16:40.754 PATIALA CB E_08(ABLWL-2) STTS OPEN GOOD Valid
'02-01-2010 3:16:42.412 NALAGARH CB E_05(T2) STTS OPEN GOOD Valid
'02-01-2010 3:16:42.424 NALAGARH CB F_5( ICT-2 TIE) STTS OPEN GOOD Valid
'02-01-2010 3:16:44.888 PATIALA CB E_09(BGARH) STTS OPEN GOOD Valid
'02-01-2010 3:16:50.115 NALAGARH CB F_3( ICT-1 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 3:16:52.689 ABDULLAPUR CB F_12 (ICT-2 BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 3:16:53.255 ABDULLAPUR CB F_12 (ICT-2 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 3:16:53.543 NALAGARH CB E_03(T1) STTS OPEN GOOD Valid
'02-01-2010 3:16:53.546 NALAGARH CB F_2 ( ICT-1 TIE) STTS OPEN GOOD Valid
'02-01-2010 3:16:54.773 PATIALA CB E_07(RAJPR) STTS OPEN GOOD Valid
'02-01-2010 3:16:58.912 NALAGARH CB E_08(CHNDI-2) STTS OPEN GOOD Valid
'02-01-2010 3:16:59.074 ABDULLAPUR XFMR_P FE_T2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 3:16:59.103 ABDULLAPUR CB F_11 (ICT-2 BR) TIE STTS OPEN GOOD Valid
'02-01-2010 3:16:59.108 ABDULLAPUR CB E_02(ICT-2) STTS OPEN GOOD Valid
'02-01-2010 3:16:59.706 MAINPURI CB F_3 (BALLB-2 MAIN BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 3:16:59.711 MAINPURI CB F_5(BALLB-2 TIE) STTS BETWEEN Bad Valid
'02-01-2010 3:16:59.781 BALLABGARH CB F_27 MAINPURI-2 MAIN BUS STTS OPEN GOOD Valid
'02-01-2010 3:17:00.943 MAINPURI CB F_3 (BALLB-2 MAIN BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 3:17:00.979 BALLABGARH CB F_28 MAINPURI-2 MAIN BUS STTS CLOSED GOOD Valid
'02-01-2010 3:17:01.005 MAINPURI CB F_3 (BALLB-2 MAIN BUS-2) STTS OPEN GOOD Valid
'02-01-2010 3:17:01.030 BALLABGARH CB F_28 MAINPURI-2 MAIN BUS STTS OPEN GOOD Valid
'02-01-2010 3:17:01.073 MAINPURI CB F_5(BALLB-2 TIE) STTS OPEN GOOD Valid
Chapter - 5 _ ANNEXE -5/II (page 16 of 18)
![Page 155: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/155.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From Central Sector RTUsANNEX-5/II
Part-2
'02-01-2010 3:17:11.164 ABDULLAPUR RE F_BR PRT PROTECTION TRIP GOOD Valid
'02-01-2010 3:17:11.217 ABDULLAPUR CB F_10 (BR BUS-1) STTS OPEN GOOD Valid
'02-01-2010 3:17:30.469 ABDULLAPUR CB E_05(TEPLA-2) STTS OPEN GOOD Valid
'02-01-2010 3:17:33.397 ABDULLAPUR CB E_03(TEPLA-1) STTS BETWEEN Bad Valid
'02-01-2010 3:17:35.577 ABDULLAPUR LINE E_ABDUL_JORIA2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 3:17:35.607 ABDULLAPUR CB E_07(JORIA-2) STTS BETWEEN Bad Valid
'02-01-2010 3:17:38.106 ABDULLAPUR CB E_07(JORIA-2) STTS OPEN GOOD Valid
'02-01-2010 3:17:38.237 ABDULLAPUR LINE E_ABDUL_JORIA1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 3:17:38.262 ABDULLAPUR CB E_06(JORIA-1) STTS BETWEEN Bad Valid
'02-01-2010 3:17:40.775 ABDULLAPUR CB E_06(JORIA-1) STTS OPEN GOOD Valid
'02-01-2010 3:17:53.028 ABDULLAPUR CB E_11(RAIL_-2) STTS OPEN GOOD Valid
'02-01-2010 3:18:01.260 ABDULLAPUR CB E_08(RAIL_-1) STTS OPEN GOOD Valid
'02-01-2010 3:18:07.971 ABDULLAPUR CB E_10(BUS COUPLER) STTS OPEN GOOD Valid
'02-01-2010 3:18:58.505 SRINAGAR CB F_L3(KISHN-1) STTS BETWEEN Bad Valid
'02-01-2010 3:18:58.648 KISHENPUR CB F_6 WAGOORA-1 BUS1 STTS OPEN GOOD Valid
'02-01-2010 3:18:58.679 KISHENPUR CB F_5 ICT-1 WAGORA-1 TIE STTS OPEN GOOD Valid
'02-01-2010 3:19:01.081 SRINAGAR CB F_L4(KISHN-2) STTS OPEN GOOD Valid
'02-01-2010 3:19:01.238 KISHENPUR CB F_3(WAGOORA-2 BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 3:19:01.281 KISHENPUR CB F_2 (CHM-2 & WAGO-2 TIE) STTS INVALID Bad Valid
'02-01-2010 3:19:25.828 KISHENPUR CB F_12 BAGLIHAR 1 MAIN BUS STTS INVALID Bad Valid
'02-01-2010 3:19:30.333 KISHENPUR CB F_24 BAGLIHAR-2 MAIN BUS STTS OPEN GOOD Valid
'02-01-2010 3:19:32.632 KISHENPUR CB F_23 I(FUTUR & BAGLHR-2 STTS OPEN GOOD Valid
'02-01-2010 3:19:35.923 KISHENPUR CB F_11 (BGLHR-1 &B REACTO STTS OPEN GOOD Valid
'02-01-2010 3:19:53.276 KISHENPUR CB E_12(T2) STTS OPEN GOOD Valid
'02-01-2010 3:19:53.286 KISHENPUR CB F_4 ICT-1 MAIN BUS-2 STTS OPEN GOOD Valid
'02-01-2010 3:20:11.309 KISHENPUR CB F_21 DULHASTI-2 MAIN BUS STTS BETWEEN Bad Valid
'02-01-2010 3:20:13.056 KISHENPUR CB F_20 ICT-2 DULHASTI-2 TI STTS OPEN GOOD Valid
'02-01-2010 3:20:14.969 KISHENPUR CB E_11(T1) STTS OPEN GOOD Valid
'02-01-2010 3:20:14.973 KISHENPUR CB F_19 ICT-2 MAIN BUS-2 STTS OPEN GOOD Valid
'02-01-2010 3:20:32.162 SRINAGAR CB F_L1(URI_R-1) STTS OPEN GOOD Valid
'02-01-2010 3:20:37.374 SRINAGAR CB F_L2(URI_R-2) STTS OPEN GOOD Valid
'02-01-2010 3:20:49.482 BALLABGARH CB F_23 KANPUR TIE STTS BETWEEN Bad Valid
'02-01-2010 3:20:49.486 BALLABGARH CB F_22 KANPR MAIN BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 3:20:50.617 BALLABGARH CB F_22 KANPR MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 3:20:50.628 BALLABGARH CB F_23 KANPUR TIE STTS CLOSED GOOD Valid
'02-01-2010 3:21:07.221 KAITHAL CB E_06(KTHAL-2) STTS BETWEEN Bad Valid
'02-01-2010 3:21:07.233 KAITHAL CB E_06(KTHAL-2) STTS INVALID Bad Valid
'02-01-2010 3:21:10.572 KAITHAL CB E_07(CHEKA-2) STTS BETWEEN Bad Valid
'02-01-2010 3:21:12.314 KAITHAL CB E_08(CHEKA-1) STTS BETWEEN Bad Valid
'02-01-2010 3:22:05.233 MANDAULA CB F_4( BAWANA MAIN BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 3:22:05.233 MANDAULA CB F_6 (BAWANA MAIN BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 3:22:06.407 MANDAULA CB F_4( BAWANA MAIN BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 3:22:07.853 MANDAULA CB F_6 (BAWANA MAIN BUS-2) STTS OPEN GOOD Valid
'02-01-2010 3:23:24.490 MANDAULA CB F_6 (BAWANA MAIN BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 3:24:52.456 SRINAGAR CB E_09(T1) STTS OPEN GOOD Valid
'02-01-2010 3:24:52.464 SRINAGAR CB F_08(T1) STTS OPEN GOOD Valid
'02-01-2010 3:29:54.794 ABDULLAPUR XFMR_P FE_T1 PRT PROTECTION OK GOOD Valid
'02-01-2010 3:30:49.163 ABDULLAPUR XFMR_P FE_T2 PRT PROTECTION OK GOOD Valid
'02-01-2010 3:31:58.079 MAINPURI CB F_5(BALLB-2 TIE) STTS CLOSED GOOD Valid
'02-01-2010 3:32:05.674 BALLABGARH CB F_27 MAINPURI-2 MAIN BUS STTS CLOSED GOOD Valid
'02-01-2010 3:32:08.380 HISSAR CB F_31 MOGA-1 MAIN BUS-1 STTS OPEN GOOD InvRTU
'02-01-2010 3:32:12.463 MAINPURI CB F_3 (BALLB-2 MAIN BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 3:42:16.936 MEERUT CB F_12 MUZA1 BUS-2 STTS OPEN GOOD Valid
'02-01-2010 3:42:16.943 MEERUT CB F_11 TEHRI-II & MUZA1 TI STTS OPEN GOOD Valid
'02-01-2010 3:42:44.944 BALLABGARH CB F_28 MAINPURI-2 MAIN BUS STTS CLOSED GOOD Valid
'02-01-2010 3:43:06.096 SRINAGAR CB E_L2(PAMPO-1) STTS OPEN GOOD InvRTU
'02-01-2010 3:43:08.499 SRINAGAR CB E_L3(PAMPO-2) STTS OPEN GOOD InvRTU
'02-01-2010 3:43:11.429 MALERKOTLA XFMR_P 400/220KV ICT-2 PRT PROTECTION OK GOOD Valid
'02-01-2010 3:43:13.770 SRINAGAR CB E_L1(ZNKOT-1) STTS OPEN GOOD InvRTU
'02-01-2010 3:43:15.805 SRINAGAR CB E_L4(ZNKOT-2) STTS OPEN GOOD InvRTU
'02-01-2010 3:43:16.697 MALERKOTLA XFMR_P 400/220KV ICT-2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 3:43:19.447 MALERKOTLA XFMR_P 400/220KV ICT-2 PRT PROTECTION OK GOOD Valid
'02-01-2010 3:43:25.334 MAINPURI CB F_3 (BALLB-2 MAIN BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 3:43:25.335 MAINPURI CB F_5(BALLB-2 TIE) STTS BETWEEN Bad Valid
'02-01-2010 3:43:25.408 BALLABGARH CB F_28 MAINPURI-2 MAIN BUS STTS OPEN GOOD Valid
'02-01-2010 3:43:25.412 BALLABGARH CB F_27 MAINPURI-2 MAIN BUS STTS OPEN GOOD Valid
'02-01-2010 3:43:26.116 MAINPURI CB F_5(BALLB-2 TIE) STTS OPEN GOOD Valid
'02-01-2010 3:43:26.118 MAINPURI CB F_3 (BALLB-2 MAIN BUS-2) STTS OPEN GOOD Valid
'02-01-2010 3:43:32.393 SRINAGAR CB E_02(T2) STTS OPEN GOOD InvRTU
'02-01-2010 3:43:41.350 SRINAGAR CB F_03(T2) STTS OPEN GOOD InvRTU
'02-01-2010 3:44:10.332 HISSAR LINE E_HISAR_HS_PG2 PRT PROTECTION TRIP GOOD InvRTU
'02-01-2010 3:44:10.332 HISSAR LINE E_HISAR_HS_PG1 PRT PROTECTION TRIP GOOD InvRTU
'02-01-2010 3:44:10.383 HISSAR CB E_L2(HISAR-2) STTS OPEN GOOD InvRTU
'02-01-2010 3:44:10.413 HISSAR CB E_L1(HISAR-1) STTS INVALID Bad InvRTU
'02-01-2010 3:48:18.162 HISSAR LINE E_HISAR_HS_PG2 PRT PROTECTION OK GOOD InvRTU
'02-01-2010 3:48:21.720 HISSAR LINE E_HISAR_HS_PG1 PRT PROTECTION OK GOOD InvRTU
'02-01-2010 3:49:07.275 BALLABGARH CB F_25 MAINPURI-1 MAIN BUS STTS CLOSED GOOD Valid
Chapter - 5 _ ANNEXE -5/II (page 17 of 18)
![Page 156: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/156.jpg)
Sequence of Events for Disturbance at 03.01 hrs of 02nd Jan 2010
From Central Sector RTUsANNEX-5/II
Part-2
'02-01-2010 3:51:58.616 MOGA_ CB F_9 (ICT-1 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 3:52:00.837 MOGA_ CB F_10( ICT-2 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 3:52:03.559 MOGA_ CB F_11 ( ICT-1 &2 TIE) STTS OPEN GOOD Valid
'02-01-2010 3:52:07.655 KANPUR CB F_31 KANPUR ICT-2 TIE STTS OPEN GOOD Valid
'02-01-2010 3:52:12.631 SINGRAULI CB F_22(KANPR) STTS BETWEEN Bad Valid
'02-01-2010 3:52:31.349 BALLABGARH CB F_13 BHIWA MAIN BUS-2 STTS OPEN GOOD Valid
'02-01-2010 3:52:31.360 BALLABGARH CB F_14 AGRA&BHIWA TIE STTS OPEN GOOD Valid
'02-01-2010 3:54:39.314 HISSAR CB E_L4(FTEBD-2) STTS BETWEEN Bad InvRTU
'02-01-2010 3:54:39.471 HISSAR CB E_L4(FTEBD-2) STTS CLOSED GOOD InvRTU
'02-01-2010 3:56:11.282 HISSAR CB E_L1(HISAR-1) STTS CLOSED GOOD InvRTU
'02-01-2010 3:57:24.199 HISSAR CB E_L2(HISAR-2) STTS BETWEEN Bad InvRTU
'02-01-2010 3:59:05.366 HISSAR CB F_31 MOGA-1 MAIN BUS-1 STTS CLOSED GOOD InvRTU
'02-01-2010 3:59:05.407 HISSAR ZBR F_HISAR_RGTPS1 PRT PROTECTION TRIP GOOD InvRTU
'02-01-2010 3:59:05.469 HISSAR CB F_31 MOGA-1 MAIN BUS-1 STTS OPEN GOOD InvRTU
'02-01-2010 3:59:05.498 HISSAR ZBR F_HISAR_RGTPS1 PRT PROTECTION OK GOOD InvRTU
Chapter - 5 _ ANNEXE -5/II (page 18 of 18)
![Page 157: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/157.jpg)
Chapter - 5 _ Exhibit-5/I (page 1 of 1)
PUNJAB
NAlAGARH
TO """0" 1<\\
TO BASSI
HIMACHAL PRADESH -~---
--~----~~ --'ll'f®s
2
KHERA (........,..01)
KUOKSHEIRA(PlPlJ)
J SAUMPUR
... NILOKHERI
~r~=#:======= UTTAR PRADESH I" MEERUT
5
LEGEND:-EXISTlNG
lHERIIW. POWER STATIONS .. HYDRO POWER STAll0NS * SUB STATIONS • 400 kY TRANSMISSION UNES
220 IN lRANSWISSlON UNES
132 kV TRANSMISSION UNES
1 GURG.tDN
2 GU~N SECTOR 52
;] EW..I..ABHGMH (B8MB)
PROPOSED
EO
* 0
![Page 158: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/158.jpg)
Cha
pter
- 5
_ Exhibit-
-5/II
(pag
e 1
of 4
)
1 ~ iiI
"'''' ::;::;
NN 00 00
~~
"" "" 0000 00 00
Zoo
H
I~I r;=l I
cEcEcEcEcEcE
§f'l:::"§1'2 ~~~~§~ ~N~N~~
;ii f'l" """ MS~;:::;:::~ /Il~i*:f55"2 • 00
~ 0 0
~;::,~Si~~
o 0 0 0 0 0 zzzzzz
oo ~ c ~ c ~ c
o 0 0 0 0 0 zzzzzz
ill:': ill:': ill:': ""
-0:>-0:;::-0:;:: II I I ~ § ~ § ~ § ~
~ § ~ ~ ~ § ~ A ~ A ~ A
QOQO~OO zzzz)-zz
HH] ! oooouo
~QQO~OQ )-zzz)-zz
co zzzzzzz ~OOOOOOO
'\'>;-'\'
<H DOD YYY w w w 000000 ::::;::::;::::;
00 00
" ~ "''''0:::0 O::::ti:~ '\'z9=?
H" 588C';~~
1 ~ l cccccc,=c 0 00000000
o '\' '" z",-z ' w",,,-:;;:;;~;
~::::~2;2;~ QZ~'\''\'Y
iB"~'
![Page 159: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/159.jpg)
Cha
pter
- 5
_ Exhibit-
-5/II
(pag
e 2
of 4
)
1 ~ iiI , , , ~ ~
101 ~ \;7,)
1" !el g1
, ' I~I "' --' --' --'--'
I
""51" " 00"" ,.,'" f;jf;j ~f::j
" " , ~
Z • " " , ~
z •
I
:E:E:E:E:E:E
, a: NOD dOM ~<o: <2 ~ ~:<l <2 N
, <2~~:<l<2N
II l "- I NOd dOM
00000 ...
ill:': ill:': ill:': ""
<{ :;;: <>:;:: -0: Q II I I = § ~ § ~ § ~
~* ~ ~ 0'; .~ .0';
h~ A ~ A
II 1,1 0000000
II H Z Z Z Z Z Z Z
] ] ] ~ ~~ 88 uooo
~QQO ~ OQ )-ZZZ)-ZZ
co zzzzzzz ~ooooooo
o "')-oo CO
~~IE'i~ ~ 999 ,",0:::0 "'''''''0>->-<.0 YYYa:'7"-z www'z9:;> ,,,,n, 588C';~~
![Page 160: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/160.jpg)
Chapter - 5 _ Exhibit--5/II (page 3 of 4)
Print Time: 1/ 2/ 2010 10: 59: 09
TIME 02101/2010 02 : 54 : 53 : 420
02/01/2010 02 : 54 : 53 : 420
02101/2010 02 : 55 : 01 : 477
02/01/2010 02 : 55 : 01 : 490
02/01/2010 02 : 55 : 01 : 490
02/01/2010 02 : 55 : 01 : 507
02/01/2010 02 : 55 : 01 : 523
In" UL""U"oL
02/01/2010 02 : 55 : 01 : 653
02/01/2010 02 : 55 : 01 : 653
02/01/2010 02 : 55 : 01 : 657
02/0112010 02 : 55 : 01 : 657
02/01/2010 02 : 55 : 01 : 663
02/01/2010 02 : 55 : 01 : 670
02/01/2010 02 : 55:01 : 670
02/01/2010 02 : 55 : 01 : 670
02/01/2010 02 : 55 : 01 : 670
02/01/2010 02 : 55 : 01 : 670
02/01/2010 02 : 55 : 01 : 680
02/01/2010 02 : 55 : 01 : 680 02/01/2010 02 : 55 : 01 : 680
02/01/2010 02 : 55 : 01 : 683
02/01/2010 02 : 55 : 01 : 690
02/01/2010 02 : 55 : 01 : 690
02/01/2010 02 : 55 : 01 : 697
02/01/2010 02 : 55 : 01 : 707
02/01/2010 02 : 55 : 01 : 707
02/01/2010 02 : 55 : 01 : 707
02/01/2010 02 : 55 : 01 : 707
02/01/2010 02 : 55 : 01 : 717
02/01/2010 02 : 55 : 01 : 727
02/0112010 02 : 55 : 01 : 727
02/01/2010 02 : 55 : 01 : 730
Process Events History
DESCRIPTION
01 1
01 - 1 BAMNAULI-2 MAIN-l START-R PH
BAMNAULI-2 MAIN - 1 PROT ECTION
BAMNAULI - 2 MAIN-1 CARRIER SEND
CB 1 252 R PHASE
CB1252 TRIP CIRCUIT 1
TK'" , BAMNAULI-2 MAIN- l START-B PH
CB 1052 GENERAL L/O 1&2
CB 1052 GENERAL L/O 1&2
CB 1052 GENERAL L/O 1&2 CBI052 TRIP CIRCUIT 2
CB 1252 B PHASE CB 1052 Y PHASE CBI052 TRIP CIRCUIT 2
CB 1252 Y PHASE
CB1052 TRIP CIRCUIT 2 CB1252 TRIP CIRCUIT 1
CB1252 TRIP CIRCUIT 2 CB1252 TRI P CIRCUIT 1
CB1252 TRIP CIRCUIT
CB1252
CB1252
TRIP
TRIP
1
2 CIRCUIT
CIRCUIT 1
CB 1052 B PHASE
CB 1052 B PHASE
CBI052 BFR
CB 1052 B PHASE CB 1052 B PHASE
CB 1052 B PHASE BAMNAU LI-2 GR-A 3PH PROTECTION
8AMNAULI-2 GR-A 3PH PROTECTION
CB 1052 B PHASE
STATUS
TRANSIT - TRANSI T
- HIGH - TRIPPED
- HIGH
- HIGH
- FAULTY
- HIGH - HIGH - LOW
- HIGH - FAULTY - HIGH - HIGH - NORMAL
- HIGH - FAULTY - FAULTY - FAULTY - NORMAL
- FAULTY
- NORMAL
- NORMAL
- HIGH - LOW
- OPERATED - HIGH - LOW
- HIGH - TRIPPED - NORMAL
- LOW
I
Page 1 of 10
![Page 161: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/161.jpg)
Chapter - 5 _ Exhibit--5/II (page 4 of 4)
Print Time : 1/2/2010 10:59:09
TIME 02/01/2010 02 : 55 : 01 : 730 02/01/2010 02 : 55 : 01:733 02/01/2010 02 :55: 01 : 737 02/01/2010 02 : 55 : 01 : 740 02/01/2010 02:55 : 01 : 743 02/01/2010 02 : 55 : 01 : 743
.12010 0>·« · 0· . ,,,
02/01/2010 02:55 : 01 : 747 02/01/2010 02 : 55 : 01 : 747 02/01/2010 02 : 55 : 01 : 747 02/01/2010 02 : 55 : 01: 757 02/01/2010 02 : 55 : 01 : 783 02/01/2010 02 : 55 : 01 : 807 02/01/2010 02:55 : 01 : 810 02/01/2010 02 : 55 : 01 : 890 02/01/2010 02 :55 : 02 :4 67 02/01/2010 02 : 55 : 04 : 097 02/01/2010 03 : 08 : 25 : 420 02/0 1/2010 03 :16:52:4 20 02/01/2010 03 : 31 : 57 : 420 02/01/2010 03 : 39 : 28:170 02/01/2010 03 : 39 : 28 : 170 02/01/2010 03 : 39 : 28 : 170 02/01/2010 03 : 39 : 28 :1 70 02/0112010 03 : 39 : 28 : 170 02/01/2010 03:39 : 28 : 170 02/01/2010 03:39 : 28 : 170 02/01/2010 03:39 : 28:170 02/01/2010 03 : 39 : 28 : 170 02/01/2010 03:39 : 28 : 170 02/01/2010 03 : 39 : 28 : 170 02/0112010 03:39 : 28 : 170 02/01/2010 03 :39 : 28 : 170
Process Events History
DESCRIPTION
CB 1052 B PHASE BAMNAULI -2 GR-A 3PH PROTECTION BAMNAULI - 2 GR- A 3PH PROTECTION BAMNAULI-2 GR- A 3PH PROTECTION CB 1052 GENERAL L/O 1&2 CB1052 TRIP CIRCUIT 2 ' 0 '0<> "",,"on, '0 '" CB1052 TRIP CIRCUIT 2 CB1052 TRIP CIRCUIT 2 CB 1052 GENERAL L/O 1&2 BAMNAOLI-2 MAIN-1 START-B PH CB1052 Bf'R BAMNAULI-2 MAIN-1 CARRIER SEND BAMNAULI - 2 MAIN-l START-R PH BAMNAULI-2 MAIN-1 PROTECTION 01 - 1 CB 1052 R PHASE 01-1
01-1
01-1 CB 1052 B PHASE CB 1052 B PHASE CB 1052 GENERAL L/O 1&2 CB 1052 GENERAL L/O 1&2 BAMNAULI - 2 MAIN-l START- R PH BAMNAULI-2 MAIN-l PROTECTION BAMNAULI-2 MAIN-1 CARRIER SEND CB 1252 R PHASE CB1252 TRIP CIRCUIT 1 BAMNAULI- 2 MAIN - 1 START-B PH CB 1052 GENERAL L/O 1&2 CB 1052 GENERAL L/O 1&2 CB1052 TRIP CIRCUI T 2
STATUS
- HIGH - TRIPPED - NORMAL
- TRIPPED - LOW - NORMAL
- f'AULTY - NORMAL - LOW - LOW - RESET - LOW
- LOW - NORMAL - TRANSIT - HIGH - HIGH - TRANSIT - HI GH - HI GH - HIGH - HIGH - HI GH - HI~H
- TRIPPED
- HIGH - HI GH - FAULTY - HIGH - HIGH - HIGH - FAULTY
I
- Ack(02 - 01-2010 02 : 45 : 54) -Ack(02 - 01-2010 02 :4 5 : 54) -Ack(02 - 01-2010 02 :4 5 : 54) -Ack(02-01-2010 02 : 45 : 54) -Ac k {02 - 01- 2010 02 : 55 : 01) -Ack(02-01-2010 02 : 55 : 01) -Ack(02 - 01-2010 02 : 55 : 01) -Ack{02-01-2010 02 : 55 : 01) -Ack(02-01- 2010 02 : 55 : 01) -Ack(02 - 01 - 2010 02 : 55 : 01) - Ack{02-01 - 2010 02 : 55 : 01) -Ack(02-01-2010 02 : 55 : 01) - Ack(02-01-2010 02 : 55 : 01)
Page 2 of 10
![Page 162: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/162.jpg)
Cha
pter
- 5
_ Exhibit-
-5/II
I (pa
ge 1
of 2
)
] l i ~
, w
~ ~
8
g ~
~
~
" ~
~ , ~
N
& " ~ e , §
~
ro
8
~ ~
~ N
§
~ ~
o ro ~ N
•
c • N
~
c • " , ,
ro
~ , ~
~
• ~
~
w
~ ~
~ • ~ ~
~ ~
~
N
~ ~
~
~
~ o
~
o
ro
![Page 163: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/163.jpg)
Cha
pter
- 5
_ Exhibit-
-5/II
I (pa
ge 2
of 2
)
f
~ ~ !
] l ~
, ~ ~ e o
~ ~ 5
,
~ c
~ ~
~
~ c
~ ~ N
N
§ ~
§ o
~ §
~
D
" ~
§
~
§
~
•
~ D
N
~ 5
~ D
N
, , ,
D
~ ~
~ M
~
,
~
~
o
~ e
~ R
~ , ~ ~
~
,
~ , R ~
• ~
o
![Page 164: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/164.jpg)
Chapter - 5 _ Exhibit- -5/IV (page 1 of 1)
Charg.t ..:a::.t ----I 400 W
RAJ A S T HAN
,L_-- FROM JESSORE
HIMACHAL PRADESH
PlNJORE
FROM DADRI
TO BHIWANI
H A R Y A N A TO MUNDKA
LEGEND:-
HYDRO POWER STATIONS
THERt.IAl. POWER STATIONS
SUB STAllONS
71m IN TRANSMISSION UNES
400 IN 1RANSMISSION UNES
220 IN TRANSMISSION UNES
132 IN TRANSMISSION UNES
H W 'TRANSMISSION UNES
• ---~ --~
EXISTING PROPOSED
" .. - .. • a
![Page 165: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/165.jpg)
1,'
I
i
ii
Histoiical Tabular 03 : 05:39 02 Jan 10
-# 3,
TS3? 06STATEACTUAI, VAL
I,a,I,1,1,1,1,1,1,1,7,1,a,1,L,t,1,a,a,1,1,I,1,1,1,1,1,1,1,I,7,1,1,a.I1
0,0,0.0,0,0,0,0,0,0,0,0,0,
v
YEOO1
MVAR
ACTUAI, VA],-4.42 ,
-4.42 ,
-o.02 ,
-0-02 ,
-o -42 ,
1. 05 ,
1.0s ,
1.05 ,
32.43,63.69 ,
108.25 ,
152 .80 .
233-L4,224.44,239.55 ,
244-O7 ,
24:..07,242-14 ,
242-74 ,
244.66. ,
247 .O2 ,
247.02 ,
247.42 ,
241 .42 ,
244, 13 ,
244.73,245.88 ,
245-AA,238-02,
235.50,235.50 ,
235.50,235-54,235.54,237 .rL ,
p-thP
p'i''. Date
02.5'7 t A'7 02-Jan-10 51302.57.06 02 -Jan- 10 51402:5?:05 02 -.lan- 10 51502.57.O4 02-Jan-10 51502 57:03 02-Jan-10 517Oist
' oz 02-Jan-10 518
02:3'7 :OI 02-.lan-10 51902:57:00 02-Jan-10 52002:56:59 02-Jan-10 52102:55:58 O2-Jan-IO 52202.56.5'7 02-Jen-10 62302.56,55 02-Jan-1O 52402 :56:55 02-Jan-10 525O2 r56 r54 02-.lan-10 52602 :56:53 02-Jan-10 52702t56r52 02-Jan-10 52802 :55:51' 'o2,iar-10 52902 :56:50 02-Jan-10 53002t56t49 02-Jan-10 53102 t56 | 4a Or-;arl-ro S:)*02.56t47 02-Jan-10 53302t56t46 02-Jan-10 53402.56.45 02-Jan-10 53502t56t44 02 -.lan-10 53602156:43 02rJan-10 537A2 t55 t42 02-Jan-10 53802|56t4\ 02 Jan-10 53902:56:40 02-Jan-10 540A2t56.39 02-Jan-10 54102:56.38 O2-Jan-IO 542A2:56:3't 02 -Jan-10 54342t56:36 02 .lan 10 54402:56:35 02-Jan-10 545A2 t56:34 02 - Jan- 10 54602 i s6 : 33,$.2 .J.$.r10;..!a'rA2t56:32 02-Jan 10 54802:56:31 02 Jan-10 549
:55:3O 02-Jan-10 550:56:29 02-Jan-10 551
02tS6 t2a 02-.lan-10 552
Mt43 01MW
ACTUAL VAL3.138,
-3.138,-3.138,-3 .138,-3.138,-3 . 138,-3.138,-3.138,-2.23,a.o2 ,
-4.02 ,
-0.02 ,
-o.02 ,
-0 .02 ,
-0.02 ,
-0.02 ,
-o-02,-o.02,-o-02,-o-02,-o.02,76.24 ,
16.24,16.24 ,
14.45 ,
18 .50 ,
46.60 .
33.63 ,
r72.4r ,
L'72 -44 ,
1'72.4r ,
r'7 2 .4r ,
a'7 2 .4I ,
165.62 ,
a65.62 ,
186.'15 ,
7'14 - 62 ,
!'7I-'72 ,
I'tI.'72 ,
r7r.72 ,
vAt VAL
TM3O1
MW
ACTUAI2495.8'72904.572913.352 913 - 352924 -342924.342929.A32935.332943 .022948.5L2955. 102964.592958.2929'75 .9829A2 -5'72988.062994.653001.243010.033015.533026 -5L3026.513034.203040.803050.683071- 563126 -493L45.7'73183 -623233.0632'tI -5I3313.263355.003398.9534 34..1J
' lrd4.563191 . 3130r9.923019. 923079 .923019.9230r9 -923079 -923019 -9230r9 -923079.923019 .923019.9234t9.92
02 t56 '2'7 02-Jan-10 55302,56 t26 02-Jan-10 55402,56|25 02-Jan-10 55502.56.24 02-Jan-10 55602t56.23 02-Jan-10 55?02.56.22 02-Jan-10 55802.56.2I 02-Jan-10 55902t56.2O 02-Ja4-10 55002t56:19 02 -.lan-1O 55102:55:18 02 -.lan-10 562
.'{*cHAPTER
- - Exhibit-5/V (page 1 of 4)l G,# 6,
Historica l Tabular Trend 1 03 : 05 : 39 02 - Jan - 1 0 , " - _"':'"
Date
02:57:07 02 -Jan-10 5 1 3
02:57:06 02 - Jao - 10 514
02:57:05 02 - Jao - 10 515
02 : 57 : 04 02-Jan- 1 0 516
o~1157 : o3 02 - Jao - 10 51 7
02;.\ 57 : 02 02 - Jao - 1 0 518
02: 57 : 0 1 02-Jao - 10 5 1 9
,1 02:57:00 02-Jao - 10 52 0
' l 02:56:59 02- Jan-lO 52 1
02 :56:58 02- Jan-1 0 522
'., 02: 56 : 57 02 - Jan - 1 0 523
)11 02: 56 : 56 02-Jao - 10 524
02 : 56 : 55 02 - J an - 10 525
02:56 : 54 02 -Jao - 10 526
02: 56:53 02- Jao- 10 527
02,56 ,-52 02 -Jan-l0 52 8
02: 56 :51 02 -Jao- 1 0 529
0 2 :56 : 50 02 - Jan - l O 530
02 :5 6 : 49 02- Jao- 1 0 531
02 :5""6 : 4 8 '02- Jao - 1 0 532"'1.
02:56: 4 7 02 - Jan - 1 0 533
02:56: 4 6 02 - Jao - 1 0 534
02:56:4 5 02-Ja o- 10 535
02: 56 :44 02 - J ao- 1 0 536
02: 5 6: 4 3 02 - J ao- 1 0 537
02 : 56:42 02 - Jao - 1 0 538
02:56 :41 02 - Jao - 1 0 539
02:56:40 02-Jan - 1 0 540
02:56:39 02 - Jan - 10 54 1
02:56:38 02-Jan-l0 542
02 :56:37 02 - Jan-l0 543
02 : 56:36 02 - Jan- l 0 544
02:56:35 02 - Jan - l0 545
02 : 56 : 3 4 02 - Jan- l 0 546
I 02 : 56.33 02 ~ Jap.- l0>~.54;'
02'56 32 02 - Jan - l0 548
02'563 1 02 - Jan - l0 549
02:56: 3 0 02 - J a n-l0 55 0
, 02:56:29 02-Jan- l 0 551
f 02,56, 28 02-Jan- l0 552
02 : 56 : 27 02- Jan- l 0 553
02 : 56 : 26 02-Jan-l0 554
02:56 : 25 02 - J an - l 0 5 55
02 : 56 : 2 4 02 - J an - l 0 5 56
02:56 : 23 02 -Ja n -l0 557
0 2 : 56 : 22 02 - J an - l0 558
0 2 : 56 : 2 1 02- J an-l0 559
0 2 : 56 : 20 02 - J an - 10 560
02 : 56: 1 9 02-Jan - 10 56 1
02 : 56: 1 8 02 - J an -10 562
MW301
MW
ACTUAL VAL
- 3.138,
-3 . 138,
- 3.138,
- 3.138 ,
-3.13 B ,
- 3 .138,
- 3 .1 38,
-3.138,
-3. 138,
- 3. 138,
- 3. 1 3B ,
- 2 . 23
- 0 . 02
-0.02
-0.02
-0.02
- 0 . 0 2
-0.02
-0.02
- 0.0 2
- 0.02
- 0.02
-0.02
- 0 .02
-0 . 02
16.24
1 6 . 24
1 6.24
1 8.45
1 8.45
18.45
18.45
24 . 09
2 4. 09
1 8 . 60
46 . 60
33 . 63
1 72 . 41
17 2 . 41
1 72 . 41
172 . 41
172 .41
165 . 62
165 . 62
186 . 7 5
174.62
171. 72
1 7 1 .72
1 71. 72
1 71. 72
TS3 706
STATE
ACTUAL VAL
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
o o o o o o o o o o o o o o
YHOO l
HZ ACTUAL VAL
44.98,
44.9B.
44.9B,
44.9B.
44.9B .
44 . 9B .
44. 9B ,
44 .98,
44.98 ,
44 . 9 8 ,
44. 98 ,
44 .98 ,
44.98 ,
4 4 .98 ,
44 .98,
44 .9B.
44 . 9B,
45 . 3
46.1
46. 7
4 7. 3
48.3
48.6
49.4
50.1
5 0.7
S1.4
5 2. 0
52.7
53.5
54.1
S4.8
55.4
55 . 6B,
55. 6B , .
S5.68'.
55.68,
55 . 3
51-1
50.9
50.9
50 . 9
50.9
50 . 9
50 . 8
50.8
50.8
50.8
50.8
50.8
TM301
MW
ACTUAL VAL
2896.87
2904.57
29 1 3.35
29 1 3.35
2 92 4. 34
2 924 . 34
2929 . 83
2935.33
2943 . 02
2948.51
29 55. 10
2961. 69
2968.29
297 5. 98
2982 .57
2 988 , 06
2 9 94.65
3001.24
301 0.03
3 015.5 3
3026.51
3026.51
3034 . 20
3040 . 80
3050.68
3071 .56
3126.49
3 145.17
3183.62
3233.06
3271. 51
3313 . 26
3 3 55 . 00
3398 . 95
31~,4 . :U
3394 . 56
319 1. 31
301 9 . 92
301 9.92
3 019.92
3019 .92
3019. 92
3 01 9 . 92
3 0 1 9 . 92
301 9.92
301 9 . 92
3019 . 92
301 9 . 92
301 9. 92
301 9.92
YEOO I
MVAR
ACTUAL VAL
- 0.02
- 0.02
- 0.02
-0 . 02
- 0.02
-0 . 02
-0 . 02
-0 . 02
1- 05
1- 05
1- 05
32.03
63.69
108.25
1 52.80
2 33. 14
2 24 .44
239.55
2 41. 0 7
24 1. 07
242. 14
24 2. 14
243 . 29
243.29
243.29
243.29
244.66.
247.02
247.02
247.02
247.02
247. 02
2 4 7.02
2 4 5.7 3
24!1.13
244.13
245.88
2 45 .88
238 . 02
235.50
235.50
235.50
235 . 50
235.50
235.5 0
237. 11
228.03
237.79
237. 7 9
237.7 9
![Page 166: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/166.jpg)
,/v'Histol dil Tabular Trend- 1
\ \,rDate
02:57:05 02 Jan 10 51502t5't,04 02 -Jan- 10 51602:5?:03 02-iran- 10 51702t5'7 tA2 02-Jan-10 518t0{ s7:01 02-Jan 10 519A2J5'7.oo 02-Jan 10 5200i,55,59 02-Jan-10 52102:56:58 O2-Ja -ao s2202t56t51 O2'JAaRlr O 52302:56:56 02-Ja']-1O 5240?:56:55 02-Jan-fO 52s02.56t54 02-Jan-10 s2602:56:53 O2-Jal IA S2"t02156.52 02-Jan-10 52802:56:51 02-,farl-10 529
r".-
a_J,
03:05:39 an-10 8"y-MW4A2TS4 705
STATEACTUAI
1
1
I1
11
1
1
1
1
1
1
1
I1
1t11
1
1
1
1
1
1
1
t-
1
111
1
0
a0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
TM4 O1
MltACTUAL VAL
2635.44 .
2635.40 ,
2644.89 ,
2646-39,2651.88 .
265't -3'1 ,
2667 -26 ,
2667 -26 ,
26',73..85.26'19.35 ,
2684r.84..tz6go .l,l' ,
2696.92,2'7 A3 .52 ,
2'7 5'7 -35 ,
YEOO1
MVAR
ACTUAI,-0.020.02
-0-020.02
-a .02-0 .42
1 .0sL.0s1.05
. 63 .69108.25152.80233.14224 -44
241,07
#! OL
02 t56 t4A 02-Jan-10 53202 t56.4'7 02-.fan-10 53302 : sG :4G ozliaitfib' s:+ 'ra. iu ,
YHOO1
HZ
VAL ACTUAI VAL, 44.98,
, 44.98,
, 44.98,, 44 -98,, 44.98,, 44.98,, .44 -98,, 44 -9B,
, 45.3 ,
, 46-',7 ,
, 4'7.3 ,
, 48.3,, 4a-6 ,
, 49-4 ,
, 50'1 ,
, 50-7,, E1".4 ,
, 52.4,
, 54.4,, 54.8,, 55.4 ,
, 55.68,, 55.58,, 55 - 68,
VAL ACTUAL VAL-103.758,-103.758,- 103 - 758,-103 .758,- 103 . 758,-103.758,-103.?58,-103. ?58,-103.75I].-103 .758,
. :3.s2 ,
-3.52 ,
6.A2 ,
, .36.4A ,r '
.i !td,ib}. .,.
54.80 .
62-L2 ,
65.97,6A -'7r ,
68 -',7r ,
60.11 ,
50 .11 ,
50 .11 ,
5'/ -13 ,
57 _73 ,
54.15 .
54.76,54.16,52.05.
34.44,r .' : .rr9f9*$:l:.,:r1 ,,t:r' , ,:-z:,'?!:., '
Trire
O2:56:29O2:56:24
-3 . L3B,-3.138,-3.138,
Mhia 01MW
ACTUAL VAl]-3.13B,3.138,
-3.138,
0.060.060.06
16 -5416.54
16 -5418-60
2461 -2a ,
2903 -4'7 ,
02 :55 :45 02-Jan-10 535A2 t56,44 02-.Jan-10 53602 :56:43 02-Jan-10 537A2:56.42 02-Jan-10 538O2"!56l"41 02-Jan-10 53902:56:40 02 Jan-10 54002.56139 02 Jan-10 54102:56:38 02-Jan-10 54202:56.37 02-Jan-10 54302 :56.36 02-Jan-10 54402:56:35 02-Jan-10 54502t56.34 02-Jan-10 546O2:55:33 02 JaIr-ao 54742.56.32 02-Jan-10 548
18.6018.5018.6018.501'8.5018 .5024.56?0.6620.6624.662A.6625 -4925 .49
2991-363030.913069.363107 .813146.2632A2.303229.-/63269 -343307 -76 ,
3348.41 ,
3401.15 ,
3445-O9,3473.66 ,
3426.42 ,
243 -29243 -29243 -29243 -29244.66241 .4224i .42247 -0224't .0224't .02241 .02
\t245.73244.13
02t56124a2 | 56 t23
a2 t56 t2102 t56:2002 :56.I902:56:IA02:56:r702:56: t E
51.150 .950.950 .950.950.950.850.850.850 .850.850.850.850.8
234.42235.50235.50235.50235,50235.50235 .50237 -aa228.03237.79237 -'/9237.79231 .1923'1 .'7 9
2.24 ,
-4.99 ,
4-99.44.45,
3 -43 ,
3.43 ,
-3.43 ,
-3 .43 ,
-3.43 ,
156 t2'155 t26
, O2:56:25
3060 .57 ,
3464.5'7 ,
3050.57 ,
3060.57 ,
3060.57 ,
3050.57 ,
3066.05 ,
30s9 -4'.7 ,
3059 -4'.7 ,
3059 -4'7 ,
3059-4'7,3059.47 ,
3059.47 ,
3459.47 ,
20 -9',7 ,
02 -.lan- 10 552 180.1102-Jan-1O 553 1AO - 1102-Jan-10 554 18 0,1102-Ja.-10 555 7'75.5402-Jan-10 556 I75.5402-.lan-10 557 204.9L02-.lan-10558 1-'75.2302-,Ian-10559 L'7a.6'7C2 -,fan- 10 560 l'78.6702 -,fan- 10 551 17A.6'702 -.lan-10 552 a78.6702-Jao-10 563 I?e - 6702-Jan-10 564 I78 -6'
_ EXHIBIT -5/V (page 2 of 4)Histol ~l' Tabular Trend. 1
Date
02:57:05 02 -Jan - l0 515
02:57: 04 02 -Jan-l0 516
02 : 57:03 02 - Jan-10 517
02:57:02
02157:01
02J 57: 00
02,56,59
02-Jan - lO 518
02-Jan - l0 519
02-Jan - l0 520
02 -Jan- lO 521
02:56:58 02-Jan-lO 522
02:56:57 02-Jan-10 523
02:56:56 02 - Jan - lO 524
02:56:55 02 - Jan-10 525 .. -02 : 56:54 02 - Jan- l0 526
02:56:53 02 - Jan- 10 527
02:56:52 02 - Jan - 1 0 528
02:56:51 02-Jan-lO 529
02~ 56:50 02-Jan-10 530
02 :'56 :49 02-Jah-16: 531
02:56:48 02 - Jan- 10 5 32
02:56:47 02 - Jan-10 533
02: 56: 46 02 ::' j anC-ib'" 534
02 : 56:45 02 - Jan - l 0 535
02:56:44 02-Jan-l0 536
02 :56:4 3 02 - Jan - l0 537
02 :56:42 02 - Jan - 10 538
02":56:41 02-Jan - l0 539
02:56:40 OZ - Jan-lO 540
02:56:39 02 - Jan - 10 541
02:56:38 02 - Jan-l0 542
02:56:37 02 - Jan- lO 543
02:56:36 02 -Ja~ - 10 544
02:56:35 02 - Jan - l0 545
02:56:34 02 -Jan - 10 546
02:56:33 02 - Jan - 10 547
02:56:32 02 - Jan - 10 548
02:56:29 02 - Jan - 10 551
02:56:28 02 - Jan - l0 552
. 02:56:27 02 - Jan-10 553
02:56:26 0~-Jan- l0 554
'02:56:25 02-Jan-10 555
02:56:24 02 -Jan-10 556
02:56:23 02 -Jan-lO 557
02:56:22 02- Jan-l0 558
02:56:21 02-Jan-10 559
02:56:20 02-Jan - l0 560
02:56:19 02 - Jan -1 0 56 1
02:56:18 02 -Jan-l0 562
02:56 :17 02 -Jan - l0 563
02:56 : 16 OZ-Jan-l0 564
'--' 03:05 ; 39 02-Jan-10
MW4 01
MW
ACTUAL VAL
- 3. 138,
- 3. 1 38.
-3.138.
- 3.138.
- 3.138,
- 3.l3B,
-3.l3B,
-3 .13B,
-3.138,
-3 .138,
0.06 , 0.06
0.06
16.54
16.54
16.54
16.54
16 . 54
18.60
18.60
1 8.60
18.60
18.60
18.60
18.60
18.60
20.66
<0.66
20.66
20.66
20.66
25.09
25.09
20.97
180.11
180. 11
180.11
18 0 .11
175.54
175.54
204.91
175.23
178.67
178.67
178.67
178.67
178.67
178.67
TS4706
STATE
ACTIJAL VAL
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
o o o o o o o o o o o o o o o o o
YH001
HZ ACnJAL VAL
44.98.
44.9B.
44.98.
44.98.
44.98,
44.98.
44.98,
44.98,
44.98,
44.98.
44.9B,
44.9a;
44.9B.
44.9B,
44.98,
45.3
TM401
MW
ACTUAL VAL
2635.40
2635.40
2640.89
2646.39
265 1 .88
2657.37
2667.26
2667.26
2673 _.85
2679.35
268~. 84.,'" 2690 . 3'3
2696 . 92
2703.52
2757.35
2793 . 60
YE001
MVAR
ACI1JAL VAL
-0. 02
- 0.02
- 0.02
- 0.02
-0 . 02
- 0.02
1. OS
1. 05
1. 05
46.1
46.7
~ 2832.-..06 ' .
32.03
63.69
108.25
152.80
233.14
224,44
239.55
241.07
241. 07
242.14
242.14
243.29
243.29
243.29
243.29
244.66
247.02
247.02
2 47.02
.247.02
2 47,02
2 47.02
47.3
48.3
48.6
49.4
50. 1
50.7
51. 4
52.0
52.7
53.5
54.1
54.8
55.4
55.6B,
55.6B,
55.6B,
>i 4- ~~:fEL . -;,;; . ,-:'5.5.3,
51.1
50.9
50.9
50.9
50.9
5 0.9
5 0.8
50.8
5 0.8
50.8
50.8
50.8
50 . 8
50.8
2867.2 1
2903.47
29"52.91
2991.36
3030.91
3069.36
3107.81
31'46.26
3202.30
3229. 76
3269 . 31
3307 . 76
3348.41
3401.15
3445.09
3473 .66
3426.42
3234 .• ;>15 ' 3~6tF57':'
3060 . 57
3060.57
3060.57
3060 .5 7
3060.57
3060.57
3066.06
3059 .4 7
3059.47
3059.4 7
3059.47
3059.4 7
3059 . 47
3059 . 47
~245.73
244.1 3
244.13
. :::::.-:.~i;t.2:~, ~ 1'j8 ,8 .' ... " 245.88
238.02
235.50
235.50
235.50
235 . 50
235 . 50
235.50
2 3 7.11
228.03
237.7 9
237. 79
237.79
237.79
237.79
MW402
ACTUAL VAL
-1 03 .758,
- 103.758.
-103.758,
-103.758,
-103.758,
-103.758,
-103.758,
-103.75B.
- 103.758,
- 103.758,
- 3.52
-3 .52
-3 .52
6,82
27,97
36. 4 0
46·.9"2
54.80
62.12
65.97
65.97
68 .71
68.71
60.11
60.11
60.11
57 .73
57 . 73
54.16
54. 16
54 .16
52 . 05
45.92
34 . 84
... ~ 9~. ~¢}::. ;, ! - 2,.,;24 ' , ~
- 2.24
-2.24
-2.24
-4.99
-4.99
- 4.99
- 4.99
44 . 45
- 3.43
- 3.43
-3.43
-3 .43
-3.43
-3 .43
![Page 167: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/167.jpg)
L
,.- -1"WFt'
Time Date
O2:56:2a 02 -Jan - 1002:56.2'7 02 Jan- 10f)2.56t26 02 - Jan- 1002t56t25 02 -Jan- 10O2:56:24 02 -Jan-1.002 t56.23 02 -Jan- L002 t56 t22 02-Jan-1002 t56 t21 02 -Jan- 1042 t56 t20 02 -.Tan-1002 r 56 | 19 02-Jan-1002 :56 :18 02 -Jan- 10O2:56:1'7 02 -Jan- 1002.56.16 02 -Jan- 1002:55:15 02 -Jan- 1002:56:14 02 -Jan- 10
55255355455555555?558559550561562553564565566
L6't .676'7 .616? -6r70 -4170.4166.9148.5165.8165.8165 .8155.8155 .8155 .8155.8155_a
50. 9
50. 9
s0.950 .950.950.8
50.850.850.850.850. I50. I50.850.8
Historic<,1 Tabular Trend 1
02t5'7 t04 02 -alan- 10 5160a:57:03 02 -Jan- 10 51?oLitS't:02 02 -Jan- 1O 5180X.:57.01 02-Jan-10 51902.57 tOO 02-Jan 10 52002t56t59 02-Jan-10 52102 :56: 58 02-Jao-10 52202t56.57 02-Jan-10 52302;56:56 02-Jan=L0 52402:56:55 02-Jan-L0 525ov Is6 |54 o2;iiltn-10 s2602:55:53 02:Jan-10 52702.56 t52 02-Jan-10 52802:55:51 02-Jan-10 52902 :56:50 02-Jan-L0 530oztsi t49 o2'r5a;:10 s310&,?56 :48 o2ljdsi.tc s32O2 :56 :4'1 02-Jan-10 533O2 :56 246 02-.fan-10 534' oztse ,48'oi4ii&iil ro s:i.02 |55:44 02-Jan-10 53602 t56:43 02-Jan-10 537A2:56:42 02-Jan-10 53842t56 t41 02-Jan-Lo 539a2 is6,4a 62 -33il$ilr$1g, :
A2:56 |39 02-Jan-10 541I 02:56:38 02 -Jan- 10 542
I A2:56:31 02-Jan 10 54302:56.36 02 -Jan-10 s44
ltI 02:56:35 02 Jan-10 545lli 02 :55.34 02 .Ian I O s46l
02 :56:33 02-Jan-10 54702.56--32 02 -Jan- 10 548
-15 .68.15.68,15 .68,
-15.68,-15.58,-15.58,-15.58.
'-15.58,. - 15.5B,
-5.9 ,
-0.1 ,
32 .1 ,
20.7 ,
t6.2 ,
18.4 ,
1 8.4 ,
18.4 ,
18 .4 ,
18 .4 ,
18.4 ,
18 .4 .
20.s ,
'.21 .5 ,
20.5 ,
20-5,20-5,23.r,23 -r ,
23.r ,
23.r ,
16.8 ,
16.8 ,
a6-a,16. a ,
15.8 ,
15.8 ,
16.8 ,
74 -'t ,
16.6 ,
16.6 ,
16.6 ,
16.6 ,
16.6 ,
L6-6,16-6,
45.346.1
.46,.741 .348 .34A.649 -450.150.7
52.O52.153.554.154.8
55.5B,55.68,55 . 68,55 . 68,
235.50 ,
235 -5A ,
235.50 ,
235-50,233.50,235.40,23'7 -rr ,
228.03 ,
237 -79 ,
23'7 -'19 ,
237 -79 ,
237.79 ,
23'7 .79 ,
34.'7 ,
37 -'7 ,
36.1 ,
40.6 ,' 46.5 ,
71.8 ,
-' L3.2 ,
13 -2 ,
13 .2 ,
a3 .2 ,
3055.083055.083 055.rO830s5.083055.083055.083055.083055,083055.083049.593049.593049.593049.593049. 59
\03:05:39 02 - Jan- 10
Mllo 01MW
ACTUA]- VAIIo.24.2a .'7
0.71.31.31.8
3.75.88.8
13.5t'l .215 .417 -5
v,.5
17.5
' ) r?.517.5r'7 .'7I'7 .'7r'7.'7
1'7 .'7
1'7 .'7
!7 -7I'l .7\1 .7I7 .7a7 .77',7 .7l'7 .'7
GEOO2
Io/ACTUA], VAL
YHOO1
HZACTUAI VA],
44 .98,
44.98,44.98,44 -98,44.98,44.98,44.98,44.98,44 -98,44 -98,44.98,44.98,44.98,
YEOO lMW
ACTUAL VAI,-0.02,-o.42 ,
0.02 ,
-o.02 ,
1.05 ,
1.05 ,
1.05 ,
32.O3,63.69 ,
108,25,152 .80 ,
233.r4 ,
224.44 ,
239.55,24r -O'7
' lir :'glf,-; G? rr "
243.2g ,
243.29 ,
243.29 ,
243.29 ,
z4'7 . 02 ,
24'7 -02 ,
24'/ _02 ,
247 .O2 ,
24't -O2 ,
24',7 .O2 ,
245.13,244.73,244.13,
MW002 TM007MVAR
ACTUAL VAL ACTUAL VAI]-103.8B, 2562.A9 ,
- 103.88, 2562.89 ,
103 .8B, 25'7A .5A ,
- 103.88, 257A.58 ,
-103 .8B, 2576 -O7 ,
,103 .8B, 2583 .76 ,
-103.88, 2583.76 ,
-103.88, 2592.55,-103.88, 2s92-55,
- 10.9 . 260A.24 ,
-0 -7 , .2.69a,24 ,
5?.0 , 26n.23. ,
136.3, 2646.39 ,
82 -2 , 2714.50 ,
'75.5 . 2754.05 ,
7s.5 , r,_. ?€por?9 ,;., ?s.s 'i. ' I,f*g*,"uns.,
75.5 , 2972.26 ,
75.5 , 2950.71 ,'75-5 , 2999.05 ,
15 -5 , 3039.'70 ,'78 -4 , 3079-25 ,'70-4 , 3115.50 ,
58.3 , ' 3153 .95 ,
68.3 , 3199.00 ,
65.4 , 323a.55 ,
65.4 , 321a.1A ,
63 -3 , 331?.65 ,
65.4 , 3358.30 ,
65.4 , 3402.25 ,
65.4 , 3454 -9A ,
65.4 , 346',7 -O7 ,
45.5 , 33\7 -65
_ EXHIBIT - 5/V (page 3 of 4)
" ,
/ Histor~.:iJ Tabul a r
_/ ' "
Ti me Date
Trend 1
02:57:04 02 - Jan - lO 516
O~;S7:03 02 -J a n - lQ 517
O~~~57:02 02 - Jan- lO 5 18
02-,: 57:01 02-Jan - lO 519
02:57:00 02 - Jan - lO 520
02 : 56 : 59 02 - Jan - l O 521
02:56 : 58 02 -Jan-lO 522
02,56 , 57 02- J an-10 523
02: 56: 56 02 - Jan -'lO 52 4
02:56:55 02 -Jan - lO 525
02 : 56 : ,54 02.-: Jan-l O 526
02 : 56:53 02 - Jan - 1 9 527
02:56:52 02-Jan - lO 528
02:56:51 02 - Jan - lO 529
02:56:50 02 -Jan-lO 530
Q2-:56:49 02-Jan-lQ 531
O.L:56:fS-,02-Jan-i-O 532
02:56:47 02-Jan- lO 533
02:56 :4 6 02 -Jan- lO 534
02~S6 ' : 4~S -'OT!"'Ja'n - lO 535
02 : 56:44 02 - Jan-lO 536
02:56 :4 3 02 -Jan - lO 537
02:56:42 02-Jan- lO 538
02:56 : 41 02 -Jan -lO 539
02 '-56 ,4 0 02 -Ja~'0 540
02:56:39 02 - Jan - lO 541
02 : 56:3 6 02-Jan-lO 54 2
02 : 56:37 02-Jan - lO 543
02:56:36 02 - J an - l 0 544
02:56:35 02 - Jan - l0 545
02:56:34 02 -Jan - l0 546
02;56:33 02 - Jan - 10 547
02:56;32 02 - Jan -1 0 548
02:56:31 02 - Jan - 10 549
, 'O~5~~~0 Pl,:~<l.;-Il;Q ,2 5,9 .
02:56:29 02~Jan',:,io 5'si
02;56:28 02 -Jan - l0 552
02:56:27 02 - Jan - 1 0 553
02:56: 26 02-Jan - 10 554
·02:56:25 02 - Jan - 10 555
02:56:24 02 -Jan -lO 556
02:56:~3 02 - Jan - 10 557
02:56:22 02 - Jan-10 558
02 ,56,21 02 - Jan' 10 559
02:56:20 02 - Jan - 10 560
02:56:19 02-Jan-10 561
02:56:18 02 -Ja n-10 562
02:56: 1 7 02 -Ja n-10 563
02:56:16 02 - Jan - l 0 564
02:56:15 02 - Jan - l0 565
02:56:14 02 - Jan - l0 566
03,05,39
M\o!001
MW
AC'TIJAL VAL
-15.68,
- 15.68,
-ls.6B,
- 1 5.6B,
.-15.6B,
-15.6B,
- 15,68,
- 15 , 68,
-15.68,
-5.9
-0.1
-0 . 1
32.1
20.7
1 6.2
1 6.2
1 8.4
18.4
18.4
18,4
18 .4
18 .4
18 .4
20.5
20.5
20 . 5
20.5
20.5
23,1
23. 1
23. 1
23. 1
9.8
31. 4
167 . 6
167 . 6
167.6
170.4
170.4
166.9
148.5
165 . 8
165.8
165.8
165.8
165.8
165.8
165.8
165.8
r .r' ,~
02-Jan-10
GE002
KV
ACTUAL VAL
0 .2
0, 2
0 . 7
0.7
1.3
1.3
1.8
2.5
3.7
5.8
8.8
13 .6
17.2
15.4
17.5
1]. 5
. c.l 7·. 5
17.5
17 . 5
17. 5
1 7.5
17.7
17.7
17 . 7
17 . 7
17.7
17.7
17.7
1 7.7
17.7
1 7 . 7
17.7
1 7 .7
17.7
16.8
16.8
16.8
16 ,8
16,8
16,8
16.8
14.7
16 ,6
16.6
16. 6
16.6
16.6
16.6
1 6.6
YH001
HZ AC'TIJAL VAL
44.98,
44.9B,
44.98,
44.98,
44.9B,
44.9B,
44.9B,
44.9B,
44.9B,
44.9B,
44.9B,
44.9B,
44.9B.
44.98,
45.3
46.1
46 .7
47.3
48.3
48,6
49.4
50,1
50. 7
51.4
52.0
52 .7
53 .5
54.1
54.8
55.4
55.68,
55.68,
55.68,
55,68,
, , , 55 ".3
51.1
50.9
50 . 9
50 .9
50,9
50.9
50.8
50.8
50.8
50.8
50 .8
50.8
50.8
50.8
50.8
50.8
YEOOl
MW
MW 002
MVAR
TMOQ7
ACTIJAL VAL ACTIJAL VAL
- 103,88 ,
ACTIJAL VAL
2562.89
2562.89
2570.58
2570.58
2576 . 07
2583.76
2583 . 76
2592.55
2592 . 55
2600 . 24
2600 . ,24
2611. 23' ,
2646.39
2 7 14.50
2754.05
2 800. 29
2·1f54-, 03 .
2872 . 71
2912.26
2950.71
2999.05
3039,70
3079 .25
3115.50
3153.95
3199 .00
323B .55
3278 .1 0
3317.65
33 58 . 30
3402.25
3454.98
3467.07
3317.65
-0.02
- 0 . 02
- 0 . 02
-0.02
- 0 . 02
1. 05
LO S
1. 05
32,03
63.69
108.25
152 . 80
233.14
224.44
239 ' 55
241.07
241..07
242.14
242.14
243 . 29
243.29
243.29
24 3.29
244 . 66
247 . 02
247.02
247.02
247.02
247.02
2 4 7.02
245.73
244. 13
244.13
245.88
' . .., ...... 245~ ~? <~, •
238' .02~
235.50
235.50
235 . 50
235.50
2 35.50
235.50
237.11
228 . 03
237 . 79
237.79
237.79
237.79
237.79
237 . 79
237.79
-103.88 ,
- 103,88,
-103.88,
-103,88,
- 1 03,88,
-1 03 . 88,
- 103,88 ,
-103.88,
- 10.9
- 0,7
57,0
136,3
82,2
75.5
75,5
75.5
75.5
75.5
75.5
75.5
75.5
78.4
70.4
68,3
68.3
65.4
65,4
63,3
65.4
65.4
65.4
65.4
45.5
r ;', ;:;,.l5",, 2· . , ~ ~I'r;~!~~~ , ~~-1~{Q:~·~ .•. ..0:" .: 'f:;
; ' .' '~j6~'·~~.0B·· ; . 28,8
28.8
31.7
31. 7
36,1
40.6
46.5
71. 8
1 3.2
1 3,2
13,2
13 ,2
13 .2
13 .2
13 .2
13 . 2
3055 .0B
3055 .08
3055 . 08
3055 . 08
3055 . 08
3055. 0B
3055.08
3055 . 08
3055.08
3055.08
3049 .59
3049.59
3049.59
3049 . 59
3049.59
![Page 168: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/168.jpg)
Itistorical Tabular Trend 2 03:05:39 02-,fan-10Tut bl^tqeer''Tl'to 0 7
ACTIJAL VAL
2590 .35 ,
2602.14,2602.44,26t1.23 ,
267r.23 ,
2620.02,2625.57,2631.0r ,
2636.50 ,
2643 .09 ,
2652.94,2',709.0r,2't59.5s,279a.OO ,
2a34.25,2A12.11 ,
2959.50 ,
49 .4 ,
62 .4 ,
62 .4 ,
' 1W
,''{_6, t-'
Cr4, tbtl}/2-/t '
GEOO2
604,Fb1.GBOO1
02:57:03 02 -Jan- 10 51702157:02 0 2 -Jan 10 51802:57.01 02-Jan L0 51902 :57:00 02 -Jan-10 52002 : s5:59 02-Jan-10 52102 :56:58 02 -Jan-10 52202 :55:57 02 -Jan-10 52302 :55:56 02 -Jan-10 S24
02 :55:55 02 -Jan- 10 52502 :56 .54 02-Jan-1o 52502 :56:53 02 -Jan-10 52702 :56.52 02-Jan-10 52802:56:51 02-Jan-10 52902.56.5O 02 ilan-1o 53002:56:4 9 02 -Jan- 10 53102 :5 6:4I 02-Jan 10 532A2:56:41 02 Jan 10 53:02.56:46 02 Jan- 10 534
02.55.43 02 ;ran-10 53702.55.42 02 Jan-10 538
o:2, se, ie oz-Jan.ro sqz02:55 :3? 02-Jan-10 543
EZ KV
ACTUAI, VAL ACTUAL VAL
02: s6:41 02 Jan 10 539 75 .52 ,
51 .39 ,
52.02,53 .11 ,
44.388,44 .388,44 . 388,44.38B,44.38B,44.388,44.388,44 .388.44.388,44 .388,44 .348,45.48,46.LO,46.'/r,4',7 .48 ,
41 .48 ,
18.16,49 .4r ,
0.500.50 ,
0.50 ,
1. 16 ,
1. 15 ,
\.56,2.66 ,
6.76 ,
72. 74 ,
16.62,46.62,76.62,16.52,16.62.16.6276_52 .
1,6 .62 ,
\5.62,
46.62a5.62).6 .62L6 .6216.6216.6216.62L6.62L6.6215 .62!6.6276.6216.6215 .6276 .62)-6 .6216 .62a6.5216.5216.5216.5215 .62t6 .6215 .6216.62
02156.36 02 Jan-10 54402 :55 :35 O2 Jan-10 54502.56,34 02 JaD-10 54602:56:33 02 -Jarl 10 547
54.76 ,
55.44,55.638,55.538,55.638,55.538,55.60 ,
51.20 ,
50. 8l ,
50. 8r ,
50.81 ,
50. g1 ,
50. 81 .
50.81 ,
50 .81 ,
50.81 ,
50. 81 ,
50. 81 ,
50.81 ,
t9.4 ,
19.4 ,
19.4 ,
24.4,35. s ,
140.6 ,
42.4 ,
42.8 .
180.1 ,
1?8.0 ,
178.0 ,
178. 0 ,
),42.9,r42.9,t71,.2,171.0 ,
180.4 ,
180.4 ,
180 .4 ,
180 .4 ,
180 .4 ,
180 .4 ,
180 .4 ,
180 .4 ,
180 .4 ,
-62 -4
-57.3-41.8-4',7.7
-2L .9
3',7 .537.53'7 .537 .540.140.137.756.718.3
16 .62 , r7.3 ,
1,6 .52 , r'7 .3 ,
r'7 .3 ,
3078.15 ,
3127 .59 ,
3164.94,''.,."9q4:.,11.,- -:
| 3244;Q4. ,' 32A4.69 ,
3344.02 ,
33'.t4.74,3416.53 ,
3451.57 .
3493 .43 ,
3493 .43 ,
3255.03 .
3075.95 ,
30't5.95,3075.95 ,
3075 _ 95 ,
30?5. 95 ,
3075.95 ,
307s.9s ,
3075.95 ,
3075.95 ,
3075.95 ,
3075.95 ,
3075.95,3075.95 ,
3075.95 ,
3075.95 ,
3075-95 ,
3075.95 .
02: 56:32 02 Jan-l-0 54802: 56:3I 02 Jan-10 54902:55 :30 O2 -Jan- 1O 55002:56.29 02 Jar-10 ss1
L
I oz'se,za 02-Jan-10 s52' 02ts6l.zz 02-.ten-1o s q't
;, 02tS6:26 02-Jan-10 55402:55:25 02-Jan-10 55502:56:24 02-Jan-10 55602:56 :23 02 -,lan- 10 Ss702.55 t22 02-Jan-LO 55A02:56:21 02-,f,an- 10 55902.56:20 02-Jan-10 55002:56:19 02-Jan-10 56102 :56:18 02-,f,ai-10 56202 :56:17 02-,lao-10 56302:56 tl6 02 ;raD-10 56402:56:15 02 -ifan- 10 56502.56.L4 02 Jan-10 566
50.8150.8150.8150 .8150.8150.81
18.3 .,
18.3 ,
18.3 ,
18.3 ,
18.3 ,
18 .3 ,
18-3 ,
18.3 ,
-i*-..
-_ EXHIBIT - 5/V (page 4 of 4)...... .
,Historical Tabular Trend 2 03:05:39
Time Date
02 ; 57:03 02 - Jan-10 517
02~57:02 02-Jan-l0 518
02:57:01 02 - Jan-10 519
02:57:00 02-Jan-10 520
02:56:59 02 - Jan-10 521
02:56:58 02-Jan-l0 522
02:56:57 02 - Jan-10 523
02:56:56 02-Jan-10 524
02:56:55 02-Jan - l0 525
02:56:54 02-Jan-l0 526
02:56:53 02-Jan-l0 527
02:56:52 02-Jan-10 528
02:56:51 02-Jan-10 529
02:56:50 02-Jan- 10 530
02:56:49 02 - Jan-l0 531
02:56:48 02 Jan-l0 532
02 :56:4 7 0 2 Jan-l0 533
534
535
536
537
538
539
:56:~8 02 -Jan~10 542
02:56:37 02-Jan- l0 543
02:56:36 02-Jan - l0 544
02:56:35 02-Jan - l 0 545
0'2:56:34 02-Jan- l0 546
02:56:33 02-Jan-l0 547
02:56:32 02-Jan-l0 548
02:56:31 02-Jan - l0 549
02:56:30 02-Jan-l0 550
02:56:29 02-Jan- l 0 551
02:56:28 02-Jan- 10 552
02:56:27 02-Jan-l0 553
02:56:26 02 - Jan-l0 554
02:56:25 02-Jan-l0 555
02:56:24 02 - Jan-l0 556
02:56:23 02 - Jan-l0 557
02:56:22 02-Jan-l0 558
02:56:21 02 - Jan-10 559
02:56:20 02-Jan-10 560
02:56:19 02-Jan- 10 561
02:56:18 02-Jan - l0 562
02:56:17 02 - Jan - l0 563
02:56:16 02-Jan-l0 564
02:56:15 02 - Jan-l0 565
02:56;14 02 - Jan-l0 566
U/l<o . FoO>f. GHOOl
HZ
ACTUAL VAL
44.38B,
44.38B,
44.38B,
44.38B,
44.38B,
44.38B,
44.38B,
44.38B,
44.38B,
44.38B,
44.38B,
45.48
46.10
46.71
47.48
47.48
48.76
49.41
51.39
52.02
53.11
54.76 ,
55.44 ,
55.63B,
55.638,
55.638,
55.638,
55.60
51.20
50.81
50.81
50.81
50.81
50.81
50.81
50.81
50.81
50.81
50.81
50.81
50.81
50.81
50.81
50.81
50.81
50.81
02 - Jan-l0 t,- u.1I--p
-t-i GE002
KV
ACTUAL VAL
0.60
0.60
0.60
1.16
1.16
1. 66
2.66
4.11
6.76
12.74
16.62
16.62
16.62
16.62
16.62
16 . 62
16.62
16.62
16.62
16.62
1 6.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
16.62
Ct"",r:. ) "'W MWOOI
MW
ACTUAL VAL
- 15.6B,
- 15.6B,
- 15.6B,
- 15.6B,
-15.6B,
- 15.6B,
-15.6B,
- 15.6B,
-7.9
0.4
23.2
20.6
14.9
14.9
17.3
17.3
17 . 3
17.3
~CH "'''AI
MW002
MVAR
ACTUAL VAL
- 118.8B,
-118.8B,
-118.8B,
-118.8B,
-118.8B,
-118.8B,
-118.8B,
- 118.8B,
-62.3
-0.8
90.6
3.7
-15.6
-20.8
-26.7
-30 . 3
-33.7
- 3 7.4
-r~ .... ,-,-a. TM007
ACTUAL VAL
2590 . 36
2602.44
2602.44
2611.23
2611.23
2620.02
2625.51
2631.01
2636.50
2643.09
2652.98
2709.01
2759.55
2798.00
2834.25
2872 . 71
2919 . 95
2959.50 I
- '. , .,. " :,.s. I. .... '~
~ 1.:] . 3. " ; . ~,,,. .-37.4 ' .' .,,,. ?)tr?';~:\J:!-j. ,,, ·., .• < ·~t.~!M~£ I
"~:~~M:~~~'~~:~'~:7 ' ;?PS/!.r!j'5'~~~;~~~;~~t~?~:~:> . L0~};.~%~~\: .'~:~;~": 17.3
17.3
17.3
1:7 :3 ., '" ~'-',' --."" ~.'.'~'
1-7.3 "
19.4
19.4
19.4
24.0
36.5
140.6
42.8
42.8
180.1
178.0
178.0
178.0
182.9
182.9
171.2
177.0
180.4
180.4
180.4
180.4
180.4
180.4
180.4
180.4
180.4
-49.4
-62.4
-62.4
.:~62 ; '4"' , ~.~~
-62.4 .. ,
- 62.4
- 62.4
- 57.3
- 41.8
- 47.7
-29.9
-2 1 .9
-21.9
37.5
37.5
37.5
37.5
40.1
40.1
37.1
56.7
18.3
18.3
18.3
18.3
18.3
18.3
18.3
18.3
18 . 3
3078.15
3127.59
3164.94
:,jp.~ .. ~ .. :3244' . 04~ ,
. 3284.69
3344.02
3374.78
3416.53
3461.57
3493.43
3493.43
3255.03
3075.95
3075.95
3075.95
3075.95
3075.95
3075.95
3075.95
3075.95
3075.95
3075.95
3075.95
3075 . 95
3075.95
3075.95
3075.95
3075.95
3075.95
![Page 169: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/169.jpg)
FO+or:\O
Ycor(ouJoaA
..''\\|
lo o o o o o o o o o o o o o o o o o o olN
N
C
.r (\ N
N
C{ N
N
N
N O
t (\ (\
(\ N
N
C{ N
O
t
o-grta' 6 t r I s E
EE
s n s t o fi fl fi n s.h'F_.?.9 o_ !+t >- =.> = >_.--.> h..2.--.> f...>-.-_.
oollr'u
g do#a
E 3 FF qE
EE
^
ErrrE
l Es trl E
iEltq
dEE
FfF-EE
nEr.fE
EH
::
!FFFFEE
HH
EE
HE
EgE
EFE
f;fssf,3sf;f,iPB
Pgig36=
cEFccFEE-i6_
r-rFFF-
#*RR
gxlxlltxXsxxf;S
gx:P
3 F F F q 3 FFq !i$ HH
$ gHbT
EE
3333HE
g$gHH
HE
gHE
EE
HH
HH
HH
3HH
H3333E
33EFE
FFF-I- i-FFF
rFl.-eI
9- I P I 9 9 9,.9 I I P
P I
-o- 9.9 -o- I Icc cc cE
ec cc cr E cc cc cc E
E cc F E
E -'r
X -
aa a a a a;a-aa E Fib6 E
dd a EFF
ri F
F F
F F
FF F
(O O
(O @
ol (ool o
ao
di d di di di d,b d d d d {ii iii d d dt 6 dt di dro tf, to ro rJ) ro ro ro ro I') ro I') to ro ro ()
ro tf) lo u)
N N
$I (Y N
N
C.I N
N
N
N N
(\ N
$I (\
c{ N
oI Noooooo()ooooooooooooo
-t-I=l (!lot
"l
.9..,9,.S?,.,9,.,9, L.9.,,C
...e.,p...9."9...9..9...9...p...9. 9...9.,9..
y>>{
rF
'El
o >
O- 6- (,)
LrJ
o;6oq?_i+
EtttrtrrILttit[[
;;EI;gE
tElC
;;;Eot\
o!.,rL\
-.:>l,l_lo-lI
;ol
a'la.I"-:l.tlol;lal
q IIIIIIII-tI
-tI
IIII;l I*t
I
;l>lal,iol(')l
zlEl
olxll{l;1JIL'rl
aLrJlol;t)l*i?t:lFl:l=iE
]Fl(,letolol;lB
ILl;lal
;l
I-lI-l""1;l--1'IF.lI-;l'l,1.nl
III
cooEa.l1!o-
ffixl6l @
l
r\.Et)t i
ItE E
t
m0
mi
e+*l_l<1:
si
8l{*l{*}
oi$l.:
ttttltll
|hl
ffi)
Ii ()@l
iieB
rsl
E{*rE
S=86-6r g0E
*B"3 f!
o;sflf,E-lE=l
_at.z-
11
,, @{f
ul :',1ilN
r-
I ^E)
|
Ll -:
a-\ E
i1! I
-l
f!!.rl-l
n$t-t'++l-t'u6qC
ha
Chapter- 5 _ E
XH
IBIT - 5/V
I (page 1 of 2),jI \
go·£'. 'i #1
filter I V Priority -.LJ-.LJ-2.:.J.2..:...l-LJ~..1.1J..11J
--rlw-L 2.' 5 6 ~.
PSEB I U#1 10:09
06.01 .10
~~ fw* 1 CONI STM I..M!!J TUR I fUEi GEN I ELE I Aux l CMNI 80E I SYS I---.J---.JI
~--.J--.J--.J--.J--.J--.J--.J--.J--.J--.J--.J--.J--.J . . V Plant Area
®.b:,g eCO -EJJ..§1Ll~~-fQJ ' OC 12!J..§LJ
AIR 01 HFE20EH113EIXG01 :02·0102:56:17 :AIR 01HFE20AN101BIXU09 , , :02·0102:56:17 :AIR 01HFE20AN101IXB01 · , 02·0102:56:17 :AIR 01HFE20AN101IXB02 :02·0102:56:17 :AIR 01HFE20AN101IXB02 :02·0102:56:17 :AIR 01HFE20AN101IXM07 :02·0102:56:17 TUR 01MAY10EH523AIXG01 , , :02·0102:56:17 :AIR 01HFE20EH113EIXG01 :02·01 02: 56: 17 AIR 01 HFE20AA 1 0 1 IXC03
:SW:02·01 02:56:17 :AIR 01HFE20AA101IXC03.1 , , :02-0102:56:17 TUR 01MAY10EH522AIXG01 :02-0102:56:18 TUR 01MAY10EH522DIXG01 , ,
:02·0102:56:18 TUR 01MAY10EH523BIXG01 · , :02-0102:56:18 :STM 01LAF10CE201IXG01 , . :02·0102:56:18 :STM 01LBA10EH504FIXG01 · , :02-0102:56:18 TUR 01MAY10EH620CIXG01 · . :02·0102:56:18 :ELE 01MAY10EH628FIXG01
:ELE 01BAT10EH602EIXG01 :02·0102:56:18 :AUX 01PAC10EH02F3IXG01
'MIL 01 HFC30EH 121 DIXG01
:PA·B MTR TRIP PA-B ELECTRICAL TRIP :PA FAN B MOTOR (HT) :PA FAN B MOTOR (HT) :PA FAN B MOTOR (HT) :PA FAN B MOTOR (HT) OVER SPEED TRIP-1 OPERATED :PA-B MTR TRIP :PA-B VANE AUTO/MANUAL :PA-B VANE CONTROL TURBINE TRIPED TUR TRIP GEAR OPERATED OVER SPEED TRIP-2 OPERATED TURBINE TRIP :MS TMP VLO TRIPING IN SERVI> TUR MSTR TRIP RL Y2 OPRTD :MSTR TRIP86T5COILS NOTHL T > :UNIT SERSGR B/C AUTO TRP :CWP-B MTR OVER LOAD
ILL-C MTR OVERLOAD
.. TRIP TRIP N.ON :OFF Off EF1 YES :N.TRIP :MANUAL :Manual YES :YES YES TRIP :NO YES eYES YES :YES
v 0::1 1 ~ 1 ~ill hIJ ~ m; ill]@j ill] ~ ::: ~ Qj lJj ® I & I AL~~~ §gl~Ji1J.1J~ ;~: ~~~rm
~
![Page 170: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/170.jpg)
f\oo..1IFL..i-ll^'tFqltvl
IC
hapter
Chapter- 5 _ E
XH
IBIT - 5/V
I (page 2 of 2)\r
"" '2- ":l ' .; (, ( S · O.t=.. .
