[Engineering] - Electrical Power and Energy Systems 1999-21 - Dynamics of Diesel and Wind Turbine...

8
 Dynamics of diesel and wind turbine generators on an isolated power system D. Das a, * , S.K. Aditya a , D.P. Kothari b a  Electrical En g. Dept., Indian Institute of Technology, Kharagpur—721302, India b Centre for Energy Studies, Indian Institute of Techn ology, New Delhi—110016, India Abstract The paper presents dynamic system analysis of an isolated electric power system consisting of a diesel generator and a wind turbine generator. The 150 kW wind turbine generator is operated in parallel with a diesel generator to serve an average load of 350 kW. Time domain solutions are used to study the performance of the power system. Optimum values of gain settings of the Proportional-Integral controller (P-I) are obtained by using the integral squared error (ISE) technique. A simple variable structure control (VSC) logic is also proposed for improvement of the dynamic performance of the system. 1998 Elsevier Science Ltd. All rights reserved. Keywords: Wind and diesel power system; Stability; Optimization 1. Introduction A con sta ntly incre asin g power demand has to be met throu gh an adeq uately planned electrical power generatio n programme. Electrical energy is environmentally the most ben ign for m of ene rgy, wit h pro duc tio n rou ted thr ough conventional fossil fuel burning or through nuclear energy and wherever possible through hydro resources. All of these in addition to other disadvantages give rise to environmental issues of a va rie d nature. Ther ef or e it is ne cessar y to consider the problems of electrical energy generation and environment jointly so that the increasing need of electricity for industrialization will be met with minimal environmen- tal degra dation. One of the solut ions is to uti liz e win d energy in favourable sites which are remote from centralised energy supply systems. Since wind power varies randomly there must be a stand-by power source to meet load demand. The diesel and wind system is one of the hybrid systems utilizing more than one energy source. A wind and diesel system is very relia ble because the diesel acts a s a cushion to take care of variation in wind speed, and would always provide power equal to load minus the wind power. Scott et al. [1] have investi gated the dynamic interaction to quantify any increased disturbance to the Block Island Power Company (BIPCO), on Block Island (which operates an isolated electric power system consisting of diesel and wind turbine generators resulting from connection of the MOD- OA wind turbin e ge ne rat or ). In th is st ud y, the dynami c simulation of the wind turbi ne genera tor operated in par alle l wit h a die sel gener ator on an iso lat ed power syste m is carried out. Optimum value s for the gain settings of the Pro por tional-Int egr al (P-I ) controller have been obtained using the Integral Squared Error (ISE) technique. A simple Variable Structure Control (VSC) logic is also proposed for the improvement of system dynamic perfor- mance. 2. Description of diesel and wind systems The model considered in this study consists of the follow- ing sub-systems [1,3,4]: Wind dynamics model; Diesel dynamics model; Blade pitch control of wind turbine; Generator dynamics model. The wind model is one feature that is unique to the wind turbine generator and is not required for the diesel generator system in the stability programme. Anderson et al. [2] have presented one model that can properly simulate the effect of wind behaviour, including gusting, rapid (ramp) changes and background noise. The basic conditions for start up and synchronization are that the wind speed is to be within an acce pt abl e range and th ere must be a phase match betwe en the generator and syst em volta ges [1]. The diesel dynamics is associated with diesel power and the na ture of th e dyna mic be havi our in this mode l is Electrical Power and Energy Systems 21 (1999) 183–189 JEPE 278 0142-0615/99/$ - see front matter 1998 Elsevier Science Ltd. All rights reserved. PII: S0142-0615(98)00033-7 * Corresponding author; e-mail: [email protected].

Transcript of [Engineering] - Electrical Power and Energy Systems 1999-21 - Dynamics of Diesel and Wind Turbine...

  • Dynamics of diesel and wind turbine generators on an isolated powersystem

    D. Dasa,*, S.K. Adityaa, D.P. KotharibaElectrical Eng. Dept., Indian Institute of Technology, Kharagpur721302, India

    bCentre for Energy Studies, Indian Institute of Technology, New Delhi110016, India

    Abstract

    The paper presents dynamic system analysis of an isolated electric power system consisting of a diesel generator and a wind turbinegenerator. The 150 kW wind turbine generator is operated in parallel with a diesel generator to serve an average load of 350 kW. Timedomain solutions are used to study the performance of the power system. Optimum values of gain settings of the Proportional-Integralcontroller (P-I) are obtained by using the integral squared error (ISE) technique. A simple variable structure control (VSC) logic is alsoproposed for improvement of the dynamic performance of the system. q 1998 Elsevier Science Ltd. All rights reserved.