2HFC31CR104AIXU01 TUR 02MAV10EH523AIXG01 TUR 02MAV10EH523AIXG01
:02-0102:56:30 :GEN 02lCB10CE101IXJ01 :02-0102:56:30 TUR 02MAV10EH522FIXG01 :02-01 02:56:30 TUR 02MAV10EH522DIXG01 '02-0102:56:30 TUR 02MAV10EH522DIXG01 :02-0102:56:30 :TUR 02MAV10EH522AIXG01 :02-0102:56:30 TUR 02MAV10EH522AIXG01 · . 92-0102:56:30 :STM 02lBA10EH504FIXG01 :02-0102:56:30 TUR 02MAV10EH523BIXG01 02-0102:56:30 TUR 02MAV10EH523BIXG01
.Gf #~ /) ""'" 2. . '3 6 J-/v'>
false :OVER SPEED TRIP-1 OPERATEDVES :OVER SPEED TRIP-1 OPERATED NO :Max_ value exceeded :10 TG BRG VIBRATION HI :VES TUR TRIP GEAR OPERATED :VES TUR TRIP GEAR OPERATED :NO TURBINE TRIPED 'YES TURBINE TRIPEDNO :MS TMP VlO TRIPING IN SERVI >NO . . :OVER SPEED TRIP-2 OPERATED :VES OVER SPEED TRIP-2 OPERATED NO
EB{ 0 e j 0 11
92-01 02:56:30 :STM 02LAF10CE201IXG01 TURBINE TRIP TRIP N_TRIP YES 'YES
02-01 02:56:30 :STM 02lAF10CE201IXG01 TURBINE TRIP :02-0102:56:30 TUR 02MAV10EH620CIXG01 :TUR MSTR TRIP RlV2 OPRTD :02-0102:56:30 :ElE 02MAV10EH628FIXG01 :MSTR TRIP86T5COIlS NOTHlT> · . '02-0102:56:30 :GEN 02BAC10CE109IXJ01 'Max_ value exceeded · . :02-01 02:56:30 AIR 02HFE10EH112EIXG01PA-A MTR TRIP
Ile- ' '02-0102:56:30 :AIR 02HFE10EH112EIXG01 :PA-A MTR TRIP
i F --, 02.01.2010 02:b6:29.609 .201002:56:29.809 Print end:
7 YES :RESET
---' v 0::7 1 ~J ~ §~~ l!IJ~ mLQ2jQ2LQ2j ~ ::: ~ QjIbJ D!J 11 ' 11 02HFC50EH123DIXG01 I~ _r ® 1 &. I ~J~.@j~ ~~.BJ lJ.mJ :;: ~ ~~ Rj
...:,.
J
![Page 171: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/171.jpg)
Chapter- 5 _ EXHIBIT - 5/VII (page 1 of 11)
ABB - Distu rbance Report
General data Nam e Stotion nom e Obj ect nom e Unit nom e Lin e l e n ~th
System FreQu ency R e cordin ~ numb er Tri ~~e r ,i ~ nol nom e Tri ~ dote ond tim e Pre-tri ~ re cordin ~ tim e Post tri ~ re cordin ~ tim e Totol re cordin ~ tim e Mox. re cordin ~ tim e R e cordin ~ in Test mod e Typ e of tim e synchronizotion lED typ e
lED ve rsion Somplin~ freQu ency
Disturbonce record e r Event record e r Foult locotor Act",e s ettin ~ ~ roup durin ~ re cordin ~
Recordin~ file: 201 001 0223 Date: 1121201 0 2:56:32 AM Station!8ay: ( 00k\' RGTPP Hisarl1 Template: D:\PC MDataBases\DRttemplates\defaultxml
Valu e 400kV RGTF'P Hi"r MOw.. LINE REL 670 M-1
Not opplicobl e 50.0 Hz ,~
TOC1_TRIP 1121201 0 2:56:32.373 AM 200 ms 499 ms 739 ms 2000 ms
" SNTP L67111 01 1.101 1.0 kHz
Instoll ed Instoll ed Not Instoll ed ,
1 (11)
![Page 172: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/172.jpg)
Chapter- 5 _ EXHIBIT - 5/VII (page 2 of 11)
ABB - Distu rbance Report
Fault location Nam e Fault loop 'we Fault location Status of hult calculation Fault Direction
Recordin~ file: 201 001 0223 Date: 1121201 0 2:56:32 AM Station!8ay: ( 00k\' RGTPP Hisarl1 Template: D:\PCMDataBases\DRttemplates\defaultxml
Valu e Not applicabl e Not applicabl e Not applicabl e Not applicabl e
2 (11)
![Page 173: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/173.jpg)
Chapter- 5 _ EXHIBIT - 5/VII (page 3 of 11)
.... 111 ABB - Distu rbance Report ,. .... ,., Analo !: channels Number Chann e l name PrefauMRMS
LlNE_A_IL1 1.3 fA , LlNE_A_IL2 1.3 fA , LlNE_A_IL3 1.3 fA , LlNE_A_IN 0.0 fA , !!LINE M CTN 0.0 fA 0 LlNE_UL1 229.6 kV , LlNE_UL2 224.8 kV , LlNE_UL3 227.7 kV , LINE_UN 5.0 kV
Reco'din~ file: 201 001 0223 Dale: 1!21201 0 2:56:32 AM Slalion!8ay: ( 00k\' RGTPP Hisa,!l
Prefaultangle
2T -11 79·
121S 74.1·
132T 0.0· -11 8.8· 120r -1 3.8·
Templale: D:\PCMDalaBases\DRttemplales\default.xml
FaultRMS
0.0 fA 0.0 fA 0.0 fA 0.0 fA 0.0 fA 549 kV 27.8 kV 99 kV 51.6 kV
Faultangle
-41.0· 57.r -21 .4. -121S -37.8· -58.6· 148.8· -96T -80.0·
3 (11)
![Page 174: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/174.jpg)
Chapter- 5 _ EXHIBIT - 5/VII (page 4 of 11)
.... 111 ABB - Distu rbance Report ,. .... ,., Digital channels Number Chann e l name Trigger Trig leve l Chann e l Trigg e rstatusat
e nabled valu e attrig trig time tim e
TRIP_TRIP C C , TRIPLI C C , TRIP L2 C C , TRIP L3 C C , ZM01-TRIP C C 0 ZM01-STM1T C C , ZM02-TRIP C C , ZM02-STM1T C C , ZM03-TRIP C C
" ZM03-STM1T C C
" ZMCl4-TRIP C C
" ZMCl4-STM1T C C n ZM05-TRIP C C
" ZM05-STM1T C C ,; SOTF_TRIP C C
" PSB_OPTD C C C
" PHS-STFI>IL 1 C C
" PHS-STFl>lL2 C C n PHS-STFl>lL3 C C
" PHS-STFI>IPE C C
" ZCOM_TRIP C C n ZCOM_CS C C n TCJAULTY C C C
" ZCAL-IREV C C C
" ZCAL-TRI>IEI C C C
" ZCAL-TRI>IEILI C C C n ZCAL-TRI>IEIL2 C C C n ZCAL-TRI>IEIL3 C C C n ZCAL_ECHO C C C ;C BRC_TRIP C C
" TEFl_TRIP C C n TEF1_STM1T C C n TOV1_STGl C C ~ TOV1_STG2 C C C
" TOV1_STM1T C C ;0 TOV2_TRIP C C n TOV2_STM1T C C
" TUV1_STGl C C C
" TUV1_STG2 C C C
" TUV1_STM1T C C
" TUV2_TRIP C C C
" LOV_TRIP C C C
" LBB_TRIP C C
" LBB_RETRIP C C C
" POOl_TRIP C C C
" FUSEJAIL C C
" TOC2_TRIP C C C
" SOTF_TBC C C C
" TOC1_TRIP
" TOCI STL1 C C
ReCO'di"?> file: 201 001 0223 Date: 112 0102:56:32 AM
4 (11)
Station!8ay: ( 00k\' RGTPP Hisa,I1 Template: D:IPCMDataBases\DRttemplates\defaultxml
![Page 175: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/175.jpg)
Chapter- 5 _ E
XH
IBIT - 5/V
II (page 5 of 11)
~g*~ ~~S~ '" '" ;::,c O"'O=> 2"'~" .00 0 0 ",,,, "' '<'-'':0 :i?,,[:g '"O)"'~ ~~;;:S "' " "I W
6~ 21'" ~
* ~ ~ , ~
> o
~~~~~~~6~~~~~g~~~~~~~~~
8g~~~~~~~gg~~~~~~~~~~bb , '1~"~ZZZZI~I~~':05':O':OZbZ~~gg ~ ~I 1 ';-' ';-' ';-' ';-' J:l)!:1 1 J:l1 1 "'I ",I 1 1 1 ~ I~~o~oo~or~~~~p~~~~~~~ ~I J:l"-J:lCJl<m~C O~I-< o(f)zJ:lJ:l"'lrr 'wP r m ~~~ ~IJ:l~(f) 0 <~w'" ~O m 1 mOm 1 I(f) oroOo
m Z m m ~
oooo~oooooooooo~~oo~~~~
~ooooooo_oo~~oooooooooo
00000000000000000000000
Z 0 . -. f~ J ; ~ , . , , !
H ~ ~,
• 0 "0 [ ~
~ o
[
3" ~ &2 • •• ., · ' = ~ , o
3" ~ ~ • _ 0
• 0 • • · " i,
,= II II
l> III III
o !!l " ~ CO>
" o
" " " " o
'"
![Page 176: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/176.jpg)
Chapter- 5 _ EXHIBIT - 5/VII (page 6 of 11)
ABB - Distu rbance Report
Total recording Tria'" timo, 1r:l!2010 25632373 AM "" 0 100
+-'_+-+----_+ ___ -+_ LIN[_UL3 (8)
f----+---if-lrl-"--+-+-----+--- -J:- LIN[_UN (9)
L--+-+------+-----i_ LIN[_A_IL3 (3)
Reco'din~ file, 201 001 0223 Date, 1121201 0 2,56,32 AM Station!8ay, ( OOkY RGTPP Hisa,I1 Template, D,\PCMDataBases\DRttemplates\defaultxml
5(11)
![Page 177: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/177.jpg)
Chapter- 5 _ EXHIBIT - 5/VII (page 7 of 11)
ABB - Distu rbance Report
Total recording Tria'" timo, 1r:l!2010 25632373 AM "" . ;;00 -1 00 0 100 m m ___ _
TRIP='I'RIP"(l)
_____ -'- ________________ "'------J _________________________ J
Reco'din~ file, 201 001 0223 Date, 1121201 0 2,56,32 AM Station!8ay, 400kY RGTPP Hisa,I1 Template, D,\PCMDataBases\DRttemplates\defaultxml
TRIP Ll (2) TRIP 12 (3) TRIP 13 (4) ZMOI_TRIP(S) ZMOI_START(6) ZM02_ TRIP (7) ZM02_ST ART (S) ZM03_ TRIP (9) ZM03_ST ART (10) ZMCI4_TRIP(II) ZMCI4_ST ART (12) ZMOS_ TRIP (13) ZMOS_START (1 4) SOTf_TRIP(IS) PSE_OPTD (16) PHS_STfWLI (17) PHS_STfWL2 (IS)
PHS_STfWL3 (19) PHS_SHWPl (:10) ZCOM_TRIP (21) ZCOM_CS (22) TC]AULTY(23) ZCAL_IR!:V (24) ZCAL_ TRWlI (2S) ZCAL_ TRWlILl (26) ZCAL_ TRWlI12 (27) ZCAL_ TRWlI13 CIS)
ZCAL_lCHO (:19) ERC_TRIP (30) TEfl_TRIP(31) TEfl_START (32) TOVI_STGI (33) TOVI_STG2 (34) TOVI_START (3S) TOv:l_TRIP (36) TOv:l_ST ART (37) TUVI_STGI (38) TUVI_STG2 (39) TUVI_START (40) TUv:I_TRIP (41) LOV_TRIP(42) LEE_TRIP (43) LEE_R!:TRIP (44) POO I_TRIP(4S) ruSl]AIL (46) TOC2_TRIP(47) SOTf_TOC(4S) TOCI_TRIP(49) TOCI_STLl (SO) TOCI_ST12 (SI) TOCI_ST13 (S2) Tlfl_STfW(S3) Tlfl_STRV(54) MAIN2_CR(SS)
AUTO_SYNC_OK(56) MAIN2_CS (S7) AROI_CLOSlCE (58) AROI_UNSUCC (S9)
7 (11)
![Page 178: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/178.jpg)
Chapter- 5 _ EXHIBIT - 5/VII (page 8 of 11)
ABB - Distu rbance Report
Disturbance 1
75 100 125 ISO 175187
,,'! ++t-H'-\-I !+t-L---------t-----l.~ LINl_A_I13 (3)
Reco'din~ file: 201 001 0223 Da1e: 1121201 0 2:56:32 AM S1a1ion!8ay: 400kY RGTPP Hisa,I1 Templa1e: D:\PCMDa1aBases\DRttempla1es\default.xml
TRIP Ll (2)
TRIP 12 (3)
TRIP 13 (4)
ERe_TRIP (30)
TOCI_TRIP(49)
TOCI_STLl (SO)
TOCI_ST12 (51)
TOCI_ST13 (52)
THI_STRV(S4)
AROI]3PH (61)
MAIN2_ TRIP (69)
EXT_TRIP _3PH (86)
8 (11)
![Page 179: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/179.jpg)
Chapter- 5 _ EXHIBIT - 5/VII (page 9 of 11)
ABB - Distu rbance Report
Disturbance 1 (Voltages)
• LN'_LLl LN'_LL2 LN'_LL3 LN'_~
Reco'din~ file: 201 001 0223
-= 185.0 211.2 219.3 B
Date: 1!21201 0 2:56:32 AM Station!8ay: 400kY RGTPP Hisa,!l
"'" 260.1 " 147.9" 17.5" 242.5"
•
Template: O:\PCMOataBases\DRttemplates\defaultxml
9 (11)
![Page 180: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/180.jpg)
Chapter- 5 _ EXHIBIT - 5/VII (page 10 of 11)
ABB - Distu rbance Report
Disturbance 1 (Voltages)
,
j
• LN'_LLl LN'_LL2 LN'_LL3 LN'_~
Reco'din~ file: 201 001 0223
-= 185.0 211.2 219.3 B
Date: 1!21201 0 2:56:32 AM Station!8ay: 400kY RGTPP Hisa,!l
-260.1 " 147.9" 17.5" 242.5"
Template: O:\PCMOataBases\DRttemplates\defaultxml
Disturbance 1 (Currents)
• LN'_A_L1 LN'_A_L2 LN'_A_U LN'_A_~
,
-252.9" 148.5" 18.3" 341.1 "
10(11)
![Page 181: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/181.jpg)
Cha
pter
- 5 _
EX
HIB
IT -
5/V
II (p
age
11 o
f 11) " o
a. " 0::
" u
" '" .c ~
:J
1ii o In In «
II II cC
•
• , "
•
~
• , • Z
~ ] · , > , • z
••••••••••••••••••••• ~~R~~~~~~~~~~~~NN~~~~ MMMMMMMM~~~~~~~~~~~~~
NNNNNNNNNNNNNNNNNNNNN MMMMMOOMMMMMMMMMMMMMMM ~~~~~~~~~~~~~~~~~~~~~ ~~~~~~~~~~~~~~~~~~~~~
NNNNNNNNNNNNNNNNNNNNN 000000000000000000000 ~~~~~~~~~~~~~~~~~~~~~
000000000000000000000 ggggggggggggggggggggg
cccccccc~~c~c~~~~~~~~
000000000000000000000
" ~ 00,,,,- "'-g:~C(C( " go >-, >-, ::J 'j 'J Zy'o~~~~ ~W:=,g:g:g:g:
it::J'j>~ M>->-gof" ",-COCOCO"
I I I IN
600C;:Z~ C(OOw «>->->-
",-~'J"'-fr"'C(g:toC(to~~NM >-, I I >-, I I --' --' --' OOOOc;:~~~~ Cl:OOCl:WC(C(C(C( m>->-",>->->->->-
~~~~NM~~~~~~g~~g~~NM~
c
~ -, ~ ~ ~ ~
'i:~ ~~
fi,",~~ 8.(~", ~N",j'l
g:Jct(l 0"':1::", "''''00
~;:~~ <=0,,0
~&l~ '2;:05-[ ~TJ~~ "'000>-
![Page 182: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/182.jpg)
Fault graphics [C:\DM(CI)\TAR\TAR\DR on Dated 020110\Nal-II\[email protected]] - SJVNL 38 Date: 02.01.0010
Data cursor: 03:01:42.742
VA-26166.199
VB-33084.688
VC59434.621
VN201.393
IA-1203.676
IB-743.582
IC1938.177
IN-3.827
Z4�
Z3�
Z2�
Z1�
L8TRIP CH 1/2REC�
L7 V>PROTN OPTD�
L4 MAIN1 CAR REC�
L15 86 LO TRIP�
L3 52 B PH OPEN�
L2 52 Y PH OPEN�
L1 52 R PH OPEN�
V
5-2.0x10
5-1.0x10
0
51.0x10
52.0x10
53.0x10
A
-1000
0
1000
Chapter- 5 _ EXHIBIT - 5/VIII (page 1 of 1)
![Page 183: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/183.jpg)
400KV DADRI LINE DT: 02/01/2010 03:01:43.810256 Dt: 131175 microsec - 6.56 Cyc 1212.0000 AS: ON
030143.DAT - 02/01/2010 - 03:01:43.679 (Peak Type) Page: 1
CH
1
2
3
4
5
6
7
8
|̂
02/01/2010 03:01:43.468000
1
2
3
14
15
16
17
18
28
29
32
Chapter- 5 _ EXHIBIT - 5/IX (page 1 of 6)
![Page 184: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/184.jpg)
030143.DAT - 02/01/2010 - 03:01:43.679 (Peak Type) Page: 2
|̂
02/01/2010 03:01:44.582456
Title
VA
RMS
166590.004
InstPeak
235404.200
Phase
144.578°
InstVal
124010.400
RefVal
-240920.00
MaxPeak
508404.600
MinPeak
-452897.90
Units
V
PixsDisp
53
Title
VB
RMS
164907.497
InstPeak
237433.000
Phase
23.584°
InstVal
93927.100
RefVal
87270.100
MaxPeak
351743.200
MinPeak
-489701.60
Units
V
PixsDisp
53
Title
VC
RMS
159464.654
InstPeak
-226750.100
Phase
263.415°
InstVal
-224309.20
RefVal
144330.100
MaxPeak
521623.500
MinPeak
-341377.30
Units
V
PixsDisp
53
Title
VN
RMS
5261.846
InstPeak
-229729.900
Phase
125.177°
InstVal
-6371.700
RefVal
-9319.800
MaxPeak
526568.700
MinPeak
-462407.90
Units
V
PixsDisp
53
Title
IA
RMS
2635.910
InstPeak
-3734.224
Phase
0.465°
InstVal
-104.956
RefVal
2615.614
MaxPeak
3723.176
MinPeak
-3734.224
Units
A
PixsDisp
7473
Title
IB
RMS
2677.958
InstPeak
-3659.650
Phase
239.375°
InstVal
-3234.302
RefVal
856.220
MaxPeak
3786.702
MinPeak
-3783.940
Units
A
PixsDisp
7367
Title
IC
RMS
2624.209
InstPeak
3712.128
Phase
118.841°
InstVal
3272.970
RefVal
-3477.358
MaxPeak
3712.128
MinPeak
-3706.604
Units
A
PixsDisp
7473
Title
IN
RMS
17.082
InstPeak
-516.494
Phase
69.864°
InstVal
-63.526
RefVal
-8.286
MaxPeak
1372.714
MinPeak
-516.494
Units
A
PixsDisp
20299
A L1 M.C.B R CLOSE A N 03:01:43.816031 001
A L2 M.C.B Y CLOSE A N 03:01:43.816031 001
A L3 M.C.B B CLOSE A N 03:01:43.816031 001
A L14 T.C.B R CLOS A N 03:01:43.816031 001
A L15 T.C.B Y CLOS A N 03:01:43.814381 001
A L16 T.C.B B CLOS A N 03:01:43.814381 001
A Z1 N N 03:01:43.778081 03:01:43.816031 002
A T1 N N 03:01:43.679081 03:01:43.820981 002
A Power Swing N N 03:01:43.677431 03:01:43.992581 002
A R2 ANY TRIP Y N N 03:01:43.778081 03:01:43.858931 002
A DIST Sig. Send N N 03:01:43.778081 03:01:43.825931 002
Chapter- 5 _ EXHIBIT - 5/IX (page 2 of 6)
![Page 185: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/185.jpg)
MALERKOTLA 1 2 Jan 2010 2:35:38 m
A 02:35:37.621 # 107 400KV DADRI LINE MAIN-II START-R
N 02:35:37.636 # 107 400KV DADRI LINE MAIN-II START-R
N 02:35:37.636 # 110 400KV DADRI LINE MAIN-II START-N
A 02:36:50.558 # 109 400KV DADRI LINE MAIN-II START-B
A 02:36:50.558 # 110 400KV DADRI LINE MAIN-II START-N
N 02:36:50.574 # 109 400KV DADRI LINE MAIN-II START-B
N 02:36:50.574 # 110 400KV DADRI LINE MAIN-II START-N
A 02:36:57.814 # 107 400KV DADRI LINE MAIN-II START-R
A 02:36:57.814 # 110 400KV DADRI LINE MAIN-II START-N
N 02:36:57.829 # 107 400KV DADRI LINE MAIN-II START-R
N 02:36:57.830 # 110 400KV DADRI LINE MAIN-II START-N
A 02:36:58.272 # 108 400KV DADRI LINE MAIN-II START-Y
A 02:36:58.272 # 110 400KV DADRI LINE MAIN-II START-N
N 02:36:58.288 # 108 400KV DADRI LINE MAIN-II START-Y
N 02:36:58.288 # 110 400KV DADRI LINE MAIN-II START-N
A 02:37:13.300 # 109 400KV DADRI LINE MAIN-II START-B
A 02:37:13.300 # 110 400KV DADRI LINE MAIN-II START-N
N 02:37:13.316 # 109 400KV DADRI LINE MAIN-II START-B
N 02:37:13.316 # 110 400KV DADRI LINE MAIN-II START-N
A 02:38:44.502 # 107 400KV DADRI LINE MAIN-II START-R
A 02:38:44.502 # 110 400KV DADRI LINE MAIN-II START-N
N 02:38:44.518 # 107 400KV DADRI LINE MAIN-II START-R
N 02:38:44.518 # 110 400KV DADRI LINE MAIN-II START-N
A 02:39:48.572 # 110 400KV DADRI LINE MAIN-II START-N
A 02:39:48.573 # 107 400KV DADRI LINE MAIN-II START-R
N 02:39:48.589 # 107 400KV DADRI LINE MAIN-II START-R
N 02:39:48.589 # 110 400KV DADRI LINE MAIN-II START-N
A 02:41:55.332 # 110 400KV DADRI LINE MAIN-II START-N
A 02:41:55.333 # 107 400KV DADRI LINE MAIN-II START-R
N 02:41:55.348 # 107 400KV DADRI LINE MAIN-II START-R
N 02:41:55.349 # 110 400KV DADRI LINE MAIN-II START-N
A 02:51:10.380 # 333 400KV LUDHIANA MAIN-II E/F START
A 02:51:10.392 # 394 PTL LINE MAIN-I TRIP B-PH
A 02:51:10.410 # 109 400KV DADRI LINE MAIN-II START-B
A 02:51:10.410 # 110 400KV DADRI LINE MAIN-II START-N
A 02:51:10.410 # 407 PTL LINE CARRIER PROT CH-II RECEIVED FOR MAIN-II
A 02:51:10.416 # 125 400KV DADRI LINE MAIN-I START-N
N 02:51:10.425 # 109 400KV DADRI LINE MAIN-II START-B
N 02:51:10.426 # 110 400KV DADRI LINE MAIN-II START-N
A 02:51:10.434 # 388 PTL LINE CARRIER PROT CH-I RECEIVED FOR MAIN-I
N 02:51:10.445 # 457 PTL LINE MAIN CB 412-52 B-PH CLOSE/OPEN
A 02:51:10.510 # 396 PTL LINE MAIN-I PROT TRIP
N 02:51:10.511 # 388 PTL LINE CARRIER PROT CH-I RECEIVED FOR MAIN-I
N 02:51:10.511 # 407 PTL LINE CARRIER PROT CH-II RECEIVED FOR MAIN-II
N 02:51:10.516 # 463 PTL LINE TIE CB 411-52 B-PH CLOSE/OPEN
N 02:51:10.531 # 125 400KV DADRI LINE MAIN-I START-N
N 02:51:10.541 # 333 400KV LUDHIANA MAIN-II E/F START Cha
Chapter- 5 _ EXHIBIT - 5/IX (page 3 of 6)
![Page 186: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/186.jpg)
N 02:51:10.548 # 456 PTL LINE MAIN CB 412-52 Y-PH CLOSE/OPEN
N 02:51:10.549 # 455 PTL LINE MAIN CB 412-52 R-PH CLOSE/OPEN
N 02:51:10.574 # 394 PTL LINE MAIN-I TRIP B-PH
N 02:51:10.650 # 396 PTL LINE MAIN-I PROT TRIP
A 02:51:10.708 # 429 PTL LINE MAIN CB1252 COMPRESSOR START/STOP
A 02:51:11.622 # 333 400KV LUDHIANA MAIN-II E/F START
A 02:51:12.693 # 463 PTL LINE TIE CB 411-52 B-PH CLOSE/OPEN
N 02:51:12.741 # 333 400KV LUDHIANA MAIN-II E/F START
A 02:51:57.746 # 455 PTL LINE MAIN CB 412-52 R-PH CLOSE/OPEN
A 02:51:57.752 # 456 PTL LINE MAIN CB 412-52 Y-PH CLOSE/OPEN
A 02:51:57.754 # 457 PTL LINE MAIN CB 412-52 B-PH CLOSE/OPEN
N 02:52:29.679 # 429 PTL LINE MAIN CB1252 COMPRESSOR START/STOP
MALERKOTLA 1 2 Jan 2010 2:53:59 m
A 02:53:58.154 # 109 400KV DADRI LINE MAIN-II START-B
A 02:53:58.154 # 110 400KV DADRI LINE MAIN-II START-N
N 02:53:58.170 # 109 400KV DADRI LINE MAIN-II START-B
N 02:53:58.170 # 110 400KV DADRI LINE MAIN-II START-N
A 02:54:58.902 # 110 400KV DADRI LINE MAIN-II START-N
A 02:54:58.903 # 108 400KV DADRI LINE MAIN-II START-Y
N 02:54:58.918 # 108 400KV DADRI LINE MAIN-II START-Y
N 02:54:58.918 # 110 400KV DADRI LINE MAIN-II START-N
A 02:55:00.214 # 108 400KV DADRI LINE MAIN-II START-Y
A 02:55:00.214 # 110 400KV DADRI LINE MAIN-II START-N
N 02:55:00.230 # 108 400KV DADRI LINE MAIN-II START-Y
N 02:55:00.230 # 110 400KV DADRI LINE MAIN-II START-N
A 02:55:03.187 # 110 400KV DADRI LINE MAIN-II START-N
A 02:55:03.188 # 107 400KV DADRI LINE MAIN-II START-R
N 02:55:03.203 # 107 400KV DADRI LINE MAIN-II START-R
N 02:55:03.203 # 110 400KV DADRI LINE MAIN-II START-N
A 02:55:03.358 # 109 400KV DADRI LINE MAIN-II START-B
A 02:55:03.358 # 110 400KV DADRI LINE MAIN-II START-N
N 02:55:03.374 # 109 400KV DADRI LINE MAIN-II START-B
N 02:55:03.374 # 110 400KV DADRI LINE MAIN-II START-N
A 02:55:03.475 # 107 400KV DADRI LINE MAIN-II START-R
A 02:55:03.475 # 110 400KV DADRI LINE MAIN-II START-N
N 02:55:03.491 # 107 400KV DADRI LINE MAIN-II START-R
N 02:55:03.491 # 110 400KV DADRI LINE MAIN-II START-N
A 02:55:11.178 # 110 400KV DADRI LINE MAIN-II START-N
A 02:55:11.179 # 108 400KV DADRI LINE MAIN-II START-Y
N 02:55:11.194 # 110 400KV DADRI LINE MAIN-II START-N
N 02:55:11.195 # 108 400KV DADRI LINE MAIN-II START-Y
A 02:55:12.345 # 109 400KV DADRI LINE MAIN-II START-B
A 02:55:12.345 # 110 400KV DADRI LINE MAIN-II START-N
N 02:55:12.361 # 109 400KV DADRI LINE MAIN-II START-B
N 02:55:12.361 # 110 400KV DADRI LINE MAIN-II START-N
A 02:56:22.777 # 107 400KV DADRI LINE MAIN-II START-R
A 02:56:22.777 # 110 400KV DADRI LINE MAIN-II START-N
N 02:56:22.793 # 107 400KV DADRI LINE MAIN-II START-R
N 02:56:22.793 # 110 400KV DADRI LINE MAIN-II START-N
A 02:56:23.630 # 110 400KV DADRI LINE MAIN-II START-N C
Chapter- 5 _ EXHIBIT - 5/IX (page 4 of 6)
![Page 187: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/187.jpg)
A 02:56:23.631 # 107 400KV DADRI LINE MAIN-II START-R
N 02:56:23.646 # 107 400KV DADRI LINE MAIN-II START-R
N 02:56:23.647 # 110 400KV DADRI LINE MAIN-II START-N
A 02:56:34.430 # 317 400KV LUDHIANA MAIN-I PSB OPERATED
N 02:56:36.440 # 317 400KV LUDHIANA MAIN-I PSB OPERATED
N 02:56:52.577 # 333 400KV LUDHIANA MAIN-II E/F START
A 02:56:52.634 # 333 400KV LUDHIANA MAIN-II E/F START
N 02:56:52.749 # 333 400KV LUDHIANA MAIN-II E/F START
A 02:56:52.795 # 333 400KV LUDHIANA MAIN-II E/F START
N 02:56:52.913 # 333 400KV LUDHIANA MAIN-II E/F START
A 02:56:52.972 # 333 400KV LUDHIANA MAIN-II E/F START
N 02:56:53.084 # 333 400KV LUDHIANA MAIN-II E/F START
A 02:56:53.130 # 333 400KV LUDHIANA MAIN-II E/F START
N 02:56:53.242 # 333 400KV LUDHIANA MAIN-II E/F START
A 02:56:53.310 # 333 400KV LUDHIANA MAIN-II E/F START
A 02:56:53.338 # 62 400KV ICT-1 COOLING/OLTC AC SUPPLY FAIL
A 02:56:53.348 # 428 PTL LINE MAIN CB 412-52 AC FAIL
N 02:56:53.358 # 333 400KV LUDHIANA MAIN-II E/F START
A 02:56:53.370 # 318 400KV LUDHIANA MAIN-I R/Y/B START
N 02:56:53.375 # 62 400KV ICT-1 COOLING/OLTC AC SUPPLY FAIL
N 02:56:53.375 # 428 PTL LINE MAIN CB 412-52 AC FAIL
N 02:56:53.392 # 318 400KV LUDHIANA MAIN-I R/Y/B START
A 02:56:53.401 # 428 PTL LINE MAIN CB 412-52 AC FAIL
MALERKOTLA 1 2 Jan 2010 2:56:55 m
A 02:56:53.402 # 363 CB852 COMPRESSOR AC SUPPLY FAIL
A 02:56:53.404 # 343 CB952 AC FAIL/CB COMPRESSOR START/STOP
A 02:56:53.406 # 62 400KV ICT-1 COOLING/OLTC AC SUPPLY FAIL
A 02:56:53.408 # 281 400KV ICT-2 COOLING SYSTEM FAIL
N 02:56:53.811 # 62 400KV ICT-1 COOLING/OLTC AC SUPPLY FAIL
N 02:57:30.263 # 363 CB852 COMPRESSOR AC SUPPLY FAIL
N 02:57:30.264 # 343 CB952 AC FAIL/CB COMPRESSOR START/STOP
N 02:57:59.457 # 428 PTL LINE MAIN CB 412-52 AC FAIL
N 02:59:20.965 # 173 400KV BUS REACTOR BKR. 652 R-Y-B PH CLOSE/OPEN
A 02:59:21.077 # 202 BUS REACTOR CB 652 TROUBLE
N 02:59:23.024 # 169 TIE BKR. 552 R-Y-B PH CLOSE/OPEN
A 02:59:23.115 # 187 CB 552 ICT II & BUS REACTOR TIE CB TROUBLE
2 Jan 2010 3:00:00 m
A 02:59:59.986 # 256 TIME SYNC PULSE FROM GPS
N 03:00:00.037 # 256 TIME SYNC PULSE FROM GPS
A 03:01:43.680 # 105 400KV DADRI LINE MAIN-II POWER SWING BLOCK
A 03:01:43.781 # 109 400KV DADRI LINE MAIN-II START-B
A 03:01:43.782 # 97 400KV DADRI LINE MAIN-II PROTN TRIP
A 03:01:43.782 # 107 400KV DADRI LINE MAIN-II START-R
A 03:01:43.782 # 108 400KV DADRI LINE MAIN-II START-Y
A 03:01:43.796 # 99 400KV DADRI LINE MAIN-II CARRIER I/T SIGNAL SEND
N 03:01:43.802 # 11 TIE CB 252 Y-PH CLOSE/OPEN
N 03:01:43.804 # 12 TIE CB 252 B-PH CLOSE/OPEN
N 03:01:43.805 # 10 TIE CB 252 R - PH CLOSE/OPEN
N 03:01:43.805 # 17 400KV DADRI LINE BKR. 352 R-PH CLOSE/OPEN CCChaC
Chapter 5 _ EXHIBIT - 5/IX (page 5 of 6)
![Page 188: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/188.jpg)
N 03:01:43.805 # 18 400KV DADRI LINE BKR. 352 Y-PH CLOSE/OPEN
N 03:01:43.805 # 19 400KV DADRI LINE BKR. 352 B-PH CLOSE/OPEN
N 03:01:43.817 # 107 400KV DADRI LINE MAIN-II START-R
N 03:01:43.817 # 108 400KV DADRI LINE MAIN-II START-Y
N 03:01:43.817 # 109 400KV DADRI LINE MAIN-II START-B
A 03:01:43.817 # 120 400KV DADRI LINE MAIN-I POWER SWING BLOCK
A 03:01:43.818 # 125 400KV DADRI LINE MAIN-I START-N
A 03:01:43.824 # 318 400KV LUDHIANA MAIN-I R/Y/B START
N 03:01:43.828 # 99 400KV DADRI LINE MAIN-II CARRIER I/T SIGNAL SEND
N 03:01:43.840 # 125 400KV DADRI LINE MAIN-I START-N
A 03:01:43.854 # 317 400KV LUDHIANA MAIN-I PSB OPERATED
N 03:01:43.856 # 318 400KV LUDHIANA MAIN-I R/Y/B START
N 03:01:43.859 # 97 400KV DADRI LINE MAIN-II PROTN TRIP
A 03:01:43.869 # 138 400KV ICT-I & DADRI LINE TIE CB TROUBLE
N 03:01:43.993 # 105 400KV DADRI LINE MAIN-II POWER SWING BLOCK
N 03:01:44.812 # 120 400KV DADRI LINE MAIN-I POWER SWING BLOCK
N 03:01:45.844 # 317 400KV LUDHIANA MAIN-I PSB OPERATED
C
Chapter- 5 _ EXHIBIT - 5/IX (page 6 of 6)
![Page 189: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/189.jpg)
Chapter- 5 _ EXHIBIT - 5/X (page 1 of 1)
""'"0 [;lI 400 leV UNSWITCHED At UNE REACTOR
THERMAL 0iiiiI 4()O kV SWITCHED :l BUS/UNE REACTOR .... III 33 IN SWITCHED BUS REACTOR
POWERGRID SUB-STATION @ HYDe BACK TO BACK --I>/<J--
BBMB SUB-STATION • q • STATIC VAR COMPENSATOR STATES SUB-STATION
Exhibif..2
NETWORK CONDITION AT 03:01 HRS OF 02 JAN 2010
705 IN TRANSMISSION UNES -tMlC _ 500 IN UNE ~
FACT I!{l
400 leV TRANSMISSION UNES
220 kV TRANSMISSION UNES
SVC 4: BUS/UNE REIICTOR RATING IN WAR
NORTHERN
WESTERN
VlNDHYACHAL 400
TO BISWANATHCHARIYAU(NER) (HVDC BIPOLE)
"""
kV
400 IV GRID DIAGRAII OF NOl!TllERN REGION
![Page 190: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/190.jpg)
Sequence of Events for Disturbance at 21.54 hrs of 02nd Jan 2010
'02-01-2010 '21:00:12.220 MAHINDERGARH CB E_05 STTS CLOSED GOOD Valid
'02-01-2010 '21:00:16.744 NUNAMAJRA CB E_07(DLTBD-1) STTS CLOSED GOOD Valid
'02-01-2010 '21:00:16.758 NUNAMAJRA CB E_10(BHADR-2) STTS BETWEEN Bad Valid
'02-01-2010 '21:00:16.762 NUNAMAJRA CB E_06 STTS BETWEEN Bad Valid
'02-01-2010 '21:00:16.762 NUNAMAJRA CB E_09(BHADR-1) STTS BETWEEN Bad Valid
'02-01-2010 '21:00:16.765 NUNAMAJRA CB E_03(T1) STTS BETWEEN Bad Valid
'02-01-2010 '21:00:16.765 NUNAMAJRA CB E_12(ROTAK-2) STTS BETWEEN Bad Valid
'02-01-2010 '21:00:16.774 NUNAMAJRA CB E_07(DLTBD-1) STTS BETWEEN Bad Valid
'02-01-2010 '21:00:16.796 NUNAMAJRA CB E_11(ROTAK-1) STTS BETWEEN Bad Valid
'02-01-2010 '21:00:23.361 NUNAMAJRA CB E_12(ROTAK-2) STTS CLOSED GOOD Valid
'02-01-2010 '21:00:23.364 NUNAMAJRA CB E_09(BHADR-1) STTS OPEN GOOD Valid
'02-01-2010 '21:00:23.365 NUNAMAJRA CB E_07(DLTBD-1) STTS OPEN GOOD Valid
'02-01-2010 '21:00:23.365 NUNAMAJRA CB E_11(ROTAK-1) STTS OPEN GOOD Valid
'02-01-2010 '21:00:23.369 NUNAMAJRA CB E_07(DLTBD-1) STTS INVALID Bad Valid
'02-01-2010 '21:00:23.381 NUNAMAJRA CB E_03(T1) STTS OPEN GOOD Valid
'02-01-2010 '21:00:39.836 MAHINDERGARH CB E_05 STTS OPEN GOOD Valid
'02-01-2010 '21:01:45.192 NUNAMAJRA CB E_09(BHADR-1) STTS CLOSED GOOD Valid
'02-01-2010 '21:02:01.657 NUNAMAJRA CB E_03(T1) STTS CLOSED GOOD Valid
'02-01-2010 '21:05:24.085 JALLANDHAR CB F_5 (MOGA-2 AMRIT TIE) STTS BETWEEN Bad InvRTU
'02-01-2010 '21:05:24.087 JALLANDHAR CB F_6(AMRITSAR BUS-2) STTS BETWEEN Bad InvRTU
'02-01-2010 '21:05:25.204 JALLANDHAR CB F_5 (MOGA-2 AMRIT TIE) STTS CLOSED GOOD InvRTU
'02-01-2010 '21:05:25.311 JALLANDHAR CB F_6(AMRITSAR BUS-2) STTS CLOSED GOOD InvRTU
'02-01-2010 '21:05:31.156 MOGA_ CB F_5 (FTEBD-2 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 '21:05:35.825 MOGA_ CB F_8 (ICT-3 HISAR-2 TIE) STTS OPEN GOOD Valid
'02-01-2010 '21:08:40.315 NUNAMAJRA CB E_10(BHADR-2) STTS CLOSED GOOD Valid
'02-01-2010 '21:09:55.948 NUNAMAJRA CB E_06 STTS CLOSED GOOD Valid
'02-01-2010 '21:11:48.223 NALAGARH CB F_7( NAPTHA-1 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:11:49.235 NALAGARH CB F_8( NAPTHA-1 B/R TIE) STTS OPEN GOOD Valid
'02-01-2010 '21:11:49.254 NAPTHA CB F_L3(NALAG-1) STTS BETWEEN Bad Valid
'02-01-2010 '21:12:14.079 NAPTHA CB F_G2(H02) STTS BETWEEN Bad Valid
'02-01-2010 '21:12:14.089 NAPTHA CB F_G2(H02) STTS INVALID Bad Valid
'02-01-2010 '21:12:41.355 NUNAMAJRA CB E_11(ROTAK-1) STTS CLOSED GOOD Valid
'02-01-2010 '21:14:30.751 NUNAMAJRA CB E_07(DLTBD-1) STTS CLOSED GOOD Valid
'02-01-2010 '21:14:30.785 NUNAMAJRA CB E_07(DLTBD-1) STTS INVALID Bad Valid
'02-01-2010 '21:16:08.307 BHAKRA DAM CB E_23(G7) STTS OPEN GOOD Valid
'02-01-2010 '21:16:57.154 ABDULLAPUR RE F_BR PRT PROTECTION TRIP GOOD InvRTU
'02-01-2010 '21:16:57.215 ABDULLAPUR CB F_10 (BR BUS-1) STTS OPEN GOOD InvRTU
'02-01-2010 '21:16:59.863 ABDULLAPUR CB F_11 (ICT-2 BR) TIE STTS OPEN GOOD InvRTU
'02-01-2010 '21:17:03.328 PANIPATTPS CB E_23(SFDON-2) STTS CLOSED GOOD Valid
'02-01-2010 '21:18:48.955 MOGA_ CB F_5 (FTEBD-2 BUS-2) STTS CLOSED GOOD Valid
'02-01-2010 '21:18:53.654 ABDULLAPUR RE F_BR PRT PROTECTION OK GOOD InvRTU
'02-01-2010 '21:18:53.673 ABDULLAPUR CB F_10 (BR BUS-1) STTS CLOSED GOOD InvRTU
1 of 8
'02-01-2010 '21:18:53.673 ABDULLAPUR CB F_10 (BR BUS-1) STTS CLOSED GOOD InvRTU
'02-01-2010 '21:19:15.997 NALAGARH CB F_7( NAPTHA-1 BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 '21:19:16.134 ABDULLAPUR CB F_11 (ICT-2 BR) TIE STTS CLOSED GOOD InvRTU
'02-01-2010 '21:19:22.038 NALAGARH CB F_8( NAPTHA-1 B/R TIE) STTS CLOSED GOOD Valid
'02-01-2010 '21:19:30.937 FTEBD_PG CB F_1 (MOGA-2 BUS-1) STTS CLOSED BAD QUAL
'02-01-2010 '21:19:30.984 FTEBD_PG CB F_1 (MOGA-2 BUS-1) STTS CLOSED BAD QUAL
'02-01-2010 '21:19:30.984 FTEBD_PG CB F_1 (MOGA-2 BUS-1) STTS CLOSED BAD QUAL
'02-01-2010 '21:19:30.984 FTEBD_PG CB F_1 (MOGA-2 BUS-1) STTS CLOSED BAD QUAL
'02-01-2010 '21:20:02.396 MOGA_ CB F_8 (ICT-3 HISAR-2 TIE) STTS CLOSED GOOD Valid
'02-01-2010 '21:20:25.505 FTEBD_PG CB F_2(MOGA-2 & XFMR-1TIE) STTS CLOSED
'02-01-2010 '21:20:43.732 PANIPATTPS CB E_22(SFDON-1) STTS CLOSED GOOD Valid
'02-01-2010 '21:20:51.000 FTEBD_PG CB F_1 (MOGA-2 BUS-1) STTS CLOSED BAD QUAL
'02-01-2010 '21:22:42.118 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '21:23:15.961 220MUKTSAR CB E_2(GNDTP) STTS CLOSED GOOD Valid
'02-01-2010 '21:24:24.000 FTEBD_PG CB F_1 (MOGA-2 BUS-1) STTS CLOSED BAD QUAL
'02-01-2010 '21:25:45.104 AURAIYA CB E_11(GT2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:25:45.104 AURAIYA CB E_11_G(GT2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:25:53.921 FTEBD_PG ZBR F_FTEBD_MOGA_2 PRT OPEN
'02-01-2010 '21:29:06.000 FTEBD_PG LINE F_FTEBD_HISAR2 PRT OPEN BAD QUAL
'02-01-2010 '21:32:49.000 FTEBD_PG LINE F_FTEBD_HISAR2 PRT OPEN BAD QUAL
'02-01-2010 '21:35:07.831 NARWANA CB E_03(BHUNA) STTS OPEN GOOD Valid
'02-01-2010 '21:35:07.840 FTEBD_PG CB E_06(FTEBD-1) STTS OPEN
'02-01-2010 '21:37:03.000 FTEBD_PG CB F_1 (MOGA-2 BUS-1) STTS CLOSED BAD QUAL
'02-01-2010 '21:40:00.228 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '21:40:00.228 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '21:40:02.277 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '21:40:02.277 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '21:41:32.039 HEERAPURA CB F_2 STTS CLOSED GOOD InvRTU
'02-01-2010 '21:42:36.542 NARWANA CB E_03(BHUNA) STTS CLOSED GOOD Valid
'02-01-2010 '21:44:02.264 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '21:44:02.264 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '21:44:08.287 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '21:44:08.287 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '21:44:09.252 BAMNAULI LINE F_BALLB_BAMNL2 ARB2 AUTO RE B-2 TRIP GOOD Valid
1 of 8
Chapter - 6 _ ANNEXE - 6/I (page 1 of 8)
![Page 191: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/191.jpg)
Sequence of Events for Disturbance at 21.54 hrs of 02nd Jan 2010
'02-01-2010 '21:44:09.255 BAMNAULI CB F_16(B GARH-2 BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 '21:44:09.288 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 '21:44:09.288 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS BETWEEN Bad Valid
'02-01-2010 '21:44:09.492 BALLABGARH CB F_50 FACT MAIN BUS-2 STTS CLOSED GOOD Valid
'02-01-2010 '21:44:09.517 BALLABGARH CB F_28 MAINPURI-2 MAIN BUS STTS OPEN GOOD Valid
'02-01-2010 '21:44:09.518 BALLABGARH CB F_9 ICT-4 MAIN BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 '21:44:09.518 BALLABGARH CB F_25 MAINPURI-1 MAIN BUS STTS OPEN GOOD Valid
'02-01-2010 '21:44:09.526 BALLABGARH CB F_18 GNOIDA MAIN BUS-1 STTS OPEN GOOD Valid
'02-01-2010 '21:44:09.528 BALLABGARH CB F_10 BAMNL-2 MAIN BUS-2 STTS OPEN GOOD Valid
'02-01-2010 '21:44:09.528 BALLABGARH CB F_15 AGRA MAIN BUS-1 STTS OPEN GOOD Valid
'02-01-2010 '21:44:09.528 BALLABGARH CB F_6 ICT-1 MAIN BUS-1 STTS OPEN GOOD Valid
'02-01-2010 '21:44:09.528 BALLABGARH CB F_12 BAMNL-2 MAIN BUS-1 STTS OPEN GOOD Valid
'02-01-2010 '21:44:09.530 BALLABGARH CB F_23 KANPUR TIE STTS OPEN GOOD Valid
'02-01-2010 '21:44:09.536 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP GOOD Valid
'02-01-2010 '21:44:09.536 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 TRIP GOOD Valid
'02-01-2010 '21:44:09.538 BAMNAULI LINE F_BALLB_BAMNL1 PRDT DIST.DIRECT.TRIP GOOD Valid
'02-01-2010 '21:44:09.540 BALLABGARH CB F_3 BAMNL-1 MAIN BUS-1 STTS OPEN GOOD Valid
'02-01-2010 '21:44:09.549 BAMNAULI LINE F_BALLB_BAMNL1 ARB2 AUTO RE B-2 TRIP GOOD Valid
'02-01-2010 '21:44:09.550 BAMNAULI LINE F_BALLB_BAMNL1 ARB1 AUTO RE B-1 TRIP GOOD Valid
'02-01-2010 '21:44:09.550 BAMNAULI LINE F_BALLB_BAMNL2 ARB1 AUTO RE B-1 TRIP GOOD Valid
'02-01-2010 '21:44:09.567 BAMNAULI CB F_14(B GARH-1 BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 '21:44:09.591 BAMNAULI CB F_16(B GARH-2 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:44:09.608 BAMNAULI CB F_13(B GARH-1 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:44:09.705 BALLABGARH CB F_1 BAMNL-1 MAIN BUS-2 STTS OPEN GOOD Valid
'02-01-2010 '21:44:10.225 DWARKA1 CB E_04(BAMNL-1) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:10.270 DWARKA1 CB E_05(BAMNL-2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:10.512 NUNAMAJRA CB E_10(BHADR-2) STTS BETWEEN Bad Valid
'02-01-2010 '21:44:10.655 NARAINA CB E_01(T1) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:10.759 NARAINA CB E_04(T2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:10.905 NAJAFGARH CB E_04(T2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:10.953 NAJAFGARH CB E_09(T4) STTS BETWEEN Bad InvRTU
'02-01-2010 '21:44:10.955 NAJAFGARH CB E_09(T4) STTS INVALID Bad InvRTU
'02-01-2010 '21:44:10.961 MEHRAULI LINE E_MEHRU_VSANT2 PRT PROTECTION TRIP GOOD InvRTU
'02-01-2010 '21:44:11.021 MEHRAULI CB E_10(VSANT-2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:11.033 NAJAFGARH CB E_01(T1) STTS BETWEEN Bad InvRTU
'02-01-2010 '21:44:11.090 NAJAFGARH CB E_06(T3) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:11.112 MEHRAULI CB E_07(BAMNL-1) STTS BETWEEN Bad InvRTU
'02-01-2010 '21:44:11.124 MEHRAULI LINE E_BAMNL_MEHRU2 PRT PROTECTION TRIP GOOD InvRTU
'02-01-2010 '21:44:11.151 NAJAFGARH CB E_01(T1) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:11.168 MEHRAULI CB E_08(BAMNL-2) STTS BETWEEN Bad InvRTU
'02-01-2010 '21:44:11.232 MEHRAULI CB E_07(BAMNL-1) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:11.290 MEHRAULI CB E_08(BAMNL-2) STTS OPEN GOOD InvRTU
2 of 8
'02-01-2010 '21:44:11.290 MEHRAULI CB E_08(BAMNL-2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:11.393 ROHINI CB E_01(BWANA-2) STTS OPEN GOOD Valid
'02-01-2010 '21:44:11.973 NUNAMAJRA CB E_06 STTS BETWEEN Bad Valid
'02-01-2010 '21:44:11.988 NUNAMAJRA CB E_11(ROTAK-1) STTS OPEN GOOD Valid
'02-01-2010 '21:44:11.990 NUNAMAJRA CB E_12(ROTAK-2) STTS OPEN GOOD Valid
'02-01-2010 '21:44:11.992 NUNAMAJRA CB E_09(BHADR-1) STTS OPEN GOOD Valid
'02-01-2010 '21:44:12.433 BAMNAULI LINE F_BALLB_BAMNL2 PRDT DIST.DIRECT.TRIP GOOD Valid
'02-01-2010 '21:44:13.697 BAMNAULI XFMR_P 400/220KV ICT-3 PRG2 MAIN.TRIP.GP-2 GOOD Valid
'02-01-2010 '21:44:13.699 BAMNAULI XFMR_P 400/220KV ICT-3 PRG1 MAIN.TRIP.GP-1 GOOD Valid
'02-01-2010 '21:44:13.725 BAMNAULI CB E_10(T3) STTS OPEN GOOD Valid
'02-01-2010 '21:44:14.974 BAMNAULI LINE F_BALLB_BAMNL2 PRDT DIST.DIRECT.OK GOOD Valid
'02-01-2010 '21:44:15.143 BAMNAULI XFMR_P 400/220KV ICT-4 PRG1 MAIN.TRIP.GP-1 GOOD Valid
'02-01-2010 '21:44:15.172 BAMNAULI CB F_12(ICT-4 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 '21:44:15.172 BAMNAULI CB E_21(T4) STTS OPEN GOOD Valid
'02-01-2010 '21:44:15.429 BAHADURGARH CB F_2(BHIWN-ICT1 TIE) STTS OPEN GOOD Valid
'02-01-2010 '21:44:15.429 BHADR_PG CB F_2(BHIWN-ICT1 TIE) STTS CLOSED
'02-01-2010 '21:44:15.436 BAHADURGARH CB F_1(BHIWN BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:44:15.436 BHADR_PG CB F_1(BHIWN BUS-1) STTS OPEN
'02-01-2010 '21:44:15.442 BAHADURGARH CB F_2(BHIWN-ICT1 TIE) STTS CLOSED GOOD Valid
'02-01-2010 '21:44:15.442 BHADR_PG CB F_2(BHIWN-ICT1 TIE) STTS CLOSED BAD QUAL
'02-01-2010 '21:44:15.444 BAHADURGARH CB F_1(BHIWN BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 '21:44:15.444 BHADR_PG CB F_1(BHIWN BUS-1) STTS OPEN
'02-01-2010 '21:44:15.517 BAHADURGARH CB F_2(BHIWN-ICT1 TIE) STTS CLOSED GOOD Valid
'02-01-2010 '21:44:15.517 BHADR_PG CB F_2(BHIWN-ICT1 TIE) STTS OPEN
'02-01-2010 '21:44:15.884 SHAHBAD CB E_06(JORIA-2) STTS OPEN GOOD Valid
'02-01-2010 '21:44:15.884 SHAHBAD LINE E_JORIA_SHBAD2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:44:16.065 ROHINI XFMR_P EC_T2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:44:16.093 ROHINI CB E_03(T2) STTS OPEN GOOD Valid
'02-01-2010 '21:44:16.115 ROHINI XFMR_P EC_T2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '21:44:16.990 BAWANA CB E_16(SHALI-2) STTS OPEN GOOD Valid
'02-01-2010 '21:44:17.276 ROHINI XFMR_P EC_T1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:44:17.341 ROHINI XFMR_P EC_T1 PRT PROTECTION OK GOOD Valid
'02-01-2010 '21:44:17.362 ROHINI CB E_05(T1) STTS OPEN GOOD Valid
'02-01-2010 '21:44:17.466 PRAGATI CB E_10(PRG_1) STTS OPEN GOOD Valid
2 of 8
Chapter - 6 _ ANNEXE - 6//I (page 2 of 8)
![Page 192: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/192.jpg)
Sequence of Events for Disturbance at 21.54 hrs of 02nd Jan 2010
'02-01-2010 '21:44:17.491 SHALIMARBG XFMR_P EB_T2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:44:17.526 SHALIMARBG CB E_05(T1) STTS OPEN GOOD Valid
'02-01-2010 '21:44:17.539 SHALIMARBG XFMR_P EB_T2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '21:44:19.303 PRAGATI XFMR_P EA_PRSTG PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:44:19.326 PRAGATI CB E_12(PRSTG) STTS OPEN GOOD Valid
'02-01-2010 '21:44:19.571 HISSAR LINE F_BWANA_HISAR PRT PROTECTION TRIP GOOD InvRTU
'02-01-2010 '21:44:19.573 HISSAR CB F_12( BAWANA MAIN BUS-2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:19.634 HISSAR LINE F_BWANA_HISAR PRT PROTECTION OK GOOD InvRTU
'02-01-2010 '21:44:19.717 HISSAR CB F_1T ( ICT-1 BAWANA TIE) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:20.938 ABDULLAPUR LINE F_ABDUL_BWANA2 PRT PROTECTION TRIP GOOD InvRTU
'02-01-2010 '21:44:20.955 ABDULLAPUR CB F_6 (BWANA -2 BUS-2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:20.956 ABDULLAPUR CB F_5 (BWANA-2 NJPC) TIE STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:20.988 ABDULLAPUR LINE F_ABDUL_BWANA1 PRT PROTECTION TRIP GOOD InvRTU
'02-01-2010 '21:44:21.009 ABDULLAPUR CB F_2( BAWANA -1 TIE) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:21.009 ABDULLAPUR CB F_3 (BAWANA-1 BUS-2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:23.342 GEETA COLONY LINE E_GEETA_WAZID2 PRT PROTECTION TRIP GOOD InvRTU
'02-01-2010 '21:44:23.400 GEETA COLONY CB E_06(WAZID-1) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:23.408 GEETA COLONY LINE E_GEETA_WAZID2 PRT PROTECTION OK GOOD InvRTU
'02-01-2010 '21:44:23.676 SOWZIRABAD LINE E_GEETA_WAZID2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:44:23.694 SOWZIRABAD CB E_02(GEETA-2) STTS INVALID Bad Valid
'02-01-2010 '21:44:26.360 KHETRI CB E_02(HISAR) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:28.391 SOWZIRABAD XFMR_P EC_T2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:44:28.409 SOWZIRABAD CB E_9A(T3) STTS OPEN GOOD Valid
'02-01-2010 '21:44:28.857 SOWZIRABAD CB E_05(T1) STTS BETWEEN Bad Valid
'02-01-2010 '21:44:29.680 NARELA CB E_09(T2) STTS OPEN GOOD Valid
'02-01-2010 '21:44:36.419 KHETRI CB E_14(DADRI-1) STTS BETWEEN Bad InvRTU
'02-01-2010 '21:44:36.436 KHETRI CB E_09(DADRI-2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:44:38.488 BAMNAULI LINE E_BAMNL_NAJAG2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:44:38.490 BAMNAULI LINE E_BAMNL_NAJAG1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:44:38.515 BAMNAULI CB E_25(NAJAG-1) STTS OPEN GOOD Valid
'02-01-2010 '21:44:38.518 BAMNAULI CB E_26(NAJAG-2) STTS OPEN GOOD Valid
'02-01-2010 '21:44:39.275 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:44:39.289 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 PRT OK GOOD Valid
'02-01-2010 '21:44:40.446 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP GOOD Valid
'02-01-2010 '21:44:40.750 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 TRIP GOOD Valid
'02-01-2010 '21:44:43.028 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:44:43.029 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 PRT OK GOOD Valid
'02-01-2010 '21:44:43.428 MANDAULA CB E_04(GOPAL-2) STTS BETWEEN Bad Valid
'02-01-2010 '21:44:44.850 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 TRIP GOOD Valid
'02-01-2010 '21:44:44.850 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP GOOD Valid
'02-01-2010 '21:44:56.595 NARELA CB E_08(T1) STTS OPEN GOOD Valid
'02-01-2010 '21:44:58.175 BAMNAULI LINE F_BALLB_BAMNL2 PRDT DIST.DIRECT.TRIP GOOD Valid
3 of 8
'02-01-2010 '21:44:58.175 BAMNAULI LINE F_BALLB_BAMNL2 PRDT DIST.DIRECT.TRIP GOOD Valid
'02-01-2010 '21:44:59.598 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:45:00.857 BAMNAULI LINE F_BALLB_BAMNL2 PRDT DIST.DIRECT.OK GOOD Valid
'02-01-2010 '21:45:02.475 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP GOOD Valid
'02-01-2010 '21:45:02.995 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:45:04.374 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP GOOD Valid
'02-01-2010 '21:45:05.757 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:45:05.846 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 PRT OK GOOD Valid
'02-01-2010 '21:45:06.429 BAMNAULI CB ICT-4 BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 '21:45:06.525 NARELA CB E_11(T3) STTS OPEN GOOD Valid
'02-01-2010 '21:45:06.843 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP GOOD Valid
'02-01-2010 '21:45:06.939 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 TRIP GOOD Valid
'02-01-2010 '21:45:07.545 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:45:07.611 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 PRT OK GOOD Valid
'02-01-2010 '21:45:08.027 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 TRIP GOOD Valid
'02-01-2010 '21:45:08.033 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP GOOD Valid
'02-01-2010 '21:45:09.184 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:45:12.352 BAMNAULI CB ICT-4 BUS-1 STTS OPEN GOOD Valid
'02-01-2010 '21:45:13.275 BAMNAULI LINE F_BALLB_BAMNL2 PRDT DIST.DIRECT.TRIP GOOD Valid
'02-01-2010 '21:45:13.732 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP GOOD Valid
'02-01-2010 '21:45:14.291 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:45:14.512 BAMNAULI LINE F_BALLB_BAMNL2 PRDT DIST.DIRECT.OK GOOD Valid
'02-01-2010 '21:45:14.672 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP GOOD Valid
'02-01-2010 '21:45:15.090 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:45:15.449 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP Bad Valid
'02-01-2010 '21:45:18.869 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 PRT OK GOOD Valid
'02-01-2010 '21:45:19.237 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 TRIP GOOD Valid
'02-01-2010 '21:45:22.322 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 PRT OK GOOD Valid
'02-01-2010 '21:45:23.649 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 TRIP GOOD Valid
'02-01-2010 '21:45:24.587 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 PRT OK GOOD Valid
'02-01-2010 '21:45:25.074 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 TRIP GOOD Valid
'02-01-2010 '21:45:25.792 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 PRT OK GOOD Valid
'02-01-2010 '21:45:26.873 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 TRIP GOOD Valid
'02-01-2010 '21:45:27.971 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 PRT OK GOOD Valid
3 of 8
Chapter - 6 _ ANNEXE - 6//I (page 3 of 8)
![Page 193: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/193.jpg)
Sequence of Events for Disturbance at 21.54 hrs of 02nd Jan 2010
'02-01-2010 '21:45:30.106 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 TRIP GOOD Valid
'02-01-2010 '21:45:30.209 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '21:45:30.209 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '21:45:30.480 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 PRT OK GOOD Valid
'02-01-2010 '21:45:30.598 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 TRIP GOOD Valid
'02-01-2010 '21:45:34.287 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '21:45:34.287 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '21:45:34.352 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:45:34.920 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP GOOD Valid
'02-01-2010 '21:45:35.614 DADRI-GAS CB E_05_G(ST1) STTS OPEN GOOD Valid
'02-01-2010 '21:45:36.582 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:45:36.647 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 PRT OK GOOD Valid
'02-01-2010 '21:45:37.508 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 TRIP GOOD Valid
'02-01-2010 '21:45:39.703 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP GOOD Valid
'02-01-2010 '21:45:39.887 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:45:40.936 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP GOOD Valid
'02-01-2010 '21:45:41.745 BAMNAULI LINE F_BALLB_BAMNL2 PRDT DIST.DIRECT.TRIP GOOD Valid
'02-01-2010 '21:45:42.059 BAMNAULI LINE F_BALLB_BAMNL2 PRDT DIST.DIRECT.OK GOOD Valid
'02-01-2010 '21:45:42.413 BAMNAULI LINE F_BALLB_BAMNL2 PRDT DIST.DIRECT.TRIP GOOD Valid
'02-01-2010 '21:45:42.661 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:45:42.702 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 PRT OK GOOD Valid
'02-01-2010 '21:45:44.137 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 TRIP GOOD Valid
'02-01-2010 '21:45:44.141 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP GOOD Valid
'02-01-2010 '21:45:44.467 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:45:44.471 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 PRT OK GOOD Valid
'02-01-2010 '21:45:46.457 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 TRIP GOOD Valid
'02-01-2010 '21:45:46.462 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP GOOD Valid
'02-01-2010 '21:45:46.891 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 PRT OK GOOD Valid
'02-01-2010 '21:45:46.897 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:45:48.552 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 TRIP GOOD Valid
'02-01-2010 '21:45:48.552 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 TRIP GOOD Valid
'02-01-2010 '21:45:49.189 BAMNAULI LINE F_BALLB_BAMNL2 PRM2 MAIN-2 PRT OK GOOD Valid
'02-01-2010 '21:45:49.212 BAMNAULI LINE F_BALLB_BAMNL2 PRM1 MAIN-1 PRT OK GOOD Valid
'02-01-2010 '21:45:52.002 SOWZIRABAD CB E_01(GEETA-1) STTS OPEN GOOD Valid
'02-01-2010 '21:45:52.229 PANIPATTPS CB E_3X(U1) STTS BETWEEN Bad Valid
'02-01-2010 '21:45:54.390 BAMNAULI LINE F_BALLB_BAMNL2 PRDT DIST.DIRECT.OK GOOD Valid
'02-01-2010 '21:46:44.167 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '21:46:44.167 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '21:46:46.267 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '21:46:46.267 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '21:48:55.185 HISSAR CB F_12( BAWANA MAIN BUS-2) STTS CLOSED GOOD InvRTU
'02-01-2010 '21:49:04.719 HISSAR CB F_1T ( ICT-1 BAWANA TIE) STTS CLOSED GOOD InvRTU
4 of 8
'02-01-2010 '21:49:04.719 HISSAR CB F_1T ( ICT-1 BAWANA TIE) STTS CLOSED GOOD InvRTU
'02-01-2010 '21:49:20.253 BAWANA CB F_11(HISAR BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 '21:49:20.257 HISSAR CB F_12( BAWANA MAIN BUS-2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:49:20.414 HISSAR CB F_1T ( ICT-1 BAWANA TIE) STTS OPEN GOOD InvRTU
'02-01-2010 '21:49:21.380 BAWANA CB F_11(HISAR BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 '21:49:21.414 HISSAR CB F_12( BAWANA MAIN BUS-2) STTS CLOSED GOOD InvRTU
'02-01-2010 '21:49:21.446 HISSAR CB F_12( BAWANA MAIN BUS-2) STTS BETWEEN Bad InvRTU
'02-01-2010 '21:49:21.472 HISSAR LINE F_BWANA_HISAR PRT PROTECTION TRIP GOOD InvRTU
'02-01-2010 '21:49:21.537 BAWANA CB F_11(HISAR BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:49:21.539 HISSAR LINE F_BWANA_HISAR PRT PROTECTION OK GOOD InvRTU
'02-01-2010 '21:49:23.864 HISSAR CB F_12( BAWANA MAIN BUS-2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:51:04.109 LUCKNOW CB F_16(BRELY-2 BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 '21:51:04.109 LUCKNOW CB F_16(BRELY-2 BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 '21:51:04.110 LUCKNOW CB F_17(BRELY-2 & BALIA-2 T STTS CLOSED GOOD Valid
'02-01-2010 '21:51:04.110 LUCKNOW CB F_16(BRELY-2 BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 '21:51:04.110 LUCKNOW CB F_17(BRELY-2 & BALIA-2 T STTS CLOSED GOOD Valid
'02-01-2010 '21:51:04.110 LUCKNOW CB F_16(BRELY-2 BUS-1) STTS CLOSED GOOD Valid
'02-01-2010 '21:51:04.111 LUCKNOW CB F_17(BRELY-2 & BALIA-2 T STTS CLOSED GOOD Valid
'02-01-2010 '21:51:04.111 LUCKNOW CB F_17(BRELY-2 & BALIA-2 T STTS CLOSED GOOD Valid
'02-01-2010 '21:51:05.404 NUNAMAJRA CB E_10(BHADR-2) STTS CLOSED GOOD Valid
'02-01-2010 '21:51:42.929 BALLABGARH CB E_03(DADRI) STTS OPEN GOOD Valid
'02-01-2010 '21:51:43.019 DADRI CB E_06(BLBGH) STTS BETWEEN Bad Valid
'02-01-2010 '21:52:08.684 ABDULLAPUR CB F_3 (BAWANA-1 BUS-2) STTS CLOSED GOOD InvRTU
'02-01-2010 '21:52:08.707 ABDULLAPUR LINE F_ABDUL_BWANA1 PRT PROTECTION OK GOOD InvRTU
'02-01-2010 '21:53:00.331 DEHAR PS CB E_01(H01) STTS OPEN GOOD Valid
'02-01-2010 '21:53:03.112 GHTP CB E_1(BARNL-1) STTS BETWEEN GOOD Valid
'02-01-2010 '21:53:03.115 GHTP CB E_10(MNSA2-2) STTS BETWEEN GOOD Valid
'02-01-2010 '21:53:03.116 GHTP CB E_8(GNDTP-2) STTS BETWEEN GOOD Valid
'02-01-2010 '21:53:03.724 GHTP CB E_6(T02) STTS BETWEEN GOOD Valid
'02-01-2010 '21:53:26.482 FTEBD_PG LINE F_FTEBD_HISAR2 PRT OPEN
'02-01-2010 '21:53:26.482 FTEBD_PG LINE F_FTEBD_HISAR2 PRT OPEN
'02-01-2010 '21:53:26.482 FTEBD_PG LINE F_FTEBD_HISAR2 PRT OPEN
'02-01-2010 '21:53:30.674 GEETA COLONY CB E_05(WAZID-2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:53:31.448 SHALIMARBG CB E_05(T1) STTS CLOSED GOOD Valid
4 of 8
Chapter - 6 _ ANNEXE - 6//I (page 4 of 8)
![Page 194: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/194.jpg)
Sequence of Events for Disturbance at 21.54 hrs of 02nd Jan 2010
'02-01-2010 '21:53:39.095 SAMAYUR CB E_07(DADRI) STTS OPEN GOOD Valid
'02-01-2010 '21:53:39.153 DADRI CB E_07(SMYUR) STTS OPEN GOOD Valid
'02-01-2010 '21:53:39.221 DADRI LINE E_DADRI_SMYUR PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:53:39.541 DADRI LINE E_DADRI_SMYUR PRT PROTECTION OK GOOD Valid
'02-01-2010 '21:53:39.892 DADRI LINE E_DADRI_SMYUR PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:53:40.204 DADRI LINE E_DADRI_SMYUR PRT PROTECTION OK GOOD Valid
'02-01-2010 '21:53:40.557 DADRI LINE E_DADRI_SMYUR PRT PROTECTION TRIP Bad Valid
'02-01-2010 '21:53:50.458 DADRI LINE E_DADRI_SMYUR PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:53:58.575 PANIPAT CB F_3(D_THM-1 &ICT-2 TIE) STTS BETWEEN Bad Valid
'02-01-2010 '21:53:58.582 DADRI (TH) CB (F_11)MURADNAGER-1 PANIP STTS OPEN GOOD Valid
'02-01-2010 '21:53:58.582 DADRI (TH) CB (F_12)PANIPAT BUS-1 STTS BETWEEN Bad Valid
'02-01-2010 '21:53:58.642 PANIPAT CB F_4(D_THM-1 BUS-1) STTS INVALID Bad Valid
'02-01-2010 '21:53:59.797 DELHI (R.R) CB E_01(NAREL-1) STTS OPEN GOOD Valid
'02-01-2010 '21:53:59.845 NARELA CB E_07(PANPT-3) STTS OPEN GOOD Valid
'02-01-2010 '21:53:59.944 PANIPAT CB F_3(D_THM-1 &ICT-2 TIE) STTS OPEN GOOD Valid
'02-01-2010 '21:54:00.647 BAWANA CB F_16(ABDUL-1 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 '21:54:00.649 BAWANA CB F_15(ABDUL-1 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:54:00.709 DADRI (TH) CB (F_12)PANIPAT BUS-1 STTS OPEN GOOD Valid
'02-01-2010 '21:54:00.748 MALERKOTLA CB F_3 DADRI MAIN BUS-2 STTS OPEN GOOD Valid
'02-01-2010 '21:54:00.765 MALERKOTLA CB F_2 DADRI ICT-1 TIE STTS OPEN GOOD Valid
'02-01-2010 '21:54:00.985 DADRI CB E_11(MHIND-1) STTS BETWEEN Bad Valid
'02-01-2010 '21:54:00.987 DADRI CB E_08(T2) STTS OPEN GOOD Valid
'02-01-2010 '21:54:00.992 DADRI CB E_12(RWARI) STTS OPEN GOOD Valid
'02-01-2010 '21:54:01.252 AURAIYA CB (F_7)AGRA MAIN BUS-1 STTS INVALID Bad InvRTU
'02-01-2010 '21:54:01.262 AURAIYA CB (F_8)AGRA TIE STTS INVALID Bad InvRTU
'02-01-2010 '21:54:01.394 AGRA CB F_6 (400KV AURAIYA-1 BUS STTS OPEN GOOD InvRTU
'02-01-2010 '21:54:01.397 AGRA CB F_4 AURAIYA-1 MAIN BUS-1 STTS OPEN GOOD InvRTU
'02-01-2010 '21:54:02.271 ABDULLAPUR CB F_3 (BAWANA-1 BUS-2) STTS BETWEEN Bad InvRTU
'02-01-2010 '21:54:04.145 BRELY_PG CB F_15(LKNOW2 BUS-2) STTS OPEN
'02-01-2010 '21:54:04.156 BRELY_PG CB F_14(MORA-2&LKNOW-2 TIE) STTS OPEN
'02-01-2010 '21:54:04.156 BRELY_PG CB F_14(MORA-2&LKNOW-2 TIE) STTS OPEN
'02-01-2010 '21:54:04.742 ABDULLAPUR LINE F_ABDUL_BWANA1 PRT PROTECTION TRIP GOOD InvRTU
'02-01-2010 '21:54:04.766 ABDULLAPUR CB F_3 (BAWANA-1 BUS-2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:54:04.894 PANIPATTPS CB E_25(U5) STTS OPEN GOOD Valid
'02-01-2010 '21:54:05.110 URI CB F_06 UNIT-G4 STTS OPEN GOOD Valid
'02-01-2010 '21:54:05.761 GORAKHPUR1 CB F_09(GRKPR-2) STTS CLOSED GOOD Valid
'02-01-2010 '21:54:06.275 DEHAR PS CB F_3(PANPT) STTS OPEN GOOD Valid
'02-01-2010 '21:54:06.289 DEHAR PS CB F_4(PANPT) STTS OPEN GOOD Valid
'02-01-2010 '21:54:07.696 SALAL CB E_10(G3) STTS OPEN GOOD Valid
'02-01-2010 '21:54:07.826 SALAL BUS E_B2 LOV LOSS OF VOLT GOOD Valid
'02-01-2010 '21:54:07.990 SALAL BUS E_B1 LOV LOSS OF VOLT GOOD Valid
'02-01-2010 '21:54:08.190 PANIPATTPS CB E_13(U4) STTS OPEN GOOD Valid
5 of 8
'02-01-2010 '21:54:08.190 PANIPATTPS CB E_13(U4) STTS OPEN GOOD Valid
'02-01-2010 '21:54:08.227 PANIPATTPS CB E_06(U2) STTS BETWEEN Bad Valid
'02-01-2010 '21:54:08.260 SRINAGAR BUS F_B2 LOV LOSS OF VOLT GOOD Valid
'02-01-2010 '21:54:08.272 SRINAGAR BUS F_B1 LOV LOSS OF VOLT GOOD Valid
'02-01-2010 '21:54:08.393 KAITHAL CB F_4(HISAR MAIN BUS-1) STTS BETWEEN Bad Valid
'02-01-2010 '21:54:08.438 KAITHAL CB F_5 (HISAR ICT-1 TIE) STTS OPEN GOOD Valid
'02-01-2010 '21:54:08.475 HISSAR BUS E_B2 LOV LOSS OF VOLT GOOD InvRTU
'02-01-2010 '21:54:08.477 HISSAR BUS E_B1 LOV LOSS OF VOLT GOOD InvRTU
'02-01-2010 '21:54:08.578 HISSAR BUS F_B1 LOV LOSS OF VOLT GOOD InvRTU
'02-01-2010 '21:54:09.007 220MUKTSAR LINE E_MKTS2_MOGAN1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:54:09.013 220MUKTSAR CB E_4(MOGAN-1) STTS OPEN GOOD Valid
'02-01-2010 '21:54:09.029 MANSA 220 CB E_2(GHTP_-2) STTS OPEN GOOD Valid
'02-01-2010 '21:54:09.039 GRKPR_PG CB F_16(GRKPR-1 BUS-1) STTS OPEN BAD TIME
'02-01-2010 '21:54:09.071 KAITHAL CB F_1 (NALAGARH-1)MAIN BUS STTS BETWEEN Bad Valid
'02-01-2010 '21:54:09.090 BARNALA CB E_2(GHTP_-1) STTS BETWEEN Bad Valid
'02-01-2010 '21:54:09.114 KAITHAL CB F_2(NALAG-ICT-2 TIE) STTS OPEN GOOD Valid
'02-01-2010 '21:54:09.907 BHAKRA DAM CB E_15(H04) STTS BETWEEN Bad Valid
'02-01-2010 '21:54:10.039 GRKPR_PG CB F_17(GRKPR-1 & LINE-F1 T STTS OPEN BAD TIME
'02-01-2010 '21:54:10.143 DEHAR PS XFMR_P FE_T1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:54:10.175 DEHAR PS CB F_01(T1) STTS OPEN GOOD Valid
'02-01-2010 '21:54:10.180 PATIALA CB F_4(HISAR BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:54:10.187 PATIALA CB F_5 (HISAR ICT-1 TIE) STTS OPEN GOOD Valid
'02-01-2010 '21:54:10.194 DEHAR PS CB E_07(T1) STTS OPEN GOOD Valid
'02-01-2010 '21:54:10.237 BHAKRA DAM CB E_35(G6) STTS OPEN GOOD Valid
'02-01-2010 '21:54:10.338 BHAKRA DAM LINE E_BHAKR_GANGL4 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:54:10.370 BHAKRA DAM CB E_26(GANGL-4) STTS BETWEEN Bad Valid
'02-01-2010 '21:54:10.424 BHAKRA DAM CB E_33(G10) STTS BETWEEN Bad Valid
'02-01-2010 '21:54:10.530 BHAKRA DAM LINE E_BHAKR_MHLPR2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:54:10.540 GORAYA LINE E_GORAY_JMSHR PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:54:10.568 GORAYA CB E_51(JMSHR) STTS OPEN GOOD Valid
'02-01-2010 '21:54:10.573 BHAKRA DAM CB E_29(MHLPR-1) STTS OPEN GOOD Valid
'02-01-2010 '21:54:10.578 MISS GANGUWAL CB E_12(BHAKR-5) STTS OPEN GOOD Valid
'02-01-2010 '21:54:10.620 GORAYA LINE E_GORAY_JMSHR PRT PROTECTION OK GOOD Valid
'02-01-2010 '21:54:10.672 JALANDHAR CB E_12(JAMAL-2) STTS OPEN GOOD Valid
5 of 8
Chapter - 6 _ ANNEXE - 6//I (page 5 of 8)
![Page 195: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/195.jpg)
Sequence of Events for Disturbance at 21.54 hrs of 02nd Jan 2010
'02-01-2010 '21:54:10.694 JALANDHAR CB E_11(JAMAL-1) STTS OPEN GOOD Valid
'02-01-2010 '21:54:10.732 JAMALPUR CB E_03(BHAKR-2) STTS OPEN GOOD Valid
'02-01-2010 '21:54:10.740 GORAYA LINE E_GGSTP_GORAY PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:54:10.744 JAMALPUR CB E_01(SNGRU-2) STTS BETWEEN Bad Valid
'02-01-2010 '21:54:10.754 SANGRUR CB E_01(JAMAL-1) STTS OPEN GOOD Valid
'02-01-2010 '21:54:10.764 GORAYA CB E_50(GGSTP) STTS OPEN GOOD Valid
'02-01-2010 '21:54:10.791 GORAYA LINE E_GGSTP_GORAY PRT PROTECTION OK GOOD Valid
'02-01-2010 '21:54:10.819 BARNALA CB E_1(SNGRU) STTS OPEN GOOD Valid
'02-01-2010 '21:54:10.824 JAMALPUR CB E_04(BHAKR-1) STTS OPEN GOOD Valid
'02-01-2010 '21:54:10.824 HISSAR CB E_08(SNGRU-2) STTS BETWEEN Bad Valid
'02-01-2010 '21:54:10.879 BHAKRA DAM CB E_33(G10) STTS OPEN GOOD Valid
'02-01-2010 '21:54:10.889 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:54:11.048 GRKPR_PG CB F_16(GRKPR-1 BUS-1) STTS OPEN BAD TIME
'02-01-2010 '21:54:11.174 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '21:54:11.339 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:54:11.621 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION OK GOOD Valid
'02-01-2010 '21:54:11.787 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION TRIP Bad Valid
'02-01-2010 '21:54:11.817 JAMALPUR CB E_01(SNGRU-2) STTS OPEN GOOD Valid
'02-01-2010 '21:54:12.048 GRKPR_PG CB F_17(GRKPR-1 & LINE-F1 T STTS OPEN BAD TIME
'02-01-2010 '21:54:12.162 CHAMERA II CB F_03(CHM_1- ) STTS BETWEEN Bad Valid
'02-01-2010 '21:54:12.162 CHAMERA II CB F_07(KISHN) STTS BETWEEN Bad Valid
'02-01-2010 '21:54:12.570 HISSAR CB E_08(SNGRU-2) STTS OPEN GOOD Valid
'02-01-2010 '21:54:13.153 GRKPR_PG CB F_1(MUZAF-1 BUS-1) STTS OPEN BAD TIME
'02-01-2010 '21:54:14.573 KNKRL_PG CB F_4 RAPPC-2 BUS-1 STTS OPEN
'02-01-2010 '21:54:14.586 KNKRL_PG CB F_4 RAPPC-2 BUS-1 STTS OPEN
'02-01-2010 '21:54:14.590 KNKRL_PG CB F_8 RAPPC-1 & XFMR-1 TIE STTS OPEN
'02-01-2010 '21:54:14.591 KNKRL_PG CB F_7 RAPPC-1 BUS-1 STTS OPEN
'02-01-2010 '21:54:14.605 KNKRL_PG CB F_8 RAPPC-1 & XFMR-1 TIE STTS OPEN
'02-01-2010 '21:54:14.606 KNKRL_PG CB F_7 RAPPC-1 BUS-1 STTS OPEN
'02-01-2010 '21:54:17.156 GRKPR_PG CB F_2(MUZAF-1 BUS-2) STTS OPEN BAD TIME
'02-01-2010 '21:54:18.164 GRKPR_PG CB F_1(MUZAF-1 BUS-1) STTS OPEN BAD TIME
'02-01-2010 '21:54:19.165 GRKPR_PG CB F_2(MUZAF-1 BUS-2) STTS OPEN BAD TIME
'02-01-2010 '21:54:21.091 GRKPR_PG CB (F_54) MUZ2 TCSC STTS CLOSED BAD TIME
'02-01-2010 '21:54:22.129 GRKPR_PG CB (F_54) MUZ2 TCSC STTS OPEN BAD TIME
'02-01-2010 '21:54:23.505 GRKPR_PG CB (F_52) MUZ2 FSC STTS CLOSED BAD TIME
'02-01-2010 '21:54:24.543 GRKPR_PG CB (F_52) MUZ2 FSC STTS OPEN BAD TIME
'02-01-2010 '21:54:28.786 BAWANA CB F_19(ABDUL-2 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 '21:54:29.000 FTEBD_PG LINE F_FTEBD_HISAR2 PRT OPEN BAD QUAL
'02-01-2010 '21:54:34.269 BAWANA CB F_18(ABDUL-2 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:54:44.000 BRELY_PG CB F_14(MORA-2&LKNOW-2 TIE) STTS OPEN BAD QUAL
'02-01-2010 '21:54:46.167 HISSAR LINE E_HISAR_SNGRU2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:54:48.000 FTEBD_PG ZBR F_FTEBD_MOGA_2 PRT OPEN BAD QUAL
6 of 8
'02-01-2010 '21:54:48.000 FTEBD_PG ZBR F_FTEBD_MOGA_2 PRT OPEN BAD QUAL
'02-01-2010 '21:54:49.000 BRELY_PG CB F_14(MORA-2&LKNOW-2 TIE) STTS OPEN BAD QUAL
'02-01-2010 '21:54:49.308 BHAKRA DAM CB E_32(JAMAL-1) STTS OPEN GOOD Valid
'02-01-2010 '21:54:57.952 BHAKRA DAM CB E_28(JAMAL-2) STTS OPEN GOOD Valid
'02-01-2010 '21:55:04.202 PANKI (T) CB E_U2(U02) STTS BETWEEN Bad Valid
'02-01-2010 '21:55:04.202 PANKI (T) CB E_U1(U01) STTS BETWEEN Bad Valid
'02-01-2010 '21:55:10.277 PANKI (T) CB E_U2(U02) STTS CLOSED GOOD Valid
'02-01-2010 '21:55:10.277 PANKI (T) CB E_U1(U01) STTS CLOSED GOOD Valid
'02-01-2010 '21:55:29.818 FTEBD_PG CB F_2(MOGA-2 & XFMR-1TIE) STTS OPEN
'02-01-2010 '21:55:29.877 MOGA_ CB F_5 (FTEBD-2 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 '21:55:29.879 MOGA_ CB F_8 (ICT-3 HISAR-2 TIE) STTS OPEN GOOD Valid
'02-01-2010 '21:55:39.436 BHAKRA DAM CB E_22(GANGL-5) STTS OPEN GOOD Valid
'02-01-2010 '21:55:41.705 JAMALPUR CB E_16(DHNDR-2) STTS OPEN GOOD Valid
'02-01-2010 '21:55:46.496 JAMALPUR CB E_15(T6) STTS OPEN GOOD Valid
'02-01-2010 '21:55:48.781 SAHNEWAL CB E_05(GGSTP-2) STTS OPEN GOOD Valid
'02-01-2010 '21:55:50.498 JAMALPUR CB E_14(T5) STTS BETWEEN Bad Valid
'02-01-2010 '21:55:52.810 MURADNGR-1 CB F_01(MUZA1) STTS OPEN GOOD Valid
'02-01-2010 '21:55:53.376 JAMALPUR CB E_13(T4) STTS OPEN GOOD Valid
'02-01-2010 '21:55:59.090 SAHNEWAL CB E_06(GGSTP-1) STTS OPEN GOOD Valid
'02-01-2010 '21:55:59.758 DHANDARI CB E_50(T5) STTS INVALID Bad Valid
'02-01-2010 '21:56:00.092 JAMALPUR CB E_11(GANGL-1) STTS OPEN GOOD Valid
'02-01-2010 '21:56:04.522 BHAKRA DAM CB E_24(MHLPR-2) STTS OPEN GOOD Valid
'02-01-2010 '21:56:05.384 FTEBD_PG CB F_4 (HISAR-2 BUS-1) STTS OPEN
'02-01-2010 '21:56:14.417 FTEBD_PG CB F_5 (HISAR-2 & XFMR-2TIE STTS OPEN
'02-01-2010 '21:56:15.996 PANIPATTPS CB E_15(SONEP-1) STTS BETWEEN Bad Valid
'02-01-2010 '21:56:17.557 BHAKRA DAM CB E_25 STTS OPEN GOOD Valid
'02-01-2010 '21:56:18.287 UNNAO CB F_14 STTS CLOSED GOOD Valid
'02-01-2010 '21:56:22.297 JAMALPUR CB E_12(GANGL-2) STTS OPEN GOOD Valid
'02-01-2010 '21:56:36.096 PATIALA CB F_9 (ICT-2 BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 '21:56:37.042 FTEBD_PG CB E_02(T2) STTS OPEN
'02-01-2010 '21:56:37.886 PATIALA CB F_9 (ICT-2 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 '21:56:39.623 PATIALA CB E_02(T2) STTS OPEN GOOD Valid
'02-01-2010 '21:56:39.628 PATIALA CB F_8 ( LUDHIANA-1&ICT-2 T STTS OPEN GOOD Valid
'02-01-2010 '21:56:42.097 BAWANA CB F_7(BHADURG H BUS-1) STTS OPEN GOOD Valid
6 of 8
Chapter - 6 _ ANNEXE - 6//I (page 6 of 8)
![Page 196: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/196.jpg)
Sequence of Events for Disturbance at 21.54 hrs of 02nd Jan 2010
'02-01-2010 '21:56:44.727 FTEBD_PG CB E_03(T1) STTS OPEN
'02-01-2010 '21:56:46.118 PATIALA CB F_9(ICT-1 MAIN BUS-2) STTS OPEN GOOD Valid
'02-01-2010 '21:56:48.197 HISSAR CB F_32 ( PATIALA BUS-2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:56:48.227 HISSAR CB F_3T (MOGA-1 PATIALA TIE STTS OPEN GOOD InvRTU
'02-01-2010 '21:56:54.851 BASSI CB F_3 BUS REACTOR MAIN BUS STTS CLOSED GOOD Valid
'02-01-2010 '21:57:00.307 FTEBD_PG CB E_07(FTEBD-2) STTS OPEN
'02-01-2010 '21:57:00.534 SAHNEWAL CB E_03(T1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:05.666 NUNAMAJRA CB E_09(BHADR-1) STTS CLOSED GOOD Valid
'02-01-2010 '21:57:05.717 NUNAMAJRA CB E_09(BHADR-1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:08.789 PATIALA CB F_1 (NALAGARH-2 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:08.920 JAMALPUR CB E_02(SNGRU-1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:09.437 FTEBD_PG CB E_08(BHUNA) STTS OPEN
'02-01-2010 '21:57:11.062 PATIALA CB F_2(NALAG-MALER K TIE) STTS OPEN GOOD Valid
'02-01-2010 '21:57:12.759 BAWANA CB F_21(MANDU-1 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:13.423 PATIALA CB F_3 (MALER K BUS-2) STTS OPEN GOOD Valid
'02-01-2010 '21:57:15.007 BAWANA CB F_22(MANDU-1 BUS-2) STTS BETWEEN Bad Valid
'02-01-2010 '21:57:15.082 MANDAULA CB F_6 (BAWANA MAIN BUS-2) STTS OPEN GOOD Valid
'02-01-2010 '21:57:15.086 MANDAULA CB F_4( BAWANA MAIN BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:17.563 FTEBD_PG CB E_09(SIRSA) STTS OPEN
'02-01-2010 '21:57:17.751 BAWANA CB F_25(MANDU-2 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 '21:57:18.598 BAWANA CB F_24(MANDU-2 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:18.668 MANDAULA CB F_7( BAWANA-2 MAIN BUS-1 STTS OPEN GOOD Valid
'02-01-2010 '21:57:18.672 MANDAULA CB F_9( BAWANA-2 MAIN BUS-2 STTS OPEN GOOD Valid
'02-01-2010 '21:57:18.824 BAWANA CB E_02(NAJAG-2) STTS OPEN GOOD Valid
'02-01-2010 '21:57:18.825 BAWANA LINE E_BWANA_NAJAG2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:57:18.829 BAWANA LINE E_BWANA_DSIDC2 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:57:18.830 BAWANA LINE E_BWANA_KANJT1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:57:18.833 BAWANA LINE E_BWANA_DSIDC1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:57:18.840 BAWANA CB E_17(DSIDC-1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:18.840 BAMNAULI LINE E_BAMNL_NRINA1 PRT PROTECTION TRIP GOOD Valid
'02-01-2010 '21:57:18.841 BAWANA CB E_01(KANJT-1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:18.842 BAWANA CB E_18(DSIDC-2) STTS OPEN GOOD Valid
'02-01-2010 '21:57:18.866 BAMNAULI CB E_05(NRINA-1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:18.884 BAMNAULI CB E_06(NRINA-2) STTS OPEN GOOD Valid
'02-01-2010 '21:57:20.746 PATIALA CB E_01(T1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:30.112 PATIALA CB E_08(ABLWL-2) STTS OPEN GOOD Valid
'02-01-2010 '21:57:32.219 PATIALA CB E_06(ABLWL) STTS OPEN GOOD Valid
'02-01-2010 '21:57:34.082 SRINAGAR CB E_09(T1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:34.086 SRINAGAR CB F_08(T1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:35.826 PATIALA CB E_09(BGARH) STTS OPEN GOOD Valid
'02-01-2010 '21:57:36.704 SRINAGAR CB F_L2(URI_R-2) STTS OPEN GOOD Valid
'02-01-2010 '21:57:36.822 FTEBD_PG CB F_3 (XFMR-1 BUS-2) STTS OPEN
7 of 8
'02-01-2010 '21:57:36.822 FTEBD_PG CB F_3 (XFMR-1 BUS-2) STTS OPEN
'02-01-2010 '21:57:38.826 PATIALA CB E_07(RAJPR) STTS OPEN GOOD Valid
'02-01-2010 '21:57:40.100 SRINAGAR CB F_L1(URI_R-1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:44.715 FTEBD_PG CB F_6 (XFMR-2 BUS-2) STTS OPEN
'02-01-2010 '21:57:44.765 JALLANDHAR CB F_5 (MOGA-2 AMRIT TIE) STTS OPEN GOOD InvRTU
'02-01-2010 '21:57:44.774 JALLANDHAR CB F_6(AMRITSAR BUS-2) STTS OPEN GOOD InvRTU
'02-01-2010 '21:57:47.049 KISHENPUR CB F_6 WAGOORA-1 BUS1 STTS OPEN GOOD InvRTU
'02-01-2010 '21:57:47.078 KISHENPUR CB F_5 ICT-1 WAGORA-1 TIE STTS OPEN GOOD InvRTU
'02-01-2010 '21:57:47.235 SAHNEWAL CB E_02(LALTN-1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:47.527 SRINAGAR CB F_L3(KISHN-1) STTS BETWEEN Bad Valid
'02-01-2010 '21:57:48.559 JALANDHAR CB E_7(DASYA-2) STTS OPEN GOOD Valid
'02-01-2010 '21:57:48.676 SRINAGAR CB E_02(T2) STTS OPEN GOOD Valid
'02-01-2010 '21:57:48.696 SRINAGAR CB F_03(T2) STTS OPEN GOOD Valid
'02-01-2010 '21:57:51.668 KISHENPUR CB F_3(WAGOORA-2 BUS-1) STTS BETWEEN Bad InvRTU
'02-01-2010 '21:57:51.710 KISHENPUR CB F_2 (CHM-2 & WAGO-2 TIE) STTS INVALID Bad InvRTU
'02-01-2010 '21:57:51.988 SRINAGAR CB F_L4(KISHN-2) STTS BETWEEN Bad Valid
'02-01-2010 '21:57:52.146 SRINAGAR CB F_L4(KISHN-2) STTS OPEN GOOD Valid
'02-01-2010 '21:57:52.930 SRINAGAR CB E_L2(PAMPO-1) STTS OPEN GOOD Valid
'02-01-2010 '21:57:56.473 SRINAGAR CB E_L3(PAMPO-2) STTS OPEN GOOD Valid
'02-01-2010 '21:58:00.095 SRINAGAR CB E_L1(ZNKOT-1) STTS OPEN GOOD Valid
'02-01-2010 '21:58:04.364 SRINAGAR CB E_L4(ZNKOT-2) STTS OPEN GOOD Valid
'02-01-2010 '21:58:10.397 JAGADHRI CB E_2 STTS OPEN GOOD Valid
'02-01-2010 '21:58:20.353 JAGADHRI CB E_1 STTS BETWEEN Bad Valid
'02-01-2010 '21:58:25.641 JAGADHRI CB E_6 STTS BETWEEN Bad Valid
'02-01-2010 '21:58:26.660 JAGADHRI CB E_5 STTS BETWEEN Bad Valid
'02-01-2010 '21:58:34.306 JAGADHRI CB E_4 STTS OPEN GOOD Valid
'02-01-2010 '21:58:35.551 DEHAR PS CB E_05(GANGL-2) STTS BETWEEN Bad Valid
'02-01-2010 '21:58:37.806 DEHAR PS CB E_03(GANGL-1) STTS OPEN GOOD Valid
'02-01-2010 '21:58:39.023 MOGA_ CB F_9 (ICT-1 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:58:40.323 JAMALPUR CB E_05(JLNDR-1) STTS BETWEEN Bad Valid
'02-01-2010 '21:58:41.681 DEHAR PS CB E_02(T2) STTS OPEN GOOD Valid
'02-01-2010 '21:58:43.154 HISSAR CB E_01(T1) STTS BETWEEN Bad Valid
'02-01-2010 '21:58:43.392 JAMALPUR CB E_06(JLNDR-2) STTS OPEN GOOD Valid
'02-01-2010 '21:58:46.009 HISSAR CB E_02(T2) STTS OPEN GOOD Valid
7 of 8
Chapter - 6 _ ANNEXE - 6//I (page 7 of 8)
![Page 197: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/197.jpg)
Sequence of Events for Disturbance at 21.54 hrs of 02nd Jan 2010
'02-01-2010 '21:58:48.668 MOGA_ CB F_13 (KISHNPUR-1 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:58:52.716 JAMALPUR CB E_08(T1) STTS OPEN GOOD Valid
'02-01-2010 '21:58:54.085 PIPLI CB E_01(JGDRI) STTS BETWEEN Bad Valid
'02-01-2010 '21:58:55.201 DEHAR PS CB F_8(BHIWN) STTS OPEN GOOD Valid
'02-01-2010 '21:58:56.432 DEHAR PS CB F_7(BHIWN) STTS OPEN GOOD Valid
'02-01-2010 '21:58:56.718 PIPLI CB E_02(PANPT) STTS OPEN GOOD Valid
'02-01-2010 '21:58:59.830 KISHENPUR CB F_13 MOGA-1 MAIN BUS-1 STTS BETWEEN Bad InvRTU
'02-01-2010 '21:58:59.836 KISHENPUR CB F_13 MOGA-1 MAIN BUS-1 STTS OPEN GOOD InvRTU
'02-01-2010 '21:58:59.841 KISHENPUR CB F_14 MOGA-1 TIE STTS OPEN GOOD InvRTU
'02-01-2010 '21:59:00.418 MOGA_ CB F_14( KISHENPUR-1 & RCTR STTS OPEN GOOD Valid
'02-01-2010 '21:59:01.159 JAMALPUR CB E_09(T2) STTS OPEN GOOD Valid
'02-01-2010 '21:59:05.523 HISSAR CB E_09(T3) STTS OPEN GOOD Valid
'02-01-2010 '21:59:07.653 MOGA_ CB F_18 (K NPUR-2 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:59:13.501 KISHENPUR CB F_16 MOGA-2 MAIN BUS-2 STTS OPEN GOOD InvRTU
'02-01-2010 '21:59:13.523 KISHENPUR CB F_17 MOGA-2&DULHA-1 TIE STTS OPEN GOOD InvRTU
'02-01-2010 '21:59:14.092 MOGA_ CB F_17 (KISHENPUR-2 TIE) STTS OPEN GOOD Valid
'02-01-2010 '21:59:17.048 MISS GANGUWAL CB E_14(BHAKR-2) STTS OPEN GOOD Valid
'02-01-2010 '21:59:22.013 MISS GANGUWAL CB E_09(T2) STTS OPEN GOOD Valid
'02-01-2010 '21:59:25.062 MISS GANGUWAL CB E_02(DEHAR-2) STTS OPEN GOOD Valid
'02-01-2010 '21:59:28.787 DADRI CB E_15(MHIND-2) STTS OPEN GOOD Valid
'02-01-2010 '21:59:30.114 MOGA_ CB F_10( ICT-2 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 '21:59:30.271 MISS GANGUWAL CB E_13(BHAKR-1) STTS OPEN GOOD Valid
'02-01-2010 '21:59:31.302 DEHAR PS CB E_09(KANGO) STTS OPEN GOOD Valid
'02-01-2010 '21:59:36.446 HEERAPURA CB F_2 STTS OPEN GOOD InvRTU
'02-01-2010 '21:59:38.296 JAMALPUR CB E_10(DHNDR-1) STTS OPEN GOOD Valid
'02-01-2010 '21:59:38.801 MOGA_ CB E_07(MOGAN-3) STTS OPEN GOOD Valid
'02-01-2010 '21:59:39.426 MOGA_ CB F_1 (J DHER-1 BUS-1) STTS OPEN GOOD Valid
'02-01-2010 '21:59:44.756 MOGA_ CB F_3 (JALANDHER-1 &2 TIE) STTS OPEN GOOD Valid
'02-01-2010 '21:59:44.759 JALLANDHAR CB F_3 MOGA-1 BUS-2 STTS OPEN GOOD InvRTU
'02-01-2010 '21:59:44.760 JALLANDHAR CB F_2 CHAMERA-1 MOGA-1 TIE STTS OPEN GOOD InvRTU
'02-01-2010 '21:59:51.918 JALLANDHAR CB F_4 MOGA-2 BUS-1 STTS OPEN GOOD InvRTU
'02-01-2010 '21:59:51.941 MOGA_ CB F_2 (J NDHER-2 BUS-2) STTS OPEN GOOD Valid
'02-01-2010 '21:59:55.556 DADRI CB E_14(BHIWN-4) STTS BETWEEN Bad Valid
'02-01-2010 '21:59:56.287 MISS GANGUWAL CB E_08(T1) STTS OPEN GOOD Valid
8 of 88 of 8
Chapter - 6 _ ANNEXE - 6//I (page 8 of 8)
![Page 198: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/198.jpg)
Page 1
Powergri\Ballabga\Bamnoli-\REL52123.1\10010219.REH Station: Ballabgarh Object: Bamnoli-II 2 JAN 2010 21:43:30.473
[ms]
0
0
500
500
1000
1000
1500
1500
2000
2000
0
R Phase Vtg 500 kV
0
R Phase Amps 20000 A
0
Y Phase Vtg 500 kV
0
Y Phase Amps 20000 A
0
B Phase Vtg 500 kV
0
B Phase Amps 20000 A
0
Nue Vtg 500 kV
0
Neutral Amps 20000 A
LINE-CB-OPN-R
LINE-CB-OPN-YLINE-CB-OPN-B
CAR-RCV-MI
MAIN-1-TRIPA/R-OPTD
A/R-UNSUCCESS
DT-RCV
MAIN2-CAR-RCVMAIN2-TRIP
BFR-OPTD
TIE-CB-OPEN-R
TIE-CB-OPEN-YTIE-CB-OPEN-B
M1-CAR-SEND
MAIN2-PSB
MII-CAR-SENDSTUB-TRIP
FUSE-VTSZ
ZM2-START
ZM3-STARTSOTF-TRIP
Chapter- 6_ EXHIBIT - 6/I (page 1 of 1
I nnA, IVVv ~" , ~ ,
I ~ 10AAAAtDD~Q00A ~mvvyvvmvv
LAAAA hAA'AAA'A\AA, m~ Vqvmmvv ~
I I ~AAA A IAAAAA IAA!A!
'v U v v IUvvvVV JVVVVVV
I I lAAA"AAhAhAIAAI
I~V~V"""V"""VV -
I A IAAAAAA!!!D!D~ ~~vvvmvmvv
![Page 199: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/199.jpg)
Page 1
Powergri\Ballabga\Bamnoli-\REL52123.1\10010220.REH Station: Ballabgarh Object: Bamnoli-II 2 JAN 2010 21:43:33.593
[ms]
0
0
500
500
1000
1000
1500
1500
2000
2000
0
R Phase Vtg 50 kV
0
R Phase Amps 5000 A
0
Y Phase Vtg 50 kV
0
Y Phase Amps 5000 A
0
B Phase Vtg 50 kV
0
B Phase Amps 5000 A
0
Nue Vtg 50 kV
Chapter- 6_ EXHIBIT - 6/I (page 2 of 6)
- I~ ________________ _
- 1 HI~I~H~I+I+IHHHI+I
![Page 200: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/200.jpg)
Page 1
Powergri\Ballabga\Bamnoli-\REL52123.1\10010220.REH Station: Ballabgarh Object: Bamnoli-II 2 JAN 2010 21:43:33.593
[ms]
0
0
500
500
1000
1000
1500
1500
2000
2000
0
Neutral Amps 5000 A
LINE-CB-OPN-RLINE-CB-OPN-Y
LINE-CB-OPN-BCAR-RCV-MI
MAIN-1-TRIPA/R-OPTD
A/R-UNSUCCESSFREQ-RLY-OPTD
DT-RCVMAIN2-CAR-RCV
MAIN2-TRIPB/B-TRIP
BFR-OPTDTIE-CB-OPEN-R
Chapter- 6_ _ EXHIBIT - 6/I (page 3 of 6)
I I I I I
I I I I
![Page 201: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/201.jpg)
Chapter - 6 _ EXHIBIT - 6/I (page 4 of 6)
44. 53.798 B»!NAULI-2 MAIH-2 C\I'l' FUSE
1.44 . 46 .516 B.IJo!NAULI-2 MAlN-2 cV'!' PUS!'.:
BAHNAULI-2 MA.l!H CV'!' PUS!
BAMNAULI-2 MAIN-l cV! rUSE
,,-2:010 21. H, 40. 437 8AMNAULI-2 MArM-t CV1' PUSE
1;1-2010 21.4L27.H9 BAMNAULI-2 CARRIER PRClrBCTION cHZ
. 01-201021.49,12.382 CB 1052 II. PHASB
j Z-Ol-ZOlO 21.44.09.933 BAMNAULI-Z GR-B 3FH PRCtI'E<:TION
I 02-01-201021.44.09.930 BAMNAULI-Z GR-B 3fH PRQPBCTION
02-01-201021.44.09.926 BAMNAULI-2 GR-B 3PH PROTECTION
02-01- 201021.44.09.920 BAMNAULI-Z GR-B 3PH PROTECTION
02 -01-201021.44.09.919 BA.."!NAULI-2 GR-B 3PH PRO'I'BC'rION
I 02-01- Z010 21.44.09.838 Bk"!NAULI-2 DlREC'l' tRIP CHl/2 RECBIVED
, 0'-'-"1-2010 21.44.09.685 BAMNAULI-l DIREC'f ,RIP CHl/ 2 RBCEIVED
i 02 -01-2010 21.44.09.680 BAJllHAULI- l Gb .. 3PH PPJ)'fEC'!'ION
02-01-201021.44.09.680 BAIOO.ULl-l GR-A 3Ft! PR07!:ctION
02 -01-201021. 44. 09 . 618 C8152 OPP.Tlt L/0-2 (OlL/ 5f6/H2)
02-01-2010 21.44.09.6'18 CB 352 y-Phe,!
1 02-01-2010 21.44,09 . 676 CB 352 R-Pha,e
02-01-2010 21.H.09 .675 ClI 352 B-PhHe
- fAILBD
- "'-- "lRl!I.L
- fAILBD
- fAILED
- fAILED
- op en
- TRIPPBD
- NORMAL
- !RIPpeD
- HORI!I.L
- !RIPPBD
- HIGH
- "'" - 'l'iUPPBD
- NORIII.L
- "'" - open
- open
- open
1 02-01-2010 21.44 .09.615 BAMNAULI-l DIRECT TRIP CHl/2 RI!!C!I!IIJ!D - HIGH
: 02 -01-2010 21.44.09.656 BAM.NAULI-1 DIRI!!CT TRIP CHl/2 RECEIVED - LCr.rI I I 02-01-201021.44.09.655 BAM.NAULI-1 DIRECT TRIP CHl/2 ReCEIVED - HlGH
1 02-01-2010 21.44 .09.643 BAMNAULI- l HAlM-1 STAR'r-!\ PH - Lew
02-01-201021.44.09.608 CB 1052 B PHASE - open
02-01-201021. 44.09 .606 CB 1052 B PHASE
02- 01-201021.44.0 9.597 CB 1052 B PHASB
11-2010 21.44.09.596 CB 1052 B PRASE
02-01-2010 21. 44 .09.584 CB 1052 B PHASE
02-01-201021. 44.09.582 CB 1052 B PHASE
02-01-2010 21.44.09.514 BAMNAULI-2 MAIJt-1 CAARIBR SBND
02-01-2010 21.44.09.574 B.OOUIULI-2 MAItH PRDrSC!IOH
02-01-2010 21.44.~9.573 B»!NAULI-2 MAIN-l stAAT-Po PH
02 -01-201021.44.09.572 B..\JI!NAULI-2 MAIM-2 S'l'AAT-R PH
'\ 02-01-2010 21.44.09.572
02-01-201021. 44.09.565
1 02-01-201021.44.09.561
1
02-01-201021. 44 .09.551
02 -01-201021.44.09.540
~01 0-0 1 -02 23:01 :25
BJ.MIiAULI-2 MArM- 2 PP.Ol'BC!ION
CB 1052 B PHA.SB
CBlOS2 6FR
BAMIiAULI- l MAIM-1 START-Po PH
ealS2 TRIP CIRCUIT-II
- open
- close
- open
- close
- "'" -"'-- "'" - "" - NORMAL
- open
- PoESET
- HIGH
- tlORMAL
Page 1
T ..
![Page 202: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/202.jpg)
Chapter - 6 _ EXHIBIT - 6/I (page 5 of 6)
~~ ______________ ~MM~NA~U=LI~S=O=E ________ ~I ____________ ~G)~· __ __
1 . I ~ . 0 9.S6S CB 1052 B PHASE
~. B. 09.561 CBI052 BPR
j'21.H.09.SSl BAKNAULI-l MoUN- l S!AAf-P. PH
, 21.44.09.5 . 0 C51St !RIP cneun-II
;Ula 21.44.09.535 ce152 !RIP CIRCUl f -II
LZOlO 21.44.09.534 C8152 TRIP CIRCUIT-ll
It-ZOIO 21.44.09.531 C8152 TRIP ClReun-II
1(01-2010 21.44 .09.530 C81S2 !RIP CIRCUIt-II
12 -01-2010 21.44.09.528 cslS2 ,RIP CIRCUI!-II
12-01-2010 21.44 .09.528 CB 10S2 GENE!V.t. Lto a 2
)2 -01-201021.44.09.528 CB1052 TRIP CIRCUIT 2
)2- 01- 2010 21.44.09.527 C81252 tRIP CIRCUIT 1
)2-01-Z010 21.14.09.52& C81252 !RIP CIRcun 1
12-0~OlO 21.44.09.525 CB 1052 GENERAL LtO HZ
)2-01-.!010 21. 44. 09.525 C81252 ,RIP CIRCUI'I' 1
02-01-2010 21. H, 09.525 C81252 tRIP CIRCUl'l' 2
02-01-Z010 21.H.09.525 C81052 , RIP CIRCUIT 2
02-01-20tD 21. H .09.524 CB 1052 GEHBW L/o HZ
02-01-2010 21.H.09.52! CS1052 f RIP CIP.CUI! 2
02-01-20.1021.41. 09.520 CB152 JJR UNSOCESSFUL
02-01-2010 21.44..09.520 C8152 GEN. 100 91'6 I:"OLE-B
02-01-201021. 44.09.520 (,B152 GEN. I.O sf6 POLE-A
02-01-2010 21.44 .09 .520 CB152 LOSS Of' 9f6 POLE-Ais/c
02-01-Z010 21.44.09.5Z0 CB15Z POLB DISCP
OZ-01-2010 21.44.09 .520 C8152 GBNERAL LO-l (On / SF6/ H2 1
02-01-2010 21.44 .09.5Z0 CB15Z GE N. LO SP6 POLE-C
OZ-01-201O Z1. H. 09. 520 CB15Z !UP CIRCUIT-II
OZ- !010 Z1.H.09. 5Z0 CBIZ5Z tRIP CIP.CUI'1' 1
OZ-01-Z010 21. 44.09.519 CB152 !UP CIRCUI'!'-ll
02-01-201021. 44 .09.519 calS2 GBNERAL 1.0-1 (OIL/ SF6/ H2 )
02-01-201021.44.09.519 CB 152 B- Phase
02-01-201021.44 .09.519 CBIS2 GEN. LO SP6 POLB-C
02- 01-201021. 44..0 9. 519 CB152 POLE DISCP
02-01-2010 21. 44. 09.519 CS 152 Y- phase
OZ-01-2010 21. 44. 09. 519 Ca152 AIR UN9UCES9PUL
OZ-01-Z010 Z1.14.09.519 CB15Z GI!!N. I.O 91'6 I:"OLB-A
02-01-201021.44 .09.519 CBlS2 GEN . I.O sr6 POLE-B
OZ -01-Z010 21. H .09.519 C815Z LOSS Of' SF6 POLB-AlB/c
02-01-Z010 Z1.44.09.519 CB1Z52 TRIP CIRCUIf 1
10-01-0222;22;01
T ••
- open
- RESET
- HIGH
- I«lW'
- !'AULTi'
- IIOP,M,U
- I'AULTi'
- ItO"""
- rAUL!Y
- LaO
- NOPJoW.
- NOruw.
- I'AULf'{
- HIGH
- '''''''' - NORMAL
- PAUL!Y
- LaO
- """'" - WI
- "" - "" - LeW
- LeW
- I\!SBt
- LCII
- """" - PAlMY
- rAUL!"{
- OP ERA!!D
- open
- HIGH
- HIGH
- npen
- HIGH
- HIGH
- HIGH
- HIGH
- lfOP..l!AL
Page 1
![Page 203: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/203.jpg)
Chapter - 6 _ EXHIBIT - 6I (page 6 of 6)
!-____________ B_A_M_NA_U"'L.I_ S,-,O_E ______ ~--------.W _
, .' , ( U19.5t9 C8152 LOSS OP SF6 POLE~A/B/C
/ .44.09. 519 c81252 , RIP CIRCUU' 1
/ 1. 44. 09 . 519 BAMNAULI~2 GR-A )PH PROO'ECTION
/ ) 21.44.09.517 CB 152 '{- Phase
()lID 21.44 .09.517 C6l252 'RIP CIRCUIT 1
~" IzOlO 21.44.09.517 BAMNAULI-2 GIH ) PH PRO'I'ECUON
~ 1-2010 21. H. 09.516 CB 152 F.- phase
11 01-'1.010 21.44. 09.516 CB 152 Y- phase
2-01-21)10 21.H.09.~16 C81252 TRIP CIRCUIT 2
02 -01-2010 21.44. 09.514 IlAMHAULI-2 GR-A 3PH PRO'I'EC'l'ION
02-01-2010 21.44.09.508 81J1HAULI-2 GR-}' 3PH PRO!EC'I'ION
02 -01-201021.44 .09.507 BAMNAULI-2 GR-A )PH PRO'I'ECTIOIl
02-01-2010 21.44 .09 .506 BAMHAULI-2 GR-A JPH PRO'PEC'J'ION
OZ-Qj -10l0 21.44. 09.506 CB 1252 B PHASE
Oh,_ 2010 21.41. 09.506 CB 1252 'i PHASB
OZ-Ol-Z(ilO 21.44.09.506 CB 1052 B PHASE
Cl-Ut-lOlD 21.44.09.5(15 BAMNAULI-2 GR-}' )PH PROOeC'f ION
OZ·01·Z010 21.44 .09.505 CB 1052 Y P!I.ASE
02·01-2010 21.44.09.505 CB 1052 B PtlASE
02-01-2010 21.H. 09 .tB6 Ca10S? BFR
02- 01- Z010 21. 44 .09.452 CSI0SZ TRIP CIRCUI! 2
OZ-01-2010 2l.H.09.4S1 CSI052 TRIP CIRCUIT 2
OZ -01-2010 21.H.OUn Cal052 TRIP CIRCUI' 2
02·01-2010 21 .. 44. 09.446 CBI052 TRIP CIRCUIT 2
02-01-Z010 21.44..09.444 CBI052 '?RIP CIRCUI,? 2
OZ-01-2010 21. 44. 09. 441 CB 1052 GENEPJ.L L/o H2
02-01-Z010 21.44.09.440 CB 1052 GENEPJ.L L/O 1&2
02- -'~010 21.44.09.431 CB 1052 GRNEfIJ.L L/O 1&2
02 -01-201021. 44. 09.436 ca 105Z GBHEPJ.J. L/O 1&2
02-01-2010 Z1.44.09.435 CB 1052 GBN!PJ.L Llo HZ
0~ -Ol-Z010 21.44.09 .345 BAMNAULI-Z MAIIi-Z PRotEC!ION
OZ-01-2010 21.H.09.310 CBIZSZ TRIP CIRCUn 1
02-01-201021.44. 09 .305 CalZ5Z TRIP CIRCUn' 1
02 "01-Z010 Z1. 44. 09. 2B7 CB l Z52 R PKASE
OZ-01-2010 21.44.09.Z71 BAMNAULI-2 KAIN-l CARRIER SEND
02-01-2010 21.44.. 09.210 BJJINAULI- Z MAIN-l PRO'l'ECfION
02-01-Z010 21.44 .09.264 B»!NAULI-2 MAIN-l START-F. PH
02 -01-2010 21.44.09.262 BAMN.l.ULI-2 MAIH-2 SfAP,,.-P. PH
02 -01-Z010 17.39.33.52B cs 152 s- Phue
0-01-02 22:21 :37
- HIGH
- HOIOO.L
- 'RIPPED
- c1o~ed
• I'AULfY
- NORMAL
- open
- open
- I'AULTY
- !RIPPED
- """" - TRIPPED
- HOOIAL
- open
- open
- clo~e
- TRIPPED
- open
- open
.~
- I'AULIfY
- 110PJ(A1
- I'AlILfY
- NO"'"
• I'AUL'1Y
• HIGH
-"" - HIGH
- '''' • HIGH
- !RIPPED
- N""'" - fAULTY
• open
• HIGH
- tRIPPED
- HIGH
- HlGH
- do~ed
''''
{lV$ _ 2-
gvs - II q,U 5,. - 'l:.
._ C 101 C'52. ] _ (..10 12-5.2.
Pa3e 1"-c~ 15'2.
<....e::. '? 5 2 eo ' ,",,'0 /..:.t tx.t - I . !
-~----------I -----
![Page 204: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/204.jpg)
Page 1
Powergri\Ballabga\Bamnauli\REL52123.1\10010203.REH Station: Ballabgarh Object: Bamnauli-I 2 JAN 2010 21:43:26.918
[ms]
0
0
500
500
1000
1000
1500
1500
2000
2000
0
U1 200 kV
0
I1 5000 A
0
U2 200 kV
0
I2 5000 A
0
U3 200 kV
0
I3 5000 A
0
U4 500 kV
0
I4 5000 A
LINE-CB-OPN-RLINE-CB-OPN-Y
LINE-CB-OPN-BCAR-RCV-MI
MAIN-1-TRIP
A/R-OPTDDT-RCV
MAIN2-CAR-RCV
MAIN2-TRIPBFR-OPTD
TIE-CB-OPEN-RTIE-CB-OPEN-Y
TIE-CB-OPEN-B
M1-CAR-SENDMII-CAR-SEND
ZM2-START
ZM3-STARTSOTF-TRIP
hapter- 6_EXHIBIT - 6/II (page 1 of 4)
INWiJ~ I I I I
I ~~" jj! I v vv
IWW H~~Am m~m -I '" , v' 'v v
I/WNl i~A~W~ ~mmv
I ,~_ I I JH mv
![Page 205: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/205.jpg)
Page 2
Powergri\Ballabga\Bamnauli\REL52123.1\10010203.REH Station: Ballabgarh Object: Bamnauli-I 2 JAN 2010 21:43:26.918
[ms]
3000
3000
3500
3500
4000
4000
4500
4500
5000
5000
0
U1 200 kV
0
I1 5000 A
0
U2 200 kV
0
I2 5000 A
0
U3 200 kV
0
I3 5000 A
0
U4 500 kV
0
I4 5000 A
LINE-CB-OPN-RLINE-CB-OPN-Y
LINE-CB-OPN-BCAR-RCV-MI
MAIN-1-TRIP
A/R-OPTDDT-RCV
MAIN2-CAR-RCV
MAIN2-TRIPBFR-OPTD
TIE-CB-OPEN-RTIE-CB-OPEN-Y
TIE-CB-OPEN-B
M1-CAR-SENDMII-CAR-SEND
ZM2-START
ZM3-STARTSOTF-TRIP
Chapter - 6 _ EXHIBIT - 6/II (page 2 of 2)
I _____________________ ' ______________________ ' ______________________ ' ______________________ ' ______________________ ' ___ _
I ___________________________________________________________________________________________________________________ _ I ___________________________________________________________________________________________________________________ _
I ___________________________________________________________________________________________________________________ _
I ___________________________________________________________________________________________________________________ _
I ___________________________________________________________________________________________________________________ _
I ___________________________________________________________________________________________________________________ _ I ___________________________________________________________________________________________________________________ _
--
--
--
--
![Page 206: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/206.jpg)
Chapter - 6 _ EXHIBIT - 6/II (page 3 of 4)
vi 44.53.198 BAMNAULI-2 K.U/f-2 CV'J' puse
1.44 . 46 .516 BAMNAULI-2 MAIN-Z CVf PUge
BAHNAULI-2 MAIN-I OJ'!' puse
I 0 21.H.40.HO !!AI'IHAlJLI-Z MAIM-l Cvt rU3!
,} 010 21. H. tn. 437 BAMNAlJLI-2 HAIN-2 CV1' PUSB
11-2010 21.4L27.H9 BAMNAULI-2 CAP.RIER PRC'ireCTION cH2 ,r
01-201021.49,12.382 CB 1052 R PHASE
jZ-01-20l0 21.44.09.933 BAMNAULI-2 GR'!! 3PH PRCtI'E<:TlON
I 02-01-201021. 44.09.930 BAMNAULI-2 GR-B 3pH pPo01'BCTION
02-01-201021. 44, 09.926 BAMNAULI-l GR-B 3pH pROO'ECTION
02-01-201021. 44.09 .920 BAMHAULI-2 GPo-B 3pH pRO!!!!C'1IOH
02-01-201021.44.09.919 BAMHAULI-2 GR-B 3pH PRO'I'EC!ION
1 02-01- 201021.44.09.838 B.t\!NAULI-2 DUEC'I' tRIP CHl/2 RECEIVBD
• O~1-2010 21.44.09.685 BAMNAULI-1 DIP.EC'I' '!'RIP CHl/2 RECEIVED
! 02-'01-2010 21.44.09.680 BAMNAULI- l Gb .. 3pH pROrBC'lION
02-01-2010 21.44.09.680 BAIOO.ULI-l GR-A JPH pRO!&C!IOH
02 -01-201021.44.09 .618 CB152 OPRTlt L1o-2 (OlL/ SF6/Jt2)
02-01-2010 21.44 .09.618 CB 352 y-Pha,e
1 02-01-2010 21.44,09 . 676 CB 352 R-pha,e
0:H)l-2010 21.44.09.675 ClI 352 B-Phue
1 02-01-201021. 44.09.675 BAMNAULI-l DII\BCT TRIP CHIll Re:CIUV!D
: 02-01-2010 21.44.09.656 BAMNAULI-1 DIRECT '!'UP CH1/2 RECEIVED I I 02-01-201021.44.09.655 BAMNAULI-l DIRECT TRIP CH1I2 ReCBIVBD
1 02-01-2010 21.44 .09.643 BAMNAULI- l MAIlt-l START-II. PH
1 02 -01-201021.44.09.608 CB 1052 B PHASB
02-01-201021.44.09.606 CB 1052 B plIJ,SB
02-01-201021.44.09.597 CB 1052 B PHASE
11-2010 21.H.09.596 CB 1052 B PfU..SE
02-01-201021.44 .09.584 CB 1052 B PfU..SE
02-01-201021.44.09.582 CB 1052 B PHASB
02-01-2010 21. 44.09.514 BAMNAULI-2 MUJt-1 CAAPJ:ER seND
02-01-201021.44.09.574 B.OOUIULI-2 MAIN-l PII.OOSC!IOH
02-01-2010 21.44.~9.573 B»!NAULI-2 MAIM-l stAA'-R PH
02 -01-2010 21.44.09 .572 BAJIOO..ULI-2 KUN-2 3'1'AA'-R PH
'1 02-01-2010 21.44.09.572 BAMNAULI~2 MUM-2 pP.QTEC!'ION
02-01-201021.44.09.565 CB 1052 B PH.'SB
02-01-201021.44.09.561 CB10S2 SFR
02-01-2010 21.H .09.S51 BAMNAULI-1 HUN-1 START-R PH
02 -01-2010 Zl.H.09.540 CB152 TRIP CIRCUIT-II
- PAILBD
- Ilom.L
- 1IORI!I.1
- rAILBD
- PAILBD
- PAILED
- open
- TRIPPBD
- NORMAL
- !RIPpeD
- HORI!I.1
- !RIPPED
- HIGH
- WI
- !RIPPBD
- NOOII.L
- WI
• open
- open
- open
- HIGH
- "" - HIGH
-"" - open
- cIo,e
- open
- close
- open
- clo,e
- La!
- NOI\JtW.
- WI
- "" - NORMAL
- open
- RESET
- HIGH
• tlORMAL
~010-01-02 23:01 :25 Page 1
T ..
![Page 207: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/207.jpg)
SECTION - 6 _ EXHIBIT - 6/II (page 4 of 4)
~~ ________________ ~B~AM~N~A~U~L~I ~SO~E~ ________ ~ _____________ ~GW=' __ __
i:~'09'S6: CB 1052 B PHASE
.H.09.561 CBI0S2 aPR
21.H.09.S51 woo.ULI-l MAIN-! S!AAT-R PH
,. 21.H.09.5~a C8152 ,RIP CIRCUIt-II
1'10 21.44.09.535 C8152 !rup CIRCUI'!'-II
""Z010 21.44.09.534 C8152 TRIP CIRcun-II
I:-Z010 21.44 .09.531 calS2 TRIP CIRCUIt-II
1-01-2010 21.44.09.530 CB152 !RIP CIRCUIt-II
12 -01-2010 21.44.09.528 C8152 ,RIP CIRCUIt-II
12-01-2010 21.44.09.528 CB 1052 GI!NERAL 1./0 HZ
12 -01-2010 21.H.09. 528 CB10S2 TRIP CIRCUIt 2
)2-01-201021.44.09.527 C81252 tRIP CIRCUI'P 1
)2-01-201021.44.09,526 ca1252 '!'RIP CIRCUIt 1
l2-0~OlO 21.44.09.525 CB 1052 GENEP.AL L/O uZ
)2-0l-.!OlO 21.44.09,525 C81252 tRIP CIRCUIt 1
Ol-Ot-201() 21.44,09.525 C81252 !RIP CIRCUIt 2
02-01-2010 21.44.09 .525 CBI0S2 !RIP CIRCut'l' 2
02-01-201021.44.09.524 CB 1052 GENBW L/O HZ
02-01-2010 21.H.09.524 C81052 'I'm CIRCUI' 2
02-01-2010 21. 44. 09.520 CB152 AIR UNSUCESSPUL
02-01-2D1O 21.44..09.520 CB152 GEH. LO sp6 POLB-B
02-01-201021. 44.09.520 CB152 GEN. LO Sf6 POLE-A
02-01 -2010 21.H .09 .520 CB152 LOSS op SP6 POLB-AiB/C
02-01-2010 21.44.09.520 CB152 POLl! DISCP
02 -01-201021.44..09.520 CB152 GI!NBP.A.L 10-1 (OIL/SP6/N2)
02-t)1-2010 21.44.09.520 C6152 GEN. LO sp6 POL!-C
02-01-2010 21.4L09.520 CB152 TRIP CIRCUI'-II
02- :01021.44.09.520 CB1252 ,RIP CIRCUI' 1
02 -01-201021.44.09 .519 CB152 ,RIP CIRCUI'-II
02-01-2010 21.14.09.519 C8152 GBIl!RA.L 10-1 (OILJSP6/M2)
02-01-2010 21.4"09.519 CB 152 B- Phase
02-01-2010 21.44.09.519 C8152 GEN. LO sp6 POL!-C
02-01-201021.44 .09.519 CB152 POLB DISCP
02-01-2010 21.44.09.519 CB 152 Y- phue
02-01-2010 21.H.09.519 CB152 AiR UNSUCESSfUL
02-01-20In 21.44.09.519 CB152 GEH. LO SP6 POLE-A
02-01-2010 21.44.09.519 C8152 GEN. LO sr6 POLE-S
02-01-2010 21.H.09.519 CB152 LOSS Of sf6 POLP.-A./B/C
02-01-2010 21.44.09.519 C81252 ,RIP CIRCUIT 1
10-01-0222:22:01
I" - open
- RESBT
- HIGH
- 1IOIIl'.At
- fAULf'r'
- HOPJtlJ.L
- fAUL'fY
- """"" - PAULf'r'
- WI -_.A1 - NOI\l4A1
- PAULf'r'
- !UGH
- """"" - N01W.L
- PAUL'fY
- WI
- """"" - WI
- "'" - "" - Wi
- WI
- USB!
- LT>i
- NOOOL
- PAUL'fY
- PAU1f'r'
- OPEPJ.'l'ED
- open
- HIGH
- HIGH
- open
- HIGH
- HIGH
- HIGH
- HIGH
- IIOPJIAL
Page 1
![Page 208: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/208.jpg)
CHAPTE
R- 6
_ E
XH
IBIT
- 6/
III (p
age 1
of 6
)
, " N
~ o
~ 5
~
~
it
• • t
~
<i1
<i1
0°
~ (>
~ Q ,
o
o " ., • ., B
mG
'~
i ~ , ' w 00
~ ~
§
~ ~
~
~ 8 ~ ~
§ §
" , ~ o 5 ~
~ ~
N N
~ , ~
m N
~ ~
~
•
~ N
• 5 A
~ o
" •
o
8 o
§ ~
8 o
~ •
w
-I NNNNN
~ 8 ::c::::::::::::: NNNNN
o N
~ § ~ , ,
~ N
D
e , N N
N D
![Page 209: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/209.jpg)
CHAPTER-- 6_ EXHIBIT - 6/III (page 2 of 6)
15:49:23.73 EL02-D2-23 + 15:49:23.74 El02-D2-06 16:22:48.06 EL01-08-20 16:22:51 .84 El02-D2-23 16:41 :41 .52 EL01-0B-20 + 16:41 :41 .52 EL01-08-03 + 16:41 :41 .52 El01-08-03 16:41 :41 .94 El02-02-06 + 16:41 :41 .94 El02-D2-23 + 16:41 :41.95 EL02-D2-23 16:41 :41 .95 EL02-D2-06 16:41 :41 .95 EL02-D2-23 + 16:41 :41 .95 EL02-D2-23 16:41:41 .95 EL02-D2-23 + 16:42:04.26 EL01-08-20 16:42:08.04 EL02-D2-23 16:45:42.22 EL01-08-03 + 16:45:42.22 EL01-08-03 16:45:42.23 EL01-08-20 + 16:45:42.65 EL02-02-06 + 16:45:42.65 EL02-02-06 16:45:42 .66 EL02-D2-23 + 16:46:46.16 EL01-08-20 16:46:49.94 cL02-02-23 16:50:01 .00 EL01-S0-01 + 16:50:02.00 EL01-S0-02 + 21:44:15.73 H01-D7-02 + 21 :44:15.73 EL01-D7-03 + 21 :44:15.74 EL01-D7-10 + 21:44:15.75 EL01-D7-06 + 21 :44:15.75 EL01-D8-14 21 :44:15.75 EL01-D8-29 21:44:15.75 EL01-D8-13 21 :44:15.75 EL01-D8-30 21 :44:15.75 EL01-D8-31 21 :44:15.75 EL01-D8-07 + 21 :44:15.75 EL01-D8-07 21:44:15.75 EL01-D8-12 21 :44:15.75 EL01-D8-OB + 21 :44:15.76 EL01-DB-OB 21:44:15.B2 EL01-D7-02 21 :44:15.82 EL01-D7-03 21:44:15.82 EL01-D7-10 21:44:15.82 EL01-D7-06
2 POWERGRIO BHADURGARH
400KV Bhiwani Tie CB GRP NB DC Fail 400KV Bhiwani GRPA NB Fail 400KV Bawana Tie CB GRP NB DC Fail 400KV Bhiwani Tie CB GRP NB DC Fail 400KV Bawana Tie CB GRP NB DC Fail 400KV Bawana GRP !VB AC Fail 400KV Bawana GRP !VB AC Fail 400KV Bhiwani GRPA NB Fail 400KV Bhiwani Tie CB GRP NB DC Fail 400KV Bhiwani Tie CB GRP NB DC Fail 400KV Bhiwani GRPA AlB Fail 400KV Bhiwani Tie CB GRP NB DC Fail 400KV Bhiwani Tie CB GRP NB DC Fail 400KV Bhiwani Tie CB GRP NB DC Fail 400KV Bawana Tie CB GRP NB DC Fail 400KV Bhiwani Tie CB GRP NB DC Fail 400KV Bawana GRP !VB AC Fail 400KV Bawana GRP !VB AC Fail 400KV Bawana Tie CB GRP NB DC Fail 400KV Bhiwani GRPA AlB Fail 400KV Bhiwani GRPA AlB Fail 400KV Bhiwani Tie CB GRP NB DC Fail 400KV Bawana Tie CB GRP NBDC Fail 400KV Bhiwani Tie CB GRP NB DC Fail Set time, old time in "El01" Set time, new time in "EL01" 400KV Bawana 3 Phase Protection Optd . 400KV Bawana Main 1 optd . 400KV Bawana Z21Z3/Multi Ph optd . 400KV Bawana Main-1!2 Directional ElF 400KV Bawana Main B Ph Bkr. Close(+)I0p 400KV Bawana Tie R Ph. Bkr. Close( + )fOp 400KV Bawana Main Y Ph Bkr. Close(+)I0p 400KV Bawana Tie Y Ph. Bkr. Close(+)I0p 400KV Bawana Tie B Ph. Bkr. Close(+)/Op 400KV Bawana Direct Trip Send ch-1 400KV Bawana Direct Trip Send ch-1 400KV Bawana Main R Ph Bkr. Close(+)10 400KV Bawana Direct Trip Send ch-2 400KV Bawana Direct Trip Send ch-2 400KV Bawana 3 Phase Protection Optd . 400KV Bawana Main 1 optd . 400KV Bawana Z21Z3lMulti Ph optd. 400KV Bawana Main-1!2 Directional ElF
Indactic 425 2 January 2010 15:49:23.73
![Page 210: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/210.jpg)
CHAPTER- - 6 _ EXHIBIT - 6/III (page 3 of 6)
21 :44:16.71 EL01-08-22 + 21:44:16.85 EL01-08-22 21:44:17.12 EL01-08-18 + 21:45:46.95 EL01-08-18 21:54:07.39 EL02-02-06 + 21 :54:07.39 EL02-02-06 21:54:07.39 EL02-02-23 + 21:54:07.73 EL01-08-03 + 21:54:07.73 EL01-08-20 + 21:54:07.74 EL01-0B-03 21:56:42.42 El01-07-11 + 21:56:42.44 EL01-07-24 + 21:56:42.86 EL01-07-24 21:56:42.87 EL01-07-11 22:00:53.73 EL01 -08-20 22:00:56.76 El02-02-23 22:06:16.08 EL02-01-14 + 22:06: 16.11 EL02-02-17 22:06:16. 11 El02-02-16 22:06: 16.11 EL02-03-01 22:06:16. 11 EL02-02-15 22:06: 16.11 El02-03-02 22:06: 16.11 EL02-02-32 22:06:16.45 EL02-01 -14 22:06:17.35 EL02-02-21 + 22:07:39.87 EL02-01-02 22:07:39.87 EL02-01-03 22:07:39.89 EL02-01 -01 22:07:47.16 EL01-01-23 22:07:47.17 EL01-01 -22 22:07:47.17 EL01-01 -24 22:07:57.72 EL02-D2-21 Sunday, 3 January 2010 00:00:00. 13 El01-<11-01 0000 00:00:00.13 EL01-<11 -17 0009 00:00:00.13 EL01-<12-01 070C 00:00:00.13 EL01-<12-17 0400 00:00:00.13 EL01-<13-01 0000 00:00:00.13 EL01-<13-17 1FOO 00:00:00.13 EL01-<14-01 0000 00:00:00.13 EL01-<14-17 0000 00:00:00.13 El01-d5-01 7500 00:00:00. 13 El01-<15-17 0000 00:00:00. 13 El01-d6-01 0000
3 POWERGRID BHADURGARH
400KV Bawana Tie N2 Lockout 400KV Bawana Tie N2 Lockout 400KV Bawana Tie CB Trouble Alarm 400KV Bawana Tie CB Trouble Alarm 400KV Bhiwani GRPA AlB Fail 400KV Bhiwani GRPA AlB Fail 400KV Bhiwani Tie CB GRP AlB DC Fail 400KV Bawana GRP AlB AC Fail 400KV Bawana Tie CB GRP AlB DC Fail 400KV Bawana GRP AlB AC Fail 400KV Bawana Direct Trip-1 Received 400KV Bawana Direct Trip-2 Received 400KV Bawana Direct Trip-2 Received 400KV Bawana Direct Trip-1 Received 400KV Bawana Tie CB GRP AlB DC Fail 400KV Bhiwani Tie CB GRP AlB DC Fail 400KV Bhiwani Direct Trip-1 Received 400KV Bhiwani B Ph. Bkr. Close 400KV Bhiwani Y Ph. Bkr. Close 400KV Shiwani Tie Y Ph. Bkr. Close 400KV Bhiwani R Ph. Bkr. Close 400KV Bhiwani Tie B Ph. Bkr. Close 400KV Bhiwani Tie R Ph. Bkr. Close 400KV Bhiwani Direct Trip-1 Received 400KV Bhiwani Tie CB Trouble Alarm 400KV ICT-1 Y Ph. Bkr. Close 400KV ICT-1 B Ph. Bkr. Close 400KV ICT-1 R Ph. Bkr. Close 220KV ICT Bkr. Close Y Ph. 220KV leT Bkr. Close R Ph. 220KV ICT Bkr. Close B Ph. 400KV Bhiwani Tie CB Trouble Alarm
State 01-01 .. 01-16 State 01 -17 .. 01-32 State 02-01 .. 02-16 State 02-17 .. 02-32 State 03-01 .. 03-16 State 03-17 .. 03-32 State 04-01 .. 04-16 Slate 04-17 .. 04-32 State 05-01 .. 05-16 State 05-17 .. 05-32 Slate 06-01 .. 06-16
Indactic 425 2 January 2010 21 :44:16.71
![Page 211: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/211.jpg)
CHAPTER- -6_ EXHIBIT - 6/III (page 4 of 6)
00:00:00 13 EL01-d6-17 0000 00:00 :00 .13 EL01-d7-01 0000 00 0000.13 EL01-d7-17 0000 00:00:00.13 EL01-dB-01 0700 0000:00.13 EL01-d8-17 0800 00:00:00.13 EL01-dS-01 0000 00:00:00.13 EL01-d9-17 COOO 00:00:00.13 EL02-d1-Q1 0000 00:00:00.13 EL02-d1-17 0000 00:00:00 13 EL02-d2-01 3800 00:00:0013 EL02-d2-17 6000 00:00:00 .13 El02-d3-01 0000 00:00:00 .13 EL02-d3-17 0000 00:00:00 .13 EL02-d4-01 0000 00:00:00 .13 EL02-d4-17 0000 00:00:00 .13 EL02-d5-01 0000 00:00:00 .13 EL02-d5-17 0000 00:00:00.13 EL02-dB-Q1 0000 00:00:00 .13 EL02-d6-17 0000 00'00-00 .13 EL02-d7-01 0000 00:00:00.13 EL02-d7-17 0000 00:14:27.76 EL01-01-24 + 00:14:27 .76 EL01-01-22 + 00:14:27 .76 El01-01-23 + 00:16:24.79 EL02-01-01 + 00:16:24 .79 El02-D1-03 + 00:162479 EL02-D1-02 + 00:23: 19.80 El02-02-32 + 00:23:19.81 EL02-D3-01 + 00:23:19.81 El02-D3-02 + 00:23:27.32 El02·01·14 + 00:23.27.36 El02·03-01 00:23:27.36 El02·03·02 00:23:27.36 El02·02-32 00:23:27.45 El02·01·14 00:23:28.53 El02·02-21 + 00:23:28.54 El02·02·21 00:23:28.60 El02·02·21 + 00:23:30.94 El02·02·25 + 00:23:31 .03 El02·02·25 00:24:38.99 El02·02·21 00:28:09.27 El01·08·30 + 00:28:09.27 El01·08·31 + 00:28:09.27 ElOl·D8·29 +
4 POWERGRIO BHADURGARH
State 06-17 .. 06·32 State 07-01 .. 07-16 State 07·17 .. 07·32 State 08-01 08-16 State 08-17 .. 08-32 State 09-01 .. 09-16 State 09-17 .. 09-32 State 01-01 .. 01-16 State 01-17 .. 01-32 State 02-01 .. 02-16 State 02-17 .. 02-32 State 03-01 .. 03-16 State 03·17 .. 03·32 State 04-01 .. 04-16 State 04-17 .. 04-32 State 05-01 .. 05-16 State 05·17 .. D5·32 State 06-01 .. 06-16 State 06-17 .. 06·32 State 07·01 .. 07-16 State 07-17 .. 07-32 220KV ICT Bkr. Close B Ph. 220KV ICT Bkr. Close R Ph. 220KV ICT Bkr. Close Y Ph. 400KV ICT-1 R Ph. Bkr. Close 400KV ICT·1 B Ph. Bkr. Close 400KV ICT -1 Y Ph. Bkr. Close 400KV Bhiwani Tie R Ph. Bkr. Close 400KV Bhiwani Tie Y Ph. Bkr. Close 400KV Bhiwani Tie B Ph. Bkr. Close 400KV Bhiwani Direct Trip·l Received 400KV Bhiwani Tie Y Ph. Bkr. Close 400KV Bhiwani Tie B Ph. Bkr. Close 400KV Bhiwani Tie R Ph. Bkr . Close 400KV Bhiwani Direct Trip·1 Received 400KV Bhiwani Tie CB Trouble Alarm 400KV Bhiwani Tie CB Trouble Alarm 400KV Bhiwani Tie CB Trouble Alarm 400KV Bhiwani Tie N2 Lockout 400KV Bhiwani Tie N2 Lockout 400KV Bhiwani Tie CB Trouble Alarm 400KV Bawana Tie Y Ph. Bkr. Close(+)lOp 400KV Bawana Tie B Ph. Bkr. Close(+)lOp 400KV Bawana Tie R Ph. Bkr. Close(+)lOp
Indactic 425 3 January 2010 00:00:00.13
![Page 212: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/212.jpg)
CHAPTER-- 6 _ EXHIBIT - 6/III (page 5 of 6)
00:28:53.81 EL01-DB-12 + 00:28:53.81 EL01-0B-14 + 00:28 :53.82 El01-D8-13 + 00:47:55.86 EL01-D7-12 + 00:47:57.18 El01-07-2S + 00:48:00.88 EL01-D7-25 00:48:05.74 ElO1-D7-12 01 :17:40.20 El02-D2-1S + 01 :17:40.20 El02-D2-17 + 01 :17:40.21 EL02-D2-16 + 01 :17:57.30 El02-D2-32 + 01 :17:57.31 EL02-D3-01 + 01 :17:57.31 EL02-D3-02 + 01 :21 :20.93 EL02-02-06 + 01 :21 :20.93 EL02-D2-06 01 :21 :20.93 EL02-02-23 + 01 :21 :20.93 EL02-D2-23 01 :21 :20.93 EL02-D2-23 + 01 :21 :21 .12 EL01-DB-03 + 01 :21 :21 .12 EL01-0B-20 + 01 :21 :21 .12 EL01-DB-03 01 :23:13.14 EL01-0B-20 01 :23:16.32 EL02-D2-23 09:21:46.53 El01-02-20 + 09:21 :46.53 EL01-D2-20 09:21 :46.54 El01-D2-20 + 09:21 :46.71 El01-D4-06 + 09:21:46.72 EL01-D4-06 09:21 :46.72 EL01-D4-06 + 09:21 :46.72 El01-D4-06 09:21:46.73 El01· D4-06 + 09:21 :48.68 El01-04-06 09:21 :49.09 El01-D2-20 09:37 :15.40 ElOl-D7-12 + 09:37:16.56 El01-D7-12 09:37:49.46 El01-D7-12 + 09:37:51 .19 El01-D7-12 11 :18:43.33 El01-D7-12 + 11 :18:45.17 El01-D7-12
5 POWERGRID 8HAOURGARH
400KV Bawana Main R Ph Bkr. Close(+)10 400KV Bawana Main B Ph Bkr. Close(+)I0p 400KV Bawana Main Y Ph Bkr. Close(+)I0p 400KV Bawana Carrier Fail Ch-1 400KV Bawana Carrier Fail Ch-2 400KV Bawana Carrier Fail Ch-2 400KV Bawana Carrier Fail Ch-1 400KV Bhiwani R Ph. Bkr. Close 400KV Bhiwani B Ph. Bkr. Close 400KV Bhiwani Y Ph. Bkr. Close 400KV Bhiwani Tie R Ph. Bkr. Close 400KV Bhiwani Tie Y Ph. Bkr. Close 400KV 8hiwani Tie B Ph. Bkr. Close 400KV Bhiwani GRPA AlB Fail 400KV Bhiwani GRPA AlB Fail 400KV Bhiwani Tie CB GRP AlB DC Fail 400KV Bhiwani Tie CB GRP AlB DC Fail 400KV Bhiwani Tie CB GRP AlB DC Fail 400KV Bawana GRP AlB AC Fail 400KV Bawana Tie CB GRP AlB DC Fail 400KV Bawana GRP AlB AC Fail 400KV Bawana Tie CB GRP AlB DC Fail 400KV Bhiwani Tie CB GRP AlB DC Fail 220KV Line 1 Carrier speech fail 220KV Line 1 Carrier speech fail 220KV Line 1 Carrier speech fail 220KV Line 2 Carrier speech fail 220KV Line 2 Carrier speech fail 220KV line 2 Carrier speech fail 220KV line 2 Carrier speech fail 220KV line 2 Carrier speech fail 220KV line 2 Carrier speech fail 220KV line 1 Carrier speech fail 400KV Bawana Carrier Fail Ch-1 400KV Bawana Carrier Fail Ch-1 400KV Bawana Carrier Fail Ch-1 400KV Bawana Carrier Fail Ch-1 400KV Bawana Carrier Fail Ch-1 400KV Bawana Carrier Fail Ch-1
Indactic 425 3 January 2010 00:28:53.81
![Page 213: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/213.jpg)
CHAPTER-- 6 _ EXHIBIT - 6/III (page 6of 6)
SIMATIC PGCIL I 400KV BAWANA + I Bawana /7SA522 VO( . 37 . 01 1/3/2010 12 ;46: 26 ft
Tri p Log 000965 / 1 / 2/2010 V04 . 37 . 01
9 44 : 0 9 . 268 ft( PGClt. / ,"001lN ~+ / Baw ...... /7SA5 22
.-. 00301
00302
00506 01358 01357 00515
00507
00508
00509
01165
01169 00533
0053(
00535
01345
00511
01125
01117
0 1118
01114
01115
01119
01120
Indicati on -POwer Sy~ tem [ .. ult
Fau lt Event 982 ON
Relay PICt>UP Earth ON El f pic ~a~ up FORWARD ON Elf JIO p P I CKED UP ON Re lay TRIP c_nd ON Ph""~" LI 23 Relay TRIP CQlNllo'l nd ON Pha"e Ll Re lay TRIP cOINIIo'Ind ON Pha" .. L2 Relay TR I P co.nand ON Ph,, ~ .. LJ E"rth t aul t OIl pro t ection ; Tr i p Jpo l e El F l lOp TRIP ON primary f au l t cur r en t 0.78 kA
'" P[i~ry fault cur r ant 0.60 kA m Primary fau l t cu rrent 0. 61 kA
'" Ea rth fault Off protection PICKE D UP R .. l a y GEtlERA L TRIP OfF ~"d fa ul t Locator Loop ON
'" nt Locator; -30 . 2 4 otun seconda ry RESISTAtlCE flt Locator ; -19 . 0 4 Ohm "econdary REACTANCE Fit Locator; pr i macy - 109.92 Ohm R~SISTANCE rlt Loca to r ; pc1mary -69.22 Oh m REACTANCE Fit Locator ; Distance -209 . 2 km t o fault nt Loca t or ; Distanc .. - 427.0 , ( \ 1 t o fault
oau and t;" C2 .C1. 20 10 21 ; "; 09 . 268 02 . 01.2010 21 ;":09. 268 O~ o . , 0= 6136 N
6136 lOS
6136 """
6136 ....