    Keywords: Wind and diesel power system; Stability; Optimization

    1. Introduction

    A constantly increasing power demand has to be metthrough an adequately planned electrical power generationprogramme. Electrical energy is environmentally the mostbenign form of energy, with production routed throughconventional fossil fuel burning or through nuclear energyand wherever possible through hydro resources. All of thesein addition to other disadvantages give rise to environmentalissues of a varied nature. Therefore it is necessary toconsider the problems of electrical energy generation andenvironment jointly so that the increasing need of electricityfor industrialization will be met with minimal environmen-tal degradation. One of the solutions is to utilize windenergy in favourable sites which are remote from centralisedenergy supply systems. Since wind power varies randomlythere must be a stand-by power source to meet load demand.The diesel and wind system is one of the hybrid systemsutilizing more than one energy source. A wind and dieselsystem is very reliable because the diesel acts as a cushion totake care of variation in wind speed, and would alwaysprovide power equal to load minus the wind power.

    Scott et al. [1] have investigated the dynamic interactionto quantify any increased disturbance to the Block IslandPower Company (BIPCO), on Block Island (which operatesan isolated electric power system consisting of diesel andwind turbine generators resulting from connection of theMOD-OA wind turbine generator). In this study, the

    dynamic simulation of the wind turbine generator operatedin parallel with a diesel generator on an isolated powersystem is carried out. Optimum values for the gain settingsof the Proportional-Integral (P-I) controller have beenobtained using the Integral Squared Error (ISE) technique.A simple Variable Structure Control (VSC) logic is alsoproposed for the improvement of system dynamic perfor-mance.

    2. Description of diesel and wind systems

    The model considered in this study consists of the follow-ing sub-systems [1,3,4]:

    Wind dynamics model;Diesel dynamics model;Blade pitch control of wind turbine;Generator dynamics model.

    The wind model is one feature that is unique to the windturbine generator and is not required for the diesel generatorsystem in the stability programme. Anderson et al. [2] havepresented one model that can properly simulate the effect ofwind behaviour, including gusting, rapid (ramp) changesand background noise. The basic conditions for start upand synchronization are that the wind speed is to be withinan acceptable range and there must be a phase matchbetween the generator and system voltages [1].

    The diesel dynamics is associated with diesel power andthe nature of the dynamic behaviour in this model is

    Electrical Power and Energy Systems 21 (1999) 183189

    JEPE 278

    0142-0615/99/$ - see front matter q 1998 Elsevier Science Ltd. All rights reserved.PII: S0142-0615(98)00033-7

    * Corresponding author; e-mail: [email protected].

  • dominated by the diesel speed governor controller. A totalpower set point is selected in which it can manually adjustedfrom zero to maximum value. The purpose of the adjustablepower set point is to allow system utility personnel to lowerthe power setting below the maximum settings of the windgenerator to prevent controlling diesel from dropping to lessthan 50% of the rated power. Operation of a diesel enginefor extended periods at two power levels could result inpossible engine damage.

    Pitch control has the potential for producing the highestlevel of interaction because of the presence of both dieseland wind turbine control loops. The pitch control systemconsists of a power measurement transducer, a manualpower set point control, a proportional plus integral feed-back function, and a hydraulic actuator which varies thepitch of the blades. Turbine blade pitch control has a signif-icant impact on the dynamic behaviour of the system. Thistype of control only exists in horizontal axis machines.

    Variable pitch turbines operate efficiently over a widerrange of wind speeds than fixed pitch machines. However,cost and complexity are higher.

    The generator dynamics model consists of a synchronousgenerator driven by a diesel engine through a flywheel andconnected in parallel with an induction generator driven bya wind turbine. The diesel generator will act as a dummygrid for the wind generator which is connected in parallel.Variations of electrical power due to changes in wind speedshould be as small as possible; this is obtained by using theinduction generator as a wind turbine drive train. Unlikesynchronous generators, induction generators are highcompliance couplings between the machine and the electri-cal system. This is true for induction generators with slip ofat least 12% at rated power. The controlled variables areturbine speed and shaft torque. Control acts on the turbineblade pitch angle (pitch control). Since the torque speedcharacteristic of the induction generator is nearly linear in

    D. Das et al. / Electrical Power and Energy Systems 21 (1999) 183189184

    Fig. 1. Conceptual model of diesel and wind turbine generator system.

    Fig. 2. Functional block diagram for wind and diesel systems with pitch control.

  • the operating region, torque changes are reflected as speedchanges. Therefore, it is possible to provide a single speedcontroller to control speed as well as torque.

    3. Mathematical model of the system

    A linear model is formulated for the wind and dieselturbine generator system for the purpose of identifyingand quantifying the underdamped oscillation. This objectiveis met by retaining the pertinent controller dynamics forboth the diesel unit governors and wind turbine generatorpitch controller/actuator. The conceptual model that resultsis shown in Fig. 1. The fluid coupling shown in Fig. 1transfers speed difference into power. The actual functionis nonlinear (Square law) but for the model it is linearized,resulting in a constant for the particular power set pointselected. Fig. 2 shows the functional block diagram that isobtained.