6137 "'S
61 37 """ 614 0 "'"
614 0 N
614 C "'''
6201 """
6087 """
6087 """
6087 """
6087 "'"
6087 """
608 7 lOS
![Page 214: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/214.jpg)
CHAPTE
R- -6_
EX
HIB
IT - 6/
IV (p
age
1 of
3)
it
• • t
~
<i1
<i1
0°
~ (>
~ Q ,
o
o " ., • ., B
mG
'~
i ~ , ' w 00
§ ~
~ ro N
~
~ ~ ~
~
N
~ ~
§
i ~ • ~
N
§ ~
~ ~
~ ~
§
m
~
~
•
§ ro N
~ ~ ro
,
ro
~ ~
§ ~
, 8
w
~ ~
~
~ ro
, ~
N
~ ~
~ 8 ro
c c
ro
![Page 215: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/215.jpg)
EXHIBIT - 4 - IV - b* 18:45:02:420 (0221) MOGA-1-PATIALA AUTORECLOSE L/O* 18:45:36:175 (0221) MOGA-1-PATIALA AUTORECLOSE L/O* 18:45:36:495 (0221) MOGA-1-PATIALA AUTORECLOSE L/O* 18:52:54:395 (0221) MOGA-1-PATIALA AUTORECLOSE L/O* 18:53:14:795 (0221) MOGA-1-PATIALA AUTORECLOSE L/O* 18:57:35:805 (0221) MOGA-1-PATIALA AUTORECLOSE L/O* 18:58:49:580 (0453) MOGA-PATIALA CLOSE IMP TO 400KV TIE C.B. R 18:58:49:635 (0451) MOGA-PATIALA TIE 400KV C.B. Y- PH CLOSED R 18:58:49:640 (0450) MOGA-PATIALA TIE 400KV C.B. R- PH CLOSE R (0452) MOGA-PATIALA TIE 400KV C.B. B- PH CLOSED * 18:58:49:850 (0453) MOGA-PATIALA CLOSE IMP TO 400KV TIE C.B. R 19:26:13:690 (0445) CLOSE IMPULSE TO BUS REACTOR C.B.* 21:44:19:590 (0068) BAWANA MAIN-2 PROT OPTD - B PH A (0070) BAWANA MAIN-2 PROT UNHEALTHY 21:44:19:595 (0388) BAWANA 400KV C.B. R - PH OPENED (0389) BAWANA 400KV C.B. Y - PH OPENED (0390) BAWANA 400KV C.B. B - PH OPENED (0378) ILT1-BAWANA TIE 400KV C.B. R - PH OPENED
(0379) ILT1-BAWANA TIE 400KV C.B. Y - PH OPENED
21:44:19:600 (0380) ILT1-BAWANA TIE 400KV C.B. B - PH OPENED
* 21:44:19:605 (0066) BAWANA MAIN-2 PROT OPTD - R PH* (0069) BAWANA MAIN-2 PROT OPTD PH-PH* 21:44:19:610 (0067) BAWANA MAIN-2 PROT OPTD - Y PH R (0070) BAWANA MAIN-2 PROT UNHEALTHY* 21:44:19:615 (0049) ICT1-BAWANA TIE 400KV C.B. AUTORECLOSE L/O* 21:44:19:625 (0081) BAWANA AUTORECLOSE L/O* 21:44:19:660 (0067) BAWANA MAIN-2 PROT OPTD - Y PH* (0068) BAWANA MAIN-2 PROT OPTD - B PH* 21:44:19:665 (0066) BAWANA MAIN-2 PROT OPTD - R PH* (0069) BAWANA MAIN-2 PROT OPTD PH-PH* 21:48:29:465 (0081) BAWANA AUTORECLOSE L/O* 21:48:34:530 (0049) ICT1-BAWANA TIE 400KV C.B. AUTORECLOSE L/O 21:48:55:105 (0391) BAWANA CLOSE IMP TO 400KV C.B. 21:48:55:185 (0388) BAWANA 400KV C.B. R - PH CLOSED 21:48:55:190 (0389) BAWANA 400KV C.B. Y - PH CLOSED (0390) BAWANA 400KV C.B. B - PH CLOSED 21:48:55:430 (0391) BAWANA CLOSE IMP TO 400KV C.B. 21:49:04:705 (0378) ILT1-BAWANA TIE 400KV C.B. R - PH CLOSED
(0380) ILT1-BAWANA TIE 400KV C.B. B - PH CLOSED
21:49:04:710 (0379) ILT1-BAWANA TIE 400KV C.B. Y - PH CLOSED
* 21:49:20:265 (0056) BAWANA MAIN-1 PROT OPTD - B PH* (0058) BAWANA MAIN-1 PROT OPTD IN ZONE-1 TIME* 21:49:20:270 (0068) BAWANA MAIN-2 PROT OPTD - B PH 21:49:20:275 (0390) BAWANA 400KV C.B. B - PH OPENED (0380) ILT1-BAWANA TIE 400KV C.B. B - PH OPENED
Page 2CHAP
- 6_ EXHIBIT -6/IV (page 2 of 3)
![Page 216: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/216.jpg)
EXHIBIT - 4 - IV - b
* 21:49:20:285 (0049) ICT1-BAWANA TIE 400KV C.B. AUTORECLOSE L/O* 21:49:20:295 (0056) BAWANA MAIN-1 PROT OPTD - B PH* (0058) BAWANA MAIN-1 PROT OPTD IN ZONE-1 TIME 21:49:20:300 (0379) ILT1-BAWANA TIE 400KV C.B. Y - PH OPENED
21:49:20:305 (0378) ILT1-BAWANA TIE 400KV C.B. R - PH OPENED
DATE 02:01:2010 TIME 21:49:26:545 HISSAR EVENT LOGGER
* 21:49:20:340 (0068) BAWANA MAIN-2 PROT OPTD - B PH 21:49:21:425 (0390) BAWANA 400KV C.B. B - PH CLOSED * 21:49:21:445 (0056) BAWANA MAIN-1 PROT OPTD - B PH* (0058) BAWANA MAIN-1 PROT OPTD IN ZONE-1 TIME 21:49:21:465 (0390) BAWANA 400KV C.B. B - PH OPENED * 21:49:21:480 (0081) BAWANA AUTORECLOSE L/O* (0056) BAWANA MAIN-1 PROT OPTD - B PH* (0058) BAWANA MAIN-1 PROT OPTD IN ZONE-1 TIME 21:49:21:495 (0388) BAWANA 400KV C.B. R - PH OPENED (0389) BAWANA 400KV C.B. Y - PH OPENED * (0066) BAWANA MAIN-2 PROT OPTD - R PH* (0068) BAWANA MAIN-2 PROT OPTD - B PH* 21:49:21:505 (0067) BAWANA MAIN-2 PROT OPTD - Y PH* 21:49:21:515 (0069) BAWANA MAIN-2 PROT OPTD PH-PH* 21:49:21:560 (0066) BAWANA MAIN-2 PROT OPTD - R PH* (0067) BAWANA MAIN-2 PROT OPTD - Y PH* (0068) BAWANA MAIN-2 PROT OPTD - B PH* 21:49:21:565 (0069) BAWANA MAIN-2 PROT OPTD PH-PH* 21:51:54:785 (0081) BAWANA AUTORECLOSE L/O* 21:51:56:325 (0049) ICT1-BAWANA TIE 400KV C.B. AUTORECLOSE L/O* 21:56:48:200 (0221) MOGA-1-PATIALA AUTORECLOSE L/O A 21:56:48:205 (0450) MOGA-PATIALA TIE 400KV C.B. R- PH OPEN
A (0451) MOGA-PATIALA TIE 400KV C.B. Y- PH OPENED A (0452) MOGA-PATIALA TIE 400KV C.B. B- PH OPENED * 22:04:39:830 (0400) KAITHAL-ICT-2 TIE 400KV C.B. R-PH OPEN
* (0401) KAITHAL-ICT-2 TIE 4OOKV C.B. Y-PH OPEN
* 22:04:39:835 (0402) KAITHAL-ICT-2 TIE C.B. B PH OPEN A 22:04:40:200 (0097) NLGH1-ILT2 TIE 400KV C.B. AIR PR LOW* 22:04:43:465 (0484) 400KV FATEHABAD C.B. B - PH OPENED * 22:04:43:470 (0482) 400KV FATEHABAD C.B. R - PH OPENED * (0483) 400KV FATEHABAD C.B. Y - PH OPENED
Page 3CHAP
- 6 _ EXHIBIT - 6/IV (page 3 of 3)
![Page 217: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/217.jpg)
CHAPTE
R- -
6 _
EX
HIB
IT - 6/
V (p
age
1 of
4)
, ~ , ~ o
~ 5
~
~
it
• • t
~
<i1
<i1
0°
~ (>
~ Q ,
o
o " ., • ., B
mG
'~
i ~ , ' w 00
§ e ~ •
8 ~
~ ~ , N • N N
~ ~
N
~ , 8
" ~
8
~
N
~ ~
§
g N
C
~
•
§ ~
• 8
§ ~
~ ~
~
§
~
~
~
~ , • ~
w
~ , §
" ~ ~
8 ~
N
, 8
N 5 ~
" ~
8 ~
D
![Page 218: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/218.jpg)
ARC...02/01/10 21:16:57:240 ABDULLAPUR BUS REACTOR-1 (361) MAIN CB R-PH OPEN ARC...02/01/10 21:16:57:270 ABDULLAPUR BUS REACTOR-1 (362) MAIN CB Y-PH OPEN ARC...02/01/10 21:16:57:272 ABDULLAPUR BUS REACTOR-1 (363) MAIN CB B-PH OPEN ARC...02/01/10 21:16:59:908 ABDULLAPUR TIE-ICT2 BR (315) TIE CB B PH OPEN ARC...02/01/10 21:16:59:912 ABDULLAPUR TIE-ICT2 BR (313) TIE CB R PH OPEN ARC...02/01/10 21:16:59:912 ABDULLAPUR TIE-ICT2 BR (314) TIE CB Y PH OPEN ARC...02/01/10 21:17:08:208 ABDULLAPUR BUS REACTOR-1 (366) 4789 R ISOLATOR CLOSE ARC...02/01/10 21:18:53:672 ABDULLAPUR BUS REACTOR-1 (361) MAIN CB R-PH CLOSE ARC...02/01/10 21:18:53:672 ABDULLAPUR BUS REACTOR-1 (362) MAIN CB Y-PH CLOSE ARC...02/01/10 21:18:53:694 ABDULLAPUR BUS REACTOR-1 (363) MAIN CB B-PH CLOSE ARC...02/01/10 21:19:16:176 ABDULLAPUR TIE-ICT2 BR (315) TIE CB B PH CLOSE ARC...02/01/10 21:19:16:178 ABDULLAPUR TIE-ICT2 BR (313) TIE CB R PH CLOSE ARC...02/01/10 21:19:16:178 ABDULLAPUR TIE-ICT2 BR (314) TIE CB Y PH CLOSE ARC...02/01/10 21:44:14:282 ABDULLAPUR 400KV BAWANA-2 (037) MAIN-2 RELAY IN OPERATIVE ALARM ARC...02/01/10 21:44:14:286 ABDULLAPUR 400KV BAWANA-1 (149) M-2 RELAY IN OPERATIVE ALARM ARC...02/01/10 21:44:20:976 ABDULLAPUR 400KV BAWANA-2 (007) MAIN-1 R-PH TRIP TRIP ARC...02/01/10 21:44:20:976 ABDULLAPUR 400KV BAWANA-2 (008) MAIN-1 Y-PH TRIP TRIP CHAP
- 6 _ EXHIBIT - 6/V (page 2 of 4)
![Page 219: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/219.jpg)
ARC...02/01/10 21:44:20:976 ABDULLAPUR 400KV BAWANA-2 (009) MAIN-1 B-PH TRIP TRIP ARC...02/01/10 21:44:21:006 ABDULLAPUR 400KV BAWANA-2 (074) CB Y-PH OPEN ARC...02/01/10 21:44:21:006 ABDULLAPUR TIE BAW2-NJ2 (106) CB Y-PH OPEN ARC...02/01/10 21:44:21:008 ABDULLAPUR 400KV BAWANA-2 (073) CB R-PH OPEN ARC...02/01/10 21:44:21:008 ABDULLAPUR 400KV BAWANA-2 (075) CB B-PH OPEN ARC...02/01/10 21:44:21:008 ABDULLAPUR TIE BAW2-NJ2 (097) A/R LOCKOUT ALARM ARC...02/01/10 21:44:21:008 ABDULLAPUR TIE BAW2-NJ2 (105) CB R-PH OPEN ARC...02/01/10 21:44:21:012 ABDULLAPUR TIE BAW2-NJ2 (107) CB B-PH OPEN ARC...02/01/10 21:44:21:024 ABDULLAPUR 400KV BAWANA-2 (065) A/R LOCKOUT ALARM ARC...02/01/10 21:44:21:028 ABDULLAPUR 400KV BAWANA-1 (119) MAIN-1 R-PH TRIP TRIP ARC...02/01/10 21:44:21:028 ABDULLAPUR 400KV BAWANA-1 (120) MAIN-1 Y-PH TRIP TRIP ARC...02/01/10 21:44:21:028 ABDULLAPUR 400KV BAWANA-1 (121) MAIN-1 B-PH TRIP TRIP ARC...02/01/10 21:44:21:044 ABDULLAPUR 400KV BAWANA-2 (037) MAIN-2 RELAY INOPERATIVE RESET ARC...02/01/10 21:44:21:058 ABDULLAPUR 400KV BAWANA-1 (186) CB Y PHASE OPEN ARC...02/01/10 21:44:21:058 ABDULLAPUR 400KV BAW-1 TIE (219) CIRCUIT BREAKER B-PH OPEN ARC...02/01/10 21:44:21:060 ABDULLAPUR 400KV BAWANA-1 (185) CB R PHASE OPEN ARC...02/01/10 21:44:21:060 ABDULLAPUR 400KV BAWANA-1 (187) CB B PHASE OPEN CHAP
- 6 _ EXHIBIT -6/V (page 3 of 4)
![Page 220: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/220.jpg)
ARC...02/01/10 21:44:21:060 ABDULLAPUR 400KV BAW-1 TIE (218) CIRCUIT BREAKER Y-PH OPEN ARC...02/01/10 21:44:21:062 ABDULLAPUR 400KV BAW-1 TIE (217) CIRCUIT BREAKER R-PH OPEN ARC...02/01/10 21:44:21:072 ABDULLAPUR 400KV BAWANA-1 (177) A/R LOCK OUT ALARM ARC...02/01/10 21:44:21:074 ABDULLAPUR 400KV BAW-1 TIE (209) A/R LOCKOUT ALARM ARC...02/01/10 21:44:21:094 ABDULLAPUR 400KV BAWANA-1 (149) M-2 RELAY INOPERATIVE RESET ARC...02/01/10 21:44:21:126 ABDULLAPUR 400KV BAWANA-2 (008) MAIN-1 Y-PH TRIP RESET ARC...02/01/10 21:44:21:128 ABDULLAPUR 400KV BAWANA-2 (007) MAIN-1 R-PH TRIP RESET ARC...02/01/10 21:44:21:128 ABDULLAPUR 400KV BAWANA-2 (009) MAIN-1 B-PH TRIP RESET ARC...02/01/10 21:44:21:178 ABDULLAPUR 400KV BAWANA-1 (119) MAIN-1 R-PH TRIP RESET ARC...02/01/10 21:44:21:178 ABDULLAPUR 400KV BAWANA-1 (120) MAIN-1 Y-PH TRIP RESET ARC...02/01/10 21:44:21:180 ABDULLAPUR 400KV BAWANA-1 (121) MAIN-1 B-PH TRIP RESET ARC...02/01/10 21:52:08:730 ABDULLAPUR 400KV BAWANA-1 (185) CB R PHASE CLOSE ARC...02/01/10 21:52:08:734 ABDULLAPUR 400KV BAWANA-1 (186) CB Y PHASE CLOSE ARC...02/01/10 21:52:08:734 ABDULLAPUR 400KV BAWANA-1 (187) CB B PHASE CLOSE ARC...02/01/10 21:54:00:708 ABDULLAPUR 400KV BAWANA-1 (125) M-1 A/R LOCK OUT ALARM ARC...02/01/10 21:54:00:720 ABDULLAPUR 400KV BAWANA-1 (122) MAIN-1 CARRIER RECEIVE ALARM ARC...02/01/10 21:54:00:764 ABDULLAPUR 400KV BAWANA-1 (122) MAIN-1 CARRIER RECEIVE RESET CHAP
- 6 _ EXHIBIT - 6/V (page 4 of 4)
![Page 221: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/221.jpg)
CHAPTE
R- -
6 _
EX
HIB
IT -6
/VI (
page
1 o
f 4)
~
~
it
• • t
~
<i1
<i1
0°
~ (>
~ Q , o
o " ., • ., B
mG
'~
i ~ , ' w 00
, I
~8~D~ ~ ~ ~ ~ICL ~ 05 8 ... --== N N ~ ~ § • 00... ...
~ ro
§
I , m
'7 '7
~
~
§
~ e ~
N
~ A
~ • 8
~ D
~ ,
-
a ~
§ , • , ~ <
•
~ R
" D
o -, ~
,
D
, " D C
~ ,
~ , ~ 8
~
w
~ , • ro ~
N
ro §
~
D
~
@ -~
" ~ ~
,
D
NNNNN :::::::::: NNNNN
![Page 222: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/222.jpg)
ARC...02/01/10 21:16:57:240 ABDULLAPUR BUS REACTOR-1 (361) MAIN CB R-PH OPEN ARC...02/01/10 21:16:57:270 ABDULLAPUR BUS REACTOR-1 (362) MAIN CB Y-PH OPEN ARC...02/01/10 21:16:57:272 ABDULLAPUR BUS REACTOR-1 (363) MAIN CB B-PH OPEN ARC...02/01/10 21:16:59:908 ABDULLAPUR TIE-ICT2 BR (315) TIE CB B PH OPEN ARC...02/01/10 21:16:59:912 ABDULLAPUR TIE-ICT2 BR (313) TIE CB R PH OPEN ARC...02/01/10 21:16:59:912 ABDULLAPUR TIE-ICT2 BR (314) TIE CB Y PH OPEN ARC...02/01/10 21:17:08:208 ABDULLAPUR BUS REACTOR-1 (366) 4789 R ISOLATOR CLOSE ARC...02/01/10 21:18:53:672 ABDULLAPUR BUS REACTOR-1 (361) MAIN CB R-PH CLOSE ARC...02/01/10 21:18:53:672 ABDULLAPUR BUS REACTOR-1 (362) MAIN CB Y-PH CLOSE ARC...02/01/10 21:18:53:694 ABDULLAPUR BUS REACTOR-1 (363) MAIN CB B-PH CLOSE ARC...02/01/10 21:19:16:176 ABDULLAPUR TIE-ICT2 BR (315) TIE CB B PH CLOSE ARC...02/01/10 21:19:16:178 ABDULLAPUR TIE-ICT2 BR (313) TIE CB R PH CLOSE ARC...02/01/10 21:19:16:178 ABDULLAPUR TIE-ICT2 BR (314) TIE CB Y PH CLOSE ARC...02/01/10 21:44:14:282 ABDULLAPUR 400KV BAWANA-2 (037) MAIN-2 RELAY IN OPERATIVE ALARM ARC...02/01/10 21:44:14:286 ABDULLAPUR 400KV BAWANA-1 (149) M-2 RELAY IN OPERATIVE ALARM ARC...02/01/10 21:44:20:976 ABDULLAPUR 400KV BAWANA-2 (007) MAIN-1 R-PH TRIP TRIP ARC...02/01/10 21:44:20:976 ABDULLAPUR 400KV BAWANA-2 (008) MAIN-1 Y-PH TRIP TRIP CHAP
Chapter- 6_ EXHIBIT - 6/VI (page 2 of 4)
![Page 223: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/223.jpg)
ARC...02/01/10 21:44:20:976 ABDULLAPUR 400KV BAWANA-2 (009) MAIN-1 B-PH TRIP TRIP ARC...02/01/10 21:44:21:006 ABDULLAPUR 400KV BAWANA-2 (074) CB Y-PH OPEN ARC...02/01/10 21:44:21:006 ABDULLAPUR TIE BAW2-NJ2 (106) CB Y-PH OPEN ARC...02/01/10 21:44:21:008 ABDULLAPUR 400KV BAWANA-2 (073) CB R-PH OPEN ARC...02/01/10 21:44:21:008 ABDULLAPUR 400KV BAWANA-2 (075) CB B-PH OPEN ARC...02/01/10 21:44:21:008 ABDULLAPUR TIE BAW2-NJ2 (097) A/R LOCKOUT ALARM ARC...02/01/10 21:44:21:008 ABDULLAPUR TIE BAW2-NJ2 (105) CB R-PH OPEN ARC...02/01/10 21:44:21:012 ABDULLAPUR TIE BAW2-NJ2 (107) CB B-PH OPEN ARC...02/01/10 21:44:21:024 ABDULLAPUR 400KV BAWANA-2 (065) A/R LOCKOUT ALARM ARC...02/01/10 21:44:21:028 ABDULLAPUR 400KV BAWANA-1 (119) MAIN-1 R-PH TRIP TRIP ARC...02/01/10 21:44:21:028 ABDULLAPUR 400KV BAWANA-1 (120) MAIN-1 Y-PH TRIP TRIP ARC...02/01/10 21:44:21:028 ABDULLAPUR 400KV BAWANA-1 (121) MAIN-1 B-PH TRIP TRIP ARC...02/01/10 21:44:21:044 ABDULLAPUR 400KV BAWANA-2 (037) MAIN-2 RELAY INOPERATIVE RESET ARC...02/01/10 21:44:21:058 ABDULLAPUR 400KV BAWANA-1 (186) CB Y PHASE OPEN ARC...02/01/10 21:44:21:058 ABDULLAPUR 400KV BAW-1 TIE (219) CIRCUIT BREAKER B-PH OPEN ARC...02/01/10 21:44:21:060 ABDULLAPUR 400KV BAWANA-1 (185) CB R PHASE OPEN ARC...02/01/10 21:44:21:060 ABDULLAPUR 400KV BAWANA-1 (187) CB B PHASE OPEN CHAP
Chapter- 6 _ EXHIBIT - 6/VI (page 3 of 4)
![Page 224: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/224.jpg)
ARC...02/01/10 21:44:21:060 ABDULLAPUR 400KV BAW-1 TIE (218) CIRCUIT BREAKER Y-PH OPEN ARC...02/01/10 21:44:21:062 ABDULLAPUR 400KV BAW-1 TIE (217) CIRCUIT BREAKER R-PH OPEN ARC...02/01/10 21:44:21:072 ABDULLAPUR 400KV BAWANA-1 (177) A/R LOCK OUT ALARM ARC...02/01/10 21:44:21:074 ABDULLAPUR 400KV BAW-1 TIE (209) A/R LOCKOUT ALARM ARC...02/01/10 21:44:21:094 ABDULLAPUR 400KV BAWANA-1 (149) M-2 RELAY INOPERATIVE RESET ARC...02/01/10 21:44:21:126 ABDULLAPUR 400KV BAWANA-2 (008) MAIN-1 Y-PH TRIP RESET ARC...02/01/10 21:44:21:128 ABDULLAPUR 400KV BAWANA-2 (007) MAIN-1 R-PH TRIP RESET ARC...02/01/10 21:44:21:128 ABDULLAPUR 400KV BAWANA-2 (009) MAIN-1 B-PH TRIP RESET ARC...02/01/10 21:44:21:178 ABDULLAPUR 400KV BAWANA-1 (119) MAIN-1 R-PH TRIP RESET ARC...02/01/10 21:44:21:178 ABDULLAPUR 400KV BAWANA-1 (120) MAIN-1 Y-PH TRIP RESET ARC...02/01/10 21:44:21:180 ABDULLAPUR 400KV BAWANA-1 (121) MAIN-1 B-PH TRIP RESET ARC...02/01/10 21:52:08:730 ABDULLAPUR 400KV BAWANA-1 (185) CB R PHASE CLOSE ARC...02/01/10 21:52:08:734 ABDULLAPUR 400KV BAWANA-1 (186) CB Y PHASE CLOSE ARC...02/01/10 21:52:08:734 ABDULLAPUR 400KV BAWANA-1 (187) CB B PHASE CLOSE ARC...02/01/10 21:54:00:708 ABDULLAPUR 400KV BAWANA-1 (125) M-1 A/R LOCK OUT ALARM ARC...02/01/10 21:54:00:720 ABDULLAPUR 400KV BAWANA-1 (122) MAIN-1 CARRIER RECEIVE ALARM ARC...02/01/10 21:54:00:764 ABDULLAPUR 400KV BAWANA-1 (122) MAIN-1 CARRIER RECEIVE RESET CHAP
-chapter 6 _ EXHIBIT -6/VI (page 4 of 4)
![Page 225: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/225.jpg)
CHAPTER- - 6 _ EXHIBIT - 6/VII (page 1 of 6)
02 .01.1021 « .36.702 .ooo.dat · 02J0112010· 21 :~~:36.702 (Peak Type) Page: 1
CH RMS InatPeak RelY"
I J . 0.147 - 1.~72 -0.147 -G.234
J
1.229 -1 .706 224.$37" -1 .229 1.'80
1.489 1.506 99.551 " 1.489 -1.377
0.120 0.120 92.421" 0.120 -0.,,8
13.595 -n.182 -13.595 .......
66.861 231.205· -86.881 17.032
80.000 84 .511 00.000 -70.384
0 .0'3 0.078 0.013 -G.03O
0.017 0.017 140.055" 0.017 0.000
87 .187 -86.025 231 .022" -87.187 78.348
172 DlST : tVmemory "'"'*1U A N 21 :44:37.882000 00'
177 - --~
02J0112010 21 :«:37 .353000
OT' 02t'01I2010 21 :44 :37.832000 Dt: 29000 miaosec - 1 .~5 eye 1000.0000 AS: ...... Delta v ; 0.087 A
._- - _ . . . --- -----------
![Page 226: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/226.jpg)
CHAPTER--6 _ EXHIBIT - 6/VII (page 2 of 6)02.01 .10 11 .44.36.702.000.dat - Om112010 - 21 :44:36.702 (Peak Type)
CH RMS
0.234 -1.48' 187.317" -0.234 -0.234
1.480 1.7'. 58.97r 1._ 1."""
1.377 -1 .508 293.893" -1.377 -1.377
0.116 -0.'22 -0.118 -0.118
..... -77 .375 183.184" ...... -8 ....
77.932 8~U0!5 65.73'" 77.932 77.932
70.384 -84.421 301.960" -70.384 -70.384
0.039 -0.117 202.574° -0.039 -0.039
0.000 0.017 334.89r 0.000 0.000
10 85.804 &5.547" 78.348 78.348
26
'3 .. .. .,
----------------------------~--------------------------i A ~S : PS1~
54
50
56
57 .. 59 --_ .......•
1 N OOT : T~ ligna!
j A DlST : Starq I» A
· A 018T : Sta"ting I>,. 8
· A 018T Slafting I"" C
· A MAIN : General startno , A MAIN : Starting A
----lA - -~.- :
!N
MAIN : S\ar1ing B
MAIN : S'-'ng C
MAIN : SWrting GF
DlST : Zero-aequo NI1Ing
A A
000
000
N N 21:44:37 .831000 21 :44:37.878000 002
N N 21:"':37 .~ 11 :44:37.88UOOO 002
N N 21:44:36.802000 21 :44:37.8MIOOO 002
N N 21:44:37.147000 21 ;44:37.887000 002
N N 21:44:38.802000 21 :44:37.887000 002
N N 21:44:37 .2~ 21 :44:31.88QOOO 002
N N 21 :44:30.802000 21 :44:37.8e8000 002
N N 21:<"':31 .'41000 21:< ... :37.881000 002
N N 21 :44:36.902000 21:0"':37.887000 004
N N 21:44:36.D02000 21:44:37.887000 004
60
.2 63 ..
.--1 A 015T: Fault forwwd IlS N N 21:44:3&.819000 21 :44;37.882000 002
I A 015T : 11 _PHd
._ .. _-- A OIST : t2 e\IIpMd
. _ .. _. - . N OIST : tJlMpeed
OW'12010 21 :44:37.3S3000
OT: 02lO1I201021 :44:37.803000 Dt OmlCfosec· OOOCyc 1000.0000 AS : "'+ Oeltay: O.OOO A
- --------- - - -- _. _ .. __ .. _--- - -
N N 21:44:3&.81901X1 21 :44:37.882000 002
N N 21:44:37.208000 21 :44:37.882000 002
N N 21 :44:37.807000 21 :44:37.882000 002
![Page 227: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/227.jpg)
CHAPTER-- 6 _ EXHIBIT - 6/VII (page 3 of 6)
PANIPAT-2MAIN-II * File Information:: * -------------------
Station: Device: COMTRADE
File Name: C:\DOCUMENTS AND SETTINGS\ADMINISTRATDR\ MY DOCUMENTS\Sl STUDIO\DISTANCE\P437 PANIPAT2MAIN2\3\DR\02.01.10 21.44.36.702 .000.dat
File Size: 182640 Bytes prefault Time: 02/01/2010 21 : 44:36.702000
Fault Time: 02/01/2010 21 : 44:36.702000 Save Time: 01/05/2010 17 : 46:32
Process Time: 01/08/201009 : 58:23 start Date && Time: 02/01/2010 21 :44:36.702000
End Date && Time: 02/01/2010 21 :44:38.984000 File Duration: 2 sec(s) - 282 Mils(s)
Sampling Frequency: 1000.000000 , 1000 Microsecond Reading Line Frequency: 50.000000
* Highest/Lowest Analog peaks Chart :: * - -------------------------- - ---- - --> Max-val Min-val LPeak-up LPeak-Dn oneBi t
HP-Di f. LP-Dif. 1. 506 -1. 506 -0.026 -0.017 0.0000 0.000 188.000 1. 740 -1. 732 0.017 0.017 0.0001
162.000 0.000 1. 541 -1. 541 -0.017 0.017 0.0000 0.000 0.000 0.122 -0.862 -0 .004 0.011 0.0000
28140.000 263.000 80.535 -82.153 76 .974 -76.846 0.0025
645.000 51.000 93.443 -87 . 373 80.159 -80.225 0.0029
2128.000 23.000 86.659 -86.635 81.442 -81.402 0.0026 9 .000 15.000 0 . 104 -0 . 129 0.052 -0.026 0 .0000
6552 .000 6552 .000 0.026 -0.017 0.017 0.026 0.0000
10920.000 10920.000 88.006 -88.057 83.966 -84.200 0.0027 19.000 87.000
* EventS/Sensors Activity summary: * --- ---------------------- --------
punits Description
A I-Current IA A
A 2-Current IB B
A 3-Current IC C
A 4-Current IN E
v 5-voltage A-G A
v 6-voltage B-G B
v 7-voltage C-G C
v 8-voltage VNG E
A 9-Current IN. par
v lO-voltage vref
>Fst Lst Fst-change Lst-change Changes Description A A xx:xx:xx.xxxxxx xx :xx :xx.xxxxxx 000 6-ARC CB drive ready EXT A A xx:xx:xx.xxxxxx xx :xx:xx . xxxxxx 000 26- PSS PS 1 active N N 21:44: 37.831000 21 :44:37 . 876000 002 43-DIST Tri p si gnal N N 21:44:37.255000 21 :44:37.869000 002 45-DIST starting 1» A N N 21:44:36.802000 21 :44:37.869000 002 46-DIST Starting I» B N N 21:44:37.147000 21 : 44:37.887000 002 47- DIST Starting 1» C N N 21:44:36 . 802000 21 : 44:37 . 887000 002 54-MAIN General starting N N 21:44:37 . 255000 21 :44: 37 . 869000 002 55-MAIN Starti ng A N N 21:44 : 36 .802000 21 :44 : 37 . 869000 002 56-MAIN Starting B N N 21:44:37.147000 21 :44 : 37 . 887000 002 57-MAIN Starting C N N 21: 44: 36.802000 21 :44:37 . 887000 004 58-MAIN starting GF N N 21:44: 36. 802000 21:44:37.887000 004 59-DIST zero-sequ. starting N N 21:44:36.819000 21 :44:37 .892000 002 60-DIST Fault forward / LS N N 21:44:36.819000 21 :44:37 .892000 002 62-DIST t1 elapsed N N 21: 44: 37.208000 21:44:37.892000 002 63-DIST t2 elapsed N N 21:44:37.807000 21 :44:37 .892000 002 64-DIST t3 elapsed N N 21:44:37.807000 21 :44:37 .892000 002 65-DIST t4 elapsed N N 21:44:37.807000 21 :44:37 .892000 002 66-DIST t5 elapsed
Page 1
- --- ---_._ .. _--_.-
![Page 228: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/228.jpg)
CHAPTER-- 6 _ EXHIBIT - 6/VII (page 4 of 6)
N N N N N N N N N A N A N N A A N N N A N N A N N N A A A A A A N N N N N N N N N A A A A A A A A A
N N N N N N N N N A N A N N A A N N N A N N A N N N A A A A A A N N N N N N N N N A A A A A A A A A
PANIPAT-2MAIN-II 21:44:37 . 831000 21 :44:37.933000 21:44:37.831000 21 :44:37.876000 21:44:37.831000 21 :44:37.876000 21:44:37.831000 21 : 44:37.876000 21:44:37.831000 21 : 44 : 37.876000 21:44:37.831000 21 :44:37.933000 21:44:37.831000 21 : 44:37.933000 21:44:37.831000 21 : 44:37.933000 21:44:37.831000 21:44:37.933000 xx:xx:xx.xxxxxx xx:xx:xX.xxxxxx 21:44:37.265000 21:44:37.892000 xx:xx:xx.xxxxxx xx : xx : xX.xxxxxx 21:44:36.819000 21:44 : 37.961000 21:44:36.802000 21:44 : 37.961000 xx:xx:xx.xxxxxx xx:xx:xx.xxxxxx xx:xx:xx.xxxxxx xx : xx : xX.xxxxxx 21:44:37.875000 xx:xx:xx.xxxxxx 21:44:37.875000 xx : xx:xx.xxxxxx 21: 44: 37 . 875000· xx : xx: xx. xxxxxx 21:44:37.892000 xx :xx:xx.xxxxxx 21:44:37.831000 21 :44:37.876000 21:44:37.831000 21:44:37.876000 xx:xx:xx.xxxxxx xx:xx:xx.xxxxxx 21:44:37.875000 xx :xx:xx.xxxxxx 21:44:37.891000 xx :xx:xx.xxxxxx 21:44:37.875000 xx :xx:xX.xxxxxx xx:xx:xX.xxxxxx xx :xx:xx.xxxxxx xx:xx:xX.xxxxxx xx:xx:xx.xxxxxx xx:xx:xx.xxxxxx xx : xx:xX.xxxxxx xx:xx:xx.xxxxxx xx : xx :xX.xxxxxx xx:xx:xx.xxxxxx xx : xx:xx.xxxxxx xx:xx:xx.xxxxxx xx:xx:xx.xxxxxx 21:44:37.941000 21:44:38 .048000 21:44:37.265000 21:44:37 .876000 21:44:36.819000 21 :44 : 37.876000 21:44 : 37 . 154000 21 : 44:37 .892000 21:44:36.819000 21 :44:37.892000 21:44:36.832000 21 :44:37.892000 21:44:36.819000 21 :44:36.832000 21:44:37.265000 21 :44:37.892000 21:44:37.288000 21 :44:37.876000 xx:xx:xx.xxxxxx xx :xx:xx.xxxxxx xx:xx:xx.xxxxxx xx :xx:xx.xxxxxx xx:xx:xx.xxxxxx xx:xx:xx.xxxxxx xx:xx:xx.xxxxxx xx :xx:xX.xxxxxx xx:xx:xX.xxxxxx xx :xx:xX.xxxxxx xx:xx:xx.xxxxxx xx:xx:xX.xxxxxx xx:xx:xx.xxxxxx xx:xx:xx.xxxxxx xx:xx:xx.xxxxxx xx : xx:xX.xxxxxx xx:xx:xx.xxxxxx xx:xx:xx.xxxxxx
002 002 002 002 002 002 002 002 002 000 002 000 002 002 000 000 001 001 001 001 002 002 000 001 001 001 000 000 000 000 000 000 002 002 002 002 004 002 002 002 002 000 000 000 000 000 000 000 000 000
67-MAIN 68-MAIN 69-MAIN 70-MAIN 71-MAIN 72-MAIN 73-MAIN 74-MAIN 75-MAIN 77-ARC 85-DIST 93-PSIG 97-FT_RC: 99-FT_RC:
100-ARC : 129-GFSC 137-LOGIC: 138-LOGIC: 139-LOGIC: 172-DIST : 177-DIST : 181-DIST 188-LOGIC: 194-LOGIC: 196-LOGIC: 198-LOGIC: 246-BUOC 247-MCMON: 248-PSB : 249-S0TF 253-LOGIC: 254-v<> 317-MAIN 352-DIST 354-DIST 356-DIST 358-DIST 362-DIST 363-DIST 365-DIST 371-DIST 373-DIST 392-LOGIC: 393- LOGIC: 394-LOGIC: 395-LOGIC: 396-LOGIC: 397-LOGIC: 398-LOGIC: 399-LOGIC:
Gen. tr1p command 1 Gen. trlp signal 1 Trip signal 1. A Trip signal 1. B Trip si~nal 1. C Gen. trlp command Trip command 1. A Tr1p command 1. B Trlp command 1. C Not ready Dir.using vmeas sys1 Enabl ed System disturb. runn Record. in progress Blocked Enabled Input 1 EXT Input 2 EXT Input 3 EXT tvmemory running Trip signal zone 5 Trip sig. zone 2-8 output 4 Output 7 Output 8 output 9 Enabled Enabled Enabled Enabled Enabled Enabled Fi na 1 tri p Fault forwd. / LS. A Fault forwd. / LS. B Fault forwd. / LS. C With . par. line compo Dir.using vmeas sys2 Dir.using vmem Sys2 Dir.using Vmeas Sys3 Impedance in zone 6 Enabl ed 1 set externally 2 set externally 3 set externally 4 set externally 5 set externally 6 set externally 7 set externally 8 set externally
• Events/Sensors Activity Log : * -------------------------- - --> State
A A A A A A A A A
Trigger-Time 02/01/2010 21 44:36.802000 02/01/2010 21 44:36.802000 02/01/2010 21 44:36.802000 02/01/2010 21 44:36.802000 02/01/2010 21 44:36.802000 02/01/2010 21 44:36.802000 02/01/2010 21 44:36.819000 02/01/2010 21 44:36.819000 02/01/2010 21 44:36.819000
Description 46-DIST Starting I» B 54-MAIN : General starting i6-MATN StartiRg B 58-MAIN: Starting GF 59-DIST : Zero-sequ . starting 99-FT_RC: Record. in progress 60-DIST : Fault forward / LS 62-DIST t1 elapsed 97-FT_RC: System disturb . runn
page 2
~1 . lt4 : "3" . go'l- l»ta Jt\ . 4,-\ ·."?>,. 1'11· P"C ':1 ' 44: '3} . .:I n;- P> 11 .ll1.~~.3,.813 .t.1e.ioJ'lttl
3'" ~~ l-n-P- 10 H.gq -n.-i'1.t.r~ .n.~'l\ oi.,... hip5~ ~1.g31 ~.I>'·i(
![Page 229: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/229.jpg)
CHAPTER- - 6 _ EXHIBIT - 6/VII (page 5 of 6)
N
N N
N
N N N N
N N N N N N N N N
N N N N N N
N N
A A A A
A A
A
A A A A A A A A A A A A A A A A A A A A A A
A A A A A A A
A
A
PANIPAT-2MAIN-II 02/01/2010 21 44 36.819000 354-0IST Fault forwd. / LS. B 02/01/20102144 36.819000 358-0IST With. par.line compo 02/01/2010 21 44 36.819000 363-0IST Oir.usin9 vmem sys2 02/01/2010 21 44 36.832000 362-0IST oir.using vmeas Sys2 02/01/2010 21 44 36.832000 363-0IST oir.using Vmem sys2 02/01/2010 21 44 37.147000 47-0IST starting I» C 02/01/2010 ~1 44 37 147000 57-MAIN Starting C 02/01/2010 21 44:37.147000 58-MAIN Starting GF 02/01/2010 21 44:37.147000 59-0IST zero-sequ. starting 02/01/2010 21 44:37.154000 356-0IST Fault forwd. / LS. C 02/01/20102144:37.154000 358-0IST With. par.line compo 02/01/2010 21 44:37.208000 63-0IST t2 elapsed 02/01/2010 2] 44·37 255000 45-0IST Starting I» A 02/01/2010 21:44:37.255000 55-MAIN Starting A 02/01/2010 21:44:37.265000 85-0IST oir.using Vmeas sys1 02/01/2010 21:44:37.265000 352-0IST Fault forwd. / LS. A 02/01/2010 21:44:37.265000 365-0IST oir.using vmeas sys3 02/01/2010 21:44·37 288000 371-0IST Impedance in zone 6 02/01/2010 21:44:37.807000 64-0IST t3 elapsed 02/01/2010 21:44:37.807000 65-0IST t4 elapsed 02/01/2010 21:44:37.807000 66-0IST t5 elapsed 02/01/2010 21: 4't!4~:~3'b7-". 8~3~1!-!!0~0~0_-:!4~3=.-QLLIj.;S~T,..-'-_T~ruju.p~s.l..ij 9IUnl.!!.Ja 1 02/01/2010 21:44:37.831000 67-MAIN Gen. tr1p command 1 02/01/2010 21:44:37.831000 68-MAIN Gen. trip signal 1 02/01/2010 21:44:37.831000 69-MAIN Trip signal 1. A 02/01/2010 21:44:37.831000 70-MAIN Trip signal 1. B 02/01/2010 21:44:37.831000 71-MAIN Trip si9nal 1. C 02/01/2010 21:44:37.831000 72-MAIN Gen. tr1p command 02/01/2010 21:44:37.831000 73-MAIN Trip command 1. A 02/01/2010 21:44:37.831000 74-MAIN Trip command 1. B 02/01/2010 21:44:37.831000 75-MAIN Trip command 1. C 02/01/2010 21:44:37.831000 177-0IST Trip signal zone 5 02/01/2010 21:44:37.831000 181-0IST Tr1p S1g. zone 2-8 02/01/2010 21:44:37.869000 45-0IST starting I» A 02/01/2010 21:44:37.869000 46-0IST Starting I» B 02/01/2010 21:44:37.869000 55-MAIN Starting A 02/01/2010 21:44:37.869000 56-MAIN starting B 02/01/2010 21:44:37.869000 58-MAIN starting GF 02/01/2010 21:44:37.869000 59-0IST: Zero-sequ. starting 02/01/2010 21:44:37.875000 137-LOGIC: Input 1 EXT 02/01/2010 21:44:37.875000 138-LOGIC: Input 2 EXT 02/01/2010 21:44:37.875000 139-LOGIC: Input 3 EXT 02/01/2010 21:44:37.875000 194-LOGIC: Output 7 02/01/2010 21:44:37.875000 198-LOGIC: Output 9 02/01/2010 21:44:37.876000 43-0IST Trip si9nal 02/01/2010 21:44:37.876000 68-MAIN Gen. tr1p signal 1 02/01/2010 21:44:37.876000 69-MAIN Trip signal 1. A 02/01/2010 21:44:37.876000 70-MAIN Trip signal 1. B 02/01/2010 21:44:37.876000 71-MAIN Trip signal 1. C 02/01/2010 21:44:37.876000 177-0IST Trip signal zone 5 02/01/2010 21:44:37.876000 181-0IST Trip sig. zone 2-8 02/01/2010 21:44:37.876000 352-0IST Fault forwd. / LS. A 02/01/2010 21:44:37.876000 354-0IST Fault forwd. / LS. B 02/01/201021:44:37.876000 358-0IST With. par. line compo 02/01/2010 21:44:37.876000 371-0IST Impedance in zone 6 02/01/2010 21:44:37.887000 47-0IST Starting I» C 02/01/2010 21:44:37.887000 54-MAIN General starting 02/01/2010 21:44:37.887000 57-MAIN Starting C 02/01/2010 21:44:37.887000 58-MAIN Starting GF 02/01/2010 21:44:37.887000 59-0IST: zero-sequ. starting 02/01/2010 21:44:37.891000 196-LOGIC: Output 8 02/01/2010 21:44:37.892000 60-0I5T: Fault forward / L5 02/01/2010 21:44:37.892000 62-0I5T: t1 elapsed
page 3
![Page 230: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/230.jpg)
CHAPTER-- 6 _ EXHIBIT - 6/VII (page 6 of 6)
N N N N N N N N N N N N N N N
N N N
A
02/01/2010 21 44 37.892000 02/01/2010 21 44 37.892000 02/01/2010 21 44 37.892000 02/01/2010 21 44 37.892000 02/01/2010 21 44 37.892000 02/01/2010 21 44 37.892000 02/01/2010 21 44 37.892000 02/01/2010 21 44 37.892000 02/01/2010 21 44 37.892000 02/01/2010 21 44 37.892000 02/01/2010 21 44 37.933000 02/01/2010 21 44 37.933000 02/01/2010 21 44 37.933000 02/01/2010 21 44 37.933000 02/01/2010 21 44 37.933000 02/01/2010 21 44 37.941000 02/01/2010 21 44 37.961000 02/01/2010 21 44 37.961000 02/01/2010 21 44 38.048000
PANIPAT-2MAIN-II 63-DIST 64-DIST 65-DIST 66-DIST 85-DIST
172-DIST 356-DIST 358-DIST 362-DIST 365-DIST
67-MAIN 72-MAIN 73-MAIN 74-MAIN 75-MAIN
317-MAIN : 97-FT_RC: 99-FT_RC:
317-MAIN :
t2 elapsed t3 elapsed t4 elapsed t5 elapsed Dir.using Vmeas sys1 tVmemory running Fault forwd. / LS. C With. par. line compo Dir.using vmeas Sys2 Dir.using vmeas Sys3 Gen. trip command 1 Gen. trip command Trip command 1. A Trip command 1. B Trip command 1. C Final trip System disturb. runn Record. in progress Final trip
page 4
![Page 231: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/231.jpg)
Page 1
DTL\Org2\BAMNAULI\BALLABHG\REL51123.1\10010224.REH Station: BAMNAULI Object: BALLABHGARH-2 2 JAN 2010 21:36:58.912
[ms]
-100
-100
0
0
100
100
200
200
300
300
400
400
500
500
600
600
700
700
800
800
900
900
1000
1000
0
U1 200 kV
0
I1 10000 A
0
U2 200 kV
0
I2 10000 A
0
U3 200 kV
0
I3 10000 A
0
U4 200 kV
CHAPTER- - 6 _ EXHIBIT - 6 /VIII (page 1 of 4)
I _
I ____ _
I --v-- v-- '¥ v ~AFV ~~~~~~~~~
I _____ _
I ~ V'o"d
I~~~~~~ ____ ~~~~~
![Page 232: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/232.jpg)
Page 1
DTL\Org2\BAMNAULI\BALLABHG\REL51123.1\10010224.REH Station: BAMNAULI Object: BALLABHGARH-2 2 JAN 2010 21:36:58.912
[ms]
-100
-100
0
0
100
100
200
200
300
300
400
400
500
500
600
600
700
700
800
800
900
900
1000
1000
0
I4 10000 A
GENERAL-TRIPTRIP-R-PH
TRIP-Y-PHTRIP-B-PH
AR-OPTDR-PHASE
Y-PHASEB-PHASE
NEUTRALZONE1-START
ZONE2-STARTZONE3-START
CHAPTER-- 6 _ EXHIBIT - 6 /VIII (page 2 of 4)
~ I I I I I I
v v
I I I I I I I I I I
![Page 233: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/233.jpg)
Page 1
DTL\Org2\BAMNAULI\BALLABHG\REL51123.1\10010225.REH Station: BAMNAULI Object: BALLABHGARH-2 2 JAN 2010 21:37:00.902
[ms]
-100
-100
0
0
100
100
200
200
300
300
400
400
500
500
600
600
700
700
800
800
900
900
1000
1000
0
U1 50 kV
0
I1 10000 A
0
U2 50 kV
0
I2 10000 A
0
U3 50 kV
0
I3 10000 A
0
U4 50 kV
CHAPTER--6_ EXHIBIT - 6 /VIII (page 3 of 4)
![Page 234: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/234.jpg)
Page 1
DTL\Org2\BAMNAULI\BALLABHG\REL51123.1\10010225.REH Station: BAMNAULI Object: BALLABHGARH-2 2 JAN 2010 21:37:00.902
[ms]
-100
-100
0
0
100
100
200
200
300
300
400
400
500
500
600
600
700
700
800
800
900
900
1000
1000
0
I4 10000 A
GENERAL-TRIPTRIP-R-PH
TRIP-Y-PHTRIP-B-PH
AR-OPTDR-PHASE
Y-PHASEB-PHASE
NEUTRALZONE1-START
ZONE2-STARTZONE3-START
CHAPTER--6_ EXHIBIT - 6 /VIII (page 4 of 4)
![Page 235: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/235.jpg)
CHAPTE
R--
6 _
EX
HIB
IT - 6/
IX (p
age
1 of
4)
~
~
it
• • t
~
<i1
<i1
0°
~ (>
~ Q ,
o
o " ., • ., B
mG
'~ ,
~ ~
~
~ ~
2 ,
~ 5
§
i §
~ •
R , §
~ , ~ ,
~ c
~
~
" , " <
--- --- ------ --- ---
§ ~
~
~
5
~
,
~
~
~ ~ , ~ o
" ~
~ , o
~
-5
~
~
~ ~
~
~
§
~
,
- -- -- ---- -- -- -- '- -- -- -- -'
, ~ '> '; ~ ~ ? < c:::=--' S:--. Y lnl 1 1 1 1 W ,, ~NCO"' ''''''''- ~ 1 00 ~NCO'"
![Page 236: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/236.jpg)
CHAPTE
R- -
6 _
EX
HIB
IT - 6/
IX (p
age
2 of
4) ~
it
• • t
~
<i1
<i1
0°
~ (>
~ Q , o
o " ., . ., B
mG
'~
i ~ , ' w 00
8
~ ~ ~
~
~ ~
2 ,
§
~ , ~ 5
§
i §
~ •
N
§
~ R , §
~ , ~ ,
o
§
~
~ c
~
~
" , 5
<
•
•
~
§ ~
~
~
5
~
,
w
w
~ c
~
~
~ ~ , ~ w 5
~
w
~
~
~ , w
~ o 5
~
~
N
~
~
~ ~
~
~
§
~
,
ro
![Page 237: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/237.jpg)
EXHIBIT - 4 - IV - b* 18:45:02:420 (0221) MOGA-1-PATIALA AUTORECLOSE L/O* 18:45:36:175 (0221) MOGA-1-PATIALA AUTORECLOSE L/O* 18:45:36:495 (0221) MOGA-1-PATIALA AUTORECLOSE L/O* 18:52:54:395 (0221) MOGA-1-PATIALA AUTORECLOSE L/O* 18:53:14:795 (0221) MOGA-1-PATIALA AUTORECLOSE L/O* 18:57:35:805 (0221) MOGA-1-PATIALA AUTORECLOSE L/O* 18:58:49:580 (0453) MOGA-PATIALA CLOSE IMP TO 400KV TIE C.B. R 18:58:49:635 (0451) MOGA-PATIALA TIE 400KV C.B. Y- PH CLOSED R 18:58:49:640 (0450) MOGA-PATIALA TIE 400KV C.B. R- PH CLOSE R (0452) MOGA-PATIALA TIE 400KV C.B. B- PH CLOSED * 18:58:49:850 (0453) MOGA-PATIALA CLOSE IMP TO 400KV TIE C.B. R 19:26:13:690 (0445) CLOSE IMPULSE TO BUS REACTOR C.B.* 21:44:19:590 (0068) BAWANA MAIN-2 PROT OPTD - B PH A (0070) BAWANA MAIN-2 PROT UNHEALTHY 21:44:19:595 (0388) BAWANA 400KV C.B. R - PH OPENED (0389) BAWANA 400KV C.B. Y - PH OPENED (0390) BAWANA 400KV C.B. B - PH OPENED (0378) ILT1-BAWANA TIE 400KV C.B. R - PH OPENED
(0379) ILT1-BAWANA TIE 400KV C.B. Y - PH OPENED
21:44:19:600 (0380) ILT1-BAWANA TIE 400KV C.B. B - PH OPENED
* 21:44:19:605 (0066) BAWANA MAIN-2 PROT OPTD - R PH* (0069) BAWANA MAIN-2 PROT OPTD PH-PH* 21:44:19:610 (0067) BAWANA MAIN-2 PROT OPTD - Y PH R (0070) BAWANA MAIN-2 PROT UNHEALTHY* 21:44:19:615 (0049) ICT1-BAWANA TIE 400KV C.B. AUTORECLOSE L/O* 21:44:19:625 (0081) BAWANA AUTORECLOSE L/O* 21:44:19:660 (0067) BAWANA MAIN-2 PROT OPTD - Y PH* (0068) BAWANA MAIN-2 PROT OPTD - B PH* 21:44:19:665 (0066) BAWANA MAIN-2 PROT OPTD - R PH* (0069) BAWANA MAIN-2 PROT OPTD PH-PH* 21:48:29:465 (0081) BAWANA AUTORECLOSE L/O* 21:48:34:530 (0049) ICT1-BAWANA TIE 400KV C.B. AUTORECLOSE L/O 21:48:55:105 (0391) BAWANA CLOSE IMP TO 400KV C.B. 21:48:55:185 (0388) BAWANA 400KV C.B. R - PH CLOSED 21:48:55:190 (0389) BAWANA 400KV C.B. Y - PH CLOSED (0390) BAWANA 400KV C.B. B - PH CLOSED 21:48:55:430 (0391) BAWANA CLOSE IMP TO 400KV C.B. 21:49:04:705 (0378) ILT1-BAWANA TIE 400KV C.B. R - PH CLOSED
(0380) ILT1-BAWANA TIE 400KV C.B. B - PH CLOSED
21:49:04:710 (0379) ILT1-BAWANA TIE 400KV C.B. Y - PH CLOSED
* 21:49:20:265 (0056) BAWANA MAIN-1 PROT OPTD - B PH* (0058) BAWANA MAIN-1 PROT OPTD IN ZONE-1 TIME* 21:49:20:270 (0068) BAWANA MAIN-2 PROT OPTD - B PH 21:49:20:275 (0390) BAWANA 400KV C.B. B - PH OPENED (0380) ILT1-BAWANA TIE 400KV C.B. B - PH OPENED
Page 2CHAP
- chapter 6 _ EXHIBIT -6/IX (page 3 of 4)
![Page 238: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/238.jpg)
EXHIBIT - 4 - IV - b
* 21:49:20:285 (0049) ICT1-BAWANA TIE 400KV C.B. AUTORECLOSE L/O* 21:49:20:295 (0056) BAWANA MAIN-1 PROT OPTD - B PH* (0058) BAWANA MAIN-1 PROT OPTD IN ZONE-1 TIME 21:49:20:300 (0379) ILT1-BAWANA TIE 400KV C.B. Y - PH OPENED
21:49:20:305 (0378) ILT1-BAWANA TIE 400KV C.B. R - PH OPENED
DATE 02:01:2010 TIME 21:49:26:545 HISSAR EVENT LOGGER
* 21:49:20:340 (0068) BAWANA MAIN-2 PROT OPTD - B PH 21:49:21:425 (0390) BAWANA 400KV C.B. B - PH CLOSED * 21:49:21:445 (0056) BAWANA MAIN-1 PROT OPTD - B PH* (0058) BAWANA MAIN-1 PROT OPTD IN ZONE-1 TIME 21:49:21:465 (0390) BAWANA 400KV C.B. B - PH OPENED * 21:49:21:480 (0081) BAWANA AUTORECLOSE L/O* (0056) BAWANA MAIN-1 PROT OPTD - B PH* (0058) BAWANA MAIN-1 PROT OPTD IN ZONE-1 TIME 21:49:21:495 (0388) BAWANA 400KV C.B. R - PH OPENED (0389) BAWANA 400KV C.B. Y - PH OPENED * (0066) BAWANA MAIN-2 PROT OPTD - R PH* (0068) BAWANA MAIN-2 PROT OPTD - B PH* 21:49:21:505 (0067) BAWANA MAIN-2 PROT OPTD - Y PH* 21:49:21:515 (0069) BAWANA MAIN-2 PROT OPTD PH-PH* 21:49:21:560 (0066) BAWANA MAIN-2 PROT OPTD - R PH* (0067) BAWANA MAIN-2 PROT OPTD - Y PH* (0068) BAWANA MAIN-2 PROT OPTD - B PH* 21:49:21:565 (0069) BAWANA MAIN-2 PROT OPTD PH-PH* 21:51:54:785 (0081) BAWANA AUTORECLOSE L/O* 21:51:56:325 (0049) ICT1-BAWANA TIE 400KV C.B. AUTORECLOSE L/O* 21:56:48:200 (0221) MOGA-1-PATIALA AUTORECLOSE L/O A 21:56:48:205 (0450) MOGA-PATIALA TIE 400KV C.B. R- PH OPEN
A (0451) MOGA-PATIALA TIE 400KV C.B. Y- PH OPENED A (0452) MOGA-PATIALA TIE 400KV C.B. B- PH OPENED * 22:04:39:830 (0400) KAITHAL-ICT-2 TIE 400KV C.B. R-PH OPEN
* (0401) KAITHAL-ICT-2 TIE 4OOKV C.B. Y-PH OPEN
* 22:04:39:835 (0402) KAITHAL-ICT-2 TIE C.B. B PH OPEN A 22:04:40:200 (0097) NLGH1-ILT2 TIE 400KV C.B. AIR PR LOW* 22:04:43:465 (0484) 400KV FATEHABAD C.B. B - PH OPENED * 22:04:43:470 (0482) 400KV FATEHABAD C.B. R - PH OPENED * (0483) 400KV FATEHABAD C.B. Y - PH OPENED
Page 3CHAP
- 6 _ EXHIBIT - 6/IX (page 4 of 4)
![Page 239: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/239.jpg)
CHAPTER--6 _ EXHIBIT - 6/X (page 1 of 1)
Po rv.pJ4-1 rnc..,:y, - ?-- \f'44?-) 02 Januaty 2010 21.56.2!HM10.da1 01J02110 · 21 :56:25.300 (Peak Type) PItQe: l
CH
10
11
12
13 ,. .. ,.
., {i j\ i\ (\, i\ t\ (\ i\ i\ J .: .' "
, '\ ! \ ,
\ : \ \ i i ! , I , ! \ ! : i il\ , I I , I i i I i i
"
, J i, I , I I , \ \. j ii,' 'I I II I
'I, I
I""i II " i
',,' \i \/ \/ \/ '\i ',i
\J '-)
:\, ;\, !\ ,n, ,/\ f\ I!\ ('I r'", n !'\ '\ ;\1 !\ ,,(I , "I I I I \ I I I II \ ; \'" I ,. I! ' " \ i \! \ I \ I ~ , \ I \ I' ;:! \ : ~
\ f \i \/ \j \.' \ I \/ \.! :.' ;;' ;: ~j ,: , I
.MS
.. , 'I , 32092.403
, : , i 1 215217.615 \ I ~ .' I
\j'
"'''''_
167046.439
-268875.789
-276826.008
Phase """'01 ."""
108.301" 185456.842 103224.272
356.005" -80U8.700 -324809.93
-217388.00 184320.000
- __ -f\/ 'l I
56385.719 -76~2.662 289.806" -60864.,", -44003.487
12494.126 18716.872 29.25" 11314 .~ -7051 .974
1597.023 -2433.525 352.924" -234.790 -2336.847
1738.3'9 -2613.070 227.672" -2027.477 1767.163
: 12159.302 18064.986 21 .343" 9051 .829 ·7618.231
· N RLI TRIPA
: N Rl2TRIPB
N N 21 :56:25.35eOO1 21 :56:25.365501 002
," .. -/ N
" " Rl3TRIPC N N
Rl7 CARRIER SEND N N
000
000
000
-----------...;1 N Al13 START AR N N 21:56:25 .359001 21 :56:25.55900' 002
-----------------______________ A Rlt4 BlOCKAR A N 21 :56:2fJ.868001
I N Rl, 5 PSB " " -----------------.,....-----------~ A Rl,6ANY TRIP A N 21:56:26 .ea8001 . --.-.. ----.;.--+--- ---- ----.- ... I N Rlt7 CARIER SEND N N
-------------------+------------...,IA RL18TIECBAR AN 21;56:26.688001
----tl- --- • j N L3 CRRECEIVE N N
· N L4 MANUAL CB CLS N N
0'" 000
001
000
001
000
000
--------__________ ----------__ A l5T3PHARFAIl AN 21 :56:26.711501 21 :58:27.e09001 003
---------------------r-----------------------A ~S~ ------------------+------------~iA ~T~
· A Zl
O, ,Q2J20 10 2 1 ;56:25.070501
A N 21 :56:28.688001
A N 21 :56:26.688001
PANIPAT MAIN - 2 OT: 01102/201021 :56:25_325001 0 1: 25000 microsee - 1.25 eye 2000_0000 AS: ++ Dena Y: 62232.570 V
001
001
![Page 240: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/240.jpg)
CHAPTE
R- -6
_ E
XH
IBIT
- 6/
XI (
page
1 o
f 5)
, R ~ ~ o
~ 5
~
~
it
• • t
~
<i1
<i1
0°
~
~ ~ ~
~
~ o c
~ N ,
§
~ § 8
~
~ ~
~ , •
8 R ~
~ R
~
~ o
8
~ ,
§
~
~ o
~
~ ~
! <
~ , o
A ~
~ ~
~ ~
,
~
• ~ , ~
• , • ~
~ , ~ ~
~ ,
~
~
, "
~ ~
8 ~
~ ~
,
~~~~ ~~~~ 8888 ;;r;;;r;;;r;;;r; NNNN
~ (>
~ ~ ·~···~~·~·!t·.··t~$ ···· I .. lllwn ~ ll l' Q ,
o
o " ., • ., B
mG
'~
~ .. ~ J:? fil l I I I III I I I I R .. ~ ~ ~ .--C . ~ ~"'''''''~OOOM ; ~ ~ lJ NCO ... '" '" "- 00 N"''''~~~~~~NN
W "
![Page 241: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/241.jpg)
CHAPTE
R--
6 _
EX
HIB
IT - 6/
XI (
page
2 o
f 5)
, R , ~ o
~ 5
~
it
• • t
~
<i1
<i1
0°
~ (>
~ Q ,
o
o " ., • ., B
mG
'~
<I >11' L ~~--~~S~~~N~'~'--"~ \
~ ~
~
~ C
8
~ ,
~ ~
~
~
~ , , •
§
" 8
m ~
~
~ ,
~
~
§ ~ ~ , ~
<
'Y> N ~
~ ~ 12
~ ~
c ~
~ ~
,
~ ~
o C o
~
8 ~
~
ro • ~
R D
N
" ~
~
~ ~
• C , • ~
~
,
~~~~ ~~~~ 8888 ;;r;;;r;;;r;;;r; NNNN
i l ~ ~ > C <: 2> 1'1 111 111 1111 ~ 0 ~ l~l N M ~ ~ ~ ~ 00 ~N~~~~~~~OOOM W " ~~~~~~NN
![Page 242: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/242.jpg)
ARC...02/01/10 21:44:21:060 ABDULLAPUR 400KV BAW-1 TIE (218) CIRCUIT BREAKER Y-PH OPEN ARC...02/01/10 21:44:21:062 ABDULLAPUR 400KV BAW-1 TIE (217) CIRCUIT BREAKER R-PH OPEN ARC...02/01/10 21:44:21:072 ABDULLAPUR 400KV BAWANA-1 (177) A/R LOCK OUT ALARM ARC...02/01/10 21:44:21:074 ABDULLAPUR 400KV BAW-1 TIE (209) A/R LOCKOUT ALARM ARC...02/01/10 21:44:21:094 ABDULLAPUR 400KV BAWANA-1 (149) M-2 RELAY INOPERATIVE RESET ARC...02/01/10 21:44:21:126 ABDULLAPUR 400KV BAWANA-2 (008) MAIN-1 Y-PH TRIP RESET ARC...02/01/10 21:44:21:128 ABDULLAPUR 400KV BAWANA-2 (007) MAIN-1 R-PH TRIP RESET ARC...02/01/10 21:44:21:128 ABDULLAPUR 400KV BAWANA-2 (009) MAIN-1 B-PH TRIP RESET ARC...02/01/10 21:44:21:178 ABDULLAPUR 400KV BAWANA-1 (119) MAIN-1 R-PH TRIP RESET ARC...02/01/10 21:44:21:178 ABDULLAPUR 400KV BAWANA-1 (120) MAIN-1 Y-PH TRIP RESET ARC...02/01/10 21:44:21:180 ABDULLAPUR 400KV BAWANA-1 (121) MAIN-1 B-PH TRIP RESET ARC...02/01/10 21:52:08:730 ABDULLAPUR 400KV BAWANA-1 (185) CB R PHASE CLOSE ARC...02/01/10 21:52:08:734 ABDULLAPUR 400KV BAWANA-1 (186) CB Y PHASE CLOSE ARC...02/01/10 21:52:08:734 ABDULLAPUR 400KV BAWANA-1 (187) CB B PHASE CLOSE ARC...02/01/10 21:54:00:708 ABDULLAPUR 400KV BAWANA-1 (125) M-1 A/R LOCK OUT ALARM ARC...02/01/10 21:54:00:720 ABDULLAPUR 400KV BAWANA-1 (122) MAIN-1 CARRIER RECEIVE ALARM ARC...02/01/10 21:54:00:764 ABDULLAPUR 400KV BAWANA-1 (122) MAIN-1 CARRIER RECEIVE RESET CHAP
- 6 _ EXHIBIT - 6/XI (page 3 of 5)
![Page 243: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/243.jpg)
ARC...02/01/10 21:54:00:802 ABDULLAPUR 400KV BAWANA-1 (125) M-1 A/R LOCKOUT RESET ARC...02/01/10 21:54:02:288 ABDULLAPUR 400KV BAWANA-1 (114) MAIN-1 ZONE-1 START ARC...02/01/10 21:54:02:288 ABDULLAPUR 400KV BAWANA-1 (120) MAIN-1 Y-PH TRIP TRIP ARC...02/01/10 21:54:02:296 ABDULLAPUR 400KV BAWANA-1 (144) MAIN-2 Y-PHASE TRIP ARC...02/01/10 21:54:02:322 ABDULLAPUR 400KV BAWANA-1 (186) CB Y PHASE OPEN ARC...02/01/10 21:54:02:330 ABDULLAPUR 400KV BAWANA-1 (122) MAIN-1 CARRIER RECEIVE ALARM ARC...02/01/10 21:54:02:342 ABDULLAPUR 400KV BAWANA-1 (114) MAIN-1 ZONE-1 RESET ARC...02/01/10 21:54:02:360 ABDULLAPUR 400KV BAWANA-1 (144) MAIN-2 Y-PHASE RESET ARC...02/01/10 21:54:02:416 ABDULLAPUR 400KV BAWANA-1 (122) MAIN-1 CARRIER RECEIVE RESET ARC...02/01/10 21:54:02:438 ABDULLAPUR 400KV BAWANA-1 (120) MAIN-1 Y-PH TRIP RESET ARC...02/01/10 21:54:04:808 ABDULLAPUR 400KV BAWANA-2 (168) CB PDR ½ OPTD ARC...02/01/10 21:54:04:826 ABDULLAPUR 400KV BAWANA-1 (185) CB R PHASE OPEN ARC...02/01/10 21:54:04:826 ABDULLAPUR 400KV BAWANA-1 (187) CB B PHASE OPEN ARC...02/01/10 21:54:04:836 ABDULLAPUR 400KV BAWANA-1 (177) A/R LOCK OUT ALARM ARC...02/01/10 21:54:04:870 ABDULLAPUR 400KV BAWANA-2 (168) CB PDR ½ RESET ARC...02/01/10 21:54:05:254 ABDULLAPUR 400KV BAWANA-1 (174) CB LOW AIR PRESSURE ALARM ARC...02/01/10 21:54:05:398 ABDULLAPUR 400KV BAWANA-1 (174) CB LOW AIR PRESSURE RESET CHAP
-6_ EXHIBIT -6/XI (page 4 of 5)
![Page 244: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/244.jpg)
ARC...02/01/10 21:54:06:028 ABDULLAPUR ICT-2 (258) COOLER SUPPLY FAIL ALARM ARC...02/01/10 21:54:06:472 ABDULLAPUR ICT-2 (250) AC SUPPLY B FAIL ALARM ARC...02/01/10 21:54:06:488 ABDULLAPUR ICT-2 (250) AC SUPPLY B FAIL RESET ARC...02/01/10 21:54:06:488 ABDULLAPUR ICT-2 (259) AC SUPPLY A FAIL ALARM OPTD ARC...02/01/10 21:54:06:498 ABDULLAPUR ICT-2 (250) AC SUPPLY B FAIL ALARM ARC...02/01/10 21:54:06:874 ABDULLAPUR ICT-1 (394) AC SUP B FAIL ALARM ARC...02/01/10 21:54:06:912 ABDULLAPUR ICT-1 (402) COOLER SUPPLY FAIL ALARM ARC...02/01/10 21:54:08:308 ABDULLAPUR ICT-1 (419) CB COMPR ACFAIL ALARM ARC...02/01/10 21:56:06:240 ABDULLAPUR 400KV BAWANA-2 (012) MAIN-1 VT FUSE FAIL ALARM ARC...02/01/10 21:56:08:770 ABDULLAPUR 400KV BAWANA-2 (012) MAIN-1 VT FUSE FAIL RESET ARC...02/01/10 21:56:33:616 ABDULLAPUR 400KV BAWANA-2 (012) MAIN-1 VT FUSE FAIL ALARM ARC...02/01/10 21:56:35:328 ABDULLAPUR 400KV BAWANA-2 (012) MAIN-1 VT FUSE FAIL RESET ARC...02/01/10 22:03:45:196 ABDULLAPUR ICT-1 (419) CB COMPR ACMFAIL RESET CHAP
- 6 _ EXHIBIT - 6/XI (page 5 of 5)
![Page 245: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/245.jpg)
CHAPTE
R- -6
_ E
XH
IBIT
- 6/
XII
(pag
e 1
of 6
)
<i1
<i1
0°
~ (>
~ Q , o
o " ., . ., B
mG
'~
o ro
§
~
~ ~ , R
~ ~
m N
~ ~ 8
o
~
~ ~
§
~
~ ~ ro
~ ~
~
S , ~
~ ,
~ §
, ~ ,
~ ~ ~
~ , N R
$
~
~
R o c
~ o ,
~ 8
~ o
><S I 1111111 1111, i . ~ ~ > (' . ~ ~ ~ ro ~~NN~"~C~~~~ ·"' ~ I ~ N co W "
![Page 246: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/246.jpg)
CHAPTE
R- -6
_ E
XH
IBIT
- 6/
XII
(pag
e 2
of 6
)
, , ~ ~ o
~ 5
~
~
it
• • t
~
<i1
<i1
0°
~ (>
~ Q , o
o " ., • ., B
mG
'~
• 5
~
~
~ §
~
~ 8
§
~ ~
~
~ , §
~ ~ § ,
~ , §
~
• §
R o D
~ ,
~ 8
~ ,
~ 8
§ , § ,
§ N
8 o
~ 8
~ o
~ o
~ D
~ ~
~----------
R o
o 5 •
I ?» ~ 00 ~~~~~~~~~~~ ~ ~ ~ ~ ]~ i'i NCO ...
![Page 247: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/247.jpg)
EL OF MALERKOTLA DATED 02.10.2010 N 21:00:00.037 # 256 TIME SYNC PULSE FROM GPS
A 21:05:25.775 # 333 400KV LUDHIANA MAIN-II E/F START
A 21:05:25.809 # 108 400KV DADRI LINE MAIN-II START-Y
A 21:05:25.809 # 110 400KV DADRI LINE MAIN-II START-N
N 21:05:25.825 # 108 400KV DADRI LINE MAIN-II START-Y
N 21:05:25.825 # 110 400KV DADRI LINE MAIN-II START-N
N 21:05:25.855 # 333 400KV LUDHIANA MAIN-II E/F START
A 21:05:25.912 # 110 400KV DADRI LINE MAIN-II START-N
A 21:05:25.913 # 108 400KV DADRI LINE MAIN-II START-Y
N 21:05:25.929 # 108 400KV DADRI LINE MAIN-II START-Y
N 21:05:25.929 # 110 400KV DADRI LINE MAIN-II START-N
A 21:15:49.285 # 187 CB 552 ICT II & BUS REACTOR TIE CB TROUBLE
N 21:19:26.956 # 187 CB 552 ICT II & BUS REACTOR TIE CB TROUBLE
A 21:43:15.934 # 429 PTL LINE MAIN CB1252 COMPRESSOR START/STOP
N 21:45:00.569 # 429 PTL LINE MAIN CB1252 COMPRESSOR START/STOP
A 21:49:21.985 # 110 400KV DADRI LINE MAIN-II START-N
A 21:49:21.986 # 109 400KV DADRI LINE MAIN-II START-B
N 21:49:22.001 # 109 400KV DADRI LINE MAIN-II START-B
N 21:49:22.002 # 110 400KV DADRI LINE MAIN-II START-N
A 21:49:23.178 # 109 400KV DADRI LINE MAIN-II START-B
A 21:49:23.178 # 110 400KV DADRI LINE MAIN-II START-N
N 21:49:23.194 # 109 400KV DADRI LINE MAIN-II START-B
N 21:49:23.194 # 110 400KV DADRI LINE MAIN-II START-N
A 21:54:00.263 # 110 400KV DADRI LINE MAIN-II START-N
A 21:54:00.264 # 107 400KV DADRI LINE MAIN-II START-R
N 21:54:00.301 # 107 400KV DADRI LINE MAIN-II START-R
N 21:54:00.301 # 110 400KV DADRI LINE MAIN-II START-N
A 21:54:02.366 # 105 400KV DADRI LINE MAIN-II POWER SWING BLOCK
MALERKOTLA 1 2 Jan 2010 21:54:03 m
A 21:54:02.371 # 120 400KV DADRI LINE MAIN-I POWER SWING BLOCK
A 21:54:02.404 # 124 400KV DADRI LINE MAIN-I START-B
A 21:54:02.406 # 123 400KV DADRI LINE MAIN-I START-Y
A 21:54:02.409 # 109 400KV DADRI LINE MAIN-II START-B
A 21:54:02.410 # 108 400KV DADRI LINE MAIN-II START-Y
A 21:54:02.411 # 122 400KV DADRI LINE MAIN-I START-R
A 21:54:02.420 # 97 400KV DADRI LINE MAIN-II PROTN TRIP
A 21:54:02.434 # 99 400KV DADRI LINE MAIN-II CARRIER I/T SIGNAL SEND
N 21:54:02.441 # 11 TIE CB 252 Y-PH CLOSE/OPEN
N 21:54:02.442 # 12 TIE CB 252 B-PH CLOSE/OPEN
N 21:54:02.442 # 17 400KV DADRI LINE BKR. 352 R-PH CLOSE/OPEN
N 21:54:02.443 # 10 TIE CB 252 R - PH CLOSE/OPEN
N 21:54:02.443 # 18 400KV DADRI LINE BKR. 352 Y-PH CLOSE/OPEN
N 21:54:02.443 # 19 400KV DADRI LINE BKR. 352 B-PH CLOSE/OPEN
N 21:54:02.456 # 123 400KV DADRI LINE MAIN-I START-Y
A 21:54:02.457 # 125 400KV DADRI LINE MAIN-I START-N
N 21:54:02.472 # 105 400KV DADRI LINE MAIN-II POWER SWING BLOCK CHAP
chapter 6_ EXHIBIT - 6/XII (page 3 of 6)
![Page 248: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/248.jpg)
N 21:54:02.472 # 108 400KV DADRI LINE MAIN-II START-Y
N 21:54:02.472 # 109 400KV DADRI LINE MAIN-II START-B
N 21:54:02.477 # 125 400KV DADRI LINE MAIN-I START-N
N 21:54:02.484 # 124 400KV DADRI LINE MAIN-I START-B
N 21:54:02.485 # 122 400KV DADRI LINE MAIN-I START-R
A 21:54:02.507 # 138 400KV ICT-I & DADRI LINE TIE CB TROUBLE
N 21:54:02.512 # 97 400KV DADRI LINE MAIN-II PROTN TRIP
N 21:54:02.524 # 99 400KV DADRI LINE MAIN-II CARRIER I/T SIGNAL SEND
N 21:54:04.119 # 120 400KV DADRI LINE MAIN-I POWER SWING BLOCK
A 21:54:08.622 # 62 400KV ICT-1 COOLING/OLTC AC SUPPLY FAIL
A 21:54:08.629 # 363 CB852 COMPRESSOR AC SUPPLY FAIL
A 21:54:08.630 # 343 CB952 AC FAIL/CB COMPRESSOR START/STOP
A 21:54:08.636 # 428 PTL LINE MAIN CB 412-52 AC FAIL
A 21:54:08.637 # 281 400KV ICT-2 COOLING SYSTEM FAIL
N 21:54:09.046 # 62 400KV ICT-1 COOLING/OLTC AC SUPPLY FAIL
A 21:54:12.503 # 314 CARRIER PROTN.CH-I RECEIVED FOR MAIN-I
N 21:54:12.516 # 314 CARRIER PROTN.CH-I RECEIVED FOR MAIN-I
N 21:55:55.404 # 372 400KV LUDHIANA LINE MAIN CB 952 Y-PH CLOSE/OPEN
N 21:55:55.408 # 373 400KV LUDHIANA LINE MAIN CB 952 B-PH CLOSE/OPEN
N 21:55:55.410 # 371 400KV LUDHIANA LINE MAIN CB 952 R-PH CLOSE/OPEN
N 21:55:55.446 # 323 MANUAL CLOSE/TRIP IMPULSE TO LUDHIANA MAIN CB
A 21:55:55.707 # 339 400KV LUDHIANA LINE CB952AIR/SF6 GAS PRESSURE LOW
N 21:55:55.759 # 339 400KV LUDHIANA LINE CB952AIR/SF6 GAS PRESSURE LOW
A 21:55:56.023 # 339 400KV LUDHIANA LINE CB952AIR/SF6 GAS PRESSURE LOW
N 21:55:56.059 # 339 400KV LUDHIANA LINE CB952AIR/SF6 GAS PRESSURE LOW
A 21:55:56.428 # 339 400KV LUDHIANA LINE CB952AIR/SF6 GAS PRESSURE LOW
N 21:55:56.467 # 339 400KV LUDHIANA LINE CB952AIR/SF6 GAS PRESSURE LOW
N 21:55:58.521 # 455 PTL LINE MAIN CB 412-52 R-PH CLOSE/OPEN
N 21:55:58.532 # 467 MANUAL CLOSE IMPULSE TO PTL LINE MAIN CB 412-52
N 21:55:58.534 # 457 PTL LINE MAIN CB 412-52 B-PH CLOSE/OPEN
N 21:55:58.540 # 456 PTL LINE MAIN CB 412-52 Y-PH CLOSE/OPEN
N 21:56:06.996 # 173 400KV BUS REACTOR BKR. 652 R-Y-B PH CLOSE/OPEN
N 21:56:10.871 # 161 400KV ICT-2 BKR. 452 R-Y-B PH CLOSE/OPEN
N 21:56:15.661 # 2 MANUAL CLOSE/TRIP IMPULSE TO 400KV ICT-1 CB 152
A 21:56:15.733 # 69 220KV ICT-1 GROUP-B 3 PH. TRIP
N 21:56:15.752 # 1 400KV ICT-1 CB 152 R-Y-B CLOSE/OPEN
N 21:56:15.765 # 7 220KV ICT-1 CB 152LV R-Y-B PH. CLOSE/OPEN
N 21:56:44.880 # 166 220KV ICT-2 BKR. 452LV R-Y-B PH CLOSE/OPEN
N 21:57:10.078 # 363 CB852 COMPRESSOR AC SUPPLY FAIL
A 21:57:10.099 # 363 CB852 COMPRESSOR AC SUPPLY FAIL
A 21:57:10.106 # 202 BUS REACTOR CB 652 TROUBLE
N 21:57:10.808 # 363 CB852 COMPRESSOR AC SUPPLY FAIL
MALERKOTLA 1 2 Jan 2010 21:57:12 m
A 21:57:11.344 # 298 ICT-2 MAIN CB452 TROUBLE
N 21:57:40.002 # 428 PTL LINE MAIN CB 412-52 AC FAIL
A 21:57:40.022 # 429 PTL LINE MAIN CB1252 COMPRESSOR START/STOP
N 21:58:01.129 # 138 400KV ICT-I & DADRI LINE TIE CB TROUBLE CHAP
chapter -6 _ EXHIBIT - 6/XII (page 4 of 6)
![Page 249: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/249.jpg)
N 21:58:55.367 # 429 PTL LINE MAIN CB1252 COMPRESSOR START/STOP
2 Jan 2010 22:00:00 m
A 21:59:59.985 # 256 TIME SYNC PULSE FROM GPS
N 22:00:00.037 # 256 TIME SYNC PULSE FROM GPS
N 22:02:04.156 # 298 ICT-2 MAIN CB452 TROUBLE
N 22:02:32.198 # 343 CB952 AC FAIL/CB COMPRESSOR START/STOP
N 22:02:51.364 # 202 BUS REACTOR CB 652 TROUBLE
A 22:04:28.013 # 17 400KV DADRI LINE BKR. 352 R-PH CLOSE/OPEN
A 22:04:28.013 # 19 400KV DADRI LINE BKR. 352 B-PH CLOSE/OPEN
A 22:04:28.014 # 18 400KV DADRI LINE BKR. 352 Y-PH CLOSE/OPEN
N 22:06:27.718 # 468 MANUAL CLOSE IMPULSE TO TIE CB 411-52
A 22:06:27.724 # 415 PTL LINE DIRECT TRIP SEND CH-2
A 22:06:27.731 # 399 PTL LINE DIRECT TRIP SEND CH-I
N 22:06:27.726 # 463 PTL LINE TIE CB 411-52 B-PH CLOSE/OPEN
N 22:06:27.737 # 462 PTL LINE TIE CB 411-52 Y-PH CLOSE/OPEN
N 22:06:27.743 # 461 PTL LINE TIE CB 411-52 R-PH CLOSE/OPEN
A 22:06:27.779 # 445 PTL. LINE CB1152 COMPRESSOR START/STOP
N 22:06:27.957 # 399 PTL LINE DIRECT TRIP SEND CH-I
N 22:06:27.972 # 415 PTL LINE DIRECT TRIP SEND CH-2
A 22:06:37.805 # 467 MANUAL CLOSE IMPULSE TO PTL LINE MAIN CB 412-52
A 22:06:37.882 # 455 PTL LINE MAIN CB 412-52 R-PH CLOSE/OPEN
A 22:06:37.887 # 456 PTL LINE MAIN CB 412-52 Y-PH CLOSE/OPEN
A 22:06:37.889 # 457 PTL LINE MAIN CB 412-52 B-PH CLOSE/OPEN
N 22:08:23.794 # 445 PTL. LINE CB1152 COMPRESSOR START/STOP
A 22:11:52.954 # 424 PTL LINE DIRECT TRIP CH-I/2 RECEIVED
A 22:11:52.968 # 451 PTL LINE TIE CB 411-52 GR-B 3-PH PROT. TRIP
A 22:11:52.969 # 433 PTL LINE MAIN CB 412-52 GR-B 3 PH PROT TRIP
A 22:11:52.983 # 432 PTL LINE MAIN CB 412-52 GR-A 3 PH PROT TRIP
N 22:11:52.989 # 456 PTL LINE MAIN CB 412-52 Y-PH CLOSE/OPEN
N 22:11:52.991 # 455 PTL LINE MAIN CB 412-52 R-PH CLOSE/OPEN
N 22:11:52.991 # 457 PTL LINE MAIN CB 412-52 B-PH CLOSE/OPEN
N 22:11:53.033 # 424 PTL LINE DIRECT TRIP CH-I/2 RECEIVED
A 22:11:53.137 # 429 PTL LINE MAIN CB1252 COMPRESSOR START/STOP
A 22:12:16.051 # 75 220KV ICT-1 LV CB AIR PR. LOW
A 22:12:23.827 # 424 PTL LINE DIRECT TRIP CH-I/2 RECEIVED
A 22:12:23.842 # 450 PTL LINE TIE CB 411-52 GR-A 3-PH PROT. TRIP
N 22:12:24.233 # 424 PTL LINE DIRECT TRIP CH-I/2 RECEIVED
A 22:12:26.839 # 424 PTL LINE DIRECT TRIP CH-I/2 RECEIVED
N 22:12:27.392 # 424 PTL LINE DIRECT TRIP CH-I/2 RECEIVED
N 22:13:08.731 # 429 PTL LINE MAIN CB1252 COMPRESSOR START/STOP
N 22:14:20.251 # 450 PTL LINE TIE CB 411-52 GR-A 3-PH PROT. TRIP
N 22:14:20.252 # 432 PTL LINE MAIN CB 412-52 GR-A 3 PH PROT TRIP
N 22:14:21.099 # 433 PTL LINE MAIN CB 412-52 GR-B 3 PH PROT TRIP
N 22:14:21.100 # 451 PTL LINE TIE CB 411-52 GR-B 3-PH PROT. TRIP
A 22:16:11.247 # 173 400KV BUS REACTOR BKR. 652 R-Y-B PH CLOSE/OPEN
A 22:16:11.444 # 202 BUS REACTOR CB 652 TROUBLE
N 22:16:12.556 # 169 TIE BKR. 552 R-Y-B PH CLOSE/OPEN
MALERKOTLA 1 2 Jan 2010 22:16:13 m
CHAP
-6 _ EXHIBIT -6/XII (page 5 of 6)
![Page 250: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/250.jpg)
A 22:16:12.694 # 187 CB 552 ICT II & BUS REACTOR TIE CB TROUBLE
N 22:16:59.821 # 311 MANUAL CLOSE/TRIP IMPULSE TO 400KV LUDHIANA LINE TIE
CB 852
N 22:16:59.824 # 379 400KV LUDHIANA LINE TIE CB 852 B-PH CLOSE/OPEN
N 22:16:59.827 # 377 400KV LUDHIANA LINE TIE CB 852 R-PH CLOSE/OPEN
N 22:16:59.827 # 378 400KV LUDHIANA LINE TIE CB 852 Y-PH CLOSE/OPEN
A 22:16:59.970 # 364 400KV LUDHIANA LINE TIE CB852 COMPRESSOR START
N 22:17:47.724 # 181 400KV ICT-2 & BUS REACTOR TIE CB GROUP-A 3PH. TRIP
N 22:17:47.728 # 196 400KV BUS REACTOR GR-A 3PH. TRIP
A 22:18:28.584 # 173 400KV BUS REACTOR BKR. 652 R-Y-B PH CLOSE/OPEN
A 22:18:29.857 # 196 400KV BUS REACTOR GR-A 3PH. TRIP
A 22:18:29.857 # 203 400 KV BUS REACTOR DIFF. TRIP
A 22:18:29.860 # 181 400KV ICT-2 & BUS REACTOR TIE CB GROUP-A 3PH. TRIP
N 22:18:29.890 # 173 400KV BUS REACTOR BKR. 652 R-Y-B PH CLOSE/OPEN
N 22:18:29.933 # 203 400 KV BUS REACTOR DIFF. TRIP
N 22:20:05.587 # 69 220KV ICT-1 GROUP-B 3 PH. TRIP
N 22:21:23.250 # 187 CB 552 ICT II & BUS REACTOR TIE CB TROUBLE
N 22:21:45.656 # 364 400KV LUDHIANA LINE TIE CB852 COMPRESSOR START
A 22:21:48.902 # 10 TIE CB 252 R - PH CLOSE/OPEN
A 22:21:48.907 # 11 TIE CB 252 Y-PH CLOSE/OPEN
A 22:21:48.912 # 12 TIE CB 252 B-PH CLOSE/OPEN
A 22:21:48.959 # 110 400KV DADRI LINE MAIN-II START-N
A 22:21:48.960 # 107 400KV DADRI LINE MAIN-II START-R
N 22:21:48.976 # 107 400KV DADRI LINE MAIN-II START-R
N 22:21:48.976 # 110 400KV DADRI LINE MAIN-II START-N
A 22:21:49.073 # 138 400KV ICT-I & DADRI LINE TIE CB TROUBLE
N 22:22:22.535 # 138 400KV ICT-I & DADRI LINE TIE CB TROUBLE
A 22:23:29.508 # 2 MANUAL CLOSE/TRIP IMPULSE TO 400KV ICT-1 CB 152
A 22:23:40.051 # 1 400KV ICT-1 CB 152 R-Y-B CLOSE/OPEN
A 22:23:49.182 # 161 400KV ICT-2 BKR. 452 R-Y-B PH CLOSE/OPEN
A 22:23:49.306 # 298 ICT-2 MAIN CB452 TROUBLE
A 22:23:57.133 # 166 220KV ICT-2 BKR. 452LV R-Y-B PH CLOSE/OPEN
N 22:26:19.442 # 298 ICT-2 MAIN CB452 TROUBLE
N 22:29:13.482 # 202 BUS REACTOR CB 652 TROUBLE
N 22:29:55.724 # 75 220KV ICT-1 LV CB AIR PR. LOW
A 22:31:10.902 # 7 220KV ICT-1 CB 152LV R-Y-B PH. CLOSE/OPEN
A 22:42:13.367 # 323 MANUAL CLOSE/TRIP IMPULSE TO LUDHIANA MAIN CB
A 22:43:17.446 # 373 400KV LUDHIANA LINE MAIN CB 952 B-PH CLOSE/OPEN
A 22:43:17.449 # 371 400KV LUDHIANA LINE MAIN CB 952 R-PH CLOSE/OPEN
A 22:43:17.452 # 372 400KV LUDHIANA LINE MAIN CB 952 Y-PH CLOSE/OPEN
N 22:43:17.524 # 344 CB952 TRIP CKT-II FAULTY
A 22:43:17.558 # 343 CB952 AC FAIL/CB COMPRESSOR START/STOP
A 22:43:31.010 # 311 MANUAL CLOSE/TRIP IMPULSE TO 400KV LUDHIANA LINE
TIE CB 852
A 22:43:31.141 # 378 400KV LUDHIANA LINE TIE CB 852 Y-PH CLOSE/OPEN
A 22:43:31.143 # 377 400KV LUDHIANA LINE TIE CB 852 R-PH CLOSE/OPEN
A 22:43:31.145 # 379 400KV LUDHIANA LINE TIE CB 852 B-PH CLOSE/OPEN
A 22:43:31.340 # 364 400KV LUDHIANA LINE TIE CB852 COMPRESSOR START
N 22:45:18.926 # 343 CB952 AC FAIL/CB COMPRESSOR START/STOP
N 22:45:31.843 # 364 400KV LUDHIANA LINE TIE CB852 COMPRESSOR START
CHAP
-6_ EXHIBIT - 6/XII (page 6 of 6)
![Page 251: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/251.jpg)
CHAPTER-- 6 _ EXHIBIT -6/XIII (page 1 of 1)
"moo I<iI 400 kV UNSWITCHED A~ LINE REACTOR
,"ER""- .... -400 ltV SWITCHED B~ BUS/LINE REACTOR
"" [j] 33 IN SWITCHED ct BUS REACTOR
POWERGRID SUB-STATION ®
• HYDe BACK TO BACK --\)j<J--BBhlB SUB-STATION
9 • STATIC VAR COMPENSATOR STATES SUB-STATION
AXIS OF CEPARATION AT 02:54Hrs OF 02 JAN 2010
7115 IN TRNISIoIISSION LINES -tM>C _ 500 kV LINE ~
FACT IH'l
400 IN TRANSMISSION LINES
220 kV TRANSMISSION LINES
SVC &: BUS/LINE REACTOR RATING IN WAR
NORTHERN
WESTERN
TO BISWANATHCHARIYAI.J(NER) (HVDe BIPOLE)
kV
![Page 252: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/252.jpg)
ti*
2a r54:3121:54 :302r.:54.2921:54:24
Date
02 Jan 1002 Jan 1002 -Jan- 1002 -Jan - 1O
44.98,44 .98,44 -98,44.98,44.98,44 -98,44.98,44.98,44.98,44.98,
44 .98,44 .98,44.98,44 -98,44.99,44 -98,44 -98,44.9E ,
44 .98,44 .98,44.98,44.98,44 .98,44 -98.44 -98.44.98,44.98,
4t .3 ,
49.7 ,
50.1 ,
s0.1 ,
50.1 ,
50.1 ,
50.1 ,
s0.1 ,
50.1 ,
50.1 ,
50.1 ,
50.1 ,
50.1 ,
50.1 ,
50.1 ,
50.1 ,
50.1 ,
50.1 ,
50.1 ,
50.1 ,
s0.1 ,
s0.1 ,
50.1 ,
TM3 01RPM
ACTUAI, VAI,
249r .5249I.5249',7 .O2505 .8
2515 .72515 -"1
2524 -4
2533 -22542 .02542.0255I.92551.92560.',72560.',7256'7.3256't.32567.3
2515.72274 . A
2301.42374.32505 .82676.12724.42428 .82944 -9298I -52974.92982.62982.62982.62942.62942 -62942 -62942.52982.62942 -62942.629a2.629A2.62982.62982.62982.62982.62982.62982.62942.6
21:54:27 02 -Jan- 1021154.26 02-.lan-1024t54t25 02-.lan-102I.54124 02 -Jan- 1024.54123 02 -Jan- 102It54:22 02 -Jan- 1027t54:27 02 -Jan- 102It54.2O 02 -Jan- 102l:542l.9 02 -Jan- 1021:54: LB 02 -iran- 102J-.54.I'7 02 -JalI- 102It54tI6 0? -Jan-102at54tls 02 -Jan- 1021154.I4 02 -Jan- 102At54t13 02 -Janl10'2I:54tI2 02 -Jan- 1021:54 :11 02 -Jan- 102I.54, LA 02 -Jan- 102I,54t49 02 .lan- 10
'i1-.54,0a 02 .lan-to2I.54: O'7 02 Jan 1021t54,06 02 .Ian 102I:54t05 02 - Jan- 1024t54:04 02 - Jan- 1021:54:03 02 -Jan-1027t54'02 02 -Jan - 102at54t0! 02 Jan-1021:54:00 02 -Jan- 1027.53.59 02 Jan- 1,0
21 : s3 : 58 -02
- +ap- 10.27153.5'7 02 -Jan- L021 : 53 :55 02 Jan 1021 :53 :55 02 -Jan- 1021:53 :54 02 -Jan- 1021:53 :53 02 -Jan- 1021.53 t52 02-\tan-1021:53:51 02 -.1an-1021:53 :50 02-Jan-102I.53.49 02 -Jatr-102I.53.48 02 -Ja!- 1024.53.47 02 .lan 1024t53 t46 02 -Jan- 1024t53 t45 02 -Jan- 102at53.44 02 -Jan- 1021: 53 :43 02 -Ja!- 1027:53 t42 02 -Jan- 102l:53 t4I 02 -Jan- 1021.53.4O 02 Jan 10
crical Tabular Trend 1
549550551
553554555555557558'559560551562
56456s5665675585695'7 0
5'7 a
81257357457557657'75785',79
580581542sd3584585586587588589590591
s93594595595597598599500
22.03 t39
MW:l0 lMW
ACTUAI, VAI,
'02 Jan-10
TS3 705
ACTI]AI,
NORMAL
NORMAL
NORT4AL
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
NORXAI,
NORMAI,
NORMAL
NORMAI,
NORMAI,
NORMAL
NORMAL
NORMAI,
NORMAL
NORMAI,
NORMAI,
NORMAI,
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
NORMAIJ
NORMAI,
YHOOlHZ
ACTUAI VAL
YEOO1
KVACTUAL VAT,
NORMAL
NORMAL
NORMAL
NORMAL
NORMAI,
NORMAI,
NORMAL
NORMAL
NORt'lAL
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
NORMALNORMAL
0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0.0,0,0,0,0,0,0,a,0,0,0,0,0,0,a,o,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
II
3596
15318420327722r22523A234227
232232232
232
232232232232
23223223223L
Chapter - 7 _ Exhibit- - 7/I (page 1 of 3)
H.~ 8_rica.l Tabular
~ ...
Trend
Time < Date
21 ."54:3 1 02-Jan 10 549
21:54:30 02-Jan 10 550
21:54:29 02 - Jan-lO 551
21:54:28 02-Jan-lO 552
21:54:27 02-Jan-lO 553
21:54:26 02 - Jan - lO 554
21:54:25 02 - Jan - lO 555
21:54:24 02 - Jan- lO 556
21:54:23 02-Jan-lO 557
21::=;4:22 02-Jan-lO 558'
21: 5 4:21 02-Jap-lO 559
21:54:20 02-Jan - lO 560
21:54:19 02-Jan-lO 561
21:54:18 02-Jan - lO 562
21:54:17 02-Jan - lO 563
21:54:16 02 - Jan - lO 564
21:54:15 02 - Jan- lO 565
21:54:14 02 - Jan-lO 566
21:54:13 02 - Jarf- lO- 567
21:54:12 02-Jan - lO 568
21:54:11 02 - Jan-lO 569
21:54:10 02-Jan-lO 570
21:54:09 02-Jan - lO 571
":2"1:54 :08 02-Jan-lO 572
21:54:07 02 Jan 10 573
2 1 :54:06 02 Jan 10 574
21:54:05 02 - Jan-lO 575
21:54:04 02 - Jan-lO 576
21:54:03 02 - Jan-10 577
21:54:02 02 - Jan-10 578
21:54:01 02-Jan - 10 579
21:54:00 02 - Jan - 10 580
21:53:59 02-Jan-10
21:53:58 02 - J;B-l}: l.o
21:53:57 ·02- J an :"' 10
581
582 -~ ....... ~' -
5l 3 ·'
21:53:56 02-Jan- 1 0 584
21:53:55 02-Jan-10 585
21:53:54 02-Jan- 10 586
21:53:53 02-Jan-10 587
21:53:52 02 - Jan-l0 588
21:53:51 02 - Jan - l0 589
21:53:50 02 - Jan - 10 590
21:53:49 02-Jan-10 591
21:53:48 02-Jan-10 592
2 1 :53:47 02-Jan-10 593
21:53:46 02 - Jan-10 594
21:53:45 02 - Jan- 10 595
21:53:44 02-Jan-10 596
21:53:43 02-Jan-10 597
21:53:42 02-Jan-10 598
2 1 :53:41 02-Jan-10 599
2 1;53;40 02-Jan- 1 0 600
~
22;03:39 '02-Jan-10
MW3 01
MW
ACTUAL VAL
-3.18,
-3.18,
-3.1B,
-3.1B,
-3.1B,
-3.1B,
- 3.1B,
-3.1B,
- 3.1B,
-3.1B,
-3.1B,
- 3.1B,
-3.1B,
-3.1B,
-3.1B,
-3.1B,
- 3.1B,
- 3.1B,
- 3.1B,
-3.1B,
- 3.1B,
- 1. 8
17.4
200.5
220.8
226.1
232.2
234.5
226.7
226".7
181.1
185.
181. 6
181. 6
181.6"4-
181.6
1 81. 6
181.6
181. 6
181. 6
181. 6
181.6
181. 6
181. 6
181. 6
181. 6
181. 6
181. 6
181. 6
181. 6
177.4
182.6
TS3706
STATE
ACTUAL VAL
NORMAL 0
NORMAL 0
NORMAL a NORMAL
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL
NORMAL
NORMAL 0
NORMAL 0
NORMAL
NORMAL 0
NORMAL a NORMAL 0
NORMAL a NORMAL a NORMAL a NORMAL 0
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
tfORMAL 0
NORMAL
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL a NORMAL 0
NORMAL 0
NORMAL a NORMAL 0
NORMAL a
YH001
HZ
ACTIJAL VAL
44.98,
44.98,
44.9B,
44.98,
44.9B,
44.98,
44.98,
44.98,
44.98,
44 . 98,
44.98,
44.98,
44.98,
44.9B,
44.9B,
44.98,
44.9B,
44.98,
44.98,
44.98,
44.9B,
44.98,
44.9B,
44.9B,
44.98,
44.98,
44.98,
44.98,
45.5
47.3
49.
50.1
50. 1
50.1
50.
50.
50.
50.1
50.
50.
50.1
50.1
50.1
50.
50.1
50.1
50.1
50.
50.1
50.1
50.1
50.1
TM301
RPM
ACTUAL VAL
2482. 7
2491. 5
2491.5
2497.0
2505.8
2505.8
2515.7
2515.7
2524.4
2524.4
2533.2
2533.2
2542.0
2542.0
2551.9
2551.9
2560.7
2560.7
2567.3
2567.3
2567.3
2555.2
2515.7
2274.0
2301.4
2378.3
2505.8
2616.7
2724.4
2828.8
2941.9
2981. 5
2974.9
2982.6
2982.6
298 2 .6
2982.6
2982.6
2982.6
2982.6
2982.6
2982.6
2982.6
2982.6
2982.6
2982.6
2982.6
2982.6
2982.6
2982.6
2982.6
2982.6
YE001
KV
AC11JAL VAL
o o
o o o o o o o o
o o o o o o 8
8
31
35
96
153
184
203
217
221
225
230
230
227
232
232
232
232
232
232
232
232
232
232
232
232
232
232
232
232
232
231
231
![Page 253: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/253.jpg)
H\?or_ical.
Time
Tabular Trend
MW402
MVAR
ACTUAL VAL
-103.8B,-103.88,-103.88,- 103 .8B,-103.88,-103.8B,- 103 .8B.-103.8B,- 103 . 8B,-103.8B,-103.8B,-103.88,- 103 .8B,-103.8B,- 103 . 8B,- 103 .88,-103.88,- 103 .88,-103 .88,- 103 . 8B.
13.6 ,
-24.7 ,
-25.3 ,
-18.f ,
-4 .1 ,
12.6,
26 .7 ,
26.1 ,
26.I ,
26.7 ,
26,-1 ,
26.r ,26.1 ,
26.i ,
26.L ,
26.1 ,
25.I ,
26 -I ,
26.r,26 -r ,
26 -7 ,
26.r ,
25.7 ,
26 -r ,
26.a ,
26.r ,
23 -6 ,
1 22:03:3 9'v2 -.Ian- 10
DateMW4 01MW
ACTUAI VAI,
-3.18,3.18,
-3 . 18,
--3.18,-3.18,
-3.18,
187.5 ,
220 -s ,
224.5 ,
234-2 ,
230 -3 ,
258.5 ,
170.'7 ,
164.3 ,
169.r ,
169 -t- ,
TS4 ? 05STATEACTUAL
NORMAL O
NORMAL O
NORMAL O
NORMAL O
NORMAL O
NORI4AL O
NOR},IAL O
NORMAL O
NORMAL O
NORMAL O
NORMAL O
NORMAL O
NORI.4AI, O
NOR!,,IAL O
NORMAL O
NORMAI, O
NORMAL O
NORMAL O
NORMAL O
NORMAT, O
NORIiIAL 0NORMAL O
NORMAL O
NORMAL O
NORMAL O
NORMAL O
NORMAI, O
NORMAL O
NORMAL O
NORMAI O
NORMAIJ O
NORMAL O
NORMAL O
NORMAL O
NORMAL O
NORMAL O
NORMAL O
NORMAT O
NORMAL O
NORMAL O
1.H0 01HZ
ACTUAI, VAL
TM4O1
RPM
ACTUAL VAL
223',1 -'7 ,
223'7 .'t ,
2247 -6 ,
2247.6 ,
22s5.3 ,
2263 -O ,
2263.O ,
2270,7,2270 -1 ,
2279.4 ,
22'7 9 .4 ,
2287 -7 ,
2293 -'7 ,
2302.5 ,
2302.5,2302-5 ,
2302-5,2282 .'7 ,
2330 .0 ,
2410.2 ,
25rI.3,264'7 .5 ,
2'756 -3 ,
2862-A,2980 -4 ,
3479.9 ,
3014-4,3019.9 ,
3019.9 ,
3019.93019.9 , 'r'l l
3019.9 ,
3019.9 ,
3019.9 ,
3019.9 ,
3019.9 ,
3019 -9 ,
3019.9 ,
3019 .9 ,
3019.9 ,
3049.9 ,
3019.9 ,
3019.9 ,
Y8001KVACTUA], VAI,
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
I8
313596
1531842432a'/22r22523A23022'/232232232232232232232232232
232
232
232
234231
:1':54:29 02 -Jan- 102a.54:2A 02 -.lan-10it'sa,,zl 02 -Jan- 1021t54126 02-Jan 102\.54t25 02 -Jan- 102I:54:24 02 -.ian-102Lt54.23 02-.lan-L024.54:22 02-.lan-1024t54.2a 02 -,Jan- 102at54t2O 02 -Jan- 1021t54t19 02 -Jan- 1021:54:18 02 -Jan- 1O
2I:54:I7 02 -.lan-102It54.16 02 -.lan- 1021:54:15 02 -Jan- 1O
2I:54:I4 02 -.lao-102a.54t73 02 -Jan- 102a,54:72 02 -Jan- 1021:54:11 02 -Jan- 102It54t1-O 02 -Jan- 102a:54t09 02-iran-1021:54:08 02 -Jan-1021:54tO7 02 -.lan-1021r 54 r 06 02-Jan-1021:54:05 02 ,fan- 102a:54.04 02 ,Jan- 1021:54.03 02 -Jan- 1021t54t02 02-Jan-1021:54:01 02 -Jan- 1021:54:00 02-Jan 1021,:53:59 02 Jan- 1021 :53 :58 02 -Jan,1027.53 | 5'7 02 alan-103&!9? i 56. 02 .ran-102SlHq, s5- o2 -.r"' - r o21r53:54 02 .lan- 1021:53:53 02 -Jan- 102r:53.52 02 -.ian-1021:53 :51 02 -.lan - 1021r53:50 02-Jan-102r t53 t49 02 -Jan- 102a.53t4a 02 -Jan- 102\:53:4'l 02 -Jan- 102a:53:46 02 -.lan-1.02a:53:45 02 -Jan- 1021:53.44 02 -.lan-1021.53:43 02 -.lan-102I.53.42 02 -Ja!t-102I:53:41- 02 -Jan,1021:53:40 02 -Jan- 10
551552553554s55555557558559560561562563564565566
56855957057L5'725735745755"t 6
5775745'7 9
580581582583584. ."\+i+EP...1 ,
58.5 ,: ;159,1 ,
169.1 ,
469.4 ,
169.7 ,
159.1 ,
169.1 ,
169.1 ,
a69 .1 ,
169.1 ,
169. 1 ,
169.a ,
169.1 ,
169-r,169.1 ,
155.1 ,
1,59.8,
NORI4AI, O .
NORIIAL O ,
NORMAL O ,
NORMAL O ,
NORMAL O ,
NORMAL O ,
NORMAL O ,
NORMAL O ,
NORMAL O ,
NORMAL O ,
58658?58858959059159259359459559659'7
598599600
Exhibit- - 7/I (page 2 of 3)...-
H","-,o:-ical Tabu lar Trend 1 22:03:39~tl2-Jan - 10
Time Date
~1~54:29 02 - J a n-lO 551
21 ; 54:28 02 - Jan-lO 552
;1: 54: 27 02-Jan - lO 553
21: 54: 2 6 02-Jan - lO 554
21: 54:25 02-Jan - l O 555
21:54:24 02 - Jan-lO 556
21:54:23 02 - Jan-lO 55?
21 :54:22 02 - Jan-lO 558
21:54 : 21 02 - Jan- lO 559
21:54: 20 02-Jan- lO 560
21:54: 19 02-Ja n - lD 561
21:54: 18 02-Jan - lO 56 2
21:54: 1 7 02-Jan-lO 56 3
21:54:16 02-Jan-lO 564
21:54:15 02-Jan - lO 565
21:54:14 02 - Jan- l O 566
21:54:13 02-Jan- lO 567
21:54:12 02-Jan- lO 568
21:54 :11 02 - ~an-lO 569
21:54 :10 02-Jan-lO 570
21:54:09 OZ-Jan-lO 571
21:54 :08 02-Jan - lO 572
21:54:07 02 - Jan-lO 57 3
21: 54 :06 02-Jan -lO S74
21 : 54:05 D2 - Jan - l D 5 75
21:54:04 02 - Jan-lO 576
21:54 :03 02 -Jan-lD 577
21:54:02 02-Jan - l O 578
21:54:01 02-Jan - l 0 579
21: 54:00 02 - Jan - 10 580
2 1 : 53:59 02 - Jan-10 581
21 : 53:58 02-Jan - 10 582
MW4 01
MW
AcruAL VAL
-3.18,
-3.1B,
- 3 . 18,
-3. 1B,
- 3.1B,
- 3.1B,
- 3.1B,
- -3 . 1B,
-3.1B ,
-3.1B ,
-3. 1B ,
-3.1B ,
-3 .1B,
- 3.12,
-3.1B,
-3.1B,
-3.1B,
-3.1B,
-3.1B,
- 3.1B,
0.1
1 87.5
212.4
220.5
220.5
234.2
23 0 . 3
258.6
170.7
164. 3
169.1
169.1
21 :53:57 02 - Jan-10 583 169.1
~,, ;5 ,~:S6 . 02 - Jan-10 58~ .•. .:,;,;,.;..J,..§y.l 2 ]-;53:55- 02-Jan-10 58·5 ;'169'. 1
21:53:54 02 - Jan - 1 0 586
21:53:53 02-Jan - 10 58 7
21:53:52 02 - Jan-10 588
21:53:51 02 -Jan- 1 0 589
21:53:50 02-Jan - l0 590
21 : 53:49 02-Jan - 10 591
21: 53 :48 02-Jan - l 0 592
21:53:47 02-Jan - l0 593
21:53:46 02 - Jan- 10 594
21:53:45 02 -Jan-1 0 59 5
2 1:53 :44 02 - Jan - 10 596
21:53:43 02 - Jan-10 597
21:53:42 02 -Jan-10 598
21:53: 41 02-Jan - 10 599
21:53:40 02 - J an-l0 600
169 . 1
169.1
169.1
169.1
169.1
169 .1
169.1
1 69.1
169.1
169. 1
169. 1
169.1
169 .1
165 .1
169.8
T$4706
STATE
ACTIJAL VAL
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL a NORMAL 0
NORMAL 0
NORMAL 0
NORMAL a NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0
NORMAL 0 NORMAL
NORMAL a NORMAL 0
NORMAL a NORMAL a NORMAL 0
NORMAL 0
NORMAL a NORMAL a NORMAL a NORMAL a NORMAL a NORMAL 0
NORMAL 0
NORMAL 0
NORMAL
NORMAL a NORMAL 0
NORMAL 0
NORMAL
NORMAL a NORMAL 0
NORMAL a NORMAL a NORMAL 0
YHOD1
HZ
ACTUAL VAL
44.9B,
44.98 ,
44.9B,
44.9B,
44 .9B,
44 .9B,
44 .98,
44. 9B,
44. 98 ,
44.98,
44.98,
44. 98 ,
44. 98 ,
44 .9B,
44.98,
44. 9B,
44 .98 ,
44 .98,
44. 98,
44. 98 ,
44.98,
44.9B,
44 .98 ,
44.98,
44.9B,
44. 98 ,
45 .5
47.3
49.1
50.1
50.1
50.1
50.1
50.1
50.1
5 0 .1
50. 1
50.
50.1
50.1
50,1
50.1
50. 1
50. 1
50.1
50.1
50. 1
50.1
50.
50.1
TM401
RPM
ACTIJAL VAL
2228.9
2237.7
223 7.7
2247.6
2247 .6
2255 .3
2255 .3
2263.0
2263 . 0
2270.7
2270.7
2279. 4
2279.4
2287 .1
2287 .1
2293.7
2293 .7
2302.5
23 02 .5
2302. 5
2302 .5
2282 .7
2330 .0
2410. 2
2511. 3
2647 .5
2 7 56. 3
2862.8
2980 .4
3019 .9
3014 .4
3019.9
3019 .9
3019 · 9
3019.9
3019.9
3019 .9
3019 .9
3019.9
3019.9
3019 .9
3019. 9
3019.9
3019.9
3019 .9
3019 .9
3019 .9
3019 . 9
3019.9
3019 .9
XE001
KV
ACTUAL VAL
o o o o o o o o o o o
o o o o o 8
8
31
35
96
153
184
203
217
22 1
225
230
230
227
232
232
2 32
232
2 32
232
232
232
232
232
232
232
232
232
232
232
232
231
23 1
MW4 02
MVAR
AC11JAL VAL
- 103 . 88,
- 103.88 ,
- 103 .8B,
- 103.8B,
- 103.88,
- 103.8B,
- 103.8B,
-103.88,
- 103.88 ,
.-1 03 .8B ,
-103.88,
- 103 .8B,
-1 03.8B,
-1 03 . 8B,
-103.8B,
-103.8B,
- 103 .8B ,
- 103.88,
- 103 .88 ,
-103.8B ,
- 3 .3
13 .6
- 12.9
- 21.1
-25.3
-18.1
-4 . 7
12 . 6
23 . 4
26. 1
26.1
26 . 1
26 .1
26 . 1
26.
26 .
2 6.1
26 .1
26. 1
26.1
26 . 1
26.1
26.1
26.
26.
26 .1
26 .
26 . 1
26 .1
23 . 6
![Page 254: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/254.jpg)
H1:-or ical Tabular Trend
Tlme Date
2 1': 54 .30 02-Jan-10fa.54,2g 02 - Jan- 1021154r28 02-Jan 102It54.27 02:Jan-102a.54t26 02 -Jan- 1027t54.25 02 -Jan- 1021t54.24 02 -.lan- 1021254:23 02 -Jan- 1021t54:22 02 -,Jan- 1021.54t2L 02 -Jan- 102L r54:2O Oi -Jan- 102I:54:19 02 -Jan- 1021:54:18 02 -Jan- L02at54.I'7 02 -.lan- 102at54tI6 02 -Jan- 1021:54 :15 02 -.]an- 102I:54:1-4 02 -.ian- 1021 | 54 :13 02-.Tan-10Zi:Ss,tz 02 -.lan-102I:54tll 02 -Jan- 102It54.IO 02 -.lan- 102at54tO9 02 -Jan- l-02I:54tOA 02 -,-fan- 1021:54 :07 "O2 -Jan- 1021 :54 :06 02 Jan-1021:54:05 02 -Jan- 1021:54:04 02-Jan L02at54t03 02 -Jan- 102a.54t02 02-Jan 102I.5410I 02-Jan 102I:54.00 02 -Jan- 1021:53:59 02 -.lan-1021:53 r 58 02-Jan l-O
'?,+..: s3: s? 02 -Ja+- 1021-:53 : 56 02 -Jan- 102l:53.55 02 -Jan- 102I t 53 t54 02-,fan 1021:53:53 02 -.fan- 102at53'52 02-aran-1021i53:51 02 -Jan- 1021:53 :50 02 -Jan- 102I:53.49 02 -Jan'1021:53 :48 02 -Jan,1024.53,47 02 -Jan- 102a:53.46 02 -Jan- 1024t53 t45 02 -Jan- 102l:53 t44 02 -Jan- 1021:53 :43 02 -Jan- 102I.53r42 02 -Jan- 1021:53 :41 02 -Jan- 102a.53:4O 02 -Jan- 10
s8A*,r,tt?46'7 ,
584 20A..7' ,
s85 206.7 ,
586 2A6.'/ ,
587 206.7 ,
588 206.'1 ,
589 206.'7 .
590 206.',7 ,
591 206.'l ,
592 206.'7 ,
593 2A6.'7 ,
594 206.? ,
595 206.7 ,
596 206 .'7 ,
59'7 206.7 ,
598 205.'1 ,
600 208 .0 ,
0 , 103 .88,0 , -103.88,0 , 103.88,0 , -103.88,0, -103.88.0 , -103.88,0 , -103 .8B,0 , ,103.88.0 , - 103 .88,0 , -103 .88,0 , 103 .88,0 , -103.88,0 , -103 .8B,0 , -103 .88,0 , - 103.88,0 , -103.88,0 , 103 .88,0 , -9.5 ,
I , -1.1 ,
8 , 6.4 ,
31 , 23.3 ,
35 , I2.5 ,
96 , 715.'7 ,
153 , 115.? ,
484 . 140.1 ,
203 , 129.4 ,
2I7 , ?8.8 ,
221 , 44.9 ,
225 , 51.4 ,
230 , 37.3 ,
230 , 37.3 ,
22'7 . 30.3 ,
232 , 30.3 ,
. f4 "-t ;1 .,. ., .3a 3 '232, ,' :. 30.3,232 , 30.3 ,
232 , 30.3 ,
232 , 3 0.3 ,
232 , 30.3 ,
232 , 3 0.3 ,
232 , 3 0.3 ,
232 , 30.3 ,
232 , 30.3 ,
232 , 3 0.3 ,
232 , 3 0.3 ,
232 , 30-3 ,
232 , 3 0.3 ,
232 , 3 0.3 ,
232 , 3 0.3 ,
23r , 3 0.3 ,
23r , 24.3
7 22.a3 t39 02 -Jan:io +f,KstrYs.- V&-\;
550551552s5355455s55655'1558559s50561562553564565566567568569s70571
5735745t55'7 6
5775745',79
580581542
4.2o.2o.2o.2o.2o -20.2o -2
0.80.80.81.51.62.73.04 -36.9
10 .415.0),9 .414 .517.213.515 .115.915.915.915.915.915.915.915 .91,5. 915.9
3058.43067.23072.'/307 9 -23085.93094.51102 .33108.93114.43!22 .1-
3135.33143 .03154.03154. 03161.63I70 .43r79 -23l'7 9 .23155.03055.0
22'7'7 .22354 .52445.32548.62654.s2789.22499.I2999 -03010.03004.53004.53004 .53004 . s3004.53004.53004.53004.53004.5
MWo 01MW
ACTUA], VAL
15.68,-15.68,-15.58,-15.58.-15.58,-15.68,-15.68,-15.58.-15 .58,-15.68,
15 . 58,-15.58,15.68,
-15.58,- 15 .68.-ls.68,-15.58,-5.4 ,
-0.1 ,
23 -r ,
18 .4 ,
246-4,
257.2 ,
206.7 ,
206 .'7 ,
GEO O2
KVACTUAL VAI,
YHOOlHZ
ACTUAI, VAI,
YEOOlXV
ACTUAL VA],
MWo02
MVAR
ACTUAL VAL
TMOOT
RPM
ACTUAL VAI,
15.9 ,
15.9 ,
45.9 ,
15.9 ,
15.9 ,
15.9 ,
15.9 ,
15.9 ,
15.9 ,
15.9 ,
15.9 ,
15.9 ,
15.9 ,
3004.5 ,
3004 .5 ,
3 004 .5 ,
3004.5 ,
1004 .5 ,
3004.5 ,
3004.5 ,
3004.5 ,
3004.5 ,
3004. 5 ,
3004 - 5
Exhibit- 7/I (page 3 of 3)
H~orical Tabular Trend 1 22:03 :3 9 02 - Jan~0
T~me Dat e
2r: 54 :30 02-Jan · l0 550
21:54:29 02-Jan - 10 551
21:54 : 28 02 - Jan - 1D 552
2i :54 :27 02- J an - 10 553
21:54:26 02-Ja n - 10 554
21: 54:25 02 ~Jan · 10 555
21:54:2 4 02-Ja n - l0 556
21:54 :23 02 - J an· 1 0 557
21:54 : 22 02-Jan · l 0 558
21:54 : 2 1 02·Jan-l O 559
21:54:20 02 -Ja n - 10 560
21:54: 19 02-Jan· l O 561
2 1 :54: 18 02 -Jan · 10 56 2
21:54 :1 7 02 - J an - l0 563
21 : 54:1 6 02 - Jan- l 0 564
21 : 54: 15 02 -Jan .- l 0 56 5
2 1 :54 :14 02 - Jan - l0 566
21:54:1 3 02 - Jan - l0 567
2i;S4: 12 02 -Ja n - l0 56 8
21:54: 11 02 - Jan - l0 569
21 : 54:1 0 02-Jan - l0 570
21 :54: 09 02 -Jan - 1 0 571
21 : 54: 08 02-Jan - l0 572
21 : 54:07 ··02-Jan·10 573
21:54: 06 02 - Jan · l0 574
21:54:05 02- Jan ·l0 575
21:54:04 02 · Jan - l0 576
21 : 54:03 02· J a n - l 0 577
2::54:02 02·Jan - l0 578
21:54:01 02-Jan - 10 57 9
21:54: 00 02 - J an-10 580
21 :53:59 02- J an -1 0 581
MWOOI
MW
ACTUAL VAL
- 1 5.6B,
- 15.6B.
-15.6B,
- 1 5.6B,
- 15.6B,
-ls.6B,
- ls.6B,
-15.6B,
- lS . 6B,
- 1 5.6B,
- l S.6B,
-15.6B ,
-15.6B,
- I S . 6B,
-lS . 6B,
-15.6B ,
-IS . 6B,
- 5. 4
- 5 . 4
- 0 . 1
23 .1
18 . 4
232.8
246.4
2 52.7
254.7
254.7
25 7 .2
252.9
213,3
203.8
206.7
21:53:58 02-Jan - l0 582 206.7
~l,53 , 57 02-.J a(l-10 5Bl .•. ,_'t~D6 , 7
2\,53,56 02-Jan-l0 584 20~.7
21 :53:55 02-Jan ~10 585
2 1 :53: 54 02 - J an - l 0 58 6
21 :53 : 53 02 - Jan - 10 587
21: 53:52 02-Jan - 10 588
21 : 53: 51 02 -Jan - 1 0 58 9
21:53:50 02 -Jan - 1 0 590
21:53:49 02 - Jan - 10 591
21: 53: 48 02 -Jan- 1 0 592
2 1 :53:47 02 - Jan-10 593
2 1 :53:46 02-Jan - 10 594
21:53: 45 02- J an - 1 0 59 5
21:53 : 44 02- J an - 10 596
2 1 :53:43 02 -Ja n - 10 597
2 1 :53 :42 02 - J an - 10 59 8
21:53 : 4 1 02-Jan - l0 599
21:53 : 40 02-Jan - 10 600
206.7
2 06.7
20G . 7
206.7
2 06.7
206.7
206.7
2 06.7
206.7
206.7
20 6 . 7
206.7
206. 7
2 06.7
203.2
208.0
GE002
KV
ACTUAL VAL
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0 . 8
0 .8
0.8
1. 6
1.6
2.1
3.0
4.3
6.9
1 0.4
16.0
19. 4
14.5
11. 2
13.5
15. 1
15.9
15.9
15.9
1 5 .9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
YHOOI
HZ
ACTUAL VAL
44.98,
44.98,
44.98.
44 .9B,
44.98,
44.98 ,
44 .98 ,
44.9B,
44.98,
44. 9B,
44.9B,
44.98,
44 .98,
44 .9B.
44 . 9B,
44 .98,
44 .9B.
44 .98,
44 . 98 ,
44.98 .
44 . 9B,
44.98,
44.98 ,
44.9B.
44.9B.
44. 98,
44 .98,
4 5.5
47.3
49. 1
50. 1
50. 1
50.1
50. 1
50. 1
50.1
50.1
50. 1
50.1
50.1
50.1
50. 1
50 . 1
50.1
50. 1
50.1
50.1
50. 1
50.1
50.1
50.1
YEOOI
KV
ACTUAL VAL
o o o o o o o o o o o o o o o o o o 8
8
31
35
96
153
184
203
217
221
22 5
230
230
227
23 2
,232
232
23 2
232
232
232
2 32
232
232
2 32
232
232
2 32
232
232
232
23 1
231
MW002
MVAR
ACTUAL VAL
- 103.S8.
- 103.88.
- 103 . 8B,
-103.8B,
- 1 03 . 8B,
-1 03 . SB.
- 1 03 . 88 ,
- 103.88 ,
- 103.8B,
- 1 03. 88 .
- 103.88.
- 103. 8B,
- 103 .88 ,
- 103.88,
- 1 03 . 8B,
- 103 .88 ,
- 103 . S8 ,
- 9. 5
- 1. 1
6 . 4
23. 3
12 .5
115.7
115 .7
140.1
129.4
78.8
44 . 9
51. 4
37 . 3
37.3
30. 3
30.3
30.3
30.3
30.3
30. 3
30.3
30.3
30 . 3
30 . 3
30.3
30 . 3
30.3
30. 3
30 . 3
30 . 3
30.3
30. 3
30 . 3
24 .3
TM0 07
RPM ACTUAL VAL
305 8 . 4
3067.2
3072 . 7
3079. 2
3086.9
3094 . 6
3102 . 3
3108.9
3114 . 4
3122 . 1
31 28.7
313 5. 3
31 43 . 0
31 54. 0
31 54 . 0
316 1. 6
3170.4
31 79 . 2
3179 . 2
3166 . 0
3065. 0
2 729 . 9
2277 . 2
2358 . 5
24 4 5 . 3
2548.6
2658 . 5
2789 . 2
2899.1
2999 . 0
301 0.0
3004 .5
3004 . 5
3.004.5
3004.5
3004 . 5
300 4. 5
3004.5
300 4. 5
300 4 .5
3004.5
3004 . 5
3004. 5
3004 . 5
3004. 5
300 4. 5
3004.5
30 04 . 5
3004. 5
3004 . 5
3004.5
![Page 255: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/255.jpg)
TRIPPING OF THE LINES FROM 29th DECEMBER 2009 TO 3RD JANUARY 2010 Annexure-7/I Name of Utility/Control Area……………………………………………PSEB P&M Circle Ludhiana
Is fault location where insulator changed with
polymer
Is fault location where
insulator manually cleaned
Yes/No Yes/No220 KV Sahnewal -Rly Ckt.2 1.1.2010 00.59 Found Nothing NO Yes220KV Sahnewal-RTP 1.1.2010 01.11 TL No.14 Discs Flashed NO Yes132KV Goraya-Phillaur 1.1.2010 01.40 Found Nothing NO Yes220 KV lalton Jagraon 1.1.2010 04.40 TL No. No.62 Discs Flashed NO Yes220 KV Lalton-Malerkotla 1.1.2010 04.42 TL No.13 Discs Flashed NO Yes220KV Jamalpur-Ganguwal Ckt.1 1.1.2010 06.49 TL No. 219 discs flashed. NO Yes220KV Jamalpur-Dhandari Ckt.1 1.1.2010 07.03 Jumper burnt at TL No. 2 NO Yes220 KV Jamlpur-Dhandari Ckt.2 1.1.2010 08.29 Jumper burnt at TL No. 2 NO Yes132KV Ghulal-Jamalpur Ckt.1 1.1.2010 07.25 Found Nothing NO Yes132KV Jamalpur-Ghulal Ckt.1 2.1.2010 01.35 Discs flashed at TL No.330,335 NO Yes
220 KV Jamalpur-Dhandar-1 2.1.2010 01.37 TL-10 Discs Flashed NO Yes * Note Below
220 Kv jamalpur-Dhandar-2 2.1.2010 01.37 TL-10 Discs Flashed NO Yes * Note Below132KV Goraya-Phillaur 2.1.2010 01.40 Found Nothing NO Yes132KV Goraya-Jamalpur 2.1.2010 02.16 Discs flashed at TL No.9 NO Yes132KV Jamalpur-phillaur 2.1.2010 06.35 Discs flashed at TL No.11 NO Yes220 KV G-1 to RTP Ckt-4 2.1.2010 01.55 Found Nothing NO Yes220 KV G-1 to RTP Ckt-2 2.1.2010 02.51 Found Nothing NO Yes220 KV G-1 to RTPm n Ckt-1 2.1.2010 02.23 Found Nothing NO Yes220KV G-2 to G-1 3.1.2010 00.40 Found Nothing NO Yes132 KV Ghulal-Jamalpur 3.1.2010 00.58 TL No. 330 Discs Flashed NO Yes220KV G-2 to Ganguwal Ckt.1 3.1.2010 00.59 Found Nothing NO Yes220KV G-2 to G-1 3.1.2010 01.36 Found Nothing NO Yes
* At This Location Antifog discs have failed. No Polymer Discs have been provided
Location of fault Date & time of tripping
/Auto reclosingName of Line Remarks
![Page 256: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/256.jpg)
TRIPPING OF THE LINES FROM 29th DECEMBER 2009 TO 3RD JANUARY 2010 Annexure 7/I (page 2/6)Name of Utility/Control Area……SE/P&M ,Amritsar……………………………………………………
Is fault location where
insulator changed with
polymer
Is fault location where
insulator manually cleaned
Yes/No Yes/No132 KV Patti-Bhikhiwind 2.1.10,21.15 to 21.20 NIL - - Due totripping of 66 KV Algon feeder132 KV Tarn Taran-Patti 3.1.10,00.32 to 16.50 NIL Found nothing132 KV Verpal-Tarntaran 3.1.10, 2.05 to 2.15 NIL Damage of Busbar LA at Verpal220 KV Verpal-W/Granthian I 2.1.10, 10.15 to 19.25 NIL Damage of Busbar LA at Verpal220 KV Verpal-W/Granthian II 2.1.10,10.15 to 13.26 of 3.1.10 T.No.6 No Yes220 KV Sarna-W/G ckt II 03.1.10, 04.38 to15.35 of 4.1.10 T.No.126 No No132KV MPH- III to IV 3.1.10 , 4.15 to 14.40 T. No. 6 No No220 KV F.G.C.-Civil Line ASR 3.1.10, 3.08 to 17.05 of 4.1.10 T.No.37 &58 No No Disc string damaged220 KV Civil Line-Khasa 3.1.10, 2.28 to 16.20 of 4.1.10 T.No. 56 No No Disc string damaged132 KV Verka-Kathunangal 2.1.10,20.20 to20.35 NIL No No Found nothing132 KV Verka-Kathunangal 2.1.10,20.35 to 10.22 of 3.1.10 T.No. 854-855 No No Due to chinese kite thread132 KV Verka-Pakharpura 2.1.10,21.45 to 11.45 of 3.1.10 T.No. 868 No No Disc string damaged132 KV Verpal-Naraingarh 2.1.10,21.50 to 17.15 of 3.1.10 T.No.44 No No Disc string damaged132 KV Civil Line-Naraingarh 2.1.10 ,21.15 to 18.20 of 3.1.10 NIL No No Found nothing132 KV Mallmandi-Verpal 2.1.10,20.35 to 14.35 of 3.1.10 T.No. 5 No No Disc string damaged & Earth wire broken132 KV Verka-Mallmandi 2.1.10,21.35 to 10.42 of 3.1.10 T.No. 45&46 No No Earth wire broken132 KV Mallmandi-Verpal 3.1.10,23.35 to10.10 of 4.1.10 NIL No No Found nothing132 KV Powercolony-Civil line 3.1.10,13.15 to 15.10 T.No. 10,11 No No Due to chinese kite thread
Name of LineDate & time of tripping /Auto
reclosingLocation of fault Remarks
![Page 257: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/257.jpg)
TRIPPING OF THE LINES FROM 29th DECEMBER 2009 TO 3RD JANUARY 2010
Name of Utility/Control Area…P & M Circle PATIALA Annexure 7/I (page 3/6)Is fault location where insulator
Is fault location where insulator
Yes/No Yes/No
220 KV S/S Rajla 66 KV Kakrala -1 31.12.09=5.14 to 5.29=0.15 hrsY-Q LA damage of 66/11 KV
T/F at S/S Kakarala. No No
220 KV S/S Malerkotla 66 KV Maloud-Siarh 31.12.09=2.18 to 2.30=0.12 hrs Found nothing No No
66 KV Maloud-Siarh 31.12.09=4.15 to 11.20=7.05 hrsDisc Insulator damaged at Pole no.10
No No
220 KVMalerkotla- G/Garh 31.12.09=07.52 to 11.10 =03.18 hrs Found nothing No No
220 KVMalerkotla- Amloh 31.12.09=7.52 to 11.05=3.13 hrs Found nothing No No
220 KV S/S Ablowal 220 KV Ablowal-G/Garh-1 31.12.09=7.05 to 7.25=0.20 hrs Due to fog/Found Nothing No No
220 KV Ablowal-G/Garh-1&2
31.12.09=8.05 to 19.55=11.50 hrsY-Q Discs damage at Tower no 37 &E/Wire Broken.
No No
220 KV Ablowal-Fagganmajra-1&2
31.12.09=8.05 to 8.28=0.23hrs Due to fog/Found Nothing No No
220 KV S/S B/garh 66 KV Devigarh 31.12.09=07.20 to 16.45=09.25 hrs Found nothing No No
220 KV Fagganmajra 31.12.09=08.03 to 8.47=00.44 hrs Found nothing No No
66 KV Bahadurgarh 31.12.09=07.16 to 07.26=00.10 hrs Found nothing No No
66 KV Bahadurgarh 31.12.09=08.15 to 08.25=00.10 hrs Found nothing No No
66 KV Ghanaur 31.12.09=08.03 to 08.15=00.12 hrs Found nothing No No
220 KV S/S Ablowal220 KV Ablowal-
Bahadurgarh ckt.I01.01.10=06.52 to 16.20=09.28 hrs
Earth wire broken between T.No. 4&5
No No
220 KV Ablowal-Bahadurgarh ckt.I
01.01.10=05.05 to 06.45=01.40 hrsEarth wire broken between
T.No. 4&5No No
220 KV Ablowal-Bahadurgarh ckt.II
01.01.10=05.10 to 16.22=11.12 hrsEarth wire broken between
T.No. 4&5No No
220 KV Ablowal-Patran 01.01.10=04.07 to 11.50=11.43 hrs Found nothing No No
220 KV Ablowal- Rajla 01.01.10=05.30 to 15.40=10.10 hrsY- phase discs string damaged on T.No.75
No No
220 KV Ablowal Bahadurgarh ckt.I
01.01.10=22.30 to 23.10=00.40 hrs Found nothing No No
220 KV S/S Malerkotla220 KV M/Kotla-Lalton
Kalan01.01.10=03.40 to 16.01=12.21 hrs
Y- phase discs dmgd on T.No.113
No No
RemarksName of Sub-Stn. Name of LineDate & time of tripping /Auto
reclosingLocation of fault
2+Page] of page6
![Page 258: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/258.jpg)
220 KV M/Kotla- G/garh 01.01.10=03.55 to 07.25=03.30 hrs Found nothing No No
220 KV M/Kotla- G/garh 01.01.10=07.32 to 09.25=11.53 hrs Found nothing No No
220 KV M/Kotla- Amloh 01.01.10=04.15 to 07.20=03.05 hrs Found nothing No No
66 KV Mahanvir Spinning Mill
01.01.10=03.15 to 13.45=10.20 hrsY- phase discs string damaged on T.No.14
No No
66 KV M/Kotla Steel Mill 01.01.10=03.25 to 14.02=10.37 hrs Found nothing No No
66 KV Maloud-Siarh 01.01.10=03.25 to 12.20=08.55 hrs Birdage on T.No.14 No No
66 KV I/C 1&2 01.01.10=03.25 to 03.35=00.10 hrs Found nothing No No
220 KV S/S Dhuri 66 KV Kanjhla 01.01.10=08.20 to 13.05=04.45 hrs Found nothing No No
220 KV S/S Patran 220 KV Patran- Rajla01.01.10=05.35 to 03.01.10=17.55
=60.20 hrs14 Nos. discs dmgd on
T.No.161No No
66 KV Rai Dharana 01.01.10=05.20 to =18.45 =03.25 hrsConduc tor Break down Vill.
DugaalNo No
220 KV S/S Mohali 220 KV Ganguwal-Mohali 02.01.10=01.05 to =02.05 =01.00 hrs Found nothing No No
220 KV Mohali-RTP Ckt.I 02.01.10=01.05 to =02.42 =01.37 hrs Found nothing No No
220 KV Mohali-RTP Ckt.II 02.01.10=01.05 to =02.55 =01.50 hrs Found nothing No No
220 KV Ganguwal-Mohali 02.01.10=02.55 to =09.50 =06.55 hrs Found nothing No No
220 KV Mohali-Rajpura Ckt.I&II
02.01.10=02.55 to =14.25 =11.20 hrs Found nothing No No
220 KV S/S Malerkotla 220 KV M/Kotla- Amloh 02.01.10=00.10 to =01.40 =01.30 hrs Found nothing No No
220 KV M/Kotla- Amloh02.01.10=02.05 to 03.01.10=18.53=
=40.53 hrsBlue phase discs dmgd on
T.No.20No No
220 KV M/Kotla- G/garh 02.01.10=02.50 to =Contunue =-- hrsBreaker dmgd at 220 KV
GBG S/S endNo No
66KV Malerkotla 02.01.10=00.25 to =01.30 =01.05 hrs Found nothing No No
66KV Malerkotla 02.01.10=01.40 to =11.01 =09.21 hrs Found nothing No No
66KV Kup Kalan Ckt.II 02.01.10=00.55 to =02.15 =01.20 hrs Found nothing No No
66KV Kup Kalan Ckt.I 02.01.10=00.55 to =01.10 =00.15 hrs Found nothing No No
66KV Kup Kalan Ckt.I 02.01.10=00.55 to =01.10 =00.15 hrs Found nothing No No
66KV Sandour 02.01.10=02.15 to =10.45 =08.30 hrsRed phase discs dmgd on H
Pole 78-
No No
2+Page] of page6
![Page 259: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/259.jpg)
66KV Mahanvir Spinning Mill
02.01.10=07.41 to =12.55 =05.14 hrsBlue phase discs dmgd on
T.No.33No No
220 KV S/S Rajpura 220 KV Rajpura-B.garh 02.01.10=01.05 to =02.05 =01.00 hrs Found nothing No No
220 KV Rajpura-Faggan Majra
02.01.10=01.05 to =06.30 =05.25 hrs Found nothing No No
220 KV Mohali-Rajpura Ckt.No.II
02.01.10=07.35 to =16.35=09.00 hrs Found nothing No No
220/66 KV 100 MVA T/F T-3
02.01.10=06.30 to =Continue =- hrsAir leakage of Controlling
Br.No No
66 KV Sirhind 02.01.10=06.35 to =20.55 =14.20 hrs Discs dmgd on Rail Pole 80 No No
220 KV S/S Patran 220 KV Patran- Sunam 02.01.10=03.15 to =14.30 =11.45 hrs Found nothing No No
220/66 KV 100 MVA T/F T-4
02.01.10=07.50 to =09.20 =01.30 hrs Over Flux Relay operate No No
220/66 KV 100 MVA T/F T-3
02.01.10=08.10 to =14.45 =06.35 hrs Main Buch. Trip No No
66 KV Moonak Banga 02.01.10=02.50 to =16.15 =13.25 hrsDiscs dmgd on Tower No.
113 & 137No No
66 KV Shatrana 02.01.10=08.02 to =12.45 =04.43hrsTree touches with line near
village Kua-cherryNo No
66 KV Khanouri 02.01.10=9.40 to16.15 =06.35 hrs Discs dmgd of Blue Phase No No
220 KV S/S Dhuri 66 KV Rangian 02.01.10=01.50 to =14.45 =12.55 hrsRed phase discs dmgd on
T.No. 86No No
220 KV S/S Ablowal220 KV G/garh-Ablowal
Ckt.No.I02.01.10=00.20 to =11.25 =11.05 hrs Found nothing No No
220 KV G/garh-Ablowal Ckt.No.II
02.01.10=01.50 to =11.58 =10.08 hrs Found nothing No No
220 KV Ablowal-Rajla 02.01.10=06.30 to =16.55 =10.25 hrsRed phase discs dmgd on
T.No. 14No No
66 KV DCW 02.01.10=06.32 to =09.10 =02.38 hrs Earth wire broken No No
2+Page] of page6
![Page 260: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/260.jpg)
TRIPPING OF THE LINES FROM 29th DECEMBER 2009 TO 3RD JANUARY 2010
Name of Utility/Control Area PSEB / P&M Circle, Jalandhar.Is fault location where insulator
Is fault location where insulator
Yes/No Yes/No
220 KV Kotla Janga- Kartarpur 31.12.09 at 5.40 Hrs.
- - - Found Nothing on patrolling
220 KV Jamsher- Mahilpur Ckt.1 2.1.10 at 21.55 Hrs.
- - - Found Nothing on patrolling
220 KV Jamsher- Mahilpur Ckt.1 2.1.10 at 6.33 Hrs. T. No. 116 No Yes Y Phase Insulator string replaced
22- KV Jamsher- Mahilpur Ckt.II 2.1.10 at 21.55 Hrs.
- - - Found Nothing on patrolling
220 KV RTP- Jamsher 2.1.10 at 2.54 Hrs. - - - Found Nothing on patrolling
132 KV Bhogpur- Mukerian 2.1.10 at 5.03 Hrs. T. No. 13 No Yes R Phase Insulator string replaced
132 KV Tanda- Mukerian 2.1.10 at 5.03 Hrs. - No Yes Found Nothing on patrolling
132 KV Tanda- Mukerian 2.1.10 at 21.50 Hrs.
T. No. 53 No Yes B Phase Insulator string replaced
220 KV Bhakra- Mahilpur Ckt.I 2.1.10 at 21.50 Hrs.
- - - Found Nothing on patrolling
220 KV Bhakra- Mahilpur Ckt.I 2.1.10 at 3.01 Hrs. T. No.55 No Yes Y Phase Insulator string replaced
220 KV Bhakra- Mahilpur Ckt.II 2.1.10 at 21.50 Hrs.
T. No.41 No Yes Y Phase Insulator string replaced
132 KV Nawanshahar- Goraya 2.1.10 at 2.55 Hrs. - - - Found Nothing on patrolling
132 KV Banga- Phagwara 2.1.10 at 2.55 Hrs. - - - Found Nothing on patrolling
132 KV Hoshiarpur- Bhogpur 2.1.10 at 21.50 Hrs.
- - - Found Nothing on patrolling
Dy.Chief Engineer,
P&M Circle, PSEB, Jalandhar.
Name of LineDate & time of tripping /Auto
reclosingLocation of fault Remarks
![Page 261: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/261.jpg)
ABSTRACT OF LOAD RELIEF
Load(MW) at 3.00 hrs Load(MW) at 21.30 hrs
Name of Circle
Patiala 10 0 10 45 0 45
Bathinda 52 27 25 40 31 9
Jalandhar 31 31 0 75 7 68
Ludhiana 96 6 90 75 72 2
Amritsar 75 8 67 185 43 142
Total 264 72 192 420 153 266
Load(MW) at 3.00 hrs Load(MW) at 21.30 hrs
Name of Circle
Patiala 54 0 54 39 0 39
Bathinda 61 44 17 81 50 31
73 48 26 48 28 20
Ludhiana 80 54 26 97 58 38
Amritsar 32 15 17 7 5 2
Total 299 160 139 272 141 131
Grand Total 564 232 331 692 295 397
Running Load (MW)
Relief due to df/dt
operation(MW)
Relief unavailable(M
W)Running Load
(MW)Relief due to df/dt operation (MW)
Relief unavailable(
MW)
Running Load (MW)
Relief due to UFR operation(MW)
Relief unavailable(M
W)Running Load
(MW)Relief due to UFR operation(MW)
Relief unavailable(
MW)
Jalandhar including RLSS
![Page 262: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/262.jpg)
Format for supply UFR and df/dt tripping details for inquiry Committee report ANNEXURE 7/II
Make and model of UFR
Settings in terms of frequency(Hz)
Time delay(ms)
Setting of under voltage blocking(%)
Setting of Sampling cycles(nos)
whether separate auxiliary supply or only PT supply
1 220 KV F.G.Churian 66 KV Ramdass ABB-SPAF340C3 48.8 PT 4.57 3.5 no system fail 5 0 no2 220 KV F.G.Churian 66 KV Jandher ABB-SPAF340C3 48.8 PT 2.33 3 no system fail 3 0 no3 220 KV F.G.Churian 66 KV Ajnala-Dial Bharan ABB-SPAF340C3 48.8 PT 8 7 no system fail 9 0 no4 220 KV W/Granthian 66 KV Udhanwal 28.26 EE FTG-11PF-8053A 48.8 PT 8 6.9 Yes system fail 0.1 0 Yes5 220 KV Patti 66 KV Chohala Sahib RMS-2H34K2(BCC) 48.8 PT 4.57 3.7 Yes system fail 3.8 3.31 Yes6 220 KV Patti 66 KV Toot RMS-2H34K2(BCC) 48.8 PT 4.57 1 Yes system fail 1.6 1.6 Yes7 220 KV K.S.Mali 66 KV Kalanaur 13 Matrix 2H34-K-2(BC 48.8 PT 3.65 3.2 Yes system fail 4.7 0 Yes8 220 KV Tibber 66 KV Purana Shalla 9.7 Matrix 2H34-K-2(BC 48.8 PT 4.22 3.7 no system fail 2.28 2.28 no
14.8 4.9117.2 2.28
7
26.5
S.No.Name of station with Voltage level where UFR installed
Name of individual Feeder with voltage level on which UF relay connected
Planned load relief(MW)
Information regarding effectiveness of UFR and df/dt relays during grid disturbance of 02.01.10 under P&M Circle, PSEB, Amritsar.
Reason if UFR did not trip
Load of feeder at 2100 Hrs(in MW)
Load of feeder at2130 Hrs(in MW)
whether feeder tripped at 2154 hrs by UFR
Detail of individual Relay (UFR)Load of feeder at 0200 Hrs(in MW)
Load of feeder at 0300 Hrs(in MW)
whether feeder tripped at 0301 hrs by UFR
![Page 263: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/263.jpg)
P&M Amritsar ANNEXURE 7/IIFormat for supply UFR and df/dt tripping details for inquiry Committee report
Make and model of df/dt
Settings in terms of frequency and rate of change(Hz,Hz/s)
Time delay(ms)
Setting of under voltage blocking(%)
Setting of Sampling cycles(nos)
whether separate auxiliary supply or only PT supply
1 132 KV Tangra Incomer 16 Areva micom 9 0.1 PT 1.37 2.4 Yes 9.6 21.3 Yes2 132 KV Jandiala Guru Incomer 18 Areva micom 9 0.1 PT 0 5.4 Yes 9.6 21.45 Yes3 132 KV Dhariwal 66 KV Dehriwal 9 Areva micom p 0.1 PT 2.85 2.5 NO 3 21.3 NO4 132 KV Dhariwal 66 KV Naushera Majja Sing 8 Areva micom p 0.1 PT 2.28 2 NO 2.5 21.3 NO5 220 KV Civil Line 66 KV Harshachhina I 18 Areva micom p 0.1 PT 6.85 6 NO 6.5 7.42 NO6 220 KV Civil Line 66 KV Harshachhina II 11 Areva micom p 0.1 PT 8 7 NO 6.5 7.42 NO7 220 KV Civil Line 66 KV Ranjit Avenue 27 Areva micom p 0.1 PT 8 7 NO 16.5 18.85 NO8 132 KV Naraingarh 66 KV Hall Gate 18 Areva micom p 0.1 PT 3.08 2.7 NO 8.5 9.71 NO9 132 KV Naraingarh 66 KV Sarai Amanat Khan 22 Areva micom p 0.2 PT 2.28 2 NO 3 3.42 NO10 132 KV Naraingarh 66 KV Gowal Mandi 20 Areva micom p 0.2 PT 5.71 5 NO 14 16 NO11 132 KV Naraingarh 66 KV OCM-2 17 Areva micom p 0.2 PT 5.71 5 NO 13 14.85 NO12 132 KV Tarn Taran 66 KV Focal Point 38 Areva micom p 0.2 PT 6.85 6 NO 10 0 NO13 132 KV Tarn Taran 66 KV Manochal 17 Areva micom p 0.2 PT 1.82 4.6 NO 4.5 0 NO14 132 KV Tarn Taran 66 KV Chabal 33 Areva micom p 0.2 PT 1.25 6 NO 8.2 0 NO15 132 KV Ekal Gadda Incomer 9 Alstom MBCH 0.2 PT 0.57 0.4 Yes 0.6 0.68 Yes16 132 KV Bhikhiwind Incomer 68 Areva micom p 0.3 PT 5.48 11 NO 28.6 21.3 NO
8.2 43.4366.8 141.57
Name of station with Voltage level where df/dt installed
Name of individual Feeder with voltage level on which df/dt relay connected
Planned load relief(MW)
Information regarding effectiveness of UFR and df/dt relays during grid disturbance of 02.01.10 under P&M Circle, PSEB, Amritsar.
Load of feeder at2130 Hrs(in MW)
whether feeder tripped at 2154 hrs bydf/dt
Detail of individual Relay (df/dt)Load of feeder at 0200 Hrs(in MW)
Load of feeder at 0300 Hrs(in MW)
whether feeder tripped at 0301 hrs by UFR
Reason if df/dt did not trip
Load of feeder at 2100 Hrs(in MW)
S.No.
![Page 264: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/264.jpg)
Make and model
of UFR
Settings in
terms of
frequency(
Hz)
Time
delay
(ms)
Setting of under voltage blocking(%)
Setting of
Sampling
cycles(no
s)
whether separate auxiliary supply or only PT
1 220kv S/S Mansa 66KV Mansa 40 ABB SPAF 340C 48.8 Auxiliry 18 14 notTripped - 19 19 not Tripped66KV Bhikhi 12 -do- 48.8 sdupply 3 2.5 notTripped - 4 4 not Tripped66KV Dhalewan 10 -do- 48.8 and PT 2.5 faulty notTripped - 3 3 not Tripped66KV Jhunir 24 -do- 48.8 supply 6 faulty notTripped - Faulty Faulty not Tripped
2 132KV Kotkror 66KV Mudki 20 Matrix RMS 48.8 PT Supply 2.28 2.3 Tripped - 49.8Hz 4.56 4.56 Tripped -
3 132 KV Sadiq 66KV I/C 1 & 2 90 MFVUM 48.8 PT Supply 20 16.7 Tripped - 19.43 19.43 Tripped4 220KV Bhottiwala66KV Thatatha Sahib 17 EEMFVUM 48.8 inst. PT Supply 2 2.3 Tripped - 3.42 3.42 Tripped5 220 KV Ghubaya 66KV Ladhuka 4 EE 48.8 4 7.43 Tripped - 5 5 not Tripped6 132 Abohar 33KV Khuikhera 5 ER 48.8 5 15.43 Tripped - 22.86 22.86 Tripped
load relief 44.16 50.27nt 16.5 31
Planned
load
relief(M
W)
Reason if UFR
did not trip
Load of feeder
at 2100 Hrs(in
MW)
Information regarding effectiveness of UFR and df/dt relays during grid disturbance of 02.01.10 under P&M Circle, PSEB, Bathinda.
Load of
feeder
at2130
Hrs(in
MW)
whether
feeder
tripped at
2154 hrs by
UFR
Detail of individual Relay (UFR) Load of
feeder at
0200
Hrs(in
MW)
Load of
feeder at
0300
Hrs(in
MW)
whether
feeder
tripped at
0301 hrs
by UFRS.No.
Name of station
with Voltage
level where UFR
installed
Name of individual
Feeder with voltage
level on which UF
relay connected
![Page 265: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/265.jpg)
Make and model of
df/dt
Settings in
terms of
frequency
and rate of
change(Hz,
Hz/s)
Time
delay(
ms)
Setting of
under
voltage
blocking(
%)
Setting of
Sampling
cycles(nos
)
whether
separate
auxiliary
supply or
only PT
supply1 132 KV Maur 66Kv T/Saboo 20 AREVAP923 MICOM 0.1 58 11 Cyc. PT Supply 6.85 6.85 no 9.14 9.14 no
66KV Jodhpur 3 AREVAP923 MICOM 0.1 58 10 PT Supply 3.2 3.2 no 2.3 faulty no66 KV Joga 20 AREVAP923 MICOM 0.1 58 10 PT Supply 8 Faulty no 3.42 faulty no
2 132 KV Mukatsar 66KV Pattanwala on AREVAP923 MICOM 0.3 on on no on yes66 KV Malout Road 3 AREVAP923 MICOM 0.3 3 3 no 4 yes66 KV Rupana 12 AREVAP923 MICOM 0.3 12 12 no 5 yes
3 132 KV Abohar 33 KV Amarpura 4 AREVAP923 MICOM 0.2 10 4 yes 5 yes33 KV Kalrkhera 3 AREVAP923 MICOM 0.2 10 3 yes 12 yes33 KV Aboharl 4 AREVAP923 MICOM 0.2 10 4 yes 2 yes33 Kv Khuianservar 3 AREVAP923 MICOM 0.2 10 3 yes 3 yes
27.4 3125.05 9.14
Information regarding effectiveness of UFR and df/dt relays during grid disturbance of 02.01.10 under P&M Circle, PSEB, Bathinda.
27.4
11.42
6.85
Reason if
df/dt did
not trip
Load of
feeder at
2100 Hrs(in
MW)
Load of
feeder
at2130
Hrs(in
MW)
whether
feeder
tripped at
2154 hrs
bydf/dt
Detail of individual Relay (UFR) Load of
feeder at
0200
Hrs(in
MW)
Load of
feeder at
0300
Hrs(in
MW)
whether
feeder
tripped at
0301 hrs
by UFRS.No.
Name of station
with Voltage level
where df/dt
installed
Name of individual Feeder
with voltage level on
which df/dt relay
connected
Planned
load
relief(MW)
![Page 266: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/266.jpg)
Make and Model of
UFR relay
Setting in terms of
Frequency and rate of change ( Hz.Hz/s)
Time delay( ms) if any
Setting of under
voltage blocking
(%) if any
Setting of
sampling
cycles ( nos)
Whether separate auxiliary supply or only PT supply
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
1 220 KV S/Stn. Kotla Janga
66 KV Shahkot 80.96 English Electric MFVUM
48.8 Hz - 0.62% 10 Cycles
PT Supply 16 14.8 Yes - 15 15 Yes
2 132 KV S/Stn.
Nakodar
66 KV Shanker 17.07 Meo Matrix RMS
48.8 Hz - 0.62% 10 Cycles
PT Supply 5.15 4.8 Yes - 1.9 1.68 Yes
3 132 KV S/Stn.
Nawanshahar
66 KV Aur & Rahon
34.53 MFNUM 48.8 Hz - - - PT Supply - - Not - - - -
4 132 KV Banga
66 KV Behram 35.88 MFNUM 48.8 Hz - - - PT Supply - - Not - - - -
5 132 KV Jadla
66 KV Balachour & Karawer
40.81 MFNUM 48.8 Hz - - - PT Supply - - Not - - - -
6 220 KV S/Stn.
Kartarpur
66 KV Nadala 66 KV JCT Mill 66 KV Hamira
66 KV Surgical-I 66 KV Surgical-II 66 KV Mustfapur
6.16 2.80 5.04
21.92 21.92 6.44
ABB SPAF 340 C-III
48.2 Hz. - - - PT Supply 6.16 2.80 5.04
21.92 21.92 6.44
1.6 1.3
2.06 9.6 9.6 1.6
NO NO NO NO NO NO
Supply tripped from
feeding S/Stn.
1.6 1.3
2.06 9.6 9.6 1.6
- NO NO NO NO NO NO
7 132 KV S/Stn.
Bhogpur
33 KV Bholath & 33 KV Kandhala
Jattan
6.25 Matrix 2 H 34 K2 ( BCC)
48.8 Hz. - - - PT Supply 6.06 5.1 Tripped - 11 11 Yes
Whether feeder
tripped at 0301 hrs by UFR
rely
Reason if UFR did not trip
Load of feeder at
2100 Hrs ( in MW)
Load of feeder at
2130 Hrs ( in MW)
Whether feeder
tripped at 21.54 Hrs.
by UFR relay
Information regarding effectiveness of UFR and df/dt relays during grid disturbance of 02.01.10 under P&M Circle, PSEB, Jalandhar.Sr. No. Name of
station with
Voltage level
where UFR
installed
Name of individual feeder(s) with
voltage level on which UFR relay
connected
planned load relief
( M/W)
Details of Individual Relay ( UFR) Load of feeder at
0200 Hrs ( in MW)
Load of feeder at
0300 Hrs ( in MW)
![Page 267: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/267.jpg)
Make and Model of df/dt relay
Setting in terms of
Frequency and rate of change ( Hz.Hz/s)
Time delay( ms) if any
Setting of under
voltage blocking (%) if any
Setting of
sampling
cycles ( nos)
Whether separate auxiliary supply or only PT supply
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 171 220 KV S/Stn.
Jamsher66 KV Daulatpur 15.94 AREVA
MICOM- P 9230.2/Sec. - 0.62% 10
CyclesPT Supply 5.04 5.04 Yes 1.12 1.12 Yes
2 132 KV S/Stn. Nurmehal
33 KV Bus bar 13.88 AREVA MICOM- P 923
03./Sec. - 0.62% 10 Cycles
PT Supply 0 0 5.88 5.60 Yes
3 132 KV S/Stn. Hoshiarpur
66 KV Attowal & Sham 84
29.98 AREVA MICOM- P 923
0.03/Sec. - - - PT Supply 8.48 8.48 Yes - 5.09 - Yes
4 132 KV S/Stn. Kapurthala
11 KV I/Comer No.1 2.78 MICOM P-623 0.1/Sec. - - - PT Supply 5 5 Yes 2.78 2.78 No
5 220 KV S/Stn. Sultanpur
66 KV Bus bar 65.67 MICOM P-623 0.1/Sec. - - - PT Supply 6 6 Yes 65.67 65.67 No
6 132 KV S/Stn. Bhogpur
11 KV Dalli, Khuradpur, Bhogpur
2 AREVA MICOM- P 923
0.3/Sec. - - - PT Supply 1.42 1.42 Tripped - 3.702 - Tripped
7 132 KV S/Stn. Tanda
11 KV Tanda, Swajpur,Bassi,Darap
ur, Khuda, Sallan
4 AREVA MICOM- P 923
0.3/Sec. - - - PT Supply 3.28 3.28 Tripped - 5 - Tripped
8 132 KV S/Stn. Alawalpur
11 KV Duhre, Alawalpur,
Kishanpur, Dasupur, Karari, Badiana
1.5 AREVA MICOM- P 923
0.2/Sec. - - - PT Supply 1.5 1.5 Tripped - 3 - Tripped
Load of feeder at
0300 Hrs ( in MW)
Load of feeder at
0200 Hrs ( in MW)
Information regarding effectiveness of UFR and df/dt relays during grid disturbance of 02.01.10 under P&M Circle, PSEB, Jalandhar.
Details of Individual df/dt Relayplanned load relief ( M/W)
Name of individual feeder(s) with
voltage level on which df/dt relay
connected
Name of station with Voltage level
where df/dt installed
Sr. No. Whether feeder
tripped at 21.54 Hrs.
by df/dt relay
Load of feeder at
2130 Hrs ( in MW)
Load of feeder at
2100 Hrs ( in MW)
Reason of df/dt did not trip
Whether feeder
tripped at 0301 hrs by df/dt
rely
![Page 268: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/268.jpg)
Sr.No. Name of Stn.with voltage level where UFR installed.
Name of individual feeder where voltage level on which UFR connected.
Planned load relief MW
Load of feeder at 0200 hrs. Amp
Load of feeder at 0300 hrs. in Amp
Whether feeder interrupted at 0301 hrs.
Reason, if UFR not tripped.
Load of feeder at 2100 hrs. in Amp
Load of feeder at 2130 hrs. in Amp
Whether feeder interrupted at2154 hrs.
Make & Model of UFR Settings in terms of frequency.
Time delay, if any
Sating of under voltage blocking if any.
Setting of sampling cycles
Whether separate auxi.supply or only PT supple.
1 220 Kv S/S Amloh 66 KV Bhadson line 45 MVA Essen Rerole 48.8 Both 44 45 Yes 60 55 Yes2 220 KV Jagraon 66/11 KV 10/12.5 MVA T/F 12.5 MVA Essen Rerole 48.8 Both 172 176 No 165 162 No3 do 66 KV Raikot 8 MVA Essen Rerole 48.8 Both 43 45 No 76 77 No4 132 KV Badhni Kalan 66 KV Bilaspur 20 MVA Essen Rerole 48.8 Both 32 30 No 26 27 No5 132 KV Sawaddi 132/11 KV T/F 20 MVA 20 MVA Essen Rerole 48.8 Both 66 70 No 192 190 No6 220 KV Dhandari-1 220/66 KV 100 MVA T/F 200 MVA Alston 48.2 Both 480 490 Yes 500 495 Yes7 132 KV Doraha 132 KV bilaspur Sihora 72.5 MVA Alston 48.6 Both Faulty Faulty No Feeder faulty 19 17 Yes8 220 KV Goraya 33 KV Apra, Dosanj kalan 12 MVA Alston 48.2 Both 24 Faulty No 140 135 No9 220 KV Sahnewal 66 KV Latala 20 MVA Essen Rerole 48.8 Both Faulty Faulty No Feeder faulty 17 17 No
53.5 58.426.26 38.22
Name of Stn.with voltage level where DF/DT installed.
Make & Model of df/dt Settings in terms of frequency.
Time delay, if any
Sating of under voltage blocking if any.
Setting of sampling cycles
Whether separate auxi.supply or only PT supple.
1 220 KV G-2 66 KV Central 60 MVA Areva 0.3Hz/Sec 75% 10 Both Faulty Faulty No Feeder faulty 67 A 66 Yes2 do 66 KV Grain Market 60 MVA Areva do 75% 10 Both Faulty Faulty No Feeder faulty 52 A 50 Yes3 do 66 KV Badinpur 40 MVA Areva do 75% 10 Both Faulty Faulty No Feeder faulty 35 A 34 Yes4 220 KV Humbran 66 KV Firozpur Rd. Ckt-1 150 MVA Areva 0.3Hz/Sec 75% 10 Both 325 330 A No 120 A 118 Yes5 do do Ckt-2 150 MVA Areva do 75% 10 Both 232 290 A No 100 A 100 Yes6 do 66 KV Humbran 150 MVA Areva do 75% 10 Both 238 241 A No 100 A 100 Yes7 220 KV Sahnewal 66 KV Sahnewal Ckt-1 27 MVA Areva 0.3Hz/Sec 75% 10 Both Faulty Faulty Yes Feeder faulty 118 A 118 Yes8 do do Ckt-2 32 MVA Areva do 75% 10 Both 55 58 A Yes 89 A 89 Yes9 do 66 KV Avery 10 MVA Areva do 75% 10 Both Faulty Faulty Yes Feeder faulty Faulty Faualty Yes
10 do 66 KV Sport king 5 MVA Areva do 75% 10 Both 15 Faulty Yes Feeder faulty 48 A 48 Yes11 132 KV Dharmkot 66 KV Kot Ise Khan 5 MV A Areva do 75% 10 Both 40 40 A No 22 A 22 No
Sr.No. Name of individual feeder where voltage level on which DF/DT connected.
Planned load relief MW
Reason, if DF/DT not tripped.
Information regarding effectiveness of UFR and df/dt relays during grid disturbance of 02.01.10 under P&M Circle, PSEB, Ludhiana.
Details of individual relay
Whether feeder interrupted
Details of individual relay Load of feeder at 0200 hrs.
Load of feeder at 0300 hrs.
Whether feeder interrupted
Load of feeder at 2100 hrs.
Load of feeder at 2130 hrs.
![Page 269: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/269.jpg)
Information regarding effectiveness of UFR and df/dt relays during grid disturbance of 02.01.10 under P&M Circle, PSEB, Patiala.