    The transfer function of the hydraulic pitch actuator isgiven as:

    DHSU1S

    Kp21 1 STp1TkS2 1 STp2 1 11 1 S

    1

    But Tk is very small compared to Tp2 and hence Tk isneglected from the mathematical model. Therefore Eq. (1)can be written as

    DHSU1S

    Kp21 1 STp11 1 STp21 1 S 2

    The transfer function Eq. (2) of the hydraulic pitch actua-tor is split into two blocks (Fig. 2) and DH1 is a dummyvariable.

    The transfer function of the diesel governor (Fig. 2) is

    given as:

    DPfSDvrefS2 Dv2S

    Kd1 1 SS1 1 ST1 3

    As vref is the reference speed setting (a constant) for thediesel generator, therefore Dvref 0.0. Substituting Dvref 0.0 in Eq. (3), we getDPfS

    2 Dv2S Kd1 1 SS1 1 ST1 4

    The transfer function of the diesel governor Eq. (4) is splitinto two blocks and DPf1 is a dummy variable.

    Appearing in a block (Fig. 2) labelled data fit pitchresponse is a simple lag which is required to match thephase/gain characteristic of the model. Other state variablesare marked in Fig. 2. The system is a linear continuous-timedynamic system and can be represented by a set of lineardifferential equations of the form:

    _X AX 1 BU 1 GP 5where X, U and P are state, control and disturbance vectorsand A, B and G are constant matrices associated with themrespectively. For this system (Fig. 2), X, U and P aregiven as

    X 0 DH1 DH DD Dv1 Dv2 DPf 1 DPf 6

    U U1 7

    P 0 DPv DPload 8where, 0 stands for transpose. A, B and G are given inAppendix 1. Data for this system are given inAppendix 2.

    D. Das et al. / Electrical Power and Energy Systems 21 (1999) 183189 185

    Fig. 3. Kp vs J for several values of KI.

  • 4. Optimization of the Proportional-Integral (P-I)controller gain settings using the ISE technique

    Many utilities prefer to use the P-I controller forbetter system dynamic response and in the presentstudy, the P-I controller is used. The P-I control law

    is given as

    U1 KpDPmax 2 DPvtg1 KIZt

    0DPmax 2 DPvtg dt 9

    For the study system, Pmax 150 kW is constant, there-fore DPmax 0.0. Substituting DPmax 0.0 in Eq. (9)we obtain

    U1 2KpDPvtg2 KIZt

    0DPvtg dt 10

    An attempt is made to obtain the optimum values of P-Igain settings (Kp and KI) using the integral squared error(ISE) technique for a 1% step increase of load.

    A performance index

    J Zt

    0DPvtg2 dt 11

    is minimized to obtain the optimum values for P-I gainsettings. Note that DPvtg is also a function of Dv1 and Dv2(Fig. 2).

    Fig. 3 shows the plot of J vs Kp for several values ofKI, where Kp and KI are proportional and integral gains

    D. Das et al. / Electrical Power and Energy Systems 21 (1999) 183189186

    Fig. 4. Plot of Kv vs J.

    Fig. 5. Frequency responses with conventional and variable structure controllers.

  • respectively. From Fig. 3, it is seen that Kp 10:0 and KI 4:0 are more or less optimum values of P-I gain settings.

    5. Variable structure control (VSC) logic

    In this study, an attempt is also made to improve thesystem dynamic performance by using a simple variablestructure control (VSC) logic which is based on proportional(P) and proportional-integral (P-I) control concept. If thecontrol law applied at the first stage of the transient (aslong as error is sufficiently large) is chosen as

    U1 2KvDPvtg if uDPvtgul1 12

    where 1 . 0 is some constant, but when the error is smallthe control law is

    U1 2KpDPvtg 2 KIZt

    0DPvtg dt if uDPvtgu # 1 13

    where uDPvtgul1 for t $ t1, then if the parameters Kv, Kp, KIand 1 are suitably selected, one can ensure a high-qualitytransient response, distinguished by good dynamic andsteady-state characteristics. Indeed taking the magnitudeof Kv as being sufficiently large, one can make sure thatthe speed of the system is high; thus, the error DPvtg, in

    response to a step input rapidly enters the regionuDPvtgu # 1. At the instant t1, when the error has fallen to1, the structure of the controller is changed by switching to aP-I control, which eliminates the steady error remaining inthe system.