Deatil of individual Relay(UFR)
1 66 KV Lung 10.2 48.80 --- --- --- ON ON not operated ON not operated
2 66 KV Ghanour 18.65 48.80 --- --- --- 8.86 MW 8.46 MW not operated 5.59 MW not operated
3 66 KV Behlolpur 9.70 48.80 --- --- --- 0.80 MW 0.80 MW not operated Grid fail 1.00 MW 1.00 MW not operated
4 66 KV Pakhoke 40.95 48.80 100 --- --- 4.80 MW 5.80 MW not operated 4.80 MW 4.80 MW not operated
5 66 KV Thuliwal 25.65 48.80 100 --- --- 7.50 MW 8.50 MW not operated 2.10 MW 2.10 MW not operated
6 66 KV Bhadour 29,25 48.80 100 --- --- 4.20 MW 4.80 MW not operated 5.80 MW 5.80 MW not operated
7 66 KV Kanjla 7.20 48.80 100 --- --- 0 0 not operated 0.50 MW 0.50 MW not operated
8 Matrex 48.80 100 --- --- 1.8, 2.5 1.8, 2.5 not operated 1.8, 2.5 1.8, 2.5 not operated
9 48.80 100 --- --- not operated not operated
not 53.56 39.1
Sr.no.
Name of Station with
Voltage level where
UFR installed
Name of individual feeder(s) with
Voltage level which UFR connecteded
Planned Load relief
(MW)
Make and Model of
UFR
Setting in term of
Frequency(Hz)
Time delay (ms) if any
Setting of Under voltage blocking (%) if any
Setting of Sampling
cycles (nos)
Wheather separate
auxiliary or only PT supply
Load of feeder at
02.00 Hrs.in (MW)
Load of feeder at
03.00 Hrs.in (MW)
Wheather feeder
tripped at 3.01 hrs.by
UFR
Reason of UFR did not
trip.
Load of feeder at
21.00 Hrs.in (MW)
Load of feeder at
21.30 Hrs.in (MW)
Wheather feeder tripped
at 21.54 hrs.by UFR
220 KV Ablowal
Matrix / RS 232
220 V DC + PT Supply
Hourly Reading
220 KV Bahadurgar
h
Matrix / RS 232
220 V DC + PT Supply
Hourly Reading
132 KV Ropar
MMS / RS 232
220 V DC + PT Supply
220 KV Barnala
Matrix / VX40
2H34K2 BCC
220 V DC + PT Supply
220 KV Barnala
Matrix / VX40
2H34K2 BCC
220 V DC + PT Supply
220 KV Barnala
English Electric / MFVOM
22D1
220 V DC + PT Supply
not operated
220 KV Dhuri
GEC Alsom / MFVOM
22D
220 V DC + PT Supply
220 KV Patran
66KV Moonak Khanauri
10.00 12.00
220 V DC + PT Supply
220 KV Sunam
66KV Chhajali, Lehragaga,
Cheema, Ubhewal, Longowal
10.00, 15.00, 10.00, 03.00, 01.05
English Electric(1
No.) / Matrix (2
No.)
220 V DC + PT Supply
5, 7.4, 4 ,1 3.5
5, 7.4, 4 ,1 3.5
2.6, 3.7, 6.8, 2.0, 5.5
2.6, 3.7, 6.8, 2.0, 5.5
![Page 270: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/270.jpg)
Information regarding effectiveness of UFR and df/dt relays during grid disturbance of 02.01.10 under P&M Circle, PSEB, Patiala.
Deatil of individual Relay(Df/Dt)
1 90 0.2 --- --- ---
2 36 0.1 --- --- ---
3 0.3 --- --- ---
nt 10.11 45
Sr.no.
Name of Station with Voltage level where df/dt
installed
Name of individual feeder(s)
with Voltage
level which df/dt
connecteded
Planned Load relief (MW)
Make and Model of
df/dt
Setting in term of
Frequency(Hz)
Time delay (ms) if
any
Setting of Under voltage blocking (%) if any
Setting of Sampling
cycles (nos)
Wheather separate auxiliary
or only PT supply
Load of feeder at
02.00 Hrs.in (MW)
Load of feeder at
03.00 Hrs.in (MW)
Wheather feeder
tripped at 3.01
hrs.by df/dt
Reason of df/dt did not trip.
Load of feeder at
21.00 Hrs.in (MW)
Load of feeder at
21.30 Hrs.in (MW)
Wheather feeder
tripped at 21.54 hrs.by df/dt
220 KV S/S Rajpura
66 KV Sirhind,Rajpura old,Gajjukhera,Banur,Dharamgarh
Areva/ Micom P
923
220 V DC + PT
Supply
supply failed at
01.05 hrs.
supply failed at
02.55 hrs.
supply failed at
02.55 hrs.
supply failed at
02.55 hrs.
38.6972 MW
Hourly Reading
supply failed at
21.52 hrs.
220 KV S/S Bahadurgarh
66 KV Ghanour,Devigarh & Bhankhar
Areva/ Micom P
923
220 V DC + PT
Supply
23.15 MW
10.11 MW
not operated
not operated
15.143 MW
Hourly Reading
not operated
220 KV S/S Derabassi
66 KV Lalru-
1&2,Mubarkpur,WinsonYarn,
Nahar Export,Rama Petro
Areva/ Micom P
923
220 V DC + PT
Supply
supply failed at
01.00 hrs.
supply failed at
01.00 hrs.
not operated
supply failed
already
30.40 MW
45.00 MW
not operated
![Page 271: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/271.jpg)
Annexure 7/III1 of 3BBMB
Make & Model of
UFR
Setting in terms of
frequency(HZ)
Time delay(ms) if any
Setting of under
voltage blocking (%) if any
Setting of sampling
cycles(Nos)
Whether separate auxiliary supply or only PT supply
1 400 Kv Panipat 132 Kv Sonepat 60 Make- ABBModel-
SPAF 340 C-3
48.80 150 30% AUX. Tripped Breakdown Breakdown 32.4 Power Cut
132 Kv Karnal 70 Make- ABBModel-
SPAF 340 C-3
48.80 150 30% AUX. 8.6 Breakdown Breakdown 26.8 Power Cut
33 Kv Chajpur 15 Make- ABBModel-
SPAF 340 C-3
48.80 150 30% AUX. Breakdown Breakdown Breakdown Under Powercut
6.5 Power Cut Under Powercut
2 220 Kv Narela 132 Kv Bhadurgarh 30 Make-ABBModel-SPAF
340C-3
48.80 150 30% 9
132 Kv Sonepat 39 Make-ABBModel-SPAF
340C-3
48.80 150 30% 13
3 220 Kv Kurukshetra132 Kv Pehowa(RLSE)
81 ABB SPAF 340C3
48.80 150 30% AUX. 8.5 Only hourly reading is recorded
Time slot 02:00 to
03:00 AM/PM and
08:00 to
4 220 Kv Jagadhri 66 Kv Sadhaura-II(Earlier Named as 66KV Adhoya-Brara)(RLSE)
0.00 ABB SPAF 340C3
48.80 150 30% AUX. 11 9 No 14.5 Only hourly reading is recorded
No
ANNEXURE 7/III
Total suppy failure
AUX. RLSE out of service due to defective UPS
RLSE out of service due to defective UPS
Total supply failure at Narela Sub-Station from
00:30 to 08:15 hrs
Breakdown from 01:43 hrs to 09:50 hrs (under shutdown) BBMB schedule powercut from
21:46 to 23:36
Name of station with voltage level where
UFR installed.
Name of individual feeder(s) with
voltage level on which UF relay
connected
Planned load relief
(MW)
Details of individual relays (UFR) Remarks (any other informatio
n)
Sr. No.
Load of feeder at 21:00 hrs (in MW)
Load of feeder at 21:30 hrs (in MW)
Whether feeder
tripped at 21:54 Hrs by UFR
Reason if UFR did not trip
Load of feeder at
02:00 Hrs. (in MW)
Load of feeder at
03:00 Hrs. (in MW)
Whether feeder
tripped at 03:01 Hrs by UFR
Reason if UFR did not trip
![Page 272: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/272.jpg)
Annexure 7/III2 of 3
Make & Model of
UFR
Setting in terms of
frequency(HZ)
Time delay(ms) if any
Setting of under
voltage blocking (%) if any
Setting of sampling
cycles(Nos)
Whether separate auxiliary supply or only PT supply
Name of station with voltage level where
UFR installed.
Name of individual feeder(s) with
voltage level on which UF relay
connected
Planned load relief
(MW)
Details of individual relays (UFR) Remarks (any other informatio
n)
Sr. No.
Load of feeder at 21:00 hrs (in MW)
Load of feeder at 21:30 hrs (in MW)
Whether feeder
tripped at 21:54 Hrs by UFR
Reason if UFR did not trip
Load of feeder at
02:00 Hrs. (in MW)
Load of feeder at
03:00 Hrs. (in MW)
Whether feeder
tripped at 03:01 Hrs by UFR
Reason if UFR did not trip
5 220 Kv Hissar 132 Kv Hansi - I (RLSE)
0.00 ABB 48.80 60% AUX. 2 4 No Ckt. under breakdown
No
33 Kv Fathebad /Jindal Metal (RLSE)
15 48.80 60% AUX. 6.5 0.5 No 5.5 No
33 Kv Barwala (RLSE)
10 48.80 60% AUX. 4 0.5 No 3 No
33 Kv Textile/HTM (RLSE)
10 48.80 60% AUX. 6 2 No 3.5 No
33 Kv Rajgarh Road (FLAT)
18.5 48.20 60% AUX. 4 0.5 No 9 No
132 Kv Sirsa (FLAT) 50 HBB FCX-1036/2
48.20 150 60% AUX. 10 4 No Ckt. under breakdown
No
132 Kv Rajgarh (FLAT)
60 HBB FCX-1036/2
48.60 500 60% AUX. 18 14 No 36 No
132 Kv Hunamangarh (FLAT)
2 HBB FCX-1034/2
48.60 500 60% AUX. 4 4 No Ckt. under breakdown
No
220 Kv Khetri (FLAT) 184 HBB FCX-1034/2
48.20 150 60% AUX. 54.34 0 No 141.3 No
6 220 Kv Dhulkote 66 Kv IOC(RLSE)
0 48.80 150 36% AUX. 0 0 No 0
66 Kv Chandigarh - I & II
32 48.20 500 30% AUX. 4 each 4 each No Possibly due to inherent features of relay during extreme condition
9 each Possibly due to inherent features of relay during extreme condition
7 220 Kv Ch. Dadri 220 Kv Rewari 90 HBB FCX-1036/2
48.20 500 60% AUX. 39.85 10.86 No 43.47 No
220 Kv Mohindergarh -I
90 HBB FCX-1036/2
48.20 500 60% AUX. 115.94 10.86 No 76.08 No
220/132 Kv 100MVA T/F T-2
53 HBB FCX-1036/2
48.20 500 60% AUX. 76.08 36.23 No 79.71 No
Only hourly reading is recorded
No
Possibly due to
inherent features of
relay during extreme
condition
Possibly due to inherent features of
relay during extreme
condition
Possibly due to
inherent features of
relay during extreme
condition
Possibly due to inherent features of
relay during extreme
condition
ABB SPAF 340C3
![Page 273: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/273.jpg)
Annexure 7/III3 of 3
Make & Model of
UFR
Setting in terms of
frequency(HZ)
Time delay(ms) if any
Setting of under
voltage blocking (%) if any
Setting of sampling
cycles(Nos)
Whether separate auxiliary supply or only PT supply
Name of station with voltage level where
UFR installed.
Name of individual feeder(s) with
voltage level on which UF relay
connected
Planned load relief
(MW)
Details of individual relays (UFR) Remarks (any other informatio
n)
Sr. No.
Load of feeder at 21:00 hrs (in MW)
Load of feeder at 21:30 hrs (in MW)
Whether feeder
tripped at 21:54 Hrs by UFR
Reason if UFR did not trip
Load of feeder at
02:00 Hrs. (in MW)
Load of feeder at
03:00 Hrs. (in MW)
Whether feeder
tripped at 03:01 Hrs by UFR
Reason if UFR did not trip
8 220 Kv Jamalpur 66 Kv Nurewal - I & II 89 48.20 60% AUX. 9 each 9 each Yes 24 each Yes
66 Kv Millerganj - I & II
110 48.20 60% AUX. 9 10
910
Yes 19.521.5
Yes
9 220 Kv Jallandhar 66 Kv Radial - I & II 60 48.20 60% AUX. 1.9 each 1.8 each Yes 6 each Yes
66 Kv Tanda Road - I & II
105 48.20 60% AUX. 11 each 10 each Yes 13 each Yes
66 Kv Cantt - I & II 61 48.20 60% AUX. 67
56
Yes 1013
Yes
10 220 Kv Sangrur 66 Kv Rangia 26 48.80 60% AUX. 2 2 No No
66 Kv Samund Garh 30 48.80 60% AUX. 0 0 No No
66 Kv Badrukha 0.00 48.80 60% AUX. 0 0 No No
66 Kv Bhawanigarh - I 39 48.20 60% AUX. 5 5 No 5 ----
66 Kv Bhawanigarh - II
25 48.20 60% AUX. 3 3 No 4
66 Kv Sunam 0.00 48.20 60% AUX. 0 0 No NoPossibly due to inherent features of relay during extreme condition
66 Kv Patran - I 0.00 48.20 60% AUX. Breakdown Breakdown Breakdown ---- Breakdown Breakdown ----
66 Kv Patran - II 30 48.20 60% AUX.
NOTE: During both collapses only group 3 RLSE i.e. relays at Hisar , 33KV Chhajpur feeder at Panipat & 66KV IOC feeder at Dhulkote were supposed to trip.
Possibly due to inherent features of
relay during extreme
condition
Under Long PTW
Powercut from 21:47
to 23:19
Possibly due to
inherent features of
relay during extreme condition
ABBSPAF340c
(RLSE-Stage3/grou
p:13-14)ABB
SPAF340c (RLSE-Stage1)
Possibly due to inherent features of
relay during extreme
condition
HBBFCX103b
HBBFCX103b
![Page 274: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/274.jpg)
ANNEXURE 7/III
Make & Model of
df/dt relay
Setting in terms of
frequency & rate of change
(HZ, HZs)
Time delay(ms)
if any
Setting of under
voltage blocking (%) if any
Setting of sampling
cycles(Nos)
Whether separate auxiliary supply or only PT supply
1 400 Kv Panipat 132 Kv Sonepat 60 49.9/0.2 200 60% AUX. Breakdown Breakdown 32.4 Powercut
132 Kv Karnal 70 49.9/0.2 200 60% AUX. Breakdown Breakdown 26.8 Powercut
33 Kv Chajpur 15 49.9/0.2 200 60% AUX. Breakdown Breakdown 6.5 Powercut
2 220 Kv Narela 132 Kv Bhadurgarh 30 Make-ABBModel-
SPAF 340 C-3
df/dt: Threshold
Freq. 49.9/0.2 Hz
200 60% AUX. 9 -- No
132 Kv Sonepat 39 Make-ABBModel-
SPAF 340 C-3
df/dt: Threshold
Freq. 49.9/0.2 Hz
200 60% AUX. 13 -- No
3 220 Kv Kurukshetra
132 Kv Pehowa 81 ABB SPAF 340C3
49.9/0.2 200 60% AUX.--
No
4 220 Kv Jagadhri 66 Kv Sadhaura-II(Earlier Named as 66KV Adhoya-Brara)
----- ABB SPAF 340C3
49.9/0.2 200 60% AUX. 11 9 No Possibly due to
inherent features of
relay during
extreme
14.5
--
No Possibly due to inherent
features of relay during
extreme condition
5 220 Kv Hissar 132 Kv Hansi - I ----- ABB 49.9/0.2 200 60% AUX. 2 4 No Ckt. under breakdown --
No
33 Kv Fathebad/Jindal
15 49.9/0.2 200 60% AUX. 6.5 0.5 No 5.5--
No
33 Kv Barwala 10 49.9/0.2 200 60% AUX. 4 0.5 No 3 -- No
33 Kv Textile/HTM 10 49.9/0.2 200 60% AUX. 6 2 No 3.5 -- No
Possibly due to
inherent features of
relay during
extreme condition
Breakdown from 01:43 hrs to 09:50 hrs
Possibly due to inherent
features of relay during
extreme condition
Total supply failure at Narela Sub-Station from 00:30 to 08:15 hrs
features of relay d
Possibly due to
inherent features of
relay during
extreme condition
-----
Load of feeder at 21:00 hrs (in MW)
Total supply failure
----
Sr. No.
Name of station with voltage level where
df/dt installed.
Remarks (any other informatio
n)
Reason if df/dt did not
trip
Load of feeder at
02:00 Hrs. (in MW)
Load of feeder at
03:00 Hrs. (in MW)
Whether feeder
tripped at 03:01 Hrs by df/dt
relay
Reason if df/dt did not trip
Load of feeder at 21:30 hrs (in MW)
Whether feeder
tripped at 21:54 Hrs by df/dt
relay
Make- ABBModel-
SPAF 340 C-3
Details of individual (df/dt) relay
Circuit under
breakdown
Name of individual
feeder(s) with voltage level on
which df/dt relay connected
Planned load relief
(MW)
![Page 275: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/275.jpg)
Make & Model of
df/dt relay
Setting in terms of
frequency & rate of change
(HZ, HZs)
Time delay(ms)
if any
Setting of under
voltage blocking (%) if any
Setting of sampling
cycles(Nos)
Whether separate auxiliary supply or only PT supply
Load of feeder at 21:00 hrs (in MW)
Sr. No.
Name of station with voltage level where
df/dt installed.
Remarks (any other informatio
n)
Reason if df/dt did not
trip
Load of feeder at
02:00 Hrs. (in MW)
Load of feeder at
03:00 Hrs. (in MW)
Whether feeder
tripped at 03:01 Hrs by df/dt
relay
Reason if df/dt did not trip
Load of feeder at 21:30 hrs (in MW)
Whether feeder
tripped at 21:54 Hrs by df/dt
relay
Details of individual (df/dt) relay Name of individual
feeder(s) with voltage level on
which df/dt relay connected
Planned load relief
(MW)
6 220 Kv Dhulkote 66 Kv IOC ----- ABB SPAF 340C3
49.9/0.2 200 60% AUX. 0 0 No Possibly due to
inherent features of
relay during
extreme
0 -- No Possibly due to inherent
features of relay during
extreme condition
7 220 Kv Ch. Dadri 220 Kv Rewari 90 ABB 49.9/0.2 200 AUX. 39..85 10.86 No 43.47 -- No
220 Kv Mohindergarh - I
90 49.9/0.2 200 AUX. 115.94 10.86 No 76.08 -- No
220/132 Kv 100MVA T/F T-2
53 49.9/0.2 200 AUX. 76.08 36.23 No 79.71 -- No
8 220 Kv Jamalpur 66 Kv Nurewal - I & II 89 49.9/0.2 200 65% AUX. 9 each 9 each No 24 each -- No
66 Kv Millerganj - I & II
110 49.9/0.2 200 AUX. 10 each 10 each No 19.521.5
-- No
9 220 Kv Sangrur 66 Kv Rangia 26 49.9/0.2 200 60% AUX. 2 2 No 3 -- No
66 Kv Samund Garh 30 49.9/0.2 200 AUX. 0 0 No 0 -- No
66 Kv Badrukha ----- 49.9/0.2 200 AUX. 0 0 No 0 -- No
ABB SPAF340c
(RLSE-Stage-2)
AREVA MICOM P-
430
Possibly due to
inherent features of
relay during
extreme condition
Possibly due to
inherent features of
relay during
extreme
Possibly due to
inherent features of
relay during
t
Tripped on UFR
Possibly due to inherent
features of relay during
extreme condition
Possibly due to inherent
features of relay during
extreme condition
Possibly due to inherent
features of relay during
extreme condition
![Page 276: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/276.jpg)
ANNEXURE 7/IV Sub: Analysis Report of Grid Incident of 2nd January, 2010 (Haryana).
1st Grid Disturbance (01:55 hrs dated : 02.01.2010).
On 02.01.10 during the period from 01:55hrs to 03.55 hrs. due to
simultaneous outage of multiple 400 kV and 220 kV lines of Northern Region due to
heavy fog, the connected power System of J & K, Punjab, Himachal and Haryana
(except South Haryana) got disconnected from the rest of Northern Grid resulting in
outage of HPGCL Generating Units i.e. PTPS Unit-1 (110MW) & PTPS Unit-
2(110MW) tripped at 03:55 hrs, PTPS Unit-5(210MW), Unit-6(210MW), Unit-
7(250MW) and Unit-8(250MW) tripped at 01:55 hrs, DCRTP Yamunanagar Unit-1
(300MW) & Unit-2 (300MW) tripped at 03:03 hrs and FTPS Unit-3(55 MW) tripped at
03:43 hrs. The PTPS Unit-4 ( 110 MW) and Railway supply from PTPS remained
intact.
A total of about 63 nos. 220 kV lines of Haryana tripped. 15 no. lines tripped
due to failure of conventional disc insulators due to heavy fog and one number
string of newly installed antifog insulator on 220 kV NunaMajra-Daultabad Ckt
- I also failed (details are as per Annexure-1).
![Page 277: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/277.jpg)
Annexure‐7/IV
SR. NO. NAME OF S/Stn. NAME OF CIRCUITDATE AND TIME OF FAULT
FROM TO
1 220 Kv Nissing
00:40 17:00
(02.01.10) (04.01.10)
2 220KV Pehowa 00:45 12:50
3 220 S/Stn Rohtak 1.40(2.01.10) 17.15(2.01.10)
4 220 Kv Kaithal 01:45 18:55 (3.1.2010)
5 220 kV Saffidon 1.50 00:20 (03.01.10)
6 220 kV Jind 1.54 19.55
7 220 Kv Kaithal 02:10 17:05
8 220 kV Narwana 2.24 17.02
9 220 kV S/Stn. IA Hisar. 220 kV Hisar-Jind-II 03:27 19:55
10 220KV Nuna Majra 3.37 19.2
11 220 kV Narwana 03:58 20:30(04.01.10)
12 220 kV S/Stn. IA Hisar. 04:13 18:29
13 220 kV Narwana 4.13 18.5
14 220 kV Jorian 5.51 13.42
15 220 Kv Nissing 06:40 15:40
CAUSE OF TRIPPING/BREAKDOWN
220 kv Nissing –Salimpur CKt No-1
Red phase disc flashed& broken at Tower no.87
220KV Pehowa-Kaithal Ckt-1
R Phase disc insulator damage at tower no-24
220 KV Rohtak- PTPS Ckt-II
B phase string at tower location No 37 found damaged
220 KV Kaithal-Nissing CKT No-2
Red & Yellow Phase disc Puntured at Tower No. 80.
220 kV Narwana – Saffidon Ckt I
Tripping is due to Disc broken at Tower No. 90 and 40.
220 kV Jind – Hisar Ckt. II
Tripping is due to Disc Broken at Tower NO. 108.
220 KV Kaithal-Narwana CKT No-2
B Phase disc puncture at Tower no-75
220- KV Narwana – Kaithal Ckt I
Tripping is due to Disc broken at Tower No. 78.
Disc Insulator found damaged of all three phases as reported by
Staff of 220 kV Jind.
220KV Nunamajra-Daultabad CKT-I
Red phase string of tower Location No 7 found damaged
220 kV Narwana – Hisar Ckt. S/C
Disc flashed/broken at tower no.22
220 kV Matana-Bhuna
Disc Insulators damaged at Tower No. 183 of R-Phase.
220 kV Narwana – Bhuna Ckt.
Tripping is due to Disc broken at Tower No. 183.
220 kV Jorian – Shahbad Ckt. II
Tripping is due to Red Phase Disc Puncture at Tower No. 114
220 kv PTPS –Nissing Ckt -2
R Phase Disc Insulator Broken At Tower no-55
![Page 278: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/278.jpg)
Information of UFR ANNEXURE-7V
Make & Model of
UFR
Setting in terms of
frequency in HZ
Time delay(ms)
if any
Setting of under
voltage blocking(%) if any
Setting of sempling
cycle(Nos)
Whether separate auxillary supply or only PT Supply
1220 KV S/Stn.
Narwana100 MVA, 220/132 KV T/F T-1 20
EE MFVUM
48.6 Hz - - -D.C.
Supply3.03 3.03 No
Frequency did not reach upto 48.6 hz
6.06 MW .- NoFrequency
did not reach upto 48.8 hz
Load not recorded at 2130 hrs. as only hourly recording is
made.
2220 KV S/Stn.
Narwana100 MVA, 220/132 KV T/F T-2 35
EE MFVUM
48.6 Hz - - -D.C.
Supply18.18 18.18 No
Frequency did not reach upto 48.6 hz
30.30 MW .- NoFrequency
did not reach upto 48.6 hz
Load not recorded at 2130 hrs. as only hourly recording is
made.
3132 KV S/Stn
Jind(N)132 KV Jind-Narnaund line 15
Areva MFVUM
48.8 Hz - - -D.C.
Supply0 0 No
Main supply failed at
01:55 hrs.Negligible .- No
Relay healthy but did not
trip
Load not recorded at 2130 hrs. as only hourly recording is
made.
220 KV S/Stn Jind 132 KV Jind - Naguran line 10Areva
MFVUM48.8 Hz - - -
D.C. Supply
0 0 NoMain supply
failed at 01:55 hrs.
18 MW .- NoRelay healthy
but did not trip
Load not recorded at 2130 hrs. as only hourly recording is
made.
4 Sec-52 A 66KV Sec-28 ckt 2 20Areva
MFVUM48.8 -
D.C. Supply
7 0Main supply
failed at 02:25 hrs.
14 .- noRelay healthy
but did not trip
Load not recorded at 2130 hrs. as only hourly recording is
made.
5 Bhiwani 132KV Tosham 20Areva
MFVUM48.8 -
D.C. Supply
0 0 noRelay
healthy but did not trip
nil nil yes .-
132KV Tosham was
shifted to Isharwal now
shifted to 132kv
bhiwani-2
6 220KV Fatehabad 132KV Bhattu 10Areva
MFVUM48.8 - 8 0 no
Relay healthy but did not trip
9 10 NoRelay healthy
but did not trip
supply fail
7 220KV Tepla 66KV BABYAL-Mulana 25Areva
MFVUM48.8 - 8 7 no
Relay healthy but did not trip
nil nil noRelay healthy
but did not trip
load restriction
20:35-21:32
8 220KV Rania 132KV Ellnabad 40Areva
MFVUM48.8 - 8 8 no
Relay healthy but did not trip
8 8 noRelay healthy
but did not trip
9 220KV Mohindergarh 132KV T/F 220/132KV T-7 35Areva
MFVUM48.8 - 50 2 NO
Relay healthy but did not trip
14 14 noRelay healthy
but did not trip
supply fail
10 220KV Cheeka 132KV cheeka 1 & 2 30Areva
MFVUM48.8 35 30 No
Relay healthy but did not trip
20 15 NoRelay healthy
but did not trip
Reason if UFR Not Tripped
Remarks if any other
information
Load of feeder at 21:30hrs
Whether the feeder tripped at 21:54hrs
Reason if UFR Not Tripped
Load of feeder at 21:00hrs
Sr No.
Name of Sub-station with voltage level
where UFR installedName of Individual feeder on
which UFR is connectedPlanned Load Relief (MW)
Detail of Individual relay (UFR)
Load of feeder at 2:00hrs
Load of feeder at 3:00hrs
Whether the feeder tripped at 3:01hrs
![Page 279: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/279.jpg)
11 220KV Hisar IA 132KV Beer 25Areva
MFVUM48.8 - 11 2 no
Relay healthy but did not trip
15 15 noRelay healthy
but did not trip
supply fail
Information of UFR
Make & Model of DF/DT
Setting in terms of
frequency in HZ
Time delay(ms)
if any
Setting of under
voltage blocking(%) if any
Setting of sempling
cycle(Nos)
Whether separate auxillary supply or only PT Supply
1132 KV S/Stn Narwana(N)
132 KV Narwana-Garhi line 26ABB , SPAF
340CB0.2HZ/SEC - - -
UPS supply provided
4 MW 4 MW No
Frequency did not reach upto tripping
level
7 MW .- No
Frequency did not reach upto tripping
level
Load not recorded at 2130 hrs. as only hourly recording is
made.
2 132 KV Narwana-Tohana line 10 Nil 0.2HZ/SEC - - -UPS supply provided
Negligible Negligible No
Frequency did not reach upto tripping
level
Negligible .- No
Frequency did not reach upto tripping
level
Load not recorded at 2130 hrs. as only hourly recording is
made.
3 132 KV Narwana-Uklana line
50
ABB , SPAF 340CB
0.2HZ/SEC - - -UPS supply provided
18 MW 14 MW No
Frequency did not reach upto tripping
level
21 MW .- No
Frequency did not reach upto tripping
level
Load not recorded at 2130 hrs. as only hourly recording is
made.
4 132 KV Narwana-Narwana(O) line
22
ABB , SPAF 340CB
0.2HZ/SEC - - -UPS supply provided
4 MW 4 MW No
Frequency did not reach upto tripping
level
15 MW .- No
Frequency did not reach upto tripping
level
Load not recorded at 2130 hrs. as only hourly recording is
made.
5 132 KV Narwana-Uchana line 0ABB , SPAF
340CB0.2HZ/SEC - - -
UPS supply provided
Negligible Negligible No
Frequency did not reach upto tripping
level
Negligible .- No
Frequency did not reach upto tripping
level
Load not recorded at 2130 hrs. as only hourly recording is
made.
6220 KV S/stn Safidon
132 KV Safidon Matlauda line 16GE make MULTILIN
6500.1 HZ 0.20 SEC 60% -
D.C. Supply
Nil Nil No
line tripped at 01:45 hrs.on df/dt relay
30 MW .- NoRelay healthy
but did not trip
Load not recorded at 2130 hrs. as only hourly recording is
made.
7 220KV Daultabad 66KV Sec-23 ckt & 2 35GE make MULTILIN
6500.1 - - -
D.C. Supply
17 0 NOSUPPLY FAILED at 2:07hrs
15 .- NORelay healthy
but did not trip
Load not recorded at 2130 hrs. as only hourly recording is
made.
8220KV Bhuna
132kv Teliwada35
GE make MULTILIN
650 0.1- - -
D.C. Supply
NIL NIL No
1.- NO
Relay healthy but did not
trip
Feeder was running from 132KV Ratia
Load of feeder at 3:00hrs
Whether the feeder tripped at 3:01hrs
Reason if UFR Not Tripped
Detail of Individual relay (DF/DT)
Load of feeder at 2:00hrs
Remarks if any other
information
Reason if UFR Not Tripped
Load of feeder at 21:00hrs
Load of feeder at 21:30hrs
Whether the feeder tripped at 21:54hrs
Sr No.
Name of Sub-station with voltage level
where DF/DT installed
Name of Individual feeder on which DF/DT is connected
Planned Load Relief (MW)
![Page 280: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/280.jpg)
DETAIL OF TRIPPINGS / BREAKDOWNS IN HVPN SYSTEM ON 02.01.10 ANNEXURE- 7/IVDATE AND TIME OF
FAULTDATE AND TIME OF
FAULTPROTECTION OPERATED
FROM TO Relay operated at This end Relay operated at Other end
1 220 Kv Nissing 220 kv Nissing –Salimpur CKt No-100:40
(02.01.10)17:00
(04.01.10) Trip R Phase, Zone -1 Zone-2 ,Zone -3 , Ar Lock
out, Distance 16.2 KMR-phase pick up, zone-1, AR lock out,
Dist. 14 Km.
2 220KV Pehowa 220KV Pehowa-Kaithal Ckt-1 00:45 12:50DPR main 1 REL511 Zone -1 Trip ,Start Zone -2 ,
Distance 0.9KM Start B Phase
DPR MICOM, Zone-II, B-Phase to E, location 38.25 Km. DPR SHPM Qutram
B-Phase to E, auto recloser
4 220KV Nuna Majra 220KV NunaMajra- Daulta Bad CKT-II 1.24 13.45 DPR BGT Zone 1 6.27 Km No tripping
5 220 kV Saffidon 220 kV Saffidon – Narwana Ckt. II 1.35 1.10 (3.1.2010)
Facia Main-I & II trip, auto recloser lockout DPR Main-I, REL-511, Main-II trip auto recloser lockouCB Red, Yellow & Blue Phase – 3 Phase start wit
neutral Zone-I trip 15.9% Relay 186, 286 Red, Yellow and Blue Phase.
th No tripping
6 220 Kv Nissing 220 kv Nissing –Salimpur CKt No-2 01:35 18:15 Trip B Phase Zone-1 with relay Ar Lock out
Distance 2.4 KmY-phase, zone-I , AR lock out Dist. 14.26
Km.
7 220 S/Stn Rohtak 220 KV Rohtak- PTPS Ckt-II 1.40(2.01.10) 17.15(2.01.10) No tripping DPR AGT Zone 1 12.6 Km
8 220 kV Jind 220 kV Jind – Hisar Ckt. I 1.40 17.10Main-I, location 0.6 KM event DGT Main-II, Yellow
Phase earth fault, Relay & Auto recloser.
Auto recloser lockout Zone-I, BG Location 14.33 KM & Jassia Main-I
protection operated & auto reclose.
9 220 Kv Nissing 220 kv PTPS –Nissing Ckt No-1 01:42 16:00 DPR Zone Y Phase Ar lock out Distance 2.35 KM trip, Y-phase, AR lock out, Zone-I, 28
Km
10 220 kV S/Stn. IA Hisar. 220 kV Hisar-Jind-I 01:43 17:10DPS Main-I, Protection operated Zone-I, Event BGT location-143.13 km and Tripping Relay,
Auto Reclose Relay-79 lockout.
DPS Main-I, Zone-I, Location-0.02 km, Event-BGT, Main-II, Y-Phase, Earth
Fault, Auto Reclose
NAME OF S/Stn.SR. NO. NAME OF CIRCUIT
![Page 281: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/281.jpg)
11 220 Kv Kaithal 220 KV Kaithal-Nissing CKT No-1 01:45 15:15 DPR B Phase to Earth Zone-2 43.33 Km No tripping
12 220 Kv Kaithal 220 KV Kaithal-Nissing CKT No-2 01:45 18:55 (3.1.2010) DPR B Phase to Earth Zone -1 , location:8.896
KMRPhase to earth fault in zone-1
13 220 S/Stn Rohtak 220 KV Rohtak- PTPS Ckt-I 1.50 7.52(02.01.10) Earth fault No tripping
14 220 Kv Sonipat 220 kv PTPS- Sonipat CKT-1 01:50 10:25 B Phase Distance 23.38 KM
Main-1 Micom ABC Phase Zone-1 trip distance 4.252KM
Main-11 Quadra MHO
15 220 kV Saffidon 220 kV Narwana – Saffidon Ckt I 1.50 00:20 (03.01.10)Start Blue Phase with Neutral Zone-I trip Red,
Yellow & Blue Phase distance 27.06 KM No tripping
16 220 kV Saffidon 220 kV Saffidon – PTPS Ckt. I 1.50 21.20 Main DPR REL-511 Trip CB, Red, Yellow & Blue Phase trip distance 91.5 %, Main II RAZOA DPR
No tripping
17 220 kV Saffidon 220 kV Saffidon – PTPS Ckt. II 1.50 21.15Main-I trip all Auto reclose lockout CB Red,
Yellow & Blue Phase trip Main-II ROZOA R.N. TripNo tripping
18 220 kV Saffidon 220 kV Saffidon – PTPS Ckt. III 1.50 15.25Main-I, Zone-I Trip all auto reclose lockout trip
distance 52.7% No tripping
19 220 kV Saffidon 220 kV Saffidon – Jind Ckt. I 1.50 13.40Main-I, MICOM Start Phase – C Zone-I fault
duration 50.73 ms. Zone-I trip.No tripping
20 220 kV Jind 220 kV Jind – Hisar Ckt. II 1.54 19.55Main-I, Zone-I, BGT, location 1.40 KM Main-II
Yellow Phase E/F auto recloser, over load alarm relay
Over load relay 50L location 101.27 KM event BG and Jassia over load alarm Ckt. II main-I protection operated auto
reclose.
21 220 kV Jind 220 kV Hisar-Jind-II 01:54 3.:24DPS Main-I Protection operated, Location-101.27 km, Event-BGT, Auto Reclose Phacia – overload
Alarm
DPS Main-II, Zone-I, Location 1.40, Event-BGT, DPS Main-II, Zone-I, Y PhaseEarth Fault, Auto Reclose, Relay, Over
load Relay
22 220 kV Jind 220 kV Jind – Saffidon Ckt. I 1.59 13.20Main-I start Phase C trip Zone-I location 2.07 KM
Carrier I & II Main-II Zone I, location 2.065 KM start Phase C trip.
Zone-I, Phase ABC location 37.17 KM onMain-I & II Zone-I location 37.27 KM
tripped phase ABC.
23 220KV Nuna Majra 220KV NunaMajra - PGCIL Ckt-I 2.07 3.05 DPR AGT Zone-1 1.19 Km DPR Zone-1 Distance 0.5 KM
24 132KV PTPS 132 kv PTPS –Diwana CKt-1 02:07 10:00 DPR R Phase Zone-1 No tripping
25 220KV Nuna Majra 220KV Nuna-Majra PGCIL Ckt-II 2.08 2.53 ABC Trip No tripping
![Page 282: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/282.jpg)
26 220 Kv Kaithal 220 KV Kaithal-Narwana CKT No-2 02:10 17:05 DPR B Phase to earth Zone-1 , 10.04 KmDPR main REL-670 trip B-Phase, Zone-
I, auto recloser
![Page 283: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/283.jpg)
27 220 kV Narwana 220 kV Narwana – Kaithal Ckt.II 2.10 17.03Main-I, REL-670, DPReral Tripp. Blue Phase Zone-
I auto recloserBlue Phase to earth zone-I distance
10.04 KM.
28 220KV S/stn Bhiwani 220KV Premnagar-Bapora Ckt-I 2.11 16.26 Dt. 04.01.10 Nil
Facia Micom p-442 Relay Trip Quadra Relay Trip Indicaton Main-1 Micom ABCPhase Zone-1 trip Active Group-1 E/F in
1st distance 4.252KM Frequency 49.95HzMain-11 Quadra MHO 86 & 86M-2A
86M2B 86& m2c 86M-2A 86M2B 86& m2c
29 220 KV S/stn Badshahpur 220 KV Badshahpur- Pali Line Ckt-I 02:15 12:55 Nil YGT Zone -I 12.3 Km
30 220 kV S/Stn. IA Hisar. 220 kV Bus Coupler 02:20 02:40 Earth Fault Relay No tripping
31 220 Kv Kaithal 220 KV Kaithal-Narwana CKT No-1 02:24 17:00 DPR R Phase to earth Zone -1 , 8.4 KM trip R-Phase Zone-II auto recloser lock
out
32 220 kV Narwana 220- KV Narwana – Kaithal Ckt I 2.24 17.02Main-I, REL-670, DPRRed Phase Zone-II auto
recloser lockout Red Phase to earth zone distance 8.04
KM on Main-I
33 220 KV S/stn Sec 52 220 KV Sec 52- Pali Line Ckt-I 02:25 11:10 nil E/F
34 220 KV S/stn Badshahpur 220 KV Badshahpur- Samaypur Ckt-II 02:33 18:46 Nil BGT Main-I & ABCG Main -II
35 132KV PTPS 132 kv PTPS –Diwana CKt-2 02:35 07:13 DPR ,RSN Zone -2 No tripping
36 220 Kv Kaithal 220 KV Kaithal-PGCIL CKT No-2 02:35 17:50 DPR R Phase to Earth Zone-1 No tripping
37 220 KV S/stn Badshahpur 220 KV Badshahpur- Pali line Ckt-II 02:40 12:55 YGT Zone -I YGT Zone -I (8.9 Km )
38 220KV S/stn Bhiwani220KV Prem Nagar-Bapora Ckt-1 & Ckt
2-
2.50 11.17 NilCkt-1 Micom p-442 DPS ABC Zone-1
Fault Loc. 3.527 KM
39 220 kV S/Stn. IA Hisar. 220 kV Hisar-IA BBMB-II 02:55 8.30 Over load Alarm Relay with Timer 50Y/2T No tripping
40 220KV Pehowa 220KV Pehowa-Kaithal CKT-II 02:55 07:20Micom P-442 Start Phase A B C –N Tripped
Phase A.B.C TOC Start Distance 40.13 KM AR Lock out DPR Main -1
No tripping
41 220 Kv Kaithal 220 KV Kaithal-PGCIL CKT No-1 02:58 07:33 DPR B Phase to Earth Zone-1 Active group one B-Phase, location 12.8
Km.
42 220 kV S/Stn. Fatehabad 220KV PGCIL Hisar-Fatehabad Ckt-II 3.02 3.55 DPS operated Zone-I, Blue Earth, 24.2 km DPS operated Zone-I, Blue Earth
43 220 KV S/stn Badshahpur 220 KV Badshahpur- Samaypur Ckt-I 03:24 18:46 Nil DPR YGT Zone -II 16.6 Km
44 220 kV Jind 220 kV Jind – Saffidon Ckt. II 3.25 12.55 DPR Main – I & II No tripping
45 220 kV Jind 220 kV Jind – PTPS Ckt. I 3.25 12.25Main-I, Zone-II location 98.72 KM event ABC Main-
II Zone-II and auto recloserDPR Main-I & II
![Page 284: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/284.jpg)
46 220 kV Jind 220 kV Jind – PTPS Ckt. II 3.25 16.15Main-I zone-I location 45.5 KM Event BGT Main-II
Phase – Yellow E/FDPR II operated auto recloser lockput
DPR-I.
47 220 kV S/Stn. IA Hisar. 220 kV Hisar-Jind-II 03:27 19:55Main-I, Zone-I, Location-41.66, Protection
Operated Relay ABC and Earth Fault Relay-86, Event BGT
- (Supply was already fail from PTPS)
48 220 kV S/Stn. IA Hisar. 220 kV Hisar-Narwana 03:27 05:20DPS location 38.9 km, R/Y/B Phase,Trip, Zone-I,
Overcurrent, Blue Phase, Auto recluse DPS Y/B Phase, location 39 km, Start
Zone-I, Zone-II, Zone-III, Trip Zone-I
49 220 kV S/Stn. IA Hisar. 220 kV Bus Coupler 03:27 03:42 Earth Fault Relay No tripping
50 220 KV S/stn Sec 52 220 KV Sec 52- Pali Line Ckt-II 03:30 24:00 nil BGT Zone-I, Auto reclose
51 220KV Nuna Majra 220KV Nuna-Majra PGCIL Ckt-I 3.37 7.37 DPR AGT -1.79 Km No tripping
52 220KV Nuna Majra 220KV Nunamajra-Daultabad CKT-I 3.37 19.2 DPR AGT Zone-1 1.93 Km No tripping
53 220 Kv Sonipat 220 kv PTPS- Sonipat CKT-2 3:50 14:40 Y-Phase fault Distance 2.94 KM
No tripping
54 220 kV Narwana 220 kV Narwana – Hisar Ckt. S/C 03:50 20:30(04.01.10)Trip Red, Yellow & Blue Zone-I trip location 39
KM DPR Zone-I distance 38.9 KM Red,
Yellow & Blue Phase
55 220 kV S/Stn. IA Hisar. 220 kV Matana-Bhuna 04:13 18:29 Red Phase to Earth, DPS 13.5 km Red phase to Earth 7 km
56 220 kV Narwana 220 kV Narwana – Bhuna Ckt. 4.13 18.5Main-I, MICON T-442, Start Red Phase with
Neutral Zone-III location 49.84 KmNo tripping
57 220KV Nuna Majra 220KV NunaMajra PGCIL Ckt-II 4.15 7.3 AB Trip Z-1 No tripping
58 220KV Pehowa 220KV Pehowa-Shahbad CKt-II 05:46 07:37Micom T-442 Active group-1 Start Phase 3
Tripped Phase ABC AR Lockout Fault in zone none DPR Main 1 Lamp SOTF Auto recloser
Low air pressure (facia)
59 220 kV Jorian 220 kV Jorian – Shahbad Ckt. II 5.51 13.42
Main-I, Zone-II, Phase-I tripped ABC tripping relaA-B Phase & Phase Main-II Phase-A Zone-II Aux., Main-II, Zone-II & III Facia Main-I & II auto reclose
lockout
y
r
Tripping of showing facia indication Main-I & II auto recloser lockout
distance 30.40 KM Zone-II Phase – A Auto recloser with Relay.
60 220 kV S/Stn. IA Hisar. 220 kV Hisar-Narwana 05:58 20 ;30 (4.01.10)DPS Zone-I, R/Y/B Fault Location 38.9 km, Auto
Reclose No tripping
61 220 Kv Nissing 220 kv PTPS –Nissing Ckt NO-2 06:40 15:40R Y B Phase DPR Zone-1 ,Zone-2 Ar Lock out
Distance 42.3 KMDPR trip, Zone-I&II, AR lock out, B-
Phase 14 Km
62 220 kV Shahbad 220 kV Shahbad – Pehowa Ckt. II 11.15 11.45DPR Main- REL-511 Zone-3 start, Start Red Phase, Start NVE, DEF. with auto recloser.
No tripping
![Page 285: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/285.jpg)
63 220 Kv Kaithal 220 KV Kaithal-PGCIL CKT No-1 11.15 14.07 (3.1.2010) DPR R- Phase to Earth Zone-1 ,16.04Kms No tripping
64 220 kV Tepla 220 kV Tepla – Madanpur Ckt. II 21.23 23.25Relay showing Type ER No fault DPR SEL C2-1 Zone-I. No found operated distance non shown
group-6 recloser lockout No tripping
65 220 kV S/Stn. Fateha-bad 220KV Fatehabad-Matana-I & II 21:54 23:55 No tripping Grid Failure
66 220 kV S/Stn. Fateha-bad 220KV Fatehabad-Mayar Ckt-I 21:54 00:56 (3.1.10) No tripping Grid Failure
67 220KV S/stn Bhiwani220KV Prem Nagar-Bapora Ckt-1 & Ckt
2-
21.54 0.04 Nil Nil
68 220 kV Tepla 220 kV Tepla – Madanpur Ckt. –I 21.54 23.25Main-I, DPR operated Zone-I type C-A distance 52
KM Group-I auto recloser lock No tripping
69 220 kV S/Stn. IA Hisar.All 220 kV main supply failed due to
Grid System Failed at 220 kV S/Stn. IA Hisar
21.54 23.05 No tripping supply fail No tripping supply fail
70 220 kV S/Stn. IA Hisar.220KV Hisar -BBMB Ckt-I & 220KV
Hisar -Jind-I & II21:54 23:05 No tripping supply fail No tripping supply fail
71 220 kV S/Stn. IA Hisar. 220KV Hisar IA- PGCIL Ckt-1 21:54 23:22 No tripping supply fail No tripping supply fail
72 220 kV S/Stn. IA Hisar. 220KV Hisar IA- PGCIL Ckt-2 21:54 00:30 No tripping supply fail No tripping supply fail
73 220 kV S/Stn. Bhuna 220 kV Bhuna-Narwana Line 21:54 23:25 No tripping supply fail No tripping supply fail
74 220 kV S/Stn. Bhuna 220 kV Matana-Bhuna line 21:54 23:45 No tripping supply fail No tripping supply fail
01:10 No tripping supply fail No tripping supply fail400KV Hisar PG 21:5475220 kV S/Stn. Isharwal, 132 kV S/Stn.
Miran & 132 kV S/Stn. Tosham
![Page 286: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/286.jpg)
Make & Model of
UFR
Setting in terms of
frequency in HZ
Time delay(ms)
if any
Setting of under
voltage blocking(%) if any
Setting of sempling
cycle(Nos)
Whether separate auxillary supply or only PT Supply
1220 k.v. S/stn. Shahbad(m)
66 k.v. s/stn. Nalvi,Babain
,Jansui81.6 MW
ABB spaf34C3
48.6 hz 0.5 sec. - -
auxillary supply and PT
both used
60 Amp60 Amp
(7.62MW)Not tripped
frequency did not
reach upto 48.6 hz
120 Amp (15.24MW
)120 Amp Yes -
It tripped at 21:54 hrs and
restored at23:35 hrs
giving relief of 10.2 MW
220KV S/Stn, Rohtak
132KV Gohana, Feeder
33MW MFVUM 48.6HZ ... ... ...D.C.
supply... ... No No supply 135 A ... No No supply
Supply failed from PTPS
end and PGCIL end at 21:50 hours
220KV S/Stn, Naunamajra
132KV Jhajjar Feeder
45MW MFVUM 48.8HZ ... ... ...D.C.
supply65A ... No No supply 120 A ... No No supply
Supply failed from PTPS
end and PGCIL end at 21:50 hours
132KV Fazilpur
33KV Incomer-I &
II
25MW & 20MW
ABB/STAF-340C3
48.80 -- -- --
Aux. Supply
provided with UPS
80Amp. & 40Amp.
-- Not tripped 0Amp.40Amp. & 40Amp.
not recorded
Not tripped
132KV PTPS132KV Munak
34.32MWABB/STAF-
340C348.80 -- -- --
Only PT supply
40Amp. 30Amp. Not trippedDue to non particular
time setting100Amp.
Not tripped
Due to non particular
time setting
132KV Sirsa - Begu line
39 (Avg.)
Hy-Tech controls SPAF-340C3
48.80 0.15 60% -Separate auxillary supply
60 Amp 60 Amp. No
Scheduled time 6 to 7 and 18 to
19
115 Amp. 115 Amp. NoScheduled time 6 to 7
and 18 to 19
132KV Sirsa - Odhan -
Dabwali line43 (Avg.) -do- 48.80 0.15 60% - -do- 210 Amp 190 Amp. No
Scheduled time 11 to 12 and 23
to 24
140 Amp. 140 Amp. NoScheduled
time 11 to 12 and 23 to 24
ANNEXURE 7/V
Format for information of UFR
220KV S/Stn. HVPNL, Sirsa
Planned Load Relief (MW)
Load of feeder at 21:30hrs
Whether the feeder tripped at 21:54hrs
Reason if UFR Not Tripped
Load of feeder at 21:00hrs
Reason if UFR Not Tripped
Because 132KV supply got failed from 220KV SNP. However prior to supply failure the record shows
good frequency i.e 49.84.
Remarks if any other
information
Sr No.
Name of Sub-station with
voltage level where UFR
installed
Name of Individual feeder on
which UFR is connected
Detail of Individual relay (UFR)
Load of feeder at 2:00hrs
Load of feeder at 3:00hrs
Whether the feeder tripped at 3:01hrs
![Page 287: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/287.jpg)
Make & Model of DF/DT
Setting in terms of
frequency in HZ
Time delay(ms)
if any
Setting of under
voltage blocking(%) if any
Setting of sempling
cycle(Nos)
Whether separate auxillary supply or only PT Supply
1220 KV s/Stn.
Jorian.
66 KV Jorian-Radaur Ckt-
II50 mw
GE make MULTILIN6
500.1 HZ .01 SEC 40% PT 5 MW 5 MW
Grid fail at 3.01 Hrs.
11 MW 11 MW
Feeder tripp. 21.55 HRS.
tripped off
1220 KV S/STN
NISSING
132 KV NISSING -
JUNDLA LINE47 MW
ABB , SPAF 340CB
0.2HZ/SEC ... .... .....P T
SUPPLYNIL NIL NO
SUPPLY FAILED
90 A 90 A 90 ASUPPLY FAILED
132 KV NISSING -
SAGGA LINE88 MW
ABB , SPAF 340CB
0.2HZ/SEC ... .... ....P T
SUPPLYNIL NIL NO
SUPPLY FAILED
90 A 90 A 90 ASUPPLY FAILED
2132 KV S/STN
KARNAL132/33KV,T-1
T/F,25 MVA
ABB , SPAF 340CB
0.2HZ/SEC .... .... ....P T
SUPPLY SUPPLY
FAILSUPPLY FAILED
SUPPLY FAILED
SUPPLY FAILED
29 A 29 ASUPPLY
FAILSUPPLY FAILED
132 KV KNL-NILOKHERI
LINE52 MVA
ABB , SPAF 340CB
0.2HZ/SEC .... .... ....P T
SUPPLY SUPPLY
FAILSUPPLY
FAILSUPPLY
FAILSUPPLY FAILED
.... .....SUPPLY
FAILSUPPLY FAILED
132 KV KNL-MADHUBAN
LINE134 MVA
ABB , SPAF 340CB
0.2HZ/SEC .... .... ....P T
SUPPLY SUPPLY
FAILSUPPLY
FAILSUPPLY
FAILSUPPLY FAILED
167 A ....SUPPLY
FAILSUPPLY FAILED
132/11 KV ,T-6 T/F
16 MVAABB , SPAF
340CB0.2HZ/SEC .... .... ....
P T SUPPLY
SUPPLY FAIL
SUPPLY FAIL
SUPPLY FAIL
SUPPLY FAILED
39 A ....SUPPLY
FAILSUPPLY FAILED
3220 KV S/STN
UNISPUR
132 KV UNISPUR-BHADSON
LINE
1.9 MW
G.E INDIA INDUSTIRAL PVT LTD , F-
650 BFBF 1GOH16
0.20HZ/SEC
.... ..... 64P T
SUPPLYSUPPLY
FAILSUPPLY
FAILSUPPLY
FAILSUPPLY
FAIL19 A 19 A
SUPPLY FAIL
SUPPLY FAILED
220KV S/Stn. HVPNL, Sirsa
132KV Sirsa - Begu line
39 (Avg.)
Hy-Tech controls SPAF-340C3
49.9 0.15 60% -Separate auxillary supply
60 Amp 60 Amp. No
Relay did not
operated however relay in healthy
condition
115 Amp. 115 Amp.Tripped
off at 21.50 Hrs.
-
Detail of Individual relay (DF/DT)
Load of feeder at 2:00hrs
Load of feeder at 3:00hrs
Whether the feeder tripped at 3:01hrs
Sr No.
Name of Sub-station with
voltage level where DF/DT
installed
Name of Individual feeder on
which DF/DT is connected
Planned Load Relief (MW)
Remarks if any other
information
Reason if dfdt Not Tripped
Load of feeder at 21:00hrs
Load of feeder at 21:30hrs
Whether the feeder tripped at 21:54hrs
Reason if Df/Dt Not Tripped
Information of df/dt
![Page 288: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/288.jpg)
Make and Model of UFR
Setting terms of frequency (Hz)
Time delay (ms), if any
Setting of Under voltage blocking (%) if any
Setting of Sampling cycles (nos)
Whether separate auxiliary supply or only PT supply
1132kV GACL Dharlaghat
In firm's premises on 132kV
10 M/s. EE 48.8 0.1 PT 20 18 Yes 17 12 Yes
2132kV ACC Barmana
In firm's premises on 132kV
10 M/s. ABB 48.8 Instt. PT 50 38 Yes 47 50 Yes
3132kV GACL Dharlaghat
In firm's premises on 132kV
10 M/s. EE 48.6 0.1 PT 0 0 No
Feeder tripped earlier stage due to grid failure
0 0 No
Feeder tripped earlier stage due to grid failure
4132kV ACC Barmana
In firm's premises on 132kV
10 M/s. ABB 48.6 Instt. PT 0 0 No
Feeder tripped earlier stage due to grid failure
0 0 No
Feeder tripped earlier stage due to grid failure
5 220kV Kunihar132kV Kunihar Barotiwala-II
75 M/s. JVS 48.2 Instt. PT 48 40 NoLoad relief obtained due to grid failure
35 29 NoLoad relief obtained due to grid failure
ANNEXURE-7/VI
Load of feeder at 2100 Hrs (in MW)
Planned load relief (MW)
Details of Individual Relay (UFR)Load of feeder at 0200 Hrs (in MW)
Load of feeder at 0300 Hrs (in MW)
Whether feeder
tripped at 0301 hrs by UFR
Reason, if UFR did not
trip
FORMAT FOR SUPPLY UFR and df/dt tripping details for Inquiry Committee Report
Name of Utility: Himachal Pradesh State Electricity Board
Load of feeder at 2130 Hrs (in MW)
Whether feeder
tripped at 2154 Hrs by UFR
Reason if UFR did not trip
Remarks (any other
information)
Sr. No.
Name of station with voltage level
where UFR installed
Name of individual feeder(s) with
voltage level on which UF relay
connected
![Page 289: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/289.jpg)
Make and Model of df/dt
Setting terms of frequency (Hz)
Time delay (ms), if any
Setting of Under voltage blocking (%) if any
Setting of Sampling cycles (nos)
Whether separate auxiliary supply or only PT supply
1 220kV Kunihar132kV Kunihar Barotiwala-I
50M/s.
EASUN49.9 0.1 PT 72 64 Yes
EntireFeeder tripped due to grid failure
58 55 Yes
EntireFeeder tripped due to grid failure
2 220/66kV Baddi 66kV Side 70M/s.
EASUN49.9 0.2 PT 18 8 No
EntireFeeder tripped due to grid failure
12 0 No
EntireFeeder tripped due to grid failure
3 132kV Giri132kV Giri Kala Amb
70M/s.
EASUN49.9 0.3 PT 65 71 No
EntireFeeder tripped due to grid failure
29 27 No
EntireFeeder tripped due to grid failure
Load of feeder at 0200 Hrs (in MW)
Load of feeder at 0300 Hrs (in MW)
Himachal Pradesh State Electricity Board
Sr. No.
Name of station with voltage level
where df/dt installed
Name of individual feeder(s) with
voltage level on which UF relay
connected
Planned load relief (MW)
Details of Individual Relay (df/dt)
Annexure -7/VI
Remarks (any other
information)
Whether feeder
tripped at 0301 hrs by df/dt
Reason, if df/dt did not
trip
Load of feeder at 2100 Hrs (in MW)
Load of feeder at 2130 Hrs (in MW)
Whether feeder
tripped at 2154 Hrs by df/dt
Reason if df/dt did not
trip
FORMAT FOR SUPPLY df/dt and df/dt tripping details for Inquiry Committee Report
Name of Utility:
![Page 290: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/290.jpg)
From
To
No.
BHAKRA BEAS MANAGEMENT BOARD (PW) SLDC Complex, Industrial Area-I, Chandigarh-160002
Ph: 0172-2652820 (Tele FAX)
Er. R. S. Lamba, Director/Power Regulation
The Member Secretary, Northern Regional Power Committee, 18-A, Shaheed Jeet Singh Marg, Katwaria Sarai, New Delhi-11 0016.
IPAlDPRlTech. Dated: 22.3.2010
Sub: Operation of UFRs and df/dt relays during the grid collapse on 2.1.2010.
Kindly refer to the discussions in the Crisis Management Group Meeting held on 4.1.2010 and subsequent discussion in the committee investigating on the subject cited grid collapse as well as discussion in the OCC meeting. The undersigned has been putting forward the point of view that the grid collapse was not caused by non-operation of UFRs & df/dt relays. The grid collapse was apparently due to inability of the collapsed region to adequately meet the shortfall of power import from other regions due to multiple trippings.
2. It is pertinent to mention here that the HDR reports generated in respect of BBMB system regarding morning & evening collapses make interesting observations. Whereas the morning collapse apparently occurred at 50.6 Hz, evening collapse occurred around 50.1 Hz to 50.3 Hz, as frequency data froze Simultaneously at that instant at various sub stations. Needless to say neither under frequency nor df/dt relays are supposed to provide any relief at this frequency.
3. Even going by the unlikely scenario that UFRs & df/dt relays might have operated; still they were unlikely to provide the compensation for shortfall in the power because; in the first instance it was a depleted system and many of the feeders on which the said relays were installed could have been under power cuts or were in tripped condition. Moreover, the relief could only be provided to the extent of loading at that time. Further, as per the literature of MIs ABB, the relays of which were initially installed by PowerGrid, the various features of relays restrict the operation of relays in extreme conditions. The notable feature of the relays are as under:-
i) The absolute value of rate of change of frequency must not exceed 70 Hz/sec. because the relay perceives such a situation as disturbance and delays tripping time by two cycles.
![Page 291: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/291.jpg)
2
ii) The minimum trip time of df/dt relays is 150 ms and UFRs is 100 ms.
iii) Undervoltage blocking is an inherent feature of UFRs and df/dt relays. The default setting of these relays is 60% the nominal voltage.
4. Going back to the observations on the HDR reports (Annexure I & II) it is seen that when the frequency was 50.6 Hz during morning collapse, the voltage at various sub stations had dipped to 28.8 kV (Ganguwal), 93.9 kV (Jamalpur), 3.4 kV (Bhakra Right Bank), 3 kV (MISS, Ganguwal), 11.9 kV (Kotla Power House) etc. Similarly, at the instant of evening collapse, the voltage at the frequency 50.1 Hz was 81.6 kV (Dehar), 30.6 kV (Jagadhari), etc. Keeping in view the feature of under voltage blocking provided in UFRs & df/dt relays, the same were not supposed to operate anyway regardless of the fact that they would have otherwise also not operated due to the prevailing frequency at that time. Furthermore, df/dt relays are not designed to operate dwring system collapse as is apparent from the literature of the relay. Keeping in view various factors explained, it is beyond doubt that the collapse could not have been averted due to operation of UFR & df/dt relays. This in no way implies that all UFR & df/dt relays installed by various constituents are not functioning. As a matter of fact these relays regularly operate in BBMB system, a fact that has been usually appreciated in the meetings of OCC.
5. It is felt that all references in the report whereby the collapse has been attributed to failure of defence mechanism need to be deleted unless it is fully evidenced and proved otherwise.
DAlAs above
(RS.lAMBA) Director/Power Regulation
![Page 292: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/292.jpg)
I,
B/SlJIJ K!: K'I
r-JASSORE
l' 18.:0 MI'I
.. 10. \l W".R
! 41, 7 MW 3[',1 WM
DASUYA
l' 63.4 MW +" 56.7 MYAR
l'
BUTARI
44.91.11'1 10.9 WAR
, l' +
0.0 MI'i 0.0 MVI>.R
BARNALA
F.~.D
t f:"4 MVI 11. 1 M1l~R
BEHP ',.":R.Il) (,'i"EP"'iJ E~~
t 145.5MW 42. l MV.~R
A""'NE~I,.It{£ - \ 2-nlJ ":lo. '0 J .2-010
t [I,~ MW 0,0 WAR
-+ -+
0.0 MI'I 1. 0 MYAR
3x50MYA
O~I, O:2-~'() 'r)"f"s
.. 10. ~ 1.11'1 ..,.. .?D.4: t.tVAA
70.4 M\'I
1..1. I.wAR i, 50.6 HZ
10.1 KV S 50.6 K!:
BHAKRA (R) 3.4 KV
('T'" r::=) S 49.8K!:
Q.O KV BHAKRA (L) S 50.6HZ
0.9 KV
! 58,:1 MW 31. 3 MVAR
PONG
JALANDHAR . 159.0MW .. 29.9 WAR
JAMALPUR
1:37.1 MI''' 41, 5 t.!"An
MAHILPU .
JAM=r-
~MI'I II .. 48. 7 WAR
DHANDARI
l' l'
205.1 "y S 48.0K!:
(1,0 1.11'1
0.0 MYAR
63.4 MW' 77.1 MVAR l'
iCl,7 MW !:.,j.,3 MVAR
. 75.:1 MW + 121.5 WAR
t
III +' 0.0 MI'i t t 4.7 WAR
15,1 MIN 1.0 WAR t 2.7 MW
0.6 M'/AR
85.9 MW 32.9 WAR
NFL RAY.KAR
M,LS.S, GANGUWAL
0.0 MI'i 0.1 WAR
" 90MVA- T2 ).. 0.0 M\'I
"t 0.5 WAR
3. I] KV s
t
MOHALl
·491.0MW + =,10. I] W."-R S ... :,4,';; MW
l' "'.3 MYAR
MW
SANGRUR ST ~J,OO.lMlN
l' ;;i.o, '3 WAR 179.1 K'{ 50.6 HZ
+- 12.0 M'/Ar.:
T KOTLA p, H. 86.5 MW
l' 6.4 M'fAR 11. 9 KY
S 50.6 HZ
HISSAR!.A. nNDALS1EEL
HISSAR
'" ..
DADRI
ii l' 0.0 1"- I),',)
-28.4 M\'i 0.0 MVAR
KHETRI (RSEB)
l' 141:', '"" l' 141. [, MYAR
• __ !!!III!!'II!!II!III!IIlIIlliiil!iifil\il: ,. 45.0 MVAR
MW MV.A.R
REIr'ARI
1"l'
PALWAL
ROPAR r 1 229.8 KV 50.9 HZ
58. 9 "~'1 5_7 WAR
500 MYA BAHADURGARH (pGz."'IL) HISSAR (PGC .... 0.0 MI'i ..
KV HZ
t- 0.0 M'/AR
BHIW ANI (HSEB)
~()
s1' 385.3MW II .,.. 0_0 'AI'J RH l' 164. 9 MVAR l' (I. [) MVAR
----~------------------~t~ITjrl-L.~---------------------~---
°c %
MW
MOHINDERGARH
210.7 KV BHIWANI 50.1 HZ
:382.7'w 50.6 ra:
10.3 1.11'1 II 1"-0.0 MVAR -+ lL 4 M\'I
:-:;: ,8 MVAR ["' l' 0.0 MW
t "". 1 MI'i _~1'~_~O:... O~~;W:':A::R:""'_ • ...,r-:-:;~~;;;~ +::: __ ,;;:.Il;:;''-..,;,?_M_V_AR ___ ""' I ';I'!~!:a:!!;r:!lii!(!;. 224.4 KV '-¥* 4"1. 8 WAR
BADSHAHPlJR PALLA
C' tAW ,,~. " Mw'
278.5 _
11.2.7 MVAR
-+ ..
[=--~
TIt I t..f',.'ttP. SAlvlAYAPUR If t t
I'! MIN·
n., MYAR l' l' tAVAP. 11 1'" tl Ml/AF:
![Page 293: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/293.jpg)
kt-/NC'f-LJR..E -II--")...~ ':::l 0'1\ J :l-O \0 2-\ ~S4~.2.' hY's
.... 26.7 MW -+ 36.7 MVAR
3x50MVA .... 114.1MW 't b.9 MilAR t 1.05.2MW
1).0 MVAR t 0.0 MW 0.0 MVAR
.... 99.3 MW .... 115.:1. WAR
2SOMVA
,j,. +-
0.(1 MW 0.0 MVAP.
74.:3 MW 9.4 MVAR
1""' r:F'~) S 49.8 HZ
0.0 1<.'1 BHAKRA (L) III .. 189.2. MW .. 46. t:: M'W
13. 6 MVA~
S 50.1HZ 65,5 KY
0" ~D~R·"""II""'I~"""I"'''''''''''''~~~I~'~''~'~~IIIIII''.11 •• Jl.~!!:I:~'~!~~!~I~!!~'~~""~~~I~'_~I' --~~~I~~-.~~~ 'II"",
II .... 106.3MW I """ 52..1 MW
S 50.0 HZ 225.41<.'1
.,.. 10Q,.2.MYAR .. l' 27.7 t.IIIAR .. 12..1 M'/AR
oIW o1YAR
t
"". "".
0.0 MW 0.0 MVAR
69. U MW 35.2 MYAR
(--v)
ROPAR
NFL RAKKAR
M,I.S,S, GANGUWAL 2B.61<.'1
MW 0.1 WAR
GANGUW AL P,H,
1'"
l' ·B.1 MW'
l' 4.8 MV."R
KOTLA p, H 52..9 MW 8,7 MVAR
I'OMVA-T2
+ 0.0 MW ,. 0.5 MVAP.
121. 4ICV S 50.3 HZ
.1 HZ
,. ,. MOHALl
50.0 HZ
18.5 MW' 58.3 MVAR
GOBI
500MVA .... 97.4MW
BAHADURGJ..RH (pGC'IL) HISSAR (pGC"IL) ",',- ~~""""".....,"-, , ~- .~ - »~,< ".~,-'-,""","
+- 201. >I WAR
VAM (HSEB) r:-(,-)
1 I I RH. 't ::,0 U t,.fW
1" 19. 4 M'/AR
11",~1 MW .", 20. ~WAR
219.21<.'1 BHIWANI 50.1 HZ
.. 6Z. MW +- 46.9 MW
'" 5c.. M'/"-R l' 0.0 MVAR
402. 1 ICV 50.1 HZ
1(','
HZ
1-
--------"'---------..-------
.LLA
It 1" 1.4". ,1 MW I 1'- 1 MVAR -.-....-.--~"--,~
218.0 ICV t
215.6 K'.' 50.1 HZ
0.0 MI." 0.0 ...... AR
0.0 MW
55.S WAR
ICV HZ
1-'t
1" 181. 1 M~f l' 105. \) M'/AA
237,:' MW'
237,3 WAR
+
Y KANGO
25.5 MW 43.3 MVAR
.. 46.2 MW 't 16.8 MVAR
CHANDIGARH
...,. 2.8 t.m 't 0.0 WAR .. 71. 0 MW
't 45,1 t.IIIAP.
r--... GARH ( "~I
.. 48.0 MW
.. 26.1 WAR
JAGADHRI 0.0 MW'
-+ 0.0 M'/AR
O.OKII KURUKSHErRA S 49.5 HZ
S l'
-t' 10.9 WI 31.9 M'/AA
0.0 MW'
12.3 M'/AR
(,~)
t
181.11<.'1 S 50.1 HZ
64.5 MW' 0.0 MVAR
ICV HZ l'.!.I..LJ.--II
" _ PAN I PAT THERMAL
NARELA 216.7 KV ~0.1 HZ
.... t,5, 'I M'W
DHULKOTE'r' l' ~,4, 6 MW 2::'::'.4 KV "". 20. 8 ~WAR
~~A
+ 373.7M1."1 -+ !l9.6 MVAR
or PANIPAT
Tl'AP °c RH
"'-u ',--..-{- «
+ 352.7t.m ... 38.6 MVAR
~~A
+ 99.1) MW l' 39.1 ...... AR
l' 8, "I M ..... " DELHI 174. 5 IC'I
S 50.1 HZ
0.0 MW'
ICV HZ
DADRI·j (N'IK')
![Page 294: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/294.jpg)
(Annexure- 7/VIII) Sub : Analysis of Grid Disturbance on 2nd January, 2010 by BBMB. This is with reference to the e-mail from NRPC vide which draft
final report regarding the grid disturbance has been forwarded. In this regard,
the following are the general observations of undersigned on the draft report :-
1) As per the draft report, during the disturbance at 21:54 hours, the
import into the region of collapse comprising Punjab, Haryana,
HP J&K was 3468 MW. At that point of time, the total load in the
effected sub system was about 9000 MW. The load relief through
under frequency & df/dt relays can at the best be estimated as
15% of the total load at any given time. It is important that
estimation in percentage is made because that takes care of
actual loading at that particular instant, shut downs, power-cuts
as well as trippings. Estimation of load relief on the basis of data
provided for maximum load by constituents is unrealistic.
Therefore, the total load relief in ideal conditions through under
frequency operation & df/dt operation might have been of the
order of 1300-1400 MW (keeping in view the sub-system load of
9000 MW at the time of collapse). Here, it is important to
remember that most of the under frequency & df/dt relays which
were earlier installed in Phase-I by PowerGrid operate during
both conditions i.e. during under frequency conditions as well as
during df/dt conditions meaning thereby that they are installed on
same feeders and therefore load relief more than 15% is unlikely.
It is relevant to mention here that as intimated by various utilities,
the following load relief was obtained during the collapse at 21:54
Hours :-
a. Punjab = 448 MW b. Haryana = 094 MW c. Himachal Pradesh = 117 MW d. BBMB = 061 MW
TOTAL = 720 MW
![Page 295: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/295.jpg)
2
Although conditions were not ideal for providing desired load
relief, due to system collapse, still about 50% of anticipated load
relief was obtained. Even if the shortfall from ideal relief i.e.
1400-720 MW say 700 MW is subtracted from total import to
collapsed region, the system would not have survived with net
balance shortage of 2800 MW from the total requirement of
9000 MW. This is apart from the fact that it has not been
established whether all relays could have possibly operated.
2) During the meeting of Crisis Management Group on 4th January,
2010, it was stated by undersigned that BBMB under frequency
and df/dt relays regularly operate and the non-operation of the
relays (which were supposed to) is an indicator that there were
technical reasons (like characteristics of relays, voltage collapse
etc.) for non-operation of the relays during specific conditions of
grid collapse. During OCC meetings, BBMB has demonstrated
the load relief through SCADA as obtained from the transformers
which is mapped. The BBMB’s data for past months/years is
available with NRPC. To an extent BBMB’s data is sacrosanct.
As a latest example, 22 incidents of RLSE operation & 2 incidents
of df/dt relays took place in BBMB system on 23rd April, 2010. As
discussed by undersigned with Er.J.S.Batra, SE/Protection of
HVPNL, relays which regularly operate in HVPN system also did
not operate during systems collapse; similar to BBMB system.
3) The tabular data of Ropar Thermal Plant has been given as
evidence for rate of change of frequency of the order of
1.8 Hz/sec. during system collapse. It is felt that during system
collapse, some intermittent island was created with Ropar
Thermal Plant and the frequency at Buses of Power houses is
likely to be that of the island (including generator) rather than the
system frequency of the grid as a whole. This view point is
supported by fact that during the last meeting when the data of
Unit-7 of Panipat Thermal Plant was matched with that of Ropar
Thermal Plant, the same did not tally. The frequency shown in
![Page 296: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/296.jpg)
3
the Panipat differed totally from the frequency shown for Ropar
data. Therefore, there is no credence to the data of RTP which
has been given as the basis of rate of fall and therefore reference
of rate of fall as 1.8 Hz/Sec. and various conclusions extended
therefrom in the report need to be deleted.
4) During the course of meetings; BBMB, NTPC, HVPN and to an
extent HPSEB have expressed that the grid collapse cannot be
related to non-operation of under frequency & df/dt relays
whereas NRLDC has expressed opposite view point which is in
line with their independent report submitted to Central Electricity
Regulatory Commission. Others have not expressed any view.
The views of members can be incorporated in report (including
ones in this mail) in a balanced way. However, as it has not been
established during the detailed deliberations of committee
members that inadequate operation of under frequency & df/dt
relays could have been the cause of collapse of the system;
attributing this factor as one of the three major causes of evening
collapse needs to be deleted wherever occurring in report (e.g. as
stated under clause 6.4). Chapter-7 needs to be modified
accordingly.
5) The analysis has been further done after last meeting. It is seen
that the frequency was very comfortable at 21:54:000 hours by
when quite a few trippings had already taken place. The ultimate
collapse occurred due to tripping of 400kV Abdullapur-Bawana-I
and 400kV Dadri-Malerkotla almost instantaneously (Abdullabpur-
Bawana-I at 21:54:00:649 at Dadri-Malerkotla at 21:54:00:765
which together might be carrying load of order of 1200-1500 MW
due to non-availability of parallel circuits. Thus, the collapse was
instantaneous due to outage of these two circuits (before which
the system was synchronized at comfortable frequency). The
period of collapse as made out in chapter-7 as 6-7 seconds is
incorrect, as the system was synchronized till the last line tripped;
the outage of which disturbed load-generation balance in the time
![Page 297: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/297.jpg)
4
period lesser than operating time of under frequency & df/dt
relays as two circuits carrying huge import tripped
instantaneously. Even as per SOE, they tripped at a gap of 116
ms, which may be due to difference in operation time of
respective CMRs.
6) Highlighting the importance of defence mechanism shall always
be appreciated but it is very difficult to study the impact of
defence mechanism during grid collapse. The extent to which the
relays are efficient and provide load relief needs to be monitored
and studied during normal period and remedial action taken
rather than arriving at conclusion based on operation of relays
during extreme conditions of grid collapse as the same has not
been established and perhaps cannot be established.
7) The detailed comments of Er.P.P.Francis of NTPC in the last
meeting need to be incorporated. The nutshell of his
comments was, “that during separation, it is unlikely that an
island formed due to tripping of lines in cascading will be
survived by operation of under frequency & df/dt relays”.
8) Correction :
What had been stated by BBMB in the meetings as well as
incorporated in the data supplied to NRPC, the reason for
non-operation of under frequency & df/dt relays in BBMB system
has been indicated as “possibly due to inherent feature of relays
during extreme conditions”. Therefore, the remarks against
Sr.No. 7.3.2.2 may be read as under :-
“BBMB has stated that wherever relays have not operated, it may be due to inherent features of relays during extreme conditions.”
(Er RS Lamba)
Director (PR,BBMB)
-o-O-o-
![Page 298: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/298.jpg)
ANNEX-8/I The broad restoration sequence after the incident at 0301
Time (hh:mm) Restored Element/Section/System
03:05:51 220 kV Bahadugarh-Nunamajra I
03:11 220 kV Samaypur-Charkhi Dadri
03:24 220 kV Hisar-Jind-II
03:21:39 220 kV Sangrur-Hisar 2
03:27:34 220 kV Sangrur-Jamalpur 2
03:28:39 220 kV Hisar-Bhiwani 2
03:32:00 220 kV Narwana-Hisar
03:35 220 kV Hisar-Fatehabad
03:39:57 220 kv Jamalpur-Bhakra 1
However system tripped. The same restoration of
extending power from Sangrur to Jamalpur to Bhakra
was done at 0404, 0429, 0509 and 0608 hrs also but
system tripped.
03:53:24 400/220 kV ICT at Bhiwani
04:58 Unit # 3 at NJHEP black started
05:07 Unit # 3 at Chamera 1 black started
05:10 400 kV NJ HEP-Abdullapur 2 charged abd supply
extended to Haryana system and Railways by charging
the ICT at Abdullapur. Subsequently start up supply to
Yamunanagar extended.
05:17 400 kV Chamera I – Jallandhar 2 charged and Supply
extended to Punjab system by charging ICT at
Jallandhar
05:20:33 220 kV Kartarpur-Kotlajanga restored
05:42 Unit # 3 at Salal HEP black started
05:47 400 kV Abdullapur-Bawana 2 restored by synchronizing
at Bawana system. This synchronized Jhakri sub-system
with the rest of the grid.
06:04 220 kV Salal-Jammu 1charged
06:07 400 kV NJ HEP-Nalagarh 2 normalised
06:09 400/220 kV ICT at Nalagarh normalized and supply
extended to Chandigarh
06:12:21 220 kV Sangrur-Barnala restored
06:16:32 220 kV Barnala-Lehra Mohabbat restored and startup
![Page 299: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/299.jpg)
Time (hh:mm) Restored Element/Section/System
supply to Lehra Mohabbat extended. Subsequently start
up supply to Bhatinda was also extended.
06:17 400 kV Nalagarh-Patiala restored.
06:22 400/220 kV ICTs at Patiala normalized and supply
extended to Punjab system.
06:37 400 kV Ludhiana-Malerkotla restored
06:40 Chamera I island collapsed
06:59 HP system normalized with supply form Uttrakhand
system and supply extended upto Bairasiul.
07:04 400 kV Patiala-Malerkotla normalized.
07:12:41 400 kV Bhiwani-Dehar normalized.
07:13 400 kV Nalagarh-Kaithal restored
07:22:55 132 kV Kotla-Ganguwal normalized and subsequently
supply extended to Ropar on 132 kV Kotla-Ropar
feeder.
07:22:55 400/220 kV ICT at Dehar normalized.
07:34:04 220 kV Ablowal-Govindgarh normalized.
07:35 Supply extended to RSD on 220 kV Jessore-RSD
07:39 400 kV Ludhiana-Jallandhar normalized.
07:40 Unit # 1 at Uri started in islanded mode to supply power
to valley area.
07:52 132 kV Kotla-Ropar 1 normalised and startup supply to
Ropar.
08:00 400/220 kV Jallandhar ICTs normalized and supply
extended to Punjab system for normalization.
08:21 400 kV Abdullapur-Bawana 1 normalized.
08:22 220 kV Jallandhar-Hamirpur 2 normalised and HP
system connected.
08:36 220 kV Jallandhar-Dasua 1 normalised.
08:45 220 kV Jallandhar-Dasua 2 normalised.
08:39 Salal island collapsed and again started at 0845 hrs.
08:41 220 kV Dehar-Ganguwal 1 normalised. This completed
connecting the Bhakra system.
08:52 400 kV Chamera1 –Chamera2 normalised and unit at
Chamera 2 taken in service to control voltages.
09:05 400 kV Chamera2 –Kishenpur normalized.
09:15 400 kV Amritsar-Jallandhar normaliised.
![Page 300: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/300.jpg)
Time (hh:mm) Restored Element/Section/System
09:22:34 220 kV Hisar-Khetri normalized.
09:37:38 220 kV Jagadari-Kurukshetra normalized.
09:39 400 kV Jallandhar-Moga 1 normalised.
09:42:25 220 kV Jallandhar-Pong normalized.
09:46:55 220 kV Ganguwal-Mohali normalized.
09:55 Supply extended to Salal on 220 kV Kishenpur-Salal 1
for normalization of Salal HEP.
09:59:40 220 kV Panipat-Kurukshetra normalized.
10:09:15 220 kV Dehar-Kangoo normalized.
10:09:15 400 kV Dehar-Panipat normalized.
10:31 400 kV Moga-Jallandhar 2 normalised.
10:32 220 kV Kishenpur-Sarna section normalized.
10:57 400 kV Moga-Kishenpur 1 normalised.
11:30 400 kV Wagoora-Kishenpur 1 normalised.
12:51 400 kV Wagoora-Uri 2 normalised.
12:56 Uri unit #2 synchronised with the grid.
![Page 301: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/301.jpg)
Ph. : 26967840, 26967842, 26967990, 26868681 Fax : 26865206
e-mail : [email protected] Website : www.nrpc.gov.in
भारत सरकार उ र क्षते्रीय िवद्युत सिमित
18-ए, शहीद जीत िसहं मागर्, कटवािरया सराय नई िद ली - 110016
Government of India Northern Regional Power Committee
18-A, Shaheed Jeet Singh Marg, Katwaria Sarai, New Delhi-110016 Fax Message
No. NRPC/SE(O)/insulator/2009-10 Date: 21-12-2009 To CMD, POWERGRID, Gurgaon, CMD, DTL, New Delhi Fax No 011 23234640 CED, North Central Railway, Allahabad, 0532-2223211, 2230204 Director (Electrical), Railway Board, New Delhi, 011- 23387045, MD, HVPNL, Panchkula Fax No 0172-2560640 CMD, RRPVNL, Jaipur Fax No 0141- 2740168 MD, UPPTCL, Lucknow Fax No 0522- 2287880/ED UPPTCL, Lucknow Chairman, BBMB, Chandigarh, Fax No 0172- 2549186, 2652820 Chief Engineer (SO&C), PSEB, Ablowal, Patiala Executive Director & CEO, Powerlinks Transmission Limited, New Delhi, Fax-
011-66306377/66306375 GM (O&M), POWERGRID, NR-I/ NR-II, fax- GM (OS), NTPC, NCR, Noida; AGM (OS), NTPC NR, Lucknow,
Sub:- Minutes of the Special meeting held on 16-12-2009 to review the progress of replacement/cleaning of porcelain insulators in Northern Region. Sir, A meeting was held on 16-12-2009 with the constituents to review the progress of replacement of porcelain insulators b y poly mer/antifog insulators in hi gh pollution areas of Northern Region. Minutes of the meeting are available on website of NRPC (www.nrpc.gov.in).
Yours faithfully,
अशोक कुमार राजपूत (A K Rajput) SE (O)
Copy for information to:
SA to Chairperson, CEA, New Delhi SA to Member (GO&D), CEA, New Delhi Director (O&M), MoP, New Delhi General Manager, NRLDC, New Delhi
Chapter - 9 _ ANNEXE - 9/I (page 1 of 18)
![Page 302: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/302.jpg)
Minutes of the special meeting taken by Member Secretary, NRPC on 16Th December, 2009 regarding replacement of porcelain insulators by polymer/antifog insulators of transmission lines List of participants is enclosed at Annexure-I. Member Secretary (MS), NRPC welcomed the participants in th e meeting to review the progress of replacement o f porcelain insulators by polym er/antifog insulators in the Northern Region. He st ated t hat Transmission Utilities must ensu re t he completion of replacement work of porcelain insulators by polymer/antifog insulators at a ll critical locations of transmiss ion li nes an d a lso the c leaning of p orcelain insulators of lin es. He mentioned that foggy weather can occur any time now. The field staff needs to be sensitized specifically in foggy weather during winter nights. After deliberations, a brief on the progress of various transmission utilities is given as under. POWERLINK h ad c ompleted t he work of repl acement of po rcelain insulators by polymer insulators on their lines. Sixty lines of POWERGRID were identified under phase-I, II and III for replacement of porc elain insulators o f tra nsmission lin es by polymer i nsulators. The wo rk for replacement of insulators has been completed on 24 lines. Whereas on 12 lines, the replacement work has been completed in the range of 50-90%. A rep resentative of POWERGRID stated that the replacement work on the balance 24 lines identified in phase-II and III would be taken up on gettin g the d elivery of polymer insulators. He informed th at th e replacement wo rk of porcelain i nsulators by polymer/antifog insulators at all critical locations of transmission lines had been completed. Representative of NRLDC informed that dur ing the winter peak season shutdown of lines may not be possible. Representative of POWERGRID NR- I stated that in respect of HVDC Rihand-Dadri line all the critical locations have been covered by them. 3 9 lines were planned by them for cleaning of porcelain insulators out of which 32 have been completed. The remaining 7 li nes would be com pleted by 28-12-2009. Cleaning o f p orcelain insulators by use of helicopters in Kanpur, Mainpuri and Allahabad areas is expected to commence in the last week of December, 2009. Representative of POWERGRID NR -II sta ted t hat the work of re placement of porcelain insulators by polymer insulators identified under phase-I on all the 12 lines had been completed. Under phase-II, 13 lines have been identified for replacement of in sulators th e wor k o f cl eaning of in sulators has been co mpleted on 7 of the se lines. Chapter - 9 _ ANNEXE - 9/I
Chapter - 9 _ ANNEXE - 9/I (page 2 of 18)
![Page 303: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/303.jpg)
Representative of DTL stated that they had received 500 polymer insulator strings on loan basis from POWERGRID and 240 strings had been replaced by them on 400 kV Bamnauli-Ballabgarh line. Representative o f Ha ryana stated that out of their 25 no s 22 0 kV lines th ey ha d replaced the porcelain insulators by antifog insulators on 7 lines. Representative of BBMB coul d n ot attend th e meeting. However, base d o n the information submitted BBMB has completed replacement of p orcelain insulators by antifog insulators on 7 nos 220 kV lines out of 21 identified lines. BBMB had informed that as regard to polymer insulators on 12 nos 220 kV lines, the price bid for procurement of i nsulators has been opened and delivery of material is expected in April 2010. Replacement work would be completed by June 2010. Regarding replacement o f po rcelain in sulators by polymer in sulators on 40 0 kV Dehar-Panipat and Dehar-Bhiwani lines BBMB i nformed t hat t he m atter r egarding obtaining s tatutory cl earance with gre ater length of p olymer insulator stri ng was referred to CEA, CPRI and POWERGRID. CEA ha s opined that the matter may be taken u p with the manufacturers for gett ing ins ulator strings o f required smaller length. Representative of UPPTCL could not attend the meeting. Based on the information submitted, the p ercentage c ompletion of the l ines pl anned for re placement of porcelain insulators by polymer insulators is 19 %. Representative of RVPNL stated that on 220 kV Badarpur-Alwar line, the percentage of completion of insulator strings replacement is 45% and the balance work would be completed by 30th Dec, 2009. Representative of PSEB stated that out of 3888 discs of antifog insulators planned in their system they had replaced 2336 discs. MS NRPC requested all the concerned utilities to complete the replacement work of porcelain insulators by polymer/antifog insulators on all lines and carry out periodic cleaning of porcelain in sulators in p olluted a reas. He sugg ested th at the u tilities should strategically plan the shutdown requirement for replacement work of porcelain insulators by polymer/antifog i nsulators o n a ll lines an d fo r other construction activities so as to avail the shut down during lean period. Chapter - 9 _ ANNEXE - 9/I Chapter - 9 _ ANNEXE - 9/I
Chapter - 9 _ ANNEXE - 9/I (page 3 of 18)
![Page 304: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/304.jpg)
He also requ ested the utilities to regularly submit the progress to NRPC secretariat on every Friday as per the Performa available at NRPC website The s ummary of status o f re placement of porcelain i nsulators by polym er/antifog insulators of transmission lines by the constituent States and POWERGRID is g iven at Annexure-II. Line wise status in respect of the constituents is at Annexure-III. Meeting ended with thanks to the chair.
Chapter - 9 _ ANNEXE - 9/I (page 4 of 18)
![Page 305: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/305.jpg)
Annexure-I
List of Participants for Special Meeting on Replacement of Porcelain Insulators by Ploymer/Antifog Insulators 10-11-2009: In Chair Sh A.K. AGGARWAL, MS, NRPC
Name (S/Sh) Designation Contract No. NRPC A.K. Aggarwal MS 26868681 A.K. Rajput SE 26868681 Vikram Singh EE 26868681
NRLDC V K Agrawal GM D.K. Jain DGM 9910344127 Rajiv Porwal Chief Manager 999903932
PGCIL Mithilesh Kumar DGM 9873637111 R K Singh Ch. Mgr, CPCC 9873918545 S Rasool Ch. Mgr, NR-I 9873549223 Ranjan Bhola Manager(OS), NR-II 9419173968
RVPNL M L Hissaria Ex Er 9414061036
HVPNL Sanjay Arora Power Controller 935273746
PSEB Rajbir Singh Sr Ex Er 9646118223 DTL B C Mathur GM, SLDC 011-23366462
Chapter - 9 _ ANNEXE - 9/I (page 5 of 18)
![Page 306: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/306.jpg)
Annexure-II
Status of Replacement of Porcelain Insulators with Polymer/Antifog Insulators (As reported by constituents)
Name of the constituent
Voltage level Lines where insulators to be replaced Type of insulator (polymer/antifog)
Remarks
Total Insulator Strings (Nos)
Insulator Strings replaced (Nos)
Scheduled completion date for replacement of balance insulators $
DTL 400kV 2595 240 NA Polymer Procurement for 400 kV in process through PGCIL, ordered in 04/09. Delivery of material is awaited. 500 insulators strings taken on loan from POWERGRID and 240 insulators strings have been replaced.
220kV 8231 nil NA Antifog Taking action for procurement of Antifog insulators
HVPNL 220kV 11834 4453 March/April 2010. Antifog Work on seven lines completed. Balance 11 would be completed by March/April, 2010.
UPPTCL 400kV 546 116 NA Polymer 1027 insulator strings replaced,
220kV 2241 911 NA Polymer
PGCIL NR-I 400kV 28850
23988 1 2/09 Polymer
220kV 831 - 12/09 Polymer Would be completed by Dec, 09 HVDC
Rihand-Dadri 4608
1498
_ Polymer Insulators not available. Would be completed in 3rd phase, i.e. in Feb, 2010.
HV DC Balia-Bhiwadi
2080 0 -
Polymer HVDC Balia-Bhiwadi line would be provided with polymer insulators. Pole-I expected in May, 2010. Replacement work shall be taken up in third pahse commencing from Feb, 2010.
PGCIL NR-II 400kV 19620 7132 - Polymer Procurement order for insulator strings required for phase-II (12,615 No.) and phase-III (10,000 No.) had been placed. Delivery of material expected in Dec/Jan’2010. 400 kV Moga-Bhiwadi line (expected in Dec 2009) would also be provided with polymer insulators.
220kV 3 80 380 Completed Polymer
BBMB 400kV 2016 June, 2010 Polymer Regarding replacement of porcelain insulators by polymer insulators on 400 kV Dehar-Panipat
Chapter - 9 _ ANNEXE - 9/I (page 6 of 18)
![Page 307: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/307.jpg)
and Dehar-Bhiwani lines BBMB informed that the matter regarding obtaining statutory clearance with greater length of polymer insulator string was referred to CEA, CPRI and POWERGRID. CEA has opined that the matter may be taken up with the manufacturers for getting insulator strings of required smaller length.
220kV 3599 06/10 Polymer Delivery of insulators expected in April, 2010.
400kV 264 264 Completed Antifog
220kV 3392 2481 12/09 Antifog Completion by Dec, 2009
POWERLINKS 400kV 1956 1956 04/09 Polymer Work Completed PSEB 220 & 132 kV 3888 discs 2336 discs Dec 09 Antifog 2336 discs replaced so far RVPNL 220 kV 390 174 Dec 09 polymer Out of 390 strings of polymer insulators required
174 strings had been completed. Balance completion expected by 1st Dec, 2009.
Note: $ The original schedule was 31-03-2009 as per decision of 10th NRPC meeting held on 30-09-2008.
SECTION - 2 _ ANNEXE - 2/I (page 7 of 18)
![Page 308: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/308.jpg)
POWERGRID (Polymer Insulators) As on 14-12-2009
S.No. Name of the Line % of total length of line planned for polymer Insulators
No. of locations on which insulators were to be replaced
No. of Insulator strings Required to be Replaced
No. of locations on which insulators replaced
No. of Insulator strings Replaced
Percentage of completion (on insulator strings)
Phase-IDate of start Date of
Completion1 400 KV Dadri Mandola-I 100 124 1338 124 1338 100
2 400 KV Dadri Mandola-II 100 124 1338 124 1338 1003 400 kV DADRI-Maharanibagh 100 68 730 68 730 1004 400 kV Maharanibagh-Ballabhgarh 100 89 1122 89 1122 1005 400 kV Dadri-G'NOIDA 100 37 429 37 429 1006 400 kV G'NOIDA-Ballabhgarh 100 108 1270 108 1270 100
7 400 KV Meerut-Mandola-I 100 166 1284 166 1284 100
8 400 KV Meerut-Mandola-II 100 166 1284 166 1284 100
9 400 KV Dadri-Panipat-I 100 301 1515 301 1515 100
10 400 KV Dadri-Panipat-II 100 328 1731 328 1731 10011 400 KV Dadri-M'Kotla (NRI) 100 282 1374 282 1374 10012 400 KV Dadri-M'Kotla (NRII) 716 716 100
13 400 KV Mainpuri-Ballabgarh-I 60 354 1377 283 1146 83 Feb, 2010 Feb, 2010
14 400 KV Mainpuri-Ballabgarh-II 60 354 1473 265 1187 81 Feb, 2010 Feb, 201015 400 KV Kanpur-Ballabgarh 60 579 2259 260 1155 51 Feb, 2010 Feb, 2010
16 400 KV Hissar-Bhiwadi (NRI) 60 293 2418 293 1842 7617 400 kV Bhiwadi-Bassi (NRI) 353 1374 205 678 49 Feb, 2010 Feb, 201018 500 KV HVDC Rh-Dadri P-I 44 885 2304 569 1518 6619 500 KV HVDC Rh-Dadri P-II 44 885 2304 589 1592 6920 400 KV Hisar- Bawana 1295 1295 10021 400 KV Bahadurgarh- Bhiwani line 839 839 10022 400 KV Hisar- Bhiwani Line 387 387 10023 400 KV Abdullapur- Bawana-I 636 636 10024 400 KV Abdullapur- Bawana-II 635 635 10025 400 kV Moga-Fatehabad 615 615 10026 400 kV Moga-Hisar 655 655 10027 220 kV Hisar-Hisar Link line -I 193 193 10028 220 kV Hisar-Hisar Link line -II 187 187 10029 400 kV Bawana-Bahadurgarh 500 500 100
33582 29191 87
Status of Replacement of Porcelain Insulators with Polymer/Antifog Insulators in Northern Region
Schedule for replacement of balance
insulators not available shall be taken up in 3rd phase
Progress of work
Chapter - 9 _ ANNEXE - 9/I (page 8 of 18)
![Page 309: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/309.jpg)
S.No. Name of the Line % of total length of line planned for polymer Insulators
No. of locations on which insulators were to be replaced
No. of Insulator strings Required to be Replaced
No. of locations on which insulators replaced
No. of Insulator strings Replaced
Percentage of completion (on insulator strings)
Phase-IIDate of start Date of
Completion
1 400 KV Dadri-Muradnagar 100 90 540 54 318 59 Feb, 2010 Feb, 20102 400 KV Moradabad- Muradnagar 60 201 798 174 717 90 Feb, 2010 Feb, 2010
3 400 KV Meerut-Muzaffarnagar 100 106 534 0 0 0 Jan, 2010 Jan, 2010
4 400 KV Agra-Ballabgarh 60 272 1304 219 1092 84 Feb, 2010 Feb, 2010
5 400 KV Ballabgarh-Bhiwadi 100 132 508 132 508 100
6400 KV Bhiwadi-Bassi-II (LILO of Old Bassi-Hissar) 60 35 240 35 240 100
7 220 KV FGPP-Palla-I&II 100 64 480 0 0 0 Dec, 2009 Dec, 2009
8 220 KV FGPP-Samaypur-I&II 100 54 351 0 0 0 Dec, 2009 Dec, 20099 400 kV Moga-Hisar 761 0 010 400 kV Moga-Fatehabad 528 0 011 400 KV Abdullapur- Bawana-I 202 0 012 400 KV Abdullapur- Bawana-II 202 0 013 400 KV Nathpa Jhakri- Abdullapur-I 346 0 014 400 KV Nathpa Jhakri- Abdullapur-II 347 0 015 400 KV Dadri-M'Kotla (NRII) 264 0 016 400 kV Hisar-Patiala 650 13 217 400 kV Hisar-Kaithal 480 13 318 400 kV Kaithal-Nalagarh 880 0 019 400 kV Nalagarh-Patiala 460 0 020 400 KV Jallandhar-Ludhiana 436 0 0
21 400 KV Ludhiana-Malerkotla 220 0 0
10531 2901 28
Schedule for replacement of balance
Chapter - 9 _ ANNEXE - 9/I (page 9 of 18)
![Page 310: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/310.jpg)
S.No. Name of the Line % of total length of line planned for polymer Insulators
No. of locations on which insulators were to be replaced
No. of Insulator strings Required to be Replaced
No. of locations on which insulators replaced
No. of Insulator strings Replaced
Percentage of completion (on insulator strings)
Phase-IIIDate of start Date of
Completion
1 400 KV Agra-Bhiwadi-I 100 198 702 0 0 0
2 400 KV Agra-Bhiwadi-II 100 205 786 0 0 0
3 LILO of 400 KV Bly-Mandola at Meerut 100 22 102 0 0 0
4 LILO of 400 KV Ballabgarh-Bhiwadi at G'Gaon 100 175 678 0 0 0
5 LILO of 400 KV Lko-Mbd at Bly. 100 22 84 0 0 0
6 400 KV Bly-Mbd 100 108 756 0 0 07 + 500 KV HVDC Ballia-Bhiwadi Pole-I 20 400 1040 0 0 0 Feb, 2010 Feb, 20108 + 500 KV HVDC Ballia-Bhiwadi Pole-II 20 400 1040 0 0 0 Feb, 2010 Feb, 20109 400 KV Moga - Bhiwadi-I 3369 0 010 400 KV Moga - Bhiwadi-II 3369 0 0
11926 0 0
Schedule for replacement of balance
Shall be taken up in Feb, 2010 after arrival of isulators in Mid January, 2010
Chapter - 9 _ ANNEXE - 9/I (page 10 of 18)
![Page 311: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/311.jpg)
DTL (Polymer/Antifog Insulators) As on 14-12-2009
S.No. Name of the Line % of total length of line planned for polymer Insulators
No. of locations on which insulators were to be replaced
No. of Insulator strings Required to be Replaced
No. of locations on which insulators replaced
No. of Insulator strings Replaced
Percentage of completion (on insulator strings)
400 kV Lines (Polymer) Date of start Date of Completion
1 Bamnauli-Ballabhgarh I&II 100 149 1214 16 234 192 Mandaula-Bawana 100 68 620 03 Bawana-Bamnauli 100 103 761 0
220 kV D/C lines(Antifog)1 Mandaula-Narela 73 561 02 Narela-Bawana 41 348 03 Bawana-Shalimarbagh 55 522 04 Shalimarbagh-Rohini 27 312 05 Bawana-Rohini 54 456 06 Bawana-Najafgarh 77 540 07 Bamnauli-Najafgarh 29 210 08 Bamnauli-Pappankalan-I 51 534 09 Bamnauli-Pappankalan-II 62 636 010 Bamnauli-Naraina 99 1098 011 Bamnauli-Mehrauli 52 462 012 Mehrauli-Vasant Kunj 37 471 013 Mandaula-SOW I&II 54 591 014 Mandaula-SOW III&IV 54 591 015 SOW-Kashmere Gate 24 389 016 Maharanibagh-Lodhi Road 30 486 017 BTPS-Okhla 36 516 018 Mandaula-Goplalpur 82 1038 019 BTPS-Mehrauli 68 951 020 IP Station-Patparganj 12 114 0
10826 234 2
Progress of workSchedule for replacement of
balance
Chapter - 9 _ ANNEXE - 9/I (page 11 of 18)
![Page 312: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/312.jpg)
HVPNL (Antifog Insulators) As on 14-12-2009
S.No. Name of the Line % of total length of line planned for polymer Insulators
No. of locations on which insulators were to be replaced
No. of Insulator strings Required to be Replaced
No. of locations on which insulators replaced
No. of Insulator strings Replaced
Percentage of completion (on insulator strings)
Date of start Date of Completion
1 220KV Sewah-PTPS Ckt-I 100 198 198 1002 220KV Sewah-PTPS Ckt-II 100 198 198 1003 220KV Sewah-PTPS Ckt-III 100 213 213 1004 220KV Sewah-PTPS Ckt-IV 100 213 213 1005 220KV PTPS -Sonepat Ckt-I 100 634 477 75 10.11.09 15.12.096 220KV PTPS -Sonepat Ckt-II 100 634 477 75 10.11.09 15.12.097 220KV Nuna-Majra-B/garh(400KV) Ckt-I 100 42 42 1008 220KV Nuna-Majra-B/garh(400KV) Ckt-II 100 42 42 1009 220KV Rohtak-B/garh Ckt-I 100 576 555 96 01.12.09 15.12.0910 220KV Rohtak-B/garh Ckt-II 100 576 555 96 01.12.09 15.12.0911 220KV Rohtak-PTPS Ckt-I 100 726 0 0 15.12.09 31.01.1012 220KV Rohtak-PTPS Ckt-II 100 726 0 0 15.12.09 31.01.1013 220KV Pali-Samaypur Ckt-I 100 342 48 14 10.12.09 31.01.1014 220KV Pali-Samaypur Ckt-II 100 342 51 15 10.12.09 31.01.1015 220KV Pali-Palla Ckt-I 100 414 39 9 16.12.09 30.12.0916 220KV Pali-Palla Ckt-II 100 414 30 7 16.12.09 30.12.0917 220KV Samaypur-Palwal Ckt-I 100 288 252 88 16.12.09 30.12.0918 220KV Samaypur-Palwal Ckt-II 100 288 156 54 16.12.09 30.12.0919 220KV Badshahpur-Rewari D/C line 100 1410 88 6 15.12.09 31.01.1020 220KV D/C Sec- 52-A-Pali line 100 690 0 0 20.12.09 31.01.1021 220KVBadshahpur-Samaypur D/C 100 642 0 0 18.12.09 31.01.1022 220KV Badshahpur-Pali D/C 100 726 0 0 01.02.2010 30.04.1023 220KV S/C Badshahpur--IMT Manesar 100 240 9 4 01.02.2010 10.02.1024 220KV D/C Daultabad-IMT Manesar 100 594 144 24 11.02.10 20.04.201025 220KV D/C Nuna-Majra-Daultabad 100 666 666 100
11834 4453 38
Progress of workSchedule for replacement of
balance
Chapter - 9 _ ANNEXE - 9/I (page 12 of 18)
![Page 313: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/313.jpg)
BBMB (Polymer Insulator) As on 14-12-2009
S.No. Name of the Line % of total length of line planned for polymer Insulators
No. of locations on which insulators were to be replaced
No. of Insulator strings Required to be Replaced
No. of locations on which insulators replaced
No. of Insulator strings Replaced
Percentage of completion (on insulator strings)
Date of start Date of Completion
1
400KV S/C Dehar-Panipat Line206 771
0
2
400KV S/C Dehar-Bhiwani Line331 1245
03 220KV Rohtak Road-Narela ckt-I 81 426 04 220KV Rohtak Road-Narela ckt-II 81 426 05 220KV Panipat-Narela ckt-I 73 263 06 220KV Panipat-Narela ckt-II 73 263 07 220KV Panipat-Narela ckt-III 81 273 08 220KV Ballabhgarh-BTPS-I 100 90 321 09 220KV Ballabhgarh-BTPS-II 100 90 321 010 220KV Samaypur-Ch. Dadri S/C 100 154 518 011 220KV Ballabhgarh-Ch. Dadri S/C 100 169 569 012 220KV Ballabhgarh-Samaypur-I 100 20 84 013 220KV Ballabhgarh-Samaypur-II 100 20 84 014 220KV Ballabhgarh-Samaypur-III 100 15 51 0
5615 0 0Note: The matter regarding obtaining statuary clearance with greater length of insulators in respect of 400KV
Polymer insulators was reffered to CEA, CPRI & POWERGRID to seek the expert opinion. CEA has opinioned that matter may be taken up with the manufactures for procuring insulators strings with smaller length. Design directorate of BBMB will take up the matter accordingly. Although they had taken up the matter with the manufactures earlier also but manufatures did not come forward for providing strings of lesser length.
Progress of workSchedule for replacement of
balance
Poly
mor
in
sula
tors
un
der
proc
urm
ent
with
Dire
ctor
P&
D (T
S)
BBM
B C
hand
igar
h.
Rep
lace
men
t w
ork
Price bid opened and delivery of material is expected in April-2010 and replacement will be completed by June-2010.
Chapter - 9 _ ANNEXE - 9/I (page 13 of 18)
![Page 314: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/314.jpg)
BBMB (Antifog Insulator) As on 14-12-2009
S.No. Name of the Line % of total length of line planned for polymer Insulators
No. of locations on which insulators were to be replaced
No. of Insulator strings Required to be Replaced
No. of locations on which insulators replaced
No. of Insulator strings Replaced
Percentage of completion (on insulator strings)
Date of start Date of Completion
1 220KV Dhulkot-Panipat ckt-I 29 117 29 117 100 .. …2 220KV Dhulkot-Panipat ckt-II 29 117 29 117 100 .. …3 220KV S/C Panipat-Ch. Dadri Line 21 81 21 81 100 .. ..4 220KV S/C Kurukshetra-Panipat Line 28 105 28 105 1005 220KV BUSES at 400KV S/S Panipat … 240 … 240 100 25.11.09 31.12.096 220KV Bhakra-Jamalpur ckt -I 13 32 204 29 174 85 16.12.09 17.12.097 220KV Bhakra-Jamalpur ckt - II 13 32 204 29 174 85 18.12.09 19.12.098 220KV Jamalpur-Jallandhar ckt-I 14 27 87 87 27 31 .. …9 220KV Jamalpur-Jallandhar ckt- II 14 27 87 87 27 31 .. ..10 220KV Pong-Jalandhar ckt- I 4 12 36 36 12 3311 220KV Pong-Jalandhar ckt- II 4 12 36 36 12 3312 220KV Jamalpur-Sangrur ckt- I 18 40 313 35 270 86 09.12.09 11.12.0913 220KV Jamalpur-Sangrur ckt- II 18 40 313 30 276 88 09.12.09 15.12.0914 220KV Hisar-Sangrur-I 100 62 186 44 132 7115 220KV Hisar-Sangrur-II 100 62 186 44 132 7116 220KV Bhiwani-Hisar-I 52 102 345 36 108 3117 220KV Bhiwani-Hisar-II 52 102 345 33 99 2918 220KV Bhiwani-Ch. Dadri-I 21 26 81 25 75 9319 220KV Bhiwani-Ch. Dadri-II 21 26 81 25 75 9320 220KV Bhiwani-Ch. Dadri-III 27 35 114 35 114 10021 220KV Bhiwani-Ch. Dadri-IV 27 35 114 35 114 100
3392 2481 73
15, 24 to 25 Dec 0907 & 08 Dec 0909 & 10 Dec 09
Progress of workSchedule for replacement of
balance
21 to 23 Dec 0916.& 28 to 30 Dec 0914, 19 & 26 Dec 09
Chapter - 9 _ ANNEXE - 9/I (page 14 of 18)
![Page 315: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/315.jpg)
UPPTCL (Polymer Insulators) As on 08-12-2009
S.No. Name of the Line % of total length of line planned for polymer Insulators
No. of locations on which insulators were to be replaced
No. of Insulator strings Required to be Replaced
No. of locations on which insulators replaced
No. of Insulator strings Replaced
Percentage of completion (on insulator strings)
Date of start Date of Completion
1
400 kV Muradnagar-Muzaffarnagar 105 12 36 34
2400 kV Muradnagar-Panki 441 NA 80 18
3220 kV Muradnagar-Shamli 345 78 234 68
4
220 kV Muradnagar-Khurja 210 31 102 49
5 220 kV Muradnagar-Sahibabad 210 31 102 496 220 kV Muradnagar-Interconnector I&II 24 7 24 100
7
220 kV Sahibabad-Muradnagar Ckt-II 600 37 215 36
8 220 kV Modipuram-Matore Ckt-I 33 11 33 1009 220 kV Modipuram-Matore Ckt-II 9 0
10
220 kV NAPP-Khurja 285 12 69 24
11 220 kV Muradnagar-Modipuram 135 012 220 kV Baraut-Muradnagar 013 220 kV Baraut-Shamli14 220 kV Shatabdinagar-Matore 015 220 kV Shatabdinagar-Modipuram16 220 kV Greater Noida-Noida Ckt-II 132 44 132 100
2787 1027
105
153
Expected to be completed on 15.11.2009
Shut down has been requested.
Area selected where brick kilns are there.
Started from 220 kV Muradnagar end due to vicinity of Gang Nahar.
To be completed by Nov, 09 end.
Total 69 Nos are to be replaced. Work in progress.
Schedule for replacement of balance
Progress of work
Chapter - 9 _ ANNEXE - 9/I (page 15 of 18)
![Page 316: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/316.jpg)
RVPNL (Polymer Insulators) As on 15-12-2009
S.No. Name of the Line % of total length of line planned for polymer Insulators
No. of locations on which insulators were to be replaced
No. of Insulator strings Required to be Replaced
No. of locations on which insulators replaced
No. of Insulator strings Replaced
Percentage of completion (on insulator strings)
Date of start Date of Completion
1 220 kV S/C Badarpur-Alwar 51 130 390 58 174 45 22.12.09 30.12.09
Progress of workSchedule for replacement of
balance
Chapter - 9 _ ANNEXE - 9/I (page 16 of 18)
![Page 317: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/317.jpg)
PSEB (Antifog Insulators) As on 15-12-2009
S.No. Name of the Line % of total length of line planned for polymer Insulators
No. of locations on which insulators were to be replaced
No. of Insulator strings Required to be Replaced
No. of locations on which insulators replaced
No. of Insulator strings Replaced
Percentage of completion (on insulator strings)
Date of start Date of Completion
1 P&M Circle Ludhiana220kV RTP-Gobindgarh-II 126220kV RTP-Gobindgarh-IV 126220kV RTP-Gobindgarh-I 84220kV RTP-Gobindgarh-II 84220kV Gobindgarh-I- Gobindgarh-II 126220kV Gobindgarh-I- Gobindgarh-II 126132kV Jamalpur-Ghulal ckt-I 157132kV Jamalpur-Ghulal ckt-II 135132kV Jamalpur-Phillaur 54132kV Jamalpur-Goraya 54Total 1072P&M Circle Jallandhar220 kV Dasuya-Jallandhar 42220 kV Dasuya-Jallandhar 45220 kV Dasuya-Jallandhar 42220 kV Dasuya-Jallandhar 42220 kV Dasuya-Jallandhar 42220 kV Jamsher-Sultanpur 24132kV Kapurthala-Khera Mandir 8Total 245P&M Circle Patiala220kV Ablowal-fagan Majra 100220kV Ablowal-fagan Majra 404Total 504P&M Circle Amritsar132kV Verka-Jandiala 48
Progress of workSchedule for replacement of
balance
2336 No. of discs replaced (i.e. 60%)
Chapter - 9 _ ANNEXE - 9/I (page 17 of 18)
![Page 318: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/318.jpg)
132 kV Jandiala-Tangra 48220kV C/Lines-Khassa-I 45132 kV Verka-Kathunangal-I 96132 kV Verka-Pakharpura-II 96Total 333P&M Circle Bathinda220kV Lehra-Bathinda 200220kV Lehra-Bathinda 200132kV Bathinda-Balluna 100132 kV Bathinda-Gidderbaha-Malaut 250132 kV Sadiq-Ferozepure 48132 kV Kotkarore-Ferozeshah 48132kV Ferozpur-Mana Singh Wala 18220 kV Botianwala-Ferozepur 168220 kV Moga-Ferozepur 168220kV Bathinda-Muktsar-I 126220kV Bathinda-Muktsar-I 126220kV Bathinda-Muktsar-II 126220kV Bathinda-Muktsar-II 126Total 1734G. Total 3888 (No
of discs)
Chapter - 9 _ ANNEXE - 9/I (page 18 of 18)
![Page 319: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/319.jpg)
,4'NN9{_Z/U t("1"**
Details of locations where insulators were planned to be cleaned using Helicopter
Under Kanpur jurisdiction.LOCATION NO
SL.No.
NAME OF LINE FROM ro No. OFTOWERS
1 500 kV HVDC Rihand-Dadri 1 103 1261 1592 400 kV S/C Allahabad-Kanpur 109€ G-1184 87a 400 kV S/C Allahabad-Kanpur-ll 1044 G-1128 85
4 400 kV S/C Singrauli-Kanpur 107e G-1158 81
5 400 kV S/C Kanpur-Agra G-001 9g 83'6 400 kV S/C Kanpur-Ballabgarh G-001 83 837 400 kV D/C Allahabad-Mainpuri 526 690 16rI 400 kV D/C Kanpur-Auraiva 122 G-211 9Cc 400 kV S/C Kanpur-Panki-l G-1 21-G 21
1C 400 kV S/C Kanpur-Panki-tt G-1 18 18
11 220 kV D/C Unchahar-Kanpur Ckt-l and ll 249 G-445 9712 220 kV D/C Unchahar-Kanpur Ckt-lll and lV 354 G-449 9613 220 kV D/C Kanpur-Panki-Mainpuri LtLO 1 G-48 4814 220 kV D/C Kanpur-Panki-Naubasta LILO G-01 78 7e
TOTAL 1191Under Mainpuri jurisdiction.
1 500 kV HVDV Rihand-Dadri 1483 1491 I1 569 1576 81700 1743 441777 1786 1C
1826 184C 1aTOTAT 86
Under Allahabad ju risdiction1
500 kV HVDV Rihand-Dadri, Pole-l & ll
425 452 31465 469 551€ 555 40o5J 660 28665 688 24
701 766 6e784 798 1E
833 841 I849 874 26
TOTAT 244
Note: Schedule is yet to be submitted by POWERGRIDChapter
_ Chapter 9- Annexure 9/II (page 1 of 1)
ANNt:-x ::-c:../11 ..1.
Details of locations where insulators were planned to be cleaned using Helicopter
Under Kanpur jurisdiction.
LOCATION NO SL. NAME OF LINE FROM TO No. OF No. TOWERS
1 500 kV HVDC Rihand-Dadri 1103 1261 159 2 400 kV SIC Allahabad-Kanpur 1098 G-1184 87 3 400 kV SIC Allahabad-Kanpur-II 1044 G-1128 85
4 400 kV SIC Singrauli-Kanpur 1078 G-1158 81
5 400 kV SIC Kanpur-Agra G-001 99 " 83
' 6 400 kV SIC Kanpur-Ballabgarh G-001 83 83
7 400 kV D/C Allahabad-Mainpuri 526 690 165
8 400 kV D/C Kanpur-Auraiya 122 G-211 90 9 400 kV SIC Kanpur-Panki-I G-1 21-G 21
10 400 kV SIC Kanpur-Panki-II G-1 18 18
11 220 kV D/C Unchahar-Kanpur Ckt-I and II 249 G-445 97
12 220 kV D/C Unchahar-Kanpur Ckt-III and IV 354 G-449 96
13 220 kV D/C Kanpur-Panki-Mainpuri LlLO 1 G-48 48
14 220 kV D/C Kanpur-Panki-Naubasta LlLO G-01 78 78
TOTAL 1191 Under Mainpuri jurisdiction.
1 500 kV HVDV Rihand-Dadri 1483 1491 9 1569 1576 8 1700 1743 44 1777 1786 10 1826 1840 15
TOTAL 86 Under Allahabad jurisdiction
1 425 452 31 465 469 5 516 555 40 633 660 28
500 kV HVDV Rihand-Dadri, Pole-I & II 665 688 24
701 766 66 784 798 15 833 841 9 849 874 26
TOTAL 244
Note: Schedule is yet to be submitted by POWERGRID
![Page 320: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/320.jpg)
NRLDC
Page 1 of 4
Annex-9/III
DETAILS OF SHUTDOWN AVAILED BY DIFFERENT CONSTITUENTS IN NORTHERN
REGION FOR INSURING THE RELIABILITY OF TRANSMISSION SYSTEM DURING WINTER
PERIOD (FROM 1st SEPTEMBER 2009 TO 31st DECEMBER 2009)
POWERGRID
NR-I SL.NO. NAME OF THE LINE AVAILED SHUTDOWN PURPOSE
1. HVDC Rihand-Dadri Pole-II 1-4th
Sept,7th
Sept, 2nd
Oct,20th
Nov,22,23,25,27,28,30th
Nov,1-4
Dec.
Porcelain insulators replaced
with polymer insulators
2. HVDC Rihand-Dadri Pole-I 2nd
Oct,8th
Nov,9th
Nov,10-18 Nov Porcelain insulators replaced
with polymer insulators
3. 400 kV Agra-Ballabhgarh 3-7th
Oct ,18th
Dec,19th
Dec,20th
Dec,22nd
Dec,23rd
Dec
Porcelain insulators replaced
with polymer insulators
4. 400 kV Ballabhgarh-Bhiwadi 11th
Sept, 3rd
Oct,30th
Oct Porcelain insulators replaced
with polymer insulators
5. 400 kV Ballabhgarh-Mainpuri-I 11th
-13th
Sept, 11-13th
Dec Porcelain insulators replaced
with polymer insulators
6. 400 kV Ballabhgarh-Mainpuri-II 14th
Sept,14th
Dec Porcelain insulators replaced
with polymer insulators
7. 400 kV Dadri-G’Noida 30-31th
Oct , 1st Oct,2
nd Oct Porcelain insulators replaced
with polymer insulators
8. 400 kV G’Noida-Ballabhgarh 1st Oct,11-15
th Oct,27-29 Oct,6
th Nov ,29
th
Nov
Porcelain insulators replaced
with polymer insulators
9. 400 kV Dadri-Maharanibagh 1-4 Nov ,29th
Nov Porcelain insulators replaced
with polymer insulators
10. 400 kV Ballabhgarh-
Maharanibagh
9-10th
Oct,16th
Oct,19th
Oct,5th
Nov 2,29th
Nov
Replacement of polymer
insulator
11. 400 KV Kanpur-Ballabhgarh 21-25st
Oct ,21st Dec Porcelain insulators replaced
with polymer insulators
12. 400 kV Bassi-Bhiwadi-I 7th
-9th
Sept, 7th
Dec,8th
Dec,9th
Dec,15th
Dec,16th
Dec
Porcelain insulators replaced
with polymer insulators
13 400 kV Meerut-Muzaffarnagar 17th
Nov,18th
Nov Pre-Winter Maintenance
14. 400 kV Dadri-Mandola-II 1st Oct Porcelain insulators replaced
with polymer insulators
15. 400 kV Dadri-Panipat-I 28th
Nov Porcelain insulators replaced
with polymer insulators
16 400 kV Meerut-Mandola-I 28th
Oct Porcelain insulators replaced
with polymer insulators
17 400 kV Dadri-Malerkotla 14th
Sep,23-31st Oct,1
-2Nov ,15
th Dec,17
th
Dec
Porcelain insulators replaced
with polymer insulators
18 400 kV Allahabad-Kanpur-I 7th
,8th
& 9th
Sept,8th
Dec,9th
Dec Pre-Winter Maintenance
19 400 kV Allahaad-Kanpur-II 11th
,12th
& 13th
Sept, 12th
Dec,13th
Dec Pre-Winter Maintenance
20 400 kV Singrauli-Kanpur 5th
Dec,29th
Dec Pre-Winter Maintenance
21 400 kV Auraiya-Agra-I 24th
Oct,4th
Nov,23rd
Nov Pre-Winter Maintenance
22 400 kV Auraiya-Agra-II 25th
Nov,26th
Nov Pre-Winter Maintenance
23 400 kV Agra-Bassi-I 22nd
Oct,23rd
Oct,12th
Nov AMP
24 400 kV Agra-Bassi-II 24th
Oct,13th
Nov Pre-Winter Maintenance
25 400 kV Agra-Bassi-III 20th
Nov,22nd
Dec Pre-Winter Maintenance
26 400 kV Bassi-Bhiwadi-II 11th
,12th
Sept Porcelain insulators replaced
with polymer insulators
27 400 kV Bassi-Heerapura-I 18th
Nov Pre-Winter Maintenance
28 400 kV Bassi-Heerapura-II 19th
Nov Pre-Winter Maintenance
29 400 kV Bareilly(PG)-Bareilly
(UP)-1
17th
Oct,19-24th
Oct,(,3,12,13,16,17-
Nov),10th
Dec
Pre-Winter Maintenance
30 400 kv Singrauli-Vindhyachal-II 23rd
Nov AMP
31 400 kv Singrauli-Vindhyachal-I 16th
Nov AMP
32 Vindhyachal HVDC Block-I 24th
to 28th
Nov AMP Chapter Chapter 9- Annexure
Annexure - 9/III (page 1 of 4)
![Page 321: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/321.jpg)
NRLDC
Page 2 of 4
Annex-9/III
33 Vindhyachal HVDC Block-II 18th
to 22nd
Nov AMP
34 400 kVAgra-Bhiwadi 1st Sept,1
st Dec Pre-Winter Maintenance
35 400 kVHissar-Bhiwadi 1st to 9
th Sept Porcelain insulators replaced
with polymer insulators
36 400kv Bassi-Bhiwadi-II 21st Nov,11
th & 12
th Dec Porcelain insulators replaced
with polymer insulators
37 400 kv Singrauli-Allahabad-I 7th
,8th
& 9th
Sept, 7th
,8th
,9th
Dec Porcelain insulators replaced
with polymer insulators
38 400 kv Singrauli-Allahabad-II 12,13 & 14th
Sept, 19th
Nov,7th
–9th
Dec Porcelain insulators replaced
with polymer insulators
39 400 kV Mainpuri-Ballabhgarh 15th
Dec ,16th
Dec Porcelain insulators replaced
with polymer insulators
NR-II SL
NO.
NAME OF THE LINE TIME / DATE OF SHUTDOWN PURPOSE
1. 400 kV Abdullapur-Bawana-I 1st Sept, 8
th ,10
th ,12
th ,14
th ,16
th ,18
th
,20th
,22nd
,25th ,27
th 29
th Nov,& 1
st
Dec
Porcelain insulators replaced
with polymer insulators
2 400 kV Fatehabad-Moga 5th
Nov,24th
Nov Porcelain insulators replaced
with polymer insulators
3.. 400 kV Hissar-Bawana 13th
oct,3rd
Nov Porcelain insulators replaced
with polymer insulators
4. 400 kV Hissar-Bhiwani 27th
Nov Porcelain insulators replaced
with polymer insulators
5 400 kV Hissar-Fatehabad 4th
,7th
,22nd
,23rd
Nov Porcelain insulators replaced
with polymer insulators
6 400 kV Hissar-Kaithal 3rd
,4th
and 5th
Sept, 4th
Dec Porcelain insulators replaced
with polymer insulators
7 400 kV Moga-Hissar 6th
& 8th
Sept, 6th
,22nd
& 23rd
Nov,6th
&
8th
Dec
Porcelain insulators replaced
with polymer insulators
8 400 kV Abdullapur-Bawana-
II
9th
,11-13,15-17,19,21,23,26,30th
Nov Porcelain insulators replaced
with polymer insulators
9 400 kV Khedar-Moga 6th
Nov Porcelain insulators replaced
with polymer insulators
10 400 kv Abdullapur-Bawana-I 14,18,20th
Nov Pre-Winter Maintenance
11 400kv Ludhiana-Jalandhar 19th
Nov AMP
12 400 kv Hissar-Bhiwadi 19th
–24th
,27,29,30th
Nov,1,2,7-9th
Dec Porcelain insulators replaced
with polymer insulators
13 400 kv Hissar-Khedar 8th
Dec Porcelain insulators replaced
with polymer insulators
14 400 kV Kisenpur-Moga-I 21st and 28
th Oct AMP
15 400 kV Kishenpur-Moga-II 23rd
& 29th
Sept AMP
ANNEXE - 9/III (page 2 of 4)
![Page 322: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/322.jpg)
NRLDC
Page 3 of 4
Annex-9/III
POWERLINKS SL.
NO.
NAME OF THE LINE TIME / DATE OF SHUTDOWN PURPOSE
1 400 kV Bareilly-Mandola-I 10th
April 09, 1st Sept,15
th -19
th Sept 170 identified locations replaced
out of 640 locations on the line in
April 09. Rest maintenance
carried out in Sep 09 during FSC
erection at Bareilly end
2 400 kV Bareilly-Mandola-II 11th
April 09,1st Sept to 8
th Sept
UPPCL SL.
NO.
NAME OF THE LINE TIME / DATE OF
SHUTDOWN
PURPOSE
1 400 KV Anpara-Obra 29,30th Nov Pre-Winter Maintenance
2 400 KV Unnao-Agra 26th
Oct ,24th
Dec,26th
,27th
,28th
,29th
30th
Dec
Pre-Winter Maintenance
3. 400 KV Panki-Muradnagar 22nd
Oct,7-13th
Dec Porcelain insulators replaced with polymer insulators
4. 400 KV Agra-Muradnagar 19th
Nov, 20-23rd
Nov Pre-Winter Maintenance
5 400 KV Panki-Unnao 26th
Nov, 27th Nov Pre-Winter Maintenance
6 400 KV Azamgarh-Sarnath 8th
Dec, 9th Dec AMP, Pre-Winter Maintenance
7 400 kV Mau-Azamgarh 18th
Dec Pre-Winter Maintenance
8 400 kV Azamgarh-
Gorakhpur
11-18th
Nov Pre-Winter Maintenance
9 400 kV Anpara-Mau 11-18th
Nov Pre-Winter Maintenance
10 400 kV Azamgarh-
Sulatanpur
30th
Dec Maintenance
11 400 kV Anpara-Sarnath-I 20-23rd
Nov,25th
Nov,3rd
Dec
Pre-Winter Maintenance
12 400 kV Anpara-Sarnath-II 2nd
Dec,4th
Dec Pre-Winter Maintenance
13 400 kV Bareilly-Unnao-I 13,15,17th
Nov Pre-Winter Maintenance
14 400 kV Bareilly-Unnao-II 14,16,18th
Nov Pre-Winter Maintenance
15 400 kV Muradnagar-
Muzaffarnagar
7-11th
Nov.13-15th
Nov Porcelain insulators replaced with polymer insulators
16 400 kV Obra-Sultanpur 15th
,16th
,17th
Dec Pre-Winter Maintenance
ANNEXE - 9/III (page 3 of 4)
![Page 323: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/323.jpg)
NRLDC
Page 4 of 4
Annex-9/III
DTL
SL.
NO.
NAME OF THE LINE TIME / DATE OF
SHUTDOWN
PURPOSE
1. 400 KV Mandola-Bawana -I 25th
Oct,7th
Nov Pre-Winter Maintenance
2. 400 KV Bawana-Bamnauli -
I
22nd
Nov Porcelain insulators replaced with polymer insulators
3 400 KV Bamnauli-
Ballabhgarh-I
26th
Oct,26th
Nov,2nd,4th
,10th
,12th
,14th
,16th
,20th
Dec,24th
Dec
Porcelain insulators replaced with polymer insulators
4 400 kV Bamnauli-
Ballabhgarh-II
27,28th Nov,7
th ,8
th ,11
th
,13th
, 15th
,17th
,18th
,19th
22nd
,23rd
,25th
Dec
Porcelain insulators replaced with polymer insulators
BBMB SL. NO. NAME OF THE LINE TIME / DATE OF
SHUTDOWN
PURPOSE
1. 400 KV Dehar-Bhiwani 16-20th
Nov,29th
Dec Pre-winter Maintenance
2. 400 KV Dehar-Panipat 5-7 Nov Pre-winter Maintenance
RRVPNL SL. NO. NAME OF THE
LINE
TIME / DATE OF
SHUTDOWN
PURPOSE
1 220 kV BTPS-Alwar 26th
Dec,27th
Dec Porcelain insulators replaced with polymer insulators
PTCUL SL. NO. NAME OF THE
LINE
TIME / DATE OF
SHUTDOWN
PURPOSE
1 400 kV Rishikesh-
Kashipur
6th
Nov AMP
2 400 Kv Rishikesh-
Roorkee
7th
,8th
& 9th
Sept, 8th
Dec AMP
ANNEXE - 9III (page 4 of 4)
![Page 324: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/324.jpg)
Chapter- 9 _ ANNEXE -9/IV (page 1 of 1)
![Page 325: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/325.jpg)
Chapter
ANNEXE -9/V (page 1 of 1)
C.I 4 Protection "'''''it I", Up..gfOdation 01 Protection Syste m in Northern Grid
MS. NRPC in_ lllal in Ihe H~ NRPC meetin<J held on 1 9~ Sep1embef 2009.
!he need for ~ irnpro""""'nt.I>i>lIrad.tion 01 prole<tion . ystem in N<>rIhern
\Ifid ..... <lelibefa ted. The SulKommi!!ee consti!uted to 'mm<Mte term. '" ",je",,,,,e [TO R) for a ppoinliog !he <00"""'"' for <a<l)"ing rut Ihe protection_~
00 as 10 bOOg irnpro""""," ' in prote ction . ystem. II .... ~O!ed two op<iono:
Option ·1
The ""bry .... e POWERGRID cookI be . ppointed • • <oo..,~."t lor identifyin<) !he
requirement lor bOO\lin<J irnpr""""""t/lJp.grad.tion ",!he protection system in d1e N<>rIhem Gr'od.
ODtion .;/
Ro-prevntalive 01 IPGCL ataled !hal the pr~tion aucIiI ohouk! cover the
lI" ....... tng oIriono -.0.
Repoe..,ntati"" of NRLDC ataled IhIoI _ !he growIh of aystem and ita inte,,:o.-..e_. !he tau' Ie~ and __ ~xitin would ;""",a ... He
1Ugr}H1ed "aI !he pilot atheme ahoukI be ..,lected !of ~ out the prolecliDn ...,drl "' IIIe _ hslanee.
Ro-prevnlalive o r HVPNL . laled lllat in view 01 dillerenl type of Pf""'ettion ""hem ... we<abve in !he ~m. ~ _ not be ..,~ !of • single ma'lUf.ClUrer 01 NIr;"I 10 tell !he _ y_m. MoreoYer . ...... , _ of
trano",I ....... elemento _ Moo be req<nred to _ Ie "es.e KtivtIies.
Ro-prHetItative of POWERGRID ataled thai !he conouI!anl could be _ from
.t"""""" Of identi~ !he ..,... ... ltant br...-ryInQ out !he prnIOttion _ •.
Membero noted the TCC debbenlliona and <le<:icIed _!he Sub-c:""""*'ee_ identrf,I!he plot o<lletne and eligible conou_ and .roo """'e ",comrnend31iono on .. c;hn;"1 and ..... .,;"r ",quir"emenl b<!he ~ _~ DI pilot ""heme.
![Page 326: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/326.jpg)
ANNEXE - 9/VI (page 1 of 3)
![Page 327: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/327.jpg)
_ ANNEXE - 9/VI (page 2 of 3)
![Page 328: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/328.jpg)
_ ANNEXE -9/VI (page 3 of 3)
![Page 329: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/329.jpg)
i
OFFICE MEMORANDUM
Sluam bhaktl Dhllwan, Ran fttllrg, New Uelhi.
! 'Sub: Met!tlng taken by Secretary(Power) tegarding tttp,U~', bt
lrtudmission Unes In the Northern Iteglon on 7tl Ibltt ~Ha March, 2008.
**********
, ;C Minutes 'of the tneetillg taken by Secretary(PowerJ at 11.30 AM on 9 th March, 2008 on the above subject are enclosed fot. il1forlldUioli: ahd necessary action. "':. ,
,':. .t
ilL : ~i:: jli' ;1
'!P:, '! .. i, . • , ., 'i' I .. ,
Chairperson, CEI\~ Ne~ Delhi. '. '{. . ,I ii,~ ~ II : i Member(ElectrkaJ), Railway Board, N~w Delhi: Ill:i;1 ;I.'i Member(GO&D), CEA ;', ,Il/l' Iii: Member(PS), CEA '\', i. :;: ~ecretary(power), Govt. of Haryaila, d~aildig~t.l , Pro Secretary(Ehergy), GovL of UP, :Lu,cknow ' Setretary(Power), Govt. 'of NCT of Delhi. C D, NTPC, New Delhi.
MD, PGCIL, Gurgaull 'Member Secretary, NRPC, New Delhi.
~L . &/ 1•
: I
'/1
1 .. ' ,
l'
"
![Page 330: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/330.jpg)
, , . Meetbtl ChaIred by Secretary (Power) 011 9 th Mar~lt, 20Ql4 ~t 11.3~
AMreillrding trippillg of 1'rallsmisslol1 llnes ltt the rfuttlle~" Region. .'.
~ , \ !.
. . An emergency ui~etillg was cOhvened b~, Sec.-eta~t~th"Ct1! l\ ' ... ·In VIew of outage of a large numb~r of high vollage Vowel· ' transmission lines in the Northern Region affecting supply of' power to Delhi, its adjoining areas as 'well as the Railways. List·
(', .... " of participants is annexed and gist of the discussiott, isgiveu below. '.'
1.
3.
! .4.
, .
! . ,j.,'
, , '\,'~.\
,
Inithitiftg the discussion's, Secretaty(Power) exptessetldeep' concern about the large number of trippings of 400 kV power transmission lines ill Northern Region on 7m & 9 th March, 2008 '(49 circuits a:nd 35 circuits respectively).' He nlel~tit>tled that the meeting has' been conven~d to Hike stock ',of the: Situation and to plan for .Corrective actions to be taken flJotlt in the short and th,e medium term. Secretary(Po1,Ner) desir~d that " : the reasons for occurrence of U1is phenOlllenOtl in the vicittity of the NCR area also need to be ascertained; , "
birector(Opcrations), DTLmentioned that high levc:ls of poUUti9n arising out of vehicle emissions, · btick kilt). 'ilnd
. Ja..-ggery-un. its, high~onstrudi?n acthri.t. ~ ... ~n. th~ •.. ~., .Cf.lf .. e '~'."'; ;!,t: t th,~ NCR coupled wIth fog, hIgh hUtrl~thty d~~J~I! • . \l'
:. c. rtJps and absen?e of~tnter r~ns it1tl~~ mOl'lil.,.I,.:. I;Wt.',.' ; e..'.' '.' ";:'1",,,1 ... 1.) •. :.\,:,.
,\~a;p~~;:~ed ~1:l~:~o;Oi~~n~U~o t1~;~h iI::'~m ~I . ,m •. j.;.!\i~.[,! ,I,
),::!~:dy~':.-:~iS kind of poIlUtionlei~l. Whi~\~,.:,~,~~, J1'~!il
. :::'!I~~~8~;~e o~o to:h~~~ c~!.!:~eliP~.:~~~f~'!;III!fl Chairman, CEA mentioned' that hutline cleamtigl~t tidlj\fttfjr eff~ctive because of thickpollutahts' for whitii·\#~ slfihgs required to be dismantled and scrubbed wi~h d~tetgelit, ttt!J ,mere washing does not serve the purpo~e. , '. I' .
i!
ly1~irtber(Electric), Raliway Board s~U~d that pUweii hulJpl,t)S I~eihg provided for railway traction,' frOIn DadH arl4 AlU'lliyEf, pqW~.. $ta{itms of NTPC and in the fibscllce or supply; trott, Didri, :supply from Auraiya was e.x.tellded '. uptd ··.IJt(ti~~,: Hdwever, even after restoration of sUpply frotH t>dtlri~ ,: ~ltt;; . ",' ~~ ,8. UP .. 'IlIY for railway tracti?l1.could not ... be, .. rest?ll~.~.".,.d.U .. i .. e.:.l.l·,.\~J)l.,.j ... ~"';i.'i,;\.... i'll! in the 132 kV transmISSIon syster, 1, ~"f ratlw~sl,\t\~$Fl~C'~, ~.) ,11<,,· '1\,\\ii·
1 ~ f~i" ;1 between Dadri aod Dankaur; . ~..: I ' .: i":ili!~i:.
Merhber(PS}, CEA pointed out that ,iu:highly ptlhUltd. tlf.~~. ,!
extra ,creepage is required in the insulators. Tl1e. cle~i.i1fJ~; f~f' .. such insulators are well known. ; 11\,' " .. _ 1~1~ ,
, .';
., :
![Page 331: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/331.jpg)
till! r-i --==============::::
:6.
8.
,,: ;.
Representative from powergrid pointed out that Incert-aiIlOIead conventional ceramic insulators had been replaced lJy polymer Insulators. In response to a query. it waS confirmed by the powergrld that bird guards have been provided 011 all th~ existing 400 kV lines of powergrid • to obviate U,e pollutiol
,
hazard n"om birds.' ' I , .i
Secretary (Powe r) re-emphasized the Ileed for clasSlliclltltlil M· ,. grid disturbances/ incidents into various categories by CEA anU powetgrld. and had becn repeatedly asked for by the'Minislry. ! After detailed, dcllberation, thc following remcdlal measuf~s
,.were decided:-' .
II Physical cleaning of insulatofs on' 11 war footing 011 t',e Identified 17 critical power transllllssioll IblCS as givcn [at . Annex-I be takcn 011 top priority and be completed witl~in (Ille week by thc rcspcctlve orgauiza.tioI1S. Cleallillg work 1m olil} ",circuit/pole of. Dadrl-Mandl1l1ll1, Dawwa- Hissiu". Rihand-Dadri be taken- up by powergrid and Mandauta-Sawana by.DTL today itself. The work of cleaning would: be
i· '.' If monitored by Melnber(GO) and Member(,PS), CEA.
ill powergrid should get the chcmical IlJlruysis of deposits ,on i .
_ the,lnsl1111l0r strings done to identify thc source ot pu IIU lion ~" mofe precisely. '" i ' i.. '.' :, ~)*,q~ergrid" would approach CC,IidA , pow~~ l:g"'lt,j~l: ,':. ii ;:JIJI;;!1 lnsUtut~(CPRIl tl? asccrt~n If the: )stlng \#-.~It .' . ,.,';i 11 ! •
. . n.P
l1f?pnate for hl~h pollut,lOn conditt.'.;i.'. ,s and W .•... ~ .. o.;'J.b .. ' I .•. · .. ', .. ' .. t'.'. ' .. 8 .. : .... , .. !.If.'·'.l
. . reqUired changes m matenal and dl! ',' \I. If antFI;idf f g ltL ~I' )'~:. :'I!i .
lv, The safety margin in the Insulators U~ployed f)l.' i Uti! I' Ii IIi' ,til Voltage Transmission Llncs (EHV) be ,eJtamlneU'b 1{;~f l L ..... iI i1
v, comple. te replacement of conventiotUU; i.nsul~rSi tN! dOl1.J/I) .• J.rl
';' 'I~i 1
. 'insulators on all vulnerable lines ill the NCR art;abetql-e oI~'lIt, ,.'i ' 2008. Translnission lines passing over sugarcahc W~t!a: ahU , brick kiln area should be Identified 9Jjd the COlltertieU slMe ,r Governments be advised to take Inutiediate measures to'alup 'I-, pollution. I\n action plan for ,11 time b'1Ulld sill biolltll f
I, Il!'plcmcntation schedule bc prepare~ by CEA{NItI'C .. ' h' ~llbstructions be sent to rcspcctlvC'Districl
r MliglliWl.lt\81or II'
• t" I enforcing pollution norms In the IJIghly pOlIl1l!:!1 "tt~~th"" If , : including avoidance of use of tuUb<!r. I'VC \\IilM", ,,\~. tur "
I combustion ill brick killls and usc of bagits$e lil' J,"ery 1 ,units in the vicinity of transmlsslb~j lines. ~et~, ~.
'of Delhi. IlmyallB and Uttar Pnr1\lesh' wltl i aU 1 d~ lilUltl _ :, ;,:, '. • < 1 • : ''! I: 1
, I • . . , : ; ,
![Page 332: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/332.jpg)
" ",'
-,-,: . . ' ; officers' for this' .purposc. , Powergrid/ OTL ~wo'uld provIde
. e",act location of stOlle quarries, brick kilnS, sugarcalle, . bagasse burning arcas, clc .
. ' vU, . Railways need to have a higher risk insurance by < hav.ing art ~ternate source of supply instead of depending 011
a single-sOurce for supply. Regulators would need ttJ Ue . , involved sO that supply to an essential sClvice like Railways
is not viewed as a purely commercial proposition by the State utiHtles. The Railway would need ernergency power supplies in contingcl.1cies from local discOlIlS.
'"w, : Chairman, CEA would cQnvene ,a meeting of the : constituents of the: Northern Region to a~uress varioUS i' issUes related to replacemen t of insulators .
. ... ~ A reference needs to he made to the Department of ~cience & . 1 Technology 'and the Indian Meteorological Department to ntH!
, , . i out the reasons for the unusual' fog and disrupting . t,' ; '~nvironment at this time of the year. '
Yx). Aerisls Managemc,;t Group headcd by Mem\;er{G&OI. CEA , " . with representatives from POCIL, NRLDC, DTL, UP;. Haryana
. andNRPC will start functioning and Ineet at short notice on a regular basis and also keep the control toom' in the
, . MInistry of Power informed. Direclor(Translllission), MoP ; L wtluld bethc nodal officer who has to be ke t infonned of. , III I' , iii III ,d!wel?pmetllbs and implell.lentation by pow n, !' I :'t "! 11
. HVPNL all'! UfPCL. ,! ' !:I: I' 1';1': I l; ~ I', , " I! 1·\1
:ala dEt\/powefgrid would immediately also take st~ps to eng, lh~: II \ i I III
" ,
~ : ~ -'i:
! !
:.' ), ,. taB ,to 'wh! the trippillgs h?-ve been ln~s~ly restti~t~t1 to hj"~'~~~i 1 ! r 1,: II!' ",I ~,~pl,tage ~lDe~ and not at sub-lransnllS~lOn level'l ' .' '1"'11': ,. Ii I!II
..0': ,: Hl.gh ... 1evclof alert w~uld conl1n~c to h.r. '1lla1nt~.b.l~ ! ',+.! .... !ll.' , antla11 leave/tours by senIor Powergnd offitlWS would: lfi! ,.;.!! ., : !;H 1 '
C\1rtailed.ti~l further notice. , The NRLDC should conliUrii~ to I l!. lj:jl 1 ,1.. h~ve Senlof Management person~lel round the cluck on ttUty .".i
tUl the stability of the gridl"elUrns.· ' ,
, , , r; '. 1,
. i
, 'I,']
\ '
, : 1 I': ' .. , . ~"" 1 i
.11 ,
," -_.
I,
![Page 333: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/333.jpg)
,l
S.No. 'L
'3 " ,; :, ",
4. 5.
,,8. 9~ ,10. 11.
, ,ttl. ,13. " ,14.
," ,15. 16. 17.
,LIST OF C,UTICALTRANSMlSSION LUtEs
400 kV TransmissIon Line B,awana-Bamnauli-I
, Bawana-BamnauJi-II aahaduf arh-Bawana Bareillv··Mandaula-11 Mandaula-Bawana-:-I Mandaula-Bawana-II
,'Oadri-Mandaula-II,
Muradn ar-Muzaffarn ar Mandaula-Bareill :.1 , Ballab arh-BamnauH-I Panki-Muradna ar IUband-Dadri Pole I
a,dri Pani at-II adri Pani at-J
Bawana-Hissar Dadri-Dankaur
1>1 ,: ! i
r 11" :'
l ' 1';1'
. ,
OTL OTL
, POCIL POWERLINK OTL OTL , POCIL' DTL UPPCL POWERLINK OTL UPPCL
,POCIL POCIL, FOCIL I'OCIL Railwa s
" i
"
i, ' i:
! •
, , ;,'
ANNEX-I
![Page 334: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/334.jpg)
; ;'"
-~~ ... ···'b1~ .. ·~ .. ( ... i,"
·r ". - ~''\\ t
LIST OF,PARTICIPANTS IN THE MEETING IIELD ON 9.3.08 AT 11.30 AM
.1\sltfISTRY OF POWER
"I ,',
; ~ , i
1. 2. 3. 4. 5. 6.
-
Shd Anil Razden, Secrctary(Power) Shri Anil Kumar, 1\.dd1. Secretary Shri O.B. Pradhan, Add1. Secretary Shri Jayant Kawale, Jt. Secretary(H) Shd Lokesh Chandra, Direclo((Trans) Shri A.K. Saxena, Direclor(OM)
;. MINISTRY or RAILWAYS
·Hi tiUH)'···
." ,
7. 8. 9.
: r" '2_ ~? /!..5::. .. :~ (, , Shri S.S. Khurana, 'Memoer(Electrical) \ .. (.' .. /.;,;;·:Y.:X':·:·:·::·::·::·:::::·:;::::::i::::::,::·:;'. Shri Atul Kumar, ED(RE) -, C\ \" t\~~ I] 3:0:.>'" q);t!I~! q\iniTj~l'l ;\;'J'l'li'::·:.:;.~ .. Shri Arvind K. Tyagi, DRE~ (Iei' III 4-1£ 1 S i~: q ~_ ~o/./I...'PI/-......... ~:
: 2 . .' /. ···t '1J'n,,·,·(,,":.:;l·<it51J:· .~. '.. .. ~ ~ ~ ~ \ U \.,1 . • i:., m-:t!)" lilft;! '''''' '--•. , ..-;./
CENTRAL ltLECTRICITY AUTHORITy .. ·: .. :·:.:;.,··.. ~. :'" ;q"·.l.·i·:::;·· 10. ' Shri Rakesh Nath, Chairperson .... :.::.:.:.:::: ... ::.~;.~.;;"':.:.::.:;.:.' ,
11. Shri V. Ramakrishna, Member(PS) 12. Shri S.M. Ohlman, Memoer(OO&D) 13. , Shri V.S.Verma, Member(Plg.)
i" f4. Shri Gurdial'Singh, Membcr(Hydro)
:'. iii, t:!,;'! I j I,:: 15. ,.Shri S.P. Singh, Member secretary., '" .. ",. I II NRPC'.i
'·;~·,:l!ll\ir'OO, :rt. OF~' YANA . i, : .. ! 'i ," Ij ,'I'd:;!' :' 16. " hri Ashok Lavase, Secretary(Powdd : ~. a:' i
1!l!'tc1PC' . !
17.~hri T. Sankaralingalll, CMO' , " , !
'QCIL i 18. j Shri S.Majulildar, Direclor(Projects)
19. Shri R.O. Yadav, ED 'l 20. ahri R.N. Nayak, EU l i 21. Shri Babri, OM
,b8LHI TRAltaco LTD. Shri Rajinder Kumar, Secrctary (power &CMD,'DTL
: 22.
, ·23. :t{\:I:I;24. [
Shri S.R. Sethi, Director(Operalions) Shri A.K. Kaul, OM, SLUe
*************
; '{
'I
. ,
,\ I" , "
;"
t : , \
; ,
i, :1
![Page 335: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/335.jpg)
'lmrlRCliR GOVERNMENT OF INDIA ~~
MINISTRY OF POWER ~~ Ji1ftM;'C0I
CENTRAL ELECTRICITY AUmORITY ftrg 3I1itR Jr1I1tJ
GRID MANAGEMENT DIVISION 9001:2(00)
Var 1ICR. 'CIfllCJidJj ~. SEW A BBA WAN, R.K. PURAM,
~~-110866 NEW DELIfl- 110066
No.6INRIDST/GM-08 \ loJ\
To
As per list
(:mf. lffi. 3Ir.
Subject: Minutes of Meeting taken by Chairperson CEA on 30.4.08 regarding replacement of porcelain insulators by polymer insulators
Sir,
Minutes of Meeting taken by Chairperson CEA on 30.4.08 regarding replacement of porcelain insulators by polymer insulators on all vulnerable lines in Northern Region are enclosed for information and necessary action.
Encl:asabove
Copy for information to:
1. SA to Chairperson CEA 2. SA to Member(GO&D) 3. Director(Transmission), MOP
!
. ~ t::/-- ~t-· J-. :~
. ..' fVl~... . D:\NR\MEETlNG\Others\Tnsulator Replaceinent -30.04.08\minutes of meting 3O.4.0S.doc
Yours faithfully,
'ULcv~:'-' t, - D Q.
(T. Chatt:~) .~ - Q
Chief Emgineer( uM)
Page6of7
![Page 336: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/336.jpg)
~._.'mll.i"".. ______________ .......... ________ .......... ____ _
LIST OF ADDRESSEE
1. Chairman & Managing Director 2. Managing Director Delhi Transco Ltd., U.P. Power Corporation Limited,
Shakti Sadan, KotJa Road, ITO, Shakti Bhawan, 14-Ashok Marg, NEW DELHI-110 002. LUCKNOW-226 001. Tel: 011-23215198 Tel: 0522-2287792,2287827 FAX: 011-23234640 FAX: 0522-2287785
3. Chairman 4. Managing Director, Punjab State Electricity Board" Haryana Vidyut Prasaran Nigam Ltd., The Mall, PATIALA-147 001. Shakti Bhawan, Sector-6, Tel: 0175-2212005 PANCHKULA-134 109. FAX: 0175-2213199
Tel: 0172-2560579 FAX: 0172-2560640
5. Chairman 6. Development Commissioner (Power), H. P. State Electricity Board, POD, Govt. of Jammu & Kashmir, Vidyut Bhawan, JAMMU (J&K) SHIMLA-171 004. Tel: 0191-2530265/2532809 Tel: 0177-2813563 FAX: 0191-2534284 FJU<:0177-2658984
7. Chainnan & Managing Director, 8. Managing Director, Rajasthan Rajya Vidyut Prasaran Nigam Power Transmission Corporation of Ltd., Uttaranchal Limited (PTCUL), Vidyut Bhavan, Jyoti Nagar, Janpath, 7 -B, Vasant Vihar Enclave, Street No.1, JAIPUR-302 005. Dehradun - 248 001.
Tel: 0141-2740118 Tel: 0135-2762460 FAX: 0135-2762473
FAX: 0141-2740168
9. Chief Engineer, 10. Chairman, Electricity Department, Bhakra Beas Management Board, UT of Chandigarh, Madhya Marg, Sector-19 B, Secretariat office building, Sector 9-0, Chandigam-16oo19 . CHANDIGARH-160 009. Tel: 0172-2548542
FAX: 0172-2549857 Tel: 0172-2741340 FAX: 0172-274273312740276 ,
11. Director (Projects) 12. Member Secretary, PGCIL ~V Northern Regional Power Committee, PlotNo,-2, Sector-29, 18A, SJS Marg, Katwaria Sarai, Near IFFCO Chowk, New Delhi-11 0016 Gurgaon-122001 Tel: 011-26511211 Tel: 0124 ... 2571930 FAX: 011-26868528 F~: 0124-2571932
13. Executive Director, NRLDC, 18 A , SJS Marg, Ka~aria Sarai, New Delhi-110016 Tel: 011-26852843 FAX:011-26852747
.' ;.
.-
'... '." .~. . '.~ '. - ~. .
; <," , .. ", ';,. "'
![Page 337: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/337.jpg)
',i
1.
2.
3. ,
Minutes of Meeting Taken by Chairperson, CEA on 30.04.08 Regarding Replacement of Insulators in Northern Region.
List of Participants is enclosed at Annexure-I
Chairperson, CEA welcomed all the delegates and recalled that there had been many incidences of trip pings of transmission lines in the Northern Region during foggy weather conditions during last three years. A Committee was set up to enquire into. the grid incidence which occurred in Northern Region on 27th January 2007 and the Committee had made very good recommendations to avoid recurrence of such incidences but there was no progress in implementation of the recommendations of the Committee. In the recommendation, the Committee had classified the pollution level on the basis of Equivalent Salt Deposit Density (ESDD). Till data are created'by ESDD measurements pollution levels Istretches would be determined on the basis of distance from source of pollution and number offlashovers. The Committee had alSo recommended that in areas exposed to heavy fog and heavy and very heavy pollution levels composite long rod (polymer insulators with silicon impregnated (SIR), weather sheds having creepage distance 25 mmlkVand 31mmlkV respectively may be employed. Chairperson, CEA mentioned that Powergrid has submitted a proposal for replacement of porcelain insulators with polymer insulators on the line sections exposed to heavy and very heavy pollution levels. He also mentioned that experience in 400 KV sub-station of Powergird at Dadri Switchyard with polymer insulators had been reported to be good.
Executive Director (SO), Powergrid intimated that Power grid had prepared plan for changing the insulators in NCR area as per the decision in the meeting taken by Secretary(power) on 9th March 2008. He also intimated that the entire stretch of lines falling under NCR area have been covered for the replacement of insulators as these line sections are exposed to heavy to very heavy pollution levels. The main criteria for selecting the lines was the number of fog related trippings and failure of insulator strings that has been observed during laSt few years. He also mentioned that polymer insulators have been' used in Ramagundam.Uyderabad and Jaypore - Gazuwaka 400 KV lines. Some portion of these lines are in the heavy industrial pollution wne and some in coastal areas and experience has been good with no flashover. In Rihand-Dadri HVDC line also polymer insulators have been used on some towers since 1997 and experience was good. ~ PTCUL also intimated that in Gujarat, the experiment of using polymer insulators in coastal area exposed to saline pollution was very successful and the number of trippings were almost nil.
Executive Director, NRLDC stated that the selection of lines for insulator replacement should be on the basis of number of fog related trippings. The lines feeding' the essential load centres like DeIh~ Railways, water pumping stations and auxiliary supply to generating stations may be included for replacement of porceIaIa insulators by polymer insulators. Chairman, PTCUL enquired about the replacement of insulators on live lines. Powergrid mentioned that the hot line method of changing inSulators is very expensive and slow and it is suitable for changing of few insulators only. It was felt that
, D:~\MEETING\Others\Insulator Replacement -30.04.OS\minutes of meting 30.4.0S.doc Page] of5
, .".~. . ':-
![Page 338: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/338.jpg)
the insulators may be changed after taking shut down of the lines to expedite the replacement. .
4. Regar~in~ change of insulators in the Hnes owned by DTL, General Manager (SLDC), ?TL mtlmated that t~ey have plan to replace porcelain insulators with polymer msulators on 400 KV hnes and they· have planned to use anti-fog insulators on 220 kV lines."pTL alS? inform~ that they have requ~ted Power~d ~o take up .the work of replacement of msulators m DTL hnes also. Director ( Projects), Powergnd informed that Powergrid could procure polymer insulators for DTL but replacement should be done by DTL. Chairperson, CEA advised DTL that the replacement of insulators should be as per recommendations of the Committee.and in Delhi, the lines are in the areas of heavy and very heavy po]]ution levels and insulators should be replaced by polymer insulators only instead of anti-fog insulators. Chairperson, CEA said that the 400 KV and 220 KV rings must be covered along with metro feeder Hnes in Delhi. The representative ofDTL agreed to replace the insulators .as per recommendations of the Committee. DTL furnished the list of 400 KV and 220 KV Hnes where existing insulators would be replaced by polymer insulators ( Annexure-II)
5. The representative of BBMB intimated that they have planned for replacement of insulators in five lines in the NCR area in first phase. Other lines would be taken subsequently. He also intimated that the area under BBMB was that of medium po]]ution levels and they plan to replace the existing insulators by anti-fog insulators. Chairperson, CEA advised the1Jl that they should go for polymer insulators where the po]]ution level is heavy e.g. withiIJ2 kms. of brick kilns. He said that sections ofBa]]abgarh- Badarpur, Ballabgarh- Dadri and Ballabhgarh- Samyapur and Panipat- Narela -220 kV lines fall under heavy po]]ution zones and replacement by polymer insulators may be necessary. He said that DBMB should classify sections of Hnes as per the recommendations of the Enquiry Committee set up to enquire into the grid incidence which occurred in Northern Region on 2th January 2007 and accordingly, anti-fog or polymer insulators should be used by BBMB. BBMB agreed to prepare list of all their lines where replacement of existing insulators by anti-fog or polymer insulators is required as per the recomo1eodation of tile committee and submit the same to CENNRPC within one week.