    An attempt is made to obtain optimum values of Kv byusing the ISE technique. The same performance index J Eq.(11) is chosen to obtain the optimum values of Kv. Through-out this optimization process, values of Kp and KI are fixed at10.0 and 4.0, respectively. Fig. 4 shows the plot of J vs Kvfor 1 0.0004. It is worth mentioning here that severalvalues of 1 are tried out. However, 1 0.0004 gives thelowest value of J. From Fig. 4, it is seen that the optimumvalue of Kv is 2 10.0. However, any positive value of Kvdoes not minimize the performance index J Eq. (11) andperhaps this is due to excessive control action.

    6. Dynamic responses

    Figs. 5 and 6 show the dynamic responses for a 1% stepincrease of load with the P-I controller and variable struc-ture controller (VSC). It is seen that the activation of pitchcontrol with the conventional P-I controller results in anunderdamped response. Although this is a stable response,the low damping allows the oscillation to continue for a

    D. Das et al. / Electrical Power and Energy Systems 21 (1999) 183189 187

    Fig. 6. Power responses with conventional and variable structure controllers.

  • longer time before damping out. It is seen that with the useof VSC, damping is greatly improved. Peak wind generatorfrequency deviation (Fig. 5(a)) and peak diesel power devia-tion (Fig. 6(a)) are much less compared to the conventionalP-I controller. From Fig. 6(b), it is also seen that with the useof VSC, the wind power deviation (DPvtg) is slow andmonotonic and hence is preferred. From Figs 5 and 6, it isalso seen that with the use of VSC, settling time is much lesscompared to that of the conventional P-I controller. There-fore, it can be concluded that the variable structure control-ler improves the system damping compared to the fixedstructure P-I controller.

    7. Conclusions

    A linear mathematical model of the wind and diesel turbinegenerators operating on an isolated electric power system hasbeen formulated for the purpose of identifying and quantifyingthe underdamped oscillation. The simulation incorporateswind turbine pitch control and diesel governor. Optimumvalues for the gain parameters of the conventional propor-tional-integral (P-I) controller and variable structure controller(VSC) have been obtained using the integral squared error(ISE) technique. Analysis reveals that the variable structurecontroller gives better dynamic performance in terms of peak

    deviations and settling time compared to that of the conven-tional fixed structure P-I controller.

    It can also be concluded that wind turbine generation,even when providing a large proportion of the powerrequired by an isolated utility can be a practical optionresulting in system disturbances no greater than thosefound in a conventional diesel system.

    Appendix 1

    A, B and G matrices of the system (Fig. 2) are givenbelow:

    Note that B is a 7 1 matrix because there is only onecontrol input.

    Appendix 2

    Area capacity; PR 350 kW;Hv inertia constant on machine base 3:5 s for wind system;Hd inertia constant on machine base 8:5 s for diesel system;

    D. Das et al. / Electrical Power and Energy Systems 21 (1999) 183189188

    A

    21Tp2

    0 0 0 0 0 0

    Kp2 2Kp2Tp1

    Tp2

    !21 0 0 0 0 0

    0 Kp3 21 0 0 0 0

    0 0Kpc2Hv

    2Kfc2Hv

    Kfc2Hv

    0 0

    0 0 0 Kfc2Hd

    2Kfc 0 1

    0 0 0 0 2Kd 0 0

    0 0 0 0 2KdT1

    1T1

    21T1

    26666666666666666666666666664

    37777777777777777777777777775

    B

    1Tp2

    Kp2Tp1Tp20

    0

    0

    0

    0

    26666666666666666666664

    37777777777777777777775

    ; G

    0 0

    0 0

    0 01

    2Hv0

    0 212Hd

    0 0

    0 0

    266666666666666666664

    377777777777777777775

  • Kfc 16:2 pu kW=Hz Kd 16:5 pu kW=Hz;

    Kp2 1:25 Tp2 0:041 s;

    Kp3 1:40 Tp1 0:60 s;

    DPload 0:01 pu kW Kpc 0:80;

    T1 0:025 s Tk 0:0009 s:

    References

    [1] Scott GW, Wilrekar VF, Shaltens RK. Wind turbine generator interac-tion with diesel generators on an isolated power system. IEEE TransPower Apparatus Syst 1984;PAS 103(5):933937.

    [2] Anderson PM, Bose A. Stability simulation of wind turbine systems.IEEE Trans Power Apparatus Syst 1983;PAS 102(12):37913795.

    [3] Hinrichsen EN. Controls for variable pitch wind turbine generators.IEEE Trans Power Apparatus Syst 1984;PAS 103(4):886892.

    [4] Hinrichsen EN, Nolan PJ. Dynamics and stability of wind turbinegenerators. IEEE Trans Power Apparatus Syst 1982;PAS101(8):26402648.

    D. Das et al. / Electrical Power and Energy Systems 21 (1999) 183189 189