6. Representative of HVPNL· informed that they have plan to use anti-fog insulators in all future lines and they would try to use anti-fog insulators in lines under commissioning. He informed that HVPNL has made a- plan in which 14 lines of 220 KV and 132 kV (840 Ckt. Km.) in NCR area were selected for insulator replacement in first phase. They will schedule for replacement ofinsulators after the time of peak load is over. Award for insulators is in pipe line. Chairperson, CEA advised HVPNL to keep the delivery period for insulators shortest possible and giv' a programme for the replacement work. HVPN agreed to submit the list of lines and programme for replacement within a week.
7. Representative of RRVNL informed that they do not have pollution problem. However, they would use anti-fog insulators in NCR area. Chairperson, CEA advised them to have survey of lines for pollution and change insulators with anti-fog/polymer as per recommendations ofthe Committee particularly in Badarpur-Alwar 220 KV line .
. '
. .. . D:\NR\Mffi.!TING\Others\Insulator Replacement -30.04.08\minutes of meting 30.4.08.doc Page2of7
. :'; .. '!
![Page 339: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/339.jpg)
il" ;,,""'"' !I'M" IMIii'
8. Representative of Punjab intimated that they do not have pollution problem but they faced problem of fog related trippings on 66 KV . lines Punjab has already changed insulators by anti-fog insulators wherever required like lines passing iIi Ludhiana District. Chairperson, CEA advised PSEB representative that they should survey the lines and change the existing insulators, if required, as per recommendation of the Committee.
9. The representative ofUPPCL intimated that 10 number,· of 400 kV and 220 kV lines of UPPCL in NCR have been identified for which they were planning the replacement of insulators. Executive Director, NRLDC mentioned that the lines emanating from Muradnagar and Moradabad sub-stations were vulnerable and these were very important for grid security. He· opined that the lines connected to Narora and Harduaganj power plants should also be included for changing of insulators by UPPCL.
10. Chairperson, CEA advised UPPCL that they should change the existing insulators with polymer near brick kiln and other high pollution area and UPPCL should consider the lines Narora-Simbhauli, Narora-Khurja, KhUlja-Harduaganj and Muradnagar -Khutja for replacement of insulators. UPPCL gave a list of 10 lines (Annexure-III) where replacement of insulators with polymer insulators has. been planned UPPCL agreed to furnish the list of additional lines as per discussion in the meeting and recommendations of Enquiry Committee to CENNRPC within a week.·
11. Regarding the supply to Railways through UPPCL network,it was felt that Railways need additional supply point from UP network as standby arrangement in addition to dedicated feed from NTPC in Kanpur-Delhi section. It was decided that Member(GO&D) would take a meeting with the representatives of Railway and UPPCL to sort out the issue relating to supply of standby power to Railways. Railways would also be advised to approach distribution companies in UP formally. Railways would also be advised to replace insulators on their dedicated transmission lines from NTPC in Northern Region.
12. Regarding removal of pollution causing installations near transmission lines, Chairperson, CEA asked the representatives of State Utilities to prepare the list of such installations and take up the issue with State Govts. In case there is any delay or inaction on part of state authorities the matter could be referred to CENMoP for using their good offices with the concerned states .
13. Member Secretary, NRPC mentioned the need of bird guards to avoid cOntamination of insulators due to bird droppings and the same were also recommended by the Enquiry Committee. Powergrid informed that bird guards were placed wherever problem due to bird droppings was observed. Chairperson,CEA advised all the Trnnsmission Utilities to p~ bird guards on all the lines wherever required.
14. Powergrid requested that the expenditure incurred by them as replacement of insulators should be capitalized and shut down time availed by them for replacement of insulators should be considered as deemed availability for calculating the line availability .
. D:\NR\MEETING\Qthers\lnsulator Replacement -30.04.08\minutes of meting 30.4.0S.doc Page30f5
, . ~. . ·r· . ' ..
.. ~,'
![Page 340: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/340.jpg)
-----------------------------------~
15. Chairperson, CEA opined that all the Transmission Utilities whether State or Central would need to capitalize the expenditure incurred on replacement of insulators to recover the cost as the bulk placement of insulators by anti-fog insulator/polymer insulators on existing lines is an R&M activity.
I
16. Regarding deemed availability for the lines due to replacement of insulators the same may be examined by Member Secretary, NRPC as availability of Powergrid is being certified by NRPC.' ' . .
In conclusion the following decisions were taken:
a) The list of transmission lines identified by Powergrid as per Annexure-IV shall be taken up for replacement of insulators with polymer insulators in Phase-I, II & ill as proposed by Powergrid. Powergrid shall furnish the time frame of completion of3 phases to CEA/NRPC. The first phase should be completed by Nov.,2ooS.
b) UP in addition to the lines indicated in Para 10 as well as in Annexure-III shall identify additional 400 KV1220 KV lines as per the discussion in the meeting and recommendations of the Enquiry Committee and intimate time frame for replacement within one week to CEAlNRPC.
c) DTL shall furnish time frame for replacement of insulators on the lines as indicated in Annexure-IL
d) BBMB in addition to the lines indicated in Para 5 shall identify additional 400 KV/2io KV lines as per the discussion in the meeting and recommendations of the Enquiry Committee and intimate time frame for replacement within one week toCEAlNRPC
e) Haryana, and Punjab shall also submit the list of lines identified for replacement of insulators as per the dlscossion in the meeting and in line with the recommendations of the Enquiry Committee and time ft8me for replacement within one week to CEA/NRPC,
t) RRVPN shall replace the insulators on the Badarpur-A1war line sections wherever required.
g) Expenditure incurred by Powergrid for replacement of insulators on existing lines shall be capitalized and recovered through tariff.
h) Member, Secretary NRPC shall examine the issue of deemed availability of Powergrid lines for the shutdown period availed for replacement of insulators.
i) NRPC shall monitor the progress of replacement of insulators as per the plan submitted by States and Powergrid .
. <
D:\NRimEuNG\Others\Jnsulator Replacement -30.D4.0S\minutes of meting 30.4.0S.doc , , Page 4 of5
',',.' ',.
![Page 341: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/341.jpg)
,I 1
JI
j) NRPC will advise Railways to replace insulators on dedicated transmission system from NTPC Dadri & Auriya to their system as per the recommendations of the Enquiry Committee.
k) CEA will advise Railways to take up the matter regarding traction supply points in UP as standby source with Distribution Companies of UP.
l):\NR\MEETING\Others\Jnsulator Replacement -30.04.08\minutes of meting 30.4.0S.doc
, . '~. . .~ .. ~,
Page 5 of7
![Page 342: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/342.jpg)
---, .
List of Participal)ts
SI Shri
Rakesh Nath, Chairperson .............................. In Chair S.M.Dhiman, Member (GO & D) , T. Chattetjee, Chief Engineer B.K.Jain, Director H.K.Pandey, Dy. Director
PGCIL
S.Majumdar,Director(Proj. ) RG. Yadav,ED(OS) P.K. Vohra, ED (NR-II) Ramesh Bahri, GM (O&M) Pankaj Kumar, AGM(OS) R. Prasad,DGM,COMML Anish Anand,DGM (Engg.TL) Atul Mittal,CM (O&M) Sanjeev Singh Rajesh Kumar
NRLDC
S.K.Soonee, B.D. R Kumar
NRPC
S.P.Singh Gaherwar, Member Secretary RP. Aggarwal, S.B. (0) Vikram Singh, E.E Rishika Saran, B.E
BBMB
N. K. Arora Member (P) S.C. Mangal, S.E. (TIS)
uppeL
V.K. Agarwal, S.B.
HPSEB
S.K. Shanna,Director (pR&CERC) " .
, .: '~. . '!
ANNEXURE-I
![Page 343: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/343.jpg)
V.P. Dutta,GM(O&M) AK.Kaul, G.M. (SLDC)
RVPN
Y. K. Raizada,Director(Tech.)
HVPNL Niraj Gulati, C.E. (SO&C)
S.l. Singh RP. Bector,Dy. ChiefEngineer,Trans.Design
PTCU,f.t S. Mohan Ram,M.D.
![Page 344: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/344.jpg)
, .",.
~3221069 GM SLDC DTL DJRECTOAtl""lNJ 91. 11 :5::ill4'i1Cl:il:
................. .,a.trzz".Cb .. ~ .... ...... ............... ,... ...... ' .•. n.,,.., ..... ' .. ....
PAGE 02
II '. ,\ ,-,hYUY,UJ1 ... 1- L ..
1Il ~ CO dlIa ....... No.P.DTLl206lo7-011P.35/Opf.(O&M!Y4:t ..... 10 •• .2001 1M w. .............. to .. rtIpIIM! ...... 01 poroeJII.a ...... sa • .., ...---..... "" an ... 400ItV ...... ~ I ..... DeaI_ .. a1Jlldcr. •.
RD. ...... ' • .. , ... "..,." .. .,CI ..... : I. _ltV MlDdlPIa a.w.n. u-2. 4OOI.V Be ... ......., IJM S. 4G11(y ................ u. ~ ........... otthe ...... MAl .... ..
DMVu... .. DQt'IUP'I'IOIIf _ LID ........ rT ...... . .. ,..,... .... ,.. ... . , ..... ...... ...,. tIKN 1 ........ ·w..IaD'CUII II $' lJ6 ,... 2
'NINJa ,._ I)IC U. 13 21 ." In , BawiM ......... Dt4C LIllI 2'7 2' ,... 1'14 4 • bIIiat OIIC ...... )' • U2 eo J ............. DttC LIIIII 20 ,. 2AO 211 , ....... Dt'CfJaIt 13 .. ." 3M 1 B .Ii s", ....... J)'C LIIIt 6 lJ n III I .U IDCUIe . " II ~M nl , .1·Oo'ClJIIIt " 13 4A I. 10 • •• ,....DlCUII ... ., '001 ,. II r n· 11M: ..... IS '7 240 m rJ "..... v .. UIII PCIJII . 31 , .. ,. l' Ie. 'I , -I.O.w CIIUaIJ DC U. •• '.0 "' 3D . ... ) .......... o."aa.muv~ ...... ... 040 3M us U $Ow &MD'ClJI. 21 ) :m I. 16 ........................... D'C ..... 3. 0 ~ H 17 . am. 0IIbIa D.tC LIM 3. 6 4H eo ,
II ra--DIC LIM l4 51 '21 SID If J1"N. ilX!'" 21 .. 51' U' 28 ,,11&.- M:u.. , ,
" ,.
![Page 345: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/345.jpg)
" .. "
.,,' ~ . Sl. No.
l.
2.
3.
4.
5.
6.
7.
8.
9.
Proposal for replacement of insulator by polymer insulators in polluted areas on 400KV & 220KV Transmission Lines in Transmission West Zone
Number of towers where Number of Polymer Disc. Disc
Cost of Cost of work Total Na~e of Tnlnsmission Line
Insulators are Insulators material
Rs. in Lac Rs. in Lac Remarks
required to be String Rs.inLac
chan2ed 35 days shut-down
400KV Panki-Muradnagar tine 147 Nos. 441 Nos. 110.25 26.50 136.75 required on day to day basis (with 4 gangs) 10 days shut-down
400KV Muradnagar-Muzaffarnagar Line 35 Nos. 135 Nos. 33.75 8.10 41.85 required on day to day basis (with 4 gangs) 15 days shut-down
220KV Muradnagar-Sahibabad Ckt-ll 90 Nos. 600 Nos. 108.00 30.00 138.00 required on day to day basis (with 4 gangs) 20 days shut-down
220KV Muradnagar-Modipurarn Line 121 Nos. 417 Nos. 75.00 20.85 95.85 required on day to day basis (with 4 gangs)
220KV DIC Muradnagar-Khurja Line 12 days shut-down
70 Nos. 420 Nos. 75.60 21.00 96.60 require<;l on day to day Ckt-l basis (with 4 gangs)
20 days shut-down 220KV Muradnagar-Shamli Line 115 Nos. 345 Nos. 62.10 17.25 79.35 required on day to day
basis (with 4 gangs) 2 days shut-down
220KV Modipuram-Matore Line 11 Nos. 33 Nos. 6.00 1.65 7.65 required on day to day basis (with 4 gangs) 7 days shut-down
220KV Baraut-Muradnagar Line 40 Nos. 120 Nos. 21.50 6.00 27.50 required on day to day basis (with 4 gangs)
220KV Interconnector-l&ll between 2 <;lays shut-down
7 Nos. 54 Nos. 9.70 2.70 12.40 required on day to day Muradnagar
. basis (with 4 gangs) 4 days shut-down
10. 220KV DIC Matore-Shatabdinagar 25 Nos. 150 Nos. 27.00 7.50 34.50 required on day to day basis (with 4 gangs)
Total 5211.96 141.55 610.45
~~~~ CHIEF ENGINEER (TW)
~,
~ .
.; ,. f"" ~
",1*10
![Page 346: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/346.jpg)
J
< - ~
1:," .,,·· .. /'..:I·-IV ,~ . -, - ....---...... , 0"1002
TUE 16:37 FAX. 911242571914 CC(OS) j@OOl
LIST OF LINES ON WHICH POAOAI!L1N INSULATORS ARE REQUIRED TO BE REPLACED WITH POLYMER INULATORS IN NORTHERN REGION
Phase -I
line Stretch I length where S.No. Name of the line length in polymer insulators
KM are to be re~aced 1. 400 KV DADRI MANDOLA-I 46 . 46 2. 400 KV DADRI MANDaLA-II 46 46 3, 400 I<VDADRI - BALlABHGARH-1 58 58 4, 400 KVDADRI - BALLABHGARH-II 58 58 5, 400 KYMEERUT-MANDOLA-I 60 60 6, 400 KVMEERUT-MANDOLA-II 60 60 7. 400 KVDADRI-PANIPAT-I 112 112 ft 400 KVDADRI-PANIPAT-II 117 117 9, 400 KVDADRI-M'KOTLA 299 157 10, 400 KVMAINPURI-BALlABGARH-1 236 142 11: 400 KVMAINPURI-BALLABGARH-II 236 .142 12. 400 KVKANPUR-BAlLABGARH 386 232 13. 400 KVBASS1-HISSAR 277 166 14. 400 KV MAHARANIBAGH UlO ·31 31 15, -t 500 KV HVDC RIHAND - DAORI POLE-I 815 354 16. -t 500 KV HVDC RIHAND - DADRI POLE-II 815 354 17, 400KV HISAR-BAWANA TRANS. LINE D/C PORTION 99 1-257
18. 400KV HISAR-BHIWANI. BHIWANI~BAHADURGARH 2.5 1-4, 94:-97
D/C PORTION 19. 400KV OIC lILO AT BAHADURGARH 18 1-46 20, 400KV HISAR-BAWANA TRANS. LINE SIC PORTION 34 1-93 21, 400KV.f-IISAR-BHIWANI TRANS. LINE SIC PORTION 34 1-88
22. 400 KV O/C ABDULLA-PUR - BAWANA TRANS. LINE. 167 40-66, 214-243. 349-369,408-438
23, 400 KV SIC HISAR-FATEHABAD-MOGA TRANS, LINES 209 200 Nos. 24. 220 KVD/G H!SAR - HISAR TRANS, LINE 14 1-46
Phase -II
Line Stretch/length where S.NO. NAME OF THE LINE length in polymer Insulators
KM are to be replaced 1. 400 'KVDAORI-MURADNAGAR 30 30 2. 400 KVMURADABAO-MURAONAGAR 133 80 3: 400 KVMEERUT - MUZAFFARNAGAR 42 42 4, 400 KVAGRA~BALLABGARH 181 109 5, 400 KVBALLABGARH-BHIWADI 61 61' 6, 400 KVBHWAOI-BASSI ~35 141 7. 220 KV FGPP - PALLA 16 16 8. . 220 KV FGPP - S'PUR 18 18 9. 4QO KV SIC HISAR-FATEHABAD-MOGA TRANS, LINES 209 200 Nos. 10. 400KV OIC LllO AT FATEHABAD 30 1-78 11, 400 KV D/C ABDULLAPUR - BAWANA TRANS, LINE. 167 244-348, 370-407
12, 400 KVD/G,NATHPA JHAKRJ-ABDUlLAPUR TRANS. 180 324-367,392-431---1 LINE.
,
13. 400KV DIG lilSAR-KAITHAL-PATIALA-N,ALAGARH 211 Between 376-676 I .. (Hisar) . I 14. I 400KV ,SIC JALANDHAR-LUOHIANA-MALERKOTLA 120.744 60% towers .J
• .: .~. . '!'
![Page 347: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/347.jpg)
TUE 16:37 FAX 911242571914 CC(OS)
Phase -III
I Stretch/length where
S.NO. NAME OF THE LINE Line length polymer insulators inKM are to be replaced.
1. AG.RA-BHIWADI-I 216 216 2. AGRA-BHIWADI-I 216 . 216 3. LlLO B'LY-MANDOLA AT MEERUT 20 20 4. LlLO B'GARH-BHIWARI AT GURGAON. 35 35 5. 400 KV LKO-M'BAO AT BAREILl Y 20 20 6. 400 KV ULO B'LY-MBAD 20 20 7.. 400 KVLllO BASSI-HISSAR 45 45 8. + 500 KV HVDC BAllA - BHIWARI - I 775 160 9. + 500 KV HVDC BAllA - BHIWARI - II 775 160 .
10. 400KV D/CMOGA -BHIWADI 350 . 1-934
, ... ~.
![Page 348: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/348.jpg)
Ph. : 26967840, 26967842, 26967990, 26868681
Fax : 26865206
e-mail : [email protected] Website : www.nrpc.gov.in
भारत सरकार उ तर क्षेत्रीय िव यतु सिमित
18-ए, शहीद जीत िसहं मागर्, कटवािरया सराय नई िद ली - 110016 1 Government of India .
. 2 Northern Regional Power Committee 18-A, Shaheed Jeet Singh Marg, Katwaria Sarai, New Delhi-110016
उ. के्ष. िव. स./अधीक्षण अिभयंता (प्रचालन)/insulators/2009-11 िदनांक 8.03.2010
No. NRPC/SE(O)/Insulators/2009-10/ Dated: 8.03 2010 To
・ CMD, POWERGRID, Gurgaon,
・ CMD, DTL, New Delhi Fax No 011 23234640
・ CED, North Central Railway, Allahabad, 0532-2223211, 2230204
・ Director (Electrical), Railway Board, New Delhi, 011- 23387045,
・ MD, HVPNL, Panchkula Fax No 0172-2560640
・ CMD, RRPVNL, Jaipur Fax No 0141- 2740168
・ MD, UPPTCL, Lucknow Fax No 0522- 2287880/ED UPPTCL, Lucknow
・ Chairman, BBMB, Chandigarh, Fax No 0172- 2549186, 2652820
・ Chief Engineer (SO&C), PSEB, Ablowal, Patiala
・ ED & CEO, Powerlinks Transmission Limited, New Delhi, Fax-01166306375
・ GM (O&M), POWERGRID, NR-I/ NR-II
・ GM (OS), NTPC, NCR, Noida; AGM (OS), NTPC NR, Lucknow, Subject: Minutes of meeting on replacement and cleaning of insulators in NR Sir, A meeting was held on 05-02-2010 with the constituents to review the progress of cleaning and replacement of porcelain insulators by polymer/antifog insulators in high pollution areas of Northern Region. Minutes of the meeting are available on website of NRPC (www.nrpc.gov.in).
Yours faithfully
SE (Operations)
![Page 349: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/349.jpg)
Minutes of the meeting taken by Member Secretary, NRPC on 5Th Feb, 2010 regarding cleaning/ replacement of porcelain insulators by polymer/antifog insulators of transmission lines List of participants is enclosed at Annexure-I. WELCOME: MS, NRPC welcomed the participants in the meeting to review the progress of replacement of porcelain insulators by polymer/antifog in the NCR and cleaning of insulators in view of prevailing fog and pollution in the northern region. He stated that there was a need for regular cleaning of insulators even though the fog related impact on the Northern Region is almost over. He emphasized that constituents might identify the new lines on which tripping and auto-reclosure were observed and should replace the insulators on these lines. He requested all the utilities to update the current status and schedule of completion for the remaining work. PUNJAB PSEB stated that the deposition on the insulators was such that they could not be removed by ordinary soap solution. So they had to apply mild HCL on the surface to clean the layers of pollution deposits on the insulators. PSEB opined that acid cleaning would deteriorate the life of the insulators. He stated that cases of insulator failure were observed at Sewa which was very near to National Fertilizers Limited (NFL). PSEB stated that they had replaced over 275 strings comprising 2484 discs of porcelain insulators by anti fog. MS, NRPC requested PSEB to submit details of locations and lines where replacement had been done to NRPC Secretariat through e-mail. The information provided by the PSEB had been included in the annexure-II.
Delhi
DTL stated that they had the received full lot of 8212 polymer strings required for replacement on their lines. They had replaced porcelain insulators at 75 towers and plan to replace at all locations on their 400 kV lines. DTL stated they want to provide the polymer insulators of 400 kV Mandola-Bawana line immediately but due to constraints of shutdown , the progress is slow.
![Page 350: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/350.jpg)
On hot-line washing of insulators, DTL intimated that they had employed two gangs for this purpose and had completed the work on 21st Jan, 2010. They would also repeat cleaning of critical locations after one week. DTL was advised to continue repeat cleaning till 15th March 2010 to avoid any fog related tripping. MS, NRPC requested DTL to submit details of replacement and cleaning as per the required format to DTL by NRPC. The information received is placed at Annexure- III.
Rajasthan
RVPNL had submitted that they had completed the replacement or insulators on 220 kV BTPS-Alwar line and had replaced 408 nos. (at136 locations) insulators with polymer insulators with polymer and 174 nos. (at 58 locations) by anti-fog insulators.
Haryana HVPNL stated that they had completed Phase I of replacement. Phase -II would be completed by June 2010. In Phase I of critical lines emanating from PTPS stage I and Bahadurgarh (POWERGRID) had been completed. The detail is enclosed at Annex. IV
BBMB
BBMB had submitted that they had initiated proposal to procure polymer insulator through POWERGRID and a purchase order has been issued on dated 2nd Feb.2010. The status submitted by BBMB is placed at Annexure- V.
POWERGRID
The status submitted by POWERGRID NR I/II is enclosed at Annex VI. POWERGRID NR I stated that in 400 kV Malerkotla line they had completed replacement in their section and no tripping was reported in the replaced stretches. The remaining portions of the line under NR-II would be completed by 20th Feb.2010. Regarding tripping of HVDC Rihand –Dadri bipolar on 2nd jan 10 POWERGRID intimated that the line so running on RVU mode due to fog and was improperly taken on normal from Dadri end which caused tripping.
![Page 351: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/351.jpg)
POWERGRID also clarified that tripping of 400 kV Dadri-Panipat line during foggy conditions was not because of line fault but because of fault in wave trap at Dadri end. MS, NRPC enquired about tripping of 400 kV Bhiwadi-Bassi line. POWERGRID intimated the line has tripped due to failure of tension insulator, as these insulators were of conventional type. MS, NRPC advised POWERGRID to replace the tension insulators also.
Hot line washing of insulator by helicopter
POWERGRID stated that the schedule was given for 3-3 ½ hours daily due to inclement whether conditions. The cleaning would continue till the expiry of 350 hours of flying of helicopter. (Annexure-VII)
MS. NRPC requested that phase wise target of schedule for lines in Allahabad, Kanpur, Panki, Muradnagar areas where high pollution had been reported and lines tripped during foggy weather. POWERGRID may identify additional lines locations and polymer requirements and procurement schedule for the same so that work is completed before onset of next winter.
MS, NRPC advised of the constituents to undertake analysis of pollutant in their respective jurisdiction as done by the POWERGRID.
He also emphasized that notified of shifting of brick kilns should also be issued by all other constituents as notified by Haryana. On forecasting mechanism MS, NRPC stated that SLDC may assure availability of competent and experienced staff during foggy conditions. He requested all the constituents to submit the information in the proper format available at NRPC website.
Meeting ended with thanks to the chair.
![Page 352: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/352.jpg)
List of participants during the meeting of polymer issue in NR on 5th Feb
2010 In chair Shri A K Agarwal, MS, NRPC
S.No Name Sh/SS
Designation Organization
Tel no./mobile no.
E mail id
1 AK Agarwal MS NRPC 26868681 [email protected] 2 KK Arya SE NRPC 26868681 [email protected] 3 Vikram Singh EE NRPC 9868893051 [email protected] 4 RK Singh Manager POWER
GRID NR
9873918545
5 SK Sharma DGM(OEM) DTL 9540040640 [email protected] 6 PP Singh MGR Lines DTL 9540046643 7 Sanjay Arora Power
Controller HVPN 9356273746 [email protected]
8 NK Sharma SE PSEB 9646118204 [email protected] Alok Kumar Dy. Manager NRLDC,
POWERGRID
09999039321 [email protected]
![Page 353: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/353.jpg)
Summary of Status of Replacement of Porcelain Insulators with Polymer/Antifog Insulators (As reported by constituents) as on 08.03.10 Name of the constituent
Voltage level Lines where insulators to be replaced Type of insulator (polymer/antifog)
Remarks
Total Insulator Strings (Nos)
Insulator Strings replaced (Nos)
Scheduled completion date for replacement of balance insulators $
400kV 7433 1296 NA Polymer Work in progress. Whole lot has been procured (8212) through POWERGRID. Status as on 5.2.10
DTL
220kV 8231 nil NA Antifog Taking action for procurement of Antifog insulators
HVPNL 220kV 11834 5751 March/April 2010. Antifog Work of Phase –I (PTPS stage-I and Bahadurgarh area) completed . Phase –II would be complted by June 2010
UPPTCL 400kV 1000 684 NA Polymer
220kV 2241 998 NA Polymer
1682 insulator strings replaced out of 2000 received so far,
PGCIL NR-I 400kV 31392
22941 Polymer After receipt of insulators
220kV 831 - Polymer After receipt of insulators HVDC
Rihand-Dadri 4608
3136
_ Polymer Insulators not available. Would be completed in 3rd phase, i.e. in Feb,/March 2010.
HVDC Balia-Bhiwadi
2080 400 -
Polymer HVDC Balia-Bhiwadi line would be provided with polymer insulators. Pole-I expected in 31st March, 2010. Replacement work shall be taken up in third phase commencing from Feb/ Mar, 2010.
400kV 19620 7532 - Polymer PGCIL NR-II 220kV 380 380 Completed Polymer
Procurement order for insulator strings required for phase-II (12,615 No.) and phase-III (10,000 No.) had been placed. Delivery of material expected in Dec/Jan’2010. 400 kV Moga-Bhiwadi line (expected in Dec 2009) would also be provided with polymer insulators.
![Page 354: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/354.jpg)
400kV 2016 June, 2010 Polymer 220kV 3599 06/10 Polymer
BBMB has initiated proposal for procurement of 400 kV polymer insulators through POWERGRID.
400kV 264 264 Completed Antifog
BBMB
220kV 3392 3176 04/2010 Antifog work would be complted by April 10; majority of work pending due to crops in the fields.
POWERLINKS 400kV 1956 1956 04/09 Polymer Work Completed PSEB 220 & 132 kV 275 275 completed Antifog More lines / strenches will be identified for
further replacement RVPNL 220 kV 136+58 408+174 Completed Polymer/antifog 408 strings of polymer and 174 antifog strings
Note: $ The original schedule was 31-03-2009 as per decision of 10th NRPC meeting held on 30-09-2008.
![Page 355: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/355.jpg)
Annexure –VI A
Status of erection of polymer insulators POWERGRID NR-I as on 8-3-10
Sl. No Name of line
Total Locations
(No)
Total Polymer Strings
Required (No)
Location Replaced(No)
Polymer Insulator strings
replaced
% Complete
Schedule for replacement of balance
In Phase- I Date of commencement
Date of completion
1 400 KV Meerut-Mandola-I 166 1284 166 1284 2 400 KV Meerut-Mandola-II 166 1284 166 1284 3 400 KV Dadri Mandola-I 124 1338 124 1338 4 400 KV Dadri Mandola-II 124 1338 124 1338 5 400 KV Dadri-Panipat-I 301 1515 301 1515 6 400 KV Dadri-Panipat-II 328 1731 328 1731 7 400 KV Dadri-M'Kotla 282 1374 282 1374 8 400 KV Dadri-G. NOIDA 37 429 37 429
9 400 KV G.NOIDA-Ballabgarh 107.5 1270 107.5 1270
10 400 KV Dadri - Maharanibagh 67.5 730 67.5 730
11 400 KV Maharanibagh-Ballabgarh 89 1122 80 1122
100%
12 400 KV S/C Hissar-Bhiwadi (up to LILO point) 360 2556 305 1920
85% complete Mar-10 Mar-10
![Page 356: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/356.jpg)
13 400 KV Mainpuri-Ballabgarh-I 354 1377 283 1146
83% complete Mar-10 Mar-10
14 400 KV Mainpuri-Ballabgarh-II 362 1473 279 1229
83% complete Mar-10 Mar-10
15 400 KV S/C Kanpur-Ballabgarh 579 2259 282 1221
55% complete Mar-10 Mar-10
16 + 500 KV HVDC Rh-Dadri P-I
885 2304 588 1568
68% complete Mar-10 Mar-10
17 + 500 KV HVDC Rh-Dadri P-II
885 2304 610 1568
68% complete Mar-10 Mar-10
In Phase- II
1 400 KV S/C Ballabgarh-Bhiwadi 132 508 132 508
100%
2 400 KV S/C Agra-Ballabgarh 283 1348 283 1348
100%
3 400 KV Dadri-Muradnagar 90 548 79.5 441
80% complete Mar-10 Mar-10
4 400 KV S/C Bhiwadi-Bassi 353 1374 205 678 50% complete Mar-10 Mar-10
5 400 KV M'nagar-Muradabad 470 1743 174 717
41 % complete
Mar-10 Mar-10
6 400 KV D/C Meerut-Muzaffarnagar 106 534 0 0
NIL Mar-10 Mar-10
![Page 357: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/357.jpg)
7 220 KV FGPP-Palla I&II 64 480 0 0 NIL Mar-10 Mar-10
8 220 KV FGPP-Samaypur I & II 54 351 0 0
NIL Mar-10 Mar-10
In Phase-III
1 400 KV S/C Bhiwadi -Bassi-II (LILO of Old Bassi-Hissar) 35 240 35 240
100 % Complete
2 400 KV Agra-Bhiwadi-I 198 702 0 0 NIL 3 400 KV Agra-Bhiwadi-II 205 786 0 0 NIL
4 LILO of 400 KV Bly-Mandola at Meerut 22 102 0 0
NIL
5 LILO of 400 KV Ballabgarh-Bhiwadi at G'Gaon 175 678 0 0
NIL
6 LILO of 400 KV Lko-Mbd at Bly. 22 84 0 0
NIL
7 400 KV Bly-Mbd 108 756 0 0 NIL
Shall be taken up after receiving Insulators under
PCK-C
8 + 500 KV HVDC Ballia-Bhiwadi Pole-I
400 1040 70 200
20% complete ( Under
progress)
9 + 500 KV HVDC Ballia-Bhiwadi Pole-II
400 1040 70 200
20% complete ( Under
progress)
Other than Phase
1 400 KV S/C Allahabad-Kanpur-I 13 39 13 39
100 % Complete
![Page 358: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/358.jpg)
2 400 KV S/C Allahabad-Kanpur-II 13 39 13 39
100 % Complete
TOTAL FOR AC LINES: 5790 31392 3867 22941 TOTAL FOR DC LINES 2570 6688 1338 3536
TOTAL FOR AC & DC LINES 8360 38080 5205 26477
![Page 359: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/359.jpg)
Annexure –VI B
Status of Replacement of porcelain insulators with polymer/antifog insulators As on 08.03.2010
POWERGRID NR-II NR-II Line Length Length where insulators to be replaced S.No. Name of line
Kms Total Insulator
Strings (No.s)
Kms Total Insulator
Strings (No.s)
Insulator Strings
replaced (No.s)
Status Cleaning Status for Balance Strings
Phase-I ( To be replaced Complete)
Completed Balance
1 400 KV Bawana- Bahadurgarh Line
48.94 500 48.94 500 500 Work completed
0
2 220 KV Hisar- Hisar Link Line Ckt- I
13.77 193 13.77 193 193 Work completed
0
3 220 KV Hisar- Hisar Link Line Ckt- II
13.77 187 13.77 187 187 Work completed
0
4 400 KV Hisar- Bhiwani Line
35.33 387 35.33 387 387 Work completed
0
5 400 KV Bahadurgarh- Bhiwani line
84.37 839 84.37 839 839 Work completed
0
6 400 KV Hisar- Bawana line
131.85 1295 131.85 1295 1295 Work completed
0
7 400 KV Hisar- Fatehabad Line
83.60 828 84.00 828 828 Work completed
0
Phase-I (Partial Replacement )
8 400 KV Dadri- 193.48 1932 24.50 716 716 Work 0
![Page 360: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/360.jpg)
Malerkotla Line completed
9 400 KV Moga- Fatehabad Line
183.99 1755 30.00 615 615 Work completed
0
10 400 KV Moga- Hisar Line
209.17 1971 36.00 655 655 Work completed
0
11 400 KV Abdullapur- Bawana Line Ckt-I
167.00 1553 22.50 636 636 Work completed
0
12 400 KV Abdullapur- Bawana Line Ckt-II
167.00 1553 22.50 635 635 Work completed
0
Phase-II (Partial Replacement )
8a 400 KV Dadri- Malerkotla Line
24.50 264 20 244 Work Completed
9a 400 KV Moga- Fatehabad Line
30.00 528 0 528 Work Completed
10a 400 KV Moga- Hisar Line
36.00 761 0 761 Work Completed
11a 400 KV Abdullapur- Bawana Line Ckt-I
22.50 202 0 202 Work Completed
12a 400 KV Abdullapur- Bawana Line Ckt-II
22.50 202 0 202 Work Completed
Phase-II ( To be replaced Complete)
13 400 KV Hisar- Patiala Line
128.17 1710 64.09 650 13 637 Work Completed
14 400 KV Hisar- Kaithal Line
113.12 1032 56.56 480 13 467 Work Completed
15 400 KV Kaithal- Nalagarh line
199.85 2052 99.92 880 0 880
16 400 KV Nalagarh- Patiala Line
93.39 1083 46.70 460 0 460
17 400 KV Jallandhar- Ludhiana Line
84.77 939 39.36 436 0 436
![Page 361: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/361.jpg)
18 400 KV Ludhiana- Malerkotla Line
35.74 387 20.31 220 0 220
19 400 KV Nathpa Jhakri- Abdullapur Line Ckt- I
180.00 2421 25.72 346 0 346
20 400 KV Nathpa Jhakri- Abdullapur Line Ckt-II
180.00 2421 25.80 347 0 347
Tr. Lines under O&M 2347.28 25037.00 1061.48 13262 7532 0 5730
Phase-III ( To be replaced Complete)
21 400 KV Moga - Bhiwadi Line Ckt- I
350.00 3369 350.00 3369 0 3369
22 400 KV Moga - Bhiwadi Line Ckt- II
350.00 3369 350.00 3369 0 3369
Total 3047.28 31775 1761.48 20000 7532 0 12468
Polymer Replacement in lines under O&M
56.79%
![Page 362: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/362.jpg)
Status & Tentative Schedule for cleaning of insulators by Helicopter as on 07.02.10by
Annexure -VII
Under Kanpur jurisdiction.
LOCATION NO
SL.No.
NAME OF LINE FROM TO
NO OF TOWERS
Tentative Schedule
1 400 kV S/C Allahabad-Kanpur-I 1098 1188 91 Complete 2 400 kV S/C Allahabad-Kanpur-II 1044 1129 86 Complete 3 400 kV S/C Singrauli-Kanpur 1068 1158 91 Complete 4 400 kV S/C Kanpur-Agra 1 99 99 Complete 5 400 kV S/C Kanpur-Ballabgarh 1 83 83 Complete 6 400 kV S/C Kanpur-Panki-I 1 21 21 Complete 7 400 kV S/C Kanpur-Panki-II 1 18 18 Complete
8 400 kV D/C Kanpur-Auraiya 122 212 91
07.02.10 – 11.02.10
9 400 kV D/C Allahabad-Mainpuri 526 690 165
12.02.10-17.02.10 & 02.03.10 – 10.03.10
TOTAL 403
Helicopter will be under maintenance from 18.02.10 to 21.02.10 Under Mainpuri jurisdiction.
1 500 kV HVDC Rihand-Dadri , Pole-I & II
1701 1800 100
12.03.10 – 18.03.10
TOTAL 100
Under Allahabad jurisdiction.
1 500 kV HVDC Rihand-Dadri, Pole-I & II709 808 100
23.02.10 – 28.02.10
TOTAL 100
![Page 363: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/363.jpg)
Progress of replacement of Normal Disc Insulators by Polymer Strings- UP as on 5th Feb 2010 SI No. Name of Line Total
Received No. of String Changed(Nos.)
Remark
1 400kV Murad Nagar-Muzaffarnagar 144 126 2 400kV Murad Nagar-Panki Line 606 558 3 4
400kV Unnao-Agra 400kV Panki-Unnao
250
Total 1000 684 1 220kV Murad Nagar-Shamli 234 234 2 220kV Murad Nagar-Khurja 120 120 3 220kV Murad Nagar-Sikandrabad 102 102 4 220kV Interconnector No.2 24 24 5 220kV Sahibabad-Muradnagar 216 215 6 Modipuram-Mataur Ist Ckt 33 33 7 220kV NAPP-Khurja 69 69 8 220kV G.Noida-Noida IInd CkT 202 201 Total 1000 998 Grand Total 2000 1682
![Page 364: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/364.jpg)
Annexure -DTL Status of replacement of porcelain insulators with polymer/antifog insulators
(A) Polymer insulators as on 04.02.10 Name of the organization: Delhi Transco Limited
Line Code
Name of line,voltage,S/C or D/C Line Length Length where insulators to be replaced
%age-wise work completed in Kms
%age-wise work completed in Location Remarks
Kms No. of locations
Total Insulator Strings(Nos) Kms
No.of locations
Total Insulators Strings required (Nos)
No. of locations
Insulators Strings replaced(Nos)*
Schedule for replacement of balance
Start Date
End Date
1
400kV Bamnauli-Ballabhgarh D/C line 52.8 149 3488 52.8 149 3488 37 496 19.11109
work in progress 30% 25%
2
400kV Bawana-Bamnauli D/C Line 37 103 2049 37 103 2049 36 696 19.11.09
work in progress 35%
3
400kV Manduala-Bawana D/C Line 23.801 68 1896 23.801 68 1896 2 104 19.11.09
work in progress 3%
(B) Antifog insulators
Name of the organization: Delhi Transco Limited Status as on: 04.02.2010
![Page 365: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/365.jpg)
Line Code
Name of line,voltage,S/C or D/C Line Length Length where insulators to be replaced
%age-wise work completed in Kms
%age-wise work completed in Locations Remarks
Kms No. of locations
Total Insulator Strings(Nos) Kms
No.of locations
Total Insulators Strings required (Nos)
No. of locations
Insulators Strings replaced(Nos)*
Schedule for replacement of
balance
![Page 366: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/366.jpg)
Kms/TowersTotal Insulator Strings (No.s)
Kms/Towers
Total Insulator Strings (No.s)
Insulator Strings
replaced (No.s)
Schedule for replacement of
balanceStart Date End Date
1 220KV Sewah-PTPS Ckt-I 12 198 12 198 198 Completed
2 220KV Sewah-PTPS Ckt-II 12 198 12 198 198 Completed
3 220KV Sewah-PTPS Ckt-III 12.5 213 12.5 213 213 Completed
4 220KV Sewah-PTPS Ckt-IV 12.5 213 12.5 213 213 Completed
220KV PTPS-Sonepat Ckt-I 51.5 634 51.5 634 600 Completed
220KV PTPS-Sonepat Ckt-II 51.5 634 51.5 634 600 Completed
220KV Nuna-Majra-B/garh(400KV) Ckt-I 2.9 42 2.9 42 42 Completed
220KV Nuna-Majra-B/garh(400KV) Ckt-II 2.9 42 2.9 42 42 Completed
220KV Rohtak-B/garh Ckt-I 46 576 46 576 567
220KV Rohtak-B/garh Ckt-II 46 576 46 576 567
220KV Rohtak-PTPS Ckt-I 63 726 63 726 NIL
220KV Rohtak-PTPS Ckt-II 63 726 63 726 NIL
220KV Pali-Samaypur Ckt-I 10.5 342 10.5 342 63
220KV Pali-Samaypur Ckt-II 10.5 342 10.5 342 63
220KV Pali-Palla Ckt-I 13.9 414 13.9 414 72
220KV Pali-Palla Ckt-II 13.9 414 13.9 414 74
220KV Samaypur-Palwal Ckt-I 18.91 288 18.91 288 288 Completed
220KV Samaypur-Palwal Ckt-II 18.91 288 18.91 288 156
12 220KV Badshahpur-Rewari D/C line 70.3 1410 70.3 1410 100
13 220KV D/C Sec-52-A-Pali line 23/89 690 23/89 690 NIL
14 220KV Badshahpur-Samaypur D/C 24/86 642 24/86 642 309
15 220KV Badshahpur-Pali D/C 24/86 726 24/86 726 210
16 220KV S/C Badshahpur-IMT Manesar 11.772 240 11.772 240 24
17 220KV D/C Daultabad-IMT Manesar 17.996 594 17.996 594 486
18 220KV D/C Nuna-Majra-Daultabad 29.898 666 29.898 666 666 Completed
Total 11834 11834 5751
Remarks
Status of Replacement of porcelain insulators with polymer/antifog insulators Annexure-IV
Name of the organization: HVPN Status as on:03.03.10
Line Length
Priority No.
Name of lineLine
shutdown (no. of days)
Length where insulators to be replaced
Other maintenance
work
Insulator Strings replaced
per day per gang
10
6
5
11
7
8
9
![Page 367: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/367.jpg)
Annexure-III
(A) Annexure-V
Kms No. of locations
Total Insulator Strings (Nos)
Kms No. of locations Total Insulator Strings required
(Nos)
No of locations Insulator Strings replaced
(Nos)
Start Date End Date400KV S/C Dehar-
Panipat Line 261.8 772 4314 … 206 771 .. .. … .. .. ..
400KV S/C Dehar-Bhiwani Line 312.15 943 4791 .. 331 1245 .. .. … .. .. ..
220KV Rohtak Road-Narela ckt-I
22 81 426 … 81 426 .. .. … .. .. ..
220KV Rohtak Road-Narela ckt-II
22 81 426 .. 81 426 .. .. … .. .. ..
220KV Panipat-Narela ckt-I
56.8 197 811 .. 73 263 .. .. … .. .. ..
220KV Panipat-Narela ckt-II
56.8 197 811 .. 73 263 .. .. … .. .. ..
220KV Panipat-Narela ckt-III
58 171 588 .. 81 273 .. .. … .. .. ..
220KV Ballabhgarh-BTPS-I
24.73 90 321 24.73 90 321
220KV Ballabhgarh-BTPS-II
24.73 90 321 24.73 90 321
220KV Samaypur-Ch. Dadri S/C
118 400 1323 118 154 518
220KV Ballabhgarh-Ch. Dadri S/C
119.7 407 1378 119.7 169 569
220KV Ballabhgarh-Samaypur-I
4.23 20 84 4.23 20 84
220KV Ballabhgarh-Samaypur-II
4.23 20 84 4.23 20 84
220KV Ballabhgarh-Samaypur-III
5.5 23 87 5.5 15 51
Note:
%age-wise work completed in
Kms
Length where insulators to be replaced
The requirement of 400KV Polymer insulators has been submitted to Powergrid. The matter was discussed in 47th OCC meeting where Powergrid had generally agreed for procurment of the insulators.
P.O
. has
bee
n is
sued
vid
e P.
O. N
o. 1
655/
P&D
(TS)
/PN
T-42
5 da
ted
02.0
2.20
10 &
165
6/P&
D(T
S)/P
NT-
425
date
d 02
.02.
2010
.
Status of replacement of porcelain insulators with polymer/antifog insulators
Name of the organization: Bhakra Beas Management Board Status as on: 08.03.2010
Line Code
Name of line, voltage,S/C or D/C
Schedule for replacement of balance
%age-wise work completed in
Location
Polymer insulators
Line Length Remarks
![Page 368: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/368.jpg)
(B)
Kms No. of locations
Total Insulator Strings (Nos)
Kms No. of locations Total Insulator Strings required
(Nos)
No. of locations Insulator Strings replaced
(Nos)
Start Date End Date220KV Dhulkot-
Panipat ckt-I130 433 1669 .. 29 117 29 117 .. …
..100%
220KV Dhulkot-Panipat ckt-II
130 433 1669 .. 29 117 29 117 .. …..
100%
220KV S/C Panipat-Ch. Dadri Line
115 342 1173 .. 21 81 21 81 .. ..
..
100%
220KV S/C Kurukshetra-Panipat Line
77.08 233 786 .. 28 105 28 105..
100%
220KV BUSES at 400KV S/S Panipat
… … 240 … 240 … 240..
100%
220KV Bhakra-Jamalpur ckt -I
86.4 1-276 1034 11 32 204 31 198 96% 97%
220KV Bhakra-Jamalpur ckt - II
86.4 1-276 1034 11 32 204 31 198 96% 97%
220KV Jamalpur-Jallandhar ckt-I
64 1-214 960 9 27 87 27 87 .. … 100% 100%
220KV Jamalpur-Jallandhar ckt- II
64 1-214 960 9 27 87 27 87 .. .. 100% 100%
220KV Pong-Jalandhar ckt- I
97.5 1-328 1204 4 12 36 12 36 100% 100%
220KV Pong-Jalandhar ckt- II
97.5 1-328 1204 4 12 36 12 36 100% 100%
220KV Jamalpur-Sangrur ckt- I
78 1-268 970 15 40 313 39 307 98% 98%
220KV Jamalpur-Sangrur ckt- II
78 1-268 970 15 40 313 39 307 98% 98%
220KV Hisar-Sangrur-I
139 477 1431 139 62 186 62 186 100% 100% Standing of water & crops in fields
220KV Hisar-Sangrur-II
139 477 1431 139 62 186 62 186 100% 100%
220KV Bhiwani-Hisar-I
57.95 199 654 30 102 345 85 255 21.04.2010 21.04.2010 74% 83% Standing of water & crops in fields
220KV Bhiwani-Hisar-II
57.95 199 654 30 102 345 84 252 24.04.2010 24.04.2010 73% 82%
220KV Bhiwani-Ch. Dadri-I
36.45 124 420 7.6 26 81 25 75 09.03.2010 09.03.2010 96% 96% Standing of water & crops in fields
220KV Bhiwani-Ch. Dadri-II
36.45 124 420 7.6 26 81 26 78 11.03.2010 11.03.2010 98% 98% Standing of water & crops in fields
220KV Bhiwani-Ch. Dadri-III
34.7 127 444 9.5 35 114 35 114 100% 100%
220KV Bhiwani-Ch. Dadri-IV
34.7 127 444 9.5 35 114 35 114 100% 100%
Line Length Length where insulators to be replaced
Antifog insulatorsName of the organization: Bhakra Beas Management BoardLine Code
Name of line, voltage,S/C or D/C Schedule for replacement of
balance
Disc of T. No. 276 could not be replaced due to 120KN 16/32 mm antifog disc received from Bhiwani are poor quality
Detail of length in Kms can not be worked out due to different locations.
Disc of T. No. 89 could not be replaced due to 120KN 16/32 mm antifog disc received from Bhiwani are poor quality
Remarks%age-wise work completed in
Location
%age-wise work completed in
Kms
Status as on: 08.03.2010
![Page 369: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/369.jpg)
![Page 370: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/370.jpg)
![Page 371: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/371.jpg)
REPORT ON
POLLUTION LEVEL MEASUREMENTS AT DIFFERENT LOCATIONS OF NORTHREN REGION. OF
MIs POWER GRiD CORPORATION OF INDIA LIMITED,
..... -' .........
. HIGH VOLTAGE DMSION CENTRAL POWER RESEARCH INSTITUTE . .
P.B.·No 8066, Prof. Sir CV RAMAN. A VENUE BANGALORE- 560080 .- ..... -""".-" ..
)
![Page 372: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/372.jpg)
OBJECTIVE
CLIENT
STUDY CONDUCTED BY
REPORT PREPARED BY
MARCH 2008
REPORT
: To carry oui ESDD, NSDD and chemical analysis of the samples Collected from the polluted I.nsulators at various locations of ·PGCIL 400 kV transmission
: PGCIL, NEW DELHI
: Dr. N.Vasudev K. Badrinarayanan K. Suryanarayanan (MTD)
: . Dr. N.Vasudev
(P.v. Vasu~evan Nambudiri) JOINT DIRECTOR
IDGHVOLTAGE
HIGH VOLTAGE DIVISION CENTRAL POWER RESEARCH INSTITUTE P.B. No 8066, Prof. Sir CV RAMAN. AVENUE . . -',' BANGALORE- 560080
![Page 373: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/373.jpg)
n rna.sllfl"r
I ~~ , . POLLUTION LEVEL MEASUREMENTS AT DIFFERENT LOCA nONS OF
NORTHREN REGION 400 kV TRANSMISSION LINES OF MIS PGCIL, ~RI
INTRODUCTION
The pollution flashover poses serious threat to the reliability of the system wh~n the .
lines are closed after a pollution flashover. The flashover may ~epeat after some
delay causing the line outage for a prolonged duratio~. The line win have to be closed
· only. after the prevailing weather conditions are cleared. Therefor~. thereJi~bilityof · the syStem is·affected. ,~' _.,
· The polluted layer when moistened becomes conductive' and the leakage curre~t '. . ~ . . .
flowing on the insulator surface· increases gradu~lIy causing. dry band . In. praCtice. : .
the d~tribution of, s~rface 'dePosit' and the wetting of, the layer is n'ot uriJform~ thus ' .' '. . -. .
causi~ ~ series of wet and. dry bands'with most of the voltag~ applied acrosS the ~ry
·b~rnfwhich" r~olts in ,dry band, ar~ing (Scintillati~ils or ,particif arc or discharges),' · .".... ." . .
Howeve~. some of t~e some of tt'!e diScharges cah develop into, complete flashover·~f
the jnsula~or string .
. . The creepage len9th ()f the· insulator string" requi~ed is decided by, the, pollution' , . '
severity. The value of the maximum withstand salinity ,depends upon'the risk of
failure to be chosen and the.· maximum "site, pOllution '- severity. "Therefore.
, "determination of pollution severity at the site is ve,ryjmportantand,pre~ise·knowledge
of pollution severity at sites is necessary .
The general approach for the design of extemal insulation is as follows: , .
- .' Determination of the tYPe of pOllution for the site under' examination and
Choice ~!the artificial test l1)ethod suitable' for simulati~g this ,type ~f. , ,poIIutionin the la'bora.tory. . ..... : .•. :.
, 7' ....
)
I I
![Page 374: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/374.jpg)
CPR! Determination, on a statistical basis, of the pollution severity level of the
site in terms of the surface conductance of simple insulator ge6metry.
Determination of the corresponding pollution severity level of the site jn
terms of the severity parameter characterizing the chosen laboratory test
method.
- Choice of the insulator type and determination of the insulator set length
required by the above value of withstand severity.
OBJECTIVE OF THE STUDY
To carry out ESDD, NSDD "and chemical analysis ~f the samp~es colle:cted from 'the
polluted Insulators at various locations of PGCIL 400 kV tranSmission iines
METHOD OF MEASU,REMENTS
1
In the present case" In order to "assess the site $everitY. Brush" wash method of " " "
measu~ment "ha~ been, used" for the" site severity measurement at each lOcation. The
polluted water has to be collected from each" of the inSUlator from line end to ground end. "
This measurement gives the pattern of pollUtion adhering" to the insulator string. In the
present.'Cas~ only two samples of poliuted insulator in a string" has been!~: -,oil for " . -
measurement.
BRUSH WASH METHOD
Both top and bottom surface contaminants are collected, separately in a known volume of
dematerialized water. The difference in the conductivity is measured and the salinity of
the water is estima~ed. The saft deposit density is thencalcuiated using the procedure"
below:
![Page 375: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/375.jpg)
a) Conductivity of de-mineralized water = (11
·RI b) Conductivity of the water after dissolving the collected pollution =CJ2
c) Temperature of water = 9. 0 C ;[CJ20= CJa K where K is the correction
required.}
d) Salinity ( Sa ) =[ 5.7'" «('12 - ('11 J ]1.03 at 20 degree centigrade
e) ESDD.( Equivalent Salt deposit Density) = Sa'" V fA
Where V is the volume of water used
A is the area of the insulator from which the pollutant is collected.
This methOd of measurement will give an idea of ESDD on top and bottom surfaces of . .
the insulators and along the string length. ThismettJod' gives an.. id~aof p{)IJutant
accumulation up 0 the period of measureJ1lent. The pollution measurements were carried
o~t . by PGC.ll an~. the polluted wate~ samples were sent to CPR I, Bangalore for· ESDi:>~ NSD~ . and chemical analysis': Only few sampleS of polh.Jt~ water was an~IysP.d" for
, ".. .~. . . . . . . .
chemical CompOsiti9n.
I. RESULTS AND ANALYSIS
)oIlUtionseveritymeasurement~ were' carried ollf on insulator $tfings at·· different . .: . . . . .
)cations of 400 kV transmissionliries wtierestrings were posing probiems·. du~ . to
ollution fl~shover. Tables~ 1 . sh~wthe results of·ttle brush wash method ·~tdifferent Ications. In . general, the results shQw that the bottom surface ESDD "of the: s!ring: hC!s
gheracctimulation of pollution compared to ·top surface. The aver~ge ESDD· of the . .". . . " .
ring is compared with the pollution level$ which are specified inlEC ~15. Generally the· . .
.lIution levels are in light ~nd medium zones. Table 2 and 3 shows the NSDD and . ". .:
emical analysis of the pollutant. It is observed from.· the chemical a·nalys·is· that the . . .'
lIutant contains predominant ferrous contents. Contaminations of a.lkalis were also
!sent pred~inantly
..... ,," ". -... . "~"'" . '
)
;i
![Page 376: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/376.jpg)
l all
CPRI Table I Results of ESOO' measurements carried out at various locations.
SI.No Name of the line Location ESDD (mg/cm2) Average Pollution Zone No pollution (as per the
measurement) Top Bolt
.. Surface surface (mg/cm2) .
1 400kV-AC- 151 0.104 0.1915 0.1477 Medium Mandolla- Meerut Cktl
3 .. -
2 400kV·AC- 151 0;0511 0.0815 0.0663 Ught MandeJIa- Meerut Ckt II 2:
3 DADRI-MANDOLA 108· 0.0388 0.0815 0.0601 light CKT-1
2 .. DADRi-MANDOLA 0.079
., 4 1P8 0,(1603 0.0978 .. light I
CKT-I
1
5 ·OAORI-MANDOLA 108 0.022 0.101 0.0615 light CKT-II . . .
1 :...:.... -6 DADRI-MANDOLA . 108 0.068 0.123 0.09 light
CKT-IJ _. 2 DAORI- PANIPATH
7' . CKT-2" 300-A 0.02 0.107 0.0635 Ught -1
8 OADRl- P[ANIPATH CKT-2 300-A 0.0274 0.132 0.0795 Ught
2 . -
9 BAllABGARH- . MAINPURI CKT-1 623 0.0195 0.0425 0.031 light 3
. - -
..
![Page 377: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/377.jpg)
~~-, lq i)
~ ~ 1\} BAllABGARH- ! I MAINPURI CKT-1 623 0_0145 0.030 0_022 light
/ 'l-)
-JR ~ 1 )
11 DADRI-MANDOLA CKT-JI 113 0,0522 0.1010 0.077 light
2 12 DADRI-MANDOLA
" CKT-JI 113 0.0522 0.127 0.0896 light
2 13 DADRJ-PANIPATH
. CKT1 98 0.058 0.236 0.147 Medium
2 14 DADRJ- PANJPATH
CKT1 98 0.04 0.369 0.2045 Medium
1
![Page 378: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/378.jpg)
CPRl Table 2
Amount of Non-Soluble Deposits in Waste Water Samples.
CPRI location Non-Soluble -NSDD Volume of Code Oepos.its (mg) mglcm2- polluted No. _ Water (ml) HV-14 Outer Mandolla Meerut 350.00 0.555 377 CKT-1 Loc 151 HV-15 -Inner Mandolla Meerut
1330.00 1.357 392 CKT-1 Loe 151
HV-16 Outer Dadri-panipath Ckt2 280.0()- :.- 0.411 391 lOC-#300A
HV-17 Inner Dadri- panipath .
Ckt2 11000.00 0.714 382 --lOC#300A
HV-18 Outer BalJabgarh -_ Mainpuri Ckt 1 LOC # 230.00 0.303 436 623
.-
HV-19 - Inner .8allabgarh -Mainpu'ri.Ckt 1 . lOC # 520.00 0.39 422 .
623 \ . HV-20 Outer Dadri-- Mandolla 260.00 0.356 .396 . Ckt 2l0C_# 113 HV-21 Inner Dadri- Mandolla 440.00 0.293 400 . . Ckt 2 lOC #113
I HV-22 Outer Dadri- Panipath 180;00 0.32 348 Ckt1 LOC # 98 --HV-23 Inner Dadri- Panipath 660.00- 0.6 392 Ckt 1 LOC#98 HV-24 Outer Dadri- Mandolla 260.00 0.356 420 Ckt 1 lOC # 108 HV-24 Inner -Dadri- Mandolla
700.00 0.466 390 Ckt 1 LOCI 108
HV-25 Outer Dadri- Mandolla 1280.00 1.75 392 Ckt 2 lOC # 108
HV-26 Inner Dadri- Mandolla 1360.00 0.906 -392 Ckt 2LOC # 108
1-
![Page 379: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/379.jpg)
Table 3
PRJ Chemical composition Analysis of. Non-Soluble Deposits in Polluted Water : Samples~
CPRI location Resulfs in ('Yo) Code, .
No. Na20 A12o, Si<h so, K~ CaO Ti02
HV-14 ,Outer Mandolla Me~rut 2.30 0 28.56 0.96 17.95 14.27 2.44
'CKT-1 Loe 151 ' , A
HV-15, Inner Mandolla Meerut ,1.75 0 26.77 0.11 17.25 13.25 2.54
CKT-1 Loe 151 HV-16 Outer Dadri- panipath Ckt 2.25 2.14 45.15 0.98 16.16 9.40 2.26
t , ,tOC#300A " .J"
HV-17 Inner Dadri- panipath Ckt 1.50 - 24.82 0.27 17.47 18.45 2.96
2 LOC#30PA
HV~18 Outer' Ballabgarh - 2.41 - 47.36 0.91 18.35 15.23 1.43
Mainpuri Ckt 1 LOC # 623'· '
Hv-19 : ,~rier Ballabgarh- 1:03 3.64 33.05 0.43 11.60 10.03 1:6.05 -.
" . Ma~npuri.: Gkt.1 LOC# " . , .. 62~ -HV-20' Outer Dadri- Mandolla ' 4.15 - 38.46 0.66 25.05 1~.48 1.94 ..
Ckt2 LOC # f13 HV-21 ' Inner Dadri- Mandolla Ckt ' 2,.80 ~ 60.16 0.73 11.73 7.42 0.64
2'lOC'#:113 HV-22 Outer Dad(i:" panipath Ckt 2.82 6.68 73.01 0.05 14.23 3.19 '0
1 LOC#98 . -
HV-23 Inner Dadri- Panipath Ckt 1.57 2.43 31.35 0.84 15.76 9.98 2.56
1 LOC#98 -
HV-24 Outer Dadri- Mandolla 1.89 0 26.10 0.45 20.33 11.99 2.95
Ckt 1 Lpe # 108 " HV-24 Inner Dadri- Mandolla Ckt 1.83 3.55 70.80 0.45 ,8;55 5.31 0.71
1 LOC # 108 HV-25 Outer Dadri- Mandolla 1'.69 1.79 37.39 o.n 14.25 9.52 2.30
Ckt 2 LOC # 108 HV-26 Inner Dadri- Mandolla Ckt ' 1.23 3.40 33.01 0.43 14.59 11.64 2.47
2 LOC#.108'
, ' ,
Me~Od: AnalysiS by Energy DiSpersive X-Ray Fluorescence Spectrometer (Minipal 2, . PANalyticat) . " .',' . :, ..,' , . .,.' ,
-r=e;o;-33.50
38.32
22.10.
34.52
14.30
24.16 .
15.23,
16.t»2
-
35.51
36.28
8.78
32.32
33.33
.::,
![Page 380: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/380.jpg)
q ,".
I
CPRl CONCLUSIONS ,
Pollution level measurements Were carried out on the samples of polluted water
which were Collected from sites from various locations. ESDDI NSDD and
Chemical analysis .were carried out on samples of po"utedwater. . .
The level of pollution at top surface of insulator at a" locations measured was
found to be ·Iight. This may be due to washing or cleaning of insulators ..
The bottom surface pollution at most· of the locations found to be in medium
range.
- The chemiCaI.analysis of the pollutant showed more of silica· and iron contents-:-Contaminations of alkalis were also present predominantly.
![Page 381: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/381.jpg)
."
~ liuzn fRef, Nwnber
A...- ~~ v -Po,. ~~4 -=~l~=-qlcl'l 10 .... 5 Cbh!ql;!~rat 3Jllli $iSlil iCt1iJ12s ------(lW«f ffiCffi <liT \RfIl) -= i POWER GRID CORPORATION OF INDIA UMITED -=l§~
(A Government of India Enterprise) Qlct"'lPcug
~ ~ : "fTlc;lfil4)·' ~1c fi. 2, ~ 29, :r-sTT1CI 122 001, ~ lllR : 2571700 - 719 ~ : 2571760,2571761 em '~'
Corporate office: "Saudamini" Plot No.2, Sector-29, Gurgaon-122 001 Haryana Tel. : 2571700 - 719, Fax: 2571760, 2571761 Gram: 'NATGRID'
C/OSfTLlI nsulatorl Date: 01-05-2009
To,
Director (Tr ?s~isSiOn) Ministry 0 ower Shram akti Bhawan, Rafi Marg New elhi
Sub: Pollution measurement, chemical analysis and Po.lYcyclic Aromatic Hydrocarbons analysis.of pollutants accumulated on insulators
Kind Attn: Shri Lokesh Chandra
Dear Sir,
1.0 PI. refer to DO No. 3/9/2008-Trans dated 24-12-2008 from Add!. Secretary, MOP regarding observations on pollution measurement and chemical analysis of pollutants on insulators. As desired, insulators were removed from the tripped lines and sent to following laboratories during last week of December'08 for carrying out pollution test and chemical analysis including presence of Hydrocarbons:
Ka. Indian Institute of Technology, New Delhi
VB. Shrlram institute for Industrial Research, New Delhi
V'Z Central Power Research Institute, Banglore
.. '.
2.0 liT, Delhi, which had accepted the insulator samples on 29th December'08, expressed their inability on 15-01-2009 stating that the required tests were not possible to be performed in their laboratory.
It may please be noted that manual cleaning of insulators was completed progressively by mid Dec'08 by POWERGRID as part of pre-winter maintenance activity prior to removal of insulators for testing in laboratory .
.. After refusaJ by liT, Delhi on 15-01-2009, matter was taken up with Indian Institute of Toxicology Research, Lucknow (IITR, Lucknow) for carrying out chemical, analysis of pollutants including analysis of Polycyclic Aromatic Hydrocarbons. Insulators were sent to them also during 3rd week of
~~ ~: <f)-9, ~ ~h~k;I{~I'i<:1 ~, (PcqlRIlI XHTIl, ~ fu~-110016 'I,~1fl1l". 26560121 Q;CR1: 011-26560039\1R '~' Registered Office: 8-9, Qutab Ins!i1utional Area, Katwaria Sarai, New Delti'i-l10016 Tel. . 26560121 Fax: 011-26560039 Gram: 'NATGRIO'
~ ~ '<I~~d i[ ~ ~ Save Energy fOl' Benefit of Self and Nation
![Page 382: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/382.jpg)
January'09. While accepting the samples, lab has indicated that direct exposure of pollutants to sun may affect the test results.
Additionally, Insulator samples were collected from UP Transco also and sent to IITR, Lucknow for analysis, speCially w.r.t. presence of hydrocarbons.
3.0 Test results of insulator samples had been received from all the three laboratories during February and March'09 and highlights of test results for the tests conducted at these labs is are under:
a. Indian Institute of Toxicology Research, Lucknow for analysis of Polynuclear Araromatic Hydrocarbons (PAHs):
SI. Name of line Total PAH Significant PAH No. concentration concentration
(~gl Litre) 1 400 kV Hisar-Bawana line 1962.46 Napthalene,
Acena~thylene 2 400 kV Oadri-Panipat-II 971.93 Fluorene+ ...
Acenaphthelene 3 400 kV Oadri-Panipat-I 805.23 Acenapthylene 4 400 kV Oadri-Mandola 126.97 Fluorene+
Acenaphthelene 5 400 kV Kanpur-Singrauli 233.40 Acenapthylene 6 400 kV Allahabad-Mainpuri 195.96 Fluorene+
Acenaphthelene
V b. Shriram institute for Industrial Research, New Delhi for chemical analysis
an.d PAH analysis: . Name of linel 400 kV Oadri-Mandola-Ckt-II 400 kV Bawana- Hisar line Chemical lron- 45665 ppm lron- 32133 ppm Composition -or. r-.Aluminium- 36401 ppm
.. Aluminium-19048 ppm
Calcium- 20967 ppm Calcium- 14065 ppm .. . , . Magnesium- 15877 ppm Magnesium- 9307 ppm Zinc- 6524 ppm Zinc- 7604 ppm Potassium- 9613 ppm Silica 10.2% by mass Silica- 20.3% by mass
Hydro Carbon Traces of Polynuclear Traces of Polynuclear Analysis aromatic Hydrocarbons found aromatictiydrocarbons found
,
/
..... '.
![Page 383: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/383.jpg)
/ c. CPRI, Bangalore for pollution test, chemical analysis and hydrocarbons
analysis:
Name of line/ 400 kV Dadri-Mandola- 400 kV Bawana- Hisar Ckt-II line
Pollution Level Light (0.053 mgt cmL) Medium (0.147 mgt cmL
)
Chemical Pollutants showed more of Pollutants showed more Composition Silica and Ferrous content of Silica and Ferrous
AI20 3 - 18.04% content Si02 - 37.02% AIz03 - 19.06% Fe203 - 22.44% Si02 - 29.53% ZnO - 6.56% Fe203 - 24.29% CaO -6.51% Unburnt- 11 %
Hydro Carbon No hydrocarbon preserit no hydrocarbon present Analysis on the surface in freeform on the surface in freeform Recommendations The insulator strings Present insulator string
presently used are which is of standard standard type which is insulator may be changed suitable for light pollution to either antifog-- profile severity. Chice of insulator or polymeric insulators in the zone insulators at most mainly depends on the sensitive polluted zones. seasonal pollution level measurement.
V d. Indian Institute of Toxl~Qlogy Research, Lucknow for analysis of PAHs on
samples obtained from UP Transco:
SI. Name of line Total PAH Significant PAH No. concentration concentration
(\..Ig/ Li tre ) 1 220 kV ICT Muradnagar 77.66 Acenapthylene 2 400 J5..V..,.Panki-Muradnagar 87.10 Napthalene 3 220 KV Secundrabad- 186.44 Fluorene+ -., ,
M"uradnagar Acenaphthelene
4.0 As decided during meeting chaired by Secretary (Power) on 09-03-2008, Pollution measurement of insulators was carried out at CPRI, Bangalore during March' 2008 and it was revealed that accumulation of pollution on bottom surface of insulators were higher than top surfaCf3 and pollution level were higher than the design criteria. Chemical analysis results showed high concentration of Silica, Alumina, Ferrous etc. Analysis of these test reports
'
were sent to Member Secretary, NRPC, New Delhi vide our letter under refer.ence ctOst ~~!~~ .. 29-05-2008 with a copy to your office. Highlights of prevIous test results qre as under:
![Page 384: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/384.jpg)
Name of linel 400 kV Meerut-Mandola line 400 kV Oadri-Panipat-I line Pollution Level Medium (0.1477 mgl cm~) Medium (0.2045 mgl cm~) Chemical Pollutal"!ts showed more of Pollutants showed more of Composition Silica and Ferrous content Silica and Ferrous content
K20 -17.95% AI20 3 - 6.68% Si02 - 28.56% Si02 - 73.01 % Fe203 - 33.50% K20 -14.23% CaO-14.27%
5.0 As mentioned above, the insulator samples were cleaned about a month ". earlier to the selection of samples and were not expected to be heavily
polluted. However, test results show that there is fast accumulation of pollutants. Insulators removed from 400 kV Hisar-Bawana, 400 kV DadriPanipat .... 1 and 400 kV Oadri-Ponipat-II lines shows significant PAH cqncentration. Other samples also confirm the presence of PAHs. PAHs would have been produced during incomplete burning of Coal, Oil ~ Gas, Garbage and Automobile tyres etc.
It can be seen from the tests carried out in March' 2008 and January! February' 2009 that there is significant concentration of Ferrous, Zinc, Aluminium, Calcium, Magnesium and Silica elements.
Pollution test results for the tests conducted in January'2009 again confirmed the previous finding that the ollution vels are higher than their· desig criteria. It appears that CPRI does not have good testing facIlity for analysis 0
~ydrocarbons which is obvioys from the fact that their analysis is vague at best .specially w.r.t. Hydro Carbon. Test results of other two specialize laboratories have indicated the presence of hydro carbons.
It is worthwhile to mention that most of transmission lines in Northern Region pass through cufflVated fields and various smoke emitting industries are al$o located in their vicinity. Many brick kilns emitting dense smoke are operati'ng around Delhi in NCR which affects mainly lines like 400 kV Hisar- BhiwaniBawana line, 400 kV Meerut-Mandola, 400 kV Dadri-Mandola, 400 kV DadriPanipat-I and 400 kV Dadri-Panipat-II transmission lines. In addition to this the lines are affected due to pollution near other cities, around location of industries, brick kiln etc. ,
After analysis of test results of different laboraties, it may be concluded that concentration of PAH, Ferrous, Zinc, Aluminium, Calcium, Magnesium and Silica may be due to:
a. Continuous cultivaoon activity and use of fertilizers in western UP, Haryana and Punjab
I I
!-
![Page 385: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/385.jpg)
b. Burning of sugar canes to clear the fields as sugarcane is the major crop in this part Of the counrtry and after harvesting, farmers burn stems of sugarcane to clear the fields. Sugarcane soots accumulate on insulators.
c. Lot of brick kilns are operative in the vicinity of transmission lines in National Cap:tal Region. For making bricks, they use soil, sand etc. even transportation of bricks from brick kiln to place of use through kaccha road cause heavy dust formation in atmosphere. They use different type of fuel like coal, wood, scrap tyres, scrap rubber foot wears etc. Burning of these items create dense smoke and accumulate sticky pollution on insulator surface which is very difficult to clean by. washing.
d. Rapid industrialization in this area and high vehicle density has contributed significantly in accumulation of PAHs and fly ash on insulators
e. Combination of these factors is also observed in the vicinity of Dadri, MandoJa, Meerut, Bahadurgarhand Bhiwani.
f. Construction activities cause heavy pollution in atmosphere.
6.0 After analysis of Polynuclear Aromatic Hydrocarbons following has emerged:
Polynuclear aromatic hydrocarbons'(PAHs) are hydrocarbon compounds with· multiple benzene rings. They are also called Polycyclic Aromatic Hydrocarbons. These are group of compounds consisting of carbon and hydrogen and having 2 or more condensed benzene ring structures -that are formed during the incomplete burning of:-
• Coal .' Oil & Gas
• Garbage • Automobile tyre
.. PAHs are present naturally in petroleum compounds and produc~d by combustion of fossil fuels or other organic matter PAHs are usually found as a~;,: mixture containing two or more of these compounds, such as soot.
Physic~1 Properties:
:, • The POlycyclic aromatic hydrocarbons (PAHs) break down by reacting with sunlight and other chemicals in the air to form low-molecular weight PAHs.
• Low molecular weight parental PAHs (2-3 rings) have a pretty good electrical conduotjvity.
7.0 As substantiated, by CPRI, Bangalore to the decision taken in meeting . conveyed by MOP to replace conventional insulators with polymer insulators
-------
. . . ' .
/
![Page 386: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/386.jpg)
on all vulnerable lines in NCR area as well as polluted stretches in other area vide Minutes of meeting dated 09-03-2008, POWERGRID have taken advance actions for replacement of conventlonal disc insulators with Polymer Insulators in vulnerable lines in Northern Region. State transmission utilities have also gone for polymer insulators as well as antifog insulators on these lines. .
8.0 During the winter season of 2008-09, POWERGRID was able to replace conventional insulators with polymer insulators in critical stretches of some of the Ijnes, hotline washing of insulators and these alongwith other measures have helped in drastic reduction in tripping of transmission lines. Before onset of winter of 2009-10, it is expected that POWERGRID as well as other utilities will be able to complete majority of the replacement work.
Thanking you,
Copy to:
Yourp faithfully 1\ i \' 1"- (f '.\ ! !.I '\.... I
. I ~ , \ ' \!,' Y
(R G. Yadav) Executive Director (OS)
1. Joint Secretary (Transmission, Admn., Pari, Ol, O&M, IC, Climate Change) Ministry of Power, New Delhi
2. Merhber (GO&D), Central Electricity Authority, New Delhi
3. i"Member Secre~ Northern Region Powerr Committee, New Delhi
,
. '.
;:., .
.;;
..
~ ..
![Page 387: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/387.jpg)
Annexure- 10/VI
A brief status on implementation of Recommendations of Inquiry
Committee on Grid Incidents on 27th Jan 2007, 7th and 9th March, 2008.
Item
Nos.
Recommendations Status
1. Recommendation of Inquiry
Committee on grid incident on
27th Jan 2007 requiring action
by the constituents.
1.1 Classification of pollution levels
of lines/line stretch by
measurement of ESDD on
insulators
The measurement of ESDD on insulators get done
by POWERGRID through CPRI, Bangalore, Shri
Ram Research Institute for Industrial Research,
Delhi, Indian Institute of Toxicology Research,
Lucknow. Other States Transmission utilities to
comply with this recommendation.
1.2 Notifications by the respective
state government that no brick
kiln or any industrial unit or
biomass or diesel based power
plant having chimney height up
to 30 meters be set up within
0.5 km of the 220 kV or higher
voltage transmission lines.
Notification done by, Haryana. Rajasthan and
Punjab transmission utilities requested the CEA to
take up with Central Pollution Control Board through
Ministry of Power to furnish the provision for
notification to be done by the State Government.
1.3 Review of pollution standards Yet to be complied by State Transmission
Utilities/State Government.
1.4 Provision of bird guards on all
towers
CTU and STUs reported that bird guards are being
provided on towers of transmission lines. Work on
400 kV Anpara- Mau line will be taken up by
UPPTCL.
2 & 3 Replacement of existing
insulators by Polymer / Anti fog
Insulators and cleaning of
The list of lines as identified by CTU and STUs for
replacement of porcelain insulator with polymer
listed in the Inquiry Committee Report along with
![Page 388: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/388.jpg)
insulators current status are given at Annexure10/III. This
work which was targeted to be completed in March
2009, had been completed on critical
locations/lines. Whereas in all other locations
cleaning of porcelain insulators had been carried
out by CTU and STUs.
4 Monitoring Mechanism The criticality of line vis-à-vis cleaning/replacement
process in NR is being monitored by NRLDC and
SLDCs and review of the status being taken by
NRPC Secretariat.
5 Alertness During high RH and
Low Temperature conditions
Complied by NRLDC by up-linking the data of three
locations i.e. Minto Road, Delhi, Hissar and Panki,
Kanpur. SLDCs is to up-link the data in respect of
all critical locations within their system on their
website.
6 Railway supply reliability To be complied by Railway.
7 Operation of Minimum filter
bank at HVDC Rihand-Dadri Bi
polar
Complied
8 Pollution control of diesel
vehicle entering NCR area
To be complied
9 Developing a fog forecasting
model for power system in NR
Weather Data from many 400 kV stations are
available in the SCADA, based on these data and
IMD forecast NRLDC had been regularly putting
the fog warnings on its website during winter
season. Further during peak winter period NRLDC
has also arrangements for getting detailed weather
forecast data from identified important stations of
NR.
Hourly weather forecasting data (updated thrice a
day) from M/s SKYNET from location Delhi, Kanpur
![Page 389: Enquiry Committee Report on Grid Disturbance of 2nd January, 2010](https://reader038.fdocuments.us/reader038/viewer/2022102407/58597acd1a28ab6e328fb2eb/html5/thumbnails/389.jpg)
and Hissar. SLDCs is to comply with this
recommendation.
10 Chemical Analysis of deposits
on Insulators Strings
The measurement of ESDD on insulators get done
by POWERGRID through CPRI, Bangalore, Sri
Ram Research Institute for Industrial Research,
Delhi, Indian Toxicology Research Institute,
Lucknow. Other States Transmission utilities to
comply with this recommendation. STUs are to get
chemical analysis of deposits on insulator strings.
11 Insulation requirement of EHV
transmission lines
CTU and STUs reported of compliance as per the
recommendation of expert committee of CEA,
regarding insulation requirement of EHV
transmission lines.
12 Pollution Mapping of the
Country
POWERGRID taken up the matter with CPRI.
CPRI formulated the proposal and submitted to
MoP for approval.